SpaceLogic MP-C Pro

Plant Room Controllers

EcoStruxure™ Building

• Versatile onboard I/O point mix


Introduction
• Advanced monitoring
SpaceLogic™ MP-C Pro is a multi-purpose, fully programmable,
IP based field controller. The MP-C models offer a flexible mix of • Configurable RS-485 port
I/O point types that suit a wide range of HVAC applications. MP-
• Sensor bus for living space sensors
C can either be used as a standalone BACnet/IP controller,
BACnet/SC node, or as part of an EcoStruxure BMS with a • Modbus RTU subnetwork
SpaceLogic AS-P or AS-B server or an Enterprise Server as the • Commission mobile application for commissioning of the
parent server. The MP-C models support an optional display that controller before the BMS is in place
provides insight and control of the inputs and outputs.
• Full EcoStruxure Building Operation software support,
MP-C has the following features: providing efficient engineering tools
• SpaceLogic Operator Display support
• IP enabled with dual-port Ethernet switch
• BACnet/SC node

www.se.com/buildings
SpaceLogic MP-C Pro
enable rapid identification of the location of the detected error
IP connectivity, flexible network while maintaining communication with the controllers on either
topologies, and support for side of the break.

BACnet/SC applications
The BACnet/IP controllers are based on open protocols that
BACnet/SC (Secure Connect)
simplify interoperability, IP configuration, and device support
management, and can be enabled as BACnet/SC nodes for
The BACnet/IP controllers support BACnet/SC applications as a
increased cybersecurity:
BACnet/SC node. This allows the controllers to be used in a
BACnet/SC network, which allows secure transport of BACnet
• IP addressing traffic and information between BACnet/SC devices over private
• BACnet/IP or BACnet/SC communications and public networks without the need for BBMDs, VLANs, and
VPNs, because the BACnet/SC protocol uses WebSocket
• DHCP for easy network configuration
technology and TLS 1.3 encryption. In addition, BACnet/SC uses
certificate management to help ensure only those devices
The BACnet/IP controllers have a dual-port Ethernet switch,
authorized to be on a BACnet/SC network can operate on that
which enables flexible network topologies:
network.
• Star
• Daisy chain
Models with a versatile mix of I/O
• Rapid Spanning Tree Protocol (RSTP) ring points
MP-C comes in five models with different I/O point count and a
In a star topology, the controller and the parent EcoStruxure BMS versatile mix of I/O point types that match a wide variety of
server are individually connected to an Ethernet switch. Daisy- applications. The universal inputs/outputs are highly flexible and
chain multiple controllers together to reduce installation time and can be configured as either inputs or outputs.
cost. When using a ring network topology, in the event of a
broken IP network or a non-operational controller, RSTP will

I/O Point Types by MP-C Models


I/O Point Types MP-C-15A MP-C-18A MP-C-18B MP-C-24A MP-C-36A

Universal I/O 8 10 10 16 20
Type Ub

Universal I/O - - - 4 8
Type Uc

Triac outputs 6 4 8 - -

Relay outputs - 3 - 4 8
Form A

High power relay 1 1 - - -


outputs
Form A

Configurations by I/O Point Types


Configurations Universal I/O Universal I/O Triac Outputs Relay Outputs High Power Relay
Type Ub Type Uc Form A Outputs
Form A

Digital inputs yes yes - - -

Counter inputs yes yes - - -

Supervised inputs yes yes - - -

Voltage inputs yes yes - - -


(0 to 10 VDC)

SpaceLogic MP-C Pro Life is On | Schneider Electric 2


SpaceLogic MP-C Pro
Continued
Configurations Universal I/O Universal I/O Triac Outputs Relay Outputs High Power Relay
Type Ub Type Uc Form A Outputs
Form A

Current inputs yes yes - - -


(0 to 20 mA)

Temperature inputs yes yes - - -

Resistive inputs yes yes - - -

2-wire RTD yes yes - - -


temperature inputs

Voltage outputs yes yes - - -


(0 to 10 VDC)

Current outputs - yes - - -


(0 to 20 mA)

Digital outputs - - yes yes yes

Digital pulsed outputs - - yes yes yes

PWM outputs - - yes yes yes

Tristate outputs - - yes yes -

Tristate pulsed - - yes yes -


outputs

Universal inputs/outputs Relay outputs


The universal inputs/outputs are ideal for any mix of temperature, The relay outputs support digital Form A point types. The Form A
pressure, flow, status points, and similar point types in a building relays are designed for direct load applications.
control system.
High power relay output
As counter inputs, the universal inputs/outputs are commonly MP-C-15A and MP-C-18A have a high power relay output, which
used in energy metering applications. As RTD inputs, they are is ideal for switching loads of up to 12 A, such as electrical
ideal for temperature points in a building control system. As heating elements.
supervised inputs, they are used for security applications where
it is critical to know whether or not a wire has been cut or shorted.
I/O expansion
These events provide a separate indication of alarms and events
in the system. For applications that require more I/O resources, the SpaceLogic
IP-IO modules provide a versatile mix of I/O points for any
For all analog inputs, maximum and minimum levels can be application. For more information, see the SpaceLogic IP-IO
defined to automatically detect over-range and under-range Specification Sheet.
values.
Advanced monitoring
The universal inputs/outputs can also be used as voltage outputs
or current outputs (Uc only), without the need for external bias The BACnet/IP controllers support local trends, schedules, and
resistors. Therefore, the universal inputs/outputs support a wide alarms, enabling local operation when the controller is offline or
range of devices, such as actuators. used in standalone applications.

With user-defined fallback values, the I/O module outputs will be


Triac outputs
in a predictable state in cases of network disruption.
The triac outputs can be used in many applications to switch 24
VAC on or off for external loads such as actuators, relays, or The battery-free power backup of the memory and real-time
indicators. The triac outputs are isolated from the controller. clock helps prevent data loss and allows seamless and quick
Triacs are silent and are not adversely affected by relay contact recovery after a power disruption.
wear.
All MP-C models can be equipped with the MP-C Display add-on
module, which features an LCD display and five keys. With this

SpaceLogic MP-C Pro Life is On | Schneider Electric 3


SpaceLogic MP-C Pro
module, you can manually override analog and digital outputs for
testing, commissioning, and maintenance of equipment
connected to the outputs. The module's dedicated processing
power helps to ensure reliable override for maintenance
applications. The override status can be viewed in EcoStruxure
Building Operation WorkStation and WebStation, enabling more
precise monitoring and control.

MP-C Display
SpaceLogic Sensor devices
In WorkStation, you update the firmware of multiple BACnet/IP
controllers at the same time and with minimum down time. The The sensor bus provides both power and communications for up
EcoStruxure BMS server keeps track of the installed firmware to to four sensors that are daisy-chained using standard Cat 5 (or
support backup, restore, and replacement of the controllers and higher) cables. The maximum number of sensors that can be
sensors. The server can host controllers of different firmware connected to a controller varies depending on the sensor model
versions. and the combination of cover and sensor base type:

Configurable RS-485 port • Blank covers: Up to four sensors of any combination of sensor
base types
The MP-C controller has one configurable RS-485 port, which
can be configured to support two different types of networks: • 3-button and touchscreen covers:
– Up to two sensor bases with CO2 option
• Sensor bus – Up to four sensor bases without CO2 option
• Modbus network • SpaceLogic LCD temperature sensors: Up to four sensors are
supported
Sensor bus for living space sensors
The maximum total length of the sensor bus is 61 m (200 ft). For
The BACnet/IP controllers provide an interface designed for the
more information, see the SpaceLogic Sensors - SXWS Sensors
SpaceLogic Sensor family of living space sensors. The
for MP and RP IP Controllers - Specification Sheet.
SpaceLogic Sensor devices offer an efficient way to sense the
temperature, humidity, CO2, and occupancy in a room. The
The RS-485 Power Adapter can be used to supply 24 VDC power
SpaceLogic Sensor devices are available with different
to the MP controller sensor bus so that the maximum number of
combinations of sensor types and various covers and user
sensor bases with CO2 option can be increased from two to four
interface options, such as touchscreen, setpoint and override
sensor bases. The adapter can be ordered from Schneider
buttons, and blank covers.
Electric. For more information, see section the RS-485 Adapters
Specification Sheet.

Modbus RTU subnetwork


The MP-C Modbus RTU (RS-485) subnetwork allows standard
Modbus devices to be connected to the controller.

The Modbus RTU protocol is used for the communication. The


MP controller acts as the Modbus client and the connected
devices act as servers.

SpaceLogic MP-C Pro Life is On | Schneider Electric 4


SpaceLogic MP-C Pro
For connection to Modbus devices, it is recommended to use the
non-isolated RS-485 adapter to provide screw termination. The
adapter converts an RS-485 RJ45 interface to screw terminals.
The adapter can be ordered from Schneider Electric. For more
information, see the RS-485 Adapters Specification Sheet.

To connect the adapter, it is recommended that you use a Cat 5


(or higher) UTP cable with eight conductors and RJ45
connectors. The cable should be rated for the target environment
and have a maximum length of 0.3 m (12 in.). The cable is not
included and needs to be purchased separately.

The maximum number of Modbus devices that can be


connected to an MP controller depends on the type of Modbus
device and the number of Modbus registers.

The MP controller Modbus network supports up to 20 connected


Modbus devices with the following restrictions: Commission mobile application

• Maximum of 1,000 Modbus registers per network Using the Commission mobile application, you can connect to
one or many BACnet/IP controllers. You can connect to a single
64-bit Modbus registers are supported, which can be used in BACnet/IP controller using the SpaceLogic Bluetooth Adapter
energy metering. connected to a SpaceLogic Sensor. Using a wireless access
point or a network switch, you can connect to a network of
Maximum total length of the Modbus network is 72 m (236 ft). BACnet/IP controllers on the local IP network.

The Modbus devices require a separate power supply unit. Device configuration
With the Commission mobile application, you can easily discover
Modbus device types BACnet/IP controllers on the IP network. You can change the
configuration of each controller, including the BACnet and IP
Modbus device types are pre-configured Modbus applications
network settings, location, and parent server. To save
for quick and easy Modbus device integration in EcoStruxure
engineering time, you can save common device settings and
Building Operation solutions. For information on the Modbus
then reuse them for controllers of the same model.
devices supported using Modbus device types, see the
document EcoStruxure Building - Modbus Device Integration -
Supported Device Brochure. Field deployment and I/O checkout
The Commission mobile application does not require an
EcoStruxure BMS server or a network infrastructure to be in
Commission mobile application place. You can use the mobile application to load the controller
The Commission mobile application is designed for local application directly into the local BACnet/IP controller and deploy
configuration, field deployment, and commissioning of BACnet/IP the controller. The controller application can be created offline
controllers. The mobile application reduces the commissioning using Project Configuration Tool or WorkStation. You can also
time, allows flexibility in project execution, and minimizes perform an I/O checkout to verify that the controller's I/O points
dependencies on network infrastructure. are configured, wired, and operating correctly.

The mobile application is designed for use with Android, Apple


(iOS), and Microsoft Windows 10 and Windows 11 devices. For
Full EcoStruxure Building Operation
more information, see the EcoStruxure Building Commission software support
Specification Sheet.
The power of the BACnet/IP controller is fully realized when it is
part of an EcoStruxure BMS, which provides the following
benefits:

• WorkStation/WebStation interface
• Script and Function Block programming options
• Device discovery
• Engineering efficiency

SpaceLogic MP-C Pro Life is On | Schneider Electric 5


SpaceLogic MP-C Pro
• Preconfigured BMS applications for HVAC more information, see the Project Configuration Tool specification
sheet.
WorkStation/WebStation interface
WorkStation and WebStation provide a consistent user Preconfigured BMS applications for HVAC
experience regardless of which EcoStruxure BMS server the user To improve engineering efficiency and standardize engineering
is logged on to. The user can log on to the parent EcoStruxure practices, fully designed and tested controller applications are
BMS server to engineer, commission, supervise, and monitor the available at bms-applications.schneider-electric.com for use with
BACnet/IP controller and its I/O as well as its attached the MP controllers. This library contains applications for different
SpaceLogic Sensor devices. For more information, see the MP controller models and application types, such as fan coil
WorkStation and WebStation specification sheets. units, VAV, and ceiling solutions. These preconfigured controller
applications are packages that include all software programs,
Script and Function Block programming options and for example graphics, alarms, and documentation such as
Unique to the industry, the BACnet/IP controllers have both functional specifications and I/O wiring schedules, that are
Script and Function Block programming options. This flexibility needed for your projects. The online repository can be accessed
assures that the best programming method can be selected for using common web browsers on Windows PCs as well as mobile
the application. Existing programs can easily be reused between devices running Apple iOS 11.3 (or later) and Android 6.0
the EcoStruxure BMS server and the controller. Marshmallow (or later).

Device discovery
The enhanced Device Discovery in WorkStation enables you to
easily identify BACnet/IP controllers on a BACnet network and to
associate the controllers with their parent server.

Engineering efficiency
The engineering and maintenance of BACnet/IP controllers can
be done very efficiently using the EcoStruxure Building Operation
reusability features. With these features, you can create library
items (Custom Types) for a complete controller application that
contains programs and all necessary objects such as trends,
alarms, and schedules. The controller application in the Custom
Types library is reusable across all controllers of the same
model. You can use the controller application as a base for
creating new controllers intended for similar applications. You
can then edit the controller application, and the changes are
automatically replicated to all controllers, while each controller Download page for preconfigured BMS applications
keeps its local values.

WorkStation supports both online and offline engineering of


SpaceLogic Operator Display
BACnet/IP controllers. You can make the configuration changes support
online or use database mode to make the changes offline. In SpaceLogic Operator Display is an easy HMI based on the
database mode, the changes are saved to the EcoStruxure BACnet B-OD profile. It can interface and interact with up to
Building Operation database so that you can apply the changes seven SpaceLogic BACnet/IP controllers in a small BMS without
to the controllers later. an EcoStruxure BMS server. It features a large 7-inch color touch
screen and a preloaded application. It is easy to install and use
Project Configuration Tool enables you to perform all the and does not require any programming. Built for the equipment
engineering off site, without the need for physical hardware, room, the panel-mounted SpaceLogic Operator Display offers an
which minimizes the time you need to spend on site. You can run ingress protection rating of IP65, which makes it both dust-tight
the EcoStruxure BMS servers virtually and engineer the and protected from low-pressure water jets. For more
BACnet/IP controllers before you deploy your server and information, see the SpaceLogic Operator Display Specification
controller applications to the servers and controllers on site. For Sheet.

SpaceLogic MP-C Pro Life is On | Schneider Electric 6


SpaceLogic MP-C Pro
Part Numbers for MP-C
Product Part number

MP-C-15A SXWMPC15A10001

MP-C-18A SXWMPC18A10001

MP-C-18B SXWMPC18B10001

MP-C-24A SXWMPC24A10001

MP-C-36A SXWMPC36A10001
a
MP-C-15A-BAA SXWMPC15A10A01

MP-C-18A-BAAa SXWMPC18A10A01
a
MP-C-18B-BAA SXWMPC18B10A01

MP-C-24A-BAAa SXWMPC24A10A01
a
MP-C-36A-BAA SXWMPC36A10A01

MP-C-15A-SMKb SXWMPC15A1S001
b
MP-C-18A-SMK SXWMPC18A1S001

MP-C-18B-SMKb SXWMPC18B1S001
b
MP-C-24A-SMK SXWMPC24A1S001

MP-C-36A-SMKb SXWMPC36A1S001

a) Buy American Act (BAA) compliant. MP-C-15A-BAA and MP-C-36A-BAA are also included in BAA compliant bundles that include either the MP-C-15A-BAA controller
and MP-C-BAA DISPLAY or the MP-C-36A-BAA controller and MP-C-BAA DISPLAY. The bundles can be ordered using the part number SXWMPC15AB10A01 for the
MP-C-15A-BAA bundle or SXWMPC36AB10A01 for the MP-C-36A-BAA bundle.
b) Approved for use in UL 864 smoke control systems. The smoke control (SMK) models are shipped with a validated UL 864 software version, which can differ from the
latest released software. For information on the approved software revisions for the device when used in UL 864 smoke control systems, see the Smoke Control System
Approved Software Revisions - EcoStruxure Building Management document, 01-16001-XX-en.

Part Numbers for MP-C Accessories


Product Part number

MP-C DISPLAYa SXWMPCDSP10001


(MP-C override display module)

MP-C-BAA DISPLAYb SXWMPCDSP10A01


(MP-C BAA override display module)

Spare terminal blocks for all MP-C models SXWMPCCON10001


(4 x 3-pin, 1 x 4-pin, 7 x 6-pin, 2 x 8-pin terminal blocks)

DIN-RAIL-CLIP, DIN-rail end clip SXWDINEND10001


package of 25 pieces

Non-isolated RS-485 adapterc SXWNISORS48510001


c
RS-485 power adapter SXWNISORS485P10001

SpaceLogic Bluetooth Adapterc SXWBTAECXX10001

a) Approved for use in UL 864 smoke control systems.


b) MP-C-BAA DISPLAY is included in Buy American Act (BAA) compliant bundles along with either the MP-C-15A-BAA or MP-C-36A-BAA controller. MP-C-BAA DISPLAY
can only be ordered using the part number for the MP-C-15A-BAA bundle (SXWMPC15AB10A01) or MP-C-36A-BAA bundle (SXWMPC36AB10A01). MP-C-BAA
DISPLAY does not differ from MP-C DISPLAY in terms of hardware and functionality.
c) The RS-485 adapters and the Bluetooth adapter are not available in Buy American Act (BAA) compliant variants.

SpaceLogic MP-C Pro Life is On | Schneider Electric 7


SpaceLogic MP-C Pro
For more information on part numbers for Network Connectivity
Accessories, see the Product Selection Guide - EcoStruxure
Building.

Specifications
SpaceLogic MP-C Pro

AC input

Nominal voltage 24 VAC

Operating voltage range +/- 20 %

Frequency 50/60 Hz

Maximum power consumption (MP-C-15A, -18A, -18B) 22 VA

Maximum power consumption (MP-C-24A) 28 VA

Maximum power consumption (MP-C-36A) 33 VA

Power input protection MOV suppression and internal fuse

DC input

Nominal voltage 24 to 30 VDC

Operating voltage range 21 to 33 VDC

Maximum power consumption (MP-C-15A, -18A, -18B) 12 W

Maximum power consumption (MP-C-24A) 15 W

Maximum power consumption (MP-C-36A) 18 W

Power input protection MOV suppression and internal fuse

Environment

Ambient temperature, operating 0 to 50 °C (32 to 122 °F) at normal operationa


-40 to +60 °C (-40 to +140 °F) for rooftop applications, horizontal installation onlya
a) MP-C Display has an operating temperature range of -30 to +60 °C (-22 to +140 °F).

Ambient temperature, storage -40 to +70 °C (-40 to +158 °F)

Maximum humidity 95 % RH non-condensing

Material

Plastic flame rating UL94-5V

Ingress protection rating IP 20

Mechanical

Dimensions (MP-C-15A, -18A, -18B) 153 W x 110 H x 64 D mm (6.0 W x 4.3 H x 2.5 D in.)

SpaceLogic MP-C Pro Life is On | Schneider Electric 8


SpaceLogic MP-C Pro
mm 64 (2.5)
(inches)
153 (6.0) 50 (2.0)

110 44
(4.3) (1.7)

122
(4.8)

44 (1.7)

Dimensions (MP-C-24A, -36A) 234 W x 110 H x 64 D mm (9.2 W x 4.3 H x 2.5 D in.)

mm 64 (2.5)
(inches)
234 (9.2) 50 (2.0)

110 44
(4.3) (1.7)

122
(4.8)

44 (1.7)

Weight, MP-C-15A
Including terminal blocks 0.358 kg (0.789 lb)

Weight, MP-C-18A
Including terminal blocks 0.371 kg (0.818 lb)

Weight, MP-C-18B
Including terminal blocks 0.361 kg (0.796 lb)

Weight, MP-C-24A
Including terminal blocks 0.495 kg (1.091 lb)

Weight, MP-C-36A
Including terminal blocks 0.547 kg (1.206 lb)

Recommended installation DIN rail or flat surface in a cabineta


a) It is recommended to install the device in an enclosure (cabinet), unless local regulations allow an exception.

Terminal blocks Removable

Compatibility

EcoStruxure BMS server communication


EcoStruxure Building Operation version 2.0.4 and later

SpaceLogic MP-C Pro Life is On | Schneider Electric 9


SpaceLogic MP-C Pro
Modbus RTU subnetwork support
EcoStruxure Building Operation software version 5.0.1 and later

BACnet/SC network support


EcoStruxure Building Operation version 6.0.1 and later

EcoStruxure Building Management Smoke Control Systema


EcoStruxure Building Operation For information, see the Smoke Control System Approved Software Revisions - EcoStruxure
Building Management document, 01-16001-XX-en.
a) Applies to the Smoke Control (SMK) models.

Agency compliances

Emission RCM; BS/EN 61000-6-3; BS/EN IEC 63044-5-2; FCC Part 15, Sub-part B, Class B

Immunity BS/EN 61000-6-2; BS/EN IEC 63044-5-3

Safety standards BS/EN 60730-1; BS/EN 60730-2-11; BS/EN IEC 63044-3; UL 916 C-UL US Listed

Smoke control product safetya UL 864


a) Applies to the Smoke Control (SMK) models and MP-C DISPLAY module. For specifications and information on the restrictions that apply to the SMK models and
display module when used in UL 864 smoke control systems, see the EcoStruxure Building Management - Smoke Control System Design Guide, 04-16014-XX-en.

Real-time clock

Accuracy, at 25 °C (77 °F) +/-1 minute per month

Backup time, at 25 °C (77 °F) 7 days minimum

Communication ports

Ethernet Dual 10/100BASE-TX (RJ45)

USB 1 USB 2.0 device port (mini-B)


1 USB 2.0 host port (type-A), 5 VDC, 2.5 W

RS-485 port Com A 24 VDC, 2 W, RS-485 (RJ45)


Transient voltage suppressors on communication and power signals

RS-485 transceiver characteristics

Transceiver type Failsafe


Non-isolated

External biasing None required

Total Unit Load (UL) per device Maximum 0.5 UL

Communications

BACnet BACnet/IP, port configurable, default 47808


BACnet/SC, port configurable, no default port
BTL B-AAC (BACnet Advanced Application Controller)a
a) See the BTL Product Catalog for up-to-date details on BTL listed firmware revisions on BACnet International's home page.

CPU

Frequency 500 MHz

Type ARM Cortex-A7 dual-core

DDR3 SDRAM 128 MB

NOR flash memory 32 MB

Memory backup 128 kB, FRAM, non-volatile

SpaceLogic MP-C Pro Life is On | Schneider Electric 10


SpaceLogic MP-C Pro
MP-C Display (Optional)

Removable No

Dimensions 74 W x 46 H x 24 D mm (2.9 W x 1.8 H x 0.9 D in.)


74 (2.9) 24
mm (0.9)
(inches) 36 (1.4)

17
46 (0.7)
(1.8)

Display size 36 W x 17 H mm (1.4 W x 0.7 H in.)

Display resolution 128 x 64 pixels

Display type FSTN monochrome LCD, white color transflective backlight

Power consumption max. 0.15 W (45 mA at 3.3 V)

Ambient temperature, operating -30 to +60 °C (-22 to +140 °F)

Ambient temperature, storage -40 to +70 °C (-40 to +158 °F)

Maximum humidity 95 % RH non-condensing

Weight 0.035 kg (0.077 lb)

Compliance with standards EN ISO 16484-2

Universal inputs/outputs, Ub and Uc

Channels, MP-C-15A 8 Ub, Ub1 to Ub8

Channels, MP-C-18A 10 Ub, Ub1 to Ub10

Channels, MP-C-18B 10 Ub, Ub1 to Ub10

Channels, MP-C-24A 16 Ub, Ub1 to Ub16


4 Uc, Uc1 to Uc4

Channels, MP-C-36A 20 Ub, Ub1 to Ub20


8 Uc, Uc1 to Uc8

Absolute maximum ratings -0.5 to +24 VDC

A/D converter resolution 16 bits

Universal input/output protection Transient voltage suppressor on each universal input/output

Digital inputs

Range Dry contact switch closure or open collector/open drain, 24 VDC, typical wetting current 2.4 mA

Minimum pulse width 150 ms

SpaceLogic MP-C Pro Life is On | Schneider Electric 11


SpaceLogic MP-C Pro
Counter inputs

Range Dry contact switch closure or open collector/open drain, 24 VDC, typical wetting current 2.4 mA

Minimum pulse width 20 ms

Maximum frequency 25 Hz

Supervised inputs

5 V circuit, 1 or 2 resistors
Monitored switch combinations Series only, parallel only, and series and parallel

Resistor range 1 to 10 kohm


For a 2-resistor configuration, each resistor must have the same value +/- 5 %

Voltage inputs

Range 0 to 10 VDC

Accuracy +/-(7 mV + 0.2 % of reading)

Resolution 1.0 mV

Impedance 100 kohm

Current inputs

Range 0 to 20 mA

Accuracy +/-(0.01 mA + 0.4 % of reading)

Resolution 1 μA

Impedance 47 ohm

Resistive inputs

10 ohm to 10 kohm accuracy +/-(7 + 4 x 10-3 x R) ohm


R = Resistance in ohm

10 kohm to 60 kohm accuracy +/-(4 x 10-3 x R + 7 x 10-8 x R2) ohm


R = Resistance in ohm

Temperature inputs (thermistors)

Range -50 to +150 °C (-58 to +302 °F)

Supported thermistors

Honeywell 20 kohm

Type I (Continuum) 10 kohm

Type II (I/NET) 10 kohm

Type III (Satchwell) 10 kohm

Type IV (FD) 10 kohm

Type V (FD w/ 11k shunt) Linearized 10 kohm

Satchwell D?T Linearized 10 kohm

Johnson Controls 2.2 kohm

SpaceLogic MP-C Pro Life is On | Schneider Electric 12


SpaceLogic MP-C Pro
Xenta 1.8 kohm

Balco 1 kohm

Measurement accuracy

20 kohm -50 to -30 °C: +/-1.5 °C (-58 to -22 °F: +/-2.7 °F)
-30 to 0 °C: +/-0.5 °C (-22 to +32 °F: +/-0.9 °F)
0 to 100 °C: +/-0.2 °C (32 to 212 °F: +/-0.4 °F)
100 to 150 °C: +/-0.5 °C (212 to 302 °F: +/-0.9 °F)

10 kohm, 2.2 kohm, and 1.8 kohm -50 to -30 °C: +/-0.75 °C (-58 to -22 °F: +/-1.35 °F)
-30 to +100 °C: +/-0.2 °C (-22 to +212 °F: +/-0.4 °F)
100 to 150 °C: +/-0.5 °C (212 to 302 °F: +/-0.9 °F)

Linearized 10 kohm -50 to -30 °C: +/-2.0 °C (-58 to -22 °F: +/-3.6 °F)
-30 to 0 °C: +/-0.75 °C (-22 to +32 °F: +/-1.35 °F)
0 to 100 °C: +/-0.2 °C (32 to 212 °F: +/-0.4 °F)
100 to 150 °C: +/-0.5 °C (212 to 302 °F: +/-0.9 °F)

1 kohm -50 to +150 °C: +/-1.0 °C (-58 to +302° F: +/-1.8 °F)

RTD temperature inputs

Supported RTDs Pt1000, Ni1000, and LG-Ni1000

Pt1000

Sensor range -50 to +150 °C (-58 to +302 °F)


BACnet/IP device environment Sensor range Measurement accuracy
0 to 50 °C (32 to 122 °F) -50 to +70 °C (-58 to +158 °F) +/-0.5 °C (+/-0.9 °F)
0 to 50 °C (32 to 122 °F) 70 to 150 °C (158 to 302 °F) +/-0.7 °C (+/-1.3 °F)
-40 to +60 °C (-40 to +140 °F) -50 to +150 °C (-58 to +302 °F) +/-1.0 °C (+/-1.8 °F)

Ni1000

Sensor range -50 to +150 °C (-58 to +302 °F)


BACnet/IP device environment Sensor range Measurement accuracy
0 to 50 °C (32 to 122 °F) -50 to +150 °C (-58 to +302 °F) +/-0.5 °C (+/-0.9 °F)
-40 to +60 °C (-40 to +140 °F) -50 to +150 °C (-58 to +302 °F) +/-0.5 °C (+/-0.9 °F)

LG-Ni1000

Sensor range -50 to +150 °C (-58 to +302 °F)


BACnet/IP device environment Sensor range Measurement accuracy
0 to 50 °C (32 to 122 °F) -50 to +150 °C (-58 to +302 °F) +/-0.5 °C (+/-0.9 °F)
-40 to +60 °C (-40 to +140 °F) -50 to +150 °C (-58 to +302 °F) +/-0.5 °C (+/-0.9 °F)

RTD temperature wiring

Maximum wire resistance 20 ohm/wire (40 ohm total)

Maximum wire capacitance 60 nF


The wire resistance and capacitance typically corresponds to a 200 m wire.

Voltage outputs

Range 0 to 10 VDC

SpaceLogic MP-C Pro Life is On | Schneider Electric 13


SpaceLogic MP-C Pro
Continued
Accuracy +/-60 mV

Resolution 10 mV

Minimum load resistance 5 kohm

Load range -1 to +2 mA

Current outputs (Uc only)

Range 0 to 20 mA

Accuracy +/-0.2 mA

Resolution 21 µA

Load range 0 to 650 ohm

Relay outputs, DO

Channels, MP-C-15A 0

Channels, MP-C-18A 3, DO5 to DO7

Channels, MP-C-18B 0

Channels, MP-C-24A 4, DO1 to DO4

Channels, MP-C-36A 8, DO1 to DO8

Contact rating 250 VAC/30 VDC, 2 A, Pilot Duty (C300)

Switch type Form A Relay


Single Pole Single Throw
Normally Open

Isolation contact to system ground 3000 VAC

Cycle life (Resistive load) At least 100,000 cycles

Minimum pulse width 100 ms

High power relay outputs, DO

Channels, MP-C-15A 1, DO7

Channels, MP-C-18A 1, DO8

Channels, MP-C-18B 0

Channels, MP-C-24A 0

Channels, MP-C-36A 0

Contact rating 250 VAC/24 VDC, 12 A, Pilot Duty (B300)

Switch type Form A Relay


Single Pole Single Throw
Normally Open

Isolation contact to system ground 5000 VAC

Cycle life (Resistive load) At least 100,000 cycles

Minimum pulse width 100 ms

SpaceLogic MP-C Pro Life is On | Schneider Electric 14


SpaceLogic MP-C Pro
Continued

Triac outputs, DO

Channels, MP-C-15A 6, DO1 to DO6

Channels, MP-C-18A 4, DO1 to DO4

Channels, MP-C-18B 8, DO1 to DO8

Channels, MP-C-24A 0

Channels, MP-C-36A 0

Output rating (for each triac output) Max. 0.5 A

Voltage 24 VAC +/-20 %

Commons COM1 for DO1 and DO2 (on MP-C-15A, -18A, -18B)
COM2 for DO3 and DO4 (on MP-C-15A, -18A, -18B)
COM3 for DO5 and DO6 (on MP-C-15A, -18B)
COM4 for DO7 and DO8 (on MP-C-18B only)
The common terminals can be connected to 24 VAC or to ground.

Common voltage, high side output 24 VAC

Common voltage, low side output 0 VAC (ground)

Minimum pulse width 100 ms

Triac output protection MOV and snubber across each triac output
MOV from triac COM to ground

Terminals • Individual 24 V power sources to the field must be current


limited to maximum 4 A for UL compliant installations, and
Follow proper installation wiring diagrams and instructions,
maximum 6 A in other areas.
including these instructions:
• For more information on wiring, see Hardware Reference
• All MP-C models have several RET terminals for connection of Guide.
I/O returns, so a common chassis/signal ground rail is optional
and may not be needed.

SpaceLogic MP-C Pro Life is On | Schneider Electric 15


SpaceLogic MP-C Pro

MP-C-15A

MP-C-18A

SpaceLogic MP-C Pro Life is On | Schneider Electric 16


SpaceLogic MP-C Pro

MP-C-18B

MP-C-24A

SpaceLogic MP-C Pro Life is On | Schneider Electric 17


SpaceLogic MP-C Pro

MP-C-36A

Part Numbers for SpaceLogic Sensor Devices, Sensor Bases


Product Part number

Sensor base with temperature sensor SXWSBTXXXSXX

Sensor base with temperature and humidity sensors SXWSBTHXXSXX

Sensor base with temperature and CO2 sensors SXWSBTXCXSXX

Sensor base with temperature, humidity, and CO2 sensors SXWSBTHCXSXX

Part Numbers for SpaceLogic Sensor Devices, Covers


Product Housing Part number

Blank cover Medium matte white SXWSCBXSELXX

Blank cover Optimum glass white SXWSCBXSELXW

Blank cover Optimum glass black SXWSCBXSELXB

Blank cover with occupancy sensor Medium matte white SXWSCBPSELXX

Blank cover with occupancy sensor Optimum glass white SXWSCBPSELXW

Blank cover with occupancy sensor Optimum glass black SXWSCBPSELXB

3-button cover Medium matte white SXWSC3XSELXX

3-button cover Optimum glass white SXWSC3XSELXW

3-button cover Optimum glass black SXWSC3XSELXB

3-button cover with occupancy sensor Medium matte white SXWSC3PSELXX

SpaceLogic MP-C Pro Life is On | Schneider Electric 18


SpaceLogic MP-C Pro
Continued
Product Housing Part number

3-button cover with occupancy sensor Optimum glass white SXWSC3PSELXW

3-button cover with occupancy sensor Optimum glass black SXWSC3PSELXB

Touchscreen display cover Medium matte white SXWSCDXSELXX

Touchscreen display cover Optimum glass white SXWSCDXSELXW

Touchscreen display cover Optimum glass black SXWSCDXSELXB

Touchscreen display cover with occupancy Medium matte white SXWSCDPSELXX


sensor

Touchscreen display cover with occupancy Optimum glass white SXWSCDPSELXW


sensor

Touchscreen display cover with occupancy Optimum glass black SXWSCDPSELXB


sensor

Part Numbers for SpaceLogic Sensor Devices, Combination Models


Product Housing Part number

Complete SpaceLogic Sensor model with Medium matte white SXWSATXXXSLX


temperature sensor, buttons for override and
setpoint control, and LCD display cover

Complete SpaceLogic Sensor model with Optimum glass white SXWSATXXXSLW


temperature sensor, buttons for override and
setpoint control, and LCD display cover

Complete SpaceLogic Sensor model with Optimum glass black SXWSATXXXSLB


temperature sensor, buttons for override and
setpoint control, and LCD display cover

Complete non-communicatinga SpaceLogic Medium matte white SLASXXX


Sensor model with resistive temperature sensor
(10 kohm type 3 thermistor) and blank cover

Complete non-communicatinga SpaceLogic Optimum glass white SLAWXXX


Sensor model with resistive temperature sensor
(10 kohm type 3 thermistor) and blank cover

Complete non-communicatinga SpaceLogic Optimum glass black SLABXXX


Sensor model with resistive temperature sensor
(10 kohm type 3 thermistor) and blank cover

a) The SpaceLogic resistive temperature sensor (SLA...) is designed to be connected to I/O points/terminals on RP or MP controllers, or I/O modules. The sensor requires
an analog input (temperature input).

SpaceLogic MP-C Pro Life is On | Schneider Electric 19


SpaceLogic MP-C Pro
Regulatory Notices

Federal Communications Commission CE - Compliance to European Union (EU)


FCC Rules and Regulations CFR 47, Part 15, Class B 2014/30/EU Electromagnetic Compatibility Directive
This device complies with part 15 of the FCC Rules. Operation is subject to the following two 2014/35/EU Low Voltage Directive
conditions: (1) This device may not cause harmful interference. (2) This device must accept any 2011/65/EU Restriction of Hazardous Substances (RoHS) Directive
interference received, including interference that may cause undesired operation. 2015/863/EU amending Annex II to Directive 2011/65/EU
Industry Canada This equipment complies with the rules, of the Official Journal of the European Union, for
This Class B digital apparatus complies with Canadian ICES-003. governing the Self Declaration of the CE Marking for the European Union as specified in the
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada. above directive(s).

Regulatory Compliance Mark (RCM) - Australian Communications and Media Authority (ACMA)
This equipment complies with the requirements of the relevant ACMA standards made under the WEEE - Directive of the European Union (EU)
Radiocommunications Act 1992 and the Telecommunications Act 1997. These standards are This equipment and its packaging carry the waste of electrical and electronic equipment (WEEE)
referenced in notices made under section 182 of the Radiocommunications Act and 407 of the label, in compliance with European Union (EU) Directive 2012/19/EU, governing the disposal
Telecommunications Act. and recycling of electrical and electronic equipment in the European community.

UK Conformity Assessed UL 916 Listed products for the United States and Canada, Open Class Energy Management
S.I. 2016/1091 - Electromagnetic Compatibility Regulations 2016 Equipment. UL file E80146.
S.I. 2016/1101 - Electrical Equipment (Safety) Regulations 2016
S.I. 2012/3032 - Restriction of the Use of Certain Hazardous Substances in Electrical and
Electronic Equipment Regulations 2012
S.I. 2013/3113 - Waste Electrical and Electronic Equipment Regulations 2013 UL 864 Listed products for the United States. 10th Edition Smoke Control System. UL file S5527.
This equipment complies with the rules, of the UK regulations, for governing the UKCA Marking
for the United Kingdom specified in the above directive(s).

www.se.com/buildings

© 2024 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
03-60035-02-en March 2024