Liebert Gxt4 UPS 120V/208V 500VA-3000VA: User Manual
Liebert Gxt4 UPS 120V/208V 500VA-3000VA: User Manual
User Manual
ii
iii
iv
                         ! WARNING
                           Observe all cautions and warnings in this manual. Failure to do so may result in serious
                                 injury or death.
                                 Refer all UPS and battery service to properly trained and qualified service personnel. Do not
                                 attempt to service this product yourself.
                                 Opening or removing the cover may expose you to lethal voltages within this unit even when
                                 it is apparently not operating and the input wiring is disconnected from the electrical source.
                                 Never work alone.
1 Liebert® GXT4™
Battery Safety
                         ! CAUTION
                           Do not dispose of batteries in a fire. The batteries may explode.
                                 Do not open or mutilate the batteries. Released electrolyte is toxic and is harmful to skin and
                                 eyes.
                                 Dispose of used batteries according to the instructions.
                         ! CAUTION
                           A battery can present a risk of electrical shock and high short circuit current. The following
                                 precautions should be observed when working on batteries:
                                 • Remove watches, rings and other metal objects.
                                 • Use tools with insulated handles.
                                 • Wear rubber gloves and boots.
                                 • Do not lay tools or metal parts on top of batteries.
                                 • Disconnect charging source prior to connecting or disconnecting battery terminals.
                                 • Determine if the battery is inadvertently grounded. If it is inadvertently grounded, remove
                                   the source of the ground. Contact with any part of a grounded battery can result in electri-
                                   cal shock. The likelihood of such shock will be reduced if grounds are removed during
                                   installation and maintenance (applicable to a UPS and a remote battery supply not having
                                   a grounded supply circuit).
Liebert® GXT4™ 2
AC input
AC output
                                    -       +
                                                   Indicates the unit contains a valve-regulated lead acid battery
                                     PbH2SO4
R Recycle
DC voltage
Bonded to ground
AC voltage
WEEE
3 Liebert® GXT4™
             1.1       Features
                         •   Intelligent battery management to extend the battery life
                         •   LCD for user-friendly operation and local monitoring and configuration of operational parameters
                         •   Controllable outlet groups
                         •   Flexible network management with Liebert MultiLink™ software
                         •   Fan fault self-inspection and automated diagnostic function
                         •   Intelligent fan operation, automatically changing rotation speed depending on system
                             requirements, to decrease power consumption and noise
                         •   Input circuit breaker to ease recovery from overloads
                         •   Safety approval from UL and cUL
                         •   Communication options: USB port, Liebert IntelliSlot® port and terminal block communication
                         •   Dry contacts for remote monitoring
                         •   Input power factor greater than 0.99
                         •   Output voltage selection function
Liebert® GXT4™ 4
                                                Ventilation Slots
                                                                            Operation and
                                                                            Display Panel
             Figure 2        Rear panel components—Liebert GXT4 120V rack/tower, 500, 700, 1000VA model
                             Liebert                                               General Output   Programmable
                             IntelliSlot                            Strain                          Output
                                                                    Relief         Receptacle                        Input Circuit
                             Port                                                                   Receptacle       Breaker
                                         USB Port                   Attachment
                   Terminal Block
                                         RS232      Cooling            External         Programmable Output
                   Communication
                                         Port       Fan                Battery          Receptacles #1
                                                                       Connector                              Input Power Plug
                                                                                                              and Cable
5 Liebert® GXT4™
                                                           External
                Terminal Block RS232                                           Strain       Programmable Output
                                                 Cooling   Battery
                Communication Port                                             Relief       Receptacle #1
                                                 Fan       Connector
                                                                               Attachment
                                                           External
                Terminal Block RS232                                           Strain       Programmable Output
                                                 Cooling   Battery
                Communication Port                                             Relief       Receptacle #1
                                                 Fan       Connector
                                                                               Attachment
Liebert® GXT4™ 6
                                                                                                                          Output
                Terminal Block         RS232     Cooling                                     Programmable Output
                                                                External                                                  Circuit
                Communication          Port      Fan                                         Receptacle #1
                                                                Battery                                                   Breaker
                                                                Connector     Output
                                                                                   Strain Relief
                                                                                   Attachment
                                                                   External
               Terminal Block                                      Battery
               Communication                Cooling               Connector                                               Programmable
                                            Fan                                                                           Output
                                                                                                                          Receptacle 2
                                                                                                                          L6-15R
                                                                                                           Non-Programmable
                                                                                                           Output Receptacle 2
                                                                                                           L6-20R
7 Liebert® GXT4™
                                                                                                    Dynamic                       Programmable
                                                                                                    Bypass                            Outlet
                                                                                                                   L                 Group 1
               L              TVSS                    Rectifier/                                          EMI/RFI
                             EMI/RFI                                              Inverter                                     Programmable
              N/L2*                                     PFC                                                Output N/L2*
                              Input                                                                        Filter                  Outlet
                                                                                                                   G
               G              Filter                                                                                              Group 2
                                                                                                                               General
                                                                    DC-DC                                                       Outlet
                                                                   Converter                                                    Group
                                                                                                                              General
                                                                                                                               Outlet
                                                                                                                          (3000 VA Only)
                                               Battery
                                                                     Battery
                                               Charger
                       The UPS is composed of utility input, TVSS and EMI/RFI filters, rectifier/PFC, inverter, battery
                       charger, DC-to-DC converter, battery, dynamic bypass and UPS output.
                       Inverter
                       In normal operation, the Liebert GXT4’s inverter utilizes the DC output of the PFC to produce
                       precise, regulated sine wave AC power. When utility power fails, the inverter receives DC power from
                       the DC-to-DC Converter. In either operation mode, the UPS inverter is online, continuously
                       generating clean, precise, regulated AC output power.
                       Battery Charger
                       The battery charger utilizes energy from the utility power and precisely regulates it to continuously
                       float charge the batteries. The batteries are being charged whenever the Liebert GXT4 is plugged in,
                       even when the UPS is not turned On.
Liebert® GXT4™ 8
                       DC-to-DC Converter
                       The DC-to-DC converter raises the DC voltage from the battery to the optimum operating voltage for
                       the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage,
                       thus increasing reliability.
                       Battery
                       The Liebert GXT4 uses valve-regulated, nonspillable, lead acid batteries. To maintain battery design
                       life, operate the Liebert GXT4 in an ambient temperature of 32°F to 77°F (0°C to 25°C).
                       Optional external battery cabinets are available to extend battery run times.
                       Dynamic Bypass
                       The Liebert GXT4 provides an alternate path for utility power to the connected loads in the unlikely
                       event of a UPS malfunction. Should the Liebert GXT4 have an overload, overtemperature or UPS
                       failure condition, the UPS automatically transfers the connected loads to bypass.
                                 NOTE
                                 The bypass power path does not protect the connected loads from disturbances on the utility.
                                 NOTICE
                                 Risk of loss of power to the connected load. Can cause equipment damage.
                                 Turning Off the UPS in Bypass Mode will result in loss of output power to the connected load.
9 Liebert® GXT4™
                                 NOTICE
                                 Risk of loss of power to the connected load. Can cause equipment damage.
                                 Turning Off the Liebert GXT4 when it is in Battery Mode will result in loss of output power to
                                 the connected load.
                                 If the UPS is turned Off manually, it must be manually restarted after mains power returns.
                                 If the UPS is turned Off by a communication signal or because the batteries are depleted, it
                                 will operate as set in the configuration program for Auto-Restart (Refer to 5.2.1 -
                                 Configuration Program).
                                 NOTE
                                 The default for all models of the Liebert GXT4 is “Auto Sensing - 50Hz or 60Hz – Bypass
                                 Enabled.”
                         ! CAUTION
                           Risk of electric shock. Can cause injury or death.
                                 Never touch the AC input receptacle while the UPS is operating. Voltage may still be present
                                 even when the AC input indicator is Off.
Liebert® GXT4™ 10
2.0 INSTALLATION
                                 NOTE
                                 The GXT4 External Battery Cabinet shipping package includes one battery cabinet, two spacers
                                 for tower configuration and one DC power cable and rack mounting hardware, including
                                 screws, handles and mounting rail kit (not included with model numbers ending with an “E”).
                                 NOTE
                                 Operating the Liebert GXT4 in temperatures above 77°F (25°C) reduces battery life.
                       Installation Clearances
                       Maintain at least 4 inches (100mm) clearance in the front and rear of the Liebert GXT4. Do not
                       obstruct the air inlets on the front panel and rear panel of the UPS; blocking the air inlets reduces
                       ventilation and heat dissipation, shortening the service life of the Liebert GXT4.
11 Liebert® GXT4™
                                 NOTE
                                 When installing the UPS or making input and output connections, comply with all relevant
                                 safety codes and standards
Support Bases
                       2. If optional Liebert external battery cabinets will be connected to the Liebert GXT4, take out the
                          spacers shipped with the battery cabinet.
                       3. Connect the spacers and the support bases as shown in Figure 8. Each Liebert GXT4 needs two
                          assembled support bases, one in the front and one in the rear.
                       4. Adjust the direction of the operation and display panel and logo on the Liebert GXT4.
                          a. Remove the front plastic bezel cover as shown in Figure 9.
                            b. Pull the operation and display panel gently, rotate it 90 degrees clockwise and snap it back
                               into position, as shown in Figure 10.
Liebert® GXT4™ 12
                            c.Pull the logo on the front plastic bezel cover gently, rotate it 90 degrees clockwise and snap it
                              back into position. The rotated front plastic bezel cover is shown in Figure 11.
                          d. Replace the front plastic bezel cover on the Liebert GXT4. At this point, the UPS operation
                              and display panel and logo have been rotated 90 degrees clockwise, which provides upright
                              viewing for users.
                       5. Place the Liebert GXT4 and any battery cabinets on the support bases. Each Liebert GXT4 needs
                          two support assemblies, as shown in Figure 11.
                                                              Support
                                                               Bases
                                                                                                                  Support
                                                                                                                  Bases
13 Liebert® GXT4™
                       Liebert GXT4 models 700-1500VA and 2000VA have three groups of outlets as shown in Figure 2.
                       One group is always On; the other two groups may be controlled with either programmed responses or
                       over an SNMP network. The 3000VA GXT4 UPS has four groups of outlets: two groups are not
                       controlled (always On), and two groups may be controlled with either programmed responses or over
                       an SNMP network.
                       Verify that the equipment is plugged into the appropriate outlets if any outlets will be controlled with
                       these features.
                       1. Plug equipment into the appropriate output receptacles on the rear of the Liebert GXT4.
                                 NOTE
                                 1. Do not overload any output receptacle.
                                 2. Output cable length should not exceed 10m (32.8 ft).
                       2. Plug the input receptacle of the Liebert GXT4 into the input power connection.
                       3. Install the two cable strain relief fixtures to secure either the input or output cables to prevent
                          accidental disconnection.
                          a. Insert one end into the provided holes on the rear of the unit.
                          b. Place the power cord(s) inside the loop.
                          c. Tighten the loop around the cables.
Liebert® GXT4™ 14
                                                                                                                  Liebert
                                                                                                                  GXT4
                                                                                                                  External
                                                                                                                  Battery
                                                                                                                  Cabinet
             2.6.2     Installing the Optional Liebert IntelliSlot® Card and Communication Cables
                       1. Remove the protective cover of the Liebert IntelliSlot port on the Liebert GXT4 and set it aside.
                       2. Insert the Liebert IntelliSlot card into the Liebert IntelliSlot port and secure it with screws.
                       3. To connect any cable associated with a Liebert IntelliSlot card, refer to the user manual provided
                          with the card.
                       To configure and use the Liebert IntelliSlot communication card, refer to the card’s user manual.
                       Manuals for the various Liebert IntelliSlot cards are available at Liebert’s Web site:
                       www.liebert.com
15 Liebert® GXT4™
Liebert® GXT4™ 16
             3.3       LCD
                       The LCD panel shows the UPS status and enables changes to the UPS settings by assisting in
                       navigating through the Liebert GXT4’s menu (see 3.4 - Menu Structure).
17 Liebert® GXT4™
                                                                                                          Audible Alarm
                                                              Output
                                                                                                          Startup on Bypass
                                                                Load
                                                                                                          Battery Cabinets
                                                    Turn UPS            Turn UPS On
                                                     On/Off             Turn UPS Off                      Low Battery Time Warning
                                                                                               BATT
                                                                                                                          Turn On
                                                                                               Outlet 1
                                   About       PN/SN/Firmware Version                                       Control       Turn Off
                                                                                                                          Reboot
                                                                                                                          1 English
                                                                                                          Language
                                                                                                                          2 French
                                                                                               LCD
Color
Liebert® GXT4™ 18
                                                               EMERSON
                                                             Network Power
                       After about 10 seconds, the LCD shows one of the On screens in Figure 17; the screen shown depends
                       on whether input power is available.
                                                                           AC NOT AVAILABLE
                                              TURN ON UPS                  START ON BATTERY?
                                                YES NO                             YES NO
                                       O/P: 0V       HZ 0.0A               O/P: 0V 0HZ 0.0A
                                       I/P : 120 V 60HZ 0.0A               I/P : 120V 60HZ 0.0A
                                       BATT: 100 % 320 MINS                BATT: 100% 320MINS
                                       LOAD: 0%                            LOAD: 0%
                                           Input Power is Available         Input Power is not Available
                       To turn On the UPS, press either the Up or Down button to select YES and press the Enter button.
                       The UPS will start up, the LCD will display UPS STARTING and then START SUCCESSFUL after
                       the UPS is turned On, as shown in Figure 18.
19 Liebert® GXT4™
                       In the default screen, the LCD shows the UPS model, output parameters, input parameters, battery
                       capacity with run time estimate and load percentage. The UPS operation mode (online /inverter,
                       ECO, Battery or Bypass) will be indicated by the LED indicators.
                       If no control button (ESC, Up, Down, Enter) is pressed for 2 minutes, the LCD will enter the screen
                       saver mode (backlight turns off). It will remain off until a control button is pressed.
                                                            1    STATUS
                                                            2    CONFIGURATION
                                                            3    CONTROL
                                                            4    LOG
                                                            5    ABOUT
                                                            6    NETWORK
                       To select a submenu, press the Up or Down button to move the cursor to the required item, then press
                       the Enter button to enter its submenu or set its parameter.
Liebert® GXT4™ 20
                       STATUS Screen
                       In the MAIN MENU screen, select STATUS to enter the Status Screen, displaying OUTPUT, LOAD,
                       INPUT, BATTERY and TIME SINCE STARTUP, as shown in Figure 21.
                                        BATTERY
                                                                            TIME SINCE STARTUP
                                        CAPACITY :               90%
                                        RUNTIME :           100 MINS         05D     15H     30M
                                        VOLTAGE :                80V
                       CONFIGURATION Screen
                       Select MAIN MENU > CONFIGURATION to enter the Configuration menu. This menu has seven
                       submenus, as shown in Figure 22.
                                                           1.   UPS
                                                           2.   BATTERY
                                                           3.   ECO MODE
                                                           4.   OUTLET 1
                                                           5.   OUTLET2
                                                           6.   LCD
                                                           7.   FACTORY DEFAULT
                       In the CONFIGURATION screen, press the Up or Down button to move the cursor to the required
                       item, then press the Enter button to enter a submenu or set its parameters.
21 Liebert® GXT4™
                       UPS Screen
                       Select MAIN MENU > CONFIGURATION > UPS to enter the UPS screen. This menu has six
                       screens, as shown in Figure 23.
OFF NO NO
                       Press the Up or Down button to move the cursor to the required item, and press the Enter button to
                       confirm the settings.
                       Battery Screen
                       Select MAIN MENU > CONFIGURATION > BATTERY to enter the BATTERY screen. This menu
                       has four screens, as shown in Figure 24.
0 CABINETS 2 MINS
8 WEEKS 2014 Y 1M 1D
                       Press the Up or Down button to increase or decrease the value of the settings, and press the Enter
                       button to confirm it.
Liebert® GXT4™ 22
ON 10%
3 Hz 5 MINS
                       Press the Up or Down button to move the cursor to the required item, and press the Enter button to
                       confirm the settings.
                       Outlet1 Screen
                       Select MAIN MENU > 2 CONFIGURATION > 4 OUTLET1 to enter the OUTLET1 screen. This menu
                       has two submenus, as shown in Figure 26.
OUTLET1
                                                            1 OUTLET CONTROL
                                                            2 OUTLET SETTING
23 Liebert® GXT4™
                       Select 1 OUTLET CONTROL and press the Enter button to enter the OUTLET CONTROL screen, as
                       shown in Figure 27.
                       Press the Up or Down button to move the cursor to the required item, and press the Enter button to
                       confirm the settings.
                       Select 2 Outlet Setting and press the Enter button to enter the OUTLET SETTING screen, as shown
                       in Figure 28.
                       Press the Up or Down button to move the cursor to the required item, and press the Enter button to
                       confirm the settings.
Liebert® GXT4™ 24
                       Outlet2 Screen
                       The Outlet2 screens are the same as the Outlet1 screens. The same settings are available as on the
                       Outlet1 screen. If the Outlet2 group will have the same settings as the Outlet1 group, the Liebert
                       GXT4 offers a programming shortcut, as shown in Figure 29. When configuring the Outlet2 group,
                       the select YES and press the Enter button to apply the Outlet1 settings to the Outlet2 screen.
YES NO
                       LCD screen
                       Select Main Menu -> 2 CONFIGURATION -> 6 LCD to enter the LCD screen. This menu has two
                       submenus, LANGUAGE and COLOR, as shown in Figure 30.
                                                           1 LANGUAGE
                                                           2 COLOR
                       Select 1 LANGUAGE and press the Enter button to enter the LANGUAGE screen, as shown in
                       Figure 31.
                       The Liebert GXT4 is capable of supporting multiple languages. For the list of supported languages
                       and instructions on how to upload them, refer to the Configuration Program user manual on the
                       included CD.
                                                           1 English
                                                           2
25 Liebert® GXT4™
Select ‘2 COLOR’ and press the Enter button to enter the COLOR screen, as shown in Figure 32.
                                                              EMERSON
                                                              EMERSON
                                                              EMERSON
                                                              EMERSON
                       Control Screen
                       Select MAIN MENU -> 3 CONTROL to enter the CONTROL screen. This screen has three
                       submenus, TURN ON & OFF, ALARM CONTROL and BATT TEST, as shown in Figure 34.
                       In the CONTROL screen, press the Up or Down button to move the cursor to the required item, and
                       press the Enter button to enter its submenu.
Liebert® GXT4™ 26
                                                           1 AUDIBLE ALARM ON
                                                           2 AUDIBLE ALARM OFF
                                                              1 START
                                                              2 CANCEL
                                                              3 BATT TEST RESULT
27 Liebert® GXT4™
                       Log Screen
                       Select MAIN MENU -> 4 LOG to enter the LOG screen. This screen has two submenus, VIEW LOG
                       and CLEAR LOG, as shown in Figure 38.
                                                                                    254 /255
                                  1 VIEW LOG                              255 OD 1H 17m AGO
                                  2 CLEAR LOG                             UPS switch to Online
                                                                          mode
                                                            DO YOU WANT TO
                                                           CLEAR EVENT LOGS?
YES NO
                       Press the Up or Down button to move the cursor to the required item. Press the Enter button to
                       confirm the settings.
                       ABOUT Screen
                       Select MAIN MENU> ABOUT to enter the ABOUT screen, as shown in Figure 40. The ABOUT
                       screen displays UPS model, serial number, software version and hardware version.
SN:1XXX60XXX1AFCXX
                                                           FW VER: U100D100
                                                           HW VER: H100
Liebert® GXT4™ 28
                       Network
                       Select MAIN MENU>NETWORK to enter the NETWORK screen.
                       The NETWORK screen displays the MAC address and the IPv4 IP address. If the Liebert GXT4 is
                       fitted with an optional Liebert IntelliSlot® Web card (Liebert IS-WEBCARD), the screen will display
                       IPv6 IP address settings (IPv6 requires configuration), as shown in Figure 41.
29 Liebert® GXT4™
Liebert® GXT4™ 30
                       If a fault occurs, the UPS automatically switches to Bypass Mode. The original operating mode will be
                       maintained only in the case of a battery disconnection fault. The fault message alternates with UPS
                       Mode once a second, the red fault indicator on the operation and display panel lights up and the alarm
                       sounds continuously.
                       If a fault occurs:
                       1. Enter the ALARM CONTROL screen (see Figure 36), and select AUDIBLE ALARM ON or
                          AUDIBLE ALARM OFF to switch the alarm On or Off.
                       2. Enter the EVENT LOG screen (see Figure 38), and select VIEW LOG to view the entire Event
                          log.
                                 NOTE
                                 There will be a short delay before the EVENT LOG screen displays the historical fault log to
                                 allow the log to load.
31 Liebert® GXT4™
             4.0       OPERATION
                       This section describes checks to be made before starting the UPS, how to start the UPS, manual
                       battery test, manual bypass, shutting down the UPS and disconnecting mains power from the UPS.
                                 NOTE
                                 The Liebert GXT4’s battery has been fully charged before delivery, but some charge will be lost
                                 during storage and shipping. To ensure that the battery has adequate reserve power to protect
                                 the connected load, charge the battery for three hours before putting the UPS into service.
Liebert® GXT4™ 32
33 Liebert® GXT4™
             5.0       COMMUNICATION
                       This section describes the four types of communication ports on the rear of the UPS:
                         •   Liebert IntelliSlot® port
                         •   USB port (standard B-type)
                         •   Terminal Block Communication
                         •   RS232 port (DB9F)
                         ! CAUTION
                           To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables
                                 should be segregated and run separate from all other power cables.
Liebert® GXT4™ 34
                                 NOTICE
                                 The output voltage settings cannot be changed while the UPS is On and powering connected
                                 loads.
                                 NOTE
                                 • Setting the output voltage of the Liebert GXT4-500RT120, GXT4-700RT120, and
                                   GXT4-1000RT120 models to 110VAC automatically derates both the VA and Watt ratings to
                                   95% of the unit’s rating.
                                 • Setting the output voltage of the Liebert GXT4-1500RT120 and GXT4-2000RT120 models to
                                   110VAC automatically derates both the VA and Watt ratings to 85% of the unit’s ratings,
                                   and programming the output voltage to 115VAC automatically derates both the VA and
                                   Watt ratings to 95% of the unit’s rating.
                                 • Setting the output voltage of the Liebert GXT4-3000RT120 model to 110VAC automatically
                                   derates both the VA and Watt ratings to 90% of the unit’s ratings (refer to 9.0 -
                                   Specifications for the VA and Watt ratings).
                                 NOTE
                                 • This program is compatible with UPS models beginning with ‘GXT4,’ as in
                                   ‘GXT4-3000RT230.’ It is not compatible with earlier versions of the Liebert GXT UPS.
                                 • A computer running Microsoft® Windows 2000®, Windows XP®, Windows Vista®,
                                   Windows 7 or Windows 8 is required to set up and run the configuration program.
35 Liebert® GXT4™
                                                           1     Any Mode
                                                           2     Shutdown
                                                           3     Battery Mode
                                                           4     Shutdown
                                                           5
                                                                 On Battery Mode
                                                           6
                                                           7
                                                                 Low Battery
                                                           8
                                 NOTE
                                 Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown,
                                 depending on the settings in the configuration program.
                                 A current-limited source for this optocoupler (+12VDC, 50mA) will be available from the UPS.
                                 The connection to the UPS for remote connection will be via terminal block connector.
                                 Any Mode Shutdown wiring must conform to all national, regional and local wiring
                                 regulations.
                         ! WARNING
                           When the Auto-Enable output option is selected and the UPS output is disabled using Pin 1
                                 and Pin 2, the Liebert GXT4’s output can turn On automatically and without warning if the
                                 Pin 1 and Pin 2 connection is changed.
Liebert® GXT4™ 36
                                 NOTE
                                 Remote Power Off will be performed by NO contact.
                                 A current-limited source (+12VDC, 50mA) will be available from UPS.
                                 The connection to the Liebert GXT4 for remote connection will be via terminal block connector.
                                 Battery Mode Shutdown wiring must conform to all national, regional and local wiring codes
                                 and laws.
                                 This signal must last for 1.5 seconds or longer.
                                 A battery shutdown signal will not cause an immediate shutdown. It will start a 2-minute
                                 shutdown timer. This timer cannot be stopped once triggered. If the mains power returns
                                 during this countdown, the Liebert GXT4 will still shut down and must remain shut down for
                                 10 seconds. Whether the UPS turns back On when the power is restored depends on the
                                 auto-restart setting.
             5.4.3     On Battery
                       On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power
                       from the battery this dry contact will be closed.
                                 NOTE
                                 The rated values for the dry contacts for the On Battery and Low Battery signals are:
                                 • Rated Voltage: 30V (AC or DC)
                                 • Rated Current: 300mA
37 Liebert® GXT4™
             6.0       MAINTENANCE
                       This section describes replacing the internal battery pack, precautions, checking the Liebert GXT4’s
                       status and checking UPS functions.
                         ! WARNING
                           The battery can present a risk of electrical shock and high short circuit current. The following
                                 precautions should be observed before replacing the battery pack:
                                 • Remove rings, watches and other metal objects.
                                 • Use tools with insulated handles.
                                 • Do not lay tools or other metal objects on the batteries.
                                 • If the battery kit is damaged in any way or shows signs of leakage, contact your local Emer-
                                   son representative immediately.
                                 • Do not dispose of batteries in a fire. The batteries may explode.
                                 • Handle, transport and recycle batteries in accordance with local regulations.
                       Read all safety cautions before proceeding. A trained user can replace the internal battery pack when
                       the UPS is always in a restricted access location (such as a rack or server closet). Contact your local
                       dealer or Emerson representative to obtain the pricing of the appropriate replacement battery pack.
                         ! CAUTION
                           Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries
                                 according to the instructions.
Liebert® GXT4™ 38
                       4. Gently pull the battery wire out and disconnect the battery plug and battery receptacle, as shown
                          in Figure 44.
             Figure 44 Disconnecting the battery plug and battery receptacle (front view)
Battery Handle
39 Liebert® GXT4™
                       6. Unpack the new internal battery pack. Take care not to destroy the packing.
                           Compare the new and old internal battery pack to make sure they are the same type and model. If
                           so, proceed with Step 7; if they are different, stop and contact your local Emerson representative,
                           or Emerson Channel Support.
                       7. Line up and slide in the new internal battery pack.
                       8. Reconnect the battery plug and battery receptacle
                       9. Push the battery wire and internal battery pack back into the UPS.
                       10. Reattach the front battery door with the six screws.
                       11. Reattach the front plastic bezel cover to the UPS.
                                 NOTE
                                 The internal battery pack is hot-swappable. However, caution should be exercised because
                                 during this procedure the load is unprotected from disturbances and power outages. Do not
                                 replace the battery while the UPS is operating in Battery Mode. This will result in a loss of
                                 output power and will drop the connected load.
             6.3       Precautions
                       Although the Liebert GXT4 has been designed and manufactured to ensure personal safety, improper
                       use can result in electrical shock or fire. To ensure safety, observe the following precautions:
                         •   Turn Off and unplug the Liebert GXT4 before cleaning it.
                         •   Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.
                         •   Never block or insert any objects into the ventilation holes or other openings of the Liebert GXT4.
                         •   Do not place the Liebert GXT4 power cord where it might be damaged.
                                 NOTE
                                 UPS function check procedures may interrupt power supply to the connected load.
                       Emerson recommends checking the UPS functions once every six months.
                       Back up the load data before conducting the UPS functions check. Procedures are as follows:
                       1. Press the Standby/Manual Bypass button to check whether the alarm and indicators are normal.
                       2. Press the On/Alarm Silence/Manual Battery Test button to check again whether the indicators
                          are On and the UPS is operating normally.
                       3. Press the On/Alarm Silence/Manual Battery Test button for three seconds after Inverter Mode;
                          the UPS should initiate battery self-test. Check to determine whether the battery is operating
                          normally. If not, stop and contact your local Emerson representative or Emerson Channel
                          Support.
Liebert® GXT4™ 40
             7.0       TROUBLESHOOTING
                       This section indicates various UPS symptoms a user may encounter and provides a troubleshooting
                       guide in the event the UPS develops a problem. Use the following information to determine whether
                       external factors caused the problem and how to remedy the situation.
                                 NOTE
                                 If the UPS encounters a fault and no correction attempt is performed within 2 minutes, the
                                 LCD backlight will flash (on 1 second and off 1 second) as an alert.
                                 Press any button to exit the alert mode. If no correction attempt is performed on the UPS, the
                                 LCD backlight will flash again until the UPS fault is corrected.
41 Liebert® GXT4™
             7.2       Troubleshooting
                       In the event of an issue with the UPS, refer to Table 12 to determine the cause and solution. If the
                       fault persists, contact Emerson® Channel Support.
             Table 12         Troubleshooting table
                   Problem                      Cause                                                 Solution
                                   UPS is short-circuited or         Ensure UPS is Off. Disconnect all loads and ensure nothing is lodged in
                                   overloaded                        output receptacles. Ensure loads are not defective or shorted internally.
              UPS fails to start                                     Check to ensure the internal battery is connected. If it is not, make the
                                   Batteries are not charged         connection and try to start the unit. If the battery is connected, leave the
                                   enough or not connected           UPS connected to input power for 24 hours to recharge batteries, then try
                                                                     to start the unit.
                                                                     UPS is operating from battery mode. Ensure UPS is securely plugged
                                   UPS is not plugged in
                                                                     into the wall receptacle.
              Battery indicator UPS input protection fuse has        UPS is operating from battery mode. Save data and close applications.
              is illuminated    blown/opened                         Replace UPS input fuse, then restart UPS.
                                                                     UPS is operating from battery mode. Save data and close applications.
                                   Mains power is out of tolerance
                                                                     Ensure mains supply voltage is within acceptable limits for UPS.
                                                                     Keep UPS plugged in continuously at least 24 hours to recharge
                                   Batteries are not fully charged
                                                                     batteries.
              UPS has
              reduced battery      UPS is overloaded                 Check load level indicator and reduce the load on the UPS.
              backup time
                                   Batteries may not be able to      Replace batteries. Contact your local dealer, Emerson representative or
                                   hold a full charge due to age     Emerson Channel Support for replacement battery kit.
                                                                     Check battery connections, completely power down and restart UPS.
              Battery indicator Battery source is not available;
                                                                     NOTE: If the battery circuit opens while the UPS is running, it will be
              is flashing.      continuous horn.
                                                                     detected when the next battery test is performed.
                                                                     The AC input powers the PFC input and serves as the bypass source. If
                               Because the voltage or
              Bypass indicator                                       the AC is present but the voltage or frequency exceeds the acceptable
                               frequency is outside acceptable
              is flashing.                                           range for safe operation with a load, the bypass will be disabled and this
                               limits, the bypass is disabled.
                                                                     indicator will flash, indicating that the bypass is unavailable.
                       When reporting a UPS issue to Emerson, include the UPS model and serial number. These are
                       located in several places for your ease of location: on the top panel (rack mount orientation); the left
                       side (tower orientation); the rear panel; on the front of the unit behind the front plastic bezel; and on
                       the LCD select Main Menu > About.
Liebert® GXT4™ 42
Isolation Breaker
Battery Connectors
                         ! WARNING
                           Do not contact the battery connectors and ground without wearing protective gloves and
                                 clothing and taking other precautions against electrical shock. The battery loop and AC input
                                 are not insulated, which may cause a dangerous voltage between the battery connectors and
                                 ground.
                                 NOTE
                                 External Battery Connectors are wired in parallel. Either connector can be connected to the
                                 UPS or to another battery cabinet.
                                 NOTE
                                 The standard battery cable delivered with the battery cabinet is 0.65m (2.13ft) long
43 Liebert® GXT4™
             9.0       SPECIFICATIONS
             Table 13       Specifications of GXT4-500RT120 - GXT4-700RT120 and GXT4-1000RT120 models
                                                                                             Product Model
                                                           GXT4-500RT120        GXT4-700RT120                    GXT4-1000RT120
                            Parameters                      (500VA/450W)        (700VA/630W)                      (1000VA/900W)
               Dimensions, D × W × H, in. (mm)
                                                                                             16.2 x 16.9 x 3.4
                                                  Unit
                                                                                             (408 x 430 x 85)
                                                                                            25.5 x 23.9 x 10.6
                                             Shipping
                                                                                            (647 x 607 x 270)
               Weight, lb (kg)
                                                  Unit                                          40 (18.2)
                                             Shipping                                           47 (21.4)
               Input AC
                             Voltage Range (typical)                        120VAC nominal; variable based on output load
                                 90% ~ 100% loading                                          90VAC/140VAC
                                  70% ~ 90% loading                                          86VAC/140VAC
                                  30% ~ 70% loading                                          77VAC/140VAC
                                     0 ~ 30% loading                                         60VAC/140VAC
                                           Frequency                                   40Hz ~ 70Hz; Auto Sensing
                                    Input Power Cord                                10 ft. attached w/ NEMA 5-15P plug
               Output AC
                                 Output Receptacles                                             5-15R × 6
                                              Voltage                         110/115/120VAC (user-configurable); ±3%
                                            Waveform                                            Sine wave
                          Utility (AC) Mode Overload               200% for 2 seconds; 150% for 50 seconds with transfer to bypass
               Battery
                                                 Type                           Valve-regulated, nonspillable, lead acid
                                     Qty × V× Rating                                         4 × 12V × 5.0Ah
                                   Battery Mfr./Part #                     YUASA/NPH5-12; CSB/ HR 1221W; CSB/GP1245
                                        Backup Time                                           See Table 17
                                                           3 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown
                                      Recharge Time
                                                                                        (Internal Batteries Only)
               Environmental Requirements
                     Operating Temperature, °F (°C)             32 to 104 (0 to 40); see Table 16 - Operating temperature parameters
                       Storage Temperature, °F (°C)                                    5ºF to 122ºF (-15ºC to 50ºC)
                                    Relative Humidity                                  0% to 95%, non-condensing
                                 Operating Elevation                    Up to 10,000 ft. (3000m) at 77ºF (25ºC) without derating
                                   Storage Elevation                                  50,000 ft. (15000m) maximum
                                                           <43dBA max @ 3ft. (1m) front and sides            < 50 dBA, at 3ft. (1m) rear
                                        Audible Noise
                                                               <46dBA max @ 3ft. (1m) rear              < 45 dBA, at 3ft. (1m) front and sides
               Agency
                                                Safety                                     UL 1778, cUL Listed
                                              RFI/EMI                                         FCC Class A
                                      Surge Immunity                                       IEC 62040-2 2nd Ed
                                       Transportation                                      ISTA Procedure 1A
Liebert® GXT4™ 44
45 Liebert® GXT4™
Liebert® GXT4™ 46
47 Liebert® GXT4™
Liebert® GXT4™ 48
49 Liebert® GXT4™