BurnerID 40688294 Date of Backup:08.04.
24
"Company Name" Parameters LMV5x
available Parameters of the Service Level
Parameter Operation Product ID
Setpoint W1: 0 °C ASN: LMV51.140C1
Setpoint W2: 0 °C Production Date: 18.03.22
Fuel selection via DOU: Gas Serial Number: 45
Display of date: 12.06.24 Parameter Set Code: 20
Display of time: 11:58:22 Parameter Set Version: 620
SW-Version LMV5: 0520
Hours run gas: 70 SW-Version LMV5: 0520
Hours run oil stage 1 or modulating: 0
Hours run oil stage 2: 0
Hours run oil stage 3: 0
Hours run total (can be reset): 70
Hours run total: 70
Hours run device under voltage: 434
start counter gas: 267
start counter oil: 18
start counter total (can be reset): 285
start counter total: 285
Lockout Counter: 225
Volume Gas: ---
Volume Oil: ---
Volume Gas(can be reset): ---
Volume Oil(can be reset): ---
Parameter Burner Control Times
Prepurge time gas: 20 s
Prepurge time oil: 15 s
Interval 1 (ts1-ts2) gas: 2.0 s
Interval 1 (ts1-ts2) oil: 2.0 s
Interval 2 (ts2 operation) gas: 2.0 s
Interval 2 (ts2 operation) oil: 2.0 s
Maximum time to low-fire: 45 s
Postpurge time 3 gas: 5.0 s
Postpurge time 3 oil: 5.0 s
Time to alarm: 35 s
Time until message start prevention: 35 s
Parameter Burner Control Configuration
alarm in the event of start prevention: Deactivated
forced intermittent operation: Deactivated
Page 1
BurnerID 40688294 Date of Backup:08.04.24
"Company Name" Parameters LMV5x
available Parameters of the Service Level
Ratio Control Gas
Actuator Gas Air Aux Aux 1 Aux 2 Aux 3 VSD
Home Position 0.0° 0.0° 0 0.0° 0.0° 0.0° 0.0%
Prepurge Position 90.0° 0 90.0° 90.0° 90.0° 100%
Ignition Position 10.0° 15.0° 0 0.0° XXXX XXXX XXXX
Postpurge Position 15.0° 15.0° 0 25.0° 25.0° 25.0° 50.0%
Program stop: Deactivated
Minimum load "Low fire": 0.0%
Maximum load "High fire": 100.0%
Duration operating ramp mod. operation: 60 s
Duration operating ramp stage operation: 10 s
Duration ramp prepurge and ignition pos.: 60 s
Startpoint Operation: 1
Behavior in Lockout Phase: Home Position
Fuel
Air
Table curve points 100
Chart curve points Aux 1
Load Gas Air Aux 1 Position [°/%]
10.0 10.0 ° 15.0 ° 0.0 ° 90
15.0 16.5 ° 18.0 ° 5.0 °
25.0 25.8 ° 25.0 ° 6.0 ° 80
28.0 29.0 ° 29.1 ° 8.0 ° 70
30.0 31.0 ° 31.0 ° 9.0 °
33.9 33.9 ° 33.0 ° 10.0 ° 60
40.0 35.5 ° 35.0 ° 12.1 °
43.0 37.0 ° 37.0 ° 13.1 ° 50
100.0 44.4 ° 37.1 ° 14.0 ° 40
30
20
10
0 Load [%]
0 10 20 30 40 50 60 70 80 90 100
Page 2
BurnerID 40688294 Date of Backup:08.04.24
"Company Name" Parameters LMV5x
available Parameters of the Service Level
Ratio Control Oil
Actuator Oil Act Air Aux Aux 1 Aux 2 Aux 3 VSD
Home Position 0.0° 0.0° 0 0.0° 0.0° 0.0° 0.0%
Prepurge Position 90.0° 0 90.0° 90.0° 90.0° 100%
Ignition Position 27.4° 9.9° 0 0.0° XXXX XXXX XXXX
Postpurge Position 0.0° 15.0° 0 25.0° 25.0° 25.0° 50.0%
Program stop: Deactivated
Minimum load "Low fire": 0.0%
Maximum load "High fire": 100.0%
Duration operating ramp mod. operation: 60 s
Duration operating ramp stage operation: 10 s
Duration ramp prepurge and ignition pos.: 60 s
Startpoint Operation: 1
Behavior in Lockout Phase: Home Position
Fuel
Air
100
Chart curve points modulating Aux 1
Load Oil Air Aux 1 Position [°/%]
33.3 34.5 ° 30.0 ° 30.0 ° 90
80
70
60
50
40
30
20
10
0 Load [%]
0 10 20 30 40 50 60 70 80 90 100
Table curve points multistage
Air Aux 1
Stage 1 Operating Point XXXX XXXX
Stage 2 Start Point XXXX XXXX
Stage 2 Off Point XXXX XXXX
Stage 2 Operating Point XXXX XXXX
Stage 3 Start Point XXXX XXXX
Stage 3 Off Point XXXX XXXX
Stage 3 Operating Point XXXX XXXX
Page 3
BurnerID 40688294 Date of Backup:08.04.24
"Company Name" Parameters LMV5x
available Parameters of the Service Level
Parameter O2
O2-Sensor: ---
Sup. Air Temp. Sensor: ---
Flue Gas Temp. Sensor: ---
Max. Temp. Flue Gas Gas: 300 °C
Max. Temp. Flue Gas Oil: 300 °C
ASN: ---
Production Date: ---
Serial Number: ---
Parameter Set Code:
Parameter Set Version:
SW-Version: ---
O2 Gas
Operation Mode: Manually deactivated
P Low-Fire: -0.1%
I Low-Fire: 65535 s
P High-Fire: -0.1%
I High-Fire: 65535 s
min. O2-Load: 0.0%
Type of Fuel: Natural Gas H
V_LNmin: 9.90
V_afNmin: 10.93
V_atrNmin: 8.89
A2: 0.65
B / 1000: 9
O2-Offset Gas: 0.0%
Load Control Suspend: 5.0%
O2 Setpoint
O2 Ratio
O2 Min Values
Table O2 Gas 10
Chart O2 Gas Lambda Factor
Load O2 Setpoint O2 Ratio O2 Min ValuesLambda Factor Position [°/%]
9
8
7
6
5
4
3
2
1
0 Load [%]
0 10 20 30 40 50 60 70 80 90 100
Page 4
BurnerID 40688294 Date of Backup:08.04.24
"Company Name" Parameters LMV5x
available Parameters of the Service Level
O2 Oil
Operation Mode: Manually deactivated
P Low-Fire: -0.1%
I Low-Fire: 65535 s
P High-Fire: -0.1%
I High-Fire: 65535 s
min. O2-Load: 0.0%
Type of Fuel: Oil EL
V_LNmin: 11.20
V_afNmin: 12.02
V_atrNmin: 10.53
A2: 0.65
B / 1000: 9
O2-Offset Oil: 0.0%
Load Control Suspend: 5.0%
O2 Setpoint
O2 Ratio
O2 Min Values
Table O2 Oil 10
Chart O2 Oil Lambda Factor
Load O2 Setpoint O2 Ratio O2 Min Values Lambda Factor Position [°/%]
9
8
7
6
5
4
3
2
1
0 Load [%]
0 10 20 30 40 50 60 70 80 90 100
Page 5
BurnerID 40688294 Date of Backup:08.04.24
"Company Name" Parameters LMV5x
available Parameters of the Service Level
Parameter Load Controller
proportional band: 6.4%
integral part: 136 s
differential part: 24 s
Minimum actuator step: 1.0%
Software filter time constant: 3s
setpoint W1: 0 °C
setpoint W2: 0 °C
switching differential burner ON modulating: 1.0%
switching differential burner OFF modulating: 10.0%
switching differential burner ON multistage: -2.0%
switching differential stage 1 OFF: 10.0%
switching differential stage 2 OFF: 8.0%
switching differential stage 3 OFF: 6.0%
Reaction threshold switching stage 2: 300
Reaction threshold switching stage 3: 600
Temperature limiter OFF threshold: 95 °C
Temperature limiter ON threshold: -5 %
cold start (thermal shock protection): Deactivated
Cold start therm. shock prot. ON threshold: 20 %
Cold start therm. shock prot. load step: 10 %
Cold start therm. shock prot. setpoint step (mod.): 5%
Cold start therm. shock prot. setpoint step (multistage): 5 %
Cold start therm. shock prot., max. time (mod.): 3 min
Cold start therm. shock prot., max. time (multistage): 3 min
Cold start therm. shock prot. OFF threshold: 80 %
Additional Sensor: Deactivated
Setpoint Add Sensor: 60 °C
Release Stages: Release
Operating Mode: Ext Load Controller X5-03
Input 1/2/4 Selection: No Sensor
End of Measurement Range Inputs 1 and 4: 150°C/302°F
Configuration Input 2: 0..10 V
End of Temperature Measurement Range Input 2: 90 °C
End of Pressure Measurement Range Input 2: 2.0 bar
Configuration Input 3: 4..20 mA
Minimum external Setpoint Input 3: 0%
Maximum external Setpoint Input 3: 60 %
Adaption Load: 100%
SW-Version: 0210
Page 6
BurnerID 40688294 Date of Backup:08.04.24
"Company Name" Parameters LMV5x
available Parameters of the Service Level
Parameter AZL
Password Time:
Summer/Winter Time: Automatic
Setting the summer-/wintertime US/EU: Summer/wintertime EU
Language: Francais
date format: DD.MM.YY
Unit Temperature:
Unit Pressure: Display bar
eBUS Adress: 1
Cycle time sending burner control's operating data: 30 s
Modbus Adress: 1
Modbus Baudrate: 19200 bit/s
Modbus-Parity: No
Modbus Timeout: 30 s
ASN: AZL52.00B1WH
Production Date: 31.05.22
Serial Number: 63
Parameter Set Code: 20
Parameter Set Version: 600
SW-Version: 0510
Parameter Actuators
Air Actuator Gas Actuator (Oil) Oil Actuator Aux Actuator
ASN SQM48.497B9WH SQM45.291B9WH SQM48.497B9WH SQM48.697B9WH
Production Date 16.02.22 07.04.22 21.04.22 21.04.22
Serial Number 5 24 19 9
Parameter Set Code 20 20 20 20
Parameter Set Version 104 104 104 104
SW-Version 0170 0170 0170 0170
Aux Act 2 Aux Act 3
ASN --- ---
Production Date --- ---
Serial Number --- ---
Parameter Set Code
Parameter Set Version
SW-Version --- ---
Permitted tolerance between the 2 potentiometer values: 15
Page 7
BurnerID 40688294 Date of Backup:08.04.24
"Company Name" Parameters LMV5x
available Parameters of the Service Level
Parameter VSD Modul
Pulses per Rotation: ---
Standardized Speed: ---
Setpoint Output: ---
Pulse Value Gas: ---
Puls Value Oil: ---
ASN: ---
Production Date: ---
Serial Number: ---
Parameter Set Code:
Parameter Set Version:
SW-Version: ---
Backup Info
Date of Backup: 08.04.24
Time of Backup: 13:44:44
BU included Yes
DOU included Yes
LC included: Yes
ACT1 included: Yes
ACT2 included: Yes
ACT3 included: Yes
ACT4 included: Yes
ACT5 included: No
ACT6 included: No
VSD included: No
O2 Modul included: No
Page 8