Product data sheet

Specifications

TeSys Deca contactor, 3P(3NO),


AC-3/AC-3e, 440V, 95 A, 220V AC
50/60 Hz coil,screw clamp terminals
LC1D95M7

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range TeSys

Product name TeSys D


TeSys Deca

Product or component type Contactor

Device short name LC1D

Contactor application Motor control


Resistive load

Utilisation category AC-1


AC-4
AC-3
AC-3e

Poles description 3P

Power pole contact composition 3 NO

[Ue] rated operational voltage Power circuit: 1000 V AC 25...400 Hz

[Ie] rated operational current 95 A (at <60 °C) at <= 440 V AC-3 for power circuit
125 A (at <60 °C) at <= 690 V AC-1 for power circuit
95 A (at <60 °C) at <= 440 V AC-3e for power circuit

Motor power kW 25 kW at 220...230 V AC 50 Hz (AC-3)


45 kW at 380...400 V AC 50 Hz (AC-3)
45 kW at 415...440 V AC 50 Hz (AC-3)
55 kW at 500 V AC 50 Hz (AC-3)
45 kW at 660...690 V AC 50 Hz (AC-3)
45 kW at 1000 V AC 50 Hz (AC-3)

Motor power HP (UL / CSA) 7.5 hp at 120 V AC 60 Hz for 1 phase motors


15 hp at 230/240 V AC 60 Hz for 1 phase motors
30 hp at 200/208 V AC 60 Hz for 3 phases motors
30 hp at 230/240 V AC 60 Hz for 3 phases motors
60 hp at 460/480 V AC 60 Hz for 3 phases motors
60 hp at 575/600 V AC 60 Hz for 3 phases motors

Control circuit type AC at 50/60 Hz

[Uc] control circuit voltage 220 V AC 50/60 Hz

Auxiliary contact composition 1 NO + 1 NC

[Uimp] rated impulse withstand 8 kV conforming to IEC 60947


voltage

Overvoltage category III

[Ith] conventional free air 10 A (at 60 °C) for signalling circuit


thermal current 125 A (at 60 °C) for power circuit

Irms rated making capacity 1100 A at 440 V AC for power circuit conforming to IEC 60947
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1

May 21, 2022 1


Rated breaking capacity 1100 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand 1100 A 40 °C - 1 s for power circuit


current 800 A 40 °C - 10 s for power circuit
400 A 40 °C - 1 min for power circuit
135 A 40 °C - 10 min for power circuit
140 A - 100 ms for signalling circuit
120 A - 500 ms for signalling circuit
100 A - 1 s for signalling circuit

Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1


200 A gG at <= 690 V coordination type 1 for power circuit
160 A gG at <= 690 V coordination type 2 for power circuit

Average impedance 0.8 mOhm - Ith 125 A 50 Hz for power circuit

[Ui] rated insulation voltage Power circuit: 1000 V conforming to IEC 60947-4-1
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified

Electrical durability 1.2 Mcycles 95 A AC-3


1.3 Mcycles 125 A AC-1
1.2 Mcycles 95 A AC-3e

Power dissipation per pole 12.5 W AC-1


7.2 W AC-3
7.2 W AC-3e

Front cover With

Mounting support Rail


Plate

Standards EN/IEC 60947-1


EN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/T 14048.4

Product certifications IECEE CB Scheme


UL
CSA
CCC
EAC
LROS (Lloyds register of shipping)
RINA
BV
DNV-GL

Connections - terminals Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: connector 1 cable(s) 4…50 mm²flexible without cable end
Power circuit: connector 2 cable(s) 4…25 mm²flexible without cable end
Power circuit: connector 1 cable(s) 4…50 mm²flexible with cable end
Power circuit: connector 2 cable(s) 4…16 mm²flexible with cable end
Power circuit: connector 1 cable(s) 4…50 mm²solid without cable end
Power circuit: connector 2 cable(s) 4…25 mm²solid without cable end

Tightening torque Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit: 12 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm
Power circuit: 12 N.m - on connector hexagonal screw head 4 mm
Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2

Operating time 20...35 ms closing


6...20 ms opening

Safety reliability level B10d = 1.3 Mcycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20 Mcycles contactor with mechanical load conforming to EN/ISO 13849-1

Mechanical durability 4 Mcycles

Maximum operating rate 3600 cyc/h 60 °C

Complementary
Coil technology Without built-in suppressor module

Control circuit voltage limits 0.8...1.1 Uc (-40…55 °C):operational AC 50 Hz

2
May 21, 2022
0.85...1.1 Uc (-40…55 °C):operational AC 60 Hz
0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
1...1.1 Uc (55…70 °C):operational AC 50/60 Hz

Inrush power in VA 245 VA 60 Hz cos phi 0.75 (at 20 °C)


245 VA 50 Hz cos phi 0.75 (at 20 °C)

Hold-in power consumption in 26 VA 60 Hz cos phi 0.3 (at 20 °C)


VA 26 VA 50 Hz cos phi 0.3 (at 20 °C)

Heat dissipation 6…10 W at 50/60 Hz

Auxiliary contacts type type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1


type mirror contact 1 NC conforming to IEC 60947-4-1

Signalling circuit frequency 25...400 Hz

Minimum switching current 5 mA for signalling circuit

Minimum switching voltage 17 V for signalling circuit

Non-overlap time 1.5 ms on de-energisation between NC and NO contact


1.5 ms on energisation between NC and NO contact

Insulation resistance > 10 MOhm for signalling circuit

Environment
IP degree of protection IP20 front face conforming to IEC 60529

Climatic withstand conforming to IACS E10

Protective treatment TH conforming to IEC 60068-2-30

Pollution degree 3

Ambient air temperature for -40…60 °C


operation 60…70 °C with derating

Ambient air temperature for -60…80 °C


storage

Operating altitude 0...3000 m

Fire resistance 850 °C conforming to IEC 60695-2-1

Mechanical robustness Vibrations contactor open: 2 Gn, 5...300 Hz


Shocks contactor open: 8 Gn for 11 ms
Vibrations contactor closed: 3 Gn, 5...300 Hz
Shocks contactor closed: 10 Gn for 11 ms

Height 127 mm

Width 85 mm

Depth 130 mm

Net weight 1.61 kg

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Weight 1.556 kg

Package 1 Height 9.5 cm

Package 1 width 13.5 cm

Package 1 Length 14 cm

Unit Type of Package 2 S02

Number of Units in Package 2 5

Package 2 Weight 8.09 kg

Package 2 Height 15 cm

Package 2 width 30 cm

May 21, 2022 3


Package 2 Length 40 cm

Unit Type of Package 3 P06

Number of Units in Package 3 80

Package 3 Weight 140.26 kg

Package 3 Height 77 cm

Package 3 width 60 cm

Package 3 Length 80 cm

Offer Sustainability
Sustainable offer status Green Premium product

REACh Regulation REACh Declaration

REACh free of SVHC Yes

EU RoHS Directive Compliant


EU RoHS Declaration

Toxic heavy metal free Yes

Mercury free Yes

RoHS exemption information Yes

China RoHS Regulation China RoHS declaration


Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental Disclosure Product Environmental Profile

WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins

PVC free Yes

California proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony
trioxide, which is known to the State of California to cause cancer. For more information go to
www.P65Warnings.ca.gov

Contractual warranty
Warranty 18 months

4
May 21, 2022
Product data sheet LC1D95M7
Dimensions Drawings

Dimensions

(1) Minimum electrical clearance

LC1 D80 D95

a 85 85

b1 with LA4 D●2 135 135

with LA4 DB3 or LAD 4BB3 135 –

with LA4 DF, DT 142 142

with LA4 DM, DW, DL 150 150

c without cover or add-on blocks 125 125

with cover, without add-on blocks 130 130

c1 with LAD N (1 contact) 150 150

with LAD N or C (2 or 4 contacts) 158 158

c2 with LA6 DK10, LAD 6DK 170 170

c3 with LAD T, R, S 178 178

with LAD T, R, S and sealing cover 182 182

May 21, 2022 5


Product data sheet LC1D95M7
Connections and Schema

Wiring

6
May 21, 2022