Installation Sheet PHA5815901-04 / 02-50015-01-en, April 2023 | 1
SpaceLogic™ MP-C
Controller Models
Part numbers: SXWMPC15A10001, SXWMPC18A10001, SXWMPC18B10001, SXWMPC24A10001, and SXWMPC36A10001
Safety Information
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by
Schneider Electric for any consequences arising out of the use of this material.
Carefully read these instructions and all information relevant for this product before trying to install it. See the list of technical literature.
Technical Literature
• SpaceLogic and EasyLogic - Hardware Reference Guide, 04-XX001-XX-en
The technical literature and declarations of conformity can be accessed on the Schneider Electric extranet, ecoxpert.se.com. Contact your
local Schneider Electric sales office for a hard copy of the documentation or for additional information.
Dimensions
mm 234 (9.2) 64 (2.5)
(inches)
153 (6.0) 50 (2.0)
110 MP-C-15A, -18A, -18B MP-C-24A, -36A
44
(4.3) (1.7)
122
(4.8)
44 (1.7)
Installation Orientation Restrictions Installing the Device on a DIN Rail
Normal operation, 0 to 50 °C (32 to 122 °F):
NOTICE
CONTROLLER DAMAGE
Use the DIN rail end clip when you install the controller on a
vertical DIN rail.
Failure to follow these instructions can result in equipment
damage.
Rooftop application, -40 to +60 °C (-40 to +140 °F):
2
PHA5815901-04 / 02-50015-01-en, April 2023 | 2
Installing the Device on a Flat Surface
110 (4.3)
72 (2.8)
A, B mm (inches) A B
Drill
Template 5 (0.2)
Scale 1:1
Wall Anchor (3x)
(Optional)
86
(3.4) No. 8 or M4 (4 mm)
Pan Head Self-tapping
Screw (3x)
1 inch = 25.4 mm
Important:
When printing this Model Types
template on paper, use
the scale marks above A MP-C-15A, -18A, -18B
to verify the template
is printed correctly.
B MP-C-24A, -36A
A B
Connections
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Disconnect all line voltage connected to the controller and its relay outputs before working on the device.
• More than one disconnect switch may be required to de-energize this equipment before servicing.
• Connect only devices with safe extra low voltage equipment (SELV/PELV) inputs/outputs to the controller universal inputs/outputs.
Failure to follow these instructions will result in death or serious injury.
NOTICE
CONTROLLER DAMAGE
Before powering up MP-C, ensure that the input power polarity is correct, the voltage level meets the specifications of the controller, and
the terminal blocks are plugged into the correct connector headers on the controller.
Failure to follow these instructions can result in equipment damage.
Torque: 0.56 (5 lbf.in)
MP-C-15A
B
NOTE: Do not push the terminal
block straight down into the header,
as this may crack the header.
Click!
PHA5815901-04 / 02-50015-01-en, April 2023 | 3
Connections, continued
MP-C-18A
B
MP-C-18B
B
MP-C-24A
MP-C-36A
D C Maximum bus lengths:
Sensor bus: 61 m (200 ft) C
Modbus: 72 m (236 ft)
Ethernet / Sensor bus:
D
Use Cat 5 (or higher)
UTP cable, 22 to 26 AWG.
E
Modbus: Use STP cable,
E
22 to 24 AWG.
Use a cable rated for the
The USB cable must not exceed 3 m (10 ft). target environment.
PHA5815901-04 / 02-50015-01-en, April 2023 | 4
Wiring
Recommended screw tightening torque: 0.56 Nm (5 lbf.in)
For information on wiring, see the SpaceLogic and EasyLogic - Hardware Reference Guide.
Part Numbers
Product Part number
MP-C-15A SXWMPC15A10001
MP-C-18A SXWMPC18A10001
MP-C-18B SXWMPC18B10001
MP-C-24A SXWMPC24A10001
MP-C-36A SXWMPC36A10001
MP-C DISPLAY SXWMPCDSP10001
(MP-C override display module)
Spare terminal blocks for all MP-C models SXWMPCCON10001
DIN-rail end clip, 25 pieces SXWDINEND10001
Non-isolated RS-485 adapter (cable not included) SXWNISORS48510001
RS-485 power adapter (cable not included) SXWNISORS485P10001
Specifications
AC input Operation environment Uc – Universal I/O
Nominal voltage Ambient temperature, operating Input rating
24 VAC 50/60 Hz 0 to 50 °C (32 to 122 °F) at normal operation 24 VDC , 2.4 mA
Power consumption -40 to +60 °C (-40 to +140 °F) for rooftop Voltage output rating
MP-C-15A, -18A, -18B: 22 VA applications, horizontal installation only 0 to 10 VDC , 5 kohm (min.)
MP-C-24A: 28 VA See section Installation Orientation Current output rating
MP-C-36A: 33 VA Restrictions. 0 to 20 mA, 650 ohm (max.)
MP-C Display temperature range: -30 to +60 Channels
DC input °C (-22 to +140 °F) MP-C-15A: 0; -18A: 0; -18B: 0;
Nominal voltage Humidity -24A: 4; -36A: 8
24 to 30 VDC Maximum 95 % RH non-condensing
Power consumption DO – Relay outputs
MP-C-15A, -18A, -18B: 12 W Mechanical Relay contact rating
MP-C-24A: 15 W Ingress protection rating 250 VAC / 30 VDC ,2A
MP-C-36A: 18 W IP 20 Pilot Duty (C300)
Plastic flame rating Channels
Port types UL94-5VB MP-C-15A: 0; -18A: 3; -18B: 0;
USB device port -24A: 4; -36A: 8
Mini-B IP networking
USB host port IP address assignment methods DO – High power relay outputs
Type-A Static, DHCP (default), Auto-IP (address Relay contact rating
Ethernet port 1 and 2 range 169.254.0.1 to 169.254.255.254, 250 VAC / 24 VDC , 12 A
10/100BASE-TX RJ45 subnet mask 255.255.0.0) Pilot Duty (B300)
RS-485 port Com A Channels
24 VDC, 2 W, RS-485 (RJ45) Ub – Universal I/O MP-C-15A: 1; -18A: 1; -18B: 0;
Input rating -24A: 0; -36A: 0
24 VDC , 2.4 mA
Voltage output rating DO – Triac outputs
0 to 10 VDC , 5 kohm (min.) Triac rating
Channels Max. 30 VAC , 0.5 A
MP-C-15A: 8; -18A: 10; -18B: 10; Channels
-24A: 16; -36A: 20 MP-C-15A: 6; -18A: 4; -18B: 8;
-24A: 0; -36A: 0
Addendum - California Proposition 65 Warning Statement for California Residents
WARNING: This product can expose you to chemicals including lead which is known to the State of California
to cause cancer and which is known to the State of California to cause birth defects or other reproductive harm.
For more information go to www.P65Warnings.ca.gov
© 2023 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
www.se.com/buildings