2.2kw Inverter
2.2kw Inverter
Contents
1 SAFETY INSTRUCTIONS
2 INTRODUCTION
2.1 Features
2.2 Basic System Architecture
2.3 Product Overview
3 INSTALLATION
3.1 Unpacking and Inspection
3.2 Preparation
3.3 Mounting the Unit
3.4 Battery Connection
3.5 AC Input/Output Connection
3.6 PV Connection
3.7 Final Assembly
3.8 Communication Connection
4 OPERATION
4.1 Power ON/OFF
4.2 Operation and Display Panel
4.3 LCD Display Icons
4.4 LCD Setting
4.5 Display Setting
4.6 Operating Mode Description
4.7 Battery Equalization Description
4.8 Fault Reference Code
4.9 Warning Indicator
5 SPECIFICATIONS
6 TROUBLE SHOOTING
6.1 Warning code 02 is displayed in the LCD
6.2 Unit shuts down automatically during startup process
6.3 No response after power on
6.4 Mains exist but the unit works in battery mode
6.5 Buzzer beeps continuously and red LED is on
7 APPROXIMATE BACK-UP TIME TABLE
SAFETY INSTRUCTIONS
This chapter contains important safety and operating instructions. Read and keep
this manual for future reference.
1. Before using the unit, read all instructions and cautionary markings on the unit, the
batteries and all appropriate sections of this manual.
2.
To reduce risk of injury, charge only deep-cycle lead acid type rechargeable
batteries.
Other types of batteries may burst, causing personal injury and damage.
3.
Do not disassemble the unit. Take it to a qualified service center when service or
repair is required.
Incorrect re-assembly may result in a risk of electric shock or fire.
4. To reduce risk of electric shock, disconnect all wirings before attempting any
maintenance or cleaning. Turning off the unit will not reduce this risk.
5.
Only qualified personnel can install this device with battery.
7. For optimum operation of this inverter/charger, please follow required spec to select
appropriate cable size. It's very important to correctly operate this inverter/charger.
8. Be very cautious when working with metal tools on or around batteries. A potential
risk exists to drop a tool to spark or short circuit batteries or other electrical parts and
could cause an explosion.
10. One piece of 150A fuse is provided as over-current protection for the battery supply.
12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains
when DC input short circuits.
13.
Only qualified service persons are able to service this device. If errors still persist
after following troubleshooting table, please send this inverter/charger back to local
dealer or service center for maintenance.
INTRODUCTION
Features
The following illustration shows basic application for this inverter/charger (See Figure
1). It also includes following devices to have a complete running system:
Generator or Utility.
PV modules
Consult with your system integrator for other possible system architectures depending
on your requirements.
This inverter can power all kinds of appliances in home or office environment, including
motor-type appliances such as tube light, fan, refrigerator and air conditioner.
Product Overview
1. LCD display
2. Status indicator
3. Charging indicator
4. Fault indicator
5. Function buttons
7. AC input
8. AC output
9. PV input
INSTALLATION
Before installation, please inspect the unit. Be sure that nothing inside the package is
damaged. You should have received the following items inside of package:
The unit x 1
User manual x 1
Communication cable x 2
Software CD x 1
Preparation
Before connecting all wirings, please take off bottom cover by removing the screws
(2pcs for 1.2KW/2.2KW, 4pcs for 3.2KW) as shown above.
Install this inverter at eye level in order to allow the LCD display to be read at all
times.
For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the
side and approx. 50 cm above and below the unit.
The ambient temperature should be between 0°C and 55°C to ensure optimal
operation.
Be sure to keep other objects and surfaces as shown in the diagram to guarantee
sufficient heat dissipation and to have enough space for removing wires.
Install the unit by screwing two screws. It's recommended to use M4 or M5 screws.
Battery Connection
For safety operation and regulation compliance, it's requested to install a separate DC
over-current protector or disconnect device between battery and inverter. It may not be
requested to have a disconnect device in some applications, however, it's still
requested to have over-current protection installed. Please refer to typical amperage in
below table as required fuse or breaker size.
All wiring must be performed by a qualified personnel.
It's very important for system safety and efficient operation to use appropriate cable for
battery connection. To reduce risk of injury, please use the proper recommended cable
as below.
2. Suggest to put bootlace ferrules on the end of positive and negative wires with a
proper crimping tool.
3. 1.2KW model supports 12VDC system and 2.2KW model supports 24VDC system.
Connect all battery packs as below chart. It's suggested to connect at least 100Ah
capacity battery.
4. Insert the battery wires flatly into battery connectors of inverter and make sure the
bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at
both the battery and the inverter/charge is correctly connected and conductors are
tightly screwed into the battery terminals.
Recommended tool: #2 Pozi Screwdriver
1. Assemble battery ring terminal based on recommended battery cable and terminal
size.
2. Connect battery packs with 24VDC system. It's suggested to connect at least 100Ah
capacity battery.
3. Insert the ring terminal of battery cable flatly into battery connector of inverter and
make sure the bolts are tightened with torque of 5 Nm. Make sure the polarity at both
the battery and the inverter/charge is correctly connected and ring terminals are
tightly screwed to the battery terminals.
Shock Hazard
Installation must be performed with care due to high battery voltage in series.
AC Input/Output Connection
Before connecting to AC input power source, please install a separate AC breaker
between inverter and AC input power source. This will ensure the inverter can be
securely disconnected during maintenance and fully protected from over current of AC
input. The recommended spec of AC breaker is 10A for 1.2KW, 20A for 2.2KW and 32A
for 3.2KW.
There are two terminal blocks with "AC IN" and "AC OUT" markings. Please do NOT
mis-connect input and output connectors.
It's very important for system safety and efficient operation to use appropriate cable for
AC input connection. To reduce risk of injury, please use the proper recommended
cable size as below.
2. Remove insulation sleeve 10mm for 5 conductors for 3.2K model and 7mm for 3
conductors for 1.2KW/2.2KW models.
3. For 1.2KW/2.2KW models, simply connect AC utility to AC input of the inverter with a
plug.
For 3.2KW models, insert AC input wires according to polarities indicated on terminal
block and tighten the terminal screws. Be sure to connect PE protective conductor (
) first.
→ Ground (yellow-green)
L → LINE (brown or black)
N → Neutral (blue)
Be sure that AC power source is disconnected before attempting to hardwire it to
the unit.
4. Then, insert AC output wires according to polarities indicated on terminal block and
tighten terminal screws.
Be sure to connect PE protective conductor ( ) first.
→ Ground (yellow-green)
L → LINE (brown or black)
N → Neutral (blue)
Appliances such as air conditioner are required at least 2~3 minutes to restart because
it's required to have enough time to balance refrigerant gas inside of circuits. If a power
shortage occurs and recovers in a short time, it will cause damage to your connected
appliances. To prevent this kind of damage, please check manufacturer of air
conditioner if it's equipped with time-delay function before installation. Otherwise, this
inverter/charger will trig overload fault and cut off output to protect your appliance but
sometimes it still causes internal damage to the air conditioner.
PV Connection
1. Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit
voltage of inverter.
2. Open circuit Voltage (Voc) of PV modules should be higher than min. battery
voltage.
Take 300Wp PV module as an example. After considering above two parameters, the
recommended module configurations listed as below table.
2. Suggest to put bootlace ferrules on the end of positive and negative wires with a
proper crimping tool.
3. Check correct polarity of wire connection from PV modules and PV input connectors.
Then, connect positive pole (+) of connection wire to positive pole (+) of PV input
connector. Connect negative pole (-) of connection wire to negative pole (-) of PV
input connector. Screw two wires tightly in clockwise direction.
Recommended tool: 4mm blade screwdriver
Final Assembly
After connecting all wirings, please put bottom cover back by screwing the screws as
shown above.
Communication Connection
Please use supplied communication cable to connect to inverter and PC. Insert bundled
CD into a computer and follow on-screen instruction to install the monitoring software.
For the detailed software operation, please check user manual of software inside of CD.
OPERATION
Power ON/OFF
Once the unit has been properly installed and the batteries are connected well, simply
press On/Off switch (located on the button of the case) to turn on the unit.
The operation and display panel, shown in below chart, is on the front panel of the
inverter. It includes three indicators, four function keys and a LCD display, indicating the
operating status and input/output power information.
LED Indicator
LED Indicator Messages
Solid On Output is powered by utility in Line mode.
Green
Flashing Output is powered by battery or PV in battery mode.
Solid On Battery is fully charged.
Green
Flashing Battery is charging.
Solid On Fault occurs in the inverter.
Red
Flashing Warning condition occurs in the inverter.
Function Keys
Function Key Description
ESC To exit setting mode
SCROLL To go to next selection
ENTER To confirm the selection in setting mode or enter setting mode
After pressing and holding " " button for 3 seconds, the unit will enter setting mode.
Press " " button to select setting programs. And then, press " " button to confirm
the selection or " " button to exit.
Setting Programs:
Display Setting
The LCD display information will be switched in turns by pressing " " button. The
selectable information is switched as the following table in order.
Operating Mode Description
LCD
Operation mode Description
display
Charging
by utility
and PV
energy.
No
charging.
Charging
by utility
and PV
energy.
Fault mode
Note:
*Fault mode: Errors are caused by PV energy and utility can
Charging
inside circuit error or external reasons charge batteries.
by utility.
such as over temperature, output short
circuited and so on.
Charging
by PV
energy.
No
charging.
Charging
by utility
and PV
energy.
The unit will provide output
power from the mains. It will
Line Mode
also charge the battery at line
mode. Charging
by utility.
Power from
battery and
The unit will provide output PV energy.
Battery Mode power from battery and PV
power.
Power from
battery
only.
Equalization function is added into charge controller. It reverses the buildup of negative
chemical effects like stratification, a condition where acid concentration is greater at the
bottom of the battery than at the top. Equalization also helps to remove sulfate crystals
that might have built up on the plates. If left unchecked, this condition, called sulfation,
will reduce the overall capacity of the battery. Therefore, it's recommended to equalize
battery periodically.
When to Equalize
In float stage, when the setting equalization interval (battery equalization cycle) is
arrived, or equalization is active immediately, the controller will start to enter
Equalize stage.
However, in Equalize stage, when battery equalized time is expired and battery
voltage doesn't rise to battery equalization voltage point, the charge controller will
extend the battery equalized time until battery voltage achieves battery equalization
voltage. If battery voltage is still lower than battery equalization voltage when
battery equalized timeout setting is over, the charge controller will stop equalization
and return to float stage.
02 Over temperature
Warning Indicator
Warning Icon
Warning Event Audible Alarm
Code flashing
1. No beep when temperature is in high
Temperature of inverter level. 2. Beep once every 0.5 second
02
inside is high when temperature is increased to close
to over-temperature protection.
Communication error
20 between MPPT SCC None
board and main board
MPPT solar charger
board cannot match with
21 main board even None
communication is
normal.
SPECIFICATIONS
Charging Curve
TROUBLE SHOOTING
Explanation / Possible
Problem LCD/LED/Buzzer What to do
cause
No beep but it
shows warning
1. Remove the
Warning code 02 in the loads.
code 02 is LCD.
Temperature of inverter inside 2. Reduce the
displayed in Beep once every is high.
0.5 second and it operation
the LCD
shows warning environment
temperature.
code 02 in the
LCD.
Unit shuts
down LCD/LEDs and 1. Re-charge
automatically buzzer will be battery.
The battery voltage is too low
during active for 3
(<1.91V/Cell) 2. Replace
startup seconds and then
complete off. battery.
process
1. Contact repair
center for
replacing the
No response 1. The battery voltage is far fuse.
after power No indication. too low. (<1.4V/Cell)
on 2. Re-charge
2. Internal fuse tripped. battery.
3. Replace
battery.
Input voltage is
Check if AC
displayed as 0 on
breaker is tripped
the LCD and Input protector is tripped
and AC wiring is
green LED is
connected well.
flashing.
1. Check if AC
wires are too
thin and/or too
Mains exist long.
but the unit
works in 2. Check if
Green LED is Insufficient quality of AC generator (if
battery mode flashing. power. (Shore or Generator) applied) is
working well or
if input voltage
range setting is
correct. (UPS →
Appliance)
Change output
Green LED is Set "Solar First" as the priority
source priority to
flashing. of output source.
Utility first.
When the unit
is turned on,
Check if battery
internal relay LCD display and
Battery is disconnected. wires are
is switched on LEDs are flashing
connected well.
and off
repeatedly
Reduce the
Overload error. The inverter is
connected load by
overload 105% and time is
switching off some
up.
equipment.
1. Reduce the
Output abnormal (Inverter connected load.
Fault code 06 voltage below than 190Vac or
is higher than 260Vac) 2. Return to repair
center
Return to repair
Fault code 08/09 Internal components failed.
center.
Model Load Backup Time @ 12Vdc 100Ah Backup Time @ 12Vdc 200Ah
(VA) (min) (min)
100 618 1235
200 259 594
300 155 396
400 109 271
500 87 210
1.2KW 600 65 177
700 57 139
800 49 109
900 43 96
1000 38 85
1200 26 71
200 587 1235
400 256 587
600 155 393
800 109 263
1000 87 210
2.2KW 1200 65 177
1400 56 139
1600 50 109
1800 43 96
2000 31 85
2200 28 78
300 393 843
600 155 393
900 95 233
1200 72 157
1500 52 127
3.2KW 1800 44 98
2100 30 84
2400 26 73
2700 23 57
3000 20 51
3200 14 47
Note: Backup time depends on the quality of the battery, age of battery and type of
battery.
Specifications of batteries may vary depending on different manufacturers.