 Innovation Design Sustainability

 

SN - SERIES

LN - SERIES

DS - SERIES

CB - SERIES

Experience
THE COMFORT in your investment
Ducted Type
Fan CoilMEIUnit
Series
District Cooling / Chiller Application
220 - 240/1P/50-60 Hz
AC / EC Series
Finpower
01............................. About Finpower
02............................. Company Profile

03............................. Major Components

SN Series
06............................. SN series
07............................. SN series Features
08............................. Dimensional Drawings
09............................. Performance Data
10............................. AHRI Standard Model
11............................. Airflow Data
12............................. Sound Pressure Level

LN Series
14............................. LN Series
15............................. LN Series Features
16............................. Dimensional Drawings
17............................. Performance Data
18............................. AHRI Standard Model
19............................. Airflow Data
20............................. Sound Pressure Level

CB Series
21............................. CB Series
22............................. Dimensional Drawings

DS Series
23............................. DB Series

24............................. Software Strength, Nomenclature


25............................. Wiring Drawing for SN & LN Series
26............................. FCU Hook Up
28............................. Testing Facilities
ABOUT FINPOWER
We at Finpower, were born out of sheer need of quality and
affordable HVACR equipment for the ever-growing
markets. Established in 2011, we strive to specialize in
manufacture of Air-conditioning and Kitchen Ventilation
equipment at the state of the art manufacturing facility at
Dubai (UAE) and Mangalore (India).

ABOUT FAN COIL UNITS


Fan Coil Units or FCU is a device used in a building to heat
or cool a specific space. It is essentially made up of a motor
with a fan, a heating or cooling coil connected to the
building’s central hot water and cold water system, and
valve with a controller. In simple terms, it is a heat
exchanger where the fan and motor brings air, which is a
medium of transfer, to the copper coil. The coil is either
having hotter or colder water so transfers the heat to the
flowing air. This catalogue displays ceiling hideaway ducted
type, exposed double skin and decorative type of units
ranging from airflows of 200 CFM to 3000 CFM.

QUALITY ASSURANCE & WARRANTY


Finpower Fan Coil Units are designed to be highly efficient
with prevalent and accessible technology. Noise,
Performance and Indoor Air Quality (IAQ) have been our
main focus of improvement. The components are selected
with great care with prior testing from renowned vendors
who have various certification and high level of
commitment. All the units are factory tested and undergo
strict quality procedures before dispatch.
COMPANY PROFILE
Finpower Aircon is an ISO certified organization Our service team is capable of handling any
focused in the manufacture of complete range of Air emergencies and are always ready to serve you. We
Conditioning, Refrigeration and Kitchen Ventilation have tagged all our units for identification and can
equipment for the International markets. quickly identify the components inside. We maintain
inventory of most of the spares relevant to our
Our specialty lies in the manufacture of highly warranty.
complicated and challenging HVAC machines with
special emphasis on Packaged units, Chillers and Finpower believes in providing value for money. Our
other airside products such as Fan Coil units, Fresh Air esteemed customers have been assured of energy
Handling Units, Ecology units and energy recovery efficient, performance oriented, safety adhered and
units. Our design and engineering team evaluates the eco-friendly materials in all product lines. With the
diverse specifications of customer and endeavors to implementation of 5 step quality control process by
provide precise machines at economical prices within our quality control experts we once again ensure our
committed delivery periods. products are consistent of the highest grade of
quality as required by customer.
Our state of art manufacturing facility is located at
Dubai Industrial City and Mangalore Baikampady With a strong local base of operations, Finpower is
Industrial area covering a spread of approx. 150,000 now ready to expand its distribution network and
sq. ft. We are constantly evolving and diversifying to increase its brand value through global strategy of
cater to global markets. We have supplied to many progressively developing and manufacturing more
projects in various countries such as South Africa, value added products, providing personalized
Uganda, UAE, Qatar, Oman, Saudi Arabia, Iran, India services, and venturing into new international
etc. markets.
FAN COIL UNITS

Finpower Fan coil units are statically & dynamically balanced DIDW
metal fans for various application. The series include:
SN SERIES: Low static Units.
LN SERIES: High Static Units.
CB SERIES: Decorative type Units
DS SERIES: Double Skin Units

MAJOR COMPONENTS
Motor
1. AC Motor (Standard Feature)
Motors are 3 speed permanent split capacitor type suitable for a
power supply of 220-240V / 1 ph / 50 -60 Hz. It is wound with
class Binsulation and the shaft rotates on a permanently
lubricated ballrace bearing which in turn rests on an
anti-vibration rubbermounting. Resilient mounted motor are IP
rated i.e. IP20 and higher
IP can be provided to make the specification on motor which are
built with thermal protection. Motors meet all the requirements of
CE with explosion proof capacitor. Motors are provided with
composite material conduit. All the motors comply to EN 60034-1.
This design gives the motor a smooth trouble free long life of 10
years.
2. EC Motor (Optional Feature)
Our green EC motor adopt “sensor less FOC (Field Oriented Control)
drive technology”, which omits the physical hall-effect sensors that
must be installed inside the motor to detect the rotor’s position,
therefore, it is free from the risk of hall-effect sensors’ failures,
making EC motor more reliable and durable, and also making the EC
motor and driver more cost effective.
• EC fans with integrated, active power-factor correction.
• Efficiency – The driver’s efficiency is up to 94%
• Precise Speed Control – Excellent control ability at ±5rpm speed
control.
• Protections – Rotor lock protection, current protection, power
module temperature protection.
• Motor can be stepless i.e. fan can be operated from 0 to 10v
based on room load or 3 speed controller is fixed outside for easy
controller access.
Specifications:
• Nominal Voltage: AC 230V, Frequency: 50/60 HZ.
• Input Signal: 0-10 Vdc or 3 speed.
• Ingress Protection: IP 54
• Class B insulation as per site requirement.

3
MAJOR COMPONENTS

Copper coil
Coils are provided in all fan coil units and are made up of 3/8” OD copper
tubes with mechanically expanded aluminum fins as a standard. The
design emphasizes on the need of minimum air side and waterside
pressure drop yet provide a highly efficient heat transfer. Various options
are available on coils depending on the application. Coils are provided with
air vent and drain plug for ease in commissioning and maintenance
respectively. The coils are tested as per ASHRAE STD 33 & tested for
performance with complete FCU’s i.e. AHRI 440.

Return Air Plenum


The return air plenum is provided as standard. All return air is brought into the unit through single side where
the filter is mounted. Thus filtered air enters the unit keeping the coil clean for efficient heat transfer. The
plenum also reduces the sound transmission through the motor and hence is insulated with class ‘O’ fire
retardant nitrile rubber insulation.

Fan
The unit is fitted with Double Inlet Double Width (DIDW)
centrifugal, forward curved galvanized steel impeller. The
volute housing is made of Galvanized steel giving it a
rugged construction. The impellers are statically and
dynamically balanced as per AMCA 204 before enclosing in
the housing.

Filter:
All the units are provided with high efficiency Nylon mesh woven media
filter as standard. These are cleanable by water or compressed air and
have long life. For higher efficiency we provide options of G2 or G3 grade
filters, however, the performance has to be rated accordingly. The filters
are tested as per ASHRAE 52.2 - 2017.

Filters come with standard lift up option, which is easy for removal &
maintenance. However, optional filter frames with bottom, side or top
removable access shall be provided on special request. Filters in split can be
provided where access is constrained.

4
MAJOR COMPONENTS

Drain Pan
Drain pan are manufactured in house with steel & corrosion resistant Epoxy coated
steel drain pan with 6mm nitrile class O insulation. We provide SS304 / SS316 along with
10mm, 19mm insulation as option. Drain pans are provided with drain nipple to ensure
all the water is flow out & designed as per ASHRAE 62.1.

Return Air Plenum

Casing
Casing
The unit is constructed out of heavy duty galvanized steel
complying ASTM A613. Anchor holes are provided at the top
of the unit for hanging the unit safely. The casing is
designed for an efficient sealing of air and water so that
neither of them get mixed apart from heat exchange area.
Units are by default with internal thermal and acoustic
insulation to prevent any heat transfer and sweating.

Electric Heater
• Finned tubular Electric heating elements with auto reset thermal cutout can be provided inside the FCU for
sensible heating
• Duct heaters with necessary safety like Auto reset thermal cutout, manual reset thermal cutout and airflow
switch can be provided as additional fitment over the FCU for humidity control. The heaters are designed and
arranged in the most efficient pattern for heat transfer.
• Different control options can be provided like stage, thyristor etc in the control panel of duct heaters.
Hot water coils
• Single row or two row are included in i.e. 4 pipe system for hot water coil where ever the hotwater is available
for heating.
• This are constructed out of 3/8” OD copper tube with aluminum fins with fin density of 9-10 FPI with brass
connection.
• Hot water coils are used for sensible heating to maintaining the room temperature in cold regions or winter
application, alternatively are used to maintain the humidity levels in the condition space.

UV Lamps
• Ultra-violent lamps can be provided after the cooling coil so that their radiation will ensure to eliminate the
bacteria and reduce the formation of algae on the coil surface and other exposed area.
• Having coverage area of 72- 125 µW/CM² at 254 nm with minimum power consumption, the UVC lights are great
protection for various air borne diseases.
• UVC lamps are designed based on average life of 16,000 hours based on standard air quality and steady power
supply.

5
FAN COIL UNIT - LN SERIES

Ceiling Suspended Concealed Fan Coil Unit


Model LN-06 LN-08 LN-10 LN-12 LN-14 LN-18 LN-24
Nominal Airflow (CFM) 600 800 1000 1200 1500 1800 2400
Nominal Airflow (L/s) 283 378 472 566 708 850 1133
No of fan blower 1 1 2 2 2 3 4
Maximum Power input(W)
(220~240V/1Ph/50-60 Hz 297 350 498 545 654 842 1090
@ freeflow

13
LN SERIES - FEATURES
Standard
•Airflow range from 400 Cfm to 3000 Cfm.
•ESP range from 20Pa to 150Pa.
•Coil - number of rows from 3 to 6 rows.
•Transfer Medium – chilled water.
•ΔT – District Cooling or chiller
•2 or 4 pipe system.
•Galvanized Iron (GI) sheet casing, well-insulated and robust construction.
•Forward curved DIDW fan with statically and dynamically balanced impeller to handle high static with low
noise.
•3 speeds permanent split capacitor (PSC) run, thermally protected motor.
•Maintenance free permanently lubricated ball bearing.
•AC 220 ~ 240 volt, 50-60 Hz, single phase, Class B insulated motors with anti-vibration rubber mounts.
•All motors are wired to the junction box for easy connection. Wiring diagram is pasted beside to identify
neutral and various speeds.
•Insulated return air plenum and filter.
•Access panel provided below plenum for access to motor and fan.
•Aluminum fins are mechanically bonded over 3/8" OD copper tubes for higher efficiency.
•Brass distributor with air vent and drain plug.
•Low height for fitting in ceiling voids.
•Powder coated/epoxy coated drain pan.
•Coarse filter with up to 65% efficiency.

Optional*
•Fan Coil Unit with EC (electronically commutated) Motor Option for power saving & precise control.
•As per IAQ requirements we can provide higher grade filters however performance will need to be checked
with us as a consequence.
•Split filters can be provided for easy maintenance.
•Bottom removable drop down filters when return is ducted can be provided.
•Bottom return plenum can also be provided.
•Cutouts can be provided on the plenum sides for treated fresh air entry mixing.
•Copper fins can be provided for highly corrosive environment.
•Aluminum fins with coating or fins produced by using coated aluminum fin stock can be provided.
•Class F insulated motors and higher IP ratings available.
•Stainless steel drain pans.
•Extended drain pan and auxiliary drain pans.
•2 way / 3 way valves with actuators.
•Heating options - electric and hot water.
•60 Hz motor.
•Decorative type (CB series): Decorative Units shall be provided with powder coating from Standard RAL Chart
to meet interior requirements.
•Double skin (DS model): Insulation options available are Nitrile rubber, rockwool, and puff insulation. Double
skins can also be provided on decorative units.

* For all optional items lead times can change. Please discuss with sales team / distributor for updated lead times.

14
LN SERIES - DIMENSIONAL DRAWINGS
E

Water Inlet Connection


CHW In/Out
Model BSP MALE PIPE THREAD
LN - 06
LN - 08
LN - 10 3/4”
LN - 12
Drain LN - 14
3/4” MPT LN - 18 1”
LN - 24

665

F
Wiring Diagram
BLUE Point Loads
RED H LINE Point Load (kgs)
YELLOW M Model
P1 P2 P3 P4
BLACK L LN - 06 13.62 13.62 5.90 5.90
Y/G LN - 08 16.20 16.20 7.30 7.30
WHITE LN - 10 20.97 20.97 10.0 10.0
Cap LN - 12 20.97 20.97 10.0 10.0
WHITE LN - 14 25.39 25.39 12.8 12.8
LN - 18 30.93 30.93 13.80 13.80
LN - 24 37.72 37.72 17.23 17.23

Dimensional Details
Model Dimensions (mm) Number of Std Filter Weight (kgs) System
A B C D E F Fan(s) Motor (s) Dim (mm) Dead Operating Volume(ltr)
LN - 06 792 591 530 583 685 365 1 1 581 x 295 37 39.06 1.60
LN - 08 942 721 683 733 685 365 1 1 683 x 295 43 47.3 1.90
LN - 10 1152 983 945 995 685 365 2 1 945 x 295 54 59.4 1.60
LN - 12 1152 983 940 995 685 365 2 1 935 x 295 58 61.66 2.80
LN - 14 1545 1308 1270 1320 685 365 2 1 1266 x 295 71 76.68 3.80
LN - 18 1735 1486 1448 1498 685 365 3 2 1445 x 295 84 89.35 4.30
LN - 24 2072 1918 1880 1930 685 365 4 2 1875 x 295 103 109.9 5.60
Note : For dimensional details of (CB) and (DS) please contact the Sales Team / Local Distributor.

15
LN SERIES - PERFORMANCE DATA
Cooling Capacity in Kilowatt - Medium Speed
4 Row Coils
Entering Air Condition DB / WB 24/17.8 °C (55% RH)
Water Flow W.P.D. Entering Water Temp °C
LN Series 5 7 9
L/sec kPa SH TH SH TH SH TH
0.10 1.00 3.39 3.53 3.11 3.11 2.75 2.75
LN-06 0.20 2.00 4.06 5.21 3.71 4.42 3.41 3.67
0.30 3.90 4.43 6.15 4.04 5.24 3.69 4.29
0.40 5.90 4.66 6.76 4.25 5.75 3.86 4.76
0.10 1.00 4.22 4.27 3.79 3.79 3.34 3.34
LN-08 0.20 2.00 5.00 6.33 4.64 5.40 4.32 4.50
0.30 3.90 5.49 7.63 5.05 6.47 4.64 5.34
0.40 6.90 5.89 8.41 5.28 7.14 4.83 5.89
0.10 1.00 5.13 5.13 4.58 4.58 0.00 0.00
LN-10 0.20 2.90 6.44 7.58 6.10 6.49 5.57 5.57
0.30 4.90 7.14 9.27 6.56 7.91 6.09 6.62
0.40 7.80 7.67 10.5 7.07 8.95 6.43 7.30
0.10 1.00 5.78 5.78 0.00 0.00 0.00 0.00
LN-12 0.20 2.90 7.56 8.50 7.13 7.35 6.40 6.40
0.30 5.90 8.34 10.5 7.73 8.98 7.18 7.56
0.40 9.80 8.99 11.9 8.22 10.1 7.53 8.46
0.20 3.90 8.70 9.36 8.15 8.15 7.17 7.17
LN-14 0.30 6.90 9.66 11.6 8.99 9.99 8.35 8.44
0.40 10.8 10.3 13.4 9.40 11.3 8.83 9.50
0.20 2.00 9.46 9.46 8.47 8.47 0.00 0.00
0.30 2.90 10.9 11.7 10.2 10.2 9.02 9.02
LN-18 0.40 3.90 11.8 13.7 10.9 11.8 10.1 10.1
0.55 6.90 12.7 16.1 11.7 13.7 10.8 11.5
0.30 1.00 12.3 12.3 11.0 11.0 9.78 9.78
0.40 1.00 14.2 14.2 12.7 12.7 11.3 11.3
0.55 2.00 15.9 16.6 14.6 14.6 12.9 12.9
LN-24 0.70 2.00 16.7 18.6 15.7 16.0 14.0 14.0

Cooling capacity in Kilowatt - Medium Speed @ 50Pa ESP - 4 Row Coils


Entering Air Condition DB / WB 26/19.5 °C (55% RH)
Water Flow W.P.D. Entering Water Temp °C
LN Series 5 7 9
L/sec kPa SH TH SH TH SH TH
0.10 1.00 3.56 4.00 3.40 3.54 3.11 3.11
0.20 2.00 4.32 6.08 3.98 5.24 3.71 4.42
LN-06 0.30 3.90 4.78 7.24 4.38 6.26 4.02 5.29
0.40 5.90 5.10 7.98 4.68 6.88 4.23 5.79
0.10 1.00 4.44 4.83 4.22 4.26 3.79 3.79
LN-08 0.20 2.00 5.39 7.39 5.02 6.35 4.64 5.40
0.30 3.90 5.95 8.88 5.54 7.69 5.05 6.47
0.40 6.90 6.34 9.90 5.79 8.51 5.29 7.24
0.10 1.00 5.67 5.67 5.13 5.13 0.00 0.00
LN-10 0.20 2.90 6.97 8.71 6.44 7.58 6.07 6.52
0.30 4.90 7.71 10.8 7.11 9.36 6.64 7.90
0.40 7.80 8.34 12.2 7.63 10.6 6.99 8.96
0.10 1.00 6.23 6.23 5.63 5.63 0.00 0.00
LN-12 0.20 2.90 7.62 9.53 7.21 8.28 6.86 7.14
0.30 5.90 8.58 11.9 7.95 10.3 7.37 8.78
0.40 9.80 9.24 13.5 8.57 11.7 7.77 9.96
0.20 3.90 9.27 10.6 8.68 9.34 8.15 8.15
LN-14 0.30 6.90 10.3 13.5 9.60 11.7 8.99 9.99
0.40 10.8 11.0 15.6 10.2 13.4 9.40 11.3
0.20 2.00 10.4 10.4 9.46 9.46 0.00 0.00
LN-18 0.30 2.90 11.6 13.3 11.0 11.7 10.2 10.2
0.40 3.90 12.6 15.9 11.6 13.7 11.0 11.7
0.55 6.90 13.5 18.8 12.5 16.1 11.7 13.6
0.30 1.00 13.6 13.6 12.3 12.3 11.0 11.0
LN-24 0.40 1.00 14.7 16.3 14.1 14.4 12.7 12.7
0.55 2.00 16.1 19.9 15.1 17.1 14.3 14.9
0.70 2.00 17.3 22.7 16.0 19.5 14.9 16.7
Airflow mentioned is at dry coil condition.
TH = Total cooling in KW SH= Sensible Cooling in KW ΔWT= Water Delta T WPD=Water Pressure Drop

16
AHRI STANDARD MODELS – LN SERIES
High speed @50pa, On coil = 26/19.6 °C
AC motor -Chiller application - 4Row
Air Flow Water Flow Water Pressure Total Sensible Water Power
Model Number Rating Rate Drop Capacity Capacity Temperature Rise Input Frequency
(L/s) (L/s) (Kpa) (Kw) (Kw) (deg F) (W) (Hz)
LN-S-06-H-4RC-C-AM-P 322 0.26 2.93 6.04 4.47 10 432 50
LN-S-08-H-4RC-C-AM-P 379 0.36 5.86 8.22 6.00 10 432 50
LN-S-10-H-4RC-C-AM-P 534 0.50 11.75 11.53 8.53 10 536 50
LN-S-12-H-4RC-C-AM-P 712 0.65 21.49 15.09 10.57 10 792 50
LN-S-14-H-4RC-C-AM-P 838 0.79 34.19 18.09 12.48 10 792 50
LN-S-18-H-4RC-C-AM-P 1047 0.88 14.65 20.39 14.88 10 910 50
LN-S-24-H-4RC-C-AM-P 1368 1.25 37.12 28.88 20.20 10 1020 50

AC motor -District Cooling application - 4Row


Air Flow Water Flow Water Pressure Total Sensible Water Power
Model Number Rating Rate Drop Capacity Capacity Temperature Rise Input Frequency
(L/s) (L/s) (Kpa) (Kw) (Kw) (deg F) (W) (Hz)
LN-S-06-H-4RC-D-AM-P 322 0.15 6.84 5.274 4.23 15 432 50
LN-S-08-H-4RC-D-AM-P 379 0.20 13.63 7.000 5.25 15 432 50
LN-S-10-H-4RC-D-AM-P 534 0.28 28.28 9.769 7.43 15 536 50
LN-S-12-H-4RC-D-AM-P 712 0.35 15.63 12.165 9.49 15 792 50
LN-S-14-H-4RC-D-AM-P 838 0.42 25.41 14.591 11.24 15 792 50
LN-S-18-H-4RC-D-AM-P 1047 0.40 3.92 14.035 12.50 15 910 50
LN-S-24-H-4RC-D-AM-P 1368 0.62 10.76 21.661 17.54 15 1020 50

EC motor -Chiller application - 4Row


Air Flow Water Flow Water Pressure Total Sensible Water Power
Model Number Rating Rate Drop Capacity Capacity Temperature Rise Input Frequency
(L/s) (L/s) (Kpa) (Kw) (Kw) (deg F) (W) (Hz)
LN-S-06-H-4RC-C-EM-P 322 0.26 2.93 6.04 4.47 10 302 50
LN-S-08-H-4RC-C-EM-P 379 0.36 5.86 8.22 6.00 10 324 50
LN-S-10-H-4RC-C-EM-P 534 0.50 11.75 11.53 8.53 10 402 50
LN-S-12-H-4RC-C-EM-P 712 0.65 21.49 15.09 10.57 10 594 50
LN-S-14-H-4RC-C-EM-P 838 0.79 34.19 18.09 12.48 10 594 50
LN-S-18-H-4RC-C-EM-P 1047 0.88 14.65 20.39 14.88 10 681 50
LN-S-24-H-4RC-C-EM-P 1368 1.25 37.12 28.88 20.20 10 765 50

EC motor -District Cooling application - 4Row


Air Flow Water Flow Water Pressure Total Sensible Water Power Frequency
Model Number Rating Rate Drop Capacity Capacity Temperature Rise Input (Hz)
(L/s) (L/s) (Kpa) (Kw) (Kw) (deg F) (W)
LN-S-06-H-4RC-D-EM-P 322 0.15 6.84 5.274 4.23 15 302 50
LN-S-08-H-4RC-D-EM-P 379 0.20 13.63 7.000 5.25 15 324 50
LN-S-10-H-4RC-D-EM-P 534 0.28 28.28 9.769 7.43 15 402 50
LN-S-12-H-4RC-D-EM-P 712 0.35 15.63 12.165 9.49 15 594 50
LN-S-14-H-4RC-D-EM-P 838 0.42 25.41 14.591 11.24 15 594 50
LN-S-18-H-4RC-D-EM-P 1047 0.40 3.92 14.035 12.50 15 681 50
LN-S-24-H-4RC-D-EM-P 1368 0.62 10.76 21.661 17.54 15 765 50
Airflow mentioned is at dry coil condition.
• Water in/out = 7/12 (chiller application) •water in/out = 7/15(District cooling application)

17
AIRFLOW DATA - LN SERIES

Airflow in L/S
Fan Speed = High
Model 0 25 50 75 100 125 150
LN-06 416 384 327 271 200 137 77
LN-08 475 435 403 378 352 330 310
LN-10 722 687 651 588 524 450 375
LN-12 741 732 723 678 634 584 534
LN-14 871 861 850 797 745 687 628
LN-18 1089 1076 1062 996 931 858 785
LN-24 1423 1405 1388 1302 1217 1121 1026

Airflow in L/S
Fan Speed = Medium
Model 0 25 50 75 100 125 150
LN-06 386 356 303 251 186 127 71
LN-08 463 420 385 357 335 297 279
LN-10 644 615 539 519 453 370 286
LN-12 676 663 649 606 596 529 463
LN-14 805 789 770 721 710 631 551
LN-18 1007 987 967 902 888 788 689
LN-24 1332 1306 1279 1193 1174 1043 912

Airflow in L/S
Fan Speed = Low
Model 0 25 50 75 100 125 150
LN-06 296 288 280 271 255 216 177
LN-08 406 382 362 334 312 252 237
LN-10 559 542 524 451 378 309 239
LN-12 592 576 561 542 511 432 354
LN-14 684 671 654 613 604 536 468
LN-18 879 856 833 804 758 642 525
LN-24 1165 1132 1099 1044 1028 913 800

Note :The airflow provided are without the plenum and filter. Above airflow are at dry coil conditions. Please contact local sales or local distributor for
customised selection.

18
LN SERIES - SOUND PRESSURE LEVEL SPL
Tested in anecholic chamber in accordance with ISO 3745 measured at freeflow
Discharge Sound Pressure level dB(A)
(In accordance with ISO 3745 standard measured at freeflow)
Fan Speed Unit Size Octave Band Center Frequency Hz
125 250 500 1000 2000 4000 8000 NC
6 43 46 37 23 17 19 18 35
8 44 47 39 25 19 20 19 35
H 10 46 48 40 26 20 22 21 40
12 46 49 40 26 20 22 21 40
14 47 50 41 27 21 23 22 40
18 48 51 42 28 22 24 23 40
24 49 52 43 29 23 25 24 45
6 42 45 35 21 15 17 15 35
8 43 47 37 24 17 18 19 35
M 10 45 48 38 24 18 20 18 40
12 45 48 38 24 18 20 18 40
14 46 49 39 25 17 19 17 40
18 47 50 40 26 20 22 20 40
24 48 51 41 27 21 23 21 40
6 41 42 33 18 12 14 11 35
6 41 42 33 18 12 14 11 35
L 6 41 42 33 18 12 14 11 35
12 44 45 36 21 15 17 14 35
14 42 44 35 20 14 16 13 35
18 46 47 38 23 17 19 16 40
24 47 48 39 24 18 20 17 40

Suction Sound Pressure level dB(A)


(In accordance with ISO 3745 standard measured at freeflow)
Fan Speed Unit Size Octave Band Center Frequency Hz
125 250 500 1000 2000 4000 8000 NC
6 49 55 50 47 47 40 31 50
8 50 57 52 49 48 39 32 55
H 10 52 58 53 50 50 43 34 55
12 52 58 53 50 50 43 34 55
14 53 59 54 51 51 44 35 55
18 54 60 55 52 52 45 36 55
24 55 61 56 53 53 46 37 55
6 48 53 48 44 45 38 28 50
8 49 55 50 46 45 40 29 50
10 51 56 51 47 48 41 31 50
M 12 51 56 51 47 48 41 31 50
14 52 57 52 48 49 42 32 50
18 53 58 53 49 50 43 33 55
24 54 59 54 50 51 44 34 55
6 47 51 46 41 42 34 24 45
8 48 51 47 43 44 35 25 50
L 10 50 54 49 44 45 37 27 50
12 50 54 49 44 45 37 27 50
14 51 55 50 45 46 38 28 50
18 52 56 51 46 47 39 29 50
24 53 57 52 47 48 40 30 50

Radiated Sound Pressure level dB(A)(Single Skin)


(In accordance with ISO 3745 standard measured at freeflow)
Fan Speed Unit Size Octave Band Center Frequency Hz
125 250 500 1000 2000 4000 8000
6 43 44 36 22 13 12 <10
8 44 45 36 23 15 12 <10
10 46 47 39 25 16 15 <10
H 12 46 47 39 25 16 15 <10
14 47 48 40 26 17 16 <10
18 48 49 41 27 18 17 <10
24 49 50 42 28 19 18 <10
6 42 43 34 20 11 10 <10
8 43 43 33 19 11 10 <10
10 45 46 37 23 14 13 <10
M 12 45 46 37 23 14 13 <10
14 46 47 38 24 13 12 <10
18 47 48 39 25 16 15 <10
24 48 49 40 26 17 16 <10
6 41 40 32 17 <10 <10 <10
8 43 42 32 17 <10 <10 <10
10 44 43 35 20 11 10 <10
L 12 44 43 35 20 11 10 <10
14 42 42 34 19 10 <10 <10
18 46 45 37 22 13 12 <10
24 47 46 38 23 14 13 <10

19
FAN COIL UNIT - CB SERIES
CABINET TYPE - Decorative

Finpower cabinet fan coil units are commonly known as decorative units, which are designed for exposed installation, longer lifetime under normal
running conditions. Units are made with pre coated GI sheets on all the four sides leaving the return and top area. Sheet metal work is done
aesthetically leaving sufficient space on both sides for access and terminations. Units are also provided with double deflection grill to direct the
airflow.
The unit is coated with sheet which are tested a per ASTM B-117. Cabinet fan coils incorporate metal fans that are quieter than usual and require
less fan power. This fan of metal construction blades provides excellent corrosion resistance and durability with continues year round operations.
The motor provided is energy-saving permanent split capacitor type motor and is resiliently mounted. In order to accommodate increasingly tough
electrical safety requirements and ease of maintenance, the capacitor is placed over motor enclosure. The motor lead out wires are sheathed and
also protected by flexible conduit.

Ceiling Suspended Exposed Fan Coil Unit


Type SN-02(CB) SN-03(CB) SN-04(CB) SN-06(CB) SN-08(CB) SN-10(CB) SN-12(CB) SN-14(CB)
Size (CFM) 200 300 400 600 800 1000 1200 1400
No of fan(s) 1 1 2 2 2 3 4 4
No of motor (s) 1 1 1 1 1 2 2 2

Type LN-06(CB) LN-08(CB) LN-10(CB) LN-12(CB) LN-14(CB) LN-18(CB) LN-24(CB)


Size (CFM) 600 800 1000 1200 1500 1800 2400
No of fan(s) 1 1 2 2 2 3 4
No of motor (s) 1 1 1 1 1 2 2

PERFORMANCE DATA
Model SN-02(CB) SN-03(CB) SN-04(CB) SN-06(CB) SN-08(CB) SN-10(CB) SN-12(CB) SN-14(CB)
Ext SP Pa 0 20 0 20 0 20 0 20 0 20 0 20 0 20 0 20
High 168 156 239 213 323 296 375 348 468 451 615 562 692 641 785 748
Air Flow
Medium 141 130 213 195 273 258 326 299 397 381 539 494 621 589 698 667
L/S
Low 120 111 183 170 198 190 246 232 300 294 429 402 520 501 549 533
Water Flow L/S 0.09 0.10 0.09 0.10 0.09 0.10 0.09 0.10 0.09 0.10 0.09 0.10 0.09 0.10 0.09 0.10
W.P.D. kPa 1.96 1.96 1.96 2.94 1.96 2.94 2.94 0.98 2.94 0.98 0.98 0.98 0.98 0.98 0.98 0.98
Note: Selection sample is based on 24° C DB/17.8° C WB on coil air temperature. 7° C/12° C entering water temperature / leaving water
temperature.
Performance details
Model LN-06(CB) LN-08(CB) LN-10(CB) LN-12(CB) LN-14(CB) LN-18(CB) LN-24(CB)
Ext SP Pa 0 25 0 25 0 25 0 25 0 25 0 25 0 25
High 416 384 475 435 667 659 741 732 871 861 1089 1076 1422.7 1405.2
Air Flow L/S Medium 386 356 463 420 608 596 676 663 805 789 1007 987 1332 1305.6
Low 325 300 406 382 532 519 592 576 592 670 879 856 1165 1132
Water Flow L/S 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.2 0.2 0.2 0.3 0.3
W.P.D. kPa 3.9 3.9 1 1 1 1 1 1 3.9 3.9 3.9 3.9 1 1

20
DIMENSION DETAIL - CB SERIES

Wiring Diagram
BLUE
RED H LINE
YELLOW M
BLACK L
Y/G
WHITE
Cap
WHITE

Dimensions (mm) Dimensions (mm)


Model WEIGHT Model WEIGHT
A B C (Kg) A B C (Kg)
SN-02/03(CB) 987 515 300 27 LN-06(CB) 987 670 400 49
SN-04(CB) 1217 515 300 35 LN-08(CB) 1137 670 400 58
SN-06(CB) 1392 515 300 38 LN-10(CB) 1347 670 400 63
SN-08(CB) 1602 515 300 45 LN-12(CB) 1347 670 400 63
SN-10(CB) 1827 515 300 55 LN-14(CB) 1740 670 400 78
SN-12(CB) 2120 515 300 64 LN-18(CB) 1930 670 400 98
SN-14(CB) 2120 515 300 68 LN-24(CB) 2367 670 400 123
Note: Finpower reserves the right to change dimension as a part of continuous improvement and research and development procedure.

21
FAN COIL UNIT - DOUBLE SKIN SERIES
DOUBLE SKIN - DUCTED TYPE

For outdoor fixing & sound sensitive areas (can be ducted both sides with filter drop down bracket.

The units are offered in a variety of thicknesses ranging from 13mm to 50mm. Among the insulation options available are Nitrile rubber, rockwool,
and puff insulation. Double skins can also be provided in colors.

Dimensions (mm) Dimensions (mm)


Model WEIGHT Model WEIGHT
A B C (Kg) A B C (Kg)
SN-02/03(DS) 305 732 547 34 LN-06(DS) 405 832 705 71
SN-04(DS) 305 962 547 42 LN-08(DS) 425 1005 725 76
SN-06(DS) 305 1137 547 49 LN-10(DS) 365 1152 665 84
SN-08(DS) 305 1347 547 60 LN-12(DS) 405 1192 705 85
SN-10(DS) 305 1572 547 73 LN-14(DS) 405 1585 705 101
SN-12(DS) 305 1865 547 87 LN-18(DS) 405 1775 705 114
SN-14(DS) 305 1865 547 92 LN-24(DS) 405 2112 705 135

LN SERIES - SOUND PRESSURE LEVEL


Radiated Sound Pressure level dB(A)(Double Skin - 19mm thick)
(In accordance with ISO 3745 standard measured at freeflow)
Fan Speed Unit Size Octave Band Center Frequency Hz
125 250 500 1000 2000 4000 8000
6 31 32 24 <10 <10 <10 <10
8 34 35 27 12 <10 <10 <10
10 34 35 27 12 <10 <10 <10
H 12 34 35 27 12 <10 <10 <10
14 35 36 28 13 <10 <10 <10
18 36 37 29 14 <10 <10 <10
24 37 38 30 15 10 <10 <10
6 30 31 22 <10 <10 <10 <10
8 31 33 24 11 <10 <10 <10
10 33 34 25 10 <10 <10 <10
M 12 33 34 25 10 <10 <10 <10
14 34 35 26 11 <10 <10 <10
18 35 36 27 12 <10 <10 <10
24 36 37 28 13 <10 <10 <10
6 29 28 20 <10 <10 <10 <10
8 30 29 22 <10 <10 <10 <10
10 32 31 23 <10 <10 <10 <10
L 12 32 31 23 <10 <10 <10 <10
14 30 30 22 <10 <10 <10 <10
18 34 33 25 <10 <10 <10 <10
24 35 34 26 10 <10 <10 <10

22
SOFTWARE STRENGTH
Fan coil unit selection software facilitates the preparation of high-quality, well-presented quotes for fan coil units quickly and efficiently.

Based on available options for a FCU, we choose a model and select a coil. We also select the air and water parameters for that model. Once we
have done that, we will be able to run a calculation of coil performance. Coil performance calcuation is initaited as a following step which include
the leaving air and water conditions, cooling and heating capacity, and fan power consumption. Calculations are based on the test results available
and correction factors.

NOMENCLATURE

SN- S -08- H-4RC- C - AM -P -F-DS-HW


LN, SN HW - Hot water
Series HE - Electric Heater
S – Standard Unit DS - Double Skin Unit
CB - Cabinet type Unit
LN - 06, 08,10, 12, 14, 18, 24
SN - 02/03, 04, 06, 08,10 FILTER -SN, G3, G4
12,14
SK – 30 to 80 (AHU Type Construction) Plenum - PI( insulated)
PU(uninsulated)
H- High Static AM - AC Motor
L- Low Static EM - EC Motor
2, 3, 4 &6 C - Chiller Type
Cooling coil D - District Type

23
WIRING DRAWING FOR SN & LN SERIES

EC Motor for SN series


N
INCOMING
POWER SUPPLY
L
230V, 1PH, 50HZ

EC MOTOR
CONTROLLER

OUTPUT
TO MOTOR -

-
THERMOSTAT
EC -

MOTOR
GND COOL
VALVE
VIN 0-10VDC

0-10V DC INPUT
FROM THERMOSTAT FIELD WIRING

EC Motor for LN series

0-10VDC
FROM
THERMOSTAT

L N E V+ RX TX C
MOTOR S P E E D R E F.

EC MOTOR
230/24V AC,
40V A
CONTROLLER
TRANSFORMER

OUTPUT
TO MOTOR

EC MOTOR
230V, 1P H, 50HZ
INC OMING

1 2 3
L N
MOTOR S P E E D R E F.
AC 24V +

AC 24V-

DC 10V +
9
8
7

3
6

2
4

POWER 24 VAC COOL


SUPPLY POWER VALVE
230V AC, 1PH, SUPPLY 0-10VDC
50HZ

THERMOSTAT FIELD WIRING

AC Motor
FP FCU UNIT

LOW
SPEED
COMMAND
THERMOSTAT FROM
THERMOSTAT LOW SPEED WIRE
L OW S P E E D

BLACK
MEDIUM
SPEED
COMMAND
FROM
ME DIUM S P E E D

THERMOSTAT MEDIUM SPEED WIRE


L N Hi Md Lo

HIGH YELLOW
SPEED FAN
COMMAND MOTOR
FROM
HIG H S P E E D

THERMOSTAT HIGH SPEED WIRE

RED
NEUTRAL
FROM
COUSTOMER NEUTRAL WIRE
SIDE
NE UT R A L

BLUE

230
VAC FIELD WIRING

24
TESTING FACILITIES
• All the units are manufactured using tested and certified components & materials.
• All the units are factory tested & approved by the quality procedures before dispatching from the
manufacturing facility.
•The quality process proven & certified by ISO 9001:2015 – which certifies Quality Management System, ISO
45001:2018 certifies Health & Safety Management, ISO 14001: 2015 certifies Environmental Management
System.
•All the quality products tested by automated machines and CNC machines under supervision of super skilled
manpower.

Airflow Testing

Airflow Testing RPM Testing

Airflow Testing Motor Testing

Coil Leakage Testing AMP Testing


Your True Cooling Partner

Middle East | India | Africa


Rev 05 -03-22

*Manufacturer reserves the right to discontinue or change the specifications or design of the product without prior
notice at any time.