7090 Safety Information
7090 Safety Information
4.0
Coriant 7090
Safety Information (SI)
A42022-L5984-A060-04-7630
The information in this document is subject to change without notice and describes only the product
defined in the introduction of this documentation. This documentation is intended for the use of
Coriant customers only for the purposes of the agreement under which the document is submitted,
and no part of it may be used, reproduced, modified or transmitted in any form or means without the
prior written permission of Coriant. The documentation has been prepared to be used by professional
and properly trained personnel, and the customer assumes full responsibility when using it. Coriant
welcomes customer comments as part of the process of continuous development and improvement of
the documentation.
The information or statements given in this documentation concerning the suitability, capacity, or
performance of the mentioned hardware or software products are given "as is" and all liability arising
in connection with such hardware or software products shall be defined conclusively and finally in a
separate agreement between Coriant and the customer. However, Coriant has made all reasonable
efforts to ensure that the instructions contained in the document are adequate and free of material
errors and omissions. Coriant will, if deemed necessary by Coriant, explain issues which may not be
covered by the document. Coriant will correct errors in this documentation as soon as possible.
IN NO EVENT WILL CORIANT BE LIABLE FOR ERRORS IN THIS DOCUMENTATION OR FOR
ANY DAMAGES, INCLUDING BUT NOT LIMITED TO SPECIAL, DIRECT, INDIRECT, INCIDENTAL
OR CONSEQUENTIAL OR ANY LOSSES, SUCH AS BUT NOT LIMITED TO LOSS OF PROFIT,
REVENUE, BUSINESS INTERRUPTION, BUSINESS OPPORTUNITY OR DATA,THAT MAY ARISE
FROM THE USE OF THIS DOCUMENT OR THE INFORMATION IN IT.
This documentation and the product it describes are considered protected by copyrights and other
intellectual property rights according to the applicable laws. Other product names mentioned in this
document may be trademarks of their respective owners, and they are mentioned for identification
purposes only.
Copyright © Coriant 2017. All rights reserved.
Table of Contents
This document has 39 pages.
1 Preface ..............................................................................................................6
1.1 Intended audience ............................................................................................ 6
1.2 Structure of this document................................................................................ 6
1.3 Symbols and conventions................................................................................. 7
1.3.1 Symbols for warnings and cautions ...................................................................7
1.3.2 Symbols for notes ..............................................................................................7
1.3.3 Conventions used ..............................................................................................7
1.4 History of changes ............................................................................................ 8
Summary of Changes
Issue Issue Date Remarks
1 June 2014 Initial version.
2 February 2015 Updated for Coriant 2.0 10.
3 February 2017 Updated for Coriant 3.0 10.
4 November 2017 Updated for Coriant 4.0.
1 Preface
The Safety Information manual provides legal statements of compliance, and
instructions on how to avoid personal injury, system damage, and
environmental hazard when operating Coriant 7090-240 M, 7090-92 M, 7090-
8 M, 7090-5 M (hereinafter referred to as 7090).
DANGER!
Will result in death or serious (irreversible) personal injury.
WARNING!
Could result in death or serious (irreversible) personal injury.
CAUTION!
May result in minor or moderate (reversible) personal injury.
NOTICE:
Property damage or malfunction. No personal injury is possible.
Tip.
Representation Meaning
“Inverted commas” Window or wizard titles are represented in “inverted commas”.
Example: Open the “Help and Support Center” window. The “New
Connection” wizard is displayed.
Bold Any field or text in the GUI is represented in bold type.
Example: Click Shutdown and then click OK to turn off the computer.
Italic Variables and file extensions are represented in italic.
Example: Enter 192.168.0.1 in the IP address field. Click OK to
produce a .pdf rendition.
<Angle brackets> Used for keyboard actions or place holders for concrete names or
values are represented in <angle brackets>. If used for a filename the
courier font must be used also.
Example: The naming convention for the log files is <NEname>.txt,
where <NEName> is the name of the NE sending the messages.
Press <CTRL> + <ALT>+<DEL> to open the task manager.
Representation Meaning
> Used for menu sequences.
Example: Click File > Print… to print the document.
• Personnel must possess sufficient training and knowledge to comply with all
relevant industry practices regarding electrically-powered equipment and
static-sensitive components.
• Personnel must possess sufficient training and knowledge to comply with all
facets of laser safety in telecommunications equipment according to IEC
60825-2:2004+A1:2006+A2:2010.
• Identification of the location type at all accessible locations of the entire end-
to-end system.
Ensuring that the hazard levels are not exceeded for those location types.
Tip
Unless indicated by state specification, all standards (e.g., European Norm
(EN), International Electrotechnical Commission (IEC), Underwriters
Laboratories (UL)) mentioned in the following paragraphs pertain to the latest,
most up-to-date issue of the respective standard.
Replacement parts
To replace any parts of devices or cables, use only original spare parts or
parts which are explicitly licensed by the manufacturer.
connected to interfaces that connect to the Outside Plant (OSP) or its wiring.
These interfaces are designed for use as intra-building interfaces only (Type 2
ports as described in GR-1089-CORE, Issue 6) and require isolation from the
exposed OSP cabling.
The addition of Primary Protectors in not sufficient protection to connect these
interfaces metallically to OSP wiring.
For shelves mounted in racks, the fuses/circuit breakers are located in a fuse
panel/breaker panel in the rack or in an equivalent device. For each shelf four
fuses/circuit breakers are for the working power supply and four fuses/circuit
breakers are for the protection power supply.
When handling the power supply or working on it, observe the safety
measures described in the standards EN 50110-1 and EN 50110-2 (operation
of electrical systems).
2.5.5 Protection against over-voltage on the -48 V/-60 V power supply input
Depending on the device type, the laser radiation may be invisible to the
human eyes.
DANGER!
The 7090 system contains laser devices which operate at high optical power
levels. Never look into the end of a fiber, fiber connector, fiber patchcord, or
fiber pigtail. Permanent eye damage or blindness can result if exposed to such
optical power levels, even for extremely short durations.
Always use whatever safety devices are supplied (caps, shutters, etc.). Read
and follow all laser warning labels affixed to the shelf. Use only approved
filtered or attenuated viewing aids or video equipment.
Devices and cards displaying either of the following warning labels contain
laser devices (see Figure 1).
DANGER!
If incorrect (non-approved) optical instruments are used, there is a risk of
damage to eyes and personal injuries.
Use only approved filtered or attenuation viewing aids.
Tip
Limitation to these IEC 60825-2 location types refer to both transmission path
and central office.
Tip
Conformity with hazard level 1 operation in IEC 60825-
2:2004+A1:2006+A2:2010 “Controlled Locations” or “Restricted Locations”
support is lost, if Installation and Service Organization, or Operating
Organization do not follow the IEC 60825-2:2004+A1:2006+A2:2010
recommendations, or do not follow the Coriant instructions in this document.
To ensure safe operation of the entire optical path, the laser safety shutdown
will activated automatically.
To avoid health hazard, observe the regulations regarding protection against
radiation from laser devices:
• EN 60825-1:2007 and EN 60825-2:2004+A1:2006+A2:2010
• IEC 60825-1:2007 and IEC 60825-2:2004+A1:2006+A2:2010
Be extremely cautions when connecting or disconnecting fibers, since high
optical power levels can be present at card connectors or fiber ends.
To guarantee acceptable system performance, any fibers supplied by the
customer that are connected to 7090 components must be terminated with LC
connectors. Failure to do so results in unacceptable optical performance. For
Small Form-Factor Pluggable (SFP)/10 Gbps Small Form-Factor Pluggable
(XFP) modules, use only LC connectors without protective cap.
Personnel must be acquainted with and follow all safety and handling
guidelines as published by the relevant regulatory agencies for the hazard
level(s) designated. Responsibility for identifying, studying, and adhering to
applicable laser, electrical, mechanical, and other safety standards for the
installation, operation, and maintenance of this equipment is limited to the
operator.
After mounting the systems into the rack, and before attaching the connecting
cables and commissioning, ground connections, and potential balancing
connections in accordance with EN 50310 and European Telecommunications
Standard (ETS) 300253 must be checked.
The grounding must be effective as long as external cables are connected to
the equipment.
If a shelf is not installed in a rack, ensure proper grounding according to ETS
300253.
Grounding or potential balancing points are normally labelled with one of the
signs shown in Figure 2 and Figure 3.
In both rack and wall mounted applications, the shelf protective earthing must
be assured by connecting a PE cable as depicted in the Interconnect, Cabling
and Mechanical Assembly (ICMA) manual.
The PE cable must be connected before each other cable connection and
disconnected last.
WARNING!
In order to connect/disconnect any connector panel cabling.
First remove the shelf fan unit. Otherwise, there is a risk of personal
injury/damage to the equipment.
Equipment cooling
CAUTION!
The high-speed rotating fan blade can seriously injure the fingers and hands.
Never approach or come in contact with the fan. Ensure the fan has been
completely stopped before being touched.
Always provide adequate air cooling. The populated shelf must not be
operated without fan unit for more than two minutes.
The standard of “Telcordia Technologies Generic Requirements GR-63-CORE
Issue 3, March 2006, (objective O4-20[78])” defines limit values for heat
dissipation. As 7090 operation may significantly exceed heat dissipation limit
values, it is recommended to place the equipment in a well-ventilated area.
Fully equipped racks may require air conditioning to ensure proper ventilation.
To ensure adequate airflow into the shelf’s intake area, all slots of the shelf
must be filled with either cards or filler panels (required for the entire input
temperature range).
Information on weight
The maximum weight to be lifted by one person is 18 kg.
On extremely hot surfaces, a label featuring the text “HOT POINT” in red on a
white background is added (see Figure 7). It marks the highest injury danger.
All cards are pluggable. They have a mechanical coding on their connectors.
This ensures that each card can only be pushed fully into a slot intended for
this type of card in the shelf.
All cards can be inserted and extracted with the power supply still connected
without damaging the card or other cards in the shelf.
WARNING!
Do not remove any card during its initialization process
Before removing the card, make sure the all cable/fiber connections on the
card are removed and no traffic is disrupted.
Be careful not to pinch your fingers when unlocking the levers on the card as
shown in Figure 8.
Connector types
To guarantee acceptable system performance, any fibers supplied by the
customer that are connected to 7090 components must be terminated with LC
connectors. Failure to do so may result in unacceptable optical performance.
For SFP/XFP modules, use only LC connectors without a protective cap.
•Laser safety hazard level 1 may be available, if other connections have been
established. In the last resort, class 3B laser power may occur at open fiber
ends.
• The minimum bending radius for optical fibers is 17 mm.
• The lines must not be kinked even for brief periods of time. Avoid applying
any tractive force to the connectors.
• Shock loads should be avoided when working with connectors. Shock loads
can lead to mechanical damage to the faces of the optical connectors and
thereby increase attenuation.
• When making an optical connection, make sure that the individual
connection elements are correctly and securely fastened.
• To handle optical cards, follow the information given in Section regarding
electrostatically-sensitive components.
WARNING!
Broken optical fibers can be very sharp and can cause injury to eyes or skin.
Small pieces of fiber that are nearly invisible can penetrate the skin or even
the eyes causing enormous damage. Eye injuries might also occur due to light
coming out of broken edges.
Providing good access to optical connectors in the front panel of the cards will
make it easier to unplug the damaged optical connections.
WARNING!
If incorrect (non-approved) optical instruments are used, there is risk of
damage to eyes and of personal injuries.
Use only approved filtered or attenuation viewing aids.
If the face of the connector is dirty, follow the procedure in the 7090 until all
dirty particles have been removed.
Handling batteries
Some equipment may contain accumulators or batteries with different
technologies.
Observe the following international standards, where applicable:
• IEC 60130-17 (device interconnections)
• IEC 61429 (recycling symbol)
• IEC 61438 (safety and health hazards)
• IEC 60086-4 (handling lithium batteries)
Accumulators or batteries integrated in the device should only be replaced by
the equipment manufacturer. If replacement is necessary, do not remove the
accumulator or the battery from the device, but send the complete device/card
or the removable battery pack.
There is a risk of explosion if the battery is not replaced correctly.
Never short-circuit batteries without using a discharging resistor. Without a
resistor, high current ensues and causes risk of explosion.
When disposing batteries, the local regulations applicable to hazardous waste
must be observed (see Section 2.7).
To replace any pars of devices or cables, use only original spare parts or parts
which are explicitly licensed by the manufacturer.
The correct disposal and separate collection of waste equipment will help
prevent potential negative consequences for the environment and human
health. It is a precondition for reuse and recycling of used electrical and
electronic equipment.
For more detailed information about disposal of such equipment, contact
Coriant.
The above statements are fully valid only for equipment installed in the
countries of the European Union and is covered by the directive 2002/96/EC.
Countries outside the European Union may have other regulations regarding
the disposal of electrical and electronic equipment.
4 Switch off the device using all relevant circuit breaker/fuses in the fuse panel
of the rack.
5 Switch off the protection power supply.
6 Switch off the working power supply.
7 Check if the device is powered off by using a measuring device or the LED
display of the device (if one is present).
Switching on
To switch on complete the following steps:
1 Switch on the device using the circuit breaker/fuses in the fuse panel of the
rack.
2 Start the EM.
3 Sicherheitshinweise: Deutsch
Dieses Kapitel enthält Sicherheitshinweise und Vorschriften, denen Sie folgen
müssen, um sicher mit 7090 zu arbeiten. Folgen Sie stets allen Anweisungen
dieses Kapitels zur Vermeidung von Personenschäden, Sachschäden und
Umwelt- und Gesundheitsschäden.
Bei Nichtbeachtung der nachfolgenden Vorschriften wird keine Haftung
seitens des Herstellers übernommen, und die Gewährleistung erlischt!
Wenn kein Datum angegeben ist, beziehen sich alle im Folgenden erwähnten
Normen (z.B. European Norm (EN), International Electrotechnical Commission
(IEC), Underwriters Laboratories (UL)) auf die jeweils neueste Ausgabe der
entsprechenden Norm.
Ersatzteile
Falls Sie an den Geräten oder an der Verkabelung irgendwelche Teile
ersetzen, so dürfen Sie nur Original-Ersatzteile oder solche Teile verwenden,
die vom Hersteller ausdrücklich zugelassen sind.
ACHTUNG: Anschlüsse der Geräte und Baugruppen sind nur für geschirmte
Kabel im Innenbereich bestimmt, wobei der Schirm der Kabel an beiden
Enden geerdet sein muss.
Die Anschlüsse der Geräte und Baugruppen DÜRFEN NICHT galvanisch mit
außergebäudlichen Schnittstellen oder deren Verkabelung verbunden werden.
Diese Anschlüsse sind nur für die Verwendung in Gebäuden bestimmt (Typ 2-
Anschlüsse nach GR-1089-CORE, Ausgabe 6) und erfordern eine Trennung
von freiliegenden Kabeln.
Die Verwendung von primärer Schirmung ist nicht ausreichend, um diese
Anschlüsse galvanisch an außergebäudliche Schnittstellen oder deren
Verkabelung anzuschliessen.
Beim Bedienen der Stromversorgung oder bei Arbeiten daran sind die Normen
EN 50110-1 und EN 50110-2 zu beachten (Betrieb von elektrischen Anlagen).
3.5.7 Brandschutz
Je nach Gerätetyp kann die Laserstrahlung für das menschliche Auge auch
unsichtbar sein!
ACHTUNG!
7090 enthält Lasereinrichtungen, die mit hohen optischen Leistungspegeln
arbeiten.
Blicken Sie nie in ein Faserende, einen Faserstecker, eine Glasfaser-
Verbindungsleitung, eine Anschlussfaser. Dauerhafte Augenschäden oder
Blindheit können hervorgerufen werden, wenn man sich solchen optischen
Leistungen auch nur für extrem kurze Dauer aussetzt. Verwenden Sie immer
die mitgelieferten Sicherheitsvorrichtungen (Abdeckkappen, Verschlüsse etc.).
Lesen und beachten Sie alle Laserwarnschilder, die am Baugruppenträger
angebracht sind. Verwenden Sie zur Ansicht ausschließlich zugelassene
optische Hilfsmittel oder Video-Geräte mit Filter oder Dämpfung.
ACHTUNG!
Bei Benutzung von ungeeigneten (nicht zugelassenen) optischen Hilfsmitteln
besteht die Gefahr von Augenschäden und Verletzungen. Verwenden Sie
ausschließlich zugelassene optische Hilfsmittel mit Filter oder Dämpfung.
Für den sicheren Betrieb der gesamten optischen Strecke muss die
Lasersicherheitsabschaltung aktiviert sein, und der automatische periodische
Laserstart muss deaktiviert sein.
Die Inbetriebnahme ("Commissioning") soll nur an Standorten mit
kontrolliertem bzw.
beschränktem Zugang nach IEC 60825-2:2004+A1:2006+A2:2010 erfolgen.
Zur Vermeidung gesundheitlicher Schäden müssen Sie die Vorschriften zur
Strahlungssicherheit von Lasereinrichtungen beachten:
• EN 60825-1:2004 und EN 60825-2:2004+A1:2006+A2:2010,
• IEC 60825-1:2004 und IEC 60825-2:2004+A1:2006+A2:2010
Besondere Vorsicht gilt beim Stecken oder Trennen von
Lichtwellenleiterkabeln, da an den Steckern der Baugruppen oder an den
Faserenden hohe optische Leistungspegel auftreten können.
Um ausreichende Systemübertragungseigenschaften zu garantieren, müssen
alle kundenseitig gelieferten Glasfaserkabel, die mit 7090-Komponenten
verbunden sind, mit LC-Steckern abgeschlossen werden. Wenn das nicht
fachgerecht ausgeführt wird, können unzulässige optische Qualitätsdaten die
Folge sein.
Bei SFP/XFP Modulen nur LC-Stecker ohne Schutzkappe verwenden.
Das Betriebspersonal muss mit allen Sicherheits- und
Handlungsanweisungen, die durch die zuständigen Regulierungsbehörden für
die genannten Gefährdungsgrade herausgegeben wurden, vertraut sein und
diese befolgen.
Die Verantwortung für das Erkennen, das Studium und die Beachtung der
anwendbaren laseroptischen, elektrischen, mechanischen und anderen
Sicherheitsstandards zur Installation, den Betrieb und die Wartung dieses
Geräts liegt beim Anwender.
Sowohl bei einem Gestell als auch bei Wandmontage muss ein
Schutzerdungskabel verwendet werden, wie im Handbuch Interconnect,
Cabling and Mechanical Assembly (ICMA) beschrieben.
Das Schutzkabel muss vor allen anderen Kabeln verbunden und als letztes
getrennt werden.
3.6 Handhabung
Anweisungen zur Handhabung von Baugruppenträgern, Baugruppen,
Lichtwellenleitern, Batterien und Ersatzteilen.
ACHTUNG!
Entfernen Sie zuerst die Lüftereinheit bevor Sie Kabel am Connector Panel
(COPA) anschließen oder entfernen. Andernfalls besteht die Gefahr von
Verletzungen oder Gerätebeschädigungen.
Gerätekühlung
ACHTUNG!
Lüfterbaugruppen haben drehende Teile.
Gewichtsangaben
7090 Beschilderung laserbestückter Baugruppen Laserbestückte Baugruppen
tragen vorne und an der Seite die folgenden Schilder.
Figure 15 Gewichtswarnschild
Auf extrem heißen Oberflächen ist zusätzlich ein Schild mit der roten Schrift
“HOT POINT” (“heißer Punkt”) auf weißem Grund angebracht (siehe Figure
17). Es kennzeichnet höchste Verletzungsgefahr.
• Legen Sie ein Erdungsarmband an, bevor Sie Geräte anfassen. Das
Erdungsarmband muss mit dem EBP-Anschluß verbunden sein. Entfernen Sie
die Vordertür nur mit angelegtem Erdungsarmband.
• Legen Sie ein Erdungsarmband an, wenn Sie Baugruppen mit EGB-Symbol
(seihe Figure 18) auspacken, einpacken, berühren, ziehen oder stecken.
Dadurch wird sichergestellt, dass die Bauteile nicht beschädigt werden.
• Verwenden Sie beim Ziehen und Stecken von Baugruppen die daran
angebrachten Zieh- und Steckhilfen (Kunststoff-, bzw. Metallhebel).
• Wenn die Baugruppen nur an den Zieh- und Steckhilfen angefasst werden,
dürfen sie nicht in waagrechter Lage transportiert werden (Bruchgefahr).
• Achten Sie darauf, dass alle verwendeten Messgeräte geerdet sind. Wenn
Sie potentialfreie Messgeräte benutzen, verbinden Sie den Messkopf
kurzzeitig mit Erde (Entladung) vor dem Messen an Bauelementen und
Baugruppen.
Es gibt keine zusätzlichen Geräteanforderungen wie z.B. besondere
Vorbereitung des Standortes, Einschränkungen bzgl. Klimatisierung,
Regelung der relativen Luftfeuchtigkeit oder Wahl von antistatischen
Materialien für Bodenbelag und Möbel.
LWL-Steckertypen
Um ausreichende Systemwerte zu garantieren, müssen alle kundenseitig
gelieferten Glasfaserkabel, die mit 7090-Komponenten verbunden sind, mit
LC-Steckern abge schlossen werden. Wenn das nicht fachgerecht ausgeführt
wird, können unzulässige optische Qualitätsdaten die Folge sein.
Bei SFP/XFP Modulen nur LC-Stecker ohne Schutzkappe verwenden!
• Netzelemente dürfen nur mit LWL-Kabeln verbunden werden, die für diese
Verbindung freigegeben wurden.
• Gefährdungsgrad 1 können eingehalten werden, wenn andere
Verbindungen hergestellt werden. Im ungünstigsten Fall kann Laserklasse 3B
am Faserende vorkommen.
• Für LWL-Leitungen darf ein Biegeradius von 30 mm nicht unterschritten
werden!
• Vermeiden Sie auf jeden Fall ein - auch nur kurzzeitiges - Knicken der
Leitungen.
Vermeiden Sie Zugkräfte an den Steckverbindern.
• Vermeiden Sie beim Umgang mit den Steckverbindern
Stoßbeanspruchungen. Stoßbeanspruchungen können zur mechanischen
Beschädigung der Stirnflächen von optischen Steckverbindern und damit zur
Dämpfungserhöhung führen.
• Achten Sie bei der Herstellung einer optischen Verbindung auf den
korrekten und festen Sitz der einzelnen Verbindungselemente.
• Beachten Sie bei der Handhabung der optischen Baugruppen die Hinweise
in Handhabung von Baugruppen mit elektrostatisch gefährdeten Bauteilen.
WARNUNG!
Bei Benutzung von ungeeigneten (nicht zugelassenen) optischen Hilfsmitteln
besteht die Gefahr von Augenschäden und Verletzungen. Verwenden Sie
ausschließlich zugelassene optische Hilfsmittel mit Filter oder Dämpfung.
VORSICHT!
Die Controller-Baugruppen SI bzw. SI-E enthalten eine Lithium-Batterie.
3.6.3 Ersatzteile
Diese Aussagen sind nur gültig für Geräte, die in den Ländern der
Europäischen Union installiert und verkauft werden und die der Europäischen
Richtlinie 2002/96/EC unterliegen.
In Ländern außerhalb der Europäischen Union können davon abweichende
Bestimmungen für die Entsorgung von Elektro- und Elektronikgeräten gelten.
Normales Abschalten
1 Stellen Sie sicher, dass das abzuschaltende Gerät keine Nutzsignale mehr
überträgt bzw. dass diese über Ersatzeinrichtungen umgeleitet werden.
2 Sichern Sie die lokale Datenbasis.
3 Schalten Sie den NE mit Hilfe des Bedienterminals (@CT) ab.
4 Schalten Sie das Gerät mit den entsprechenden relevanten
Sicherungsautomaten/Sicherungen im Gestell-Sicherungsfeld aus.
5 Schalten Sie die Ersatz-Stromversorgung aus.
6 Schalten Sie die Betriebs-Stromversorgung aus.
7 Überprüfen Sie nach dem Abschalten, ob das Gerät spannungsfrei ist -
entweder mit Hilfe eines Messgerätes oder gegebenenfalls durch die LED-
Anzeige am Gerät.
Einschalten
1 Schalten Sie das Gerät mit den Sicherungsautomaten/Sicherungen im
Gestellsicherungsfeld ein.
2 Starten Sie das Bedienterminal @CT.