"Company Name" Parameters LMV5x: Parameter Operation Product ID

The document provides detailed parameters and operational data for a burner system identified by BurnerID 40688294, including setpoints, operational hours, and control configurations for gas and oil. It includes information on actuator positions, O2 sensor settings, load controller parameters, and backup details. The backup was performed on April 8, 2024, and includes various components of the burner system.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
19 views9 pages

"Company Name" Parameters LMV5x: Parameter Operation Product ID

The document provides detailed parameters and operational data for a burner system identified by BurnerID 40688294, including setpoints, operational hours, and control configurations for gas and oil. It includes information on actuator positions, O2 sensor settings, load controller parameters, and backup details. The backup was performed on April 8, 2024, and includes various components of the burner system.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

BurnerID 40688294 Date of Backup:08.04.

24

"Company Name" Parameters LMV5x


available Parameters of the Service Level

Parameter Operation Product ID


Setpoint W1: 0 °C ASN: LMV51.140C1
Setpoint W2: 0 °C Production Date: 18.03.22
Fuel selection via DOU: Gas Serial Number: 45
Display of date: 12.06.24 Parameter Set Code: 20
Display of time: 11:58:22 Parameter Set Version: 620
SW-Version LMV5: 0520
Hours run gas: 70 SW-Version LMV5: 0520
Hours run oil stage 1 or modulating: 0
Hours run oil stage 2: 0
Hours run oil stage 3: 0
Hours run total (can be reset): 70
Hours run total: 70
Hours run device under voltage: 434
start counter gas: 267
start counter oil: 18
start counter total (can be reset): 285
start counter total: 285
Lockout Counter: 225
Volume Gas: ---
Volume Oil: ---
Volume Gas(can be reset): ---
Volume Oil(can be reset): ---

Parameter Burner Control Times


Prepurge time gas: 20 s
Prepurge time oil: 15 s
Interval 1 (ts1-ts2) gas: 2.0 s
Interval 1 (ts1-ts2) oil: 2.0 s
Interval 2 (ts2 operation) gas: 2.0 s
Interval 2 (ts2 operation) oil: 2.0 s
Maximum time to low-fire: 45 s
Postpurge time 3 gas: 5.0 s
Postpurge time 3 oil: 5.0 s
Time to alarm: 35 s
Time until message start prevention: 35 s

Parameter Burner Control Configuration


alarm in the event of start prevention: Deactivated
forced intermittent operation: Deactivated

Page 1
BurnerID 40688294 Date of Backup:08.04.24

"Company Name" Parameters LMV5x


available Parameters of the Service Level

Ratio Control Gas


Actuator Gas Air Aux Aux 1 Aux 2 Aux 3 VSD
Home Position 0.0° 0.0° 0 0.0° 0.0° 0.0° 0.0%
Prepurge Position 90.0° 0 90.0° 90.0° 90.0° 100%
Ignition Position 10.0° 15.0° 0 0.0° XXXX XXXX XXXX
Postpurge Position 15.0° 15.0° 0 25.0° 25.0° 25.0° 50.0%

Program stop: Deactivated


Minimum load "Low fire": 0.0%
Maximum load "High fire": 100.0%
Duration operating ramp mod. operation: 60 s
Duration operating ramp stage operation: 10 s
Duration ramp prepurge and ignition pos.: 60 s
Startpoint Operation: 1
Behavior in Lockout Phase: Home Position
Fuel
Air
Table curve points 100
Chart curve points Aux 1
Load Gas Air Aux 1 Position [°/%]
10.0 10.0 ° 15.0 ° 0.0 ° 90
15.0 16.5 ° 18.0 ° 5.0 °
25.0 25.8 ° 25.0 ° 6.0 ° 80
28.0 29.0 ° 29.1 ° 8.0 ° 70
30.0 31.0 ° 31.0 ° 9.0 °
33.9 33.9 ° 33.0 ° 10.0 ° 60
40.0 35.5 ° 35.0 ° 12.1 °
43.0 37.0 ° 37.0 ° 13.1 ° 50
100.0 44.4 ° 37.1 ° 14.0 ° 40
30
20

10
0 Load [%]
0 10 20 30 40 50 60 70 80 90 100

Page 2
BurnerID 40688294 Date of Backup:08.04.24

"Company Name" Parameters LMV5x


available Parameters of the Service Level

Ratio Control Oil


Actuator Oil Act Air Aux Aux 1 Aux 2 Aux 3 VSD
Home Position 0.0° 0.0° 0 0.0° 0.0° 0.0° 0.0%
Prepurge Position 90.0° 0 90.0° 90.0° 90.0° 100%
Ignition Position 27.4° 9.9° 0 0.0° XXXX XXXX XXXX
Postpurge Position 0.0° 15.0° 0 25.0° 25.0° 25.0° 50.0%

Program stop: Deactivated


Minimum load "Low fire": 0.0%
Maximum load "High fire": 100.0%
Duration operating ramp mod. operation: 60 s
Duration operating ramp stage operation: 10 s
Duration ramp prepurge and ignition pos.: 60 s
Startpoint Operation: 1
Behavior in Lockout Phase: Home Position
Fuel
Air
100
Chart curve points modulating Aux 1
Load Oil Air Aux 1 Position [°/%]
33.3 34.5 ° 30.0 ° 30.0 ° 90
80
70

60
50

40
30
20

10
0 Load [%]
0 10 20 30 40 50 60 70 80 90 100

Table curve points multistage


Air Aux 1
Stage 1 Operating Point XXXX XXXX
Stage 2 Start Point XXXX XXXX
Stage 2 Off Point XXXX XXXX
Stage 2 Operating Point XXXX XXXX
Stage 3 Start Point XXXX XXXX
Stage 3 Off Point XXXX XXXX
Stage 3 Operating Point XXXX XXXX

Page 3
BurnerID 40688294 Date of Backup:08.04.24

"Company Name" Parameters LMV5x


available Parameters of the Service Level

Parameter O2
O2-Sensor: ---
Sup. Air Temp. Sensor: ---
Flue Gas Temp. Sensor: ---
Max. Temp. Flue Gas Gas: 300 °C
Max. Temp. Flue Gas Oil: 300 °C
ASN: ---
Production Date: ---
Serial Number: ---
Parameter Set Code:
Parameter Set Version:
SW-Version: ---

O2 Gas
Operation Mode: Manually deactivated
P Low-Fire: -0.1%
I Low-Fire: 65535 s
P High-Fire: -0.1%
I High-Fire: 65535 s
min. O2-Load: 0.0%
Type of Fuel: Natural Gas H
V_LNmin: 9.90
V_afNmin: 10.93
V_atrNmin: 8.89
A2: 0.65
B / 1000: 9
O2-Offset Gas: 0.0%
Load Control Suspend: 5.0%
O2 Setpoint
O2 Ratio
O2 Min Values
Table O2 Gas 10
Chart O2 Gas Lambda Factor
Load O2 Setpoint O2 Ratio O2 Min ValuesLambda Factor Position [°/%]
9

8
7
6

5
4
3

2
1
0 Load [%]
0 10 20 30 40 50 60 70 80 90 100
Page 4
BurnerID 40688294 Date of Backup:08.04.24

"Company Name" Parameters LMV5x


available Parameters of the Service Level

O2 Oil
Operation Mode: Manually deactivated
P Low-Fire: -0.1%
I Low-Fire: 65535 s
P High-Fire: -0.1%
I High-Fire: 65535 s
min. O2-Load: 0.0%
Type of Fuel: Oil EL
V_LNmin: 11.20
V_afNmin: 12.02
V_atrNmin: 10.53
A2: 0.65
B / 1000: 9
O2-Offset Oil: 0.0%
Load Control Suspend: 5.0%
O2 Setpoint
O2 Ratio
O2 Min Values
Table O2 Oil 10
Chart O2 Oil Lambda Factor
Load O2 Setpoint O2 Ratio O2 Min Values Lambda Factor Position [°/%]
9
8

7
6
5

4
3
2

1
0 Load [%]
0 10 20 30 40 50 60 70 80 90 100

Page 5
BurnerID 40688294 Date of Backup:08.04.24

"Company Name" Parameters LMV5x


available Parameters of the Service Level

Parameter Load Controller


proportional band: 6.4%
integral part: 136 s
differential part: 24 s
Minimum actuator step: 1.0%
Software filter time constant: 3s
setpoint W1: 0 °C
setpoint W2: 0 °C
switching differential burner ON modulating: 1.0%
switching differential burner OFF modulating: 10.0%
switching differential burner ON multistage: -2.0%
switching differential stage 1 OFF: 10.0%
switching differential stage 2 OFF: 8.0%
switching differential stage 3 OFF: 6.0%
Reaction threshold switching stage 2: 300
Reaction threshold switching stage 3: 600
Temperature limiter OFF threshold: 95 °C
Temperature limiter ON threshold: -5 %

cold start (thermal shock protection): Deactivated


Cold start therm. shock prot. ON threshold: 20 %
Cold start therm. shock prot. load step: 10 %
Cold start therm. shock prot. setpoint step (mod.): 5%
Cold start therm. shock prot. setpoint step (multistage): 5 %
Cold start therm. shock prot., max. time (mod.): 3 min
Cold start therm. shock prot., max. time (multistage): 3 min
Cold start therm. shock prot. OFF threshold: 80 %
Additional Sensor: Deactivated
Setpoint Add Sensor: 60 °C
Release Stages: Release

Operating Mode: Ext Load Controller X5-03


Input 1/2/4 Selection: No Sensor
End of Measurement Range Inputs 1 and 4: 150°C/302°F
Configuration Input 2: 0..10 V
End of Temperature Measurement Range Input 2: 90 °C
End of Pressure Measurement Range Input 2: 2.0 bar
Configuration Input 3: 4..20 mA
Minimum external Setpoint Input 3: 0%
Maximum external Setpoint Input 3: 60 %
Adaption Load: 100%

SW-Version: 0210

Page 6
BurnerID 40688294 Date of Backup:08.04.24

"Company Name" Parameters LMV5x


available Parameters of the Service Level

Parameter AZL
Password Time:
Summer/Winter Time: Automatic
Setting the summer-/wintertime US/EU: Summer/wintertime EU
Language: Francais
date format: DD.MM.YY
Unit Temperature:
Unit Pressure: Display bar
eBUS Adress: 1
Cycle time sending burner control's operating data: 30 s
Modbus Adress: 1
Modbus Baudrate: 19200 bit/s
Modbus-Parity: No
Modbus Timeout: 30 s
ASN: AZL52.00B1WH
Production Date: 31.05.22
Serial Number: 63
Parameter Set Code: 20
Parameter Set Version: 600
SW-Version: 0510

Parameter Actuators
Air Actuator Gas Actuator (Oil) Oil Actuator Aux Actuator
ASN SQM48.497B9WH SQM45.291B9WH SQM48.497B9WH SQM48.697B9WH
Production Date 16.02.22 07.04.22 21.04.22 21.04.22
Serial Number 5 24 19 9
Parameter Set Code 20 20 20 20
Parameter Set Version 104 104 104 104
SW-Version 0170 0170 0170 0170

Aux Act 2 Aux Act 3


ASN --- ---
Production Date --- ---
Serial Number --- ---
Parameter Set Code
Parameter Set Version
SW-Version --- ---

Permitted tolerance between the 2 potentiometer values: 15

Page 7
BurnerID 40688294 Date of Backup:08.04.24

"Company Name" Parameters LMV5x


available Parameters of the Service Level

Parameter VSD Modul


Pulses per Rotation: ---
Standardized Speed: ---
Setpoint Output: ---
Pulse Value Gas: ---
Puls Value Oil: ---
ASN: ---
Production Date: ---
Serial Number: ---
Parameter Set Code:
Parameter Set Version:
SW-Version: ---

Backup Info
Date of Backup: 08.04.24
Time of Backup: 13:44:44
BU included Yes
DOU included Yes
LC included: Yes
ACT1 included: Yes
ACT2 included: Yes
ACT3 included: Yes
ACT4 included: Yes
ACT5 included: No
ACT6 included: No
VSD included: No
O2 Modul included: No