PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM

DOCUMENT TITLE SHOP DRAWING-DEEP UNDERGROUND STATION-3E4-BMS-INPUT/OUTPUT SCHEDULE

DOCUMENT NO. M-ANM-3E4DS0-CJ00-SCH-000002

MODULE RELAY MODULE CHANNE


SR. NO. EQUIPMENT TAG PLC TAG EASA SITE Response RLM COMMENTS FROM CWG DESCRIPTION PANEL SHORT TAG (OLD) PANEL FULL TAG (NEW) RACK NO. SLOT NO. TERMINAL NO. PLC IO ADDRESS MODULE ID DATE STATUS
ID NO. TYPE L NO.
SIGNAL 3E4DS0-DPR-MES-DWTV-000001-V_OPN_CMD (DWT_VALVE_ARR_UDT[1].OPN_CLS_CMD) IS MAPPED TO THIS
ACPWMO_AENTR1:3:O.5 O 4/14/2025 DONE
70 3E4DS0-DPR-MES-DWTV-000001-V 3E4DS0-DPR-MES-DWTV-000001-V_OPN_CMD RELAY ACPWMO_AENTR1:3:O.5.IN SITE ALSO,IT IS CONNECTED TO THE SAME SIGNAL As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DOMESTIC
signal to beWATER
confirmed
TANK VALVE ACPWMO 3E4DS0-ACP-BMS-RIOP-000023 DO-1 AENTR1 3 - 1R6 : 11,14 DO-16 5 AENTR1:3:O.5 DO
3E4DS0-ACY-HVAC-DYC-010001 CHILLED WATER VALVE POSITION (DYC_ARR_UDT[1].OPN_FB) IS MAPPED TO THIS
ACYGO_AENTR1:0:I.10 4/14/2025 DONE
11 SPARE SPARE CHANNEL ACYGO_AENTR1:0:I.Data.10 IN LOGIX.IN SITE,ALSO CABLE IS CONNECTED TO THIS SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE ACYGO 3E4DS0-ACY-BMS-RIOP-000001 DI-1 AENTR1 0 1XDI1 : 21,22 - DI-32 10 AENTR1:0:I.Data.10 DI I
3E4DS0-ACY-HVAC-DYC-010002 CHILLED WATER VALVE POSITION (DYC_ARR_UDT[2].OPN_FB) IS MAPPED TO THIS
ACYGO_AENTR1:0:I.13 4/14/2025 DONE
14 SPARE SPARE CHANNEL ACYGO_AENTR1:0:I.Data.13 IN LOGIX.IN SITE,ALSO CABLE IS CONNECTED TO THIS SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE ACYGO 3E4DS0-ACY-BMS-RIOP-000001 DI-1 AENTR1 0 1XDI1 : 27,28 - DI-32 13 AENTR1:0:I.Data.13 DI I
3E4DS0-ACY-HVAC-DYCFS-010001
IN LOGIX,SIGNAL 3E4DS0-ACY-HVAC-DYC-010001 CHILLED WATER (DYC_ARR_UDT[1].FLOW_FB) IS MAPPED TO
3E4DS0-ACY-HVAC-DYCFS-010001_FLOW_FB As per CWG RLM, this channel is spare at site, please check. CHILLED WATER SUPPLY FLOW ACYGO DI-1 AENTR1 0 1XDI1 : 35,36 - DI-32 17 DI ACYGO_AENTR1:0:I.17 DONE
CHANNEL ACYGO_AENTR1:0:I.Data.17 .BUT IN SITE,CABLE IS NOT CONNECTED.
18 3E4DS0-ACY-BMS-RIOP-000001 AENTR1:0:I.Data.17 I 4/14/2025
3E4DS0-ACY-HVAC-DYCFS-010002
IN LOGIX,SIGNAL 3E4DS0-ACY-HVAC-DYC-010002 CHILLED WATER (DYC_ARR_UDT[2].FLOW_FB) IS MAPPED TO
3E4DS0-ACY-HVAC-DYCFS-010002_FLOW_FB As per CWG RLM, this channel is spare at site, please check. CHILLED WATER SUPPLY FLOW ACYGO DI-1 AENTR1 0 1XDI1 : 37,38 - DI-32 18 DI ACYGO_AENTR1:0:I.18 4/14/2025 DONE
CHANNEL ACYGO_AENTR1:0:I.Data.18 .BUT IN SITE,CABLE IS NOT CONNECTED.
19 3E4DS0-ACY-BMS-RIOP-000001 AENTR1:0:I.Data.18 I
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,IT IS A EXTRA CABLE.WHICH NEED TO BE REMOVED FROM
ACYGO_AENTR1:2:I.6
55 SPARE SPARE SITE. As per CWG RLM, this channel is used at site, please check. SPARE ACYGO 3E4DS0-ACY-BMS-RIOP-000001 AI-1 AENTR1 2 1XAI1 : 13,14 - AI-08 6 AENTR1:2:I.Ch6Data AI I 4/14/2025 DONE

EGRECO_AENTR2:1:I.0
SIGNAL 3E4DS0-CO03-EVS-MFD-101138_OPN_FB (EVS_FD_ARR_UDT[2].OPN_FB) IS MAPPED TO THIS CHANNEL
1 3E4DS0-CO03-EVS-MFD-101138 3E4DS0-CO03-EVS-MFD-101138_OPN_FB EGRECO_AENTR2:1:I.0.IN SITE ALSO ,CABLE IS CONNECTED TO THIS SAME SIGNAL As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed EGRECO 3E4DS0-EGR-BMS-RIOP-000013 SDI-1 AENTR2 1 2XSDI1 : 1,2 - SDI-16 0 AENTR2:1:I.0 DI I 4/14/2025 DONE

EGRECO_AENTR2:1:I.1
SIGNAL 3E4DS0-CO03-EVS-MFD-101138_CLS_FB_DOOR1 (EVS_FD_ARR_UDT[2].CLS_FB_DOOR1) IS MAPPED TO THIS
2 3E4DS0-CO03-EVS-MFD-101138 3E4DS0-CO03-EVS-MFD-101138_CLS_FB_DOOR1 CHANNEL EGRECO_AENTR2:1:I.1 IN LOGIX,ONLY .IN SITE ALSO,THERE IS NO CABLE IS CONNECTED TO THIS CHANNEL. As per CWG RLM, this channel is spare at site, please check. DOOR CLOSE STATUS EGRECO 3E4DS0-EGR-BMS-RIOP-000013 SDI-1 AENTR2 1 2XSDI1 : 3,4 - SDI-16 1 AENTR2:1:I.1 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-FCC-FDPS-FACP-100003_FACP1_FIRE_ALARM.1 (FACP_ARR_UDT[1].FACP1_FIRE_ALARM.1) IS MAPPED
EGRECO_AENTR2:1:I.2
3 3E4DS0-FCC-FDPS-FACP-100003 3E4DS0-FCC-FDPS-FACP-100003_FACP1_FIRE_ALARM.1 TO THIS CHANNEL EGRECO_AENTR2:1:I.2 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
[FACP-1]
signal
FIREtoALARM
be confirmed
STATION\GRADE ENTRANCE 02 (FIRE ALARM ZONE NO. 4)EGRECO 3E4DS0-EGR-BMS-RIOP-000013 SDI-1 AENTR2 1 2XSDI1 : 5,6 - SDI-16 2 AENTR2:1:I.2 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-FCC-FDPS-FACP-100003_FACP1_FIRE_ALARM.2 (FACP_ARR_UDT[1].FACP1_FIRE_ALARM.2) IS MAPPED
EGRECO_AENTR2:1:I.3
4 3E4DS0-FCC-FDPS-FACP-100003 3E4DS0-FCC-FDPS-FACP-100003_FACP1_FIRE_ALARM.2 TO THIS CHANNEL EGRECO_AENTR2:1:I.3 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
[FACP-1]
signal
FIREtoALARM
be confirmed
STATION\GRADE ENTRANCE 03 (FIRE ALARM ZONE NO. 5)EGRECO 3E4DS0-EGR-BMS-RIOP-000013 SDI-1 AENTR2 1 2XSDI1 : 7,8 - SDI-16 3 AENTR2:1:I.3 DI I 4/14/2025 DONE

SIGNAL 3E4DS0-FCC-FDPS-FACP-100003_FACP1_FIRE_ALARM.3 (FACP_ARR_UDT[1].FACP1_FIRE_ALARM.3) IS MAPPED EGRECO_AENTR2:1:I.4


5 3E4DS0-FCC-FDPS-FACP-100003 3E4DS0-FCC-FDPS-FACP-100003_FACP1_FIRE_ALARM.3 TO THIS CHANNEL EGRECO_AENTR2:1:I.4 .IN SITE ALSO ,CABLE IS CONNECTED TO THIS SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
[FACP-1]
signal
FIREtoALARM
be confirmed
STATION\GRADE ENTRANCE 04 (FIRE ALARM ZONE NO. 6)EGRECO 3E4DS0-EGR-BMS-RIOP-000013 SDI-1 AENTR2 1 2XSDI1 : 9,10 - SDI-16 4 AENTR2:1:I.4 DI I 4/14/2025 DONE

SIGNAL 3E4DS0-FCC-FDPS-FACP-100004_FACP1_SMOKE_DETECTOR.1 (FACP_ARR_UDT[1].FACP1_SMOKE_DETECTOR.1) EGRECO_AENTR2:1:I.5


6 3E4DS0-FCC-FDPS-FACP-100004 3E4DS0-FCC-FDPS-FACP-100004_FACP1_SMOKE_DETECTOR.1 IS MAPPED TO THIS CHANNEL EGRECO_AENTR2:1:I.5 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
[FACP-1]
signal
Smoke
to be
Detectors/Manual
confirmed station Entrance Chiller Yard & EST.05 - BOHEGRECO 3E4DS0-EGR-BMS-RIOP-000013 SDI-1 AENTR2 1 2XSDI1 : 11,12 - SDI-16 5 AENTR2:1:I.5 DI I 4/14/2025 DONE

SIGNAL 3E4DS0-FCC-FDPS-FACP-100004_FACP1_SMOKE_DETECTOR.2 (FACP_ARR_UDT[1].FACP1_SMOKE_DETECTOR.2) EGRECO_AENTR2:1:I.6


7 3E4DS0-FCC-FDPS-FACP-100004 3E4DS0-FCC-FDPS-FACP-100004_FACP1_SMOKE_DETECTOR.2 IS MAPPED TO THIS CHANNEL EGRECO_AENTR2:1:I.6 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Smokesignal
Detectors-
to be confirmed
EST-01 EGRECO 3E4DS0-EGR-BMS-RIOP-000013 SDI-1 AENTR2 1 2XSDI1 : 13,14 - SDI-16 6 AENTR2:1:I.6 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-CO03-EVS-MFD-101138_OPN_CLS_CMD (EVS_FD_ARR_UDT[2].OPN_CLS_CMD) IS MAPPED TO THE
EGRECO_AENTR2:0:O.0
17 3E4DS0-CO03-EVS-MFD-101138 3E4DS0-CO03-EVS-MFD-101138_OPN_CLS_CMD CHANNEL EGRECO_AENTR2:0:O.0 .IN SITE ALSO ,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN COMMAND
signal to be confirmed EGRECO 3E4DS0-EGR-BMS-RIOP-000013 SDO-1 AENTR2 0 - 2SR1 : 11,14 SDO-16 0 AENTR2:0:O.0 DO O 4/14/2025 DONE
SIGNAL (FULG_000001 TANK LEAK DETECTION )FULG_ARR_UDT[1].TANK_1_LD IS MAPPED TO THIS CHANNEL
EGRECO_AENTR1:0:I.1
34 SPARE SPARE EGRECO_AENTR1:0:I.1 .IN SITE,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-1 AENTR1 0 2XDI1 : 3,4 - DI-16 1 AENTR1:0:I.1 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-GR-ELS-FULG-000001-V_OPN_FB (FULG_VALVE_ARR_UDT[1].OPN_FB) IS MAPPED TO THIS CHANNEL
EGRECO_AENTR1:0:I.3
36 3E4DS0-GR-ELS-FULG-000001-V 3E4DS0-GR-ELS-FULG-000001-V_OPN_FB EGRECO_AENTR1:0:I.3 IN LOGIX.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN FUEL
signalTANK
to beNO.
confirmed
1 VALVE POSITION EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-1 AENTR1 0 2XDI1 : 7,8 - DI-16 3 AENTR1:0:I.3 DI I 4/14/2025 DONE
SIGNAL (FULG_000002 TANK LEAK DETECTION )FULG_ARR_UDT[2].TANK_1_LD IS MAPPED TO THIS CHANNEL
EGRECO_AENTR1:4:I.1
50 SPARE SPARE EGRECO_AENTR1:4:I.Data.1 .IN SITE,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-2 AENTR1 4 2XDI2 : 3,4 - DI-32 1 AENTR1:4:I.Data.1 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-GR-POS-GSMP-000001-AUT2_RACKIN_FB (GMP_OG_ARR_UDT[2].RACKIN_FB) IS MAPPED TO THIS
EGRECO_AENTR1:4:I.7
56 3E4DS0-GR-POS-GSMP-000001-AUT2 3E4DS0-GR-POS-GSMP-000001-AUT2_RACKIN_FB CHANNEL EGRECO_AENTR1:4:I.Data.7 .IN SITE ALSO,IT IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
RACKEDsignal
IN STATUS
to be confirmed
OUTGOING FEED EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-2 AENTR1 4 2XDI2 : 15,16 - DI-32 7 AENTR1:4:I.Data.7 DI I 4/14/2025 DONE

SIGNAL 3E4DS0-MER-HVAC-MAU-050000_OPN_FB (D_MAU_ARR_UDT[2].OPN_FB) IS MAPPED TO NON FM200 MFD LOOP EGRECO_AENTR1:4:I.21


EGRECO_AENTR1:4:I.Data.29,SINCE THE CHANNEL EGRECO_AENTR1:4:I.Data.21 IS FAULTY.THERE IS NO CABLE
70 3E4DS0-MER-HVAC-MAU-050000 3E4DS0-MER-HVAC-MAU-050000_OPN_FB CONNECTED TO THIS CHANNEL. As per CWG RLM, this channel is spare at site, please check. EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-2 AENTR1 4 2XDI2 : 43,44 - DI-32 21 AENTR1:4:I.Data.21 DI I 4/14/2025 DONE

SIGNAL 3E4DS0-GR-ELS-FULG-000001 RETURN FLOW LEAK DETECTION (FULG_ARR_UDT[1].TANK_1_RET_LD) IS MAPPED


EGRECO_AENTR1:4:I.22
TO CHANNEL EGRECO_AENTR1:4:I.Data.22 IN LOGIX.IN SITE ALSO,IT IS CONNECTED TO THE SAME SIGNAL.BUT WITH
71 SPARE SPARE REFERENCE TO SIGNAL LIST REV 13.07,IT IS DELETED.IT NEED TO BE REMOVED FROM SITE & LOGIX ASWELL. As per CWG RLM, this channel is used at site, please check. SPARE EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-2 AENTR1 4 2XDI2 : 45,46 - DI-32 22 AENTR1:4:I.Data.22 DI I 4/14/2025 DONE

SIGNAL 3E4DS0-GR-ELS-FULG-000002 RETURN FLOW LEAK DETECTION (FULG_ARR_UDT[2].TANK_1_RET_LD) IS MAPPED


EGRECO_AENTR1:4:I.23
TO CHANNEL EGRECO_AENTR1:4:I.Data.23 IN LOGIX.IN SITE ALSO,IT IS CONNECTED TO THE SAME SIGNAL.BUT WITH
72 SPARE SPARE REFERENCE TO SIGNAL LIST REV 13.07,IT IS DELETED.IT NEED TO BE REMOVED FROM SITE & LOGIX ASWELL. As per CWG RLM, this channel is used at site, please check. SPARE EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-2 AENTR1 4 2XDI2 : 47,48 - DI-32 23 AENTR1:4:I.Data.23 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-FUT-MES-DP-000010_PANEL_HTY_FB (DP_ARR_UDT[1].PANEL_HTY_FB) IS MAPPED TO THIS CHANNEL
EGRECO_AENTR1:4:I.28
77 3E4DS0-FUT-MES-DP-000010 3E4DS0-FUT-MES-DP-000010_PANEL_HTY_FB EGRECO_AENTR1:4:I.Data.28 IN LOGIX ONLY.BUT IN SITE,THERE IS NO CABLE CONNECTED TO IT. As per CWG RLM, this channel is spare at site, please check. FUEL OIL PUMP PANEL HEALTHY STATUS EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-2 AENTR1 4 2XDI2 : 57,58 - DI-32 28 AENTR1:4:I.Data.28 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-MAU-050000_OPN_FB (D_MAU_ARR_UDT[2].OPN_FB) IS MAPPED TO
EGRECO_AENTR1:4:I.29
78 SPARE SPARE EGRECO_AENTR1:4:I.Data.29.IN SITE,ALSO CABLE IS CONNECTED TO THIS SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-2 AENTR1 4 2XDI2 : 59,60 - DI-32 29 AENTR1:4:I.Data.29 DI I 4/14/2025 DONE

EGRECO_AENTR1:1:I.0
SIGNAL 3E4DS0-GR-HVAC-FAN-070000_TRIP_FB (FAN_ARR_UDT[6].TRIP_FB) IS MAPPED TO THIS CHANNEL
81 3E4DS0-GR-HVAC-FAN-070000 3E4DS0-GR-HVAC-FAN-070000_TRIP_FB EGRECO_AENTR1:1:I.Data.0 .IN SITE,ALSO IT IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
EXHAUST
be confirmed
FAN EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-3 AENTR1 1 2XDI3 : 1,2 - DI-32 0 AENTR1:1:I.Data.0 DI I 4/14/2025 DONE

EGRECO_AENTR1:1:I.1
SIGNAL 3E4DS0-GR-HVAC-FAN-070000_LOC_FB (FAN_ARR_UDT[6].LOC_FB) IS MAPPED TO THIS CHANNEL
82 3E4DS0-GR-HVAC-FAN-070000 3E4DS0-GR-HVAC-FAN-070000_LOC_FB EGRECO_AENTR1:1:I.Data.1 .IN SITE,ALSO IT IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalSWITCH
to be confirmed
EXHAUST FAN EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-3 AENTR1 1 2XDI3 : 3,4 - DI-32 1 AENTR1:1:I.Data.1 DI I 4/14/2025 DONE

EGRECO_AENTR1:1:I.2
SIGNAL 3E4DS0-GR-HVAC-FAN-070000_REM_FB (FAN_ARR_UDT[6].REM_FB) IS MAPPED TO THIS CHANNEL
83 3E4DS0-GR-HVAC-FAN-070000 3E4DS0-GR-HVAC-FAN-070000_REM_FB EGRECO_AENTR1:1:I.Data.2 .IN SITE,ALSO IT IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalSWITCH
to be confirmed
EXHAUST FAN EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-3 AENTR1 1 2XDI3 : 5,6 - DI-32 2 AENTR1:1:I.Data.2 DI I 4/14/2025 DONE

EGRECO_AENTR1:1:I.3
SIGNAL 3E4DS0-GR-HVAC-FAN-070000_RUN_FB (FAN_ARR_UDT[6].RUN_FB) IS MAPPED TO THIS CHANNEL
84 3E4DS0-GR-HVAC-FAN-070000 3E4DS0-GR-HVAC-FAN-070000_RUN_FB EGRECO_AENTR1:1:I.Data.3 .IN SITE,ALSO IT IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
RUNNING
signal
OFtoEXHAUST
be confirmed
FAN EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-3 AENTR1 1 2XDI3 : 7,8 - DI-32 3 AENTR1:1:I.Data.3 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-GR-ELS-FULG-000001 RETURN FLOW LEAK DETECTION(FUT_ARR_UDT[1].TANK_1_RET_LD) IS
CONNECTED TO THIS CHANNEL EGRECO_AENTR1:1:I.Data.12 IN LOGIX.IN SITE ALSO,CABLE IS CONNECTED TO THIE
EGRECO_AENTR1:1:I.12
SAME SIGNAL.AS PER LATEST SIGNAL LIST REV 13.07,IF THIS SIGNAL IS N/A.THIS NEED TO BE REMOVED FROM LOGIX
93 SPARE SPARE AND SITE ASWELL. As per CWG RLM, this channel is used at site, please check. SPARE EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-3 AENTR1 1 2XDI3 : 25,26 - DI-32 12 AENTR1:1:I.Data.12 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-GR-HVAC-FAN-080000_TRIP_FB (FAN_ARR_UDT[7].TRIP_FB) IS MAPPED TO THIS CHANNEL
EGRECO_AENTR1:5:I.0
113 3E4DS0-GR-HVAC-FAN-080000 3E4DS0-GR-HVAC-FAN-080000_TRIP_FB EGRECO_AENTR1:5:I.Data.0 .IN SITE ALSO,IT IS CONNECTED TO THE SAME SIGNAL As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
EXHAUST
be confirmed
FAN EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-4 AENTR1 5 2XDI4 : 1,2 - DI-32 0 AENTR1:5:I.Data.0 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-GR-HVAC-FAN-080000_LOC_FB (FAN_ARR_UDT[7].LOC_FB) IS MAPPED TO THIS CHANNEL
EGRECO_AENTR1:5:I.1
114 3E4DS0-GR-HVAC-FAN-080000 3E4DS0-GR-HVAC-FAN-080000_LOC_FB EGRECO_AENTR1:5:I.Data.1 ..IN SITE ALSO,IT IS CONNECTED TO THE SAME SIGNAL As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalSWITCH
to be confirmed
EXHAUST FAN EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-4 AENTR1 5 2XDI4 : 3,4 - DI-32 1 AENTR1:5:I.Data.1 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-GR-HVAC-FAN-080000_REM_FB IS MAPPED TO THE CHANNEL EGRECO_AENTR1:5:I.Data.2 .IN SITE
EGRECO_AENTR1:5:I.2
115 3E4DS0-GR-HVAC-FAN-080000 3E4DS0-GR-HVAC-FAN-080000_REM_FB ALSO,IT IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalSWITCH
to be confirmed
EXHAUST FAN EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-4 AENTR1 5 2XDI4 : 5,6 - DI-32 2 AENTR1:5:I.Data.2 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-GR-HVAC-FAN-080000_RUN_FB IS MAPPED TO THE CHANNEL EGRECO_AENTR1:5:I.Data.3 .IN SITE
EGRECO_AENTR1:5:I.3
116 3E4DS0-GR-HVAC-FAN-080000 3E4DS0-GR-HVAC-FAN-080000_RUN_FB ALSO,IT IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
RUNNING
signal
OFtoEXHAUST
be confirmed
FAN EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-4 AENTR1 5 2XDI4 : 7,8 - DI-32 3 AENTR1:5:I.Data.3 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-GR-POS-DGFS-000001_FLOW_FB (DG_ARR_UDT[1].FLOW_FB) IS MAPPED TO THIS CHANNEL
EGRECO_AENTR1:5:I.22
135 3E4DS0-GR-POS-DGFS-000001 3E4DS0-GR-POS-DGFS-000001_FLOW_FB EGRECO_AENTR1:5:I.Data.22 .IN SITE ALSO,IT IS CONNECTED TO THE SAME SIGNAL As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Chilledsignal
waterto
supply
be confirmed
flow EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-4 AENTR1 5 2XDI4 : 45,46 - DI-32 22 AENTR1:5:I.Data.22 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-GR-POS-DGFS-000002_FLOW_FB (DG_ARR_UDT[2].FLOW_FB) IS MAPPED TO THIS CHANNEL
EGRECO_AENTR1:5:I.23
136 3E4DS0-GR-POS-DGFS-000002 3E4DS0-GR-POS-DGFS-000002_FLOW_FB EGRECO_AENTR1:5:I.Data.23 .IN SITE ALSO,IT IS CONNECTED TO THE SAME SIGNAL As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Chilledsignal
waterto
supply
be confirmed
flow EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DI-4 AENTR1 5 2XDI4 : 47,48 - DI-32 23 AENTR1:5:I.Data.23 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-GR-HVAC-FAN-070000_ON_OFF_CMD (FAN_ARR_UDT[6].ON_OFF_CMD) IS MAPPED TO THIS RELAY
EGRECO_AENTR1:2:O.4
149 3E4DS0-GR-HVAC-FAN-070000 3E4DS0-GR-HVAC-FAN-070000_ON_OFF_CMD EGRECO_AENTR1:2:O.Data.4 .IN SITE,ALSO CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
EXHAUST
be confirmed
FAN EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DO-1 AENTR1 2 - 2R5 : 11,14 DO-32 4 AENTR1:2:O.Data.4 DO O 4/14/2025 DONE
SIGNAL 3E4DS0-GR-HVAC-FAN-080000_ON_OFF_CMD (FAN_ARR_UDT[7].ON_OFF_CMD) IS MAPPED TO THIS RELAY
EGRECO_AENTR1:2:O.5
150 3E4DS0-GR-HVAC-FAN-080000 3E4DS0-GR-HVAC-FAN-080000_ON_OFF_CMD EGRECO_AENTR1:2:O.Data.5 .IN SITE,ALSO CABLE IS CONNECTED TO THE SAME As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
EXHAUST
be confirmed
FAN EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DO-1 AENTR1 2 - 2R6 : 11,14 DO-32 5 AENTR1:2:O.Data.5 DO O 4/14/2025 DONE
SIGNAL 3E4DS0-GR-POS-GSMP-000001-INC1_CLS_CMD (GMP_INC_ARR_UDT[1].CLS_CMD) IS MAPPED TO THIS RELAY
EGRECO_AENTR1:2:O.15
160 3E4DS0-GR-POS-GSMP-000001-INC1 3E4DS0-GR-POS-GSMP-000001-INC1_CLS_CMD EGRECO_AENTR1:2:O.Data.15 .IN SITE ALSO,CABLE IS CONNECTED TO THIS SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
INCOMING
to be confirmed
FROM GENERATOR EGRECO 3E4DS0-EGR-BMS-RIOP-000013 DO-1 AENTR1 2 - 2R16 : 11,14 DO-32 15 AENTR1:2:O.Data.15 DO O 4/14/2025 DONE

SIGNAL 3E4DS0-PLT01-MES-LDR-000004-TRACK2DPE_LADDER_MOVED_FB (LDR_ARR_UDT[4].LADDER_MOVED_FB)IS ELE03EPO_AENTR1:0:I.1


2 3E4DS0-PLT01-MES-LDR-000004-TRACK2DPE 3E4DS0-PLT01-MES-LDR-000004-TRACK2DPE_LADDER_MOVED_FB MAPPED TO THIS CHANNEL ELE03EPO_AENTR1:0:I.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
LEDDERsignal
MOVEDto beFEEDBACK
confirmed ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 SDI-1 AENTR1 0 1XSDI1 : 3,4 - SDI-16 1 AENTR1:0:I.1 DI I 4/14/2025 DONE

SIGNAL 3E4DS0-FCC-FDPS-FACP-200003_FACP2_FIRE_ALARM.1(FACP_ARR_UDT[2].FACP2_FIRE_ALARM.1) IS MAPPED ELE03EPO_AENTR1:0:I.2


3 3E4DS0-FCC-FDPS-FACP-200003 3E4DS0-FCC-FDPS-FACP-200003_FACP2_FIRE_ALARM.1 TO THIS CHANNEL ELE03EPO_AENTR1:0:I.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
[FACP-2]
signal
Fireto
alarm
be confirmed
Station\Platform-Mezzanine (Smoke Zone No. 1) ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 SDI-1 AENTR1 0 1XSDI1 : 5,6 - SDI-16 2 AENTR1:0:I.2 DI I 4/14/2025 DONE

SIGNAL 3E4DS0-FCC-FDPS-FACP-200003_FACP2_FIRE_ALARM.2 (FACP_ARR_UDT[2].FACP2_FIRE_ALARM.2) IS MAPPED ELE03EPO_AENTR1:0:I.3


4 3E4DS0-FCC-FDPS-FACP-200003 3E4DS0-FCC-FDPS-FACP-200003_FACP2_FIRE_ALARM.2 TO THIS CHANNEL ELE03EPO_AENTR1:0:I.3.IT SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
[FACP-2]
signal
Fireto
alarm
be confirmed
Station\Concourse Paid and Un-Paid Area (Fire Alarm ZoneELE03EPO
No. 2) 3E4DS0-ELE03-BMS-RIOP-000028 SDI-1 AENTR1 0 1XSDI1 : 7,8 - SDI-16 3 AENTR1:0:I.3 DI I 4/14/2025 DONE

SIGNAL 3E4DS0-FCC-FDPS-FACP-200003_FACP2_FIRE_ALARM.3 (FACP_ARR_UDT[2].FACP2_FIRE_ALARM.3) IS MAPPED ELE03EPO_AENTR1:0:I.4


5 3E4DS0-FCC-FDPS-FACP-200003 3E4DS0-FCC-FDPS-FACP-200003_FACP2_FIRE_ALARM.3 TO THIS CHANNEL ELE03EPO_AENTR1:0:I.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
[FACP-2]
signal
Fireto
alarm
be confirmed
Station\Concourse North (Fire Alarm Zone No. 3) ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 SDI-1 AENTR1 0 1XSDI1 : 9,10 - SDI-16 4 AENTR1:0:I.4 DI I 4/14/2025 DONE
[FACP-2] Smoke Detectors - Technical Elevator
SIGNAL 3E4DS0-FCC-FDPS-FACP-200004_FACP2_SMOKE_DETECTOR.3 (FACP_ARR_UDT[2].FACP2_SMOKE_DETECTOR.3) ELE03EPO_AENTR1:0:I.5
(01,02,03,04) Lobby - BOH
6 3E4DS0-FCC-FDPS-FACP-200004 3E4DS0-FCC-FDPS-FACP-200004_FACP2_SMOKE_DETECTOR.3 IS MAPPED TO THIS CHANNEL ELE03EPO_AENTR1:0:I.5 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 SDI-1 AENTR1 0 1XSDI1 : 11,12 - SDI-16 5 AENTR1:0:I.5 DI I 4/14/2025 DONE

ELE03EPO_AENTR2:0:I.13
SIGNAL 3E4DS0-ELE01-ELS-PPB-002101_INC_OPN_CLS_FB (PPB_ICB_ARR_UDT[1].INC_OPN_CLS_FB) IS MAPPED TO THIS
46 3E4DS0-ELE01-ELS-PPB-002101 3E4DS0-ELE01-ELS-PPB-002101_INC_OPN_CLS_FB CHANNEL ELE03EPO_AENTR2:0:I.Data.13 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
INCOMING
signalCIRCUIT
to be confirmed
TO PP ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 DI-1 AENTR2 0 1XDI1 : 27,28 - DI-32 13 AENTR2:0:I.Data.13 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-ELE01-HVAC-WLKD-000031_LEAK_ALM (WLKD_ARR_UDT[31].LEAK_ALM) IS MAPPED TO THIS CHANNEL
ELE03EPO_AENTR2:0:I.14
47 3E4DS0-ELE01-HVAC-WLKD-000031 3E4DS0-ELE01-HVAC-WLKD-000031_LEAK_ALM ELE03EPO_AENTR2:0:I.Data.14 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WATERsignal
LEAKto
DETECTION
be confirmed ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 DI-1 AENTR2 0 1XDI1 : 29,30 - DI-32 14 AENTR2:0:I.Data.14 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-ELE03-HVAC-WLKD-000033_LEAK_ALM (WLKD_ARR_UDT[33].LEAK_ALM) IS MAPPED TO THIS CHANNEL
ELE03EPO_AENTR2:0:I.15
48 3E4DS0-ELE03-HVAC-WLKD-000033 3E4DS0-ELE03-HVAC-WLKD-000033_LEAK_ALM ELE03EPO_AENTR2:0:I.Data.15.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WATERsignal
LEAKto
DETECTION
be confirmed ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 DI-1 AENTR2 0 1XDI1 : 31,32 - DI-32 15 AENTR2:0:I.Data.15 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-PSD-HVAC-WLKD-000034_LEAK_ALM (WLKD_ARR_UDT[34].LEAK_ALM) IS MAPPED TO THIS CHANNEL
ELE03EPO_AENTR2:0:I.16
49 3E4DS0-PSD-HVAC-WLKD-000034 3E4DS0-PSD-HVAC-WLKD-000034_LEAK_ALM ELE03EPO_AENTR2:0:I.Data.16.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WATERsignal
LEAKto
DETECTION
be confirmed ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 DI-1 AENTR2 0 1XDI1 : 33,34 - DI-32 16 AENTR2:0:I.Data.16 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-RCR-HVAC-WLKD-000035_LEAK_ALM (WLKD_ARR_UDT[35].LEAK_ALM) IS MAPPED TO THIS CHANNEL
ELE03EPO_AENTR2:0:I.17
50 3E4DS0-RCR-HVAC-WLKD-000035 3E4DS0-RCR-HVAC-WLKD-000035_LEAK_ALM ELE03EPO_AENTR2:0:I.Data.17.IN SITE ALSO,CABLE IS MAPPED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WATERsignal
LEAKto
DETECTION
be confirmed ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 DI-1 AENTR2 0 1XDI1 : 35,36 - DI-32 17 AENTR2:0:I.Data.17 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-RCR-HVAC-WLKD-000036_LEAK_ALM (WLKD_ARR_UDT[36].LEAK_ALM) IS MAPPED TO THIS CHANNEL
ELE03EPO_AENTR2:0:I.18
51 3E4DS0-RCR-HVAC-WLKD-000036 3E4DS0-RCR-HVAC-WLKD-000036_LEAK_ALM ELE03EPO_AENTR2:0:I.Data.18 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WATERsignal
LEAKto
DETECTION
be confirmed ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 DI-1 AENTR2 0 1XDI1 : 37,38 - DI-32 18 AENTR2:0:I.Data.18 DI I 4/14/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL ELE03EPO_AENTR2:0:I.Data.27.IN SITE,IT IS A EXTRA CABLE.WHICH
ELE03EPO_AENTR2:0:I.27
60 3E4DS0-ELE01-HVAC-MFD-014127 3E4DS0-ELE01-HVAC-MFD-014127_OPN_FB NEED TO BE REMOVED FROM SITE. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTORIZED
signal to
FIRE
beDAMPER
confirmed
FM200 OPEN ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 DI-1 AENTR2 0 1XDI1 : 55,56 - DI-32 27 AENTR2:0:I.Data.27 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-ELE01-HVAC-MFD-014111_OPN_FB (HVAC_FD_ARR_UDT[83].OPN_FB) IS MAPPED TO THIS CHANNEL
ELE03EPO_AENTR2:0:I.28
61 3E4DS0-ELE01-HVAC-MFD-014111 3E4DS0-ELE01-HVAC-MFD-014111_OPN_FB ELE03EPO_AENTR2:0:I.Data.28 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTORIZED
signal to
FIRE
beDAMPER
confirmed
FM200 OPEN ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 DI-1 AENTR2 0 1XDI1 : 57,58 - DI-32 28 AENTR2:0:I.Data.28 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-ELE01-HVAC-MFD-014118_OPN_FB(HVAC_FD_ARR_UDT[84].OPN_FB) IS MAPPED TO THIS CHANNEL
ELE03EPO_AENTR2:0:I.29
62 3E4DS0-ELE01-HVAC-MFD-014118 3E4DS0-ELE01-HVAC-MFD-014118_OPN_FB ELE03EPO_AENTR2:0:I.Data.29 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTORIZED
signal to
FIRE
beDAMPER
confirmed
FM200 OPEN ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 DI-1 AENTR2 0 1XDI1 : 59,60 - DI-32 29 AENTR2:0:I.Data.29 DI I 4/14/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL ELE03EPO_AENTR2:0:I.Data.30.IN SITE,IT IS A EXTRA CABLE.WHICH
ELE03EPO_AENTR2:0:I.30
63 3E4DS0-ELE01-HVAC-MFD-014134 3E4DS0-ELE01-HVAC-MFD-014134_OPN_FB NEED TO BE REMOVED FROM SITE. As per CWG RLM, this channel is spare at site, please check. MOTORIZED FIRE DAMPER FM200 OPEN ELE03EPO 3E4DS0-ELE03-BMS-RIOP-000028 DI-1 AENTR2 0 1XDI1 : 61,62 - DI-32 30 AENTR2:0:I.Data.30 DI I 4/14/2025 DONE
IN LOGIX ,SIGNAL 3E4DS0-STT-HVAC-FAN-050000_OPN_FB(FAN_ARR_UDT[4].OPN_FB) IS MAPPED TO THIS CHANNEL
MOTORIZED FIRE DAMPERS NON FM200 OPEN FPRWCO_AENTR1:0:I.25
26 3E4DS0-STT-HVAC-FAN-050000 3E4DS0-STT-HVAC-FAN-050000_OPN_FB FPRWCO_AENTR1:0:I.Data.25 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed FPRWCO 3E4DS0-FPR-BMS-RIOP-000005 DI-1 AENTR1 0 1XDI1 : 51,52 - DI-32 25 AENTR1:0:I.Data.25 DI I 4/14/2025 DONE
IN LOGIX,SIGNAL 3E4DS0-TRR-HVAC-FAN-060000_OPN_FB (FAN_ARR_UDT[5].OPN_FB) IS MAPPED TO THIS CHANNEL
MOTORIZED FIRE DAMPERS NON FM200 OPEN FPRWCO_AENTR1:0:I.26
27 3E4DS0-TRR-HVAC-FAN-060000 3E4DS0-TRR-HVAC-FAN-060000_OPN_FB FPRWCO_AENTR1:0:I.Data.26.IN SITE ALSO ,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed FPRWCO 3E4DS0-FPR-BMS-RIOP-000005 DI-1 AENTR1 0 1XDI1 : 53,54 - DI-32 26 AENTR1:0:I.Data.26 DI I 4/14/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,IT IS A EXTRA CABLE.WHICH NEED TO BE REMOVED FROM
LV01ETO_AENTR1:1:I.4
37 SPARE SPARE SITE. As per CWG RLM, this channel is used at site, please check. SPARE LV01ETO 3E4DS0-LV01-BMS-RIOP-000021 DI-2 AENTR1 1 2XDI2 : 9,10 - DI-32 4 AENTR1:1:I.Data.4 DI I 4/14/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,IT IS A EXTRA CABLE.WHICH NEED TO BE REMOVED FROM
LV01ETO_AENTR1:2:I.4
69 SPARE SPARE SITE. As per CWG RLM, this channel is used at site, please check. SPARE LV01ETO 3E4DS0-LV01-BMS-RIOP-000021 DI-3 AENTR1 2 2XDI3 : 9,10 - DI-32 4 AENTR1:2:I.Data.4 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-LV01-ELS-MDB-001001-AUT1_REM_FB (MDB_OG_ARR_UDT[2].REM_FB) IS MAPPED TO THIS CHANNEL
LV01ETO_AENTR1:3:I.3
100 3E4DS0-LV01-ELS-MDB-001001-AUT1 3E4DS0-LV01-ELS-MDB-001001-AUT1_REM_FB LV01ETO_AENTR1:3:I.Data.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Auto Status
signalincoming
to be confirmed
breaker from AUT LV01ETO 3E4DS0-LV01-BMS-RIOP-000021 DI-4 AENTR1 3 2XDI4 : 7,8 - DI-32 3 AENTR1:3:I.Data.3 DI I 4/14/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,IT IS A EXTRA CABLE.WHICH NEED TO BE REMOVED FROM
LV02ETO_AENTR1:0:I.4
5 SPARE SPARE SITE. As per CWG RLM, this channel is used at site, please check. SPARE LV02ETO 3E4DS0-LV02-BMS-RIOP-000022 DI-1 AENTR1 0 2XDI1 : 9,10 - DI-32 4 AENTR1:0:I.Data.4 DI I 4/14/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,IT IS A EXTRA CABLE.WHICH NEED TO BE REMOVED FROM
LV02ETO_AENTR2:0:I.4
37 SPARE SPARE SITE. As per CWG RLM, this channel is used at site, please check. SPARE LV02ETO 3E4DS0-LV02-BMS-RIOP-000022 DI-2 AENTR2 0 2XDI2 : 9,10 - DI-32 4 AENTR2:0:I.Data.4 DI I 4/14/2025 DONE
3E4DS0-LV02-ELS-MDB-002001_TR3_REM_FB (MDB_INC_ARR_UDT[3].REM_FB) IS MAPPED ONLY IN LOGIX.IN
LV02ETO_AENTR2:2:I.19
180 3E4DS0-LV02-ELS-MDB-002001 3E4DS0-LV02-ELS-MDB-002001_REM_FB SITE,THERE IS NO PROVISION THIS SIGNAL & THERE IS NO CABLE CONNECTED TO THIS TERMINAL. As per CWG RLM, this channel is spare at site, please check. Auto Status incoming breaker from TR3 LV02ETO 3E4DS0-LV02-BMS-RIOP-000022 DI-6 AENTR2 2 2XDI6 : 39,40 - DI-32 19 AENTR2:2:I.Data.19 DI I 4/14/2025 DONE
3E4DS0-LV02-ELS-MDB-002001_TR4_REM_FB (MDB_INC_ARR_UDT[4].REM_FB) IS MAPPED ONLY IN LOGIX.IN
LV02ETO_AENTR2:2:I.20
181 3E4DS0-LV02-ELS-MDB-002001 3E4DS0-LV02-ELS-MDB-002001_REM_FB SITE,THERE IS NO PROVISION FOR THIS SIGNAL & THERE IS NO CABLE CONNECTED TO THIS TERMINAL. As per CWG RLM, this channel is spare at site, please check. Auto Status incoming breaker from TR4 LV02ETO 3E4DS0-LV02-BMS-RIOP-000022 DI-6 AENTR2 2 2XDI6 : 41,42 - DI-32 20 AENTR2:2:I.Data.20 DI I 4/14/2025 DONE

# General
PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM

DOCUMENT TITLE SHOP DRAWING-DEEP UNDERGROUND STATION-3E4-BMS-INPUT/OUTPUT SCHEDULE

DOCUMENT NO. M-ANM-3E4DS0-CJ00-SCH-000002

MODULE RELAY MODULE CHANNE


SR. NO. EQUIPMENT TAG PLC TAG EASA SITE Response RLM COMMENTS FROM CWG DESCRIPTION PANEL SHORT TAG (OLD) PANEL FULL TAG (NEW) RACK NO. SLOT NO. TERMINAL NO. PLC IO ADDRESS MODULE ID DATE STATUS
ID NO. TYPE L NO.
SIGNAL 3E4DS0-MER01-HVAC-AHU-090000_DAMPER_OPN_FB (S_AHU_ARR_UDT[9].OPN_FB) IS MAPPED TO THIS
MOTORIZED FIRE DAMPERS NON FM200 MER01EMO_AENTR1:1:I.10
27 3E4DS0-MER01-HVAC-AHU-090000 3E4DS0-MER01-HVAC-AHU-090000_OPN_FB CHANNEL (MER01EMO_AENTR1:1:I.Data.10).IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01EMO 3E4DS0-MER01-BMS-RIOP-000025 DI-2 AENTR1 1 2XDI2 : 21,22 - DI-32 10 AENTR1:1:I.Data.10 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MU1B-HVAC-FAN-020000 (FAN_ARR_UDT[2].OPN_FB) IS MAPPED TO THIS CHANNEL
MER01EMO_AENTR1:1:I.Data.26 .THESE ARE DAMPERS(Motorized Fire Dampers not FM200 (MFD-
MER01EMO_AENTR1:1:I.26
021104&021103&023136)) ASSOSIATED WITH FAN.TAG IN FIELD,NEED TO BE UPDATED AS PER LATEST SIGNAL LIST REV
43 SPARE SPARE 13.07 As per CWG RLM, this channel is used for MFD-613136 at site, please check. SPARE MER01EMO 3E4DS0-MER01-BMS-RIOP-000025 DI-2 AENTR1 1 2XDI2 : 53,54 - DI-32 26 AENTR1:1:I.Data.26 DI I 4/14/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,ALSO THERE IS NO CABLE CONNECTED TO THIS TERMINAL.IT
MER01EMO_AENTR1:1:I.28
45 3E4DS0-EBR-HVAC-MFD-23135 3E4DS0-EBR-HVAC-MFD-23135_OPN_FB IS A SPARE TERMINAL. As per CWG RLM, this channel is spare at site, please check. MOTORIZED FIRE DAMPER FM200 OPEN MER01EMO 3E4DS0-MER01-BMS-RIOP-000025 DI-2 AENTR1 1 2XDI2 : 57,58 - DI-32 28 AENTR1:1:I.Data.28 DI I 4/14/2025 DONE

SIGNAL 3E4DS0-MU1A-HVAC-MAU-030000_DAMPER FEEDBACK (S_MAU_ARR_UDT[3].OPN_FB) IS MAPPED TO THIS


NON FM200 MFD LOOP MER01EMO_AENTR1:1:I.29
CHANNEL MER01EMO_AENTR1:1:I.Data.29 .THESE ARE DAMPERS (Motorized Fire Dampers not FM200 (MFD-
251105&493131&251106&252107)) ASSOCIATED WITH MAU.TAG IN THE FIELD NEED TO BE UPDATED AS PER LATEST
46 3E4DS0-MU1A-HVAC-MAU-030000 3E4DS0-MU1A-HVAC-MAU-030000_OPN_FB SIGNAL LIST REV 13.07 As per CWG RLM, this channel is used for MFD-494139 at site, please check. MER01EMO 3E4DS0-MER01-BMS-RIOP-000025 DI-2 AENTR1 1 2XDI2 : 59,60 - DI-32 29 AENTR1:1:I.Data.29 DI I 4/14/2025 DONE

SIGNAL FCU-210004 (FCU_ARR_UDT[108].OPN_FB) IS MAPPED TO THIS CHANNEL MER01EMO_AENTR1:2:I.Data.1 IN MER01EMO_AENTR1:2:I.1


50 SPARE SPARE LOGIX. As per CWG RLM, this channel is used at site, please check. SPARE MER01EMO 3E4DS0-MER01-BMS-RIOP-000025 DI-3 AENTR1 2 2XDI3 : 3,4 - DI-32 1 AENTR1:2:I.Data.1 DI I 4/14/2025 DONE

SIGNAL FCU-210001 (FCU_ARR_UDT[105].OPN_FB) IS MAPPED TO THIS CHANNEL MER01EMO_AENTR1:2:I.Data.2 IN MER01EMO_AENTR1:2:I.2


51 SPARE SPARE LOGIX. As per CWG RLM, this channel is used at site, please check. SPARE MER01EMO 3E4DS0-MER01-BMS-RIOP-000025 DI-3 AENTR1 2 2XDI3 : 5,6 - DI-32 2 AENTR1:2:I.Data.2 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MU1B-HVAC-FAN-020000_3E4DS0-EBR-HVAC-MFD-23135 OPN_FB (HVAC_FD_ARR_UDT[80].OPN_FB) IS
MAPPED TO THIS CHANNEL MER01EMO_AENTR1:2:I.19 IN LOGIX.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME MOTORIZED FIRE DAMPERS NON FM200 OPEN MER01EMO_AENTR1:2:I.19
68 3E4DS0-MU1B-HVAC-FAN-020000 3E4DS0-MU1B-HVAC-FAN-020000_OPN_FB SIGNAL. As per CWG RLM, this channel is used for MFD-023135 at site, please check. MER01EMO 3E4DS0-MER01-BMS-RIOP-000025 DI-3 AENTR1 2 2XDI3 : 39,40 - DI-32 19 AENTR1:2:I.Data.19 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MU1B-HVAC-FAN-010000_OPN_FB(FAN_ARR_UDT[1].OPN_FB) IS MAPPED TO THIS CHANNEL
MER01EMO_AENTR1:2:I.Data.20 .IN SITE CABLE IS CONNECTED TO THIS SIGNAL DAMPERS (Motorized Fire Dampers not
MOTORIZED FIRE DAMPERS NON FM200 OPEN MER01EMO_AENTR1:2:I.20
FM200 (MFD-021102&021101&023133)) ASSOSIATED WITH FAN-010000.IN SITE,DAMPER FERRULE TAG NEED TO BE
69 3E4DS0-MU1B-HVAC-FAN-010000 3E4DS0-MU1B-HVAC-FAN-010000_OPN_FB UPDATED AS PER LATEST SIGNAL LIST REV 13.07 As per CWG RLM, this channel is used for MFD-023132 at site, please check. MER01EMO 3E4DS0-MER01-BMS-RIOP-000025 DI-3 AENTR1 2 2XDI3 : 41,42 - DI-32 20 AENTR1:2:I.Data.20 DI I 4/14/2025 DONE
IN LOGIX THIS SIGNAL (S_AHU_ARR_UDT[8].SS2_LOC_FB) IS MAPPED TO THIS CHANNEL
MER01EMO_AENTR1:2:I.24
73 3E4DS0-MER01-HVAC-AHU-080000 3E4DS0-MER01-HVAC-AHU-080000_SS2_LOC_FB MER01EMO_AENTR1:2:I.Data.24 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Manual/Local
signal toBMS
be confirmed
Selector Switch (SS2) Status MER01EMO 3E4DS0-MER01-BMS-RIOP-000025 DI-3 AENTR1 2 2XDI3 : 49,50 - DI-32 24 AENTR1:2:I.Data.24 DI I 4/14/2025 DONE
IN LOGIX ONLY, THIS SIGNAL (S_AHU_ARR_UDT[8].SS2_REM_FB) IS MAPPED TO THIS CHANNEL
MER01EMO_AENTR1:2:I.Data.25 .IN SITE,THERE IS NO SIGNAL PROVISION.SO THERE IS NO CABLE CONNECTED TO THIS MER01EMO_AENTR1:2:I.25
74 3E4DS0-MER01-HVAC-AHU-080000 3E4DS0-MER01-HVAC-AHU-080000_SS2_REM_FB TERMINAL. As per CWG RLM, this channel is spare at site, please check. Start Push Button RM relay activated/deactivated Status MER01EMO 3E4DS0-MER01-BMS-RIOP-000025 DI-3 AENTR1 2 2XDI3 : 51,52 - DI-32 25 AENTR1:2:I.Data.25 DI I 4/14/2025 DONE
IN LOGIX THIS SIGNAL (S_AHU_ARR_UDT[9].SS2_LOC_FB) IS MAPPED TO THIS CHANNEL MER01EMO_AENTR1:2:I.26 .IN
MER01EMO_AENTR1:2:I.26
75 3E4DS0-MER01-HVAC-AHU-090000 3E4DS0-MER01-HVAC-AHU-090000_SS2_LOC_FB SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Manual/Local
signal toBMS
be confirmed
Selector Switch (SS2) Status MER01EMO 3E4DS0-MER01-BMS-RIOP-000025 DI-3 AENTR1 2 2XDI3 : 53,54 - DI-32 26 AENTR1:2:I.Data.26 DI I 4/14/2025 DONE
IN LOGIX ONLY, THIS SIGNAL (SS_AHU_ARR_UDT[9].SS2_REM_FB) IS MAPPED TO THIS CHANNEL
MER01EMO_AENTR1:2:I.Data.27.IN SITE,THERE IS NO SIGNAL PROVISION.SO THERE IS NO CABLE CONNECTED TO THIS MER01EMO_AENTR1:2:I.27
76 3E4DS0-MER01-HVAC-AHU-090000 3E4DS0-MER01-HVAC-AHU-090000_SS2_REM_FB TERMINAL. As per CWG RLM, this channel is spare at site, please check. Start Push Button RM relay activated/deactivated Status MER01EMO 3E4DS0-MER01-BMS-RIOP-000025 DI-3 AENTR1 2 2XDI3 : 55,56 - DI-32 27 AENTR1:2:I.Data.27 DI I 4/14/2025 DONE

SIGNAL 3E4DS0-MER01-HVAC-AHU-080000_SF_ON_OFF_CMD(S_AHU_ARR_UDT[8].SF_ON_OFF_CMD) IS MAPPED TO MER01EMO_AENTR1:3:O.6


103 3E4DS0-MER01-HVAC-AHU-080000 3E4DS0-MER01-HVAC-AHU-080000_SF_ON_OFF_CMD THIS RELAY MER01EMO_AENTR1:3:O.6. IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Switch signal
On AHU to be
Power
confirmed
Supply MER01EMO 3E4DS0-MER01-BMS-RIOP-000025 DO-1 AENTR1 3 - 2R7 : 11,14 DO-16 6 AENTR1:3:O.6 DO O 4/14/2025 DONE

SIGNAL 3E4DS0-MER01-HVAC-AHU-090000_SF_ON_OFF_CMD (S_AHU_ARR_UDT[9].SF_ON_OFF_CMD) IS MAPPED TO MER01EMO_AENTR1:3:O.7


104 3E4DS0-MER01-HVAC-AHU-090000 3E4DS0-MER01-HVAC-AHU-090000_SF_ON_OFF_CMD THIS RELAY MER01EMO_AENTR1:3:O.7 .IN SITE ALSO ,THE CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Switch signal
On AHU to be
Power
confirmed
Supply MER01EMO 3E4DS0-MER01-BMS-RIOP-000025 DO-1 AENTR1 3 - 2R8 : 11,14 DO-16 7 AENTR1:3:O.7 DO O 4/14/2025 DONE
3E4DS0-MER01-HVAC-AHURT-090001_RM_TEMP IS MAPPED TO THIS CHANNEL MER01EMO_AENTR1:6:I.Ch7Data IN
MER01EMO_AENTR1:6:chdata.7
136 3E4DS0-MER01-HVAC-AHURT-090001 3E4DS0-MER01-HVAC-AHURT-090001_RM_TEMP LOGIX.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
ROOMsignal
TEMPERATURE
to be confirmed MER01EMO 3E4DS0-MER01-BMS-RIOP-000025 AI-3 AENTR1 6 2XAI3 : 15,16 - AI-08 7 AENTR1:6:I.Ch7Data AI chdata 4/14/2025 DONE
[FACP-1] Smoke Detectors/Manual station - Concourse
SIGNAL 3E4DS0-FCC-FDPS-FACP-100004_FACP1_SMOKE_DETECTOR.3 (FACP_ARR_UDT[1].FACP1_SMOKE_DETECTOR.3)
3E4DS0-FCC-FDPS-FACP-100004 3E4DS0-FCC-FDPS-FACP-100004_FACP1_SMOKE_DETECTOR.3 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal
(BOH and NottoFM-200
be confirmed
rooms and Not SE and MER01WCO SDI-1 AENTR2 0 1XSDI1 : 7,8 - SDI-16 3 MER01WCO_AENTR2:0:I.3
IS MAPPED TO THIS CHANNEL MER01WCO_AENTR2:0:I.3 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
4 TVR,OTE/UPE Rooms) 3E4DS0-MER01-BMS-RIOP-000002 AENTR2:0:I.3 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-FCC-FDPS-FACP-100004_FACP1_SMOKE_DETECTOR.4 (FACP_ARR_UDT[1].FACP1_SMOKE_DETECTOR.4)
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR2:0:I.4
IS MAPPED TO THIS CHANNEL MER01WCO_AENTR2:0:I.4 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
5 3E4DS0-FCC-FDPS-FACP-100004 3E4DS0-FCC-FDPS-FACP-100004_FACP1_SMOKE_DETECTOR.4 [FACP-1] Smoke Detectors - Concourse (SE Rooms and TVR,OTE/UPE Rooms)MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 SDI-1 AENTR2 0 1XSDI1 : 9,10 - SDI-16 4 AENTR2:0:I.4 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-FCC-FDPS-FACP-100004_FACP1_SMOKE_DETECTOR.5 (FACP_ARR_UDT[1].FACP1_SMOKE_DETECTOR.5)
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR2:0:I.5
IS MAPPED TO THIS CHANNEL MER01WCO_AENTR2:0:I.5 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
6 3E4DS0-FCC-FDPS-FACP-100004 3E4DS0-FCC-FDPS-FACP-100004_FACP1_SMOKE_DETECTOR.5 Smoke Detectors- EST-02 MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 SDI-1 AENTR2 0 1XSDI1 : 11,12 - SDI-16 5 AENTR2:0:I.5 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-FCC-FDPS-FACP-100004_FACP1_SMOKE_DETECTOR.6 (FACP_ARR_UDT[1].FACP1_SMOKE_DETECTOR.6)
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR2:0:I.6
IS MAPPED TO THIS CHANNEL MER01WCO_AENTR2:0:I.6 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
7 3E4DS0-FCC-FDPS-FACP-100004 3E4DS0-FCC-FDPS-FACP-100004_FACP1_SMOKE_DETECTOR.6 Smoke Detectors- EST-03 MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 SDI-1 AENTR2 0 1XSDI1 : 13,14 - SDI-16 6 AENTR2:0:I.6 DI I 4/14/2025 DONE
3E4DS0-UA 01-MES-SESD-000001_ENABLE_DISABLE_FB (SESD_ARR_UDT[1].OPN_FB) IS MAPPED TO THIS CHANNEL
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR2:0:I.9
10 3E4DS0-UA 01-MES-SESD-000001 3E4DS0-UA 01-MES-SESD-000001_ENABLE_DISABLE_FB MER01WCO_AENTR2:0:I.9 .IN SITE ALSO,THE CABLE IS CONNECTED TO THE SAME SIGNAL Enable/Disable status Entry Doors MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 SDI-1 AENTR2 0 1XSDI1 : 19,20 - SDI-16 9 AENTR2:0:I.9 DI I 4/14/2025 DONE
SIGNAL FACP_ARR_UDT[1].FACP1_SMOKE_DETECTOR.7 IS MAPPED TO THIS CHANNEL MER01WCO_AENTR2:0:I.10.IN
MER01WCO_AENTR2:0:I.10
11 SPARE SPARE SITE ALSO,THE CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 SDI-1 AENTR2 0 1XSDI1 : 21,22 - SDI-16 10 AENTR2:0:I.10 DI I 4/14/2025 DONE

SIGNAL FACP_ARR_UDT[1].FACP1_SMOKE_DETECTOR.7 IS MAPPED TO THIS CHANNEL MER01WCO_AENTR2:0:I.10.IN


MER01WCO_AENTR2:0:I.11
SITE ALSO,THE CABLE IS CONNECTED TO THE SAME SIGNAL. THIS CHANNEL MER01WCO_AENTR2:0:I.11 , IS SPARE IN
12 3E4DS0-FCC-FDPS-FACP-100004 3E4DS0-FCC-FDPS-FACP-100004_FACP1_SMOKE_DETECTOR.7 SITE,THERE IS NO CABLE CONNECTED TO THIS TERMINAL.THERE IS NO MAPPING IN LOGIX AS WELL. As per CWG RLM, this channel is spare at site, please check. [FACP-1] Smoke Detectors - 2nd stage FM-200 Alarm - Concourse Generator room
MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 SDI-1 AENTR2 0 1XSDI1 : 23,24 - SDI-16 11 AENTR2:0:I.11 DI I 4/14/2025 DONE

SIGNAL 3E4DS0-FCC-FDPS-FACP-100001_FACP1_ES_ACT_FB (FACP_ARR_UDT[1].HMI_INT[0].9) IS MAPPED TO THIS MER01WCO_AENTR2:0:I.12


13 3E4DS0-FCC-FDPS-FACP-100001 3E4DS0-FCC-FDPS-FACP-100001_FACP1_ES_ACT_FB CHANNEL MER01WCO_AENTR2:0:I.12IN LOGIX,ONLY,IN SITE THERE IS NO CABLE IS CONNECTED TO THIS TERMINAL. As per CWG RLM, this channel is spare at site, please check. [FACP-1] Activate station Evacution due to fire on incoming train MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 SDI-1 AENTR2 0 1XSDI1 : 25,26 - SDI-16 12 AENTR2:0:I.12 DI I 4/14/2025 DONE

As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR1:0:I.0
SIGNAL 3E4DS0-MER01-HVAC-AHU-110000_SF_TRIP (S_AHU_ARR_UDT[10].SF_TRIP) IS MAPPED TO THIS CHANNEL
33 3E4DS0-MER01-HVAC-AHU-110000 3E4DS0-MER01-HVAC-AHU-110000_SF_TRIP MER01WCO_AENTR1:0:I.0 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. TRIP STATUS SUPPLY FAN MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DI-1 AENTR1 0 1XDI1 : 1,2 - DI-16 0 AENTR1:0:I.0 DI I 4/14/2025 DONE

As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR1:0:I.1
SIGNAL 3E4DS0-MER01-HVAC-AHU-110000_SF_LOC (S_AHU_ARR_UDT[10].SF_LOC) IS MAPPED TO THIS CHANNEL
34 3E4DS0-MER01-HVAC-AHU-110000 3E4DS0-MER01-HVAC-AHU-110000_SF_LOC MER01WCO_AENTR1:0:I.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. HAND/OFF SWITCH SUPPLY FAN MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DI-1 AENTR1 0 1XDI1 : 3,4 - DI-16 1 AENTR1:0:I.1 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER01-HVAC-AHU-110000_SF_REM(S_AHU_ARR_UDT[10].SF_REM) IS MAPPED TO THIS SIGNAL
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR1:0:I.2
35 3E4DS0-MER01-HVAC-AHU-110000 3E4DS0-MER01-HVAC-AHU-110000_SF_REM MER01WCO_AENTR1:0:I.2 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. AUTO/OFF SWITCH SUPPLY FAN MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DI-1 AENTR1 0 1XDI1 : 5,6 - DI-16 2 AENTR1:0:I.2 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER01-HVAC-AHU-110000_SF_RUN_FB (S_AHU_ARR_UDT[10].SF_RUN_FB) IS MAPPED TO THIS
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR1:0:I.3
36 3E4DS0-MER01-HVAC-AHU-110000 3E4DS0-MER01-HVAC-AHU-110000_SF_RUN_FB CHANNEL MER01WCO_AENTR1:0:I.3..IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. AHU Power Supply On/Off Status MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DI-1 AENTR1 0 1XDI1 : 7,8 - DI-16 3 AENTR1:0:I.3 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER01-HVAC-AHU-110000_EC_TRIP (S_AHU_ARR_UDT[10].EC_TRIP) IS MAPPED TO THIS CHANNEL
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR1:0:I.4
37 3E4DS0-MER01-HVAC-AHU-110000 3E4DS0-MER01-HVAC-AHU-110000_EC_TRIP MER01WCO_AENTR1:0:I.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. ELECTRICAL COIL TRIP STATUS MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DI-1 AENTR1 0 1XDI1 : 9,10 - DI-16 4 AENTR1:0:I.4 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER01-HVAC-AHU-110000_EC_OH_PROT(S_AHU_ARR_UDT[10].EC_OH_PROT) IS MAPPED TO THIS
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR1:0:I.5
38 3E4DS0-MER01-HVAC-AHU-110000 3E4DS0-MER01-HVAC-AHU-110000_EC_OH_PROT CHANNEL MER01WCO_AENTR1:0:I.5 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. ELECTRICAL COIL OVERHEAT PROTECTION MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DI-1 AENTR1 0 1XDI1 : 11,12 - DI-16 5 AENTR1:0:I.5 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER01-HVAC-AHUSFDPS-110001_SF_DPS_FB(S_AHU_ARR_UDT[10].SF_DPS_FB) IS MAPPED TO THIS
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR1:0:I.7
40 3E4DS0-MER01-HVAC-AHUSFDPS-110001 3E4DS0-MER01-HVAC-AHUSFDPS-110001_SF_DPS_FB CHANNEL MER01WCO_AENTR1:0:I.7..IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. SUPPLY FAN PROOF OF FLOW MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DI-1 AENTR1 0 1XDI1 : 15,16 - DI-16 7 AENTR1:0:I.7 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER01-HVAC-AHU-110000_OPN_FB(S_AHU_ARR_UDT[10].OPN_FB) IS MAPPED TO THIS CHANNEL
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTORIZED
signal to
FIRE
beDAMPERS
confirmedNON FM200 MER01WCO_AENTR1:0:I.9
42 3E4DS0-MER01-HVAC-AHU-110000 3E4DS0-MER01-HVAC-AHU-110000_OPN_FB MER01WCO_AENTR1:0:I.9 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DI-1 AENTR1 0 1XDI1 : 19,20 - DI-16 9 AENTR1:0:I.9 DI I 4/14/2025 DONE

NON FM200 MFD LOOP MER01WCO_AENTR1:0:I.12


IN LOGIX ALSO,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE ALSO THERE IS NO CABLE CONNECTED TO THIS
CHANNEL.SIGNAL (3E4DS0-MER-HVAC-MAU-040000_OPN_FB) IS MAPPPED TO THIS CHANNEL
45 3E4DS0-MER-HVAC-MAU-040000 3E4DS0-MER-HVAC-MAU-040000_OPN_FB SPWPO_AENTR2:0:I.Data.19 IN LOGIC ,IN SITE ALSO ,CABLE IS CONNECTED TO THIS CHANNEL As per CWG RLM, this channel is spare at site, please check. MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DI-1 AENTR1 0 1XDI1 : 25,26 - DI-16 12 AENTR1:0:I.12 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER01-HVAC-AHU-110000_SS2_LOC_FB (S_AHU_ARR_UDT[10].SS2_LOC_FB) IS MAPPED TO THIS
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR1:0:I.13
46 3E4DS0-MER01-HVAC-AHU-110000 3E4DS0-MER01-HVAC-AHU-110000_SS2_LOC_FB CHANNEL MER01WCO_AENTR1:0:I.13 IN LOGIX.IN SITE ALSO,IT IS CONNECTED TO THE SAME SIGNAL. Manual/Local BMS Selector Switch (SS2) Status MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DI-1 AENTR1 0 1XDI1 : 27,28 - DI-16 13 AENTR1:0:I.13 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER01-HVAC-AHU-110000_SS2_REM_FB (S_AHU_ARR_UDT[10].SS2_REM_FB) IS MAPPED TO THIS
CHANNEL MER01WCO_AENTR1:0:I.14 ,IN LOGIX ONLY.IN SITE THERE IS NO SIGNAL PROVISION,SO THERE IS NO CABLE MER01WCO_AENTR1:0:I.14
47 3E4DS0-MER01-HVAC-AHU-110000 3E4DS0-MER01-HVAC-AHU-110000_SS2_REM_FB CONNECTED TO THAT TERMINAL. As per CWG RLM, this channel is spare at site, please check. Start Push Button RM relay activated/deactivated Status MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DI-1 AENTR1 0 1XDI1 : 29,30 - DI-16 14 AENTR1:0:I.14 DI I 4/14/2025 DONE

SIGNAL 3E4DS0-MER01-HVAC-AHU-110000_SF_SPD_CMD (S_AHU_ARR_UDT[10].SF_SPD_CMD) IS MAPPED TO THIS As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR1:3:chdata.2
83 3E4DS0-MER01-HVAC-AHU-110000 3E4DS0-MER01-HVAC-AHU-110000_SF_SPD_CMD CHANNEL MER01WCO_AENTR1:3:O.Ch2Data .IN SITE ALSO,THE CABLE IS CONNECTED TO THE SAME SIGNAL. SUPPLY FAN SPEED CONTROL MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 AO-1 AENTR1 3 1XAO1 : 5,6 - AO-12 2 AENTR1:3:O.Ch2Data AO chdata 4/14/2025 DONE
IN LOGIX ALSO,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE ALSO THERE IS NO CABLE CONNECTED TO THIS
CHANNEL.SIGNAL (3E4DS0-MER01-HVAC-AHU-110000_SF_ON_OFF_CMD) (S_AHU_ARR_UDT[10].SF_ON_OFF_CMD) IS
MER01WCO_AENTR1:3:chdata.4
MAPPED TO THIS RELAY MER01WCO_AENTR1:4:O.1 IN LOGIX.IN SITE ALSO,CABLE IS CONNECTED TO THIS RELAY
85 3E4DS0-MER01-HVAC-AHU-110000 3E4DS0-MER01-HVAC-AHU-110000_SF_ON_OFF_CMD MER01WCO_AENTR1:4:O.1 As per CWG RLM, this channel is spare at site, please check. Switch On AHU Power Supply MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 AO-1 AENTR1 3 1XAO1 : 9,10 - AO-12 4 AENTR1:3:O.Ch4Data AO chdata 4/14/2025 DONE
3E4DS0-MER01-HVAC-AHU-110000_EC_ON_CMD (S_AHU_ARR_UDT[10].EC_ON_CMD) IS MAPPED TO THIS RELAY
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER01WCO_AENTR1:4:O.0
93 3E4DS0-MER01-HVAC-AHU-110000 3E4DS0-MER01-HVAC-AHU-110000_EC_ON_CMD MER01WCO_AENTR1:4:O.0 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME RELAY. SWITCH ON ELECTRICAL COIL MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DO-1 AENTR1 4 - 1R1 : 11,14 DO-16 0 AENTR1:4:O.0 DO O 4/14/2025 DONE
SIGNAL (3E4DS0-MER01-HVAC-AHU-110000_SF_ON_OFF_CMD) (S_AHU_ARR_UDT[10].SF_ON_OFF_CMD) IS MAPPED
TO THIS RELAY MER01WCO_AENTR1:4:O.1 IN LOGIX.IN SITE ALSO,CABLE IS CONNECTED TO THIS RELAY MER01WCO_AENTR1:4:O.1
94 SPARE SPARE MER01WCO_AENTR1:4:O.1 As per CWG RLM, this channel is used at site, please check. SPARE MER01WCO 3E4DS0-MER01-BMS-RIOP-000002 DO-1 AENTR1 4 - 1R2 : 11,14 DO-16 1 AENTR1:4:O.1 DO O 4/14/2025 DONE
SIGNAL 3E4DS0-MER02-HVAC-AHU-010000_EC_ON_CMD (S_AHU_ARR_UDT[1].EC_ON_CMD) IS MAPPED TO THE RELAY
MER02WCO_AENTR1:0:O.2
3 3E4DS0-MER02-HVAC-AHU-010000 3E4DS0-MER02-HVAC-AHU-010000_EC_ON_CMD MER02WCO_AENTR1:0:O.2 .IN SITE ALSO CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
SWITCHsignal
ON ELECTRICAL
to be confirmed
COIL MER02WCO 3E4DS0-MER02-BMS-RIOP-000006 DO-1 AENTR1 0 - 1R3 : 11,14 DO-16 2 AENTR1:0:O.2 DO O 4/14/2025 DONE

SIGNAL 3E4DS0-MER02-HVAC-AHU-010000_SF_ON_OFF_CMD (S_AHU_ARR_UDT[1].SF_ON_OFF_CMD) IS MAPPED TO MER02WCO_AENTR1:0:O.5


6 3E4DS0-MER02-HVAC-AHU-010000 3E4DS0-MER02-HVAC-AHU-010000_SF_ON_OFF_CMD THIS RELAY MER02WCO_AENTR1:0:O.5..IN SITE ALSO CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Switch signal
On AHU to be
Power
confirmed
Supply MER02WCO 3E4DS0-MER02-BMS-RIOP-000006 DO-1 AENTR1 0 - 1R6 : 11,14 DO-16 5 AENTR1:0:O.5 DO O 4/14/2025 DONE
SIGNAL 3E4DS0-MER02-HVAC-AHU-010000_SF_TRIP (S_AHU_ARR_UDT[1].SF_TRIP) IS MAPPED TO THIS CHANNEL
MER02WCO_AENTR1:1:I.0
17 3E4DS0-MER02-HVAC-AHU-010000 3E4DS0-MER02-HVAC-AHU-010000_SF_TRIP MER02WCO_AENTR1:1:I.Data.0 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
SUPPLY
be confirmed
FAN MER02WCO 3E4DS0-MER02-BMS-RIOP-000006 DI-1 AENTR1 1 1XDI1 : 1,2 - DI-32 0 AENTR1:1:I.Data.0 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER02-HVAC-AHU-010000_SF_LOC (S_AHU_ARR_UDT[1].SF_LOC) IS MAPPED TO THIS CHANNEL
MER02WCO_AENTR1:1:I.1
18 3E4DS0-MER02-HVAC-AHU-010000 3E4DS0-MER02-HVAC-AHU-010000_SF_LOC MER02WCO_AENTR1:1:I.Data.1 ..IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalSWITCH
to be confirmed
SUPPLY FAN MER02WCO 3E4DS0-MER02-BMS-RIOP-000006 DI-1 AENTR1 1 1XDI1 : 3,4 - DI-32 1 AENTR1:1:I.Data.1 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER02-HVAC-AHU-010000_SF_REM (S_AHU_ARR_UDT[1].SF_REM) IS MAPPED TO THIS CHANNEL
MER02WCO_AENTR1:1:I.2
19 3E4DS0-MER02-HVAC-AHU-010000 3E4DS0-MER02-HVAC-AHU-010000_SF_REM MER02WCO_AENTR1:1:I.Data.2 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME CHANNEL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalSWITCH
to be confirmed
SUPPLY FAN MER02WCO 3E4DS0-MER02-BMS-RIOP-000006 DI-1 AENTR1 1 1XDI1 : 5,6 - DI-32 2 AENTR1:1:I.Data.2 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER02-HVAC-AHU-010000_SF_RUN_FB (S_AHU_ARR_UDT[1].SF_RUN_FB) IS MAPPED TO THIS
MER02WCO_AENTR1:1:I.3
20 3E4DS0-MER02-HVAC-AHU-010000 3E4DS0-MER02-HVAC-AHU-010000_SF_RUN_FB CHANNEL MER02WCO_AENTR1:1:I.Data.3 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AHU Power
signalSupply
to be confirmed
On/Off Status MER02WCO 3E4DS0-MER02-BMS-RIOP-000006 DI-1 AENTR1 1 1XDI1 : 7,8 - DI-32 3 AENTR1:1:I.Data.3 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER02-HVAC-AHU-010000_EC_TRIP (S_AHU_ARR_UDT[1].EC_TRIP) IS MAPPED TO THIS CHANNEL
MER02WCO_AENTR1:1:I.4
21 3E4DS0-MER02-HVAC-AHU-010000 3E4DS0-MER02-HVAC-AHU-010000_EC_TRIP MER02WCO_AENTR1:1:I.Data.4 .IN SITE ALSO,THE CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
ELECTRICAL
signalCOIL
to beTRIP
confirmed
STATUS MER02WCO 3E4DS0-MER02-BMS-RIOP-000006 DI-1 AENTR1 1 1XDI1 : 9,10 - DI-32 4 AENTR1:1:I.Data.4 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER02-HVAC-AHU-010000_EC_OH_PROT (S_AHU_ARR_UDT[1].EC_OH_PROT) IS CONNECTED TO THIS
MER02WCO_AENTR1:1:I.5
22 3E4DS0-MER02-HVAC-AHU-010000 3E4DS0-MER02-HVAC-AHU-010000_EC_OH_PROT CHANNEL MER02WCO_AENTR1:1:I.Data.5.IN SITE ALSO ,CABLE IS CONNECTED TO THE SAME SIGNAL As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
ELECTRICAL
signalCOIL
to beOVERHEAT
confirmed PROTECTION MER02WCO 3E4DS0-MER02-BMS-RIOP-000006 DI-1 AENTR1 1 1XDI1 : 11,12 - DI-32 5 AENTR1:1:I.Data.5 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER02-HVAC-AHU-010000_EC_ON (S_AHU_ARR_UDT[1].EC_ON) IS MAPPED TO THIS CHANNEL
MER02WCO_AENTR1:1:I.6
23 3E4DS0-MER02-HVAC-AHU-010000 3E4DS0-MER02-HVAC-AHU-010000_EC_ON MER02WCO_AENTR1:1:I.Data.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
ON ELECTRICAL
signal to be
COIL
confirmed MER02WCO 3E4DS0-MER02-BMS-RIOP-000006 DI-1 AENTR1 1 1XDI1 : 13,14 - DI-32 6 AENTR1:1:I.Data.6 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER02-HVAC-AHU-010000_AIP1_ON (S_AHU_ARR_UDT[1].AIP1_ON) IS MAPPED TO THIS CHANNEL
MER02WCO_AENTR1:1:I.7
24 3E4DS0-MER02-HVAC-AHU-010000 3E4DS0-MER02-HVAC-AHU-010000_AIP1_ON MER02WCO_AENTR1:1:I.Data.7 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
ON AIRsignal
IONIZER
to be
PURIFIER
confirmed
NO. 1 MER02WCO 3E4DS0-MER02-BMS-RIOP-000006 DI-1 AENTR1 1 1XDI1 : 15,16 - DI-32 7 AENTR1:1:I.Data.7 DI I 4/14/2025 DONE
SIGNAL 3E4DS0-MER02-HVAC-AHUFDPS-010001_AIR_FIL1_FB (S_AHU_ARR_UDT[1].AIR_FIL1_FB) IS MAPPED TO THIS
MER02WCO_AENTR1:1:I.Data.9
26 3E4DS0-MER02-HVAC-AHUFDPS-010001 3E4DS0-MER02-HVAC-AHUFDPS-010001_AIR_FIL1_FB CHANNEL MER02WCO_AENTR1:1:I.Data.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AIR FILTER
signal to be confirmed MER02WCO 3E4DS0-MER02-BMS-RIOP-000006 DI-1 AENTR1 1 1XDI1 : 19,20 - DI-32 9 AENTR1:1:I.Data.9 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-MER02-HVAC-AHU-010000_OPN_FB (S_AHU_ARR_UDT[1].OPN_FB) IS MAPPED TO THIS CHANNEL
MOTORIZED FIRE DAMPERS NON FM200 MER02WCO_AENTR1:1:I.Data.10
27 3E4DS0-MER02-HVAC-AHU-010000 3E4DS0-MER02-HVAC-AHU-010000_OPN_FB MER02WCO_AENTR1:1:I.Data.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER02WCO 3E4DS0-MER02-BMS-RIOP-000006 DI-1 AENTR1 1 1XDI1 : 21,22 - DI-32 10 AENTR1:1:I.Data.10 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-ELE-ELS-ELP-001404_TRIP_CKT04_FB (ELP_ARR_UDT[8].TRIP_CKT04_FB) IS MAPPED TO THIS CHANNEL
MER02WCO_AENTR1:1:I.Data.23
40 3E4DS0-ELE-ELS-ELP-001404 3E4DS0-ELE-ELS-ELP-001404_TRIP_CKT04_FB MER02WCO_AENTR1:1:I.Data.23.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
ELP TRIP
signal
STATUS
to beCIRCUIT
confirmed
- 05 MER02WCO 3E4DS0-MER02-BMS-RIOP-000006 DI-1 AENTR1 1 1XDI1 : 47,48 - DI-32 23 AENTR1:1:I.Data.23 DI I.Data 4/15/2025 DONE

SIGNAL 3E4DS0-ELE-ELS-ELP-001404_TRIP_CKT05_FB (ELP_ARR_UDT[8].TRIP_CKT05_FB) IS MAPPED TO THIS CHANNEL MER02WCO_AENTR1:1:I.Data.25


42 3E4DS0-ELE-ELS-ELP-001404 3E4DS0-ELE-ELS-ELP-001404_TRIP_CKT05_FB MER02WCO_AENTR1:1:I.Data.25 ,IN LOGIX ONLY.IN SITE ,THERE IS NO CABLE CONNECTED TO THIS SIGNAL. As per CWG RLM, this channel is spare at site, please check. TRIP STATUS EVACUATION LIGHTING OF EMERGENCY STAIRCASE 03,04,05 MER02WCO 3E4DS0-MER02-BMS-RIOP-000006 DI-1 AENTR1 1 1XDI1 : 51,52 - DI-32 25 AENTR1:1:I.Data.25 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-MER02-HVAC-AHU-010000_SS2_LOC_FB (S_AHU_ARR_UDT[1].SS2_LOC_FB) IS MAPPED TO THIS
MER02WCO_AENTR1:1:I.Data.28
45 3E4DS0-MER02-HVAC-AHU-010000 3E4DS0-MER02-HVAC-AHU-010000_SS2_LOC_FB CHANNEL MER02WCO_AENTR1:1:I.Data.28.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Manual/Local
signal toBMS
be confirmed
Selector Switch (SS2) Status MER02WCO 3E4DS0-MER02-BMS-RIOP-000006 DI-1 AENTR1 1 1XDI1 : 57,58 - DI-32 28 AENTR1:1:I.Data.28 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-MER02-HVAC-AHU-010000_SS2_REM_FB (S_AHU_ARR_UDT[1].SS2_REM_FB) IS MAPPED TO THIS
MER02WCO_AENTR1:1:I.Data.29
46 3E4DS0-MER02-HVAC-AHU-010000 3E4DS0-MER02-HVAC-AHU-010000_SS2_REM_FB CHANNEL MER02WCO_AENTR1:1:I.Data.29.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Start Push
signal
Button
to beRM
confirmed
relay activated/deactivated Status MER02WCO 3E4DS0-MER02-BMS-RIOP-000006 DI-1 AENTR1 1 1XDI1 : 59,60 - DI-32 29 AENTR1:1:I.Data.29 DI I.Data 4/15/2025 DONE
THERE IS NO MAPPING IN LOGIX.IN SITE ,IT IS EXTRA CABLE CONNECTED TO THIS CHANNEL.WHICH NEED TO BE
MER02WCO_AENTR1:1:I.Data.30
47 SPARE SPARE REMOVED FROM SITE. As per CWG RLM, this channel is used at site, please check. SPARE MER02WCO 3E4DS0-MER02-BMS-RIOP-000006 DI-1 AENTR1 1 1XDI1 : 61,62 - DI-32 30 AENTR1:1:I.Data.30 DI I.Data 4/15/2025 DONE

SIGNAL 3E4DS0-MER02-HVAC-AHUFAD-010001_FA_DAMP_POS (S_AHU_ARR_UDT[1].FA_DAMP_POS) IS MAPPED TO MER02WCO_AENTR1:2:chdata.0


65 3E4DS0-MER02-HVAC-AHUFAD-010001 3E4DS0-MER02-HVAC-AHUFAD-010001_FA_DAMP_POS THIS CHANNEL MER02WCO_AENTR1:2:I.Ch0Data .IN SITE ALSO,CABLE IS CONNECTED TO THIS TERMINAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FRESH signal
AIR DAMPER
to be confirmed
POSITION MER02WCO 3E4DS0-MER02-BMS-RIOP-000006 AI-1 AENTR1 2 1XAI1 : 1,2 - AI-08 0 AENTR1:2:I.Ch0Data AI chdata 4/15/2025 DONE
SIGNAL 3E4DS0-MER02-HVAC-AHUSAT-010001_SA_TEMP (S_AHU_ARR_UDT[1].SA_TEMP) IS MAPPED TO THIS CHANNEL
MER02WCO_AENTR1:2:chdata.5
70 3E4DS0-MER02-HVAC-AHUSAT-010001 3E4DS0-MER02-HVAC-AHUSAT-010001_SA_TEMP MER02WCO_AENTR1:2:I.Ch5Data .IN SITE ALSO,CABLE IS CONNECTED TO THIS SAME TERMINAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
SUPPLYsignal
AIR TEMPERATURE
to be confirmed MER02WCO 3E4DS0-MER02-BMS-RIOP-000006 AI-1 AENTR1 2 1XAI1 : 11,12 - AI-08 5 AENTR1:2:I.Ch5Data AI chdata 4/15/2025 DONE
SIGNAL 3E4DS0-MER02-HVAC-AHU-010000_SF_SPD (S_AHU_ARR_UDT[1].SF_SPD) IS MAPPED TO THIS CHANNEL
MER02WCO_AENTR1:2:chdata.6
71 3E4DS0-MER02-HVAC-AHU-010000 3E4DS0-MER02-HVAC-AHU-010000_SF_SPD MER02WCO_AENTR1:2:I.Ch6Data .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
SUPPLYsignal
FAN SPEED
to be confirmed
CONTROL FEEDBACK MER02WCO 3E4DS0-MER02-BMS-RIOP-000006 AI-1 AENTR1 2 1XAI1 : 13,14 - AI-08 6 AENTR1:2:I.Ch6Data AI chdata 4/15/2025 DONE
THERE IS NO MAPPING IN LOGIX.IN SITE ,IT IS EXTRA CABLE CONNECTED TO THIS CHANNEL.WHICH NEED TO BE
MER02WCO_AENTR1:4:O.5
86 SPARE SPARE REMOVED FROM SITE. As per CWG RLM, this channel is used at site, please check. SPARE MER02WCO 3E4DS0-MER02-BMS-RIOP-000006 AO-1 AENTR1 4 1XAO1 : 11,12 - AO-12 5 AENTR1:4:O.Ch5Data AO O 4/15/2025 DONE

# General
PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM

DOCUMENT TITLE SHOP DRAWING-DEEP UNDERGROUND STATION-3E4-BMS-INPUT/OUTPUT SCHEDULE

DOCUMENT NO. M-ANM-3E4DS0-CJ00-SCH-000002

MODULE RELAY MODULE CHANNE


SR. NO. EQUIPMENT TAG PLC TAG EASA SITE Response RLM COMMENTS FROM CWG DESCRIPTION PANEL SHORT TAG (OLD) PANEL FULL TAG (NEW) RACK NO. SLOT NO. TERMINAL NO. PLC IO ADDRESS MODULE ID DATE STATUS
ID NO. TYPE L NO.
SIGNAL 3E4DS0-MER03-HVAC-AHU-020000_SF_TRIP (S_AHU_ARR_UDT[2].SF_TRIP) IS MAPPED TO THIS CHANNEL
MER03WCO_AENTR1:0:I.Data.0
1 3E4DS0-MER03-HVAC-AHU-020000 3E4DS0-MER03-HVAC-AHU-020000_SF_TRIP MER03WCO_AENTR1:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
SUPPLY
be confirmed
FAN MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-1 AENTR1 0 1XDI1 : 1,2 - DI-16 0 AENTR1:0:I.0 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-MER03-HVAC-AHU-020000_SF_LOC (S_AHU_ARR_UDT[2].SF_LOC) IS MAPPED TO THIS CHANNEL
MER03WCO_AENTR1:0:I.Data.1
2 3E4DS0-MER03-HVAC-AHU-020000 3E4DS0-MER03-HVAC-AHU-020000_SF_LOC MER03WCO_AENTR1:0:I.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalSWITCH
to be confirmed
SUPPLY FAN MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-1 AENTR1 0 1XDI1 : 3,4 - DI-16 1 AENTR1:0:I.1 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-MER03-HVAC-AHU-020000_SF_REM (S_AHU_ARR_UDT[2].SF_REM) IS MAPPED TO THIS CHANNEL
MER03WCO_AENTR1:0:I.Data.2
3 3E4DS0-MER03-HVAC-AHU-020000 3E4DS0-MER03-HVAC-AHU-020000_SF_REM MER03WCO_AENTR1:0:I.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalSWITCH
to be confirmed
SUPPLY FAN MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-1 AENTR1 0 1XDI1 : 5,6 - DI-16 2 AENTR1:0:I.2 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-MER03-HVAC-AHU-020000_SF_RUN_FB (S_AHU_ARR_UDT[2].SF_RUN_FB) IS MAPPED TO THIS
MER03WCO_AENTR1:0:I.Data.3
4 3E4DS0-MER03-HVAC-AHU-020000 3E4DS0-MER03-HVAC-AHU-020000_SF_RUN_FB CHANNEL MER03WCO_AENTR1:0:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AHU Power
signalSupply
to be confirmed
On/Off Status MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-1 AENTR1 0 1XDI1 : 7,8 - DI-16 3 AENTR1:0:I.3 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-MER03-HVAC-AHU-020000_EC_TRIP (S_AHU_ARR_UDT[2].EC_TRIP) IS MAPPED TO THIS CHANNEL
MER03WCO_AENTR1:0:I.Data.4
5 3E4DS0-MER03-HVAC-AHU-020000 3E4DS0-MER03-HVAC-AHU-020000_EC_TRIP MER03WCO_AENTR1:0:I.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
ELECTRICAL
signalCOIL
to beTRIP
confirmed
STATUS MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-1 AENTR1 0 1XDI1 : 9,10 - DI-16 4 AENTR1:0:I.4 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-MER03-HVAC-AHU-020000_EC_OH_PROT (S_AHU_ARR_UDT[2].EC_OH_PROT) IS MAPPED TO THIS
MER03WCO_AENTR1:0:I.Data.5
6 3E4DS0-MER03-HVAC-AHU-020000 3E4DS0-MER03-HVAC-AHU-020000_EC_OH_PROT CHANNEL MER03WCO_AENTR1:0:I.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
ELECTRICAL
signalCOIL
to beOVERHEAT
confirmed PROTECTION MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-1 AENTR1 0 1XDI1 : 11,12 - DI-16 5 AENTR1:0:I.5 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-MER03-HVAC-AHU-020000_EC_ON (S_AHU_ARR_UDT[2].EC_ON) IS MAPPED TO THIS CHANNEL
MER03WCO_AENTR1:0:I.Data.6
7 3E4DS0-MER03-HVAC-AHU-020000 3E4DS0-MER03-HVAC-AHU-020000_EC_ON MER03WCO_AENTR1:0:I.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
ON ELECTRICAL
signal to be
COIL
confirmed MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-1 AENTR1 0 1XDI1 : 13,14 - DI-16 6 AENTR1:0:I.6 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-STT-HVAC-FAN-050000_TRIP_FB (FAN_ARR_UDT[4].TRIP_FB) IS MAPPED TO THIS CHANNEL
MER03WCO_AENTR1:0:I.Data.10
11 3E4DS0-STT-HVAC-FAN-050000 3E4DS0-STT-HVAC-FAN-050000_TRIP_FB MER03WCO_AENTR1:0:I.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
EXHAUST
be confirmed
FAN MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-1 AENTR1 0 1XDI1 : 21,22 - DI-16 10 AENTR1:0:I.10 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-STT-HVAC-FAN-050000_LOC_FB (FAN_ARR_UDT[4].LOC_FB) IS MAPPED TO THIS CHANNEL
MER03WCO_AENTR1:0:I.Data.11
12 3E4DS0-STT-HVAC-FAN-050000 3E4DS0-STT-HVAC-FAN-050000_LOC_FB MER03WCO_AENTR1:0:I.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalSWITCH
to be confirmed
EXHAUST FAN MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-1 AENTR1 0 1XDI1 : 23,24 - DI-16 11 AENTR1:0:I.11 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-STT-HVAC-FAN-050000_REM_FB (FAN_ARR_UDT[4].REM_FB) IS MAPPED TO THIS CHANNEL
MER03WCO_AENTR1:0:I.Data.12
13 3E4DS0-STT-HVAC-FAN-050000 3E4DS0-STT-HVAC-FAN-050000_REM_FB MER03WCO_AENTR1:0:I.12.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalSWITCH
to be confirmed
EXHAUST FAN MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-1 AENTR1 0 1XDI1 : 25,26 - DI-16 12 AENTR1:0:I.12 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-STT-HVAC-FAN-050000_RUN_FB (FAN_ARR_UDT[4].RUN_FB) IS MAPPED TO THIS CHANNEL
MER03WCO_AENTR1:0:I.Data.13
14 3E4DS0-STT-HVAC-FAN-050000 3E4DS0-STT-HVAC-FAN-050000_RUN_FB MER03WCO_AENTR1:0:I.13.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
RUNNING
signal
OFtoEXHAUST
be confirmed
FAN MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-1 AENTR1 0 1XDI1 : 27,28 - DI-16 13 AENTR1:0:I.13 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-MER03-HVAC-HRU-010000_SF_TRIP (HRU_ARR_UDT[1].SF_TRIP) IS MAPPED TO THIS CHANNEL
MER03WCO_AENTR1:0:I.Data.15
16 3E4DS0-MER03-HVAC-HRU-010000 3E4DS0-MER03-HVAC-HRU-010000_SF_TRIP MER03WCO_AENTR1:0:I.15.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
SUPPLY
be confirmed
FAN MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-1 AENTR1 0 1XDI1 : 31,32 - DI-16 15 AENTR1:0:I.15 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-MER03-HVAC-MAU-010000_SF_TRIP (S_MAU_ARR_UDT[1].SF_TRIP) IS MAPPED TO THIS CHANNEL
MER03WCO_AENTR1:1:I.Data.0
17 3E4DS0-MER03-HVAC-MAU-010000 3E4DS0-MER03-HVAC-MAU-010000_SF_TRIP MER03WCO_AENTR1:1:I.Data.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
SUPPLY
be confirmed
FAN MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-2 AENTR1 1 1XDI2 : 1,2 - DI-32 0 AENTR1:1:I.Data.0 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-MER03-HVAC-MAU-010000_SF_LOC (S_MAU_ARR_UDT[1].SF_LOC) IS MAPPED TO THIS CHANNEL
MER03WCO_AENTR1:1:I.Data.1
18 3E4DS0-MER03-HVAC-MAU-010000 3E4DS0-MER03-HVAC-MAU-010000_SF_LOC MER03WCO_AENTR1:1:I.Data.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalSWITCH
to be confirmed
SUPPLY FAN MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-2 AENTR1 1 1XDI2 : 3,4 - DI-32 1 AENTR1:1:I.Data.1 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-MER03-HVAC-MAU-010000_SF_REM (S_MAU_ARR_UDT[1].SF_REM) IS MAPPED TO THIS CHANNEL
MER03WCO_AENTR1:1:I.Data.2
19 3E4DS0-MER03-HVAC-MAU-010000 3E4DS0-MER03-HVAC-MAU-010000_SF_REM MER03WCO_AENTR1:1:I.Data.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalSWITCH
to be confirmed
SUPPLY FAN MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-2 AENTR1 1 1XDI2 : 5,6 - DI-32 2 AENTR1:1:I.Data.2 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-MER03-HVAC-MAU-010000_SF_RUN_FB (S_MAU_ARR_UDT[1].SF_RUN_FB) IS MAPPED TO THIS
MER03WCO_AENTR1:1:I.Data.3
20 3E4DS0-MER03-HVAC-MAU-010000 3E4DS0-MER03-HVAC-MAU-010000_SF_RUN_FB CHANNEL MER03WCO_AENTR1:1:I.Data.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MAU Power
signal Supply
to be confirmed
On/Off Status MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-2 AENTR1 1 1XDI2 : 7,8 - DI-32 3 AENTR1:1:I.Data.3 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-MER03-HVAC-MAU-010000_OPN_FB (S_MAU_ARR_UDT[1].OPN_FB) IS MAPPED TO THIS CHANNEL
NON FM200 MFD LOOP MER03WCO_AENTR1:1:I.Data.6
23 3E4DS0-MER03-HVAC-MAU-010000 3E4DS0-MER03-HVAC-MAU-010000_OPN_FB MER03WCO_AENTR1:1:I.Data.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-2 AENTR1 1 1XDI2 : 13,14 - DI-32 6 AENTR1:1:I.Data.6 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-TRR-HVAC-FAN-060000_TRIP_FB (FAN_ARR_UDT[5].TRIP_FB) IS MAPPED TO THIS CHANNEL
MER03WCO_AENTR1:1:I.Data.7
24 3E4DS0-TRR-HVAC-FAN-060000 3E4DS0-TRR-HVAC-FAN-060000_TRIP_FB MER03WCO_AENTR1:1:I.Data.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
EXHAUST
be confirmed
FAN MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-2 AENTR1 1 1XDI2 : 15,16 - DI-32 7 AENTR1:1:I.Data.7 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-TRR-HVAC-FAN-060000_LOC_FB (FAN_ARR_UDT[5].LOC_FB) IS MAPPED TO THIS CHANNEL
MER03WCO_AENTR1:1:I.Data.8
25 3E4DS0-TRR-HVAC-FAN-060000 3E4DS0-TRR-HVAC-FAN-060000_LOC_FB MER03WCO_AENTR1:1:I.Data.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalSWITCH
to be confirmed
EXHAUST FAN MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-2 AENTR1 1 1XDI2 : 17,18 - DI-32 8 AENTR1:1:I.Data.8 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-TRR-HVAC-FAN-060000_REM_FB (FAN_ARR_UDT[5].REM_FB) IS MAPPED TO THIS CHANNEL
MER03WCO_AENTR1:1:I.Data.9
26 3E4DS0-TRR-HVAC-FAN-060000 3E4DS0-TRR-HVAC-FAN-060000_REM_FB MER03WCO_AENTR1:1:I.Data.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalSWITCH
to be confirmed
EXHAUST FAN MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-2 AENTR1 1 1XDI2 : 19,20 - DI-32 9 AENTR1:1:I.Data.9 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-TRR-HVAC-FAN-060000_RUN_FB (FAN_ARR_UDT[5].RUN_FB) IS MAPPED TO THIS CHANNEL
MER03WCO_AENTR1:1:I.Data.10
27 3E4DS0-TRR-HVAC-FAN-060000 3E4DS0-TRR-HVAC-FAN-060000_RUN_FB MER03WCO_AENTR1:1:I.Data.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
RUNNING
signal
OFtoEXHAUST
be confirmed
FAN MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-2 AENTR1 1 1XDI2 : 21,22 - DI-32 10 AENTR1:1:I.Data.10 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-MER03-HVAC-HRU-010000_SF_LOC (HRU_ARR_UDT[1].SF_LOC) IS MAPPED TO THIS CHANNEL
MER03WCO_AENTR1:1:I.Data.12
29 3E4DS0-MER03-HVAC-HRU-010000 3E4DS0-MER03-HVAC-HRU-010000_SF_LOC MER03WCO_AENTR1:1:I.Data.12.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HRU INsignal
MANUALto beMODE
confirmed MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-2 AENTR1 1 1XDI2 : 25,26 - DI-32 12 AENTR1:1:I.Data.12 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-MER03-HVAC-HRU-010000_SF_REM (HRU_ARR_UDT[1].SF_REM) IS MAPPED TO THIS CHANNEL
MER03WCO_AENTR1:1:I.Data.13
30 3E4DS0-MER03-HVAC-HRU-010000 3E4DS0-MER03-HVAC-HRU-010000_SF_REM MER03WCO_AENTR1:1:I.Data.13.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HRU INsignal
AUTOtoMODE
be confirmed MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-2 AENTR1 1 1XDI2 : 27,28 - DI-32 13 AENTR1:1:I.Data.13 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-MER03-HVAC-HRU-010000_OPN_FB (HRU_ARR_UDT[1].OPN_FB) IS MAPPED TO THIS CHANNEL
MER03WCO_AENTR1:1:I.Data.14
31 3E4DS0-MER03-HVAC-HRU-010000 3E4DS0-MER03-HVAC-HRU-010000_OPN_FB MER03WCO_AENTR1:1:I.Data.14.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTORIZED
signal to
FIRE
beDAMPERS
confirmedNON FM200 OPEN MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-2 AENTR1 1 1XDI2 : 29,30 - DI-32 14 AENTR1:1:I.Data.14 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-MER03-HVAC-AHU-020000_OPN_FB (S_AHU_ARR_UDT[2].OPN_FB) IS MAPPED TO THIS CHANNEL
MOTORIZED FIRE DAMPERS NON FM200 MER03WCO_AENTR1:1:I.Data.17
34 3E4DS0-MER03-HVAC-AHU-020000 3E4DS0-MER03-HVAC-AHU-020000_OPN_FB MER03WCO_AENTR1:1:I.Data.17.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-2 AENTR1 1 1XDI2 : 35,36 - DI-32 17 AENTR1:1:I.Data.17 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-MER03-HVAC-AHU-020000_SS2_LOC_FB (S_AHU_ARR_UDT[2].SS2_LOC_FB) IS MAPPED TO THIS
MER03WCO_AENTR1:1:I.Data.18
35 3E4DS0-MER03-HVAC-AHU-020000 3E4DS0-MER03-HVAC-AHU-020000_SS2_LOC_FB CHANNEL MER03WCO_AENTR1:1:I.Data.18.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Manual/Local
signal toBMS
be confirmed
Selector Switch (SS2) Status MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-2 AENTR1 1 1XDI2 : 37,38 - DI-32 18 AENTR1:1:I.Data.18 DI I.Data 4/15/2025 DONE

SIGNAL 3E4DS0-MER03-HVAC-AHU-020000_SS2_REM_FB (S_AHU_ARR_UDT[2].SS2_REM_FB) IS MAPPED TO THIS MER03WCO_AENTR1:1:I.Data.19


36 3E4DS0-MER03-HVAC-AHU-020000 3E4DS0-MER03-HVAC-AHU-020000_SS2_REM_FB CHANNEL MER03WCO_AENTR1:1:I.Data.19 in logix,only.IN SITE ALSO,CABLE IS NOT CONNECTED TO THIS TERMINAL As per CWG RLM, this channel is spare at site, please check. Start Push Button RM relay activated/deactivated Status MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-2 AENTR1 1 1XDI2 : 39,40 - DI-32 19 AENTR1:1:I.Data.19 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-MER03-HVAC-MAU-010000_SS2_LOC_FB (S_MAU_ARR_UDT[1].SS2_LOC_FB) IS MAPPED TO THIS
MER03WCO_AENTR1:1:I.Data.20
37 3E4DS0-MER03-HVAC-MAU-010000 3E4DS0-MER03-HVAC-MAU-010000_SS2_LOC_FB CHANNEL MER03WCO_AENTR1:1:I.Data.20.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Manual/Local
signal toBMS
be confirmed
Selector Switch (SS2) Status MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-2 AENTR1 1 1XDI2 : 41,42 - DI-32 20 AENTR1:1:I.Data.20 DI I.Data 4/15/2025 DONE

SIGNAL 3E4DS0-MER03-HVAC-MAU-010000_SS2_REM_FB (S_MAU_ARR_UDT[1].SS2_REM_FB) IS MAPPED TO THIS MER03WCO_AENTR1:1:I.Data.21


38 3E4DS0-MER03-HVAC-MAU-010000 3E4DS0-MER03-HVAC-MAU-010000_SS2_REM_FB CHANNEL MER03WCO_AENTR1:1:I.Data.21 in logix,only.IN SITE ALSO,CABLE IS NOT CONNECTED TO THIS TERMINAL As per CWG RLM, this channel is spare at site, please check. Start Push Button RM relay activated/deactivated Status MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DI-2 AENTR1 1 1XDI2 : 43,44 - DI-32 21 AENTR1:1:I.Data.21 DI I.Data 4/15/2025 DONE
SIGNAL 3E4DS0-MER03-HVAC-AHU-020000_EC_ON_CMD (S_AHU_ARR_UDT[2].EC_ON_CMD) IS MAPPED TO THIS RELAY
MER03WCO_AENTR1:2:O.0
49 3E4DS0-MER03-HVAC-AHU-020000 3E4DS0-MER03-HVAC-AHU-020000_EC_ON_CMD MER03WCO_AENTR1:2:O.0 IN LOGIX.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
SWITCHsignal
ON ELECTRICAL
to be confirmed
COIL MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DO-1 AENTR1 2 - 1R1 : 11,14 DO-16 0 AENTR1:2:O.0 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-STT-HVAC-FAN-050000_ON_OFF_CMD (FAN_ARR_UDT[4].ON_OFF_CMD) IS MAPPED TO THIS RELAY
MER03WCO_AENTR1:2:O.3
52 3E4DS0-STT-HVAC-FAN-050000 3E4DS0-STT-HVAC-FAN-050000_ON_OFF_CMD MER03WCO_AENTR1:2:O.3 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
EXHAUST
be confirmed
FAN MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DO-1 AENTR1 2 - 1R4 : 11,14 DO-16 3 AENTR1:2:O.3 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-TRR-HVAC-FAN-060000_ON_OFF_CMD (FAN_ARR_UDT[5].ON_OFF_CMD) IS MAPPED TO THIS RELAY
MER03WCO_AENTR1:2:O.4
53 3E4DS0-TRR-HVAC-FAN-060000 3E4DS0-TRR-HVAC-FAN-060000_ON_OFF_CMD MER03WCO_AENTR1:2:O.4 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
EXHAUST
be confirmed
FAN MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DO-1 AENTR1 2 - 1R5 : 11,14 DO-16 4 AENTR1:2:O.4 DO O 4/15/2025 DONE

SIGNAL 3E4DS0-MER03-HVAC-AHU-020000_SF_ON_OFF_CMD (S_AHU_ARR_UDT[2].SF_ON_OFF_CMD) IS MAPPED TO MER03WCO_AENTR1:2:O.5


54 3E4DS0-MER03-HVAC-AHU-020000 3E4DS0-MER03-HVAC-AHU-020000_SF_ON_OFF_CMD THIS RELAY MER03WCO_AENTR1:2:O.5 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Switch signal
On AHU to be
Power
confirmed
Supply MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DO-1 AENTR1 2 - 1R6 : 11,14 DO-16 5 AENTR1:2:O.5 DO O 4/15/2025 DONE

SIGNAL 3E4DS0-MER03-HVAC-MAU-010000_SF_ON_OFF_CMD (S_MAU_ARR_UDT[1].SF_ON_OFF_CMD) IS MAPPED TO MER03WCO_AENTR1:2:O.6


55 3E4DS0-MER03-HVAC-MAU-010000 3E4DS0-MER03-HVAC-MAU-010000_SF_ON_OFF_CMD THIS RELAY MER03WCO_AENTR1:2:O.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Switch signal
On MAU to be
Power
confirmed
Supply MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 DO-1 AENTR1 2 - 1R7 : 11,14 DO-16 6 AENTR1:2:O.6 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-MER03-HVAC-AHU-020000_SF_SPD_CMD (S_AHU_ARR_UDT[2].SF_SPD_CMD) IS MAPPED TO THIS
MER03WCO_AENTR1:5:O.3
84 3E4DS0-MER03-HVAC-AHU-020000 3E4DS0-MER03-HVAC-AHU-020000_SF_SPD_CMD CHANNEL MER03WCO_AENTR1:5:O.Ch3Data .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
SUPPLYsignal
FAN SPEED
to be confirmed
CONTROL MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 AO-1 AENTR1 5 1XAO1 : 7,8 - AO-12 3 AENTR1:5:O.Ch3Data AO O 4/15/2025 DONE

SIGNAL 3E4DS0-MER03-HVAC-MAU-010000_SF_SPD_CMD (S_MAU_ARR_UDT[1].SF_POS_CMD) IS MAPPED TO THIS MER03WCO_AENTR1:5:O.5


86 3E4DS0-MER03-HVAC-MAU-010000 3E4DS0-MER03-HVAC-MAU-010000_SF_SPD_CMD CHANNEL MER03WCO_AENTR1:5:O.Ch5Data .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
SUPPLYsignal
FAN SPEED
to be confirmed
CONTROL MER03WCO 3E4DS0-MER03-BMS-RIOP-000003 AO-1 AENTR1 5 1XAO1 : 11,12 - AO-12 5 AENTR1:5:O.Ch5Data AO O 4/15/2025 DONE
SIGNAL 3E4DS0-CA-EVS-MFD-231218_OPN_FB (EVS_FD_ARR_UDT[7].OPN_FB) IS MAPPED TO THIS CHANNEL
MER04WCO_AENTR2:0:I.3
4 3E4DS0-CA-EVS-MFD-231218 3E4DS0-CA-EVS-MFD-231218_OPN_FB MER04WCO_AENTR2:0:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-1 AENTR2 0 1XSDI1 : 7,8 - SDI-16 3 AENTR2:0:I.3 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-CA-EVS-MFD-731214_OPN_FB (EVS_FD_ARR_UDT[19].OPN_FB) IS MAPPED TO THIS CHANNEL
MER04WCO_AENTR2:0:I.4
5 3E4DS0-CA-EVS-MFD-731214 3E4DS0-CA-EVS-MFD-731214_OPN_FB MER04WCO_AENTR2:0:I.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-1 AENTR2 0 1XSDI1 : 9,10 - SDI-16 4 AENTR2:0:I.4 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-CA-EVS-MFD-731215_OPN_FB (EVS_FD_ARR_UDT[20].OPN_FB) IS MAPPED TO THIS CHANNEL
MER04WCO_AENTR2:0:I.5
6 3E4DS0-CA-EVS-MFD-731215 3E4DS0-CA-EVS-MFD-731215_OPN_FB MER04WCO_AENTR2:0:I.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-1 AENTR2 0 1XSDI1 : 11,12 - SDI-16 5 AENTR2:0:I.5 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-EST01-EVS-MFD-561206_OPN_FB (EVS_FD_ARR_UDT[11].OPN_FB) IS MAPPED TO THIS CHANNEL
MER04WCO_AENTR2:0:I.6
7 3E4DS0-EST01-EVS-MFD-561206 3E4DS0-EST01-EVS-MFD-561206_OPN_FB MER04WCO_AENTR2:0:I.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-1 AENTR2 0 1XSDI1 : 13,14 - SDI-16 6 AENTR2:0:I.6 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-EST01-EVS-MFD-561207_OPN_FB (EVS_FD_ARR_UDT[12].OPN_FB) IS MAPPED TO THIS CHANNEL
MER04WCO_AENTR2:0:I.7
8 3E4DS0-EST01-EVS-MFD-561207 3E4DS0-EST01-EVS-MFD-561207_OPN_FB MER04WCO_AENTR2:0:I.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-1 AENTR2 0 1XSDI1 : 15,16 - SDI-16 7 AENTR2:0:I.7 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-EST01-EVS-MFD-561204_OPN_FB (EVS_FD_ARR_UDT[9].OPN_FB) IS MAPPED TO THIS CHANNEL
MER04WCO_AENTR2:0:I.8
9 3E4DS0-EST01-EVS-MFD-561204 3E4DS0-EST01-EVS-MFD-561204_OPN_FB MER04WCO_AENTR2:0:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-1 AENTR2 0 1XSDI1 : 17,18 - SDI-16 8 AENTR2:0:I.8 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-EST01-EVS-MFD-561205_OPN_FB (EVS_FD_ARR_UDT[10].OPN_FB) IS MAPPED TO THIS CHANNEL
MER04WCO_AENTR2:0:I.9
10 3E4DS0-EST01-EVS-MFD-561205 3E4DS0-EST01-EVS-MFD-561205_OPN_FB MER04WCO_AENTR2:0:I.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-1 AENTR2 0 1XSDI1 : 19,20 - SDI-16 9 AENTR2:0:I.9 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-UA 04-MES-SESD-000005_OPN_FB (SESD_ARR_UDT[5].OPN_FB) IS MAPPED TO THIS CHANNEL
MER04WCO_AENTR2:0:I.12
13 3E4DS0-UA 04-MES-SESD-000005 3E4DS0-UA 04-MES-SESD-000005_OPN_FB MER04WCO_AENTR2:0:I.12.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Door Opened
signal tofor
bestation
confirmed
Evacuation MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-1 AENTR2 0 1XSDI1 : 25,26 - SDI-16 12 AENTR2:0:I.12 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-CA-EVS-SPR-050002_TRIP_FB (SPR_ARR_UDT[6].TRIP_FB) IS CONNECTED TO THIS CHANNEL
SE02WCO_AENTR1:1:I.0.IN SITE ALSO,CABLE CONNECTED TO THE SAME SIGNAL.IN LOGIX THERE IS NO MAPPING WITH
MER04WCO_AENTR2:2:I.0
THIS CHANNEL .IN LOGIX ,THERE IS NO MAPPING WITH THIS CHANNEL MER04WCO_AENTR2:2:I.0 .IN SITE ALSO,THERE IS
17 3E4DS0-CA-EVS-SPR-050002 3E4DS0-CA-EVS-SPR-050002_TRIP_FB NO CABLE CONNECTED TO THIS TERMINAL. As per CWG's RLM comments, SDI2 module is not available at site, please check TRIP STATUS ELEVATOR PRESSURIZATION FAN MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-2 AENTR2 2 1XSDI1 : 1,2 - SDI-16 0 AENTR2:2:I.0 DI I 4/15/2025 DONE

SIGNAL 3E4DS0-CA-EVS-SPR-050002_LOC_FB (SPR_ARR_UDT[6].LOC_FB) IS MAPPED TO THIS CHANNEL


MER04WCO_AENTR2:2:I.1
SE02WCO_AENTR1:1:I.1 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL..IN LOGIX ,THERE IS NO MAPPING
18 3E4DS0-CA-EVS-SPR-050002 3E4DS0-CA-EVS-SPR-050002_LOC_FB WITH THIS CHANNEL MER04WCO_AENTR2:2:I.1 .IN SITE ALSO,THERE IS NO CABLE CONNECTED TO THIS TERMINAL. As per CWG's RLM comments, SDI2 module is not available at site, please check HAND/OFF ELEVATOR PRESSURIZATION FAN MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-2 AENTR2 2 1XSDI1 : 3,4 - SDI-16 1 AENTR2:2:I.1 DI I 4/15/2025 DONE

SIGNAL 3E4DS0-CA-EVS-SPR-050002_REM_FB (SPR_ARR_UDT[6].REM_FB) IS CONNECTED TO THIS CHANNEL


MER04WCO_AENTR2:2:I.2
SE02WCO_AENTR1:1:I.2 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL..IN LOGIX ,THERE IS NO MAPPING
19 3E4DS0-CA-EVS-SPR-050002 3E4DS0-CA-EVS-SPR-050002_REM_FB WITH THIS CHANNEL MER04WCO_AENTR2:2:I.2 .IN SITE ALSO,THERE IS NO CABLE CONNECTED TO THIS TERMINAL. As per CWG's RLM comments, SDI2 module is not available at site, please check AUTO/OFF ELEVATOR PRESSURIZATION FAN MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-2 AENTR2 2 1XSDI1 : 5,6 - SDI-16 2 AENTR2:2:I.2 DI I 4/15/2025 DONE

SIGNAL 3E4DS0-CA-EVS-SPR-050002_RUN_FB (SPR_ARR_UDT[6].RUN_FB) IS CONNECTED TO THIS CHANNEL


MER04WCO_AENTR2:2:I.3
SE02WCO_AENTR1:1:I.3 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL..IN LOGIX ,THERE IS NO MAPPING
20 3E4DS0-CA-EVS-SPR-050002 3E4DS0-CA-EVS-SPR-050002_RUN_FB WITH THIS CHANNEL MER04WCO_AENTR2:2:I.3 .IN SITE ALSO,THERE IS NO CABLE CONNECTED TO THIS TERMINAL. As per CWG's RLM comments, SDI2 module is not available at site, please check RUNNING OF ELEVATOR PRESSURIZATION FAN MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-2 AENTR2 2 1XSDI1 : 7,8 - SDI-16 3 AENTR2:2:I.3 DI I 4/15/2025 DONE

SIGNAL 3E4DS0-CA-EVS-SPRDPS-050002_DPS_FB (SPR_ARR_UDT[6].DPS_FB) IS CONNECTED TO THIS CHANNEL


MER04WCO_AENTR2:2:I.4
SE02WCO_AENTR1:1:I.4 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL..IN LOGIX ,THERE IS NO MAPPING
21 3E4DS0-CA-EVS-SPRDPS-050002 3E4DS0-CA-EVS-SPRDPS-050002_DPS_FB WITH THIS CHANNEL MER04WCO_AENTR2:2:I.4 .IN SITE ALSO,THERE IS NO CABLE CONNECTED TO THIS TERMINAL. As per CWG's RLM comments, SDI2 module is not available at site, please check ELEVATOR PRESSURIZATION FAN PROOF OF FLOW MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-2 AENTR2 2 1XSDI1 : 9,10 - SDI-16 4 AENTR2:2:I.4 DI I 4/15/2025 DONE
IN LOGIX ,THERE IS NO MAPPING WITH THIS CHANNEL MER04WCO_AENTR2:2:I.5 .IN SITE ALSO,THERE IS NO CABLE
MER04WCO_AENTR2:2:I.5
22 SPARE SPARE CONNECTED TO THIS TERMINAL. As per CWG's RLM comments, SDI2 module is not available at site, please check SPARE MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-2 AENTR2 2 1XSDI1 : 11,12 - SDI-16 5 AENTR2:2:I.5 DI I 4/15/2025 DONE
IN LOGIX ,THERE IS NO MAPPING WITH THIS CHANNEL MER04WCO_AENTR2:2:I.6 .IN SITE ALSO,THERE IS NO CABLE
MER04WCO_AENTR2:2:I.6
23 SPARE SPARE CONNECTED TO THIS TERMINAL. As per CWG's RLM comments, SDI2 module is not available at site, please check SPARE MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-2 AENTR2 2 1XSDI1 : 13,14 - SDI-16 6 AENTR2:2:I.6 DI I 4/15/2025 DONE
IN LOGIX ,THERE IS NO MAPPING WITH THIS CHANNEL MER04WCO_AENTR2:2:I.7 .IN SITE ALSO,THERE IS NO CABLE
MER04WCO_AENTR2:2:I.7
24 SPARE SPARE CONNECTED TO THIS TERMINAL. As per CWG's RLM comments, SDI2 module is not available at site, please check SPARE MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-2 AENTR2 2 1XSDI1 : 15,16 - SDI-16 7 AENTR2:2:I.7 DI I 4/15/2025 DONE
IN LOGIX ,THERE IS NO MAPPING WITH THIS CHANNEL MER04WCO_AENTR2:2:I.8 .IN SITE ALSO,THERE IS NO CABLE
MER04WCO_AENTR2:2:I.8
25 SPARE SPARE CONNECTED TO THIS TERMINAL. As per CWG's RLM comments, SDI2 module is not available at site, please check SPARE MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-2 AENTR2 2 1XSDI1 : 17,18 - SDI-16 8 AENTR2:2:I.8 DI I 4/15/2025 DONE
IN LOGIX ,THERE IS NO MAPPING WITH THIS CHANNEL MER04WCO_AENTR2:2:I.9 .IN SITE ALSO,THERE IS NO CABLE
MER04WCO_AENTR2:2:I.9
26 SPARE SPARE CONNECTED TO THIS TERMINAL. As per CWG's RLM comments, SDI2 module is not available at site, please check SPARE MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-2 AENTR2 2 1XSDI1 : 19,20 - SDI-16 9 AENTR2:2:I.9 DI I 4/15/2025 DONE
IN LOGIX ,THERE IS NO MAPPING WITH THIS CHANNEL MER04WCO_AENTR2:2:I.10 .IN SITE ALSO,THERE IS NO CABLE
MER04WCO_AENTR2:2:I.10
27 SPARE SPARE CONNECTED TO THIS TERMINAL. As per CWG's RLM comments, SDI2 module is not available at site, please check SPARE MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-2 AENTR2 2 1XSDI1 : 21,22 - SDI-16 10 AENTR2:2:I.10 DI I 4/15/2025 DONE
IN LOGIX ,THERE IS NO MAPPING WITH THIS CHANNEL MER04WCO_AENTR2:2:I.11 .IN SITE ALSO,THERE IS NO CABLE
MER04WCO_AENTR2:2:I.11
28 SPARE SPARE CONNECTED TO THIS TERMINAL. As per CWG's RLM comments, SDI2 module is not available at site, please check SPARE MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-2 AENTR2 2 1XSDI1 : 23,24 - SDI-16 11 AENTR2:2:I.11 DI I 4/15/2025 DONE
IN LOGIX ,THERE IS NO MAPPING WITH THIS CHANNEL MER04WCO_AENTR2:2:I.12 .IN SITE ALSO,THERE IS NO CABLE
MER04WCO_AENTR2:2:I.12
29 SPARE SPARE CONNECTED TO THIS TERMINAL. As per CWG's RLM comments, SDI2 module is not available at site, please check SPARE MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-2 AENTR2 2 1XSDI1 : 25,26 - SDI-16 12 AENTR2:2:I.12 DI I 4/15/2025 DONE
IN LOGIX ,THERE IS NO MAPPING WITH THIS CHANNEL MER04WCO_AENTR2:2:I.13 .IN SITE ALSO,THERE IS NO CABLE
MER04WCO_AENTR2:2:I.13
30 SPARE SPARE CONNECTED TO THIS TERMINAL. As per CWG's RLM comments, SDI2 module is not available at site, please check SPARE MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-2 AENTR2 2 1XSDI1 : 27,28 - SDI-16 13 AENTR2:2:I.13 DI I 4/15/2025 DONE
IN LOGIX ,THERE IS NO MAPPING WITH THIS CHANNEL MER04WCO_AENTR2:2:I.14 .IN SITE ALSO,THERE IS NO CABLE
MER04WCO_AENTR2:2:I.14
31 SPARE SPARE CONNECTED TO THIS TERMINAL. As per CWG's RLM comments, SDI2 module is not available at site, please check SPARE MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-2 AENTR2 2 1XSDI1 : 29,30 - SDI-16 14 AENTR2:2:I.14 DI I 4/15/2025 DONE

SIGNAL 3E4DS0-MER04-BMS-MER04WCO-000000_MER04WCO_PWR_SPLY1_FAIL (MER04WCO_PWR_SPLY1_FAIL)


3E4DS0-MER04-BMS-RIOP-000007 3E4DS0-MER04-BMS-MER04WCO-000000_MER04WCO_PWR_SPLY1_FAIL MER04WCO_AENTR2:2:I.15
IS MAPPED TO THIS CHANNEL MER04WCO_AENTR2:2:I.15 .IN SITE ALSO,CABLE IS CONNECTED
TO THE SAME SIGNAL.
32 As per CWG's RLM comments, SDI2 module is not available at site, please check POWER SUPPLY FAILURE ALARM MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDI-2 AENTR2 2 1XSDI1 : 31,32 - SDI-16 15 AENTR2:2:I.15 DI I 4/15/2025 DONE

SIGNAL 3E4DS0-UA 03-MES-SESD-000003_ENABLE_DISABLE_CMD (SESD_ARR_UDT[3].ENABLE_DISABLE_CMD) IS MER04WCO_AENTR2:1:O.0


33 3E4DS0-UA 03-MES-SESD-000003 3E4DS0-UA 03-MES-SESD-000003_ENABLE_DISABLE_CMD MAPPED TO THIS RELAY,MER04WCO_AENTR2:1:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Disablesignal
automatic
to be operation
confirmed MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDO-1 AENTR2 1 - 1SR1 : 11,14 SDO-16 0 AENTR2:1:O.0 DO O 4/15/2025 DONE

SIGNAL 3E4DS0-UA 04-MES-SESD-000005_ENABLE_DISABLE_CMD (SESD_ARR_UDT[5].ENABLE_DISABLE_CMD) IS MER04WCO_AENTR2:1:O.1


34 3E4DS0-UA 04-MES-SESD-000005 3E4DS0-UA 04-MES-SESD-000005_ENABLE_DISABLE_CMD MAPPED TO THIS RELAY,MER04WCO_AENTR2:1:O.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Disablesignal
automatic
to be operation
confirmed MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDO-1 AENTR2 1 - 1SR2 : 11,14 SDO-16 1 AENTR2:1:O.1 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-CA-EVS-MFD-231218_OPN_CLS_CMD (EVS_FD_ARR_UDT[7].OPN_CLS_CMD) IS MAPPED TO THIS
MER04WCO_AENTR2:1:O.2
35 3E4DS0-CA-EVS-MFD-231218 3E4DS0-CA-EVS-MFD-231218_OPN_CLS_CMD RELAY,MER04WCO_AENTR2:1:O.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN COMMAND
signal to be confirmed MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDO-1 AENTR2 1 - 1SR3 : 11,14 SDO-16 2 AENTR2:1:O.2 DO O 4/15/2025 DONE

MER04WCO_AENTR2:1:O.3
SIGNAL 3E4DS0-CA-EVS-SPR-050002_ON_OFF_CMD (SPR_ARR_UDT[6].ON_OFF_CMD) IS MAPPED TO THIS
RELAY,SE02WCO_AENTR1:2:O.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.IN LOGIX,THERE IS NO
36 3E4DS0-CA-EVS-SPR-050002 3E4DS0-CA-EVS-SPR-050002_ON_OFF_CMD MAPPING TO THIS RELAY,MER04WCO_AENTR2:1:O.3.IN SITE ALSO,THERE IS NO CABLE CONNECTED TO THIS RELAY. As per CWG RLM, this channel is spare at site, please check. START/STOP ELEVATOR PRESSURIZATION FAN MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDO-1 AENTR2 1 - 1SR4 : 11,14 SDO-16 3 AENTR2:1:O.3 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-CA-EVS-MFD-731215_OPN_CLS_CMD (EVS_FD_ARR_UDT[20].OPN_CLS_CMD) IS MAPPED TO THIS
MER04WCO_AENTR2:1:O.6
39 3E4DS0-CA-EVS-MFD-731215 3E4DS0-CA-EVS-MFD-731215_OPN_CLS_CMD RELAY,MER04WCO_AENTR2:1:O.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN COMMAND
signal to be confirmed MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDO-1 AENTR2 1 - 1SR7 : 11,14 SDO-16 6 AENTR2:1:O.6 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-EST01-EVS-MFD-561206_OPN_CLS_CMD (EVS_FD_ARR_UDT[11].OPN_CLS_CMD) IS MAPPED TO THIS
MER04WCO_AENTR2:1:O.8
41 3E4DS0-EST01-EVS-MFD-561206 3E4DS0-EST01-EVS-MFD-561206_OPN_CLS_CMD RELAY,MER04WCO_AENTR2:1:O.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN COMMAND
signal to be confirmed MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDO-1 AENTR2 1 - 1SR9 : 11,14 SDO-16 8 AENTR2:1:O.8 DO O 4/15/2025 DONE

# General
PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM

DOCUMENT TITLE SHOP DRAWING-DEEP UNDERGROUND STATION-3E4-BMS-INPUT/OUTPUT SCHEDULE

DOCUMENT NO. M-ANM-3E4DS0-CJ00-SCH-000002

MODULE RELAY MODULE CHANNE


SR. NO. EQUIPMENT TAG PLC TAG EASA SITE Response RLM COMMENTS FROM CWG DESCRIPTION PANEL SHORT TAG (OLD) PANEL FULL TAG (NEW) RACK NO. SLOT NO. TERMINAL NO. PLC IO ADDRESS MODULE ID DATE STATUS
ID NO. TYPE L NO.
SIGNAL 3E4DS0-EST01-EVS-MFD-561207_OPN_CLS_CMD (EVS_FD_ARR_UDT[12].OPN_CLS_CMD) IS MAPPED TO THIS
MER04WCO_AENTR2:1:O.10
43 3E4DS0-EST01-EVS-MFD-561207 3E4DS0-EST01-EVS-MFD-561207_OPN_CLS_CMD RELAY,MER04WCO_AENTR2:1:O.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN COMMAND
signal to be confirmed MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDO-1 AENTR2 1 - 1SR11 : 11,14 SDO-16 10 AENTR2:1:O.10 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-EST01-EVS-MFD-561204_OPN_CLS_CMD (EVS_FD_ARR_UDT[9].OPN_CLS_CMD) IS MAPPED TO THIS
MER04WCO_AENTR2:1:O.12
45 3E4DS0-EST01-EVS-MFD-561204 3E4DS0-EST01-EVS-MFD-561204_OPN_CLS_CMD RELAY,MER04WCO_AENTR2:1:O.12.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN COMMAND
signal to be confirmed MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDO-1 AENTR2 1 - 1SR13 : 11,14 SDO-16 12 AENTR2:1:O.12 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-EST01-EVS-MFD-561205_OPN_CLS_CMD (EVS_FD_ARR_UDT[10].OPN_CLS_CMD) IS MAPPED TO THIS
MER04WCO_AENTR2:1:O.13
46 3E4DS0-EST01-EVS-MFD-561205 3E4DS0-EST01-EVS-MFD-561205_OPN_CLS_CMD RELAY,MER04WCO_AENTR2:1:O.13.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN COMMAND
signal to be confirmed MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 SDO-1 AENTR2 1 - 1SR14 : 11,14 SDO-16 13 AENTR2:1:O.13 DO O 4/15/2025 DONE

IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL MER04WCO_AENTR1:0:I.13.IN SITE,ALSO THERE IS NO CABLE MER04WCO_AENTR1:0:I.13


CONNECTED TO THIS TERMINAL.IT IS A SPARE TERMINAL. SIGNAL 3E4DS0-ELE-ELS-ELVDP-001500_INC_OPN_CLS_FB
(ELVDP_ICB_ARR_UDT[3].INC_OPN_CLS_FB) IS MAPPED TO THIS CHANNEL MER02WCO_AENTR1:1:I.Data.30 IN LOGIX.IN
62 3E4DS0-ELE-ELS-ELVDP-001500 3E4DS0-ELE-ELS-ELVDP-001500_INC_OPN_CLS_FB SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is spare at site, please check. INCOMING CIRCUIT OPEN CLOSE FEEDBACK MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 DI-1 AENTR1 0 1XDI1 : 27,28 - DI-32 13 AENTR1:0:I.Data.13 DI I 4/15/2025 DONE

SIGNAL 3E4DS0-MER04-HVAC-AHU-120000_SS2_REM_FB (S_AHU_ARR_UDT[11].SS2_REM_FB) IS MAPPED TO THIS MER04WCO_AENTR1:0:I.27


CHANNEL IN LOGIX,ONLY.IN SITE,SINCE THERE IS NO PROVISION FOR THIS SIGNAL.CABLE IS NOT CONNECTED TO THIS
76 3E4DS0-MER04-HVAC-AHU-120000 3E4DS0-MER04-HVAC-AHU-120000_SS2_REM_FB TERMINAL. As per CWG RLM, this channel is spare at site, please check. Start Push Button RM relay activated/deactivated Status MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 DI-1 AENTR1 0 1XDI1 : 55,56 - DI-32 27 AENTR1:0:I.Data.27 DI I 4/15/2025 DONE

IN LOGIX ALSO,MER04WCO_PWR_SPLY1_FAIL IS MAPPED TO THIS CHANNEL MER04WCO_AENTR1:0:I.Data.31 .IN SITE MER04WCO_AENTR1:0:I.31


80 SPARE SPARE ALSO,RIOP POWER SUPPLY ALARM (,MER04WCO_PWR_SPLY1_FAIL) CABLE IS CONNECTED TO THIS CHANNEL. As per CWG RLM, this channel is used for "RIOP Power Supply Alarm" at site, please check. SPARE MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 DI-1 AENTR1 0 1XDI1 : 63,64 - DI-32 31 AENTR1:0:I.Data.31 DI I 4/15/2025 DONE

SIGNAL 3E4DS0-MER04-HVAC-AHU-120000_SF_ON_OFF_CMD (S_AHU_ARR_UDT[11].SF_ON_OFF_CMD) IS MAPPED TO MER04WCO_AENTR1:4:O.1


98 3E4DS0-MER04-HVAC-AHU-120000 3E4DS0-MER04-HVAC-AHU-120000_SF_ON_OFF_CMD THIS RELAY MER04WCO_AENTR1:4:O.1 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Switch signal
On AHU to be
Power
confirmed
Supply MER04WCO 3E4DS0-MER04-BMS-RIOP-000007 DO-1 AENTR1 4 - 1R2 : 11,14 DO-16 1 AENTR1:4:O.1 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-CA-EVS-MFD-231219_OPN_FB (EVS_FD_ARR_UDT[8].OPN_FB) IS MAPPED TO THIS CHANNEL
MER05WCO_AENTR2:0:I.5
6 3E4DS0-CA-EVS-MFD-231219 3E4DS0-CA-EVS-MFD-231219_OPN_FB MER05WCO_AENTR2:0:I.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-1 AENTR2 0 1XSDI1 : 11,12 - SDI-16 5 AENTR2:0:I.5 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-CA-EVS-MFD-731216_OPN_FB (EVS_FD_ARR_UDT[21].OPN_FB) IS MAPPED TO THIS CHANNEL
MER05WCO_AENTR2:0:I.6
7 3E4DS0-CA-EVS-MFD-731216 3E4DS0-CA-EVS-MFD-731216_OPN_FB MER05WCO_AENTR2:0:I.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-1 AENTR2 0 1XSDI1 : 13,14 - SDI-16 6 AENTR2:0:I.6 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-CA-EVS-MFD-731217_OPN_FB (EVS_FD_ARR_UDT[22].OPN_FB) IS MAPPED TO THIS CHANNEL
MER05WCO_AENTR2:0:I.7
8 3E4DS0-CA-EVS-MFD-731217 3E4DS0-CA-EVS-MFD-731217_OPN_FB MER05WCO_AENTR2:0:I.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-1 AENTR2 0 1XSDI1 : 15,16 - SDI-16 7 AENTR2:0:I.7 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-EST02-EVS-MFD-561208_OPN_FB (EVS_FD_ARR_UDT[13].OPN_FB) IS MAPPED TO THIS CHANNEL
MER05WCO_AENTR2:0:I.8
9 3E4DS0-EST02-EVS-MFD-561208 3E4DS0-EST02-EVS-MFD-561208_OPN_FB MER05WCO_AENTR2:0:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-1 AENTR2 0 1XSDI1 : 17,18 - SDI-16 8 AENTR2:0:I.8 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-EST02-EVS-MFD-561209_OPN_FB (EVS_FD_ARR_UDT[14].OPN_FB) IS MAPPED TO THIS CHANNEL
MER05WCO_AENTR2:0:I.9
10 3E4DS0-EST02-EVS-MFD-561209 3E4DS0-EST02-EVS-MFD-561209_OPN_FB MER05WCO_AENTR2:0:I.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-1 AENTR2 0 1XSDI1 : 19,20 - SDI-16 9 AENTR2:0:I.9 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-EST02-EVS-MFD-561210_OPN_FB (EVS_FD_ARR_UDT[15].OPN_FB) IS MAPPED TO THIS CHANNEL
MER05WCO_AENTR2:0:I.10
11 3E4DS0-EST02-EVS-MFD-561210 3E4DS0-EST02-EVS-MFD-561210_OPN_FB MER05WCO_AENTR2:0:I.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-1 AENTR2 0 1XSDI1 : 21,22 - SDI-16 10 AENTR2:0:I.10 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-EST02-EVS-MFD-561211_OPN_FB (EVS_FD_ARR_UDT[16].OPN_FB) IS MAPPED TO THIS CHANNEL
MER05WCO_AENTR2:0:I.11
12 3E4DS0-EST02-EVS-MFD-561211 3E4DS0-EST02-EVS-MFD-561211_OPN_FB MER05WCO_AENTR2:0:I.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-1 AENTR2 0 1XSDI1 : 23,24 - SDI-16 11 AENTR2:0:I.11 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-UA 06-MES-SESD-000006_OPN_FB (SESD_ARR_UDT[6].OPN_FB) IS MAPPED TO THIS CHANNEL
MER05WCO_AENTR2:0:I.14
15 3E4DS0-UA 06-MES-SESD-000006 3E4DS0-UA 06-MES-SESD-000006_OPN_FB MER05WCO_AENTR2:0:I.14.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Door Opened
signal tofor
bestation
confirmed
Evacuation MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-1 AENTR2 0 1XSDI1 : 29,30 - SDI-16 14 AENTR2:0:I.14 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-SCADA-BMS-ECSPLC-000000_ECSPLC_PWR_SPLY1_FAIL (ECSPLC_PWR_SPLY1_FAIL) IS MAPPED TO THIS
3E4DS0-MER05-BMS-RIOP-000009 MER05WCO_AENTR2:0:I.15
CHANNEL MER05WCO_AENTR2:0:I.15.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
16 3E4DS0-SCADA-BMS-ECSPLC-000000_ECSPLC_PWR_SPLY1_FAIL As per CWG RLM, this channel is spare at site, please check. POWER SUPPLY FAILURE ALARM MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-1 AENTR2 0 1XSDI1 : 31,32 - SDI-16 15 AENTR2:0:I.15 DI I 4/15/2025 DONE
3E4DS0-SE03-EVS-SE-020000 SIGNAL 3E4DS0-SE03-EVS-SE-020000_TRIP_FB (SEF_ARR_UDT[2].TRIP_FB) IS MAPPED TO THIS CHANNEL
SE03WCO_AENTR2:0:I.5 .IN SITE ALSO, CABLE IS CONNECTED TO THE SAME SIGNAL.IN LOGIX,THERE IS NO MAPPING TO
3E4DS0-SE03-EVS-SE-020000_TRIP_FB DI MER05WCO_AENTR2:2:I.0
THIS CHANNEL,MER05WCO_AENTR2:2:I.0 .IN SITE ALSO,THERE IS NO CABLE CONNECTED TO THIS
17 TERMINAL.MER05WCO_AENTR2:2:I.0 As per CWG's RLM comments, SDI2 modules is spare at site, please check. TRIP STATUS SMOKE EXHAUST FAN MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-2 AENTR2 2 1XSDI2 : 1,2 - SDI-16 0 AENTR2:2:I.0 I 4/15/2025 DONE
3E4DS0-SE03-EVS-SE-020000 SIGNAL 3E4DS0-SE03-EVS-SE-020000_LOC_FB(SEF_ARR_UDT[2].LOC_FB) IS MAPPED TO THIS CHANNEL
SE03WCO_AENTR2:0:I.6 .IN SITE ALSO, CABLE IS CONNECTED TO THE SAME SIGNAL.IN LOGIX,THERE IS NO MAPPING TO
3E4DS0-SE03-EVS-SE-020000_LOC_FB DI MER05WCO_AENTR2:2:I.1
THIS CHANNEL,MER05WCO_AENTR2:2:I.1 .IN SITE ALSO,THERE IS NO CABLE CONNECTED TO THIS
18 TERMINAL.MER05WCO_AENTR2:2:I.1 As per CWG's RLM comments, SDI2 modules is spare at site, please check. HAND/OFF SMOKE EXHAUST FAN MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-2 AENTR2 2 1XSDI2 : 3,4 - SDI-16 1 AENTR2:2:I.1 I 4/15/2025 DONE
3E4DS0-SE03-EVS-SE-020000 SIGNAL 3E4DS0-SE03-EVS-SE-020000_REM_FB (SEF_ARR_UDT[2].REM_FB) IS MAPPED TO THIS CHANNEL
SE03WCO_AENTR2:0:I.7 .IN SITE ALSO, CABLE IS CONNECTED TO THE SAME SIGNAL.IN LOGIX,THERE IS NO MAPPING TO
3E4DS0-SE03-EVS-SE-020000_REM_FB DI MER05WCO_AENTR2:2:I.2
THIS CHANNEL,MER05WCO_AENTR2:2:I.2 .IN SITE ALSO,THERE IS NO CABLE CONNECTED TO THIS
19 TERMINAL.MER05WCO_AENTR2:2:I.2 As per CWG's RLM comments, SDI2 modules is spare at site, please check. AUTO/OFF SMOKE EXHAUST FAN MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-2 AENTR2 2 1XSDI2 : 5,6 - SDI-16 2 AENTR2:2:I.2 I 4/15/2025 DONE
3E4DS0-SE03-EVS-SE-020000 SIGNAL 3E4DS0-SE03-EVS-SE-020000_RUN_FB (SEF_ARR_UDT[2].RUN_FB) IS MAPPED TO THIS CHANNEL
SE03WCO_AENTR2:0:I.8 .IN SITE ALSO, CABLE IS CONNECTED TO THE SAME SIGNAL.IN LOGIX,THERE IS NO MAPPING TO
3E4DS0-SE03-EVS-SE-020000_RUN_FB DI MER05WCO_AENTR2:2:I.3
THIS CHANNEL,MER05WCO_AENTR2:2:I.3 .IN SITE ALSO,THERE IS NO CABLE CONNECTED TO THIS
20 TERMINAL.MER05WCO_AENTR2:2:I.3 As per CWG's RLM comments, SDI2 modules is spare at site, please check. RUNNING OF SMOKE EXHAUST FAN MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-2 AENTR2 2 1XSDI2 : 7,8 - SDI-16 3 AENTR2:2:I.3 I 4/15/2025 DONE
3E4DS0-SE03-EVS-SEDPS-020001 SIGNAL 3E4DS0-SE03-EVS-SEDPS-020001_DPS_FB(SEF_ARR_UDT[2].DPS_FB) IS MAPPED TO THIS CHANNEL
SE03WCO_AENTR2:0:I.9 .IN SITE ALSO, CABLE IS CONNECTED TO THE SAME SIGNAL.IN LOGIX,THERE IS NO MAPPING TO
3E4DS0-SE03-EVS-SEDPS-020001_DPS_FB DI MER05WCO_AENTR2:2:I.4
THIS CHANNEL,MER05WCO_AENTR2:2:I.4 .IN SITE ALSO,THERE IS NO CABLE CONNECTED TO THIS
21 TERMINAL.MER05WCO_AENTR2:2:I.4 As per CWG's RLM comments, SDI2 modules is spare at site, please check. SMOKE EXHAUST FAN PROOF OF FLOW MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-2 AENTR2 2 1XSDI2 : 9,10 - SDI-16 4 AENTR2:2:I.4 I 4/15/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL,MER05WCO_AENTR2:2:I.5 .IN SITE ALSO,THERE IS NO CABLE
MER05WCO_AENTR2:2:I.5
22 SPARE SPARE CONNECTED TO THIS TERMINAL.MER05WCO_AENTR2:2:I.5 As per CWG's RLM comments, SDI2 modules is spare at site, please check. SPARE MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-2 AENTR2 2 1XSDI2 : 11,12 - SDI-16 5 AENTR2:2:I.5 DI I 4/15/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL,MER05WCO_AENTR2:2:I.6 .IN SITE ALSO,THERE IS NO CABLE
MER05WCO_AENTR2:2:I.6
23 SPARE SPARE CONNECTED TO THIS TERMINAL.MER05WCO_AENTR2:2:I.6 As per CWG's RLM comments, SDI2 modules is spare at site, please check. SPARE MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-2 AENTR2 2 1XSDI2 : 13,14 - SDI-16 6 AENTR2:2:I.6 DI I 4/15/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL,MER05WCO_AENTR2:2:I.7 .IN SITE ALSO,THERE IS NO CABLE
MER05WCO_AENTR2:2:I.7
24 SPARE SPARE CONNECTED TO THIS TERMINAL.MER05WCO_AENTR2:2:I.7 As per CWG's RLM comments, SDI2 modules is spare at site, please check. SPARE MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-2 AENTR2 2 1XSDI2 : 15,16 - SDI-16 7 AENTR2:2:I.7 DI I 4/15/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL,MER05WCO_AENTR2:2:I.8 .IN SITE ALSO,THERE IS NO CABLE
MER05WCO_AENTR2:2:I.8
25 SPARE SPARE CONNECTED TO THIS TERMINAL.MER05WCO_AENTR2:2:I.8 As per CWG's RLM comments, SDI2 modules is spare at site, please check. SPARE MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-2 AENTR2 2 1XSDI2 : 17,18 - SDI-16 8 AENTR2:2:I.8 DI I 4/15/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL,MER05WCO_AENTR2:2:I.9 .IN SITE ALSO,THERE IS NO CABLE
MER05WCO_AENTR2:2:I.9
26 SPARE SPARE CONNECTED TO THIS TERMINAL.MER05WCO_AENTR2:2:I.9 As per CWG's RLM comments, SDI2 modules is spare at site, please check. SPARE MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-2 AENTR2 2 1XSDI2 : 19,20 - SDI-16 9 AENTR2:2:I.9 DI I 4/15/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL,MER05WCO_AENTR2:2:I.10 .IN SITE ALSO,THERE IS NO CABLE
MER05WCO_AENTR2:2:I.10
27 SPARE SPARE CONNECTED TO THIS TERMINAL.MER05WCO_AENTR2:2:I.10 As per CWG's RLM comments, SDI2 modules is spare at site, please check. SPARE MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-2 AENTR2 2 1XSDI2 : 21,22 - SDI-16 10 AENTR2:2:I.10 DI I 4/15/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL,MER05WCO_AENTR2:2:I.11 .IN SITE ALSO,THERE IS NO CABLE
MER05WCO_AENTR2:2:I.11
28 SPARE SPARE CONNECTED TO THIS TERMINAL.MER05WCO_AENTR2:2:I.11 As per CWG's RLM comments, SDI2 modules is spare at site, please check. SPARE MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-2 AENTR2 2 1XSDI2 : 23,24 - SDI-16 11 AENTR2:2:I.11 DI I 4/15/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL,MER05WCO_AENTR2:2:I.12 .IN SITE ALSO,THERE IS NO CABLE
MER05WCO_AENTR2:2:I.12
29 SPARE SPARE CONNECTED TO THIS TERMINAL.MER05WCO_AENTR2:2:I.12 As per CWG's RLM comments, SDI2 modules is spare at site, please check. SPARE MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-2 AENTR2 2 1XSDI2 : 25,26 - SDI-16 12 AENTR2:2:I.12 DI I 4/15/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL,MER05WCO_AENTR2:2:I.13 .IN SITE ALSO,THERE IS NO CABLE
MER05WCO_AENTR2:2:I.13
30 SPARE SPARE CONNECTED TO THIS TERMINAL.MER05WCO_AENTR2:2:I.13 As per CWG's RLM comments, SDI2 modules is spare at site, please check. SPARE MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-2 AENTR2 2 1XSDI2 : 27,28 - SDI-16 13 AENTR2:2:I.13 DI I 4/15/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL,MER05WCO_AENTR2:2:I.14 .IN SITE ALSO,THERE IS NO CABLE
MER05WCO_AENTR2:2:I.14
31 SPARE SPARE CONNECTED TO THIS TERMINAL.MER05WCO_AENTR2:2:I.14 As per CWG's RLM comments, SDI2 modules is spare at site, please check. SPARE MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-2 AENTR2 2 1XSDI2 : 29,30 - SDI-16 14 AENTR2:2:I.14 DI I 4/15/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL,MER05WCO_AENTR2:2:I.15 .IN SITE ALSO,THERE IS NO CABLE
MER05WCO_AENTR2:2:I.15
32 SPARE SPARE CONNECTED TO THIS TERMINAL.MER05WCO_AENTR2:2:I.15 As per CWG's RLM comments, SDI2 modules is spare at site, please check. SPARE MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDI-2 AENTR2 2 1XSDI2 : 31,32 - SDI-16 15 AENTR2:2:I.15 DI I 4/15/2025 DONE
3E4DS0-SE03-EVS-SE-020000

IN LOGIX,THERE IS NO MAPPING TO THIS RELAY,MER05WCO_AENTR2:1:O.0 .IN SITE ALSO,THERE IS NO CABLE


3E4DS0-SE03-EVS-SE-020000_ON_OFF_CMD CONNECTED TO THIS RELAY,MER05WCO_AENTR2:1:O.0. MER05WCO_AENTR2:1:O.0

SIGNAL 3E4DS0-SE03-EVS-SE-020000_ON_OFF_CMD (SEF_ARR_UDT[2].ON_OFF_CMD) IS MAPPED TO THIS


RELAY,SE03WCO_AENTR1:1:O.3.
33 IN SITE ALSO,CABLE IS CONNECTED TO THIS RELAY,SE03WCO_AENTR1:1:O.3. As per CWG RLM, this channel is spare at site, please check. START/STOP SMOKE EXHAUST FAN MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDO-1 AENTR2 1 - 1SR1 : 11,14 SDO-16 0 AENTR2:1:O.0 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-CA-EVS-MFD-731216_OPN_CLS_CMD (EVS_FD_ARR_UDT[21].OPN_CLS_CMD) IS MAPPED TO THIS
MER05WCO_AENTR2:1:O.4
37 3E4DS0-CA-EVS-MFD-731216 3E4DS0-CA-EVS-MFD-731216_OPN_CLS_CMD RELAY,MER05WCO_AENTR2:1:O.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN COMMAND
signal to be confirmed MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDO-1 AENTR2 1 - 1SR5 : 11,14 SDO-16 4 AENTR2:1:O.4 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-EST02-EVS-MFD-561208_OPN_CLS_CMD (EVS_FD_ARR_UDT[13].OPN_CLS_CMD) IS MAPPED TO THIS
MER05WCO_AENTR2:1:O.6
39 3E4DS0-EST02-EVS-MFD-561208 3E4DS0-EST02-EVS-MFD-561208_OPN_CLS_CMD RELAY,MER05WCO_AENTR2:1:O.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN COMMAND
signal to be confirmed MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDO-1 AENTR2 1 - 1SR7 : 11,14 SDO-16 6 AENTR2:1:O.6 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-EST02-EVS-MFD-561210_OPN_CLS_CMD (EVS_FD_ARR_UDT[15].OPN_CLS_CMD) IS MAPPED TO THIS
MER05WCO_AENTR2:1:O.8
41 3E4DS0-EST02-EVS-MFD-561210 3E4DS0-EST02-EVS-MFD-561210_OPN_CLS_CMD RELAY,MER05WCO_AENTR2:1:O.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN COMMAND
signal to be confirmed MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDO-1 AENTR2 1 - 1SR9 : 11,14 SDO-16 8 AENTR2:1:O.8 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-CA-EVS-MFD-231219_OPN_CLS_CMD (EVS_FD_ARR_UDT[8].OPN_CLS_CMD) IS MAPPED TO THIS
MER05WCO_AENTR2:1:O.9
42 3E4DS0-CA-EVS-MFD-231219 3E4DS0-CA-EVS-MFD-231219_OPN_CLS_CMD RELAY,MER05WCO_AENTR2:1:O.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN COMMAND
signal to be confirmed MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDO-1 AENTR2 1 - 1SR10 : 11,14 SDO-16 9 AENTR2:1:O.9 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-CA-EVS-MFD-731217_OPN_CLS_CMD (EVS_FD_ARR_UDT[22].OPN_CLS_CMD) IS MAPPED TO THIS
MER05WCO_AENTR2:1:O.10
43 3E4DS0-CA-EVS-MFD-731217 3E4DS0-CA-EVS-MFD-731217_OPN_CLS_CMD RELAY,MER05WCO_AENTR2:1:O.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN COMMAND
signal to be confirmed MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDO-1 AENTR2 1 - 1SR11 : 11,14 SDO-16 10 AENTR2:1:O.10 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-EST02-EVS-MFD-561209_OPN_CLS_CMD (EVS_FD_ARR_UDT[14].OPN_CLS_CMD) IS MAPPED TO THIS
MER05WCO_AENTR2:1:O.11
44 3E4DS0-EST02-EVS-MFD-561209 3E4DS0-EST02-EVS-MFD-561209_OPN_CLS_CMD RELAY,MER05WCO_AENTR2:1:O.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN COMMAND
signal to be confirmed MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDO-1 AENTR2 1 - 1SR12 : 11,14 SDO-16 11 AENTR2:1:O.11 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-EST02-EVS-MFD-561211_OPN_CLS_CMD (EVS_FD_ARR_UDT[16].OPN_CLS_CMD) IS MAPPED TO THIS
MER05WCO_AENTR2:1:O.12
45 3E4DS0-EST02-EVS-MFD-561211 3E4DS0-EST02-EVS-MFD-561211_OPN_CLS_CMD RELAY,MER05WCO_AENTR2:1:O.12.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN COMMAND
signal to be confirmed MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 SDO-1 AENTR2 1 - 1SR13 : 11,14 SDO-16 12 AENTR2:1:O.12 DO O 4/15/2025 DONE

SIGNAL 3E4DS0-SMR-ELS-EUDP-002603_INC_OPN_CLS_FB (EUDP_CKT_ARR_UDT[4].INC_OPN_CLS_FB) IS MAPPED TO MER05WCO_AENTR1:0:I.23


72 3E4DS0-SMR-ELS-EUDP-002603 3E4DS0-SMR-ELS-EUDP-002603_INC_OPN_CLS_FB THIS CHANNEL MER05WCO_AENTR1:0:I.Data.23 .IN SITE ,ALSO CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
INCOMING
signalCIRCUIT
to be confirmed
TO EUDP MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 DI-1 AENTR1 0 1XDI1 : 47,48 - DI-32 23 AENTR1:0:I.Data.23 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-MER05-HVAC-AHU-130000_SS2_REM_FB(S_AHU_ARR_UDT[12].SS2_REM_FB) IS MAPPED TO THIS
CHANNEL MER05WCO_AENTR1:0:I.Data.28 IN LOGIX,ONLY.IN SITE,SINCE THERE IS NO SIGNAL PROVISION ,CABLE IS NOT MER05WCO_AENTR1:0:I.28
77 3E4DS0-MER05-HVAC-AHU-130000 3E4DS0-MER05-HVAC-AHU-130000_SS2_REM_FB CONNECTED TO THIS TERMINAL. As per CWG RLM, this channel is spare at site, please check. Start Push Button RM relay activated/deactivated Status MER05WCO 3E4DS0-MER05-BMS-RIOP-000009 DI-1 AENTR1 0 1XDI1 : 57,58 - DI-32 28 AENTR1:0:I.Data.28 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-CO-EVS-MFD-102129_OPN_FB (EVS_FD_ARR_UDT[4].OPN_FB) IS MAPPED TO THIS CHANNEL
MERETO_AENTR3:0:I.0
1 3E4DS0-CO-EVS-MFD-102129 3E4DS0-CO-EVS-MFD-102129_OPN_FB MERETO_AENTR3:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed MERETO 3E4DS0-MER-BMS-RIOP-000020 SDI-1 AENTR3 0 2XSDI1 : 1,2 - SDI-16 0 AENTR3:0:I.0 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-CO-EVS-MFD-102129_CLS_FB_DOOR1 (EVS_FD_ARR_UDT[4].CLS_FB_DOOR1) IS MAPPED TO THIS
MERETO_AENTR3:0:I.1
2 3E4DS0-CO-EVS-MFD-102129 3E4DS0-CO-EVS-MFD-102129_CLS_FB_DOOR1 CHANNEL MERETO_AENTR3:0:I.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
DOOR signal
CLOSEto
STATUS
be confirmed
-1 MERETO 3E4DS0-MER-BMS-RIOP-000020 SDI-1 AENTR3 0 2XSDI1 : 3,4 - SDI-16 1 AENTR3:0:I.1 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-CO-EVS-MFD-102129_CLS_FB_DOOR2 (EVS_FD_ARR_UDT[4].CLS_FB_DOOR2) IS MAPPED TO THIS
MERETO_AENTR3:0:I.2
3 3E4DS0-CO-EVS-MFD-102129 3E4DS0-CO-EVS-MFD-102129_CLS_FB_DOOR2 CHANNEL MERETO_AENTR3:0:I.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
DOOR signal
CLOSEto
STATUS
be confirmed
-2 MERETO 3E4DS0-MER-BMS-RIOP-000020 SDI-1 AENTR3 0 2XSDI1 : 5,6 - SDI-16 2 AENTR3:0:I.2 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-BATR-HVAC-HYD-010001_ALM (HYD_010001_ALM) IS MAPPED TO THIS CHANNEL
MERETO_AENTR3:0:I.3
4 3E4DS0-BATR-HVAC-HYD-010001 3E4DS0-BATR-HVAC-HYD-010001_ALM MERETO_AENTR3:0:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is spare at site, please check. Hydrogen sensor Alarm and Fault MERETO 3E4DS0-MER-BMS-RIOP-000020 SDI-1 AENTR3 0 2XSDI1 : 7,8 - SDI-16 3 AENTR3:0:I.3 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-BATR-HVAC-HYD-010002_ALM (HYD_010002_ALM) IS MAPPED TO THIS CHANNEL
MERETO_AENTR3:0:I.4
5 3E4DS0-BATR-HVAC-HYD-010002 3E4DS0-BATR-HVAC-HYD-010002_ALM MERETO_AENTR3:0:I.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is spare at site, please check. Hydrogen sensor Alarm and Fault MERETO 3E4DS0-MER-BMS-RIOP-000020 SDI-1 AENTR3 0 2XSDI1 : 9,10 - SDI-16 4 AENTR3:0:I.4 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-EBR-HVAC-HYD-010003_ALM (HYD_010003_ALM) IS MAPPED TO THIS CHANNEL
MERETO_AENTR3:0:I.5
6 3E4DS0-EBR-HVAC-HYD-010003 3E4DS0-EBR-HVAC-HYD-010003_ALM MERETO_AENTR3:0:I.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is spare at site, please check. Hydrogen sensor Alarm and Fault MERETO 3E4DS0-MER-BMS-RIOP-000020 SDI-1 AENTR3 0 2XSDI1 : 11,12 - SDI-16 5 AENTR3:0:I.5 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-EBR-HVAC-HYD-010004_ALM (HYD_010004_ALM) IS MAPPED TO THIS CHANNEL
MERETO_AENTR3:0:I.6
7 3E4DS0-EBR-HVAC-HYD-010004 3E4DS0-EBR-HVAC-HYD-010004_ALM MERETO_AENTR3:0:I.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is spare at site, please check. Hydrogen sensor Alarm and Fault MERETO 3E4DS0-MER-BMS-RIOP-000020 SDI-1 AENTR3 0 2XSDI1 : 13,14 - SDI-16 6 AENTR3:0:I.6 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-CO-EVS-MFD-102129_OPN_CLS_CMD(EVS_FD_ARR_UDT[4].OPN_CLS_CMD) IS MAPPED TO THIS RELAY,
MERETO_AENTR3:1:O.0
17 3E4DS0-CO-EVS-MFD-102129 3E4DS0-CO-EVS-MFD-102129_OPN_CLS_CMD MERETO_AENTR3:1:O.0 .IN SITE ALSO,CABLE IS CONNECTED TO THIS RELAY. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN COMMAND
signal to be confirmed MERETO 3E4DS0-MER-BMS-RIOP-000020 SDO-1 AENTR3 1 - 2SR1 : 11,14 SDO-16 0 AENTR3:1:O.0 DO O 4/15/2025 DONE

IN SITE THERE IS NO CABLE CONNECTED TO THIS CHANNEL MERETO_AENTR3:2:I.Ch0Data.IN LOGIX,ALSO THERE IS NO


MERETO_AENTR3:2:chdata.0
MAPPING TO THIS CHANNEL MERETO_AENTR3:2:I.Ch0Data .SIGNAL 3E4DS0-BATR-HVAC-HYD-010001_CON_LVL,IS
33 3E4DS0-BATR-HVAC-HYD-010001 3E4DS0-BATR-HVAC-HYD-010001_CON_LVL MAPPED TO THIS CHANNEL MERETO_AENTR3:2:I.Ch3Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is spare at site, please check. Hydrogen Concentration Level MERETO 3E4DS0-MER-BMS-RIOP-000020 SAI-1 AENTR3 2 2XSAI1 : 7,8 - SAI-08 0 AENTR3:2:I.Ch0Data chdata 4/15/2025 DONE

IN SITE THERE IS NO CABLE CONNECTED TO THIS CHANNEL MERETO_AENTR3:2:I.Ch1Data.IN LOGIX,ALSO THERE IS NO


MERETO_AENTR3:2:chdata.1
MAPPING TO THIS CHANNEL MERETO_AENTR3:2:I.Ch1Data .SIGNAL 3E4DS0-BATR-HVAC-HYD-010002_CON_LVL,IS
34 3E4DS0-BATR-HVAC-HYD-010002 3E4DS0-BATR-HVAC-HYD-010002_CON_LVL MAPPED TO THIS CHANNEL MERETO_AENTR3:2:I.Ch4Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is spare at site, please check. Hydrogen Concentration Level MERETO 3E4DS0-MER-BMS-RIOP-000020 SAI-1 AENTR3 2 2XSAI1 : 9,10 - SAI-08 1 AENTR3:2:I.Ch1Data chdata 4/15/2025 DONE

IN SITE THERE IS NO CABLE CONNECTED TO THIS CHANNEL MERETO_AENTR3:2:I.Ch2Data.IN LOGIX,ALSO THERE IS NO


MERETO_AENTR3:2:chdata.2
MAPPING TO THIS CHANNEL MERETO_AENTR3:2:I.Ch2Data .SIGNAL 3E4DS0-EBR-HVAC-HYD-010003_CON_LVL,IS
35 3E4DS0-EBR-HVAC-HYD-010003 3E4DS0-EBR-HVAC-HYD-010003_CON_LVL MAPPED TO THIS CHANNEL MERETO_AENTR3:2:I.Ch5Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is spare at site, please check. Hydrogen Concentration Level MERETO 3E4DS0-MER-BMS-RIOP-000020 SAI-1 AENTR3 2 2XSAI1 : 11,12 - SAI-08 2 AENTR3:2:I.Ch2Data chdata 4/15/2025 DONE

IN SITE THERE IS NO CABLE CONNECTED TO THIS CHANNEL MERETO_AENTR3:2:I.Ch3Data.IN LOGIX,ALSO THERE IS NO


MERETO_AENTR3:2:chdata.3
MAPPING TO THIS CHANNEL MERETO_AENTR3:2:I.Ch3Data .SIGNAL 3E4DS0-EBR-HVAC-HYD-010004_CON_LVL,IS
36 3E4DS0-EBR-HVAC-HYD-010004 3E4DS0-EBR-HVAC-HYD-010004_CON_LVL MAPPED TO THIS CHANNEL MERETO_AENTR3:2:I.Ch6Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is spare at site, please check. Hydrogen Concentration Level MERETO 3E4DS0-MER-BMS-RIOP-000020 SAI-1 AENTR3 2 2XSAI1 : 13,14 - SAI-08 3 AENTR3:2:I.Ch3Data chdata 4/15/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-MAU-050000_SF_TRIP (D_MAU_ARR_UDT[2].SF_TRIP) IS MAPPED TO THIS CHANNEL
MERETO_AENTR1:0:I.0
41 3E4DS0-MER-HVAC-MAU-050000 3E4DS0-MER-HVAC-MAU-050000_SF_TRIP MERETO_AENTR1:0:I.0.IN SITE ALSO CABLE IS CONNECTED TO THIS TERMINAL. As per CWG RLM, this channel is spare at site, please check. TRIP STATUS SUPPLY FAN MERETO 3E4DS0-MER-BMS-RIOP-000020 DI-1 AENTR1 0 2XDI1 : 1,2 - DI-16 0 AENTR1:0:I.0 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-MAU-050000_RUN_FB ( D_MAU_ARR_UDT[2].RF_RUN_FB) IS MAPPED TO THIS CHANNEL
MERETO_AENTR1:0:I.7
48 SPARE SPARE MERETO_AENTR1:0:I.7.IN SITE ALSO CABLE IS CONNECTED TO THIS TERMINAL. As per CWG RLM, this channel is used at site, please check. SPARE MERETO 3E4DS0-MER-BMS-RIOP-000020 DI-1 AENTR1 0 2XDI1 : 15,16 - DI-16 7 AENTR1:0:I.7 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-AHU-040000_AIP1_ON (S_AHU_ARR_UDT[4].AIP1_ON) IS MAPPED TO THIS CHANNEL
MERETO_AENTR2:0:I.Data.16.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.SINCE THERE IS A ISSUE WITH
MERETO_AENTR2:0:I.7
CHANNEL MERETO_AENTR2:0:I.7 ,ALTERNATIVE CHANNEL IS USED IN SITE.IN SITE,THERE IS NO CABLE CONNECTED TO
64 3E4DS0-MER-HVAC-AHU-040000 3E4DS0-MER-HVAC-AHU-040000_AIP1_ON THIS CHANNEL MERETO_AENTR2:0:I.7 As per CWG RLM, this channel is spare at site, please check. ON AIR IONIZER PURIFIER NO. 1 MERETO 3E4DS0-MER-BMS-RIOP-000020 DI-2 AENTR2 0 2XDI2 : 15,16 - DI-32 7 AENTR2:0:I.Data.7 DI I 4/15/2025 DONE
SIGNAL S_AHU_ARR_UDT[4].AIP1_ON IS CONNECTED TO THIS CHANNEL MERETO_AENTR2:0:I.Data.16.IN SITE
MERETO_AENTR2:0:I.16
73 SPARE SPARE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE MERETO 3E4DS0-MER-BMS-RIOP-000020 DI-2 AENTR2 0 2XDI2 : 33,34 - DI-32 16 AENTR2:0:I.Data.16 DI I 4/15/2025 DONE

# General
PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM

DOCUMENT TITLE SHOP DRAWING-DEEP UNDERGROUND STATION-3E4-BMS-INPUT/OUTPUT SCHEDULE

DOCUMENT NO. M-ANM-3E4DS0-CJ00-SCH-000002

MODULE RELAY MODULE CHANNE


SR. NO. EQUIPMENT TAG PLC TAG EASA SITE Response RLM COMMENTS FROM CWG DESCRIPTION PANEL SHORT TAG (OLD) PANEL FULL TAG (NEW) RACK NO. SLOT NO. TERMINAL NO. PLC IO ADDRESS MODULE ID DATE STATUS
ID NO. TYPE L NO.

SIGNAL 3E4DS0-ELE-HVAC-MFD-012118 (HVAC_FD_ARR_UDT[9].OPN_FB) IS MAPPED TO THIS


MERETO_AENTR2:0:I.18
CHANNEL,MERETO_AENTR2:0:I.18.
75 SPARE SPARE IN SITE ALSO CABLE IS CONNECTED TO THIS TERMINAL. As per CWG RLM, this channel is used at site, please check. SPARE MERETO 3E4DS0-MER-BMS-RIOP-000020 DI-2 AENTR2 0 2XDI2 : 37,38 - DI-32 18 AENTR2:0:I.Data.18 DI I 4/15/2025 DONE
SIGNAL S_AHU_ARR_UDT[4].SS2_REM_FB IS MAPPED TO THIS CHANNEL MERETO_AENTR1:1:I.23 IN LOGIX,ONLY.IN SITE
THERE IS NO PROVISION FOR THIS SIGNAL,SO MERETO_AENTR1:1:I.23
112 3E4DS0-MER-HVAC-AHU-040000 3E4DS0-MER-HVAC-AHU-040000_SS2_REM_FB CABLE IS NOT CONNECTED FOR THIS TERMINAL. As per CWG RLM, this channel is spare at site, please check. Start Push Button RM relay activated/deactivated Status MERETO 3E4DS0-MER-BMS-RIOP-000020 DI-3 AENTR1 1 2XDI3 : 47,48 - DI-32 23 AENTR1:1:I.Data.23 DI I 4/15/2025 DONE
SIGNAL S_AHU_ARR_UDT[5].SS2_REM_FB IS MAPPED TO THIS CHANNEL MERETO_AENTR1:1:I.25 IN LOGIX,ONLY.IN SITE
THERE IS NO PROVISION FOR THIS SIGNAL,SO MERETO_AENTR1:1:I.25
114 3E4DS0-MER-HVAC-AHU-050000 3E4DS0-MER-HVAC-AHU-050000_SS2_REM_FB CABLE IS NOT CONNECTED FOR THIS TERMINAL. As per CWG RLM, this channel is spare at site, please check. Start Push Button RM relay activated/deactivated Status MERETO 3E4DS0-MER-BMS-RIOP-000020 DI-3 AENTR1 1 2XDI3 : 51,52 - DI-32 25 AENTR1:1:I.Data.25 DI I 4/15/2025 DONE
SIGNAL S_AHU_ARR_UDT[5].SS2_REM_FB IS MAPPED TO THIS CHANNEL MERETO_AENTR1:1:I.27 IN LOGIX,ONLY.IN SITE
THERE IS NO PROVISION FOR THIS SIGNAL,SO MERETO_AENTR1:1:I.27
116 3E4DS0-MER-HVAC-MAU-050000 3E4DS0-MER-HVAC-MAU-050000_SS2_REM_FB CABLE IS NOT CONNECTED FOR THIS TERMINAL. As per CWG RLM, this channel is spare at site, please check. Start Push Button RM relay activated/deactivated Status MERETO 3E4DS0-MER-BMS-RIOP-000020 DI-3 AENTR1 1 2XDI3 : 55,56 - DI-32 27 AENTR1:1:I.Data.27 DI I 4/15/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-MVD-052130_OPN_CLS_CMD (MVD_ARR_UDT[1].OPN_CLS_CMD) IS MAPPED TO THIS
MERETO_AENTR2:1:O.10
131 3E4DS0-MER-HVAC-MVD-052130 3E4DS0-MER-HVAC-MVD-052130_OPN_CLS_CMD RELAY,MERETO_AENTR2:1:O.Data.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
DAMPERsignal
MVD toOPEN
be confirmed
CLOSE COMMAND MERETO 3E4DS0-MER-BMS-RIOP-000020 DO-1 AENTR2 1 - 2R11 : 11,14 DO-32 10 AENTR2:1:O.Data.10 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-MVD-052131_OPN_CLS_CMD (MVD_ARR_UDT[2].OPN_CLS_CMD) IS MAPPED TO THIS
MERETO_AENTR2:1:O.11
132 3E4DS0-MER-HVAC-MVD-052131 3E4DS0-MER-HVAC-MVD-052131_OPN_CLS_CMD RELAY,MERETO_AENTR2:1:O.Data.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
DAMPERsignal
MVD toOPEN
be confirmed
CLOSE COMMAND MERETO 3E4DS0-MER-BMS-RIOP-000020 DO-1 AENTR2 1 - 2R12 : 11,14 DO-32 11 AENTR2:1:O.Data.11 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-MER -HVAC-MVD-052132_OPN_CLS_CMD (MVD_ARR_UDT[3].OPN_CLS_CMD) IS MAPPED TO THIS
MERETO_AENTR2:1:O.12
133 3E4DS0-MER -HVAC-MVD-052132 3E4DS0-MER -HVAC-MVD-052132_OPN_CLS_CMD RELAY,MERETO_AENTR2:1:O.Data.12.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
DAMPERsignal
MVD toOPEN
be confirmed
CLOSE COMMAND MERETO 3E4DS0-MER-BMS-RIOP-000020 DO-1 AENTR2 1 - 2R13 : 11,14 DO-32 12 AENTR2:1:O.Data.12 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-MER -HVAC-MVD-052133_OPN_CLS_CMD (MVD_ARR_UDT[4].OPN_CLS_CMD) IS MAPPED TO THIS
MERETO_AENTR2:1:O.13
134 3E4DS0-MER -HVAC-MVD-052133 3E4DS0-MER -HVAC-MVD-052133_OPN_CLS_CMD RELAY,MERETO_AENTR2:1:O.Data.13.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
DAMPERsignal
MVD toOPEN
be confirmed
CLOSE COMMAND MERETO 3E4DS0-MER-BMS-RIOP-000020 DO-1 AENTR2 1 - 2R14 : 11,14 DO-32 13 AENTR2:1:O.Data.13 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-MAU-050000_SF_ON_OFF_CMDMERETO_AENTR2:1:O.Data.14
D_MAU_ARR_UDT[2].SF_ON_OFF_CMD IS MAPPED TO THIS RELAY,MERETO_AENTR2:1:O.Data.14.IN SITE ALSO,CABLE MERETO_AENTR2:1:O.14
135 3E4DS0-MER-HVAC-MAU-050000 3E4DS0-MER-HVAC-MAU-050000_SF_ON_OFF_CMD IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Switch signal
On MAU to be
Power
confirmed
Supply MERETO 3E4DS0-MER-BMS-RIOP-000020 DO-1 AENTR2 1 - 2R15 : 11,14 DO-32 14 AENTR2:1:O.Data.14 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-AHU-040000_SF_ON_OFF_CMDMERETO_AENTR2:1:O.Data.15
S_AHU_ARR_UDT[4].SF_ON_OFF_CMD IS MAPPED TO THIS RELAY,MERETO_AENTR2:1:O.Data.15.IN SITE ALSO,CABLE IS MERETO_AENTR2:1:O.15
136 3E4DS0-MER-HVAC-AHU-040000 3E4DS0-MER-HVAC-AHU-040000_SF_ON_OFF_CMD CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Switch signal
On AHU to be
Power
confirmed
Supply MERETO 3E4DS0-MER-BMS-RIOP-000020 DO-1 AENTR2 1 - 2R16 : 11,14 DO-32 15 AENTR2:1:O.Data.15 DO O 4/15/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-AHU-050000_SF_ON_OFF_CMDMERETO_AENTR2:1:O.Data.16
S_AHU_ARR_UDT[5].SF_ON_OFF_CMD IS MAPPED TO THIS RELAY,MERETO_AENTR2:1:O.Data.16.IN SITE ALSO,CABLE IS MERETO_AENTR2:1:O.16
137 3E4DS0-MER-HVAC-AHU-050000 3E4DS0-MER-HVAC-AHU-050000_SF_ON_OFF_CMD CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Switch signal
On AHU to be
Power
confirmed
Supply MERETO 3E4DS0-MER-BMS-RIOP-000020 DO-1 AENTR2 1 - 2R17 : 11,14 DO-32 16 AENTR2:1:O.Data.16 DO O 4/15/2025 DONE

SIGNAL 3E4DS0-CO01-EVS-MFD-103030_OPN_FB (EVS_FD_ARR_UDT[5].OPN_FB) IS MAPPED TO THIS CHANNEL MERWMO_AENTR3:0:I.0


1 3E4DS0-CO01-EVS-MFD-103030 3E4DS0-CO01-EVS-MFD-103030_OPN_FB MERWMO_AENTR3:0:I.0 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed MERWMO 3E4DS0-MER-BMS-RIOP-000024 SDI-1 AENTR3 0 2XSDI1 : 1,2 - SDI-16 0 AENTR3:0:I.0 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-CO01-EVS-MFD-103030_CLS_FB_DOOR1 (EVS_FD_ARR_UDT[5].CLS_FB_DOOR1) IS MAPPED TO THIS
MERWMO_AENTR3:0:I.1
2 3E4DS0-CO01-EVS-MFD-103030 3E4DS0-CO01-EVS-MFD-103030_CLS_FB_DOOR1 CHANNEL MERWMO_AENTR3:0:I.1 .IN SITE ALSO ,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
DOOR signal
CLOSEto
STATUS
be confirmed
-1 MERWMO 3E4DS0-MER-BMS-RIOP-000024 SDI-1 AENTR3 0 2XSDI1 : 3,4 - SDI-16 1 AENTR3:0:I.1 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-CO01-EVS-MFD-103030_CLS_FB_DOOR2 (EVS_FD_ARR_UDT[5].CLS_FB_DOOR2) IS MAPPED TO THIS
MERWMO_AENTR3:0:I.2
3 3E4DS0-CO01-EVS-MFD-103030 3E4DS0-CO01-EVS-MFD-103030_CLS_FB_DOOR2 CHANNEL MERWMO_AENTR3:0:I.2 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
DOOR signal
CLOSEto
STATUS
be confirmed
-2 MERWMO 3E4DS0-MER-BMS-RIOP-000024 SDI-1 AENTR3 0 2XSDI1 : 5,6 - SDI-16 2 AENTR3:0:I.2 DI I 4/17/2025 DONE

SIGNAL 3E4DS0-FCC-FDPS-FACP-200004_FACP2_SMOKE_DETECTOR.1 (FACP_ARR_UDT[2].FACP2_SMOKE_DETECTOR.1) [FACP-2] Smoke Detectors/Manual station/Beam


3E4DS0-FCC-FDPS-FACP-200004 3E4DS0-FCC-FDPS-FACP-200004_FACP2_SMOKE_DETECTOR.1 IS MAPPED TO THIS CHANNEL MERWMO_AENTR3:0:I.4 .IN LOGIX.IN SITE,ALSO CABLE IS CONNECTED TO THIS As per CWG RLM, this channel is spare at site, please check. detector - Mezzanine (BOH and Not FM-200 rooms and MERWMO SDI-1 AENTR3 0 2XSDI1 : 9,10 - SDI-16 4 MERWMO_AENTR3:0:I.4
TERMINAL. Not SE,TVR,OTE/UPE Rooms)
5 3E4DS0-MER-BMS-RIOP-000024 AENTR3:0:I.4 DI I 4/17/2025 DONE

SIGNAL 3E4DS0-FCC-FDPS-FACP-200004_FACP2_SMOKE_DETECTOR.2 (FACP_ARR_UDT[2].FACP2_SMOKE_DETECTOR.2) [FACP-2] Smoke Detectors -Mezzanine Elevator


MERWMO_AENTR3:0:I.5
IS MAPPED TO THIS CHANNEL MERWMO_AENTR3:0:I.5. IN LOGIX.IN SITE,ALSO CABLE IS CONNECTED TO THIS (01,02,03,04) Lobby - BOH
6 3E4DS0-FCC-FDPS-FACP-200004 3E4DS0-FCC-FDPS-FACP-200004_FACP2_SMOKE_DETECTOR.2 TERMINAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MERWMO 3E4DS0-MER-BMS-RIOP-000024 SDI-1 AENTR3 0 2XSDI1 : 11,12 - SDI-16 5 AENTR3:0:I.5 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-CO01-EVS-MFD-103030_OPN_CLS_CMD (EVS_FD_ARR_UDT[5].OPN_CLS_CMD) IS MAPPED TO THIS
MERWMO_AENTR3:1:O.0
17 3E4DS0-CO01-EVS-MFD-103030 3E4DS0-CO01-EVS-MFD-103030_OPN_CLS_CMD RELAY MERWMO_AENTR3:1:O.0 .IN SITE ALSO,CABLE IS CONNECTED TO THIS RELAY. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN COMMAND
signal to be confirmed MERWMO 3E4DS0-MER-BMS-RIOP-000024 SDO-1 AENTR3 1 - 2SR1 : 11,14 SDO-16 0 AENTR3:1:O.0 DO O 4/17/2025 DONE

MERWMO_AENTR3:1:O.1
SIGNAL Open MFD-644028 Platform ( EVS_FD_ARR_UDT[17].OPN_CLS_CMD) IS MAPPED TO THIS RELAY
18 SPARE SPARE MERWMO_AENTR3:1:O.1 .IN SITE ALSO,CABLE IS CONNECTED TO THIS RELAY. As per CWG RLM, this channel is used at site, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 SDO-1 AENTR3 1 - 2SR2 : 11,14 SDO-16 1 AENTR3:1:O.1 DO O 4/17/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-MAU-040000 RF RUN FB ( D_MAU_ARR_UDT[1].RF_RUN_FB )IS MAPPED TO THIS CHANNEL
MERWMO_AENTR1:0:I.7
40 SPARE SPARE MERWMO_AENTR1:0:I.7 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DI-1 AENTR1 0 2XDI1 : 15,16 - DI-16 7 AENTR1:0:I.7 DI I 4/17/2025 DONE

MERWMO_AENTR1:0:I.13
46 SPARE SPARE IN LOGIX ALSO,THERE IS NO MAPPING.IN SITE,EXTRA CABLE IS CONNECTED TO THIS TERMINAL. As per CWG RLM, this channel is used at site, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DI-1 AENTR1 0 2XDI1 : 27,28 - DI-16 13 AENTR1:0:I.13 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-MAU-020000_OPN_FB (S_MAU_ARR_UDT[2].OPN_FB) IS MAPPED TO THIS CHANNEL
NON FM200 MFD LOOP MERWMO_AENTR2:0:I.14
63 3E4DS0-MER-HVAC-MAU-020000 3E4DS0-MER-HVAC-MAU-020000_OPN_FB MERWMO_AENTR2:0:I.Data.14 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MERWMO 3E4DS0-MER-BMS-RIOP-000024 DI-2 AENTR2 0 2XDI2 : 29,30 - DI-32 14 AENTR2:0:I.Data.14 DI I 4/17/2025 DONE
MERWMO_AENTR2:0:I.18
67 SPARE SPARE IN LOGIX ALSO,THERE IS NO MAPPING.IN SITE,EXTRA CABLE IS CONNECTED TO THIS TERMINAL. As per CWG RLM, this channel is used at site, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DI-2 AENTR2 0 2XDI2 : 37,38 - DI-32 18 AENTR2:0:I.Data.18 DI I 4/17/2025 DONE

MERWMO_AENTR2:0:I.19
SIGNAL 3E4DS0-MER-ELS-MCC-002005_INC_OPN_CLS_FB (MCC_ICB_ARR_UDT[6].INC_OPN_CLS_FB) IS MAPPED TO
68 3E4DS0-MER-ELS-MCC-002005 3E4DS0-MER-ELS-MCC-002005_INC_OPN_CLS_FB THIS CHANNEL MERWMO_AENTR2:0:I.Data.19 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
INCOMING
signalCIRCUIT
to be confirmed
01 MERWMO 3E4DS0-MER-BMS-RIOP-000024 DI-2 AENTR2 0 2XDI2 : 39,40 - DI-32 19 AENTR2:0:I.Data.19 DI I 4/17/2025 DONE

MERWMO_AENTR2:0:I.22
SIGNAL AHU-6 (S_AHU_ARR_UDT[6].OPN_FB) IS MAPPED TO THIS CHANNEL MERWMO_AENTR2:0:I.Data.22 . IN SITE
71 SPARE SPARE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DI-2 AENTR2 0 2XDI2 : 45,46 - DI-32 22 AENTR2:0:I.Data.22 DI I 4/17/2025 DONE

MERWMO_AENTR2:0:I.23
SIGNAL AHU-7 (S_AHU_ARR_UDT[7].OPN_FB) IS MAPPED TO THIS CHANNEL MERWMO_AENTR2:0:I.Data.23. IN SITE
72 SPARE SPARE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DI-2 AENTR2 0 2XDI2 : 47,48 - DI-32 23 AENTR2:0:I.Data.23 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-AHU-070000_EC_OH_PROT (S_AHU_ARR_UDT[7].EC_OH_PROT) IS MAPPED TO THIS
MERWMO_AENTR1:1:I.5
86 3E4DS0-MER-HVAC-AHU-070000 3E4DS0-MER-HVAC-AHU-070000_EC_OH_PROT CHANNEL MERWMO_AENTR1:1:I.Data.5 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
ELECTRICAL
signalCOIL
to beOVERHEAT
confirmed PROTECTION MERWMO 3E4DS0-MER-BMS-RIOP-000024 DI-3 AENTR1 1 2XDI3 : 11,12 - DI-32 5 AENTR1:1:I.Data.5 DI I 4/17/2025 DONE

SIGNAL 3E4DS0-MER-HVAC-AHU-070000_AIP1_ON (S_AHU_ARR_UDT[7].AIP1_ON) IS MAPPED TO THIS CHANNEL MERWMO_AENTR1:1:I.7


88 3E4DS0-MER-HVAC-AHU-070000 3E4DS0-MER-HVAC-AHU-070000_AIP1_ON MERWMO_AENTR1:1:I.Data.16 IN LOGIX.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is spare at site, please check. ON AIR IONIZER PURIFIER NO. 1 MERWMO 3E4DS0-MER-BMS-RIOP-000024 DI-3 AENTR1 1 2XDI3 : 15,16 - DI-32 7 AENTR1:1:I.Data.7 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-AHU-060000_SS2_REM_FB (S_AHU_ARR_UDT[6].SS2_REM_FB) IS MAPPED TO THIS
MERWMO_AENTR1:1:I.22
103 3E4DS0-MER-HVAC-AHU-060000 3E4DS0-MER-HVAC-AHU-060000_SS2_REM_FB CHANNEL,MERWMO_AENTR1:1:I.Data.22.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. Start Push Button RM relay activated/deactivated Status MERWMO 3E4DS0-MER-BMS-RIOP-000024 DI-3 AENTR1 1 2XDI3 : 45,46 - DI-32 22 AENTR1:1:I.Data.22 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-AHU-070000_SS2_REM_FB (S_AHU_ARR_UDT[7].SS2_REM_FB) IS MAPPED TO THIS
MERWMO_AENTR1:1:I.24
105 3E4DS0-MER-HVAC-AHU-070000 3E4DS0-MER-HVAC-AHU-070000_SS2_REM_FB CHANNEL,MERWMO_AENTR1:1:I.Data.24.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. Start Push Button RM relay activated/deactivated Status MERWMO 3E4DS0-MER-BMS-RIOP-000024 DI-3 AENTR1 1 2XDI3 : 49,50 - DI-32 24 AENTR1:1:I.Data.24 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-MAU-020000_SS2_REM_FB (S_MAU_ARR_UDT[2].SS2_REM_FB) IS MAPPED TO THIS
MERWMO_AENTR1:1:I.26
107 3E4DS0-MER-HVAC-MAU-020000 3E4DS0-MER-HVAC-MAU-020000_SS2_REM_FB CHANNEL,MERWMO_AENTR1:1:I.Data.26.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. Start Push Button RM relay activated/deactivated Status MERWMO 3E4DS0-MER-BMS-RIOP-000024 DI-3 AENTR1 1 2XDI3 : 53,54 - DI-32 26 AENTR1:1:I.Data.26 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-MAU-040000_SS2_REM_FB (D_MAU_ARR_UDT[1].SS2_REM_FB) IS MAPPED TO THIS
MERWMO_AENTR1:1:I.28
109 3E4DS0-MER-HVAC-MAU-040000 3E4DS0-MER-HVAC-MAU-040000_SS2_REM_FB CHANNEL,MERWMO_AENTR1:1:I.Data.28.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. Start Push Button RM relay activated/deactivated Status MERWMO 3E4DS0-MER-BMS-RIOP-000024 DI-3 AENTR1 1 2XDI3 : 57,58 - DI-32 28 AENTR1:1:I.Data.28 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-MVD-063031_OPN_CLS_CMD (MVD_ARR_UDT[5].OPN_CLS_CMD) IS MAPPED TO THIS
MERWMO_AENTR2:4:O.6
119 3E4DS0-MER-HVAC-MVD-063031 3E4DS0-MER-HVAC-MVD-063031_OPN_CLS_CMD RELAY,MERWMO_AENTR2:4:O.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
DAMPERsignal
MVD toOPEN
be confirmed
CLOSE COMMAND MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-1 AENTR2 4 - 2R7 : 11,14 DO-16 6 AENTR2:4:O.6 DO O 4/17/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-MVD-063032_OPN_CLS_CMD (MVD_ARR_UDT[6].OPN_CLS_CMD) IS MAPPED TO THIS
MERWMO_AENTR2:4:O.7
120 3E4DS0-MER-HVAC-MVD-063032 3E4DS0-MER-HVAC-MVD-063032_OPN_CLS_CMD RELAY,MERWMO_AENTR2:4:O.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
DAMPERsignal
MVD toOPEN
be confirmed
CLOSE COMMAND MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-1 AENTR2 4 - 2R8 : 11,14 DO-16 7 AENTR2:4:O.7 DO O 4/17/2025 DONE
SIGNAL 3E4DS0-MER -HVAC-MVD-063033_OPN_CLS_CMD (MVD_ARR_UDT[7].OPN_CLS_CMD) IS MAPPED TO THIS
MERWMO_AENTR2:4:O.8
121 3E4DS0-MER -HVAC-MVD-063033 3E4DS0-MER -HVAC-MVD-063033_OPN_CLS_CMD RELAY,MERWMO_AENTR2:4:O.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
DAMPERsignal
MVD toOPEN
be confirmed
CLOSE COMMAND MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-1 AENTR2 4 - 2R9 : 11,14 DO-16 8 AENTR2:4:O.8 DO O 4/17/2025 DONE
SIGNAL 3E4DS0-MER -HVAC-MVD-063034_OPN_CLS_CMD (MVD_ARR_UDT[8].OPN_CLS_CMD) IS MAPPED TO THIS
MERWMO_AENTR2:4:O.9
122 3E4DS0-MER -HVAC-MVD-063034 3E4DS0-MER -HVAC-MVD-063034_OPN_CLS_CMD RELAY,MERWMO_AENTR2:4:O.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
DAMPERsignal
MVD toOPEN
be confirmed
CLOSE COMMAND MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-1 AENTR2 4 - 2R10 : 11,14 DO-16 9 AENTR2:4:O.9 DO O 4/17/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-MAU-040000_SF_ON_OFF_CMD (D_MAU_ARR_UDT[1].SF_ON_OFF_CMD &
D_MAU_ARR_UDT[1].FIRE_ALM) IS MAPPED TO THIS RELAY,MERWMO_AENTR2:4:O.10.IN SITE ALSO,CABLE IS MERWMO_AENTR2:4:O.10
123 3E4DS0-MER-HVAC-MAU-040000 3E4DS0-MER-HVAC-MAU-040000_SF_ON_OFF_CMD CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Switch signal
On MAU to be
Power
confirmed
Supply MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-1 AENTR2 4 - 2R11 : 11,14 DO-16 10 AENTR2:4:O.10 DO O 4/17/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-AHU-060000_SF_ON_OFF_CMD (S_AHU_ARR_UDT[6].SF_ON_OFF_CMD) IS MAPPED TO
MERWMO_AENTR2:4:O.11
124 3E4DS0-MER-HVAC-AHU-060000 3E4DS0-MER-HVAC-AHU-060000_SF_ON_OFF_CMD THIS RELAY,MERWMO_AENTR2:4:O.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Switch signal
On AHU to be
Power
confirmed
Supply MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-1 AENTR2 4 - 2R12 : 11,14 DO-16 11 AENTR2:4:O.11 DO O 4/17/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-MAU-020000_SF_ON_OFF_CMD (S_MAU_ARR_UDT[2].SF_ON_OFF_CMD) IS MAPPED TO
MERWMO_AENTR2:4:O.12
125 3E4DS0-MER-HVAC-MAU-020000 3E4DS0-MER-HVAC-MAU-020000_SF_ON_OFF_CMD THIS RELAY,MERWMO_AENTR2:4:O.12.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Switch signal
On MAU to be
Power
confirmed
Supply MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-1 AENTR2 4 - 2R13 : 11,14 DO-16 12 AENTR2:4:O.12 DO O 4/17/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-AHU-070000_SF_ON_OFF_CMD (S_AHU_ARR_UDT[7].SF_ON_OFF_CMD) IS MAPPED TO
MERWMO_AENTR2:4:O.13
126 3E4DS0-MER-HVAC-AHU-070000 3E4DS0-MER-HVAC-AHU-070000_SF_ON_OFF_CMD THIS RELAY,MERWMO_AENTR2:4:O.13.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Switch signal
On AHU to be
Power
confirmed
Supply MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-1 AENTR2 4 - 2R14 : 11,14 DO-16 13 AENTR2:4:O.13 DO O 4/17/2025 DONE
THERE IS NO MAPPING TO THIS CHANNEL/RELAY,MERWMO_AENTR1:6:O.0 .IN SITE ALSO,THERE IS NO CABLE
MERWMO_AENTR1:6:O.0
129 SPARE SPARE CONNECTED TO THIS RELAY,MERWMO_AENTR1:6:O.0 As per CWG's RLM comments, DO2 modules is not availale in the panel, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-2 AENTR1 6 - 2R17 : 11,14 DO-16 0 AENTR1:6:O.0 DO O 4/17/2025 DONE
THERE IS NO MAPPING TO THIS CHANNEL/RELAY,MERWMO_AENTR1:6:O.1 .IN SITE ALSO,THERE IS NO CABLE
MERWMO_AENTR1:6:O.1
130 SPARE SPARE CONNECTED TO THIS RELAY,MERWMO_AENTR1:6:O.1 As per CWG's RLM comments, DO2 modules is not availale in the panel, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-2 AENTR1 6 - 2R18 : 11,14 DO-16 1 AENTR1:6:O.1 DO O 4/17/2025 DONE
THERE IS NO MAPPING TO THIS CHANNEL/RELAY,MERWMO_AENTR1:6:O.2 .IN SITE ALSO,THERE IS NO CABLE
MERWMO_AENTR1:6:O.2
131 SPARE SPARE CONNECTED TO THIS RELAY,MERWMO_AENTR1:6:O.2 As per CWG's RLM comments, DO2 modules is not availale in the panel, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-2 AENTR1 6 - 2R19 : 11,14 DO-16 2 AENTR1:6:O.2 DO O 4/17/2025 DONE
THERE IS NO MAPPING TO THIS CHANNEL/RELAY,MERWMO_AENTR1:6:O.3 .IN SITE ALSO,THERE IS NO CABLE
MERWMO_AENTR1:6:O.3
132 SPARE SPARE CONNECTED TO THIS RELAY,MERWMO_AENTR1:6:O.3 As per CWG's RLM comments, DO2 modules is not availale in the panel, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-2 AENTR1 6 - 2R20 : 11,14 DO-16 3 AENTR1:6:O.3 DO O 4/17/2025 DONE
THERE IS NO MAPPING TO THIS CHANNEL/RELAY,MERWMO_AENTR1:6:O.4 .IN SITE ALSO,THERE IS NO CABLE
MERWMO_AENTR1:6:O.4
133 SPARE SPARE CONNECTED TO THIS RELAY,MERWMO_AENTR1:6:O.4 As per CWG's RLM comments, DO2 modules is not availale in the panel, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-2 AENTR1 6 - 2R21 : 11,14 DO-16 4 AENTR1:6:O.4 DO O 4/17/2025 DONE
THERE IS NO MAPPING TO THIS CHANNEL/RELAY,MERWMO_AENTR1:6:O.5 .IN SITE ALSO,THERE IS NO CABLE
MERWMO_AENTR1:6:O.5
134 SPARE SPARE CONNECTED TO THIS RELAY,MERWMO_AENTR1:6:O.5 As per CWG's RLM comments, DO2 modules is not availale in the panel, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-2 AENTR1 6 - 2R22 : 11,14 DO-16 5 AENTR1:6:O.5 DO O 4/17/2025 DONE
THERE IS NO MAPPING TO THIS CHANNEL/RELAY,MERWMO_AENTR1:6:O.6 .IN SITE ALSO,THERE IS NO CABLE
MERWMO_AENTR1:6:O.6
135 SPARE SPARE CONNECTED TO THIS RELAY,MERWMO_AENTR1:6:O.6 As per CWG's RLM comments, DO2 modules is not availale in the panel, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-2 AENTR1 6 - 2R23 : 11,14 DO-16 6 AENTR1:6:O.6 DO O 4/17/2025 DONE
THERE IS NO MAPPING TO THIS CHANNEL/RELAY,MERWMO_AENTR1:6:O.7 .IN SITE ALSO,THERE IS NO CABLE
MERWMO_AENTR1:6:O.7
136 SPARE SPARE CONNECTED TO THIS RELAY,MERWMO_AENTR1:6:O.7 As per CWG's RLM comments, DO2 modules is not availale in the panel, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-2 AENTR1 6 - 2R24 : 11,14 DO-16 7 AENTR1:6:O.7 DO O 4/17/2025 DONE
THERE IS NO MAPPING TO THIS CHANNEL/RELAY,MERWMO_AENTR1:6:O.8 .IN SITE ALSO,THERE IS NO CABLE
MERWMO_AENTR1:6:O.8
137 SPARE SPARE CONNECTED TO THIS RELAY,MERWMO_AENTR1:6:O.8 As per CWG's RLM comments, DO2 modules is not availale in the panel, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-2 AENTR1 6 - 2R25 : 11,14 DO-16 8 AENTR1:6:O.8 DO O 4/17/2025 DONE
THERE IS NO MAPPING TO THIS CHANNEL/RELAY,MERWMO_AENTR1:6:O.9 .IN SITE ALSO,THERE IS NO CABLE
MERWMO_AENTR1:6:O.9
138 SPARE SPARE CONNECTED TO THIS RELAY,MERWMO_AENTR1:6:O.9 As per CWG's RLM comments, DO2 modules is not availale in the panel, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-2 AENTR1 6 - 2R26 : 11,14 DO-16 9 AENTR1:6:O.9 DO O 4/17/2025 DONE
THERE IS NO MAPPING TO THIS CHANNEL/RELAY,MERWMO_AENTR1:6:O.10 .IN SITE ALSO,THERE IS NO CABLE
MERWMO_AENTR1:6:O.10
139 SPARE SPARE CONNECTED TO THIS RELAY,MERWMO_AENTR1:6:O.10 As per CWG's RLM comments, DO2 modules is not availale in the panel, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-2 AENTR1 6 - 2R27 : 11,14 DO-16 10 AENTR1:6:O.10 DO O 4/17/2025 DONE
THERE IS NO MAPPING TO THIS CHANNEL/RELAY,MERWMO_AENTR1:6:O.11 .IN SITE ALSO,THERE IS NO CABLE
MERWMO_AENTR1:6:O.11
140 SPARE SPARE CONNECTED TO THIS RELAY,MERWMO_AENTR1:6:O.11 As per CWG's RLM comments, DO2 modules is not availale in the panel, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-2 AENTR1 6 - 2R28 : 11,14 DO-16 11 AENTR1:6:O.11 DO O 4/17/2025 DONE
THERE IS NO MAPPING TO THIS CHANNEL/RELAY,MERWMO_AENTR1:6:O.12 .IN SITE ALSO,THERE IS NO CABLE
MERWMO_AENTR1:6:O.12
141 SPARE SPARE CONNECTED TO THIS RELAY,MERWMO_AENTR1:6:O.12 As per CWG's RLM comments, DO2 modules is not availale in the panel, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-2 AENTR1 6 - 2R29 : 11,14 DO-16 12 AENTR1:6:O.12 DO O 4/17/2025 DONE
THERE IS NO MAPPING TO THIS CHANNEL/RELAY,MERWMO_AENTR1:6:O.13 .IN SITE ALSO,THERE IS NO CABLE
MERWMO_AENTR1:6:O.13
142 SPARE SPARE CONNECTED TO THIS RELAY,MERWMO_AENTR1:6:O.13 As per CWG's RLM comments, DO2 modules is not availale in the panel, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-2 AENTR1 6 - 2R30 : 11,14 DO-16 13 AENTR1:6:O.13 DO O 4/17/2025 DONE
THERE IS NO MAPPING TO THIS CHANNEL/RELAY,MERWMO_AENTR1:6:O.14 .IN SITE ALSO,THERE IS NO CABLE
MERWMO_AENTR1:6:O.14
143 SPARE SPARE CONNECTED TO THIS RELAY,MERWMO_AENTR1:6:O.14 As per CWG's RLM comments, DO2 modules is not availale in the panel, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-2 AENTR1 6 - 2R31 : 11,14 DO-16 14 AENTR1:6:O.14 DO O 4/17/2025 DONE
THERE IS NO MAPPING TO THIS CHANNEL/RELAY,MERWMO_AENTR1:6:O.15 .IN SITE ALSO,THERE IS NO CABLE
MERWMO_AENTR1:6:O.15
144 SPARE SPARE CONNECTED TO THIS RELAY,MERWMO_AENTR1:6:O.15 As per CWG's RLM comments, DO2 modules is not availale in the panel, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 DO-2 AENTR1 6 - 2R32 : 11,14 DO-16 15 AENTR1:6:O.15 DO O 4/17/2025 DONE

MERWMO_AENTR2:1:Chdata.3
SIGNAL 3E4DS0-MER-HVAC-MAUMAD-040000_MA_DAMP_POS (D_MAU_ARR_UDT[1].MA_DAMP_POS) IS MAPPED TO
156 3E4DS0-MER-HVAC-MAUMAD-040000 3E4DS0-MER-HVAC-MAUMAD-040000_MA_DAMP_POS THIS CHANNEL MERWMO_AENTR2:1:I.Ch3Data .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MIX AIR
signal
MVDtoPOSITION
be confirmed MERWMO 3E4DS0-MER-BMS-RIOP-000024 AI-2 AENTR2 1 2XAI2 : 7,8 - AI-08 3 AENTR2:1:I.Ch3Data AI Chdata 4/17/2025 DONE

SIGNAL 3E4DS0-MER-HVAC-MAUMAD-040000_MA_DAMP_POS_CMD(D_MAU_ARR_UDT[1].MA_DAMP_POS_CMD) IS MERWMO_AENTR1:5:O.8


205 3E4DS0-MER-HVAC-MAUMAD-040000 3E4DS0-MER-HVAC-MAUMAD-040000_MA_DAMP_POS_CMD MAPPED TO THIS CHANNEL MERWMO_AENTR1:5:O.Ch8Data.IN SITE ALSO CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MIX AIR
signal
MVDtoCONTROL
be confirmed MERWMO 3E4DS0-MER-BMS-RIOP-000024 AO-2 AENTR1 5 2XAO2 : 17,18 - AO-12 8 AENTR1:5:O.Ch8Data AO O 4/17/2025 DONE
IN LOGIX ALSO,HARDWARE CONFIGURATION IS NOT THERE.IN LOGIX ALSO,THERE IS NO MAPPING.IN SITE,ALSO THERE
MERWMO_AENTR3:2:O.0
209 SPARE SPARE IS NO CABLE, CONNECTED TO THIS TERMINAL. As per CWG's RLM comments, AO3 modules is not availale in the panel, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 AO-3 AENTR3 2 2XAO3 : 1,2 AO-04 0 AENTR3:2:O.Ch0Data O 4/17/2025 DONE
IN LOGIX ALSO,HARDWARE CONFIGURATION IS NOT THERE.IN LOGIX ALSO,THERE IS NO MAPPING.IN SITE,ALSO THERE
MERWMO_AENTR3:2:O.1
210 SPARE SPARE IS NO CABLE, CONNECTED TO THIS TERMINAL. As per CWG's RLM comments, AO3 modules is not availale in the panel, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 AO-3 AENTR3 2 2XAO3 : 3,4 AO-04 1 AENTR3:2:O.Ch1Data O 4/17/2025 DONE
IN LOGIX ALSO,HARDWARE CONFIGURATION IS NOT THERE.IN LOGIX ALSO,THERE IS NO MAPPING.IN SITE,ALSO THERE
MERWMO_AENTR3:2:O.2
211 SPARE SPARE IS NO CABLE, CONNECTED TO THIS TERMINAL. As per CWG's RLM comments, AO3 modules is not availale in the panel, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 AO-3 AENTR3 2 2XAO3 : 5,6 AO-04 2 AENTR3:2:O.Ch2Data O 4/17/2025 DONE
IN LOGIX ALSO,HARDWARE CONFIGURATION IS NOT THERE.IN LOGIX ALSO,THERE IS NO MAPPING.IN SITE,ALSO THERE
MERWMO_AENTR3:2:O.3
212 SPARE SPARE IS NO CABLE, CONNECTED TO THIS TERMINAL. As per CWG's RLM comments, AO3 modules is not availale in the panel, please check. SPARE MERWMO 3E4DS0-MER-BMS-RIOP-000024 AO-3 AENTR3 2 2XAO3 : 7,8 AO-04 3 AENTR3:2:O.Ch3Data O 4/17/2025 DONE
SIGNAL 3E4DS0-SE-EVS-SE-090000_TRIP_FB (SEF_ARR_UDT[11].TRIP_FB) IS MAPPED TO THIS
MERWTO_AENTR2:0:I.0
1 3E4DS0-SE-EVS-SE-090000 3E4DS0-SE-EVS-SE-090000_TRIP_FB CHANNEL,MERWTO_AENTR2:0:I.0 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
SMOKE
be confirmed
EXHAUST FAN MERWTO 3E4DS0-MER-BMS-RIOP-000018 SDI-1 AENTR2 0 1XSDI1 : 1,2 - SDI-16 0 AENTR2:0:I.0 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-SE-EVS-SE-090000_LOC_FB (SEF_ARR_UDT[11].LOC_FB) IS MAPPED TO THIS
MERWTO_AENTR2:0:I.1
2 3E4DS0-SE-EVS-SE-090000 3E4DS0-SE-EVS-SE-090000_LOC_FB CHANNEL,MERWTO_AENTR2:0:I.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalSMOKE
to be confirmed
EXHAUST FAN MERWTO 3E4DS0-MER-BMS-RIOP-000018 SDI-1 AENTR2 0 1XSDI1 : 3,4 - SDI-16 1 AENTR2:0:I.1 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-SE-EVS-SE-090000_REM_FB (SEF_ARR_UDT[11].REM_FB) IS MAPPED TO THIS
MERWTO_AENTR2:0:I.2
3 3E4DS0-SE-EVS-SE-090000 3E4DS0-SE-EVS-SE-090000_REM_FB CHANNEL,MERWTO_AENTR2:0:I.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalSMOKE
to be confirmed
EXHAUST FAN MERWTO 3E4DS0-MER-BMS-RIOP-000018 SDI-1 AENTR2 0 1XSDI1 : 5,6 - SDI-16 2 AENTR2:0:I.2 DI I 4/17/2025 DONE

# General
PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM

DOCUMENT TITLE SHOP DRAWING-DEEP UNDERGROUND STATION-3E4-BMS-INPUT/OUTPUT SCHEDULE

DOCUMENT NO. M-ANM-3E4DS0-CJ00-SCH-000002

MODULE RELAY MODULE CHANNE


SR. NO. EQUIPMENT TAG PLC TAG EASA SITE Response RLM COMMENTS FROM CWG DESCRIPTION PANEL SHORT TAG (OLD) PANEL FULL TAG (NEW) RACK NO. SLOT NO. TERMINAL NO. PLC IO ADDRESS MODULE ID DATE STATUS
ID NO. TYPE L NO.
SIGNAL 3E4DS0-SE-EVS-SE-090000_RUN_FB (SEF_ARR_UDT[11].RUN_FB) IS MAPPED TO THIS
MERWTO_AENTR2:0:I.3
4 3E4DS0-SE-EVS-SE-090000 3E4DS0-SE-EVS-SE-090000_RUN_FB CHANNEL,MERWTO_AENTR2:0:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
RUNNING
signal
OFtoSMOKE
be confirmed
EXHAUST FAN MERWTO 3E4DS0-MER-BMS-RIOP-000018 SDI-1 AENTR2 0 1XSDI1 : 7,8 - SDI-16 3 AENTR2:0:I.3 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-SE-EVS-SEDPS-090001_DPS_FB (SEF_ARR_UDT[11].DPS_FB) IS MAPPED TO THIS
MERWTO_AENTR2:0:I.6
7 3E4DS0-SE-EVS-SEDPS-090001 3E4DS0-SE-EVS-SEDPS-090001_DPS_FB CHANNEL,MERWTO_AENTR2:0:I.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
SMOKEsignal
EXHAUST
to beFAN
confirmed
PROOF OF FLOW MERWTO 3E4DS0-MER-BMS-RIOP-000018 SDI-1 AENTR2 0 1XSDI1 : 13,14 - SDI-16 6 AENTR2:0:I.6 DI I 4/17/2025 DONE

[FACP-1] Smoke Detectors/Manual station - Technical


SIGNAL 3E4DS0-FCC-FDPS-FACP-100004_FACP1_SMOKE_DETECTOR.9 (FACP_ARR_UDT[1].FACP1_SMOKE_DETECTOR.9)
3E4DS0-FCC-FDPS-FACP-100004 3E4DS0-FCC-FDPS-FACP-100004_FACP1_SMOKE_DETECTOR.9 (BOH and Not FM-200 rooms and Not SE and MERWTO SDI-1 AENTR2 0 1XSDI1 : 15,16 - SDI-16 7 MERWTO_AENTR2:0:I.7
IS MAPPED TO THIS CHANNEL,MERWTO_AENTR2:0:I.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
TVR,OTE/UPE Rooms)
8 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed 3E4DS0-MER-BMS-RIOP-000018 AENTR2:0:I.7 DI I 4/17/2025 DONE

SIGNAL 3E4DS0-FCC-FDPS-FACP-100004_FACP1_SMOKE_DETECTOR.8 (FACP_ARR_UDT[1].FACP1_SMOKE_DETECTOR.8) MERWTO_AENTR2:0:I.8


9 3E4DS0-FCC-FDPS-FACP-100004 3E4DS0-FCC-FDPS-FACP-100004_FACP1_SMOKE_DETECTOR.8 IS MAPPED TO THIS CHANNEL,MERWTO_AENTR2:0:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
[FACP-1]
signal
Smoke
to be
Detectors
confirmed
- Technical (SE Rooms and TVR,OTE/UPE Rooms) MERWTO 3E4DS0-MER-BMS-RIOP-000018 SDI-1 AENTR2 0 1XSDI1 : 17,18 - SDI-16 8 AENTR2:0:I.8 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-CO01-EVS-MFD-102027_OPN_FB (EVS_FD_ARR_UDT[3].OPN_FB) IS MAPPED TO THIS
MERWTO_AENTR2:0:I.9
10 3E4DS0-CO01-EVS-MFD-102027 3E4DS0-CO01-EVS-MFD-102027_OPN_FB CHANNEL,MERWTO_AENTR2:0:I.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed MERWTO 3E4DS0-MER-BMS-RIOP-000018 SDI-1 AENTR2 0 1XSDI1 : 19,20 - SDI-16 9 AENTR2:0:I.9 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-CO01-EVS-MFD-102027_CLS_FB_DOOR1 (EVS_FD_ARR_UDT[3].CLS_FB_DOOR1) IS MAPPED TO THIS
MERWTO_AENTR2:0:I.10
11 3E4DS0-CO01-EVS-MFD-102027 3E4DS0-CO01-EVS-MFD-102027_CLS_FB_DOOR1 CHANNEL,MERWTO_AENTR2:0:I.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
DOOR signal
CLOSEto
STATUS
be confirmed
-1 MERWTO 3E4DS0-MER-BMS-RIOP-000018 SDI-1 AENTR2 0 1XSDI1 : 21,22 - SDI-16 10 AENTR2:0:I.10 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-CO01-EVS-MFD-102027_CLS_FB_DOOR2 (EVS_FD_ARR_UDT[3].CLS_FB_DOOR2) IS MAPPED TO THIS
MERWTO_AENTR2:0:I.11
12 3E4DS0-CO01-EVS-MFD-102027 3E4DS0-CO01-EVS-MFD-102027_CLS_FB_DOOR2 CHANNEL,MERWTO_AENTR2:0:I.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
DOOR signal
CLOSEto
STATUS
be confirmed
-2 MERWTO 3E4DS0-MER-BMS-RIOP-000018 SDI-1 AENTR2 0 1XSDI1 : 23,24 - SDI-16 11 AENTR2:0:I.11 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-SE-EVS-SE-090000_ON_OFF_CMD (SEF_ARR_UDT[11].ON_OFF_CMD) IS MAPPED TO THIS RELAY
MERWTO_AENTR2:1:O.0
17 3E4DS0-SE-EVS-SE-090000 3E4DS0-SE-EVS-SE-090000_ON_OFF_CMD MERWTO_AENTR2:1:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
SMOKE
be confirmed
EXHAUST FAN MERWTO 3E4DS0-MER-BMS-RIOP-000018 SDO-1 AENTR2 1 - 1SR1 : 11,14 SDO-16 0 AENTR2:1:O.0 DO O 4/17/2025 DONE

SIGNAL 3E4DS0-CO01-EVS-MFD-102027_OPN_CMD (EVS_FD_ARR_UDT[3].OPN_CLS_CMD) IS MAPPED TO THIS RELAY MERWTO_AENTR2:1:O.4


21 3E4DS0-CO01-EVS-MFD-102027 3E4DS0-CO01-EVS-MFD-102027_OPN_CMD MERWTO_AENTR2:1:O.4 .IN SITE ALSO CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
DAMPERsignal
OPEN/CLOSE
to be confirmed
COMMAND MERWTO 3E4DS0-MER-BMS-RIOP-000018 SDO-1 AENTR2 1 - 1SR5 : 11,14 SDO-16 4 AENTR2:1:O.4 DO O 4/17/2025 DONE

SIGNAL 3E4DS0-MER-HVAC-AHU-030000_SF_TRIP (S_AHU_ARR_UDT[3].SF_TRIP) IS MAPPED TO THIS MERWTO_AENTR1:0:I.0


33 3E4DS0-MER-HVAC-AHU-030000 3E4DS0-MER-HVAC-AHU-030000_SF_TRIP CHANNEL,MERWTO_AENTR1:0:I.Data.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
SUPPLY
be confirmed
FAN MERWTO 3E4DS0-MER-BMS-RIOP-000018 DI-1 AENTR1 0 1XDI1 : 1,2 - DI-32 0 AENTR1:0:I.Data.0 DI I 4/17/2025 DONE

SIGNAL 3E4DS0-MER-HVAC-AHU-030000_SF_LOC (S_AHU_ARR_UDT[3].SF_LOC) IS MAPPED TO THIS MERWTO_AENTR1:0:I.1


34 3E4DS0-MER-HVAC-AHU-030000 3E4DS0-MER-HVAC-AHU-030000_SF_LOC CHANNEL,MERWTO_AENTR1:0:I.Data.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalSWITCH
to be confirmed
SUPPLY FAN MERWTO 3E4DS0-MER-BMS-RIOP-000018 DI-1 AENTR1 0 1XDI1 : 3,4 - DI-32 1 AENTR1:0:I.Data.1 DI I 4/17/2025 DONE

SIGNAL 3E4DS0-MER-HVAC-AHU-030000_SF_REM (S_AHU_ARR_UDT[3].SF_REM) IS MAPPED TO THIS MERWTO_AENTR1:0:I.2


35 3E4DS0-MER-HVAC-AHU-030000 3E4DS0-MER-HVAC-AHU-030000_SF_REM CHANNEL,MERWTO_AENTR1:0:I.Data.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalSWITCH
to be confirmed
SUPPLY FAN MERWTO 3E4DS0-MER-BMS-RIOP-000018 DI-1 AENTR1 0 1XDI1 : 5,6 - DI-32 2 AENTR1:0:I.Data.2 DI I 4/17/2025 DONE

SIGNAL 3E4DS0-MER-HVAC-AHU-030000_SF_RUN_FB (S_AHU_ARR_UDT[3].SF_RUN_FB) IS MAPPED TO THIS MERWTO_AENTR1:0:I.3


36 3E4DS0-MER-HVAC-AHU-030000 3E4DS0-MER-HVAC-AHU-030000_SF_RUN_FB CHANNEL,MERWTO_AENTR1:0:I.Data.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AHU Power
signalSupply
to be confirmed
On/Off Status MERWTO 3E4DS0-MER-BMS-RIOP-000018 DI-1 AENTR1 0 1XDI1 : 7,8 - DI-32 3 AENTR1:0:I.Data.3 DI I 4/17/2025 DONE

SIGNAL 3E4DS0-MER-HVAC-AHU-030000_EC_TRIP (S_AHU_ARR_UDT[3].EC_TRIP) IS MAPPED TO THIS MERWTO_AENTR1:0:I.4


37 3E4DS0-MER-HVAC-AHU-030000 3E4DS0-MER-HVAC-AHU-030000_EC_TRIP CHANNEL,MERWTO_AENTR1:0:I.Data.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
ELECTRICAL
signalCOIL
to beTRIP
confirmed
STATUS MERWTO 3E4DS0-MER-BMS-RIOP-000018 DI-1 AENTR1 0 1XDI1 : 9,10 - DI-32 4 AENTR1:0:I.Data.4 DI I 4/17/2025 DONE

SIGNAL 3E4DS0-MER-HVAC-AHU-030000_EC_ON (S_AHU_ARR_UDT[3].EC_ON) IS MAPPED TO THIS MERWTO_AENTR1:0:I.6


39 3E4DS0-MER-HVAC-AHU-030000 3E4DS0-MER-HVAC-AHU-030000_EC_ON CHANNEL,MERWTO_AENTR1:0:I.Data.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
ON ELECTRICAL
signal to be
COIL
confirmed MERWTO 3E4DS0-MER-BMS-RIOP-000018 DI-1 AENTR1 0 1XDI1 : 13,14 - DI-32 6 AENTR1:0:I.Data.6 DI I 4/17/2025 DONE

SIGNAL 3E4DS0-MER-HVAC-AHU-030000_OPN_FB (S_AHU_ARR_UDT[3].OPN_FB) IS MAPPED TO THIS MOTORIZED FIRE DAMPERS NON FM200 MERWTO_AENTR1:0:I.14
47 3E4DS0-MER-HVAC-AHU-030000 3E4DS0-MER-HVAC-AHU-030000_OPN_FB CHANNEL,MERWTO_AENTR1:0:I.Data.14.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MERWTO 3E4DS0-MER-BMS-RIOP-000018 DI-1 AENTR1 0 1XDI1 : 29,30 - DI-32 14 AENTR1:0:I.Data.14 DI I 4/17/2025 DONE

MERWTO_AENTR1:0:I.17
SIGNAL 3E4DS0-MER-HVAC-AHU-030000_SS2_LOC_FB (S_AHU_ARR_UDT[3].SS2_LOC_FB) IS MAPPED TO THIS
50 3E4DS0-MER-HVAC-AHU-030000 3E4DS0-MER-HVAC-AHU-030000_SS2_LOC_FB CHANNEL,MERWTO_AENTR1:0:I.Data.17.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Manual/Local
signal toBMS
be confirmed
Selector Switch (SS2) Status MERWTO 3E4DS0-MER-BMS-RIOP-000018 DI-1 AENTR1 0 1XDI1 : 35,36 - DI-32 17 AENTR1:0:I.Data.17 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-AHU-030000_SS2_REM_FB (S_AHU_ARR_UDT[3].SS2_REM_FB) IS MAPPED TO THIS
CHANNEL,MERWTO_AENTR1:0:I.Data.18,in logix only.IN SITE,SINCE THERE IS NO SIGNAL PROVISION.THERE IS NO CABLE MERWTO_AENTR1:0:I.18
51 3E4DS0-MER-HVAC-AHU-030000 3E4DS0-MER-HVAC-AHU-030000_SS2_REM_FB CONNECTED TO THIS CHANNEL. As per CWG RLM, this channel is spare at site, please check. Start Push Button RM relay activated/deactivated Status MERWTO 3E4DS0-MER-BMS-RIOP-000018 DI-1 AENTR1 0 1XDI1 : 37,38 - DI-32 18 AENTR1:0:I.Data.18 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-AHU-030000_EC_ON_CMD (S_AHU_ARR_UDT[3].EC_ON_CMD) IS MAPPED TO THIS
MERWTO_AENTR1:4:O.0
93 3E4DS0-MER-HVAC-AHU-030000 3E4DS0-MER-HVAC-AHU-030000_EC_ON_CMD RELAY,MERWTO_AENTR1:4:O.0 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
SWITCH signal
ON ELECTRICAL
to be confirmed
COIL MERWTO 3E4DS0-MER-BMS-RIOP-000018 DO-1 AENTR1 4 - 1R1 : 11,14 DO-16 0 AENTR1:4:O.0 DO O 4/17/2025 DONE

SIGNAL 3E4DS0-MER-HVAC-AHU-030000_SF_ON_OFF_CMD (S_AHU_ARR_UDT[3].SF_ON_OFF_CMD) IS MAPPED TO MERWTO_AENTR1:4:O.2


95 3E4DS0-MER-HVAC-AHU-030000 3E4DS0-MER-HVAC-AHU-030000_SF_ON_OFF_CMD THIS RELAY,MERWTO_AENTR1:4:O.2 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Switch signal
On AHU to be
Power
confirmed
Supply MERWTO 3E4DS0-MER-BMS-RIOP-000018 DO-1 AENTR1 4 - 1R3 : 11,14 DO-16 2 AENTR1:4:O.2 DO O 4/17/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL ,MMERWTO_AENTR1:5:I.3 .IN SITE ALSO,NO CABLE CONNECTED TO
IT.
MERWTO_AENTR1:5:I.3
SIGNAL 3E4DS0-ELE-HVAC-MFD-012118_OPN_FB (HVAC_FD_ARR_UDT[9].OPN_FB) ,IS MAPPED TO THIS
112 3E4DS0-ELE-HVAC-MFD-012118 3E4DS0-ELE-HVAC-MFD-012118_OPN_FB CHANNEL,MERETO_AENTR2:0:I.Data.18 IN LOGIX.IN SITE ALSO,CABLE IS CONNECTED TO THIS TERMINAL. As per CWG RLM, this channel is spare at site, please check. MOTORIZED FIRE DAMPER FM200 OPEN MERWTO 3E4DS0-MER-BMS-RIOP-000018 DI-2 AENTR1 5 1XDI2 : 7,8 - DI-16 3 AENTR1:5:I.3 DI I 4/17/2025 DONE
SIGNAL IS THERE, IT IS NOT SPARE.SIGNAL MUF-040000_TRIP_FB (MUF_ARR_UDT[4].TRIP_FB) IS MAPPED TO THIS
MU1AECO_AENTR2:0:I.0
1 SPARE SPARE CHANNEL,MU1AECO_AENTR2:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-1 AENTR2 0 1XSDI1 : 1,2 - SDI-16 0 AENTR2:0:I.0 DI I 4/17/2025 DONE
SIGNAL IS THERE, IT IS NOT SPARE.SIGNAL MUF-040000_LOC_FB (MUF_ARR_UDT[4].LOC_FB) IS MAPPED TO THIS
MU1AECO_AENTR2:0:I.1
2 SPARE SPARE CHANNEL,MU1AECO_AENTR2:0:I.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-1 AENTR2 0 1XSDI1 : 3,4 - SDI-16 1 AENTR2:0:I.1 DI I 4/17/2025 DONE
SIGNAL IS THERE, IT IS NOT SPARE.SIGNAL MUF-040000_REM_FB (MUF_ARR_UDT[4].REM_FB) IS MAPPED TO THIS
MU1AECO_AENTR2:0:I.2
3 SPARE SPARE CHANNEL,MU1AECO_AENTR2:0:I.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-1 AENTR2 0 1XSDI1 : 5,6 - SDI-16 2 AENTR2:0:I.2 DI I 4/17/2025 DONE
SIGNAL IS THERE, IT IS NOT SPARE.SIGNAL MUF-040000_RUN_FB (MUF_ARR_UDT[4].RUN_FB) IS MAPPED TO THIS
MU1AECO_AENTR2:0:I.3
4 SPARE SPARE CHANNEL,MU1AECO_AENTR2:0:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-1 AENTR2 0 1XSDI1 : 7,8 - SDI-16 3 AENTR2:0:I.3 DI I 4/17/2025 DONE
SIGNAL IS THERE, IT IS NOT SPARE.SIGNAL MUF-040000_DPS_FB (MUF_ARR_UDT[4].DPS_FB) IS MAPPED TO THIS
MU1AECO_AENTR2:0:I.4
5 SPARE SPARE CHANNEL,MU1AECO_AENTR2:0:I.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-1 AENTR2 0 1XSDI1 : 9,10 - SDI-16 4 AENTR2:0:I.4 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MU1B-EVS-MUF-030000_TRIP_FB (MUF_ARR_UDT[3].TRIP_FB) IS MAPPED TO THIS
MU1AECO_AENTR2:0:I.5
6 3E4DS0-MU1B-EVS-MUF-030000 3E4DS0-MU1B-EVS-MUF-030000_TRIP_FB CHANNEL,MU1AECO_AENTR2:0:I.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
MAKE-UP
be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-1 AENTR2 0 1XSDI1 : 11,12 - SDI-16 5 AENTR2:0:I.5 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MU1B-EVS-MUF-030000_LOC_FB (MUF_ARR_UDT[3].LOC_FB) IS MAPPED TO THIS
MU1AECO_AENTR2:0:I.6
7 3E4DS0-MU1B-EVS-MUF-030000 3E4DS0-MU1B-EVS-MUF-030000_LOC_FB CHANNEL,MU1AECO_AENTR2:0:I.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalMAKE-UP
to be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-1 AENTR2 0 1XSDI1 : 13,14 - SDI-16 6 AENTR2:0:I.6 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MU1B-EVS-MUF-030000_REM_FB (MUF_ARR_UDT[3].REM_FB) IS MAPPED TO THIS
MU1AECO_AENTR2:0:I.7
8 3E4DS0-MU1B-EVS-MUF-030000 3E4DS0-MU1B-EVS-MUF-030000_REM_FB CHANNEL,MU1AECO_AENTR2:0:I.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalMAKE-UP
to be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-1 AENTR2 0 1XSDI1 : 15,16 - SDI-16 7 AENTR2:0:I.7 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MU1B-EVS-MUF-030000_RUN_FB (MUF_ARR_UDT[3].RUN_FB) IS MAPPED TO THIS
MU1AECO_AENTR2:0:I.8
9 3E4DS0-MU1B-EVS-MUF-030000 3E4DS0-MU1B-EVS-MUF-030000_RUN_FB CHANNEL,MU1AECO_AENTR2:0:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
RUNNING
signal
OFtoMAKE-UP
be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-1 AENTR2 0 1XSDI1 : 17,18 - SDI-16 8 AENTR2:0:I.8 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MU1B-EVS-MUFDPS-030001_DPS_FB (MUF_ARR_UDT[3].DPS_FB) IS MAPPED TO THIS
MU1AECO_AENTR2:0:I.9
10 3E4DS0-MU1B-EVS-MUFDPS-030001 3E4DS0-MU1B-EVS-MUFDPS-030001_DPS_FB CHANNEL,MU1AECO_AENTR2:0:I.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MAKE-UP
signal
FANtoPROOF
be confirmed
OF FLOW MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-1 AENTR2 0 1XSDI1 : 19,20 - SDI-16 9 AENTR2:0:I.9 DI I 4/17/2025 DONE
3E4DS0-MU1B-EVS-SPR-030000
IN LOGIX THERE IS NO MAPPING TO THIS CHANNEL.IN SITE ALSO,THERE IS NO CABLE CONNECTED TO THIS CHANNEL.
3E4DS0-MU1B-EVS-SPR-030000_TRIP_FB SIGNAL, 3E4DS0-MU1B-EVS-SPR-030000_TRIP_FB (SPR_ARR_UDT[3].TRIP_FB) IS MAPPED TO THIS As per CWG RLM, this channel is spare at site, please check. DI MU1AECO_AENTR2:0:I.10
CHANNEL,MU1AECO_AENTR3:0:I.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
11 TRIP STATUS ELEVATOR PRESSURIZATION FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-1 AENTR2 0 1XSDI1 : 21,22 - SDI-16 10 AENTR2:0:I.10 I 4/17/2025 DONE
3E4DS0-MU1B-EVS-SPR-030000
IN LOGIX THERE IS NO MAPPING TO THIS CHANNEL.IN SITE ALSO,THERE IS NO CABLE CONNECTED TO THIS CHANNEL.
3E4DS0-MU1B-EVS-SPR-030000_LOC_FB SIGNAL, 3E4DS0-MU1B-EVS-SPR-030000_LOC_FB (SPR_ARR_UDT[3].LOC_FB) IS MAPPED TO THIS As per CWG RLM, this channel is spare at site, please check. DI MU1AECO_AENTR2:0:I.11
CHANNEL,MU1AECO_AENTR3:0:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
12 HAND/OFF ELEVATOR PRESSURIZATION FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-1 AENTR2 0 1XSDI1 : 23,24 - SDI-16 11 AENTR2:0:I.11 I 4/17/2025 DONE
3E4DS0-MU1B-EVS-SPR-030000
IN LOGIX THERE IS NO MAPPING TO THIS CHANNEL.IN SITE ALSO,THERE IS NO CABLE CONNECTED TO THIS CHANNEL.
3E4DS0-MU1B-EVS-SPR-030000_REM_FB SIGNAL, 3E4DS0-MU1B-EVS-SPR-030000_REM_FB (SPR_ARR_UDT[3].REM_FB) IS MAPPED TO THIS As per CWG RLM, this channel is spare at site, please check. DI MU1AECO_AENTR2:0:I.12
CHANNEL,MU1AECO_AENTR3:0:I.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
13 AUTO/OFF ELEVATOR PRESSURIZATION FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-1 AENTR2 0 1XSDI1 : 25,26 - SDI-16 12 AENTR2:0:I.12 I 4/17/2025 DONE
3E4DS0-MU1B-EVS-SPR-030000
IN LOGIX THERE IS NO MAPPING TO THIS CHANNEL.IN SITE ALSO,THERE IS NO CABLE CONNECTED TO THIS CHANNEL.
3E4DS0-MU1B-EVS-SPR-030000_RUN_FB SIGNAL, 3E4DS0-MU1B-EVS-SPR-030000_RUN_FB (SPR_ARR_UDT[3].RUN_FB) IS MAPPED TO THIS As per CWG RLM, this channel is spare at site, please check. DI MU1AECO_AENTR2:0:I.13
CHANNEL,MU1AECO_AENTR3:0:I.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
14 RUNNING OF ELEVATOR PRESSURIZATION FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-1 AENTR2 0 1XSDI1 : 27,28 - SDI-16 13 AENTR2:0:I.13 I 4/17/2025 DONE
3E4DS0-MU1B-EVS-SPRDPS-030001

IN LOGIX THERE IS NO MAPPING TO THIS CHANNEL.IN SITE ALSO,THERE IS NO CABLE CONNECTED TO THIS CHANNEL.
3E4DS0-MU1B-EVS-SPRDPS-030001_DPS_FB SIGNAL, 3E4DS0-MU1B-EVS-SPRDPS-030001_DPS_FB (SPR_ARR_UDT[3].DPS_FB) IS MAPPED TO THIS As per CWG RLM, this channel is spare at site, please check. DI MU1AECO_AENTR2:0:I.14
CHANNEL,MU1AECO_AENTR3:0:I.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.

15 ELEVATOR PRESSURIZATION FAN PROOF OF FLOW MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-1 AENTR2 0 1XSDI1 : 29,30 - SDI-16 14 AENTR2:0:I.14 I 4/17/2025 DONE
3E4DS0-MU1A-EVS-SPR-040000
SIGNAL, 3E4DS0-MU1A-EVS-SPR-040000_TRIP_FB (SPR_ARR_UDT[4].TRIP_FB) IS MAPPED TO THIS
3E4DS0-MU1A-EVS-SPR-040000_TRIP_FB DI MU1AECO_AENTR3:0:I.0
CHANNEL,MU1AECO_AENTR3:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
17 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
ELEVATOR
be confirmed
PRESSURIZATION FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-2 AENTR3 0 1XDI2 : 1,2 - SDI-16 0 AENTR3:0:I.0 I 4/17/2025 DONE
3E4DS0-MU1A-EVS-SPR-040000
SIGNAL, 3E4DS0-MU1A-EVS-SPR-040000_LOC_FB (SPR_ARR_UDT[4].LOC_FB) IS MAPPED TO THIS
3E4DS0-MU1A-EVS-SPR-040000_LOC_FB DI MU1AECO_AENTR3:0:I.1
CHANNEL,MU1AECO_AENTR3:0:I.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
18 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalELEVATOR
to be confirmed
PRESSURIZATION FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-2 AENTR3 0 1XDI2 : 3,4 - SDI-16 1 AENTR3:0:I.1 I 4/17/2025 DONE
3E4DS0-MU1A-EVS-SPR-040000
SIGNAL, 3E4DS0-MU1A-EVS-SPR-040000_REM_FB (SPR_ARR_UDT[4].REM_FB) IS MAPPED TO THIS
3E4DS0-MU1A-EVS-SPR-040000_REM_FB DI MU1AECO_AENTR3:0:I.2
CHANNEL,MU1AECO_AENTR3:0:I.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
19 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalELEVATOR
to be confirmed
PRESSURIZATION FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-2 AENTR3 0 1XDI2 : 5,6 - SDI-16 2 AENTR3:0:I.2 I 4/17/2025 DONE
3E4DS0-MU1A-EVS-SPR-040000
SIGNAL, 3E4DS0-MU1A-EVS-SPR-040000_RUN_FB (SPR_ARR_UDT[4].RUN_FB) IS MAPPED TO THIS
3E4DS0-MU1A-EVS-SPR-040000_RUN_FB DI MU1AECO_AENTR3:0:I.3
CHANNEL,MU1AECO_AENTR3:0:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
20 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
RUNNING
signal
OFtoELEVATOR
be confirmed
PRESSURIZATION FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-2 AENTR3 0 1XDI2 : 7,8 - SDI-16 3 AENTR3:0:I.3 I 4/17/2025 DONE
3E4DS0-MU1A-EVS-MUF-040000
SIGNAL, 3E4DS0-MU1A-EVS-MUF-040000_TRIP_FB (SPR_ARR_UDT[3].TRIP_FB) IS MAPPED TO THIS
3E4DS0-MU1A-EVS-MUF-040000_TRIP_FB DI MU1AECO_AENTR3:0:I.5
CHANNEL,MU1AECO_AENTR3:0:I.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
22 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
MAKE-UP
be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-2 AENTR3 0 1XDI2 : 11,12 - SDI-16 5 AENTR3:0:I.5 I 4/17/2025 DONE
3E4DS0-MU1A-EVS-MUF-040000
SIGNAL, 3E4DS0-MU1A-EVS-MUF-040000_LOC_FB (SPR_ARR_UDT[3].REM_FB) IS MAPPED TO THIS
3E4DS0-MU1A-EVS-MUF-040000_LOC_FB DI MU1AECO_AENTR3:0:I.6
CHANNEL,MU1AECO_AENTR3:0:I.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
23 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalMAKE-UP
to be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-2 AENTR3 0 1XDI2 : 13,14 - SDI-16 6 AENTR3:0:I.6 I 4/17/2025 DONE
3E4DS0-MU1A-EVS-MUF-040000
SIGNAL 3E4DS0-MU1A-EVS-MUF-040000_REM_FB (SPR_ARR_UDT[3].RUN_FB) IS MAPPED TO THIS
3E4DS0-MU1A-EVS-MUF-040000_REM_FB DI MU1AECO_AENTR3:0:I.7
CHANNEL,MU1AECO_AENTR3:0:I.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
24 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalMAKE-UP
to be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-2 AENTR3 0 1XDI2 : 15,16 - SDI-16 7 AENTR3:0:I.7 I 4/17/2025 DONE
3E4DS0-MU1A-EVS-MUF-040000
SIGNAL 3E4DS0-MU1A-EVS-MUF-040000_RUN_FB (SPR_ARR_UDT[3].LOC_FB) IS MAPPED TO THIS
3E4DS0-MU1A-EVS-MUF-040000_RUN_FB DI MU1AECO_AENTR3:0:I.8
CHANNEL,MU1AECO_AENTR3:0:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
25 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
RUNNING
signal
OFtoMAKE-UP
be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-2 AENTR3 0 1XDI2 : 17,18 - SDI-16 8 AENTR3:0:I.8 I 4/17/2025 DONE
3E4DS0-MU1A-EVS-MUFDPS-040001
SIGNAL 3E4DS0-MU1A-EVS-MUFDPS-040001_DPS_FB (SPR_ARR_UDT[3].DPS_FB) IS MAPPED TO THIS
3E4DS0-MU1A-EVS-MUFDPS-040001_DPS_FB DI MU1AECO_AENTR3:0:I.9
CHANNEL,MU1AECO_AENTR3:0:I.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
26 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MAKE-UP
signal
FANtoPROOF
be confirmed
OF FLOW MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDI-2 AENTR3 0 1XDI2 : 19,20 - SDI-16 9 AENTR3:0:I.9 I 4/17/2025 DONE
SIGNAL, 3E4DS0-MU1A-EVS-MUF-040000_ON_OFF_CMD (MUF_ARR_UDT[4].ON_OFF_CMD) IS MAPPED TO THIS
MU1AECO_AENTR2:1:O.0
33 3E4DS0-MU1A-EVS-MUF-040000 3E4DS0-MU1A-EVS-MUF-040000_ON_OFF_CMD RELAY,MU1AECO_AENTR2:1:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
MAKE-UP
be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDO-1 AENTR2 1 - 1SR1 : 11,14 SDO-16 0 AENTR2:1:O.0 DO O 4/17/2025 DONE
SIGNAL, 3E4DS0-MU1A-EVS-SPR-040000_ON_OFF_CMD (SPR_ARR_UDT[4].ON_OFF_CMD) IS MAPPED TO THIS
MU1AECO_AENTR2:1:O.1
34 3E4DS0-MU1A-EVS-SPR-040000 3E4DS0-MU1A-EVS-SPR-040000_ON_OFF_CMD RELAY,MU1AECO_AENTR2:1:O.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
ELEVATOR
be confirmed
PRESSURIZATION FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDO-1 AENTR2 1 - 1SR2 : 11,14 SDO-16 1 AENTR2:1:O.1 DO O 4/17/2025 DONE
SIGNAL, 3E4DS0-MU1B-EVS-MUF-030000_ON_OFF_CMD (MUF_ARR_UDT[3].ON_OFF_CMD) IS MAPPED TO THIS
MU1AECO_AENTR2:1:O.2
35 3E4DS0-MU1B-EVS-MUF-030000 3E4DS0-MU1B-EVS-MUF-030000_ON_OFF_CMD RELAY,MU1AECO_AENTR2:1:O.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
MAKE-UP
be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDO-1 AENTR2 1 - 1SR3 : 11,14 SDO-16 2 AENTR2:1:O.2 DO O 4/17/2025 DONE
SIGNAL, 3E4DS0-MU1B-EVS-SPR-030000_ON_OFF_CMD (SPR_ARR_UDT[3].ON_OFF_CMD) IS MAPPED TO THIS
MU1AECO_AENTR2:1:O.3
36 3E4DS0-MU1B-EVS-SPR-030000 3E4DS0-MU1B-EVS-SPR-030000_ON_OFF_CMD RELAY,MU1AECO_AENTR2:1:O.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
ELEVATOR
be confirmed
PRESSURIZATION FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 SDO-1 AENTR2 1 - 1SR4 : 11,14 SDO-16 3 AENTR2:1:O.3 DO O 4/17/2025 DONE
SIGNAL, 3E4DS0-MU1A-HVAC-MAU-030000_SF_TRIP (S_MAU_ARR_UDT[3].SF_TRIP) IS MAPPED TO THIS
MU1AECO_AENTR1:0:I.0
65 3E4DS0-MU1A-HVAC-MAU-030000 3E4DS0-MU1A-HVAC-MAU-030000_SF_TRIP CHANNEL,MU1AECO_AENTR1:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
SUPPLY
be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-1 AENTR1 0 1XDI1 : 1,2 - DI-16 0 AENTR1:0:I.0 DI I 4/17/2025 DONE
SIGNAL, 3E4DS0-MU1A-HVAC-MAU-030000_SF_LOC (S_MAU_ARR_UDT[3].SF_LOC) IS MAPPED TO THIS
MU1AECO_AENTR1:0:I.1
66 3E4DS0-MU1A-HVAC-MAU-030000 3E4DS0-MU1A-HVAC-MAU-030000_SF_LOC CHANNEL,MU1AECO_AENTR1:0:I.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalSWITCH
to be confirmed
SUPPLY FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-1 AENTR1 0 1XDI1 : 3,4 - DI-16 1 AENTR1:0:I.1 DI I 4/17/2025 DONE
SIGNAL, 3E4DS0-MU1A-HVAC-MAU-030000_SF_REM (S_MAU_ARR_UDT[3].SF_REM) IS MAPPED TO THIS
MU1AECO_AENTR1:0:I.2
67 3E4DS0-MU1A-HVAC-MAU-030000 3E4DS0-MU1A-HVAC-MAU-030000_SF_REM CHANNEL,MU1AECO_AENTR1:0:I.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalSWITCH
to be confirmed
SUPPLY FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-1 AENTR1 0 1XDI1 : 5,6 - DI-16 2 AENTR1:0:I.2 DI I 4/17/2025 DONE
SIGNAL, 3E4DS0-MU1A-HVAC-MAU-030000_SF_RUN_FB (S_MAU_ARR_UDT[3].SF_RUN_FB) IS MAPPED TO THIS
MU1AECO_AENTR1:0:I.3
68 3E4DS0-MU1A-HVAC-MAU-030000 3E4DS0-MU1A-HVAC-MAU-030000_SF_RUN_FB CHANNEL,MU1AECO_AENTR1:0:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MAU Power
signal Supply
to be confirmed
On/Off Status MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-1 AENTR1 0 1XDI1 : 7,8 - DI-16 3 AENTR1:0:I.3 DI I 4/17/2025 DONE

# General
PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM

DOCUMENT TITLE SHOP DRAWING-DEEP UNDERGROUND STATION-3E4-BMS-INPUT/OUTPUT SCHEDULE

DOCUMENT NO. M-ANM-3E4DS0-CJ00-SCH-000002

MODULE RELAY MODULE CHANNE


SR. NO. EQUIPMENT TAG PLC TAG EASA SITE Response RLM COMMENTS FROM CWG DESCRIPTION PANEL SHORT TAG (OLD) PANEL FULL TAG (NEW) RACK NO. SLOT NO. TERMINAL NO. PLC IO ADDRESS MODULE ID DATE STATUS
ID NO. TYPE L NO.
SIGNAL, 3E4DS0-MU1B-HVAC-FAN-020000_TRIP_FB (FAN_ARR_UDT[2].TRIP_FB) IS MAPPED TO THIS
MU1AECO_AENTR1:0:I.6
71 3E4DS0-MU1B-HVAC-FAN-020000 3E4DS0-MU1B-HVAC-FAN-020000_TRIP_FB CHANNEL,MU1AECO_AENTR1:0:I.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
EXHAUST
be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-1 AENTR1 0 1XDI1 : 13,14 - DI-16 6 AENTR1:0:I.6 DI I 4/17/2025 DONE
SIGNAL, 3E4DS0-MU1B-HVAC-FAN-020000_LOC_FB (FAN_ARR_UDT[2].LOC_FB) IS MAPPED TO THIS
MU1AECO_AENTR1:0:I.7
72 3E4DS0-MU1B-HVAC-FAN-020000 3E4DS0-MU1B-HVAC-FAN-020000_LOC_FB CHANNEL,MU1AECO_AENTR1:0:I.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalSWITCH
to be confirmed
EXHAUST FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-1 AENTR1 0 1XDI1 : 15,16 - DI-16 7 AENTR1:0:I.7 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MU1B-HVAC-FAN-020000_REM_FB (FAN_ARR_UDT[2].REM_FB) IS MAPPED TO THIS
MU1AECO_AENTR1:0:I.8
73 3E4DS0-MU1B-HVAC-FAN-020000 3E4DS0-MU1B-HVAC-FAN-020000_REM_FB CHANNEL,MU1AECO_AENTR1:0:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalSWITCH
to be confirmed
EXHAUST FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-1 AENTR1 0 1XDI1 : 17,18 - DI-16 8 AENTR1:0:I.8 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MU1B-HVAC-FAN-020000_RUN_FB (FAN_ARR_UDT[2].RUN_FB) IS MAPPED TO THIS
MU1AECO_AENTR1:0:I.9
74 3E4DS0-MU1B-HVAC-FAN-020000 3E4DS0-MU1B-HVAC-FAN-020000_RUN_FB CHANNEL,MU1AECO_AENTR1:0:I.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
RUNNING
signal
OFtoEXHAUST
be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-1 AENTR1 0 1XDI1 : 19,20 - DI-16 9 AENTR1:0:I.9 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MU1B-HVAC-FAN-010000_TRIP_FB (FAN_ARR_UDT[1].TRIP_FB) IS MAPPED TO THIS
MU1AECO_AENTR1:1:I.0
81 3E4DS0-MU1B-HVAC-FAN-010000 3E4DS0-MU1B-HVAC-FAN-010000_TRIP_FB CHANNEL,MU1AECO_AENTR1:1:I.Data.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
EXHAUST
be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-2 AENTR1 1 1XDI2 : 1,2 - DI-32 0 AENTR1:1:I.Data.0 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MU1B-HVAC-FAN-010000_LOC_FB (FAN_ARR_UDT[1].LOC_FB) IS MAPPED TO THIS
MU1AECO_AENTR1:1:I.1
82 3E4DS0-MU1B-HVAC-FAN-010000 3E4DS0-MU1B-HVAC-FAN-010000_LOC_FB CHANNEL,MU1AECO_AENTR1:1:I.Data.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalSWITCH
to be confirmed
EXHAUST FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-2 AENTR1 1 1XDI2 : 3,4 - DI-32 1 AENTR1:1:I.Data.1 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MU1B-HVAC-FAN-010000_REM_FB (FAN_ARR_UDT[1].REM_FB) IS MAPPED TO THIS
MU1AECO_AENTR1:1:I.2
83 3E4DS0-MU1B-HVAC-FAN-010000 3E4DS0-MU1B-HVAC-FAN-010000_REM_FB CHANNEL,MU1AECO_AENTR1:1:I.Data.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalSWITCH
to be confirmed
EXHAUST FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-2 AENTR1 1 1XDI2 : 5,6 - DI-32 2 AENTR1:1:I.Data.2 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MU1B-HVAC-FAN-010000_RUN_FB (FAN_ARR_UDT[1].RUN_FB) IS MAPPED TO THIS
MU1AECO_AENTR1:1:I.3
84 3E4DS0-MU1B-HVAC-FAN-010000 3E4DS0-MU1B-HVAC-FAN-010000_RUN_FB CHANNEL,MU1AECO_AENTR1:1:I.Data.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
RUNNING
signal
OFtoEXHAUST
be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-2 AENTR1 1 1XDI2 : 7,8 - DI-32 3 AENTR1:1:I.Data.3 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-VS02-HVAC-FAN-100000_TRIP_FB (FAN_ARR_UDT[9].TRIP_FB) IS MAPPED TO THIS
MU1AECO_AENTR1:1:I.7
88 3E4DS0-VS02-HVAC-FAN-100000 3E4DS0-VS02-HVAC-FAN-100000_TRIP_FB CHANNEL,MU1AECO_AENTR1:1:I.Data.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
PURGE
be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-2 AENTR1 1 1XDI2 : 15,16 - DI-32 7 AENTR1:1:I.Data.7 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-VS02-HVAC-FAN-100000_LOC_FB (FAN_ARR_UDT[9].LOC_FB) IS MAPPED TO THIS
MU1AECO_AENTR1:1:I.8
89 3E4DS0-VS02-HVAC-FAN-100000 3E4DS0-VS02-HVAC-FAN-100000_LOC_FB CHANNEL,MU1AECO_AENTR1:1:I.Data.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalSWITCH
to be confirmed
PURGE FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-2 AENTR1 1 1XDI2 : 17,18 - DI-32 8 AENTR1:1:I.Data.8 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-VS02-HVAC-FAN-100000_REM_FB (FAN_ARR_UDT[9].REM_FB) IS MAPPED TO THIS
MU1AECO_AENTR1:1:I.9
90 3E4DS0-VS02-HVAC-FAN-100000 3E4DS0-VS02-HVAC-FAN-100000_REM_FB CHANNEL,MU1AECO_AENTR1:1:I.Data.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalSWITCH
to be confirmed
PURGE FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-2 AENTR1 1 1XDI2 : 19,20 - DI-32 9 AENTR1:1:I.Data.9 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-VS02-HVAC-FAN-100000_RUN_FB (FAN_ARR_UDT[9].RUN_FB) IS MAPPED TO THIS
MU1AECO_AENTR1:1:I.10
91 3E4DS0-VS02-HVAC-FAN-100000 3E4DS0-VS02-HVAC-FAN-100000_RUN_FB CHANNEL,MU1AECO_AENTR1:1:I.Data.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
RUNNING
signal
OFtoPURGE
be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-2 AENTR1 1 1XDI2 : 21,22 - DI-32 10 AENTR1:1:I.Data.10 DI I 4/17/2025 DONE
THERE IS NO MAPPING,TO THIS CHANNEL,MU1AECO_AENTR1:1:I.14.IN SITE ,EXTRA CABLE IS CONNECTED TO THIS
MU1AECO_AENTR1:1:I.14
95 SPARE SPARE CHANNEL. As per CWG RLM, this channel is used at site, please check. SPARE MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-2 AENTR1 1 1XDI2 : 29,30 - DI-32 14 AENTR1:1:I.Data.14 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MER-HVAC-AHU-060000_OPN_FB (S_AHU_ARR_UDT[6].OPN_FB) IS MAPPED TO THIS
MOTORIZED FIRE DAMPERS NON FM200 MU1AECO_AENTR1:1:I.20
101 3E4DS0-MER-HVAC-AHU-060000 3E4DS0-MER-HVAC-AHU-060000_OPN_FB CHANNEL,MU1AECO_AENTR1:1:I.Data.20.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-2 AENTR1 1 1XDI2 : 41,42 - DI-32 20 AENTR1:1:I.Data.20 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MER01-HVAC-AHU-080000_OPN_FB (S_AHU_ARR_UDT[8].OPN_FB) IS MAPPED TO THIS
MOTORIZED FIRE DAMPERS NON FM200 MU1AECO_AENTR1:1:I.21
102 3E4DS0-MER01-HVAC-AHU-080000 3E4DS0-MER01-HVAC-AHU-080000_OPN_FB CHANNEL,MU1AECO_AENTR1:1:I.Data.21.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-2 AENTR1 1 1XDI2 : 43,44 - DI-32 21 AENTR1:1:I.Data.21 DI I 4/17/2025 DONE
SIGNAL 3E4DS0-MU1A-HVAC-MAU-030000_SS2_REM_FB (S_MAU_ARR_UDT[3].SS2_REM_FB) IS MAPPED TO THIS
CHANNEL,MU1AECO_AENTR1:1:I.Data.28.IN SITE ,SINCE THERE IS NO SIGNAL PROVISION.CABLE IS NOT CONNECTED TO MU1AECO_AENTR1:1:I.28
109 3E4DS0-MU1A-HVAC-MAU-030000 3E4DS0-MU1A-HVAC-MAU-030000_SS2_REM_FB THIS TERMINAL. As per CWG RLM, this channel is spare at site, please check. Start Push Button RM relay activated/deactivated Status MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DI-2 AENTR1 1 1XDI2 : 57,58 - DI-32 28 AENTR1:1:I.Data.28 DI I 4/17/2025 DONE

SIGNAL 3E4DS0-MU1A-HVAC-MAU-030000_SF_SPD_CMD (S_MAU_ARR_UDT[3].SF_POS_CMD) IS MAPPED TO THIS MU1AECO_AENTR1:3:chdata.0


137 3E4DS0-MU1A-HVAC-MAU-030000 3E4DS0-MU1A-HVAC-MAU-030000_SF_SPD_CMD CHANNEL,MU1AECO_AENTR1:3:O.Ch0Data.IN SITE ALSO,CABLE IS CONNECTED TO THIS CHANNEL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
SUPPLYsignal
FAN SPEED
to be confirmed
CONTROL MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 AO-1 AENTR1 3 1XAO1 : 1,2 - AO-04 0 AENTR1:3:O.Ch0Data AO chdata 4/17/2025 DONE
SIGNAL 3E4DS0-VS02-HVAC-FAN-100000_RUN_FB (FAN_ARR_UDT[1].ON_OFF_CMD) IS MAPPED TO THIS
MU1AECO_AENTR1:4:O.0
141 3E4DS0-MU1B-HVAC-FAN-010000 3E4DS0-MU1B-HVAC-FAN-010000_ON_OFF_CMD RELAY,MU1AECO_AENTR1:4:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
EXHAUST
be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DO-1 AENTR1 4 - 1R1 : 11,14 DO-16 0 AENTR1:4:O.0 DO O 4/17/2025 DONE
SIGNAL 3E4DS0-MU1B-HVAC-FAN-020000_ON_OFF_CMD(FAN_ARR_UDT[2].ON_OFF_CMD) IS MAPPED TO THIS
MU1AECO_AENTR1:4:O.1
142 3E4DS0-MU1B-HVAC-FAN-020000 3E4DS0-MU1B-HVAC-FAN-020000_ON_OFF_CMD RELAY,MU1AECO_AENTR1:4:O.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
EXHAUST
be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DO-1 AENTR1 4 - 1R2 : 11,14 DO-16 1 AENTR1:4:O.1 DO O 4/17/2025 DONE
SIGNAL 3E4DS0-VS02-HVAC-FAN-100000_ON_OFF_CMD (FAN_ARR_UDT[9].ON_OFF_CMD) IS MAPPED TO THIS
MU1AECO_AENTR1:4:O.2
143 3E4DS0-VS02-HVAC-FAN-100000 3E4DS0-VS02-HVAC-FAN-100000_ON_OFF_CMD RELAY,MU1AECO_AENTR1:4:O.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
PURGE
be confirmed
FAN MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DO-1 AENTR1 4 - 1R3 : 11,14 DO-16 2 AENTR1:4:O.2 DO O 4/17/2025 DONE

SIGNAL 3E4DS0-MU1A-HVAC-MAU-030000_SF_ON_OFF_CMD (S_MAU_ARR_UDT[3].SF_ON_OFF_CMD) IS MAPPED TO MU1AECO_AENTR1:4:O.3


144 3E4DS0-MU1A-HVAC-MAU-030000 3E4DS0-MU1A-HVAC-MAU-030000_SF_ON_OFF_CMD THIS RELAY,MU1AECO_AENTR1:4:O.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Switch signal
On MAU to be
Power
confirmed
Supply MU1AECO 3E4DS0-MU1A-BMS-RIOP-000012 DO-1 AENTR1 4 - 1R4 : 11,14 DO-16 3 AENTR1:4:O.3 DO O 4/17/2025 DONE
SIGNAL 3E4DS0-SE01-EVS-SE-050001_ON_OFF_CMD (SEF_ARR_UDT[5].ON_OFF_CMD) IS MAPPED TO THIS RELAY,
SE01WCO_AENTR1:1:O.0
33 3E4DS0-SE01-EVS-SE-050001 3E4DS0-SE01-EVS-SE-050001_ON_OFF_CMD SE01WCO_AENTR1:1:O.0 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME RELAY. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
SMOKE
be confirmed
EXHAUST FAN SE01WCO 3E4DS0-SE01-BMS-RIOP-000004 SDO-1 AENTR1 1 - 1SR1 : 11,14 SDO-16 0 AENTR1:1:O.0 DO O 4/19/2025 DONE
SIGNAL, Trip status Elevator Pressurization Fan SPR-050002 (SPR_ARR_UDT[6].TRIP_FB) IS MAPPED TO THIS
SE02WCO_AENTR1:1:I.0
17 SPARE SPARE CHANNEL,SE02WCO_AENTR1:1:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE SE02WCO 3E4DS0-SE02-BMS-RIOP-000008 SDI-2 AENTR1 1 1XSDI2 : 1,2 - SDI-16 0 AENTR1:1:I.0 DI I 4/19/2025 DONE
SIGNAL, Hand/off Elevator Pressurization Fan SPR-050002 (SPR_ARR_UDT[6].LOC_FB) IS MAPPED TO THIS
SE02WCO_AENTR1:1:I.1
18 SPARE SPARE CHANNEL,SE02WCO_AENTR1:1:I.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE SE02WCO 3E4DS0-SE02-BMS-RIOP-000008 SDI-2 AENTR1 1 1XSDI2 : 3,4 - SDI-16 1 AENTR1:1:I.1 DI I 4/19/2025 DONE
SIGNAL, Auto/off Elevator Pressurization Fan SPR-050002 (SPR_ARR_UDT[6].REM_FB) IS MAPPED TO THIS
SE02WCO_AENTR1:1:I.2
19 SPARE SPARE CHANNEL,SE02WCO_AENTR1:1:I.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE SE02WCO 3E4DS0-SE02-BMS-RIOP-000008 SDI-2 AENTR1 1 1XSDI2 : 5,6 - SDI-16 2 AENTR1:1:I.2 DI I 4/19/2025 DONE
SIGNAL, Running of Elevator Pressurization Fan SPR-050002 (SPR_ARR_UDT[6].RUN_FB) IS MAPPED TO THIS
SE02WCO_AENTR1:1:I.3
20 SPARE SPARE CHANNEL,SE02WCO_AENTR1:1:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE SE02WCO 3E4DS0-SE02-BMS-RIOP-000008 SDI-2 AENTR1 1 1XSDI2 : 7,8 - SDI-16 3 AENTR1:1:I.3 DI I 4/19/2025 DONE
SIGNAL, Elevator Pressurization Fan proof of flow SPR-050002 (SPR_ARR_UDT[6].DPS_FB) IS MAPPED TO THIS
SE02WCO_AENTR1:1:I.4
21 SPARE SPARE CHANNEL,SE02WCO_AENTR1:1:I.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE SE02WCO 3E4DS0-SE02-BMS-RIOP-000008 SDI-2 AENTR1 1 1XSDI2 : 9,10 - SDI-16 4 AENTR1:1:I.4 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-CA-EVS-SPR-050001_Elevator Pressurization Fan ON_OFF COMMAND
(SPR_ARR_UDT[5].ON_OFF_CMD) IS MAPPED TO THIS RELAY,SE02WCO_AENTR1:2:O.0 .IN SITE ALSO,CABLE IS SE02WCO_AENTR1:2:O.0
33 3E4DS0-CA-EVS-SPR-050001 3E4DS0-CA-EVS-SPR-050001_ON_OFF_CMD CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
ELEVATOR
be confirmed
PRESSURIZATION FAN SE02WCO 3E4DS0-SE02-BMS-RIOP-000008 SDO-1 AENTR1 2 - 1SR1 : 11,14 SDO-16 0 AENTR1:2:O.0 DO O 4/19/2025 DONE

SIGNAL 3E4DS0-SE02-EVS-SE-010000_Smoke Exhaust Fan ON_OFF COMMAND (SEF_ARR_UDT[1].ON_OFF_CMD) IS SE02WCO_AENTR1:2:O.1


34 SPARE SPARE MAPPED TO THIS RELAY,SE02WCO_AENTR1:2:O.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE SE02WCO 3E4DS0-SE02-BMS-RIOP-000008 SDO-1 AENTR1 2 - 1SR2 : 11,14 SDO-16 1 AENTR1:2:O.1 DO O 4/19/2025 DONE
SIGNAL, 3E4DS0-CA-EVS-SPR-050003_TRIP_FB (SPR_ARR_UDT[7].TRIP_FB) IS MAPPED TO THIS
SE03WCO_AENTR1:0:I.0
1 3E4DS0-CA-EVS-SPR-050003 3E4DS0-CA-EVS-SPR-050003_TRIP_FB CHANNEL,SE03WCO_AENTR1:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
ELEVATOR
be confirmed
PRESSURIZATION FAN SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDI-1 AENTR1 0 1XSDI1 : 1,2 - SDI-16 0 AENTR1:0:I.0 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-CA-EVS-SPR-050003_LOC_FB (SPR_ARR_UDT[7].LOC_FB) IS MAPPED TO THIS
SE03WCO_AENTR1:0:I.1
2 3E4DS0-CA-EVS-SPR-050003 3E4DS0-CA-EVS-SPR-050003_LOC_FB CHANNEL,SE03WCO_AENTR1:0:I.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalELEVATOR
to be confirmed
PRESSURIZATION FAN SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDI-1 AENTR1 0 1XSDI1 : 3,4 - SDI-16 1 AENTR1:0:I.1 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-CA-EVS-SPR-050003_REM_FB (SPR_ARR_UDT[7].REM_FB) IS MAPPED TO THIS
SE03WCO_AENTR1:0:I.2
3 3E4DS0-CA-EVS-SPR-050003 3E4DS0-CA-EVS-SPR-050003_REM_FB CHANNEL,SE03WCO_AENTR1:0:I.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalELEVATOR
to be confirmed
PRESSURIZATION FAN SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDI-1 AENTR1 0 1XSDI1 : 5,6 - SDI-16 2 AENTR1:0:I.2 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-CA-EVS-SPR-050003_RUN_FB (SPR_ARR_UDT[7].RUN_FB) IS MAPPED TO THIS
SE03WCO_AENTR1:0:I.3
4 3E4DS0-CA-EVS-SPR-050003 3E4DS0-CA-EVS-SPR-050003_RUN_FB CHANNEL,SE03WCO_AENTR1:0:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
RUNNING
signal
OFtoELEVATOR
be confirmed
PRESSURIZATION FAN SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDI-1 AENTR1 0 1XSDI1 : 7,8 - SDI-16 3 AENTR1:0:I.3 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-CA-EVS-SPRDPS-050003_DPS_FB (SPR_ARR_UDT[7].DPS_FB) IS MAPPED TO THIS
SE03WCO_AENTR1:0:I.4
5 3E4DS0-CA-EVS-SPRDPS-050003 3E4DS0-CA-EVS-SPRDPS-050003_DPS_FB CHANNEL,SE03WCO_AENTR1:0:I.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
ELEVATOR
signal
PRESSURIZATION
to be confirmedFAN PROOF OF FLOW SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDI-1 AENTR1 0 1XSDI1 : 9,10 - SDI-16 4 AENTR1:0:I.4 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-CA-EVS-SPR-050004_TRIP_FB (SPR_ARR_UDT[8].TRIP_FB) IS MAPPED TO THIS
SE03WCO_AENTR2:0:I.0
17 3E4DS0-CA-EVS-SPR-050004 3E4DS0-CA-EVS-SPR-050004_TRIP_FB CHANNEL,SE03WCO_AENTR2:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
ELEVATOR
be confirmed
PRESSURIZATION FAN SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDI-2 AENTR2 0 1XSDI2 : 1,2 - SDI-16 0 AENTR2:0:I.0 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-CA-EVS-SPR-050004_LOC_FB (SPR_ARR_UDT[8].LOC_FB) IS MAPPED TO THIS
SE03WCO_AENTR2:0:I.1
18 3E4DS0-CA-EVS-SPR-050004 3E4DS0-CA-EVS-SPR-050004_LOC_FB CHANNEL,SE03WCO_AENTR2:0:I.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalELEVATOR
to be confirmed
PRESSURIZATION FAN SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDI-2 AENTR2 0 1XSDI2 : 3,4 - SDI-16 1 AENTR2:0:I.1 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-CA-EVS-SPR-050004_REM_FB (SPR_ARR_UDT[8].REM_FB) IS MAPPED TO THIS
SE03WCO_AENTR2:0:I.2
19 3E4DS0-CA-EVS-SPR-050004 3E4DS0-CA-EVS-SPR-050004_REM_FB CHANNEL,SE03WCO_AENTR2:0:I.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalELEVATOR
to be confirmed
PRESSURIZATION FAN SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDI-2 AENTR2 0 1XSDI2 : 5,6 - SDI-16 2 AENTR2:0:I.2 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-CA-EVS-SPR-050004_RUN_FB (SPR_ARR_UDT[8].RUN_FB) IS MAPPED TO THIS
SE03WCO_AENTR2:0:I.3
20 3E4DS0-CA-EVS-SPR-050004 3E4DS0-CA-EVS-SPR-050004_RUN_FB CHANNEL,SE03WCO_AENTR2:0:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
RUNNING
signal
OFtoELEVATOR
be confirmed
PRESSURIZATION FAN SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDI-2 AENTR2 0 1XSDI2 : 7,8 - SDI-16 3 AENTR2:0:I.3 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-CA-EVS-SPRDPS-050004_DPS_FB (SPR_ARR_UDT[8].DPS_FB) IS MAPPED TO THIS
SE03WCO_AENTR2:0:I.4
21 3E4DS0-CA-EVS-SPRDPS-050004 3E4DS0-CA-EVS-SPRDPS-050004_DPS_FB CHANNEL,SE03WCO_AENTR2:0:I.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
ELEVATOR
signal
PRESSURIZATION
to be confirmedFAN PROOF OF FLOW SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDI-2 AENTR2 0 1XSDI2 : 9,10 - SDI-16 4 AENTR2:0:I.4 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-SE03-EVS-SE-020000-Trip status Smoke Exhaust Fan (SEF_ARR_UDT[2].TRIP_FB) IS MAPPED TO THIS
SE03WCO_AENTR2:0:I.5
22 SPARE SPARE CHANNEL,SE03WCO_AENTR2:0:I.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDI-2 AENTR2 0 1XSDI2 : 11,12 - SDI-16 5 AENTR2:0:I.5 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-SE03-EVS-SE-020000-Hand/off Smoke Exhaust Fan (SEF_ARR_UDT[2].LOC_FB) IS MAPPED TO THIS
SE03WCO_AENTR2:0:I.6
23 SPARE SPARE CHANNEL,SE03WCO_AENTR2:0:I.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDI-2 AENTR2 0 1XSDI2 : 13,14 - SDI-16 6 AENTR2:0:I.6 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-SE03-EVS-SE-020000-Auto/off Smoke Exhaust Fan (SEF_ARR_UDT[2].REM_FB) IS MAPPED TO THIS
SE03WCO_AENTR2:0:I.7
24 SPARE SPARE CHANNEL,SE03WCO_AENTR2:0:I.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDI-2 AENTR2 0 1XSDI2 : 15,16 - SDI-16 7 AENTR2:0:I.7 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-SE03-EVS-SE-020000-Running of Smoke Exhaust Fan (SEF_ARR_UDT[2].RUN_FB) IS MAPPED TO THIS
SE03WCO_AENTR2:0:I.8
25 SPARE SPARE CHANNEL,SE03WCO_AENTR2:0:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDI-2 AENTR2 0 1XSDI2 : 17,18 - SDI-16 8 AENTR2:0:I.8 DI I 4/19/2025 DONE

SIGNAL 3E4DS0-SE03-EVS-SEDPS-020001-Smoke Exhaust Fan proof of flow (SEF_ARR_UDT[2].DPS_FB) IS MAPPED TO SE03WCO_AENTR2:0:I.9


26 SPARE SPARE THIS CHANNEL,SE03WCO_AENTR2:0:I.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDI-2 AENTR2 0 1XSDI2 : 19,20 - SDI-16 9 AENTR2:0:I.9 DI I 4/19/2025 DONE

SE03WCO_AENTR2:0:I.14
SIGNAL 3E4DS0-SE03-EVS-SEDPS-080001-Smoke Exhaust Fan proof of flow (SEF_ARR_UDT[9].DPS_FB) IS MAPPED TO
31 3E4DS0-SE03-EVS-SEDPS-080001 3E4DS0-SE03-EVS-SEDPS-080001_DPS_FB THIS CHANNEL,SE03WCO_AENTR2:0:I.14.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
SMOKEsignal
EXHAUST
to beFAN
confirmed
PROOF OF FLOW SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDI-2 AENTR2 0 1XSDI2 : 29,30 - SDI-16 14 AENTR2:0:I.14 DI I 4/19/2025 DONE

SIGNAL SE03WCO Panel Power Supply Fail (SE03WCO_PWR_SPLY1_FAIL) IS MAPPED TO THIS


3E4DS0-SE03-BMS-RIOP-000010 3E4DS0-SE03-BMS-SE03WCO-000000_SE03WCO_PWR_SPLY1_FAIL As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed SE03WCO_AENTR2:0:I.15
CHANNEL,SE03WCO_AENTR2:0:I.15.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
32 POWER SUPPLY FAILURE ALARM SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDI-2 AENTR2 0 1XSDI2 : 31,32 - SDI-16 15 AENTR2:0:I.15 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-CA-EVS-SPR-050003_Elevator Pressurization Fan_ON_OFF COMMAND
(SPR_ARR_UDT[7].ON_OFF_CMD) IS MAPPED TO THIS RELAY,SE03WCO_AENTR1:1:O.0.IN SITE ALSO,CABLE IS SE03WCO_AENTR1:1:O.0
33 3E4DS0-CA-EVS-SPR-050003 3E4DS0-CA-EVS-SPR-050003_ON_OFF_CMD CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
ELEVATOR
be confirmed
PRESSURIZATION FAN SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDO-1 AENTR1 1 - 1SR1 : 11,14 SDO-16 0 AENTR1:1:O.0 DO O 4/19/2025 DONE

SIGNAL 3E4DS0-SE03-EVS-SE-080002_Smoke Exhaust Fan_ON_OFF COMMAND (SEF_ARR_UDT[10].ON_OFF_CMD) IS SE03WCO_AENTR1:1:O.2


35 3E4DS0-SE03-EVS-SE-080002 3E4DS0-SE03-EVS-SE-080002_ON_OFF_CMD MAPPED TO THIS RELAY,SE03WCO_AENTR1:1:O.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
SMOKE
be confirmed
EXHAUST FAN SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDO-1 AENTR1 1 - 1SR3 : 11,14 SDO-16 2 AENTR1:1:O.2 DO O 4/19/2025 DONE

SIGNAL 3E4DS0-SE03-EVS-SE-020000_Smoke Exhaust Fan_ON_OFF COMMAND (SEF_ARR_UDT[2].ON_OFF_CMD) IS SE03WCO_AENTR1:1:O.3


36 SPARE SPARE MAPPED TO THIS RELAY,SE03WCO_AENTR1:1:O.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDO-1 AENTR1 1 - 1SR4 : 11,14 SDO-16 3 AENTR1:1:O.3 DO O 4/19/2025 DONE

SIGNAL 3E4DS0-SE03-EVS-SE-080001_Smoke Exhaust Fan_ON_OFF COMMAND (SEF_ARR_UDT[9].ON_OFF_CMD) IS SE03WCO_AENTR2:1:O.0


49 3E4DS0-SE03-EVS-SE-080001 3E4DS0-SE03-EVS-SE-080001_ON_OFF_CMD MAPPED TO THIS RELAY,SE03WCO_AENTR2:1:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
SMOKE
be confirmed
EXHAUST FAN SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDO-2 AENTR2 1 - 1SR17 : 11,14 SDO-16 0 AENTR2:1:O.0 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-CA-EVS-SPR-050004_Elevator Pressurization Fan_ON_OFF COMMAND
(SPR_ARR_UDT[8].ON_OFF_CMD) IS MAPPED TO THIS RELAY,SE03WCO_AENTR2:1:O.1.IN SITE ALSO,CABLE IS SE03WCO_AENTR2:1:O.1
50 3E4DS0-CA-EVS-SPR-050004 3E4DS0-CA-EVS-SPR-050004_ON_OFF_CMD CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
START/STOP
signal to
ELEVATOR
be confirmed
PRESSURIZATION FAN SE03WCO 3E4DS0-SE03-BMS-RIOP-000010 SDO-2 AENTR2 1 - 1SR18 : 11,14 SDO-16 1 AENTR2:1:O.1 DO O 4/19/2025 DONE
SIGNAL, 3E4DS0-SE-EVS-SE-100000-Trip status Smoke Exhaust Fan (SEF_ARR_UDT[12].TRIP_FB) IS MAPPED TO THIS
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed SEECO_AENTR1:0:I.0
1 3E4DS0-SE-EVS-SE-100000 3E4DS0-SE-EVS-SE-100000_TRIP_FB CHANNEL,SEECO_AENTR1:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. TRIP STATUS SMOKE EXHAUST FAN SEECO 3E4DS0-SE-BMS-RIOP-000011 SDI-1 AENTR1 0 1XSDI1 : 1,2 - SDI-16 0 AENTR1:0:I.0 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-SE-EVS-SE-100000-Hand/off Smoke Exhaust Fan (SEF_ARR_UDT[12].LOC_FB) IS MAPPED TO THIS
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed SEECO_AENTR1:0:I.1
2 3E4DS0-SE-EVS-SE-100000 3E4DS0-SE-EVS-SE-100000_LOC_FB CHANNEL,SEECO_AENTR1:0:I.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. HAND/OFF SMOKE EXHAUST FAN SEECO 3E4DS0-SE-BMS-RIOP-000011 SDI-1 AENTR1 0 1XSDI1 : 3,4 - SDI-16 1 AENTR1:0:I.1 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-SE-EVS-SE-100000-Auto/off Smoke Exhaust Fan (SEF_ARR_UDT[12].REM_FB) IS MAPPED TO THIS
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed SEECO_AENTR1:0:I.2
3 3E4DS0-SE-EVS-SE-100000 3E4DS0-SE-EVS-SE-100000_REM_FB CHANNEL,SEECO_AENTR1:0:I.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. AUTO/OFF SMOKE EXHAUST FAN SEECO 3E4DS0-SE-BMS-RIOP-000011 SDI-1 AENTR1 0 1XSDI1 : 5,6 - SDI-16 2 AENTR1:0:I.2 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-SE-EVS-SE-100000-Running of Smoke Exhaust Fan (SEF_ARR_UDT[12].RUN_FB) IS MAPPED TO THIS
As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed SEECO_AENTR1:0:I.3
4 3E4DS0-SE-EVS-SE-100000 3E4DS0-SE-EVS-SE-100000_RUN_FB CHANNEL,SEECO_AENTR1:0:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. RUNNING OF SMOKE EXHAUST FAN SEECO 3E4DS0-SE-BMS-RIOP-000011 SDI-1 AENTR1 0 1XSDI1 : 7,8 - SDI-16 3 AENTR1:0:I.3 DI I 4/19/2025 DONE
3E4DS0-SE-EVS-SE-030000
SIGNAL, 3E4DS0-SE-EVS-SE-040000-Trip status Smoke Exhaust Fan (SEF_ARR_UDT[4].TRIP_FB) IS MAPPED TO THIS
3E4DS0-SE-EVS-SE-030000_TRIP_FB As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed DI SEECO_AENTR1:0:I.8
CHANNEL,SEECO_AENTR1:0:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
9 TRIP STATUS SMOKE EXHAUST FAN SEECO 3E4DS0-SE-BMS-RIOP-000011 SDI-1 AENTR1 0 1XSDI1 : 17,18 - SDI-16 8 AENTR1:0:I.8 I 4/19/2025 DONE
3E4DS0-SE-EVS-SE-030000
SIGNAL, 3E4DS0-SE-EVS-SE-040000-Hand/off Smoke Exhaust Fan (SEF_ARR_UDT[4].LOC_FB) IS MAPPED TO THIS
3E4DS0-SE-EVS-SE-030000_LOC_FB As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed DI SEECO_AENTR1:0:I.9
CHANNEL,SEECO_AENTR1:0:I.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
10 HAND/OFF SMOKE EXHAUST FAN SEECO 3E4DS0-SE-BMS-RIOP-000011 SDI-1 AENTR1 0 1XSDI1 : 19,20 - SDI-16 9 AENTR1:0:I.9 I 4/19/2025 DONE
3E4DS0-SE-EVS-SE-030000
SIGNAL 3E4DS0-SE-EVS-SE-040000-Auto/off Smoke Exhaust Fan (SEF_ARR_UDT[4].REM_FB) IS MAPPED TO THIS
3E4DS0-SE-EVS-SE-030000_REM_FB As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed DI SEECO_AENTR1:0:I.10
CHANNEL,SEECO_AENTR1:0:I.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
11 AUTO/OFF SMOKE EXHAUST FAN SEECO 3E4DS0-SE-BMS-RIOP-000011 SDI-1 AENTR1 0 1XSDI1 : 21,22 - SDI-16 10 AENTR1:0:I.10 I 4/19/2025 DONE
3E4DS0-SE-EVS-SE-030000
SIGNAL 3E4DS0-SE-EVS-SE-040000-Running of Smoke Exhaust Fan (SEF_ARR_UDT[4].RUN_FB) IS MAPPED TO THIS
3E4DS0-SE-EVS-SE-030000_RUN_FB As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed DI SEECO_AENTR1:0:I.11
CHANNEL,SEECO_AENTR1:0:I.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
12 RUNNING OF SMOKE EXHAUST FAN SEECO 3E4DS0-SE-BMS-RIOP-000011 SDI-1 AENTR1 0 1XSDI1 : 23,24 - SDI-16 11 AENTR1:0:I.11 I 4/19/2025 DONE
3E4DS0-SE-EVS-SE-040000
SIGNAL, 3E4DS0-SE-EVS-SE-030000-Trip status Smoke Exhaust Fan (SEF_ARR_UDT[3].TRIP_FB) IS MAPPED TO THIS
3E4DS0-SE-EVS-SE-040000_TRIP_FB As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed SEECO_AENTR2:0:I.0
CHANNEL,SEECO_AENTR2:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
17 TRIP STATUS SMOKE EXHAUST FAN SEECO 3E4DS0-SE-BMS-RIOP-000011 SDI-2 AENTR2 0 1XSDI2 : 1,2 - SDI-16 0 AENTR2:0:I.0 DI I 4/19/2025 DONE
3E4DS0-SE-EVS-SE-040000
SIGNAL, 3E4DS0-SE-EVS-SE-030000-Hand/off Smoke Exhaust Fan (SEF_ARR_UDT[3].LOC_FB) IS MAPPED TO THIS
3E4DS0-SE-EVS-SE-040000_LOC_FB As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed SEECO_AENTR2:0:I.1
CHANNEL,SEECO_AENTR2:0:I.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
18 HAND/OFF SMOKE EXHAUST FAN SEECO 3E4DS0-SE-BMS-RIOP-000011 SDI-2 AENTR2 0 1XSDI2 : 3,4 - SDI-16 1 AENTR2:0:I.1 DI I 4/19/2025 DONE
3E4DS0-SE-EVS-SE-040000
SIGNAL, 3E4DS0-SE-EVS-SE-030000-Auto/off Smoke Exhaust Fan (SEF_ARR_UDT[3].REM_FB) IS MAPPED TO THIS
3E4DS0-SE-EVS-SE-040000_REM_FB As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed SEECO_AENTR2:0:I.2
CHANNEL,SEECO_AENTR2:0:I.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
19 AUTO/OFF SMOKE EXHAUST FAN SEECO 3E4DS0-SE-BMS-RIOP-000011 SDI-2 AENTR2 0 1XSDI2 : 5,6 - SDI-16 2 AENTR2:0:I.2 DI I 4/19/2025 DONE
3E4DS0-SE-EVS-SE-040000
SIGNAL, 3E4DS0-SE-EVS-SE-030000-Running of Smoke Exhaust Fan (SEF_ARR_UDT[3].RUN_FB) IS MAPPED TO THIS
3E4DS0-SE-EVS-SE-040000_RUN_FB As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed SEECO_AENTR2:0:I.3
CHANNEL,SEECO_AENTR2:0:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
20 RUNNING OF SMOKE EXHAUST FAN SEECO 3E4DS0-SE-BMS-RIOP-000011 SDI-2 AENTR2 0 1XSDI2 : 7,8 - SDI-16 3 AENTR2:0:I.3 DI I 4/19/2025 DONE

# General
PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM

DOCUMENT TITLE SHOP DRAWING-DEEP UNDERGROUND STATION-3E4-BMS-INPUT/OUTPUT SCHEDULE

DOCUMENT NO. M-ANM-3E4DS0-CJ00-SCH-000002

MODULE RELAY MODULE CHANNE


SR. NO. EQUIPMENT TAG PLC TAG EASA SITE Response RLM COMMENTS FROM CWG DESCRIPTION PANEL SHORT TAG (OLD) PANEL FULL TAG (NEW) RACK NO. SLOT NO. TERMINAL NO. PLC IO ADDRESS MODULE ID DATE STATUS
ID NO. TYPE L NO.

SEECO_AENTR2:0:I.5
SIGNAL, 3E4DS0-CO01-EVS-MFD-101137_OPN_FB_DOOR (EVS_FD_ARR_UDT[1].OPN_FB) IS MAPPED TO THIS
22 3E4DS0-CO01-EVS-MFD-101137 3E4DS0-CO01-EVS-MFD-101137_OPN_FB CHANNEL,SEECO_AENTR2:0:I.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed SEECO 3E4DS0-SE-BMS-RIOP-000011 SDI-2 AENTR2 0 1XSDI2 : 11,12 - SDI-16 5 AENTR2:0:I.5 DI I 4/19/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,EXTRA CABLE IS CONNECTED TO THIS CHANNEL.IT NEED TO
SEECO_AENTR2:0:I.7
24 SPARE SPARE BE REMOVED. As per CWG RLM, this channel is used at site, please check. SPARE SEECO 3E4DS0-SE-BMS-RIOP-000011 SDI-2 AENTR2 0 1XSDI2 : 15,16 - SDI-16 7 AENTR2:0:I.7 DI I 4/19/2025 DONE
32 3E4DS0-SE-BMS-RIOP-000011 3E4DS0-SE-BMS-SEECO-000000_SEECO_PWR_SPLY1_FAIL SIGNAL 3E4DS0-SE-BMS-SEECO-000000_SEECO_PWR_SPLY1_FAIL IS MAPPED TO THIS CHANNEL,SEECO_AENTR2:0:I.15.IN As
SITE
per
ALSO,IT
CWG RLM,
IS CONNECTED
Cable tag/ferrule
TO THEisSAME
not available,
SIGNAL. terminated cable to be identify at site and mapped
POWERsignal to be
SUPPLY confirmed
FAILURE ALARM SEECO 3E4DS0-SE-BMS-RIOP-000011 SDI-2 AENTR2 0 1XSDI2 : 31,32 - SDI-16 15 AENTR2:0:I.15 DI SEECO_AENTR2:0:I.15 I 4/19/2025 DONE

As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed SEECO_AENTR1:1:O.0
SIGNAL 3E4DS0-SE-EVS-SEDPS-100001_ON_OFF_COMMAND (SEF_ARR_UDT[12].ON_OFF_CMD) IS MAPPED TO THIS
33 3E4DS0-SE-EVS-SE-100000 3E4DS0-SE-EVS-SE-100000_ON_OFF_CMD RELAY,SEECO_AENTR1:1:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. START/STOP SMOKE EXHAUST FAN SEECO 3E4DS0-SE-BMS-RIOP-000011 SDO-1 AENTR1 1 - 1SR1 : 11,14 SDO-16 0 AENTR1:1:O.0 DO O 4/19/2025 DONE

SIGNAL 3E4DS0-SE-EVS-SE-040000_ON_OFF_COMMAND (SEF_ARR_UDT[4].ON_OFF_CMD) IS MAPPED TO THIS As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed SEECO_AENTR1:1:O.1
34 3E4DS0-SE-EVS-SE-030000 3E4DS0-SE-EVS-SE-030000_ON_OFF_CMD RELAY,SEECO_AENTR1:1:O.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. START/STOP SMOKE EXHAUST FAN SEECO 3E4DS0-SE-BMS-RIOP-000011 SDO-1 AENTR1 1 - 1SR2 : 11,14 SDO-16 1 AENTR1:1:O.1 DO O 4/19/2025 DONE

As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed SEECO_AENTR1:1:O.2
SIGNAL 3E4DS0-SE-EVS-SE-030000_ON_OFF_COMMAND (SEF_ARR_UDT[3].ON_OFF_CMD) IS MAPPED TO THIS
35 3E4DS0-SE-EVS-SE-040000 3E4DS0-SE-EVS-SE-040000_ON_OFF_CMD RELAY,SEECO_AENTR1:1:O.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. START/STOP SMOKE EXHAUST FAN SEECO 3E4DS0-SE-BMS-RIOP-000011 SDO-1 AENTR1 1 - 1SR3 : 11,14 SDO-16 2 AENTR1:1:O.2 DO O 4/19/2025 DONE

As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped signal to be confirmed SEECO_AENTR1:1:O.3
SIGNAL 3E4DS0-CO01-EVS-MFD-101137_OPN_FB_DOOR (EVS_FD_ARR_UDT[1].OPN_CLS_CMD) IS MAPPED TO THIS
36 3E4DS0-CO01-EVS-MFD-101137 3E4DS0-CO01-EVS-MFD-101137_OPN_CLS_CMD RELAY,SEECO_AENTR1:1:O.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. OPEN COMMAND SEECO 3E4DS0-SE-BMS-RIOP-000011 SDO-1 AENTR1 1 - 1SR4 : 11,14 SDO-16 3 AENTR1:1:O.3 DO O 4/19/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,EXTRA CABLE IS CONNECTED TO THIS CHANNEL.IT NEED TO
SEECO_AENTR1:1:O.8
41 SPARE SPARE BE REMOVED. As per CWG RLM, this channel is used at site, please check. SPARE SEECO 3E4DS0-SE-BMS-RIOP-000011 SDO-1 AENTR1 1 - 1SR9 : 11,14 SDO-16 8 AENTR1:1:O.8 DO O 4/19/2025 DONE

SPWPO_AENTR1:0:I.0
SIGNAL, 3E4DS0-EST02-EVS-MFD-644029_OPN_FB (EVS_FD_ARR_UDT[18].OPN_FB) IS MAPPED TO THIS
1 3E4DS0-EST02-EVS-MFD-644029 3E4DS0-EST02-EVS-MFD-644029_OPN_FB CHANNEL,SPWPO_AENTR1:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed SPWPO 3E4DS0-SP-BMS-RIOP-000027 SDI-1 AENTR1 0 1XSDI1 : 1,2 - SDI-16 0 AENTR1:0:I.0 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-FCC-FDPS-FACP-200004_FACP2_SMOKE_DETECTOR.4
(FACP_ARR_UDT[2].FACP2_SMOKE_DETECTOR.4) IS MAPPED TO THIS CHANNEL,SPWPO_AENTR1:0:I.2.IN SITE SPWPO_AENTR1:0:I.2
3 3E4DS0-FCC-FDPS-FACP-200004 3E4DS0-FCC-FDPS-FACP-200004_FACP2_SMOKE_DETECTOR.4 ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
[FACP-2]
signal
Smoke
to be
Detectors/Manual
confirmed station - Platform (BOH and Not FM-200 rooms)
SPWPO 3E4DS0-SP-BMS-RIOP-000027 SDI-1 AENTR1 0 1XSDI1 : 5,6 - SDI-16 2 AENTR1:0:I.2 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-FCC-FDPS-FACP-200003_FACP2_SMOKE_DETECTOR.5
(FACP_ARR_UDT[2].FACP2_SMOKE_DETECTOR.5) IS MAPPED TO THIS CHANNEL,SPWPO_AENTR1:0:I.3.IN SITE SPWPO_AENTR1:0:I.3
4 3E4DS0-FCC-FDPS-FACP-200003 3E4DS0-FCC-FDPS-FACP-200003_FACP2_SMOKE_DETECTOR.5 ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Smokesignal
Detectors-
to be confirmed
EST-04 SPWPO 3E4DS0-SP-BMS-RIOP-000027 SDI-1 AENTR1 0 1XSDI1 : 7,8 - SDI-16 3 AENTR1:0:I.3 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-FCC-FDPS-FACP-200004_FACP2_SMOKE_DETECTOR.6
(FACP_ARR_UDT[2].FACP2_SMOKE_DETECTOR.6) IS MAPPED TO THIS CHANNEL,SPWPO_AENTR1:0:I.4.IN SITE SPWPO_AENTR1:0:I.4
5 3E4DS0-FCC-FDPS-FACP-200004 3E4DS0-FCC-FDPS-FACP-200004_FACP2_SMOKE_DETECTOR.6 ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
[FACP-2]
signal
Smoke
to be
Detectors/Manual
confirmed station - Underplatform SPWPO 3E4DS0-SP-BMS-RIOP-000027 SDI-1 AENTR1 0 1XSDI1 : 9,10 - SDI-16 4 AENTR1:0:I.4 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-FCC-FDPS-FACP-200001_FACP2_ES_ACT_FB (FACP2_ONBOARD_TRAIN_ON_FIRE_FB) IS MAPPED TO
SPWPO_AENTR1:0:I.5
6 3E4DS0-FCC-FDPS-FACP-200001 3E4DS0-FCC-FDPS-FACP-200001_FACP2_ES_ACT_FB THIS CHANNEL,SPWPO_AENTR1:0:I.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is spare at site, please check. [FACP-TRACK] ACTIVATE STATION EVACUATION DUE TO FIRE ON INCOMING TRAIN
SPWPO 3E4DS0-SP-BMS-RIOP-000027 SDI-1 AENTR1 0 1XSDI1 : 11,12 - SDI-16 5 AENTR1:0:I.5 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-EST02-EVS-MFD-644029_OPN_CLS_CMD (EVS_FD_ARR_UDT[18].OPN_CLS_CMD) IS MAPPED TO THIS
SPWPO_AENTR1:1:O.0
17 3E4DS0-EST02-EVS-MFD-644029 3E4DS0-EST02-EVS-MFD-644029_OPN_CLS_CMD RELAY,SPWPO_AENTR1:1:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN COMMAND
signal to be confirmed SPWPO 3E4DS0-SP-BMS-RIOP-000027 SDO-1 AENTR1 1 - 1SR1 : 11,14 SDO-16 0 AENTR1:1:O.0 DO O 4/19/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,EXTRA CABLE IS CONNECTED TO THIS CHANNEL.IT NEED TO
SPWPO_AENTR1:1:O.1
18 SPARE SPARE BE REMOVED. As per CWG RLM, this channel is used at site, please check. SPARE SPWPO 3E4DS0-SP-BMS-RIOP-000027 SDO-1 AENTR1 1 - 1SR2 : 11,14 SDO-16 1 AENTR1:1:O.1 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-FCC-FDPS-FACP-200001_FACP2_ES_ACT_CMD (FACP_ARR_UDT[2].FACP2_ES_ACT_CMD) IS MAPPED TO
SPWPO_AENTR1:1:O.2
19 3E4DS0-FCC-FDPS-FACP-200001 3E4DS0-FCC-FDPS-FACP-200001_FACP2_ES_ACT_CMD THIS RELAY,SPWPO_AENTR1:1:O.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is spare at site, please check. [FACP-TRACK] ACTIVATE STATION EVACUATION DUE TO FIRE ON INCOMING TRAIN
SPWPO 3E4DS0-SP-BMS-RIOP-000027 SDO-1 AENTR1 1 - 1SR3 : 11,14 SDO-16 2 AENTR1:1:O.2 DO O 4/19/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,EXTRA CABLE IS CONNECTED TO THIS CHANNEL.IT NEED TO
SPWPO_AENTR2:0:I.4
37 SPARE SPARE BE REMOVED. As per CWG RLM, this channel is used at site, please check. SPARE SPWPO 3E4DS0-SP-BMS-RIOP-000027 DI-1 AENTR2 0 1XDI1 : 9,10 - DI-32 4 AENTR2:0:I.Data.4 DI I 4/19/2025 DONE
SIGNAL, MFD 014118_OPN_FB (HVAC_FD_ARR_UDT[85].OPN_FB) IS MAPPED TO THIS
SPWPO_AENTR2:0:I.25
58 SPARE SPARE CHANNEL,SPWPO_AENTR2:0:I.Data.25.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE SPWPO 3E4DS0-SP-BMS-RIOP-000027 DI-1 AENTR2 0 1XDI1 : 25,26 - DI-32 25 AENTR2:0:I.Data.25 DI I 4/19/2025 DONE
SIGNAL, MFD-014134_OPN_FB (HVAC_FD_ARR_UDT[86].OPN_FB) IS MAPPED TO THIS
SPWPO_AENTR2:0:I.26
59 SPARE SPARE CHANNEL,SPWPO_AENTR2:0:I.Data.26.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE SPWPO 3E4DS0-SP-BMS-RIOP-000027 DI-1 AENTR2 0 1XDI1 : 25,26 - DI-32 26 AENTR2:0:I.Data.26 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-WMR-WMS-WMCP-000001_PANEL_HTY_FB2 (WMCP_ARR_UDT[1].PANEL_HTY_FB2) IS MAPPED TO WMREMO_AENTR1:0:I.0


1 3E4DS0-WMR-WMS-WMCP-000001 3E4DS0-WMR-WMS-WMCP-000001_PANEL_HTY_FB2 THIS CHANNEL,WMREMO_AENTR1:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WMS PLC
signal
PANEL
to beHEALTHY
confirmed
STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-1 AENTR1 0 2XSDI1 : 1,2 - SDI-16 0 AENTR1:0:I.0 DI I 4/19/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,EXTRA CABLE IS CONNECTED TO THIS CHANNEL.IT NEED TO
WMREMO_AENTR1:0:I.1
2 SPARE SPARE BE REMOVED. As per CWG RLM, this channel is used at site, please check. SPARE WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-1 AENTR1 0 2XSDI1 : 3,4 - SDI-16 1 AENTR1:0:I.1 DI I 4/19/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,EXTRA CABLE IS CONNECTED TO THIS CHANNEL.IT NEED TO
WMREMO_AENTR1:0:I.3
4 SPARE SPARE BE REMOVED. As per CWG RLM, this channel is used at site, please check. SPARE WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-1 AENTR1 0 2XSDI1 : 7,8 - SDI-16 3 AENTR1:0:I.3 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-WMR-WMS-WMCP-000001-MISTPUMP-2_PMP2_REM_FB (WMCP_ARR_UDT[3].PMP2_REM_FB) IS WMREMO_AENTR1:0:I.4


5 3E4DS0-WMR-WMS-WMCP-000001-MISTPUMP-2 3E4DS0-WMR-WMS-WMCP-000001-MISTPUMP-2_PMP2_REM_FB MAPPED TO THIS CHANNEL,WMREMO_AENTR1:0:I.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalWATER
to be confirmed
MIST PUMP 2 WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-1 AENTR1 0 2XSDI1 : 9,10 - SDI-16 4 AENTR1:0:I.4 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-WMR-WMS-WMCP-000001-MISTPUMP-3_PMP3_REM_FB (WMCP_ARR_UDT[4].PMP3_REM_FB) IS WMREMO_AENTR1:0:I.6


7 3E4DS0-WMR-WMS-WMCP-000001-MISTPUMP-3 3E4DS0-WMR-WMS-WMCP-000001-MISTPUMP-3_PMP3_REM_FB MAPPED TO THIS CHANNEL,WMREMO_AENTR1:0:I.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalWATER
to be confirmed
MIST PUMP 3 WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-1 AENTR1 0 2XSDI1 : 13,14 - SDI-16 6 AENTR1:0:I.6 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-WMR-WMS-WMCP-000001-MISTPUMP-4_PMP4_REM_FB (WMCP_ARR_UDT[5].PMP4_REM_FB) IS WMREMO_AENTR1:0:I.8


9 3E4DS0-WMR-WMS-WMCP-000001-MISTPUMP-4 3E4DS0-WMR-WMS-WMCP-000001-MISTPUMP-4_PMP4_REM_FB MAPPED TO THIS CHANNEL,WMREMO_AENTR1:0:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalWATER
to be confirmed
MIST PUMP 4 WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-1 AENTR1 0 2XSDI1 : 17,18 - SDI-16 8 AENTR1:0:I.8 DI I 4/19/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,EXTRA CABLE IS CONNECTED TO THIS CHANNEL.IT NEED TO
WMREMO_AENTR1:0:I.9
10 SPARE SPARE BE REMOVED. As per CWG RLM, this channel is used at site, please check. SPARE WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-1 AENTR1 0 2XSDI1 : 19,20 - SDI-16 9 AENTR1:0:I.9 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-WMR-WMS-WMCP-000001-MISTPUMP-5_PMP5_REM_FB (WMCP_ARR_UDT[6].PMP5_REM_FB) IS WMREMO_AENTR1:0:I.10


11 3E4DS0-WMR-WMS-WMCP-000001-MISTPUMP-5 3E4DS0-WMR-WMS-WMCP-000001-MISTPUMP-5_PMP5_REM_FB MAPPED TO THIS CHANNEL,WMREMO_AENTR1:0:I.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalWATER
to be confirmed
MIST PUMP 5 WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-1 AENTR1 0 2XSDI1 : 21,22 - SDI-16 10 AENTR1:0:I.10 DI I 4/19/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,EXTRA CABLE IS CONNECTED TO THIS CHANNEL.IT NEED TO
WMREMO_AENTR1:0:I.11
12 SPARE SPARE BE REMOVED. As per CWG RLM, this channel is used at site, please check. SPARE WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-1 AENTR1 0 2XSDI1 : 23,24 - SDI-16 11 AENTR1:0:I.11 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-WMR-WMS-WMCP-000001-MBP_Pump_1_PMP1_REM_FB (WMCP_ARR_UDT[7].PMP1_REM_FB) IS WMREMO_AENTR1:0:I.12


13 3E4DS0-WMR-WMS-WMCP-000001-MBP_Pump_1 3E4DS0-WMR-WMS-WMCP-000001-MBP_Pump_1_PMP1_REM_FB MAPPED TO THIS CHANNEL,WMREMO_AENTR1:0:I.12.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalBOOSTER
to be confirmed
PUMP 1 WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-1 AENTR1 0 2XSDI1 : 25,26 - SDI-16 12 AENTR1:0:I.12 DI I 4/19/2025 DONE

SIGNAL 3E4DS0-WMR-WMS-WMCP-000001-MBP_Pump_2_PMP2_REM_FB (WMCP_ARR_UDT[8].PMP2_REM_FB) IS WMREMO_AENTR1:0:I.14


15 3E4DS0-WMR-WMS-WMCP-000001-MBP_Pump_2 3E4DS0-WMR-WMS-WMCP-000001-MBP_Pump_2_PMP2_REM_FB MAPPED TO THIS CHANNEL,WMREMO_AENTR1:0:I.14.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalBOOSTER
to be confirmed
PUMP 2 WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-1 AENTR1 0 2XSDI1 : 29,30 - SDI-16 14 AENTR1:0:I.14 DI I 4/19/2025 DONE

SIGNAL 3E4DS0-E3TE4-WMS-DV-103100-DV-103100_OPN_CLS_FB (DV_WMS_ARR_UDT[5].OPN_CLS_FB) IS MAPPED TO WMREMO_AENTR1:0:I.15


16 3E4DS0-E3TE4-WMS-DV-103100-DV-103100 3E4DS0-E3TE4-WMS-DV-103100-DV-103100_OPN_CLS_FB THIS CHANNEL,WMREMO_AENTR1:0:I.15.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-1 AENTR1 0 2XSDI1 : 31,32 - SDI-16 15 AENTR1:0:I.15 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E3TE4-WMS-DV-101100-DV-101100_OPN_CLS_FB (DV_WMS_ARR_UDT[1].OPN_CLS_FB) IS MAPPED WMREMO_AENTR2:0:I.0


17 3E4DS0-E3TE4-WMS-DV-101100-DV-101100 3E4DS0-E3TE4-WMS-DV-101100-DV-101100_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR2:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-2 AENTR2 0 2XSDI2 : 1,2 - SDI-16 0 AENTR2:0:I.0 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E3TE4-WMS-DV-103200-DV-103200_OPN_CLS_FB (DV_WMS_ARR_UDT[6].OPN_CLS_FB) IS MAPPED WMREMO_AENTR2:0:I.1


18 3E4DS0-E3TE4-WMS-DV-103200-DV-103200 3E4DS0-E3TE4-WMS-DV-103200-DV-103200_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR2:0:I.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-2 AENTR2 0 2XSDI2 : 3,4 - SDI-16 1 AENTR2:0:I.1 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E3TE4-WMS-DV-105200-DV-105200_OPN_CLS_FB (DV_WMS_ARR_UDT[10].OPN_CLS_FB) IS MAPPED WMREMO_AENTR2:0:I.2


19 3E4DS0-E3TE4-WMS-DV-105200-DV-105200 3E4DS0-E3TE4-WMS-DV-105200-DV-105200_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR2:0:I.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-2 AENTR2 0 2XSDI2 : 5,6 - SDI-16 2 AENTR2:0:I.2 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E4TE5-WMS-DV-201200-DV-201200_OPN_CLS_FB (DV_WMS_ARR_UDT[14].OPN_CLS_FB) IS MAPPED WMREMO_AENTR2:0:I.3


20 3E4DS0-E4TE5-WMS-DV-201200-DV-201200 3E4DS0-E4TE5-WMS-DV-201200-DV-201200_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR2:0:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-2 AENTR2 0 2XSDI2 : 7,8 - SDI-16 3 AENTR2:0:I.3 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E4TE5-WMS-DV-203200-DV-203200_OPN_CLS_FB (DV_WMS_ARR_UDT[18].OPN_CLS_FB) IS MAPPED WMREMO_AENTR2:0:I.4


21 3E4DS0-E4TE5-WMS-DV-203200-DV-203200 3E4DS0-E4TE5-WMS-DV-203200-DV-203200_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR2:0:I.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-2 AENTR2 0 2XSDI2 : 9,10 - SDI-16 4 AENTR2:0:I.4 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E4TE5-WMS-DV-205200-DV-205200_OPN_CLS_FB (DV_WMS_ARR_UDT[22].OPN_CLS_FB) IS MAPPED WMREMO_AENTR2:0:I.5


22 3E4DS0-E4TE5-WMS-DV-205200-DV-205200 3E4DS0-E4TE5-WMS-DV-205200-DV-205200_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR2:0:I.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-2 AENTR2 0 2XSDI2 : 11,12 - SDI-16 5 AENTR2:0:I.5 DI I 4/19/2025 DONE

SIGNAL 3E4DS0-E4TE5-WMS-DV-207200-DV-207200_OPN_CLS_FB (DV_WMS_ARR_UDT[26].OPN_CLS_FB) IS MAPPED WMREMO_AENTR2:0:I.6


23 3E4DS0-E4TE5-WMS-DV-207200-DV-207200 3E4DS0-E4TE5-WMS-DV-207200-DV-207200_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR2:0:I.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-2 AENTR2 0 2XSDI2 : 13,14 - SDI-16 6 AENTR2:0:I.6 DI I 4/19/2025 DONE

SIGNAL 3E4DS0-E4TE5-WMS-DV-209200-DV-209200_OPN_CLS_FB (DV_WMS_ARR_UDT[30].OPN_CLS_FB) IS MAPPED WMREMO_AENTR2:0:I.7


24 3E4DS0-E4TE5-WMS-DV-209200-DV-209200 3E4DS0-E4TE5-WMS-DV-209200-DV-209200_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR2:0:I.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-2 AENTR2 0 2XSDI2 : 15,16 - SDI-16 7 AENTR2:0:I.7 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-WMR-WMS-WMBP-000001_PMP1_TRIP_FB (WMBP_ARR_UDT[1].PMP1_TRIP_FB) IS MAPPED TO THIS
WMREMO_AENTR2:0:I.8
25 3E4DS0-WMR-WMS-WMBP-000001 3E4DS0-WMR-WMS-WMBP-000001_PMP1_TRIP_FB CHANNEL,WMREMO_AENTR2:0:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
BOOSTER
be confirmed
PUMP WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-2 AENTR2 0 2XSDI2 : 17,18 - SDI-16 8 AENTR2:0:I.8 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-WMR-WMS-WMP-000003_PMP1_TRIP_FB (WMP_ARR_UDT[3].PMP1_TRIP_FB) IS MAPPED TO THIS
WMREMO_AENTR2:0:I.9
26 3E4DS0-WMR-WMS-WMP-000003 3E4DS0-WMR-WMS-WMP-000003_PMP1_TRIP_FB CHANNEL,WMREMO_AENTR2:0:I.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
WATER
be confirmed
MIST PUMP WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-2 AENTR2 0 2XSDI2 : 19,20 - SDI-16 9 AENTR2:0:I.9 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-WMR-WMS-WMCP-000001_PANEL_HTY_FB1 (WMCP_ARR_UDT[1].PANEL_HTY_FB1) IS MAPPED TO
THIS CHANNEL,WMREMO_AENTR2:0:I.10,IN LOGIX ONLY.IN SITE,SINCE IS NO SIGNAL PROVISION,CABLE IS NOT WMREMO_AENTR2:0:I.10
27 3E4DS0-WMR-WMS-WMCP-000001 3E4DS0-WMR-WMS-WMCP-000001_PANEL_HTY_FB1 CONNECTED TO THIS TERMINAL. As per CWG RLM, this channel is spare at site, please check. PANEL HEALTHY STATUS -PBD WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-2 AENTR2 0 2XSDI2 : 21,22 - SDI-16 10 AENTR2:0:I.10 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E3TE4-WMS-DV-101200-DV-101200_OPN_CLS_FB (DV_WMS_ARR_UDT[2].OPN_CLS_FB) IS MAPPED WMREMO_AENTR1:1:I.0


33 3E4DS0-E3TE4-WMS-DV-101200-DV-101200 3E4DS0-E3TE4-WMS-DV-101200-DV-101200_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR1:1:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-3 AENTR1 1 2XSDI3 : 1,2 - SDI-16 0 AENTR1:1:I.0 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E3TE4-WMS-DV-104100-DV-104100_OPN_CLS_FB (DV_WMS_ARR_UDT[7].OPN_CLS_FB) IS MAPPED WMREMO_AENTR1:1:I.1


34 3E4DS0-E3TE4-WMS-DV-104100-DV-104100 3E4DS0-E3TE4-WMS-DV-104100-DV-104100_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR1:1:I.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-3 AENTR1 1 2XSDI3 : 3,4 - SDI-16 1 AENTR1:1:I.1 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E3TE4-WMS-DV-106100-DV-106100_OPN_CLS_FB (DV_WMS_ARR_UDT[11].OPN_CLS_FB) IS MAPPED WMREMO_AENTR1:1:I.2


35 3E4DS0-E3TE4-WMS-DV-106100-DV-106100 3E4DS0-E3TE4-WMS-DV-106100-DV-106100_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR1:1:I.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-3 AENTR1 1 2XSDI3 : 5,6 - SDI-16 2 AENTR1:1:I.2 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E4TE5-WMS-DV-202100-DV-202100_OPN_CLS_FB (DV_WMS_ARR_UDT[15].OPN_CLS_FB) IS MAPPED WMREMO_AENTR1:1:I.3


36 3E4DS0-E4TE5-WMS-DV-202100-DV-202100 3E4DS0-E4TE5-WMS-DV-202100-DV-202100_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR1:1:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-3 AENTR1 1 2XSDI3 : 7,8 - SDI-16 3 AENTR1:1:I.3 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E4TE5-WMS-DV-204100-DV-204100_OPN_CLS_FB (DV_WMS_ARR_UDT[19].OPN_CLS_FB) IS MAPPED WMREMO_AENTR1:1:I.4


37 3E4DS0-E4TE5-WMS-DV-204100-DV-204100 3E4DS0-E4TE5-WMS-DV-204100-DV-204100_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR1:1:I.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-3 AENTR1 1 2XSDI3 : 9,10 - SDI-16 4 AENTR1:1:I.4 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E4TE5-WMS-DV-206100-DV-206100_OPN_CLS_FB (DV_WMS_ARR_UDT[23].OPN_CLS_FB) IS MAPPED WMREMO_AENTR1:1:I.5


38 3E4DS0-E4TE5-WMS-DV-206100-DV-206100 3E4DS0-E4TE5-WMS-DV-206100-DV-206100_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR1:1:I.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-3 AENTR1 1 2XSDI3 : 11,12 - SDI-16 5 AENTR1:1:I.5 DI I 4/19/2025 DONE

SIGNAL 3E4DS0-E4TE5-WMS-DV-208100-DV-208100_OPN_CLS_FB (DV_WMS_ARR_UDT[27].OPN_CLS_FB) IS MAPPED WMREMO_AENTR1:1:I.6


39 3E4DS0-E4TE5-WMS-DV-208100-DV-208100 3E4DS0-E4TE5-WMS-DV-208100-DV-208100_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR1:1:I.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-3 AENTR1 1 2XSDI3 : 13,14 - SDI-16 6 AENTR1:1:I.6 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-CO-EVS-MFD-103144_OPN_CLS_FB (EVS_FD_ARR_UDT[6].OPN_FB) IS MAPPED TO THIS
WMREMO_AENTR1:1:I.7
40 3E4DS0-CO-EVS-MFD-103144 3E4DS0-CO-EVS-MFD-103144_OPN_CLS_FB CHANNEL,WMREMO_AENTR1:1:I.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN DAMPER
signal to be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-3 AENTR1 1 2XSDI3 : 15,16 - SDI-16 7 AENTR1:1:I.7 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-WMR-WMS-WMBP-000002_PMP1_TRIP_FB (WMBP_ARR_UDT[2].PMP1_TRIP_FB) IS MAPPED TO THIS
WMREMO_AENTR1:1:I.8
41 3E4DS0-WMR-WMS-WMBP-000002 3E4DS0-WMR-WMS-WMBP-000002_PMP1_TRIP_FB CHANNEL,WMREMO_AENTR1:1:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
BOOSTER
be confirmed
PUMP WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-3 AENTR1 1 2XSDI3 : 17,18 - SDI-16 8 AENTR1:1:I.8 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-WMR-WMS-WMP-000004_PMP1_TRIP_FB (WMP_ARR_UDT[4].PMP1_TRIP_FB) IS MAPPED TO THIS
WMREMO_AENTR1:1:I.9
42 3E4DS0-WMR-WMS-WMP-000004 3E4DS0-WMR-WMS-WMP-000004_PMP1_TRIP_FB CHANNEL,WMREMO_AENTR1:1:I.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
WATER
be confirmed
MIST PUMP WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-3 AENTR1 1 2XSDI3 : 19,20 - SDI-16 9 AENTR1:1:I.9 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-CO-EVS-MFD-103144_CLS_FB_DOOR1 (EVS_FD_ARR_UDT[6].CLS_FB_DOOR1) IS MAPPED TO THIS
WMREMO_AENTR1:1:I.10
43 3E4DS0-CO-EVS-MFD-103144 3E4DS0-CO-EVS-MFD-103144_CLS_FB_DOOR1 CHANNEL,WMREMO_AENTR1:1:I.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
DOOR signal
CLOSEto
STATUS
be confirmed
-1 WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-3 AENTR1 1 2XSDI3 : 21,22 - SDI-16 10 AENTR1:1:I.10 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-CO-EVS-MFD-103144_CLS_FB_DOOR2 (EVS_FD_ARR_UDT[6].CLS_FB_DOOR2) IS MAPPED TO THIS
WMREMO_AENTR1:1:I.11
44 3E4DS0-CO-EVS-MFD-103144 3E4DS0-CO-EVS-MFD-103144_CLS_FB_DOOR2 CHANNEL,WMREMO_AENTR1:1:I.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
DOOR signal
CLOSEto
STATUS
be confirmed
-2 WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-3 AENTR1 1 2XSDI3 : 23,24 - SDI-16 11 AENTR1:1:I.11 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E3TE4-WMS-DV-102100-DV-102100_OPN_CLS_FB (DV_WMS_ARR_UDT[3].OPN_CLS_FB) IS MAPPED WMREMO_AENTR2:1:I.0


49 3E4DS0-E3TE4-WMS-DV-102100-DV-102100 3E4DS0-E3TE4-WMS-DV-102100-DV-102100_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR2:1:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-4 AENTR2 1 2XSDI4 : 1,2 - SDI-16 0 AENTR2:1:I.0 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E3TE4-WMS-DV-104200-DV-104200_OPN_CLS_FB (DV_WMS_ARR_UDT[8].OPN_CLS_FB) IS MAPPED WMREMO_AENTR2:1:I.1


50 3E4DS0-E3TE4-WMS-DV-104200-DV-104200 3E4DS0-E3TE4-WMS-DV-104200-DV-104200_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR2:1:I.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-4 AENTR2 1 2XSDI4 : 3,4 - SDI-16 1 AENTR2:1:I.1 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E3TE4-WMS-DV-106200-DV-106200_OPN_CLS_FB (DV_WMS_ARR_UDT[12].OPN_CLS_FB) IS MAPPED WMREMO_AENTR2:1:I.2


51 3E4DS0-E3TE4-WMS-DV-106200-DV-106200 3E4DS0-E3TE4-WMS-DV-106200-DV-106200_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR2:1:I.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-4 AENTR2 1 2XSDI4 : 5,6 - SDI-16 2 AENTR2:1:I.2 DI I 4/19/2025 DONE

# General
PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM

DOCUMENT TITLE SHOP DRAWING-DEEP UNDERGROUND STATION-3E4-BMS-INPUT/OUTPUT SCHEDULE

DOCUMENT NO. M-ANM-3E4DS0-CJ00-SCH-000002

MODULE RELAY MODULE CHANNE


SR. NO. EQUIPMENT TAG PLC TAG EASA SITE Response RLM COMMENTS FROM CWG DESCRIPTION PANEL SHORT TAG (OLD) PANEL FULL TAG (NEW) RACK NO. SLOT NO. TERMINAL NO. PLC IO ADDRESS MODULE ID DATE STATUS
ID NO. TYPE L NO.

SIGNAL, 3E4DS0-E4TE5-WMS-DV-202200-DV-202200_OPN_CLS_FB (DV_WMS_ARR_UDT[16].OPN_CLS_FB) IS MAPPED WMREMO_AENTR2:1:I.3


52 3E4DS0-E4TE5-WMS-DV-202200-DV-202200 3E4DS0-E4TE5-WMS-DV-202200-DV-202200_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR2:1:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-4 AENTR2 1 2XSDI4 : 7,8 - SDI-16 3 AENTR2:1:I.3 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E4TE5-WMS-DV-204200-DV-204200_OPN_CLS_FB (DV_WMS_ARR_UDT[20].OPN_CLS_FB) IS MAPPED WMREMO_AENTR2:1:I.4


53 3E4DS0-E4TE5-WMS-DV-204200-DV-204200 3E4DS0-E4TE5-WMS-DV-204200-DV-204200_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR2:1:I.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-4 AENTR2 1 2XSDI4 : 9,10 - SDI-16 4 AENTR2:1:I.4 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E4TE5-WMS-DV-206200-DV-206200_OPN_CLS_FB (DV_WMS_ARR_UDT[24].OPN_CLS_FB) IS MAPPED WMREMO_AENTR2:1:I.5


54 3E4DS0-E4TE5-WMS-DV-206200-DV-206200 3E4DS0-E4TE5-WMS-DV-206200-DV-206200_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR2:1:I.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-4 AENTR2 1 2XSDI4 : 11,12 - SDI-16 5 AENTR2:1:I.5 DI I 4/19/2025 DONE

SIGNAL 3E4DS0-E4TE5-WMS-DV-208200-DV-208200_OPN_CLS_FB (DV_WMS_ARR_UDT[28].OPN_CLS_FB) IS MAPPED WMREMO_AENTR2:1:I.6


55 3E4DS0-E4TE5-WMS-DV-208200-DV-208200 3E4DS0-E4TE5-WMS-DV-208200-DV-208200_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR2:1:I.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-4 AENTR2 1 2XSDI4 : 13,14 - SDI-16 6 AENTR2:1:I.6 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-WMR-WMS-WMT-000001_TANK_1_LVL_L (WMT_ARR_UDT[1].TANK_1_LVL_L) IS MAPPED TO THIS
CHANNEL,WMREMO_AENTR2:1:I.7,IN LOGIX ONLY.IN SITE ,SINCE THERE IS NO SIGNAL PROVISION.CABLE IS NOT WMREMO_AENTR2:1:I.7
56 3E4DS0-WMR-WMS-WMT-000001 3E4DS0-WMR-WMS-WMT-000001_TANK_1_LVL_L CONNECTED TO THIS TERMINAL. As per CWG RLM, this channel is spare at site, please check. LOW LEVEL WATER TANK WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-4 AENTR2 1 2XSDI4 : 15,16 - SDI-16 7 AENTR2:1:I.7 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-WMR-WMS-WMT-000001_TANK_1_LVL_H (WMT_ARR_UDT[1].TANK_1_LVL_H) IS MAPPED TO THIS
WMREMO_AENTR2:1:I.8
57 3E4DS0-WMR-WMS-WMT-000001 3E4DS0-WMR-WMS-WMT-000001_TANK_1_LVL_H CHANNEL,WMREMO_AENTR2:1:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HIGH LEVEL
signalWATER
to be confirmed
TANK WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-4 AENTR2 1 2XSDI4 : 17,18 - SDI-16 8 AENTR2:1:I.8 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-WMR-WMS-WMP-000001_PMP1_TRIP_FB (WMP_ARR_UDT[1].PMP1_TRIP_FB) IS MAPPED TO THIS
WMREMO_AENTR2:1:I.9
58 3E4DS0-WMR-WMS-WMP-000001 3E4DS0-WMR-WMS-WMP-000001_PMP1_TRIP_FB CHANNEL,WMREMO_AENTR2:1:I.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
WATER
be confirmed
MIST PUMP WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-4 AENTR2 1 2XSDI4 : 19,20 - SDI-16 9 AENTR2:1:I.9 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-WMR-WMS-WMP-000005_PMP1_TRIP_FB (WMP_ARR_UDT[5].PMP1_TRIP_FB) IS MAPPED TO THIS
WMREMO_AENTR2:1:I.10
59 3E4DS0-WMR-WMS-WMP-000005 3E4DS0-WMR-WMS-WMP-000005_PMP1_TRIP_FB CHANNEL,WMREMO_AENTR2:1:I.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
WATER
be confirmed
MIST PUMP WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-4 AENTR2 1 2XSDI4 : 21,22 - SDI-16 10 AENTR2:1:I.10 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-WMR-WMS-WMVLV-000001-V_VLV_OPN_FB (WMT_VALVE_ARR_UDT[1].OPN_FB) IS MAPPED TO THIS
CHANNEL,WMREMO_AENTR2:1:I.11,IN LOGIX ONLY.IN SITE ,SINCE THERE IS NO SIGNAL PROVISION.CABLE IS NOT WMREMO_AENTR2:1:I.11
60 3E4DS0-WMR-WMS-WMVLV-000001-V 3E4DS0-WMR-WMS-WMVLV-000001-V_VLV_OPN_FB CONNECTED TO THIS TERMINAL. As per CWG RLM, this channel is spare at site, please check. WMT SUPPLY VALVE STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-4 AENTR2 1 2XSDI4 : 23,24 - SDI-16 11 AENTR2:1:I.11 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E3TE4-WMS-DV-102200-DV-102200_OPN_CLS_FB (DV_WMS_ARR_UDT[4].OPN_CLS_FB) IS MAPPED WMREMO_AENTR1:2:I.0


65 3E4DS0-E3TE4-WMS-DV-102200-DV-102200 3E4DS0-E3TE4-WMS-DV-102200-DV-102200_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR1:2:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-5 AENTR1 2 2XSDI5 : 1,2 - SDI-16 0 AENTR1:2:I.0 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E3TE4-WMS-DV-105100-DV-105100_OPN_CLS_FB (DV_WMS_ARR_UDT[9].OPN_CLS_FB) IS MAPPED WMREMO_AENTR1:2:I.1


66 3E4DS0-E3TE4-WMS-DV-105100-DV-105100 3E4DS0-E3TE4-WMS-DV-105100-DV-105100_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR1:2:I.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-5 AENTR1 2 2XSDI5 : 3,4 - SDI-16 1 AENTR1:2:I.1 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E4TE5-WMS-DV-201100-DV-201100_OPN_CLS_FB (DV_WMS_ARR_UDT[13].OPN_CLS_FB) IS MAPPED WMREMO_AENTR1:2:I.2


67 3E4DS0-E4TE5-WMS-DV-201100-DV-201100 3E4DS0-E4TE5-WMS-DV-201100-DV-201100_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR1:2:I.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-5 AENTR1 2 2XSDI5 : 5,6 - SDI-16 2 AENTR1:2:I.2 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E4TE5-WMS-DV-203100-DV-203100_OPN_CLS_FB (DV_WMS_ARR_UDT[17].OPN_CLS_FB) IS MAPPED WMREMO_AENTR1:2:I.3


68 3E4DS0-E4TE5-WMS-DV-203100-DV-203100 3E4DS0-E4TE5-WMS-DV-203100-DV-203100_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR1:2:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-5 AENTR1 2 2XSDI5 : 7,8 - SDI-16 3 AENTR1:2:I.3 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E4TE5-WMS-DV-205100-DV-205100_OPN_CLS_FB (DV_WMS_ARR_UDT[21].OPN_CLS_FB) IS MAPPED WMREMO_AENTR1:2:I.4


69 3E4DS0-E4TE5-WMS-DV-205100-DV-205100 3E4DS0-E4TE5-WMS-DV-205100-DV-205100_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR1:2:I.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-5 AENTR1 2 2XSDI5 : 9,10 - SDI-16 4 AENTR1:2:I.4 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-E4TE5-WMS-DV-207100-DV-207100_OPN_CLS_FB (DV_WMS_ARR_UDT[25].OPN_CLS_FB) IS MAPPED WMREMO_AENTR1:2:I.5


70 3E4DS0-E4TE5-WMS-DV-207100-DV-207100 3E4DS0-E4TE5-WMS-DV-207100-DV-207100_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR1:2:I.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-5 AENTR1 2 2XSDI5 : 11,12 - SDI-16 5 AENTR1:2:I.5 DI I 4/19/2025 DONE

SIGNAL 3E4DS0-E4TE5-WMS-DV-209100-DV-209100_OPN_CLS_FB (DV_WMS_ARR_UDT[29].OPN_CLS_FB) IS MAPPED WMREMO_AENTR1:2:I.6


71 3E4DS0-E4TE5-WMS-DV-209100-DV-209100 3E4DS0-E4TE5-WMS-DV-209100-DV-209100_OPN_CLS_FB TO THIS CHANNEL,WMREMO_AENTR1:2:I.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN /CLOSE
signal toVALVE
be confirmed
TRACK STATUS WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-5 AENTR1 2 2XSDI5 : 13,14 - SDI-16 6 AENTR1:2:I.6 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-PLT02-MES-LDR-000002-TRACK1DPE_LADDER_MOVED_FB (LDR_ARR_UDT[2].LADDER_MOVED_FB) IS
MAPPED TO THIS CHANNEL,WMREMO_AENTR1:2:I.7,IN LOGIX ONLY.IN SITE ,SINCE THERE IS NO SIGNAL LEDDER MOVED FEEDBACK WMREMO_AENTR1:2:I.7
72 3E4DS0-PLT02-MES-LDR-000002-TRACK1DPE 3E4DS0-PLT02-MES-LDR-000002-TRACK1DPE_LADDER_MOVED_FB PROVISION,CABLE IS NOT CONNECTED TO THIS TERMINAL. As per CWG RLM, this channel is spare at site, please check. WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-5 AENTR1 2 2XSDI5 : 15,16 - SDI-16 7 AENTR1:2:I.7 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-WMR-WMS-WMP-000002_PMP1_TRIP_FB (WMP_ARR_UDT[2].PMP1_TRIP_FB) IS MAPPED TO THIS
WMREMO_AENTR1:2:I.8
73 3E4DS0-WMR-WMS-WMP-000002 3E4DS0-WMR-WMS-WMP-000002_PMP1_TRIP_FB CHANNEL,WMREMO_AENTR1:2:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
WATER
be confirmed
MIST PUMP WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDI-5 AENTR1 2 2XSDI5 : 17,18 - SDI-16 8 AENTR1:2:I.8 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-101100-DV-101100_OPN_CMD (DV_WMS_ARR_UDT[1].OPN_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:2:O.0
81 3E4DS0-E3TE4-WMS-DV-101100-DV-101100 3E4DS0-E3TE4-WMS-DV-101100-DV-101100_OPN_CMD RELAY,WMREMO_AENTR2:2:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-1 AENTR2 2 - 2SR1 : 11,14 SDO-16 0 AENTR2:2:O.0 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-101100-DV-101100_CLS_CMD (DV_WMS_ARR_UDT[1].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:2:O.1
82 3E4DS0-E3TE4-WMS-DV-101100-DV-101100 3E4DS0-E3TE4-WMS-DV-101100-DV-101100_CLS_CMD RELAY,WMREMO_AENTR2:2:O.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-1 AENTR2 2 - 2SR2 : 11,14 SDO-16 1 AENTR2:2:O.1 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-103200-DV-103200_OPN_CMD (DV_WMS_ARR_UDT[6].OPN_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:2:O.2
83 3E4DS0-E3TE4-WMS-DV-103200-DV-103200 3E4DS0-E3TE4-WMS-DV-103200-DV-103200_OPN_CMD RELAY,WMREMO_AENTR2:2:O.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-1 AENTR2 2 - 2SR3 : 11,14 SDO-16 2 AENTR2:2:O.2 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-103200-DV-103200_CLS_CMD (DV_WMS_ARR_UDT[6].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:2:O.3
84 3E4DS0-E3TE4-WMS-DV-103200-DV-103200 3E4DS0-E3TE4-WMS-DV-103200-DV-103200_CLS_CMD RELAY,WMREMO_AENTR2:2:O.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-1 AENTR2 2 - 2SR4 : 11,14 SDO-16 3 AENTR2:2:O.3 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-106100-DV-106100_OPN_CMD (DV_WMS_ARR_UDT[11].OPN_CMD) IS MAPPED TO
WMREMO_AENTR2:2:O.4
85 3E4DS0-E3TE4-WMS-DV-106100-DV-106100 3E4DS0-E3TE4-WMS-DV-106100-DV-106100_OPN_CMD THIS RELAY,WMREMO_AENTR2:2:O.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-1 AENTR2 2 - 2SR5 : 11,14 SDO-16 4 AENTR2:2:O.4 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-106100-DV-106100_CLS_CMD (DV_WMS_ARR_UDT[11].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:2:O.5
86 3E4DS0-E3TE4-WMS-DV-106100-DV-106100 3E4DS0-E3TE4-WMS-DV-106100-DV-106100_CLS_CMD RELAY,WMREMO_AENTR2:2:O.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-1 AENTR2 2 - 2SR6 : 11,14 SDO-16 5 AENTR2:2:O.5 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-202200-DV-202200_OPN_CMD (DV_WMS_ARR_UDT[16].OPN_CMD) IS MAPPED TO
WMREMO_AENTR2:2:O.6
87 3E4DS0-E4TE5-WMS-DV-202200-DV-202200 3E4DS0-E4TE5-WMS-DV-202200-DV-202200_OPN_CMD THIS RELAY,WMREMO_AENTR2:2:O.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-1 AENTR2 2 - 2SR7 : 11,14 SDO-16 6 AENTR2:2:O.6 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-202200-DV-202200_CLS_CMD (DV_WMS_ARR_UDT[16].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:2:O.7
88 3E4DS0-E4TE5-WMS-DV-202200-DV-202200 3E4DS0-E4TE5-WMS-DV-202200-DV-202200_CLS_CMD RELAY,WMREMO_AENTR2:2:O.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-1 AENTR2 2 - 2SR8 : 11,14 SDO-16 7 AENTR2:2:O.7 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-106100-DV-106100_OPN_CMD (DV_WMS_ARR_UDT[21].OPN_CMD) IS MAPPED TO
WMREMO_AENTR2:2:O.8
89 3E4DS0-E4TE5-WMS-DV-205100-DV-205100 3E4DS0-E4TE5-WMS-DV-205100-DV-205100_OPN_CMD THIS RELAY,WMREMO_AENTR2:2:O.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-1 AENTR2 2 - 2SR9 : 11,14 SDO-16 8 AENTR2:2:O.8 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-106100-DV-106100_CLS_CMD (DV_WMS_ARR_UDT[21].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:2:O.9
90 3E4DS0-E4TE5-WMS-DV-205100-DV-205100 3E4DS0-E4TE5-WMS-DV-205100-DV-205100_CLS_CMD RELAY,WMREMO_AENTR2:2:O.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-1 AENTR2 2 - 2SR10 : 11,14 SDO-16 9 AENTR2:2:O.9 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-202200-DV-202200_OPN_CMD (DV_WMS_ARR_UDT[26].OPN_CMD) IS MAPPED TO
WMREMO_AENTR2:2:O.10
91 3E4DS0-E4TE5-WMS-DV-207200-DV-207200 3E4DS0-E4TE5-WMS-DV-207200-DV-207200_OPN_CMD THIS RELAY,WMREMO_AENTR2:2:O.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-1 AENTR2 2 - 2SR11 : 11,14 SDO-16 10 AENTR2:2:O.10 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-202200-DV-202200_CLS_CMD (DV_WMS_ARR_UDT[26].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:2:O.11
92 3E4DS0-E4TE5-WMS-DV-207200-DV-207200 3E4DS0-E4TE5-WMS-DV-207200-DV-207200_CLS_CMD RELAY,WMREMO_AENTR2:2:O.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-1 AENTR2 2 - 2SR12 : 11,14 SDO-16 11 AENTR2:2:O.11 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-205100-DV-205100_OPN_CMD (EVS_FD_ARR_UDT[6].OPN_CLS_CMD) IS MAPPED TO
WMREMO_AENTR2:2:O.12
93 3E4DS0-CO-EVS-MFD-103144 3E4DS0-CO-EVS-MFD-103144_OPN_CLS_CMD THIS RELAY,WMREMO_AENTR2:2:O.12.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN COMMAND
signal to be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-1 AENTR2 2 - 2SR13 : 11,14 SDO-16 12 AENTR2:2:O.12 DO O 4/19/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS RELAY.IN SITE,EXTRA CABLE IS CONNECTED TO THIS RELAY.IT NEED TO BE WMREMO_AENTR2:2:O.13
94 SPARE SPARE REMOVED. As per CWG RLM, this channel is used at site, please check. SPARE WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-1 AENTR2 2 - 2SR14 : 11,14 SDO-16 13 AENTR2:2:O.13 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-101200-DV-101200_OPN_CMD (DV_WMS_ARR_UDT[2].OPN_CMD) IS MAPPED TO THIS
WMREMO_AENTR1:3:O.0
97 3E4DS0-E3TE4-WMS-DV-101200-DV-101200 3E4DS0-E3TE4-WMS-DV-101200-DV-101200_OPN_CMD RELAY,WMREMO_AENTR1:3:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-2 AENTR1 3 - 2SR17 : 11,14 SDO-16 0 AENTR1:3:O.0 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-101200-DV-101200_CLS_CMD (DV_WMS_ARR_UDT[2].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR1:3:O.1
98 3E4DS0-E3TE4-WMS-DV-101200-DV-101200 3E4DS0-E3TE4-WMS-DV-101200-DV-101200_CLS_CMD RELAY,WMREMO_AENTR1:3:O.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-2 AENTR1 3 - 2SR18 : 11,14 SDO-16 1 AENTR1:3:O.1 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-104100-DV-104100_OPN_CMD (DV_WMS_ARR_UDT[7].OPN_CMD) IS MAPPED TO THIS
WMREMO_AENTR1:3:O.2
99 3E4DS0-E3TE4-WMS-DV-104100-DV-104100 3E4DS0-E3TE4-WMS-DV-104100-DV-104100_OPN_CMD RELAY,WMREMO_AENTR1:3:O.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-2 AENTR1 3 - 2SR19 : 11,14 SDO-16 2 AENTR1:3:O.2 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-104100-DV-104100_CLS_CMD (DV_WMS_ARR_UDT[7].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR1:3:O.3
100 3E4DS0-E3TE4-WMS-DV-104100-DV-104100 3E4DS0-E3TE4-WMS-DV-104100-DV-104100_CLS_CMD RELAY,WMREMO_AENTR1:3:O.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-2 AENTR1 3 - 2SR20 : 11,14 SDO-16 3 AENTR1:3:O.3 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-106200-DV-106200_OPN_CMD (DV_WMS_ARR_UDT[12].OPN_CMD) IS MAPPED TO
WMREMO_AENTR1:3:O.4
101 3E4DS0-E3TE4-WMS-DV-106200-DV-106200 3E4DS0-E3TE4-WMS-DV-106200-DV-106200_OPN_CMD THIS RELAY,WMREMO_AENTR1:3:O.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-2 AENTR1 3 - 2SR21 : 11,14 SDO-16 4 AENTR1:3:O.4 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-106200-DV-106200_CLS_CMD (DV_WMS_ARR_UDT[12].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR1:3:O.5
102 3E4DS0-E3TE4-WMS-DV-106200-DV-106200 3E4DS0-E3TE4-WMS-DV-106200-DV-106200_CLS_CMD RELAY,WMREMO_AENTR1:3:O.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-2 AENTR1 3 - 2SR22 : 11,14 SDO-16 5 AENTR1:3:O.5 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-203100-DV-203100_OPN_CMD (DV_WMS_ARR_UDT[17].OPN_CMD) IS MAPPED TO
WMREMO_AENTR1:3:O.6
103 3E4DS0-E4TE5-WMS-DV-203100-DV-203100 3E4DS0-E4TE5-WMS-DV-203100-DV-203100_OPN_CMD THIS RELAY,WMREMO_AENTR1:3:O.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-2 AENTR1 3 - 2SR23 : 11,14 SDO-16 6 AENTR1:3:O.6 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-203100-DV-203100_CLS_CMD (DV_WMS_ARR_UDT[17].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR1:3:O.7
104 3E4DS0-E4TE5-WMS-DV-203100-DV-203100 3E4DS0-E4TE5-WMS-DV-203100-DV-203100_CLS_CMD RELAY,WMREMO_AENTR1:3:O.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-2 AENTR1 3 - 2SR24 : 11,14 SDO-16 7 AENTR1:3:O.7 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-106200-DV-106200_OPN_CMD (DV_WMS_ARR_UDT[22].OPN_CMD) IS MAPPED TO
WMREMO_AENTR1:3:O.8
105 3E4DS0-E4TE5-WMS-DV-205200-DV-205200 3E4DS0-E4TE5-WMS-DV-205200-DV-205200_OPN_CMD THIS RELAY,WMREMO_AENTR1:3:O.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-2 AENTR1 3 - 2SR25 : 11,14 SDO-16 8 AENTR1:3:O.8 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-106200-DV-106200_CLS_CMD (DV_WMS_ARR_UDT[22].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR1:3:O.9
106 3E4DS0-E4TE5-WMS-DV-205200-DV-205200 3E4DS0-E4TE5-WMS-DV-205200-DV-205200_CLS_CMD RELAY,WMREMO_AENTR1:3:O.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-2 AENTR1 3 - 2SR26 : 11,14 SDO-16 9 AENTR1:3:O.9 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-203100-DV-203100_OPN_CMD (DV_WMS_ARR_UDT[27].OPN_CMD) IS MAPPED TO
WMREMO_AENTR1:3:O.10
107 3E4DS0-E4TE5-WMS-DV-208100-DV-208100 3E4DS0-E4TE5-WMS-DV-208100-DV-208100_OPN_CMD THIS RELAY,WMREMO_AENTR1:3:O.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-2 AENTR1 3 - 2SR27 : 11,14 SDO-16 10 AENTR1:3:O.10 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-203100-DV-203100_CLS_CMD (DV_WMS_ARR_UDT[27].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR1:3:O.11
108 3E4DS0-E4TE5-WMS-DV-208100-DV-208100 3E4DS0-E4TE5-WMS-DV-208100-DV-208100_CLS_CMD RELAY,WMREMO_AENTR1:3:O.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-2 AENTR1 3 - 2SR28 : 11,14 SDO-16 11 AENTR1:3:O.11 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-102100-DV-102100_OPN_CMD (DV_WMS_ARR_UDT[3].OPN_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:3:O.0
113 3E4DS0-E3TE4-WMS-DV-102100-DV-102100 3E4DS0-E3TE4-WMS-DV-102100-DV-102100_OPN_CMD RELAY,WMREMO_AENTR2:3:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-3 AENTR2 3 - 2SR33 : 11,14 SDO-16 0 AENTR2:3:O.0 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-102100-DV-102100_CLS_CMD (DV_WMS_ARR_UDT[3].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:3:O.1
114 3E4DS0-E3TE4-WMS-DV-102100-DV-102100 3E4DS0-E3TE4-WMS-DV-102100-DV-102100_CLS_CMD RELAY,WMREMO_AENTR2:3:O.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-3 AENTR2 3 - 2SR34 : 11,14 SDO-16 1 AENTR2:3:O.1 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-104200-DV-104200_OPN_CMD (DV_WMS_ARR_UDT[8].OPN_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:3:O.2
115 3E4DS0-E3TE4-WMS-DV-104200-DV-104200 3E4DS0-E3TE4-WMS-DV-104200-DV-104200_OPN_CMD RELAY,WMREMO_AENTR2:3:O.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-3 AENTR2 3 - 2SR35 : 11,14 SDO-16 2 AENTR2:3:O.2 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-104200-DV-104200_CLS_CMD (DV_WMS_ARR_UDT[8].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:3:O.3
116 3E4DS0-E3TE4-WMS-DV-104200-DV-104200 3E4DS0-E3TE4-WMS-DV-104200-DV-104200_CLS_CMD RELAY,WMREMO_AENTR2:3:O.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-3 AENTR2 3 - 2SR36 : 11,14 SDO-16 3 AENTR2:3:O.3 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-201100-DV-201100_OPN_CMD (DV_WMS_ARR_UDT[13].OPN_CMD) IS MAPPED TO
WMREMO_AENTR2:3:O.4
117 3E4DS0-E4TE5-WMS-DV-201100-DV-201100 3E4DS0-E4TE5-WMS-DV-201100-DV-201100_OPN_CMD THIS RELAY,WMREMO_AENTR2:3:O.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-3 AENTR2 3 - 2SR37 : 11,14 SDO-16 4 AENTR2:3:O.4 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-201100-DV-201100_CLS_CMD (DV_WMS_ARR_UDT[13].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:3:O.5
118 3E4DS0-E4TE5-WMS-DV-201100-DV-201100 3E4DS0-E4TE5-WMS-DV-201100-DV-201100_CLS_CMD RELAY,WMREMO_AENTR2:3:O.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-3 AENTR2 3 - 2SR38 : 11,14 SDO-16 5 AENTR2:3:O.5 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-203200-DV-203200_OPN_CMD (DV_WMS_ARR_UDT[18].OPN_CMD) IS MAPPED TO
WMREMO_AENTR2:3:O.6
119 3E4DS0-E4TE5-WMS-DV-203200-DV-203200 3E4DS0-E4TE5-WMS-DV-203200-DV-203200_OPN_CMD THIS RELAY,WMREMO_AENTR2:3:O.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-3 AENTR2 3 - 2SR39 : 11,14 SDO-16 6 AENTR2:3:O.6 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-203200-DV-203200_CLS_CMD (DV_WMS_ARR_UDT[18].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:3:O.7
120 3E4DS0-E4TE5-WMS-DV-203200-DV-203200 3E4DS0-E4TE5-WMS-DV-203200-DV-203200_CLS_CMD RELAY,WMREMO_AENTR2:3:O.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-3 AENTR2 3 - 2SR40 : 11,14 SDO-16 7 AENTR2:3:O.7 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-201100-DV-201100_OPN_CMD (DV_WMS_ARR_UDT[23].OPN_CMD) IS MAPPED TO
WMREMO_AENTR2:3:O.8
121 3E4DS0-E4TE5-WMS-DV-206100-DV-206100 3E4DS0-E4TE5-WMS-DV-206100-DV-206100_OPN_CMD THIS RELAY,WMREMO_AENTR2:3:O.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-3 AENTR2 3 - 2SR41 : 11,14 SDO-16 8 AENTR2:3:O.8 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-201100-DV-201100_CLS_CMD (DV_WMS_ARR_UDT[23].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:3:O.9
122 3E4DS0-E4TE5-WMS-DV-206100-DV-206100 3E4DS0-E4TE5-WMS-DV-206100-DV-206100_CLS_CMD RELAY,WMREMO_AENTR2:3:O.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-3 AENTR2 3 - 2SR42 : 11,14 SDO-16 9 AENTR2:3:O.9 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-203200-DV-203200_OPN_CMD (DV_WMS_ARR_UDT[28].OPN_CMD) IS MAPPED TO
WMREMO_AENTR2:3:O.10
123 3E4DS0-E4TE5-WMS-DV-208200-DV-208200 3E4DS0-E4TE5-WMS-DV-208200-DV-208200_OPN_CMD THIS RELAY,WMREMO_AENTR2:3:O.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-3 AENTR2 3 - 2SR43 : 11,14 SDO-16 10 AENTR2:3:O.10 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-203200-DV-203200_CLS_CMD (DV_WMS_ARR_UDT[28].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:3:O.11
124 3E4DS0-E4TE5-WMS-DV-208200-DV-208200 3E4DS0-E4TE5-WMS-DV-208200-DV-208200_CLS_CMD RELAY,WMREMO_AENTR2:3:O.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-3 AENTR2 3 - 2SR44 : 11,14 SDO-16 11 AENTR2:3:O.11 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-102200-DV-102200_OPN_CMD (DV_WMS_ARR_UDT[4].OPN_CMD) IS MAPPED TO THIS
WMREMO_AENTR1:4:O.0
129 3E4DS0-E3TE4-WMS-DV-102200-DV-102200 3E4DS0-E3TE4-WMS-DV-102200-DV-102200_OPN_CMD RELAY,WMREMO_AENTR1:4:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-4 AENTR1 4 - 2SR49 : 11,14 SDO-16 0 AENTR1:4:O.0 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-102200-DV-102200_CLS_CMD (DV_WMS_ARR_UDT[4].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR1:4:O.1
130 3E4DS0-E3TE4-WMS-DV-102200-DV-102200 3E4DS0-E3TE4-WMS-DV-102200-DV-102200_CLS_CMD RELAY,WMREMO_AENTR1:4:O.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-4 AENTR1 4 - 2SR50 : 11,14 SDO-16 1 AENTR1:4:O.1 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-105100-DV-105100_OPN_CMD (DV_WMS_ARR_UDT[9].OPN_CMD) IS MAPPED TO THIS
WMREMO_AENTR1:4:O.2
131 3E4DS0-E3TE4-WMS-DV-105100-DV-105100 3E4DS0-E3TE4-WMS-DV-105100-DV-105100_OPN_CMD RELAY,WMREMO_AENTR1:4:O.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-4 AENTR1 4 - 2SR51 : 11,14 SDO-16 2 AENTR1:4:O.2 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-105100-DV-105100_CLS_CMD (DV_WMS_ARR_UDT[9].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR1:4:O.3
132 3E4DS0-E3TE4-WMS-DV-105100-DV-105100 3E4DS0-E3TE4-WMS-DV-105100-DV-105100_CLS_CMD RELAY,WMREMO_AENTR1:4:O.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-4 AENTR1 4 - 2SR52 : 11,14 SDO-16 3 AENTR1:4:O.3 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-201200-DV-201200_OPN_CMD (DV_WMS_ARR_UDT[14].OPN_CMD) IS MAPPED TO
WMREMO_AENTR1:4:O.4
133 3E4DS0-E4TE5-WMS-DV-201200-DV-201200 3E4DS0-E4TE5-WMS-DV-201200-DV-201200_OPN_CMD THIS RELAY,WMREMO_AENTR1:4:O.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-4 AENTR1 4 - 2SR53 : 11,14 SDO-16 4 AENTR1:4:O.4 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-201200-DV-201200_CLS_CMD (DV_WMS_ARR_UDT[14].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR1:4:O.5
134 3E4DS0-E4TE5-WMS-DV-201200-DV-201200 3E4DS0-E4TE5-WMS-DV-201200-DV-201200_CLS_CMD RELAY,WMREMO_AENTR1:4:O.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-4 AENTR1 4 - 2SR54 : 11,14 SDO-16 5 AENTR1:4:O.5 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-204100-DV-204100_OPN_CMD (DV_WMS_ARR_UDT[19].OPN_CMD) IS MAPPED TO
WMREMO_AENTR1:4:O.6
135 3E4DS0-E4TE5-WMS-DV-204100-DV-204100 3E4DS0-E4TE5-WMS-DV-204100-DV-204100_OPN_CMD THIS RELAY,WMREMO_AENTR1:4:O.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-4 AENTR1 4 - 2SR55 : 11,14 SDO-16 6 AENTR1:4:O.6 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-204100-DV-204100_CLS_CMD (DV_WMS_ARR_UDT[19].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR1:4:O.7
136 3E4DS0-E4TE5-WMS-DV-204100-DV-204100 3E4DS0-E4TE5-WMS-DV-204100-DV-204100_CLS_CMD RELAY,WMREMO_AENTR1:4:O.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-4 AENTR1 4 - 2SR56 : 11,14 SDO-16 7 AENTR1:4:O.7 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-201200-DV-201200_OPN_CMD (DV_WMS_ARR_UDT[24].OPN_CMD) IS MAPPED TO
WMREMO_AENTR1:4:O.8
137 3E4DS0-E4TE5-WMS-DV-206200-DV-206200 3E4DS0-E4TE5-WMS-DV-206200-DV-206200_OPN_CMD THIS RELAY,WMREMO_AENTR1:4:O.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-4 AENTR1 4 - 2SR57 : 11,14 SDO-16 8 AENTR1:4:O.8 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-201200-DV-201200_CLS_CMD (DV_WMS_ARR_UDT[24].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR1:4:O.9
138 3E4DS0-E4TE5-WMS-DV-206200-DV-206200 3E4DS0-E4TE5-WMS-DV-206200-DV-206200_CLS_CMD RELAY,WMREMO_AENTR1:4:O.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-4 AENTR1 4 - 2SR58 : 11,14 SDO-16 9 AENTR1:4:O.9 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-204100-DV-204100_OPN_CMD (DV_WMS_ARR_UDT[29].OPN_CMD) IS MAPPED TO
WMREMO_AENTR1:4:O.10
139 3E4DS0-E4TE5-WMS-DV-209100-DV-209100 3E4DS0-E4TE5-WMS-DV-209100-DV-209100_OPN_CMD THIS RELAY,WMREMO_AENTR1:4:O.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-4 AENTR1 4 - 2SR59 : 11,14 SDO-16 10 AENTR1:4:O.10 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-204100-DV-204100_CLS_CMD (DV_WMS_ARR_UDT[29].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR1:4:O.11
140 3E4DS0-E4TE5-WMS-DV-209100-DV-209100 3E4DS0-E4TE5-WMS-DV-209100-DV-209100_CLS_CMD RELAY,WMREMO_AENTR1:4:O.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-4 AENTR1 4 - 2SR60 : 11,14 SDO-16 11 AENTR1:4:O.11 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-103100-DV-103100_OPN_CMD (DV_WMS_ARR_UDT[5].OPN_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:4:O.0
145 3E4DS0-E3TE4-WMS-DV-103100-DV-103100 3E4DS0-E3TE4-WMS-DV-103100-DV-103100_OPN_CMD RELAY,WMREMO_AENTR2:4:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-5 AENTR2 4 - 2SR65 : 11,14 SDO-16 0 AENTR2:4:O.0 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-103100-DV-103100_CLS_CMD (DV_WMS_ARR_UDT[5].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:4:O.1
146 3E4DS0-E3TE4-WMS-DV-103100-DV-103100 3E4DS0-E3TE4-WMS-DV-103100-DV-103100_CLS_CMD RELAY,WMREMO_AENTR2:4:O.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-5 AENTR2 4 - 2SR66 : 11,14 SDO-16 1 AENTR2:4:O.1 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E3TE4-WMS-DV-105200-DV-105200_OPN_CMD (DV_WMS_ARR_UDT[10].OPN_CMD) IS MAPPED TO
WMREMO_AENTR2:4:O.2
147 3E4DS0-E3TE4-WMS-DV-105200-DV-105200 3E4DS0-E3TE4-WMS-DV-105200-DV-105200_OPN_CMD THIS RELAY,WMREMO_AENTR2:4:O.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-5 AENTR2 4 - 2SR67 : 11,14 SDO-16 2 AENTR2:4:O.2 DO O 4/19/2025 DONE

# General
PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM

DOCUMENT TITLE SHOP DRAWING-DEEP UNDERGROUND STATION-3E4-BMS-INPUT/OUTPUT SCHEDULE

DOCUMENT NO. M-ANM-3E4DS0-CJ00-SCH-000002

MODULE RELAY MODULE CHANNE


SR. NO. EQUIPMENT TAG PLC TAG EASA SITE Response RLM COMMENTS FROM CWG DESCRIPTION PANEL SHORT TAG (OLD) PANEL FULL TAG (NEW) RACK NO. SLOT NO. TERMINAL NO. PLC IO ADDRESS MODULE ID DATE STATUS
ID NO. TYPE L NO.
SIGNAL 3E4DS0-E3TE4-WMS-DV-105200-DV-105200_CLS_CMD (DV_WMS_ARR_UDT[10].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:4:O.3
148 3E4DS0-E3TE4-WMS-DV-105200-DV-105200 3E4DS0-E3TE4-WMS-DV-105200-DV-105200_CLS_CMD RELAY,WMREMO_AENTR2:4:O.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-5 AENTR2 4 - 2SR68 : 11,14 SDO-16 3 AENTR2:4:O.3 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-202100-DV-202100_OPN_CMD (DV_WMS_ARR_UDT[15].OPN_CMD) IS MAPPED TO
WMREMO_AENTR2:4:O.4
149 3E4DS0-E4TE5-WMS-DV-202100-DV-202100 3E4DS0-E4TE5-WMS-DV-202100-DV-202100_OPN_CMD THIS RELAY,WMREMO_AENTR2:4:O.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-5 AENTR2 4 - 2SR69 : 11,14 SDO-16 4 AENTR2:4:O.4 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-202100-DV-202100_CLS_CMD (DV_WMS_ARR_UDT[15].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:4:O.5
150 3E4DS0-E4TE5-WMS-DV-202100-DV-202100 3E4DS0-E4TE5-WMS-DV-202100-DV-202100_CLS_CMD RELAY,WMREMO_AENTR2:4:O.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-5 AENTR2 4 - 2SR70 : 11,14 SDO-16 5 AENTR2:4:O.5 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-204200-DV-204200_OPN_CMD (DV_WMS_ARR_UDT[20].OPN_CMD) IS MAPPED TO
WMREMO_AENTR2:4:O.6
151 3E4DS0-E4TE5-WMS-DV-204200-DV-204200 3E4DS0-E4TE5-WMS-DV-204200-DV-204200_OPN_CMD THIS RELAY,WMREMO_AENTR2:4:O.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-5 AENTR2 4 - 2SR71 : 11,14 SDO-16 6 AENTR2:4:O.6 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-204200-DV-204200_CLS_CMD (DV_WMS_ARR_UDT[20].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:4:O.7
152 3E4DS0-E4TE5-WMS-DV-204200-DV-204200 3E4DS0-E4TE5-WMS-DV-204200-DV-204200_CLS_CMD RELAY,WMREMO_AENTR2:4:O.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-5 AENTR2 4 - 2SR72 : 11,14 SDO-16 7 AENTR2:4:O.7 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-202100-DV-202100_OPN_CMD (DV_WMS_ARR_UDT[25].OPN_CMD) IS MAPPED TO
WMREMO_AENTR2:4:O.8
153 3E4DS0-E4TE5-WMS-DV-207100-DV-207100 3E4DS0-E4TE5-WMS-DV-207100-DV-207100_OPN_CMD THIS RELAY,WMREMO_AENTR2:4:O.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-5 AENTR2 4 - 2SR73 : 11,14 SDO-16 8 AENTR2:4:O.8 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-202100-DV-202100_CLS_CMD (DV_WMS_ARR_UDT[25].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:4:O.9
154 3E4DS0-E4TE5-WMS-DV-207100-DV-207100 3E4DS0-E4TE5-WMS-DV-207100-DV-207100_CLS_CMD RELAY,WMREMO_AENTR2:4:O.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-5 AENTR2 4 - 2SR74 : 11,14 SDO-16 9 AENTR2:4:O.9 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-204200-DV-204200_OPN_CMD (DV_WMS_ARR_UDT[30].OPN_CMD) IS MAPPED TO
WMREMO_AENTR2:4:O.10
155 3E4DS0-E4TE5-WMS-DV-209200-DV-209200 3E4DS0-E4TE5-WMS-DV-209200-DV-209200_OPN_CMD THIS RELAY,WMREMO_AENTR2:4:O.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN VALVE
signal to
TRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-5 AENTR2 4 - 2SR75 : 11,14 SDO-16 10 AENTR2:4:O.10 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-E4TE5-WMS-DV-204200-DV-204200_CLS_CMD (DV_WMS_ARR_UDT[30].CLS_CMD) IS MAPPED TO THIS
WMREMO_AENTR2:4:O.11
156 3E4DS0-E4TE5-WMS-DV-209200-DV-209200 3E4DS0-E4TE5-WMS-DV-209200-DV-209200_CLS_CMD RELAY,WMREMO_AENTR2:4:O.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSE signal
VALVEtoTRACK
be confirmed WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-5 AENTR2 4 - 2SR76 : 11,14 SDO-16 11 AENTR2:4:O.11 DO O 4/19/2025 DONE
IN LOGIX,THERE IS NO MAPPING TO THIS RELAY.IN SITE,EXTRA CABLE IS CONNECTED TO THIS RELAY.IT NEED TO BE
WMREMO_AENTR2:4:O.12
157 SPARE SPARE REMOVED. As per CWG RLM, this channel is used at site, please check. SPARE WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SDO-5 AENTR2 4 - 2SR77 : 11,14 SDO-16 12 AENTR2:4:O.12 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-WMR-WMS-WMSP-000001_MANIFOLD_PT (PT_ARR_UDT[1].MANIFOLD_PT) IS MAPPED TO THIS
WMREMO_AENTR1:5:chdata.0
161 3E4DS0-WMR-WMS-WMSP-000001 3E4DS0-WMR-WMS-WMSP-000001_MANIFOLD_PT CHANNEL, WMREMO_AENTR1:5:I.Ch0Data .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WATERsignal
MISTto
MANIFOLD
be confirmed
STATIC PRESSURE WMREMO 3E4DS0-WMR-BMS-RIOP-000026 SAI-1 AENTR1 5 2XSAI1 : 1,2 - SAI-08 0 AENTR1:5:I.Ch0Data AI chdata 4/19/2025 DONE
SIGNAL, 3E4DS0-TVR-ELS-EMCC-001100_TRIP_FB (TVS_EMCC_ICB_ARR_UDT[11].TRIP_FB) IS MAPPED TO THIS
TVRECO1 TVRECO1_AENTR2:0:I.9
26 3E4DS0-TVR-ELS-EMCC-001100 3E4DS0-TVR-ELS-EMCC-001100_TRIP_FB CHANNEL,TVRECO1_AENTR2:0:I.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Closed/Open
signal tocircuit
be confirmed
to EMCC 1-1 incomer 3E4DS0-TVR-BMS-RIOP-000014 SDI-2 AENTR2 0 2XSDI2 : 19,20 - SDI-16 9 AENTR2:0:I.9 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-TVR-ELS-EMCC-001100-MD-DP-1-1_TRIP_FB (TVS_EMCC_ICB_ARR_UDT[12].TRIP_FB) IS MAPPED TO TVRECO1 TVRECO1_AENTR2:0:I.10


27 3E4DS0-TVR-ELS-EMCC-001100-MD-DP-1-1 3E4DS0-TVR-ELS-EMCC-001100-MD-DP-1-1_TRIP_FB THIS CHANNEL,TVRECO1_AENTR2:0:I.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
FEED
be confirmed
TO MD-DP-1-1 3E4DS0-TVR-BMS-RIOP-000014 SDI-2 AENTR2 0 2XSDI2 : 21,22 - SDI-16 10 AENTR2:0:I.10 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-OTE02-TVS-TEF-210000_EMG_STP (TEF_3E4_ARR_UDT[3].EMG_STP) IS MAPPED TO THIS
TVRECO1 TVRECO1_AENTR3:0:I.0
33 3E4DS0-OTE02-TVS-TEF-210000 3E4DS0-OTE02-TVS-TEF-210000_EMG_STP CHANNEL,TVRECO1_AENTR3:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
EMERGENCY
signal to
STOP
be confirmed
BUTTON STATUS 3E4DS0-TVR-BMS-RIOP-000014 SDI-3 AENTR3 0 2XSDI3 : 1,2 - SDI-16 0 AENTR3:0:I.0 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-TVR-TVS-VFD-210002_VFD.BYPASS (TEF_3E4_ARR_UDT[3].VFD.BYPASS) IS MAPPED TO THIS
TVRECO1 TVRECO1_AENTR3:0:I.3
36 3E4DS0-TVR-TVS-VFD-210002 3E4DS0-TVR-TVS-VFD-210002_VFD.BYPASS CHANNEL,TVRECO1_AENTR3:0:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
VFD INsignal
BYPASSto STATUS
be confirmed 3E4DS0-TVR-BMS-RIOP-000014 SDI-3 AENTR3 0 2XSDI3 : 7,8 - SDI-16 3 AENTR3:0:I.3 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-OTE02-TVS-TEF-210000_WD_TEMP_ALM (TEF_3E4_ARR_UDT[3].WD_TEMP_ALM) IS MAPPED TO THIS
TVRECO1 TVRECO1_AENTR3:0:I.8
41 3E4DS0-OTE02-TVS-TEF-210000 3E4DS0-OTE02-TVS-TEF-210000_WD_TEMP_ALM CHANNEL,TVRECO1_AENTR3:0:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WINDING
signal
TEMPERATURE
to be confirmed
STATUS 3E4DS0-TVR-BMS-RIOP-000014 SDI-3 AENTR3 0 2XSDI3 : 17,18 - SDI-16 8 AENTR3:0:I.8 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-TVR-ELS-EMCC-001100-TEF-2-1_OPN_CLS_FB (TVS_EMCC_ICB_ARR_UDT[9].OPN_CLS_FB) IS MAPPED TVRECO1 TVRECO1_AENTR3:0:I.9


42 3E4DS0-TVR-ELS-EMCC-001100-TEF-2-1 3E4DS0-TVR-ELS-EMCC-001100-TEF-2-1_OPN_CLS_FB TO THIS CHANNEL,TVRECO1_AENTR3:0:I.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSED/OPEN
signal to CIRCUIT
be confirmed
TO TUNNELEXHAUST FAN 3E4DS0-TVR-BMS-RIOP-000014 SDI-3 AENTR3 0 2XSDI3 : 19,20 - SDI-16 9 AENTR3:0:I.9 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-SFR/CO06-TVS-VSAD-200019-Access door limit switch open (VSAD_ARR_UDT[2].OPN_CLS_FB) IS TVRECO1 TVRECO1_AENTR2:1:I.8


73 3E4DS0-SFR/CO06-TVS-VSAD-200019 3E4DS0-SFR/CO06-TVS-VSAD-200019_OPN_CLS_FB MAPPED TO THIS CHANNEL,TVRECO1_AENTR2:1:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
ACCESSsignal
DOOR toLIMIT
be confirmed
SWITCH OPEN 3E4DS0-TVR-BMS-RIOP-000014 SDI-5 AENTR2 1 2XSDI5 : 17,18 - SDI-16 8 AENTR2:1:I.8 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-SFR-TVS-VSID-200028-Internal Access door limit switch open (VSID_ARR_UDT[5].OPN_CLS_FB) IS


MAPPED TO THIS CHANNEL,TVRECO1_AENTR2:1:I.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. TVRECO1 TVRECO1_AENTR2:1:I.9

SIGNAL, 3E4DS0-SFR-TVS-VSID-200031-Internal Access door limit switch open (VSID_ARR_UDT[8].OPN_CLS_FB) IS


74 3E4DS0-SFR-TVS-VSID-200031 3E4DS0-SFR-TVS-VSID-200031_OPN_CLS_FB MAPPED TO THIS CHANNEL,TVRECO1_AENTR2:1:I.12.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
INTERNAL
signal
ACCESS
to be confirmed
DOOR LIMIT SWITCH OPEN 3E4DS0-TVR-BMS-RIOP-000014 SDI-5 AENTR2 1 2XSDI5 : 19,20 - SDI-16 9 AENTR2:1:I.9 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-SFR-TVS-VSID-200029-Internal Access door limit switch open (VSID_ARR_UDT[6].OPN_CLS_FB) IS


MAPPED TO THIS CHANNEL,TVRECO1_AENTR2:1:I.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. TVRECO1 TVRECO1_AENTR2:1:I.10

SIGNAL, 3E4DS0-SFR-TVS-VSID-200028-Internal Access door limit switch open (VSID_ARR_UDT[5].OPN_CLS_FB) IS


75 3E4DS0-SFR-TVS-VSID-200028 3E4DS0-SFR-TVS-VSID-200028_OPN_CLS_FB MAPPED TO THIS CHANNEL,TVRECO1_AENTR2:1:I.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
INTERNAL
signal
ACCESS
to be confirmed
DOOR LIMIT SWITCH OPEN 3E4DS0-TVR-BMS-RIOP-000014 SDI-5 AENTR2 1 2XSDI5 : 21,22 - SDI-16 10 AENTR2:1:I.10 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-SFR-TVS-VSID-200030-Internal Access door limit switch open (VSID_ARR_UDT[7].OPN_CLS_FB) IS


MAPPED TO THIS CHANNEL,TVRECO1_AENTR2:1:I.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. TVRECO1 TVRECO1_AENTR2:1:I.11

SIGNAL, 3E4DS0-SFR-TVS-VSID-200029-Internal Access door limit switch open (VSID_ARR_UDT[6].OPN_CLS_FB) IS


76 3E4DS0-SFR-TVS-VSID-200029 3E4DS0-SFR-TVS-VSID-200029_OPN_CLS_FB MAPPED TO THIS CHANNEL,TVRECO1_AENTR2:1:I.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
INTERNAL
signal
ACCESS
to be confirmed
DOOR LIMIT SWITCH OPEN 3E4DS0-TVR-BMS-RIOP-000014 SDI-5 AENTR2 1 2XSDI5 : 23,24 - SDI-16 11 AENTR2:1:I.11 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-SFR-TVS-VSID-200031-Internal Access door limit switch open (VSID_ARR_UDT[8].OPN_CLS_FB) IS


MAPPED TO THIS CHANNEL,TVRECO1_AENTR2:1:I.12.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. TVRECO1 TVRECO1_AENTR2:1:I.12

SIGNAL, 3E4DS0-SFR-TVS-VSID-200030-Internal Access door limit switch open (VSID_ARR_UDT[7].OPN_CLS_FB) IS


77 3E4DS0-SFR-TVS-VSID-200030 3E4DS0-SFR-TVS-VSID-200030_OPN_CLS_FB MAPPED TO THIS CHANNEL,TVRECO1_AENTR2:1:I.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
INTERNAL
signal
ACCESS
to be confirmed
DOOR LIMIT SWITCH OPEN 3E4DS0-TVR-BMS-RIOP-000014 SDI-5 AENTR2 1 2XSDI5 : 25,26 - SDI-16 12 AENTR2:1:I.12 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-TVR-ELS-EMCC-002100-MD-DP-2-1_OPN_CLS_FB (TVS_EMCC_ICB_ARR_UDT[6].OPN_CLS_FB) IS


MAPPED TO THIS CHANNEL,TVRECO1_AENTR2:1:I.14.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. TVRECO1 TVRECO1_AENTR2:1:I.14

SIGNAL 3E4DS0-TVR-ELS-EMCC-001100-MD-DP-1-1_OPN_CLS_FB (TVS_EMCC_ICB_ARR_UDT[1].OPN_CLS_FB) IS


MAPPED TO THIS CHANNEL,TVRWTO1_AENTR2:0:I.11.
79 3E4DS0-TVR-ELS-EMCC-001100-MD-DP-1-1 3E4DS0-TVR-ELS-EMCC-001100-MD-DP-1-1_OPN_CLS_FB IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSED/OPEN
signal to CIRCUIT
be confirmed
MD-DP 3E4DS0-TVR-BMS-RIOP-000014 SDI-5 AENTR2 1 2XSDI5 : 29,30 - SDI-16 14 AENTR2:1:I.14 DI I 4/19/2025 DONE

SIGNAL 3E4DS0-OTE01-TVS-MTED-110021-Damper Limit Switch Close Status (MTED_ARR_UDT[5].CLS_FB) IS MAPPED TVRECO1 TVRECO1_AENTR2:2:I.11
124 SPARE SPARE TO THIS CHANNEL,TVRWTO1_AENTR2:1:I.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is used at site, please check. SPARE 3E4DS0-TVR-BMS-RIOP-000014 SDI-8 AENTR2 2 2XSDI8 : 23,24 - SDI-16 11 AENTR2:2:I.11 DI I 4/19/2025 DONE

SIGNAL 3E4DS0-TVR-ELS-MDDP-001010-UPED 2-2-1-Trip status UPED 2-2-1 (UPED_MDDP_ARR_UDT[7].TRIP_FB) IS


TVRECO1 TVRECO1_AENTR3:5:I.0
MAPPED TO THIS CHANNEL,TVRECO1_AENTR3:5:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.AS PER
145 SPARE SPARE LATEST SIGNAL REV 9.06.THIS SIGNAL IS DELETED.THIS SIGNAL NEED TO BE REMOVED FROM SITE & LOGIX. As per CWG RLM, this channel is used at site, please check. SPARE 3E4DS0-TVR-BMS-RIOP-000014 SDI-10 AENTR3 5 2XSDI10 : 1,2 - SDI-16 0 AENTR3:5:I.0 DI I 4/19/2025 DONE

SIGNAL 3E4DS0-TVR-ELS-MDDP-001010-UPED 2-2-1-OPN_CLS UPED 2-2-1 (UPED_MDDP_ARR_UDT[7].OPN_CLS_FB) IS


TVRECO1 TVRECO1_AENTR3:5:I.1
MAPPED TO THIS CHANNEL,TVRECO1_AENTR3:5:I.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL..AS PER
146 SPARE SPARE LATEST SIGNAL REV 9.06.THIS SIGNAL IS DELETED.THIS SIGNAL NEED TO BE REMOVED FROM SITE & LOGIX. As per CWG RLM, this channel is used at site, please check. SPARE 3E4DS0-TVR-BMS-RIOP-000014 SDI-10 AENTR3 5 2XSDI10 : 3,4 - SDI-16 1 AENTR3:5:I.1 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-1-1_TRIP_FB (UPED_MDDP_ARR_UDT[5].TRIP_FB) IS MAPPED TO THIS TVRECO1 TVRECO1_AENTR3:5:I.2


147 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-1-1 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-1-1_TRIP_FB CHANNEL,TVRECO1_AENTR3:5:I.2.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
FEED
be confirmed
TO SHAFT DAMPER 3E4DS0-TVR-BMS-RIOP-000014 SDI-10 AENTR3 5 2XSDI10 : 5,6 - SDI-16 2 AENTR3:5:I.2 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-1-1_OPN_CLS_FB (UPED_MDDP_ARR_UDT[5].OPN_CLS_FB) IS MAPPED TVRECO1 TVRECO1_AENTR3:5:I.3


148 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-1-1 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-1-1_OPN_CLS_FB TO THIS CHANNEL,TVRECO1_AENTR3:5:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN/CLOSE
signal to
STATUS
be confirmed
FEED TO SHAFT DAMPER 3E4DS0-TVR-BMS-RIOP-000014 SDI-10 AENTR3 5 2XSDI10 : 7,8 - SDI-16 3 AENTR3:5:I.3 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-1-GROUP_LOC_FB (UPED_GROUP_ARR_UDT[3].LOC_FB) IS MAPPED


TVRECO1 TVRECO1_AENTR3:5:I.4
TO THIS CHANNEL,TVRECO1_AENTR3:5:I.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.AS PER LATEST
149 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-1-GROUP 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-1-GROUP_LOC_FB SIGNAL REV 9.06.THIS SIGNAL IS DELETED.THIS SIGNAL NEED TO BE REMOVED FROM SITE & LOGIX. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalACTUATOR
to be confirmed
GROUP 3E4DS0-TVR-BMS-RIOP-000014 SDI-10 AENTR3 5 2XSDI10 : 9,10 - SDI-16 4 AENTR3:5:I.4 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-1-GROUP_REM_FB (UPED_GROUP_ARR_UDT[3].REM_FB) IS MAPPED


TVRECO1 TVRECO1_AENTR3:5:I.5
TO THIS CHANNEL,TVRECO1_AENTR3:5:I.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.AS PER LATEST
150 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-1-GROUP 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-1-GROUP_REM_FB SIGNAL REV 9.06.THIS SIGNAL IS DELETED.THIS SIGNAL NEED TO BE REMOVED FROM SITE & LOGIX. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalACTUATOR
to be confirmed
GROUP 3E4DS0-TVR-BMS-RIOP-000014 SDI-10 AENTR3 5 2XSDI10 : 11,12 - SDI-16 5 AENTR3:5:I.5 DI I 4/19/2025 DONE
SIGNAL 3E4DS0-TVR-TVS-SOST-211000-Enable Emergency Mode Command
(JTF_3E4_ARR_UDT[3].SOST.EMG_ENABLE_CMD) IS MAPPED TO THIS RELAY,TVRECO1_AENTR2:3:O.0.IN SITE TVRECO1 TVRECO1_AENTR2:3:O.0
161 3E4DS0-TVR-TVS-SOST-211000 3E4DS0-TVR-TVS-SOST-211000_SOST.EMG_ENABLE_CMD ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
ENABLEsignal
EMERGENCY
to be confirmed
MODE COMMAND 3E4DS0-TVR-BMS-RIOP-000014 SDO-1 AENTR2 3 - 2SR1:11,14 SDO-16 0 AENTR2:3:O.0 DO O 4/19/2025 DONE

SIGNAL 3E4DS0-SFR-TVS-MVSBD-210002_OPN_CLS_CMD (MVSBD_ARR_UDT[10].OPN_CLS_CMD) IS MAPPED TO THIS TVRECO1 TVRECO1_AENTR2:3:O.6


167 3E4DS0-SFR-TVS-MVSBD-210002 3E4DS0-SFR-TVS-MVSBD-210002_OPN_CLS_CMD RELAY,TVRECO1_AENTR2:3:O.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
DAMPERsignal
OPENto be
/ CLOSE
confirmed
COMMAND 3E4DS0-TVR-BMS-RIOP-000014 SDO-1 AENTR2 3 - 2SR7:11,14 SDO-16 6 AENTR2:3:O.6 DO O 4/19/2025 DONE

SIGNAL 3E4DS0-TVR-TVS-VFD-210002_VFD.FIRE_MODE_CMD (TEF_3E4_ARR_UDT[3].VFD.FIRE_MODE_CMD) IS TVRECO1 TVRECO1_AENTR3:3:O.0


177 3E4DS0-TVR-TVS-VFD-210002 3E4DS0-TVR-TVS-VFD-210002_VFD.FIRE_MODE_CMD MAPPED TO THIS RELAY,TVRECO1_AENTR3:3:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
VFD FIRE
signal
MODEto be
COMMAND
confirmed 3E4DS0-TVR-BMS-RIOP-000014 SDO-2 AENTR3 3 - 2SR17:11,14 SDO-16 0 AENTR3:3:O.0 DO O 4/19/2025 DONE

TVRECO1 TVRECO1_AENTR3:3:O.5
SIGNAL 3E4DS0-OTE02-TVS-UPED-210000_OPN_CLS_CMD (UPED_ARR_UDT[3].OPN_CLS_CMD) IS MAPPED TO THIS
182 3E4DS0-OTE02-TVS-UPED-210000 3E4DS0-OTE02-TVS-UPED-210000_OPN_CLS_CMD RELAY,TVRECO1_AENTR3:3:O.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
SUB-DAMPER
signal to1be
OPEN/CLOSE
confirmed COMMAND 3E4DS0-TVR-BMS-RIOP-000014 SDO-2 AENTR3 3 - 2SR22:11,14 SDO-16 5 AENTR3:3:O.5 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-TVR-TVS-VFD-210001_VFD.FIRE_FWD_CMD (VSF_3E4_ARR_UDT[3].VFD.FIRE_FWD_CMD) IS MAPPED
TVRECO1 TVRECO1_AENTR1:3:O.0
193 3E4DS0-TVR-TVS-VFD-210001 3E4DS0-TVR-TVS-VFD-210001_VFD.FIRE_FWD_CMD TO THIS RELAY,TVRECO1_AENTR1:3:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FIRE MODE
signal-FORWARD
to be confirmed
DIRECTION COMMAND 3E4DS0-TVR-BMS-RIOP-000014 SDO-3 AENTR1 3 - 2SR33:11,14 SDO-16 0 AENTR1:3:O.0 DO O 4/19/2025 DONE
SIGNAL 3E4DS0-TVR-TVS-VFD-210001_VFD.FIRE_REV_CMD (VSF_3E4_ARR_UDT[3].VFD.FIRE_REV_CMD) IS MAPPED TO
TVRECO1 TVRECO1_AENTR1:3:O.1
194 3E4DS0-TVR-TVS-VFD-210001 3E4DS0-TVR-TVS-VFD-210001_VFD.FIRE_REV_CMD THIS RELAY,TVRECO1_AENTR1:3:O.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FIRE MODE
signal-REVERSE
to be confirmed
DIRECTION COMMAND 3E4DS0-TVR-BMS-RIOP-000014 SDO-3 AENTR1 3 - 2SR34:11,14 SDO-16 1 AENTR1:3:O.1 DO O 4/19/2025 DONE
SIGNAL, 3E4DS0-OTE02-TVS-TEF-210000_BR_TEMP_WEST (TEF_3E4_ARR_UDT[3].BR_TEMP_WEST) IS MAPPED TO THIS
TVRECO1 TVRECO1_AENTR3:4:ch1data
234 3E4DS0-OTE02-TVS-TEF-210000 3E4DS0-OTE02-TVS-TEF-210000_BR_TEMP_WEST CHANNEL,TVRECO1_AENTR3:4:I.Ch1Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
BEARING
signal
TEMPERATURE
to be confirmed
TUNNEL SIDE 3E4DS0-TVR-BMS-RIOP-000014 SAI-2 AENTR3 4 2XSAI2 : 3,4 - SAI-08 1 AENTR3:4:I.Ch1Data AI ch1data 4/19/2025 DONE
SIGNAL, 3E4DS0-OTE02-TVS-TEF-210000_BR_TEMP_EAST (TEF_3E4_ARR_UDT[3].BR_TEMP_EAST) IS MAPPED TO THIS
TVRECO1 TVRECO1_AENTR3:4:ch2data
235 3E4DS0-OTE02-TVS-TEF-210000 3E4DS0-OTE02-TVS-TEF-210000_BR_TEMP_EAST CHANNEL,TVRECO1_AENTR3:4:I.Ch2Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
BEARING
signal
TEMPERATURE
to be confirmed
ATMOSPHERE SIDE 3E4DS0-TVR-BMS-RIOP-000014 SAI-2 AENTR3 4 2XSAI2 : 5,6 - SAI-08 2 AENTR3:4:I.Ch2Data AI ch2data 4/19/2025 DONE
SIGNAL 3E4DS0-OTE02-TVS-TEFDPT-210000_FLOW_EAST (TEF_3E4_ARR_UDT[3].FLOW_EAST) IS MAPPED TO THIS
TVRECO1 TVRECO1_AENTR3:4:ch3data
236 3E4DS0-OTE02-TVS-TEFDPT-210000 3E4DS0-OTE02-TVS-TEFDPT-210000_FLOW_EAST CHANNEL,TVRECO1_AENTR3:4:I.Ch3Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FLOW MEASURE
signal to beTO
confirmed
TUNNEL/ATMOSPHERE DIRECTION 3E4DS0-TVR-BMS-RIOP-000014 SAI-2 AENTR3 4 2XSAI2 : 7,8 - SAI-08 3 AENTR3:4:I.Ch3Data AI ch3data 4/19/2025 DONE
SIGNAL 3E4DS0-OTE02-TVS-TEF-210000_FAN_VIB (TEF_3E4_ARR_UDT[3].FAN_VIB) IS MAPPED TO THIS
TVRECO1 TVRECO1_AENTR3:4:ch4data
237 3E4DS0-OTE02-TVS-TEF-210000 3E4DS0-OTE02-TVS-TEF-210000_FAN_VIB CHANNEL,TVRECO1_AENTR3:4:I.Ch4Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTOR signal
VIBRATION
to be confirmed
LEVEL (MM/S) 3E4DS0-TVR-BMS-RIOP-000014 SAI-2 AENTR3 4 2XSAI2 : 9,10 - SAI-08 4 AENTR3:4:I.Ch4Data AI ch4data 4/19/2025 DONE
SIGNAL 3E4DS0-TVR-TVS-VFD-210001_VFD.SPD (VSF_3E4_ARR_UDT[3].VFD.SPD) IS MAPPED TO THIS
TVRECO1 TVRECO1_AENTR1:4:ch0data
241 3E4DS0-TVR-TVS-VFD-210001 3E4DS0-TVR-TVS-VFD-210001_VFD.SPD CHANNEL,TVRECO1_AENTR1:4:I.Ch0Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTOR signal
SPEEDto FEEDBACK
be confirmed 3E4DS0-TVR-BMS-RIOP-000014 SAI-3 AENTR1 4 2XSAI3 : 1,2 - SAI-08 0 AENTR1:4:I.Ch0Data AI ch0data 4/19/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSF-220000_EMG_STP (VSF_3E4_ARR_UDT[4].EMG_STP) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR1:0:I.0
1 3E4DS0-SFR-TVS-VSF-220000 3E4DS0-SFR-TVS-VSF-220000_EMG_STP CHANNEL,TVRECO2_AENTR1:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
EMERGENCY
signal to
STOP
be confirmed
BUTTON STATUS 3E4DS0-TVR-BMS-RIOP-000015 SDI-1 AENTR1 0 2XSDI1 : 1,2 - SDI-16 0 AENTR1:0:I.0 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-TVR-TVS-VFD-220001_VFD.BYPASS (VSF_3E4_ARR_UDT[4].VFD.BYPASS) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR1:0:I.3
4 3E4DS0-TVR-TVS-VFD-220001 3E4DS0-TVR-TVS-VFD-220001_VFD.BYPASS CHANNEL,TVRECO2_AENTR1:0:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
VFD INsignal
BYPASSto STATUS
be confirmed 3E4DS0-TVR-BMS-RIOP-000015 SDI-1 AENTR1 0 2XSDI1 : 7,8 - SDI-16 3 AENTR1:0:I.3 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSF-220000_WD_TEMP_ALM (VSF_3E4_ARR_UDT[4].WD_TEMP_ALM) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR1:0:I.11
12 3E4DS0-SFR-TVS-VSF-220000 3E4DS0-SFR-TVS-VSF-220000_WD_TEMP_ALM CHANNEL,TVRECO2_AENTR1:0:I.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WINDING
signal
TEMPERATURE
to be confirmed
ALARM 3E4DS0-TVR-BMS-RIOP-000015 SDI-1 AENTR1 0 2XSDI1 : 23,24 - SDI-16 11 AENTR1:0:I.11 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-OTE02-TVS-TEF-220000_EMG_STP (TEF_3E4_ARR_UDT[4].EMG_STP) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR2:0:I.0
17 3E4DS0-OTE02-TVS-TEF-220000 3E4DS0-OTE02-TVS-TEF-220000_EMG_STP CHANNEL,TVRECO2_AENTR2:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
EMERGENCY
signal to
STOP
be confirmed
BUTTON STATUS 3E4DS0-TVR-BMS-RIOP-000015 SDI-2 AENTR2 0 2XSDI2 : 1,2 - SDI-16 0 AENTR2:0:I.0 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-OTE02-TVS-TEF-220000_WD_TEMP_ALM (TEF_3E4_ARR_UDT[4].WD_TEMP_ALM) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR2:0:I.8
25 3E4DS0-OTE02-TVS-TEF-220000 3E4DS0-OTE02-TVS-TEF-220000_WD_TEMP_ALM CHANNEL,TVRECO2_AENTR2:0:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WINDING
signal
TEMPERATURE
to be confirmed
STATUS 3E4DS0-TVR-BMS-RIOP-000015 SDI-2 AENTR2 0 2XSDI2 : 17,18 - SDI-16 8 AENTR2:0:I.8 DI I 4/19/2025 DONE

SIGNAL, 3E4DS0-TVR-ELS-EMCC-002100-TEF-1-2_OPN_CLS_FB (TVS_EMCC_ICB_ARR_UDT[10].OPN_CLS_FB) IS MAPPED


TO THIS CHANNEL,TVRECO2_AENTR2:0:I.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.SIGNAL 3E4DS0- TVRECO2 TVRECO2_AENTR2:0:I.9
TVR-ELS-EMCC-001100-TEF-2-2_OPN_CLS_FB ,THERE IS NO MAPPING FOR OPN_CLS_FB IN LOGIX.ONLY TRIP_FB IS
26 3E4DS0-TVR-ELS-EMCC-001100-TEF-2-2 3E4DS0-TVR-ELS-EMCC-001100-TEF-2-2_OPN_CLS_FB AVAILABLE IN LOGIX. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSED/OPEN
signal to CIRCUIT
be confirmed
TO TUNNELEXHAUST FAN 3E4DS0-TVR-BMS-RIOP-000015 SDI-2 AENTR2 0 2XSDI2 : 19,20 - SDI-16 9 AENTR2:0:I.9 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-E4TE5-TVS-JTF-212000_WD_TEMP_ALM (JTF_3E4_ARR_UDT[4].WD_TEMP_ALM) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR3:0:I.6
39 3E4DS0-E4TE5-TVS-JTF-212000 3E4DS0-E4TE5-TVS-JTF-212000_WD_TEMP_ALM CHANNEL,TVRECO2_AENTR3:0:I.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WINDING
signal
TEMPERATURE
to be confirmed
STATUS 3E4DS0-TVR-BMS-RIOP-000015 SDI-3 AENTR3 0 2XSDI3 : 13,14 - SDI-16 6 AENTR3:0:I.6 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-TVR-TVS-SOST-212000_SOST.EMG_STP (JTF_3E4_ARR_UDT[4].SOST.EMG_STP) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR3:0:I.7
40 3E4DS0-TVR-TVS-SOST-212000 3E4DS0-TVR-TVS-SOST-212000_SOST.EMG_STP CHANNEL,TVRECO2_AENTR3:0:I.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
EMERGENCY
signal to
STOP
be confirmed
BUTTON STATUS 3E4DS0-TVR-BMS-RIOP-000015 SDI-3 AENTR3 0 2XSDI3 : 15,16 - SDI-16 7 AENTR3:0:I.7 DI I 4/19/2025 DONE

# General
PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM

DOCUMENT TITLE SHOP DRAWING-DEEP UNDERGROUND STATION-3E4-BMS-INPUT/OUTPUT SCHEDULE

DOCUMENT NO. M-ANM-3E4DS0-CJ00-SCH-000002

MODULE RELAY MODULE CHANNE


SR. NO. EQUIPMENT TAG PLC TAG EASA SITE Response RLM COMMENTS FROM CWG DESCRIPTION PANEL SHORT TAG (OLD) PANEL FULL TAG (NEW) RACK NO. SLOT NO. TERMINAL NO. PLC IO ADDRESS MODULE ID DATE STATUS
ID NO. TYPE L NO.

SIGNAL, 3E4DS0-TVR-ELS-EMCC-002100-JTF-1-1-2_OPN_CLS_FB (TVS_EMCC_ICB_ARR_UDT[8].OPN_CLS_FB) IS MAPPED


TO THIS CHANNEL,TVRECO2_AENTR3:0:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. TVRECO2 TVRECO2_AENTR3:0:I.8

SIGNAL, 3E4DS0-TVR-ELS-EMCC-001100-JTF-2-1-2_OPN_CLS_FB (TVS_EMCC_ICB_ARR_UDT[3].OPN_CLS_FB) IS MAPPED


TO THIS CHANNEL,TVRWTO2_AENTR3:0:I.8.
41 3E4DS0-TVR-ELS-EMCC-001100-JTF-2-1-2 3E4DS0-TVR-ELS-EMCC-001100-JTF-2-1-2_OPN_CLS_FB IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSED/OPEN
signal to CIRCUIT
be confirmed
TO JET FAN 3E4DS0-TVR-BMS-RIOP-000015 SDI-3 AENTR3 0 2XSDI3 : 17,18 - SDI-16 8 AENTR3:0:I.8 DI I 4/19/2025 DONE
SIGNAL, 3E4DS0-OTE02-TVS-TESID-200024_OPN_CLS_FB (TESID_ARR_UDT[6].OPN_CLS_FB) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR3:1:I.11
92 3E4DS0-OTE02-TVS-TESID-200024 3E4DS0-OTE02-TVS-TESID-200024_OPN_CLS_FB CHANNEL,TVRECO2_AENTR3:1:I.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
INTERNAL
signal
ACCESS
to be confirmed
DOOR LIMIT SWITCH OPEN 3E4DS0-TVR-BMS-RIOP-000015 SDI-6 AENTR3 1 2XSDI6 : 23,24 - SDI-16 11 AENTR3:1:I.11 DI I 4/20/2025 DONE

SIGNAL, 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-2-GROUP_LOC_FB (UPED_GROUP_ARR_UDT[4].LOC_FB) IS MAPPED TVRECO2 TVRECO2_AENTR2:7:I.0


145 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-2-GROUP 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-2-GROUP_LOC_FB TO THIS CHANNEL,TVRECO2_AENTR2:7:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalACTUATOR
to be confirmed
GROUP 3E4DS0-TVR-BMS-RIOP-000015 SDI-10 AENTR2 7 2XSDI10 : 1,2 - SDI-16 0 AENTR2:7:I.0 DI I 4/20/2025 DONE

SIGNAL, 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-2-GROUP_REM_FB (UPED_GROUP_ARR_UDT[4].REM_FB) IS MAPPED TVRECO2 TVRECO2_AENTR2:7:I.1


146 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-2-GROUP 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-2-GROUP_REM_FB TO THIS CHANNEL,TVRECO2_AENTR2:7:I.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalACTUATOR
to be confirmed
GROUP 3E4DS0-TVR-BMS-RIOP-000015 SDI-10 AENTR2 7 2XSDI10 : 3,4 - SDI-16 1 AENTR2:7:I.1 DI I 4/20/2025 DONE

SIGNAL, 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-2-1_TRIP_FB (UPED_MDDP_ARR_UDT[6].TRIP_FB) IS MAPPED TO THIS TVRECO2 TVRECO2_AENTR2:7:I.4


149 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-2-1 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-2-1_TRIP_FB CHANNEL,TVRECO2_AENTR2:7:I.4.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
FEED
be confirmed
TO SHAFT DAMPER 3E4DS0-TVR-BMS-RIOP-000015 SDI-10 AENTR2 7 2XSDI10 : 9,10 - SDI-16 4 AENTR2:7:I.4 DI I 4/20/2025 DONE

SIGNAL, 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-2-1_OPN_CLS_FB (UPED_MDDP_ARR_UDT[6].OPN_CLS_FB) IS MAPPED TVRECO2 TVRECO2_AENTR2:7:I.5


150 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-2-1 3E4DS0-TVR-ELS-MDDP-001100-UPED-2-2-1_OPN_CLS_FB TO THIS CHANNEL,TVRECO2_AENTR2:7:I.5.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN/CLOSE
signal to
STATUS
be confirmed
FEED TO SHAFT DAMPER 3E4DS0-TVR-BMS-RIOP-000015 SDI-10 AENTR2 7 2XSDI10 : 11,12 - SDI-16 5 AENTR2:7:I.5 DI I 4/20/2025 DONE
SIGNAL 3E4DS0-TVR-TVS-VFD-220002_VFD.FIRE_MODE_CMD (TEF_3E4_ARR_UDT[4].VFD.FIRE_MODE_CMD) IS
TVRECO2 TVRECO2_AENTR2:3:O.0
161 3E4DS0-TVR-TVS-VFD-220002 3E4DS0-TVR-TVS-VFD-220002_VFD.FIRE_MODE_CMD MAPPED TO THIS RELAY,TVRECO2_AENTR2:3:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
VFD FIRE
signal
MODEto be
COMMAND
confirmed 3E4DS0-TVR-BMS-RIOP-000015 SDO-1 AENTR2 3 - 2SR1:11,14 SDO-16 0 AENTR2:3:O.0 DO O 4/20/2025 DONE
SIGNAL 3E4DS0-TVR-TVS-VFD-220001_VFD.FIRE_FWD_CMD (VSF_3E4_ARR_UDT[4].VFD.FIRE_FWD_CMD) IS MAPPED
TVRECO2 TVRECO2_AENTR1:3:O.0
193 3E4DS0-TVR-TVS-VFD-220001 3E4DS0-TVR-TVS-VFD-220001_VFD.FIRE_FWD_CMD TO THIS RELAY,TVRECO2_AENTR1:3:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FIRE MODE
signal-FORWARD
to be confirmed
DIRECTION COMMAND 3E4DS0-TVR-BMS-RIOP-000015 SDO-3 AENTR1 3 - 2SR33:11,14 SDO-16 0 AENTR1:3:O.0 DO O 4/20/2025 DONE
SIGNAL 3E4DS0-TVR-TVS-VFD-220001_VFD.FIRE_REV_CMD (VSF_3E4_ARR_UDT[4].VFD.FIRE_REV_CMD) IS MAPPED TO
TVRECO2 TVRECO2_AENTR1:3:O.1
194 3E4DS0-TVR-TVS-VFD-220001 3E4DS0-TVR-TVS-VFD-220001_VFD.FIRE_REV_CMD THIS RELAY,TVRECO2_AENTR1:3:O.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FIRE MODE
signal-REVERSE
to be confirmed
DIRECTION COMMAND 3E4DS0-TVR-BMS-RIOP-000015 SDO-3 AENTR1 3 - 2SR34:11,14 SDO-16 1 AENTR1:3:O.1 DO O 4/20/2025 DONE
SIGNAL 3E4DS0-OTE02-TVS-UPED-220000_OPN_CLS_CMD (UPED_ARR_UDT[4].OPN_CLS_CMD) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR2:4:O.0
209 3E4DS0-OTE02-TVS-UPED-220000 3E4DS0-OTE02-TVS-UPED-220000_OPN_CLS_CMD RELAY,TVRECO2_AENTR2:4:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
SUB-DAMPER
signal to1be
OPEN/CLOSE
confirmed COMMAND 3E4DS0-TVR-BMS-RIOP-000015 SDO-4 AENTR2 4 - 2SR49:11,14 SDO-16 0 AENTR2:4:O.0 DO O 4/20/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSF-220000_BR_TEMP_WEST (VSF_3E4_ARR_UDT[4].BR_TEMP_WEST) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR1:4:ch1data
234 3E4DS0-SFR-TVS-VSF-220000 3E4DS0-SFR-TVS-VSF-220000_BR_TEMP_WEST CHANNEL,TVRECO2_AENTR1:4:I.Ch1Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
BEARING
signal
TEMPERATURE
to be confirmed
TUNNEL SIDE 3E4DS0-TVR-BMS-RIOP-000015 SAI-2 AENTR1 4 2XSAI2 : 3,4 - SAI-08 1 AENTR1:4:I.Ch1Data AI ch 4/20/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSF-220000_BR_TEMP_EAST (VSF_3E4_ARR_UDT[4].BR_TEMP_EAST) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR1:4:ch2data
235 3E4DS0-SFR-TVS-VSF-220000 3E4DS0-SFR-TVS-VSF-220000_BR_TEMP_EAST CHANNEL,TVRECO2_AENTR1:4:I.Ch2Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
BEARING
signal
TEMPERATURE
to be confirmed
ATMOSPHERE SIDE 3E4DS0-TVR-BMS-RIOP-000015 SAI-2 AENTR1 4 2XSAI2 : 5,6 - SAI-08 2 AENTR1:4:I.Ch2Data AI ch 4/20/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSF-220000_FAN_VIB (VSF_3E4_ARR_UDT[4].FAN_VIB) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR1:4:ch3data
236 3E4DS0-SFR-TVS-VSF-220000 3E4DS0-SFR-TVS-VSF-220000_FAN_VIB CHANNEL,TVRECO2_AENTR1:4:I.Ch3Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTOR signal
VIBRATION
to be confirmed
LEVEL (MM/S) 3E4DS0-TVR-BMS-RIOP-000015 SAI-2 AENTR1 4 2XSAI2 : 7,8 - SAI-08 3 AENTR1:4:I.Ch3Data AI ch 4/20/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSFDPT-220000_FLOW_WEST (VSF_3E4_ARR_UDT[4].FLOW_WEST) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR1:4:ch4data
237 3E4DS0-SFR-TVS-VSFDPT-220000 3E4DS0-SFR-TVS-VSFDPT-220000_FLOW_WEST CHANNEL,TVRECO2_AENTR1:4:I.Ch4Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FLOW MEASURE
signal to beTO
confirmed
TUNNEL DIRECTION 3E4DS0-TVR-BMS-RIOP-000015 SAI-2 AENTR1 4 2XSAI2 : 9,10 - SAI-08 4 AENTR1:4:I.Ch4Data AI ch 4/20/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSFDPT-220000_FLOW_EAST (VSF_3E4_ARR_UDT[4].FLOW_EAST) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR1:4:ch5data
238 3E4DS0-SFR-TVS-VSFDPT-220000 3E4DS0-SFR-TVS-VSFDPT-220000_FLOW_EAST CHANNEL,TVRECO2_AENTR1:4:I.Ch5Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FLOW MEASURE
signal to beTO
confirmed
ATMOSPHERE DIRECTION 3E4DS0-TVR-BMS-RIOP-000015 SAI-2 AENTR1 4 2XSAI2 : 11,12 - SAI-08 5 AENTR1:4:I.Ch5Data AI ch 4/20/2025 DONE
SIGNAL, 3E4DS0-OTE02-TVS-TEF-220000_BR_TEMP_WEST (TEF_3E4_ARR_UDT[4].BR_TEMP_WEST) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR2:5:ch1data
242 3E4DS0-OTE02-TVS-TEF-220000 3E4DS0-OTE02-TVS-TEF-220000_BR_TEMP_WEST CHANNEL,TVRECO2_AENTR2:5:I.Ch1Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
BEARING
signal
TEMPERATURE
to be confirmed
TUNNEL SIDE 3E4DS0-TVR-BMS-RIOP-000015 SAI-3 AENTR2 5 2XSAI3 : 3,4 - SAI-08 1 AENTR2:5:I.Ch1Data AI ch 4/20/2025 DONE
SIGNAL 3E4DS0-OTE02-TVS-TEF-220000_BR_TEMP_EAST (TEF_3E4_ARR_UDT[4].BR_TEMP_EAST) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR2:5:ch2data
243 3E4DS0-OTE02-TVS-TEF-220000 3E4DS0-OTE02-TVS-TEF-220000_BR_TEMP_EAST CHANNEL,TVRECO2_AENTR2:5:I.Ch2Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
BEARING
signal
TEMPERATURE
to be confirmed
ATMOSPHERE SIDE 3E4DS0-TVR-BMS-RIOP-000015 SAI-3 AENTR2 5 2XSAI3 : 5,6 - SAI-08 2 AENTR2:5:I.Ch2Data AI ch 4/20/2025 DONE
SIGNAL 3E4DS0-OTE02-TVS-TEFDPT-220000_FLOW_EAST (TEF_3E4_ARR_UDT[4].FLOW_EAST) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR2:5:ch3data
244 3E4DS0-OTE02-TVS-TEFDPT-220000 3E4DS0-OTE02-TVS-TEFDPT-220000_FLOW_EAST CHANNEL,TVRECO2_AENTR2:5:I.Ch3Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FLOW MEASURE
signal to beTO
confirmed
TUNNEL/ATMOSPHERE DIRECTION 3E4DS0-TVR-BMS-RIOP-000015 SAI-3 AENTR2 5 2XSAI3 : 7,8 - SAI-08 3 AENTR2:5:I.Ch3Data AI ch 4/20/2025 DONE
SIGNAL 3E4DS0-OTE02-TVS-TEF-220000_FAN_VIB (TEF_3E4_ARR_UDT[4].FAN_VIB) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR2:5:ch4data
245 3E4DS0-OTE02-TVS-TEF-220000 3E4DS0-OTE02-TVS-TEF-220000_FAN_VIB CHANNEL,TVRECO2_AENTR2:5:I.Ch4Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTOR signal
VIBRATION
to be confirmed
LEVEL (MM/S) 3E4DS0-TVR-BMS-RIOP-000015 SAI-3 AENTR2 5 2XSAI3 : 9,10 - SAI-08 4 AENTR2:5:I.Ch4Data AI ch 4/20/2025 DONE
SIGNAL 3E4DS0-E4TE5-TVS-ANE-212000_AIR_FLOW (ANE_ARR_UDT[5].AIR_FLOW) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR3:5:ch0data
249 3E4DS0-E4TE5-TVS-ANE-212000 3E4DS0-E4TE5-TVS-ANE-212000_AIR_FLOW CHANNEL,TVRECO2_AENTR3:5:I.Ch0Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AIR FLOW
signal to be confirmed 3E4DS0-TVR-BMS-RIOP-000015 SAI-4 AENTR3 5 2XSAI4 : 1,2 - SAI-08 0 AENTR3:5:I.Ch0Data AI ch 4/20/2025 DONE
SIGNAL 3E4DS0-E4TE5-TVS-ANE-222000_AIR_FLOW (ANE_ARR_UDT[7].AIR_FLOW) IS MAPPED TO THIS
TVRECO2 TVRECO2_AENTR3:5:ch1data
250 3E4DS0-E4TE5-TVS-ANE-222000 3E4DS0-E4TE5-TVS-ANE-222000_AIR_FLOW CHANNEL,TVRECO2_AENTR3:5:I.Ch1Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AIR FLOW
signal to be confirmed 3E4DS0-TVR-BMS-RIOP-000015 SAI-4 AENTR3 5 2XSAI4 : 3,4 - SAI-08 1 AENTR3:5:I.Ch1Data AI ch 4/20/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSF-110000_EMG_STP (VSF_3E4_ARR_UDT[1].EMG_STP) IS MAPPED TO THIS
TVRWTO1 TVRWTO1_AENTR1:0:I.0
1 3E4DS0-SFR-TVS-VSF-110000 3E4DS0-SFR-TVS-VSF-110000_EMG_STP CHANNEL,TVRWTO1_AENTR1:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
EMERGENCY
signal to
STOP
be confirmed
BUTTON STATUS 3E4DS0-TVR-BMS-RIOP-000016 SDI-1 AENTR1 0 2XSDI1 : 1,2 - SDI-16 0 AENTR1:0:I.0 DI I 4/20/2025 DONE
SIGNAL, 3E4DS0-TVR-TVS-VFD-110001_VFD.BYPASS (VSF_3E4_ARR_UDT[1].VFD.BYPASS) IS MAPPED TO THIS
TVRWTO1 TVRWTO1_AENTR1:0:I.3
4 3E4DS0-TVR-TVS-VFD-110001 3E4DS0-TVR-TVS-VFD-110001_VFD.BYPASS CHANNEL,TVRWTO1_AENTR1:0:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
VFD INsignal
BYPASSto STATUS
be confirmed 3E4DS0-TVR-BMS-RIOP-000016 SDI-1 AENTR1 0 2XSDI1 : 7,8 - SDI-16 3 AENTR1:0:I.3 DI I 4/20/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSF-110000_WD_TEMP_ALM (VSF_3E4_ARR_UDT[1].WD_TEMP_ALM) IS MAPPED TO THIS
TVRWTO1 TVRWTO1_AENTR1:0:I.11
12 3E4DS0-SFR-TVS-VSF-110000 3E4DS0-SFR-TVS-VSF-110000_WD_TEMP_ALM CHANNEL,TVRWTO1_AENTR1:0:I.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WINDING
signal
TEMPERATURE
to be confirmed
ALARM 3E4DS0-TVR-BMS-RIOP-000016 SDI-1 AENTR1 0 2XSDI1 : 23,24 - SDI-16 11 AENTR1:0:I.11 DI I 4/20/2025 DONE
SIGNAL, 3E4DS0-OTE01-TVS-TEF-110000_EMG_STP (TEF_3E4_ARR_UDT[1].EMG_STP) IS MAPPED TO THIS
TVRWTO1 TVRWTO1_AENTR2:0:I.0
17 3E4DS0-OTE01-TVS-TEF-110000 3E4DS0-OTE01-TVS-TEF-110000_EMG_STP CHANNEL,TVRWTO1_AENTR2:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
EMERGENCY
signal to
STOP
be confirmed
BUTTON STATUS 3E4DS0-TVR-BMS-RIOP-000016 SDI-2 AENTR2 0 2XSDI2 : 1,2 - SDI-16 0 AENTR2:0:I.0 DI I 4/20/2025 DONE
SIGNAL, 3E4DS0-OTE01-TVS-TEF-110000_WD_TEMP_ALM (TEF_3E4_ARR_UDT[1].WD_TEMP_ALM) IS MAPPED TO THIS
TVRWTO1 TVRWTO1_AENTR2:0:I.8
25 3E4DS0-OTE01-TVS-TEF-110000 3E4DS0-OTE01-TVS-TEF-110000_WD_TEMP_ALM CHANNEL,TVRWTO1_AENTR2:0:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WINDING
signal
TEMPERATURE
to be confirmed
STATUS 3E4DS0-TVR-BMS-RIOP-000016 SDI-2 AENTR2 0 2XSDI2 : 17,18 - SDI-16 8 AENTR2:0:I.8 DI I 4/20/2025 DONE

SIGNAL, 3E4DS0-TVR-ELS-EMCC-001100-TEF-2-1_OPN_CLS_FB (TVS_EMCC_ICB_ARR_UDT[4].OPN_CLS_FB) IS MAPPED


TO THIS CHANNEL,TVRWTO1_AENTR2:0:I.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
TVRWTO1 TVRWTO1_AENTR2:0:I.9

SIGNAL 3E4DS0-TVR-ELS-EMCC-002100-TEF-1-1_OPN_CLS_FB (TVS_EMCC_ICB_ARR_UDT[1].OPN_CLS_FB) IS MAPPED


26 3E4DS0-TVR-ELS-EMCC-002100-TEF-1-1 3E4DS0-TVR-ELS-EMCC-002100-TEF-1-1_OPN_CLS_FB TO THIS CHANNEL TVRWTO1_AENTR2:0:I.11 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSED/OPEN
signal to CIRCUIT
be confirmed
TO TUNNELEXHAUST FAN 3E4DS0-TVR-BMS-RIOP-000016 SDI-2 AENTR2 0 2XSDI2 : 19,20 - SDI-16 9 AENTR2:0:I.9 DI I 4/20/2025 DONE

SIGNAL 3E4DS0-TVR-ELS-EMCC-001100-MD-DP-1-1-Trip status feed to MD-DP-1-1


(TVS_EMCC_ICB_ARR_UDT[1].TRIP_FB) IS MAPPED TO THIS CHANNEL,TVRWTO1_AENTR2:0:I.10.IN SITE ALSO,CABLE IS TVRWTO1 TVRWTO1_AENTR2:0:I.10
CONNECTED TO THE SAME SIGNAL.

SIGNAL 3E4DS0-TVR-ELS-EMCC-002100_TRIP_FB ( TVS_EMCC_ICB_ARR_UDT[11].TRIP_FB),IS MAPPED TO THIS CHANNEL


27 3E4DS0-TVR-ELS-EMCC-002100 3E4DS0-TVR-ELS-EMCC-002100_TRIP_FB TVRECO1_AENTR2:0:I.9 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
Closed/Open
signal tocircuit
be confirmed
to EMCC 2-1 incomer 3E4DS0-TVR-BMS-RIOP-000016 SDI-2 AENTR2 0 2XSDI2 : 21,22 - SDI-16 10 AENTR2:0:I.10 DI I 4/20/2025 DONE

SIGNAL 3E4DS0-TVR-ELS-EMCC-001100-MD-DP-1-1_TRIP_FB (TVS_EMCC_ICB_ARR_UDT[1].OPN_CLS_FB) IS MAPPED TO


THIS CHANNEL,TVRWTO1_AENTR2:0:I.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. TVRWTO1 TVRWTO1_AENTR2:0:I.11

SIGNAL 3E4DS0-TVR-ELS-EMCC-002100-MD-DP-2-1_TRIP_FB IS NOT MAPPED TO ANY CHANNEL .SIGNAL (3E4DS0-TVR-


28 3E4DS0-TVR-ELS-EMCC-002100-MD-DP-2-1 3E4DS0-TVR-ELS-EMCC-002100-MD-DP-2-1_TRIP_FB ELS-EMCC-002100-MD-DP-2-1_OPN_CLS_FB) IS MAPPED TO THIS CHANNEL,TVRECO1_AENTR2:1:I.14 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
FEED
be confirmed
TO MD-DP-2-1 3E4DS0-TVR-BMS-RIOP-000016 SDI-2 AENTR2 0 2XSDI2 : 23,24 - SDI-16 11 AENTR2:0:I.11 DI I 4/20/2025 DONE
SIGNAL 3E4DS0-E3TE4-TVS-JTF-111000_WD_TEMP_ALM (JTF_3E4_ARR_UDT[1].WD_TEMP_ALM) IS MAPPED TO THIS
TVRWTO1 TVRWTO1_AENTR3:0:I.6
39 3E4DS0-E3TE4-TVS-JTF-111000 3E4DS0-E3TE4-TVS-JTF-111000_WD_TEMP_ALM CHANNEL,TVRWTO1_AENTR3:0:I.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WINDING
signal
TEMPERATURE
to be confirmed
STATUS 3E4DS0-TVR-BMS-RIOP-000016 SDI-3 AENTR3 0 2XSDI3 : 13,14 - SDI-16 6 AENTR3:0:I.6 DI I 4/20/2025 DONE
SIGNAL 3E4DS0-TVR-TVS-SOST-111000_SOST.EMG_STP (JTF_3E4_ARR_UDT[1].SOST.EMG_STP) IS MAPPED TO THIS
TVRWTO1 TVRWTO1_AENTR3:0:I.7
40 3E4DS0-TVR-TVS-SOST-111000 3E4DS0-TVR-TVS-SOST-111000_SOST.EMG_STP CHANNEL,TVRWTO1_AENTR3:0:I.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
EMERGENCY
signal to
STOP
be confirmed
BUTTON STATUS 3E4DS0-TVR-BMS-RIOP-000016 SDI-3 AENTR3 0 2XSDI3 : 15,16 - SDI-16 7 AENTR3:0:I.7 DI I 4/20/2025 DONE

SIGNAL 3E4DS0-TVR-ELS-EMCC-001100-JTF-2-1-1_OPN_CLS_FB(TVS_EMCC_ICB_ARR_UDT[2].OPN_CLS_FB) IS MAPPED


TVRWTO1 TVRWTO1_AENTR3:0:I.8
TO THIS CHANNEL,TVRWTO1_AENTR3:0:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.

SIGNAL 3E4DS0-TVR-ELS-EMCC-002100-JTF-1-1-1_OPN_CLS_FB IS NOT MAPPED TO ANY CHANNEL.TRIP FB


41 3E4DS0-TVR-ELS-EMCC-002100-JTF-1-1-1 3E4DS0-TVR-ELS-EMCC-002100-JTF-1-1-1_OPN_CLS_FB (TVS_EMCC_ICB_ARR_UDT[12].TRIP_FB) IS MAPPED TO THIS CHANNEL TVRECO1_AENTR2:0:I.10. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSED/OPEN
signal to CIRCUIT
be confirmed
TO JET FAN 3E4DS0-TVR-BMS-RIOP-000016 SDI-3 AENTR3 0 2XSDI3 : 17,18 - SDI-16 8 AENTR3:0:I.8 DI I 4/20/2025 DONE

SIGNAL 3E4DS0-TVR-ELS-EMCC-002100-MD-DP-2-1_OPN_CLS_FB (MVSD_MDDP_ARR_UDT[20].OPN_CLS_FB) IS


MAPPED TO THIS CHANNEL,TVRWTO1_AENTR3:1:I.14.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
TVRWTO1 TVRWTO1_AENTR3:1:I.14

SIGNAL (3E4DS0-TVR-ELS-EMCC-002100-MD-DP-2-1_OPN_CLS_FB) IS MAPPED TO THIS


95 3E4DS0-TVR-ELS-EMCC-002100-MD-DP-2-1 3E4DS0-TVR-ELS-EMCC-002100-MD-DP-2-1_OPN_CLS_FB CHANNEL,TVRECO1_AENTR2:1:I.14 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSED/OPEN
signal to CIRCUIT
be confirmed
MD-DP 3E4DS0-TVR-BMS-RIOP-000016 SDI-6 AENTR3 1 2XSDI6 : 29,30 - SDI-16 14 AENTR3:1:I.14 DI I 4/20/2025 DONE
SIGNAL 3E4DS0-TVR-ELS-MDDP-002100-NW_OPN_CLS_FB (MDDP_ICB_ARR_UDT[3].OPN_CLS_FB) IS MAPPED TO THIS
TVRWTO1 TVRWTO1_AENTR3:2:I.10
139 3E4DS0-TVR-ELS-MDDP-002100-NW 3E4DS0-TVR-ELS-MDDP-002100-NW_OPN_CLS_FB CHANNEL,TVRWTO1_AENTR3:2:I.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN/CLOSE
signal to
STATUS
be confirmed
BREAKER (LOOP) 3E4DS0-TVR-BMS-RIOP-000016 SDI-9 AENTR3 2 2XSDI9 : 21,22 - SDI-16 10 AENTR3:2:I.10 DI I 4/20/2025 DONE
SIGNAL 3E4DS0-TVR-ELS-MDDP-002010-UPED 1-2-1-Trip status feed to Bypass UPED-1-2-1
(UPED_MDDP_ARR_UDT[3].TRIP_FB) IS MAPPED TO THIS CHANNEL,TVRWTO1_AENTR2:3:I.10.IN SITE ALSO,CABLE IS
TVRWTO1 TVRWTO1_AENTR2:3:I.10
CONNECTED TO THE SAME SIGNAL.WITH REFERENCE TO SIGNAL LIST REV 9.06.IT IS DELETED.IT NEED TO BE DELETED
171 SPARE SPARE FROM LOGIX & IO LIST. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
SPARE signal to be confirmed 3E4DS0-TVR-BMS-RIOP-000016 SDI-11 AENTR2 3 2XSDI11 : 21,22 - SDI-16 10 AENTR2:3:I.10 DI I 4/20/2025 DONE
SIGNAL 3E4DS0-TVR-ELS-MDDP-002010-UPED 1-2-1-OPEN_CLOSE status feed to Bypass UPED-1-2-1
(UPED_MDDP_ARR_UDT[3].OPN_CLS_FB) IS MAPPED TO THIS CHANNEL,TVRWTO1_AENTR2:3:I.11.IN SITE ALSO,CABLE
TVRWTO1 TVRWTO1_AENTR2:3:I.11
IS CONNECTED TO THE SAME SIGNAL.WITH REFERENCE TO SIGNAL LIST REV 9.06.IT IS DELETED.IT NEED TO BE DELETED
172 SPARE SPARE FROM LOGIX & IO LIST. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
SPARE signal to be confirmed 3E4DS0-TVR-BMS-RIOP-000016 SDI-11 AENTR2 3 2XSDI11 : 23,24 - SDI-16 11 AENTR2:3:I.11 DI I 4/20/2025 DONE

SIGNAL 3E4DS0-TVR-ELS-MDDP-002100-UPED-1-1-GROUP_LOC_FB (UPED_GROUP_ARR_UDT[1].LOC_FB) IS MAPPED TO TVRWTO1 TVRWTO1_AENTR2:3:I.12


173 3E4DS0-TVR-ELS-MDDP-002100-UPED-1-1-GROUP 3E4DS0-TVR-ELS-MDDP-002100-UPED-1-1-GROUP_LOC_FB THIS CHANNEL,TVRWTO1_AENTR2:3:I.12.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalACTUATOR
to be confirmed
GROUP 3E4DS0-TVR-BMS-RIOP-000016 SDI-11 AENTR2 3 2XSDI11 : 25,26 - SDI-16 12 AENTR2:3:I.12 DI I 4/20/2025 DONE

SIGNAL 3E4DS0-TVR-ELS-MDDP-002100-UPED-1-1-GROUP_REM_FB (UPED_GROUP_ARR_UDT[1].REM_FB) IS MAPPED TVRWTO1 TVRWTO1_AENTR2:3:I.13


174 3E4DS0-TVR-ELS-MDDP-002100-UPED-1-1-GROUP 3E4DS0-TVR-ELS-MDDP-002100-UPED-1-1-GROUP_REM_FB TO THIS CHANNEL,TVRWTO1_AENTR2:3:I.13.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalACTUATOR
to be confirmed
GROUP 3E4DS0-TVR-BMS-RIOP-000016 SDI-11 AENTR2 3 2XSDI11 : 27,28 - SDI-16 13 AENTR2:3:I.13 DI I 4/20/2025 DONE

SIGNAL 3E4DS0-TVR-ELS-MDDP-002100-UPED-1-1-1_TRIP_FB (UPED_MDDP_ARR_UDT[1].TRIP_FB) IS MAPPED TO THIS TVRWTO1 TVRWTO1_AENTR2:3:I.14


175 3E4DS0-TVR-ELS-MDDP-002100-UPED-1-1-1 3E4DS0-TVR-ELS-MDDP-002100-UPED-1-1-1_TRIP_FB CHANNEL,TVRWTO1_AENTR2:3:I.14.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
FEED
be confirmed
TO SHAFT DAMPER 3E4DS0-TVR-BMS-RIOP-000016 SDI-11 AENTR2 3 2XSDI11 : 29,30 - SDI-16 14 AENTR2:3:I.14 DI I 4/20/2025 DONE

SIGNAL 3E4DS0-TVR-ELS-MDDP-002100-UPED 1-1-1_OPN_CLS_FB (UPED_MDDP_ARR_UDT[1].OPN_CLS_FB) IS MAPPED TVRWTO1 TVRWTO1_AENTR2:3:I.15


176 3E4DS0-TVR-ELS-MDDP-002100-UPED 1-1-1 3E4DS0-TVR-ELS-MDDP-002100-UPED 1-1-1_OPN_CLS_FB TO THIS CHANNEL,TVRWTO1_AENTR2:3:I.15.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN/CLOSE
signal to
STATUS
be confirmed
FEED TO SHAFT DAMPER 3E4DS0-TVR-BMS-RIOP-000016 SDI-11 AENTR2 3 2XSDI11 : 31,32 - SDI-16 15 AENTR2:3:I.15 DI I 4/20/2025 DONE

SIGNAL 3E4DS0-TVR-TVS-SOST-111000_SOST.EMG_ENABLE_CMD (JTF_3E4_ARR_UDT[1].SOST.EMG_ENABLE_CMD) IS TVRWTO1 TVRWTO1_AENTR3:3:O.0


177 3E4DS0-TVR-TVS-SOST-111000 3E4DS0-TVR-TVS-SOST-111000_SOST.EMG_ENABLE_CMD MAPPED TO THIS RELAY,TVRWTO1_AENTR3:3:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
ENABLEsignal
EMERGENCY
to be confirmed
MODE COMMAND 3E4DS0-TVR-BMS-RIOP-000016 SDO-1 AENTR3 3 - 2SR1:11,14 SDO-16 0 AENTR3:3:O.0 DO O 4/20/2025 DONE
SIGNAL 3E4DS0-TVR-TVS-VFD-110001_VFD.FIRE_FWD_CMD (VSF_3E4_ARR_UDT[1].VFD.FIRE_FWD_CMD) IS MAPPED
TVRWTO1 TVRWTO1_AENTR1:4:O.0
193 3E4DS0-TVR-TVS-VFD-110001 3E4DS0-TVR-TVS-VFD-110001_VFD.FIRE_FWD_CMD TO THIS RELAY,TVRWTO1_AENTR1:4:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FIRE MODE
signal-FORWARD
to be confirmed
DIRECTION COMMAND 3E4DS0-TVR-BMS-RIOP-000016 SDO-2 AENTR1 4 - 2SR17:11,14 SDO-16 0 AENTR1:4:O.0 DO O 4/20/2025 DONE
SIGNAL 3E4DS0-TVR-TVS-VFD-110001_VFD.FIRE_REV_CMD (VSF_3E4_ARR_UDT[1].VFD.FIRE_REV_CMD) IS MAPPED TO
TVRWTO1 TVRWTO1_AENTR1:4:O.1
194 3E4DS0-TVR-TVS-VFD-110001 3E4DS0-TVR-TVS-VFD-110001_VFD.FIRE_REV_CMD THIS RELAY,TVRWTO1_AENTR1:4:O.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FIRE MODE
signal-REVERSE
to be confirmed
DIRECTION COMMAND 3E4DS0-TVR-BMS-RIOP-000016 SDO-2 AENTR1 4 - 2SR18:11,14 SDO-16 1 AENTR1:4:O.1 DO O 4/20/2025 DONE

SIGNAL 3E4DS0-TVR-TVS-VFD-110002_VFD.FIRE_MODE_CMD (TEF_3E4_ARR_UDT[1].VFD.FIRE_MODE_CMD) IS TVRWTO1 TVRWTO1_AENTR2:4:O.0


209 3E4DS0-TVR-TVS-VFD-110002 3E4DS0-TVR-TVS-VFD-110002_VFD.FIRE_MODE_CMD MAPPED TO THIS RELAY,TVRWTO1_AENTR2:4:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
VFD FIRE
signal
MODEto be
COMMAND
confirmed 3E4DS0-TVR-BMS-RIOP-000016 SDO-3 AENTR2 4 - 2SR33:11,14 SDO-16 0 AENTR2:4:O.0 DO O 4/20/2025 DONE
SIGNAL 3E4DS0-OTE01-TVS-UPED-110000_OPN_CLS_CMD (UPED_ARR_UDT[1].OPN_CLS_CMD) IS MAPPED TO THIS
TVRWTO1 TVRWTO1_AENTR2:4:O.13
222 3E4DS0-OTE01-TVS-UPED-110000 3E4DS0-OTE01-TVS-UPED-110000_OPN_CLS_CMD RELAY,TVRWTO1_AENTR2:4:O.13.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
SUB-DAMPER
signal to1be
OPEN/CLOSE
confirmed COMMAND 3E4DS0-TVR-BMS-RIOP-000016 SDO-3 AENTR2 4 - 2SR46:11,14 SDO-16 13 AENTR2:4:O.13 DO O 4/20/2025 DONE
TVRWTO1 TVRWTO1_AENTR3:4:ch4data
245 SPARE SPARE IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,IT IS A EXTRA CABLE.IT NEED TO BE REMOVED FROM SITE. As per CWG RLM, this channel is used at site, please check. SPARE 3E4DS0-TVR-BMS-RIOP-000016 SAI-1 AENTR3 4 2XSAI1 : 9,10 - SAI-08 4 AENTR3:4:I.Ch4Data AI ch 4/20/2025 DONE

TVRWTO1 TVRWTO1_AENTR1:5:ch0data
SIGNAL, 3E4DS0-TVR-TVS-VFD-110001_VFD.SPD (VSF_3E4_ARR_UDT[1].VFD.SPD) IS MAPPED TO THIS
249 3E4DS0-TVR-TVS-VFD-110001 3E4DS0-TVR-TVS-VFD-110001_VFD.SPD CHANNEL,TVRWTO1_AENTR1:5:I.Ch0Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTOR signal
SPEEDto FEEDBACK
be confirmed 3E4DS0-TVR-BMS-RIOP-000016 SAI-2 AENTR1 5 2XSAI2 : 1,2 - SAI-08 0 AENTR1:5:I.Ch0Data AI ch 4/20/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSF-110000_BR_TEMP_WEST (VSF_3E4_ARR_UDT[1].BR_TEMP_WEST) IS MAPPED TO THIS
TVRWTO1 TVRWTO1_AENTR1:5:ch1data
250 3E4DS0-SFR-TVS-VSF-110000 3E4DS0-SFR-TVS-VSF-110000_BR_TEMP_WEST CHANNEL,TVRWTO1_AENTR1:5:I.Ch1Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
BEARING
signal
TEMPERATURE
to be confirmed
TUNNEL SIDE 3E4DS0-TVR-BMS-RIOP-000016 SAI-2 AENTR1 5 2XSAI2 : 3,4 - SAI-08 1 AENTR1:5:I.Ch1Data AI ch 4/20/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSF-110000_BR_TEMP_EAST (VSF_3E4_ARR_UDT[1].BR_TEMP_EAST) IS MAPPED TO THIS
TVRWTO1 TVRWTO1_AENTR1:5:ch2data
251 3E4DS0-SFR-TVS-VSF-110000 3E4DS0-SFR-TVS-VSF-110000_BR_TEMP_EAST CHANNEL,TVRWTO1_AENTR1:5:I.Ch2Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
BEARING
signal
TEMPERATURE
to be confirmed
ATMOSPHERE SIDE 3E4DS0-TVR-BMS-RIOP-000016 SAI-2 AENTR1 5 2XSAI2 : 5,6 - SAI-08 2 AENTR1:5:I.Ch2Data AI ch 4/20/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSF-110000_FAN_VIB (VSF_3E4_ARR_UDT[1].FAN_VIB) IS MAPPED TO THIS
TVRWTO1 TVRWTO1_AENTR1:5:ch3data
252 3E4DS0-SFR-TVS-VSF-110000 3E4DS0-SFR-TVS-VSF-110000_FAN_VIB CHANNEL,TVRWTO1_AENTR1:5:I.Ch3Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTOR signal
VIBRATION
to be confirmed
LEVEL (MM/S) 3E4DS0-TVR-BMS-RIOP-000016 SAI-2 AENTR1 5 2XSAI2 : 7,8 - SAI-08 3 AENTR1:5:I.Ch3Data AI ch 4/20/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSFDPT-110000_FLOW_WEST (VSF_3E4_ARR_UDT[1].FLOW_WEST) IS MAPPED TO THIS
TVRWTO1 TVRWTO1_AENTR1:5:ch4data
253 3E4DS0-SFR-TVS-VSFDPT-110000 3E4DS0-SFR-TVS-VSFDPT-110000_FLOW_WEST CHANNEL,TVRWTO1_AENTR1:5:I.Ch4Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FLOW MEASUREM
signal to be confirmed
TO TUNNEL DIRECTION 3E4DS0-TVR-BMS-RIOP-000016 SAI-2 AENTR1 5 2XSAI2 : 9,10 - SAI-08 4 AENTR1:5:I.Ch4Data AI ch 4/20/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSFDPT-110000_FLOW_EAST (VSF_3E4_ARR_UDT[1].FLOW_EAST) IS MAPPED TO THIS
TVRWTO1 TVRWTO1_AENTR1:5:ch5data
254 3E4DS0-SFR-TVS-VSFDPT-110000 3E4DS0-SFR-TVS-VSFDPT-110000_FLOW_EAST CHANNEL,TVRWTO1_AENTR1:5:I.Ch5Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FLOW MEASURE
signal to beTO
confirmed
ATMOSPHERE DIRECTION 3E4DS0-TVR-BMS-RIOP-000016 SAI-2 AENTR1 5 2XSAI2 : 11,12 - SAI-08 5 AENTR1:5:I.Ch5Data AI ch 4/20/2025 DONE

SIGNAL 3E4DS0-TVR-TVS-VFD-110002_VFD.SPD (TEF_3E4_ARR_UDT[1].VFD.SPD) IS MAPPED TO THIS TVRWTO1 TVRWTO1_AENTR2:5:ch0data


257 3E4DS0-TVR-TVS-VFD-110002 3E4DS0-TVR-TVS-VFD-110002_VFD.SPD CHANNEL,TVRWTO1_AENTR2:5:I.Ch0Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTOR signal
SPEEDto FEEDBACK
be confirmed 3E4DS0-TVR-BMS-RIOP-000016 SAI-3 AENTR2 5 2XSAI3 : 1,2 - SAI-08 0 AENTR2:5:I.Ch0Data AI ch 4/20/2025 DONE

# General
PROJECT TITLE RIYADH METRO PROJECT PACKAGE 2 LINE 3 BMS SYSTEM

DOCUMENT TITLE SHOP DRAWING-DEEP UNDERGROUND STATION-3E4-BMS-INPUT/OUTPUT SCHEDULE

DOCUMENT NO. M-ANM-3E4DS0-CJ00-SCH-000002

MODULE RELAY MODULE CHANNE


SR. NO. EQUIPMENT TAG PLC TAG EASA SITE Response RLM COMMENTS FROM CWG DESCRIPTION PANEL SHORT TAG (OLD) PANEL FULL TAG (NEW) RACK NO. SLOT NO. TERMINAL NO. PLC IO ADDRESS MODULE ID DATE STATUS
ID NO. TYPE L NO.

SIGNAL 3E4DS0-OTE01-TVS-TEF-110000_BR_TEMP_WEST (TEF_3E4_ARR_UDT[1].BR_TEMP_WEST) IS MAPPED TO THIS TVRWTO1 TVRWTO1_AENTR2:5:ch1data


258 3E4DS0-OTE01-TVS-TEF-110000 3E4DS0-OTE01-TVS-TEF-110000_BR_TEMP_WEST CHANNEL,TVRWTO1_AENTR2:5:I.Ch1Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
BEARING
signal
TEMPERATURE
to be confirmed
TUNNEL SIDE 3E4DS0-TVR-BMS-RIOP-000016 SAI-3 AENTR2 5 2XSAI3 : 3,4 - SAI-08 1 AENTR2:5:I.Ch1Data AI ch 4/20/2025 DONE

SIGNAL 3E4DS0-OTE01-TVS-TEF-110000_BR_TEMP_EAST (TEF_3E4_ARR_UDT[1].BR_TEMP_EAST) IS MAPPED TO THIS TVRWTO1 TVRWTO1_AENTR2:5:ch2data


259 3E4DS0-OTE01-TVS-TEF-110000 3E4DS0-OTE01-TVS-TEF-110000_BR_TEMP_EAST CHANNEL,TVRWTO1_AENTR2:5:I.Ch2Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
BEARING
signal
TEMPERATURE
to be confirmed
ATMOSPHERE SIDE 3E4DS0-TVR-BMS-RIOP-000016 SAI-3 AENTR2 5 2XSAI3 : 5,6 - SAI-08 2 AENTR2:5:I.Ch2Data AI ch 4/20/2025 DONE

SIGNAL 3E4DS0-OTE01-TVS-TEFDPT-110000_FLOW_EAST (TEF_3E4_ARR_UDT[1].FLOW_EAST) IS MAPPED TO THIS TVRWTO1 TVRWTO1_AENTR2:5:ch3data


260 3E4DS0-OTE01-TVS-TEFDPT-110000 3E4DS0-OTE01-TVS-TEFDPT-110000_FLOW_EAST CHANNEL,TVRWTO1_AENTR2:5:I.Ch3Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FLOW MEASURE
signal to beTO
confirmed
TUNNEL/ATMOSPHERE DIRECTION 3E4DS0-TVR-BMS-RIOP-000016 SAI-3 AENTR2 5 2XSAI3 : 7,8 - SAI-08 3 AENTR2:5:I.Ch3Data AI ch 4/20/2025 DONE

TVRWTO1 TVRWTO1_AENTR2:5:ch4data
SIGNAL 3E4DS0-OTE01-TVS-TEF-110000_FAN_VIB (TEF_3E4_ARR_UDT[1].FAN_VIB) IS MAPPED TO THIS
261 3E4DS0-OTE01-TVS-TEF-110000 3E4DS0-OTE01-TVS-TEF-110000_FAN_VIB CHANNEL,TVRWTO1_AENTR2:5:I.Ch4Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTOR signal
VIBRATION
to be confirmed
LEVEL (MM/S) 3E4DS0-TVR-BMS-RIOP-000016 SAI-3 AENTR2 5 2XSAI3 : 9,10 - SAI-08 4 AENTR2:5:I.Ch4Data AI ch 4/20/2025 DONE

TVRWTO1 TVRWTO1_AENTR3:5:ch0data
SIGNAL 3E4DS0-E3TE4-TVS-ANE-111000_AIR_FLOW (ANE_ARR_UDT[2].AIR_FLOW) IS MAPPED TO THIS
265 3E4DS0-E3TE4-TVS-ANE-111000 3E4DS0-E3TE4-TVS-ANE-111000_AIR_FLOW CHANNEL,TVRWTO1_AENTR3:5:I.Ch0Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AIR FLOW
signal to be confirmed 3E4DS0-TVR-BMS-RIOP-000016 SAI-4 AENTR3 5 2XSAI4 : 1,2 - SAI-08 0 AENTR3:5:I.Ch0Data AI ch 4/20/2025 DONE

SIGNAL 3E4DS0-E3TE4-TVS-ANE-121000_AIR_FLOW (ANE_ARR_UDT[4].AIR_FLOW) IS MAPPED TO THIS TVRWTO1 TVRWTO1_AENTR3:5:ch1data


266 3E4DS0-E3TE4-TVS-ANE-121000 3E4DS0-E3TE4-TVS-ANE-121000_AIR_FLOW CHANNEL,TVRWTO1_AENTR3:5:I.Ch1Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AIR FLOW
signal to be confirmed 3E4DS0-TVR-BMS-RIOP-000016 SAI-4 AENTR3 5 2XSAI4 : 3,4 - SAI-08 1 AENTR3:5:I.Ch1Data AI ch 4/20/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSF-120000_EMG_STP (VSF_3E4_ARR_UDT[2].EMG_STP) IS MAPPED TO THIS
TVRWTO2 TVRWTO2_AENTR1:0:I.0
1 3E4DS0-SFR-TVS-VSF-120000 3E4DS0-SFR-TVS-VSF-120000_EMG_STP CHANNEL,TVRWTO2_AENTR1:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
EMERGENCY
signal to
STOP
be confirmed
BUTTON STATUS 3E4DS0-TVR-BMS-RIOP-000017 SDI-1 AENTR1 0 2XSDI1 : 1,2 - SDI-16 0 AENTR1:0:I.0 DI I 4/20/2025 DONE
SIGNAL, 3E4DS0-TVR-TVS-VFD-120001_VFD.BYPASS (VSF_3E4_ARR_UDT[2].VFD.BYPASS) IS MAPPED TO THIS
TVRWTO2 TVRWTO2_AENTR1:0:I.3
4 3E4DS0-TVR-TVS-VFD-120001 3E4DS0-TVR-TVS-VFD-120001_VFD.BYPASS CHANNEL,TVRWTO2_AENTR1:0:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
VFD INsignal
BYPASSto STATUS
be confirmed 3E4DS0-TVR-BMS-RIOP-000017 SDI-1 AENTR1 0 2XSDI1 : 7,8 - SDI-16 3 AENTR1:0:I.3 DI I 4/20/2025 DONE
SIGNAL, 3E4DS0-SFR-TVS-VSF-120000_WD_TEMP_ALM (VSF_3E4_ARR_UDT[2].WD_TEMP_ALM) IS MAPPED TO THIS
TVRWTO2 TVRWTO2_AENTR1:0:I.11
12 3E4DS0-SFR-TVS-VSF-120000 3E4DS0-SFR-TVS-VSF-120000_WD_TEMP_ALM CHANNEL,TVRWTO2_AENTR1:0:I.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WINDING
signal
TEMPERATURE
to be confirmed
ALARM 3E4DS0-TVR-BMS-RIOP-000017 SDI-1 AENTR1 0 2XSDI1 : 23,24 - SDI-16 11 AENTR1:0:I.11 DI I 4/20/2025 DONE
SIGNAL, 3E4DS0-OTE01-TVS-TEF-120000_EMG_STP (TEF_3E4_ARR_UDT[2].EMG_STP) IS MAPPED TO THIS
TVRWTO2 TVRWTO2_AENTR2:0:I.0
17 3E4DS0-OTE01-TVS-TEF-120000 3E4DS0-OTE01-TVS-TEF-120000_EMG_STP CHANNEL,TVRWTO2_AENTR2:0:I.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
EMERGENCY
signal to
STOP
be confirmed
BUTTON STATUS 3E4DS0-TVR-BMS-RIOP-000017 SDI-2 AENTR2 0 2XSDI2 : 1,2 - SDI-16 0 AENTR2:0:I.0 DI I 4/20/2025 DONE
SIGNAL, 3E4DS0-TVR-TVS-VFD-120002_VFD.BYPASS (TEF_3E4_ARR_UDT[2].VFD.BYPASS) IS MAPPED TO THIS
TVRWTO2 TVRWTO2_AENTR2:0:I.3
20 3E4DS0-TVR-TVS-VFD-120002 3E4DS0-TVR-TVS-VFD-120002_VFD.BYPASS CHANNEL,TVRWTO2_AENTR2:0:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
VFD INsignal
BYPASSto STATUS
be confirmed 3E4DS0-TVR-BMS-RIOP-000017 SDI-2 AENTR2 0 2XSDI2 : 7,8 - SDI-16 3 AENTR2:0:I.3 DI I 4/20/2025 DONE
SIGNAL, 3E4DS0-OTE01-TVS-TEF-120000_WD_TEMP_ALM (TEF_3E4_ARR_UDT[2].WD_TEMP_ALM) IS MAPPED TO THIS
TVRWTO2 TVRWTO2_AENTR2:0:I.8
25 3E4DS0-OTE01-TVS-TEF-120000 3E4DS0-OTE01-TVS-TEF-120000_WD_TEMP_ALM CHANNEL,TVRWTO2_AENTR2:0:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WINDING
signal
TEMPERATURE
to be confirmed
ALARM 3E4DS0-TVR-BMS-RIOP-000017 SDI-2 AENTR2 0 2XSDI2 : 17,18 - SDI-16 8 AENTR2:0:I.8 DI I 4/20/2025 DONE

SIGNAL 3E4DS0-TVR-ELS-EMCC-001100-TEF-2-2_OPN_CLS_FB (TVS_EMCC_ICB_ARR_UDT[5].OPN_CLS_FB) IS MAPPED


TVRWTO2 TVRWTO2_AENTR2:0:I.9
TO THIS CHANNEL,TVRWTO2_AENTR2:0:I.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.

SIGNAL 3E4DS0-TVR-ELS-EMCC-002100-TEF-1-2_OPN_CLS_FB(TVS_EMCC_ICB_ARR_UDT[10]_OPN_CLS_FB) IS MAPPED


26 3E4DS0-TVR-ELS-EMCC-002100-TEF-1-2 3E4DS0-TVR-ELS-EMCC-002100-TEF-1-2_OPN_CLS_FB TO THIS CHANNEL,TVRECO2_AENTR2:0:I.9 As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSED/OPEN
signal to CIRCUIT
be confirmed
TO TUNNELEXHAUST FAN 3E4DS0-TVR-BMS-RIOP-000017 SDI-2 AENTR2 0 2XSDI2 : 19,20 - SDI-16 9 AENTR2:0:I.9 DI I 4/20/2025 DONE
SIGNAL 3E4DS0-TVR-TVS-SOST-112000_SOST.RUN_FB (JTF_3E4_ARR_UDT[2].SOST.RUN_FB) IS MAPPED TO THIS
TVRWTO2 TVRWTO2_AENTR3:0:I.3
36 3E4DS0-TVR-TVS-SOST-112000 3E4DS0-TVR-TVS-SOST-112000_SOST.RUN_FB CHANNEL,TVRWTO2_AENTR3:0:I.3.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
JET FAN
signal
START/STOP
to be confirmed
STATUS 3E4DS0-TVR-BMS-RIOP-000017 SDI-3 AENTR3 0 2XSDI3 : 7,8 - SDI-16 3 AENTR3:0:I.3 DI I 4/20/2025 DONE
SIGNAL 3E4DS0-E3TE4-TVS-JTF-112000_WD_TEMP_ALM (JTF_3E4_ARR_UDT[2].WD_TEMP_ALM) IS MAPPED TO THIS
TVRWTO2 TVRWTO2_AENTR3:0:I.6
39 3E4DS0-E3TE4-TVS-JTF-112000 3E4DS0-E3TE4-TVS-JTF-112000_WD_TEMP_ALM CHANNEL,TVRWTO2_AENTR3:0:I.6.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
WINDING
signal
TEMPERATURE
to be confirmed
STATUS 3E4DS0-TVR-BMS-RIOP-000017 SDI-3 AENTR3 0 2XSDI3 : 13,14 - SDI-16 6 AENTR3:0:I.6 DI I 4/20/2025 DONE
SIGNAL 3E4DS0-TVR-TVS-SOST-112000_SOST.EMG_STP (JTF_3E4_ARR_UDT[2].SOST.EMG_STP) IS MAPPED TO THIS
TVRWTO2 TVRWTO2_AENTR3:0:I.7
40 3E4DS0-TVR-TVS-SOST-112000 3E4DS0-TVR-TVS-SOST-112000_SOST.EMG_STP CHANNEL,TVRWTO2_AENTR3:0:I.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
EMERGENCY
signal to
STOP
be confirmed
BUTTON STATUS 3E4DS0-TVR-BMS-RIOP-000017 SDI-3 AENTR3 0 2XSDI3 : 15,16 - SDI-16 7 AENTR3:0:I.7 DI I 4/20/2025 DONE

SIGNAL 3E4DS0-TVR-ELS-EMCC-001100-JTF-2-1-2_OPN_CLS_FB (TVS_EMCC_ICB_ARR_UDT[3].OPN_CLS_FB) IS MAPPED TVRWTO2 TVRWTO2_AENTR3:0:I.8


TO THIS CHANNEL,TVRWTO2_AENTR3:0:I.8.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.

SIGNAL 3E4DS0-TVR-ELS-EMCC-002100-TEF-1-2_OPN_CLS_FB(TVS_EMCC_ICB_ARR_UDT[8]_OPN_CLS_FB) IS MAPPED


41 3E4DS0-TVR-ELS-EMCC-002100-JTF-1-1-2 3E4DS0-TVR-ELS-EMCC-002100-JTF-1-1-2_OPN_CLS_FB TO THIS CHANNEL,TVRECO2_AENTR3:0:I.8 .IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
CLOSED/OPEN
signal to CIRCUIT
be confirmed
TO JET FAN 3E4DS0-TVR-BMS-RIOP-000017 SDI-3 AENTR3 0 2XSDI3 : 17,18 - SDI-16 8 AENTR3:0:I.8 DI I 4/20/2025 DONE
TVRWTO2 TVRWTO2_AENTR3:0:I.14
47 SPARE SPARE IN LOGIX,THERE IS NO MAPPING TO THIS CHANNEL.IN SITE,IT IS A EXTRA CABLE.IT NEED TO BE REMOVED FROM SITE. As per CWG RLM, this channel is used at site, please check. SPARE 3E4DS0-TVR-BMS-RIOP-000017 SDI-3 AENTR3 0 2XSDI3 : 29,30 - SDI-16 14 AENTR3:0:I.14 DI I 4/20/2025 DONE
SIGNAL, 3E4DS0-TVR-ELS-MDDP-002100-MVSD-1-2-1-3_OPN_CLS_FB
(MVSD_MDDP_ARR_UDT[11].OPN_CLS_FB) IS MAPPED TO THIS CHANNEL,TVRWTO2_AENTR1:2:I.7.IN SITE ALSO,CABLE TVRWTO2 TVRWTO2_AENTR1:2:I.7
104 3E4DS0-TVR-ELS-MDDP-002100-MVSD-1-2-1-3 3E4DS0-TVR-ELS-MDDP-002100-MVSD-1-2-1-3_OPN_CLS_FB IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN/CLOSE
signal to
STATUS
be confirmed
FEED TO SHAFT DAMPER 3E4DS0-TVR-BMS-RIOP-000017 SDI-7 AENTR1 2 2XSDI7 : 15,16 - SDI-16 7 AENTR1:2:I.7 DI I 4/20/2025 DONE

TVRWTO2 TVRWTO2_AENTR2:2:I.9

SIGNAL, 3E4DS0-TVR-ELS-MDDP-002100-MTED-1-2-1-4_OPN_CLS_FB (MTED_MDDP_ARR_UDT[12].OPN_CLS_FB) IS


122 3E4DS0-TVR-ELS-MDDP-002100-MTED-1-2-1-4 3E4DS0-TVR-ELS-MDDP-002100-MTED-1-2-1-4_OPN_CLS_FB MAPPED TO THIS CHANNEL,TVRWTO2_AENTR2:2:I.9.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN/CLOSE
signal to
STATUS
be confirmed
FEED TO SHAFT DAMPER 3E4DS0-TVR-BMS-RIOP-000017 SDI-8 AENTR2 2 2XSDI8 : 19,20 - SDI-16 9 AENTR2:2:I.9 DI I 4/20/2025 DONE

SIGNAL, 3E4DS0-TVR-ELS-MDDP-002100-SW_OPN_CLS_FB (MDDP_ICB_ARR_UDT[4].OPN_CLS_FB) IS MAPPED TO THIS TVRWTO2 TVRWTO2_AENTR3:2:I.10


139 3E4DS0-TVR-ELS-MDDP-002100-SW 3E4DS0-TVR-ELS-MDDP-002100-SW_OPN_CLS_FB CHANNEL,TVRWTO2_AENTR3:2:I.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN/CLOSE
signal to
STATUS
be confirmed
BREAKER (LOOP) 3E4DS0-TVR-BMS-RIOP-000017 SDI-9 AENTR3 2 2XSDI9 : 21,22 - SDI-16 10 AENTR3:2:I.10 DI I 4/20/2025 DONE

SIGNAL, 3E4DS0-TVR-ELS-MDDP-002100-MVSD-1-2-2-4_OPN_CLS_FB (MVSD_MDDP_ARR_UDT[16].OPN_CLS_FB) IS TVRWTO2 TVRWTO2_AENTR1:3:I.7


152 3E4DS0-TVR-ELS-MDDP-002100-MVSD-1-2-2-4 3E4DS0-TVR-ELS-MDDP-002100-MVSD-1-2-2-4_OPN_CLS_FB MAPPED TO THIS CHANNEL,TVRWTO2_AENTR1:3:I.7.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN/CLOSE
signal to
STATUS
be confirmed
FEED TO SHAFT DAMPER 3E4DS0-TVR-BMS-RIOP-000017 SDI-10 AENTR1 3 2XSDI10 : 15,16 - SDI-16 7 AENTR1:3:I.7 DI I 4/20/2025 DONE

SIGNAL, 3E4DS0-TVR-ELS-MDDP-002100-UPED-1-2-GROUP_LOC_FB (UPED_GROUP_ARR_UDT[2].LOC_FB) IS MAPPED TVRWTO2 TVRWTO2_AENTR2:6:I.10


171 3E4DS0-TVR-ELS-MDDP-002100-UPED-1-2-GROUP 3E4DS0-TVR-ELS-MDDP-002100-UPED-1-2-GROUP_LOC_FB TO THIS CHANNEL,TVRWTO2_AENTR2:6:I.10.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
HAND/OFF
signalACTUATOR
to be confirmed
GROUP 3E4DS0-TVR-BMS-RIOP-000017 SDI-11 AENTR2 6 2XSDI11 : 21,22 - SDI-16 10 AENTR2:6:I.10 DI I 4/20/2025 DONE

SIGNAL, 3E4DS0-TVR-ELS-MDDP-002100-UPED-1-2-GROUP_REM_FB (UPED_GROUP_ARR_UDT[2].REM_FB) IS MAPPED TVRWTO2 TVRWTO2_AENTR2:6:I.11


172 3E4DS0-TVR-ELS-MDDP-002100-UPED-1-2-GROUP 3E4DS0-TVR-ELS-MDDP-002100-UPED-1-2-GROUP_REM_FB TO THIS CHANNEL,TVRWTO2_AENTR2:6:I.11.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AUTO/OFF
signalACTUATOR
to be confirmed
GROUP 3E4DS0-TVR-BMS-RIOP-000017 SDI-11 AENTR2 6 2XSDI11 : 23,24 - SDI-16 11 AENTR2:6:I.11 DI I 4/20/2025 DONE
SIGNAL 3E4DS0-TVR-ELS-MDDP-002100-UPED 1-2_TRIP_FB (UPED_MDDP_ARR_UDT[2].TRIP_FB) IS MAPPED TO THIS
TVRWTO2 TVRWTO2_AENTR2:6:I.12
173 3E4DS0-TVR-ELS-MDDP-002100-UPED-1-2-1 3E4DS0-TVR-ELS-MDDP-002100-UPED-1-2-1_TRIP_FB CHANNEL,TVRWTO2_AENTR2:6:I.12.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
TRIP STATUS
signal to
FEED
be confirmed
TO SHAFT DAMPER 3E4DS0-TVR-BMS-RIOP-000017 SDI-11 AENTR2 6 2XSDI11 : 25,26 - SDI-16 12 AENTR2:6:I.12 DI I 4/20/2025 DONE

SIGNAL 3E4DS0-TVR-ELS-MDDP-002100-UPED 1-2_OPN_CLS_FB (UPED_MDDP_ARR_UDT[2].OPN_CLS_FB) IS MAPPED TVRWTO2 TVRWTO2_AENTR2:6:I.13


174 3E4DS0-TVR-ELS-MDDP-002100-UPED 1-2-1 3E4DS0-TVR-ELS-MDDP-002100-UPED 1-2-1_OPN_CLS_FB TO THIS CHANNEL,TVRWTO2_AENTR2:6:I.13.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
OPEN/CLOSE
signal to
STATUS
be confirmed
FEED TO SHAFT DAMPER 3E4DS0-TVR-BMS-RIOP-000017 SDI-11 AENTR2 6 2XSDI11 : 27,28 - SDI-16 13 AENTR2:6:I.13 DI I 4/20/2025 DONE

SIGNAL 3E4DS0-TVR-TVS-SOST-112000_SOST.EMG_ENABLE_CMD (JTF_3E4_ARR_UDT[2].SOST.EMG_ENABLE_CMD) IS TVRWTO2 TVRWTO2_AENTR3:3:O.0


177 3E4DS0-TVR-TVS-SOST-112000 3E4DS0-TVR-TVS-SOST-112000_SOST.EMG_ENABLE_CMD MAPPED TO THIS RELAY,TVRWTO2_AENTR3:3:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
ENABLEsignal
EMERGENCY
to be confirmed
MODE COMMAND 3E4DS0-TVR-BMS-RIOP-000017 SDO-1 AENTR3 3 - 2SR1:11,14 SDO-16 0 AENTR3:3:O.0 DO O 4/20/2025 DONE
SIGNAL 3E4DS0-TVR-TVS-VFD-120001_VFD.FIRE_FWD_CMD (VSF_3E4_ARR_UDT[2].VFD.FIRE_FWD_CMD) IS MAPPED
TVRWTO2 TVRWTO2_AENTR1:4:O.0
193 3E4DS0-TVR-TVS-VFD-120001 3E4DS0-TVR-TVS-VFD-120001_VFD.FIRE_FWD_CMD TO THIS RELAY,TVRWTO2_AENTR1:4:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FIRE MODE
signal-FORWARD
to be confirmed
DIRECTION COMMAND 3E4DS0-TVR-BMS-RIOP-000017 SDO-2 AENTR1 4 - 2SR17:11,14 SDO-16 0 AENTR1:4:O.0 DO O 4/20/2025 DONE
SIGNAL 3E4DS0-TVR-TVS-VFD-120001_VFD.FIRE_REV_CMD (VSF_3E4_ARR_UDT[2].VFD.FIRE_REV_CMD) IS MAPPED TO
TVRWTO2 TVRWTO2_AENTR1:4:O.1
194 3E4DS0-TVR-TVS-VFD-120001 3E4DS0-TVR-TVS-VFD-120001_VFD.FIRE_REV_CMD THIS RELAY,TVRWTO2_AENTR1:4:O.1.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FIRE MODE
signal-REVERSE
to be confirmed
DIRECTION COMMAND 3E4DS0-TVR-BMS-RIOP-000017 SDO-2 AENTR1 4 - 2SR18:11,14 SDO-16 1 AENTR1:4:O.1 DO O 4/20/2025 DONE

SIGNAL 3E4DS0-TVR-TVS-VFD-120002_VFD.FIRE_MODE_CMD (TEF_3E4_ARR_UDT[2].VFD.FIRE_MODE_CMD) IS TVRWTO2 TVRWTO2_AENTR2:3:O.0


209 3E4DS0-TVR-TVS-VFD-120002 3E4DS0-TVR-TVS-VFD-120002_VFD.FIRE_MODE_CMD MAPPED TO THIS RELAY,TVRWTO2_AENTR2:3:O.0.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
VFD FIRE
signal
MODEto be
COMMAND
confirmed 3E4DS0-TVR-BMS-RIOP-000017 SDO-3 AENTR2 3 - 2SR33:11,14 SDO-16 0 AENTR2:3:O.0 DO O 4/20/2025 DONE
SIGNAL 3E4DS0-OTE01-TVS-UPED-120000_OPN_CLS_CMD (UPED_ARR_UDT[2].OPN_CLS_CMD) IS MAPPED TO THIS
TVRWTO2 TVRWTO2_AENTR2:3:O.13
222 3E4DS0-OTE01-TVS-UPED-120000 3E4DS0-OTE01-TVS-UPED-120000_OPN_CLS_CMD RELAY,TVRWTO2_AENTR2:3:O.13.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
SUB-DAMPER
signal to1be
OPEN/CLOSE
confirmed COMMAND 3E4DS0-TVR-BMS-RIOP-000017 SDO-3 AENTR2 3 - 2SR46:11,14 SDO-16 13 AENTR2:3:O.13 DO O 4/20/2025 DONE
SIGNAL, 3E4DS0-TVR-TVS-VFD-120002_VFD.SPD (TEF_3E4_ARR_UDT[2].VFD.SPD) IS MAPPED TO THIS
TVRWTO2 TVRWTO2_AENTR2:4:ch0data
241 3E4DS0-TVR-TVS-VFD-120002 3E4DS0-TVR-TVS-VFD-120002_VFD.SPD CHANNEL,TVRWTO2_AENTR2:4:I.Ch0Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, this channel is spare at site, please check. MOTOR SPEED FEEDBACK 3E4DS0-TVR-BMS-RIOP-000017 SAI-1 AENTR2 4 2XSAI1 : 1,2 - SAI-08 0 AENTR2:4:I.Ch0Data AI ch 4/20/2025 DONE
SIGNAL, 3E4DS0-OTE01-TVS-TEF-120000_BR_TEMP_WEST (TEF_3E4_ARR_UDT[2].BR_TEMP_WEST) IS MAPPED TO THIS
TVRWTO2 TVRWTO2_AENTR2:4:ch1data
242 3E4DS0-OTE01-TVS-TEF-120000 3E4DS0-OTE01-TVS-TEF-120000_BR_TEMP_WEST CHANNEL,TVRWTO2_AENTR2:4:I.Ch1Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
BEARING
signal
TEMPERATURE
to be confirmed
TUNNEL SIDE 3E4DS0-TVR-BMS-RIOP-000017 SAI-1 AENTR2 4 2XSAI1 : 3,4 - SAI-08 1 AENTR2:4:I.Ch1Data AI ch 4/20/2025 DONE
SIGNAL, 3E4DS0-OTE01-TVS-TEF-120000_BR_TEMP_EAST (TEF_3E4_ARR_UDT[2].BR_TEMP_EAST) IS MAPPED TO THIS
TVRWTO2 TVRWTO2_AENTR2:4:ch2data
243 3E4DS0-OTE01-TVS-TEF-120000 3E4DS0-OTE01-TVS-TEF-120000_BR_TEMP_EAST CHANNEL,TVRWTO2_AENTR2:4:I.Ch2Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
BEARING
signal
TEMPERATURE
to be confirmed
ATMOSPHERE SIDE 3E4DS0-TVR-BMS-RIOP-000017 SAI-1 AENTR2 4 2XSAI1 : 5,6 - SAI-08 2 AENTR2:4:I.Ch2Data AI ch 4/20/2025 DONE
SIGNAL, 3E4DS0-OTE01-TVS-TEFDPT-120000_FLOW_EAST (TEF_3E4_ARR_UDT[2].FLOW_EAST) IS MAPPED TO THIS
TVRWTO2 TVRWTO2_AENTR2:4:ch3data
244 3E4DS0-OTE01-TVS-TEFDPT-120000 3E4DS0-OTE01-TVS-TEFDPT-120000_FLOW_EAST CHANNEL,TVRWTO2_AENTR2:4:I.Ch3Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FLOW MEASURE
signal to beTO
confirmed
TUNNEL/ATMOSPHERE DIRECTION 3E4DS0-TVR-BMS-RIOP-000017 SAI-1 AENTR2 4 2XSAI1 : 7,8 - SAI-08 3 AENTR2:4:I.Ch3Data AI ch 4/20/2025 DONE
SIGNAL, 3E4DS0-OTE01-TVS-TEF-120000_FAN_VIB (TEF_3E4_ARR_UDT[2].FAN_VIB) IS MAPPED TO THIS
TVRWTO2 TVRWTO2_AENTR2:4:ch4data
245 3E4DS0-OTE01-TVS-TEF-120000 3E4DS0-OTE01-TVS-TEF-120000_FAN_VIB CHANNEL,TVRWTO2_AENTR2:4:I.Ch4Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTOR signal
VIBRATION
to be confirmed
LEVEL (MM/S) 3E4DS0-TVR-BMS-RIOP-000017 SAI-1 AENTR2 4 2XSAI1 : 9,10 - SAI-08 4 AENTR2:4:I.Ch4Data AI ch 4/20/2025 DONE
SIGNAL, 3E4DS0-E3TE4-TVS-JTF-112000_BR_TEMP_WEST (JTF_3E4_ARR_UDT[2].BR_TEMP_WEST) IS MAPPED TO THIS
TVRWTO2 TVRWTO2_AENTR3:5:ch0data
249 3E4DS0-E3TE4-TVS-JTF-112000 3E4DS0-E3TE4-TVS-JTF-112000_BR_TEMP_WEST CHANNEL,TVRWTO2_AENTR3:5:I.Ch0Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
BEARING
signal
TEMPERATURE
to be confirmed
WEST SIDE 3E4DS0-TVR-BMS-RIOP-000017 SAI-2 AENTR3 5 2XSAI2 : 1,2 - SAI-08 0 AENTR3:5:I.Ch0Data AI ch 4/20/2025 DONE

SIGNAL 3E4DS0-E3TE4-TVS-ANE-111000_AIR_FLOW_SCADA (ANE_ARR_UDT[1].AIR_FLOW) IS MAPPED TO THIS


CHANNEL,TVRWTO2_AENTR3:5:I.Ch3Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL.
TVRWTO2 TVRWTO2_AENTR3:5:ch3data
3E4DS0-E3TE4-TVS-ANE-112000_AIR_FLOW_SCADA
(ANE_ARR_UDT[2].AIR_FLOW)is mapped to this channel,
252 3E4DS0-E3TE4-TVS-ANE-112000 3E4DS0-E3TE4-TVS-ANE-112000_AIR_FLOW TVRWTO1_AENTR3:5:I.Ch0Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AIR FLOW
signal to be confirmed 3E4DS0-TVR-BMS-RIOP-000017 SAI-2 AENTR3 5 2XSAI2 : 7,8 - SAI-08 3 AENTR3:5:I.Ch3Data AI ch 4/20/2025 DONE

SIGNAL 3E4DS0-E3TE4-TVS-ANE-121000_AIR_FLOW_SCADA (ANE_ARR_UDT[3].AIR_FLOW) IS MAPPED TO THIS


CHANNEL,TVRWTO2_AENTR3:5:I.Ch4Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. TVRWTO2 TVRWTO2_AENTR3:5:ch4data

SIGNAL 3E4DS0-E3TE4-TVS-ANE-122000_AIR_FLOW (ANE_ARR_UDT[4].AIR_FLOW) IS MAPPED TO THIS


253 3E4DS0-E3TE4-TVS-ANE-122000 3E4DS0-E3TE4-TVS-ANE-122000_AIR_FLOW CHANNEL,TVRWTO1_AENTR3:5:I.Ch1Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
AIR FLOW
signal to be confirmed 3E4DS0-TVR-BMS-RIOP-000017 SAI-2 AENTR3 5 2XSAI2 : 9,10 - SAI-08 4 AENTR3:5:I.Ch4Data AI ch 4/20/2025 DONE
SIGNAL 3E4DS0-SFR-TVS-VSF-120000_BR_TEMP_WEST (VSF_3E4_ARR_UDT[2].BR_TEMP_WEST) IS MAPPED TO THIS
TVRWTO2 TVRWTO2_AENTR1:5:ch1data
258 3E4DS0-SFR-TVS-VSF-120000 3E4DS0-SFR-TVS-VSF-120000_BR_TEMP_WEST CHANNEL,TVRWTO2_AENTR1:5:I.Ch1Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
BEARING
signal
TEMPERATURE
to be confirmed
TUNNEL SIDE 3E4DS0-TVR-BMS-RIOP-000017 SAI-3 AENTR1 5 2XSAI3 : 3,4 - SAI-08 1 AENTR1:5:I.Ch1Data AI ch 4/20/2025 DONE
SIGNAL 3E4DS0-SFR-TVS-VSF-120000_BR_TEMP_EAST (VSF_3E4_ARR_UDT[2].BR_TEMP_EAST) IS MAPPED TO THIS
TVRWTO2 TVRWTO2_AENTR1:5:ch2data
259 3E4DS0-SFR-TVS-VSF-120000 3E4DS0-SFR-TVS-VSF-120000_BR_TEMP_EAST CHANNEL,TVRWTO2_AENTR1:5:I.Ch2Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
BEARING
signal
TEMPERATURE
to be confirmed
ATMOSPHERE SIDE 3E4DS0-TVR-BMS-RIOP-000017 SAI-3 AENTR1 5 2XSAI3 : 5,6 - SAI-08 2 AENTR1:5:I.Ch2Data AI ch 4/20/2025 DONE
SIGNAL 3E4DS0-SFR-TVS-VSF-120000_FAN_VIB (VSF_3E4_ARR_UDT[2].FAN_VIB) IS MAPPED TO THIS
TVRWTO2 TVRWTO2_AENTR1:5:ch3data
260 3E4DS0-SFR-TVS-VSF-120000 3E4DS0-SFR-TVS-VSF-120000_FAN_VIB CHANNEL,TVRWTO2_AENTR1:5:I.Ch3Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
MOTOR signal
VIBRATION
to be confirmed
LEVEL (MM/S) 3E4DS0-TVR-BMS-RIOP-000017 SAI-3 AENTR1 5 2XSAI3 : 7,8 - SAI-08 3 AENTR1:5:I.Ch3Data AI ch 4/20/2025 DONE
SIGNAL 3E4DS0-SFR-TVS-VSFDPT-120000_FLOW_WEST (VSF_3E4_ARR_UDT[2].FLOW_WEST) IS MAPPED TO THIS
TVRWTO2 TVRWTO2_AENTR1:5:ch4data
261 3E4DS0-SFR-TVS-VSFDPT-120000 3E4DS0-SFR-TVS-VSFDPT-120000_FLOW_WEST CHANNEL,TVRWTO2_AENTR1:5:I.Ch4Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FLOW MEASURE
signal to beTO
confirmed
TUNNEL DIRECTION 3E4DS0-TVR-BMS-RIOP-000017 SAI-3 AENTR1 5 2XSAI3 : 9,10 - SAI-08 4 AENTR1:5:I.Ch4Data AI ch 4/20/2025 DONE
SIGNAL 3E4DS0-SFR-TVS-VSFDPT-120000_FLOW_EAST (VSF_3E4_ARR_UDT[2].FLOW_EAST) IS MAPPED TO THIS
TVRWTO2 TVRWTO2_AENTR1:5:ch5data
262 3E4DS0-SFR-TVS-VSFDPT-120000 3E4DS0-SFR-TVS-VSFDPT-120000_FLOW_EAST CHANNEL,TVRWTO2_AENTR1:5:I.Ch5Data.IN SITE ALSO,CABLE IS CONNECTED TO THE SAME SIGNAL. As per CWG RLM, Cable tag/ferrule is not available, terminated cable to be identify at site and mapped
FLOW MEASURE
signal to beTO
confirmed
ATMOSPHERE DIRECTION 3E4DS0-TVR-BMS-RIOP-000017 SAI-3 AENTR1 5 2XSAI3 : 11,12 - SAI-08 5 AENTR1:5:I.Ch5Data AI ch 4/20/2025 DONE