CAKJ-XHB-8X~48X
Microcomputer type central signal alarm device
X Series
8,12,16,24,32,48 Loop
Xuchang Changan Technology Co., Ltd.
1,OVERVIEW
CAKJ-XHB separate micro computer central signal alarm device is a centralized management device
that designed for Power station and Transformer substation signal system. The device that extensively
used in electric, petrochemical, chemical industry, metallurgy and coal industry, is a high intelligent
product that automatic monitoring and signal alarm for power and industrial.
2,FUNCTIONAL CHARACTERISTICS
1)The panel includes digital display and power on self test (POST).Integrated design.
2)Provide with test (light test), confirm (accept), return(reset), signal recall and clear function. With
function buttons.
3)Provide with manual and automatic accept function, automatic accept time limit (0-200s) able to set.
4 ) Signal alarm type able to distinguish: accident signal S, warning signal Y, position signal P, all
available to set.
5)Alarm window color: able to choose red, white, yellow, green, accord to signal alarm type, separated
by color is more arresting and visually.
6)Input signal status: switch contact (h), switch hold contact (E), and pulse hold contact (C). (Note)
7 ) The input signal is normally open and normally closed. For each signal, the normally open and
normally closed alarm (default) can be set, and the normally closed variable normally open alarm can be
set.
8)Signal delayed alarm: 0-9999ms delay alarm time limit able to set.
9)Device bring with buzzer, when accident happy it sounds “bi---”, warning signal sounds short beep “bi,
bi, bi, bi”, position signal doesn’t sound.
10)Device with accident and warning signal alarm output contact, able to activate electric bell, enhance
the alarm effect.
11)With remote signal output contacts, connect to other devices or as an accident stop signal.
12)It has the device power disappearance contact output.
13 ) Provide with digital communication output, RS485 serial communication contact, MODBUS
communication protocol.
◆Note: Explanation of input signal status and alarm procedures
When“h” is selected as the input signal state (default), the workflow is as follows:
Line Run Button Alarm status Light plate Sound status Remark
1 Normal - Normal Off Silent
2A Abnormal - Alarm Flash Sound Alarm
2B Abnormal Silence Alarm Flash Silent Alarm hold
3A Abnormal Confirm Comfirmed Bright Silent Alarm hold
3B Normal - To line 4 Instant alarm
4 Normal - Normal Off Silent Automatic reset
When the state of the input signal is "C" or "E", the work flow is as follows:
Line Run Button Alarm status Light plate Sound status Remark
1 Normal - Normal Off Silent
2A Abnormal - Alarm Flash Sound Alarm
2B Abnormal Silence Alarm Flash Silent Alarm hold
3 Abnormal/Normal Confirm Comfirmed Bright Silent Alarm hold
4A Abnormal Reset - To line 3 Alarm hold
4B Normal Normal 灭 无声 Manual reset
Note: The signal is normal if the signal is not alarmed, and the signal abnormal is if it is alarmed
1
3,CONMENT TECHNIQUE REQUIREMENT
1.Working power supply: DC220V, DC110V, DC125V, AC220V, AC240V,Optional
2.Signal capacity: 8-48 loop,
3.Input signal method: Normally open active dry contact, or active contact.
4.Alarm window: Flash window measures are 53×28, colors: red, green, yellow, white to
choose.
5.Alarm output: Alarm window flash, buzzer or sound equipment sounds.
6.Alarm sound: Buzzer beeps 60DB; we provide intensive sound equipment CAKJ-DL
electric bell, CAKJ-DD electric whistle,Or CA-XXS-YX Electronic audio.
7.Contact output: 5 relay contact outputs, corresponding to power disappearance, warning
alarm, accident alarm, pre-emptive remote communication (follow-up), accident remote
communication (follow-up).
8.Contact capacity: AC250V, 3A pure resistance load, DC220V, 0.125A inductive load.
9.Function setup: touch button setting, 5 digits display.
10.Power consume: The whole device consumed no greater than 30W.
11.Communication contact: Standard RS485 serial communication contact, MODBUS
communication protocol.
12.Insulation resistance: no less than 100 MΩ in-between input-output-power supply-cage.
13.Power frequency voltage: in-between input- output-power supply-cage, able to bear the
tests of 2kV, 1min, 5mA, 50/60HZ, no signs of flashover and breakdown.
14.Capacity of resisting disturbance: able to bear 1 MHz and 100 kHz high frequency
interference of attenuated shock wave. First half wave voltage amplitude common mode is
2.5 kV, different mode voltage is 1.0 kV, the product shouldn’t appear unwanted operation or
failure of operate.
15.Environment condition: surrounding temperature -10℃~60℃; surrounding humidity no
greater than 90%.
16.Weight: 5 kg.
4,DEVICE ALARM AND TESTING
1)POST (power on self test), when device power on, digital display window on device panel
shows in sequence 【0.0.0.0.0】【1.1.1.1.1】…【7.7.7.7.7】【8.8.8.8.8】alarm window all
light 【9.9.9.9.9】alarm window all light scroll display 【CA n L】(for power indicate). POST
finish. "n" is the total number of circuits of the alarm device.
2) Press “test” button, all alarm window flash, buzzer sounds, output audio equipment
act. Release test button, return to monitoring status.
3)When signal alarm, recording alarm window flash, and buzzer sounds, output audio
equipment act to start electric whistle sound. Digital display window shows recording loop
number.
4)Press “confirm” button (or 0-200s affirm automatically), alarm window turns from flash to
light, buzzer silence, output audio contact return, electrical whiles and bell silence.
5)When signal return, switch type contact input signal recording alarm window lights off.
Retention type contact input signal alarm window remain alarm, require manual reset (press
“reset” button), and alarm window lights off.
6)Long press “recall” button, alarmed signals will shine one by one which followed alarm
sequence by FILO (first in last out) rules. At the same time LED display shows alarmed loop,
maximum 200 signals can be recalled, and alarm signals have priority.
2
5,DEVICE SETUP
Press “SET” set button, press “←” to move, “↑” to add 1, insert PIN (8080) into setup mode. Recording
to menu indication press “SET” to turn pages for function setting. (Edition no. v1.1)
Symbol Setting content Operate Setting Instruction
C 0 Insert PIN “←”“↑” PIN 8080
n. n total loops no. “SET” n loop n this is factory setting
30 Setting auto “←”“↑” 0~200s 30s ( “0” not confirm automatically)
confirm time
d. 20 Setting signal “←”“↑” 0-9999ms 20,20ms,
delay alarm time
y--A Alarm audio “↑”selected A,F,d, A(A audio all on, F buzzer only, d external audio
setting n only, n audio all off)
S. 1 comm. adds. “←”“↑” 0~255 1(communication add. is the only one)
b.9600 Communication “↑”selected 9600/4800 9600
Baud rate
J. 0 Memory signal “←”“↑” Clear PIN 1001(correct pin clear record)
clear
L01-y Setting 01 type “↑”selected, y,S,P y(the device default all signals are “y” warning
L02-y Setting 02 type “←”turn pages, signals, recording every single signal type, press
------ setting signal “↑” to choose “S” failure signal, press “↑”to choose
- - - -
type “P” location signal, while finish, press “←” to turn
Ln-y Setting n type
one by one pages, setting signal types one by one.
E01-h Setting 01 status “↑”selected, h(h device default switch contact), press “↑”to
h, C,E
E02-h Setting 02 status “←”turn pages, choose “C” pulse type retaining contact, press“↑”
- - - - - - - - - - setting signal to choose “E” switch retaining contact, while
En-h Setting n status input type one finish, press “←” to turn pages,setting signal type
by one one by one)
F01-o Setting 01 op/co “↑”selected, o,c o (Device by default, Normally open contacts
F02-o Setting 02 op/co “←”turn pages, closed alarm),press the "↑" choose "c" Normally
- - - - - - - - - - setting signal closed contacts open alarm. press← to flip pages,
Fn-o Setting n op/co open/closed one set normally open/closed alarm them one by one.
by on
while setting finish or no setting press “SET” button to save and exit, restore to normal alarm condition.
◆ Signal unified setting table; press "SET" to enter the setting, press "←" to shift, press "↑" to add 1,
after entering the code, press "SET" to complete the setting and return
Enter code Set 1-n signal alarm type Enter code Set 1-n signal input status
C1101 Unified settings for accident signals S C1104 Uniformly set as switch contacts h
C1102 Uniformly set as a warning signal y C1105 Uniformly set as pulse contacts C
C1103 Uniformly set as position signal P C1106 Uniformly set to keep contacts E
Note: This setting is convenient for the user to set all signals to one type or state on site, do not operate
easily.
★Light word plate alarm name printing transparent paper or light board replacement
diagram ☞
3
6,Model specifications
Model Alarm loop Series code signal type Detailed description
CAKJ-XHB Changan integrated signal alarm device
-8 8 Loop alarm signals (8 alarm light plates)
-12 12 Loop alarm signals (12alarm light plates)
-16 16 Loop alarm signals (16 alarm light plates)
-24 24 Loop alarm signals (24 alarm light plates)
-32 32 Loop alarm signals (32alarm light plates)
-48 48 Loop alarm signals (64 alarm light plates))
X X series size, Standard type
X2 X series non-standard improved type (size change)
blank Alarm signal is passive dry contact signal input
-A Alarm signal is active voltage signal input
(DC220V, DC110V, etc., specified when ordering)
Example:CAKJ-XHB-32X Central signal alarm device (32 Loop passive signal input alarm)
CAKJ-XHB-32X-A Central signal alarm device (32-Loop active signal input alarm, DC220V)
7,System wiring diagram
◆Meaning of terminal
Terminals for basic control operation circuit(8,12,16,24 Loop)
A1 A2 A3
power supply Ground
B1 B2 B3 B4 B5 B6 B7 B8 B9 BA C4 N1 N2 N3 N4 X1 X2 XG
Power warning Accident Warning Accident COM2 Test accept reset recall RS485 DG
distant distant
dis. sound sound signal signal
Signal input circuit terminal (8,12,16,24 Loop)
01 02 03 04 05 06 07 08 09 10 11 12 C5
1-12 Loop signal input
13 14 15 16 17 18 19 20 21 22 23 24
13-24 Loop signal input COM1
Terminals for basic control operation circuit(32,48 Loop)
A1 A2 A3 B1 B2 B3 B4 B5 B6 B7 B8 B9 BA NC NC X1 X2 XG
power Ground Power warning Accident Warning Accident Space RS485 GD
distant distant
supply dis。 sound sound signal signal
C4 C4 NC NC N6 N5 N4 N3 N2 N1
COM2 Space Un. recall reset silence accept Test Note: The silence button needs to be connected externally
Signal input circuit terminal (32,48 Loop)
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 C5 C5
01-16 Loop signal input COM1
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 C5 C5
17-32 Loop signal input COM1
C5 C5 48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
COM1 33-48 Loop signal input
4
◆ Basic control operation circuit
◆ Signal input circuit wiring diagram
◆ Schematic diagram of passive dry contact and active voltage signal input
5
8,Device outline and opening size
List of appearance and installation dimensions
Alarm loop L(mm) H(mm) D1(mm)D2(mm) Remark
8 297 160 289 152 Rear mounting bracket
12,16 297 205 289 197
12X2 Change 220 170 211 161
24 382 205 374 197
24X2 Change 263 263 255 255
32 382 227 374 219
48 382 327 374 319
48X2 Change 324 394 316 386
--------------------------------------------------------------------------
◆Electric bell and whistle (optional)
CAKJ-DL Electric bell
CAKJ-DD Electric whistle
Installation: 35mm rail type
Terminals
L+ N-
AC/DC30-265V
-------------------------------------------------------------------------
◆Electronic audio (optional)
CA-XXS-YX Electronic audio(Accident fire sound, warning siren sound, volume, tone
adjustable)
Installation: wall-mounted or panel embedded
Terminals
1 2 3 4 5 6 7
L+ N-
AC/DC80-265V Space Accident Warning
External dimensions: 210x135x92
Opening size: 202x127
Installation method: wall mounted or embedded