Masterys Ip+: Installation and Operating Manual
Masterys Ip+: Installation and Operating Manual
MASTERYS IP+
                                                           10-40 kVA
IOMMASIPXX09-GB 04
                     2. SAFETY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
                                  2.1 Important. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
                                  2.2 Description of the symbols used on the labels applied to the . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
                                                                                                                                                                                                                                                                                                           ENGLISH
                                  3.4 Identifying switching and connection devices.                                         .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .11
                                  3.5 Electrical requisites . . . . . . . . . . . . . . . . . .                             .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .12
                                         3.5.1 Backfeed protection . . . . . . . . . . . .                                  .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .13
                                  3.6 Installation procedure and instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
                                  3.7 ADC card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
                                  3.8 External battery cabinet connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
                                                                                                                                                                                                                                                                IOMMASIPXX09-GB 04                  3
Downloaded from www.Manualslib.com manuals search engine
                     INDEX
                                                                                                                                                                                                        MASTERYS IP+
                                                                                                                                                                                                                                                                                    10-40 kVA
                     8 MENU . . . . . . . . . . . . . . . . . . .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .33
                              8.1 “Allarms” menu. . . . . .         .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .33
                              8.2 “Measurements” menu.              .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .34
                              8.3 “Commands” menu . . .             .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .35
                                  8.4 “Parameters” menu . . . . .           .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .36
                                  8.5 “Service” menu. . . . . . . .         .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .36
                                  8.6 “Event log” menu . . . . . .          .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .39
                                  8.7 Mimic Panel Concentrator              .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .39
          ITALIANO
                     9. COMMUNICATION. . . . . . . . . . . . . .                    .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .40
           ENGLISH
4 IOMMASIPXX09-GB 04
                     This SOCOMEC UPS continuous power system is guaranteed against any manufacturing and material defects.
                     The period of validity of the warranty is 12 (twelve) months from the date of commissioning, if said activation is
                     carried out by SOCOMEC UPS personnel or personnel from a support centre authorised by SOCOMEC UPS, and not
                     however more than 15 (fifteen) months from the date of shipment by SOCOMEC UPS.
                     The warranty is recognized within national territory. If the UPS is exported out of national territory, the warranty shall
                     be limited to the cover of the parts used to repair the fault.
                     The warranty is valid ex-works and covers labour and parts used to repair the fault.
                                                                                                                                                       ENGLISH
                     The warranty shall not apply in the following cases:
                     • Failures due to fortuitous circumstances or force majeure (lightning, floods, etc.);
                     • Failures due to negligence or improper use (use out of tolerance: temperature, humidity, ventilation, electric pow-
                       er supply, applied load, batteries);
                     • Insufficient or inadequate maintenance;
                     • Attempted maintenance, repairs or modifications not carried out by SOCOMEC UPS personnel or personnel from
                       a support centre authorised by SOCOMEC UPS.
                     • If the battery has not been recharged in accordance with the terms indicated on the packaging and in the manual,
                       in cases of extended storage or UPS inactivity.
                     SOCOMEC UPS may, at its own discretion, opt for the repair of the product or for the replacement of the faulty or
                     defective parts with new parts or with used parts that are equivalent to new parts with regard to functions and
                     performance.
                     Defective or faulty parts replaced free of charge are to be put at the disposal of SOCOMEC UPS who becomes the
                     sole owner.
                     Replacements or repairs of parts and any modifications to the product during the warranty period cannot extend
                     the duration of the warranty.
                     In no case will SOCOMEC UPS be responsible for damages (including, without limitations, damage for loss of earn-
                     ings, interruption of activity, loss of information or other economic losses) deriving from the use of the product.
                     The present conditions are subject to Italian law. Any dispute falls under the province of the Court of Vicenza.
                                                                                                                              IOMMASIPXX09-GB 04   5
Downloaded from www.Manualslib.com manuals search engine
                                                                                                        MASTERYS IP+
                         2           SAFETY                                                                                        10-40 kVA
                     2.1 IMPORTANT.
                     • This document provides important instructions for the safe use, movement and connection of the MASTERYS™ un-
                       interruptible power system (UPS).
                     • SOCOMEC UPS retains the full and exclusive ownership rights over this document. Only a personal right to utilize
                       the document for the application indicated by SOCOMEC UPS is granted to the recipient of such document. All
                       reproduction, modification, dissemination of this document whether in part or whole and by any manner are
                       expressly prohibited except upon Socomec’s express prior written consent.
                     • This document is not a specification. SOCOMEC UPS reserves the right to make any changes to data without prior
                       notice.
          ITALIANO
           ENGLISH
• The unit must be installed and activated only by qualified technical personnel and authorised by SOCOMEC UPS.
The UPS MUST only be moved by two people at least by the means of a forklift.
                     • Before connecting any external battery cabinet, ensure that it is fully compatible with the model of UPS it is to be
                       used with.
6 IOMMASIPXX09-GB 04
                     • The use of external battery cabinets not supplied by the manufacturers is not recommended.
                                FOR TECHNICAL PERSONAL:
                                Switch off and isolate the UPS and then wait for 5 minutes before removing the protection panels
                                in order to carry out work on parts under dangerous voltage.
                     The product you have chosen is designed for commercial and industrial use only.
                     In order to be used for particular “critical applications” such as life support systems, medical applications, commercial
                     transportation, nuclear facilities or any other application or systems where product failure is likely to cause substan-
                     tial harms to person or property, the products may have to be adapted.
                                                                                                                                                      ENGLISH
                     For such uses we would advise you to contact SOCOMEC UPS beforehand to confirm the ability of these products
                     to meet the requested level of safety, performance, reliability and compliance with applicable laws, regulations and
                     specifications.
                                WARNING!
                                This is a category C2 UPS product. In a residential environment, this product may cause radio
                                interference, in which case the user may be required to take additional measures.
                     2.2 DESCRIPTION OF THE SYMBOLS USED ON THE LABELS APPLIED TO THE UNIT.
                     All the precautions and the warnings on the labels and plates on the inside and outside of the equipment should
                     be respected.
GROUND TERMINAL
                                                                                                                             IOMMASIPXX09-GB 04   7
Downloaded from www.Manualslib.com manuals search engine
                                 UNPACKING AND INSTALLATION                                           MASTERYS IP+
                       3         OF THE UNIT                                                                                   10-40 kVA
                     The packaging guarantees the stability of the UPS during shipping and physical transfer. Carry the packaged unit as
                     close as possible to the installation site.
The UPS MUST only be moved by two people at least by the means of a forklift.
                                  CAUTION IF DAMAGED.
                                  BATTERIES, NON SPILLABLE.
                                  Packages, crushed, punctured, or torn such that contents are revealed
                                  must be set aside in an isolated area and inspected by a qualified per-
                                  son. If the package is deemed to be not shippable, the contents must       Battery is NOT connected!
                                  be promptly collected, segregated, and either the consignor or consignee
                                  contacted.
                                  All packaging material must be recycled in compliance with the laws in force in the country where
                                  the system is installed.
8 IOMMASIPXX09-GB 04
3.2-1 3.2-2
                                                                                                     ENGLISH
                       3.2-3
                                                                            IOMMASIPXX09-GB 04   9
Downloaded from www.Manualslib.com manuals search engine
                               UNPACKING AND INSTALLATION                                                  MASTERYS IP+
                       3       OF THE UNIT                                                                                                10-40 kVA
                      3.3-1                                                                             3.3-2
                                           40 cm
                                                                                                                                40 cm
                                 20 cm                                                                          20 cm                   20 cm
                                    door                                                                          door
                                                                                         1,5 m
1,5 m
3.3-3 Place the UPS in the installation area, then secure it to the floor.
40 cm
10 IOMMASIPXX09-GB 04
                     Legend.
                     A LAN RJ45 connector for Ethernet.
                     B Serial RS232 connector for Modem.
                     C Serial RS232/485 connector                                                                                  Q2     Q6
                     D Cable trunking for control cables.
                     E Fans.
                     F DIN rail (behind the panel).
                     G Fuses.                                                                                    L
                     H Power connections (behind the plastic protection).
                                                                                                                                                       ENGLISH
                     I Battery pack.
                                                                                                                 D
                     L Slots for communication cards (ADC card installed as                                                  Q1                   I
                         standard, 1 slot available for an additional card).
                     Q1 Battery switch.                                                                                  E
                     Q2 Input switch (MAINS).
                     Q6 Output switch.
                                                                                                                     F
                                                                                                                                     G
A B C
Q2 Q6
                                                                                                                         E
                                                                                                                 D
                                                                                                                     F
                                                                                                                                     G
                                                                                                                             IOMMASIPXX09-GB 04   11
Downloaded from www.Manualslib.com manuals search engine
                                    UNPACKING AND INSTALLATION                                                                 MASTERYS IP+
                          3         OF THE UNIT                                                                                                                   10-40 kVA
                                     WARNING!
                                     The default transformer is normally connected to the output.
          ITALIANO
           ENGLISH
12 IOMMASIPXX09-GB 04
                                The UPS is designed for transitory overvoltages in category II installations. If the UPS is part of
                                the building’s electric circuit or if it is likely to be subject to transitory overvoltages in category III
                                installations, further external protection must be provided, either on the UPS or in the AC power
                                supply network to the UPS.
                                In the event of three-phase non-linear loads connected in output, the current on the neutral
                                conductor may have a value that is 1.5 - 2 times the phase value (also for the input bypass). In this
                                case, size the neutral cables and the input/output protection properly.
                                                                                                                                                   ENGLISH
                     3.5.1 Back-feed protection.
                     Since the UPS does not have an internal automatic protection device against current back-feed, the operator/install-
                     er must add a warning label to all the mains power disconnecting switches installed at a distance from the UPS area.
                     This is a reminder for the technicians about the circuit is connected to a UPS (see the CAUTION section in paragraph
                     2 of this manual and paragraph 4.5.3. of the EN62040-1-1 standard). The label is supplied with the system.
                     To install the external back-feed protection it is necessary to connect an external electromechanical switch. For
                     further information on the connection and the type of remote switch, please read paragraph 11.6 of this manual.
                                ATTENTION.
                                The neutral is not disconnected as, even in the event of a single fault on the UPS, it never has high poten-
                                tial when the mains and/or auxiliary power supplies are disconnected upstream. This is to avoid modifica-
                                tions of the electrical system in case of a power failure.
                                If, in certain anomaly states, or because of the installation upstream (e.g. undetected and protec-
                                ted earth fault, or high leakage in a phase, or with IT systems) there is a hazardous potential on
                                neutral, a suitable isolating switch must be provided on the neutral as well, or else there must be
                                a detection, signalling and protection system.
                                NOTE.
                                The neutral of the AUX Mains line must be electrically common with the neutral of the main input
                                feed line.
                                                                                                                         IOMMASIPXX09-GB 04   13
Downloaded from www.Manualslib.com manuals search engine
                               UNPACKING AND INSTALLATION                                                                                        MASTERYS IP+
                       3       OF THE UNIT                                                                                                                                                10-40 kVA
                                 WARNING!
          ITALIANO
           ENGLISH
                                 The transformer cannot be connected to the output on UPS units connected in parallel configuration.
                                 WARNING!
                                 Check the presence and the right position of the jumper on terminal socket labelled “TRAFO IN/
                                 OUT SETTING”.
                                                                                                                                                                                              20 cm
                                                                                                                                                       B
B 90°
                                                                                                                                                                                          A
                                                                OPEN
                              COM1     TA1       L1   L2   L3    N   L11    L21   L31   N1   L14   L24   L34   N4   L13   L23   L33   N3   L12   L22   L32   N2   +B2   -B2   -B1   +B1
                                 NC1     TA2          MAINS                AUXILIARY              OUT                     IN
                                 COM2      TA3        SUPPLY                MAINS             TRANSFORMER            TRANSFORMER                 OUTPUT             EXT. BATTERY
                                     NC2
                                                                                                                                                 Cable specifications:
                                                                                                                                                 • stripping length: 18 mm
                                                                                                                                                 • tightening torque: 2,5÷4,5 Nm
14 IOMMASIPXX09-GB 04
                                       L1   L2   L3   N    L11    L21   L31   N1   L14   L24   L34   N4   L13   L23   L33   N3   L12   L22   L32   N2   +B2   -B2   -B1   +B1
                               TA1          MAINS                AUXILIARY              OUT                     IN                     OUTPUT             EXT. BATTERY
                                 TA2        SUPPLY                MAINS             TRANSFORMER            TRANSFORMER
                         Cable                                                                                                               Cables
                      provided                                                                                                               provided
                                                                                                                                                                                         ENGLISH
                                            MAINS           AUXILIARY                     TO
                                        cable section        MAINS                       LOAD
                                         ø 6÷35 mm2         cable section           cable section
                                                             ø 6÷35 mm2              ø 6÷35 mm2
                                       L1   L2   L3   N    L11    L21   L31   N1   L14   L24   L34   N4   L13   L23   L33   N3   L12   L22   L32   N2   +B2   -B2   -B1   +B1
                               TA1                                                      OUT                     IN
                                                                                                                                       OUTPUT             EXT. BATTERY
                                 TA2                                                TRANSFORMER            TRANSFORMER
                         Cable              MAINS
                                            SUPPLY
                                                                 AUXILIARY
                                                                  MAINS
                                                                                                                                             Cables
                      provided                                                                                                               provided
                                            MAINS                                    TO LOAD
                                        cable section                               cable section
                                         ø 6÷35 mm2                                  ø 6÷35 mm2
                                                                                                                                                               IOMMASIPXX09-GB 04   15
Downloaded from www.Manualslib.com manuals search engine
                               UNPACKING AND INSTALLATION                                                                             MASTERYS IP+
                     3         OF THE UNIT                                                                                                                                     10-40 kVA
                                                                                                         WARNING!
                     3/3 MAINS AND AUXILIARY MAINS
                            ARE CONNECTED SEPARATELY.                                                    Remove the connecting cables provided between
                            Transformer on the rectifier                                                 OUTPUT and IN TRANSFORMER and use them to
                            power supply input                                                           connect MAINS SUPPLY and OUT TRANSFORMER.
                                                                                                         Move the bridge cable provided from TA1-TA2 to
                                                                                                         TA2-TA3.
          ITALIANO
                                         L1     L2   L3   N   L11    L21    L31   N1   L14   L24   L34   N4   L13   L23   L33   N3   L12   L22   L32   N2   +B2   -B2   -B1   +B1
           ENGLISH
                        Cable                  MAINS
                                               SUPPLY
                                                                    AUXILIARY
                                                                     MAINS
                                                                                            OUT
                                                                                        TRANSFORMER
                     provided
                                                                                                         WARNING!
                     3/3 MAINS AND AUXILIARY MAINS
                            ARE CONNECTED SEPARATELY.                                                    Remove the connecting cables provided between
                            Transformer on the bypass                                                    OUTPUT and IN TRANSFORMER and use them to con-
                            power supply input                                                           nect AUXILIARY MAINS and OUT TRANSFORMER.
                                                                                                         Move the bridge cable provided from TA1-TA2 to
                                                                                                         TA2-TA3.
                                          L1    L2   L3   N   L11     L21   L31   N1   L14   L24   L34   N4   L13   L23   L33   N3   L12   L22   L32   N2   +B2   -B2   -B1   +B1
                                 TA2           MAINS                                                                IN                     OUTPUT             EXT. BATTERY
                                   TA3         SUPPLY                                                          TRANSFORMER
                        Cable                                       AUXILIARY
                                                                     MAINS
                                                                                            OUT
                                                                                        TRANSFORMER
                     provided
16 IOMMASIPXX09-GB 04
                                        L1   L2   L3       L11    L21   L31   N1   L14    L24   L34    N4   L13   L23   L33   N3   L12   L22   L32   N2   +B2    -B2    -B1    +B1
                                TA1          MAINS               AUXILIARY              OUT                       IN                     OUTPUT             EXT. BATTERY
                                  TA2        SUPPLY               MAINS             TRANSFORMER              TRANSFORMER
                         Cables                                                                                                                Cables
                       provided                                                                                                                provided
                                                                                                                                                                                             ENGLISH
                                             MAINS          AUXILIARY                    TO LOAD
                                         cable section       MAINS                      cable section
                                          ø 6÷35 mm2        cable section                ø 6÷35 mm2
                                                             ø 6÷35 mm2
                                                                        L1    L2   L3      N    L11A L11 N11A N11       L14   N4   L13   N3    L12   N2   +B2     -B2    -B1   +B1
                                                                              MAINS                   AUXILIARY         OUT
                                                                              SUPPLY                                                                            EXT. BATTERY
                                                                                                       MAINS        TRANSFORMER
                                                                                                                                    IN   OUTPUT
                                                                                                                               TRANSFORMER
                                                                                                                                                                   IOMMASIPXX09-GB 04   17
Downloaded from www.Manualslib.com manuals search engine
                               UNPACKING AND INSTALLATION                                                     MASTERYS IP+
                     3         OF THE UNIT                                                                                                            10-40 kVA
                                                           L1   L2   L3   N   L11A L11 N11A N11   L14   N4   L13   N3   L12   N2   +B2   -B2   -B1   +B1
                                                                MAINS                              OUT
                                                                SUPPLY                         TRANSFORMER                           EXT. BATTERY
          ITALIANO
           ENGLISH
                                                                                 AUXILIARY                   IN   OUTPUT
                                                                                  MAINS                 TRANSFORMER
                                                           L1   L2   L3   N   L11A L11 N11A N11   L14   N4   L13   N3   L12   N2   +B2   -B2   -B1   +B1
                                                                MAINS                                        IN   OUTPUT             EXT. BATTERY
                                                                SUPPLY                                  TRANSFORMER
                                                                                 AUXILIARY         OUT
                                                                                  MAINS        TRANSFORMER
                                                                MAINS                                   AUXILIARY                   TO
                                                            cable section                                MAINS                     LOAD
                                                             ø 6÷35 mm2         Cables                  cable section
                                                                                provided                ø 16÷50 mm2
18 IOMMASIPXX09-GB 04
                                                            L1    L2   L3    L11A L11 N11A N11   L14   N4   L13   N3   L12   N2   +B2   -B2   -B1   +B1
                                                                 MAINS          AUXILIARY         OUT
                                                                 SUPPLY                                                             EXT. BATTERY
                                                                                 MAINS        TRANSFORMER
                                                                                                            IN   OUTPUT
                                                                                                       TRANSFORMER
                                                                                                                                                                   ENGLISH
                                                                 MAINS        AUXILIARY TO                                   Cables
                                                             cable section     MAINS    LOAD                                 provided
                                                              ø 6÷35 mm2      cable section
                                                                              ø 16÷50 mm2
                     • Electrical data.
                     - Admitted Nominal current and voltage of NO or NC contacts: 2 A 250 Vac depending on the terminal used.
                     - Inputs are activated on loop closing.
                     • Connection of the generator.
                     If your system uses a generator, connect the “generator set ready” no-potential contact to connector IN 2 on the op-
                     tional ADC card configured in standard or power safe mode. This automatically extends the voltage and frequency
                     value range when power is supplied by the generator set.
                     • External E.S.D. connection.
                     A remote emergency shutdown system (E.S.D.) can be installed by means of the optional ADC card. Connect a
                     normally closed zero-potential contact to terminals IN1+ and IN1- of the ADC card.
                                                                                                                                         IOMMASIPXX09-GB 04   19
Downloaded from www.Manualslib.com manuals search engine
                                    UNPACKING AND INSTALLATION                                                                                                                     MASTERYS IP+
                        1
                        3           OF THE UNIT                                                                                                                                                                  10-40 kVA
                                                                                                    2
                                                                                        OUT
                                                                                        1
                                     IN1
                                                                                                                                                                                                   DIP1   DIP2
                                     IN2                                                                                                            IN3
                                                                                                                                                                                                     0 1 2 P3
                                                                                                                                                                                                    A
                                   OUT4                                                                                                             OUT3
                                                                                              OUT
                                                                                                    3
                                                                                        4
          ITALIANO
           ENGLISH
                     The filter level indicates the activation delay: 1 immediate activation (1 seconds minimum communication
                     time), 2 10 s delay, 3 30 s delay.
20 IOMMASIPXX09-GB 04
                      Description of signals
                      Message on the mimic panel           Description
                      General Alarm                        “General Alarm” contact output.
                                                           No alarm.
                                                                          NO1
                                                           C1
                                                                          NC1
                                                                                                                                                      ENGLISH
                      Battery Low or Imminent stop         Battery low voltage and imminent shutdown contact output.
                      UPS on bypass                        Contact input for emergency shutdown device.
                      E.S.D.                               UPS on bypass contact output
                      Supply from GenSet                   Generator ready signal input.
                      Isolation controller                 Isolation leakage controller signal input
                      Power safe plug 1                    Non privileged load 1 command output activated by overload or loss of redundancy.
                      Power safe plug 2                    Non privileged load 1 command output activated by battery discharging.
                      Power safe plug 3                    Non privileged load 1 command output activated by battery low.
                      Management of energy consumption     Input for the battery to help providing energy in the event of peak consumption.
                      E.S.D. activation                    Shutdown for E.S.D. contact output.
                      Over-heating                         Internal over-heating contact output.
                      Overload/Loss of redundancy          Overload / loss of redundancy contact output
                                                                                                                            IOMMASIPXX09-GB 04   21
Downloaded from www.Manualslib.com manuals search engine
                               UNPACKING AND INSTALLATION                                                                                                               MASTERYS IP+
                       1
                       3       OF THE UNIT                                                                                                                                                         10-40 kVA
If the UPS has internal batteries, connecting external battery cabinets is forbidden.
                                 • the battery fuses located inside the battery cabinet are open.
                     • Remove the terminal boards protection.
                     • Connect the ground cable (figure 3.8-1).
                     • Connect the cables between the UPS terminals and the battery cabinet terminals, strictly observing the polarity of
                       each individual string (figure 3.8-1) and the cross-sections indicated in the table at page 12.
                                 Use double insulated cables or the cables supplied with the unit to connect the UPS to the Bat-
                                 tery cabinet. The lenght L of battery cable must not be more than 8 metres long (if L > 8 m, please
                                 contact the support service).
                                 Cabling errors with inversion of the battery polarity may cause permanent damage to the equip-
                                 ment.
                                 If using cabinets not supplied by the SOCOMEC UPS, it is the installer’s responsibility to check the
                                 electrical compatibility and the presence of appropriate protection devices between the UPS and
                                 the battery cabinet (fuses and switches of sufficient capacity to protect the cables from the UPS
                                 to the battery cabinet). As soon as the UPS is switched on (before closing the battery switches)
                                 the battery parameters (voltage, capacity, number of elements, etc.) must be verified accordingly
                                 on the mimic panel menu. If the values indicated on the battery cabinet data plate are different
                                 from those shown on the mimic panel, use the SERVICE > CONFIGURATIONS menu to correct the
                                 settings.
                              UPS
                                                                                                                                                                                +B2
                                                                                                                                                                                +B1
                                                                                                                                                                                –B2
                                                                                                                                                                                –B1
EXTERNAL BATTERY
                                           L1   L2   L3   N   L11    L21   L31   N1   L14   L24   L34   N4   L13   L23   L33   L12   L22   L32   N2   +B2   -B2   -B1   +B1
                                                MAINS               AUXILIARY              OUT                     IN                OUTPUT
                                                SUPPLY               MAINS             TRANSFORMER            TRANSFORMER                               EXT. BATTERY
22 IOMMASIPXX09-GB 04
                                                                                                                                                   ENGLISH
                        The inverter is constantly synchronised in frequency with the auxiliary mains to enable load transfer (due to an
                        overload or inverter shutdown) without any break in the power supply to the load.
                        The battery charger supplies the energy required to maintain or recharge the battery.
                     • “Bypass” mode.
                     In case of inverter failure, the load is automatically transferred onto the auxiliary mains without any interruption in
                     the power supply. This procedure may occur in the following situations:
                     - in the event of a temporary overload, the inverter continues to power the load. If the condition persists, the UPS
                       output is switched onto the auxiliary mains via the automatic bypass. Normal operation, which is from inverter,
                       returns automatically a few seconds after the overload disappears.
                     - when the voltage generated by the inverter goes is out of tolerances due to a major overload or a fault on the
                       inverter.
                     - When the internal temperature exceeds the maximum value allowed.
                     • “Battery” mode.
                       In the event of a mains failure (micro interruptions or extended black-outs), the UPS continues to power the load
                       using the energy stored in the battery. The Expert Battery System keeps the user constantly informed on the
                       battery status and on the back-up time available. The disconnection of non mission critical applications during
                       battery discharge can be programmed (after a certain laps of time) by using the Power Share option, so that the
                       battery resources can be reserved for the most critical applications.
                                                                                                                         IOMMASIPXX09-GB 04   23
Downloaded from www.Manualslib.com manuals search engine
                                                                                                   MASTERYS IP+
                       4       MODES OF OPERATION                                                                             10-40 kVA
                                 The external manual maintenance bypass connection is not allowed when the internal transformer
          ITALIANO
           ENGLISH
24 IOMMASIPXX09-GB 04
                      This chapter identifies the electromechanical switches described here below used for start-up, shutdown and
                      maintenance bypass procedures.
                      Access to the control area is from the front by opening the door. The control area also contains the communication
                      interface connectors and the slots for the optional signalling cards. Please refer to the relevant chapter for more
                      details on the connection and use of the related communication interfaces/cards.
                                                                                                                                                          ENGLISH
                       5.1-1
Q2 Q6 Q2 Q6
Q1
                                                B
                                                                        B1            IN            OUT
                                                                             TRANSFORMER            TRANSFORMER
                                                                                                                                IOMMASIPXX09-GB 04   25
Downloaded from www.Manualslib.com manuals search engine
                               ACCESS TO CONTROLS                                                    MASTERYS IP+
                       5       AND COMMUNICATION INTERFACES                                                                     10-40 kVA
                     • Position 1 “UPS”: this is the position for normal operation of the UPS for a continuous power supply to the load;
                     • Position 2 “MANUAL BY-PASS”: This position should only be selected for ordinary or extraordinary maintenance
                       operations (manual bypass); the load is connected directly to the mains power supply. It may be used in the event
                       of a UPS failure to power applications from the auxiliary mains while awaiting the intervention of technical person-
                       nel;
                     • Position 0 “OFF”: This completely isolates the UPS output by removing the voltage from the applications in any
                       operating condition. It is used for the emergency shutdown of the system (internal E.PO.).
                     Battery switch Q1 (UPS batteries).
                     When closed, this switch connects the batteries of the UPS to the DC/DC converter stage to power the inverter in
                      the event of a mains failure. The normal operating position is 1 (closed).
26 IOMMASIPXX09-GB 04
                                                                                                                                              ENGLISH
                     B. multicoloured luminous bar that identifies the
                        condition of the power supply to the load;
                                                                                                                   D
                     C. alphanumeric information that uses a menu layout                  B
                        to provide details on any alarms that may occur
                        and on the measurements, controls and param-
                        eters.
                                                                                                                    IOMMASIPXX09-GB 04   27
Downloaded from www.Manualslib.com manuals search engine
                                                                                                                     MASTERYS IP+
                      6           MIMIC PANEL                                                                                                            10-40 kVA
                      6.2-1
                                                                                    M1
                           M2                                         M8
                                                                                         M9
                                                                                                                            M30
                                 M10                          M11
                                                                                                                            M31
          ITALIANO
           ENGLISH
                                                                                                                                 M19
                                                  M3                                                                                   M18
                                                                                                          M24
                                                                                                                                             M20
                                        M4                                                      M28
                                                                                                                                                   M21
                                                                                              M27
                                       M5                                                                                                          M22
                                                                                              M26
                                                                                                                                              M23
                                        M6                                  M7                      M25
                     Meaning of ideograms
                     Code                   Description                                                         Condition
                     M1                     Load on bypass, in Eco-mode or Maintenance bypass closed            Steady
                                            Automatic bypass alarm                                              Flashing
                     M2                     Input rectifier active.                                             Steady
                                            Input rectifier general alarm.                                      Flashing
                     M3                     Battery OK.                                                         Steady
                                            Battery alarm.                                                      Flashing
                     M4-M7                  Remaining battery capacity.                                         Steps of 25%
                                            Battery recharging.                                                 Sequence M7 M4
                     M8                     Inverter on                                                         Steady
                                            Inverter general alarm.                                             Flashing
                     M9                     Switch Q6 in position 1.                                            Steady
                     M10                    Input mains OK.                                                     Steady
                                            Input mains alarm.                                                  Flashing
                     M11                    Inverter on.                                                        Steady
                     M12                    Module 1 present.                                                   Steady
                                            Module 1 general alarm.                                             Flashing
                     M13                    Module 2 present.                                                   Steady
                                            Module 2 general alarm.                                             Flashing
                     M18                    Load present.                                                       Steady
                                            Overload.                                                           Flashing
                     M19-M28                Output load indicator.                                              Steps of 10%
                     M29                    Periodic maintenance alarm/warning.                                 Flashing
                     M30                    Activation code alarm.                                              Steady
                                            General alarm.                                                      Flashing
                     M31                    LAN connection ready (Cable Connected).                             Steady
28 IOMMASIPXX09-GB 04
                                                                                                                                                               ENGLISH
                      YELLOW flashing              UPS in stand-by or Ups on manual bypass
                                                   Alarm indicating request for ordinary maintenance according to conditions of use (type of load,
                      temperature), after over 25.000 – 30.000 hours of operation (M29 flashing and alarm A44)
                      YELLOW                       Warning for preventive maintenance according to conditions of use (type of load, temperature),
                      after over 10.000 - 12.000 hours of operation (M29 flashing)
                      YELLOW                       Load on battery or battery discharging if M11 is on steady and M10 is off
                      YELLOW                       On automatic bypass if M1 is on steady
                      YELLOW                       First maintenance period expired (10,000 hours of operation) UPS in maintenance mode
                      GREEN flashing               Battery test in progress
                      GREEN                        Load powered from inverter or in high efficiency mod
                       6.4-1
                                                                                                                     Legend.
                                                                                                                     A Current menu.
                                                                                                                     B Active sub menu.
                                                                                                                     C Additional values or information.
                                                        A                                                            D Scrolling contextual help line.
                                B                                                                                    E Scroll bar.
                                                                                                            F        F Statistical graphics display.
                            C                                  E
                                    D                                           D
                                                                                                                                     IOMMASIPXX09-GB 04   29
Downloaded from www.Manualslib.com manuals search engine
                                                                                 MASTERYS IP+
                     1
                     6         MIMIC PANEL                                                              10-40 kVA
                      Parallel UPS
                                                   Single UPS
2.2 STATISTICS
5.2 SETTING
30 IOMMASIPXX09-GB 04
                     The operating modes to activate and manage the UPS are defined in this chapter; please also refer to chapters 6
                     “Mimic panel” and 8 “Menus”.
                                                                                                                                                 ENGLISH
                     7.1 START-UP IN NORMAL MODE.
                     • Check that all UPS and external battery switches are in position 0 (open);
                     • Supply the mains and auxiliary mains to the UPS and put switch Q2 into position 1 (mains ON);
                     • Wait for the mimic panel to switch on;
                     • Activate the procedure COMMANDS > IMMEDIATE COMMANDS > START PROCEDURE;
                     • Carry out the operations indicated on the mimic panel.
                     7.2 SHUTDOWN.
                     Shutdown interrupts the power supply to the load and causes the UPS and the battery charger to stop.
                     • Activate the procedure COMMANDS > IMMEDIATE COMMANDS > STOP PROCEDURE;
                     • Wait approx. 2 minutes for the UPS to shut down (the controlled shutdown of any servers is managed with shut-
                       down software);
                     • Carry out the operations indicated on the mimic panel.
                                                                                                                       IOMMASIPXX09-GB 04   31
Downloaded from www.Manualslib.com manuals search engine
                                                                                                  MASTERYS IP+
                       7       OPERATING PROCEDURES                                                                         10-40 kVA
                                 The UPS output can only be electrically disconnected by putting Q6 to position 00.
                                 If the UPS is operating from the manual bypass (Q6 in position 2) with mains present, the emer-
                                 gency shutdown does not interrupt the power supply to the load. In emergency conditions all the
                                 power supplies upstream of the UPS must be disconnected.
32 IOMMASIPXX09-GB 04
                                                                                                                                                         ENGLISH
                                                                            exceeded.
                      A07      OVER TEMPERATURE                             Temperature excessive or ventilation problems.
                      A08      MAINTENANCE BYPASS ACTIVE                    Q5 in position 1.
                      A17      IMPROPER CONDITION OF USE                    Improper conditions of use verified (load, mains, and temperature).
                      A18      BLOCKING INVERTER FOR OVERLOAD               Inverter shutdown due to overload.
                      A20      WRONG CONFIGURATION                          Error in the configuration parameters (e.g. different parameters
                                                                            between several UPSs in parallel).
                      A22      INPUT MAINS OUT OF TOLERANCE                 The voltage or frequency limits accepted by the rectifier have been
                                                                            exceeded.
                      A23      RECTIFIER GENERAL ALARM                      Rectifier fault.
                      A25      INVERTER GENERAL ALARM                       Inverter fault.
                      A26      BATTERY CHARGER GENERAL ALARM                Battery charger fault.
                      A29      BYPASS GENERAL ALARM                         Bypass fault.
                      A30      STOP FOR OVERLOAD                            The duration of the overload has inhibited the bypass.
                      A32      MODULE 1 GENERAL ALARM                       Module 1 failure.
                      A33      MODULE 2 GENERAL ALARM                       Module 2 failure.
                      A38      EXTERNAL ALARM 1                             Signalling from ADC input.
                      A39      EXTERNAL ALARM 2                             Signalling from ADC input.
                      A40      EXTERNAL ALARM 3                             Signalling from ADC input.
                      A41      EXTERNAL ALARM 4                             Signalling from ADC input.
                      A42      E-SERVICE GENERAL ALARM                      Alarm that generates automatic sending of a signal to the support
                                                                            centre (if the service has been activated).
                      A43      REDUNDANCY LOST                              The power required by the load no longer allows the preset
                               redundancy N+x to be maintained (for UPSs in parallel only).
                      A44      PERIODIC SERVICE CHECK-UP                    Warning for periodic check by support service.
                      A47      MAX BATTERY TEMPERATURE                      Control of the temperature of battery cabinet.
                      A49      BATTERY DISCHARGED                           The energy available in the battery has been used up.
                      A51      OPTION BOARD GENERAL ALARM                   Fault related to the optional PCBs in the slots.
                      A56      GENERATOR SET GENERAL ALARM                  Minor alarm on generator set.
                      A57      GENERATOR SET FAULT                          Major alarm on generator set.
                      A58      E.S.D. ACTIVATED                             The remote emergency shutdown command has been activated.
                      A59      BATTERY CIRCUIT OPEN                         The battery switch is open.
                      A60      FAN FAILURE                                  Fans faulty or blocked.
                      A61      PHASE ROTATION FAULT                         Wrong phase cycle direction.
                                                                                                                               IOMMASIPXX09-GB 04   33
Downloaded from www.Manualslib.com manuals search engine
                                                                                                     MASTERYS IP+
                       1
                       8       MENU                                                                                              10-40 kVA
34 IOMMASIPXX09-GB 04
                                                                                                                                                         ENGLISH
                      MAINTENANCE BY-PASS                  Control to activate the manual bypass and shutdown of the UPS.
                      PROCEDURE
                      HIGH EFFICIENCY MODE                 Activates Eco mode / always on mode.
                      NORMAL MODE                          Activates normal double conversion operation.
                      ALARM RESET                          Resets all the alarms.
                      LEDS TEST                            Performs the test on the mimic panel LEDs.
                                                                                                                               IOMMASIPXX09-GB 04   35
Downloaded from www.Manualslib.com manuals search engine
                                                                                                         MASTERYS IP+
                       8       MENU                                                                                                   10-40 kVA
                     The activation code is provided directly by the reference Support Centre upon communication of the serial number
                     of the equipment which is displayed in the next message by pressing ENTER.
                                                             SEE INSTALLATION MANUAL
                                                             FOR PROCEDURE
                                                             SN: 0000000000
                     When contact is made with the Support Centre for the activation code, detailed information can be obtained on the
                     UPS functions available and on the periodic preventive maintenance programmes.
36 IOMMASIPXX09-GB 04
                     Once the code is obtained, enter it by pressing ENTER to activate the entry (two asterisks will appear). Select the
                     first character with the UP      and DOWN keys and confirm with ENTER to accept the character. Then move
                     on to the next character. Pressing the ENTER key after selecting the fourth character activates code.
                                                                                                                                                          ENGLISH
                     8.5.2 “Present configurations” menu.
                     This is used to change the configuration parameters.
                     Press ENTER. Access is via the password MAST which is keyed in by using the UP                    and DOWN             keys and
                     ENTER to go on to the next letter.
                     Note.
                     Column A shows whether the parameter is visible in the PARAMETERS “CONFIGURATIONS” menu.
                                                                                                                                IOMMASIPXX09-GB 04   37
Downloaded from www.Manualslib.com manuals search engine
                                                                                                          MASTERYS IP+
                      8        MENU                                                                                                 10-40 kVA
38 IOMMASIPXX09-GB 04
                                                                                                                                                      ENGLISH
                     8.6 “EVENT LOG” MENU.
                     Shows a list of UPS events in chronological order.
                     It allows the user to analyse UPS operation with regard to variations in the power supply, load or the environment.
                        8.6-1
                                                                                                       Legend.
                            A                                                       B                  A Shows date and time of event.
                                                                                                       B Shows the event code.
                                                                                                       C Describes the event.
                                                                                                       D ON/OFF status of event.
                                                                                                       E Progressive number of event.
                            C                                                       E
                                                                                                                          IOMMASIPXX09-GB 04   39
Downloaded from www.Manualslib.com manuals search engine
                                                                                                         MASTERYS IP+
                          1
                          9        COMMUNICATION                                                                                                 10-40 kVA
                                                                                                         5       4       3       2       1
                                       Slot 1      Slot 2 RS 232/485 RS 232 RJ45 10BT
                     ADC card            •          •
                     GSS card            •          •                                                        9       8       7       6
                     NetVision card      •   2
                                                    •2
                     UniVision pro                           •                  •4
                                                                                        Legend pin RS232/485 C1                      Legend pin Modem C2
                     Remote Panel                            •                          1 Not connected                              1 Reserved
                     BMS                                     •1
                                                                      •   1
                                                                                •4      2 RX for RS232                               2 RX for RS232
                     Modem                                            •   3             3 TX for RS232                               3 TX for RS232
                     LAN (ethernet)                                             •       4 Data +
                                                                                        5 GND for RS232
                                                                                                                                     4 Reserved
                                                                                                                                     5 GND for RS232
                     1
                         Building Management System.                                    6 Data −                                     6 Not connected
                     2
                         Ethernet adapter with Web/SNMP 10/100Mb functions              7 Reserved                                   7 RTS
                         (E-service via Web required).                                  8 Not connected                              8 CTS
                     3
                         For T-service via telephone network.                           9 +12 V                                      9 +12 V
                     4
                         By jbus tunnelling on TCP/IP.
                     As each channel is independent, simultaneous connections can be made to satisfy the different levels of signalling
                     and remote monitoring.
                     See the options paragraph to access the detailed functions of the PCBs installed in the slots.
                                     Please note that two Net Vision cards or two GSS cards cannot be connected simultaneously.
                                     Only one card of a kind can be used.
40 IOMMASIPXX09-GB 04
                     9.2.1 Activation.
                     Comply with the following operations to activate the mo-
                     nitoring system:
                     • Connect the UPS to the LAN network (connector A in the
                       picture aside).
                                                                                                                                                  ENGLISH
                                                           A
                     A. If the BOOT DHCP protocol is enabled in the local network: verify the IP address shown in the PARAMETERS >
                        PRESENT CONFIG > LOCAL AREA NETWORK IP menu on the UPS mimic panel (go to point C).
                                                                                                                        IOMMASIPXX09-GB 04   41
Downloaded from www.Manualslib.com manuals search engine
                                                                                                 MASTERYS IP+
                       9        COMMUNICATION                                                                               10-40 kVA
                     9.2.2-1
                                                A
B C
                        Legend.
                        A Navigation bar.
                        B Menu bar.
                        C system information area.
42 IOMMASIPXX09-GB 04
                                                                                                                                                 ENGLISH
                                Alarm present: shows the alarms table (this icon appears when the UPS detects an anomaly).
Generator operating mode (this icon appears when the UPS is powered by the generator).
                                Technical support department e-mail address. This connection opens the e-mail program and automati-
                                cally fills in the addressee and subject lines.
                     9.2.2.4 Statistics.
                     The counter folder shows the number of events that have occurred over a given period of time.
                     The average minimum and maximum values of a measurement can be seen by clicking on the measurement folder.
                     A sampling time from one to 10 weeks can be set by clicking on the period folder.
                                                                                                                       IOMMASIPXX09-GB 04   43
Downloaded from www.Manualslib.com manuals search engine
                                                                                                      MASTERYS IP+
                       1
                       9       COMMUNICATION                                                                                      10-40 kVA
                     • Client JBUS IP address to be authorised: if a specific IP address is inserted in this box, then only that address/
                       user will be able to access the html pages. If the address 0.0.0.0 is used, all the PCs on the network will be able to
                       access the supervisor (one client at a time). If the address 255.255.255.255 is inserted, access will be denied to all
                       users.
                     • Software updating: if on, allows the supervisor to be updated.
                     • Page refresh (sec): the page refresh rate can be set.
                     • Installation: text string used to describe the UPS installation site, which is useful if there are more than one unit
                       connected (this value is inserted in SMS messages or e-mails).
                     • NTP Server: indicates the IP address of the time server to automatically update the date and time on the system.
                     • GMT Correction (minutes): indicates local time and the offset in minutes with respect to the zero meridian of
                       Greenwich
                     • Apply the parameter settings: restarts the monitoring system with the new settings.
44 IOMMASIPXX09-GB 04
                                                                                                                                                                                                      ENGLISH
                     This html page is used to update automatically the monitoring software, which could be useful to add new languages
                     or the SNMP function.
                     Once the file has been acquired (by requesting it from the support service) select it with the browse button.
                     Click on the “start update” button; once the update has been completed, reload the html page.
                                                                                                                                                                            IOMMASIPXX09-GB 04   45
Downloaded from www.Manualslib.com manuals search engine
                                                                                                     MASTERYS IP+
                       1
                       9       COMMUNICATION                                                                                    10-40 kVA
                     • Remote shutdown via proxy agent and optional Java shutdown clients
           ENGLISH
                     NET VISION is a solution for managing UPS units connected directly to the local network. It is normally used on
                     medium/large, complex networks and in multi-server environments where the IT manager centrally controls all the
                     network resources. The physical position of the UPS is not significant. The main functions are:
                     • 10/100Mb Ethernet connection (RJ45)
                     • Graphic monitoring of the UPS via web browser
                     • Remote shutdown of up to 40 computers
                     • Notification of anomalies via e-mail to a maximum of 8 addresses
                     • UPS management using SNMP protocol
                     • Diagnostics via Internet offered by e-Service.
                     Java & .NET shutdown Client (JNC) is an optional Java application to be installed on a server for the automatic
                     shutdown of the computers on the network before the UPS stops due critical operating conditions (imminent battery
                     failure, overload, etc.). It is supplied as an option and can be associated to the UNI VISION PRO or NET VISION commu-
                     nication solutions. The main features/functions are:
                     • Use of the TCP/IP standard network protocol
                     • Graphics interface for easy configuration
                     • Minimum use of CPU resources
                     • Personalisation of shutdown parameters and script
                     • Continuous monitoring of the efficiency of the connection to the UPS.
                     T.Service is a cutting edge supervision service ensuring 24/7/365 service. It ensures effective prevention and con-
                     stant monitoring of the system. Communication between the UPS and the local Socomec Service Centre is via
                     modem (free-air GSM or ANALOG fixed line). The auto-diagnostic system analyses UPS operating conditions, identi-
                     fies faults and monitors environmental conditions such as temperature, overload, avoiding the risk of equipment
                     stoppages. In the event of a failure, the system immediately sends a “diagnostic report” via modem to the Service
                     Centre. Any emergency situation is managed and resolved extremely quickly and remotely by the Service Centre,
                     with immediate intervention on site if needed.
46 IOMMASIPXX09-GB 04
                                                                                                                                                      ENGLISH
                       disconnect any loads that do not need uninterruptible power.
                       Important!
                       The accepted overload time limit is defined in the technical specifications. When this time limit is exceeded, the
                       loads will no longer be powered by the inverter.
                     • A06: auxiliary mains out of tolerance.
                       The auxiliary mains exceeds the acceptable tolerance values. Possible causes are:
                       • No voltage or frequency present or voltage and frequency out of acceptable values (see the technical specifica-
                         tions).
                       • The frequency is subject to continuous variations (typical with power supplied from an incorrectly sized GE).
                     • A07: temperature over the limits.
                       The UPS internal temperature is higher than 50 °C (please refer to Measurements menu on the mimic panel).
                       Check the ventilation or air conditioning system in the UPS room.
                     • A08: maintenance bypass activated.
                       The output disconnecting switch Q6 is in position 2 (maintenance bypass).
                       The load is therefore powered directly by mains power supply.
                     • A17: improper conditions of use.
                       This alarm does not indicate a malfunction or failure of the UPS, but an incorrect use/sizing of the system. It is
                       activated in the event of:
                       • Operation for long periods at high temperatures (battery deterioration)
                       • High number of overloads (wrong sizing)
                       • Continuous battery discharging (mains not stable)
                       • High number of switches onto the bypass (high impulsive loads)
                     • A22: input mains out of tolerance.
                       The input mains is not present or not sufficient (voltage and/or frequency values incorrect with reference to the
                       technical data); if there is no input mains outage, check if no protections upstream of the UPS have tripped.
                       Check that the voltage applied and frequency values are in compliance with the values set on the mimic panel.
                     • A38, A39, A40, A41: external alarm 1, 2, 3, 4.
                       One of the ADC PCB inputs has been activated; check the situation of the devices connected to this PCB.
                     • A56, A57: generator general alarm.
                       The generator has sent an alarm; check directly on the GE.
                                                                                                                            IOMMASIPXX09-GB 04   47
Downloaded from www.Manualslib.com manuals search engine
                                                                                                        MASTERYS IP+
                     10        PROBLEM SOLVING                                                                                      10-40 kVA
48 IOMMASIPXX09-GB 04
                                                                                                                                                ENGLISH
                     10.3.1 Batteries.
                     The state of the battery is fundamental to UPS operation.
                     Thanks to the Expert Battery System, the information relating to the state and the conditions of use of the battery
                     are processed in real time and the recharging and discharging procedures are selected automatically in order to
                     optimise battery life expectancy and offer maximum performance.
                     Furthermore, during the operating life of the battery, MASTERYS™ stores statistics on the conditions of use of the
                     battery for analysis.
                     Since the expected life of the batteries is very much dependent on operating conditions (number of charging and
                     discharging cycles, load rate, temperature), a periodic check by authorised personnel is recommended.
                                When replacing the batteries, use the same type and configuration by placing them in the appro-
                                priate containers so as to avoid the risk of acid leakage.
                                The replaced batteries must be disposed of at authorised recycling and disposal centres.
                                Do not open the plastic cover of the batteries as they contain harmful substances.
                     10.3.2 Fans.
                     The life of the fans used to cool the power parts is dependent on the using and environmental conditions (tem-
                     perature, dust).
                     Preventive replacement by an authorised technician is recommended within four years (in normal operating condi-
                     tions).
                     10.3.3 Capacitors.
                     The equipment houses electrolytic capacitors (used in the rectifier and inverter section) and filtering capacitors
                     (used in the output section), whose life is dependent on using and environmental conditions.
                     The average expected life of these components is shown below:
                     • Electrolytic capacitors: 5 years;
                     • Filtering capacitors: 7 years.
                     In any case the effective state of the components is verified during preventive maintenance.
                                                                                                                      IOMMASIPXX09-GB 04   49
Downloaded from www.Manualslib.com manuals search engine
                                                                                                    MASTERYS IP+
                     11        OPTIONS                                                                                                     10-40 kVA
                                                                                                     Legend.
                                                                                                     A LAN RJ45 connector for Ethernet.
                                                                                                     B Serial RS232 connector for Modem.
                                                                                                     C Serial RS232/485 connector for after sales.
                                                               A        B       C                    F DIN rail (under the panel)
                                                                                                     L Slots for communication cards (ADC card
                                                                                                         installed as standard, 1 slot available for an
                                                                                                         additional card).
          ITALIANO
           ENGLISH
L L
F F
50 IOMMASIPXX09-GB 04
                                                                                                                                                                                                        ENGLISH
                     11.6 EXTERNAL BACK-FEED PROTECTION.
                     External devices can be installed to protect against the backfeed of dangerous currents, both on the MAINS SUPPLY
                     and on the AUX MAINS SUPPLY.
                     These devices have to be connected to the terminals provided (see picture 11.6-1).
                     Refer to the following paragraphs for details on the electrical connections and on activating the chosen protec-
                     tion.
                     Attention.
                     In some failure conditions (earth leakage, significant phase dispersion or in case of non-isolated neutral system), high
                     potential can be detected in the neutral. It will therefore be necessary to install either adequate neutral switching
                     or protection system.
                               COM1          L1      L2   L3   N   L11    L21   L31   N1   L14   L24   L34   N4   L13   L23   L33   N3   L12   L22   L32   N2   +B2   -B2   -B1   +B1
                                  NC1             MAINS                  AUX MAINS              OUT                     IN
                                  COM2            SUPPLY                  SUPPLY            TRANSFORMER            TRANSFORMER                 OUTPUT             EXT. BATTERY
                                      NC2
                                                                                                                                                                              IOMMASIPXX09-GB 04   51
Downloaded from www.Manualslib.com manuals search engine
                                                                                                         MASTERYS IP+
                     11         OPTIONS                                                                                                  10-40 kVA
11.6.1-1 UPS 3/3 with separate auxiliary supply. 11.6.1-2 UPS 3/1 with separate auxiliary supply.
                                      A                                UPS                          A                            UPS
          ITALIANO
                                SW1             T1                        M1                  SW1         T1                        M1
           ENGLISH
                          L1                                   L1                       L1                                L1
                          L2                                   L2                       L2                                L2
                          L3                                   L3                       L3                                L3
                          N                                    N                        N                                 N
B B
                                SW2             T2                        M2                  SW2         T2                        M2
                          L11                                  L11
                          L21                                  L21
                          L31                                  L31                      L11                               L11
                          N1                                   N1                       N1                                N1
B B
                                                                          M3                                                        M3
                                                               NC1                                                        NC1
                                                               COM1                                                       COM1
                                                               NC2                                                        NC2
                                                               COM2                                                       COM2
                     Legend.                                                      1
                                                                                      Remote switches - rated current
                     A                  Distribution panel
                     B                  Coil remote switch                              Model                  T1                       T2
                     L1-L2-L3-N         Input power source                              10 3/1              32 A AC1                 45 A AC1
                     L11-L21-L31-N1     Backup power source                             15 3/1              32 A AC1                 45 A AC1
                     M1                 Input power terminals                           20 3/1              45 A AC1                 60 A AC1
                     M2                 Backup power terminals
                                                                                        30 3/1              60 A AC1                 60 A AC1
                     M3                 Backfeed terminals
                     T1                 Remote switch1
                                                                                        10 3/3              32 A AC1                 32 A AC1
                     T2                 Remote switch1                                  15 3/3              32 A AC1                 32 A AC1
                     SW1                Input power switch on the distribution          20 3/3              45 A AC1                 45 A AC1
                     SW2                Backup power switch on the distribution         30 3/3              60 A AC1                 60 A AC1
                                                                                        40 3/3              90 A AC1                 90 A AC1
52 IOMMASIPXX09-GB 04
                      11.7 PROFIBUS.
                      On request, the UPS can be provided with a Profibus pro-
                      tocol converter, installation software, configuration software
                      and user manuals (detail P on the picture aside).
                                                                                                                                                   ENGLISH
                                                                                                                     P
                                                                                                                         IOMMASIPXX09-GB 04   53
Downloaded from www.Manualslib.com manuals search engine
                                                                                                                              MASTERYS IP+
                     11             TECHNICAL SPECIFICATIONS                                                                                        10-40 kVA
                     Models
                                                                      10            15              20             30            40
                     Input/Output phases                         3/1 and 3/3   3/1 and 3/3     3/1 and 3/3    3/1 and 3/3        3/3
                                                                                                                                                                 1400
                     Electrical specifications - Input
                                                                     10            15           20            30            40
                     Mains voltage                                     3P+N 400 V +20% -15% (up to -35% @70% of nominal load)                              800
                     Input frequency                                                      50-60 Hz ±10%
          ITALIANO
                                                                                                                                            600
           ENGLISH
                     Environment
                                                                     10             15              20             30              40
                     Operating temperature                              0÷40 °C (15÷25 °C recommended for longer battery life)
                     Storage temperature                                                        -5÷45 °C
                     Relative humidity                                                  0÷95% condensation-free
                     Max. altitude                                     1.000 m (3.300 ft) without derating; 3.000 m (10.000 ft) max
                     Acoustic noise (dB)                            < 52           < 52            < 52           < 55            < 55
                     Required cooling capacity (m3/h)               280            280             280             465             465
                     Dissipated power max (W)                       680            900             1150           1750            2300
                     Dissipated power (BTU/h)                       2300           3050            4070           6050            7900
                     Standards
                                                                     10             15               20           30              40
                     Safety (TÜV SÜD certified)                                          EN 62040-1-1, EN 60950-1
                     Type and performance                                                 EN 62040-3 (VFI-SS-111)
                     EMC                                                                       EN 62040-2
                     Product certification                                                     CE, TÜV SÜD
                     Protection level                                                               IP31
54 IOMMASIPXX09-GB 04
                     MASTERYS IP+
                                                           10-40 kVA
                     MASTERYS IP+ allows both parallel power and parallel 1+1 redundant configurations.
                                 WARNING!
                                 Parallel power configuration is possible ONLY with the transformer connected in the input (Mains
                                 or Auxiliary Mains).
                                 WARNING!
                                 Parallel with transformer connected to the output is possible only by using the specific kit
                                 including two specific UPS (one with transformer and one without transformer) for 1+1 redundant
                                 configuration.
          ITALIANO
           ENGLISH
                                 WARNING!
                                 Parallel configuration must only be activated by SOCOMEC UPS qualified personnel.
                     Use the UPS in accordance with the technical specifications given in this Installation and Operating Manual.
                     The UPS units connected in parallel configuration are identical to a standard UPS, as a result safety, shipping and
                     installation recommendations in chapters 2 and 3 also apply.
                     INSTALLATION.
                     • Parallel power configuration:
                       Please check that the transformer is connected on the input side (Mains or Aux Mains - refer to paragraph 3.5).
                       UPS units operating in parallel are interconnected using control cables and are configured differently depending
                       on the position they are assigned. For this reason the units have a position label:
                       • The “LEFT” label means that the unit must be positioned to the left.
                       • The “RIGHT” label means that the unit must be positioned to the right.
                       • The “INTERNAL” label (used only on systems with three UPS) means that this unit must be positioned between
                         the two other cabinets.
                     • Parallel 1+1 redundant configuration:
                       UPS units operating in parallel 1+1 redundant configuration are interconnected using control cables and are
                       configured differently depending on the position they are assigned. For this reason the units have a position
                       label:
                       • The “LEFT” label means that the unit must be positioned to the left (UPS with transformer configured as concentrator).
                       • The “RIGHT” label means that the unit must be positioned to the right (UPS without transformer).
                     The control cables supplied allow a maximum distance of about 3 metres between the UPS units. This gives enough
                     room for an external battery cabinet to be inserted beside each UPS.
                                 WARNING!
                                 The UPS must be secured to the floor (see paragraph 3.3).
                     POWER CONNECTIONS.
                     • The power supply to each unit must be protected as indicated in the table in paragraph 3.4.
                     • The cross section and length of the input and output cables must be identical for all the units.
                     • The phase rotation must be the same for all units connected in parallel.
56 IOMMASIPXX09-GB 04
                     • Cables of the same length and cross section must be used for the connection between the general power
                       switch ❶, the switches ➋ and the respective UPS units.
                     • If a differential switch is installed on the mains power switch (optional), it must be inserted upstream from the
                       distribution panel, it must be a selective type and the trigger value must be 0.5 A by the number of UPS
                       connected in parallel.
                     CONTROL CONNECTIONS.
                     In order for units connected in a parallel configuration to operate correctly, control cables are required to exchange
                     data between the various UPS units making up the parallel system, for management of correct load sharing and
                                                                                                                                                   ENGLISH
                     synchronisation logic. The cables in question are supplied with the UPSs.
                                                                                                                         IOMMASIPXX09-GB 04   57
Downloaded from www.Manualslib.com manuals search engine
                     PARALLEL CONFIGURATION
                                                                                                 MASTERYS IP+
                                                                                                                                 10-40 kVA
                                                                    ❶                      ❶
          ITALIANO
           ENGLISH
                                               ➋       ➋         ➋             ➋       ➋         ➋
                                25 m max
➋ ➋ ➋ ➋ ➋ ➋
L I I I I R
                                                           ➌       ➌           ➌           ➌         ➌
                                15 m max
❹ ❹ ❹ ❹ ❹ ❹
                                                                           ❺
                                                                                       ❻                 Legend.
                                                                                                         1 Main differential magneto-thermal
                                                                                                            switch.
                                                                                                         2 Magneto-thermal switch.
                                                                                                         3 “Parallel bus” cable.
                                                                                                         4 Output switch.
                                                                                                         5 System shutdown switch.
                                                                                                         6 Distribution.
                                                                                                         I Internal UPS.
                                                                                                         L Left UPS
                                                                                                         R Right UPS
58 IOMMASIPXX09-GB 04
❶ ❶
                                                                                                                                                  ENGLISH
                                                                      ➋           ➋
                                                           25 m max
➋ ➋
L R
                                                                                  ➐
                                                           15 m max
                                                                      ❺
                                                                                          ❻          Legend.
                                                                                                     1 Main differentialmagneto-thermal
                                                                                                       switch.
                                                                                                     2 Magneto-thermal switch.
                                                                                                     3 “Parallel bus” cable.
                                                                                                     4 Output switch.
                                                                                                     5 System shutdown switch.
                                                                                                     6 Distribution.
                                                                                                     7 Power connections (refer to page 60)
                                                                                                     L Left UPS
                                                                                                     R Right UPS
                                                                                                                        IOMMASIPXX09-GB 04   59
Downloaded from www.Manualslib.com manuals search engine
                     PARALLEL CONFIGURATION
                                                                                                                                     MASTERYS IP+
                                                                                                                                                                               10-40 kVA
                                 WARNING!
                                 Before connecting TA4 and TA5 remove the bridge cable from TA4-TA5 on both UPSs
                                           L1   L2   L3   N   L11    L21   L31   N1   L14   L24   L34   N4   L13   L23   L33   N3    L12   L22   L32   N2   +B2   -B2   -B1    +B1
                                                MAINS               AUXILIARY              OUT                     IN
                                                                                                                                           OUTPUT             EXT. BATTERY
                                                SUPPLY               MAINS             TRANSFORMER            TRANSFORMER
                                           L1   L2   L3   N   L11    L21   L31   N1   L14   L24   L34   N4   +B2   -B2   -B1   +B1
                                                MAINS               AUXILIARY               OUTPUT
                                                                                                               EXT. BATTERY
                                                SUPPLY               MAINS
60 IOMMASIPXX09-GB 04
L1 L2 L3 N L11A L11 N11A N11 L14 N4 L13 N3 L12 N2 +B2 -B2 -B1 +B1
                                                                                                                                                                     ENGLISH
                                                                MAINS            AUXILIARY       OUT
                                                                SUPPLY                                                                 EXT. BATTERY
                                                                                  MAINS      TRANSFORMER
                                                                                                             IN   OUTPUT
                                                                                                        TRANSFORMER
Cables provided
                                                                                                                                           IOMMASIPXX09-GB 04   61
Downloaded from www.Manualslib.com manuals search engine
Downloaded from www.Manualslib.com manuals search engine
                     IP52 VERSION
                     MASTERYS IP+
                                                           10-30 kVA
                                   IMPORTANT.
                                   • This section provides important instructions for the safe use, movement and connection of
                                     MASTERYS IP+ IP52 version.
                                   • All the information included in this manual are valid except for the following ones that are
                                     specific for MASTERYS IP+ IP52 version.
                                   • To ensure the IP52 protection, the floor roughness tolerance must be 3 mm max.
                                                        MAST
                                                            ERYS
                                                                 IP+
1 2 3
64 IOMMASIPXX09-GB 04
                                                                                                                                                 ENGLISH
                                                                                                           3 mm max
                                                                                                                       IOMMASIPXX09-GB 04   65
Downloaded from www.Manualslib.com manuals search engine
                     IP52 VERSION
                                                                                          MASTERYS IP+
                                                                                                    10-40 kVA
Not provided
                     PREVENTIVE MAINTENANCE.
                     Please also refer to paragraph 10.3.
                     The user is allowed ONLY to replace the front
                     door internal air filter. A spare part kit is avail-
                     able as options.
                     It is strongly recommended to replace the front
                     door internal air filters at least every 6 months,
                     but their wear can be increased by the environ-
                     mental conditions.
                     Any other maintenace operation on the equip-
                     ment must be only carried out by SOCOMEC
                     UPS personnel or by authorised support per-
                     sonnel.
Air filters
66 IOMMASIPXX09-GB 04
                      Models
                                                                      10                15                  20                 30
                      Input/Output phases                        3/1 and 3/3       3/1 and 3/3         3/1 and 3/3        3/1 and 3/3
                                                                                                                                                                         1400
                      Electrical specifications - Input
                                                                     10              15                20                30
                      Mains voltage                                  3P+N 400 V +20% -15% (up to -35% @70% of nominal load)
                      Input frequency                                                   50-60 Hz ±10%
                                                                                                                                                                                ENGLISH
                      Input power factor                                                     0,99
                                                                                                                                                                   800
                      THDI                                                                  < 2.5%
                                                                                                                                           600
                      Environment
                                                                     10                 15                 20                  30
                      Operating temperature                                                    0÷35 °C
                      Storage temperature                                                     -5÷45 °C
                      Relative humidity                                               0÷95% condensation-free
                      Max. altitude                                  1.000 m (3.300 ft) without derating; 3.000 m (10.000 ft) max
                      Acoustic noise (dB)                           < 52                < 52               < 52                < 55
                      Required cooling capacity (m3/h)              625                 625                 625                625
                      Dissipated power max (W)                      680                 900                1150               1750
                      Dissipated power (BTU/h)                      2300                3050               4070               6050
                      Standards
                                                                     10                 15                20                   30
                      Safety                                                          EN 62040-1-1, EN 60950-1
                      Type and performance                                             EN 62040-3 (VFI-SS-111)
                      EMC                                                                   EN 62040-2
                      Product certification                                                      CE
                      Protection level                                                          IP52
                                                                                                                                             IOMMASIPXX09-GB 04   67
Downloaded from www.Manualslib.com manuals search engine
Downloaded from www.Manualslib.com manuals search engine
Downloaded from www.Manualslib.com manuals search engine
Downloaded from www.Manualslib.com manuals search engine
Downloaded from www.Manualslib.com manuals search engine
                 Socomec worldwide
                 IN WESTERN EUROPE                                          IN EASTERN EUROPE,                    IN ASIA PACIFIC                               IN AMERICA
                                                                            MIDDLE EAST, AFRICA
                 BELGIUM                                                    UNITED ARAB EMIRATES                  AUSTRALIA                                     LATIN AMERICAN COUNTRIES
                 B - 1190 Bruxelles                                         371355 Dubai airport free zone        Macquarie Park NSW 2113                       Tel. +34 935 407 575
                 Tel. +32 (0)2 340 02 34                                    Dubai (United Arab Emirates)          Tel. +61 2 9325 3900                          info.ups.sib@socomec.com
                 info.ups.be@socomec.com                                    Tel.: +971 (0) 4 29 98 441            info.ups.au@socomec.com
                                                                            info.ups.ae@socomec.com
                 FRANCE                                                                                           CHINA
                 F - 94132 Fontenay-sous-Bois Cedex                         POLAND                                Chaoyang, Beijing 100016 P.R., China
                 Tel. +33 (0)1 45 14 63 90                                  01-625 Warszawa                       Tel. +86 10 59756108
                 dcm.ups.fr@socomec.com                                     Tel. +48 22 825 73 60                 info.ups.cn@socomec.com
                                                                            info.ups.pl@socomec.com
                 GERMANY                                                                                          INDIA
                 D - 68309 Mannheim                                         ROMANIA                               Guindy, Chennai – 600 032
                 Tel. +49 (0) 621 71 68 40                                  023383 Bucharest                      Tel. +91 44 3921 5400
                 info.ups.de@socomec.com                                    Tel. +40 21 319 36 88 ( 89, 81, 82)   info.ups.in@socomec.com
                                                                            info.ups.ro@socomec.com
                 ITALY                                                                                            MALAYSIA
                 20098 San Giuliano Milanese (MI)                           RUSSIA                                47301 Petaling Jaya.- Selangor, Malaysia
                 Tel. +39 02 98 242 942                                     125167 - Moscow                       Tel. +603 7804 0850
                 info.ups.it@socomec.com                                    Tel. +7 495 775 19 85                 info.ups.my@socomec.com
                                                                            info.ups.ru@socomec.com
                 PORTUGAL                                                                                         SINGAPORE
                 2640-486 Mafra                                             SLOVENIA                              Singapore 408694
                 Tel. +351 261 812 599                                      SI - 1000 Ljubljana                   Tel. +65 6506 7600
                 info.ups.pt@socomec.com                                    Tel. +386 1 5807 860                  info.ups.sg@socomec.com
                                                                            info.ups.si@socomec.com
                 SPAIN                                                                                            THAILAND
                 E - 08329 Teià (Barcelona)                                 TURKEY                                Chatujak Bangkok 10900
                 Tel. +34 935 407 575                                       34357 Istanbul                        Tel. +66 2 941-1644-7
                 info.ups.sib@socomec.com                                   Tel. +90 (0) 216 540 71 20            info.ups.th@socomec.com
                                                                            info.ups.tr@socomec.com
                 THE NETHERLANDS                                                                                  VIETNAM
                 NL - 3991 CD Houten                                        OTHER COUNTRIES                       Ho Chi Minh City
                 Tel. +31 (0)30 760 0911                                    Tel. +39 0444 598 611                 Tel. +84-839734.990
                 info.ups.nl@socomec.com                                    info.ups.emea@socomec.com             info.ups.vn@socomec.com
                 UNITED KINGDOM                                                                                   ASIA PACIFIC HEAD OFFICE
                 Cirencester - GL7 5XL                                                                            Tel. +65 6507 9770
                 Tel. +44 (0)1285 863300                                                                          info.ups.apac@socomec.com
                 info.ups.uk@socomec.com
                 OTHER COUNTRIES
                 Tel. +34 935 407 575
                 info.ups.europe@socomec.com
                                                                                                                  *IOMMASIPXX09-GB 04*
                 SOCOMEC Isola Vicentina
                 Via Sila, 1/3 - I - 36033 Isola Vicentina (VI) - ITALY
                 Tel. +39 0444 598611 - Fax +39 0444 598622
                 hr.ups.it@socomec.com
                                                                                                                                      IOMMASIPXX09-GB             04     12.2012
www.socomec.com