Catalogue Havells InstaShift
Catalogue Havells InstaShift
Catalogue 2023
1
ABOUT US
Care 360
first FMEG Company to offer door
step service via its initiative
2
CONTENTS
InstaShift Manual Changeover Switches 4
3
MANUAL
CHANGEOVER SWITCH
C
4
The InstaShift Manual Changeover Switches
are manually operated four pole Changeover Switches,
having ratings 40 A to 800 A in 4 different frame sizes. The
main components of this changeover switch are proven
technology devices, fulfilling all the requirements for LV
distribution.
USPs
• 3 Stable Positions
• Staggered Terminals • Direct Aluminium Cable Connection
• Load and Line Reversibility • Easy wiring facilities for auxiliary switches
• Neutral Pole Interchangeability • 360° Mounting Orientation
• IP 43 Enclosure available • Voltage Sensing Kit for Automatic Transfer Switching Equipment
Unit
Rating A
Reference Standards
No. of Poles
No. of Breaks per pole
Electrical Characteristics
Rated Operational Voltage (Ue) VAC
Rated Insulation Voltage (Ui) V
Rated Impulse Withstand Voltage (Uimp) kV
Rated Frequency Hz
Pollution Degree
6
IS00 IS02 IS04 IS06
IS00A IS00C IS02A IS02C IS04A IS04C IS06A IS06C
40 A, 63 A, 80 A, 100 A 125 A 125 A, 160 A, 200 A 250 A 250 A, 315 A 400 A 400 A, 630 A 800 A
IS / IEC 60947-3, IEC 60947-3, IS/IEC 60947-6-1, IEC 60947-6-1
FP
2
415 VAC
1000 V
6 kV 8 kV 12 kV 12 kV
50 Hz / 60 Hz
3 3 3 3
40 A 63 A 80 A 100 A 125 A 125 A 160 A 200 A 250 A 250 A 315 A 400 A 400 A 630 A 800 A
40 A 63 A 80 A 100 A 125 A 125 A 160 A 200 A 250 A 250 A 315 A 400 A 400 A 630 A 800 A
Unmarked Terminals
16 25 35 50 50 70 120 150 185 185 2x120 2x150 2x150 2x300 3x240
16 mm 22 mm 30 mm 40 mm 40 mm 50 mm 50 mm 60 mm
2 mm 4.7 mm 5 mm 8 mm 8 mm 2x8 mm 2x8 mm 2x10 mm
3.7 Nm 10 Nm 20 Nm 27 Nm
PC
5 - 10 10 -
- - - - 12.6
7.7 - 17 17 25.2
40 63 80 100 - 125 160 200 250 250 315 400 400 630 800
- - - - - - - - 250 315 400 400 500 630
- - - - - - - - - 200 200 200 200 400 400
7
Dimension
Open Execution
R
S
T
IS00 IS02 - IS06
DOOR DRILLING DOOR DRILLING
4.5
3
37
30
25
35.5
37 30
J J J
H
B
D
E
F
G
J J J K K C1
M
O
P N
8
With Enclosure
Frame L M N O P Q
IS00 260 200 260 215 4.3 181
IS02 325 275 370 300 4.3 241
IS04 410 340 420 350 4.3 241
IS06 500 390 730 460 4.3 326
Exploded View
1. Changeover Switch
8 2. Line Terminals
6 3. Load Terminals
3
10 4. Contact Pocket
7
5. Mechanism Housing
11 6. Shorting Link
1
7. Mounting Bracket
4
13 8. Phase Separator
9. Source Separator
5 10. Cam Holding Housing Cover
15 14
11. Auxiliary Switches
2
12 12. Rotary Handle
13. Shaft
14. Cam
15. Center Shaft
9
MOTORIZED
CHANGEOVER SWITCH
10
Dimensions MOTORIZED
CHANGEOVER SWITCH
USPs
• 3 Stable Positions
• Staggered Terminals • Direct Aluminium Cable Connection
• Load and Line Reversibility • Easy wiring facilities for auxiliary switches
• Neutral Pole Interchangeability • 360° Mounting Orientation
• IP 43 Enclosure available • Voltage Sensing Kit for Automatic Transfer Switching Equipment
Exploded View
1. Changeover Switch
2. Motorized Unit
1
3. Dummy Cover
4. Emergency Handle
Fascia Description
4
3
4 5. Padlock Lever
7. Position Window
11
Technical Characteristics
Unit
Rating A
Reference Standards
No. of Poles
No. of Breaks per pole
Electrical Characteristics
Rated Operational Voltage (Ue) VAC
Rated Insulation Voltage (Ui) (Power Circuit) V
Rated Insulation Voltage (Ui) (Control Circuit) V
Rated Impulse Withstand Voltage (Uimp) (Power Circuit) kV
Rated Impulse Withstand Voltage (Uimp) (Control Circuit) kV
Rated Frequency Hz
Pollution Degree
Data according to IEC 60947-3, IS / IEC 60947-3
Conventional thermal current (Ith) at 50 °C A
Conventional enclosed thermal current (Ithe) at 50 °C A
Rated Operational Current (Ie)
415 VAC, AC-21A/ AC-22A / AC-23A A
415 VAC, AC-21A/ AC-22A A
Rated Breaking Capacity for AC-23A A
Rated Making Capacity for AC-23A A
Rated Breaking Capacity for AC-22A / AC-21A
Rated Making Capacity for AC-22A / AC-21A
Short-time withstand (Icw), 1s kArms
Short-circuit making capacity, Icm kApeak
Rated short-circuit current at 415 V, 50 Hz / 60 Hz kArms
Mechanical Endurance O-I-O-II-O cycle
Electrical Endurance
Termination
Max. Al. cable with lug mm2
Max. link width mm
Max. link thickness mm
Termination tightening torque Nm
Weight kg
Data as per IS/IEC60947-6-1, IEC 60947-6-1
Conventional thermal current (Ith) at 50 °C A
Conventional enclosed thermal current (Ithe) at 50 °C A
Rated Operational current (Ie):
415 VAC, AC-31B A
415 VAC, AC-32B A
415 VAC, AC-33B A
Short-time withstand (Icw) for 30 ms kArms
Short-time withstand (Icw) for 60 ms kArms
Short-circuit making capacity (Icm) kApeak
Switching time (rated voltage, after receiving
command)
Time of transfer I-II or II-I s
I-0 or II-0 s
Time of contact transfer (black-out I-II) minimum s
Power supply
Min./max. power VAC
Control supply power demand
Demand/rated power VA
12
IS02 IS04 IS06
IS02A IS02C IS04A IS04C IS06A IS06C
125 A, 160 A, 200 A 250 A 250 A, 315 A 400 A 400 A, 630 A 800 A
IS / IEC 60947-3, IS/IEC 60947-6-1
FP
2
415 VAC
1000 V
300 V
8 kV 12 kV 12 kV
4 kV
50 Hz / 60 Hz
3
125 A 160 A 200 A 250 A 250 A 315 A 400 A 400 A 630 A 800 A
125 A 160 A 200 A 250 A 250 A 315 A 400 A 400 A 630 A 800 A
125 A 160 A 200 A 250 A 250 A 315 A 400 A 400 A 630 A 800 A
125 A 160 A 200 A 250 A 250 A 315 A 400 A 400 A 630 A 800 A
125 A 160 A 200 A 250 A 250 A 315 A 400 A 400 A 630 A 800 A
- - - - 250 A 315 A 400 A 400 A 500 A 630 A
200 A 200 A 200 A 200 A 400 A 400 A
10 kArms 10 kArms -
- - 12.6 kArms
17 kApeak 17 kApeak 25.2 kApeak
0.8 s 0.9 s
0.5 s
0.3 s 0.4 s
Control Inputs
[Pin 31: Remote Mode]
The remote mode is active when Pin 31 (Ctrl) is closed with pin 36 (C). Only when pin 31 is closed with 36 other inputs 33, 34 and 35
are activated.
NOTE: Pin 32 (OFF) is an exception and its activation state doesn’t depends on the state of 31. Even if 31 is not closed with 36, pin
32 will remain active.
Action on pin 32 is having priority over actions on other input pins.
Output Status
[Pin 41|42: Product available output]
Pin 41|42 is a normally open contact which remains closed when the product is available to operate.
This contact gives the feedback about the product availability and its capacity to be operated remotely or automatically.
[Pin 43: Common] Common pin to be used with pin 44, 45, 46
[Pin 44: Position 0 Status] Pin 44 closed with pin 43 shows the Position 0 of the RTSE. This signal can be used for LED/buzzer etc.
[Pin 45: Position II Status] Pin 45 closed with pin 43 shows the Position II of the RTSE. This signal can be used for LED/buzzer etc.
[Pin 46: Position I Status] Pin 46 closed with pin 43 shows the Position I of the RTSE. This signal can be used for LED/buzzer etc.
Power Connector
InstaShift RTSE is to be powered between terminals 8 and 9 with a supply within the limits of:
208 Vac – 277 Vac ± 20% (166 Vac – 332 Vac) 50 Hz / 60 Hz ±10%
14
Auto / Manual / Padlock Knob
There are three different Modes of Operation of Switch; Manual Mode, Automatic Mode and Padlock Mode. This knob is
to provide visual indication for different Modes of Operation of Changeover Switch.
Manual Mode
(Fault LED will
activate in this position)
Auto Mode
Padlock Mode*
This lever to
be pulled for
padlocking
*Padlock can be put in this condition
Wiring Diagram
Source I Source II
To Load
N L1 L2 L3 L3 L2 L1 N
Output Status
Control Inputs Product
240 V / 2A
24 V / 2 A
41 42 43 44 45 46
31 32 33 34 35 36
15
Dimension
Open Execution
A
H
B B B
CONTROL CONNECTION
& DISCONNECTION AREA
C
J
D
E M
N
G
F
R R
Q
P
O
HANDLE 124
48
86
16
With Enclosure
S 34
T W 19
U
V
DOOR CUTOUT
192 20
67
55
112
36
38
Frame Rating
Overall Dimnesions
(A)
A B C D E F G H I J K L M N O P Q R S T U V W
125 339 48 137 154 22 27 347 205.9 143 100 6.2 8.5 8.5 158 253 143 47 3.2 435 375 300 370 250
160 339 48 137 154 22 27 347 205.9 143 100 6.2 8.5 8.5 158 253 143 47 3.2 435 375 300 370 250
IS02
200 339 48 137 154 22 27 347 205.9 143 100 6.2 8.5 8.5 159 253 143 47 3.2 435 375 300 370 250
250 CD 339 48 137 154 22 27 347 205.9 143 100 6.2 8.5 8.5 160 253 143 47 4 435 375 300 370 250
250 399 60 160 194 34 41 245 265.5 143 112 6.2 17 11.2 160 253 144 47 4 511 430 350 420 250
IS04 315 399 60 160 194 34 41 245 265.5 143 112 6.2 17 11.2 160 253 144 47 4 511 430 350 420 250
400 CD 405 66 179 213 40 50 285 265.5 143 112 6.2 17 11.2 160 253 144 47 4 511 430 350 420 250
400 429 70 230 260 44 50 407 294.3 190.9 160 8.2 15 12.5 220 300 184 61 6 565 472 460 730 298
IS06 630 429 70 230 260 44 50 407 294.3 190.9 160 8.2 15 12.5 220 300 184 61 6 565 472 460 730 298
800 CD 429 80 250 295 50 50 407 294.3 190.9 160 8.2 22.5 12.5 220 300 185.4 61.7 8 565 472 460 730 298
17
Ordering Code - Manual Changeover Switch
18
AUTOMATIC
TRANSFER SWITCH
19
AUTOMATIC
TRANSFER SWITCH
1. Changeover Switch
2. Motorized Unit
1
3. Display Module B Type
4 4. Emergency Handle
3
• Allows Setting for : • Offers measurement of Line & phase voltage and Frequency
- Under and Over Voltage
- Under and Over Frequency
1. Changeover Switch
1 2. Motorized Unit
3. Display Module M
Type
4. Emergency Handle
4 3
20
Exploded View - H Type
Salient Features:
• Remote connectivity enabling monitoring and controlling
• Feasibility of remote configuration through Cloud
• Wi-Fi connectivity
• Wired ETHERNET for achieving real-time monitoring and display of energy parameters
• Data logger showing event history
• Multiple ports for communication with genset control module: RS485, RS232
• Parameters adjust function: users can adjust parameters via USB port
1. Changeover Switch
2. Motorized Unit
4. Emergency Handle
4
21
Accessories - MTSE
Castell Lock
Auxiliary Switch
*Available on request
22
Accessories - RTSE
MTSE to RTSE Conversion Kit
*Available on request
23
REGIONAL & BRANCH OFFICES:
NORTH - REGIONAL OFFICE: Corporate Office: QRG Towers, 2D, Sector-126, Expressway, Noida-201304, Tel: 0120-3331000, Delhi: 011-47676700, 23888200, Chandigarh: 0172-4232400-401,
Dehradun: 0135-6670202, Haldwani: 05946-222935/222933, Noida / Haryana: 0120-3331000, Ludhiana: 0161-4676000/24,
Amritsar: 0183-5202400/401, Jammu: 0191-2478330, 2479330, Sri Nagar: 0194-2459248, Jaipur: 0141-4211000, 4211011, Jodhpur: 9214201640/41,
Lucknow: 0522- 4921600/4921649, Kanpur: 0512-6710400
EAST - REGIONAL OFFICE: Kolkata: ICC Tower, 5th Floor, 4 India Exchange Place, Kolkata-700001, Tel: 033-40129851/52, Bhubaneshwar: 0674-6668101/102/103/104, Guwahati: 0361-2458923,
2134521, Siliguri: 0353-2525907, Ranchi: 0651-2244861, 2244862, 2244864, 2244868, 2244869, Jamshedpur: 0657-6542492, 09234369436, Patna: 0612-2207221, 2207222, 2207223, 2655518
WEST - REGIONAL OFFICE: 1271, Solitaire Corporate Park, Bldg. No. 12, 7th Floor, Andheri - Ghatkopar Link Road, Chakala, Andheri (East), Mumbai- 400093.
Tel: 022 - 67298600-602, Ahmedabad: 079-40061111, 40060738/740, Indore: 0731-4219444/4219422, 0731-2572340, Rajkot: 0281-2481112, 2921212, Nagpur: 0712-2240932, 2242692, 2242699
Pune: 020-26056175-76, Raipur: 0771-4243400/01, Surat: 0261-2350137, 9979890137, Jabalpur: 0761-4064491, Bhopal: 0755-4271544, 0755-4011025,
SOUTH - REGIONAL OFFICE: Chennai: Sigapi Achi Building, No. 18 / 3, 6th Floor, Rukmani Lakshmipathy Road, Egmore, Chennai-600008, Tel: 044-42280600, 605, Bangalore: 080-49075000,
Coimbatore: 0422-4550200/282, Hyderabad: 040-27533372, 27533355, 27533632, Cochin: 0484-4099000, Calicut: 0495-4019193/4/5, Trivandrum: 0471-4015323, Vizag: 0891-6514339,
Vijayawada: 0866-2546161/62/67/68/69, Madurai: 0452-4267000, Hubli: 0836-4248660, Trichy: 0431-4041005/06
Representative Offices: • Goa • Solapur • Gwalior • Kathmandu • Bhopal • Kolapur • Vadodara
Warranty Policy: Terms & Conditions
All the products listed in the price list carry a warranty, against manufacturing Prices are in Indian `.
defects for a period of 18* months from the date of purchase / 12 months This Price List supersedes all our previous Price Lists.
from the date of commissioning, whichever is earlier. Prices are subject to change without notice.
*Proof of purchase to be retained to avail warranty. Company reserves the right to issue amendments, which may arise due to any errors in the price list.
Actual products may vary in colour, design, description and colour combination etc. Although every effort has been made to ensure accuracy in the compilation of the technical detail within this
publication. Specifications & performance data are constantly changing.
“Copyright Subsists. Imitation of trade dress, graphics and color scheme of this document is a punishable offence.”
Note: All Products to be billed at 18% *GST (Subject to change as per Govt. Notification).