L8542839
Rev. 04/05/03
                                      CENTRALE DI COMANDO
                                             CONTROL UNIT
                                             STEUEREINHEIT
                                    CENTRALE DE COMMANDE
                                         CENTRAL DE MANDO
                                      CENTRALKA STEROWANIA
Libro istruzioni
Operating instructions
Betriebsanleitung
Livret d’instructions         UNIONE NAZIONALE COSTRUTTORI
Manuale de instrucciones    AUTOMATISMI PER CANCELLI, PORTE,
Książeczka z instrukcjami                SERRANDE ED AFFINI
          Dichiarazione CE di conformità                                    Déclaration CE de conformité
          EC declaration of confirmity                                      Declaracion CE de conformidad
          EG-Konformitatserklarung                                          Deklaracja UE o zgodności
                                      Con la presente dichiariamo che il nostro prodotto
                                               We hereby declare that our product
                                            Hiermit erklaren wir, dass unser Produkt
                                       Nous déclarons par la présente que notre produit
                                       Por la presente declaramos que nuestro producto
                                           Niniejszym oświadczamy że nasz produkt
                                                              Head
                                       è conforme alle seguenti disposizioni pertinenti:
                                       complies with the following relevant provisions:
                                     folgenden einschlagigen Bestimmungen entspricht:
                                      correspond aux dispositions pertinentes suivantes:
                                       satisface las disposiciones pertinentes siguientes:
                                 zgodny jest z poniżej wyszczególnionymi rozporządzeniami:
    Direttiva sulla compatibilità elettromagnetica (89/336/    Direttiva sulla bassa tensione (73/23/CEE, 93/68/CEE)
    CCE, 93/68/CEE)                                            Low voltage guidelines (73/23/EEC, 93/68/EEC)
    EMC guidelines (89/336/EEC, 93/68/EEC)                     Tiefe Spannung Richtlinie (73/23/EWG, 93/68/EWG)
    EMV-Richtlinie (89/336/EWG, 93/68/EWG)                     Directive bas voltage (73/23/CEE, 93/68/CEE)
    Directive EMV (89/336/CCE, 93/68/CEE) (Compatibilité       Reglamento de bajo Voltaje (73/23/MCE, 93/68/MCE)
    électromagnétique)                                         Wytyczna odnośnie niskiego napięcia (73/23/EWG, 93/
    Reglamento de compatibilidad electromagnética (89/336/     68/EWG)
    MCE, 93/68/MCE)
    Wytyczna odnośnie zdolności współdziałania elektromagne-
    tycznego (89/336/EWG, 93/68/EWG)
    Norme armonizzate applicate in particolare:                Norme armonizzate applicate in particolare:
    Applied harmonized standards, in particular:               Applied harmonized standards, in particular:
    Angewendete harmonisierte Normen, insbesondere:            Angewendete harmonisierte Normen, insbesondere:
    Normes harmonisée utilisées, notamment:                    Normes harmonisée utilisées, notamment:
    Normas armonizadas utilzadas particularmente:              Normas armonizadas utilzadas particularmente:
    Normy standard najczęściej stosowane:                      Normy standard najczęściej stosowane:
    EN 55022, EN 61000-3-2, EN 61000-3-3, EN 50082-1           EN 60204-1, EN 60335-1
    Data/Firma                                                 Data/Firma
                                                                                     Automatismi Benincà Srl
                                                                                     Via Capitello, 45
                                                                                     36066 Sandrigo (VI)
                                                                                     ITALIA
2
                                                     � ��
                                   �               ���
                                   ��              ��� ��
                                   ��
                                                   ���
                                                   ��� ��
     ����
                                                                                      � ���� ���
                                                                                      � ����
                                                            ��                        � �����
                                                                        �           � � ��������
     ��                                                          ���
               ���
                                                                                                                   �����
 �                                                                     �� �� �� ��
��
                               �� �� �� �� ��
��                             ��� ��� ���� ���� ��
                                                                       �� �� �� �� ��
��                                                                                                  ��
��                             ���� ���� ���� ����
��                                                                                        ����
                     ��
          �����
                          � � � � � � � ��                        �� �� �� �� �� �� �� �� ��
           �     �        ����� �� ��� �� �� ��� ��               ����� ���� ���                   ��� ���
                                                                                                  ������
                                                                                                             ���
                                   ����         ����
                                                                             ���
                                                                                           ��
          ������           ����                                             �����         � ���            ���
                                    ��           ��
           ����           ������
                                                                   �����
                                   �           �                  �� ��� ���
                                                                             �����
                                                                            �� ���
                                                                                                                           3
                                           HEAD Control Unit
The electronic control unit HEAD can be used to control 2 motors with a power not exceeding 350+350W.
                                            GENERAL WARNINGS
a) The wire connections and the operating logic should be in compliance with regulations in force.
b) The cables featuring different voltage should be physically detached, or adequately insulated by an additional
   insulation of at least 1 mm.
c) The cables should be further fastened in proximity to the terminals.
d) Check all connections before powering the unit.
e) Check that settings of the Dip-switches are the required ones.
f) The N.C. inputs which are not in use should be short-circuited.
                                        INPUT/OUTPUT FUNCTIONS
 Terminal No.      Function           Description
 1-2               Power supply       Input, 230Vac 50Hz (1-Phase/2-Neutral)
 3-4               Flashing light     Output, flashing light connection, 230Vac 40W max.
 5-6-7             Motor 2            Connection to motor 2 : (5-move/6-Com/7-move)
 8-9-10            Motor 1            Connection to motor 1 : (8-move/9-Com/10-move) – delayed in closing
                                      phase. If only one motor is used, connect Motor 1 output and adjust
                                      TRAC to the minimum value.
 11-12             24 Vac             Output, accessories power supply 24Vac/1A max.
 13-14             Electric lock      Electric lock connection, 12Vac/0,5A max.
 11-15             SCA                Open gate indicator light connection, 24 Vac/3W max.
 16-17             RX 2ch.            Output, second radio channel. N.O. contact, voltage free.
                                      It is enabled with both fixed receiver and expandable two-channel re-
                                      ceiver
 18-19             Aerial             Aerial connection, radio receiver card and incorporated radio module
                                      (18-screen/19-signal).
 20                Pedestrian         Input, N.O. pedestrian push-button
                                      Activation is carried out on motor M1 (8-9-10)
 21                Step-by-Step       Input, N.O. step-by-step push-button
 22                STOP               Input, N.C. STOP push-button
 23                PHOT               Input, safety devices connection, N.C. terminal (e.g. photocells)
 24                +V                 Common to all control inputs.
 25-26-27          0-24-12            Connection to transformer secondary winding
 28-29-30          L1-T1-N1           Connection to transformer primary winding
 J3                Radio receiver     Connector for two-channel radio receiver (optional)
                                             To check connections:
1) Cut-off power supply.
2) Manually release the wings, move them to approx. half-stroke and lock them again.
3) Reset power supply.
4) Send a step-by-step control signal by pressing the button or the remote control key.
5) The wings should start an opening movement. If this is not the case, invert the movement wires of the motor.
   (8/10 for motor M1, and 5/7 for motor M2).
6) Adjust Time, Operating Logic and Motor Power.
                                           To adjust the motor power
WARNING! This adjustment affects the safety of the automatic system.
Check that the thrust applied onto the wing complies with regulations in force.
A Faston (T1) connector is provided on the power supply transformer which allows the power adjustment of the
motors on 4 different levels. By moving the Faston (T1) to 120, power is at minimum, by moving it to 230, power
is at maximum.
Position 230 can be used only with motors complete with adjustable mechanical clutch.
                                                                                                                    7
    In any case, check compliance with regulations in force.
                                               Functions of Trimmers
    TCA        The automatic closure time can be adjusted with this trimmer. Check Dip-switch N°2= On.
               This function can be adjusted between 1 s minimum and 125 s maximum
    TL         The maximum time of the opening and closing phases can be adjusted with this trimmer.
               Time should be preset approx. 4 sec. longer than the actual stroke time of the automatic system.
               Adjustment ranges from 5 s minimum to 130 s maximum
               Note: In the event of partial opening/closing, the control unit calculates the remaining time to
               complete the operation in order to avert useless overheating of the motor.
    TRAC       It allows to adjust the delay time with which motor 1 starts closing with respect to motor 2.
               Adjustment range from 3 s minimum to 30 s maximum. During opening, the out of phase time of the
               motors is 2 seconds.
                                                Dip-Switch functions
    DIP 1   “P.P. Mod”    The operating mode of ”Pulsante P.P.” (Step-by-step push button) and of the transmitter
                          is selected.
                          Off: operation : APRE > STOP > CHIUDE > STOP >
                          On: operation: APRE > CHIUDE > APRE >
    DIP 2   “C.A.”        Automatic closure is enabled or disabled.
                          Off: disabled automatic closure
                          On: enabled automatic closure
    DIP 3   “Cond.”       The multi-flat function is enabled or disabled.
                          Off: disabled multi-flat function.
                          On: enabled multi-flat function. The P.P. (Step-by-step) impulse or the impulse of the
                          transmitter have no effect in the opening phase.
    DIP 4   “Prelam.”     Forewarning flashing light enabled or disabled
                          Off: disabled forewarning flashing light
                          On: enabled forewarning flashing light. The flashing light is activated 3 s before the motor
                          starts.
    Note: After modifying the setting of trimmers and Dip-Switches, switch off and power the unit again.
                                       Configuration of the built-in receiver
    The control unit is complete with an incorporated radio receiver for both fixed-code and variable code radio
    controls, at 433.92MHz frequency.
    To use a radio control, its code should be copied first. The memorization procedure is shown here under. The
    device is able to store up to 14 different codes in memory.
    Memorization of a new transmitter with activation of the P.P. (step-by-step) function
    - Press PGM button once for 2 seconds, the D4 LED starts flashing rapidly.
    - Within 10s, press the transmitter push-button which should be stored in memory with P.P. function.
    Memorization of a new transmitter with activation of 2nd radio channel output (Terminals 16-17)
    - Press button PGM twice, each time for at least 2 seconds, the D4 LED switches on with fixed light.
    - Within 10s, press the transmitter push-button which should be stored in memory with 2nd radio channel
       function.
    To exit the programming mode, wait for 10s or press the PGM button for 2 seconds, the D4 LED flashes regularly
    again.
    To delete the control unit codes from memory
    - Cut-off power supply to the control unit
    - Reset power supply by keeping the PGM button pressed for 5 seconds; the D4 LED switches on with fixed
       light and then off when deletion is completed.
    - Release the PGM button, memory is deleted and the D4 LED starts flashing regularly again.
    NOTE: If the D4 LED switches on with two long flashes and then switches off, when entering the transmitter
    codes memorization mode, this means that the receiver is full and no other transmitter code can be stored in
    memory.
8
                                                LED diagnostics
The control unit is complete with a series of self-diagnostics LED’s which allow checking of all functions:
LED PD     It switches on when the pedestrian push-button is activated
LED PP     It switches on when the step-by-stop push-button is activated
LED SP     It switches off when the STOP push-button is activated
LED PH     It switches off when photocells are not aligned or when obstacles are present
LED D4     Programming of radio-controls. It is usually flashing to indicate the regular operation of the control
           unit.
                                           Advanced programming
The advanced programming permits to activate some special functions:
1) Photocells input, activated in both opening and closure on terminal 22.
   In swing gates, it might be useful to connect the inside photocells (columns) to this terminal and connect the
   outside photocells to input PHOT (terminal 23).
   In this way, the gate opening movement is impaired if the inside photocells detect the presence of an obstacle.
   The outside photocells remain, as usual, activated only in the closing phase.
2) Rapid closure activation. If the photocells are passed by, this function carries out the gate closure after 3s,
   without considering the TCA time. The 2 “CA” Dip-Switch should be positioned to ON.
3) Radio receiver enabled only to variable code transmitters. Any possible programmable code transmitters
   which have been previously installed remain stored in the receiver memory but are deactivated.
To activate the advanced functions, proceed as follows:
1 - Press the PGM button for 2 seconds and then release it - the D4 LED light flashes rapidly
2 - Press the PGM button for 2 seconds and then release it - the D4 LED light stays switched on
3 - Press the PGM button and keep it pressed                - the D4 LED flashes three times and then a pause
    follows
4 - Within 30s, keeping the PGM button pressed, carry out the enabling of the special functions by using the
    following Dip-Switches :
           DIP 1 “STOP/PHOT Opn/Cls”. The operating mode of input 22 is selected with this Dip-Switch.
           On: Terminal 22: Input, photocell activated in both opening and closure
           Off: Terminal 22: Input, STOP push-button
           DIP 2 ”Rapid closure” . This automatic closure is enabled or disabled by this Dip-Switch.
           On: Enabled rapid closure
           Off: Disabled rapid closure
           DIP 3 “Radio”. This enables or disables the programmable code transmitters.
           On: Radio receiver, enabled exclusively for variable code transmitters.
           Off: Receiver, enabled for variable code and programmable code transmitters.
    At end of 30 seconds, the D4 LED stays on, the control unit reads out the position of Dip-Switches 1/2/3 and
    enables or disables the advanced functions.
5 - Release the PGM button - Move the Dip-Switches to the original position.
6 - Cut-off mains power supply and power the unit again.