6/10(12) kV CV (CE Optional)*
IEC 60502-2 (1 CORE)
1. Conductor : Compact round stranded annealed copper wires
2. Conductor screen : Semi-conductive Cross-linked polyethylene (XLPE) compound
3. Insulation : Cross-linked polyethylene (XLPE)
4. Insulation screen : Semi-conductive Cross-linked polyethylene (XLPE) compound
5. Metallic screen : Copper wires and copper contact tape
6. Binding tape : Polyester / Spunbond tape
7. Sheath : Polyvinyl chloride (PVC), ( Optional : PE )*
For general purpose power distribution in dry and wet location, installation in exposed,
in conduit or duct or direct burial in ground.
Conductor Insulation Diameter Sheath Overall Maximum Current Cable Standard
Size Number Diameter thickness over thickness diameter DC. rating weight length
of wires (Approx.) nominal insulation nominal (Approx.) Conductor in air (Approx.)
(Min.) (Approx.) resistance
at 20°C
mm2 mm mm mm. mm mm ohm/km A kg/km m
16 6 4.69 3.4 12.9 1.5 21 1.15 130 530 500
25 6 5.90 3.4 14.1 1.6 22 0.727 170 650 500
35 6 6.95 3.4 15.2 1.6 23 0.524 205 765 500
50 6 8.33 3.4 16.6 1.7 25 0.387 245 920 500
70 12 9.73 3.4 18.0 1.7 27 0.268 305 1140 500
95 15 11.43 3.4 19.7 1.8 29 0.193 375 1435 500
120 18 12.95 3.4 21.2 1.8 30 0.153 435 1695 500
150 18 14.27 3.4 22.5 1.9 32 0.124 495 2040 500
185 30 15.98 3.4 24.2 1.9 33 0.0991 570 2420 500
240 34 18.47 3.4 27.3 2.0 37 0.0754 675 3115 500
300 34 20.68 3.4 29.5 2.1 39 0.0601 780 3750 500
400 53 23.39 3.4 32.3 2.2 42 0.0470 905 4595 500
500 53 26.67 3.4 35.5 2.3 46 0.0366 1055 5790 300
630 53 30.22 3.4 39.1 2.4 50 0.0283 1225 7230 300
800 53 34.00 3.4 42.9 2.5 54 0.0221 1410 8990 250