PROJECT : PROPOSED B+G+10+ROOF RESIDENTIAL APARTMENT BUILDING ON PLOT NO. PJCRC300 AT NAKHLAT AL JUMEIRAH, DUBAI - UAE.
DOCUMENT TYPE: COMPLIACE STETEMENT FOR Structural Calculation of curtain wall (GF TO 9 FLOOR ) EXCLUDED THE CURVED CORNER
CONSALTANT: LACASA ARCHITECTS & ENGINEERING CONSULTANTS
DATE: 23-06-2025
           SL.NO                                                                          CONSULTANT COMMENTS/OBSERVATIONS                                            GENERAL ALUM. RESPONSE
                                                                                                                                     GENERAL COMMENTS
                                                                                                                                                        In this calculation we use Just the coefficient in Zone 4
             1               1. Wind Loads breakup to be provided as wind load coefficients will be different for Zone 4 & Zone 5.                                 In curved Corner We Using Zone 5
                                                                                                                                                                              see page 4-5
             2               • Design Verification for the Steel insert to be provided.                                                                                      see page 6 : 11
             3               • Glass Load resistance shall be calculated as per ASTM E1300 Graphs.                                                                           see page 12:13
             4               • Deflection limits considered for Aluminum members to be mentioned in the report                                                          see page 49:50 & 79:80