0% found this document useful (0 votes)
37 views2 pages

Standard Specifications: Alternator Options

The document provides specifications for the P350 generating set model, detailing its output ratings for both prime and standby operations at different voltages and frequencies. It includes technical data about the engine, filtration system, cooling system, exhaust system, and control panel, as well as standard reference conditions and available options and accessories. The document emphasizes the generator's capability to operate in high ambient temperatures and offers customization options to meet specific power needs.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
37 views2 pages

Standard Specifications: Alternator Options

The document provides specifications for the P350 generating set model, detailing its output ratings for both prime and standby operations at different voltages and frequencies. It includes technical data about the engine, filtration system, cooling system, exhaust system, and control panel, as well as standard reference conditions and available options and accessories. The document emphasizes the generator's capability to operate in high ambient temperatures and offers customization options to meet specific power needs.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

ALTERNATOR OPTIONS:

P350
GENERATING SET MODEL (P350)
Output Ratings Prime Standby
380-415 V, 3 ph, 50 Hz, 1500 rpm 350 KVA 400 KVA
280 KW 320 KW
480 V, 3 ph, 60 Hz, 1800 rpm 400 KVA 438 KVA
320 KW 350.4 KW
Alternators ratings may change at different voltages. Ratings at 0.8 Power Factor

ENGINE / TECHNICAL DATA


Engine Make Perkins
Engine Model 2206A-E13TAG2
Governing Type ISO 8528-5 G2
STANDARD SPECIFICATIONS Number of Cylinders 6
1. ENGINE Cylinder Arrangement Vertical in line
Perkins four stroke heavy duty high performance Bore and Stroke mm 130 x 157
industrial type diesel engine. Displacement / Cubic Capacity litres 12.5
2. ENGINE FILTRATION SYSTEM Induction System Turbocharged and air to air charge cooled
• Cartridge type dry air filter. Cycle 4 stroke
• Two Cartridge type fuel filters. Combustion System Direct Injection
• Full flow lube oil filter.
All filters have replaceable elements. Compression Ratio 16.3:1
Rotation Anti-clockwise, viewed on flywheel
3. COOLING RADIATOR Cooling System Water - cooled
Radiator and cooling fan, complete with safety
guards, designed to cool the engine at high ambient Frequency and Engine Speed 50Hz & 1500rpm 60Hz & 1800rpm
temperatures (consult your dealer for de-ration factors) Prime Standby Prime Standby
Gross Engine Power kW 324 (434) 368 (493) 373 (500) 407 (546)
4. EXHAUST SYSTEM
Heavy duty Industrial Exhaust Silencer Fuel Consumption @ %50 load L/hr 37 - 43 -
@ %75 load L/hr 54 - 62 -
Silencer noise reduction level 13 (dB)
@ %100 load L/hr 71 80 81 87
Maximum allowable back pressure 10.0 (kPa)
Total Lubrication System Capacity litres 40 40 40 40
5. CIRCUIT BREAKER TYPE Total Coolant Capacity litres 51.4 51.4 51.4 51.4
ABB 3 pole MCCB. (4 pole is optional) Boost Pressure Ratio 2.8 3.2 3.1 3.4
Exhaust Temperature: °C 630 630 630 660
(contd.) Radiator Cooling Air Flow (Min): m3/sec 9.4 9.4 12.0 12.0
Combustion Air Flow: m3/min 21.3 23.6 27.4 29
CONTROL PANEL Exhaust Gas Flow: m3/min 56.6 64.8 67.5 73.5
Make Deep Sea Fuel Tank Capacity: litres 650 650 650 650
Model DSE6110
The DSE6110 is an Auto Start Control Module for
single genset applications. It includes a backlit LCD
display which clearly shows the status of the engine Leroy Somer
all the times. This module can either be programmed TAL 046H
using the front panel or by using the DSE 1
configuration suite PC software. H
Metering and Alarm indications: <3.5%
• Generator frequency
6
• Underspeed, Overspeed
• Generator volts (L-L, L-N) IP23
• Generator current SHUNT
• Engine oil pressure 2/3 (n° 6)
• Engine coolant temperature
• Fuel level (Warning or shutdown) - Optional
R150
• Hours run counter 2250 mn-1
• Battery volts ± 1%
• Fail to start/stop -
• Emergency stop
PMG Excitation System Available as Optional.
• Failed to reach loading voltage/frequency
• Charge fail
• Loss of magnetic pick-up signal - Optional
• Low DC voltage
• CAN diagnostics and CAN fail/error
(Please refer to DSE6110 brochure for more details) 3770 1300 2000 3174
AN INSPIRED DESIGN TO MEET YOUR NEEDS
STANDARD REFERENCE CONDITIONS
Output ratings are presented at 25°C air inlet temperature, barometric pressure 100 kPa, relative humidity 30%. This generating set is designed to operate at high ambient
temperatures (up to 55°C), humidity (up to 99%) and higher altitudes. De-ration may apply, please consult your dealer for specific site ratings.
Some of the specifications are not standard on all Genset models.

AVAILABLE OPTIONS & ACCESSORIES


We offer a range of optional features and accessories to tailor our generating sets to meet your power needs.
OPTIONS ACCESSORIES
• A variety of generating set control and synchronizing panels • Genuine spare parts
• Additional protection alarms and shutdowns • Load banks
• Water fuel seperator • Auxiliary fuel tanks
• Water jacket heater • Manual & automatic transfer
• Battery charger switches

STANDARD GENERATOR DIAMENSION AND WEIGHT

Silent Type (with Soundproof Canopy)

Open Type (without Soundproof Canopy)

P.O.Box: 14085, China Optical Center Building, Baniyas Square, Deira, Dubai, U.A.E., Tel : +971 4 22 38 253, E-mail : inquiry@azb.ae, Website : www.azb.ae