EGRECO_AENTR2:1:I.0
SIGNAL 3E4DS0-CO03-EVS-MFD-101138_OPN_FB (EVS_FD_ARR_UDT[2].OPN_FB) IS MAPPED TO THIS CHANNEL
1 3E4DS0-CO03-EVS-MFD-101138 3E4DS0-CO03-EVS-MFD-101138_OPN_FB EGRECO_AENTR2:1:I.0.IN SITE ALSO ,CABLE IS CONNECTED TO THIS SAME SIGNAL As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed EGRECO 3E4DS0-EGR-BMS-RIOP-000013 SDI-1 AENTR2 1 2XSDI1 : 1,2 - SDI-16 0 AENTR2:1:I.0 DI I 4/14/2025 DONE
EGRECO_AENTR2:1:I.1
SIGNAL 3E4DS0-CO03-EVS-MFD-101138_CLS_FB_DOOR1 (EVS_FD_ARR_UDT[2].CLS_FB_DOOR1) IS MAPPED TO THIS
2 3E4DS0-CO03-EVS-MFD-101138 3E4DS0-CO03-EVS-MFD-101138_CLS_FB_DOOR1 CHANNEL EGRECO_AENTR2:1:I.1 IN LOGIX,ONLY .IN SITE ALSO,THERE IS NO CABLE IS CONNECTED TO THIS CHANNEL. As per CWG RLM, this channel is spare at site, please check. DOOR CLOSE STATUS EGRECO 3E4DS0-EGR-BMS-RIOP-000013 SDI-1 AENTR2 1 2XSDI1 : 3,4 - SDI-16 1 AENTR2:1:I.1 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-FCC-FDPS-FACP-100003_FACP1_FIRE_ALARM.1 (FACP_ARR_UDT[1].FACP1_FIRE_ALARM.1) IS MAPPED
EGRECO_AENTR2:1:I.2
3 3E4DS0-FCC-FDPS-FACP-100003 3E4DS0-FCC-FDPS-FACP-100003_FACP1_FIRE_ALARM.1 TO THIS CHANNEL EGRECO_AENTR2:1:I.2 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
[FACP-1]
signal
FIREtoALARM
be confirmed
STATION\GRADE ENTRANCE 02 (FIRE ALARM ZONE NO. 4)EGRECO 3E4DS0-EGR-BMS-RIOP-000013 SDI-1 AENTR2 1 2XSDI1 : 5,6 - SDI-16 2 AENTR2:1:I.2 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-FCC-FDPS-FACP-100003_FACP1_FIRE_ALARM.2 (FACP_ARR_UDT[1].FACP1_FIRE_ALARM.2) IS MAPPED
EGRECO_AENTR2:1:I.3
4 3E4DS0-FCC-FDPS-FACP-100003 3E4DS0-FCC-FDPS-FACP-100003_FACP1_FIRE_ALARM.2 TO THIS CHANNEL EGRECO_AENTR2:1:I.3 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
[FACP-1]
signal
FIREtoALARM
be confirmed
STATION\GRADE ENTRANCE 03 (FIRE ALARM ZONE NO. 5)EGRECO 3E4DS0-EGR-BMS-RIOP-000013 SDI-1 AENTR2 1 2XSDI1 : 7,8 - SDI-16 3 AENTR2:1:I.3 DI I 4/14/2025 DONE
EGRECO_AENTR1:1:I.0
SIGNAL 3E4DS0-GR-HVAC-FAN-070000_TRIP_FB (FAN_ARR_UDT[6].TRIP_FB) IS MAPPED TO THIS CHANNEL
81 3E4DS0-GR-HVAC-FAN-070000 3E4DS0-GR-HVAC-FAN-070000_TRIP_FB EGRECO_AENTR1:1:I.Data.0 .IN SITE,ALSO IT IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
EXHAUST
be confirmed
FAN EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-3 AENTR1 1 2XDI3 : 1,2 - DI-32 0 AENTR1:1:I.Data.0 DI I 4/14/2025 DONE
EGRECO_AENTR1:1:I.1
SIGNAL 3E4DS0-GR-HVAC-FAN-070000_LOC_FB (FAN_ARR_UDT[6].LOC_FB) IS MAPPED TO THIS CHANNEL
82 3E4DS0-GR-HVAC-FAN-070000 3E4DS0-GR-HVAC-FAN-070000_LOC_FB EGRECO_AENTR1:1:I.Data.1 .IN SITE,ALSO IT IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalSWITCH
to be confirmed
EXHAUST FAN EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-3 AENTR1 1 2XDI3 : 3,4 - DI-32 1 AENTR1:1:I.Data.1 DI I 4/14/2025 DONE
EGRECO_AENTR1:1:I.2
SIGNAL 3E4DS0-GR-HVAC-FAN-070000_REM_FB (FAN_ARR_UDT[6].REM_FB) IS MAPPED TO THIS CHANNEL
83 3E4DS0-GR-HVAC-FAN-070000 3E4DS0-GR-HVAC-FAN-070000_REM_FB EGRECO_AENTR1:1:I.Data.2 .IN SITE,ALSO IT IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalSWITCH
to be confirmed
EXHAUST FAN EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-3 AENTR1 1 2XDI3 : 5,6 - DI-32 2 AENTR1:1:I.Data.2 DI I 4/14/2025 DONE
EGRECO_AENTR1:1:I.3
SIGNAL 3E4DS0-GR-HVAC-FAN-070000_RUN_FB (FAN_ARR_UDT[6].RUN_FB) IS MAPPED TO THIS CHANNEL
84 3E4DS0-GR-HVAC-FAN-070000 3E4DS0-GR-HVAC-FAN-070000_RUN_FB EGRECO_AENTR1:1:I.Data.3 .IN SITE,ALSO IT IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
RUNNING
signal
OFtoEXHAUST
be confirmed
FAN EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-3 AENTR1 1 2XDI3 : 7,8 - DI-32 3 AENTR1:1:I.Data.3 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-GR-ELS-FULG-000001 RETURN FLOW LEAK DETECTION(FUT_ARR_UDT[1].TANK_1_RET_LD) IS
CONNECTED TO THIS CHANNEL EGRECO_AENTR1:1:I.Data.12 IN LOGIX.IN SITE ALSO,CABLE IS CONNECTED TO THIE
EGRECO_AENTR1:1:I.12
SAME SIGNAL.AS PER LATEST SIGNAL LIST REV 13.07,IF THIS SIGNAL IS N/A.THIS NEED TO BE REMOVED FROM LOGIX
93 SPARE SPARE AND SITE ASWELL. As per CWG RLM, this channel is used at site, please check. SPARE EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-3 AENTR1 1 2XDI3 : 25,26 - DI-32 12 AENTR1:1:I.Data.12 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-GR-HVAC-FAN-080000_TRIP_FB (FAN_ARR_UDT[7].TRIP_FB) IS MAPPED TO THIS CHANNEL
EGRECO_AENTR1:5:I.0
113 3E4DS0-GR-HVAC-FAN-080000 3E4DS0-GR-HVAC-FAN-080000_TRIP_FB EGRECO_AENTR1:5:I.Data.0 .IN SITE ALSO,IT IS CONNECTED TO THE SAME SIGNAL As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
EXHAUST
be confirmed
FAN EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-4 AENTR1 5 2XDI4 : 1,2 - DI-32 0 AENTR1:5:I.Data.0 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-GR-HVAC-FAN-080000_LOC_FB (FAN_ARR_UDT[7].LOC_FB) IS MAPPED TO THIS CHANNEL
EGRECO_AENTR1:5:I.1
114 3E4DS0-GR-HVAC-FAN-080000 3E4DS0-GR-HVAC-FAN-080000_LOC_FB EGRECO_AENTR1:5:I.Data.1 ..IN SITE ALSO,IT IS CONNECTED TO THE SAME SIGNAL As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalSWITCH
to be confirmed
EXHAUST FAN EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-4 AENTR1 5 2XDI4 : 3,4 - DI-32 1 AENTR1:5:I.Data.1 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-GR-HVAC-FAN-080000_REM_FB IS MAPPED TO THE CHANNEL EGRECO_AENTR1:5:I.Data.2 .IN SITE
EGRECO_AENTR1:5:I.2
115 3E4DS0-GR-HVAC-FAN-080000 3E4DS0-GR-HVAC-FAN-080000_REM_FB ALSO,IT IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalSWITCH
to be confirmed
EXHAUST FAN EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-4 AENTR1 5 2XDI4 : 5,6 - DI-32 2 AENTR1:5:I.Data.2 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-GR-HVAC-FAN-080000_RUN_FB IS MAPPED TO THE CHANNEL EGRECO_AENTR1:5:I.Data.3 .IN SITE
EGRECO_AENTR1:5:I.3
116 3E4DS0-GR-HVAC-FAN-080000 3E4DS0-GR-HVAC-FAN-080000_RUN_FB ALSO,IT IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
RUNNING
signal
OFtoEXHAUST
be confirmed
FAN EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-4 AENTR1 5 2XDI4 : 7,8 - DI-32 3 AENTR1:5:I.Data.3 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-GR-POS-DGFS-000001_FLOW_FB (DG_ARR_UDT[1].FLOW_FB) IS MAPPED TO THIS CHANNEL
EGRECO_AENTR1:5:I.22
135 3E4DS0-GR-POS-DGFS-000001 3E4DS0-GR-POS-DGFS-000001_FLOW_FB EGRECO_AENTR1:5:I.Data.22 .IN SITE ALSO,IT IS CONNECTED TO THE SAME SIGNAL As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Chilledsignal
waterto
supply
be confirmed
flow EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-4 AENTR1 5 2XDI4 : 45,46 - DI-32 22 AENTR1:5:I.Data.22 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-GR-POS-DGFS-000002_FLOW_FB (DG_ARR_UDT[2].FLOW_FB) IS MAPPED TO THIS CHANNEL
EGRECO_AENTR1:5:I.23
136 3E4DS0-GR-POS-DGFS-000002 3E4DS0-GR-POS-DGFS-000002_FLOW_FB EGRECO_AENTR1:5:I.Data.23 .IN SITE ALSO,IT IS CONNECTED TO THE SAME SIGNAL As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Chilledsignal
waterto
supply
be confirmed
flow EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-4 AENTR1 5 2XDI4 : 47,48 - DI-32 23 AENTR1:5:I.Data.23 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-GR-HVAC-FAN-070000_ON_OFF_CMD (FAN_ARR_UDT[6].ON_OFF_CMD) IS MAPPED TO THIS RELAY
EGRECO_AENTR1:2:O.4
149 3E4DS0-GR-HVAC-FAN-070000 3E4DS0-GR-HVAC-FAN-070000_ON_OFF_CMD EGRECO_AENTR1:2:O.Data.4 .IN SITE,ALSO CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
EXHAUST
be confirmed
FAN EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DO-1 AENTR1 2 - 2R5 : 11,14 DO-32 4 AENTR1:2:O.Data.4 DO O 4/14/2025 DONE
SIGNAL 3E4DS0-GR-HVAC-FAN-080000_ON_OFF_CMD (FAN_ARR_UDT[7].ON_OFF_CMD) IS MAPPED TO THIS RELAY
EGRECO_AENTR1:2:O.5
150 3E4DS0-GR-HVAC-FAN-080000 3E4DS0-GR-HVAC-FAN-080000_ON_OFF_CMD EGRECO_AENTR1:2:O.Data.5 .IN SITE,ALSO CABLE IS CONNECTED TO THE SAME As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
EXHAUST
be confirmed
FAN EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DO-1 AENTR1 2 - 2R6 : 11,14 DO-32 5 AENTR1:2:O.Data.5 DO O 4/14/2025 DONE
SIGNAL 3E4DS0-GR-POS-GSMP-000001-INC1_CLS_CMD (GMP_INC_ARR_UDT[1].CLS_CMD) IS MAPPED TO THIS RELAY
EGRECO_AENTR1:2:O.15
160 3E4DS0-GR-POS-GSMP-000001-INC1 3E4DS0-GR-POS-GSMP-000001-INC1_CLS_CMD EGRECO_AENTR1:2:O.Data.15 .IN SITE ALSO,CABLE IS CONNECTED TO THIS SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
INCOMING
to be confirmed
FROM GENERATOR EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DO-1 AENTR1 2 - 2R16 : 11,14 DO-32 15 AENTR1:2:O.Data.15 DO O 4/14/2025 DONE
ELE03EPO_AENTR2:0:I.13
SIGNAL 3E4DS0-ELE01-ELS-PPB-002101_INC_OPN_CLS_FB (PPB_ICB_ARR_UDT[1].INC_OPN_CLS_FB) IS MAPPED TO THIS
46 3E4DS0-ELE01-ELS-PPB-002101 3E4DS0-ELE01-ELS-PPB-002101_INC_OPN_CLS_FB CHANNEL ELE03EPO_AENTR2:0:I.Data.13 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
INCOMING
signalCIRCUIT
to be confirmed
TO PP ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 DI-1 AENTR2 0 1XDI1 : 27,28 - DI-32 13 AENTR2:0:I.Data.13 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-ELE01-HVAC-WLKD-000031_LEAK_ALM (WLKD_ARR_UDT[31].LEAK_ALM) IS MAPPED TO THIS CHANNEL
ELE03EPO_AENTR2:0:I.14
47 3E4DS0-ELE01-HVAC-WLKD-000031 3E4DS0-ELE01-HVAC-WLKD-000031_LEAK_ALM ELE03EPO_AENTR2:0:I.Data.14 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WATERsignal
LEAKto
DETECTION
be confirmed ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 DI-1 AENTR2 0 1XDI1 : 29,30 - DI-32 14 AENTR2:0:I.Data.14 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-ELE03-HVAC-WLKD-000033_LEAK_ALM (WLKD_ARR_UDT[33].LEAK_ALM) IS MAPPED TO THIS CHANNEL
ELE03EPO_AENTR2:0:I.15
48 3E4DS0-ELE03-HVAC-WLKD-000033 3E4DS0-ELE03-HVAC-WLKD-000033_LEAK_ALM ELE03EPO_AENTR2:0:I.Data.15.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WATERsignal
LEAKto
DETECTION
be confirmed ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 DI-1 AENTR2 0 1XDI1 : 31,32 - DI-32 15 AENTR2:0:I.Data.15 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-PSD-HVAC-WLKD-000034_LEAK_ALM (WLKD_ARR_UDT[34].LEAK_ALM) IS MAPPED TO THIS CHANNEL
ELE03EPO_AENTR2:0:I.16
49 3E4DS0-PSD-HVAC-WLKD-000034 3E4DS0-PSD-HVAC-WLKD-000034_LEAK_ALM ELE03EPO_AENTR2:0:I.Data.16.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WATERsignal
LEAKto
DETECTION
be confirmed ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 DI-1 AENTR2 0 1XDI1 : 33,34 - DI-32 16 AENTR2:0:I.Data.16 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-RCR-HVAC-WLKD-000035_LEAK_ALM (WLKD_ARR_UDT[35].LEAK_ALM) IS MAPPED TO THIS CHANNEL
ELE03EPO_AENTR2:0:I.17
50 3E4DS0-RCR-HVAC-WLKD-000035 3E4DS0-RCR-HVAC-WLKD-000035_LEAK_ALM ELE03EPO_AENTR2:0:I.Data.17.IN SITE ALSO,CABLE IS MAPPED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WATERsignal
LEAKto
DETECTION
be confirmed ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 DI-1 AENTR2 0 1XDI1 : 35,36 - DI-32 17 AENTR2:0:I.Data.17 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-RCR-HVAC-WLKD-000036_LEAK_ALM (WLKD_ARR_UDT[36].LEAK_ALM) IS MAPPED TO THIS CHANNEL
ELE03EPO_AENTR2:0:I.18
51 3E4DS0-RCR-HVAC-WLKD-000036 3E4DS0-RCR-HVAC-WLKD-000036_LEAK_ALM ELE03EPO_AENTR2:0:I.Data.18 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WATERsignal
LEAKto
DETECTION
be confirmed ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 DI-1 AENTR2 0 1XDI1 : 37,38 - DI-32 18 AENTR2:0:I.Data.18 DI I 4/14/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL ELE03EPO_AENTR2:0:I.Data.27.IN SITE,IT IS A EXTRA CABLE.WHICH
ELE03EPO_AENTR2:0:I.27
60 3E4DS0-ELE01-HVAC-MFD-014127 3E4DS0-ELE01-HVAC-MFD-014127_OPN_FB NEED TO BE REMOVED FROM SITE. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTORIZED
signal to
FIRE
beDAMPER
confirmed
FM200 OPEN ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 DI-1 AENTR2 0 1XDI1 : 55,56 - DI-32 27 AENTR2:0:I.Data.27 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-ELE01-HVAC-MFD-014111_OPN_FB (HVAC_FD_ARR_UDT[83].OPN_FB) IS MAPPED TO THIS CHANNEL
ELE03EPO_AENTR2:0:I.28
61 3E4DS0-ELE01-HVAC-MFD-014111 3E4DS0-ELE01-HVAC-MFD-014111_OPN_FB ELE03EPO_AENTR2:0:I.Data.28 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTORIZED
signal to
FIRE
beDAMPER
confirmed
FM200 OPEN ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 DI-1 AENTR2 0 1XDI1 : 57,58 - DI-32 28 AENTR2:0:I.Data.28 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-ELE01-HVAC-MFD-014118_OPN_FB(HVAC_FD_ARR_UDT[84].OPN_FB) IS MAPPED TO THIS CHANNEL
ELE03EPO_AENTR2:0:I.29
62 3E4DS0-ELE01-HVAC-MFD-014118 3E4DS0-ELE01-HVAC-MFD-014118_OPN_FB ELE03EPO_AENTR2:0:I.Data.29 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTORIZED
signal to
FIRE
beDAMPER
confirmed
FM200 OPEN ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 DI-1 AENTR2 0 1XDI1 : 59,60 - DI-32 29 AENTR2:0:I.Data.29 DI I 4/14/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL ELE03EPO_AENTR2:0:I.Data.30.IN SITE,IT IS A EXTRA CABLE.WHICH
ELE03EPO_AENTR2:0:I.30
63 3E4DS0-ELE01-HVAC-MFD-014134 3E4DS0-ELE01-HVAC-MFD-014134_OPN_FB NEED TO BE REMOVED FROM SITE. As per CWG RLM, this channel is spare at site, please check. MOTORIZED FIRE DAMPER FM200 OPEN ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 DI-1 AENTR2 0 1XDI1 : 61,62 - DI-32 30 AENTR2:0:I.Data.30 DI I 4/14/2025 DONE
IN LOGIX ,SIGNAL 3E4DS0-STT-HVAC-FAN-050000_OPN_FB(FAN_ARR_UDT[4].OPN_FB) IS MAPPED TO THIS CHANNEL
MOTORIZED FIRE DAMPERS NON FM200 OPEN FPRWCO_AENTR1:0:I.25
26 3E4DS0-STT-HVAC-FAN-050000 3E4DS0-STT-HVAC-FAN-050000_OPN_FB FPRWCO_AENTR1:0:I.Data.25 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed FPRWCO 3E4DS0-FPR-BMS-RIOP-000005 DI-1 AENTR1 0 1XDI1 : 51,52 - DI-32 25 AENTR1:0:I.Data.25 DI I 4/14/2025 DONE
IN LOGIX,SIGNAL 3E4DS0-TRR-HVAC-FAN-060000_OPN_FB (FAN_ARR_UDT[5].OPN_FB) IS MAPPED TO THIS CHANNEL
MOTORIZED FIRE DAMPERS NON FM200 OPEN FPRWCO_AENTR1:0:I.26
27 3E4DS0-TRR-HVAC-FAN-060000 3E4DS0-TRR-HVAC-FAN-060000_OPN_FB FPRWCO_AENTR1:0:I.Data.26.IN SITE ALSO ,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed FPRWCO 3E4DS0-FPR-BMS-RIOP-000005 DI-1 AENTR1 0 1XDI1 : 53,54 - DI-32 26 AENTR1:0:I.Data.26 DI I 4/14/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,IT IS A EXTRA CABLE.WHICH NEED TO BE REMOVED FROM
LV01ETO_AENTR1:1:I.4
37 SPARE SPARE SITE. As per CWG RLM, this channel is used at site, please check. SPARE LV01ETO 3E4DS0-LV01-BMS-RIOP-000021 DI-2 AENTR1 1 2XDI2 : 9,10 - DI-32 4 AENTR1:1:I.Data.4 DI I 4/14/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,IT IS A EXTRA CABLE.WHICH NEED TO BE REMOVED FROM
LV01ETO_AENTR1:2:I.4
69 SPARE SPARE SITE. As per CWG RLM, this channel is used at site, please check. SPARE LV01ETO 3E4DS0-LV01-BMS-RIOP-000021 DI-3 AENTR1 2 2XDI3 : 9,10 - DI-32 4 AENTR1:2:I.Data.4 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-LV01-ELS-MDB-001001-AUT1_REM_FB (MDB_OG_ARR_UDT[2].REM_FB) IS MAPPED TO THIS CHANNEL
LV01ETO_AENTR1:3:I.3
100 3E4DS0-LV01-ELS-MDB-001001-AUT1 3E4DS0-LV01-ELS-MDB-001001-AUT1_REM_FB LV01ETO_AENTR1:3:I.Data.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Auto Status
signalincoming
to be confirmed
breaker from AUT LV01ETO 3E4DS0-LV01-BMS-RIOP-000021 DI-4 AENTR1 3 2XDI4 : 7,8 - DI-32 3 AENTR1:3:I.Data.3 DI I 4/14/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,IT IS A EXTRA CABLE.WHICH NEED TO BE REMOVED FROM
LV02ETO_AENTR1:0:I.4
5 SPARE SPARE SITE. As per CWG RLM, this channel is used at site, please check. SPARE LV02ETO 3E4DS0-LV02-BMS-RIOP-000022 DI-1 AENTR1 0 2XDI1 : 9,10 - DI-32 4 AENTR1:0:I.Data.4 DI I 4/14/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,IT IS A EXTRA CABLE.WHICH NEED TO BE REMOVED FROM
LV02ETO_AENTR2:0:I.4
37 SPARE SPARE SITE. As per CWG RLM, this channel is used at site, please check. SPARE LV02ETO 3E4DS0-LV02-BMS-RIOP-000022 DI-2 AENTR2 0 2XDI2 : 9,10 - DI-32 4 AENTR2:0:I.Data.4 DI I 4/14/2025 DONE
3E4DS0-LV02-ELS-MDB-002001_TR3_REM_FB (MDB_INC_ARR_UDT[3].REM_FB) IS MAPPED ONLY IN LOGIX.IN
LV02ETO_AENTR2:2:I.19
180 3E4DS0-LV02-ELS-MDB-002001 3E4DS0-LV02-ELS-MDB-002001_REM_FB SITE,THERE IS NO PROVISION THIS SIGNAL & THERE IS NO CABLE CONNECTED TO THIS TERMINAL. As per CWG RLM, this channel is spare at site, please check. Auto Status incoming breaker from TR3 LV02ETO 3E4DS0-LV02-BMS-RIOP-000022 DI-6 AENTR2 2 2XDI6 : 39,40 - DI-32 19 AENTR2:2:I.Data.19 DI I 4/14/2025 DONE
3E4DS0-LV02-ELS-MDB-002001_TR4_REM_FB (MDB_INC_ARR_UDT[4].REM_FB) IS MAPPED ONLY IN LOGIX.IN
LV02ETO_AENTR2:2:I.20
181 3E4DS0-LV02-ELS-MDB-002001 3E4DS0-LV02-ELS-MDB-002001_REM_FB SITE,THERE IS NO PROVISION FOR THIS SIGNAL & THERE IS NO CABLE CONNECTED TO THIS TERMINAL. As per CWG RLM, this channel is spare at site, please check. Auto Status incoming breaker from TR4 LV02ETO 3E4DS0-LV02-BMS-RIOP-000022 DI-6 AENTR2 2 2XDI6 : 41,42 - DI-32 20 AENTR2:2:I.Data.20 DI I 4/14/2025 DONE
# General
PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR1:0:I.0
SIGNAL 3E4DS0-MER01-HVAC-AHU-110000_SF_TRIP (S_AHU_ARR_UDT[10].SF_TRIP) IS MAPPED TO THIS CHANNEL
33 3E4DS0-MER01-HVAC-AHU-110000 3E4DS0-MER01-HVAC-AHU-110000_SF_TRIP MER01WCO_AENTR1:0:I.0 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. TRIP STATUS SUPPLY FAN MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DI-1 AENTR1 0 1XDI1 : 1,2 - DI-16 0 AENTR1:0:I.0 DI I 4/14/2025 DONE
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR1:0:I.1
SIGNAL 3E4DS0-MER01-HVAC-AHU-110000_SF_LOC (S_AHU_ARR_UDT[10].SF_LOC) IS MAPPED TO THIS CHANNEL
34 3E4DS0-MER01-HVAC-AHU-110000 3E4DS0-MER01-HVAC-AHU-110000_SF_LOC MER01WCO_AENTR1:0:I.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. HAND/OFF SWITCH SUPPLY FAN MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DI-1 AENTR1 0 1XDI1 : 3,4 - DI-16 1 AENTR1:0:I.1 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER01-HVAC-AHU-110000_SF_REM(S_AHU_ARR_UDT[10].SF_REM) IS MAPPED TO THIS SIGNAL
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR1:0:I.2
35 3E4DS0-MER01-HVAC-AHU-110000 3E4DS0-MER01-HVAC-AHU-110000_SF_REM MER01WCO_AENTR1:0:I.2 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. AUTO/OFF SWITCH SUPPLY FAN MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DI-1 AENTR1 0 1XDI1 : 5,6 - DI-16 2 AENTR1:0:I.2 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER01-HVAC-AHU-110000_SF_RUN_FB (S_AHU_ARR_UDT[10].SF_RUN_FB) IS MAPPED TO THIS
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR1:0:I.3
36 3E4DS0-MER01-HVAC-AHU-110000 3E4DS0-MER01-HVAC-AHU-110000_SF_RUN_FB CHANNEL MER01WCO_AENTR1:0:I.3..IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. AHU Power Supply On/Off Status MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DI-1 AENTR1 0 1XDI1 : 7,8 - DI-16 3 AENTR1:0:I.3 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER01-HVAC-AHU-110000_EC_TRIP (S_AHU_ARR_UDT[10].EC_TRIP) IS MAPPED TO THIS CHANNEL
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR1:0:I.4
37 3E4DS0-MER01-HVAC-AHU-110000 3E4DS0-MER01-HVAC-AHU-110000_EC_TRIP MER01WCO_AENTR1:0:I.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. ELECTRICAL COIL TRIP STATUS MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DI-1 AENTR1 0 1XDI1 : 9,10 - DI-16 4 AENTR1:0:I.4 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER01-HVAC-AHU-110000_EC_OH_PROT(S_AHU_ARR_UDT[10].EC_OH_PROT) IS MAPPED TO THIS
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR1:0:I.5
38 3E4DS0-MER01-HVAC-AHU-110000 3E4DS0-MER01-HVAC-AHU-110000_EC_OH_PROT CHANNEL MER01WCO_AENTR1:0:I.5 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. ELECTRICAL COIL OVERHEAT PROTECTION MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DI-1 AENTR1 0 1XDI1 : 11,12 - DI-16 5 AENTR1:0:I.5 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER01-HVAC-AHUSFDPS-110001_SF_DPS_FB(S_AHU_ARR_UDT[10].SF_DPS_FB) IS MAPPED TO THIS
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR1:0:I.7
40 3E4DS0-MER01-HVAC-AHUSFDPS-110001 3E4DS0-MER01-HVAC-AHUSFDPS-110001_SF_DPS_FB CHANNEL MER01WCO_AENTR1:0:I.7..IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. SUPPLY FAN PROOF OF FLOW MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DI-1 AENTR1 0 1XDI1 : 15,16 - DI-16 7 AENTR1:0:I.7 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER01-HVAC-AHU-110000_OPN_FB(S_AHU_ARR_UDT[10].OPN_FB) IS MAPPED TO THIS CHANNEL
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTORIZED
signal to
FIRE
beDAMPERS
confirmedNON FM200 MER01WCO_AENTR1:0:I.9
42 3E4DS0-MER01-HVAC-AHU-110000 3E4DS0-MER01-HVAC-AHU-110000_OPN_FB MER01WCO_AENTR1:0:I.9 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DI-1 AENTR1 0 1XDI1 : 19,20 - DI-16 9 AENTR1:0:I.9 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER01-HVAC-AHU-110000_SF_SPD_CMD (S_AHU_ARR_UDT[10].SF_SPD_CMD) IS MAPPED TO THIS As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR1:3:chdata.2
83 3E4DS0-MER01-HVAC-AHU-110000 3E4DS0-MER01-HVAC-AHU-110000_SF_SPD_CMD CHANNEL MER01WCO_AENTR1:3:O.Ch2Data .IN SITE ALSO,THE CABLE IS CONNECTED TO THE SAME SIGNAL. SUPPLY FAN SPEED CONTROL MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 AO-1 AENTR1 3 1XAO1 : 5,6 - AO-12 2 AENTR1:3:O.Ch2Data AO chdata 4/14/2025 DONE
IN LOGIX ALSO,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE ALSO THERE IS NO CABLE CONNECTED TO THIS
CHANNEL.SIGNAL (3E4DS0-MER01-HVAC-AHU-110000_SF_ON_OFF_CMD) (S_AHU_ARR_UDT[10].SF_ON_OFF_CMD) IS
MER01WCO_AENTR1:3:chdata.4
MAPPED TO THIS RELAY MER01WCO_AENTR1:4:O.1 IN LOGIX.IN SITE ALSO,CABLE IS CONNECTED TO THIS RELAY
85 3E4DS0-MER01-HVAC-AHU-110000 3E4DS0-MER01-HVAC-AHU-110000_SF_ON_OFF_CMD MER01WCO_AENTR1:4:O.1 As per CWG RLM, this channel is spare at site, please check. Switch On AHU Power Supply MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 AO-1 AENTR1 3 1XAO1 : 9,10 - AO-12 4 AENTR1:3:O.Ch4Data AO chdata 4/14/2025 DONE
3E4DS0-MER01-HVAC-AHU-110000_EC_ON_CMD (S_AHU_ARR_UDT[10].EC_ON_CMD) IS MAPPED TO THIS RELAY
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR1:4:O.0
93 3E4DS0-MER01-HVAC-AHU-110000 3E4DS0-MER01-HVAC-AHU-110000_EC_ON_CMD MER01WCO_AENTR1:4:O.0 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME RELAY. SWITCH ON ELECTRICAL COIL MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DO-1 AENTR1 4 - 1R1 : 11,14 DO-16 0 AENTR1:4:O.0 DO O 4/14/2025 DONE
SIGNAL (3E4DS0-MER01-HVAC-AHU-110000_SF_ON_OFF_CMD) (S_AHU_ARR_UDT[10].SF_ON_OFF_CMD) IS MAPPED
TO THIS RELAY MER01WCO_AENTR1:4:O.1 IN LOGIX.IN SITE ALSO,CABLE IS CONNECTED TO THIS RELAY MER01WCO_AENTR1:4:O.1
94 SPARE SPARE MER01WCO_AENTR1:4:O.1 As per CWG RLM, this channel is used at site, please check. SPARE MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DO-1 AENTR1 4 - 1R2 : 11,14 DO-16 1 AENTR1:4:O.1 DO O 4/14/2025 DONE
SIGNAL 3E4DS0-MER02-HVAC-AHU-010000_EC_ON_CMD (S_AHU_ARR_UDT[1].EC_ON_CMD) IS MAPPED TO THE RELAY
MER02WCO_AENTR1:0:O.2
3 3E4DS0-MER02-HVAC-AHU-010000 3E4DS0-MER02-HVAC-AHU-010000_EC_ON_CMD MER02WCO_AENTR1:0:O.2 .IN SITE ALSO CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
SWITCHsignal
ON ELECTRICAL
to be confirmed
COIL MER02WCO 3E4DS0-MER02-BMS-RIOP-000006 DO-1 AENTR1 0 - 1R3 : 11,14 DO-16 2 AENTR1:0:O.2 DO O 4/14/2025 DONE
# General
PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM
MER04WCO_AENTR2:1:O.3
SIGNAL 3E4DS0-CA-EVS-SPR-050002_ON_OFF_CMD (SPR_ARR_UDT[6].ON_OFF_CMD) IS MAPPED TO THIS
RELAY,SE02WCO_AENTR1:2:O.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.IN LOGIX,THERE IS NO
36 3E4DS0-CA-EVS-SPR-050002 3E4DS0-CA-EVS-SPR-050002_ON_OFF_CMD MAPPING TO THIS RELAY,MER04WCO_AENTR2:1:O.3.IN SITE ALSO,THERE IS NO CABLE CONNECTED TO THIS RELAY. As per CWG RLM, this channel is spare at site, please check. START/STOP ELEVATOR PRESSURIZATION FAN MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDO-1 AENTR2 1 - 1SR4 : 11,14 SDO-16 3 AENTR2:1:O.3 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-CA-EVS-MFD-731215_OPN_CLS_CMD (EVS_FD_ARR_UDT[20].OPN_CLS_CMD) IS MAPPED TO THIS
MER04WCO_AENTR2:1:O.6
39 3E4DS0-CA-EVS-MFD-731215 3E4DS0-CA-EVS-MFD-731215_OPN_CLS_CMD RELAY,MER04WCO_AENTR2:1:O.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN COMMAND
signal to be confirmed MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDO-1 AENTR2 1 - 1SR7 : 11,14 SDO-16 6 AENTR2:1:O.6 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-EST01-EVS-MFD-561206_OPN_CLS_CMD (EVS_FD_ARR_UDT[11].OPN_CLS_CMD) IS MAPPED TO THIS
MER04WCO_AENTR2:1:O.8
41 3E4DS0-EST01-EVS-MFD-561206 3E4DS0-EST01-EVS-MFD-561206_OPN_CLS_CMD RELAY,MER04WCO_AENTR2:1:O.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN COMMAND
signal to be confirmed MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDO-1 AENTR2 1 - 1SR9 : 11,14 SDO-16 8 AENTR2:1:O.8 DO O 4/15/2025 DONE
# General
PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM
# General
PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM
MERWMO_AENTR3:1:O.1
SIGNAL Open MFD-644028 Platform ( EVS_FD_ARR_UDT[17].OPN_CLS_CMD) IS MAPPED TO THIS RELAY
18 SPARE SPARE MERWMO_AENTR3:1:O.1 .IN SITE ALSO,CABLE IS CONNECTED TO THIS RELAY. As per CWG RLM, this channel is used at site, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 SDO-1 AENTR3 1 - 2SR2 : 11,14 SDO-16 1 AENTR3:1:O.1 DO O 4/17/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-MAU-040000 RF RUN FB ( D_MAU_ARR_UDT[1].RF_RUN_FB )IS MAPPED TO THIS CHANNEL
MERWMO_AENTR1:0:I.7
40 SPARE SPARE MERWMO_AENTR1:0:I.7 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DI-1 AENTR1 0 2XDI1 : 15,16 - DI-16 7 AENTR1:0:I.7 DI I 4/17/2025 DONE
MERWMO_AENTR1:0:I.13
46 SPARE SPARE IN LOGIX ALSO,THERE IS NO MAPPING.IN SITE,EXTRA CABLE IS CONNECTED TO THIS TERMINAL. As per CWG RLM, this channel is used at site, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DI-1 AENTR1 0 2XDI1 : 27,28 - DI-16 13 AENTR1:0:I.13 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-MAU-020000_OPN_FB (S_MAU_ARR_UDT[2].OPN_FB) IS MAPPED TO THIS CHANNEL
NON FM200 MFD LOOP MERWMO_AENTR2:0:I.14
63 3E4DS0-MER-HVAC-MAU-020000 3E4DS0-MER-HVAC-MAU-020000_OPN_FB MERWMO_AENTR2:0:I.Data.14 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MERWMO 3E4DS0-MER-BMS-RIOP-000024 DI-2 AENTR2 0 2XDI2 : 29,30 - DI-32 14 AENTR2:0:I.Data.14 DI I 4/17/2025 DONE
MERWMO_AENTR2:0:I.18
67 SPARE SPARE IN LOGIX ALSO,THERE IS NO MAPPING.IN SITE,EXTRA CABLE IS CONNECTED TO THIS TERMINAL. As per CWG RLM, this channel is used at site, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DI-2 AENTR2 0 2XDI2 : 37,38 - DI-32 18 AENTR2:0:I.Data.18 DI I 4/17/2025 DONE
MERWMO_AENTR2:0:I.19
SIGNAL 3E4DS0-MER-ELS-MCC-002005_INC_OPN_CLS_FB (MCC_ICB_ARR_UDT[6].INC_OPN_CLS_FB) IS MAPPED TO
68 3E4DS0-MER-ELS-MCC-002005 3E4DS0-MER-ELS-MCC-002005_INC_OPN_CLS_FB THIS CHANNEL MERWMO_AENTR2:0:I.Data.19 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
INCOMING
signalCIRCUIT
to be confirmed
01 MERWMO 3E4DS0-MER-BMS-RIOP-000024 DI-2 AENTR2 0 2XDI2 : 39,40 - DI-32 19 AENTR2:0:I.Data.19 DI I 4/17/2025 DONE
MERWMO_AENTR2:0:I.22
SIGNAL AHU-6 (S_AHU_ARR_UDT[6].OPN_FB) IS MAPPED TO THIS CHANNEL MERWMO_AENTR2:0:I.Data.22 . IN SITE
71 SPARE SPARE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DI-2 AENTR2 0 2XDI2 : 45,46 - DI-32 22 AENTR2:0:I.Data.22 DI I 4/17/2025 DONE
MERWMO_AENTR2:0:I.23
SIGNAL AHU-7 (S_AHU_ARR_UDT[7].OPN_FB) IS MAPPED TO THIS CHANNEL MERWMO_AENTR2:0:I.Data.23. IN SITE
72 SPARE SPARE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DI-2 AENTR2 0 2XDI2 : 47,48 - DI-32 23 AENTR2:0:I.Data.23 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-AHU-070000_EC_OH_PROT (S_AHU_ARR_UDT[7].EC_OH_PROT) IS MAPPED TO THIS
MERWMO_AENTR1:1:I.5
86 3E4DS0-MER-HVAC-AHU-070000 3E4DS0-MER-HVAC-AHU-070000_EC_OH_PROT CHANNEL MERWMO_AENTR1:1:I.Data.5 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
ELECTRICAL
signalCOIL
to beOVERHEAT
confirmed PROTECTION MERWMO 3E4DS0-MER-BMS-RIOP-000024 DI-3 AENTR1 1 2XDI3 : 11,12 - DI-32 5 AENTR1:1:I.Data.5 DI I 4/17/2025 DONE
MERWMO_AENTR2:1:Chdata.3
SIGNAL 3E4DS0-MER-HVAC-MAUMAD-040000_MA_DAMP_POS (D_MAU_ARR_UDT[1].MA_DAMP_POS) IS MAPPED TO
156 3E4DS0-MER-HVAC-MAUMAD-040000 3E4DS0-MER-HVAC-MAUMAD-040000_MA_DAMP_POS THIS CHANNEL MERWMO_AENTR2:1:I.Ch3Data .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MIX AIR
signal
MVDtoPOSITION
be confirmed MERWMO 3E4DS0-MER-BMS-RIOP-000024 AI-2 AENTR2 1 2XAI2 : 7,8 - AI-08 3 AENTR2:1:I.Ch3Data AI Chdata 4/17/2025 DONE
# General
PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM
SIGNAL 3E4DS0-MER-HVAC-AHU-030000_OPN_FB (S_AHU_ARR_UDT[3].OPN_FB) IS MAPPED TO THIS MOTORIZED FIRE DAMPERS NON FM200 MERWTO_AENTR1:0:I.14
47 3E4DS0-MER-HVAC-AHU-030000 3E4DS0-MER-HVAC-AHU-030000_OPN_FB CHANNEL,MERWTO_AENTR1:0:I.Data.14.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MERWTO 3E4DS0-MER-BMS-RIOP-000018 DI-1 AENTR1 0 1XDI1 : 29,30 - DI-32 14 AENTR1:0:I.Data.14 DI I 4/17/2025 DONE
MERWTO_AENTR1:0:I.17
SIGNAL 3E4DS0-MER-HVAC-AHU-030000_SS2_LOC_FB (S_AHU_ARR_UDT[3].SS2_LOC_FB) IS MAPPED TO THIS
50 3E4DS0-MER-HVAC-AHU-030000 3E4DS0-MER-HVAC-AHU-030000_SS2_LOC_FB CHANNEL,MERWTO_AENTR1:0:I.Data.17.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Manual/Local
signal toBMS
be confirmed
Selector Switch (SS2) Status MERWTO 3E4DS0-MER-BMS-RIOP-000018 DI-1 AENTR1 0 1XDI1 : 35,36 - DI-32 17 AENTR1:0:I.Data.17 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-AHU-030000_SS2_REM_FB (S_AHU_ARR_UDT[3].SS2_REM_FB) IS MAPPED TO THIS
CHANNEL,MERWTO_AENTR1:0:I.Data.18,in logix only.IN SITE,SINCE THERE IS NO SIGNAL PROVISION.THERE IS NO CABLE MERWTO_AENTR1:0:I.18
51 3E4DS0-MER-HVAC-AHU-030000 3E4DS0-MER-HVAC-AHU-030000_SS2_REM_FB CONNECTED TO THIS CHANNEL. As per CWG RLM, this channel is spare at site, please check. Start Push Button RM relay activated/deactivated Status MERWTO 3E4DS0-MER-BMS-RIOP-000018 DI-1 AENTR1 0 1XDI1 : 37,38 - DI-32 18 AENTR1:0:I.Data.18 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-AHU-030000_EC_ON_CMD (S_AHU_ARR_UDT[3].EC_ON_CMD) IS MAPPED TO THIS
MERWTO_AENTR1:4:O.0
93 3E4DS0-MER-HVAC-AHU-030000 3E4DS0-MER-HVAC-AHU-030000_EC_ON_CMD RELAY,MERWTO_AENTR1:4:O.0 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
SWITCH signal
ON ELECTRICAL
to be confirmed
COIL MERWTO 3E4DS0-MER-BMS-RIOP-000018 DO-1 AENTR1 4 - 1R1 : 11,14 DO-16 0 AENTR1:4:O.0 DO O 4/17/2025 DONE
IN LOGIX THERE IS NO MAPPING TO THIS CHANNEL.IN SITE ALSO,THERE IS NO CABLE CONNECTED TO THIS CHANNEL.
3E4DS0-MU1B-EVS-SPRDPS-030001_DPS_FB SIGNAL, 3E4DS0-MU1B-EVS-SPRDPS-030001_DPS_FB (SPR_ARR_UDT[3].DPS_FB) IS MAPPED TO THIS As per CWG RLM, this channel is spare at site, please check. DI MU1AECO_AENTR2:0:I.14
CHANNEL,MU1AECO_AENTR3:0:I.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
15 ELEVATOR PRESSURIZATION FAN PROOF OF FLOW MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-1 AENTR2 0 1XSDI1 : 29,30 - SDI-16 14 AENTR2:0:I.14 I 4/17/2025 DONE
3E4DS0-MU1A-EVS-SPR-040000
SIGNAL, 3E4DS0-MU1A-EVS-SPR-040000_TRIP_FB (SPR_ARR_UDT[4].TRIP_FB) IS MAPPED TO THIS
3E4DS0-MU1A-EVS-SPR-040000_TRIP_FB DI MU1AECO_AENTR3:0:I.0
CHANNEL,MU1AECO_AENTR3:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
17 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
ELEVATOR
be confirmed
PRESSURIZATION FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-2 AENTR3 0 1XDI2 : 1,2 - SDI-16 0 AENTR3:0:I.0 I 4/17/2025 DONE
3E4DS0-MU1A-EVS-SPR-040000
SIGNAL, 3E4DS0-MU1A-EVS-SPR-040000_LOC_FB (SPR_ARR_UDT[4].LOC_FB) IS MAPPED TO THIS
3E4DS0-MU1A-EVS-SPR-040000_LOC_FB DI MU1AECO_AENTR3:0:I.1
CHANNEL,MU1AECO_AENTR3:0:I.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
18 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalELEVATOR
to be confirmed
PRESSURIZATION FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-2 AENTR3 0 1XDI2 : 3,4 - SDI-16 1 AENTR3:0:I.1 I 4/17/2025 DONE
3E4DS0-MU1A-EVS-SPR-040000
SIGNAL, 3E4DS0-MU1A-EVS-SPR-040000_REM_FB (SPR_ARR_UDT[4].REM_FB) IS MAPPED TO THIS
3E4DS0-MU1A-EVS-SPR-040000_REM_FB DI MU1AECO_AENTR3:0:I.2
CHANNEL,MU1AECO_AENTR3:0:I.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
19 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalELEVATOR
to be confirmed
PRESSURIZATION FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-2 AENTR3 0 1XDI2 : 5,6 - SDI-16 2 AENTR3:0:I.2 I 4/17/2025 DONE
3E4DS0-MU1A-EVS-SPR-040000
SIGNAL, 3E4DS0-MU1A-EVS-SPR-040000_RUN_FB (SPR_ARR_UDT[4].RUN_FB) IS MAPPED TO THIS
3E4DS0-MU1A-EVS-SPR-040000_RUN_FB DI MU1AECO_AENTR3:0:I.3
CHANNEL,MU1AECO_AENTR3:0:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
20 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
RUNNING
signal
OFtoELEVATOR
be confirmed
PRESSURIZATION FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-2 AENTR3 0 1XDI2 : 7,8 - SDI-16 3 AENTR3:0:I.3 I 4/17/2025 DONE
3E4DS0-MU1A-EVS-MUF-040000
SIGNAL, 3E4DS0-MU1A-EVS-MUF-040000_TRIP_FB (SPR_ARR_UDT[3].TRIP_FB) IS MAPPED TO THIS
3E4DS0-MU1A-EVS-MUF-040000_TRIP_FB DI MU1AECO_AENTR3:0:I.5
CHANNEL,MU1AECO_AENTR3:0:I.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
22 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
MAKE-UP
be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-2 AENTR3 0 1XDI2 : 11,12 - SDI-16 5 AENTR3:0:I.5 I 4/17/2025 DONE
3E4DS0-MU1A-EVS-MUF-040000
SIGNAL, 3E4DS0-MU1A-EVS-MUF-040000_LOC_FB (SPR_ARR_UDT[3].REM_FB) IS MAPPED TO THIS
3E4DS0-MU1A-EVS-MUF-040000_LOC_FB DI MU1AECO_AENTR3:0:I.6
CHANNEL,MU1AECO_AENTR3:0:I.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
23 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalMAKE-UP
to be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-2 AENTR3 0 1XDI2 : 13,14 - SDI-16 6 AENTR3:0:I.6 I 4/17/2025 DONE
3E4DS0-MU1A-EVS-MUF-040000
SIGNAL 3E4DS0-MU1A-EVS-MUF-040000_REM_FB (SPR_ARR_UDT[3].RUN_FB) IS MAPPED TO THIS
3E4DS0-MU1A-EVS-MUF-040000_REM_FB DI MU1AECO_AENTR3:0:I.7
CHANNEL,MU1AECO_AENTR3:0:I.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
24 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalMAKE-UP
to be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-2 AENTR3 0 1XDI2 : 15,16 - SDI-16 7 AENTR3:0:I.7 I 4/17/2025 DONE
3E4DS0-MU1A-EVS-MUF-040000
SIGNAL 3E4DS0-MU1A-EVS-MUF-040000_RUN_FB (SPR_ARR_UDT[3].LOC_FB) IS MAPPED TO THIS
3E4DS0-MU1A-EVS-MUF-040000_RUN_FB DI MU1AECO_AENTR3:0:I.8
CHANNEL,MU1AECO_AENTR3:0:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
25 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
RUNNING
signal
OFtoMAKE-UP
be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-2 AENTR3 0 1XDI2 : 17,18 - SDI-16 8 AENTR3:0:I.8 I 4/17/2025 DONE
3E4DS0-MU1A-EVS-MUFDPS-040001
SIGNAL 3E4DS0-MU1A-EVS-MUFDPS-040001_DPS_FB (SPR_ARR_UDT[3].DPS_FB) IS MAPPED TO THIS
3E4DS0-MU1A-EVS-MUFDPS-040001_DPS_FB DI MU1AECO_AENTR3:0:I.9
CHANNEL,MU1AECO_AENTR3:0:I.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
26 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MAKE-UP
signal
FANtoPROOF
be confirmed
OF FLOW MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-2 AENTR3 0 1XDI2 : 19,20 - SDI-16 9 AENTR3:0:I.9 I 4/17/2025 DONE
SIGNAL, 3E4DS0-MU1A-EVS-MUF-040000_ON_OFF_CMD (MUF_ARR_UDT[4].ON_OFF_CMD) IS MAPPED TO THIS
MU1AECO_AENTR2:1:O.0
33 3E4DS0-MU1A-EVS-MUF-040000 3E4DS0-MU1A-EVS-MUF-040000_ON_OFF_CMD RELAY,MU1AECO_AENTR2:1:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
MAKE-UP
be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDO-1 AENTR2 1 - 1SR1 : 11,14 SDO-16 0 AENTR2:1:O.0 DO O 4/17/2025 DONE
SIGNAL, 3E4DS0-MU1A-EVS-SPR-040000_ON_OFF_CMD (SPR_ARR_UDT[4].ON_OFF_CMD) IS MAPPED TO THIS
MU1AECO_AENTR2:1:O.1
34 3E4DS0-MU1A-EVS-SPR-040000 3E4DS0-MU1A-EVS-SPR-040000_ON_OFF_CMD RELAY,MU1AECO_AENTR2:1:O.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
ELEVATOR
be confirmed
PRESSURIZATION FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDO-1 AENTR2 1 - 1SR2 : 11,14 SDO-16 1 AENTR2:1:O.1 DO O 4/17/2025 DONE
SIGNAL, 3E4DS0-MU1B-EVS-MUF-030000_ON_OFF_CMD (MUF_ARR_UDT[3].ON_OFF_CMD) IS MAPPED TO THIS
MU1AECO_AENTR2:1:O.2
35 3E4DS0-MU1B-EVS-MUF-030000 3E4DS0-MU1B-EVS-MUF-030000_ON_OFF_CMD RELAY,MU1AECO_AENTR2:1:O.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
MAKE-UP
be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDO-1 AENTR2 1 - 1SR3 : 11,14 SDO-16 2 AENTR2:1:O.2 DO O 4/17/2025 DONE
SIGNAL, 3E4DS0-MU1B-EVS-SPR-030000_ON_OFF_CMD (SPR_ARR_UDT[3].ON_OFF_CMD) IS MAPPED TO THIS
MU1AECO_AENTR2:1:O.3
36 3E4DS0-MU1B-EVS-SPR-030000 3E4DS0-MU1B-EVS-SPR-030000_ON_OFF_CMD RELAY,MU1AECO_AENTR2:1:O.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
ELEVATOR
be confirmed
PRESSURIZATION FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDO-1 AENTR2 1 - 1SR4 : 11,14 SDO-16 3 AENTR2:1:O.3 DO O 4/17/2025 DONE
SIGNAL, 3E4DS0-MU1A-HVAC-MAU-030000_SF_TRIP (S_MAU_ARR_UDT[3].SF_TRIP) IS MAPPED TO THIS
MU1AECO_AENTR1:0:I.0
65 3E4DS0-MU1A-HVAC-MAU-030000 3E4DS0-MU1A-HVAC-MAU-030000_SF_TRIP CHANNEL,MU1AECO_AENTR1:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
SUPPLY
be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-1 AENTR1 0 1XDI1 : 1,2 - DI-16 0 AENTR1:0:I.0 DI I 4/17/2025 DONE
SIGNAL, 3E4DS0-MU1A-HVAC-MAU-030000_SF_LOC (S_MAU_ARR_UDT[3].SF_LOC) IS MAPPED TO THIS
MU1AECO_AENTR1:0:I.1
66 3E4DS0-MU1A-HVAC-MAU-030000 3E4DS0-MU1A-HVAC-MAU-030000_SF_LOC CHANNEL,MU1AECO_AENTR1:0:I.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalSWITCH
to be confirmed
SUPPLY FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-1 AENTR1 0 1XDI1 : 3,4 - DI-16 1 AENTR1:0:I.1 DI I 4/17/2025 DONE
SIGNAL, 3E4DS0-MU1A-HVAC-MAU-030000_SF_REM (S_MAU_ARR_UDT[3].SF_REM) IS MAPPED TO THIS
MU1AECO_AENTR1:0:I.2
67 3E4DS0-MU1A-HVAC-MAU-030000 3E4DS0-MU1A-HVAC-MAU-030000_SF_REM CHANNEL,MU1AECO_AENTR1:0:I.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalSWITCH
to be confirmed
SUPPLY FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-1 AENTR1 0 1XDI1 : 5,6 - DI-16 2 AENTR1:0:I.2 DI I 4/17/2025 DONE
SIGNAL, 3E4DS0-MU1A-HVAC-MAU-030000_SF_RUN_FB (S_MAU_ARR_UDT[3].SF_RUN_FB) IS MAPPED TO THIS
MU1AECO_AENTR1:0:I.3
68 3E4DS0-MU1A-HVAC-MAU-030000 3E4DS0-MU1A-HVAC-MAU-030000_SF_RUN_FB CHANNEL,MU1AECO_AENTR1:0:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MAU Power
signal Supply
to be confirmed
On/Off Status MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-1 AENTR1 0 1XDI1 : 7,8 - DI-16 3 AENTR1:0:I.3 DI I 4/17/2025 DONE
# General
PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM
SE03WCO_AENTR2:0:I.14
SIGNAL 3E4DS0-SE03-EVS-SEDPS-080001-Smoke Exhaust Fan proof of flow (SEF_ARR_UDT[9].DPS_FB) IS MAPPED TO
31 3E4DS0-SE03-EVS-SEDPS-080001 3E4DS0-SE03-EVS-SEDPS-080001_DPS_FB THIS CHANNEL,SE03WCO_AENTR2:0:I.14.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
SMOKEsignal
EXHAUST
to beFAN
confirmed
PROOF OF FLOW SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDI-2 AENTR2 0 1XSDI2 : 29,30 - SDI-16 14 AENTR2:0:I.14 DI I 4/19/2025 DONE
# General
PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM
SEECO_AENTR2:0:I.5
SIGNAL, 3E4DS0-CO01-EVS-MFD-101137_OPN_FB_DOOR (EVS_FD_ARR_UDT[1].OPN_FB) IS MAPPED TO THIS
22 3E4DS0-CO01-EVS-MFD-101137 3E4DS0-CO01-EVS-MFD-101137_OPN_FB CHANNEL,SEECO_AENTR2:0:I.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed SEECO 3E4DS0-SE-BMS-RIOP-000011 SDI-2 AENTR2 0 1XSDI2 : 11,12 - SDI-16 5 AENTR2:0:I.5 DI I 4/19/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,EXTRA CABLE IS CONNECTED TO THIS CHANNEL.IT NEED TO
SEECO_AENTR2:0:I.7
24 SPARE SPARE BE REMOVED. As per CWG RLM, this channel is used at site, please check. SPARE SEECO 3E4DS0-SE-BMS-RIOP-000011 SDI-2 AENTR2 0 1XSDI2 : 15,16 - SDI-16 7 AENTR2:0:I.7 DI I 4/19/2025 DONE
32 3E4DS0-SE-BMS-RIOP-000011 3E4DS0-SE-BMS-SEECO-000000_SEECO_PWR_SPLY1_FAIL SIGNAL 3E4DS0-SE-BMS-SEECO-000000_SEECO_PWR_SPLY1_FAIL IS MAPPED TO THIS CHANNEL,SEECO_AENTR2:0:I.15.IN As
SITE
per
ALSO,IT
CWG RLM,
IS CONNECTED
Cable tag/ferrule
TO THEisSAME
not available,
SIGNAL. terminated cable to be identify at site and mapped
POWERsignal to be
SUPPLY confirmed
FAILURE ALARM SEECO 3E4DS0-SE-BMS-RIOP-000011 SDI-2 AENTR2 0 1XSDI2 : 31,32 - SDI-16 15 AENTR2:0:I.15 DI SEECO_AENTR2:0:I.15 I 4/19/2025 DONE
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed SEECO_AENTR1:1:O.0
SIGNAL 3E4DS0-SE-EVS-SEDPS-100001_ON_OFF_COMMAND (SEF_ARR_UDT[12].ON_OFF_CMD) IS MAPPED TO THIS
33 3E4DS0-SE-EVS-SE-100000 3E4DS0-SE-EVS-SE-100000_ON_OFF_CMD RELAY,SEECO_AENTR1:1:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. START/STOP SMOKE EXHAUST FAN SEECO 3E4DS0-SE-BMS-RIOP-000011 SDO-1 AENTR1 1 - 1SR1 : 11,14 SDO-16 0 AENTR1:1:O.0 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-SE-EVS-SE-040000_ON_OFF_COMMAND (SEF_ARR_UDT[4].ON_OFF_CMD) IS MAPPED TO THIS As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed SEECO_AENTR1:1:O.1
34 3E4DS0-SE-EVS-SE-030000 3E4DS0-SE-EVS-SE-030000_ON_OFF_CMD RELAY,SEECO_AENTR1:1:O.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. START/STOP SMOKE EXHAUST FAN SEECO 3E4DS0-SE-BMS-RIOP-000011 SDO-1 AENTR1 1 - 1SR2 : 11,14 SDO-16 1 AENTR1:1:O.1 DO O 4/19/2025 DONE
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed SEECO_AENTR1:1:O.2
SIGNAL 3E4DS0-SE-EVS-SE-030000_ON_OFF_COMMAND (SEF_ARR_UDT[3].ON_OFF_CMD) IS MAPPED TO THIS
35 3E4DS0-SE-EVS-SE-040000 3E4DS0-SE-EVS-SE-040000_ON_OFF_CMD RELAY,SEECO_AENTR1:1:O.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. START/STOP SMOKE EXHAUST FAN SEECO 3E4DS0-SE-BMS-RIOP-000011 SDO-1 AENTR1 1 - 1SR3 : 11,14 SDO-16 2 AENTR1:1:O.2 DO O 4/19/2025 DONE
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed SEECO_AENTR1:1:O.3
SIGNAL 3E4DS0-CO01-EVS-MFD-101137_OPN_FB_DOOR (EVS_FD_ARR_UDT[1].OPN_CLS_CMD) IS MAPPED TO THIS
36 3E4DS0-CO01-EVS-MFD-101137 3E4DS0-CO01-EVS-MFD-101137_OPN_CLS_CMD RELAY,SEECO_AENTR1:1:O.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. OPEN COMMAND SEECO 3E4DS0-SE-BMS-RIOP-000011 SDO-1 AENTR1 1 - 1SR4 : 11,14 SDO-16 3 AENTR1:1:O.3 DO O 4/19/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,EXTRA CABLE IS CONNECTED TO THIS CHANNEL.IT NEED TO
SEECO_AENTR1:1:O.8
41 SPARE SPARE BE REMOVED. As per CWG RLM, this channel is used at site, please check. SPARE SEECO 3E4DS0-SE-BMS-RIOP-000011 SDO-1 AENTR1 1 - 1SR9 : 11,14 SDO-16 8 AENTR1:1:O.8 DO O 4/19/2025 DONE
SPWPO_AENTR1:0:I.0
SIGNAL, 3E4DS0-EST02-EVS-MFD-644029_OPN_FB (EVS_FD_ARR_UDT[18].OPN_FB) IS MAPPED TO THIS
1 3E4DS0-EST02-EVS-MFD-644029 3E4DS0-EST02-EVS-MFD-644029_OPN_FB CHANNEL,SPWPO_AENTR1:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed SPWPO 3E4DS0-SP-BMS-RIOP-000027 SDI-1 AENTR1 0 1XSDI1 : 1,2 - SDI-16 0 AENTR1:0:I.0 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-FCC-FDPS-FACP-200004_FACP2_SMOKE_DETECTOR.4
(FACP_ARR_UDT[2].FACP2_SMOKE_DETECTOR.4) IS MAPPED TO THIS CHANNEL,SPWPO_AENTR1:0:I.2.IN SITE SPWPO_AENTR1:0:I.2
3 3E4DS0-FCC-FDPS-FACP-200004 3E4DS0-FCC-FDPS-FACP-200004_FACP2_SMOKE_DETECTOR.4 ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
[FACP-2]
signal
Smoke
to be
Detectors/Manual
confirmed station - Platform (BOH and Not FM-200 rooms)
SPWPO 3E4DS0-SP-BMS-RIOP-000027 SDI-1 AENTR1 0 1XSDI1 : 5,6 - SDI-16 2 AENTR1:0:I.2 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-FCC-FDPS-FACP-200003_FACP2_SMOKE_DETECTOR.5
(FACP_ARR_UDT[2].FACP2_SMOKE_DETECTOR.5) IS MAPPED TO THIS CHANNEL,SPWPO_AENTR1:0:I.3.IN SITE SPWPO_AENTR1:0:I.3
4 3E4DS0-FCC-FDPS-FACP-200003 3E4DS0-FCC-FDPS-FACP-200003_FACP2_SMOKE_DETECTOR.5 ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Smokesignal
Detectors-
to be confirmed
EST-04 SPWPO 3E4DS0-SP-BMS-RIOP-000027 SDI-1 AENTR1 0 1XSDI1 : 7,8 - SDI-16 3 AENTR1:0:I.3 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-FCC-FDPS-FACP-200004_FACP2_SMOKE_DETECTOR.6
(FACP_ARR_UDT[2].FACP2_SMOKE_DETECTOR.6) IS MAPPED TO THIS CHANNEL,SPWPO_AENTR1:0:I.4.IN SITE SPWPO_AENTR1:0:I.4
5 3E4DS0-FCC-FDPS-FACP-200004 3E4DS0-FCC-FDPS-FACP-200004_FACP2_SMOKE_DETECTOR.6 ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
[FACP-2]
signal
Smoke
to be
Detectors/Manual
confirmed station - Underplatform SPWPO 3E4DS0-SP-BMS-RIOP-000027 SDI-1 AENTR1 0 1XSDI1 : 9,10 - SDI-16 4 AENTR1:0:I.4 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-FCC-FDPS-FACP-200001_FACP2_ES_ACT_FB (FACP2_ONBOARD_TRAIN_ON_FIRE_FB) IS MAPPED TO
SPWPO_AENTR1:0:I.5
6 3E4DS0-FCC-FDPS-FACP-200001 3E4DS0-FCC-FDPS-FACP-200001_FACP2_ES_ACT_FB THIS CHANNEL,SPWPO_AENTR1:0:I.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is spare at site, please check. [FACP-TRACK] ACTIVATE STATION EVACUATION DUE TO FIRE ON INCOMING TRAIN
SPWPO 3E4DS0-SP-BMS-RIOP-000027 SDI-1 AENTR1 0 1XSDI1 : 11,12 - SDI-16 5 AENTR1:0:I.5 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-EST02-EVS-MFD-644029_OPN_CLS_CMD (EVS_FD_ARR_UDT[18].OPN_CLS_CMD) IS MAPPED TO THIS
SPWPO_AENTR1:1:O.0
17 3E4DS0-EST02-EVS-MFD-644029 3E4DS0-EST02-EVS-MFD-644029_OPN_CLS_CMD RELAY,SPWPO_AENTR1:1:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN COMMAND
signal to be confirmed SPWPO 3E4DS0-SP-BMS-RIOP-000027 SDO-1 AENTR1 1 - 1SR1 : 11,14 SDO-16 0 AENTR1:1:O.0 DO O 4/19/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,EXTRA CABLE IS CONNECTED TO THIS CHANNEL.IT NEED TO
SPWPO_AENTR1:1:O.1
18 SPARE SPARE BE REMOVED. As per CWG RLM, this channel is used at site, please check. SPARE SPWPO 3E4DS0-SP-BMS-RIOP-000027 SDO-1 AENTR1 1 - 1SR2 : 11,14 SDO-16 1 AENTR1:1:O.1 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-FCC-FDPS-FACP-200001_FACP2_ES_ACT_CMD (FACP_ARR_UDT[2].FACP2_ES_ACT_CMD) IS MAPPED TO
SPWPO_AENTR1:1:O.2
19 3E4DS0-FCC-FDPS-FACP-200001 3E4DS0-FCC-FDPS-FACP-200001_FACP2_ES_ACT_CMD THIS RELAY,SPWPO_AENTR1:1:O.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is spare at site, please check. [FACP-TRACK] ACTIVATE STATION EVACUATION DUE TO FIRE ON INCOMING TRAIN
SPWPO 3E4DS0-SP-BMS-RIOP-000027 SDO-1 AENTR1 1 - 1SR3 : 11,14 SDO-16 2 AENTR1:1:O.2 DO O 4/19/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,EXTRA CABLE IS CONNECTED TO THIS CHANNEL.IT NEED TO
SPWPO_AENTR2:0:I.4
37 SPARE SPARE BE REMOVED. As per CWG RLM, this channel is used at site, please check. SPARE SPWPO 3E4DS0-SP-BMS-RIOP-000027 DI-1 AENTR2 0 1XDI1 : 9,10 - DI-32 4 AENTR2:0:I.Data.4 DI I 4/19/2025 DONE
SIGNAL, MFD 014118_OPN_FB (HVAC_FD_ARR_UDT[85].OPN_FB) IS MAPPED TO THIS
SPWPO_AENTR2:0:I.25
58 SPARE SPARE CHANNEL,SPWPO_AENTR2:0:I.Data.25.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE SPWPO 3E4DS0-SP-BMS-RIOP-000027 DI-1 AENTR2 0 1XDI1 : 25,26 - DI-32 25 AENTR2:0:I.Data.25 DI I 4/19/2025 DONE
SIGNAL, MFD-014134_OPN_FB (HVAC_FD_ARR_UDT[86].OPN_FB) IS MAPPED TO THIS
SPWPO_AENTR2:0:I.26
59 SPARE SPARE CHANNEL,SPWPO_AENTR2:0:I.Data.26.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE SPWPO 3E4DS0-SP-BMS-RIOP-000027 DI-1 AENTR2 0 1XDI1 : 25,26 - DI-32 26 AENTR2:0:I.Data.26 DI I 4/19/2025 DONE
# General
PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM
# General
PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM
SIGNAL 3E4DS0-OTE01-TVS-MTED-110021-Damper Limit Switch Close Status (MTED_ARR_UDT[5].CLS_FB) IS MAPPED TVRECO1 TVRECO1_AENTR2:2:I.11
124 SPARE SPARE TO THIS CHANNEL,TVRWTO1_AENTR2:1:I.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE 3E4DS0-TVR-BMS-RIOP-000014 SDI-8 AENTR2 2 2XSDI8 : 23,24 - SDI-16 11 AENTR2:2:I.11 DI I 4/19/2025 DONE
TVRECO1 TVRECO1_AENTR3:3:O.5
SIGNAL 3E4DS0-OTE02-TVS-UPED-210000_OPN_CLS_CMD (UPED_ARR_UDT[3].OPN_CLS_CMD) IS MAPPED TO THIS
182 3E4DS0-OTE02-TVS-UPED-210000 3E4DS0-OTE02-TVS-UPED-210000_OPN_CLS_CMD RELAY,TVRECO1_AENTR3:3:O.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
SUB-DAMPER
signal to1be
OPEN/CLOSE
confirmed COMMAND 3E4DS0-TVR-BMS-RIOP-000014 SDO-2 AENTR3 3 - 2SR22:11,14 SDO-16 5 AENTR3:3:O.5 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-TVR-TVS-VFD-210001_VFD.FIRE_FWD_CMD (VSF_3E4_ARR_UDT[3].VFD.FIRE_FWD_CMD) IS MAPPED
TVRECO1 TVRECO1_AENTR1:3:O.0
193 3E4DS0-TVR-TVS-VFD-210001 3E4DS0-TVR-TVS-VFD-210001_VFD.FIRE_FWD_CMD TO THIS RELAY,TVRECO1_AENTR1:3:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FIRE MODE
signal-FORWARD
to be confirmed
DIRECTION COMMAND 3E4DS0-TVR-BMS-RIOP-000014 SDO-3 AENTR1 3 - 2SR33:11,14 SDO-16 0 AENTR1:3:O.0 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-TVR-TVS-VFD-210001_VFD.FIRE_REV_CMD (VSF_3E4_ARR_UDT[3].VFD.FIRE_REV_CMD) IS MAPPED TO
TVRECO1 TVRECO1_AENTR1:3:O.1
194 3E4DS0-TVR-TVS-VFD-210001 3E4DS0-TVR-TVS-VFD-210001_VFD.FIRE_REV_CMD THIS RELAY,TVRECO1_AENTR1:3:O.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FIRE MODE
signal-REVERSE
to be confirmed
DIRECTION COMMAND 3E4DS0-TVR-BMS-RIOP-000014 SDO-3 AENTR1 3 - 2SR34:11,14 SDO-16 1 AENTR1:3:O.1 DO O 4/19/2025 DONE
SIGNAL, 3E4DS0-OTE02-TVS-TEF-210000_BR_TEMP_WEST (TEF_3E4_ARR_UDT[3].BR_TEMP_WEST) IS MAPPED TO THIS
TVRECO1 TVRECO1_AENTR3:4:ch1data
234 3E4DS0-OTE02-TVS-TEF-210000 3E4DS0-OTE02-TVS-TEF-210000_BR_TEMP_WEST CHANNEL,TVRECO1_AENTR3:4:I.Ch1Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
BEARING
signal
TEMPERATURE
to be confirmed
TUNNEL SIDE 3E4DS0-TVR-BMS-RIOP-000014 SAI-2 AENTR3 4 2XSAI2 : 3,4 - SAI-08 1 AENTR3:4:I.Ch1Data AI ch1data 4/19/2025 DONE
SIGNAL, 3E4DS0-OTE02-TVS-TEF-210000_BR_TEMP_EAST (TEF_3E4_ARR_UDT[3].BR_TEMP_EAST) IS MAPPED TO THIS
TVRECO1 TVRECO1_AENTR3:4:ch2data
235 3E4DS0-OTE02-TVS-TEF-210000 3E4DS0-OTE02-TVS-TEF-210000_BR_TEMP_EAST CHANNEL,TVRECO1_AENTR3:4:I.Ch2Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
BEARING
signal
TEMPERATURE
to be confirmed
ATMOSPHERE SIDE 3E4DS0-TVR-BMS-RIOP-000014 SAI-2 AENTR3 4 2XSAI2 : 5,6 - SAI-08 2 AENTR3:4:I.Ch2Data AI ch2data 4/19/2025 DONE
SIGNAL 3E4DS0-OTE02-TVS-TEFDPT-210000_FLOW_EAST (TEF_3E4_ARR_UDT[3].FLOW_EAST) IS MAPPED TO THIS
TVRECO1 TVRECO1_AENTR3:4:ch3data
236 3E4DS0-OTE02-TVS-TEFDPT-210000 3E4DS0-OTE02-TVS-TEFDPT-210000_FLOW_EAST CHANNEL,TVRECO1_AENTR3:4:I.Ch3Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FLOW MEASURE
signal to beTO
confirmed
TUNNEL/ATMOSPHERE DIRECTION 3E4DS0-TVR-BMS-RIOP-000014 SAI-2 AENTR3 4 2XSAI2 : 7,8 - SAI-08 3 AENTR3:4:I.Ch3Data AI ch3data 4/19/2025 DONE
SIGNAL 3E4DS0-OTE02-TVS-TEF-210000_FAN_VIB (TEF_3E4_ARR_UDT[3].FAN_VIB) IS MAPPED TO THIS
TVRECO1 TVRECO1_AENTR3:4:ch4data
237 3E4DS0-OTE02-TVS-TEF-210000 3E4DS0-OTE02-TVS-TEF-210000_FAN_VIB CHANNEL,TVRECO1_AENTR3:4:I.Ch4Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTOR signal
VIBRATION
to be confirmed
LEVEL (MM/S) 3E4DS0-TVR-BMS-RIOP-000014 SAI-2 AENTR3 4 2XSAI2 : 9,10 - SAI-08 4 AENTR3:4:I.Ch4Data AI ch4data 4/19/2025 DONE
SIGNAL 3E4DS0-TVR-TVS-VFD-210001_VFD.SPD (VSF_3E4_ARR_UDT[3].VFD.SPD) IS MAPPED TO THIS
TVRECO1 TVRECO1_AENTR1:4:ch0data
241 3E4DS0-TVR-TVS-VFD-210001 3E4DS0-TVR-TVS-VFD-210001_VFD.SPD CHANNEL,TVRECO1_AENTR1:4:I.Ch0Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTOR signal
SPEEDto FEEDBACK
be confirmed 3E4DS0-TVR-BMS-RIOP-000014 SAI-3 AENTR1 4 2XSAI3 : 1,2 - SAI-08 0 AENTR1:4:I.Ch0Data AI ch0data 4/19/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSF-220000_EMG_STP (VSF_3E4_ARR_UDT[4].EMG_STP) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR1:0:I.0
1 3E4DS0-SFR-TVS-VSF-220000 3E4DS0-SFR-TVS-VSF-220000_EMG_STP CHANNEL,TVRECO2_AENTR1:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
EMERGENCY
signal to
STOP
be confirmed
BUTTON STATUS 3E4DS0-TVR-BMS-RIOP-000015 SDI-1 AENTR1 0 2XSDI1 : 1,2 - SDI-16 0 AENTR1:0:I.0 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-TVR-TVS-VFD-220001_VFD.BYPASS (VSF_3E4_ARR_UDT[4].VFD.BYPASS) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR1:0:I.3
4 3E4DS0-TVR-TVS-VFD-220001 3E4DS0-TVR-TVS-VFD-220001_VFD.BYPASS CHANNEL,TVRECO2_AENTR1:0:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
VFD INsignal
BYPASSto STATUS
be confirmed 3E4DS0-TVR-BMS-RIOP-000015 SDI-1 AENTR1 0 2XSDI1 : 7,8 - SDI-16 3 AENTR1:0:I.3 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSF-220000_WD_TEMP_ALM (VSF_3E4_ARR_UDT[4].WD_TEMP_ALM) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR1:0:I.11
12 3E4DS0-SFR-TVS-VSF-220000 3E4DS0-SFR-TVS-VSF-220000_WD_TEMP_ALM CHANNEL,TVRECO2_AENTR1:0:I.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WINDING
signal
TEMPERATURE
to be confirmed
ALARM 3E4DS0-TVR-BMS-RIOP-000015 SDI-1 AENTR1 0 2XSDI1 : 23,24 - SDI-16 11 AENTR1:0:I.11 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-OTE02-TVS-TEF-220000_EMG_STP (TEF_3E4_ARR_UDT[4].EMG_STP) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR2:0:I.0
17 3E4DS0-OTE02-TVS-TEF-220000 3E4DS0-OTE02-TVS-TEF-220000_EMG_STP CHANNEL,TVRECO2_AENTR2:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
EMERGENCY
signal to
STOP
be confirmed
BUTTON STATUS 3E4DS0-TVR-BMS-RIOP-000015 SDI-2 AENTR2 0 2XSDI2 : 1,2 - SDI-16 0 AENTR2:0:I.0 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-OTE02-TVS-TEF-220000_WD_TEMP_ALM (TEF_3E4_ARR_UDT[4].WD_TEMP_ALM) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR2:0:I.8
25 3E4DS0-OTE02-TVS-TEF-220000 3E4DS0-OTE02-TVS-TEF-220000_WD_TEMP_ALM CHANNEL,TVRECO2_AENTR2:0:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WINDING
signal
TEMPERATURE
to be confirmed
STATUS 3E4DS0-TVR-BMS-RIOP-000015 SDI-2 AENTR2 0 2XSDI2 : 17,18 - SDI-16 8 AENTR2:0:I.8 DI I 4/19/2025 DONE
# General
PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM
TVRWTO1 TVRWTO1_AENTR1:5:ch0data
SIGNAL, 3E4DS0-TVR-TVS-VFD-110001_VFD.SPD (VSF_3E4_ARR_UDT[1].VFD.SPD) IS MAPPED TO THIS
249 3E4DS0-TVR-TVS-VFD-110001 3E4DS0-TVR-TVS-VFD-110001_VFD.SPD CHANNEL,TVRWTO1_AENTR1:5:I.Ch0Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTOR signal
SPEEDto FEEDBACK
be confirmed 3E4DS0-TVR-BMS-RIOP-000016 SAI-2 AENTR1 5 2XSAI2 : 1,2 - SAI-08 0 AENTR1:5:I.Ch0Data AI ch 4/20/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSF-110000_BR_TEMP_WEST (VSF_3E4_ARR_UDT[1].BR_TEMP_WEST) IS MAPPED TO THIS
TVRWTO1 TVRWTO1_AENTR1:5:ch1data
250 3E4DS0-SFR-TVS-VSF-110000 3E4DS0-SFR-TVS-VSF-110000_BR_TEMP_WEST CHANNEL,TVRWTO1_AENTR1:5:I.Ch1Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
BEARING
signal
TEMPERATURE
to be confirmed
TUNNEL SIDE 3E4DS0-TVR-BMS-RIOP-000016 SAI-2 AENTR1 5 2XSAI2 : 3,4 - SAI-08 1 AENTR1:5:I.Ch1Data AI ch 4/20/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSF-110000_BR_TEMP_EAST (VSF_3E4_ARR_UDT[1].BR_TEMP_EAST) IS MAPPED TO THIS
TVRWTO1 TVRWTO1_AENTR1:5:ch2data
251 3E4DS0-SFR-TVS-VSF-110000 3E4DS0-SFR-TVS-VSF-110000_BR_TEMP_EAST CHANNEL,TVRWTO1_AENTR1:5:I.Ch2Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
BEARING
signal
TEMPERATURE
to be confirmed
ATMOSPHERE SIDE 3E4DS0-TVR-BMS-RIOP-000016 SAI-2 AENTR1 5 2XSAI2 : 5,6 - SAI-08 2 AENTR1:5:I.Ch2Data AI ch 4/20/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSF-110000_FAN_VIB (VSF_3E4_ARR_UDT[1].FAN_VIB) IS MAPPED TO THIS
TVRWTO1 TVRWTO1_AENTR1:5:ch3data
252 3E4DS0-SFR-TVS-VSF-110000 3E4DS0-SFR-TVS-VSF-110000_FAN_VIB CHANNEL,TVRWTO1_AENTR1:5:I.Ch3Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTOR signal
VIBRATION
to be confirmed
LEVEL (MM/S) 3E4DS0-TVR-BMS-RIOP-000016 SAI-2 AENTR1 5 2XSAI2 : 7,8 - SAI-08 3 AENTR1:5:I.Ch3Data AI ch 4/20/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSFDPT-110000_FLOW_WEST (VSF_3E4_ARR_UDT[1].FLOW_WEST) IS MAPPED TO THIS
TVRWTO1 TVRWTO1_AENTR1:5:ch4data
253 3E4DS0-SFR-TVS-VSFDPT-110000 3E4DS0-SFR-TVS-VSFDPT-110000_FLOW_WEST CHANNEL,TVRWTO1_AENTR1:5:I.Ch4Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FLOW MEASUREM
signal to be confirmed
TO TUNNEL DIRECTION 3E4DS0-TVR-BMS-RIOP-000016 SAI-2 AENTR1 5 2XSAI2 : 9,10 - SAI-08 4 AENTR1:5:I.Ch4Data AI ch 4/20/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSFDPT-110000_FLOW_EAST (VSF_3E4_ARR_UDT[1].FLOW_EAST) IS MAPPED TO THIS
TVRWTO1 TVRWTO1_AENTR1:5:ch5data
254 3E4DS0-SFR-TVS-VSFDPT-110000 3E4DS0-SFR-TVS-VSFDPT-110000_FLOW_EAST CHANNEL,TVRWTO1_AENTR1:5:I.Ch5Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FLOW MEASURE
signal to beTO
confirmed
ATMOSPHERE DIRECTION 3E4DS0-TVR-BMS-RIOP-000016 SAI-2 AENTR1 5 2XSAI2 : 11,12 - SAI-08 5 AENTR1:5:I.Ch5Data AI ch 4/20/2025 DONE
# General
PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM
TVRWTO1 TVRWTO1_AENTR2:5:ch4data
SIGNAL 3E4DS0-OTE01-TVS-TEF-110000_FAN_VIB (TEF_3E4_ARR_UDT[1].FAN_VIB) IS MAPPED TO THIS
261 3E4DS0-OTE01-TVS-TEF-110000 3E4DS0-OTE01-TVS-TEF-110000_FAN_VIB CHANNEL,TVRWTO1_AENTR2:5:I.Ch4Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTOR signal
VIBRATION
to be confirmed
LEVEL (MM/S) 3E4DS0-TVR-BMS-RIOP-000016 SAI-3 AENTR2 5 2XSAI3 : 9,10 - SAI-08 4 AENTR2:5:I.Ch4Data AI ch 4/20/2025 DONE
TVRWTO1 TVRWTO1_AENTR3:5:ch0data
SIGNAL 3E4DS0-E3TE4-TVS-ANE-111000_AIR_FLOW (ANE_ARR_UDT[2].AIR_FLOW) IS MAPPED TO THIS
265 3E4DS0-E3TE4-TVS-ANE-111000 3E4DS0-E3TE4-TVS-ANE-111000_AIR_FLOW CHANNEL,TVRWTO1_AENTR3:5:I.Ch0Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AIR FLOW
signal to be confirmed 3E4DS0-TVR-BMS-RIOP-000016 SAI-4 AENTR3 5 2XSAI4 : 1,2 - SAI-08 0 AENTR3:5:I.Ch0Data AI ch 4/20/2025 DONE
TVRWTO2 TVRWTO2_AENTR2:2:I.9
# General