Beginning January 1, 2017, UL 67 requires enhanced safety provisions for panelboards and load centers to prevent accidental contact with live circuit parts when the service disconnect is opened. Siemens provides factory installed and field installable service entrance barrier kits to comply with these requirements, which also align with the 2017 National Electric Code. Existing installations do not need retrofitting, and proper safety practices and PPE are recommended when servicing electrical equipment.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views4 pages

UL67 Document

Beginning January 1, 2017, UL 67 requires enhanced safety provisions for panelboards and load centers to prevent accidental contact with live circuit parts when the service disconnect is opened. Siemens provides factory installed and field installable service entrance barrier kits to comply with these requirements, which also align with the 2017 National Electric Code. Existing installations do not need retrofitting, and proper safety practices and PPE are recommended when servicing electrical equipment.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

UL 67 Compliant Load

Centers and Panelboards

Service entrance barrier changes to meet new enhanced safety requirements.

What is UL 67?
Beginning January 1, 2017, enhanced UL 67 safety
requirements will take effect, applying to all panelboards
and load centers with service equipment applications. To
comply, any single service disconnect panelboard or load
center must have provisions such that, when the service
disconnect is opened, no person in the field servicing the
equipment load side can make accidental contact to live
circuit parts. Barriers to protect against unintended
contact shall be constructed in such a way that they are
easily installable and removable without contacting or
damaging bare or insulated live parts.
In addition to meeting new UL 67 requirements, these
enhancements will meet the new requirements in Section
408.3(A)(2) of the 2017 National Electric Code. Although
these new service barrier requirements enhance the safety
of working on panelboards, Siemens recommends turning
off and locking all power supplying these panelboards
before working inside to avoid any potential hazards. Electrical
equipment should always be placed in an electrically safe
condition prior to working inside. Installation and maintenance
of this equipment should only be done by a qualified person.
Appropriate personal protective equipment (PPE) must be worn
and safe work practices must be followed. See NFPA 70E for
information on PPE and safe work practices.
Lighting panels and power panels
Panels are factory labeled suitable for use as service entrance equipment when NEC requirements are met. Factory installed and
field installable Service Entrance Barrier kits are now available as required by UL 67.

ND Main Breaker (With line side UL 67 barrier installed on the left side of the breaker)

Type P1 Service entrance barriers Type P4 Service entrance barriers


Field installable barriers to meet UL 67 service entrance requirements Field installable barriers to meet UL 67 service entrance requirements
Catalog Catalog number Breaker type
number Description SEBP4V1 (S)JD, (S)LD, MG
SEBKRP1V1 FD, QJ, QR Service Entrance Barrier Kit (Revised P1) SEBP4V2 CJD, CLD
SEBKRP1V2 ED Service Entrance Barrier Kit (Revised P1) SEBP4V3 JG, LG
SEBKRP1V3 BQD Service Entrance Barrier Kit (Revised P1) back-fed
SEBKRP1V4 xGB Service Entrance Barrier Kit (Revised P1) back-fed Type P5 Service entrance barriers
SEBKRP1P2P3V1 JD, LD Service Entrance Barrier Kit (RP1, P2, P3) Field installable barriers to meet UL 67 service entrance requirements
Catalog number Breaker type
Type P2 Service entrance barriers SEBP4V1 (S)JD, (S)LD, MG
Field installable barriers to meet UL 67 service entrance requirements SEBP4V2 CJD, CLD
Catalog SEBP4V3 JG, LG
number Description SEBP5V1 (S)MD, (S)ND without shield
SEBKP2V1 BL, BQD Main Service Entrance Barrier (P2 only) SEBP5V2 (S)MD, (S)ND without shield
SEBKP2V2 xGB Main Service Entrance Barrier (P2 only) SEBP5V3 Vacu-Break Switches
FD, QJ, QR Horizontal Main Service Entrance Barrier SEBP5V4 HCP Switches
SEBKP2V3
(P2, P2 with SEM3, P3)
FD, QJ, QR Vertical Main Service Entrance Barrier
SEBKP2V4
(P2, P2 with SEM3)
ED Horizontal Main Service Entrance Barrier
SEBKP2V5
(P2, P2 with SEM3)
ED Vertical Main Service Entrance Barrier
SEBKP2V6
(P2, P2 with SEM3)
SEBKP1P2P3V1 D, LD Service Entrance Barrier Kit (RP1, P2, P3)

Type P3 Service entrance barriers


Field installable barriers to meet UL 67 service entrance requirements
Catalog
number Description
SEBP3V1 Service Entrance Barrier Kit CFD, FD (P3 only)
SEBKP1P2P3V1 JD, LD Service Entrance Barrier Kit (RP1, P2, P3
Load centers and meter combos
Touchsafe barriers are required for any single main service
entrance application for a panel covered under UL 67. Line
Terminal Barriers will be included in Main Breaker Load
Centers and Single Main Meter Combos manufactured after
January 1, 2017.
Single phase and 3-phase main breaker kits will include a
barrier. Field installable kits are being created for replacements
if needed and line terminal barriers are being added to hold
down kits that can be used in back-fed applications. The
barriers are designed to have minimal interference during
load center installation, and can be removed and reattached
as necessary.

Service entrance barriers


Catalog number Description

ECLTB1 For EQ Main Breakers / MBK kits 100A-125A

ECLTB2 For EQ Main Breakers / MBK kits 150A-225A

ECLTB3 For QN / QNR type breakers

ECLTB4 For QR 3 phase breakers

For 2 Pole QP / MP-T type breakers for EQIII


ECMBR1
(extruded basepan) and Line 5 Load Centers

For 2 Pole QP / MP-T type breakers to be used with Ultimate LCs (now ES / PL),
ECMBR2
Murray or Rock Solid

ECMBR3 For 3 Pole QP / MP-T type breakers to be used with PL, ES 3 phase load centers

ECLX387HD For 2 Pole MP-T type breakers in legacy Murray load centers
Questions and Clarifications Page

Q: When is the COMPAS launch?


A: COMPAS Launch is set for week of Oct. 24. Click the check
box to include a service entrance barrier kit in BOM.

Q. What if a job has already been ordered, but is


shipping after Jan. 1, 2017?
A. Please contact the plant directly or customer service to
coordinate a service entrance barrier kit to be shipped to
the job site.

Q. Does UL 67 apply to any other Siemens products?


A. Switchboards, Motor Control Centers and Low Voltage
Switchgear are not affected by UL 67 because they already
have their own service entrance requirements.

Q. What about panelboards and load centers already


installed in the field that do not have service entrance
barrier provisions?
A. According to the standard, existing field sites/jobs do not
need to be retrofitted.

Q. How do I work with and around the barrier when it is


installed?
A. Instruction sheets will come with every kit. Sheets can also
be downloaded online in case they are lost.

For more information, please contact Subject to changes and errors. The information given
Published by in this document only contains general descriptions and/or
our Customer Support Center.
Siemens Industry, Inc. 2016. performance features which may not always specifically
Phone: 1-800-241-4453
Siemens Industry, Inc. E-mail: info.us@siemens.com reflect those described, or which may undergo modification
5400 Triangle Parkway in the course of further development of the products. The
usa.siemens.com/panelboards requested performance features are binding only when they
Norcross, GA 30092
Order No.: PDBR-SEB67-1216 are expressly agreed upon in the concluded contract.
Printed in U.S.A.
© 2016 Siemens Industry, Inc.