Product Manual: 6 MM Series of Temperature Converters

The document is a product manual for the 3000 series of temperature converters, detailing their features, safety instructions, and installation guidelines. It emphasizes the reliability and performance of the devices in industrial environments, highlighting their compliance with safety standards and ease of integration. The manual includes technical specifications, programming instructions, and troubleshooting tips to assist users in proper device operation.

Uploaded by

umar.siddique
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
28 views21 pages

Product Manual: 6 MM Series of Temperature Converters

The document is a product manual for the 3000 series of temperature converters, detailing their features, safety instructions, and installation guidelines. It emphasizes the reliability and performance of the devices in industrial environments, highlighting their compliance with safety standards and ease of integration. The manual includes technical specifications, programming instructions, and troubleshooting tips to assist users in proper device operation.

Uploaded by

umar.siddique
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 21

PERFORMANCE

MADE
SMARTER

Product manual
3000
6 mm series of
temperature converters

ZONE 2 Zone 2 ZONE 2 / DIV 2

T E M P E R AT U R E   |   I . S . I N T E R FA C E S   |   CO M M U N I C AT I O N I N T E R FA C E S   |   M U LT I F U N C T I O N A L   |   I S O L AT I O N   |   D I S P L AY

Models no. 3 101 / 3102 / 3111 / 3112 / 3113 /


3331 / 3333 / 3337
No. 30 0 0V10 6 - UK
6 Product Pillars
to meet your every need
Individually outstanding, unrivalled in combination
With our innovative, patented technologies, we make signal conditioning smarter and simpler. Our portfolio is composed of six
product areas, where we offer a wide range of analog and digital devices covering over a thousand applications in industrial
and factory automation. All our products comply with or surpass the highest industry standards, ensuring reliability in even
the harshest of environments and have a 5-year warranty for greater peace of mind.

Our range of temperature transmitters and sensors provides the highest level of signal integrity from the
measurement point to your control system. You can convert industrial process temperature signals to analog, bus or
digital communications using a highly reliable point-to-point solution with a fast response time, automatic self-
calibration, sensor error detection, low drift, and top EMC performance in any environment.
Temperature

We deliver the safest signals by validating our products against the toughest safety standards. Through our
commitment to innovation, we have made pioneering achievements in developing I.S. interfaces with SIL 2 Full
Assessment that are both efficient and cost-effective. Our comprehensive range of analog and digital intrinsically
safe isolation barriers offers multifunctional inputs and outputs, making PR an easy-to-implement site standard.
I.S. Interface Our backplanes further simplify large installations and provide seamless integration to standard DCS systems.

We provide inexpensive, easy-to-use, future-ready communication interfaces that can access your PR installed base
of products. All the interfaces are detachable, have a built-in display for readout of process values and diagnostics,
and can be configured via push-buttons. Product specific functionality includes communication via Modbus and
Bluetooth and remote access using our PR Process Supervisor (PPS) application, available for iOS and Android.
Communication

Our unique range of single devices covering multiple applications is easily deployable as your site standard. Having
one variant that applies to a broad range of applications can reduce your installation time and training, and greatly
simplify spare parts management at your facilities. Our devices are designed for long-term signal accuracy, low
power consumption, immunity to electrical noise and simple programming.
Multifunction

Our compact, fast, high-quality 6 mm isolators are based on microprocessor technology to provide exceptional
performance and EMC-immunity for dedicated applications at a very low total cost of ownership. They can be
stacked both vertically and horizontally with no air gap separation between units required.

Isolation

Our display range is characterized by its flexibility and stability. The devices meet nearly every demand for display
readout of process signals and have universal input and power supply capabilities. They provide a real-time
measurement of your process value no matter the industry and are engineered to provide a user-friendly and reliable
relay of information, even in demanding environments.
Display
6 mm series of
temperature converters
3101 / 3102 / 3111 / 3112 / 3113 /
3331 / 3333 / 3337

Table of contents
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Symbol identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Mounting / demounting of system 3000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Installation on DIN rail / power rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Flexible supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Technical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Product overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
DIP-switch configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Temperature range programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Operation & troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
UL installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
IECEx, ATEX and UKEX installation in Zone 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
cFMus installation in Division 2 or Zone 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Document history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

3100V106-UK 3
Warnings
To avoid the risk of electric shock and fire, the safety instructions of this product manual must be
observed, and the guidelines followed. The specifications must not be exceeded, and the device must
only be applied as described in the following.
Prior to the commissioning of the device, this product manual must be examined carefully.
Only qualified personnel (technicians) should install this device. If the equipment is used in a manner not
GENERAL specified by the manufacturer, the protection provided by the equipment may be impaired.

To avoid explosion and serious injury: Modules having mechanical failures must be returned to PR
electronics for repair or replacement.

Repair of the device and replacement of circuit breakers must be done by PR electronics A/S only.

Until the device is fixed, do not connect hazardous voltages to the device.

In applications where hazardous voltage is connected to in-/outputs of the device, sufficient spacing or
HAZARDOUS isolation from wires, terminals, and enclosure - to surroundings (incl. neighboring devices), must be
VOLTAGE ensured to maintain protection against electric shock.

Potential electrostatic charging hazard. To avoid the risk of explosion due to electrostatic charging of the
enclosure, do not handle the units unless the area is known to be safe, or appropriate safety measures
are taken to avoid electrostatic discharge.

CAUTION

Symbol identification
Triangle with an exclamation mark: Warning /demand. Potentially lethal situations. Read the manual
before installation and commissioning of the device in order to avoid incidents that could lead to
personal injury or mechanical damage.

The CE mark proves the compliance of the device with the essential requirements of the EU directives.

The UKCA mark proves the compliance of the device with the essential requirements of the UK
regulations.

Ex devices have been approved acc. to the ATEX directive for use in connection with installations in
explosive areas. See installation instructions.

4 3100V106-UK
Safety instructions
Receipt and unpacking
Unpack the device without damaging it and check whether the device type corresponds to the one ordered. The packing
should always follow the device until this has been permanently mounted.
Environment
Avoid direct sun light, dust, high temperatures, mechanical vibrations and shock, and rain and heavy moisture. If necessary,
heating in excess of the stated limits for ambient temperatures should be avoided by way of ventilation.
The device must be installed in pollution degree 2 or better.
The device is designed to be safe at least under an altitude up to 2000 m.
The device is designed for indoor use.
Mounting
Only technicians who are familiar with the technical terms, warnings, and instructions in the manual and who are able to
follow these should connect the device. Should there be any doubt as to the correct handling of the device, please contact
your local distributor or, alternatively,
PR electronics A/S
www.prelectronics.com

Mounting and connection of the device should comply with national legislation for mounting of electric materials, e.g. wire
cross section, protective fuse, and location.

Descriptions of input / output and supply connections are shown in the block diagram and side label.

The device is provided with field wiring terminals and shall be supplied from a Power Supply having double / reinforced
insulation. A power switch should be easily accessible and close to the device. The power switch shall be marked as the
disconnecting unit for the device.

SYSTEM 3000 must be mounted on a DIN rail according to EN 60715.

Year of manufacture can be taken from the first two digits in the serial number.
Cleaning
When disconnected, the device may be cleaned with a cloth moistened with distilled water.
Liability
To the extent the instructions in this manual are not strictly observed, the custom­er cannot advance a demand against PR
electronics A/S that would otherwise exist according to the concluded sales agreement.

3100V106-UK 5
Mounting / demounting of system 3000

Mounting on DIN rail / power rail (Fig.1) Demounting from DIN rail / power rail (Fig.2)
Click the device onto the rail First, remember to demount the connectors with
hazardous voltages.
Detach the device from the rail by moving the bottom
lock down.

System 3000 devices can be mounted on DIN rail or power rail (where applicable).
When installing system 3000 devices with power rail connectors on a standard 7.5 mm DIN rail the head of the
screws holding the rail shall be no more than 3.5 mm high to prevent potential short circuit of the power rail
connectors.
35 mm
> 24 mm

< 3.5 mm

6 3100V106-UK
Installation on DIN rail / power rail
System 3000 devices can be installed on a DIN rail or on a power rail.

Module stop

For marine applications, the devices must be supported by a module stop (PR part number 9404).

Power supply units can be mounted on the power rail according to customer requirements.

Marking
The front cover of the 3000 devices has been designed with an area for affixation of a click-on marker. The area assigned to
the marker measures 5 x 7.5 mm. Markers from Weidmüller’s MultiCard System, type MF 5/7.5, are suitable.

3100V106-UK 7
Flexible supply

The technical specifications specify the maximum required power at nominal operating values, e.g. 24 V supply voltage, 60°C
ambient temperature, 600 Ω load, and 20 mA output current.
External protective fuses may be required depending on power source selected. Protective fuse ratings are specified below.

DIN rail solution - device daisy chain: Power rail solution #2:
The 3101, 3102, 3111, 3112 and 3113 can be The PR 3405 power connector unit allows
supplied with 24 VDC ±30% via direct wiring easy connection of a 24 VDC / 2.5 A source to
and a loop between the devices. the power rail.
Protective fuse: 2.5 A. Protective fuse: 2.5 A.

3405

Protective fuse: 0.4 A. Protective fuse: Located inside the PR 9410.


Power rail solution #1: Power rail solution #3:
Alternately, you can connect 24 VDC to any The PR 9410 power control unit can energize
one 3111, 3112, 3113 device with power rail and power 96 W to the rail. Redundant power
connector which will then energize other supplies are possible.
units on the rail.

Note:
Device type 3101, 3102, 3111-N, 3112-N, 3113-N, 3331, 3333 and 3337 can only be supplied via the DIN rail solution with
direct wiring on each device.

External fuse characteristics:


The 2.5 A fuse must break after not more than 120 seconds at 6.4 A.

8 3100V106-UK
6 mm series of temperature and converters
3101 / 3102 / 3111 / 3112 / 3113 / 3331 / 3333 / 3337

• Converts process measurements from Pt100, TC J and K temperature sensors to


voltage or current outputs
• Multiple pre-calibrated temperature ranges are selectable via DIP-switches
• High accuracy, better than 0.05% and excellent 50/60 Hz noise suppression
• Fast signal response time < 30 ms
• 3113 and 3337 with HART 7 protocol and fast signal response time < 60 ms
• HART 7 protocol enables extended device programming for 3113 and 3337

Applications
• The temperature converters measure standard 2-, 3- or 4-wire Pt100 and/or TC J & K temperature sensors, and provides
an analog voltage or current output.
• High 3 port isolation provides surge suppression and protects the control system from transients and noise.
• The loop powered devices have high 2-port galvanic separation to eliminate ground loops.
• The devices can be mounted in the Safe area or in Zone 2 / Division 2 areas.
• Approved for marine applications.
Technical characteristics
• High conversion accuracy, better than 0.05% of span.
• A visible green LED indicates operational status and status of the input sensor.
• All terminals are protected against overvoltage and polarity error.
• Meeting the NAMUR NE21 recommendations, the system 3000 devices ensure top measurement performance in harsh
EMC environments.
• The devices meet the NAMUR NE43 standard defining out of range and sensor error output values.
• High galvanic isolation of 2.5 kVAC.
• Excellent signal/noise ratio of > 60 dB.
• Wide temperature operation range of -25...+70°C.
Programming
• Selectable DIP-mode for easy configuration of more than 1000 factory calibrated measurement ranges with HART read
only feature.
• Selectable HART-mode to enable full HART read-write capabilitytur
Mounting
• Units can be mounted side by side, horizontally and vertically, without air gap on a standard DIN rail, even at 70°C ambient
temperature.
• Units can be supplied separately (3101 / 3102 / 3331 / 3333 / 3337) or installed on PR 9400 power rail (3111 / 3112 /
3113).
• The narrow 6.1 mm housing allows up to 163 units per meter.

3100V106-UK 9
Connections
Input wiring

4
+ 3
CJC
- 2

1
External CJC
(2- or 3-wire Pt100)

+ - CJC Type
- - - 3 2 Y* 3101 *3101 - only
1,2 & 3,4 1,2 & 3 2&3 - - N 3102 internal CJC

- - - 3 2 Y 3111
1,2 & 3,4 1,2 & 3 2&3 - - N 3112
1,2 & 3,4 1,2 & 3 2&3 3 2 Y 3113
1,2 & 3,4 1,2 & 3 2&3 3 2 Y 3331

112 mm
1,2 & 3,4 1,2 & 3 2&3 - - N 3333
1,2 & 3,4 1,2 & 3 2&3 3 2 Y 3337
3xxx Housing

106.5 mm
115 mm

Output wiring
+ Vsupply Supply wiring
+ + +
5

6
mA V 4...20 mA
- - - +
7
24 VDC
8
-
107 mm

Power
HART + - + - + - + - rail

6.1 mm
3101 N 5 6 5 6 - - 7 8 N
3102 N 5 6 5 6 - - 7 8 N
112 mm

3111 N 5 6 5 6 - - 7 8 Y
3111-N N 5 6 5 6 - - 7 8 N
3112 N 5 6 5 6 - - 7 8 Y
3112-N N 5 6 5 6 - - 7 8 N
3113 Y 5 6 - - - - 7 8 Y
3113-N Y 5 6 - - - - 7 8 N
3331 N - - - - 5 6 - - N
3333 N - - - - 5 6 - - N
3337 Y - - - - 5 6 - - N
3405 N - - - - - - 7 8 Y

3101, 3102 and 3333: No galvanic isolation


3331 and 3337: 2 port isolation (reinforced)
3111, 3112 and 3113: 3 port isolation (reinforced)

10 3100V106-UK
Product overview
Input Output
TC Pt100 Current
LED Supply Isolated HART
Ext. 2-, 3-, Volt­age
J & K Int. CJC Active Passive
CJC 4-wire
3101      24 VDC
3102     24 VDC
24 VDC /
3111       2.5 kV
power rail
3111-N       24 VDC 2.5 kV
24 VDC /
3112     2.5 kV
power rail
3112-N     24 VDC 2.5 kV
24 VDC /
3113       2.5 kV 
power rail
3113-N       24 VDC 2.5 kV 
3331      Loop-powered 2.5 kV
3333   Loop-powered
3337      Loop-powered 2.5 kV 

Order

Type Version

3101 TC converter Supplied via terminals :-

3102 Pt100 converter Supplied via terminals :-

3111 TC converter - isolated With power rail connector / terminals :-


Supplied via terminals : -N

3112 Pt100 converter - isolated With power rail connector / terminals :-


Supplied via terminals : -N

3113 HART 7 temperature converter - isolated With power rail connector / terminals :-
Supplied via terminals : -N

3331 Temperature converter, loop-powered - Supplied via terminals :-


isolated

3333 Pt100 converter, loop-powered Supplied via terminals :-

3337 HART 7 temperature converter, loop- Supplied via terminals :-


powered

Example: 3112-N (Pt100 converter - isolated, supplied via terminals)


Accessories

9404 = Module stop for rail

Accessories for power rail devices

3405 = Power rail connector unit


9400 = Power rail - 7.5 or 15 mm high
9410 = Power control unit
9421 = Power supply

3100V106-UK 11
Technical data

Environmental conditions:
Operating temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -25°C to +70°C
Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -40°C to +85°C
Calibration temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20...28°C
Relative humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 95% RH (non-cond.)
Protection degree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP20
Installation in pollution degree 2 & overvoltage category II.
Mechanical specifications:
Dimensions (HxWxD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 x 6.1 x 115 mm
Weight approx. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 g
DIN rail type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DIN EN 60715 - 35 mm
Wire size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.13...2.5 mm2 / AWG 26...12 stranded wire
Screw terminal torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.5 Nm
Vibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IEC 60068-2-6
2...25 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±1,6 mm
25...100 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±4 g
Common electrical specifications:
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16.8...31.2 VDC
Loop-powered:
3331 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.5...35 VDC
3333 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.3...35 VDC
3337 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2...35 VDC
Power requirements:
Max. power Max. required
Type
dissipation power
3101 0.52 0.52
3102 0.52 0.52
3111 0.70 0.70
3112 0.70 0.70
3113 0.70 0.70
3331 0.80 0.80
3333 0.80 0.80
3337 0.80 0.80

Max. required power is the maximum power needed at power supply terminals or rail connector.
Max. power dissipation is the maximum power dissipated at nominal operating values.
Isolation voltage, test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5 kVAC
Isolation voltage working . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300 VAC (reinforced) /
250 VAC (Zone 2, Div. 2)
Double isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input / output 1 / output 2 / supply
Signal dynamics, input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 bit
Signal dynamics, output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 bit
Signal / noise ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Min. 60 dB
Long-term stability, better than (only 3113) . . . . . . . . . . . . . . . . . . ±0.1% of span / year (±0.3% of span / 5 years)

12 3100V106-UK
Response time
HART read only
Selectable HART mode
mode

< 30 ms < 300 ms < 60 ms 0.06...60 s

3101  
3102  
3111  
3112  
3113  
3331  
3333  
3337  

Incorrect DIP-sw setting identification:


Supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 V / 0 mA output; LED 0.5 s / 1 Hz
Loop-powered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.5 mA output
Accuracy

Device Input Basic accuracy General accuracy Temperature coefficient

3112, 3113, 0.02°C/°C (basic) or


Pt100 ≤ 0.1°C
3331, 3337 ≤ ± 0.01% of span / °C
≤ ± 0.05%
of span
3111, 3113, 0.1°C/°C (basic) or
TC ≤ 0.5°C
3331, 3337 ≤ ± 0.01% of span / °C

0.02°C/°C (basic) or
3102, 3333 Pt100 ≤ 0.2°C
≤ ± 0.1% of ≤ ± 0.01% of span / °C
span 0.1°C/°C (basic) or
3101 TC ≤ 1°C
≤ ± 0.01% of span / °C

EMC immunity influence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < ±0.5% of span


Extended EMC immunity:
NAMUR NE 21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < ±1% of span
Input specifications:
Specifications for Pt100 input:
Temperature range, Pt100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -200...+850°C - IEC 60751
Min. measuring range (span) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10°C
Sensor current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 150 mA
Sensor cable resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 50 W per wire
Effect of sensor cable resistance, 3- / 4-wire . . . . . . . . . . . . . . . . . . < 0.002 Ω / Ω
Sensor error detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes - selectable via DIP-switch
Broken sensor detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . > 800 Ω
Shorted sensor detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 18 Ω
Specifications for TC input:
Temperature range, TC J . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -100...+1200°C - IEC 60584-1
Min. measuring range (span) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50°C
Temperature range, TC K . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -180...+1372°C - IEC 60584-1
Min. measuring range (span) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50°C
Sensor cable resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 5 kΩ per wire
Cold junction compensation (CJC) accuracy:
Accuracy @ external Pt100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . Better than ±0.15°C
Accuracy @ internal CJC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Better than ±2.5°C

3100V106-UK 13
Open Thermocouple detection . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes – selectable via DIP-switch
Internal CJC error detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes
External CJC error detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes – selectable via DIP-switch
Output specifications:
Current output
Selectable NAMUR NE43
Active Passive Range Max. load
Invert Range Limit Sensor error
4...20 mA
3101  0/4...20 mA 0/3.8...20.5 mA 0/3.5/23 mA  ≤ 600 Ω
3102  0/4...20 mA 0/3.8...20.5 mA 0/3.5/23 mA  ≤ 600 Ω
3111  0/4...20 mA 0/3.8...20.5 mA 0/3.5/23 mA  ≤ 600 Ω
3112  0/4...20 mA 0/3.8...20.5 mA 0/3.5/23 mA  ≤ 600 Ω
3113  4...20 mA 0/3.8...20.5 mA 0/3.5/23 mA  ≤ 600 Ω
3331   4...20 mA 3.8...20.5 mA 3.5 / 23 mA  (Vsupply-5.5)/0.023 [Ω]
3333   4...20 mA 3.8...20.5 mA 3.5 / 23 mA  (Vsupply-3.3)/0.023 [Ω]
3337   4...20 mA 3.8...20.5 mA 3.5 / 23 mA  (Vsupply-6.2)/0.023 [Ω]

Updating time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 ms
Load stability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≤ 0.01% of span / 100 Ω

Selectable voltage output


Low range High range
Sensor Sensor Min. load
Range Limit Range Limit
error error

3101, 3102,
0/1...5 V 0/0.875...5.125 V 0/5.5 V 0/2...10 V 0/1.75...10.25 V 0/11 V 10 kΩ
3111, 3112

of span = of the selected range

Observed authority requirements:


EMC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2014/30/EU & UK SI 2016/1091
EMC Emission . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CISPR 22, Class B
LVD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2014/35/EU & UK SI 2016/1101
RoHS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2011/65/EU & UK SI 2012/3032
ATEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2014/34/EU & UK SI 2016/1107
EAC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TR-CU 020/2011
EAC Ex . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TR-CU 012/2011
Approvals:
DNV, Ships & Offshore . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TAA00001RW
c UL us, UL 61010-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E314307
I.S. / Ex approvals:
ATEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KEMA 10ATEX0147 X
IECEx . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KEM 10.0068 X
UKEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DEKRA 21UKEX0055X
c FM us . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FM17US0004X / FM17CA0003X
EAC Ex . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RU C-DK.HA65.B.00355/19

14 3100V106-UK
DIP-switch configuration
Applicable devices can be configured via DIP-switches. The DIP-switches are located on the side of the device and can be
adjusted with a small screwdriver or other implement.

ON
1
2
3
4
5
6
7
8
9
10

Default factory settings (with all DIP-switches in the OFF position):

3102, 3112, 3331, 3333 3101, 3111 3113, 3337


Sensor type Pt100, 3 wire TC K (int. CJC) Pt100, 3 wire
Output range 4...20 mA 4...20 mA 4...20 mA
Error detection Short circuit detection Short circuit detection Short circuit detection
Broken circuit detection Broken circuit detection
Error output current 3.5 mA 3.5 mA 3.5 mA
Noise suppression 50 Hz 50 Hz 50 Hz
Input lower limit 0°C 0°C 0°C
Input upper limit 150°C 600°C 150°C
Response time < 30 ms < 30 ms < 60 ms
Configuration mode - - DIP switch configuration

DIP-switch settings
3101 and 3111 3102 and 3112 3113 and 3337
TC J & K Pt100 Pt100 & TC J/K + HART

*3101 - only int. CJC

3331 3333
Pt100 & TC J/K Pt100

Remember to cycle power for power rail / terminals to reload DIP-switch values at power up.

For easy DIP-switch programming, our DIP-switch configurator can be found at:
www.prelectronics.com/dip-switch-configurator/

3100V106-UK 15
Temperature range programming

Please note:
• 3101 and 3111 - only TC input available
Valid TC J range: -100...+1200°C = correct DIP-switch setting
Valid TC K range: -180...+1372°C = correct DIP-switch setting
• 3102, 3112 and 3333 - only Pt100 input available
Valid Pt100 range: -200...+850°C = correct DIP-switch setting
• ”Start temp” must be lower than ”End temp” = correct DIP-switch setting
• Power must be cycled after DIP-switch positions are changed

16 3100V106-UK
Operation & troubleshooting
The 3000 series devices provide multiple features for easy user operation and for performing efficient troubleshooting.

Monitoring the operational status is easy from the front LED.

Status indicator front LED


For 3101, 3102, 3111, 3112 and 3113

Power - Green

Output and
Condition LED Action required
loop supply
Connect supply /
No supply / device error OFF De-energized
replace device
1 Flash
Power-up or restart De-energized -
(0.5 s OFF + 0.5 s ON)
Flashing 13 Hz
Device OK Energized -
(15 ms ON)
Flashing 1 Hz Correct setting and
Incorrect DIP-switch setting De-energized
(500 ms ON) re-power device

Flashing 1 Hz
Sensor error indication Up- or Downscale Check sensor
(15 ms ON)

3100V106-UK 17
Installation instructions
UL installation
Use 60/75°C copper conductors only.
Wire size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AWG 26-12
UL file number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E314307
The device is an Open Type Listed Process Control Equipment. To prevent injury resulting from accessibility to live parts the
equipment must be installed in an enclosure. The power Supply unit must comply with NEC Class 2, as described by the
National Electrical Code® (ANSI / NFPA 70).
IECEx, ATEX and UKEX installation in Zone 2
IECEx KEM 10.0068 X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ex ec IIC T4 Gc
KEMA 10ATEX0147 X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I 3 G Ex ec IIC T4 Gc
DEKRA 21UKEX0055X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . II 3 G Ex ec IIC T4 Gc

For safe installation, the following must be observed. The device shall only be installed by qualified personnel who are familiar
with the national and international laws, directives and standards that apply to this area.

The devices shall be installed in a suitable enclosure providing a degree of protection of at least IP54 according to EN IEC
60079-0, taking into account the environmental conditions under which the equipment will be used.

When the temperature under rated conditions exceeds 70°C at the cable or conduit entry point, or 80°C at the branching point
of the conductors, the temperature specification of the selected cable shall be in compliance with the actual measured
temperature.

To prevent ignition of the explosive atmospheres, disconnect power before servicing and do not separate connectors when
energized and an explosive gas mixture is present.

For installation on power rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit type 9410 is allowed.

Do not mount or remove devices from the power rail when an explosive gas mixture is present.
cFMus installation in Division 2 or Zone 2
FM17CA0003X / FM17US0004X . . . . . . . . . . . . . . . . . . . . . . . . .  lass I, Div. 2, Group A, B, C, D T4 or
C
Class I, Zone 2, AEx nA IIC T4 or Ex nA IIC T4

In class I, Division 2 or Zone 2 installations, the subject equipment shall be mounted within a tool-secured enclosure which is
capable of accepting one or more of Class I, Division 2 wiring methods specified in the National Electrical Code (ANSI/NFPA 70)
or in Canada in the Canadian Electrical Code (C22.1).

The 3000 System Isolators and Converters must be connected to limited output NEC Class 2 circuits, as outlined in the
National Electrical Code® (ANSI / NFPA 70), only. If the devices are connected to a redundant power supply (two separate
power supplies), both must meet this requirement.

Where installed in outdoor or potentially wet locations the enclosure shall at a minimum meet the requirements of IP54.

Warning: Substitution of components may impair suitability for zone 2 / division 2.

Warning: To prevent ignition of the explosive atmospheres, disconnect power before servicing and do not separate
connectors when energised and an explosive gas mixture is present.

Warning: Do not mount or remove devices from the power rail when an explosive gas mixture is present.

18 3100V106-UK
Document history
The following list provides notes concerning revisions of this document.
Rev. ID Date Notes
103 1803 Models 31xx-N added.
Specifications for max. required power and power
dissipation added.
PESO/CCOE approval added.
104 2037 EAC Ex approval added.
PESO/CCOE approval discontinued .
105 2108 ATEX and IECEx approvals updated - Ex na changed
to Ex ec.
Side label updated.
106 2205 UKEX approval added.
We are near you,
all over the world
Our trusted red boxes are supported wherever you are

All our devices are backed by expert service and a 5-year business with a global reach. This means that we are
warranty. With each product you purchase, you receive always nearby and know your local markets well.
personal technical support and guidance, day-to-day We are committed to your satisfaction and provide
delivery, repair without charge within the warranty period PERFORMANCE MADE SMARTER all around the world.
and easily accessible documentation.
For more information on our warranty program, or to
We are headquartered in Denmark, and have offices and meet with a sales representative in your region, visit
authorized partners the world over. We are a local prelectronics.com.
Benefit today from
PERFORMANCE MADE SMARTER

PR electronics is the leading technology company specialized in making industrial process


control safer, more reliable and more efficient. Since 1974, we have been dedicated to
perfecting our core competence of innovating high precision technology with low power
consumption. This dedication continues to set new standards for products communicating,
monitoring and connecting our customers’ process measurement points to their process
control systems.

Our innovative, patented technologies are derived from our extensive R&D facilities and
from having a great understanding of our customers’ needs and processes. We are guided
by principles of simplicity, focus, courage and excellence, enabling some of the world’s
greatest companies to achieve PERFORMANCE MADE SMARTER.

www.prelectronics.com

You might also like