Installation Sheet 02-40058-02-en, March 2022 | 1

SpaceLogic™ RP-C 230 V


Controller Models
Part numbers: SXWRCF16A10003 and SXWRCF16B10002
Regulatory Compliance and Safety Information
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by
Schneider Electric for any consequences arising out of the use of this material.
Carefully read these instructions and all information relevant for this product before trying to install it. See the list of technical literature.
The technical literature and declarations of conformity can be accessed on the Schneider Electric Exchange website, ecobuilding.schneider-
electric.com. Contact your local Schneider Electric sales office for a hard copy of the documentation or for additional information.
Technical Literature
• SpaceLogic Hardware Reference Guide, 04-XX001-XX-en
Recommended Installation Location
The controller is intended for fan coil, ceiling systems, and other applications. The controller is typically installed next to or inside the fan coil
equipment. The controller can be equipped with optional covers to reduce access to the screw terminals and wires.
Dimensions

Installation Orientation Restrictions Installing the Device on a DIN Rail

NOTICE
CONTROLLER DAMAGE
Use the DIN rail end clip when you install the controller on a
vertical DIN rail.
Failure to follow these instructions can result in equipment
damage.
02-40058-02-en, March 2022 | 2

Installing the Device on a Flat Surface

Installing and Removing the Optional Covers

Connections

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Disconnect all line voltage connected to the controller and its relay outputs before working on the device.
• More than one disconnect switch may be required to de-energize this equipment before servicing.
• Connect only devices with safe extra low voltage equipment (SELV/PELV) inputs/outputs to the controller universal inputs/outputs.
Failure to follow these instructions will result in death or serious injury.
02-40058-02-en, March 2022 | 3

Connections, continued

WARNING
HAZARD OF ELECTRIC SHOCK
For RP-C-16A-F-230V hardware version 9 and earlier, do not connect signal ground (RET terminals, USB shield, Ethernet network shield, or
antenna shield) between RP-C controllers without connecting at least one of the RET terminals to protective earth ground.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

NOTICE
EQUIPMENT DAMAGE
Do not connect signal ground (RET terminals, USB shield, Ethernet network shield, or antenna shield) between RP-C controllers.
Failure to follow these instructions can result in equipment damage.

NOTICE
CONTROLLER DAMAGE
Before powering up the controller, ensure that the input power voltage level meets the specifications of the controller.
Failure to follow these instructions can result in equipment damage.

Wiring
Recommended screw tightening torque: 0.56 to 0.79 Nm (5 to 7 lbf.in)
For information on wiring, including connection diagrams, rating of and location of fuses (circuit breakers), and cable specifications, see the
SpaceLogic Hardware Reference Guide.
02-40058-02-en, March 2022 | 4

Part Numbers
Product Part number

RP-C-16A-F-230V SXWRCF16A10003

RP-C-16B-F-230V SXWRCF16B10002

Optional covers SXWRPCCOV10001

DIN-rail end clip, 25 pieces SXWDINEND10001

Isolated RS-485 adapter (cable not included) SXWISORS48510001

Non-isolated RS-485 adapter (cable not included) SXWNISORS48510001

RS-485 power adapter (cable not included) SXWNISORS485P10001

For more information on the RS-485 adapters and the cable required, see the Isolated and Non-isolated RS-485 Adapter Installation Sheet.

Specifications
AC input Antenna Channels
Nominal voltage Integrated antenna 8
230 VAC 50/60 Hz Approved external antenna (optional)
Maximum power consumption Manufacturer: Linx Technologies, Model: DO – Relay outputs
65 VA ANT-2.4-WRT-MON-SMA, Gain: 0.8 dBi, Relay contact rating
Power consumption without load Type: Monopole, Impedance: 50 ohm, Pilot Duty (C300)
5W Connector: SMA Min. current: 100 mA (5 VDC)
Overvoltage category Resistive: 250 VAC / 30 VDC ,
III Operation environment 4 A (cos phi = 1)
Pollution degree Ambient temperature, operating Inductive: 250 VAC / 30 VDC ,
2 0 to 50 °C (32 to 122 °F) 4 A (cos phi = 0.4)
See section Installation Orientation Channels
AC output Restrictions. 3
Type Humidity
Isolated Class 2 output Maximum 95 % RH non-condensing DO – High power relay outputs
Nominal voltage Relay contact rating
24 VAC 50/60 Hz Mechanical Pilot Duty (B300)
Power rating Ingress protection rating Normally Open, resistive: 250 VAC
19 VA IP 20 / 24 VDC , 12 A (cos phi = 1)
Plastic flame rating Normally Closed, inductive: 250 VAC
Port types UL94-5VB / 24 VDC , 3 A (cos phi = 0.4)
USB device port Channels
Mini-B IP networking 1
USB host port IP address assignment methods
Type-A, 5 VDC, 0.5 A Static, DHCP (default), Auto-IP (address DO – Solid-state relay outputs
Ethernet port 1 and 2 range 169.254.0.1 to 169.254.255.254, Output rating
10/100BASE-TX RJ45 subnet mask 255.255.0.0) 30 VAC / 30 VDC ,2A
RS-485 port Com A and Com B Max. 4 A total load
Ub – Universal I/O Channels
24 VDC, 3 W, RS-485 (RJ45) Input rating 4
Wireless connectivity 24 VDC , 2.4 mA
Bluetooth® Low Energy (Bluetooth® 5) Voltage output rating
2.402 to 2.480 GHz, max. 10 dBm output 0 to 10 VDC , 2.4 kohm (min.)
power, 100 m (328 ft) line-of-sight range
Differences from Previous Hardware Versions
For information on differences from previous versions, see the SpaceLogic Hardware Reference Guide.
eu.bac Approved Controller Applications
A eu.bac approved controller application must operate in the controller to maintain compliance with the eu.bac certification. Approved
controller applications can be downloaded from the Schneider Electric BMS Applications website, bms-applications.schneider-electric.com.

© 2022 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.