B12-B22-Bus Section - R0
B12-B22-Bus Section - R0
PH11-8G-238-33-C001
66/11kV POLICE TRAINING INSTITUTE SUBSTATION Rev. No. A
66kV CT / VT SIZING CALCULATION Date 30-Aug-15
INPUTS
System data
Bay Number B12-B22
Feeder details Bus Section
Nominal System Voltage 66 kV
System frequency 50 Hz
Maximum fault current 31.5 kA
Over Current & Earth Fault Protection Siemens 7SJ61 1 0.05 No : 6.1 Over Current & Earth Fault Protection
Bay Control Unit Siemens 6MD6 1 0.1 Bay Control Unit
Busbar Protection Siemens 7SS522 1 0.1 No : 6.2 Busbar Protection
Ammeter ABB Fb 96 1 0.8 Ammeter
ICT ABB MT 1 2.5 Metering
Busbar Protection Siemens 7SS522 1 0.1 No : 6.3 Busbar Protection
CB
Opening time 38 m.sec
Tripping time 60 m.sec
% DC 45 %
Rated Current 1250 Amps
Transfromer Details
Capacity of the transformer 32/40 MVA
Total auxiliary loss @ full load 7 KW
Max load loss at ONAF 216 KW
% Impedance (%Z) 13.6 %
Line feeder
Cable size 2000 Sq.mm
Circuit 120 MVA
Route Length 0 km
Cable Possitive/Negative sequence 0.0128 Ohm/km
Resistance
Cable Possitive/Negative sequence 0.165 Ohm/km
Reactance
Cable zero sequence Resistance 0.08 Ohm/km
Cable zero sequence Reactance 0.046 Ohm/km
CT2 : Core-1 7SJ61 2000 1 5P20/1.0 15 7 15 Over Current & Earth Fault Protection
BCU Bay Control Unit
Ammeter
INPUTS
Length 100 mtrs Changed as per KM Specification . (earlier submission value- 120 m)
Conductor Material Copper
Conductor size 4 Sq.mm
Copper resistance 0.0056 Ohms/m
KM specification
Safty factor (K) for Differential Protection
Safty factor (K) For Over current & earh fault
Annexure Details
INDEX
REFERENCE
No : 6.1
B12-B22
2000/1 A
CLASS : 5P20/1.0
CONTRACT NO. GTC/488G/2012 Doc No. PH11-8G-238-33-C001
66/11kV POLICE TRAINING INSTITUTE SUBSTATIONRev. No. A
66kV CT / VT SIZING CALCULATION Date 30-Aug-15
Core Details
CT2 : Core-1 : B12-B22
c. Rated current IR : 1 A
d. Rated burden for 7SJ61 SR1 : 0.05 VA (Refer No : 10.1 - Page # 197 )
e. Rated burden for 6MD6 SR2 : 0.1 VA (Refer No : 10.1 - Page # 197 )
f. Rated burden for Ammeter SR3 : 0.8 VA (Refer No : 10.4 - Page # 208)
: 0.05+0.1+0.8
SR : 0.95 VA
6.1.3 Details of lead from CT to Relay
a. Size of the cable from CT to relay S = 4 Sqmm
= 2 x (0.0056 x 100)
c. Class = 5P20/1.0
d. VA Burden = 15 VA
As per technical specification, volume-3, section 3.3.8, rev-3, clause 2.1.30, page 48 of 171, CT maximum secondary
resistance shall be 3.5 ohms per 1000 turn of CT secondary winding.
RCT = 7 Ω
= 7 VA
= 0.95/1
= 0.95 Ω
6.1.5 VA Burden and Accuracy class of CT
Actual Burden Connected Sb'cal = (RI+Rrelay) * IR2
= 2.07 VA
As technical specification,volume-3 section 3.3.8, rev-3, clause 2.1.31, item no.3, minimum 15VA burden has to be
choosen, Hence,
Sb'req ≥ Sb'cal
15 VA ≥ 2.07 VA
As technical specification, volume-3, section 3.3.8, rev-2 clause 2.1.23. item no, the CT continuous VA burden is given by,
= 2.48 VA
CONTRACT NO. GTC/488G/2012 Doc No. PH11-8G-238-33-C001
66/11kV POLICE TRAINING INSTITUTE SUBSTATIONRev. No. A
66kV CT / VT SIZING CALCULATION Date 30-Aug-15
As technical specification,volume-3 section 3.3.8, rev-3, clause 2.1.31, item no.3, minimum 15VA burden has to be
choosen. Hence,
Sb'req ≥ Sb'cal
15 VA ≥ 2.48 VA
= 2.48 VA
The 5P20 class CT shall comply within composite error of ± 5% for 20 times the rated CT current flow in its winding at rated
burden
= 7 * 1^2
= 7 VA
= 20 * (15 + 7) / (2.07 + 7)
~ 49
Accuracy limit current refered to the secondary of ALF'a = Accuracy limit at actual burden * IR
CT for 5P20
= 49 * 1
~ 49 A
= 15.75
49 VA ≥ 15.75 VA
Since the accuracy limit current at actual burden is greater than the CT secondary current at max. fault level.The composite
error will be with in limit. Hence proposed CT parameter are adequate.
CONTRACT NO. GTC/488G/2012 Doc No. PH11-8G-238-33-C001
66/11kV POLICE TRAINING INSTITUTE SUBSTATIONRev. No. A
66kV CT / VT SIZING CALCULATION Date 30-Aug-15
Description 2000/1 A
Class : 5P20/1.0
Proposed Burden VA 15 VA
Rated frequency HZ : 50 Hz
INDEX
REFERENCE
No : 6.2
Busbar Protection
B12-B22
2000/1 A
CLASS : PX
CONTRACT NO. GTC/488G/2012 Doc No. PH11-8G-238-33-C001
66/11kV POLICE TRAINING INSTITUTE SUBSTATION Rev. No. A
66kV CT / VT SIZING CALCULATION Date 30-Aug-15
Core Details
b. System frequency fn : 50 Hz
a. Make : Siemens
b. Model : 7SS522
c. Rated current IR : 1 A
= 2 x (0.0056 x 100)
As per technical specification, volume-3, section 3.3.8, rev-3, clause 2.1.30, page 48 of 171, CT maximum secondary
resistance shall be 3.5 ohms per 1000 turn of CT secondary winding. Since the selected CT ratio is 2000/1, hence the
maximum secondary winding resistance shall be as follows,
= 7 Ohm
= ( 0.1 / 1 )
= 7 + 1.12 + 0.1
= 8.22 Ohm
6.2.5 Differential Cheak
Formula Used:
Where,
Vkmin = Knee point voltage
Iscc_max_ext_fault = maximum symmetrical external short-circuit current = 31500 A
Ipn = CT rated primary current = 2000 A
RCT = Winding resistance of CT = 7 ohm
R'b = Total External load Resistance
= Rlead + Rrelay = 1.12 + 0.1 = 1.22 ohm
Isn = CT rated secondary current = 1 A
Transient dimensioning factor (Ktd) = 0.5 (Refer No : 9.1 - Page # 188 )
= 7.88
CONTRACT NO. GTC/488G/2012 Doc No. PH11-8G-238-33-C001
66/11kV POLICE TRAINING INSTITUTE SUBSTATION Rev. No. A
66kV CT / VT SIZING CALCULATION Date 30-Aug-15
~ 50 V
Vk ~ 60 V
Vk ≤ (100/1.3)*(Rct+R'b)*Isn
Vkmin 60 ≤ 100/1.3*(RCT+R'b)*Isn
~ 632 V
Hence the case-1 condition is satified
where
Z = Ohmic burden on CT circuits of loads connected in series with the relay
zero ohms (since there are no loads connected in series to relay)
Rr = Resistance of protection Relay = 0.1 ohm
In = CT secondary current = 1 A
K = 20 or If/Ipn = 20
If = Maximum fault current = 31500 A
Ipn = Rated primary current = 2000 A
If/In = 31500/2000
= 15.75
2Rl = Total lead loop resistance = 1.12 ohm
RCT = Winding Resistance of CT = 7 ohm
Since If/In < 20, hence K=20 is adopted for knee point voltage calculation (Recommended by Relay Technical manual)
Vk = K*In*(RCT+2Rl+Rr+Z)
= 20 * 1 * (7 + 1.12 + 0.1 + 0)
Vk ~ 164 V
Vk ~ 197 V
CONTRACT NO. GTC/488G/2012 Doc No. PH11-8G-238-33-C001
66/11kV POLICE TRAINING INSTITUTE SUBSTATION Rev. No. A
66kV CT / VT SIZING CALCULATION Date 30-Aug-15
Conclusion:
Hence calculated knee point voltage based on Relay manufacturer is less than proposed knee point voltage.Hence the given
CT parameters are adquate.
= MAX(60, 197)
Vk ~ 197 V
As per Kahramaa technical specification, Vol-3, sec.3.3.8, Rev-3, Clause-2.1.31, Item-6, the minimum knee voltage the CT
magnetising current is given by,
where, `
= 1.21 A
From the above calculation the magnetising current of proposed CT is less than the calculated magnetizing current.
CONTRACT NO. GTC/488G/2012 Doc No. PH11-8G-238-33-C001
66/11kV POLICE TRAINING INSTITUTE SUBSTATION Rev. No. A
66kV CT / VT SIZING CALCULATION Date 30-Aug-15
Description 2000/1
Class : PX
Rated frequency Hz : 50
INDEX
REFERENCE
No : 6.3
Busbar Protection
B12-B22
2000/1 A
CLASS : PX
CONTRACT NO. GTC/488G/2012 Doc No. PH11-8G-238-33-C001
66/11kV POLICE TRAINING INSTITUTE SUBSTATION Rev. No. A
66kV CT / VT SIZING CALCULATION Date 30-Aug-15
Core Details
b. System frequency fn : 50 Hz
a. Make : Siemens
b. Model : 7SS522
c. Rated current IR : 1 A
= 2 x (0.0056 x 100)
As per technical specification, volume-3, section 3.3.8, rev-3, clause 2.1.30, page 48 of 171, CT maximum secondary
resistance shall be 3.5 ohms per 1000 turn of CT secondary winding. Since the selected CT ratio is 2000/1, hence the
maximum secondary winding resistance shall be as follows,
= 7.00 Ohm
= ( 0.1 / 1 )
= 7 + 1.12 + 0.1
= 8.22 Ohm
6.3.5 Differential Cheak
Formula Used:
Where,
Vkmin = Knee point voltage
Iscc_max_ext_fault = maximum symmetrical external short-circuit current = 31500 A
Ipn = CT rated primary current = 2000 A
RCT = Winding resistance of CT = 7 ohm
R'b = Total External load Resistance
= Rlead + Rrelay = 1.12 + 0.1 = 1.22 ohm
Isn = CT rated secondary current = 1 A
Transient dimensioning factor (Ktd) = 0.5 (Refer No : 9.1 - Page # 188 )
= 7.88
CONTRACT NO. GTC/488G/2012 Doc No. PH11-8G-238-33-C001
66/11kV POLICE TRAINING INSTITUTE SUBSTATION Rev. No. A
66kV CT / VT SIZING CALCULATION Date 30-Aug-15
~ 50 V
Vk ~ 60 V
Vk ≤ (100/1.3)*(Rct+R'b)*Isn
Vkmin 60 ≤ 100/1.3*(RCT+R'b)*Isn
~ 632 V
Hence the case-1 condition is satified
where
Z = Ohmic burden on CT circuits of loads connected in series with the relay
zero ohms (since there are no loads connected in series to relay)
Rr = Resistance of the protection Relay = 0.1 ohm
In = CT secondary current = 1 A
K = 20 or If/Ipn = 20
If = Maximum fault current = 31500 A
Ipn = Rated primary current = 2000 A
If/In = 31500/2000
= 15.75
2Rl = Total lead loop resistance = 1.12 ohm
RCT = Winding Resistance of CT = 7 ohm
Since If/In < 20, hence K=20 is adopted for knee point voltage calculation (Recommended by Relay Technical manual)
Vk = K*In*(Rct+2Rl+Rr+Z)
= 20 * 1 * (7 + 1.12 + 0.1 + 0)
Vk ~ 164 V
Vk ~ 197 V
CONTRACT NO. GTC/488G/2012 Doc No. PH11-8G-238-33-C001
66/11kV POLICE TRAINING INSTITUTE SUBSTATION Rev. No. A
66kV CT / VT SIZING CALCULATION Date 30-Aug-15
Conclusion:
Hence calculated knee point voltage based on Relay manufacturer is less than proposed knee point voltage.Hence the given
CT parameters are adquate.
= MAX(0, 197)
Vk ~ 197 V
As per Kahramaa technical specification, Vol-3, sec.3.3.8, Rev-3, Clause-2.1.31, Item-6, the minimum knee voltage the CT
magnetising current is given by,
where, `
= 1.21 A
From the above calculation the magnetising current of proposed CT is less than the calculated magnetizing current.
CONTRACT NO. GTC/488G/2012 Doc No. PH11-8G-238-33-C001
66/11kV POLICE TRAINING INSTITUTE SUBSTATION Rev. No. A
66kV CT / VT SIZING CALCULATION Date 30-Aug-15
Description 2000/1
Class : PX
Rated frequency Hz : 50
INDEX
REFERENCE
No : 1.2
Resistance of 4 Sqmm Copper Cable @ 20°C (R20) = 4.61 ohm/km (Refer No : 12.4 - Page # 253)
Resistance of 4 Sqmm Copper Cable @ 75°C (R75) = R20 (1+α (t2 - t1))
Where,
= 5.6065 ohm/km
= 0.0056 ohm/m