Masterys Ip PDF
Masterys Ip PDF
MASTERYS IP+
                                                           40-60 kVA 3/1
                                                                                                                                                                                                                                                                  ENGLISH
                            3.4 Electrical requirements . . . . . . . . . . . . . . .                               .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   11
                            3.5 Identifying switching and connection organs .                                       .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   13
                            3.6 Installation procedures and instructions . . . .                                    .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   14
                            3.7 Connection of the generator . . . . . . . . . . .                                   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   16
                            3.8 External E.S.D. connection . . . . . . . . . . . . .                                .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   16
                            3.9 Isolation transformer . . . . . . . . . . . . . . . .                               .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   16
                            3.10 ADC card with temperature sensor. . . . . . .                                      .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   16
                            3.11 External battery cabinet connection . . . . . .                                    .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   19
                     4. MODES OF OPERATION . . . . . . . . . . . . . . . . . . . . .                                .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   20
                           4.1 ON LINE operations . . . . . . . . . . . . . . . . .                                 .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   20
                           4.2 Operation in high efficiency mode. . . . . . . .                                     .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   21
                           4.3 Operation with manual maintenance bypass .                                           .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   21
                           4.4 Operation with maintenance bypass . . . . . .                                        .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   21
                           4.5 Operation in GE configuration . . . . . . . . . .                                    .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   21
                     5. ACCESS TO CONTROLS AND COMMUNICATION INTERFACES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
                            5.1 Functions of the switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
                     6. MIMIC PANEL . . . . . . . . . . . . . . . . .       .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   23
                            6.1 Mimic Panel . . . . . . . . . . . .         .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   23
                            6.2 Meaning of ideograms . . . . .              .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   24
                            6.3 Meaning of the luminous bar .               .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   25
                            6.4 Mimic panel menu. . . . . . . .             .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   25
                     7. OPERATING PROCEDURES . . . . . . . . . .                .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   27
                            7.1 Start-up in normal mode . . . . .               .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   27
                            7.2 Shutdown . . . . . . . . . . . . . .            .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   27
                            7.3 Extended out of service. . . . . .              .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   27
                            7.4 Switching onto manual bypass .                  .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   28
                            7.5 Return to normal mode. . . . . .                .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   28
                            7.6 Emergency shutdown (ESD) . . .                  .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .    .   .   .   .   .   .   .   .   28
                                                                                                                                                                                                                            IOMMASIPXX07-GB 02               3
Downloaded from www.Manualslib.com manuals search engine
                     INDEX                                                                                                                                      MASTERYS IP+
                                                                                                                                                                                                                            40-60 kVA 3/1
                     8. MENU . . . . . . . . . . . . . . . . . . . .    .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   29
                            8.1 “Alarms” menu. . . . . . . . .          .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   29
                            8.2 ”Measurements” menu . . .               .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   30
                            8.3 ”Commands” menu . . . . .               .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   31
                            8.4 ”Parameters” menu. . . . . .            .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   32
                            8.5 ”Service” menu . . . . . . . .          .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   32
                            8.6 ”Event log” menu . . . . . . .          .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   35
                            8.7 Mimic panel concentrator .              .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   35
          ITALIANO
                     9. COMMUNICATION . . . . . . . . . . . . .             .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   36
           ENGLISH
                           91 Multi-Level Communication .                   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   36
                           9.2 Standard Lan web page . . .                  .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   37
                           9.3 Accessories and SW options .                 .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   44
                     10. PROBLEM SOLVING . . . . . . . . . .        .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   46
                             10.1 System alarms . . . . . . .       .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   46
                             10.2 UPS Alarms. . . . . . . . .       .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   46
                             10.3 Preventive maintenance            .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   48
                     11. OPTIONS . . . . . . . . . . . . . . . . . . . . . . . .                .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   49
                              11.1 Kit GSS (Global Supply System) . . .                         .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   49
                              11.2 Isolation Controller . . . . . . . . . . .                   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   49
                              11.3 Remote mimic panel. . . . . . . . . .                        .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   49
                              11.4 ACS PCB. . . . . . . . . . . . . . . . . .                   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   49
                              11.5 Separate auxiliary power supply . .                          .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   49
                              11.6 ADC card with temperature sensor.                            .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   49
                              11.7 External back-feed protection . . . .                        .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   50
                     12. TECHNICAL SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
                     PARALLEL 1+1 REDUNDANT CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
4 IOMMASIPXX07-GB 02
                     This SOCOMEC UPS continuous power system is guaranteed against any manufacturing and material defects.
                     The period of validity of the warranty is 12 (twelve) months from the date of commissioning, if said activation is
                     carried out by SOCOMEC UPS personnel or personnel from a support centre authorised by SOCOMEC UPS, and not
                     however more than 15 (fifteen) months from the date of shipment by SOCOMEC UPS.
                     The warranty is recognized within national territory. If the UPS is exported out of national territory, the warranty shall
                     be limited to the cover of the parts used to repair the fault.
                     The warranty is valid ex-works and covers labour and parts used to repair the fault.
                                                                                                                                                       ENGLISH
                     The warranty shall not apply in the following cases:
                     • Failures due to fortuitous circumstances or force majeure (lightning, floods, etc.);
                     • Failures due to negligence or improper use (use out of tolerance: temperature, humidity, ventilation, electric pow-
                       er supply, applied load, batteries);
                     • Insufficient or inadequate maintenance;
                     • Attempted maintenance, repairs or modifications not carried out by SOCOMEC UPS personnel or personnel from
                       a support centre authorised by SOCOMEC UPS.
                     • If the battery has not been recharged in accordance with the terms indicated on the packaging and in the manual,
                       in cases of extended storage or UPS inactivity.
                     SOCOMEC UPS may, at its own discretion, opt for the repair of the product or for the replacement of the faulty or
                     defective parts with new parts or with used parts that are equivalent to new parts with regard to functions and
                     performance.
                     Defective or faulty parts replaced free of charge are to be put at the disposal of SOCOMEC UPS who becomes the
                     sole owner.
                     Replacements or repairs of parts and any modifications to the product during the warranty period cannot extend
                     the duration of the warranty.
                     In no case will SOCOMEC UPS be responsible for damages (including, without limitations, damage for loss of earn-
                     ings, interruption of activity, loss of information or other economic losses) deriving from the use of the product.
                     The present conditions are subject to Italian law. Any dispute falls under the province of the Court of Vicenza.
                                                                                                                              IOMMASIPXX07-GB 02   5
Downloaded from www.Manualslib.com manuals search engine
                         2           SAFETY                                                        MASTERYS IP+
                                                                                                                             40-60 kVA 3/1
                     2.1 IMPORTANT.
                     • This document provides important instructions for the safe use, movement and connection of the MASTERYS™ un-
                       interruptible power system (UPS).
                     • SOCOMEC UPS retains the full and exclusive ownership rights over this document. Only a personal right to utilize
                       the document for the application indicated by SOCOMEC UPS is granted to the recipient of such document. All
                       reproduction, modification, dissemination of this document whether in part or whole and by any manner are
                       expressly prohibited except upon Socomec’s express prior written consent.
                     • This document is not a specification. SOCOMEC UPS reserves the right to make any changes to data without prior
                       notice.
          ITALIANO
           ENGLISH
• The unit must be installed and activated only by qualified technical personnel and authorised by SOCOMEC UPS.
The UPS MUST only be moved by two people at least bt the mean of a forklift.
                     • Before connecting any external battery cabinet, ensure that it is fully compatible with the model of UPS it is to be
                       used with.
                     • The use of external battery cabinets not supplied by the manufacturers is not recommended.
6 IOMMASIPXX07-GB 02
                     • Switch off and isolate the UPS and then wait for 5 minutes before removing the protection panels in order to carry
                       out work on parts under dangerous voltage.
                     The product you have chosen is designed for commercial and industrial use only.
                     In order to be used for particular “critical applications” such as life support systems, medical applications, commercial
                     transportation, nuclear facilities or any other application or systems where product failure is likely to cause substan-
                     tial harms to person or property, the products may have to be adapted.
                     For such uses we would advise you to contact SOCOMEC UPS beforehand to confirm the ability of these products
                     to meet the requested level of safety, performance, reliability and compliance with applicable laws, regulations and
                                                                                                                                                      ENGLISH
                     specifications.
                                WARNING!
                                This is a product for commercial and industrial application in the second environment –
                                installation restrictions or additional measures may be needed to prevent disturbances..
                     2.2 DESCRIPTION OF THE SYMBOLS USED ON THE LABELS APPLIED TO THE UNIT.
                     All the precautions and the warnings on the labels and plates on the inside and outside of the equipment should
                     be respected.
GROUND TERMINAL
                                                                                                                             IOMMASIPXX07-GB 02   7
Downloaded from www.Manualslib.com manuals search engine
                       3         UNPACKING AND INSTALLATION
                                 OF THE UNIT
                                                                                                MASTERYS IP+
                                                                                                                         40-60 kVA 3/1
                     The packaging guarantees the stability of the UPS during shipping and physical transfer. Carry the packaged unit as
                     close as possible to the installation site.
                                  When moving the unit on even slightly sloping surfaces, use the blocking equipment and break-
                                  ing devices to ensure that the unit does not fall over.
• Ensure that the floor is strong enough to support the weight of the UPS and of the battery cabinet, if used.
The UPS MUST only be moved by two people at least bt the mean of a forklift.
                                  All packaging material must be recycled in compliance with the laws in force in the country where
                                  the system is installed.
8 IOMMASIPXX07-GB 02
3.2-1 3.2-2
                                                                                                                  ENGLISH
                     Secure the UPS to the floor by using the suitable holes C
                     provided (see picture 3.2-5).
859
                                                                         ø13
                                                                   700
                                                                                         IOMMASIPXX07-GB 02   9
Downloaded from www.Manualslib.com manuals search engine
                       3       UNPACKING AND INSTALLATION
                               OF THE UNIT
                                                                                                 MASTERYS IP+
                                                                                                                          40-60 kVA 3/1
                       the UPS for maintenance purposes. It is also recommended to ensure that the cable connections are sufficiently
                       long and flexible to allow easy maintenance operations (see figure 3.3-1).
                     • If it is not possible to leave sufficient space at the front, adequate access must be ensured from both sides.
                      3.3-1
                                                40 cm
20 cm 20 cm
                                               MASTERYS
                                                 UPS
                                                          1,5 m
free area
                                 WARNING!
                                 This is a product for commercial and industrial application in the second environment – installation
                                 restrictions or additional measures may be needed to prevent disturbances.
10 IOMMASIPXX07-GB 02
                                                                                                                                                                                  ENGLISH
                                                                                                                           (mm2)               (mm2)                 (A)
                     40 kVA              80 A                250 A       0.5 A selective type (3)    25÷35 mm2          95÷120 mm2           25÷95 mm2             100 gR
                     60 kVA             125 A                400 A       0.5 A selective type (3)    35÷50 mm2          120÷185 mm2          50÷95 mm2             200 aR
                     1
                         D curve magneto-thermal switch recommended.
                     2
                         Protection on the external battery cabinet (preferably 2 bipolar protection devices or one quadripolar).
                     3
                         Caution! Use type B selective circuit breakers. Load leakage currents are added to those generated by the UPS and during transitory phases
                         (power failure and power return) short current peaks may occur. If loads with high leakage current are present, adjust the differential protection.
                         It is advisable in all cases to carry out a preliminary check on the earth current leakage with the UPS installed and operational with the definitive
                         load, so as to prevent the sudden activation of the above switches.
                                    This unit has been designed for connection to an ordinary AC power supply, i.e. with transient voltage
                                    in overvoltage II category. Should it be necessary to connect the UPS to a higher overvoltage category
                                    (e.g. at the beginning of the installation, or to primary distribution circuits), or should the UPS risk
                                    being exposed to higher transient overvoltages, adequate external protections must be installed.
                                                                                                                                                        IOMMASIPXX07-GB 02   11
Downloaded from www.Manualslib.com manuals search engine
                       3       UNPACKING AND INSTALLATION
                               OF THE UNIT
                                                                                                 MASTERYS IP+
                                                                                                                         40-60 kVA 3/1
                     The back-feed protection device may be built into the system (only on specific request), or an electromechanical
                     switch may be installed externally in the input of the UPS.
                     To install the external back-feed protection an external electromechanical switch should be installed as close as
                     possible to the UPS. For further information on the connection and the type of remote switch, please refer to
                     paragraph 11.7 of this manual.
                                 ATTENTION.
                                 The neutral is not disconnected as, even in the event of a single fault on the UPS, it never has high po-
                                 tential when the mains and/or auxiliary power supplies are disconnected upstream. This is to prevent
                                 transformation of the power source to the UPS every time there is a power failure.
                                 Should the neutral potential be very high due to certain error conditions or due to installations
                                 downstream (e.g. ground fault not detected and protected, high dispersion of a phase, or the IT
                                 system), it will be necessary to install either devices that disconnect the Neutral or alternatively a
                                 system that detects, signals and protects against high neutral/ground potential that could lead to
                                 UPS failure.
                                 NOTE.
                                 The neutral of the AUX Mains line must be electrically common with the neutral of the main input feed
                                 line.
12 IOMMASIPXX07-GB 02
                                                                                                                                                            ENGLISH
                                                                                 Q3                  Q2
Q5
Q4
                                                                                           C
                                                                                                                              H   E
                                                                                                                          F
                                                                                       B
                                                                                                                          G       E
                     Legend.
                     A Mimic panel.                                  Q2   Input switch (MAINS).
                     B Fans.                                         Q3   Output switch.
                     C Fan fuses.                                    Q4   Auxiliary mains Input switch (AUX MAINS).
                     D Power connections.                            Q5   Output maintenance bypass switch.
                     E Slot for optional communication cards.
                     F Serial RS232/485 connector (JBUS protocol).
                     G Serial RS232 connector for Modem.
                     H LAN RJ45 connector for Ethernet.
                                                                                                                                  IOMMASIPXX07-GB 02   13
Downloaded from www.Manualslib.com manuals search engine
                       3       UNPACKING AND INSTALLATION
                               OF THE UNIT
                                                                                                          MASTERYS IP+
                                                                                                                                                   40-60 kVA 3/1
                                 For the power connections to the connecting bars use cables with tinned eyelets only.
          ITALIANO
           ENGLISH
                                                                                                                                                           20 cm
                                                                                                                   B
B 90°
A A
                                                                                                               A. power cables
                           OPEN                                                                                B. control cables
14 IOMMASIPXX07-GB 02
                                                                                                                                                                 ENGLISH
                                                SUPPLY
                                                                TO
                                                               LOAD
                                             L11     N11                                      L1 L2 L3 N
                                            ø 95÷120 mm2             ø 95÷120 mm2             ø 25÷35 mm2
3.6.2 MAINS and AUX MAINS network connections on UPS without neutral on the main network
3.6.2-1
                                                                TO
                                                               LOAD
                                              L11     N11                                     L1 L2 L3
                                             ø 95÷120 mm2            ø 95÷120 mm2            ø 25÷35 mm2
                                                                                                                                       IOMMASIPXX07-GB 02   15
Downloaded from www.Manualslib.com manuals search engine
                       3       UNPACKING AND INSTALLATION
                               OF THE UNIT
                                                                                                MASTERYS IP+
                                                                                                                        40-60 kVA 3/1
16 IOMMASIPXX07-GB 02
                                                                                                                   2
                                                                                                       OUT
                                                                                                       1
OUT1 OUT2
                                                                                                                                                                                                                                                           ENGLISH
                                     IN1
                                                    IN1
                                                                                                                                                                                                                          DIP1    DIP2
                                                    IN2                                                                                                            IN3
                                                                                                                                                                                                                            0 1 2 P3
                                                                                                                                                                                                                           A
                                                   OUT4                                                                                                            OUT3
                                     IN2
                                                                                                             OUT
                                                                                                                   3
                                                                                                       4
                     Up to four operating modes can be selected using the two DIP switches 1 or 2.
                     • The filter level indicates:
                       1 immediate activation (1 seconds minimum communication time) - 2 10 s delay - 3 30 s delay.
                         Mode 1 - STANDARD configuration                                                                                                                                   Mode 2 - POWER SAFE configuration
                      Position              IN/OUT                                          Description                                                                     Filter          Position   IN/OUT      Description                 Filter
                     dip1 dip2                                                                                                                                              level          dip1 dip2                                           level
                     OFF OFF                 Out 1                                          General Alarm                                                                     2            ON OFF      Out 1       General Alarm                 2
                     OFF OFF                 Out 2                                          Battery discharging                                                               3            ON OFF      Out 2       Power safe plug 1             2
                     OFF OFF                 Out 3                                          Battery low or                                                                    2            ON OFF      Out 3       Power safe plug 2             2
                                                                                            imminent stop                                                                                  ON OFF      Out 4       Power safe plug 3             2
                     OFF         OFF         Out 4                                          UPS on by-pass                                                                    2            ON OFF      In 1*       E.S.D.                        1
                     OFF         OFF         In 1*                                          E.S.D.                                                                            1            ON OFF       In 2       Supply from GenSet            1
                     OFF         OFF          In 2                                          Supply from GenSet                                                                1            ON OFF       In 3       Management of                 1
                     OFF         OFF          In 3                                          Isolation controller                                                              2                                    energy consuption
                                                                                                                                                                                                                                 IOMMASIPXX07-GB 02   17
Downloaded from www.Manualslib.com manuals search engine
                       3       UNPACKING AND INSTALLATION
                               OF THE UNIT
                                                                                                 MASTERYS IP+
                                                                                                                           40-60 kVA 3/1
                     Description of signals
                     Message on the mimic panel         Description
                     General Alarm                      “General Alarm” contact output.
                                                        No alarm.
                                                                       NO1
                                                        C1
                                                                       NC1
          ITALIANO
                     Battery Low or Imminent stop       Battery low voltage and imminent shutdown contact output.
                     UPS on bypass                      Contact input for emergency shutdown device.
                     E.S.D.                             UPS on bypass contact output
                     Supply from GenSet                 Generator ready signal input.
                     Isolation controller               Isolation leakage controller signal input
                     Power safe plug 1                  Non privileged load 1 command output activated by overload or loss of redundancy.
                     Power safe plug 2                  Non privileged load 1 command output activated by battery discharging.
                     Power safe plug 3                  Non privileged load 1 command output activated by battery low.
                     Management of energy consumption   Input for the battery to help providing energy in the event of peak consumption.
                     E.S.D. activation                  Shutdown for E.S.D. contact output.
                     Over-heating                       Internal over-heating contact output.
                     Overload/Loss of redundancy        Overload / loss of redundancy contact output
18 IOMMASIPXX07-GB 02
                                                                                                                                                                                  ENGLISH
                     • Connect the ground cable.
                     • Connect the cables between the UPS terminals and the battery cabinet terminals, strictly observing the polarity of
                       each individual string and the cross-sections indicated in table 3.4.
                                 Use double insulated cables or the cables supplied with the unit to connect the UPS to the Bat-
                                 tery cabinet. The lenght L of battery cable must not be more than 8 metres long (if L > 8 m, please
                                 contact the support service).
                                 Cabling errors with inversion of the battery polarity may cause permanent damage to the equip-
                                 ment.
                                 If using cabinets not supplied by the manufacturers of the UPS, it is the installer’s responsibility
                                 to check the electrical compatibility and the presence of appropriate protection devices between
                                 the UPS and the battery cabinet (fuses and switches of sufficient capacity to protect the cables
                                 from the UPS to the battery cabinet). As soon as the UPS is switched on (before closing the bat-
                                 tery switches) the battery parameters must be verified accordingly (voltage, capacity, number of
                                 elements, etc.) on the mimic panel menu. If the values indicated on the battery cabinet data plate
                                 are different from those shown on the mimic panel, use the SERVICE > CONFIGURATIONS menu
                                 to correct the settings.
                      3.11-1
                                                                                                                                            Battery cabinet
                                                                                          L1   L2   L3   N   +B2     -B2   -B1    +B1
                                                                                          MAINS SUPPLY             EXT. BATTERY
                                            L11     N1     L14     N4      L12     N2
                                             AUX MAINS   OUT TRANSFORMER IN TRANSFORMER
                                              SUPPLY
                                                                                                                                                +B2
                                                                                                                                                +B1
                                                                                                                                                –B2
                                                                                                                                                –B1
EXTERNAL BATTERY
MASTERYS IP
                                                                                                                                                        IOMMASIPXX07-GB 02   19
Downloaded from www.Manualslib.com manuals search engine
                       4       MODES OF OPERATION                                                  MASTERYS IP+
                                                                                                                            40-60 kVA 3/1
                     ON LINE operation provides three operating modes according to mains and load conditions:
                     • “Normale” mode.
                       This is the most frequent operating condition: the energy is drawn from the primary mains power supply and is
          ITALIANO
           ENGLISH
                       converted and used by the inverter to generate the output voltage to power the loads connected.
                       The inverter is constantly synchronised in frequency with the auxiliary mains to enable load transfer (due to an
                       overload or inverter shutdown) without any break in the power supply to the load.
                       The battery charger supplies the energy required to maintain or recharge the battery.
                     • “Bypass” mode.
                       In case of inverter failure, the load is automatically transferred onto the auxiliary mains without any interruption in
                       the power supply. This procedure may occur in the following situations:
                       - in the event of a temporary overload, the inverter continues to power the load. If the condition persists, the UPS
                         output is switched onto the auxiliary mains via the automatic bypass. Normal operation, which is from inverter,
                         returns automatically a few seconds after the overload disappears.
                       - when the voltage generated by the inverter goes is out of tolerances due to a major overload or a fault on the
                         inverter.
                       - wWhen the internal temperature exceeds the maximum value allowed.
                     • “Battery” mode.
                       In the event of a mains failure (micro interruptions or extended black-outs), the UPS continues to power the load
                       using the energy stored in the battery. The Expert Battery System keeps the user constantly informed on the
                       battery status and on the back-up time available. The disconnection of non mission critical applications during
                       battery discharge can be programmed (after a certain laps of time) by using the Power Share option, so that the
                       battery resources can be reserved for the most critical applications.
20 IOMMASIPXX07-GB 02
                                                                                                                                                 ENGLISH
                       directly from the auxiliary mains via the automatic bypass in normal operating conditions.
                     • Always On operating mode: the innovative Always On mode combines very high efficiency and the active filte-
                       ring of the harmonics re-injected onto the upstream mains by the distorting load. In normal conditions the load is
                       powered directly from the auxiliary mains via the automatic bypass, while the inverter contributes to compensate
                       the re-injected harmonics..
                                                                                                                       IOMMASIPXX07-GB 02   21
Downloaded from www.Manualslib.com manuals search engine
                       5       ACCESS TO CONTROLS
                               AND COMMUNICATION INTERFACES
                                                                                                  MASTERYS IP+
                                                                                                                         40-60 kVA 3/1
                     This chapter identifies the electromechanical switches, described below, and used for start-up, shutdown and main-
                     tenance bypass procedures. Access to the control area is from the front by opening the front door. The control area
                     also contains the communication interface connectors and the slots for the optional signalling cards. Please refer to
                     the relevant chapter for more details on the connection and use of the related communication interfaces/cards.
                          AUX MAINS
          ITALIANO
           ENGLISH
                                               Q4
                                                                                                                      INPUT
                                                                                                                      TRANSFORMER
                                                                                                                      OUTPUT
                               MAINS                                                                                  TRANSFORMER
                                               Q2                                        Q3
                       Legend.
                       B1 Battery cabinet
                       Q2 Input switch                                 B1
                       Q3 Output disconnecting switch
                       Q4 Auxiliary Mains switch
                       Q5 Manual bypass switch
22 IOMMASIPXX07-GB 02
                                                                                                                                           ENGLISH
                     B. multicoloured luminous bar that identifies the
                        condition of the power supply to the load;
                                                                                                                D
                     C. alphanumeric information that uses a menu lay-                  B
                        out to provide details on any alarms that may
                        occur and on the measurements, controls and
                        parameters.
                                                                                                                 IOMMASIPXX07-GB 02   23
Downloaded from www.Manualslib.com manuals search engine
                      6           MIMIC PANEL                                                                    MASTERYS IP+
                                                                                                                                            40-60 kVA 3/1
                     6.2-1
                                                                                   M1
                           M2                                        M8
                                                                                        M9
                                                                                                                           M30
                                 M10                          M11
                                                                                                                           M31
          ITALIANO
           ENGLISH
                                                                                                                                M19
                                                  M3                                                                                  M18
                                                                                                         M24
                                                                                                                                            M20
                                        M4                                                     M28
                                                                                                                                              M21
                                                                                             M27
                                       M5                                                                                                         M22
                                                                                             M26
                                                                                                                                             M23
                                        M6                                 M7                      M25
                     Meaning of ideograms
                     Code                   Description                                                        Condition
                     M1                     Load on bypass, in Eco-mode or Maintenance bypass closed           Steady
                                            Automatic bypass alarm                                             Flashing
                     M2                     Input rectifier active.                                            Steady
                                            Input rectifier general alarm.                                     Flashing
                     M3                     Battery OK.                                                        Steady
                                            Battery alarm.                                                     Flashing
                     M4-M7                  Remaining battery capacity.                                        Steps of 25%
                                            Battery recharging.                                                Sequence M7 M4
                     M8                     Inverter on                                                        Steady
                                            Inverter general alarm.                                            Flashing
                     M9                     Switch Q3 closed and output voltage present.                       Steady
                     M10                    Input mains OK.                                                    Steady
                                            Input mains alarm.                                                 Flashing
                     M11                    Inverter on.                                                       Steady
                     M12                    Module 1 present.                                                  Steady
                                            Module 1 general alarm.                                            Flashing
                     M13                    Module 2 present.                                                  Steady
                                            Module 2 general alarm.                                            Flashing
                     M18                    Load present.                                                      Steady
                                            Overload.                                                          Flashing
                     M19-M28                Output load indicator.                                             Steps of 10%
                     M29                    Periodic maintenance alarm/warning.                                Flashing
                     M30                    Activation code alarm.                                             Steady
                                            General alarm.                                                     Flashing
                     M31                    LAN connection ready (Cable Connected).                            Steady
24 IOMMASIPXX07-GB 02
                                                                                                                                                            ENGLISH
                      RED flashing                Imminent shutdown alarm (the load will be disconnected in a few minutes)
                      RED                         Load not powered or battery circuit open
                      YELLOW flashing             UPS in stand-by or Ups on manual bypass
                                                  Alarm indicating request for ordinary maintenance according to conditions of use (type of load,
                                                  temperature), after over 25.000 – 30.000 hours of operation (M29 flashing and alarm A44)
                      YELLOW                      Warning for preventive maintenance according to conditions of use (type of load, temperature),
                                                  after over 10.000 - 12.000 hours of operation (M29 flashing)
                      YELLOW                      Load on battery or battery discharging if M11 is on steady and M10 is off
                      YELLOW                      On automatic bypass if M1 is on steady
                      YELLOW                      First maintenance period expired (10,000 hours of operation) UPS in maintenance mode
                      GREEN flashing              Battery test in progress
                      GREEN                       Load powered from inverter or in high efficiency mod
                       6.4-1
                                                                                                                  Legend.
                                                                                                                  A Current menu.
                                                                                                                  B Active sub menu.
                                                                                                                  C Additional values or information.
                                                       A                                                          D Scrolling contextual help line.
                               B                                                                                  E Scroll bar.
                                                                                                         F        F Statistical graphics display.
                           C                                  E
                                   D                                          D
                                                                                                                                  IOMMASIPXX07-GB 02   25
Downloaded from www.Manualslib.com manuals search engine
                     6         MIMIC PANEL                                     MASTERYS IP+
                                                                                                 40-60 kVA 3/1
                      Parallel UPS
                                                   Single UPS
2.2 STATISTICS
5.2 SETTING
26 IOMMASIPXX07-GB 02
                     The operating modes to activate and manage the UPS are defined            7-1
                     in this chapter; please also refer to chapters 6 “Mimic panel” and 8
                     “Menus”.
                                                                                                      Q3     Q2
                                For UPSs in parallel 1+1 redundant configuration:
                                • Carry out the procedures on all the UPSs before going               Q5
                                  on to the next operation.
                                • All procedures should be carried out on all the UPSs                Q4
                                  within 30 seconds.
                                • The mimic panel operations are carried out on the “LEFT”
                                                                                                                                            ENGLISH
                                  UPS with transformer configured as concentrator. Be
                                  sure to operate on the SYSTEM menu.
                     7.2 SHUTDOWN.
                     Shutdown interrupts the power supply to the load and causes the UPS and the battery charger to stop.
                     • Activate the procedure COMMANDS > IMMEDIATE COMMANDS > STOP PROCEDURE;
                     • Wait approx. 2 minutes for the UPS to shut down (the controlled shutdown of any servers is managed with
                       shutdown software);
                     • Carry out the operations indicated on the mimic panel.
                                                                                                                  IOMMASIPXX07-GB 02   27
Downloaded from www.Manualslib.com manuals search engine
                       7       OPERATING PROCEDURES                                        MASTERYS IP+
                                                                                                                  40-60 kVA 3/1
28 IOMMASIPXX07-GB 02
                                                                                                                                                 ENGLISH
                                                                      exceeded.
                      A07      OVER TEMPERATURE                       Temperature excessive or ventilation problems.
                      A08      MAINTENANCE BYPASS ACTIVE              Q5 in position 1.
                      A17      IMPROPER CONDITION OF USE              Improper conditions of use verified (load, mains, and temperature).
                      A18      BLOCKING INVERTER FOR OVERLOAD         Inverter shutdown due to overload.
                      A20      WRONG CONFIGURATION                    Error in the configuration parameters (e.g. different parameters
                                                                      between several UPSs in parallel).
                      A22      INPUT MAINS OUT OF TOLERANCE           The voltage or frequency limits accepted by the rectifier have been
                                                                      exceeded.
                      A23      RECTIFIER GENERAL ALARM                Rectifier fault.
                      A25      INVERTER GENERAL ALARM                 Inverter fault.
                      A26      BATTERY CHARGER GENERAL ALARM          Battery charger fault.
                      A29      BYPASS GENERAL ALARM                   Bypass fault.
                      A30      STOP FOR OVERLOAD                      The duration of the overload has inhibited the bypass.
                      A32      MODULE 1 GENERAL ALARM                 Module 1 failure.
                      A33      MODULE 2 GENERAL ALARM                 Module 2 failure.
                      A38      EXTERNAL ALARM 1                       Signalling from ADC input.
                      A39      EXTERNAL ALARM 2                       Signalling from ADC input.
                      A40      EXTERNAL ALARM 3                       Signalling from ADC input.
                      A41      EXTERNAL ALARM 4                       Signalling from ADC input.
                      A42      E-SERVICE GENERAL ALARM                Alarm that generates automatic sending of a signal to the support
                                                                      centre (if the service has been activated).
                      A43      REDUNDANCY LOST                        The power required by the load no longer allows the preset
                                                                      redundancy N+x to be maintained (for UPSs in parallel only).
                      A44      PERIODIC SERVICE CHECK-UP              Warning for periodic check by support service.
                      A47      MAX BATTERY TEMPERATURE                Control of the temperature of battery cabinet.
                      A49      BATTERY DISCHARGED                     The energy available in the battery has been used up.
                      A51      OPTION BOARD GENERAL ALARM             Fault related to the optional PCBs in the slots.
                      A56      GENERATOR SET GENERAL ALARM            Minor alarm on generator set.
                      A57      GENERATOR SET FAULT                    Major alarm on generator set.
                      A58      E.S.D. ACTIVATED                       The remote emergency shutdown command has been activated.
                      A59      BATTERY CIRCUIT OPEN                   The battery switch is open.
                      A60      FAN FAILURE                            Fans faulty or blocked.
                      A61      PHASE ROTATION FAULT                   Wrong phase cycle direction.
                                                                                                                       IOMMASIPXX07-GB 02   29
Downloaded from www.Manualslib.com manuals search engine
                       8       MENU                                                         MASTERYS IP+
                                                                                                                     40-60 kVA 3/1
30 IOMMASIPXX07-GB 02
                                                                                                                                                      ENGLISH
                      MAINTENANCE BY-PASS                  Control to activate the manual bypass and shutdown of the UPS.
                      PROCEDURE
                      HIGH EFFICIENCY MODE                 Activates Eco mode / always on mode.
                      NORMAL MODE                          Activates normal double conversion operation.
                      ALARM RESET                          Resets all the alarms.
                      LEDS TEST                            Performs the test on the mimic panel LEDs.
                                                                                                                            IOMMASIPXX07-GB 02   31
Downloaded from www.Manualslib.com manuals search engine
                       8       MENU                                                                MASTERYS IP+
                                                                                                                             40-60 kVA 3/1
                     LAN SINOTTICO MAC ADDRESS             Identifie the mac addres of LAN PCB.
                     XX . XX . XX . XX . XX . XX
                     FW X.XX
                     SCHEDA DIGITALE                       Identifie the micro prosessor software version.
                     UP RV 000 CKS: 0000                   Identifie the mac addres of LAN PCB.
                     DSP RV 000 CKS: 0000
                     The activation code is provided directly by the reference Support Centre upon communication of the serial
                     number of the equipment which is displayed in the next message by pressing ENTER.
                                                             SEE INSTALLATION MANUAL
                                                             FOR PROCEDURE
                                                             SN: 0000000000
                     When contact is made with the Support Centre for the activation code, detailed information can be obtained
                     on the UPS functions available and on the periodic preventive maintenance programmes.
32 IOMMASIPXX07-GB 02
                     Once the code is obtained, enter it by pressing ENTER to activate the entry (two asterisks will appear). Select
                     the first character with the UP   and DOWN keys and confirm with ENTER to accept the character. Then
                     move on to the next character. Pressing the ENTER key after selecting the fourth character activates code.
                                                                                                                                                         ENGLISH
                     dure.
                                                                                                                               IOMMASIPXX07-GB 02   33
Downloaded from www.Manualslib.com manuals search engine
                      8        MENU                                                                MASTERYS IP+
                                                                                                                              40-60 kVA 3/1
34 IOMMASIPXX07-GB 02
                                                                                                                                                    ENGLISH
                     8.6 “EVENT LOG” MENU.
                     Shows a list of UPS events in chronological order.
                     It allows the user to analyse UPS operation with regard to variations in the power supply, load or the environ-
                     ment.
                        8.6-1
                                                                                                    Legend.
                            A                                                     B                 A Shows date and time of event.
                                                                                                    B Shows the event code.
                                                                                                    C Describes the event.
                                                                                                    D ON/OFF status of event.
                                                                                                    E Progressive number of event.
                            C                                                     E
                                                                                                                      IOMMASIPXX07-GB 02   35
Downloaded from www.Manualslib.com manuals search engine
                          9        COMMUNICATION                                                     MASTERYS IP+
                                                                                                                                             40-60 kVA 3/1
                                                                                                         5       4       3       2       1
                                       Slot 1      Slot 2 RS 232/485 RS 232 RJ45 10BT
                     ADC card            •          •
                     GSS card            •          •                                                        9       8       7       6
                     NetVision card      •   2
                                                    •2
                     UniVision pro                           •                  •4
                                                                                        Legend pin RS232/485 C1                      Legend pin Modem C2
                     Remote Panel                            •                          1 Not connected                              1 Reserved
                     BMS                                     •1
                                                                      •   1
                                                                                •4      2 RX for RS232                               2 RX for RS232
                     Modem                                            •   3             3 TX for RS232                               3 TX for RS232
                     LAN (ethernet)                                             •       4 Data +
                                                                                        5 GND for RS232
                                                                                                                                     4 Reserved
                                                                                                                                     5 GND for RS232
                     1
                         Building Management System.                                    6 Data −                                     6 Not connected
                     2
                         Ethernet adapter with Web/SNMP 10/100Mb functions              7 Reserved                                   7 RTS
                         (E-service via Web required).                                  8 Not connected                              8 CTS
                     3
                         For T-service via telephone network.                           9 +12 V                                      9 +12 V
                     4
                         By jbus tunnelling on TCP/IP.
                     As each channel is independent, simultaneous connections can be made to satisfy the different levels of signalling
                     and remote monitoring.
                     See the options paragraph to access the detailed functions of the PCBs installed in the slots.
                                     Please note that two Net Vision cards or two GSS cards cannot be connected simultaneously.
                                     Only one card of a kind can be used.
36 IOMMASIPXX07-GB 02
                     9.2.1 Activation.
                     Comply with the following operations to activate            9.2.1-1
                     the monitoring system:
                     • Connect the UPS to the LAN network (connector
                       D in Fig. 9.2.1-1).
                                                                                                               D
                                                                                                                                                  ENGLISH
                     A. If the DHCP protocol (Dynamic Host Configura-
                        tion Protocol) is enabled in the local network,
                        check the UPS mimic panel for the IP address in
                        the menu PARAMETERS > PRESENT CONFIG >
                        LOCAL AREA NETWORK IP (go on to point C).
                     B. If the BOOT DHCP protocol is not enabled in the
                        local network:
                        Foreword: the following is applicable only if the user is in possession of the administrator rights, otherwise the
                        procedure indicated below is only valid if using a stand-alone PC (i.e. not in a network of computers with admin-
                        istrator privileges) and a network twisted cable.
                         Deactivate DHCP mode in the COMMAND> EXT.COMMAND> DHCP DISABLE menu on the UPS mimic
                         panel.
                         Read the IP address given in the PARAMETERS > PRESENT CONFIG > LOCAL AREA NETWORK IP menu
                         on the UPS mimic panel (by default 192.168.7.19).
                         From a PC connected to the network add the address read by means of the following command: Route add
                         192.168.7.19 210.67.192.147 (assuming 210.67.192.147 to be the IP address of the PC being used).
                     C. Open an internet browser and key in the address http://XXX.XXX.XXX.XXX and press send (where xxx.xxx.
                        xxx.xxxx is the IP address read on the mimic panel). 9.2.1-2
                     D. A login and a password will be requested
                        (fig. 9.2.1-2), the default parameters are:
                         • login: admin
                         • password: public
                                                                                                                        IOMMASIPXX07-GB 02   37
Downloaded from www.Manualslib.com manuals search engine
                       9        COMMUNICATION                                               MASTERYS IP+
                                                                                                                   40-60 kVA 3/1
                     9.2.2-1
                                                A
          ITALIANO
           ENGLISH
B C
                        Legend.
                        A Navigation bar.
                        B Menu bar.
                        C system information area.
38 IOMMASIPXX07-GB 02
                                                                                                                                             ENGLISH
                                Alarm present: shows the alarms table (this icon appears when the UPS detects an anomaly).
Generator operating mode (this icon appears when the UPS is powered by the generator).
                                Technical support department e-mail address. This connection opens the e-mail program and auto-
                                matically fills in the addressee and subject lines.
                     9.2.2.4 Statistics.
                     The counter folder shows the
                     number of events that have oc-
                     curred over a given period of time
                                                                                                                   IOMMASIPXX07-GB 02   39
Downloaded from www.Manualslib.com manuals search engine
                       9       COMMUNICATION                                                   MASTERYS IP+
                                                                                                                        40-60 kVA 3/1
40 IOMMASIPXX07-GB 02
                                                                                                                                                 ENGLISH
                     • Client JBUS IP address to be au-
                       thorised: if a specific IP address is
                       inserted in this box, then only that
                       address/user will be able to ac-
                       cess the html pages. If the address
                       0.0.0.0 is used, all the PCs on the
                       network will be able to access the
                       supervisor (one client at a time). If the address 255.255.255.255 is inserted, access will be denied to all users.
                     • Software updating: if on, allows the supervisor to be updated.
                     • Page refresh (sec): the page refresh rate can be set.
                     • Installation: text string used to describe the UPS installation site, which is useful if there are more than one
                       unit connected (this value is inserted in SMS messages or e-mails).
                     • NTP Server: indicates the IP address of the time server to automatically update the date and time on the system.
                     • GMT Correction (minutes): indicates local time and the offset in minutes with respect to the zero meridian of
                       Greenwich
                     • Apply the parameter settings: restarts the monitoring system with the new settings.
                                                                                                                       IOMMASIPXX07-GB 02   41
Downloaded from www.Manualslib.com manuals search engine
                        9         COMMUNICATION                                                                                  MASTERYS IP+
                                                                                                                                                                     40-60 kVA 3/1
42 IOMMASIPXX07-GB 02
                                                                                                                                             ENGLISH
                     9.2.2.11 System Information Area.
                     This area of the screen page shows
                     the measurements and the UPS op-
                     erating mode.
                     • Click on icon A to display the in-
                       put measurements.                                                                                D
                     • Click on icon B to display the bat-
                                                                     A              B              C
                       tery measurements.
                     • Click on icon C or D to display the
                       output measurements.
                                                                                                                   IOMMASIPXX07-GB 02   43
Downloaded from www.Manualslib.com manuals search engine
                      8
                      9        COMMUNICATION                                                 MASTERYS IP+
                                                                                                                     40-60 kVA 3/1
                                                     UNI VISION PRO is the solution for the management of a UPS connected to
                                                     the local server via RS232 or via LAN. It is normally used at departmental level
                                                     to automatically shutdown the systems and ensure secure control of the UPS
                                                     that in turn protect servers and workstations.
                                                     The main functions are:
                                                     • Graphic monitoring of the UPS via web browser
          ITALIANO
                                                     • Remote shutdown via proxy agent and optional Java shutdown clients
                                                     • Notification of anomalies via e-mail to a maximum of 8 addresse.
                                                     NET VISION is a solution for managing UPS units connected directly to the
                                                     local network. It is normally used on medium/large, complex networks and
                                                     in multi-server environments where the IT manager centrally controls all the
                                                     network resources.
                                                     The physical position of the UPS is not significant.
                                                     The main functions are:
                                                     • 10/100Mb Ethernet connection (RJ45)
                                                     • Graphic monitoring of the UPS via web browser
                                                     • Remote shutdown of up to 40 computers (expandable with options)
                                                     • Notification of anomalies via e-mail to a maximum of 8 addresses
                                                     • UPS management using SNMP protocol
                                                     • Diagnostics via Internet offered by e-Service.
                                                     Java & .NET shutdown Client (JNC) is an optional Java application to be in-
                                                     stalled on a server for the automatic shutdown of the computers on the network
                                                     before the UPS stops due critical operating conditions (imminent battery failure,
                                                     overload, etc.). It is supplied as an option and can be associated to the UNI VI-
                                                     SION PRO or NET VISION communication solutions.
                                                     The main features/functions are:
                                                     • Use of the suite of standard TCP/IP network protocols;
                                                     Graphic interface to improve the simplicity of the configuration;
                                                     • Minimum use of CPU resources
                                                     • Personalisation of shutdown parameters and script
                                                     • Continuous monitoring of the efficiency of the connection to the UPS.
44 IOMMASIPXX07-GB 02
                                                                                                                                                  ENGLISH
                                                           motely by the Service Centre, with immediate intervention on site if needed.
                                                                                                                        IOMMASIPXX07-GB 02   45
Downloaded from www.Manualslib.com manuals search engine
                     10        PROBLEM SOLVING                                                 MASTERYS IP+
                                                                                                                        40-60 kVA 3/1
                       Check that the load is well balanced on the three phases by checking the measurements on the display. If
                       needed, disconnect any loads that do not need uninterruptible power.
                      Important!
                      The accepted overload time limit is defined in the technical specifications. When this time limit is exceeded,
                      the loads will no longer be powered by the inverter.
                     • A06: auxiliary mains out of tolerance.
                       The auxiliary mains exceeds the acceptable tolerance values. Possible causes are:
                       • No voltage or frequency present or voltage and frequency out of acceptable values (see the technical speci-
                         fications).
                       • The frequency is subject to continuous variations (typical with power supplied from an incorrectly sized GE).
                     • A07: temperature over the limits.
                       The technical plant temperature is higher than the maximum value recommended.
                       Check the ventilation or air conditioning system in the UPS room.
                     • A08: maintenance bypass activated.
                       The Q5 maintenance bypass switch Q5 is closed.
                       The load is therefore powered directly by mains power supply. See Chapter 7.4.
                     • A17: improper conditions of use.
                       This alarm does not indicate a malfunction or failure of the UPS, but an incorrect use/sizing of the system. It
                       is activated in the event of:
                       • Operation for long periods at high temperatures (battery deterioration)
                       • High number of overloads (wrong sizing)
                       • Continuous battery discharging (mains not stable)
                       • High number of switches onto the bypass (high impulsive loads)
                     • A22: input mains out of tolerance.
                       The input mains is not present or not sufficient (voltage and/or frequency values incorrect with reference
                       to the technical data); if there is no input mains outage, check if no protections upstream of the UPS have
                       tripped. Check that the voltage applied and frequency values are in compliance with the values set on the
                       mimic panel.
46 IOMMASIPXX07-GB 02
                                                                                                                                               ENGLISH
                     10.2 UPS ALARMS.
                     • A01: battery alarm.
                       Failure or problem on the battery circuit. Check that the battery switch is closed.
                     • A18: inverter blocked due to overload.
                       Reduce the load rate applied to the UPS and reset the alarms.
                     • A20: wrong configuration.
                       Error in the configuration parameters; please contact the support service.
                     • A30: block due to overload.
                       Reduce the load rate applied to the UPS and reset the alarms.
                     • A42: T.Service general alarm.
                       The MASTERYS™ products can be remotely serviced. This alarm indicates that a procedure for analysing the
                       UPS failure has been activated by the support centre (if an e-service contract has been concluded).
                     • A44: programmed control.
                       The equipment has to undergo periodic checks by the support service in order to ensure optimum perform-
                       ance and efficiency. If the “Programmed Control” signal appears on the mimic panel, the equipment should
                       be inspected by an adequately trained technician.
                     • A47: maximum battery temperature.
                       The temperature of the battery cabinet (or of the battery room) is higher than the maximum allowed. Check
                       the ventilation or air conditioning system in the premises.
                     • A59: battery circuit open.
                       Battery switch open.
                     • A60: fan failure.
                       Fault in the ventilation system; check that the air inlet at the front and the air outlet of the UPS are not ob-
                       structed.
                                                                                                                     IOMMASIPXX07-GB 02   47
Downloaded from www.Manualslib.com manuals search engine
                     10        PROBLEM SOLVING                                                MASTERYS IP+
                                                                                                                      40-60 kVA 3/1
                                 All operations on the equipment must be carried out solely by SOCOMEC UPS personnel or by
                                 authorised service personnel.
                     Maintenance requires accurate functionality checks of the various electronic and mechanical parts and, if neces-
                     sary, the replacement of parts subject to wear and tear (batteries, fans and condensers). It is recommended to
                     carry out periodic specialised maintenance (annually), in order to keep the equipment at the maximum level
                     of efficiency and to avoid the installation being out of service with possible damage/risks. Moreover, attention
                     should be paid to any requests for preventive maintenance that the equipment may automatically display with
          ITALIANO
           ENGLISH
                     10.3.2 Fans.
                     The life of the fans used to cool the power parts is dependent on the using and environmental conditions
                     (temperature, dust).
                     Preventive replacement by an authorised technician is recommended within four years (in normal operating
                     conditions).
                     10.3.3 Capacitors.
                     The equipment houses electrolytic capacitors (used in the rectifier and inverter section) and filtering capacitors
                     (used in the output section), whose life is dependent on using and environmental conditions.
                     The average expected life of these components is shown below:
                     • Electrolytic capacitors: 5 years;
                     • Filtering capacitors: 7 years.
                     In any case the effective state of the components is verified during preventive maintenance.
48 IOMMASIPXX07-GB 02
                                                                                                                                                      ENGLISH
                     11.3 REMOTE MIMIC PANEL.
                     This device monitors and interacts with the UPS through a serial link RS 485 (maximum distance of 175 m) 25 m cable
                     supplied standard; 50 m cable available as an option). Refer to the relevant user manual for instructions on how to use
                     the device.
                                                                                                                            IOMMASIPXX07-GB 02   49
Downloaded from www.Manualslib.com manuals search engine
                     11         OPTIONS                                                             MASTERYS IP+
                                                                                                                             40-60 kVA 3/1
50 IOMMASIPXX07-GB 02
                      Models
                      Input/Output phases                                            3/1
                                                                                                                                                        1.400
                      Mains voltage                        3P+N 400 V ±20% (up to -35% @70% of nominal load)
                      Input frequency                                       50-60 Hz ±10%
                      Input power factor                                          0,99
                      THDI                                                      < 10%
                                                                                                                                                                ENGLISH
                                                                                                                                                835
                                                                                                                           1000
                      Electrical specifications - Output
                      Output voltage (P+N)                230 V single phase (selectable: 208*/220/230/240 V) ±1%
                      Frequency                              50-60 Hz ±2% (from 1% to 8% if generator is used)
                                                                                                                                  Weight:
                      Automatic bypass                                  nominal output voltage ±15%
                                                              (from 10% to 20% selectable if generator is used)                   - 40 kVA: 490 kg
                      Nominal power                                             40 kVA: 32 kW                                     - 60 kVA: 540 kg
                                                                                60 kVA: 48 kW
                      Overload on mains power supply                          125% 10 minutes
                                                                               150% 1 minute
                      Crest factor                                                   2.5:1
                      Voltage distortion                                     1% with linear load
                      * @ Pout = 90% Pnom
                      Environment
                      Operating temperature               0÷40 °C (15÷25 °C recommended for longer battery life)
                      Storage temperature                                          -5÷45 °C
                      Relative humidity                                   0÷95% condensation-free
                      Protection level                                               IP31
                      Max. altitude                      1.000 m (3.300 ft) without derating; 3.000 m (10.000 ft) max
                      Acoustic noise (dB)                                            < 62
                      Required cooling capacity (m3/h)                               1810
                      Dissipated power max                                      40 kVA: 3800 W
                                                                                60 kVA: 5500 W
                      Dissipated power                                       40 kVA: 13100 BTU/h
                                                                             60 kVA: 18800 BTU/h
                      Standards
                      Safety                                             EN 62040-1-1, EN 60950-1
                      Type and performance                                EN 62040-3 (VFI-SS-111)
                      EMC                                                      EN 62040-2
                      Product certification
                      Protection level                                              IP31
                                                                                                                                   IOMMASIPXX07-GB 02   51
Downloaded from www.Manualslib.com manuals search engine
Downloaded from www.Manualslib.com manuals search engine
                 PARALLEL 1+1 REDUNDANT CONFIGURATION
                 MASTERYS IP
                                                   40-60 kVA 3/1
                     INSTALLATION.
                     UPS units operating in parallel are interconnected using control cable A and are configured differently depending
          ITALIANO
           ENGLISH
                     on the position they are assigned. For this reason the units have a position label C:
                     The “LEFT” label means that the unit must be positioned to the left (UPS with transformer configured as concentrator);
                     • The “RIGHT” label means that the unit must be positioned to the right (UPS without transformer).
                     The control cables supplied allow a maximum distance of about 3 metres between the UPS units. This gives enough
                     room for an external battery cabinet to be inserted beside each UPS.
                     POWER CONNECTIONS.
                     • The power supply to each unit must be protected as indicated in the table in paragraph 3.4.
                     • The cross section and length of the input and output cables must be identical for all the units.
                     • The phase rotation must be the same for both unit connected in parallel.
                     • Cables of the same length and cross section must be used for the connection between the general power switch 1,
                       the switches 3 and the respective UPS units.
                     • If a differential switch is installed on the mains power switch (optional), it must be inserted upstream from the
                       distribution panel, it must be a selective type and the trigger value must be 0.5 A by the number of UPS con-
                       nected in parallel.
                     CONTROL CONNECTIONS.
                     In order for units connected in a parallel configuration to operate correctly, control cables are required to exchange
                     data between the various UPS units making up the parallel system, for management of correct load sharing and
                     synchronisation logic.
                     The cables in question are supplied with the UPSs.
                     Parallel configuration must only be activated by SOCOMEC UPS qualified personnel; in each case arrange the
                     running of the control cables in the relative cable run as shown in figure 2 leaving the connectors unconnected.
54 IOMMASIPXX07-GB 02
❶ ❶
                                                                                                                                                             ENGLISH
                                     ❸       ❸         ❸       ❸
                         25 m max
                                                   ❷
                                         ❼                 ❽
                                                                                   Legend.
                                                                                   A “Parallel bus” cable; leave approx. a 20 cm cable length
                                                                                     at the exit of the cable run.
                         7.5 m max
                                                                ❾
                                         ❹
                                         ❺
                                                       ❻
                       Legend.
                       1 Main differential             6 Distribution.
                         magneto-thermal switch.       7 UPS with transformer.
                       2 “Parallel bus” cable.         8 UPS without transformer
                       3 Magneto-thermal switch.       9 Power connections
                       4 Output switch.                  (refer to page 54)
                       5 System shutdown switch.
                                                                                                                                   IOMMASIPXX07-GB 02   55
Downloaded from www.Manualslib.com manuals search engine
                     PARALLEL 1+1 REDUNDANT CONFIGURATION                                                                          MASTERYS IP+
                                                                                                                                                                        40-60 kVA 3/1
56 IOMMASIPXX07-GB 02
                                                                                                                  *IOMMASIPXX07-GB 02*
                 SOCOMEC Isola Vicentina
                 Via Sila, 1/3 - I - 36033 Isola Vicentina (VI) - ITALY
                 Tel. +39 0444 598611 - Fax +39 0444 598622
                 hr.ups.it@socomec.com
                                                                                                                                      IOMMASIPXX07-GB             02     12.2012
www.socomec.com