0id Connection HardWare
0id Connection HardWare
                     B-64303EN/03
 • No part of this manual may be reproduced in any form.
 • All specifications and designs are subject to change without notice.
The products in this manual are controlled based on Japan’s “Foreign Exchange and
Foreign Trade Law”. The export from Japan may be subject to an export license by the
government of Japan.
Further, re-export to another country may be subject to the license of the government of
the country from where the product is re-exported. Furthermore, the product may also be
controlled by re-export regulations of the United States government.
Should you wish to export or re-export these products, please contact FANUC for advice.
The products in this manual are manufactured under strict quality control. However, when
using any of the products in a facility in which a serious accident or loss is predicted due to
a failure of the product, install a safety device.
In this manual we have tried as much as possible to describe all the various matters.
However, we cannot describe all the matters which must not be done, or which cannot be
done, because there are so many possibilities.
Therefore, matters which are not especially described as possible in this manual should be
regarded as ”impossible”.
B-64303EN/03                                    DEFINITION OF WARNING, CAUTION, AND NOTE
          WARNING
          Applied when there is a danger of the user being injured or when there is a
          danger of both the user being injured and the equipment being damaged if the
          approved procedure is not observed.
          CAUTION
          Applied when there is a danger of the equipment being damaged, if the
          approved procedure is not observed.
       NOTE
         The Note is used to indicate supplementary information other than Warning and
         Caution.
                                                       s-1
B-64303EN/03                                                                                         PREFACE
PREFACE
   This manual describes the electrical and structural specifications required for connecting the CNC control
   unit to a machine tool. The manual outlines the components commonly used for FANUC CNC control
   units, as shown in the configuration diagram in Chapter 2, and supplies additional information on using
   these components.
    The manual outlines the I/O unit, servo, spindle, and other components common to FANUC CNC
   control units, and supplies additional information on using these components in this CNC control unit.
   For detailed specifications, refer to the manuals of these components.
For options not covered in this manual, also refer to the manuals of these components.
Applicable models
   The models covered by this manual, and their abbreviations are :
                        Model name                                           Abbreviation
   FANUC Series 0i-TD                               0i –TD
                                                                                    Series 0i
   FANUC Series 0i-MD                               0i –MD
   FANUC Series 0i Mate-TD                          0i Mate-TD
                                                                                    Series 0i Mate
   FANUC Series 0i Mate-MD                          0i Mate-MD
                                                     p-1
PREFACE                                                                                                  B-64303EN/03
   This manual mainly assumes that the FANUC SERVO MOTOR αi series of servo motor is used. For
   servo motor and spindle information, refer to the manuals for the servo motor and spindle that are actually
   connected.
                                                     p-3
B-64303EN/03                                                                                                       TABLE OF CONTENTS
TABLE OF CONTENTS
DEFINITION OF WARNING, CAUTION, AND NOTE .................................s-1
PREFACE ....................................................................................................p-1
1     CONFIGURATION .................................................................................. 1
      1.1       CONTROL UNIT CONFIGURATION AND COMPONENT NAMES .............. 1
                1.1.1      Configurations of Control Units...............................................................................1
      1.2       HARDWARE OVERVIEW.............................................................................. 5
                1.2.1      Control Unit Overview.............................................................................................5
                                                            c-4
B-64303EN/03                                                                                                      TABLE OF CONTENTS
                            9.9.3.8        Manual pulse generator connection ................................................................. 246
                            9.9.3.9        Connector (on the cable side) specifications ................................................... 249
               9.9.4        I/O Address...........................................................................................................250
                            9.9.4.1        Keyboard of main panel................................................................................... 250
                            9.9.4.2        Override signals ............................................................................................... 250
               9.9.5        I/O Mapping .........................................................................................................251
                            9.9.5.1        Connector locations of main panel .................................................................. 252
               9.9.6        Specifications .......................................................................................................254
                            9.9.6.1        Environmental requirement ............................................................................. 254
                            9.9.6.2        Order specification........................................................................................... 254
                            9.9.6.3        Main panel specification.................................................................................. 254
                            9.9.6.4        Sub panel A/B1 specification .......................................................................... 254
                            9.9.6.5        Power supply specification .............................................................................. 255
                            9.9.6.6        General-purpose DI signal definition .............................................................. 255
                            9.9.6.7        General-purpose DO signal definition............................................................. 255
               9.9.7        Key Symbol Indication on Machine Operator’s Panel.........................................255
                            9.9.7.1        Meaning of key symbols.................................................................................. 255
                            9.9.7.2        Detachable key top .......................................................................................... 257
      9.10     CONNECTION TO THE SMALL MACHINE OPERATOR'S PANEL OR
               SMALL MACHINE OPERATOR'S PANEL B ............................................. 258
               9.10.1       Overview ..............................................................................................................258
               9.10.2       Overall Connection Diagram................................................................................258
               9.10.3       Connection of Each Section .................................................................................260
                            9.10.3.1       Power connection ............................................................................................ 260
                            9.10.3.2       Emergency stop switch .................................................................................... 260
                            9.10.3.3       I/O Link connection......................................................................................... 261
                            9.10.3.4       Manual pulse generator connection ................................................................. 261
               9.10.4       DI Signal Connection (Rotary Switch Connection) .............................................263
               9.10.5       General-purpose DI/DO Connection (Only for the Small Machine Operator's
                            Panel B) ................................................................................................................264
                            9.10.5.1 Connector pin allocation.................................................................................. 264
                            9.10.5.2 General-purpose DI (input signal) connection................................................. 265
                            9.10.5.3 General-purpose DO (output signal) connection ............................................. 267
               9.10.6       I/O Address...........................................................................................................268
                            9.10.6.1 Keyboard of the operator's panel ..................................................................... 268
                            9.10.6.2 Override signals ............................................................................................... 269
               9.10.7       I/O Address Allocation.........................................................................................270
                            9.10.7.1 For small machine operator's panel ................................................................. 270
                            9.10.7.2 For small machine operator's panel B.............................................................. 271
               9.10.8       External Dimensions ............................................................................................274
                            9.10.8.1 Outline drawing and panel-cut drawing of the small machine operator's
                                     panel................................................................................................................. 274
                            9.10.8.2 Layout of the key sheet (Same for both the small machine operator's panel
                                     and small machine operator's panel B) ............................................................ 276
               9.10.9 Connector Layout of the Small Machine Operator's Panel ..................................278
               9.10.10 Specifications .......................................................................................................279
                            9.10.10.1      Environmental requirement ............................................................................. 279
                            9.10.10.2      Order specification........................................................................................... 279
                            9.10.10.3      Operator's panel specification.......................................................................... 280
                            9.10.10.4      Power supply specification .............................................................................. 280
               9.10.11 Key Symbol Indication on Machine Operator's Panel .........................................280
                            9.10.11.1 Meaning of key symbols.................................................................................. 280
                            9.10.11.2 Customization of the key sheet........................................................................ 281
               9.10.12 Maintenance Parts ................................................................................................282
      9.11     CONNECTION OF TERMINAL TYPE I/O MODULE ................................. 282
               9.11.1       Overview ..............................................................................................................282
                                                                       c-5
TABLE OF CONTENTS                                                                                                                      B-64303EN/03
APPENDIX
A   EXTERNAL DIMENSIONS OF EACH UNIT ....................................... 369
B   20-PIN INTERFACE CONNECTORS AND CABLES ......................... 411
    B.1     BOARD-MOUNTED CONNECTORS ........................................................ 411
            B.1.1      Vertical-type Connectors......................................................................................411
            B.1.2      Straight and Right-angled Connectors (for Spring and Screw-fixing Connector
                       Housings) .............................................................................................................411
    B.2     CABLE CONNECTORS ............................................................................ 411
            B.2.1      Strand Wire Press-mount Connector ....................................................................412
            B.2.2      Soldering Type Connector....................................................................................412
    B.3     RECOMMENDED CONNECTORS, APPLICABLE HOUSINGS, AND
            CABLES .................................................................................................... 413
            B.3.1      Recommended Connectors...................................................................................414
            B.3.2      Applicable Cables.................................................................................................415
                                                                   c-9
B-64303EN/03                                                                             1.CONFIGURATION
1               CONFIGURATION
     NOTE
       See Chapter 12, “CONNECTION OF THE STAND-ALONE TYPE”, for
       stand-alone type CNC.
For the 8.4-inch color LCD, the touch panel is attached to only lathe system CNCs.
                                                        -1-
1.CONFIGURATION                                                                    B-64303EN/03
Control unit
                                                                           MDI
                                   LCD
                                                                     (See Section 5.1)
   NOTE
     This figure is a front view of the 8.4-inch color LCD/MDI (horizontal) type control
     unit.
                                           -2-
B-64303EN/03                                                                                             1.CONFIGURATION
Rear of unit
Fuse
     NOTE
       This figure is a rear view of the control unit without option slots.
       The numbers in parentheses () in the figures are keyed to the item numbers of
       the descriptions in this manual. The numbers in brackets [] in the figures are
       connector numbers.
                                                              -3-
1.CONFIGURATION                             B-64303EN/03
                  -4-
B-64303EN/03                                                                                   1.CONFIGURATION
                                                                                          Main board
                                                                                 • CPU for controlling CNC
                                                                                 • Power supply
                                                                                 • Axis control
                                                                                 • Spindle interface
                                                                                 • LCD/MDI interface
                                                                                 • I/O Link
                                                                                 • PMC control function
                                                                                 • High-speed DI
                                                                                 • RS-232C
                                                                                 • Memory card interface
                                                                                 • Ethernet (Series 0i only)
Basic system
         The control unit of the Series 0i Mate has no optional slots, so no option board can be inserted.
         A unit with optional slots can have as many option boards as option slots.
         The Fast Ethernet board can be inserted into only the slot on the LCD side.
                                                           -5-
2.TOTAL CONNECTION DIAGRAMS                                                                                                                                               B-64303EN/03
                                                  Main board
                                                        24V-IN(CP1)
                               LCD display unit
                                                               (CA122)
                                                                         Soft key cable                   MDI UNIT
MDI(JA2) CK1
                                                        SPDL(JA41)
                                                                                                                                              Circuit breaker
                                                                                                                                                        200VAC
                                                                         To 3rd spindle                              AC reactor                         200VAC
                                                                                                                                     MCC Circuit breaker
αi PS
Position coder
αi SP
                                                     FSSB(COP10A)                                COP10B
                                                                                                              αi SV                                Servo motor
                                                                                                 COP10A
                                                                                              COP10B
                                                                                                              αi SV                                Servo motor
                                                                                              COP10A
                                                                                              COP10B
                                                                                                              αi SV                                Servo motor
                                                                                              COP10A
                                                                                              COP10B
                                                                                                              αi SV                                Servo motor
                                                                                              COP10A
ETHERNET(CD38A) Ethernet
                                                                                                  -6-
B-64303EN/03                                                                        2.TOTAL CONNECTION DIAGRAMS
ETHERNET(CD38R) Ethernet
                         PROFIBUS-DP
                         master board
                         PROFIBUS-DP
                         slave board
                         DeviceNet
                         master board
                         DeviceNet
                         slave board
FL-net board
                                                                     -7-
2.TOTAL CONNECTION DIAGRAMS                                                                                                B-64303EN/03
                          DI/DO-4
                          (CB107)
Series 0i Mate
                 Series 0i Mate
                                                        I/O for operator’s panel(with MPG)
                 Main board
                                      I/O Link          JD1B                       JA3                     Manual pulse generator
                   I/O Link (JD51A)
                                                        JD1A                                               (up to three units)
                                                          -8-
B-64303EN/03                                                                               3.INSTALLATION
3                 INSTALLATION
3.1               ENVIRONMENTAL REQUIREMENTS
    NOTE
    1 If the CNC is installed 1000 m or higher above sea level, the allowable upper
      ambient temperature of the CNC in the cabinet is changed as follows.
      Assume that the allowable upper ambient temperature of the CNC in the cabinet
      installed 1000 m or higher above sea level decreases by 1.0°C for every 100 m
      rise in altitude.
      Example)
          The upper allowable ambient temperature of the CNC in the cabinet installed
          1750 m above sea level is:
           58°C-(1750-1000)/100×1.0°C=50.5°C
      Therefore, the allowable ambient temperature range is from 0°C to 50.5°C.
    2 When using a unit for which the installation conditions are specified separately,
      the conditions also need to be met.
    NOTE
    1 The liquid-crystal display and MDI unit are included. Optional boards are not
      included.
    2 When connecting an RS-232-C unit (powered by the NC) to the RS-232-C port,
      add the current capacity of the unit. Up to 1 A can be supplied from the two
      channels of the port.
    3 Use memory cards that consume no more than 2 W.
    4 For other peripheral units (such as I/O units), see Table 3.2.1 (b) and also refer
      to the relevant manuals.
    5 When you select the input DC power supply for the CNC control section,
      consider the restrictions other than the power supply capacity. Be sure to see
      also Subsection 4.2.2.
                                                       - 10 -
B-64303EN/03                                                                                3.INSTALLATION
     NOTE
       The power supply capacity for DO is not assumed for I/O units.
          CAUTION
         If the air blows directly from the fan to the unit, dust easily adheres to the unit.
         This may cause the unit to fail. (This is not necessary for a unit with fan.)
   (4) For the air to move easily, a clearance of 100 mm is required between each unit and the wall of the
       cabinet.
   (5) Packing materials must be used for the cable port and the door in order to seal the cabinet.
   (6) The display unit must not be installed in such a place that coolant would directly fall onto the unit.
       The control unit has a dust-proof front panel, but the unit should not be placed in a location where
       coolant would directly fall onto it.
   (7) Noise must be minimized.
       As the machine and the CNC unit are reduced in size, the parts that generate noise may be placed
       near noise-sensitive parts in the magnetics cabinet.
       The CNC unit is built to protect it from external noise. Cabinet design to minimize noise
       generation and to prevent it from being transmitted to the CNC unit is necessary. See section 3.5
       for details of noise elimination/management.
   (8) When placing units in the cabinet, also consider ease of maintenance.
       The units should be placed so that they can be checked and replaced easily when maintenance is
       performed.
   (9) The installation conditions of the I/O unit and connector panel I/O module must be satisfied.
       To obtain good ventilation in the module, the I/O unit and connector panel I/O module must be
       installed in the direction shown in the following figure. Clearances of 100 mm or more both above
       and below the I/O unit are required for wiring and ventilation.
                                                       - 11 -
3.INSTALLATION                                                                                             B-64303EN/03
       Equipment radiating too much heat must not be put below the I/O unit and connector panel I/O
       module.
                                      Top
                                                             Connector panel I/O module or
                                                             I/O base unit
                                                             (No screws or protrusions shall extend
                                                             from the bottom of this unit.)
Bottom
                                                     - 12 -
B-64303EN/03                                                                               3.INSTALLATION
     NOTE
     1 The liquid-crystal display and MDI unit are included. Optional boards are not
       included.
     2 When installing the CF card on the Fast Ethernet board, add 0.3 W for the Fast
       Ethernet board to the heat output. (The heat output of the CF card may be
       changed if its specification is changed.)
     NOTE
     1 The indicated values are when 50% of the module input signals are ON.
     2 Heat output generated within the separate detector is not included.
An example of the thermal design for the cabinet shown in Fig. 3.4.3 is shown below.
                                                      - 13 -
3.INSTALLATION                                                                                 B-64303EN/03
Fig. 3.4.3
  In this case, the allowable total heat dissipation for the cabinet is:
        8 × 0.5722 × 13 + 3.7 × 0.2632 × 13 = 72 W.
  In consequence, it can be concluded that the units shown in Table 3.4.3 on the next page can be installed
  in this cabinet.
                                                     Table 3.4.3
  Control unit (Optional two-slots)                                             37W
  Optional board (Fast data server board)                                       3W
  Optional board (Profibus master board)                                        5W
  Standard machine operator's panel                                             15W
  120-mm square fan motor for air mixing                                        8W
  Total heat dissipation of the above                                           68W
    NOTE
      The 15 W quoted for the standard machine operator's panel represents an
      example heat output value when half of all the input signals are turned on. This
      value varies, depending on the mechanical configuration.
                                                      - 14 -
B-64303EN/03                                                                            3.INSTALLATION
3.5.1          Grounding
   Grounding the power magnetics cabinet and devices is very important to prevent an electric shock and
   suppress a noise influence. The following describes the grounding methods for suppressing the noise
   influence.
                                                    - 15 -
3.INSTALLATION                                                                                   B-64303EN/03
    NOTE
      Impedance includes a resistance component that converts electric current to
      heat as well as a component called “reactance”, and indicates a characteristic of
      resistance to the flow of alternating current at a certain frequency.
                                                   - 16 -
                                                                                                                                                                                                       B-64303EN/03
                                                                                                         α i PS α i SP α i SV
                                                                                                                                      Ground bar for shield
                                                                                                                                      clamp
                                                                                                           CX1               JF*
                                                                                                            A                                                           CNC
                                                                              Provide grounding
                                                                              in the vicinity of a
                                                                                    device.
                                                                                  24V power
                                                                                    supply                                                                        Operator’s panel
- 17 -
                                                                                    AC input                                               Connection at
                                                                                                                                           low impedance              Pendant box
                                                                                                                                                              (Lowe-impedance metal plates)
                                                                                                                                         Signal
                                                                                                                                          line
                                                                                                                                         Power
                                                                                                                                          line
                                                                                                       Cabinet
                                                                                             (Lowe-impedance metal plates)                                                    Machine side
- 18 -
                                                                                      AC input
                                                                                                                                                            Signal system ground bar
                                                                                                                                            Signal
                                                                                                                                             line
                                                                                                                                            Power
                                                                                                 Signal system ground bar                    line
Machine side
ƒP [ƒuƒ‹
Cable
     NOTE
       Select a cable with a proper length.
       If the cable is too long, the noise immunity may be reduced or noise may be
       caused on other cables. In addition, when the excess length is coiled, the
       inductance is increased and a high voltage is induced during turning on or off of
       signals. This may cause a malfunction due to a failure or noise.
                                                        - 19 -
3.INSTALLATION                                                                                          B-64303EN/03
                                                                               Machine side
                                                                               installation board
Control unit
Ground plate
Shield cover
    NOTE
      Bundle the cables connected to a CNC or amplifier near each unit and shield
      them.
                                                                                      Ground terminal
                                                                                      (grounded)
For the ground plate, use a metal plate of 2 mm or thicker, which surface is plated with nickel.
                                                             - 20 -
B-64303EN/03                                                                                    3.INSTALLATION
                                                                                       Ground plate
                                        8
12
20
Max. 55
28
17
3.5.1.4         Cabinet
   A cabinet is an important element in improving noise immunity and suppressing radiated noise. One of
   the causes of problems related to noise immunity and radiated noise is faulty electrical continuity between
   the metal plates that make up the cabinet. Typically, noise that becomes a problem is high–frequency
   noise, against which measures must be taken in the cabinet design.
                                                          - 21 -
3.INSTALLATION                                                                                               B-64303EN/03
      As for a cabinet welding method, bead welding is more suitable than spot welding for providing
      low–impedance electrical continuity between the metal plates.
      For an assembly–type cabinet structure, provide electrical continuity by bringing the metal plates
      into direct contact with each other, without applying a coating to their joint surface areas.
      In a structure that has the metal plates connected only with wires because of structural constraints,
      low–impedance connections are more difficult to make than in a structure in which welding is made
      or the metal plates are brought into direct contact with each other. It is necessary to maintain
      sufficient levels of items such as the cross–sectional area of a wire to use, continuity of connections,
      and contact areas.
                Bead welding                                Bring the m etal plates into direct contact with each
                                                            other, without applying a coating to their joint areas.
    NOTE
      For improved noise immunity, how to provide low-impedance electrical continuity
      in the cabinet is described here. To construct a protective circuit, a protective
      grounding connection must be made between the metal plates by using electric
      wires with a cross-sectional area appropriate for the AC input power capacity of
      the unit mounted on each metal plate.
                                                   - 22 -
B-64303EN/03                                                                                   3.INSTALLATION
Unit
Unit
Note that for each FANUC CNC, the 0V output in the CNC is connected to a protective circuit (ground).
                                                   - 23 -
3.INSTALLATION                                                                                                     B-64303EN/03
Machine
                                                                                           24 VDC power
                                                                         Power             supply
                                                                         magnetics
                                                          Output
                                                                         cabinet
                                                          signal
                                                                                       Relay
                                          NC ground terminal
                                                                   Machine protective circuit (ground) network
           This bold line indicates grounding for the control unit described in the connection manual.
           As shown in this figure, by just connecting the ground terminal of the control unit to the machine ground,
           the 0 V output of the relay circuit in the power magnetics cabinet is connected to the ground (protective
           circuit).
                                                         - 24 -
B-64303EN/03                                                                               3.INSTALLATION
               For the 8.4" LCD/MDI (horizontal) type
M4 screw
M4 screw
M4 stud
   Connect the 0V line in the control unit to the ground plate of the cabinet via the protective ground
   terminal (shown in the above figure).
   For the locations of the ground terminals of the other units, see the external dimensions of each unit in the
   appendix.
                                                         - 25 -
3.INSTALLATION                                                                                          B-64303EN/03
      NOTE
      1 Binding the cables in one group separately from another means that the groups
        are placed 10 cm or more apart from one another.
      2 Covering a group with an electromagnetic shield means that shielding is
        provided between groups with grounded steel plates.
      3 The shield is not required when the cable between the CNC and MDI is no more
        than 30 cm in length.
                                                     - 26 -
B-64303EN/03                                                                            3.INSTALLATION
                                                        - 27 -
3.INSTALLATION                                                                                                   B-64303EN/03
                                                                         R         C
                          Equivalent circuit of the spark killer
                                                                          Spark killer
                                                 AC relay
Motor
Spark killer
       NOTE
         Use a CR-type noise eliminator. Varistor-type noise eliminators clamp the peak
         pulse voltage but cannot suppress a sharp rising edge.
Diode
                                                               - 28 -
B-64303EN/03                                                                          3.INSTALLATION
Unit : mm
Fig. 3.6.1
                                                   - 29 -
3.INSTALLATION                                                                                     B-64303EN/03
Fig. 3.6.2
                                                    - 30 -
B-64303EN/03                                                                          3.INSTALLATION
   8)   Since coolant accumulated on the top of a cabinet or pendant box may drip onto the panel surface of
        a display unit of operator's panel, use a structure that prevents coolant from being accumulating on
        the top or from being dripping onto the panel surface. For example, install a canopy over a display
        unit or operator's panel.
   9)   The front surface of a display unit must be vertical. Otherwise, coolant is likely to accumulate in
        the lower part of the display screen.
                                                   - 31 -
4.POWER SUPPLY CONNECTION                                                                     B-64303EN/03
Fig. 4.2.1
                                                  - 32 -
B-64303EN/03                                                     4.POWER SUPPLY CONNECTION
   Load fluctuations (including rush current):
        The output voltage must not go out of the above range due to load fluctuations by external DO and
        other factors.
   Instantaneous input interruption retention time:
        10 ms (for -100%), 20 ms (for -50%)
   -   Circuit configurations
   The following circuit configurations are not recommended.
       Forbidden
   <1> Circuit examples that cannot retain the output voltage at an instantaneous interruption (the voltage
       reduces to 21.6 V or below)
                                                  - 33 -
4.POWER SUPPLY CONNECTION                                                                      B-64303EN/03
                  Example 1
                                                        Rectifier
                    AC input                            circuit
                                                                                 CNC unit
                  Example 2
                                                        Rectifier
                    AC input                            circuit                  CNC unit
   NOTE
     The rectifier circuit means a circuit using diodes for full-wave rectification.
 <2> Circuit examples that exceed the output voltage specifications (21.6 V to 26.4 V) due to an abrupt
     load change
                 Example 1
                                      Regulated
                    AC input          power supply                              CNC unit
                                                                            Device with
                                                                            remarkable load
                                                                            fluctuations
Example 2
                                      Regulated
                    AC input
                                      power supply                              CNC unit
 For a circuit configuration in <2>, connect another regulated power supply to be specifically used for the
 device with remarkable load fluctuations so that the CNC and other units are not affected.
 Avoid the use of a configuration in <2> if possible, even in an environment with small load fluctuations
 or rush current. When two or more units are connected to the same power supply, the 24-VDC power
 may not be turned on due to a failure in a unit other than the CNC. If this happens, it takes much time to
 locate the failure because the CNC cannot start and no alarm indication is provided.
 When the CNC and other units are connected to the same power supply because of limited space for the
 power magnetics cabinet or for some other reason, careful consideration must be given to possible rush
 currents and voltage fluctuations. In addition, to prevent power supply noise from entering the CNC, a
 noise filter must be inserted before the power to the CNC. (Recommended noise filter: ZGB2203-01U
 manufactured by TDK)
                                                     - 34 -
B-64303EN/03                                                                     4.POWER SUPPLY CONNECTION
  Recommended
   The following circuit configuration is recommended.
   The power to the CNC and other, FANUC Servo Unit β series with an I/O link (β amplifier with an I/O
   link), and so on in the sample configuration below) is assumed to be turned on or off at the same time.
   (The power to any unit is not assumed to be turned on during operation or before the power to the CNC is
   turned on.
                              On/off                          Regulated
         AC input             circuit                         power                           CNC unit
                                                              supply
I/O Unit-A
                                                                                            β amplifier with
                                                                                            an I/O link
                                                                Regulated
                                                                power                      Device with large noise
                                                                supply                     or load fluctuations
       Caution
   Turning the power to units on simultaneously when turning the power to the CNC:
   When the following power-on timing condition is satisfied, the power to units is assumed to be turned on
   simultaneously when the power to the CNC is turned on.
                                                    On
                             Power to the CNC
                                                    Off
                                                                            t1      t2
                             Power to units         On
                             (including the Power
                             Mate)                  Off
   t1:200ms         Means that the power to units (including the Power Mate) is turned on within 200 ms before
                    the power to the CNC is turned on.
   t2:-500ms        Means that the power to units (including the Power Mate) is turned on within 500 ms after
                    the power to the CNC is turned on.
                                                           - 35 -
4.POWER SUPPLY CONNECTION                                                                                   B-64303EN/03
 Turning the power to units off simultaneously when turning the power to the CNC off:
 This means that the power to units may be turned off within 500 ms before the power to the CNC control
 unit is turned off. If the power to units is turned off earlier, alarm information is left in the NC.
                                                  On
                          Power to the CNC
                                                  Off
                                                                      t1
 t1:500ms    Means that the power to units are turned off within 500 ms before the power to the CNC is
             turned off.
 The power to the CNC must not be turned on or off with the power to units on.
 “Turning on the power to all the units at the same time” means completing the power–on operations in 1
 and 2 above within 500 ms of performing power–on in 3.
 Do not remove the memory backup battery (3VDC) and the separate absolute pulse coder battery (6VDC)
 regardless of whether the power of the CNC controller is on or off. If the batteries are removed when
 the CNC controller is off, the parameters and programs saved in the CNC controller and the position data
 in the pulse coder are lost.
 For information on replacing the memory backup battery, see Subsection 4.4.1.
 When turning off the power of the CNC controller, be sure to turn off the power of units such as the slave
 I/O devices connected through I/O Link, β amplifier with I/O Link, Power Mate and separate detector
 interface unit, control power supply of the servo amplifier, and separate detector (such as a scale).
 “Turning off the power to all units at the same time” means completing the power–off operations in 2 and
 3 above within 500 ms before the power–off operation described in 1 above. If the power to the units
 indicated in 2 or 3 is turned off other than within 500 ms of the power in 1 being turned off, alarm
 information is left in the NC.
 When the power is turned off or when the power is momentarily disconnected, processing must be
 performed from the machine as necessary, because motor control is disabled.
 For example, when movement along a vertical axis is controlled, a brake should be applied to prevent
 falling. Usually, the brake clamps the motor when the servo is not activated or when the motor is not
 turning. The clamp is released only when the motor is turning.
                                                        - 36 -
B-64303EN/03                                                                  4.POWER SUPPLY CONNECTION
   When servo axis control is disabled by power-off or momentary power disconnection, the brake usually
   clamps the servo motor. In this case, before the relay for clamping operates, the controlled axis may fall.
   So, also consider whether the distance the axis is likely to fall will cause a problem.
   When the power is turned off:
        Be sure to apply a brake for clamping before turning off the power to CNC.
   When the power fails:
        If a power failure is detected, a brake must be applied immediately. Select the power supply with a
        longer DC power retention time after AC power-off, because the servo is deactivated if the power to
        CNC is turned off.
                            CP1
                               1    +24V                                         24VDC stabilized
                               2      0V                                         power
                               3                                                 24VDC ±10%
                       Cable
                          CP1
                          AMP Japan
                          1-178288-3 (housing)
                          1-175218-5 (Contact)
                                                                                 External power
4.4              BATTERIES
   In a system using this CNC, batteries are used as follows:
4.4.1            Battery for Memory Backup in the CNC Control Unit (3 VDC)
   Offset data, and system parameters are stored in SRAM in the control unit. The power to the SRAM is
   backed up by a lithium battery mounted on the front panel of the control unit. The above data is not lost
   even when the main battery goes dead. The backup battery is mounted on the control unit at shipping.
   This battery can maintain the contents of memory for about a year.
   When the voltage of the battery becomes low, alarm message "BAT" blinks on the display and the battery
   alarm signal is output to the PMC. When this alarm is displayed, replace the battery as soon as possible.
   In general, the battery can be replaced within two or three weeks, however, this depends on the system
   configuration.
                                                             - 37 -
4.POWER SUPPLY CONNECTION                                                                       B-64303EN/03
  If the voltage of the battery becomes any lower, memory can no longer be backed up. Turning on the
  power to the control unit in this state causes system alarm to occur because the contents of memory are
  lost. Clear the entire memory and reenter data after replacing the battery.
  FANUC thus recommends that the battery be replaced periodically, once a year, regardless of whether a
  battery alarm is issued.
  The following two kinds of batteries can be used.
  •     Lithium battery built into the CNC control unit.
  •     Two alkaline dry cells (size D) in the external battery case.
    NOTE
      A lithium battery is installed as standard at the factory.
  (3) Mount the new battery unit. (Push the battery unit in until the claw is latched into the case.) Ensure
      that the latch is engaged securely.
                                                   - 38 -
B-64303EN/03                                                         4.POWER SUPPLY CONNECTION
         WARNING
         Using other than the recommended battery may result in the battery exploding.
         Replace the battery only with the specified battery (A02B-0309-K102).
          CAUTION
         Steps 1 to 3 should be completed within 30 minutes. Do not leave the control
         unit without a battery for any longer than the specified period. Otherwise, the
         contents of memory may be lost.
         If steps 1 to 3 may not be completed within 30 minutes, save all contents of the
         SRAM memory to the memory card beforehand. Thus, if the contents of the
         SRAM memory are lost, the contents can be restored easily.
   When discarding a battery, observe the applicable ordinances or other rules of your local government.
   In addition, cover the exposed pins with tape or other insulation materials to prevent a short circuit before
   discarding the battery.
   - Connection method
   Remove the factory-mounted lithium battery from the control unit as described in the battery replacement
   method above. Connect the battery cable (A02B-0309-K103) to the battery case (A02B-0236-C282). This
   battery cable has the same connector as the lithium battery unit, so connect the connector to the place
   where the lithium battery unit was installed as shown in the figure below. Since the connector has a
   simple lock system, make sure that the lock is applied during installation.
                                                     - 39 -
4.POWER SUPPLY CONNECTION                                                   B-64303EN/03
   NOTE
   1 The battery case (A02B-0236-C282) needs to be installed in a position
     where dry cells can be replaced even when the control unit is powered on.
   2 The connector part of this battery cable engages with a simple lock system.
     Therefore, fix a cable portion up to 500mm long from the connector side
     without the portion being yanked to prevent the connector being removed by
     the cable weight or tensile stress.
                                       - 40 -
B-64303EN/03                                                         4.POWER SUPPLY CONNECTION
           CAUTION
          To replace the battery when the power is off, follow the same procedure as that
          for the replacement of a lithium battery, described above.
Dry cell × 2
Cover
           Connection terminal
           on the rear
                                                       - 41 -
4.POWER SUPPLY CONNECTION                                                                      B-64303EN/03
 Replacing a battery
 Obtain four commercially available alkaline batteries (size D).
 (1) Turn on the power of the machine (CNC).
 (2) Loosen the screws of the battery case, and remove the cover.
 (3) Replace the dry batteries in the case.
                                                                                Screws
Cover
         WARNING
        If the batteries are installed incorrectly, an explosion may occur. Never use
        batteries other than the specified type (Size D alkaline batteries).
         CAUTION
        The battery must be replaced with the power of the CNC turned on (the servo
        amplifier turned on).
        Note that, if batteries are replaced while no power is supplied to the CNC, the
        recorded absolute position is lost.
4.4.3         Battery for Absolute Pulsecoder Built into the Motor (6VDC)
 The battery for the absolute pulse coder built into the motor is installed in the servo amplifier. For the
 methods of connection and replacement, refer to the maintenance manual of your servo amplifier.
                                                   - 42 -
B-64303EN/03                                                5.CONNECTION TO CNC PERIPHERALS
5.1.1          Overview
   The CNC controller and the display unit are connected within the unit, so a machine tool builder does not
   need to connect them. The MDI cable is also included except for the 10.4" color LCD, so a machine
   tool builder does not need to connect it. Therefore, this subsection describes how to connect the CNC
   control unit and the MDI unit for the 10.4" color LCD.
                                                   - 43 -
5.CONNECTION TO CNC PERIPHERALS                                  B-64303EN/03
ファンモータ ファンモータ
                                    Rear
                                ユニット裏面        of unit
バッテリ
JA2
MDI Cable
MDI unit
                                     - 44 -
B-64303EN/03                                                        5.CONNECTION TO CNC PERIPHERALS
                                         *KEY00   01                         01   *KEY00
                                         *KEY02   02                         02   *KEY02
                                         *KEY01   11                         11   *KEY01
                                                  12                         12
                                         *KEY03                                   *KEY03
                                                  03                         03
                                         *KEY04                                   *KEY04
                                                  04                         04
                                         *KEY06                                   *KEY06
                                                  13                         13
                                         *KEY05                                   *KEY05
                                                  14                         14
                                         *KEY07                                   *KEY07
                                                  05                         05
                                         *COM00                                   *COM00
                                                  06                         06
                                         *COM02                                   *COM02
                                                  15                         15
                                         *COM01                                   *COM01
                                                  16                         16
                                         *COM03                                   *COM03
                                                  07                         07
                                         *COM04                                   *COM04
                                                  08                         08
                                         *COM06                                   *COM06
                                                  17                         17
                                         *COM05                                   *COM05
                                                  18                         18
                                         *COM07                                   *COM07
                                                  09                         09
                                         *COM08                                   *COM08
                                                  10                         10
                                         *COM10                                   *COM10
                                                  19                         19
                                         *COM09                                   *COM09
                                                  20                         20
                                         *COM11                                   *COM11
                                                                       Shield
                                                            Grounding plate
     NOTE
       The MDI cable needs to be clamped to prevent a heavy load caused by vibration
       from being applied to the cable. When the cable length is 50 cm or less,
       however, shielding or clamping is not necessary.
                                                           - 45 -
5.CONNECTION TO CNC PERIPHERALS                                                                                          B-64303EN/03
Edit keys
                                                                                                 INPUT key
                Function keys
                                                                                                 SHIFT key
                                                                                                 HELP key
             Page change keys
                                                                                                 RESET key
Edit keys
                                                            - 46 -
B-64303EN/03                                                          5.CONNECTION TO CNC PERIPHERALS
Soft keys
RESET key
Function keys
HELP key
Edit keys
Edit keys
                                                             - 47 -
5.CONNECTION TO CNC PERIPHERALS                                                                                                 B-64303EN/03
                                                                                                        INPUT key
            Function keys
                                                                                                        SHIFT key
                                                                                                        HELP key
          Page change keys
                                                                                                        RESET key
Edit keys
Soft keys
RESET key
Function keys
HELP key
Edit keys
                                                            - 48 -
B-64303EN/03                                                5.CONNECTION TO CNC PERIPHERALS
5.2.1          Overview
   An input/output device is used to enter information such as CNC programs and parameters from an
   external device to the CNC, or to output information from the CNC to an external device.
   The interface of the input/output devices electrically conforms to RS-232-C, so that a connection can be
   made with a device that has an RS-232-C interface.
   The tables below indicate the serial ports of this CNC.
     NOTE
       When using the touch panel, the interface of the second channel cannot be used
       as the interface of input/output devices because it is used to communicate with
       the touch panel on the CNC side.
                                                   - 49 -
5.CONNECTION TO CNC PERIPHERALS                                             B-64303EN/03
I/O device
   NOTE
      When the PANEL i is used in the stand-alone type, the RS-232-C interface on
      the PC side is normally used to input or output parameters or programs. The
      cases where the PANEL i is used and RS-232-C interface on the CNC side is
      used are described below.
     • Ladder uploading or downloading via RS-232-C using FANUC LADDER or
         FANUC LADDER II
     • Ladder monitoring from an external PC using FANUC LADDER III
     • DNC operation via RS-232-C, external I/O device control
     • Input/output of parameters and programs by using the CNC screen display
         function
                                            - 50 -
B-64303EN/03                                            5.CONNECTION TO CNC PERIPHERALS
CNC
                                                              Relay connector
                    JD36A, JD36B                              (DBM-25S)
                    FI80-20P, DF1R020WB1
                    (PCR-EV20MDT)                              1   FG
                                                                          14
                                                               2   SD
                     1    RD     11 SD                                    15
                                                               3   RD
                     2    0V     12 0V                                    16
                                               >   >      <    4   RS
                     3    DR     13 ER                                    17
                                                               5   CS
                     4    0V     14 0V                                    18
                                                               6   DR
                     5    CS     15 RS                                    19
                                                               7   SG
                     6    0V     16 0V                                    20    ER
                                                               8   CD
                     7    CD     17 (*)                                   21
                                                               9
                     8    0V     18 (+5V)(*)                              22
                                                              10
                      9   (*)    19 +24V                                  23
                                                              11
                     10   +24V   20 (+5V)(*)                              24
                                                              12
                                                                          25    +24V
                                                              13
     NOTE
     1 +24 V can be used as the power supply for FANUC RS-232-C equipment.
     2 Do not connect anything to those pins for which signal names are not indicated.
     3 Pins 18 and 20 (+5V) are provided for touch channel connection.
     4 The upper connector names on the CNC side are for the LCD-mounted type.
       The lower connector name in parentheses is for the stand-alone type.
                                               - 51 -
5.CONNECTION TO CNC PERIPHERALS                                              B-64303EN/03
Cable connection
                                  1                       3
                            RD                                RD
                                  2
                            0V
                                  3                       6
                            DR                                DR
                                  4
                            0V
                                  5                       5
                            CS                                CS
                                  6
                            0V
                                  7                       8
                            CD                                CD
                                  8
                            0V
                                  9
                                  10
                          +24V                            2
                            SD    11
                                                              SD
                            0V    12
                                  13                     20
                            ER                                ER
                            0V    14
                                  15                      4
                            RS                                RS
                            0V    16                      7
                                  17
                                  18
                                  19                     25
                          +24V                                +24V
                                  20                      1
                                                              FG
                                             Shield
                                                        GND
                                   Grounding plate
                 Recommended wire specification
                 A66L-0001-0284#10P (#28AWG × 10 pairs)
                 Recommended cable–side connectors(JD36A, JD36B)
                 PCR-E20FA (Honda Tsushin Kogyo Co., Ltd.)
                 FI30-20S (Hirose Electric Co., Ltd.)
                 FCN-247J020-G/E (Fujitsu, Ltd.)
                 52622-2011 (Molex Japan Co., Ltd.)
   NOTE
   1 Do not connect anything to those pins for which signal names are not indicated.
   2 Recommended cable connector FI30-20S (Hirose Electric) cannot be used for
     the stand-alone type.
                                            - 52 -
B-64303EN/03                                                         5.CONNECTION TO CNC PERIPHERALS
CNC
                          Output
                                               SD (Send data)
                                               RS (Request to Send)
                                                                                   When CS is not used short CS
                                                                                   and RS.
                                               CS (Enable to send)
SG (Signal ground)
FG (Frame ground)
                                            data
     RD             104            Input    Receiving
                                                                     (When ISO code 0 is sent)
                                            data
      RS            105            Output   Sending         This signal is set to on when NC starts sending data and is
                                            request         turned off when transmission ends.
      CS            106            Input    Sending         When both this signal and the DR signal are set, the NC can
                                            permitted       send data. If external device processing is delayed by a
                                                            punching operation, etc., NC data sending can be stopped by
                                                            turning off this signal after sending two characters, including
                                                            the data being sent currently. If this signal will not be used,
                                                            make sure to strap this signal circuit to the RS signal circuit.
     DR             107            Input    Data set        When external device is ready to operate, this signal is set.
                                            ready           This signal should usually be connected to the signal
                                                            indicating external device power supply being on. (ER signal
                                                            of external device). See Note below.
                                                            The NC transfers data when this signal is set. If the signals
                                                            turned off during data transfer, alarm 086 is issued. If the DR
                                                            signal will not be used, make sure to strap this signal circuit
                                                            to the ER signal circuit.
                                                            - 53 -
5.CONNECTION TO CNC PERIPHERALS                                                                                            B-64303EN/03
       NOTE
         Signal on/off state is defined as follows;
b1 b2 b3 b4 b5 b6 b7 b8
  -      Codes
  Transmission codes are as follows:
  (i) EIA code and Control codes DC1 to DC4.
  (ii) ISO code and Control codes DC1 to DC4 (Optional ISO code input is necessary.)
  The connected external device must be able to recognize the following control codes, sent from NC.
                      Control code                            8           7        6        5      4                3        2     1
        DC1       Tape reader start                                                         ○                ○                    ○
        DC2       Tape punch designation                                                    ○                ○              ○
        DC3       Tape reader stop                            ○                             ○                ○              ○     ○
        DC4       Tape punch release                                                        ○                ○      ○
       NOTE
         The listed control codes are used for both EIA and ISO.
                                                                  Table 5.3.4
                       ISO code                                             EIA code                                  Meaning
     Character   8   7 6 5 4             3   2   1    Character    8   7     6 5 4          3   2   1
   0                     ○ ○         ●               0                       ○          ●                   Numeral   0
   1             ○       ○ ○         ●           ○   1                                  ●           ○       Numeral   1
   2             ○       ○ ○         ●       ○       2                                  ●       ○           Numeral   2
   3                     ○ ○         ●       ○   ○   3                          ○       ●       ○   ○       Numeral   3
   4             ○       ○ ○         ●   ○           4                                  ●   ○               Numeral   4
   5                     ○ ○         ●   ○       ○   5                          ○       ●   ○       ○       Numeral   5
   6                     ○ ○         ●   ○   ○       6                          ○       ●   ○   ○           Numeral   6
   7             ○       ○ ○         ●   ○   ○   ○   7                                  ●   ○   ○   ○       Numeral   7
   8             ○       ○ ○ ○       ●               8                              ○   ●                   Numeral   8
   9                     ○ ○ ○       ●           ○   9                          ○   ○   ●           ○       Numeral   9
   A                 ○               ●           ○   a                 ○    ○           ●           ○       Address   A
   B                 ○               ●       ○       b                 ○    ○           ●       ○       ?   Address   B
   C             ○   ○               ●       ○   ○   c                 ○    ○   ○       ●       ○   ○       Address   C
   D                 ○               ●   ○           d                 ○    ○           ●   ○           ?   Address   D
   E             ○   ○               ●   ○       ○   e                 ○    ○   ○       ●   ○       ○   ?   Address   E
   F             ○   ○               ●   ○   ○       f                 ○    ○   ○       ●   ○   ○           Address   F
   G                 ○               ●   ○   ○   ○   g                 ○    ○   ○       ●   ○   ○   ○       Address   G
   H                 ○          ○    ●               h                 ○    ○       ○   ●                   Address   H
   I             ○   ○          ○    ●           ○   i                 ○    ○   ○   ○   ●           ○       Address   I
   J             ○   ○          ○    ●       ○       j                 ○        ○       ●       ○   ○   ?   Address   J
   K                 ○          ○    ●       ○   ○   k                 ○        ○       ●       ○           Address   K
   L             ○   ○          ○    ●   ○           l                 ○                ●       ○   ○   ?   Address   L
   M                 ○          ○    ●   ○       ○   m                 ○        ○       ●   ○               Address   M
   N                 ○          ○    ●   ○   ○       n                 ○                ●   ○       ○       Address   N
   O             ○   ○          ○    ●   ○   ○   ○   o                 ○                ●   ○   ○           Address   O
   P                 ○      ○        ●               p                 ○        ○       ●   ○   ○   ○       Address   P
   Q             ○   ○      ○        ●           ○   q                 ○        ○   ○   ●                   Address   Q
   R             ○   ○      ○        ●       ○       r                 ○            ○   ●           ○       Address   R
   S                 ○      ○        ●       ○   ○   s                      ○   ○       ●       ○           Address   S
   T             ○   ○      ○        ●   ○           t                      ○           ●       ○   ○       Address   T
   U                 ○      ○        ●   ○       ○   u                      ○   ○       ●   ○               Address   U
   V                 ○      ○        ●   ○   ○       v                      ○           ●   ○       ○   ?   Address   V
   W             ○   ○      ○        ●   ○   ○   ○   w                      ○           ●   ○   ○           Address   W
   X             ○   ○      ○ ○      ●               x                      ○   ○       ●   ○   ○   ○       Address   X
   Y                 ○      ○ ○      ●           ○   y                      ○   ○   ○   ●               ?   Address   Y
   Z                 ○      ○ ○      ●       ○       z                      ○       ○   ●           ○       Address   Z
   DEL           ○   ○ ○ ○ ○         ●   ○   ○   ○   Del               ○    ○   ○   ○   ●   ○   ○   ○   *
   NUL                               ●               Blank                              ●               *
   BS            ○               ○   ●               BS                     ○       ○   ●       ○       *
   HT                            ○   ●           ○   Tab                    ○   ○   ○   ●   ○   ○       *
   LF or NL                      ○   ●       ○       CR or         ○                    ●
                                                     EOB
   CR            ○               ○   ●   ○       ○                                                      *
   SP            ○       ○           ●               SP                         ○       ●               *
   %             ○       ○           ●   ○       ○   ER                             ○   ●       ○   ○
   (                     ○       ○   ●               ( 2-4-5 )                  ○   ○   ●       ○
   )             ○       ○       ○   ●           ○   ( 2-4-7 )         ○            ○   ●       ○
   +                     ○       ○   ●       ○   ○   +                 ○    ○   ○       ●               *
   -                     ○       ○   ●   ○       ○   -                 ○                ●
   :                     ○   ○   ○   ●       ○
   /             ○       ○       ○   ●   ○   ○   ○   /                      ○   ○       ●           ○
   .                     ○       ○   ●   ○   ○       .                 ○    ○       ○   ●       ○   ○
   #             ○       ○           ●       ○   ○
   $                     ○           ●   ○
   &             ○       ○           ●   ○   ○       &                              ○   ●   ○   ○       *
                         ○           ●   ○   ○   ○                                                      *
   *             ○       ○       ○   ●       ○                                                          *
   ,             ○       ○       ○   ●   ○           ,                      ○   ○   ○   ●       ○   ○   *
   ;             ○       ○   ○   ○   ●       ○   ○                                                      *
   <                     ○   ○   ○   ●   ○                                                              *
   =             ○       ○   ○   ○   ●   ○       ○                                                      *
   >             ○       ○   ○   ○   ●   ○   ○                                                          *
   ?                     ○   ○   ○   ●   ○   ○   ○                                                      *
   @             ○   ○               ●                                                                  *
   ”                     ○                   ○                                                          *
                                                                   - 55 -
5.CONNECTION TO CNC PERIPHERALS                                                                                                     B-64303EN/03
    NOTE
    1 When the external device is equipped with an ISO/EIA converter, the following
      items must be noted in Table 5.3.4 (a).
                                                                              Control out (Comment field start)
                                                                              Control in (Comment field end)
       Condition1 Left parenthesis "("of the ISO code punches holes at bits 2, 4 and 5
                  when used in the EIA code.
                  Right parenthesis ")"of the ISO code punches holes at bits 2, 4 and
                  7 when used in the EIA code.
       Condition2 EIA code CR is LF in ISO code.
       Condition3 EIA code O is : in ISO code.
    2 Control codes DC1 to DC4 are transmission codes output from the NC.
      So they need not to be punched on the NC tape.
      [Example]
           Baud rate : 110
           When using one start bit and two stop bits (totalling 11 bits per character):
           Transmission characters/second= 110/11
           =10 characters/second (Max.)
  (4) Cable length
      The cable length depends on the external device type. Consult with the device manufacturers for
      actual connecting cable lengths.
      Cable length is as follows by the specification of NC.
      for RS-232C
      100m or less         4800 bauds or less
      50m or less          19200 bauds or less
                                                                  - 56 -
B-64303EN/03                                                         5.CONNECTION TO CNC PERIPHERALS
      ER
       (output)
      RS (output)
                                     DC1         DC3           DC1                           DC3
      SD (output)
                                                                                        ER code
RD (input)
DR (input)
CS (input)
                                                 Up to 10 characters
                      1ms or longer
ER (output)
      RS (output)
                                           DC2                                    DC4
SD (output)
RD (input)
CS (input)
                                                            - 57 -
5.CONNECTION TO CNC PERIPHERALS                                                                  B-64303EN/03
ER (output)
    RS (output)
                                         DC2                                      DC4
    SD (output)
                                                    DC3              DC1
    RD (input)
Within 2 characters
DR (input)
CS (input)
1ms or longer
SD SD
RD RD
RS RS
CS CS
ER ER
DR DR
CD CD
SG SG
FG FG
                                                            - 58 -
B-64303EN/03                                                        5.CONNECTION TO CNC PERIPHERALS
   ●    Use the connection shown in the figure below when the ER and DR signals are not used for
        handshaking.
                             CNC side                                                     I/O device side
SD SD
RD RD
RS RS
CS CS
ER ER
DR DR
CD CD
SG SG
FG FG
   he cable for connecting the I/O device to the CNC should be connected as shown in the below diagram.
                       Serial interface
                                          SD
                                          RD
                                          RS
                                          CS
                                          SG
                                          ER
                                          DR
                                                                          2
                                          Cable : twist 10 pairs × 0.18mm , with shield
                                                           - 59 -
5.CONNECTION TO CNC PERIPHERALS                                               B-64303EN/03
                      1    HDI0   11   HDI1
                      2     0V    12    0V
                      3    HDI2   13   HDI3
                      4     0V    14    0V
                      5     0V    15
                      6           16
                      7           17
                      8           18
                      9           19
                      10   0V     20
   NOTE
   1 The upper connector specification on the JA40 is for the LCD-mounted type.
     The lower connector specification in parentheses is for the stand-alone type.
   2 Do not connect any signal to the pins with no signal name.
                                              - 60 -
B-64303EN/03                                                  5.CONNECTION TO CNC PERIPHERALS
Cable connections
                       JA40
                                 1
                        HDI0
                                 2
                         0V
                                 11
                        HDI1
                                 12
                         0V
                                 3
                        HDI2
                                 4
                         0V
                                 13
                        HDI3
                                 14
                         0V
                                 6
                                 5
                         0V
                                 15
                                 16
                                 17
                                 18
                                 19
                                 20
                                 7
                                 8
                                 9
0V 10
Shield
Ground plate
     NOTE
       Recommended cable connector FI30-20S (Hirose Electric) cannot be used for
       the stand-alone type.
CNC
VH/VL
SHIELD
                                                     - 61 -
5.CONNECTION TO CNC PERIPHERALS                                                          B-64303EN/03
    NOTE
    1 The plus (+) sign of IiH/IiL represents the direction of flow into the receiver. The
      minus (-) sign of IiH/IiL represents the direction of flow out of the receiver.
    2 The high-speed skip signal is assumed to be 1 when the input voltage is at the
      low level and 0 when it is at the high level.
    3 The input level for the CNC receiver is high when the circuit is open. So, the
      input level for the external driver must be low.
                                               - 62 -
B-64303EN/03                                                    5.CONNECTION TO CNC PERIPHERALS
                        Max. 100m
                                                                          Shield
                                                                 HUB
                                                           (line concentrator)
     NOTE
     1 To make a connection to the 10BASE-T Ethernet, use a hub that meets the
       following conditions.
       • Compliant with 100BASE-TX
       • With the auto-negotiation function
       • Support for the store & forward system
     2 Some of the units (hub, transceiver, etc.) required to build a network are not
       dust-proof/water-proof (oil-proof). Using them in an atmosphere with dust or oil
       mist may lead to a communication error or failure. They should be enclosed in a
       dust-proof/water-proof (oil-proof) cabinet.
Control unit
Ethernet cable
Clamp
Grounding plate
                                                       - 63 -
5.CONNECTION TO CNC PERIPHERALS                                                                              B-64303EN/03
CD38A HUB
                                1     TX+                                      1         TX+
                                2     TX-          RJ-45 modular jack          2         TX-
                                3     RX+                                      3         RX+
                                4                                              4
                                5                                              5
                                6     RX-                                      6         RX-
                                7                                              7
                                8                                              8
                                                         Max. 100m
CD38A
                                            1                              1
                                      TX+                                          TX+
                                            2                              2
                                      TX-                                          TX-
                                            3                              3
                                      RX+                                          RX+
                                            6                              6
                                      RX-                                          RX-
Shield
    NOTE
      The cable can be up to 100 m long (for the FANUC- recommended cable for
      movable sections, up to 50 m). Do not make the cable longer than necessary.
Cable Wires
  Many cables without a shield (UTP cables) are commercially available as twisted pair cables conforming
  to 10BASE-T or 100BASE-TX. To improve noise immunity in factory automation environments,
  however, be sure to use twisted pair cables (STP cables) with a common shield in category 5.
    NOTE
      No cable recommended for use in fixed sections shall be used in movable
      sections. Be sure to use the following movable-section cables.
                                                      - 64 -
B-64303EN/03                                               5.CONNECTION TO CNC PERIPHERALS
   Recommended cable (for movable sections)
               Manufacturer                      Specification                             Remark
   Oki Electric Cable Co., Ltd.    AWG26 4P TPMC-C5-F(SB)                       Dedicated to FANUC products
     NOTE
       Use the TM21CP-88P(03) connector made by Hirose Electric Co., Ltd. to this
       cable.
Connector specification
   An 8-pin modular connector called the RJ-45 is used with a twisted-pair cable for Ethernet interfaces.
   Use the connector listed below or equivalent.
                                                            Specification         Manufacturer        Remark
   Connector used with cable AWG26 4P TPMC-C5-F(SB)        TM21CP-88P(03) Hirose Electric Co., Ltd.   (Note)
     NOTE
       About TM21CP-88P(03)
       Connector (manufacturer's standard product)
       Drawing number: A63L-0001-0823#P
       Manufacturer: Hirose Electric Co., Ltd.
       Manufacturer's model number: TM21CP-88P(03)
       Complying with EIA/TIA 568A categories 3 and 5
       Ask Hirose Electric Co., Ltd. for explanations about how to attach the connector
       to a cable.
   (Hirose Electric Co., Ltd. offers the TM21CP-88P(03) Wiring Procedure Specification (Engineering
   Specification No. ATAD-E2367) to explain the related technical information.)
                                                  - 65 -
5.CONNECTION TO CNC PERIPHERALS                                                            B-64303EN/03
                                                - 66 -
B-64303EN/03                                       5.CONNECTION TO CNC PERIPHERALS
     NOTE
     1 Ground the PC and backbone cable separately from the machine system.
       If this is impossible because there is only one grounding point, use separate
       grounding wires for the PC/backbone cable and the machine system up to the
       grounding point.
       The grounding resistance must not be higher than 100 Ω (class 3 grounding).
       The grounding wire must not be thinner than the AC power line conductor, and
       its cross-sectional area must not smaller than 5.5 mm2.
     2 In some cases, the aforementioned isolation/separation method based on
       100BASE-TX cannot assure normal communication because of influence by
       noise. In such worst environments, use optical fiber media to completely isolate
       the machine from the PC.
                                          - 67 -
5.CONNECTION TO CNC PERIPHERALS                                                                 B-64303EN/03
                                                                                    R232-2
                                                                                    JD36B
                                               - 68 -
B-64303EN/03                                                5.CONNECTION TO CNC PERIPHERALS
Connection cable
   The connection diagram is shown below.
                          NC side                                      External touch panel
                                       JD36B                           side
                                       SD (11)                    SD
RD (1) RD
RS (15) RS
CS (5) CS
ER (13)
DR (3)
CD (7)
0V (4,6,8,14,16) SG
                                                   - 69 -
5.CONNECTION TO CNC PERIPHERALS                                          B-64303EN/03
                                 JD36B
                                 11                              RD
                           SD
                                 12
                            0V
                                 1
                           RD                                    SD
                                 2
                            0V
                                 15
                           RS                                    RS
                                 5
                           CS                                    CS
                                 3
                           DR
                                 7
                           CD
                                 13
                           ER
                                 4,6,8,14,16
                           0V                                    SG
                                                        Shield
                                               Grounding
                                               plate
   NOTE
     Recommended cable connector FI30-20S (Hirose Electric) cannot be used for
     the stand-alone type.
                                                      - 70 -
B-64303EN/03                                                                           6.SPINDLE CONNECTION
6               SPINDLE CONNECTION
   The figure below shows the spindle–related connections. Note that the number of connectable spindles
   depends on the model. So, see the tables that follow the figure below.
When using third serial spindle, the serial spindle connector panel is necessary.
                                                                - 71 -
6.SPINDLE CONNECTION                                                                              B-64303EN/03
                       (1)
                                                                                    Position coder
                                                           Spindle Amp. (first)
                                     JA7A-1                    JA7B
                       (2)       (Channel 1)
          JA41                  JA48                                     TB2
                                     JA7A-2                    JA7A
                                 (Channel 2)                                      Spindle motor
                       (3)
                                 Serial spindle                                      Position coder
                                 connector                 Spindle Amp.(second)
                                 panel
                                                               JA7B
                                                               JA7A      TB2
       CNC
       Main                                                                       Spindle motor
       board
                                                                                    Position coder
                                                           Spindle Amp. (first)
                                                               JA7B αi SP
                                                               JA7A      TB2
                                                                                  Spindle motor
                                                           Position coder for analog spindle
                                                           Inverter
          JA40
                                                                             Analog spindle
 (1) To use one serial spindle, make a direct connection from JA41 on CNC to the spindle amplifier. And,
     to two serial spindles, make a direct connection from JA7A on the first amplifier to the second
     spindle amplifier.
 (2) To use third serial spindle, make a connection from JA41 on CNC to the serial spindle connector
     panel for a branch. And, make a connection from JA7A-1 on the serial spindle connector panel for a
     branch to the first spindle amplifier, make a connection from JA7A-2 on the serial spindle connector
     panel for a branch to the third spindle amplifier
 (3) To use the position coder for an analog spindle, make a direct connection from JA41 to the position
     coder.
   NOTE
     When using the serial spindle interface, the position coder interface for analog
     spindles cannot be used.
                                                  - 72 -
B-64303EN/03                                                                                  6.SPINDLE CONNECTION
Interconnection cable 1
CNC
                                                 Optical cable
                                                                                                               Spindle amplifier
                                                                          Spindle amplifier
                  Interconnection cable 2
                                                                          JA7B                                    JA7B
JA7A JA7A
Interconnection cable 1
                                                                 - 73 -
6.SPINDLE CONNECTION                                                                                          B-64303EN/03
 Interconnection cable 1
                    CNC, spindle amplifier, serial                           Spindle amplifier
                      spindle connector panel
                   JA41(FI80-20P, DF1R020WB1)
                   JA7A(PCR-EV20MDT)                                           JA7B
                   JA7A-1,2(PCR-E20MD)                                         PCR-EV20MDT
                     1 SIN          11                                         1 SIN         11 0V
                     2 *SIN         12 0V                                      2 *SIN        12 0V
                     3 SOUT         13                                         3 SOUT        13 0V
                     4 *SOUT        14 0V                                      4 *SOUT       14 0V
                     5 [       ]    15 [        ]                              5             15 0V
                     6 [       ]    16 0V                                      6             16 0V
                     7 [       ]    17 [        ]                              7             17
                     8 [       ]    18 (+5V)                                   8             18 (+5V)
                     9 (+5V)        19 [        ]                              9 (+5V)       19
                     10 [      ]    20 (+5V)                                   10            20 (+5V)
   NOTE
   1 When an optical cable is used for connection between the NC and a spindle
     amplifier, the +5V signals indicated in parentheses are used to feed power to the
     optical adapter.
   2 The signals indicated in angle brackets [ ] are reserved for functional
     expansion, so no connection to them is allowed.
   3 The upper connector specification of JA41 is for the LCD-mounted type.
     The lower connector specification is for the stand-alone type.
Cable connection
                                                            - 74 -
B-64303EN/03                                                                              6.SPINDLE CONNECTION
   Interconnection cable 2
                      CNC, spindle amplifier, serial
                        spindle connector panel                                      Optical adapter
                     JA41(FI80-20P, DF1R020WB1)
                     JA7B(PCR-EV20MDT)                                         JD1
                     JA7A-1,2(PCR-E20MD)
                                                                               PCR-E20LMDT
                       1 SIN            11                                     1 SIN        11 0V
                       2 *SIN           12 0V                                  2 *SIN       12 0V
                       3 SOUT           13                                     3 SOUT       13 0V
                       4 *SOUT          14 0V                                  4 *SOUT      14 0V
                       5 [          ]   15 [      ]                            5            15 0V
                       6 [          ]   16 0V                                  6            16 0V
                       7 [          ]   17 [      ]                            7            17
                       8 [          ]   18 +5V                                 8            18 +5V
                       9 +5V            19 [      ]                            9 +5V        19
                       10 [         ]   20 +5V                                 10           20 +5V
     NOTE
     1 The signals indicated in angle brackets are reserved for functional expansion, so
       no connection to them is allowed.
     2 The upper connector specification of JA41 is for the LCD-mounted type.
       The lower connector specification is for the stand-alone type.
40 4-M3
                                  Connector for
                                  connecting a                              Optical
                                  unit                                      connector
                                  JD1                  FANUC                COP1
                             45
18
                                                             - 75 -
6.SPINDLE CONNECTION                                                                                                              B-64303EN/03
45
                         40
                                                                  Connector for connection with a spindle
                                                                  amplifier JA7A-1 (first channel)
18
 Connection diagram
 (Connection diagram when only electrical cables are used)
                                 Serial spindle
                                 connector panel
                                                                              Spindle amplifier
                Interconnection cable 3
                                                                - 76 -
B-64303EN/03                                                                                           6.SPINDLE CONNECTION
   (Connection diagram when optical cables are used)
                                   Serial spindle connector panel
           CNC                                                                       JD1
                                                  JA7A-1
                                                                                            COP1
                                                                                                             Optical adapter
               JA41                         JA48
                                                                                     JD1
                                                  JA7A-2                                    COP1
Interconnection cable 2
                                                        JD1                          JA7B
                                                 COP1                                        JA7A
Spindle amplifier
     NOTE
     1 When an optical cable is used for the connection between the CNC and a
       spindle, the +5V signals indicated in parentheses are used to feed power to the
       optical adapter.
     2 No connections must be made to the pins with angle brackets (< >) because
       they are reserved for expansions.
     3 The upper connector specification of JA41 is for the LCD-mounted type.
       The lower connector specification in parentheses is for the stand-alone type.
                                                                  - 77 -
6.SPINDLE CONNECTION                                                                                B-64303EN/03
Cable connection
                     JA41                                                                 JA48
                              SINA       1                               3
                                                                               SOUTA
                             *SINA       2                               4
                                                                               *SOUTA
                                         3                               1
                            SOUTA                                              SINA
                                         4                               2
                            *SOUTA                                             *SINA
                                         15                             15
                               SINB                                            SOUTB
                                         17                             17
                              *SINB                                            *SOUTB
                                         19                             19
                             SOUTB                                             SINB
                                         10                             10
                            *SOUTB                                      12     *SINB
                                         12
                                 0V                                            0V
                                         14                             14
                                 0V                                            0V
                                         16                             16
                                 0V                                            0V
                                                   Shield
                                Ground plate
   NOTE
     When this cable is installed close to other cables such as a power line, a
     shielded wire must be connected to the ground plate. When the CNC is
     installed close to the serial spindle connector panel, however, no connection to
     the ground plate is necessary.
   NOTE
   1 No connections must be made to the pins with angle brackets (< >) because
     they are reserved for expansions.
   2 The upper connector specification of JA41 is for the LCD-mounted type.
     The lower connector name in parentheses is for the stand-alone type.
                                                   - 78 -
B-64303EN/03                                                                  6.SPINDLE CONNECTION
                    Cable connection
                    JA41               1                              3             JA48
                             SINA                                         SOUTA
                                       2                              4
                            *SINA                                         *SOUTA
                                       3                              1
                           SOUTA                                          SINA
                                       4                              2
                           *SOUTA                                         *SINA
                                       15                            15
                              SINB                                        SOUTB
                                       17                            17
                             *SINB                                        *SOUTB
                                       19                            19
                            SOUTB                                         SINB
                                       10                            10
                           *SOUTB                                         *SINB
                                       9                              9
                               +5V                                        +5V
                                       18                            18
                               +5V                                        +5V
                                       20                            20
                               +5V                                        +5V
                                       12                            12
                                0V                                        0V
                                       14                            14
                                0V                                        0V
                                       16                            16
                                0V                                        0V
                                                   Shield
                                 Ground plate
     NOTE
     1 When this cable is installed close to other cables such as a power line, a
       shielded wire needs to be connected to the ground plate. When the CNC is
       installed close to the serial spindle connector panel, however, a connection to
       the ground plate is unnecessary.
     2 Connection cable 1 between the serial spindle connector panel and the spindle
       amplifier, and connection cable 2 between the serial spindle connector panel and
       the optical module are the same as those used when one or two serial spindles
       are connected.
     3 When this cable is installed close to other cables such as a power line, a
       shielded wire needs to be connected to the ground plate. However, when the
       serial spindle connector panel is installed near the spindle amplifier or when the
       serial spindle connector panel is installed near the optical module, no connection
       to the ground plate is necessary.
                                                   - 79 -
6.SPINDLE CONNECTION                                                                                  B-64303EN/03
                                                7                        10
                                        SVC                              12   DA2
                                                5
                                         ES                                   E
                                                8                        14
                                       ENB1
                                                9                        16
                                       ENB2                 Shield
Ground plate
   NOTE
   1 ENB1 and ENB2 are turned on when the spindle voltage command is valid.
     These signals are used when other than the FANUC analog spindle servo unit is
     used.
   2 The rating of analog output is shown below.
     Output voltage: ±10 V
     Output current: 2 mA (Max.)
     Output impedance: 100 Ω
   3 The signals enclosed by parentheses ( ) are used for high-speed skip (HDI).
   4 The upper connector specification of JA40 is for the LCD-mounted type.
     The lower connector name in parentheses is for the stand-alone type.
                                                          - 80 -
B-64303EN/03                                                                                        6.SPINDLE CONNECTION
Cable connection
                         JA41                       1                                  3
                                          PA                                               A(PA)
                                                    2                                  4
                                         *PA                                               N(*PA)
                                                    3                                  1
                                          PB                                               C(PB)
                                                    4                                  2
                                         *PB                                               R(*PB)
                                                    15                                15
                                          SC                                               B(PZ)
                                                    17                                17
                                         *SC                                               P(*PZ)
                                                    19                                19
                                         +5V                                               H
                                                    10                                10
                                          0V                                               K
                                                                        Shield
                                                             Ground plate
                    Recommended cable connector:
                    PCR-E20FA (manufactured by Honda Tsushin Kogyo)
                    FCN-247J020-G/E (manufactured by Fujitsu)
                    52622-2011 (manufactured by Molex Japan)
     NOTE
     1 The signals enclosed by parentheses ( ) are used for serial spindles. These
       signals are not used for analog spindles.
     2 The 15-pin soldering connector (FI40B-2015S (conventionally, FI40-2015S))
       manufactured by Hirose Electric cannot be used for the connector on the cable
       side.
     3 The upper connector specification of JA41 is for the LCD-mounted type.
       The lower connector name in parentheses is for the stand-alone type.
                                                                        - 81 -
7.SERVO INTERFACE                                                   B-64303EN/03
7                SERVO INTERFACE
7.1              CONNECTION TO THE SERVO AMPLIFIERS
Control unit
Rear of unit
COP10A-1
                                                           - 82 -
B-64303EN/03                                                                                           7.SERVO INTERFACE
7.1.1           Overview
   This chapter generally describes connections between this CNC and servo units.
   For details on connections to servo amplifiers, refer to the manual of each servo amplifier.
   (2) The cable length between CNC and the first slave unit is
       •    Within 50m with A66L-6001-0026#~
                                                                               3)
                                                                                          COP10B
                                                                                          COP10A
                                                                               3)
                                                                                          COP10B
                                                                                          COP10A
                                                                               3)
                                                                                          COP10B
                                                                                          COP10A
                                                                                          Separate
                                                                                          detector
                                                                                          interface unit
                                                                               3)
                                                                                          COP10B
                                                                                          COP10A
     NOTE
       For details and handling of optical cables, see Appendix D.
                                                              - 83 -
7.SERVO INTERFACE                                                                                       B-64303EN/03
                                                                                      CP11A
                             Servo amplifier
                                           Digital output
                                           Linear encoder or rotary encoder
                                                       - 84 -
B-64303EN/03                                                                                           7.SERVO INTERFACE
               CNC
                                                                                           Servo amplifier
                     Servo card
                                                     Optical fiber cable
                                  COP10A                                                       COP10B
                                                                                               COP10A
                                                                                               COP10B
                                                                                               COP10A
                                                                                               COP10B
                                       Optical fiber cable
                                                                                               COP10A
                  Flat cable
                                           Separate detector interface unit (additional)
   When a separate detector such as a separate rotary encoder or linear encoder is used, a separate detector
   interface unit is required. The separate detector interface unit is connected through an optical fiber cable
   as an unit on an FSSB line.
   A separate detector interface unit consists of basic units and additional units. Up to four pulse coders or
   liner scales can be connected by adding an additional unit (up to eight units can be connected as a total).
   An additional unit is connected to a basic unit through a flat cable. The maximum number of separate
   detector interface units that can be connected to an FSSB line is two for HRV2 and HRV3.
     NOTE
     1 Unused optical connectors must be covered with the caps.
     2 When using an encoder with an analog output of 1 Vp-p, see the description of
       the analog input separate detector interface.
                                                             - 85 -
7.SERVO INTERFACE                                                                                                B-64303EN/03
                 Item                                                          Specification
  Ordering information                       A02B-0303-C205 (basic)
                                             A02B-0236-C204 (additional)
  Method of installation                     An interface unit can be installed by using screws or a DIN rail.
                               CP11A
                                1     +24V                                        24 VDC regulated power
                                2       0V                                        supply
                                3                                                 24 VDC ±10%
GND
Cable
                            CP11A
                           AMP JAPAN
                           1-178288-3 (Housing)
                           1-175218-5 (Contact)                                  External power supply
 The 24 VDC input to CP11A can be output at CP11B for use in branching. The connection of CP11B is
 identical to that of CP11A. In this case, the power supplied to CP11A should be equal to the sum of the
 rating of the separate detector interface unit and that of the units after CP11B.
 Be sure to ground the 0-V line of the power supply to the separate detector interface unit. In addition,
 keep any noise source (such as an AC power cable and contactor) away from the power line of the
 separate detector interface unit as far as possible to prevent noise from being picked up through the power
 line.
 Secure the ground line to the ground terminal (GND) for signals of a separate detector interface unit,
 which is located at the bottom of the unit, with an M3 screw as shown in the figure below. Connect the
 ground line to the ground plate of the cabinet.
                                                               - 86 -
B-64303EN/03                                                       7.SERVO INTERFACE
GND
     NOTE
       The torque with which a screw is tightened is 5 kgf⋅cm or less.
                                                - 87 -
7.SERVO INTERFACE                                                                         B-64303EN/03
              JF101 to JF108
              (PCR-EV20MDT)
                1    SD     11
                2   *SD     12    0V
                3           13
                4           14    0V
                5    REQ    15
                6   *REQ 16       0V
                7   (+6V)   17                  The +6V signal is provided for absolute
                8           18    +5V           position detectors that require battery
                9    +5V    19                  backup.
               10           20   +5V
Cable connection
                            1
                      SD                                                      SD
                            2
                     *SD                                                      *SD
                            5
                    REQ                                                       REQ
                            6
                    *REQ                                                      *REQ
                            7
                    (+6V)                                                     (+6V)
                            18
                     +5V                                                      +5V
                            20
                     +5V                                                      +5V
                            12
                       0V                                                     0V
                            14
                       0V                                                     0V
                            16             Shielded drain wire
                       0V                                                     FG
                                                         Shield               (Frame
                                   Ground plate
               Recommended cable:
               A66L-0001-0286 (#20AWG × 6 + #24AWG × 3-pair)
               Recommended connectors:
               PCR-E20FA (Honda Tsushin Kogyo)
               FI30-20S (Hirose Electric)
               FCN-247J020-G/E (Fujitsu)
               52622-2011 (Molex)
               FI40B-2015S (Hirose Electric)
                                                - 88 -
B-64303EN/03                                                        7.SERVO INTERFACE
     NOTE
     1 The +5V signals above can be used to feed power to the detectors. The supply
       current per linear scale is 0.35 A maximum.
       Lower limit of the 5V signals: 4.95 V for the basic unit, and 4.9 V for the
       additional unit
     2 If the cable is connected to JA4A when the separate absolute pulse coder
       battery case contains the battery, the battery voltage is applied to the battery
       power supply pin (+6 V) for each of the feedback connectors (JF101 to JF108).
       In this case, if the battery line and 0 V are short-circuited, the battery may heat
       up or the protection circuit within the separate detector interface unit may fail.
       First, make sure the battery case contains no battery or the cable is not
       connected to JA4A. Then, complete all cabling work and confirm cables are
       correctly connected. Finally, place the battery or connect the cable to JA4A.
                                            - 89 -
7.SERVO INTERFACE                                                                          B-64303EN/03
               1     PCA     11
               2    *PCA     12   0V
               3     PCB     13
               4    *PCB     14   0V
               5     PCZ     15
               6    *PCZ     16   0V
               7    (+6V)    17
               8    (REQ)    18   +5V           The +6V and REQ signals are provided for
               9     +5V     19                 absolute position detectors that require
               10            20   +5V           battery backup.
Cable connection
                             1
                      PCA                                                       PCA
                             2
                    *PCA                                                        *PCA
                             3
                      PCB                                                       PCB
                             4
                    *PCB                                                        *PCB
                             5
                      PCZ                                                       PCZ
                             6
                    *PCZ                                                        *PCZ
                             7
                     (+6V)                                                      (+6V)
                             8
                     (REQ)                                                      (REQ)
                             9
                      +5V                                                       +5V
                             18
                      +5V                                                       +5V
                             20
                      +5V                                                       +5V
                             12
                       0V                                                       0V
                             14
                       0V                                                       0V
                             16
                       0V                                                       0V
                                                   Shield
                                        Ground plate
                RECOMMENDED CABLE MATERIAL
                A66L-0001-0286 (#20AWG × 6 + #24AWG × 3-pair)
                Recommended connectors:
                PCR-E20FA (Honda Tsushin Kogyo)
                FI30-20S (Hirose Electric)
                FCN-247J020-G/E (Fujitsu)
                52622-2011 (Molex)
                FI40B-2015S (Hirose Electric)
                                                 - 90 -
B-64303EN/03                                                                                  7.SERVO INTERFACE
     NOTE
     1 The +5V signals above can be used to feed power to the detectors. The supply
       current per detector is 0.35 A maximum.
       Minimum tolerance to 5 V: 4.95 V for main unit and 4.9 V for added section
     2 If the cable is connected to JA4A when the separate absolute pulse coder
       battery case contains the battery, the battery voltage is applied to the battery
       power supply pin (+6 V) for each of the feedback connectors (JF101 to JF108).
       In this case, if the battery line and 0 V are short-circuited, the battery may heat
       up or the protection circuit within the separate detector interface unit may fail.
       First, make sure the battery case contains no battery or the cable is not
       connected to JA4A. Then, complete all cabling work and confirm cables are
       correctly connected. Finally, place the battery or connect the cable to JA4A.
B phase signal
                                                       A phase signal
                            Shift in minus direction
B phase signal
                                                              - 91 -
7.SERVO INTERFACE                                                                                      B-64303EN/03
                                  *PCZ
                                                       0.5V
                                  PCZ
                                                       Tw
                                                                            TOFF
Z phase signal
Time requirements
  Requirements for the signals at the input pins of input connectors JF101 to JF108. The signals for these
  connectors are differential input signals with A and B phases. An important factor is time TD from
  point A, when the potential difference between PCA and *PCA exceeds 0.5V, to point B, when the
  potential difference between PCB and *PCB becomes lower than 0.5V. The minimum value of TD is
  0.15msec. The period and pulse width of the signals must be long enough to satisfy the above
  requirements.
  The Z phase signal is also a differential signal. The following conditions are stipulated for the time from
  when the potential difference between PCZ and *PCZ exceeds 0.5 V to when the potential difference
  becomes lower than 0.5 V.
Receiver circuit
                                 PCA
                     A-phase                    110Ω
                     signal
                                 *PCA
                                                560Ω
                                                                The same circuit is used for B-phase
                                                                signals (PCB and *PCB)
                                           5V
                                                       - 92 -
B-64303EN/03                                                                              7.SERVO INTERFACE
   When the separate absolute position detector that needs battery backup is connected, the battery case for
   the separate absolute pulse coder must be connected.
                                                   - 93 -
7.SERVO INTERFACE                                                                               B-64303EN/03
                    Cable connection
                            JA4A                                 Battery case
                               7                                      +
                      +6V                                                  +6V
                               3                                      -
                       0V                                                  0V
                   Recommended connectors:
                   PCR-E20FA (Honda Tsushin Kogyo)
                   FI30-20S (Hirose Electric)
                   FCN-247J020-G/E (Fujitsu)
                   52622-2011 (Molex)
   NOTE
     If the cable is connected to JA4A when the separate absolute pulse coder
     battery case contains the battery, the battery voltage is applied to the battery
     power supply pin (+6 V) for each of the feedback connectors (JF101 to JF108).
     In this case, if the battery line and 0 V are short-circuited, the battery may heat
     up or the protection circuit within the separate detector interface unit may fail.
     First, make sure the battery case contains no battery or the cable is not
     connected to JA4A. Then, complete all cabling work and confirm cables are
     correctly connected. Finally, place the battery or connect the cable to JA4A.
                                                       - 94 -
B-64303EN/03                                                                          7.SERVO INTERFACE
                                                                                     Mounting
                                                                                     surface
CNF1 CNF2
Marking
                                                                                     mark
                                                         mark
Place an order on a flat cable together with separate detector interface units.
GND
                                                        - 95 -
7.SERVO INTERFACE                                                                           B-64303EN/03
7.2.9        Installation
 1)   Notes on installation
      (1) Use an interface unit in a completely enclosed cabinet.
      (2) Install an interface unit on a vertical surface, and provide a space of 100 mm above and below
          the unit. Below an interface unit, do not place equipment that generates a large amount of
          heat.
      (3) When using a basic unit and additional unit, place the units as shown below so that the flat
          cable connecting the units does not block the vent holes. A flat cable not longer than 100 mm
          must be used.
                                  Vent holes   Flat cable
                                                    - 96 -
B-64303EN/03                                                                    7.SERVO INTERFACE
   2)   Installation using screws
   When using both a basic unit and additional unit, install the units as shown above, with the mounting
   holes horizontally separated by 70 to 80 mm.
                                                     - 97 -
7.SERVO INTERFACE                                                                                     B-64303EN/03
DIN rail
DIN rail
                                                         - 98 -
B-64303EN/03                                                              7.SERVO INTERFACE
   Installing the unit:
   1. Hook the unit on the top of the DIN rail.
   2. Push the unit in until it clicks.
   Removing the unit:
   1. Push down the lock by using a screwdriver.
   2. Remove the unit by pulling the lower end of the unit towards you.
          CAUTION
         When removing the unit, be careful not to damage the lock by applying
         excessive force. When installing and removing the unit, hold the upper and
         lower ends of the unit so that stress is not applied to the side (that surface with
         the slits) of the unit.
                                                 - 99 -
7.SERVO INTERFACE                                                                                             B-64303EN/03
CP11A
Servo amplifier
                                                    - 100 -
B-64303EN/03                                                                                                      7.SERVO INTERFACE
7.3.1           Overview
   When a separate detector such as a rotary encoder or linear encoder with an analog output of 1 Vp-p is
   used, an analog input separate detector interface unit is used. The analog input separate detector unit is
   connected via an optical cable as a unit on the FSSB line. Up to four 1-Vp-p output separate detectors
   can be connected to a basic unit.
   One additional unit (A02B-0236-C204) can be connected to the basic unit with a flat cable. Four
   separate detectors with digital output can be connected to the additional unit. When five or more 1-Vp-p
   output separate detectors are to be used, more than one basic unit (analog input separate detector interface
   unit) is required. The JA4A connector is provided for the battery for absolute position detectors
   connected to the additional unit.
   The maximum number of separate detector interface units that can be connected to one FSSB line is two
   for HRV2 and HRV3, regardless of which input type, the analog input type or digital input type, is used.
     NOTE
     1 Unused optical connectors must be covered with the caps.
     2 A digital output encoder refers to an encoder that outputs A and B rectangular
       waveforms (parallel) or a FANUC serial interface output encoder (serial).
     3 No 1-Vp-p output encoder can be connected to additional units.
                                                                                                    COP10B
                                                                                                    COP10A
                                                                                                    COP10B
                                                Optical fiber cable
                                                                                                    COP10A
CNF1 JA4A
                                                                  - 101 -
7.SERVO INTERFACE                                                                                                                B-64303EN/03
                                                          COP10B           JF111
                                                                                               1Vp-p output encoder 1 axis
                      Optical fiber cable                 COP10A           JF112               1Vp-p output encoder 2 axes
                     24VDC                                CP11A            JF113
                                                                                               1Vp-p output encoder 3 axes
                                                                           JF114               1Vp-p output encoder 4 axes
                                                          CNF1              JA4A
                                                                            JF111
                                                          COP10B                                 1Vp-p output encoder 5 axes
                                                          COP10A            JF112                1Vp-p output encoder 6 axes
                                                          CP11A             JF113                1Vp-p output encoder 7 axes
                                                                            JF114                1Vp-p output encoder 8 axes
                                                          CNF1               JA4A
 (3) Connecting 1-Vp-p output encoders to the 1st to 4th axes and digital output encoders to the 1st to
     4th axes
                                   Optical fiber cable
                                                          COP10B          JF111
                                                                                               1Vp-p output encoder 1 axis
                                                          COP10A          JF112
                                                                                               1Vp-p output encoder 2 axes
                     24VDC                                CP11A           JF113
                                                                                               1Vp-p output encoder 3 axes
                                                                          JF114                1Vp-p output encoder 4 axes
                                                          CNF1             JA4A                Battery for separate absolute
                                                                                               position detectors connected to
                      Flat cable                                                               additional unit
                                                          CNF2             JF105
                                                                                                 Digital output encoder 1 axis
                                                                           JF106                 Digital output encoder 2 axes
                                                                           JF107
                                                                                                 Digital output encoder 3 axes
                                                                           JF108                 Digital output encoder 4 axes
                                                                   - 102 -
B-64303EN/03                                                                                                                  7.SERVO INTERFACE
   (4) Connecting 1-Vp-p output encoders to the 1st to 4th axes and digital output encoders to the 5th to
       8th axes
                                          Optical fiber cable
                                                                                 JF111
                                                                COP10B                                  1Vp-p output encoder 1 axis
                            Optical fiber cable
                                                                                 JF112
                                                                COP10A                                  1Vp-p output encoder 2 axes
                            24VDC                                                JF113
                                                                CP11A                                   1Vp-p output encoder 3 axes
                                                                                 JF114                  1Vp-p output encoder 4 axes
                                                                CNF1              JA4A
                                                                                 JF101
                                                                COP10B                                  Digital output encoder 1 axis
                                                                                 JF102
                                                                COP10A                                  Digital output encoder 2 axes
                            24VDC                                                JF103
                                                                CP11A                                   Digital output encoder 3 axes
                                                                                 JF104                  Digital output encoder 4 axes
                                                                CNF1              JA4A                  Battery for separate absolute
                                                                                                        detector
                            Flat cable
                                                        Separate detector interface unit (additional unit)
                                                                CNF2             JF105
                                                                                                     Digital output encoder 5 axes
                                                                                 JF106
                                                                                                     Digital output encoder 6 axes
                                                                                 JF107
                                                                                                     Digital output encoder 7 axes
                                                                                 JF108               Digital output encoder 8 axes
                                                                         - 103 -
7.SERVO INTERFACE                                                                                         B-64303EN/03
                         CP11A
                          1    +24V                                          24 VDC regulated power
                          2      0V                                          supply
                          3                                                  24 VDC ±10%
GND
Cable
                      CP11A
                     AMP JAPAN
                     1-178288-3 (Housing)
                     1-175218-5 (Contact)                                   External power supply
 The 24 VDC input to CP11A can be output at CP11B for use in branching. The connection of CP11B is
 identical to that of CP11A. In this case, the power supplied to CP11A should be equal to the sum of the
 rating of the analog input separate detector interface unit and that of the units after CP11B.
 Be sure to ground the 0-V line of the power supply to the analog input separate detector interface unit.
 In addition, keep any noise source (such as an AC power cable and contactor) away from the power line
 of the analog input separate detector interface unit as far as possible to prevent noise from being picked
 up through the power line.
 Secure the ground line to the ground terminal (GND) for signals of an analog input separate detector
 interface unit, which is located at the bottom of the unit, with an M3 screw as shown in the figure below.
 Connect the ground line to the ground plate of the cabinet.
                                                        - 104 -
B-64303EN/03                                                       7.SERVO INTERFACE
GND
     NOTE
       The torque with which a screw is tightened is 5 kgf⋅cm or less.
                                                - 105 -
7.SERVO INTERFACE                                                                                    B-64303EN/03
                  JF111 to F114
                   (PCR-EV20MDT)
                   1     PCA    11   NC
                   2     *PCA 12     0V
                   3     PCB    13   NC
                   4     *PCB   14   0V
                   5     PCZ    15   NC
                   6     *PCZ   16   0V
                   7            17              Leave NC (No Connection) open.
                   8            18   +5V
                   9     +5V    19   NC
                  10            20   +5V
Cable connection
                        PCA     1
                                                                                    PCA
                       *PCA
                                2
                                                                                    *PCA
                        PCB
                                3
                                                                                    PCB
                   *PCB         4
                                                                                    *PCB
                        PCZ     5
                                                                                    PCZ
                                6
                   *PCZ                                                             *PCZ
                        +5V
                                9
                                                                                    +5V
                                18
                        +5V                                                         +5V
                                20                                                  +5V
                        +5V
                                12
                         0V                                                         0V
                                14
                         0V                                                         0V
                                16                Shielded drain wire
                         0V                                                         FG
                                                                                    (Frame ground)
                                                          Shield
                                           Ground plate
               Recommended cable:
               A66L-0001-0286 (#20AWG × 6 + #24AWG × 3-pair)
               Recommended connectors:
               PCR-E20FA (Honda Tsushin Kogyo)
               FI30-20S (Hirose Electric)
               FCN-247J020-G/E (Fujitsu)
               52622-2011 (Molex)
               FI40B-2015S (Hirose Electric)
   NOTE
     When supplementary descriptions other than warnings and notes are provided,
     the above +5V signals can be used as the power supply of detectors.
     In this case, the maximum current consumption per detector is 0.35 A.
     Lower limit of the 5V signals: 4.95 V for the basic unit, and 4.9 V for the
     additional unit
                                                     - 106 -
B-64303EN/03                                                                                 7.SERVO INTERFACE
                  VB
                                                         a/2
                                                                                      TZ LZ
        VXA VXB
                                                                          Z
                         VA
                                                         a/2
                                                                                                       c/2    Effective
                                                                                                              component c
                                                     VOA,VOB
                                                                                                VOZ    c/2
         0V
                   VB
                         VA                              b/2
                        VXA                              b/2
                  VXB
                                                     VOA,VOXA
         0V                                          VOB,VOXB
* The detection precision depends on the precision of signals from the encoder.
                                                       - 107 -
7.SERVO INTERFACE                                                                               B-64303EN/03
                        Cable connection
                                JA4A                            Battery case
                                   7                                 +
                          +6V                                             +6V
                                   3                                 -
                           0V                                             0V
                        Recommended connectors:
                        PCR-E20FA (Honda Tsushin Kogyo)
                        FI30-20S (Hirose Electric)
                        FCN-247J020-G/E (Fujitsu)
                        52622-2011 (Molex)
   NOTE
     If the cable is connected to JA4A when the separate absolute pulse coder
     battery case contains the battery, the battery voltage is applied to the battery
     power supply pin (+6 V) for each of the feedback connectors (JF105 to JF108).
     In this case, if the battery line and 0 V are short-circuited, the battery may heat
     up or the protection circuit within the separate detector interface unit may fail.
     First, make sure the battery case contains no battery or the cable is not
     connected to JA4A. Then, complete all cabling work and confirm cables are
     correctly connected. Finally, place the battery or connect the cable to JA4A.
                                                     - 108 -
B-64303EN/03                                                                             7.SERVO INTERFACE
CNF1 CNF2
Marking
                                                                                         mark
                                                             mark
Place an order on a flat cable together with separate detector interface units.
GND
                                                         - 109 -
7.SERVO INTERFACE                                                                              B-64303EN/03
7.3.9        Installation
 1)   Notes on installation
      (1) Use an interface unit in a completely enclosed cabinet.
      (2) Install an interface unit on a vertical surface, and provide a space of 100 mm above and below
          the unit. Below an interface unit, do not place equipment that generates a large amount of
          heat.
      (3) When using an analog input separate detector interface unit and addition unit, place the units as
          shown below so that the flat cable connecting the units does not block the vent holes. A flat
          cable not longer than 100 mm must be used.
                                  Vent holes     Flat cable
 When using both an analog input separate detector interface unit and additional unit, install the units as
 shown above, with the mounting holes horizontally separated by 70 to 80 mm.
                                                       - 110 -
B-64303EN/03                                                                               7.SERVO INTERFACE
                                                      - 111 -
7.SERVO INTERFACE                                                                   B-64303EN/03
DIN rail
DIN rail
        CAUTION
       When removing the unit, be careful not to damage the lock by applying
       excessive force. When installing and removing the unit, hold the upper and
       lower ends of the unit so that stress is not applied to the side (that surface with
       the slits) of the unit.
                                                 - 112 -
B-64303EN/03                                                             8.CONNECTION TO FANUC I/O Link
8.1            OVERVIEW
   FANUC I/O Link is a serial interface that has a CNC, a cell controller, various I/O units, the machine
   operator's panel, or the Power Mate connected and receives or sends I/O signals (bit data) at high speed
   between the devices. The FANUC I/O Link regards one device as the master and other devices as slaves
   when more than one device is connected. Input signals from the slaves are sent to the master at specified
   intervals. Output signals from the master are also sent to the slaves at specified intervals.
8.2            CONNECTION
   The I/O Link interface connector JD51A is provided on the main board.
   In the I/O there are the master station and its slave stations. The master is the control unit of the CNC,
   and the slave is the I/O unit-A. The slaves are divided into groups, and up to 16 groups can be
   connected to one I/O Link. (For the Series 0i Mate, however, the number of I/O points are limited.)
   The I/O Link is connected in different ways depending on the types of units actually used and the I/O
   points. To connect the I/O Link, the assignment and addresses of the I/O signals have been made
   programmable with the PMC program. The total number of I/O points for each channel of I/O Link is
   1024 or less.
   There are two I/O Link connectors: JD1A and JD1B. These connectors are provided for all units that have
   the I/O Link function. A cable must be connected from JD1A to JD1B. Although JD1A of the last unit
   is not used and left open, it need not be connected with a terminator.
   The pin assignments of connectors JD1A and JD1B are common to all units on the I/O Link, and are
   illustrated on Subsec. 8.2.1. Use the figures when connecting the I/O Link irrespective of the type of
   unit.
                        Control unit                          I/O256/256 or less per group
                        JD51A
                                         FANUC I/O Link       I/O1024/1024 or less per channel
                                              JD1B
                                              JD1A
                                                                                                 circuit
                                                                                                 Magnetic
                           Max.
                           16 group           JD1B
                                              JD1A
                                              JD1B
                                              JD1A
                                                                                         Machine operator’s
                                                                                               panel
                                                                                         (See Section 9.9.)
                                                       Rear of unit
  The following example assumes that two operator's panel I/Os and one machine operator's panel are used.
                            DI space map                                         DO space map
           X4               Operator’s panel I/O                           Y0     Operator’s panel I/O
           X5               48 DI points                                   Y1     32 DO points
            :                                                              Y2
           X9                                                              Y3
           X10              Reserved                                       Y4     Operator’s panel I/O
            :               Reserved                                       Y5     32 DO points
           X15              Reserved                                       Y6
           X16              1st MPG                                        Y7
           X17              2nd MPG                                        Y8     Machine operator’s panel
           X18              3rd MPG                                        Y9
           X19              DO alarm detection                             Y10
           X20              Operator’s panel I/O                           Y11
           X21              48 DI points                                   Y12
            :                                                              Y13
           X25                                                             Y14
           X26              Reserved                                       Y15
            :               Reserved
            :               Reserved
           X34              Reserved
           X35              DO alarm detection
           X36              Machine operator’s panel
            :
           X47
    NOTE
    1 The manual pulse generators in X16 to X18 are directly read by the CNC, so
      only the above allocation must be performed by the PMC.
    2 For DO alarm detection in X19 and X35, see Subsection 9.4.9.
    3 For the Series 0i Mate, up to 256 DI points and up to 256 Do points can be used.
                                                                 - 114 -
B-64303EN/03                                                   8.CONNECTION TO FANUC I/O Link
Rear of unit
                                                                            Machine operator’s
                                                                                  panel
                                                                            (See Section 9.9.)
                                               - 115 -
8.CONNECTION TO FANUC I/O Link                                                                    B-64303EN/03
    NOTE
    1 The manual pulse generators in X12 to X14 are directly read by the CNC, so
      only the above allocation must be performed by the PMC.
    2 For DO alarm detection in X15, see Section 9.6.
  +5 V terminals are for an optical I/O Link adapter. They are not necessary when connecting with a
  metal cable.
  A line for the +5V terminal is not required when the Optical I/O Link Adapter is not used.
  No connections must be made to the pins with brackets ([ ]) because they are used in JD51A when the
  second channels are connected in the FANUC I/O Link.
  Do not make a connection to a pin for which no signal is assigned.
                                                    - 116 -
B-64303EN/03                                                   8.CONNECTION TO FANUC I/O Link
   •    When there is concern that the cable is influenced by strong noise; for example :When there is a
        strong electromagnetic noise source beside the cable such as a welding machine.
        When a noise generating cable such as a power cable runs for a long distance in parallel with the
        cable.
                                                   - 117 -
8.CONNECTION TO FANUC I/O Link                                       B-64303EN/03
- Connection
- Connection diagram
                                              - 118 -
B-64303EN/03                                                                 8.CONNECTION TO FANUC I/O Link
   -    Optical cable
       NOTE
         For handling of optical cables, see Appendix D.
       NOTE
         It is impossible to use both high-speed and standard type adapters on the same
         line.
   •     Power supply
         The same power supply type can be used for both the standard type (A13B-0154-B001) and
         high-speed type (A13B-0154-B004).
         (a) Power supply voltage: 4.75 to 5.25 V (at receiving end)
         (b) Required current: 200 mA
   •     Installation conditions
         (a) The optical link adapter enclosure is not fully sealed ; install it with the CNC control unit in the
              fully enclosed cabinet.
         (b) Ground the case using the case fixing screw of the optical link adapter.
         (c) The optical link adapter is light, and it may not be necessary to mount it with screws.
              However, keep it from coming in contact with other circuits to prevent possible short-circuits.
              When mounting the optical link adapter in a cabinet, attach it with an L-type fitting using the
              case fixing screws (M3) of the optical link adapter.
   •     Required parts
         (a) For making up an I/O Link using the optical link adapter, the following parts are necessary:
              <1> Optical I/O Link adapter............................................................................ 2
              <2> Interunit connecting cable.......................................................................... 2
              <3> Optical cable .............................................................................................. 1
   •     Relay with an optical fiber relay adapter
         For the outline drawing of the optical fiber relay adapter, see Appendix D.
                                                              - 119 -
8.CONNECTION TO FANUC I/O Link                                                                                      B-64303EN/03
      NOTE
        Optical fiber cables can be relayed only at are location.
        When a high-speed optical link adapter is used, no optical fiber relay adapter can
        be used.
      NOTE
        When Dual Check Safety is used in the Series 0i, up to three channels of
        FANUC I/O Link interfaces can be used. However, the third channel can be
        used only for connection of safety-related I/Os in Dual Check Safety. For
        connection when using Dual Check Safety, refer to the FANUC Series
        0i-MODEL D Dual Check Safety Connection Manual (B-64303EN-4).
Connection
                    CNC                            I/O Link branching adapter
                           JD51A                   JD44B
                                                                                         FANUC I/O Link channel 1
                                                                   JD1A-1
Connection after the I/O Link branching adapter is the same as that for the FANUC I/O Link.
                                                         - 120 -
B-64303EN/03                                                8.CONNECTION TO FANUC I/O Link
   The +5V pin is provided to use the optical I/O Link adapter for optical fiber transmission. When not
   using the optical I/O Link adapter, leave the +5V pin unconnected.
Cabling
Connection between the I/O Link branching adapter and slave I/O devices
   The I/O Link branching adapter can be connected to slave I/O devices in the same way as for the
   conventional FANUC I/O Link. See 8.2.1.
                                                - 121 -
8.CONNECTION TO FANUC I/O Link                                                                            B-64303EN/03
Cable length
                    CNC                       I/O Link branching adapter                  I/O device
                                      lA
                           JD44A              JD44B
                                                                               lB
                                                              JD1A-1                      JD1B
JD1A-2
  The total of lA and lB must not exceed 10 m; where lA is the length of the cable between connector JD44A
  on the CNC and connector JD44B on the I/O Link branching adapter, and lB is the length of the cable
  between connector JD1A-1 or JD1A-2 on the I/O Link branching adapter and connector JD1B on the I/O
  unit. When all cables are accommodated in the same cabinet, however, a total cable length of up to 15
  m is allowed.
                                                      34
                                                 23
                                                                                                                  45
                                                                                         85
                                                                                                            Unit : mm
Allow a clearance of about 10 cm above the adapter for connection and routing of cables.
25
Unit: mm
                                                   - 122 -
B-64303EN/03                                                     8.CONNECTION TO FANUC I/O Link
   2)   Screwing
11.6
                                        2-M4
                                                         70            Unit: mm
                                                    - 123 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                        B-64303EN/03
9.2.1 Configuration
                                                                                                                               Direction to be
                                                                                                                               used when the
               Direction to be used when                                                                                       modules are
               the modules are                                                                                                 mounted using
               connected directly to the                                                                                       DIN rails or
               connection printed circuit                                                                                      screws
               board
                                                                                                                   Expansion module 3
                                               JD1A
                                                                     JD1B                            Expansion module 2
                                                                         Basic module
                              I/O Link cable
     NOTE
       For direction connection to the connection printed circuit board, expansion
       modules are installed to the right of the basic module on the installation plane.
       For installation using DIN rails or screws, expansion modules are installed to the
       left of the basic module on the installation plane.
                                                                          - 125 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                         B-64303EN/03
JD51A
   NOTE
   1 Ensure that the expansion module with the MPG interface is located nearest to
     the basic module, as shown in the figure. When this module is used with other
     units (such as I/O modules for the operator's panel) that are connected to the I/O
     Link and have the MPG interface, only the MPG interface of the unit (module)
     that is on the I/O Link and is nearest to the CNC is enabled.
   2 The connection diagram above shows an example of using a DI/DO module, 2A
     output module, and analog input module as expansion modules. These
     expansion modules can be used in any combination.
                                         - 126 -
B-64303EN/03                                           9.CONNECTION OF I/O Link SLAVE DEVICES
   For the specifications (such as signal input requirements) specific to each module, see the relevant pages
   of each item.
Installation conditions
   Ambient temperature for the     Operation: 0°C to 55°C
   unit                            Storage and transportation: -20°C to 60°C
   Temperature change              1.1°C/minute maximum
   Humidity                        Normal condition: 75% (relative humidity)
                                   Short term (within one month): 95% (relative humidity)
   Vibration                       Operation: 0.5 G or less
   Atmosphere                      Normal machining factory environment (For use in an environment with relatively
                                   high levels of dust, coolant, organic solutions, and so forth, additional measures
                                   are required.)
                                                       - 127 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                                                                       B-64303EN/03
  Other conditions              (1) Use each I/O module in a completely sealed cabinet.
                                (2) For ventilation within each I/O module, each module must be installed in the
                                    orientation shown below.
                                    Moreover, for ventilation and wiring, allow a clearance of 100 mm or more
                                    above and below each module. Never place a device that generates a large
                                    amount of heat below an I/O module.
                                (3) While referring to Subsection 9.2.7, ensure that the vent hole of the basic
                                    module is not obstructed by the flat cable.
                                                                                                                        Upper side
Expansion module 1
Expansion module 2
                                                                                                                           Expansion module 3
                                                           Expansion module
                                I/O Link connection
                                                                                                                        Lower side
                                     MPG connection
As a guideline for the heat dissipation, assume [power supply capacity × 24 (W)].
                                                      - 128 -
B-64303EN/03                                     9.CONNECTION OF I/O Link SLAVE DEVICES
     NOTE
     1 The DI and DO addresses for the basic and expansion modules run
       contiguously. These basic and expansion module DI and DO addresses are
       allocated to the I/O Link as a group. For example, when the DI and DO top
       addresses are X0004 and Y0000 (m = 4 and n = 0), respectively, then the
       addresses are allocated as shown in the following table.
     2 Pins 18 and 50 (+24V) of connector CB150 are used to apply 24 V externally to
       a module. Be sure to connect these pins because the +24 V applied to the
       module is used internally.
                                                      DI                              DO
   Basic module                                   X4 to X6                          Y0 to Y1
   Expansion module 1                             X7 to X9                          Y2 to Y3
   Expansion module 2                            X10 to X12                         Y4 to Y5
   Expansion module 3                            X13 to X15                         Y6 to Y7
                                                 - 129 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                         B-64303EN/03
  •   A maximum of 96 points are provided (24 points per module; 1 basic module + 3 expansion
      modules).
                                                           Pin No.
                          Address No.
                          Bit No.
                                               - 130 -
B-64303EN/03                              9.CONNECTION OF I/O Link SLAVE DEVICES
Pin No.
                         Address No.
                         Bit No.
     NOTE
       Xm+0.0 through Xm+0.7 are DI pins for which a common voltage can be
       selected. That is, by connecting the DICOM0 CB150(24) pin to the +24 V power
       supply, a DI signal can be input with its logical state reversed. If, however, a
       cable is connected to ground, it has the same effect as inputting an ON state DI
       signal. To prevent such accidents, the connection of the DICOM0 CB150(24) pin
       to the 0 V power supply is recommended whereever possible.
       For safety reasons, the emergency stop signal needs to be allocated to an
       appropriate bit of the addresses for which the common voltage is fixed, ranging
       from Xm+1.0 to Xm+1.7 or from Xm+2.0 to Xm+2.7. See Subsection 8.4.19 for
       information about how to allocate the emergency stop signal.
       For unused DI pins allocated to the addresses for which the common voltage is
       fixed (fromXm+1.0 to Xm+1.7 and from Xm+2.0 to Xm+2.7), the logic is fixed to
       “0”. For unused pins allocated to Xm+0.0 to Xm+0.7 for which the common
       voltage can be selected, the logic is fixed to “0” when the DICOM0 CB150(24)
       pin is connected to the 0 V power supply. When the DICOM0 CB150(24) pin is
       connected to the +24 V power supply, the logic is fixed to “1”. The logic of the
       unused pins allocated to Xm+0.0 to Xm+0.7 is variable when the contact of the
       DICOM0 CB150(24) pin is open.
                                          - 131 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                     B-64303EN/03
  •   A maximum of 64 points are provided (16 points per module; 1 basic module + 3 expansion
      modules).
Pin No.
                                      Address No.
                                      Bit No.
Relay
                                                    - 132 -
B-64303EN/03                                            9.CONNECTION OF I/O Link SLAVE DEVICES
   ON/OFF of the power supply (DO common) for DO signals (output signals)
   By turning off (opening) the power supply pin (DOCOM) for the DO signals (output signals), all the DO
   signals of each module can be turned off at the same time. At this time, the DO state is as shown below.
                                           ON
                              DOCOM
                                           OFF
                      DO state when DO is ON
                      on in the sequence  OFF
                      DO state when DO is ON
                      off in the sequence OFF
     NOTE
       When DO is on in the sequence, the ON/OFF state of DOCOM is directly
       reflected in the DO state as indicated above by the dashed box. The +24 V
       signal to be supplied to the I/O module must not be turned off during operation.
       Otherwise, a CNC communication alarm is issued. Ensure that +24 V is supplied
       either when or before the power to the CNC is turned on, and that +24 V is
       removed either when or after the power to the CNC is turned off.
                                                       - 133 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                          B-64303EN/03
                                                  DOCOM
                                                            CB150(01),(33)
                                                                  +24V        0V
                                                                   +24 V regulated
                                                                   power supply
                                                                             Relay
                                             DV
DV
    NOTE
    1 The DI/DO addresses of an expansion module and the DI/DO addresses of the
      basic module are contiguous.
      Addresses allocated to I/O Link are handled as a group covering the basic and
      expansion modules. That is, when the first addresses allocated are X0004 and
      Y0000 (m = 4, n = 0), the DI/DO addresses are as listed below.
    2 When the 2A output module is used, the DI addresses of the module cannot be
      used. (When the 2A output module is used as expansion module 3, X13 through
      X15 cannot be used.)
                                                       DI                                DO
             Basic module                          X4 to X6                          Y0 to Y1
            Basic module 1                         X7 to X9                          Y2 to Y3
                                                  - 134 -
B-64303EN/03                                     9.CONNECTION OF I/O Link SLAVE DEVICES
                                                      DI                                 DO
               Basic module 2                     X10 to X12                           Y4 to Y5
               Basic module 3                     X13 to X15                           Y6 to Y7
                                Address No.
                                Bit No.
                                                                          Solenoid,
                                                                          etc.
                                                 - 135 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                B-64303EN/03
  ON/OFF of the power supply (DO common) for DO signals (output signals)
  By turning off (opening) the power supply pin (DOCOM) for the DO signals (output signals), all the DO
  signals of each module can be turned off at one time. At this time, the DO state is as shown below.
                                         ON
                             DOCOM
                                         OFF
                      DO state when DO is ON
                      on in the sequence  OFF
                      DO state when DO is ON
                      off in the sequence OFF
    NOTE
      When DO is on in the sequence, the ON/OFF state of DOCOM is directly
      reflected in the DO state as indicated above by the dashed box. The +24 V
      signal to be supplied to the I/O module must not be turned off during operation.
      Otherwise, a CNC communication alarm is issued. Ensure that +24 V is supplied
      either when or before the power to the CNC is turned on, and that +24 V is
      removed either when or after the power to the CNC is turned off.
                                                     - 136 -
B-64303EN/03                                       9.CONNECTION OF I/O Link SLAVE DEVICES
     NOTE
     1 The DI/DO addresses of an expansion module and the DI/DO addresses of the
       basic module are contiguous.
       Addresses allocated to I/O Link are handled as a group covering the basic and
       expansion modules. That is, when the first addresses allocated are X0004 and
       Y0000 (m = 4, n = 0), the DI/DO addresses are as listed below.
     2 With the analog input module, the DO space is also used as an input channel
       selection area.
                                                       DI                                DO
   Basic module                                     X4 to X6                           Y0 to Y1
   Basic module 1                                   X7 to X9                           Y2 to Y3
   Basic module 2                                  X10 to X12                          Y4 to Y5
   Basic module 3                                  X13 to X15                          Y6 to Y7
                                                  - 137 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                       B-64303EN/03
Pin number
                                                Not connected
                      For voltage input
           Voltage
           source
            Current
            source¹
    NOTE
    1 In the diagram above, n represents each channel (n = 1, 2, 3, 4).
    2 Current input or voltage input can be selected on a channel–by–channel basis.
      For current input, connect JMPn to INPn.
    3 For the connection, use a shielded twisted pair.
    4 In the diagram above, the shield of each channel is connected to FGNDn, and
      FGND is used for shield processing of all channels. However, the shield of a
      channel may be directly connected to frame ground with a cable clamp, instead
      of using FGNDn.
    5 If the voltage (current) source has a GND pin, as shown in the figure above,
      connect COMn to this pin. Otherwise, connect INMn and COMn together in the
      analog input module.
                                                      - 138 -
B-64303EN/03                                             9.CONNECTION OF I/O Link SLAVE DEVICES
   Resolution                      5 mV or 20 µA
   Overall precision               Voltage input: ±0.5%                         With respect to full scale
                                   Current input: ±1%
   Maximum input voltage/current   ±15V/±30mA
   Minimum conversion time (Note) Ladder scan period of CNC connected
   Number of occupied input/output DI = 3 bytes, DO = 2 bytes
   points (Note)
     NOTE
       This analog input module has four input channels. The digital output section
       consists of a group of 12 bits within the three–byte occupied input points. This
       means that the channel to be used can be dynamically selected by the ladder.
       The channel switching DO point for channel selection is included in the two–byte
       occupied output points.
   D00 to D11 represent 12–bit digital output data. D00 and D11 correspond to weightings of 20 and 211,
   respectively.
   D11 is a sign bit expressed as a two’s complement. CHA and CHB represent analog input channels.
   This means that when the two bytes above are read with a PMC program, the A–D converted data of the
   CHA and CHB input channels can be read from D11 to D00. For CHA and CHB, see the description of
   channel selection, below.
   When data is read with a PMC program, some notes need to be observed. See "(Address allocation)" on
   the next page.
                                                         - 139 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                      B-64303EN/03
  (Channel selection)
  With this analog input module, which of the four channels is to be output to the digital output section
  must be determined with a PMC program.
  The DO points used for this selection are CHA and CHB (two–byte occupied output points). These are
  mapped as indicated below.
       Address in the module      7           6            5            4         3         2          1          0
                           Yn     X           X            X            X         X         X          X          X
                         Yn+1     X           X            X            X         X         X         CHB        CHA
  By writing the values indicated below to CHA and CHB, the corresponding channel is selected, and the
  A–D converted data of the channel and the data of the selected channel can be read as DI data. The
  character X indicated above represents an unused bit, so that either 1 or 0 may be written in place of X.
                  CHB                                  CHA                                 Channel selected
                    0                                      0                                    Channel 1
                    0                                      1                                    Channel 2
                    1                                      0                                    Channel 3
                    1                                      1                                    Channel 4
  Immediately after channel switching, some time is required until the channel is switched to the selected
  one and A-D converted data is enabled. Be sure to confirm the channel before obtaining A-D converted
  data.
  (Address allocation)
  The start address of X (DI) of the basic modules including the analog input module must always be
  allocated at an even–numbered address. With this allocation, the digital output addresses of the analog
  input module are as described below, depending on where the analog input module is allocated
  •     When the analog input module is allocated in the space for expansion module 1 (m represents the
        allocation start address.)
          Address in the module          7         6            5            4        3         2           1      0
         Xm+3(odd–numbered address)                                          Undefined
        Xm+4(even–numbered address)     D07       D06          D05          D04      D03     D02        D01       D00
         Xm+5(odd–numbered address)      0         0           CHB          CHA      D11     D10        D09       D08
  •     When the analog input module is allocated in the space for expansion module 2 (m represents the
        allocation start address.)
          Address in the module          7         6            5            4        3       2          1         0
        Xm+6(even–numbered address)     D07       D06          D05          D04      D03     D02        D01       D00
         Xm+7(odd–numbered address)      0         0           CHB          CHA      D11     D10        D09       D08
        Xm+8(even–numbered address)                                          Undefined
  •     When the analog input module is allocated in the space for expansion module 3 (m represents the
        allocation start address.)
           Address in the module             7         6            5        4        3          2          1      0
           Xm+9(odd–numbered address)                                        Undefined
         Xm+10(even–numbered address)    D07       D06         D05          D04      D03        D02     D01       D00
          Xm+11(odd–numbered address)     0         0          CHB          CHA      D11        D10     D09       D08
      NOTE
        When two–byte digital output addresses are to be referenced with a PMC
        program, a read must always be performed word–by–word (16 bits).
                                                  - 140 -
B-64303EN/03                                   9.CONNECTION OF I/O Link SLAVE DEVICES
     NOTE
       The number of connectable manual pulse generators depends on the type and
       option configuration.
                                               - 141 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                             B-64303EN/03
            m
    L≤
            R
  Therefore, the cable length can be determined using the following expression.
  In the case of the A66L–0001–0286 cable, for example, when three pairs of signal wires and six power
  supply wires (20/0.18, 0.0394 Ω/m) are used (three power supply wires connected to 5 V and the other
  three to 0 V), the cable length is:
               3
    L≤                 =76.75[m]
            0.0394
  However, the maximum pulse transmission distance for the manual pulse generator is 50 m. Taking this
  into consideration, the cable length may be extended to:
  38.37 m (when two generators are used), or
  25.58 m (when three generators are used).
                                                        - 142 -
B-64303EN/03                               9.CONNECTION OF I/O Link SLAVE DEVICES
     NOTE
       Modules need to be spaced at least 32 mm apart, in which case a flat cable of
       about 20 mm in length is required. To install modules further away from each
       other, the cable length will be 20 mm plus the extra distance. Note that the
       maximum length of a flat cable is 300 mm. To ensure adequate ventilation,
       install the modules in such a way that the flat cables lie on top of them. The
       basic module has a vent at the top (as indicated by the dotted lines in the above
       figure). When connecting modules, install expansion modules so that the flat
       cables do not cover the vent, as shown in the above figure.
       Therefore, for direct connection to the connection printed circuit board,
       expansion modules are installed to the right of the basic module on the
       installation plane. For installation using DIN rails or screws, expansion modules
       are installed to the left of the basic module on the installation plane.
                                           - 143 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                             B-64303EN/03
                                No.1 pin
                      Note)
Square hole
                                                                                              I/O Link
                                                                                              interface
                                                          I/O interface
                                                                                        MPG interface
                                                                                        (for expansion module)
                                                                          JD1A   JD1B
      Connector panel printed circuit board connector specification:
      HONDA MRH–50FD (50–pin female straight connector without fitting)
    NOTE
    1 A connector with a fitting (HONDA MRH–50RMA) is used for the module–side
      I/O interface.
      Always use a connector having no fitting for the connector panel printed circuit
      board.
    2 Area where pattern printing is prohibited
               : Prohibited area on component side
               : Prohibited area on soldered side
                                                          - 144 -
B-64303EN/03                                                    9.CONNECTION OF I/O Link SLAVE DEVICES
   When connecting a connector panel printed circuit board directly (mounting and dismounting a module)
Hook
                            Stopper
    Connector panel
    printed circuit
    board
     NOTE
       When mounting and dismounting a module, hold the module by its top and
       bottom surfaces.
       Avoid applying force to the sides where there are slits.
                                                               - 145 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                        B-64303EN/03
When mounting a DIN rail (external module view and mounting diagram)
I/O interface
                                                                         MPG interface
                                                                         (for expansion module)
    NOTE
      Recommended connector:
         A02B–0098–K891 (including the following connector and case)
         (Connector: HONDA MR–50FH solder type)
         (Case: HONDA MR–50NSB angled type)
      Recommended wire material:
         A66L–0001–0042 (7/0.18, 50 pins)
                                              - 146 -
B-64303EN/03                                                         9.CONNECTION OF I/O Link SLAVE DEVICES
   When mounting a DIN rail (mounting and dismounting a module)
Hook
DIN rail
Stopper
     NOTE
       When dismounting the module, take care not to damage the stopper by applying
       excessive force with the screwdriver.
       When mounting and dismounting a module, hold the module by its top and
       bottom surfaces.
       Avoid applying force to the sides where there are slits.
                                                                     - 147 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                             B-64303EN/03
When mounting a module using screws (external module view and mounting diagram)
                                                                                                     Screw
                                                                                                     holes
I/O interface
                                                                          MPG interface
                                                                          (for expansion module)
JD1A JD1B
    NOTE
      Recommended connector:
         A02B–0098–K891 (including the following connector and case)
         (Connector: HONDA MR–50FH solder type)
         (Case: HONDA MR–50NSB angled type)
      Recommended wire material:
          A66L–0001–0042 (7/0.18, 50 pins)
                                                 - 148 -
B-64303EN/03                                          9.CONNECTION OF I/O Link SLAVE DEVICES
Address allocation
   For the connector panel I/O module, I/O addresses are mapped as follows.
                               DI space map                      DO space map
                       Xm                                       Yn
                                              Basic module                       Basic module
                       Xm+1                                     Yn+1
                       Xm+2                                     Yn+2            Expansion
                       Xm+3                                     Yn+3            module 1
                                              Expansion
                       Xm+4                                     Yn+4            Expansion
                                              module 1
                                                                Yn+5            module 2
                       Xm+5
                       Xm+6                                     Yn+6            Expansion
                                              Expansion                         module 3
                       Xm+7                   module 2          Yn+7
                       Xm+8
                       Xm+9
                                              Expansion
                       Xm+10                  module 3
                       Xm+11
                       Xm+12(for 1st MPG)
                                              Expansion
                       Xm+13(for 2nd MPG)     module 1
                       Xm+14(for 3rd MPG)
                       Xm+15(DO alarm         Basic module
                       detection)
   The basic connector panel I/O module is allocated a group of DI addresses (16 bytes) and a group of DO
   addresses (8 bytes). Up to three hardware expansion modules can be added or removed as required.
   The reason for this address allocation is explained below.
   The MPG interface (MPG counter) occupies a DI space from Xm+12 through Xm+14. These addresses
   are fixed regardless of whether expansion module 2 or 3 is used, and Xm+12 through Xm+14 must be
   allocated as a DI work area to enable the use of the MPG. Therefore, when using an MPG for the i
   series CNC, allocate DI addresses in units of 16 bytes. Do not use the DI space from Xm+12 through
   Xm+14 for Ladder; the CNC processes the MPG counter value directly.
   DI address Xm+15 is used for detecting overcurrent and overheating alarms that occur in the IC used in
   the DO driver. [For details, see the section describing the detection of DO (output signal) alarms.]
   This address is fixed regardless of whether expansion module 2 or 3 is used, and it must be allocated as a
   work area before it can be used. When using this area, therefore, allocate DI addresses in units of 16
   bytes.
   Basically, I/O addresses can be allocated to the connector panel I/O modules freely. When allocating DI
   addresses, however, consider also the addresses that are directly supervised by the CNC, and keep the
   following in mind.
                                                     - 149 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                         B-64303EN/03
                                                         - 150 -
B-64303EN/03                                                                                                                            9.CONNECTION OF I/O Link SLAVE DEVICES
     NOTE
       This function is not supported by the 2A output module or analog input module.
Expansion module 2
Expansion module 3
Expansion module 1
Expansion module 2
Expansion module 3
Expansion module 1
Expansion module 2
                                                                                                                                                                                                                                                    Expansion module 3
               Basic module
Basic module
Basic module
                                                                                                                                        - 151 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                                                          B-64303EN/03
  Each setting position of the rotary switch has the following meaning:
     Setting
                 Actual indication                                                                                 Meaning of setting
     position
        0                  0                                 This is the standard setting. The rotary switch is factory-set to this position.
                                                             This setting is used when no expansion module is omitted.
        1                    -                               Set the rotary switch on an expansion module to this position when the
                                                             preceding expansion module is omitted.
        2                  2                                 Set the rotary switch on an expansion module to this position when the
                                                             preceding two expansion modules are omitted.
         3                -                                  This setting is prohibited.
      4 to F         4, -, 6, -,                             4, 8, or C has the same effect as 0.
                     8, -, A, -,                             5, 9, or D has the same effect as 1.
                     C, -, E, -,                             6, A, or E has the same effect as 2.
                                                             7, B, or F has the same effect as 3. (This setting, however, is prohibited.)
Expansion module 2
Expansion module 3
Expansion module 2
Expansion module 3
Expansion module 2
Expansion module 3
                                                                                                        omitted)
                                                                                                        On expansion module 3, set the rotary
                         Basic module
    NOTE
    1 Expansion module A (DI/DO = 24/16, with manual pulse interface)
      (A03B-0815-C002) is fitted with an additional rotary switch as other types of
      modules are modified. However, expansion module A is always mounted at the
      location of expansion module 1, so that its factory setting need not be changed.
    2 This setting is a function that was added newly.
      This function is not provided in the expansion models shipped in August 1998 or
      earlier.
                                                                                                       - 152 -
B-64303EN/03                                          9.CONNECTION OF I/O Link SLAVE DEVICES
JD51A
     NOTE
       When the operator's panel I/O module is used together with a unit (connector
       panel I/O module) connected to the I/O Link supporting another MPG interface,
       only the MPG interface of the unit (module) closest to the CNC connected to the
       I/O Link is enabled. The following screw type connectors cannot be used to
       connect the I/O Link or MPG.
                                                  - 153 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                      B-64303EN/03
                                                                               CPD1(IN)
                                                                                01   +24V
                     24 V power
                                                                                02     0V
                     supply
                                                                                03
                                                                              CPD1(OUT)
                                                                               01    +24V
                     24 V power
                     supply                                                    02     0V
                                                                               03
    NOTE
      The specification of the power supply connector CPD1 (IN) is the same as that
      for CPD1 (OUT). There are no indications on the printed circuit board to
      distinguish between the IN and OUT connectors. Do not turn off the +24 V
      supply to the connector during operation. Turning off the +24 V supply will
      cause a CNC communication alarm. When turning on the power, the +24 V
      supply to the I/O module must be turned on before or at the same time as the
      power supply to the CNC. When turning off the power, the +24 V supply to the
      I/O module must be turned off after or at the same time as the power supply to
      the CNC.
                                                       - 154 -
B-64303EN/03                                          9.CONNECTION OF I/O Link SLAVE DEVICES
                                      CE53                                       CE54
                                 A              B                            A               B
                      01       0V              0V                 01        0V              0V
                      02       N.C.           +24V                02       COM1           +24V
                      03     Xm+0.0          Xm+0.1               03      Xm+1.0         Xm+1.1
                      04     Xm+0.2          Xm+0.3               04      Xm+1.2         Xm+1.3
                      05     Xm+0.4          Xm+0.5               05      Xm+1.4         Xm+1.5
                      06     Xm+0.6          Xm+0.7               06      Xm+1.6         Xm+1.7
                      07     Yn+0.0          Yn+0.1               07      Yn+3.0         Yn+3.1
                      08     Yn+0.2          Yn+0.3               08      Yn+3.2         Yn+3.3
                      09     Yn+0.4          Yn+0.5               09      Yn+3.4         Yn+3.5
                      10     Yn+0.6          Yn+0.7               10      Yn+3.6         Yn+3.7
                      11     Yn+1.0          Yn+1.1               11      Yn+4.0         Yn+4.1
                      12     Yn+1.2          Yn+1.3               12      Yn+4.2         Yn+4.3
                      13     Yn+1.4          Yn+1.5               13      Yn+4.4         Yn+4.5
                      14     Yn+1.6          Yn+1.7               14      Yn+4.6         Yn+4.7
                      15     Yn+2.0          Yn+2.1               15      Yn+5.0         Yn+5.1
                      16     Yn+2.2          Yn+2.3               16      Yn+5.2         Yn+5.3
                      17     Yn+2.4          Yn+2.5               17      Yn+5.4         Yn+5.5
                      18     Yn+2.6          Yn+2.7               18      Yn+5.6         Yn+5.7
                      19       KYD0           KYD1                19      Yn+6.0         Yn+6.1
                      20       KYD2           KYD3                20      Yn+6.2         Yn+6.3
                      21       KYD4           KYD5                21      Yn+6.4         Yn+6.5
                      22       KYD6           KYD7                22      Yn+6.6         Yn+6.7
                      23       KCM1           KCM2                23       KCM5           KCM6
                      24       KCM3           KCM4                24       KCM7           DOCOM
                      25      DOCOM          DOCOM                25      DOCOM           DOCOM
     NOTE
       An output DC voltage of +24 V at CE53 (B02) and CE54 (B02) is for DI signals.
       Do not supply 24 VDC to these pins from the outside.
                                                      - 155 -
9.CONNECTION OF I/O Link SLAVE DEVICES                      B-64303EN/03
                          Address No.
                          Bit No.
                                        - 156 -
B-64303EN/03                                   9.CONNECTION OF I/O Link SLAVE DEVICES
     NOTE
     1 Xm+1.0 through Xm+1.7 are DI pins for which a common voltage can be
       selected. That is, by connecting the COM1 CE54(A02) pin to the +24 V power
       supply, a DI signal can be input with its logical state reversed. If, however, a
       cable is connected to ground, it has the same effect as inputting an ON state DI
       signal. To prevent this from occurring, the connection of the COM1 CE54(A02)
       pin to the 0 V power supply is recommended whereever possible.
       For safety reasons, the emergency stop signal needs to be allocated to an
       appropriate bit of the addresses for which the common voltage is fixed, ranging
       from Xm+0.0 to Xm+0.7. See "Address allocation" in Section 8.5.10 for details
       of how to allocate the emergency stop signal.
       For unused DI pins allocated to the addresses for which the common voltage is
       fixed (from Xm+0.0 to Xm+0.7), the logic is fixed to "0". For unused pins
       allocated to Xm+1.0 to Xm+1.7 for which the common voltage can be selected,
       the logic is fixed to "0" when the COM1 CE54(A02) pin is connected to the 0 V
       power supply. When the COM1 CE54(A02) pin is connected to the +24 V
       power supply, the logic is fixed to "1". The logic of the unused pins allocated to
       Xm+1.0 to Xm+1.7 is variable when the contact of the COM1 CE54(A02) pin is
       open.
     2 An output DC voltage of +24 V at CE53 (B02) and CE54 (B02) is for DI signals.
       Do not supply 24 VDC to these pins from the outside.
                                               - 157 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                       B-64303EN/03
   NOTE
   1 Detour prevention diodes must be incorporated for matrix signal input, as shown
     in the following figure. Otherwise, only two signals can be input at the same
     time. Inputting three or more signals simultaneously without using detour
     prevention diodes may result in data input errors.
   2 A cable for matrix input signals must be 150 mm or less in length.
*KCMn
*KYDn
                                        - 158 -
B-64303EN/03                                     9.CONNECTION OF I/O Link SLAVE DEVICES
Pin No.
                                       Address No.
                                       Bit No.
Relay
                                                - 159 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                            B-64303EN/03
Pin No.
                           Address No.
                           Bit No.
Relay
                                         - 160 -
B-64303EN/03                 9.CONNECTION OF I/O Link SLAVE DEVICES
Pin No.
               Address No.
               Bit No.
Relay
                             - 161 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                            B-64303EN/03
Pin No.
                           Address No.
                           Bit No.
Relay
                                         - 162 -
B-64303EN/03                                                    9.CONNECTION OF I/O Link SLAVE DEVICES
5-φ3.2
65
95 95
                                  Note) Lead wires and other components are mounted on the rear face of the printed
                           Note
                                        circuit board. Ensure that printed circuit boards are spaced 5 mm or more
                                        from one another to prevent interference.
               : Polarity guide
               : A1 pin mark
                                                                - 163 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                B-64303EN/03
9.3.9           Specifications
  Installation specifications
                                   During operation                       0°C to 58°C
  Ambient temperature
                                   During storage and transportation -20°C to 60°C
  Temperature change               Max.             1.1°C/min.
                                   Normal                         75% or less
  Relative humidity
                                   Short term (1 month or less) 95% or less
  Vibration                        During operation               0.5 G or less
                                   Ordinary machining factory environment (Special consideration is required when
  Environment                      installing the module in a dusty location or where highly concentrated cutting
                                   lubricant or organic solvent is used.)
  Other requirements               (1) Install the I/O module in a fully enclosed cabinet.
  Ordering specifications
               Item                     Specification                                Remarks
                                                                General-purpose DI: 16 points
                                                                Matrix DI: 56 points
  Operator's panel I/O module    A20B-2002-0470
                                                                DO: 56 points
                                                                MPG interface is supported.
  Fuse (replacement part)        A03B-0815-K001                 1A
  Module specifications
               Item                     Specification                                Remarks
  General-purpose DI             16 points                      24-V input
  Matrix DI                      56 points (8 × 7)              5-V input
  DO points                      56 points                      24 V source type output
                                                                Up to 16 modules can be connected as CNC slaves.
  CNC interface                  FANUC I/O Link connection      Or, amaximum of 1024 points can be supported on
                                                                both the input and output sides.
  MPG interface                  Max. 3 units
                                                     - 164 -
B-64303EN/03                                        9.CONNECTION OF I/O Link SLAVE DEVICES
        (Matrix input signal)
   Contact rating                    6 VDC, 2 mA or more
   Open circuit intercontact leakage
                                     0.2 mA or less (at 6 V)
   current
   Closed circuit intercontact
                                     0.9 V or less (with a current of 1 mA)
   voltage drop
                                     The maximum matrix period of 16 ms, the maximum time of I/O Link transfer
   Delay                             between CNC and I/O module of 2 ms, and the ladder scanning period (by
                                     CNC) must be considered.
     NOTE
       When detour prevention diodes are used, the voltage drop across closed
       contacts indicated above must be maintained, including the diode voltage drop.
     NOTE
       Ensure that the maximum current per DOCOM pin (DO power supply pin) does
       not exceed 0.7 A.
                                                   - 165 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                        B-64303EN/03
Address allocation
  For the operator's panel I/O module, I/O addresses are mapped as follows.
  The operator's panel I/O module is allocated a group of DI addresses (16 bytes) and a group of DO
  addresses (8 bytes). This address allocation is explained below.
  The MPG interface (MPG counter) occupies DI space from Xm+12 through Xm+14. These addresses
  are fixed, and Xm+12 through Xm+14 must be allocated as a DI work area to enable the use of the MPG.
  Therefore, when using an MPG for the i series CNC, allocate DI addresses in units of 16 bytes. Do not
  use the DI space from Xm+12 through Xm+14 for Ladder; the CNC processes the MPG counter value
  directly.
  DI address Xm+15 is used for detecting overcurrent and overheating alarms that may occur in the IC used
  in the DO driver. [For details, see the section describing the detection of DO (output signal) alarms.]
  This address is fixed, and must be allocated as a work area before it can be used. Therefore, when using
  this area, allocate DI addresses in units of 16 bytes.
  Basically, I/O addresses can be allocated to the operator's panel I/O module freely. When allocating DI
  addresses, however, consider also the fixed addresses that are directly supervised by the CNC, and keep
  the following in mind.
                                                            - 166 -
B-64303EN/03                                                   9.CONNECTION OF I/O Link SLAVE DEVICES
                         When DO is OFF in        ON
                         the sequence             OFF
     NOTE
       When the DO signal is in the ON state in the sequence, the ON or OFF state of
       the DOCOM pin determines the state of the signal, as indicated by the dotted
       lines in the above figure. Do not turn off the +24 V supply, provided by the
       CPD1 to the I/O module, during the operation. Turning off the +24 V supply
       would cause a CNC communication alarm. When turning on the power, the
       +24 V supply to the I/O module must be turned on before or at the same time as
       the power supply to the CNC. When turning off the power, the +24 V supply to
       the I/O module must be turned off after or at the same time as the power supply
       to the CNC.
                                                              - 167 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                             B-64303EN/03
                                                              CE53(A25), (B25)
                                                    DOCOM     CE54(B24), (A25), (B25)
                                                                     +24V         0V
                                                                    +24V stabilized
                                                                    power supply
                                                                                Relay
                                              DV
DV
                                                   - 168 -
B-64303EN/03                                          9.CONNECTION OF I/O Link SLAVE DEVICES
JD51A
     NOTE
       When the operator's panel I/O module is used together with a unit (connector
       panel I/O module) connected to the I/O Link supporting another MPG interface,
       only the MPG interface of the unit (module) closest to the CNC connected to the
       I/O Link is enabled. The following screw type connectors cannot be used to
       connect the I/O Link or MPG.
                                                  - 169 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                        B-64303EN/03
                                                                            CPD1(IN)
                                                      DOCOM
                                                                             01   +24V
                   24 V power                                                02    0V
                   supply
                                                                             03
CPD1(OUT)
                                                                            01    +24V
                   24 V power                                               02    0V
                   supply
                                                                            03
    NOTE
      The specification of the power supply connector CPD1 (IN) is the same as that
      for CPD1 (OUT). There are no indications on the printed circuit board to
      distinguish between the IN and OUT connectors. Do not turn off the +24 V
      supply to the connector during operation. Turning off the +24 V supply will
      cause a CNC communication alarm. When turning on the power, the +24 V
      supply to the I/O module must be turned on before or at the same time as the
      power supply to the CNC. When turning off the power, the +24 V supply to the
      I/O module must be turned off after or at the same time as the power supply to
      the CNC.
                                                     - 170 -
B-64303EN/03                             9.CONNECTION OF I/O Link SLAVE DEVICES
     NOTE
       An output DC voltage of +24 V at CE56 (B01) and CE57 (B01) is for DI signals.
       Do not supply 24 VDC to these pins from the outside.
                                         - 171 -
9.CONNECTION OF I/O Link SLAVE DEVICES                      B-64303EN/03
Pin No.
                          Address No.
                          Bit No.
                                        - 172 -
B-64303EN/03                 9.CONNECTION OF I/O Link SLAVE DEVICES
Pin No.
               Address No.
               Bit No.
                             - 173 -
9.CONNECTION OF I/O Link SLAVE DEVICES                      B-64303EN/03
Pin No.
                          Address No.
                          Bit No.
                                        - 174 -
B-64303EN/03                               9.CONNECTION OF I/O Link SLAVE DEVICES
     NOTE
     1 Xm+0.0 through Xm+0.7 and Xm+5.0 through Xm+5.7 are DI pins for which a
       common voltage can be selected. That is, by connecting the DICOM0
       CE56(A14) or DICOM5 CE57(B14) pin to the +24 V power supply, a DI signal
       can be input with its logical state reversed. If, however, a cable is connected to
       ground, it has the same effect as inputting an ON state DI signal. To prevent
       this from occurring, the connection of the DICOM0 CE56(A14) and DICOM5
       CE57(B14) pins to the 0 V power supply is recommended whereever possible.
       For safety reasons, the emergency stop signal needs to be allocated to an
       appropriate bit of the addresses for which the common voltage is fixed. See
       "Address allocation" in Section 9.6.9 for details of how to allocate the emergency
       stop signal.
       For unused DI pins allocated to the addresses for which the common voltage is
       fixed, the logic is fixed to "0". For unused pins allocated to the addresses for
       which the common voltage can be selected, the logic is fixed to "0" when the
       DICOM0 CE56(A14) or DICOM5 CE57(B14) pin is connected to the 0 V power
       supply. When the DICOM0 CE56(A14) or DICOM5 CE57(B14) pin is
       connected to the +24 V power supply, the logic is fixed to "1". The logic of the
       unused pins is variable when the contacts of the DICOM0 CE56(A14) and
       DICOM5 CE57(B14) pins are open.
     2 An output DC voltage of +24 V at CE56 (B01) and CE57 (B01) is for DI signals.
       Do not supply 24 VDC to these pins from the outside.
                                           - 175 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                           B-64303EN/03
Pin No.
                          Address No.
                          Bit No.
Relay
                                        - 176 -
B-64303EN/03                                          9.CONNECTION OF I/O Link SLAVE DEVICES
Pin No.
                                        Address No.
                                        Bit No.
Relay
                                                      - 177 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                    B-64303EN/03
5-φ3.2
65
                                                                                            95
              95
                                                             24 V power supply
                                                             connection
                                         Manual pulse generator connection
                                  I/O Link signal connection
        Operator's panel DI/DO interface
24 V power supply
                              Note) Lead wires and other components are mounted on the rear face of the
                       Note
                                    printed circuit board. Ensure that the printed circuit boards are
                                    spaced 5 mm or more from one another to prevent interference.
        : Polarity guide
        : A1 pin mark
                                                            - 178 -
B-64303EN/03                                             9.CONNECTION OF I/O Link SLAVE DEVICES
9.4.8           Specifications
   Installation specifications
                             During operation                       0°C to 58°C
   Ambient temperature
                             During storage and transportation -20C to 60°C
   Temperature change        Max. 1.1°C/min.
                             Normal                        75% or less
   Relative humidity
                             Short term (1 month or less) 95% or less
   Vibration                 During operation              0.5 G or less
                             Ordinary machining factory environment (Special consideration is required when installing
   Environment               the module in a dusty place or where highly concentrated cutting lubricant or organic
                             solvent is used.)
   Other requirements        (1) Install the I/O module in a fully enclosed cabinet.
   Ordering specifications
                   Item                      Specification                              Remarks
   Operator's panel I/O module           A20B-2002-0520            DI : 48 points
   (with MPG interface)                                            DO : 32 points
                                                                   MPG interface is supported.
   Power magnetics panel I/O module      A20B-2002-0521            DI : 48 points
   (without MPG interface)                                         DO : 32 points
                                                                   MPG interface is not supported.
   Fuse (replacement part)               A03B-0815-K001            1A
   Module specifications
                   Item                      Specification                              Remarks
   DI points                             48 points                 24 V input
   DO points                             32 points                 24 V source type output
   CNC interface                         FANUC I/O Link            Up to 16 modules can be connected as CNC slaves.
                                         connection                Or, a maximum of 1024 points can be supported on
                                                                   both the input and output sides.
   MPG interface                         Max. 3 units
                                                         - 179 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                              B-64303EN/03
    NOTE
      Ensure that the maximum current per DOCOM pin (DO power supply pin) does
      not exceed 0.7 A.
Address allocation
  For the operator's panel I/O module, I/O addresses are mapped as follows.
  Basically, this 48/32-point I/O module is allocated a group of DI addresses (16 bytes) and a group of DO
  addresses (4 bytes). This address allocation is explained below.
  The MPG interface (MPG counter) occupies DI space from Xm+12 through Xm+14. These addresses
  are fixed, and Xm+12 through Xm+14 must be allocated as a DI work area to enable the use of the MPG.
  Therefore, when using an MPG for the i series CNC, allocate DI addresses in units of 16 bytes.
  Do not use the DI space from Xm+12 through Xm+14 for Ladder; the CNC processes the MPG counter
  value directly.
                                                       - 180 -
B-64303EN/03                                                 9.CONNECTION OF I/O Link SLAVE DEVICES
   DI address Xm+15 is used for detecting overcurrent and overheating alarms that occur in the IC used in
   the DO driver. (For details, see the section describing the detection of DO (output signal) alarms.)
   This address is fixed, and must be allocated as a work area before it can be used. When using this area,
   therefore, allocate DI addresses in units of 16 bytes.
   Basically, I/O addresses can be allocated to the 48/32-point I/O module freely. When allocating DI
   addresses, however, consider also the fixed addresses that are directly supervised by the CNC, and keep
   the following in mind.
                        When DO is OFF in         ON
                        the sequence              OFF
                                                            - 181 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                              B-64303EN/03
    NOTE
      When the DO signal is in the ON state in the sequence, the ON or OFF state of
      the DOCOM pin determines the state of the signal, as shown within dotted lines
      in the above figure. Do not turn off the +24 V supply provided by the CPD1 to
      the I/O module during the operation. Turning off the +24 V supply causes a
      CNC communication alarm. When turning on the power, the +24 V supply to
      the I/O module must be turned on before or at the same time as the power
      supply to the CNC. When turning off the power, the +24 V supply to the I/O
      module must be turned off after or at the same time as the power supply to the
      CNC.
                                                                    +24V        0V
                                                                   +24V stabilized
                                                                   power supply
                                                                              Relay
                                               DV
DV
                                                    - 182 -
B-64303EN/03                                         9.CONNECTION OF I/O Link SLAVE DEVICES
9.5.1 Configuration
                                                                                  Inter-module flat
                                                                                  cable
      Installed on
      connector panel
      PC board
Basic module
     NOTE
       Be sure to install the basic module on the left side of the expansion module.
       This unit cannot be installed on the DIN rail.
       In a maximum configuration, one basic module plus one expansion module can
       be installed per group as shown above (DI/DO=96/64).
                                                     - 183 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                     B-64303EN/03
Basic module
Fuse
               Connector for
     inter-module connection
                    (CA101)
Front Rear
Expansion module
        Connector for
        inter-module                                       Connector for connector
        connection (CA102)                                 panel PC board
                                                           connection (CB162)
Front Rear
                                        - 184 -
B-64303EN/03                              9.CONNECTION OF I/O Link SLAVE DEVICES
      CNC or preceding
      I/O Link slave unit
                                                                   Following I/O Link
                                                                   slave unit
                                                                     JD1B
           I/O Link
           JD1A(JD51A)
JD1B
JD1A
               MPG                           JA3
                                                           CB161
               MPG                                                                        +24V
                                                                        Connector panel
                                             CA101                                        power
               MPG
                            Flat              Basic module
                            cable
                                             CA102
                                                                                          DI/DO
                                                                                          on
                                                           CB161                          machine
                                                                                          side
Expansion module
     NOTE
       The maximum configuration of a group consists of one basic module plus one
       expansion module as shown above. At this time, the number of input points is
       96, and the number of output points is 64. To add points, connect an additional
       slave onto the I/O Link.
                                          - 185 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                    B-64303EN/03
Installation conditions
   Ambient temperature           Operation: 0°C to 55°C
   for the unit                  Storage and transportation: -20°C to 60°C
   Temperature change            1.1°C/minute maximum
   Humidity                      Normal condition: 75% (relative humidity) or less, no condensation
                                 Short term (within one month): 95% or less (relative humidity), no condensation
   Vibration                     Operation: 0.5 G or less. FANUC performs evaluation test under the following
                                             conditions:
                                             10 Hz to 58 Hz: 0.075 mm (amplitude)
                                             58 Hz to 500 Hz: 1 G
                                             Vibration direction: X, Y, and Z
                                             Number of sweeps: 10 cycles
                                             Compliance with IEC68-2-6
                                 Non-operation: 1.0 G or less
   Atmosphere                    Normal machining factory environment (For use in an environment with relatively high
                                 levels of dust, coolant, organic solutions, and so forth, additional measures are
                                 required.)
   Other conditions              (1) Use each I/O module in a completely sealed cabinet.
                                 (2) For ventilation within each I/O module, allow a clearance of 40 mm or more
                                     between modules. Moreover, allow a clearance of 50 mm or more above and
                                     below each module.
                                     Never place a device that generates a large amount of heat below an I/O module.
                                 (3) When mounting I/O modules, ensure that the basic module is mounted on the left
                                     side when viewed from the flat cable.
                                                        - 186 -
B-64303EN/03                                   9.CONNECTION OF I/O Link SLAVE DEVICES
     NOTE
     1 Each of Xm and Yn represents the start address of the module on the I/O Link.
     2 The A32, B32, and C32 pins of each connector are used to feed 24 V to the
       module externally. Be sure to connect these pins.
                                               - 187 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                B-64303EN/03
                               Address number
                                                                           Pin number
                               Bit number
                   Xm+0.0        RV
                                                              CB161(C29)
Xm+0.1 RV CB161(A28)
Xm+0.2 RV CB161(B28)
Xm+0.3 RV CB161(C28)
Xm+0.4 RV CB161(A27)
Xm+0.5 RV CB161(B27)
Xm+0.6 RV CB161(C27)
Xm+0.7 RV CB161(A26)
                                                            CB161(A31,B31,C31,
                                             0V
                                                                  A30,B30,C30)
                   Xm+1.0        RV
                                                              CB161(B26)
                   Xm+1.1        RV
                                                              CB161(C26)
                   Xm+1.2        RV
                                                              CB161(A25)
                   Xm+1.3        RV
                                                              CB161(B25)
                   Xm+1.4        RV
                                                              CB161(C25)
                   Xm+1.5        RV
                                                              CB161(A24)
                   Xm+1.6        RV
                                                              CB161(B24)
                   Xm+1.7        RV
                                                              CB161(C24)
                                                                                        +24V       0V
                                        0V                                              +24 V stabilized
                                                                                        power supply
                                                  - 188 -
B-64303EN/03                                        9.CONNECTION OF I/O Link SLAVE DEVICES
                                Address number
                                                                               Pi n number
                                Bit numb er
                    Xm+2.0       RV
                                                                 CB161(A23)
                    Xm+2.1       RV
                                                                 CB161(B23)
                    Xm+2.2       RV
                                                                 CB161(C23)
                    Xm+2.3       RV
                                                                 CB161(A22)
                    Xm+2.4       RV
                                                                 CB161(B22)
                    Xm+2.5       RV
                                                                 CB161(C22)
                    Xm+2.6       RV
                                                                 CB161(A21)
                                          0V
                    Xm+3.0       RV
                                                                CB161(C21 )
                    Xm+3.1       RV
                                                                CB161(A20)
                    Xm+3.2       RV
                                                                CB161(B20)
                    Xm+3.3       RV
                                                                CB161(C20 )
                    Xm+3.4       RV
                                                                CB161(A19)
                    Xm+3.5       RV
                                                                CB161(B19)
                    Xm+3.6       RV
                                                                CB161(C19 )
                    Xm+3.7       RV
                                                                CB161(A18)
                                                              CB161(A31,B31,C31,
                                               0V
                                                                    A30,B30,C30)
                                                                                              +24V     0V
                                                                                             +24V stabilized
                                                                                             power supply
                                                    - 189 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                    B-64303EN/03
                      Address number
                                                              Pin number
                      Bit number
             Xm+4.0    RV
                                                 CB161(B18)
             Xm+4.1    RV
                                                 CB161(C18)
             Xm+4.2    RV
                                                 CB161(A17)
             Xm+4.3    RV
                                                 CB161(B17)
             Xm+4.4    RV
                                                 CB161(C17)
             Xm+4.5    RV
                                                 CB161(A16)
             Xm+4.6    RV
                                                 CB161(B16)
             Xm+4.7    RV
                                                 CB161(C16)
                               0V
             Xm+5.0    RV
                                                 CB161(A15)
             Xm+5.1    RV
                                                 CB161(B15)
             Xm+5.2    RV
                                                 CB161(C15)
             Xm+5.3    RV
                                                 CB161(A14)
             Xm+5.4    RV
                                                 CB161(B14)
             Xm+5.5    RV
                                                 CB161(C14)
             Xm+5.6    RV
                                                 CB161(A13)
             Xm+5.7    RV
                                                 CB161(B13)
                                             CB161(A31,B31,C31,
                                                   A30,B30,C30)
                               0V
                                                                            +24V     0V
                                                                           +24 V stabilized
                                                                           power supply
                                       - 190 -
B-64303EN/03                                          9.CONNECTION OF I/O Link SLAVE DEVICES
                                 Address number
                                                                              Pin number
                                 Bit number
                    Xm+6.0        RV
                                                                 CB162(C29)
                    Xm+6.1        RV
                                                                 CB162(A28)
                    Xm+6.2        RV
                                                                 CB162(B28)
                    Xm+6.3        RV
                                                                 CB162(C28)
                    Xm+6.4        RV
                                                                 CB162(A27)
                    Xm+6.5        RV
                                                                 CB162(B27)
                    Xm+6.6        RV
                                                                 CB162(C27)
                    Xm+6.7        RV
                                                                 CB162(A26)
                                                                CB162(A31,B31,C31,
                                                 0V                   A30,B30,C30)
                     Xm+7.0       RV
                                                                 CB162(B26)
                     Xm+7.1       RV
                                                                 CB162(C26)
                     Xm+7.2       RV
                                                                 CB162(A25)
                     Xm+7.3       RV
                                                                 CB162(B25)
                     Xm+7.4       RV
                                                                 CB162(C25)
                     Xm+7.5       RV
                                                                 CB162(A24)
                     Xm+7.6       RV
                                                                 CB162(B24)
                     Xm+7.7       RV
                                                                 CB162(C24)
                                                                                            +24V     0V
                                            0V                                             +24 V stabilized
                                                                                           power supply
                                                      - 191 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                            B-64303EN/03
                            Address number
                                                                       Pin number
                            Bit number
               Xm+8.0        RV
                                                          CB162(A23)
               Xm+8.1        RV
                                                          CB162(B23)
               Xm+8.2        RV
                                                          CB162(C23)
               Xm+8.3        RV
                                                          CB162(A22)
               Xm+8.4        RV
                                                          CB162(B22)
               Xm+8.5        RV
                                                          CB162(C22)
               Xm+8.6        RV
                                                          CB162(A21)
               Xm+8.7        RV
                                                          CB162(B21)
                                      0V
                Xm+9.0       RV
                                                          CB162(C21)
                Xm+9.1       RV
                                                          CB162(A20)
                Xm+9.2       RV
                                                          CB162(B20)
                Xm+9.3       RV
                                                          CB162(C20)
                Xm+9.4       RV
                                                          CB162(A19)
                Xm+9.5       RV
                                                          CB162(B19)
                Xm+9.6       RV
                                                          CB162(C19)
                Xm+9.7       RV
                                                          CB162(A18)
                                                          CB162(A31,B31,C31,
                                           0V                   A30,B30,C30)
                                                                                     +24V     0V
                                                                                    +24 V stabilized
                                                                                    power supply
                                                - 192 -
B-64303EN/03                              9.CONNECTION OF I/O Link SLAVE DEVICES
                         Address number
                                                                  Pin number
                         Bit number
               Xm+10.0    RV
                                                     CB162(B18)
               Xm+10.1    RV
                                                     CB162(C18)
               Xm+10.2    RV
                                                     CB162(A17)
               Xm+10.3    RV
                                                     CB162(B17)
               Xm+10.4    RV
                                                     CB162(C17)
               Xm+10.5    RV
                                                     CB162(A16)
               Xm+10.6    RV
                                                     CB162(B16)
               Xm+10.7    RV
                                                     CB162(C16)
                                  0V
               Xm+11.0    RV
                                                     CB162(A15)
               Xm+11.1    RV
                                                     CB162(B15)
               Xm+11.2    RV
                                                     CB162(C15)
               Xm+11.3    RV
                                                     CB162(A14)
               Xm+11.4    RV
                                                     CB162(B14)
               Xm+11.5    RV
                                                     CB162(C14)
               Xm+11.6    RV
                                                     CB162(A13)
               Xm+11.7    RV
                                                     CB162(B13)
                                                    CB162(A31,B31,C31,
                                                          A30,B30,C30)
                                  0V
                                                                                +24V     0V
                                                                               +24 V stabilized
                                                                               power supply
                                          - 193 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                            B-64303EN/03
DOCOM01 CB161(A01,B01)
                    Yn+0.0                                    CB161(C01)
                                                                                    Relay
                                      DV
Yn+0.1 DV CB161(A02)
Yn+0.2 DV CB161(B02)
Yn+0.3 DV CB161(C02)
Yn+0.4 DV CB161(A03)
Yn+0.5 DV CB161(B03)
Yn+0.6 DV CB161(C03)
Yn+0.7 DV CB161(A04)
Yn+1.0 DV CB161(B04)
Yn+1.1 DV CB161(C04)
Yn+1.2 DV CB161(A05)
Yn+1.3 DV CB161(B05)
Yn+1.4 DV CB161(C05)
Yn+1.5 DV CB161(A06)
Yn+1.6 DV CB161(B06)
Yn+1.7 DV CB161(C06)
                                                              CB161(A31,B31,C31,
                                               0V                   A30,B30,C30)
                                                    - 194 -
B-64303EN/03                              9.CONNECTION OF I/O Link SLAVE DEVICES
Pin number
                                     DOCOM23
                                                    CB161(A07,B07)
                                                                      +24V     0V
                        Address number                               +24 V stabilized
                        Bit number                                   power supply
               Yn+2.0                               CB161(C07)
                                                                          Relay
                                DV
               Yn+2.1           DV
                                                    CB161(A08)
               Yn+2.2           DV
                                                    CB161(B08)
               Yn+2.3           DV
                                                    CB161(C08)
               Yn+2.4           DV
                                                    CB161(A09)
               Yn+2.5           DV
                                                    CB161(B09)
               Yn+2.6           DV
                                                    CB161(C09)
               Yn+2.7           DV
                                                    CB161(A10)
Yn+3.0 DV CB161(B10)
Yn+3.1 DV CB161(C10)
Yn+3.2 DV CB161(A11)
Yn+3.3 DV CB161(B11)
Yn+3.4 DV CB161(C11)
Yn+3.5 DV CB161(A12)
Yn+3.6 DV CB161(B12)
Yn+3.7 DV CB161(C12)
                                                    CB161(A31,B31,C31,
                                     0V                   A30,B30,C30)
                                          - 195 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                  B-64303EN/03
Pin number
                                     DOCOM45
                                                    CB162(A01,B01)
               Yn+4.0                               CB162(C01)
                                                                          Relay
                               DV
               Yn+4.1          DV
                                                    CB162(A02)
               Yn+4.2          DV
                                                    CB162(B02)
               Yn+4.3          DV
                                                    CB162(C02)
               Yn+4.4          DV
                                                    CB162(A03)
               Yn+4.5          DV
                                                    CB162(B03)
               Yn+4.6          DV
                                                    CB162(C03)
               Yn+4.7          DV
                                                    CB162(A04)
               Yn+5.0          DV
                                                    CB162(B04)
               Yn+5.1          DV
                                                    CB162(C04)
               Yn+5.2          DV
                                                    CB162(A05)
               Yn+5.3          DV
                                                    CB162(B05)
               Yn+5.4          DV
                                                    CB162(C05)
               Yn+5.5          DV
                                                    CB162(A06)
               Yn+5.6          DV
                                                    CB162(B06)
               Yn+5.7          DV
                                                    CB162(C06)
                                                    CB162(A31,B31,C31,
                                     0V                   A30,B30,C30)
                                          - 196 -
B-64303EN/03                                  9.CONNECTION OF I/O Link SLAVE DEVICES
Pin number
                                         DOCOM67
                                                       CB162(A07,B07)
               Yn+6.0                                  CB162(C07)
                                                                              Relay
                                DV
               Yn+6.1           DV
                                                        CB162(A08)
               Yn+6.2           DV
                                                        CB162(B08)
               Yn+6.3           DV
                                                        CB162(C08
               Yn+6.4           DV
                                                        CB162(A09)
               Yn+6.5           DV
                                                        CB162(B09)
               Yn+6.6           DV
                                                        CB162(C09)
               Yn+6.7           DV
                                                        CB162(A10)
               Yn+7.0           DV
                                                        CB162(B10)
               Yn+7.1           DV
                                                        CB162(C10)
               Yn+7.2           DV
                                                        CB162(A11)
               Yn+7.3           DV
                                                        CB162(B11)
               Yn+7.4           DV
                                                        CB162(C11)
               Yn+7.5           DV
                                                        CB162(A12)
               Yn+7.6           DV
                                                        CB162(B12)
               Yn+7.7           DV
                                                        CB162(C12)
                                                       CB162(A31,B31,C31,
                                     0V                      A30,B30,C30)
                                             - 197 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                      B-64303EN/03
  ON/OFF of the power supply (DO common) for DO signals (output signals)
  By turning off (opening) the power supply pin (DOCOM) for the DO signals (output signals), all the DO
  signals of each module can be turned off at the same time. At this time, the DO state is as shown below.
                                           ON
                              DOCOM
                                           OFF
                     DO state when DO is   ON
                     on in the sequence
                                           OFF
                     DO state when DO is   ON
                     off in the sequence   OFF
    NOTE
      When DO is on in the sequence, the ON/OFF state of DOCOM is directly
      reflected in the DO state as indicated above by the dashed box.
      The +24 V signal to be supplied to the I/O module must not be turned off during
      operation. Otherwise, a CNC communication alarm is issued. Ensure that +24 V
      is supplied either when or before the power to the CNC is turned on, and that
      +24 V is removed either when or after the power to the CNC is turned off.
                                                       - 198 -
B-64303EN/03                                      9.CONNECTION OF I/O Link SLAVE DEVICES
                                                  DOCOM
                                                            CB150(01),(33)
                                                                   +24V                0V
                                                                   +24 V stabilized power supply
                                                                                     Relay
                                             DV
DV
                               +24V           CB161(A32,B32,C32)
                                              CB162(A32,B32,C32)
+24V 0V
                                               CB161(A31,B31,C31, A30,B30,C30)
                                0V             CB162(A31,B31,C31, A30,B30,C30)
     NOTE
       The +24 V signal to be supplied to the I/O module must not be turned on/off
       during operation.
       If the +24V signal is turned off during operation, a CNC communication alarm is
       issued. Ensure that +24 V is supplied either when or before the power to the
       CNC is turned on, and that +24 V is removed either when or after the power to
       the CNC is turned off.
                                                  - 199 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                           B-64303EN/03
40 mm
             A1 pin mark
                                                                    34-pin flat cable
    NOTE
      When installing a flat cable, ensure that all pins are connected on a one-to-one
      basis.
      The modules must be spaced at least 40 mm apart.
      In this case, the length of the flat cable is about 35 mm. When the modules are
      separated furthermore, the length of the flat cable is:
      35 mm + (module spacing - 40 mm)
      Note, however, that the maximum allowable flat cable length is 300 mm.
                                                   - 200 -
B-64303EN/03                                       9.CONNECTION OF I/O Link SLAVE DEVICES
     NOTE
       When mounting and dismounting a module, hold the module by its top and
       bottom surfaces. Avoid applying force to the sides (where slits are provided).
                                                   - 201 -
9.CONNECTION OF I/O Link SLAVE DEVICES                              B-64303EN/03
Hook
                       A
                                                                C
                                        Stopper
                                                                     B
                                  - 202 -
B-64303EN/03                              9.CONNECTION OF I/O Link SLAVE DEVICES
                                            Printing prohibited
                                            area on solder side
                                            (14×5)
      Printing
      prohibited area
      on component
      side (4 - 5×3)
                                      MRF-96MD
                                      A1 pin
      Printing
      prohibited area
      on solder side
      (14×3)
                                         - 203 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                              B-64303EN/03
50mm
10mm 10mm
     Basic
                                                         Expansion module
     module
50mm
   NOTE
   1 To ensure adequate ventilation within an I/O module, allow a clearance of 50
     mm or more above and below the module and a clearance of 10 mm or more on
     the left and right sides. Never place a device that generates a large amount of
     heat below an I/O module.
   2 To the front panel of an I/O module, the cables for the I/O Link and manual pulse
     generator are connected.
     For cabling, allow a clearance of about 70 mm at the front of an I/O module.
   3 Space the basic module and expansion module at least 40 mm apart from each
     other.
   4 An I/O module is secured to the connector panel by inserting the hook into a
     hole on the connector panel as with the current distribution I/O module. Allow a
     clearance for hooking on the rear side of the connector panel.
   5 For securing an I/O module, four printing prohibited areas are provided on the
     surface of the connector panel, and a printing prohibited area is also provided
     beside the upper and lower square holes on the rear side.
   6 When mounting the basic module and expansion module side by side, ensure
     that the basic module is mounted on the left side when viewed from the I/O Link
     connector.
   7 When inserting an I/O module into the connector panel, provide pedestals at
     positions nearest to the connector of the connector panel to support the top and
     bottom areas of the connector from the rear side to protect the connector panel
     from being warped.
   8 Ensure that the thickness of the connector panel printed circuit board is 1.7 mm
     ±0.1 mm.
                                                    - 204 -
B-64303EN/03                                      9.CONNECTION OF I/O Link SLAVE DEVICES
   Dimensions of the connector (MRF-96FD) for the connector panel printed circuit board
   (Part order specification drawing number: : A03B-0815-K030)
<1>
<2>
<3>
Unit: mm
                                                                                   <1> Insulator
                                                                                   <2> Locking hardware
                                                                                   <3> Contact
                                                  - 205 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                               B-64303EN/03
Address allocation
  For the connector panel I/O module, I/O addresses are mapped as follow:
  Each of Xm and Yn represents the start address of the module on the I/O Link.
  Basically, I/O module type-2 is allocated a group of DI addresses (16 bytes) and a group of DO addresses
  (8 bytes). Add or remove expansion module hardware as required. The reason is explained below.
  The MPG interface (MPG counter) occupies a DI space from Xm+12 to Xm+14. These addresses are
  fixed regardless of whether an expansion module is used, and Xm+12 to Xm+14 must be allocated as a
  DI work area to enable the use of an MPG. Therefore, when using an MPG, allocate DI addresses in units
  of 16-byte groups. The CNC directly processes the value of the MPG counter. So, ensure that the ladder
  does not use this area.
  DI address Xm+15 is used to detect an overheating alarm issued for a cause such as overcurrent of the IC
  used for a DO driver. Address Xm+15 is fixed regardless of whether an expansion module is used. This
  address must be allocated as a work area before this address can be used.
For the reason mentioned above, allocate DI addresses for I/O module type-2 in units of 16-byte groups.
                                                        - 206 -
B-64303EN/03                                      9.CONNECTION OF I/O Link SLAVE DEVICES
9.6.1          Overview
   With the I/O unit for 0i, up to 96 DI points and up to 64 DO points can be used.
   I/O Link is used to connect to controls. For the connection method, see Subsection 8.2.1.
   For the I/O unit for 0i, it is necessary to perform I/O Link assignment.
                                                            Power magnetic
                                                            panel circuit
                                                  - 207 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                           B-64303EN/03
   X0        DI 96 points                                       Y0         DO 64 points
   X1                                                           Y1
   X2                                                           Y2
   X3                                                           Y3
   X4                                                           Y4
   X5                                                           Y5
   X6                                                           Y6
   X7                                                           Y7
   X8
                                                                Module name: CM08O
   X9
   X10
   X11
   X12       First MPG
   X13       Second MPG
   X14       Third MPG
   X15       DO alarm detection
    NOTE
      Since readout from a manual pulse generator (X12 to X14) is directly performed
      by the CNC, only the above assignment must be performed by the PMC.
  If the number of DI/DO points is not sufficient, external I/O units such as the dispersed I/O can be added
  using the FANUC I/O Link.
  A MIL-compatible ribbon cable connector is used as the interface connector of the I/O unit for 0i to
  simplify connection to the connector panel.
  The connector can also be used for the Series 0i Mate.
                                                   - 208 -
B-64303EN/03                                        9.CONNECTION OF I/O Link SLAVE DEVICES
9.6.2           Cautions
   The following cautions must be observed when using I/O signal receivers and drivers for the machine
   interface.
                                                    - 209 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                            B-64303EN/03
                     Cable
                             CP1
                             AMP Japan
                             1-178288-3 (housing)
                             1-175218-5 (Contact)                        External power
                                                                       Select a source that
                                       +24V (1)                        meets the external
                                         0V (2)
                                                                       power terminal.
  Part of the 24 VDC power input to CP1 can be taken out from CP2 by branching. CP2 should be
  connected as shown below. In this case, the rating of the external 24 VDC power supplied to CP1 must
  be the sum of the power consumed within the control unit and that supplied to external equipment via
  CP2. The maximum capacity of power that can be obtained from a branch is 1.0 A.
                          CP2
                          1   +24V
                          2     0V
                          3
                     Cable
                          CP2
                          AMP JAPAN
                          2-178288-3 (Housing)
                          1-175218-5 (Contact)                            External device
                                                                        Select a connector that
                                        +24V (1)                        matches the pin layout
                                          0V (2)                        of the external device.
    NOTE
      Do not interrupt +24 V supplied to this connector during operation. Otherwise,
      an alarm about communication with the CNC is issued.
      A voltage of +24 V must not be supplied after power-on of the CNC and +24 V
      must not be interrupted before power-off of the CNC. When powering off the
      CNC body, be sure to power off the I/O unit for 0i.
                                                     - 210 -
B-64303EN/03                                          9.CONNECTION OF I/O Link SLAVE DEVICES
                 A          B            A        B                     A        B            A         B
        01       0V      +24V    01     0V      +24V            01     0V      +24V    01     0V      +24V
        02     Xm+0.0   Xm+0.1   02   Xm+3.0   Xm+3.1           02   Xm+4.0   Xm+4.1   02   Xm+7.0   Xm+7.1
        03     Xm+0.2   Xm+0.3   03   Xm+3.2   Xm+3.3           03   Xm+4.2   Xm+4.3   03   Xm+7.2   Xm+7.3
        04     Xm+0.4   Xm+0.5   04   Xm+3.4   Xm+3.5           04   Xm+4.4   Xm+4.5   04   Xm+7.4   Xm+7.5
        05 Xm+0.6       Xm+0.7   05 Xm+3.6     Xm+3.7           05 Xm+4.6     Xm+4.7   05 Xm+7.6     Xm+7.7
        06 Xm+1.0       Xm+1.1   06 Xm+8.0     Xm+8.1           06 Xm+5.0     Xm+5.1   06 Xm+10.0 Xm+10.1
        07 Xm+1.2       Xm+1.3   07 Xm+8.2     Xm+8.3           07 Xm+5.2     Xm+5.3   07 Xm+10.2 Xm+10.3
        08 Xm+1.4       Xm+1.5   08 Xm+8.4     Xm+8.5           08 Xm+5.4     Xm+5.5   08 Xm+10.4 Xm+10.5
        09 Xm+1.6       Xm+1.7   09 Xm+8.6     Xm+8.7           09 Xm+5.6     Xm+5.7   09 Xm+10.6 Xm+10.7
        10 Xm+2.0       Xm+2.1   10 Xm+9.0     Xm+9.1           10 Xm+6.0     Xm+6.1   10 Xm+11.0 Xm+11.1
        11 Xm+2.2       Xm+2.3   11 Xm+9.2     Xm+9.3           11 Xm+6.2     Xm+6.3   11 Xm+11.2 Xm+11.3
        12 Xm+2.4       Xm+2.5   12 Xm+9.4     Xm+9.5           12 Xm+6.4     Xm+6.5   12 Xm+11.4 Xm+11.5
        13 Xm+2.6       Xm+2.7   13 Xm+9.6     Xm+9.7           13 Xm+6.6     Xm+6.7   13 Xm+11.6 Xm+11.7
        14                       14                             14 COM4                14
        15                       15                             15                     15
        16 Yn+0.0       Yn+0.1   16 Yn+2.0     Yn+2.1           16 Yn+4.0     Yn+4.1   16 Yn+6.0     Yn+6.1
        17 Yn+0.2       Yn+0.3   17 Yn+2.2     Yn+2.3           17 Yn+4.2     Yn+4.3   17 Yn+6.2     Yn+6.3
        18 Yn+0.4       Yn+0.5   18 Yn+2.4     Yn+2.5           18 Yn+4.4     Yn+4.5   18 Yn+6.4     Yn+6.5
        19 Yn+0.6       Yn+0.7   19 Yn+2.6     Yn+2.7           19 Yn+4.6     Yn+4.7   19 Yn+6.6     Yn+6.7
        20 Yn+1.0       Yn+1.1   20 Yn+3.0     Yn+3.1           20 Yn+5.0     Yn+5.1   20 Yn+7.0     Yn+7.1
        21 Yn+1.2       Yn+1.3   21 Yn+3.2     Yn+3.3           21 Yn+5.2     Yn+5.3   21 Yn+7.2     Yn+7.3
        22 Yn+1.4       Yn+1.5   22 Yn+3.4     Yn+3.5           22 Yn+5.4     Yn+5.5   22 Yn+7.4     Yn+7.5
        23 Yn+1.6       Yn+1.7   23 Yn+3.6     Yn+3.7           23 Yn+5.6     Yn+5.7   23 Yn+7.6     Yn+7.7
        24     DOCOM DOCOM       24   DOCOM DOCOM               24   DOCOM DOCOM       24   DOCOM DOCOM
        25     DOCOM DOCOM       25   DOCOM DOCOM               25   DOCOM DOCOM       25   DOCOM DOCOM
       NOTE
       1 The B01 +24 V pins of the connectors (CB104, CB105, CB106, and CB107) are
         used for the DI input signals, and which output 24 VDC.
         Do not connect +24 V of an external power supply to these pins.
       2 Each DOCOM is connected in the printer board. If using the DO signal (Y) of a
         connector, be sure to input 24 VDC to each pin of the DOCOM of that connector.
                                                      - 211 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                    B-64303EN/03
                     Xm+0.0                       CB104(A02)
                               RV
                     Xm+0.1                       CB104(B02)
                               RV
                     Xm+0.2                       CB104(A03)
                               RV
                     Xm+0.3                       CB104(B03)
                               RV
                     Xm+0.4                       CB104(A04)
                               RV
                     Xm+0.5                       CB104(B04)
                               RV
                     Xm+0.6                       CB104(A05)
                               RV
                     Xm+0.7                       CB104(B05)
                               RV
0V
                     Xm+1.0                       CB104(A06)
                               RV
                     Xm+1.1                       CB104(B06)
                               RV
                     Xm+1.2                       CB104(A07)
                               RV
                     Xm+1.3                       CB104(B07)
                               RV
                     Xm+1.4                       CB104(A08)
                               RV
                     Xm+1.5                       CB104(B08)
                               RV
                     Xm+1.6                       CB104(A09)
                               RV
                     Xm+1.7                       CB104(B09)
                               RV
0V
                                        - 212 -
B-64303EN/03                      9.CONNECTION OF I/O Link SLAVE DEVICES
                                                     Terminal
                                                        ’[Žq”ÔNo.†
                        Address No.†
                        ƒAƒhƒŒƒX”Ô
                        Bit No.
                        ƒrƒbƒg”Ô   † +24V
                                            CB104(B01),CB105(B01)
               Xm+2.0                       CB104(A10)
                         RV
               Xm+2.1                       CB104(B10)
                         RV
               Xm+2.2                       CB104(A11)
                         RV
               Xm+2.3                       CB104(B11)
                         RV
               Xm+2.4                       CB104(A12)
                         RV
               Xm+2.5                       CB104(B12)
                         RV
               Xm+2.6                       CB104(A13)
                         RV
               Xm+2.7                       CB104(B13)
                         RV
0V
               Xm+3.0                       CB105(A02)
                         RV
               Xm+3.1                       CB105(B02)
                         RV
               Xm+3.2                       CB105(A03)
                         RV
               Xm+3.3                       CB105(B03)
                         RV
               Xm+3.4                       CB105(A04)
                         RV
               Xm+3.5                       CB105(B04)
                         RV
               Xm+3.6                       CB105(A05)
                         RV
               Xm+3.7                       CB105(B05)
                         RV
0V
                                  - 213 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                   B-64303EN/03
                                                                        Terminal
                                                                           ’[Žq”ÔNo.†
                                     Address No.†
                                     ƒAƒhƒŒƒX”Ô
                                     Bit No.
                                     ƒrƒbƒg”Ô   † +24V
                                                                CB106(B01)
                            Xm+4.0                              CB106(A02)
                                      RV
                            Xm+4.1                              CB106(B02)
                                      RV
                            Xm+4.2                              CB106(A03)
                                      RV
                            Xm+4.3                              CB106(B03)
                                      RV
                            Xm+4.4                              CB106(A04)
                                      RV
                            Xm+4.5                              CB106(B04)
                                      RV
                            Xm+4.6                              CB106(A05)
                                      RV
                            Xm+4.7                              CB106(B05)
                                      RV
COM4 CB106(A14)
CB106(A01)
0V
                            Xm+5.0                              CB106(A06)
                                      RV
                            Xm+5.1                              CB106(B06)
                                      RV
                            Xm+5.2                              CB106(A07)
                                      RV
                            Xm+5.3                              CB106(B07)
                                      RV
                            Xm+5.4                              CB106(A08)
                                      RV
                            Xm+5.5                              CB106(B08)
                                      RV
                            Xm+5.6                              CB106(A09)
                                      RV
                            Xm+5.7                              CB106(B09)
                                      RV
0V
  For address Xm+4, either a source or sink type (with a 0- or 24-V common voltage) can be selected.
  COM4 must be connected to either 24 or 0 V; never leave it open. From the viewpoint of safety
  standards, it is recommended that a sink type signal be used. The above diagram shows an example in
  which the signal is of sink type (with a 24-V common voltage).
                                               - 214 -
B-64303EN/03                      9.CONNECTION OF I/O Link SLAVE DEVICES
                                                     Terminal
                                                        ’[Žq”ÔNo.†
                        Address No.†
                        ƒAƒhƒŒƒX”Ô
                        Bit No.
                        ƒrƒbƒg”Ô   † +24V
                                            CB106(B01),CB107(B01)
               Xm+6.0                       CB106(A10)
                         RV
               Xm+6.1                       CB106(B10)
                         RV
               Xm+6.2                       CB106(A11)
                         RV
               Xm+6.3                       CB106(B11)
                         RV
               Xm+6.4                       CB106(A12)
                         RV
               Xm+6.5                       CB106(B12)
                         RV
               Xm+6.6                       CB106(A13)
                         RV
               Xm+6.7                       CB106(B13)
                         RV
0V
               Xm+7.0                       CB107(A02)
                         RV
               Xm+7.1                       CB107(B02)
                         RV
               Xm+7.2                       CB107(A03)
                         RV
               Xm+7.3                       CB107(B03)
                         RV
               Xm+7.4                       CB107(A04)
                         RV
               Xm+7.5                       CB107(B04)
                         RV
               Xm+7.6                       CB107(A05)
                         RV
               Xm+7.7                       CB107(B05)
                         RV
0V
                                  - 215 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                   B-64303EN/03
                                                         Terminal No.†
                                                             ’[Žq”Ô
                             Address No.†
                             ƒAƒhƒŒƒX”Ô
                             Bit No.
                             ƒrƒbƒg”Ô   † +24V
                                                 CB105(B01)
                    Xm+8.0                       CB105(A06)
                              RV
                    Xm+8.1                       CB105(B06)
                              RV
                    Xm+8.2                       CB105(A07)
                              RV
                    Xm+8.3                       CB105(B07)
                              RV
                    Xm+8.4                       CB105(A08)
                              RV
                    Xm+8.5                       CB105(B08)
                              RV
                    Xm+8.6                       CB105(A09)
                              RV
                    Xm+8.7                       CB105(B09)
                              RV
0V
                    Xm+9.0                       CB105(A10)
                              RV
                    Xm+9.1                       CB105(B10)
                              RV
                    Xm+9.2                       CB105(A11)
                              RV
                    Xm+9.3                       CB105(B11)
                              RV
                    Xm+9.4                       CB105(A12)
                              RV
                    Xm+9.5                       CB105(B12)
                              RV
                    Xm+9.6                       CB105(A13)
                              RV
                    Xm+9.7                       CB105(B13)
                              RV
0V
                                       - 216 -
B-64303EN/03                       9.CONNECTION OF I/O Link SLAVE DEVICES
                                                      Terminal No.†
                                                          ’[Žq”Ô
                         Address No.†
                         ƒAƒhƒŒƒX”Ô
                         Bit No.
                         ƒrƒbƒg”Ô   † +24V
                                             CB107(B01)
               Xm+10.0                        CB107(A06)
                          RV
               Xm+10.1                        CB107(B06)
                          RV
               Xm+10.2                        CB107(A07)
                          RV
               Xm+10.3                        CB107(B07)
                          RV
               Xm+10.4                        CB107(A08)
                          RV
               Xm+10.5                        CB107(B08)
                          RV
               Xm+10.6                        CB107(A09)
                          RV
               Xm+10.7                        CB107(B09)
                          RV
0V
               Xm+11.0                        CB107(A10)
                          RV
               Xm+11.1                        CB107(B10)
                          RV
               Xm+11.2                        CB107(A11)
                          RV
               Xm+11.3                        CB107(B11)
                          RV
               Xm+11.4                        CB107(A12)
                          RV
               Xm+11.5                        CB107(B12)
                          RV
               Xm+11.6                        CB107(A13)
                          RV
               Xm+11.7                        CB107(B13)
                          RV
0V
                                   - 217 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                     B-64303EN/03
                                                      +24V            0V
                                                      +24V stabilized
                                                       +24VˆÀ’艻“dŒ¹
                                                      power supply
DV
                Yn+0.0                      CB104(A16)
                                                             Relay
                                                             ƒŠ
                                                             ƒŒ [
                Yn+0.1                      CB104(B16)
                           DV
                Yn+0.2                      CB104(A17)
                           DV
                Yn+0.3                      CB104(B17)
                           DV
                Yn+0.4                      CB104(A18)
                           DV
                Yn+0.5                      CB104(B18)
                           DV
                Yn+0.6                      CB104(A19)
                           DV
                Yn+0.7                      CB104(B19)
                           DV
                Yn+1.0                      CB104(A20)
                           DV
                Yn+1.1                      CB104(B20)
                           DV
                Yn+1.2                      CB104(A21)
                           DV
                Yn+1.3                      CB104(B21)
                           DV
                Yn+1.4                      CB104(A22)
                           DV
                Yn+1.5                      CB104(B22)
                           DV
                Yn+1.6                      CB104(A23)
                           DV
                Yn+1.7                      CB104(B23)
                           DV
                                            CB104(A01)
0V
                                        - 218 -
B-64303EN/03                            9.CONNECTION OF I/O Link SLAVE DEVICES
                                                         Terminal
                                                          ’[Žq”Ô †No.
                        Address No. †
                        ƒAƒhƒŒƒX”Ô
                        Bit No.
                        ƒrƒbƒg”Ô   †        CB104(A24,B24,A25,B25)
                                            CB105(A24,B24,A25,B25)
                                            CB106(A24,B24,A25,B25)
                                            CB107(A24,B24,A25,B25)
                                   DOCOM
                                                      +24V            0V
                                                       +24V stabilized
                                                       +24VˆÀ’艻“dŒ¹
                                                       power supply
DV
               Yn+2.0                       CB105(A16)
                                                              Relay
                                                              ƒŠ
                                                              ƒŒ [
               Yn+2.1                       CB105(B16)
                           DV
               Yn+2.2                       CB105(A17)
                           DV
               Yn+2.3                       CB105(B17)
                           DV
               Yn+2.4                       CB105(A18)
                           DV
               Yn+2.5                       CB105(B18)
                           DV
               Yn+2.6                       CB105(A19)
                           DV
               Yn+2.7                       CB105(B19)
                           DV
               Yn+3.0                       CB105(A20)
                           DV
               Yn+3.1                       CB105(B20)
                           DV
               Yn+3.2                       CB105(A21)
                           DV
               Yn+3.3                       CB105(B21)
                           DV
               Yn+3.4                       CB105(A22)
                           DV
               Yn+3.5                       CB105(B22)
                           DV
               Yn+3.6                       CB105(A23)
                           DV
               Yn+3.7                       CB105(B23)
                           DV
                                            CB105(A01)
0V
                                        - 219 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                        B-64303EN/03
                                                           Terminal
                                                           ’[Žq”Ô †No.
                         Address No.†
                         ƒAƒhƒŒƒX”Ô
                         Bit No.
                         ƒrƒbƒg”Ô   †       CB104(A24,B24,A25,B25)
                                            CB105(A24,B24,A25,B25)
                                            CB106(A24,B24,A25,B25)
                                            CB107(A24,B24,A25,B25)
                                   DOCOM
                                                         +24V            0V
                                                          +24V stabilized
                                                          +24VˆÀ’艻“dŒ¹
                                                          power supply
DV
                Yn+4.0                      CB106(A16)
                                                                Relay
                                                                ƒŠ
                                                                ƒŒ [
                Yn+4.1                      CB106(B16)
                           DV
                Yn+4.2                      CB106(A17)
                           DV
                Yn+4.3                      CB106(B17)
                           DV
                Yn+4.4                      CB106(A18)
                           DV
                Yn+4.5                      CB106(B18)
                           DV
                Yn+4.6                      CB106(A19)
                           DV
                Yn+4.7                      CB106(B19)
                           DV
                Yn+5.0                      CB106(A20)
                           DV
                Yn+5.1                      CB106(B20)
                           DV
                Yn+5.2                      CB106(A21)
                           DV
                Yn+5.3                      CB106(B21)
                           DV
                Yn+5.4                      CB106(A22)
                           DV
                Yn+5.5                      CB106(B22)
                           DV
                Yn+5.6                      CB106(A23)
                           DV
                Yn+5.7                      CB106(B23)
                           DV
                                            CB106(A01)
0V
                                        - 220 -
B-64303EN/03                                      9.CONNECTION OF I/O Link SLAVE DEVICES
                                                                      Terminal
                                                                       ’[Žq”Ô †No.
                                  Address No.†
                                  ƒAƒhƒŒƒX”Ô
                                  Bit No.
                                  ƒrƒbƒg”Ô   †        CB104(A24,B24,A25,B25)
                                                      CB105(A24,B24,A25,B25)
                                                      CB106(A24,B24,A25,B25)
                                                      CB107(A24,B24,A25,B25)
                                            DOCOM
                                                                   +24V            0V
                                                                    +24V stabilized
                                                                    +24VˆÀ’艻“dŒ¹
                                                                    power supply
DV
                       Yn+6.0                         CB107(A16)
                                                                           Relay
                                                                           ƒŠ
                                                                           ƒŒ [
                       Yn+6.1                         CB107(B16)
                                    DV
                       Yn+6.2                         CB107(A17)
                                    DV
                       Yn+6.3                         CB107(B17)
                                    DV
                       Yn+6.4                         CB107(A18)
                                    DV
                       Yn+6.5                         CB107(B18)
                                    DV
                       Yn+6.6                         CB107(A19)
                                    DV
                       Yn+6.7                         CB107(B19)
                                    DV
                       Yn+7.0                         CB107(A20)
                                    DV
                       Yn+7.1                         CB107(B20)
                                    DV
                       Yn+7.2                         CB107(A21)
                                    DV
                       Yn+7.3                         CB107(B21)
                                    DV
                       Yn+7.4                         CB107(A22)
                                    DV
                       Yn+7.5                         CB107(B22)
                                    DV
                       Yn+7.6                         CB107(A23)
                                    DV
                       Yn+7.7                         CB107(B23)
                                    DV
                                                      CB107(A01)
0V
      CAUTION
    1 Never use the following DO parallel connection.
DOCOM
+24V 0V
DV
                                                                         Relay
                                                                         ƒŠ
                                                                         ƒŒ [
                                    DV
0V
                                                    - 222 -
B-64303EN/03                                  9.CONNECTION OF I/O Link SLAVE DEVICES
       CAUTION
     2 When using a dark lighting resistor as shown in the following figure, use a
       leakage-proof diode.
DOCOM
                                                                 +24V     0V
                                                 Dark
                                                 lighting
                                                 ˆÃ“_“”’ï
                                                 resister
                                                    R
                               DV                                         Lamp
                                                                          ƒ‰ƒ“ƒv
                                                  Leakage-proof diode [
                                                  ƒŠ [ƒN–hŽ~—pƒ_ƒCƒI
                                                  ƒh
0V
                                              - 223 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                            B-64303EN/03
   NOTE
     Output signal driver
     Each of the output signal driver devices used on this I/O board outputs eight
     signals.
      A driver device monitors the current of each output signal. If it detects an
      overcurrent on an output, it turns off the output. Once an overcurrent causes
      an output to turn off, the overcurrent is no longer present. Then, the output is
      turned on again. In ground-fault or overload conditions, outputs may turn on
      and off alternately. This phenomenon also occurs when a load with a high
      surge current is connected.
      Each driver device contains an overheat detector circuit. If an overcurrent is
      observed on an output continuously because of a ground-fault or similar reason
      and the temperature in the device rises, the overheat detector circuit turns off all
      eight outputs. The output-off state is maintained. This state can be released
      by logically turning off then on again the outputs after the internal temperature of
      the device drops to a specified level. This state can also be released by turning
      off the system power supply.
      The output signals of the driver devices are assigned the following addresses:
      Device #0: Yn+0.0 to Yn+0.7
      Device #1: Yn+1.0 to Yn+1.7
      Device #2: Yn+2.0 to Yn+2.7
      Device #3: Yn+3.0 to Yn+3.7
      Device #4: Yn+4.0 to Yn+4.7
      Device #5: Yn+5.0 to Yn+5.7
      Device #6: Yn+6.0 to Yn+6.7
      Device #7: Yn+7.0 to Yn+7.7
      If NC diagnosis shows that an output is on but the output is actually not turned
      on, an overload on that output or another output in the same device may have
      turned off the eight outputs of that device. In such a case, turn off the system
      power supply and remove the cause of the overload.
                                          - 224 -
B-64303EN/03                  9.CONNECTION OF I/O Link SLAVE DEVICES
DOCOM
OHD
                      CONTROL
               IN#0   LOGIC                                                  OUT#0
OCD
                      CONTROL
               IN#1   LOGIC                                                  OUT#1
OCD
                E       E                   E                                    E
               ・E      ・E                  ・E                                   ・E
               ・E      ・                   ・                                    ・E
               ・                                                                ・
                      CONTROL
               IN#7   LOGIC                                                  OUT#7
OCD
                                      HD : ‰ß”MŒŸ
                       HD: Over-heat detector           o‰ñ˜H,
                                              circuit, OCD:    OCD : ‰ß“d—¬ŒŸ
                                                            Over-current          o‰ñ˜H
                                                                         detector circuit
                             - 225 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                         B-64303EN/03
                                              MPG
                                              JA3
                                                    - 226 -
B-64303EN/03                                              9.CONNECTION OF I/O Link SLAVE DEVICES
                            Cable connection
                                                                                         Manual Pulse
                                                                        T.B.
                                                                                         Generator
                                                                                          #1
                                   1       7 RD                       HA1              5    HA1
                            HA1    2       7 WH                                        6
                            HB1                                       HB1                  HB1
                                   9       5 RD                                        3
                            +5V                                       +5V                  +5V
                                   12      2 BK                                        4
                             0V                                        0V                   0V
                                                                                          #2
                                   3       8 RD                       HA2              5 HA2
                            HA2    4       8 BK                                        6
                            HB2                                       HB2                  HB2
                                   18      4 RD                                        3
                            +5V                                       +5V                  +5V
                                   14      3 BK                                        4
                             0V                                        0V                   0V
                                                                                          #3
                                   5       9 BK                                        5
                                                                      HA3                  HA3
                            HA3    6       9 WH                                        6
                            HB3                                       HB3              3 HB3
                                   20      6 RD
                            +5V    16      1 BK                       +5V                  +5V
                                                                                       4
                             0V                                        0V                   0V
                                                shield
                                     Ground Plate
                                              Cable                            Wires
                                                          - 227 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                        B-64303EN/03
  Therefore,
           3
  L≦           =76.75 [m]
        0.0394
  Example: When cable A66L-0001-0286 is used
  This cable consists of three pairs of signal lines and six power wires (20/0.18, 0.0394 Ω/m).
  When these three cables are used for 0V and 5V lines, the cable length is:
  The maximum distance is, however, 50 m for the transmission of a pulse signal from the manual pulse
  generator. The cable length is, therefore, up to 50 m.
  The maximum cable length is 38.37 m when using the two manual pulse generators, or 25.58 m when
  using the three generators.
Connection example
  Connection example in which more than one unit equipped with a manual handle interface is connected
  with an I/O LINK
                            JA3
                                                       Operator's panel I/O
                                                          ‘€ ì”ÕI/O
                           I/O unit
                         I/Oƒ†ƒjƒbƒg
Parameter
                            #7          #6           #5               #4      #3           #2           #1         #0
       7105                                                                                             HDX
                                                            - 228 -
B-64303EN/03                                       9.CONNECTION OF I/O Link SLAVE DEVICES
       12302                          X signal address associated with the third manual handle
                                                   - 229 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                               B-64303EN/03
9.7.1         Overview
  This unit connects FANUC I/O Link master devices' such as the CNC, via an I/O Link to enable the
  transfer of DI/DO signals.
System A System B
                                                          FANUC I/O
                                                         FANUC    I/OLink
                                                                      Link
                                                          connection unit
                                                         Œ‹・‡ƒ†ƒjƒbƒg
                                                    DI                 DO
DO DI
Fig. 9.7.1 System which uses FANUC I/O Link connection units
    This system enable I/O data transfer between two independent FANUC I/O Link
    master devices. When the system is adjusted and maintained, the FANUC I/O Link
    can be operated with the system power for one of the FANUC I/O Link lines
    switched off, that is, the link operation is stopped.
    NOTE
     Take the following point into consideration when you design your system.
      1. If one of the links is stopped, the system power supply is turned off for
         maintenance or adjustment, or the link is stopped due to a failure of CNC or
         I/O Link slave module, the circuit of this unit is designed so that all DI signals
         sent from a system at rest consists entirely of zeros.
      2. If one of the links is stopped, either abnormally or normally, it takes up to
         several hundred milliseconds for NOTE 1 function to take effect. During this
         period, that data which exists immediately before the link stops is sent out.
         Take this into account when designing your system.
      3. It cannot be guaranteed that the operation described to NOTE 1 and NOTE2
         is carried out that way. Therefore, manage signals related to safety by
         making a safety circuit outside this FANUC I/O Link connection unit.
                                                          - 230 -
B-64303EN/03                                                  9.CONNECTION OF I/O Link SLAVE DEVICES
9.7.2             Specification
               Item                                                        Specification
   I/O Link function             Provided with two slave mode I/O Link interface channels, between which DI/DO data can be
                                 transferred.
                                 [Interface types]
                                 Electrical - optical
                                 Electrical - electrical   One of the following combinations is selected:
                                 Optical - optical
Ordering information
                                 Interface type                                                     Specification
   Electrical-optical interface                                                                   A20B-2000-0410
   Electrical-electrical interface                                                                A20B-2000-0411
   Optical-optical interface                                                                      A20B-2000-0412
     NOTE
       The optical interface of this unit is equivalent to the standard type
       (A13B-0154-B001) of an optical I/O Link adapter. Therefore, when this unit is
       combined with an optical I/O Link adapter, the optical I/O Link adapter must be
       of the standard type (A13B-0154-B001).
                                                             - 231 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                              B-64303EN/03
LED indications
                  LED5       LED3                                    LED4        LED2
                  (GREEN)    (RED)                                   (GREEN)     (RED)
                                     DC-DC
                                     CONVERTER
CP2 CP1
+5V
LED1 (RED)
0V : Check pin
                      LED1                 Normal
      1
                      LED1                 A RAM parity error occurred because of a hardware failure.
                    LED4 LED2
                                           A communication error occurred in a channel of CP1.
                    LED5 LED3
                                           A communication error occurred in a channel of CP2.
: On : Off
                                                 - 232 -
B-64303EN/03                             9.CONNECTION OF I/O Link SLAVE DEVICES
180 Unit: mm
                10                          160                           10
         30
                                        Printed-circuit board
         90
                                                                                    150
         30
        Cable                                                                       Cable
                                        Mounted components
                                                                                   50 or less
                           Fig. 9.7.2 (b)     Outline drawing
                                         - 233 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                                       B-64303EN/03
9.7.3 Connection
                                                                                      Optical I/O
                                                                                      Link adapter
                                                     CP*                     CP*
                                                                                               <2>
                                                   Electrical         Optical
                                                   interface          interface
                                                   JD1B*                  COPB*
                                                   JD1A*                   COPA*
                                     <1>                                                       <2>
                                                  FANUC I/O Link connection unit (for
                                                  electrical-optical interface)
                                                                                                     (*)    1 or 2 (channel No.)
                                                            - 234 -
B-64303EN/03                                  9.CONNECTION OF I/O Link SLAVE DEVICES
   (2) Signal cable (electrical)
9.8.1          Overview
  The FANUC servo unit β series with I/O Link (called the β amplifier with I/O Link) is a servo unit that
  can be easily connected to a CNC control unit via the FANUC I/O Link.
                                                   - 236 -
B-64303EN/03                                        9.CONNECTION OF I/O Link SLAVE DEVICES
9.8.2            Connection
   The β amplifier with I/O Link is connected to the control unit using the usual FANUC I/O Link
   connection.
      Control unit
Connection to β amplifier
                                                   - 237 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                       B-64303EN/03
9.9.1         Overview
  Standard machine operator's panel is connected with CNC by I/O Link, which is composed by some
  following operator's panels.
  Main panel
       All key tops are detachable. MTB can customize keys and make his original key layout easily.
  Sub panel
       Operator's panel with switches such as an emergency stop switch, memory protect switch, and rotary
       switch for override
    NOTE
      As the main panel for a standard machine operator's panel, use a 3-keystroke
      support model, which does not accept more than three simultaneous keystrokes.
      See Subsection 9.9.6.2, "Order specification".
                                                - 238 -
B-64303EN/03                                      9.CONNECTION OF I/O Link SLAVE DEVICES
CNC
CNK1
                                                  JD1A
                                                                JA3            MPG
MPG
                                                                            Pendant type
                     +24V Power supply            CA64(IN)      JA58           MPG
CM65 (SA1)
CM66 (SA2)
     NOTE
     1 This CNC is only possible to use the MPG interface on this operator's panel. If
       Series 0i uses some I/O unit having MPG interface (ex. Dispersion type I/O
       module for panel) and this operator's panel, the MPG interface nearest the CNC
       is only available on the I/O Link connection.
       To enable the MPG interface of a second or subsequent unit, use the manual
       handle allocation function.
     2 MPG cannot be connected with either of JA3 and JA58.
                                                  - 239 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                         B-64303EN/03
   NOTE
     Input/output Pins shaded by       are in pairs. Only one in each pair is usable.
     Pins shaded by       are those for forwarding signals. Pins with the same name
     are connected directly to one another.
                                         - 240 -
B-64303EN/03                                         9.CONNECTION OF I/O Link SLAVE DEVICES
                                                                        CA64(OUT)
                                                                        01 +24V
                            24VDC power¹                                02 0V
                                                                        03
     NOTE
     1 Both connectors CA64(IN) and CA64(OUT) are same specification. And there is
       not indication of (IN) and (OUT) on the PCB.
     2 Power supply for the operator's panel must not turn off at operation. If +24V is
       turned off at operation, CNC happen to get system alarm(Communication alarm
       between CNC and operator's panel). +24V for operator's panel must be supplied
       before or same time CNC power on.
                                                     - 241 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                                 B-64303EN/03
                   +5V terminals are for an optical I/O Link adapter. They are not necessary when connecting with a metal cable.
                   A line for the +5V terminal is not required when the Optical I/O Link Adapter is not used.
Shield
                                                           Ground
                                                           plate
                                              Recommended wire material:
                                              A66L-0001-0284#10P (#AWG28 × 10 pairs)
                                                            - 242 -
B-64303EN/03                                                 9.CONNECTION OF I/O Link SLAVE DEVICES
                                    (2a2b)
                                             ESPCM1                                  ESPCM1
                                                       B04                B03                     +24V
                                                EON
                                                        A01                    A01                        EON
                                               COM1
                                                        A02                    A02                    COM
                        OFF switch (SB3)
                                               EOFF
                                                        B01                    B01                        EOFF
                                               COM2
                                                        B02                    B02
                                                             - 243 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                B-64303EN/03
   NOTE
     Connection of Xm+0.0 to Xm+0.7, Xm+1.0 to Xm+1.4 shows when the Sub
     panel is used.
                                    - 244 -
B-64303EN/03                               9.CONNECTION OF I/O Link SLAVE DEVICES
     NOTE
     1 Xm+3.0 to 3.7 have a common line that is possible to select the source/sink
       type. If DICOM (CM69-B06pin) is connected to +24V, the DI signal logic is
       negative. But in this connection, if the DI signal wires happen to drop the ground
       level, the status of the DI signal is same as the DI signal is "ON". From the
       safety viewpoint, DICOM should be connected 0V.
     2 From the safety viewpoint, Emergency Stop signal must be assigned on the
       address Xm+0.0 to 0.7 or Xm+1.0 to 1.7 or Xm+2.0 to 2.7. As refer to the 5.
       DI/DO mapping, assign the Emergency stop DI.
     3 Xm+0.0 to 0.7, Xm+1.0 to 1.7 and Xm+2.0 to 0.7 common lines are fixed. So, if
       these DI pins in this address open, the status of these one stay "0". And in case
       of Xm+3.0 to 3.7 which have a selectable common line, if the DICOM
       (CM69-B06pin) is connected to 0V and these DI pins open, the status of these
       one stay "0". And if the DICOM are connected to +24V and these DI pins open,
       the status of these one stay "1". And if the DICOM is not connected to 0V or
       +24V and these DI pins open, the status of these one don't care.
                                           - 245 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                           B-64303EN/03
                                                   - 246 -
B-64303EN/03                                                 9.CONNECTION OF I/O Link SLAVE DEVICES
     NOTE
       Calculate the MPG cable max. Length as refer to the following calculation.
   MPG needs a 5VDC power supply and the voltage must be less than 0.2V dropping. (the 0.2V dropping
   includes the resistance in the cable.)
               0.1×R×2L
    0.2≥
                   m
   0.1 : MPG power supply current 0.1A
   R : Resistance per wire length (Ω/m)
   m : Wire Number (Both 0V and 5V)
   L : Cable length (m)
   Because
                  m
    L≤
                  R
                                                            - 247 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                     B-64303EN/03
    NOTE
    1 When Xm+1.5 to Xm+2.5 of connector JA58 are allocated as the Dis used for
      the axis selection and multiplier setting, Xm+1.5 to Xm+2.5 of connector CM68
      cannot be used.
    2 One DO is available for the manual pulse generator side at the user's direction.
      When this is used, Yn+5.3 of CM68 cannot be used, as in the case for DIs
      above.
                                                - 248 -
B-64303EN/03                                    9.CONNECTION OF I/O Link SLAVE DEVICES
                                               - 249 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                                                       B-64303EN/03
                 BIT
                               7                6                 5               4                 3             2                 1               0
  Key/LED
     Xm+4/Yn+0                 B4           B3                   B2              B1                 A4           A3             A2                  A1
     Xm+5/Yn+1                 D4           D3                   D2              D1                 D4           C3             C2                  C1
     Xm+6/Yn+2                 A8           A7                   A6              A5                 E4           E3             E2                  E1
     Xm+7/Yn+3                 C8           C7                   C6              C5                 B8           B7             B6                  B5
     Xm+8/Yn+4                 E8           E7                   E6              E5                 D8           D7             D6                  D5
     Xm+9/Yn+5                              B11                  B10             B9                              A11            A10                 A9
     Xm+10/Yn+6                             D11                  D10             D9                              C11            C10                 C9
     Xm+11/Yn+7                                                                                                  E11            E10                 E9
Address 1 2 3 4 5 6 7 8 9 10 11
    NOTE
      Xm+0.5 is a parity bit.
                                                                       - 250 -
B-64303EN/03                                        9.CONNECTION OF I/O Link SLAVE DEVICES
     NOTE
       Xm+1.2 is a parity bit.
   DI mapping should be assigned 1 group = 16 byte mapping and DO mapping should be assigned 1 group
   = 8 byte mapping. The reason is as follows.
   MPG interface(the counter for MPG) uses Xm+12 to Xm+14 area and it is fixed. And if MPG interface
   will be used, Xm+12 to Xm+14 area must be assigned. therefore, in case of 30i series and using MPG
   interface, DI mapping must be assigned 16 byte mapping. MPG counter area are directly processed by
   CNC software. So you must not use this area by customer ladder.
   When the MPG interface is not used, its DI area may be assigned to another I/O group. I/O mapping of
   the standard machine operator's panel can basically be assigned to any area of addresses. As for DI
   mapping, however, there are fixed signals directly monitored by the CNC. The fixed signals cannot be
   assigned to the keyswitch-input area. To use the fixed signals, therefore, assign them to an area other
   than the keyswitch-input area.
                                                    - 251 -
9.CONNECTION OF I/O Link SLAVE DEVICES         B-64303EN/03
                                  - 252 -
B-64303EN/03              9.CONNECTION OF I/O Link SLAVE DEVICES
                          - 253 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                        B-64303EN/03
9.9.6 Specifications
                                                         - 254 -
B-64303EN/03                                        9.CONNECTION OF I/O Link SLAVE DEVICES
EDIT EDIT mode selection signal; Sets program edit operation mode.
                         REF
                                    Reference position return mode selection; Sets reference position return mode.
                       RETURN
                         INC
                                    Step feed mode selection; Sets step feed mode.
                         JOG
HANDLE Manual handle feed mode selection; Sets manual handle feed mode.
                                    Teach-in jog (reach-in handle) mode selection signal; Sets teach-in jog
                        TEACH
                                    (teach-in handle) mode.
                                                    - 255 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                         B-64303EN/03
                          Manual feed axis selection; Axes are selected, when these buttons are set to
                          on in the jog feed mode or step feed mode.
                          Manual feed operation; Performs movement along selected axes when these
                          buttons are set on in the jog feed mode or step feed mode.
                TRVRS     Traverse; Performs jog feed at rapid traverse rate when this button is set to on.
                SPDL      Positive spindle rotation direction; Rotates the spindle motor in the positive
                 CW       direction.
                SPDL      Negative spindle rotation direction; Rotates the spindle motor in the negative
                CCW       direction.
                SPDL
                          Spindle stop; Stops the spindle motor rotation.
                STOP
                                           - 256 -
B-64303EN/03                                     9.CONNECTION OF I/O Link SLAVE DEVICES
     NOTE
     (*) Use the oil-proof sheet in the environment which oil is used for.
                                                 - 257 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                  B-64303EN/03
9.10.1        Overview
  The small machine operator's panel or small machine operator's panel B is a machine operator's panel
  connected to the CNC with an I/O Link. The operator's panel contains 30 keys, an emergency stop
  switch, and two override rotary switches.
    NOTE
      Use a 3-keystroke support model, which does not accept more than three
      simultaneous keystrokes. See Subsection 9.10.10.2, "Order specification".
                       JD1A (JD51A)
                              JD1A
                                                                      Small machine
                                                                       ¬Œ^‹@ŠB‘€  ì”Õoperator's panel
                                                     JD1B JD1A
                                                      Operator's
                                                        ‘€ ì”ÕI/O                      ƒL [ƒ{ [ƒh
                                                                                      Keyboard
                                                      panel I/O
                                                               CE53                  CE53
                               MPG                   JA3
                                                               CE54                  CE54
MPG
                               MPG
                                                        CPD1(OUT)                    CPD(IN)
                +24V +24
                     power supply
                         V“dŒ¹                       CPD1(IN)
                                                                                      CM65     CM66
                                                                       Emergency
                                                                        ”ñ í’âŽ~     Rotary
                                                                                     Û°Àذ Rotary
                                                                                            Û°Àذ
                                                                       stop½²¯Á
                                                                            switch   switch
                                                                                      ½²¯Á switch
                                                                                            ½²¯Á
                                                                             (SB1)   (SA1) (SA2)
                                                     - 258 -
B-64303EN/03                                             9.CONNECTION OF I/O Link SLAVE DEVICES
                                                                                            JD1B
                    I/O Link
                    JD1A  (JA44)
                    JD1A (JD51A)
JD1B
                                                              JD1A
                                                                                             Keyboard
                                                                                             ƒL [ƒ{ [ƒh
                          MPG                       JA3
                                                              CE72                    CE72
                          MPG
                                                       I/O board
                                                       I/Oƒ{ [ƒh
                          MPG
          General-purpose   DI/DO
                       ”Ä—pDI/DO                              CM66
          DI: 24 pointsDI:24“_                       CE73
          DO: 16 pointsDO:16“_
                                                              CM65
                    +24VDC
                     +24 VDC                                  CE74
                                                     CA102
                  power“dŒ¹
                        supply
                                                                             ”ñ í’âŽ~
                                                                            Emergency       Rotary
                                                                                            Û°Àذ       Rotary
                                                                                                        Û°Àذ
                                                                            stop switch
                                                                               ½²¯Á         switch
                                                                                             ½²¯Á       switch
                                                                                                         ½²¯Á
                                                                              (SB1)         (SA1)       (SA2)
    The small machine operator's panel B is different from the small machine operator's panel in connection as
        ¬Œ^‹@ŠB‘€ ì”ÕB‚Í ¬Œ^‹@ŠB‘€ ì”Õ‚Æ”äŠr‚µ‚Ä A‰º‹L‚Ì Ú‘±‚ªˆÙ‚È‚è‚Ü‚· B
    described
        E Ӗ below.
              í’âŽ~ƒXƒCƒbƒ` (SB1) ‚ðƒRƒlƒNƒ^CE74‚É Ú‘±‚·‚邱‚Æ‚ª‚Å‚«‚Ü‚· BCE74‚ÍI/Oƒ{ [ƒh“à‚ŔėpDI‚Ì
    - ƒAƒhƒŒƒXXm2+4.4‚Æ
       The emergency stop switch  (SB1) can be
                             Ú‘±‚³‚ê‚Ä‚¢‚Ü‚·  B connected to connector CE74. Connector CE74 is connected to
       general-purpose DI address Xm2+4.4 in
        E DI:24“_ ADO16“_‚̔ėpDI/DO‚ð          the I/O board.
                                              Ú‘±‚·‚邱‚Æ‚ª‚Å‚«‚Ü‚· B
    - The following general-purpose DI/DO points can be connected: 24 DI points and 16 DO points.
     NOTE
     1 If this operator's panel is used together with a unit (such as an I/O module for
       branching) connected to an I/O Link having another MPG interface, only the
       MPG interface of the unit (module) nearest the CNC connected to the I/O Link
       will be enabled by default. To enable the MPG interfaces of the second and
       subsequent units, set appropriate parameters. For details, refer to the manual
       supplied with the NC used.
     2 The following screw-on connectors cannot be used for the connection of an I/O
       Link and manual pulse generator.
         Connectors that cannot used on the cable side
                                                 Specification               Manufacturer
         Connector case                         FI-20-CV7             Hirose Electric Co., Ltd.
         Connector case and connector           FI30-20S-CV7          Hirose Electric Co., Ltd.
                                                        - 259 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                          B-64303EN/03
                                                                            CPD1
                                                                             01
                                                                             01 +24V
                                                                                 +24
                    24VDC “dŒ¹                                               02  V0V
                    DC24V                                                    02   0V
                    power supply                                             03
                                                                             03
                    Recommended  connector
                    CPD1ƒP [ƒuƒ‹‘¤           for use on the CPD1 cable side
                                     „ §ƒRƒlƒNƒ^
                       A02B-0120-K324(‰º‹L‚̃RƒlƒNƒ^ƒnƒEƒWƒ“ƒO‚ƃRƒ“ƒ^ƒNƒg‚ðŠÜ‚Þ)
                      A02B-0120-K324  (including the following connector housing and contact)
                         ƒnƒEƒWƒ“ƒO3ƒsƒ“
                             Housing: Japanj AMP 1-178288-3 (3 pins)
                         ƒRƒ“ƒ^ƒNƒg
                             Contact: Japan AMP 1-175218-5
    NOTE
      The +24V power supplied to this connector must be turned OFF during
      operation. Turning it OFF will cause a CNC communication alarm to be
      generated. Make sure that at power ON, the supply of this +24V power is at the
      same time as or earlier than the supply of the power to the CNC and that at
      power OFF, it is at the same time as or later than the interruption of the power to
      the CNC.
      When the CNC connected to this operator's panel with an I/O Link is to be turned
      off, the power to this operator's panel must also be turned off.
  With the small machine operator's panel B, the input (pin 02) of the emergency stop input connector
  (CE74) is connected to general-purpose DI address Xm2+4.4 in the I/O board as shown below.
  When the general-purpose DI start address is X0004, the input of CE74 is X0008.4, to which the signal of
  the emergency stop switch can be directly connected.
                                                     - 260 -
B-64303EN/03                                       9.CONNECTION OF I/O Link SLAVE DEVICES
   When the input signal (Xm2+4.4) is used as an emergency stop signal, the signal should be input to pin
   02 of the emergency stop input connector (CE74) or pin A08 of the general-purpose DI/DO connector
   (CE73).
                                                  - 261 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                          B-64303EN/03
                                 GROUNDING PLATE
                                            Cable                       Wiring
  Calculate the maximum allowable length of the cable for the manual pulse generator, with the method
  described below.
  Manual pulse generators are supplied with 5 VDC power. The drop in voltage due to cable resistance
  must not exceed 0.2V (on 0V and 5V lines in total).
         0.1×R×2L
  0.2≧
             m
  Where
         m    0.1   :       Power supply current for the manual pulse generator = 0.1 A
  L≦
         R    R     :       Wire resistance per unit length [Ω/m]
              m     :       Number of 0-V wires (= number of 5-V wires)
              L     :       Cable length [m]
  Therefore,
            3
   L≦           =76.75 [m]
         0.0394
  Example: When cable A66L-0001-0286 is used
  This cable consists of three pairs of signal lines and six power wires (20/0.18, 0.0394 Ω/m).
  When these three cables are used for 0V and 5V lines, the cable length is:
                                                          - 262 -
B-64303EN/03                                        9.CONNECTION OF I/O Link SLAVE DEVICES
   Thus, the length is 76.75 m. (Because of the applicable regulation of FANUC, however, the length is
   limited to 50 m.)
   For two units, the cable can be extended to 38.37 m.
   For three units, it can be extended to 25.58 m.
+24V
                        Xm+1.2                                CM66(A05)
                                                              CM66(A05)       B
                                   RV
                        Xm+1.3                                CM66(B03)
                                                              CM66(B03)       E
                                   RV
                        Xm+1.4                                CM66(B04)
                                                              CM66(B04)       C
                                   RV
                        Xm+1.5                                CM66(B02)
                                                              CM66(B02)       G
                                   RV
0V
                                                    - 263 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                            B-64303EN/03
    NOTE
    1 Xm2 and Yn2 indicate the general-purpose DI/DO start addresses in the I/O
      Link.
    2 The B01 pin, +24 V, is 24 VDC output for DI signals. Do not supply 24 VDC to
      this pin from the outside.
                                                   - 264 -
B-64303EN/03                    9.CONNECTION OF I/O Link SLAVE DEVICES
                                - 265 -
9.CONNECTION OF I/O Link SLAVE DEVICES      B-64303EN/03
                                  - 266 -
B-64303EN/03                   9.CONNECTION OF I/O Link SLAVE DEVICES
                               - 267 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                           B-64303EN/03
                BIT
                           5              4                     3       2              1              0
   Key/LED
     Xm+4/Yn+0             A6            A5                 A4          A3            A2             A1
     Xm+5/Yn+1            B6/            B5/               B4/          B3            B2             B1
                      Without LED    Without LED       Without LED
     Xm+6/Yn+2            C6/            C5/               C4/          C3            C2             C1
                      Without LED    Without LED       Without LED
     Xm+7/Yn+3            D6/            D5/               D4/          D3            D2             D1
                      Without LED    Without LED       Without LED
     Xm+8/Yn+4            E6             E5                E4           E3            E2             E1
                                                  Key
                                                   ƒL switch/LED
                                                       [ƒXƒCƒbƒ`arrangement
                                                                 ^LED”z—ñ
                          Address
                        ƒAƒhƒŒƒX              1   2         3       4   5     6
                                                      - 268 -
B-64303EN/03                                              9.CONNECTION OF I/O Link SLAVE DEVICES
     NOTE
     1 Xm+0.5 and Xm+1.4 are parity bits.
     2 If parity bits are used, the output timing of override signals may differ from that of
       the parity bits.
                                                          - 269 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                          B-64303EN/03
                                                    - 270 -
B-64303EN/03                                      9.CONNECTION OF I/O Link SLAVE DEVICES
JD51A
                                                 - 271 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                       B-64303EN/03
  Xm1 and Yn1 indicate the start addresses for the machine operator's panel section of the small machine
  operator's panel B in the I/O Link, while Xm2 and Yn2 indicate the start addresses for the
  general-purpose DI/DO section.
                                               Module name
                                                                 DI                       DO
   Machine operator's panel section                   CM16I (16byte)            CM08O (8byte)
   General-purpose DI/DO section                      CM06I (6byte)             CM02O (2byte)
  To use a DO alarm in the general-purpose DI/DO space, 16-byte allocation is required. In this case, set
  CM16I as a DI module name in the general-purpose DI/DO section.
                                                - 272 -
B-64303EN/03                                    9.CONNECTION OF I/O Link SLAVE DEVICES
   When DI addresses in the general-purpose DI/DO section are allocated starting at X0004, the fixed
   signals such as SKIP, *DECn, and *ESP can be allocated as shown below.
                                                - 273 -
9.CONNECTION OF I/O Link SLAVE DEVICES                       B-64303EN/03
                                  - 274 -
B-64303EN/03                       9.CONNECTION OF I/O Link SLAVE DEVICES
                                   - 275 -
9.CONNECTION OF I/O Link SLAVE DEVICES                         B-64303EN/03
9.10.8.2 Layout of the key sheet (Same for both the small machine
           operator's panel and small machine operator's panel B)
M series
                                  - 276 -
B-64303EN/03   9.CONNECTION OF I/O Link SLAVE DEVICES
T series
               - 277 -
9.CONNECTION OF I/O Link SLAVE DEVICES                       B-64303EN/03
                                  - 278 -
B-64303EN/03                                        9.CONNECTION OF I/O Link SLAVE DEVICES
9.10.10          Specifications
9.10.10.1 Environmental requirement
    Temperature around a   At operation               0°C to 55°C
    unit                   Storing or transporting    -20°C to 60°C
    Temperature variance   Max.            1.155°C/min
    Humidity               Normally                           75% or less (Relative humidity)
                           Short time (Within one month       95% or less (Relative humidity)
    Vibration              Operating                          0.5G or less
    Atmosphere             Normal FA atmosphere (Consult us when using the system under environments with
                           higher degree of dust, coolant, or organic solution.)
                                                    - 279 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                     B-64303EN/03
EDIT EDIT mode selection signal; Sets program edit operation mode.
                                HANDLE          Manual handle feed mode selection; Sets manual handle feed
                                                mode.
                                  TEACH         Teach-in jog (reach-in handle) mode selection signal; Sets teach-in
                                                jog (teach-in handle) mode.
                                  SINGLE        Single block signal; Executes program one by one. This key is
                                  BLOCK         used to check a program.
                                  BLOCK         Block skip: Pressing this button during automatic operation
                                   SKIP         causes the block under execution to stop, skipping to the end of
                                                block (;).
                                  PRG           Program stop (output only); Turns on the LED on the button when
                                  STOP          automatic operation is stopped by M00 specified in the program.
                                                       - 280 -
B-64303EN/03                                       9.CONNECTION OF I/O Link SLAVE DEVICES
13 mm
13 mm
                                                  - 281 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                 B-64303EN/03
      NOTE
        If a small machine operator's panel customized in this way is to be maintained
        (replaced), the application of the sticker must be performed by the customer.
        The customer must prepare a sticker. Once peeled off, the transparent sheet
        cannot be reused. Another transparent sheet must be used.
  Items to be repaired
                                   Name                                  Ordering specification      Remarks
   Operator's panel I/O printed circuit board for small machine          A20B-2002-0470
   operator's panel
   Keyboard printed circuit board for small machine operator's panel     A20B-2004-0220
   Small machine operator's panel                                        A02B-0299-C152#M         M series
                                                                         A02B-0299-C152#T         T series
   Operator's panel I/O printed circuit board for small machine          A20B-2004-0160
   operator's panel B
   Keyboard printed circuit board for small machine operator's panel B   A20B-2004-0170
   Small machine operator's panel B                                      A02B-0309-C151#M         M series
                                                                         A02B-0309-C151#T         T series
9.11.1          Overview
  The terminal type I/O module can be connected to the I/O Link, and the specifications of the existing
  connector panel I/O module (Section 9.1) are applicable to the terminal type I/O module. The terminal
  type I/O module has the following features:
  •     Input/output signals are connected on a spring-type terminal block (ferrule terminal block).
  •     A terminal block can be attached to or detached from the main body of the module.
  •     An LED for state indication is provided for each I/O signal.
  •     The digital output circuit is photocoupler-insulated.
  •     The terminal type I/O module can be installed on the DIN rail.
  •     By using expansion modules, the maximum number of digital input points can be extended to 96 and
        the maximum number of digital output points can be extended to 64.
  •     An expansion module with a manual pulse generator (MPG) interface is available.
      NOTE
        Expansion module D has no LED for state indication.
                                                       - 282 -
B-64303EN/03                                          9.CONNECTION OF I/O Link SLAVE DEVICES
CNC, etc.
                                                                                            Up to 3 expansion
                                                                                            modules can be
                                                                                            connected.
                                   Input    Output                   Input    Output
                                  24 points 16 points               24 points 16 points
     NOTE
       A cable-side terminal block is shipped with the main unit. Spare terminal blocks
       are used for replacement.
   For the specifications (such as signal input requirements) specific to each module, see the relevant pages
   of each item.
                                                      - 283 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                 B-64303EN/03
                                                   Digital output
  Number of points                          16 points
  Common                                    8 points/common (8 common terminals)
  Rated output voltage                      12 VDC to 24 VDC (+20%, −15%)
  Rated output current                      0.2 A/pt
  Polarity                                  Source type
  Maximum voltage decrease when ON          0.63 V (load current × 1.25Ω)
  Maximum leakage current when OFF          40 μA
  Insulation method                         Photocoupler insulation
  Output protection function                Protection against overheat and overcurrent
  Response time                             Driver delay time: 50μs(MAX)
                                            In addition, the I/O Link transfer time between the CNC and the I/O
                                            module and the ladder scan cycle time (by the CNC) need to be taken
                                            into account.
                                                     - 284 -
B-64303EN/03                                            9.CONNECTION OF I/O Link SLAVE DEVICES
 Expansion module C
                                                     Digital output
    Number of points                          16 points
    Common                                    4 points/common
    Rated output voltage                      12 VDC to 24 VDC (+20%, −15%)
    Rated output current                      2 A/pt (4 A/common)
    Polarity                                  Source type
    Maximum voltage decrease when ON          0.18 V (load current × 0.09Ω)
    Maximum leakage current when OFF          0.1 mA
    Insulation method                         Photocoupler insulation
    Output protection function                Protection against overheat, overcurrent, short-circuiting, and open load
    Response time                             Driver delay time: 50μs(MAX)
                                              In addition, the I/O Link transfer time between the CNC and the I/O
                                              module and the ladder scan cycle time (by the CNC) need to be taken
                                              into account.
 Expansion module D
                                                      Analog input
    Number of input channels                  4 channels
    Analog input range                        -10 VDC to +10 VDC                   Voltage input or current input can
                                              (Input resistance: 4.7 MΩ)           be selected on a
                                                                                   channel–by–channel basis by
                                              -20 VDC to +20 mA
                                                                                   wiring.
                                              (Input resistance: 250Ω)
    Digital conversion range                  12 bits (binary), two's complement representation
    Input/output correspondence
                                                          Analog input         Digital output
                                                             +10 V                  +2000
                                                         +5 V or +20 mA             +1000
                                                           0 V or 0 mA                0
                                                         -5 V or -20 mA             -1000
                                                              -10 V                 -2000
    Resolution                                5 mV or 20 μA
    Overall precision                         Voltage input: ±0.5% (with respect to full scale)
                                              Current input: ±1.0% (with respect to full scale)
    Maximum input voltage/current             ±15 V/±30 mA
    A-D conversion time                       2 ms or less
    Minimum update period of digital output   Ladder scan period of CNC connected
    Number of occupied input/output points    DI = 3 bytes, DO = 2 bytes(NOTE)
     NOTE
       This module has four analog input channels but has only one 12-bit digital output
       channel within the occupied input points (3 bytes). Namely, a channel for
       conversion is selected dynamically using a ladder program. Channel switching
       DO points for selecting a channel are present in the occupied output points (2
       bytes).
       (See "Addresses of expansion module D" in Subsection 9.11.6.1, "Address
       map".)
                                                       - 285 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                 B-64303EN/03
9.11.2.6 Weight
                           Module name                                              Weight (g)
                         Basic module                                                   420
                      Expansion module A                                                400
                      Expansion module B                                                380
                      Expansion module C                                                440
                      Expansion module D                                                400
                                                   - 286 -
  B-64303EN/03                                             9.CONNECTION OF I/O Link SLAVE DEVICES
φD2
Insulation cover
L L2
                                                                          φD1
                                                      The dimensions indicated below are based on the products of
                                                                        Weidmuller Color., Ltd.
Cross sec-                                                                              Inner                 Outer
                                                 Electric wire            Length of                Inner
tional area   JIS VSF             UL1007 UL1015 sheath          Overall              diameter of              diam-
                        JIS IV                         stripped            metallic      con-
                                                                                                 diameter
of electric     KIV          2                      length       length                                      eter of
    wire           2    (mm )                                                part      ductor    of sheath
               (mm )              (AWG) (AWG)      (mm)         L1 (mm)                                      sheath
       2
   (mm )                                                                   L2 (mm) D1 (mm) D2 (mm)
                                                                                                            D3 (mm)
                                                      10           14          8
   0.5           -         -        20      -                                              1         2.6       3.1
                                                      12           16         10
                                                      10           14          8
   0.75         0.5        -        18     20                                             1.2        2.8       3.3
                                                      12           16         10
                                                      10           14          8
   1.0         0.75       0.9        -     18                                             1.4         3        3.5
                                                      12           16         10
     NOTE
       Use a ferrule terminal from the viewpoint of long-term reliability.
                                                          - 287 -
9.CONNECTION OF I/O Link SLAVE DEVICES                     B-64303EN/03
                                                             Unit: mm
                                            280
            150
                                  - 288 -
B-64303EN/03                                             9.CONNECTION OF I/O Link SLAVE DEVICES
                                                                                      DO terminal block T2
        DO terminal block T1                                                          Label color: Yellow green
        Label color: Light blue
                                                                                      DI terminal block T4
                                                                                      Label color: Pink
           DI terminal block T3
           Label color: Yellow
View from A
                                                      - 289 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                      B-64303EN/03
                                                                               DO terminal block T2
       DO terminal block T1                                                    Label color: Yellow green
       Label color: Light blue
                                                                               DI terminal block T4
                                                                               Label color: Pink
          DI terminal block T3
          Label color: Yellow
JA3 (MPG)
Rotary switch
View from A
   NOTE
     Be sure to connect expansion module A beside the basic module.
                                            - 290 -
B-64303EN/03                                      9.CONNECTION OF I/O Link SLAVE DEVICES
                                                                                 DI terminal block T4
                                                                                 Label color: Pink
      DI terminal block T3
      Label color: Yellow
Rotary switch
View from A
                                                  - 291 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                B-64303EN/03
    DO terminal block T1
    Label color: Light blue
 DO terminal block T2
 Label color: Yellow green
Rotary switch
View from A
                                                  - 292 -
B-64303EN/03                         9.CONNECTION OF I/O Link SLAVE DEVICES
Rotary switch
View from A
                                     - 293 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                    B-64303EN/03
9.11.4        Installation
Notes on installation
  1) Use a module in a completely sealed cabinet.
  2) Be sure to install a module on a vertical plane and allow a clearance of 100 mm or more above and
     below the module. Do not place a device that generates a large amount of heat below the module.
2-M4
                                               - 294 -
B-64303EN/03                                         9.CONNECTION OF I/O Link SLAVE DEVICES
DIN rail
Locking section
   1)     Place the hook of the module onto the top of the DIN rail.
   2)     Push the module until it clicks into place.
        NOTE
          Ensure that the locking section is not left lowered.
2) Method of dismounting
DIN rail
        NOTE
          When dismounting the module, be careful not to damage the locking section by
          applying an excessive force.
                                                     - 295 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                                         B-64303EN/03
9.11.5 Connection
                  I/O Link
                    JD51A
                                                                                    JD1B                     JD1A
                                                                                    T1
   24 VDC power supply                                                                                     Relay, etc.
                                                                   Terminal block
                              CP11A
                                                                                                                             16 DO points
                                                                                    T2
                                          Basic module                                                     Relay, etc.
         External device      CP11B                                                                           Switch, etc.
                                                                                    T3
                                                                                                                                  24 DI
                                                                                                                                  points
                              CA105
                                                                                    T4
        Inter-module                                                                                          Switch, etc.
        cable A
                                                                                            Power supply for load
                                                 or                                                        Relay, etc
                              CA106
         MPG                          Expansion module B, C or
                                                D                                                             Switch, etc.
                                                                                    T3 T4
                                                                                                                                  24 DI
        MPG                   CA105        Without MPG                                                                            points
                                                                                                              Switch, etc.
                                                                                                           Relay, etc.
       Inter-module cable                                                                                                    16 DO points
                                                                                    T2
       A                                                                                                    Relay, etc.
                              CA106   Expansion module B, C,
                                               or D
                                                                                    T3 T4
                                                                                                              Switch, etc.
                                           Without MPG                                                                            24 DI
                              CA105                                                                                               points
                                                                                                              Switch, etc.
       cable A
                                                                   Terminal block
                                                                                                              Switch, etc.
                              CA105                                                                                               24 DI
                                                                                                              Switch, etc.        points
    NOTE
      Expansion module C does not have DI points.
      With expansion module D, only the terminal blocks for analog input, T1 and T2,
      are available.
                                              - 296 -
B-64303EN/03                                                   9.CONNECTION OF I/O Link SLAVE DEVICES
                      Key arrangement
                                Recommended cable (for using external power): A02B-0124-K830
                                 (5 m long, with an M3 terminal on the 24 V power supply side)
   The 24 VDC input to CP11A (A1, A2) can be output from CP11B (B1, B2) for branching. CP11B (B1,
   B2) is connected as shown below. In this case, the external 24 VDC power supply needs to provide
   CP11A (A1, A2) with a current which is equal to the sum of the current consumed by the control unit and
   the current used via CP11B (B1, B2).
                      Basic module
                     CP11A
                                     For input
                           A3        A2        A1                                        External device
                                     0V
                                                           Connected for branching
                           B3        B2        B1
                                     0V
                     CP11B
                         For branching                  Tyco Electronics AMP
                                                                                Make a selection matching
                                                        2-178288-3 (housing)
                                                                                     the external device.
                                                        1-175218-5 (contact)
                     Key arrangement
     NOTE
     1 Ensure that +24 V is supplied either when or before the power to the CNC is
       turned on, and that +24 V is removed either when or after the power to the CNC
       is turned off.
     2 When turning off the power to the CNC control unit, be sure to turn off the power
       to the terminal type I/O module and other slave I/O units connected via the I/O
       Link as well.
                                                               - 297 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                         B-64303EN/03
      NOTE
        The terminal blocks on the cable side are shipped with the terminal type I/O
        module.
                                                       - 298 -
B-64303EN/03                                         9.CONNECTION OF I/O Link SLAVE DEVICES
Expansion module C
   -    Assignment of signals for output
                                T1 (Label color: Light blue)     Label indication
                                       1     DOCOM0                    V
                                       2      Yn+0.0                   0
                                       3       0V-0                    G
                                       4      Yn+0.1                   1
                                       5      Yn+0.2                   2
                                       6       0V-0                    G
                                       7      Yn+0.3                   3
                                       8     DOCOM1                    V
                                       9      Yn+0.4                   4
                                       10      0V-1                    G
                                       11     Yn+0.5                   5
                                       12     Yn+0.6                   6
                                       13      0V-1                    G
                                       14     Yn+0.7                   7
       NOTE
         The terminal blocks on the cable side are shipped with the terminal type I/O
         module.
                                                     - 299 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                           B-64303EN/03
Expansion module D
  -    Assignment of signals for analog input
                               T1 (Label color: Yellow)       Label indication
                                      1        JMP0                  J
                                     2         INP0                  +
                                     3        INM0                   -
                                     4        COM0                   C
                                     5         FG0I                  F
                                     6        FG0O                   F
                                     7
                                     8        JMP1                   J
                                     9         INP1                  +
                                     10       INM1                   -
                                     11       COM1                   C
                                     12        FG1I                  F
                                     13       FG1O                   F
                                     14
      NOTE
        The terminal blocks on the cable side are shipped with the terminal type I/O
        module.
                                                   - 300 -
B-64303EN/03                                                               9.CONNECTION OF I/O Link SLAVE DEVICES
                                       0   ○T3-2               Xm+0.0           I
                                       1   ○T4-2               Xm+0.1           I
                                       2   ○T3-3               Xm+0.2           I
                                       3   ○T4-3               Xm+0.3           I
                                       4   ○T3-4               Xm+0.4           I
                                       5   ○T4-4               Xm+0.5           I
                                       6   ○T3-5               Xm+0.6           I
                                       7   ○T4-5               Xm+0.7           I                   I :入力回路
                                                                                                        LE
                                        0 ○T3-7                Xm+1.0           I                                  I Input circuit
   Switch, etc.                         1 ○T4-7                                 I                                 レシーバ
                                        2 ○T3-8                Xm+1.1           I                                    LED
                                                                                            入力端子
                                        3 ○T4-8                Xm+1.2           I                                             Receiver
                                        4 ○T3-9                                 I
                                                                                                        Input pin
                                        5 ○T4-9                Xm+1.3           I
                                        6 ○T3-10                                I
                                        7 ○T4-10               Xm+1.4                                    0V
                                                                                I
                                                                                                                        0V
                                       0   ○T3-12              Xm+2.0           I
                                       1   ○T4-12                               I
                                                               Xm+2.1
                                       2   ○T3-13                               I
                                       3   ○T4-13              Xm+2.2           I
                                       4   ○T3-14                               I
                                       5   ○T4-14              Xm+2.3           I
                                       6   ○T3-15                               I
                                       7   ○T4-15              Xm+2.4           I
                                                                                  24V
          Control power                                                 Fuse                                                             24V
                       24VIN             ○A1                                                                                                    ○
                                       CP11                                2A       C                                EXPANSION
                        0VIN             ○A2
                                                                                                              (Connected to expansion module)
          Ex-                              ○B1
                      24VOUT                                                                                                                   ○
          ternal
                                      CP11                                                                                               0V
          devic
          e            0VOUT            ○B2
                                                                                           0V                 C     : Control circuit
    NOTE
      The circuitry enclosed in the dashed rectangle shown above is mounted on the
      basic module only. In the case of an expansion module, 24 V for DICOM is
      supplied via the extension cable from the basic module or the expansion module
      at the preceding stage.
                                                                        - 301 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                             B-64303EN/03
 DO connection
                                                                          Inside module
        Indication on terminal                                Terminal
             block label         Terminal block and pin No.   name
                                        V ○T1-1               DOCOM0
                                        V ○T2-1               DOCOM0
                                 L       0 ○T1-2              Yn+0.0       O
                                 L       1 ○T2-2              Yn+0.1       O
                                 L       2 ○T1-4              Yn+0.2       O
      +
                                         3 ○T2-4              Yn+0.3       O
    Regulated power              L
     supply for load             L       4 ○T1-5              Yn+0.4       O
                                 L       5 ○T2-5              Yn+0.5       O
      -
                                 L       6 ○T1-7              Yn+0.6       O
                                         7 ○T2-7              Yn+0.7       O
                                 L
                                        G ○T1-3                0V-0
                                        G ○T2-3                0V-0                                      Address number
                                                                                                         Bit number
                                        G ○T1-6                0V-0
                                        G ○T2-6                0V-0
                                        V ○T1-8                DOCOM1
                                        V ○T2-8                DOCOM1
                                 L      0 ○T1-9               Yn+1.0       O
                                 L      1 ○T2-9               Yn+1.1       O
                                 L      2 ○T1-11              Yn+1.2
                                                                           O
      +                                 3 ○T2-11              Yn+1.3
                                 L                                         O
   Regulated power
                                 L      4 ○T1-12              Yn+1.4       O
    supply for load                                                                                      O : Output circuit
                                        5 ○T2-12              Yn+1.5                      DOCOM0
                                 L                                         O
      -                                                                                        or
                                 L      6 ○T1-14              Yn+1.6       O              DOCOM1
                                                                                                             Internal
                                 L      7 ○T2-14              Yn+1.7       O              Output pin
                                        G ○T1-10               0V-1                                           circuit
                                                                                                   LED
                                        G ○T2-10               0V-1
     L : Load
                                                                                               0V-0
                                        G ○T1-13               0V-1
                                                                                                 or
                                        G ○T2-13               0V-1                            0V-1
   NOTE
     Be sure to connect the 0 V signal from the regulated power supply for load to the
     0 V terminal (with label indication "G") of the module. Otherwise, a load error can
     occur.
                                                                - 302 -
B-64303EN/03                                    9.CONNECTION OF I/O Link SLAVE DEVICES
Expansion module C
                                                              Inside module
           Indication on                       Terminal
        terminal block label                    name
V ○T1-1 DOCOM0
                                   0 ○T1-2    Yn+0.0      O
         +                     L
    Regulated power                1 ○T1-4    Yn+0.1      O
                               L
     supply for load               2 ○T1-5    Yn+0.2      O
                               L                                                        Address number
                                   3 ○T1-7    Yn+0.3      O
         -                     L                                                        Bit number
                                   G ○T1-3      0V-0
                                   G ○T1-6      0V-0
V ○T1-8 DOCOM1
        +                          4 ○T1-9    Yn+0.4      O
                               L
     Regulated power               5 ○T1-11   Yn+0.5      O
                               L
      supply for load              6 ○T1-12   Yn+0.6
                               L                          O
        -                          7 ○T1-14   Yn+0.7      O
                               L
                                   G ○T1-10     0V-1
                                   G ○T1-13     0V-1
V ○T2-1 DOCOM2
        +                      L   0 ○T2-2     Yn+1.0     O
     Regulated power               1 ○T2-4     Yn+1.1     O
                               L
      supply for load
                                   2 ○T2-5     Yn+1.2     O
                               L
        -                          3 ○T2-7     Yn+1.3     O
                               L
                                   G ○T2-3       0V-2
                                   G ○T2-6      0V-2
                                   V ○T2-9    DOCOM3
                                                                                        O : Output circuit
        +                      L   4 ○T2-10    Yn+1.4     O          DOCOMn
     Regulated power           L   5 ○T2-12    Yn+1.5     O                                 Internal
      supply for load              6 ○T2-13    Yn+1.6     O
                                                                     Output pin
                               L                                                                circuit
        -                          7 ○T2-15    Yn+1.7     O                   LED
                               L
                                   G ○T2-11       0V-3
                                                                         0V-n
                                   G ○T2-14       0V-3
                                                                                    n: 0 to 3
                  L : Load
     NOTE
       Be sure to connect the 0 V signal from the regulated power supply for load to the
       0 V terminal (with label indication "G") of the module. Otherwise, a load error can
       occur.
                                               - 303 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                             B-64303EN/03
Expansion module D
  In the example of connection below, CH1 is used for voltage input, CH3 is used for current input, and
  CH2 and CH4 are not used.
                                            Label indication                                       250Ω
                                                                                                Inside module
                                                                                     Terminal
               For       voltage                  CH1           Terminal block No.
               i   t                                                J ○T1-1          JMP0
                                                                                      name
                                                                    + ○T1-2          INP0
     Voltage source +                                               - ○T1-3          INM0
                   -                                                C ○T1-4          COM0
                GND                                                 F ○T1-5          FG0I
                                                                    F ○T1-6          FG0O
                                                                                                    250Ω
                                                                        ○T1-7
                                          NOTE 4                    J                JMP1
                                                                        ○T1-8
                                                   NOTE 3           +                INP1
                                                                        ○T1-9
                                                                    -                INM1
                               NOTE 2                                   ○T1-10
                                                        CH2         C                COM1
                                                                        ○T1-11
                                                                    F                FG1I
                                                                        ○T1-12
                                                                    F                FG1O
                                                 NOTE 1                 ○T1-13                                  Internal
                                                                                                  250Ω
                                                                      ○T1-14                                     circuit
           For current input                      CH3               J ○T2-1          JMP2
     Current source +                                               + ○T2-2          INP2
                    -                                               - ○T2-3          INM2
                 GND                                                C ○T2-4          COM2
                                                                    F ○T2-5          FG2I
                                                                    F ○T2-6          FG2O
                                                                        ○T2-7                      250Ω
                                        NOTE 4                      J ○T2-8          JMP3
                                                   NOTE 3
                                                                    + ○T2-9          INP3
                                                                    - ○T2-10         INM3
                                                      CH4
                                                                C ○T2-11             COM3
                                                                    F ○T2-12         FG3I
                                                                    F ○T2-13         FG3O
                                                                        ○T2-14
                                                                        ○T2-15
    NOTE
    1 When JMPn and INPn (n=0, 1, 2, 3) are connected with each other, the channel
      becomes a current input channel.
    2 For the connection cable, use a shielded twisted pair.
    3 In the figure above, the shield is connected to FGnI for grounding to FGnO.
      However, the shield may be directly connected to frame ground by using a cable
      clamp without using FGnI and FGnO.
    4 When a voltage source (current source) has a GND terminal as shown above,
      connect COMn to the terminal. When no GND terminal is provided, connect
      INMn and COMn with each other on the analog input module as indicated by the
      dotted line. COMn of each channel is connected to the common analog ground
      inside the module.
                                                          - 304 -
B-64303EN/03                                        9.CONNECTION OF I/O Link SLAVE DEVICES
                                                    - 305 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                          B-64303EN/03
                                                             Recommended screwdriver
                                                               Weidmuller
                                                               Product number: SDI 0.4X2.5X80
    NOTE
      Do not pry the screwdriver in a clamp. Otherwise, the terminal block can be
      damaged.
                                                 - 306 -
B-64303EN/03                                        9.CONNECTION OF I/O Link SLAVE DEVICES
Terminal block
Mounting screw
                                                    - 307 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                            B-64303EN/03
9.11.6 Settings
  Basically, the module is allocated a group of DI addresses (16 bytes) and a group of DO addresses (8
  bytes). Add or remove up to three expansion modules by hardware as required. The reason is explained
  below.
  The MPG interface (MPG counter) occupies a DI space from Xm+12 to Xm+14. These addresses are
  fixed regardless of whether expansion module 2 or 3 is used, and Xm+12 to Xm+14 must be allocated as
  a DI work area to enable the use of the MPG. Therefore, when using an MPG with the i series, allocate DI
  addresses in units of 16-byte groups. The CNC directly processes the value of the MPG counter. So,
  ensure that the ladder does not use this area.
  DI address Xm+15 is used to detect an overheating alarm issued for a cause such as overcurrent of the IC
  used for a DO driver. (For details, see Subsection 9.11.6.2, "DO alarm detection".) Address Xm+15 is
  fixed regardless of whether expansion module 2 or 3 is used. This address must be allocated as a work
  area before this address can be used. When using this area, therefore, allocate DI addresses in units of
  16-byte groups.
                                                   - 308 -
B-64303EN/03                                          9.CONNECTION OF I/O Link SLAVE DEVICES
   D00 to D11 represent 12-bit digital output data (represented as a complement). D00 corresponds to the
   weight of 20, and D11 corresponds to the weight of -211. This means that D11 corresponds to the sign bit
   of a two's complement.
   CHA and CHB select a converted data channel. This means that when the two bytes above are read by a
   ladder program, A-D converted data on an input channel selected by CHA and CHB is read as D11 to
   D00.
 <Channel selection>
   When expansion module D is used, which of the four channels is to be output to the DI area of the
   module needs to be selected by a ladder program. The channel switching DO points, CHA and CHB, are
   mapped to the DO area of the module as indicated below. The symbol × represents an unused bit, and an
   unused bit may be set to either 1 or 0.
   CHA and CHB select a channel as indicated in the table below. The A-D converted data of a selected
   channel and the selected channel data are written to the DI area.
               CHB                      CHA                               Channel selected
                0                           0                                Channel 1
                0                           1                                Channel 2
                1                           0                                Channel 3
                1                           1                                Channel 4
 <Address>
   Be sure to allocate the start address in the DI area of the basic module including expansion module D at
   an even-numbered address. When the start address is allocated in this way, the digital output address of
   expansion module D is as indicated below, depending on the allocation area.
   •     When expansion module D is allocated as expansion module 1 (Xm represents an allocation start
         address.)
          Address in the module         7        6             5    4       3       2         1      0
           Xm+3 (odd address)                                       Undefined
          Xm+4 (even address)          D07      D06        D05     D04     D03     D02       D01    D00
           Xm+5 (odd address)           0        0         CHB     CHA     D11     D10       D09    D08
   •     When expansion module D is allocated as expansion module 2 (Xm represents an allocation start
         address.)
          Address in the module         7        6         5        4       3        2        1      0
          Xm+6 (even address)          D07      D06       D05      D04     D03      D02      D01    D00
           Xm+7 (odd address)           0        0        CHB      CHA     D11      D10      D09    D08
          Xm+8 (even address)                                       Undefined
   •     When expansion module D is allocated as expansion module 3 (Xm represents an allocation start
         address.)
          Address in the module         7        6             5    4       3       2         1      0
           Xm+9 (odd address)                                       Undefined
          Xm+10 (even address)         D07      D06        D05     D04     D03     D02       D01    D00
          Xm+11 (odd address)           0        0         CHB     CHA     D11     D10       D09    D08
       NOTE
         When referencing a 2-byte digital output address with a ladder program, be sure
         to read from the address in units of 16-bit words.
                                                     - 309 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                            B-64303EN/03
    NOTE
      DO alarm information of expansion module C is not written to Xm+15. See the
      next item.
      Expansion module D does not have this function.
 Expansion module C
  The DO driver of expansion module C has not only the overheat protection function (overcurrent
  detection and temperature detection) as available with the basic module and expansion modules A and B
  but also an over voltage protection function and disconnection detection function, and a DO bit is
  allocated to each protection circuit.
  When any of these functions is activated, the bit corresponding to the LED "ALARM" of the module is
  turned on. The CNC continues operation with no alarm issued. However, the DI address area identifies
  which DO driver has detected an alarm. The next page indicates the correspondence between the DI
  address bits and the DO address bits.
                                                  - 310 -
B-64303EN/03                                                          9.CONNECTION OF I/O Link SLAVE DEVICES
   DO alarm bit addresses when expansion module C is allocated as expansion modules 1 to 3 (0: No DO
   alarm issued, 1: DO alarm issued). *=Don’t care
                                                                      Bit
    Address          7            6              5            4                3          2          1            0         Module
     Xm+3         Bit 7 of     Bit 6 of       Bit 5 of     Bit 4 of         Bit 3 of   Bit 2 of   Bit 1 of     Bit 0 of
                   Yn+2         Yn+2           Yn+2         Yn+2             Yn+2       Yn+2       Yn+2         Yn+2      DO alarm on
      Xm+4        Bit 7 of     Bit 6 of       Bit 5 of     Bit 4 of         Bit 3 of   Bit 2 of   Bit 1 of     Bit 0 of    expansion
                   Yn+3         Yn+3           Yn+3         Yn+3             Yn+3       Yn+3       Yn+3         Yn+3       module 1
      Xm+5            *            *              *            *                *          *          *            *
      Xm+6        Bit 7 of     Bit 6 of       Bit 5 of     Bit 4 of         Bit 3 of   Bit 2 of   Bit 1 of     Bit 0 of
                   Yn+4         Yn+4           Yn+4         Yn+4             Yn+4       Yn+4       Yn+4         Yn+4      DO alarm on
      Xm+7        Bit 7 of     Bit 6 of       Bit 5 of     Bit 4 of         Bit 3 of   Bit 2 of   Bit 1 of     Bit 0 of    expansion
                   Yn+5         Yn+5           Yn+5         Yn+5             Yn+5       Yn+5       Yn+5         Yn+5       module 2
      Xm+8            *            *              *            *                *          *          *            *
      Xm+9        Bit 7 of     Bit 6 of       Bit 5 of     Bit 4 of         Bit 3 of   Bit 2 of   Bit 1 of     Bit 0 of
                   Yn+6         Yn+6           Yn+6         Yn+6             Yn+6       Yn+6       Yn+6         Yn+6      DO alarm on
     Xm+10        Bit 7 of     Bit 6 of       Bit 5 of     Bit 4 of         Bit 3 of   Bit 2 of   Bit 1 of     Bit 0 of    expansion
                   Yn+7         Yn+7           Yn+7         Yn+7             Yn+7       Yn+7       Yn+7         Yn+7       module 3
     Xm+11            *            *              *            *                *          *          *            *
   How to view the table above
   DO alarm data assigned to bit 5 of address Yn+3 is written to bit 5 of Xm+4.
     NOTE
     1 DO alarm information on expansion module C is written not to Xm+15 but to the
       address indicated above.
     2 Xm+5, Xm+8, and Xm+11 cannot be used with expansion module C.
     3 Even when expansion module A or B is allocated as expansion module 1 or 2,
       address space is not shifted.
   The DO driver with the DI address bit set to 1 has detected an alarm. If a DO alarm is issued,
   troubleshooting and recovery can be enhanced by checking the contents of the DI area with the DGN
   screen of the CNC or by performing DI alarm processing in advance with the ladder.
   If a protection function is activated, turn off the DO power and system power then correct the cause that
   has activated the protection function.
   The table below indicates the DO output state and alarm bit state set when each protection function is
   activated.
                                                                      - 311 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                                                                                                                                                                        B-64303EN/03
    NOTE
    1 If the overheat protection function or over voltage protection function among the
      protection functions above is activated, the DO bit is kept OFF until the cause is
      eliminated. When the cause is eliminated, the DO bit is set to ON without
      restarting the system.
    2 Disconnection detection is performed by monitoring, with an output element in
      the module, the current flowing through a load when DO output is ON. When the
      detected current value is about 100 mA or less, disconnection detection is
      assumed. So, when a device (such as an LED) with a small load current is
      connected, the DO alarm state results, assuming disconnection detection. Unlike
      the other protection functions, however, this function does not turn off DO output.
      If a connection is reactivated after the state of disconnection is once set,
      disconnection detection is canceled without restarting the system.
Expansion module 2
Expansion module 3
Expansion module 1
Expansion module 2
Expansion module 3
Expansion module 1
Expansion module 2
                                                                                                                                                                                                                                         Expansion module 3
           Basic module
Basic module
Basic module
Standard setting
                                                                                                                                   - 312 -
B-64303EN/03                                                                                            9.CONNECTION OF I/O Link SLAVE DEVICES
   Each setting position of the rotary switch has the following meaning:
      Setting
                  Actual indication                                                                                 Meaning of setting
      position
          0                 0                                 This is the standard setting. The rotary switch is factory-set to this position.
                                                              This setting is used when no expansion module is omitted.
          1               -                                   Set the rotary switch on an expansion module to this position when the
                                                              preceding expansion module is omitted.
          2                 2                                 Set the rotary switch on an expansion module to this position when the
                                                              preceding two expansion modules are omitted.
         3                -                                   This setting is prohibited.
        4~F           4, -, 6, -,                             4, 8, or C has the same effect as 0.
                      8, -, A, -,                             5, 9, or D has the same effect as 1.
                      C, -, E, -,                             6, A, or E has the same effect as 2.
                                                              7, B, or F has the same effect as 3. (This setting, however, is prohibited.)
Expansion module 2
Expansion module 3
Expansion module 2
Expansion module 3
Expansion module 2
Expansion module 3
                                                                                                         omitted)
                                                                                                         On expansion module 3, set the rotary
                          Basic module
     NOTE
       Expansion module A (A03B-0823-C002, with a manual pulse generator
       interface) is always mounted at the location of expansion module 1, so that its
       setting need not be changed.
                                                                                                        - 313 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                           B-64303EN/03
9.11.7 Others
                                                   - 314 -
B-64303EN/03                                      9.CONNECTION OF I/O Link SLAVE DEVICES
Unit: mm
     NOTE
       To fasten a terminal block, use M3 tap screws not longer than 10 mm.
                                                  - 315 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                         B-64303EN/03
Load
    NOTE
      Expansion module C does not allow parallel DO connection.
                                                 - 316 -
B-64303EN/03                                             9.CONNECTION OF I/O Link SLAVE DEVICES
9.12.1           Overview
   The FANUC I/O Link-AS-i converter unit (hereinafter referred to as the AS-i converter) is a stand-alone
   unit that converts I/O Link data to the Actuator Sensor Interface (hereinafter referred to as the AS-i),
   which is an I/O-level open network.
9.12.1.1 Features
   The AS-i converter converts the AS-i to the I/O Link so that the DI/DO signals of an AS-i slave module
   can be used by the PMC of a CNC that has the I/O Link.
               CNC
               I/O LINK
                                         I/O Unit
                                                        - 317 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                 B-64303EN/03
    NOTE
      Note that when the AS-i converter is used, a large number of I/O points are
      occupied on the I/O Link side as described in Subsection 9.12.4.
9.12.2         Specifications
9.12.2.1 Specifications of the AS-i converter
 Power supply
       Input power supply: 24 VDC (±10%)
                                                        For Ver. 2.0                       For Ver. 2.1
                                                      A03B-0817-C001                     A03B-0817-C002
            Power supply capacity                          100 mA                             120 mA
              Heat dissipation                              2.4 W                              2.9 W
 Weight
                         For Ver. 2.0                                           For Ver. 2.1
                       A03B-0817-C001                                         A03B-0817-C002
                           350 g                                                    370 g
                                                     - 318 -
B-64303EN/03                                           9.CONNECTION OF I/O Link SLAVE DEVICES
                                                      - 319 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                     B-64303EN/03
9.12.2.4 Installation
 Notes on installation
  (1) Use the unit in a completely sealed cabinet.
  (2) Be sure to install the unit on a vertical plane and allow a clearance of 100 mm or more above and
  below the unit. Do not place a device that generates a large amount of heat below the unit.
    NOTE
    1 A screwdriver is inserted on a slant to mount and dismount the unit, so that a
      sufficient maintenance space is required on both sides of the unit. When the
      front face of an adjacent unit is flush with the front face of the unit or is recessed,
      provide a clearance of about 20 mm from the adjacent unit. When the front face
      of an adjacent unit is more projected toward you than the front face of the unit,
      provide a clearance of about 70 mm from the adjacent unit.
    2 When the unit is to be installed near a side plane of the cabinet, provide a
      clearance of about 70 mm between the unit and the side plane of the cabinet.
                                                - 320 -
B-64303EN/03        9.CONNECTION OF I/O Link SLAVE DEVICES
Unit: mm
                    - 321 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                           B-64303EN/03
DIN rail
  1. Place the hook of the unit onto the top of the DIN rail.
  2. Push the unit until it clicks into place.
2) Method of dismounting
DIN rail
    NOTE
      When dismounting the unit, be careful not to damage the locking section by
      applying an excessive force. When mounting and dismounting the unit, hold the
      unit by its top and bottom surfaces. Avoid applying force to the sides (where slits
      are provided).
                                                    - 322 -
B-64303EN/03                                                   9.CONNECTION OF I/O Link SLAVE DEVICES
9.12.3 Connection
                         CP1
                              For branch output
                                                                                       24 VDC power supply
                             B1   B2     B3
                                                     Connected for input                    Regulated
                             +24E 0V
                                                                                          power supply
                             A1    A2    A3                                               24 VDC ±10%
                             +24   0V
                                    For input
                                                       Tyco Electronics AMP         Make a selection matching
                                                       1-178288-3 (housing)          the power supply used.
                                                       1-175218-5 (contact)
                             Key arrangement
A02B-0124-K830
   The 24 VDC input to CP1 (A1, A2) can be output from CP1 (B1, B2) for branching. CP1 (B1, B2) is
   connected as shown below. In this case, the external 24 VDC power supply needs to provide CP1 (A1,
   A2) with a current which is equal to the sum of the current consumed by the control unit and the current
   used via CP1 (B1, B2).
                                                               - 323 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                             B-64303EN/03
AS-i converter
                        CP1
                        For branch output                                     External device
                         A1    A2   A3
                         +24   0V
                                            Tyco Electronics AMP             Make a selection
                               For input    2-178288-3 (housing)           matching the external
                                            1-175218-5 (contact)                 device.
Key arrangement
    NOTE
    1 Ensure that +24 V is supplied either when or before the power to the CNC is
      turned on, and that +24 V is removed either when or after the power to the CNC
      is turned off.
    2 When turning off the power to the CNC control unit, be sure to turn off the power
      to the AS-i converter and other slave I/O units connected via the I/O Link as well.
    3 Turn on the power to the AS-i power supply (power supply connected to the AS-i
      communication cable) either when or before the power to the CNC control unit is
      turned on. If the power to the AS-i power supply is turned on after the power to
      the CNC control unit is turned on, the system may not be started.
                                               - 324 -
B-64303EN/03                                        9.CONNECTION OF I/O Link SLAVE DEVICES
+: Brown
   1)     Peel off the coating of the AS-i cable then screw the cable onto the terminal block of the AS-i
          converter.
   2)     This terminal block is detachable, and work can be done on the terminal block after being detached
          from the AS-i converter. When attaching the terminal block, firmly tighten the screws for mounting
          the terminal block.
   3)     To facilitate AS-i cable branching, two AS-i + terminals and two AS-i − terminals are provided. A +
          terminal and a − terminal are connected with each other in the AS-i converter. Use those terminals
          that can be handled more easily.
   4)     Do not connect two cables to each terminal.
   5)     Connect the GND terminal to ground.
        NOTE
          To protect against induction noise, separate high-voltage lines and the power
          line from the AS-i communication cable as much as possible. (It is
          recommended to separate high-voltage lines and the power line from the AS-i
          communication cable by 300 mm or more.) Moreover, attach a surge absorber to
          a device that tends to generate noise.
                                                    - 325 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                          B-64303EN/03
                               <Input>                                               <Output>
        X            bit 7-4             bit 3-0                   Y            bit 7-4         bit 3-0
       +0            DI #1             Reserved                   +0            DO #1          Reserved
       +1            DI #3               DI #2                    +1            DO #3           DO #2
       +2            DI #5               DI #4                    +2            DO #5           DO #4
       +3            DI #7               DI #6                    +3            DO #7           DO #6
       +4            DI #9               DI #8                    +4            DO #9           DO #8
       +5           DI #11               DI #10                   +5            DO #11          DO #10
       +6           DI #13               DI #12                   +6            DO #13          DO #12
       +7           DI #15               DI #14                   +7            DO #15          DO #14
       +8           DI #17               DI #16                   +8            DO #17          DO #16
       +9           DI #19               DI #18                   +9            DO #19          DO #18
       +10          DI #21               DI #20                   +10           DO #21          DO #20
       +11          DI #23               DI #22                   +11           DO #23          DO #22
       +12          DI #25               DI #24                   +12           DO #25          DO #24
       +13          DI #27               DI #26                   +13           DO #27          DO #26
       +14          DI #29               DI #28                   +14           DO #29          DO #28
       +15          DI #31               DI #30                   +15           DO #31          DO #30
       +16            AS-i master status (1)                      +16               Command flag
       +17            AS-i master status (2)                      +17               Command code
       +18               Board status (1)                         +18           Command parameter (1)
       +19               Board status (2)                         +19           Command parameter (2)
       +20            Slave list (1) #1 to #7                     +20           Command parameter (3)
       +21           Slave list (2) #8 to #15                     +21           Command parameter (4)
       +22           Slave list (3) #16 to #23                    +22                  Reserved
       +23           Slave list (4) #24 to #31                    +23                  Reserved
       +24              Command status                            +24                  Reserved
       +25            Command error code                          +25                  Reserved
       +26         Command response data (1)                      +26                  Reserved
       +27         Command response data (2)                      +27                  Reserved
       +28         Command response data (3)                      +28                  Reserved
       +29         Command response data (4)                      +29                  Reserved
       +30                   Reserved                             +30                  Reserved
       +31                   Reserved                             +31                  Reserved
    NOTE
      A number after # represents an AS-i slave number.
                                                   - 326 -
B-64303EN/03                                    9.CONNECTION OF I/O Link SLAVE DEVICES
    NOTE
      A number and letter after # represent an AS-i slave number.
                                                - 327 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                         B-64303EN/03
 <Output>
                         Group α                                Group α+1
     Y        bit 7-4         bit 3-0               Y'        bit 7-4          bit 3-0
    +0       DO #1A          Reserved              +0        DO #1B           Reserved
    +1       DO #3A           DO #2A               +1        DO #3B            DO #2B
    +2       DO #5A           DO #4A               +2        DO #5B            DO #4B
    +3       DO #7A           DO #6A               +3        DO #7B            DO #6B
    +4       DO #9A           DO #8A               +4        DO #9B            DO #8B
    +5       DO #11A          DO #10A              +5        DO #11B          DO #10B
    +6       DO #13A          DO #12A              +6        DO #13B          DO #12B
    +7       DO #15A          DO #14A              +7        DO #15B          DO #14B
    +8       DO #17A          DO #16A              +8        DO #17B          DO #16B
    +9       DO #19A          DO #18A              +9        DO #19B          DO #18B
    +10      DO #21A          DO #20A              +10       DO #21B          DO #20B
    +11      DO #23A          DO #22A              +11       DO #23B          DO #22B
    +12      DO #25A          DO #24A              +12       DO #25B          DO #24B
    +13      DO #27A          DO #26A              +13       DO #27B          DO #26B
    +14      DO #29A          DO #28A              +14       DO #29B          DO #28B
    +15      DO #31A          DO #30A              +15       DO #31B          DO #30B
    +16            Command flag                    +16              Reserved
    +17           Command code                     +17              Reserved
    +18        Command parameter (1)               +18         Command parameter (6)
    +19        Command parameter (2)               +19         Command parameter (7)
    +20        Command parameter (3)               +20         Command parameter (8)
    +21        Command parameter (4)               +21         Command parameter (9)
    +22        Command parameter (5)               +22              Reserved
    +23              Reserved                      +23              Reserved
    +24              Reserved                      +24              Reserved
    +25              Reserved                      +25              Reserved
    +26              Reserved                      +26              Reserved
    +27              Reserved                      +27              Reserved
    +28              Reserved                      +28              Reserved
    +29              Reserved                      +29              Reserved
    +30              Reserved                      +30              Reserved
    +31              Reserved                      +31              Reserved
   NOTE
   1 A number and letter after # represent an AS-i slave number.
   2 To group α, the standard slave or an A slave of the A/B slaves is assigned.
     To group α+1, a B slave of the A/B slaves is assigned.
                                        - 328 -
B-64303EN/03                                                     9.CONNECTION OF I/O Link SLAVE DEVICES
 <Input>
     Address            bit 7            bit 6        bit 5         bit 4       bit 3        bit 2              bit 1     bit 0
        X+0                            DI of slave address #1                                        Reserved
                        IN4               IN3          IN2          IN1       Reserved     Reserved        Reserved     Reserved
        X+1                            DI of slave address #3                              DI of slave address #2
                        IN4               IN3          IN2          IN1         IN4           IN3          IN2            IN1
         :               :                 :             :            :           :             :            :              :
         :               :                 :             :            :           :             :            :              :
        X+15                          DI of slave address #31                             DI of slave address #30
                        IN4               IN3          IN2          IN1         IN4           IN3          IN2            IN1
 <Output>
     Address            bit 7            bit 6        bit 5         bit 4       bit 3        bit 2              bit 1     bit 0
        Y+0                           DO of slave address #1                                         Reserved
                       OUT4            OUT3         OUT2           OUT1       Reserved     Reserved        Reserved     Reserved
        Y+1                           DO of slave address #3                              DO of slave address #2
                       OUT4            OUT3         OUT2           OUT1        OUT4        OUT3         OUT2             OUT1
         :               :                :            :             :           :            :            :               :
         :               :                :            :             :           :            :            :               :
        Y+15                          DO of slave address #31                             DO of slave address #30
                       OUT4             OUT3         OUT2          OUT1        OUT4         OUT3         OUT2            OUT1
                                                                 - 329 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                            B-64303EN/03
 <Output>
         Address             bit 7        bit 6      bit 5       bit 4          bit 3      bit 2         bit 1        bit 0
              Y+0                  DO of slave address #1A                                    Reserved
   G                       OUT4(NOTE)     OUT3      OUT2        OUT1        Reserved     Reserved      Reserved     Reserved
   r          Y+1                  DO of slave address #3A                            DO of slave address #2A
   o                       OUT4(NOTE)     OUT3      OUT2        OUT1       OUT4(NOTE)     OUT3        OUT2            OUT1
   u        :                  :             :         :          :           :              :           :              :
   p        :                  :             :         :          :           :              :           :              :
          X+15                     DO of slave address #31A                           DO of slave address #30A
   α                       OUT4(NOTE)     OUT3      OUT2        OUT1       OUT4(NOTE)     OUT3        OUT2            OUT1
   G          Y'+0                 DO of slave address #1B                                    Reserved
   r                        Reserved      OUT3      OUT2        OUT1        Reserved     Reserved      Reserved     Reserved
   o          Y'+1                 DO of slave address #3B                           DO of slave address #2B
   u                        Reserved      OUT3      OUT2        OUT1        Reserved     OUT3        OUT2             OUT1
   p        :                  :             :         :          :            :            :           :               :
            :                  :             :         :          :            :            :           :               :
   α      Y'+15                    DO of slave address #31B                          DO of slave address #30B
   +                        Reserved      OUT3      OUT2        OUT1        Reserved     OUT3        OUT2             OUT1
   1
   NOTE
     A number and letter after # represent an AS-i slave number.
     When the standard slave is used, DI/DO signals are assigned to group α (X+0 to
     X+15 and Y+0 to Y+15).
     When the A/B slave is used, OUT4 is reserved and cannot be used.
                                                             - 330 -
B-64303EN/03                                                      9.CONNECTION OF I/O Link SLAVE DEVICES
    Address      Bit                      Item                          Bit status                    Condition for ON
      X+17        0             Offline operation status       0: Not offline
                                                               1: Offline
                  1             Reserved
                  2             EEPROM status in AS-i          0: Abnormal                   When the EEPROM in the AS-i
                                master                         1: Normal                     master is normal
                  3             Automatic addressing           0: Disabled                   When automatic addressing is
                                enable status                  1: Enabled                    enabled
                4 to 7          Reserved
     NOTE
       To use the AS-i safely, be sure to monitor the AS-i status.
       When using DI/DO data on the AS-i side, be sure to monitor the AS-i power
       supply monitor information in Subsection 9.12.5.2, the AS-i data ready bit in
       Subsection 9.12.5.3, and other error information items. If any of these
       information items indicates an error or illegal status, the DI/DO data on the AS-i
       converter side is also invalid. So, correct the system to maintain the safe status.
                                                                  - 331 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                        B-64303EN/03
  Mode 0: Discrepancy between LPS (list of configured slaves) and LES (list of detected slaves)
     0: There is no discrepancy between LPS and LES.
     1: There is a discrepancy between LPS and LES.
    NOTE
      If the list output mode is switched, up to about 3 seconds may be required until
     an output change actually takes place after the mode switching. When reading
     with a ladder, be sure to check the list output mode in status information
     beforehand.
                                                    - 332 -
B-64303EN/03                                            9.CONNECTION OF I/O Link SLAVE DEVICES
                                                        - 333 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                      B-64303EN/03
Command parameter
                                        <1>
                Request flag
                                                                           <3>
                                                                                            <4>
                       End flag
Error status
              Response data
                                                    Command execution
<2>
                                                     - 334 -
B-64303EN/03                                          9.CONNECTION OF I/O Link SLAVE DEVICES
   <1> PMC side: Command code is written after checking that both of the request flag and end flag are
       OFF. If the command has parameter data, the parameter data is written simultaneously. Next, the
       request flag is set to ON. Within the same scan period, command code may be written and the
       request flag may be set to ON.
   <2> Converter side: When the request flag is set, command code is read then the command is executed.
       Upon completion of command execution, error status and response data are transferred then the end
       flag is set to ON.
   <3> PMC side: The end flag set to ON is awaited. When the end flag is set to ON, error status is read. In
       the case of normal termination with response data, the response data is read. Upon completion of
       processing, the end flag is set to OFF.
<4> Converter side: When the request flag is set to OFF, the end flag is set to OFF.
     NOTE
       The operations of <2> and <4> are performed by the AS-i converter.
 (2) Reading the parameter of a particular slave from the EEPROM of the AS-i
      master
                      Address       bit 7     bit 6        bit 5     bit 4    bit 3     bit 2        bit 1   bit 0
      Execution       Y+17                                                0BH
        data          Y+18                            Slave address (01H to 1FH, 21H to 3FH)(NOTE)
                   Y+19 to Y+21                                         Not set
      Response         X+25                                            Error code
        data           X+26                            0                               Parameter value
                                                      - 335 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                     B-64303EN/03
                                                    - 336 -
B-64303EN/03                                                 9.CONNECTION OF I/O Link SLAVE DEVICES
     NOTE
       Input an AS-i slave address number as follows:
                      Slave type                                       Address input method
               Standard slave or A slave       Input an address number directly in hexadecimal (01H to 1FH).
                       B slave                 Input an address number added to 32 (20hex) in hexadecimal.
                                                             - 337 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                              B-64303EN/03
(4)AS-i 端子台
                                                 - 338 -
B-64303EN/03                                             9.CONNECTION OF I/O Link SLAVE DEVICES
                Name        Color                                        Description
      AS-i      AUP         Green       Turned on when the operation mode is the protection mode and automatic
                                        addressing is enabled.
                 CM         Green       Turned on when the operation mode is the configuration mode and turned off
                                        when the operation mode is the protection mode.
                APF          Red        Turned on when the voltage of the AS-i power supply is low.
                CER          Red        Turned on when there is a discrepancy between the configured slaves and the
                                        currently connected slaves (when there is a discrepancy in LPS, ID code, or I/O
                                        configuration).
      Operation mode               In normal operation              When the setting switch (DISP) is pressed
    Configuration mode       No display                       Displays all connected slaves at intervals of about one
                                                              second (display of LES).
    Protection mode          The smallest slave address       Displays all configuration-mismatching slaves at intervals
                             among those of the               of about one second (displays a list of discrepancies
                             configuration-mismatching        between LPS and LES).
                             slaves is displayed.             * No data is displayed when there is no
                                                              configuration-mismatching slave.
                                                         - 339 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                        B-64303EN/03
  (Example)
      When the following slaves are connected, the slave numbers are displayed in the order shown below:
               Address #10                  Standard slave
               Address #20A                 A/B slave
               Address #20B                 A/B slave
               Address #30                  Standard slave
X1 X1 X1 X1
    NOTE
      If a slave with address 0 is connected, the configuration cannot be registered
      and the mode is not switched to the protection mode. Alarm E5 is indicated.
                                                      - 340 -
B-64303EN/03                                         9.CONNECTION OF I/O Link SLAVE DEVICES
                                                    - 341 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                                      B-64303EN/03
   NOTE
   1 In the protection mode, the smallest one of the addresses of the
     configuration-mismatching slaves is displayed. No data is displayed in the
     configuration mode.
   2 Use a ladder program to detect and display an AS-i converter error.
   3 When an AS-i converter error occurs, both of the DO signals and DI signals are
     turned off.
   4 When AS-i communication fails, a watchdog alarm is issued on the slave unit
     side. When a slave watchdog alarm is issued, the behavior of DO signals is
     determined by the type of slave unit and parameter setting. For details, refer to
     the specifications of the slave unit.
   5 Corrective action for an AS-i master EEPROM error
     When the 7-segment LEDs indicate E1, the registered configuration may have
     been destroyed. So, register the configuration again according to the procedure
     below.
                                                  Turn off the power.
The 7-segment LEDs indicate "E1". (Keep the switch set to SET.)
                Keep the switch set to SET until the LED ”CM” switches from off to on or vice versa.
                                   (This operation may require 5 seconds or more.)
Release the switch. Next, turn off the power then turn on the power again to restart the system.
          The register configuration is recovered if the 7-segment LEDs do not indicate "E1". (If the LED ”CM” is
          turned on, protect the registered configuration in preparation for subsequent operation. Keep the switch
          set to SET until the LED "CM" is turned off. This operation may require 5 seconds or more.)
                        If the 7-segment LEDs still indicate "E1" after the operation above,
                        replace the AS-i converter.
      AS-i converters with this function were shipped in June, 2005 or later.
      The corrective action mentioned above cannot be applied to those AS-i
      converters that were shipped earlier. In this case, replace the AS-i converter if an
      EEPROM error occurs.
                                                      - 342 -
B-64303EN/03                                         9.CONNECTION OF I/O Link SLAVE DEVICES
9.12.8.1 Installation
   The operation below can be performed even when the I/O Link is not connected (for example, when the
   power to the CNC is not turned on with only the power to the AS-i converter and AS-i power supply
   turned on or when the I/O Link cable is not connected).
Start
NO
End of installation
     NOTE
     1 When the operation mode is switched to the protection mode, the slave
       configuration is registered and automatic addressing is enabled.
     2 The operation mode remains unchanged, regardless of whether the power to the
       AS-i converter is turned on or off. To switch the operation mode, use the SET
       switch.
                                                     - 343 -
9.CONNECTION OF I/O Link SLAVE DEVICES                                                              B-64303EN/03
      a) Disconnected cable
  The cause may be identified as a disconnected cable if all slaves after a particular slave are
  configuration-mismatching slaves.
      b) Communication error
  A temporary communication error may be recovered by restarting the operation. In this case, however,
  check whether a large noise source is located nearby and whether all connections are made normally.
      d) No address setting
  An AS-i slave with address "0" is connected.
                                                    - 344 -
B-64303EN/03                                          9.CONNECTION OF I/O Link SLAVE DEVICES
9.12.9 Others
9.12.9.1 CE marking
   The AS-i converter has CE marking certification.
   Note, however, that because of its conformance to the AS-i EN standard (EN50295), the AS-i converter
   has not undergone surge test.
9.12.9.2 Fuse
   The AS-i converter has a built-in fuse. If the fuse blows, replace the fuse after correcting the cause.
                                                      - 345 -
10.STOP AND EMERGENCY STOP                                                                     B-64303EN/03
 A controlled stop is the quickest. However, a stop may be made by immediately shutting off the motor
 power for safety reasons.
        WARNING
       Pressing the RESET key stops the running program. As a result, the servo axis
       stops and the spindle axis remains rotating without changing the speed. The
       RESET key may not function due to an MDI failure or the like, so, for safety, use
       the emergency stop button instead of the RESET key to stop the motor safely.
       When a failure of the CNC, machine contact, or connection is also assumed,
       further safety actions must be taken.
                                                 - 346 -
B-64303EN/03                                                      10.STOP AND EMERGENCY STOP
        CAUTION
     1 If the CNC enters the system alarm state, the Ladder program does not run. In
       this case, the spindle amplifier can be decelerated to a stop. Make proper
       parameter settings because such a stop depends on the settings.
     2 If the spindle motor cannot be controlled due to an alarm in the spindle amplifier
       itself or for some other reason, the motor power is shut off by the IGBT
       immediately. After the servo motor has stopped, an MCC control signal is
       output.
                                                    - 347 -
10.STOP AND EMERGENCY STOP                                                     B-64303EN/03
                                        - 348 -
B-64303EN/03                                                                         10.STOP AND EMERGENCY STOP
                                                     Spark killer
                                       SK
                                   EMG
                               Relay                      I/O unit (module) connected to
                                emg1                      the CNC
                                                          +24
                                                          * ESP
                                                          MCCOFF3
                                                          MCCOFF4
                    External
                    power                                            L1    L2    L3
                    source
Spark killer
SK
           3φ
                                  coil
           200VAC
           L1
L2
L3
Fig. 10.5
          WARNING
         To use a spindle motor and amplifier produced by a manufacturer other than
         FANUC, refer to the corresponding documentation as well as this manual.
         Design the emergency stop sequence such that, if the emergency stop signal
         contact opens while the spindle motor is rotating, the spindle motor is
         decelerated until it stops.
Cautions for configuring an emergency stop circuit in compliance with safety standards
   To configure an emergency stop circuit in compliance with JIS safety standards(*), observe the following
   cautions. Compliance with these JIS safety standards is a prerequisite for complying with the EC Machine
   Instructions.
   The method for shutting off the motor power section in the amplifier is based on an IGBT (transistor)
   rather than an electromechanical scheme.
                                                                - 349 -
10.STOP AND EMERGENCY STOP                                                                      B-64303EN/03
 When configuring an emergency stop circuit, therefore, install a line contactor on the power input line for
 motor power in the power supply module in order to ensure electromechanical shut-off, and apply voltage
 to the control coil of the contactor via the contactor control output of the power supply module.
 A failure in the amplifier may disable the output relay of the power supply module from going off, thus
 preventing the line contactor from shutting off the power, even when the emergency stop command input
 (*ESP) of the amplifier becomes low.
 To secure motor power shut-off, design the emergency stop circuit in a redundancy configuration. To be
 specific, the emergency stop circuit must have a direct line contactor shut-off route based on an
 emergency stop switch that is independent of the shut-off function of the amplifier.
 If a spindle amplifier module is used, shutting off the motor power line during spindle rotation disables
 the spindle from stopping quickly because the power regenerative function does not work, allowing the
 spindle to coast. So, provide the redundancy circuit mentioned above with a delay function based on an
 off-delay timer that allows a usual stop time.
 Refer to the following material for detailed descriptions about cautions related to safety circuits.
 A-71429-S13J:
       About Requirements for Safety Circuits and Configuration Samples
 To get a copy of this material, contact your FANUC sales representative.
                                                 - 350 -
B-64303EN/03                                           11.CONNECTION TO OTHER NETWORKS
                                                  - 351 -
12.CONNECTION OF THE STAND-ALONE TYPE                                                           B-64303EN/03
 The stand-alone type Series 0i-D uses the FANUC PANEL i or an IBM PC compatible PC as a display
 device.
 This chapter mainly provides descriptions specific to connection of the stand-alone type. For
 descriptions common to the stand-alone type and LCD-mounted type, which are not given in this chapter,
 see other chapters. For connection of the FANUC PANEL i, refer to the FANUC PANEL i Connection
 and Maintenance Manual (B-64223EN).
 The type in which the display unit is integrated with the control unit is called the LCD-mounted type and
 the type in which the display unit is separated from the control unit is called the stand-alone type below.
                                                 - 352 -
B-64303EN/03                                    12.CONNECTION OF THE STAND-ALONE TYPE
                                                                                Analog spindle or
        Memory card                                                             high-speed skip connector
        interface                                                               [JA40] (5.3, 6.2)
                                                                                 Display unit
                                                                                 connector
                                                                                 [COP21A]
                                                                                 GND connection
                                                                                 terminal
                                                   - 353 -
12.CONNECTION OF THE STAND-ALONE TYPE                                                     B-64303EN/03
2-slot rack
Main board
Slot 1
Slot 2
                                           - 354 -
B-64303EN/03                                                   12.CONNECTION OF THE STAND-ALONE TYPE
                         Main board
                  Slot    24V-IN(CPD19A)                                                                                  24 VDC power supply
                          24V-OUT(CPD19B)                        To I/O device
                                                  Optical fiber ccable
                                                                                                                          PANEL i or personal
                          DISPLAY(COP21A)
                                                                                                                          computer
                            R232-1(JD36A)
                                                                                                     RS-232-C I/O device
                            R232-2(JD36B)
                                                                                                     RS-232-C I/O device
                               SPDL(JA41)
                                                                                                                      Circuit breaker
                                                                                                                                200VAC
                                                                                            AC reactor                          200VAC
                                                                                                             MCC Circuit breaker
αi PS
Position coder
3rd spindle
αi SP
                                                                      COP10B                                               Axis 2
                                                                                      αi SV                                servo motor
                                                                      COP10A
                                                                                                                           Axis 3
                                                                      COP10B
                                                                                      αi SV                                servo motor
                                                                      COP10A
                                                                      COP10B                                               Axis 4
                                                                                      αi SV                                servo motor
                                                                      COP10A
ETHERNET(CD38A) Ethernet
                                                                      - 355 -
12.CONNECTION OF THE STAND-ALONE TYPE                                                               B-64303EN/03
12.5 INSTALLATION
 The other conditions are the same as those of the LCD-mounted type.                  See the Subsection 3.1.2,
 “Environmental Conditions of the Control Unit.”
    NOTE
      See FANUC PANEL i CONNECTION AND MAINTENANCE MANUAL
      (B-64223EN), for PANEL i.
                                                   - 356 -
B-64303EN/03                                       12.CONNECTION OF THE STAND-ALONE TYPE
                                                        Ground cable
                                                              2
                                                         2mm or more                    Grounding plate of
                                                                                        the cabinet
                                                                                                    Ì
PE
   Connect the 0-V lines of the electronic circuits in the control unit to the ground plate of the cabinet via the
   protection ground terminal (above figure).
   Use the Faston terminal (FANUC specification: A02B-0166-K330).
                                                        - 357 -
12.CONNECTION OF THE STAND-ALONE TYPE                                                                  B-64303EN/03
 There is a spare connector located at the far end (at middle height) on the right side of the control unit.
                                                                                                           C
 This connector is used for controller testing and other purposes.                Therefore, space (area       ) for
 handling the connector is required.
Space for air flow, and access area for fan replacement
30 Approx. 180
50 A A
               50               B                                                           B
                                                                        80
Fig. 12.5.5
                                                      - 358 -
B-64303EN/03                                         12.CONNECTION OF THE STAND-ALONE TYPE
                           CPD19A
                              1   +24V                                          24VDC stabilized
                              2     0V                                          power
                              3                                                 24VDC±10%
Cable
                         CPD19A
                         日本 AMP
                         1-178288-3 (housing)
                         1-175218-5 (Contact)                                   External power
   As for an stand-alone type control unit, part of the 24 VDC power input to CPD19A can be taken out
   from CPD19B by branching. CPD19B should be connected as shown below. In this case, the rating of
   the external 24 VDC power supplied to CPD19A must be the sum of the power consumed within the
   control unit and that supplied to external equipment via CPD19B. Up to 1.0 A can be supplied to the
   external equipment.
                       CNC control unit                                         External device
                           CPD19B
                              1   +24V
                              2     0V
                              3
                      Cable
                         CPD19B
                         AMP Japan
                         2-178288-3 (Housing)
                         1-175218-5 (Contact)
                                                                                External device
                                                        - 359 -
12.CONNECTION OF THE STAND-ALONE TYPE                                                        B-64303EN/03
12.6.3        Batteries
Replacing the battery for stand-alone type control unit
  If a lithium battery is used, have A02B-0200-K102 (FANUC internal code: A98L-0031-0012) handy.
  1      Turn the CNC on. About 30 seconds later, turn the CNC off.
  2      Remove the battery from the top area of the CNC unit.
         First, pull the battery cable to unplug the connector. Then, remove the battery from the battery
         case.
         The battery case is provided in the top area of the face plate of the main board.
  3      Replace the battery, then connect the connector.
        WARNING
        Using other than the recommended battery may result in the battery exploding.
        Replace the battery only with the specified battery (A02B-0200-K102).
         CAUTION
        Steps 1 to 3 should be completed within 30 minutes. Do not leave the control
        unit without a battery for any longer than the specified period. Otherwise, the
        contents of memory may be lost.
        If steps 1 to 3 may not be completed within 30 minutes, save all contents of the
        SRAM memory to the memory card beforehand. Thus, if the contents of the
        SRAM memory are lost, the contents can be restored easily. For the method of
        operation, refer to Maintenance manual.
  Discard the dead battery, observing appropriate municipal rules and regulations. When discarding the
  battery, insulate the terminal with a tape so that no short-circuit would occur.
                                                - 360 -
B-64303EN/03                                        12.CONNECTION OF THE STAND-ALONE TYPE
12.7.1           Overview
   The high-speed serial bus (HSSB) enables the high-speed transfer of large amounts of data between a
   commercially available IBM PC or compatible personal computer and a CNC, by connecting them via a
   high-speed optical fiber.
   For a stand-alone type CNC, the HSSB interface is provided as a standard feature.
   On the personal computer, an appropriate interface board is installed.
   You can use the FANUC PANEL i instead of a commercial PC. The FANUC PANEL i comes standard
   with the HSSB interface.
12.7.2           Cautions
   The use of the HSSB requires an IBM PC/AT compatible computer or FANUC intelligent terminal. The
   machine tool builder or end user is required to procure and maintain the personal computer.
To enable the use of the HSSB, Windows XP must have been installed on the personal computer.
   The software mentioned above and the contents of the related manuals may not be used or reproduced in
   part or whole without the prior written permission of FANUC.
     NOTE
       IBM is a registered trademark of IBM Corp. of the US.
       Windows XP is registered trademarks of Microsoft Corp. of the US.
       The company and product names mentioned in this manual are trademarks or
       registered trademarks of the respective companies.
COP21M
Personal computer
                                                                                           COP21A
                                                                                           (on a main board)
                              COP21M
                                                                          Stand-alone type control unit
               PANEL i                    Note: Only an interface board for the PCI bus is provided as the interface board to
                                                be installed in the personal computer.
                                                        - 361 -
12.CONNECTION OF THE STAND-ALONE TYPE                                                            B-64303EN/03
       If the environmental requirement of the using personal computer is different from the above, please
       keep the environmental requirement to be satisfied by the both equipments.
 (1) Remove the covering plate of extension slot on the personal computer.
 (2) Insert the interface board for the personal computer to the PCI connector tightly.
 (3) Screw the plate of interface board to the computer.
 (4) Confirm connection (in only case of HSSB multi-connection)
     Confirm following items for installing drivers of HSSB interface board in case of HSSB
     multi-connection.
     -    PCI slot number which HSSB board is mounted (slot number is marked to PCB normally).
     -    Correspondence between HSSB channel and CNC
 (5) Restore the covering plate.
        CAUTION
        Do not touch the leads running to the card edge of the interface board (that
        match with connectors).
                                                    - 362 -
B-64303EN/03                                    12.CONNECTION OF THE STAND-ALONE TYPE
COP21A COP21M
                                                    - 363 -
12.CONNECTION OF THE STAND-ALONE TYPE                              B-64303EN/03
                           Memory
                           card
                                                   Weight: 1.7kg
                                                   (Unit: mm)
                               - 364 -
B-64303EN/03                                    12.CONNECTION OF THE STAND-ALONE TYPE
The panel cut dimensions of this punch panel are indicated below.
     NOTE
       This punch panel cannot used for the PANEL i.
                                                    - 365 -
APPENDIX
                                                                               A.EXTERNAL DIMENSIONS
B-64303EN/03                                         APPENDIX                           OF EACH UNIT
                                                        - 369 -
A. EXTERNAL DIMENSIONS
   OF EACH UNITTABLE                                                                                    APPENDIX                                                                                      B-64303EN/03
No option slot
                                                                                                                          Weight: 3kg
                                                                                         Area for pasted
                                                                                         packing
                                                                 Installation hole processing picture
                                                                                                         - 370 -
                                                                                           A.EXTERNAL DIMENSIONS
B-64303EN/03                                                 APPENDIX                               OF EACH UNIT
                                     Installation hole
                                     processing picture
                                                                                                  No option slot
                                               Area for pasted packing
                                                                - 371 -
A. EXTERNAL DIMENSIONS
   OF EACH UNITTABLE                                             APPENDIX                                                    B-64303EN/03
Fig. U3
     Touch panel interface unit   CNC control unit (10.4” color LCD)
     (only with touch panel)
No option slot
                                                                                                                               Weight: 3kg
                                                                    Area for pasted
                                                                    packing
                                                                                      Installation hole processing picture
   NOTE The unit is stopped with the screw from outside of the cabinet, then
        install the screw cap.
        The unit with a touch panel has no soft keys.
                                                                  - 372 -
                                                                                                                                                     B-64303EN/03
- 373 -
          Installation hole processing picture
                                                                                                                                                     APPENDIX
                                                                                       Weight: 1.3kg
                                                                                       (Unit: mm)
                                                                                                                                                     A.EXTERNAL DIMENSIONS
                                                                                                                                                              OF EACH UNIT
                                                                                                                                                      OF EACH UNITTABLE
                                                                                                                                                   A. EXTERNAL DIMENSIONS
- 374 -
          Installation hole processing picture
                                                                                                                                                   APPENDIX
                                                                                       Weight: 1.3kg
                                                                                       (Unit: mm)
                                                                                                                                                   B-64303EN/03
                                                                                                                                                              B-64303EN/03
- 375 -
          Installation hole processing picture
                                                                                                                                                              APPENDIX
                                       Packing
                                        Unit                                      Width
   CAUTION
   When installing the control unit, be sure to seal between the unit and the operator’s panel with packing.
   For the installation margin (thickness) and width, see the table below.
                                                              - 376 -
                                                     A.EXTERNAL DIMENSIONS
B-64303EN/03                              APPENDIX            OF EACH UNIT
Slot 1
                                                               Weight:
                                                                  d—Ê 1.2kg
                                                                       F1.2kg
                                           - 377 -
A. EXTERNAL DIMENSIONS
   OF EACH UNITTABLE           APPENDIX                  B-64303EN/03
MS connector
                                - 378 -
                                                  A.EXTERNAL DIMENSIONS
B-64303EN/03                        APPENDIX               OF EACH UNIT
                                        - 379 -
A. EXTERNAL DIMENSIONS
   OF EACH UNITTABLE            APPENDIX            B-64303EN/03
                                  - 380 -
                                                  A.EXTERNAL DIMENSIONS
B-64303EN/03                          APPENDIX             OF EACH UNIT
                                        - 381 -
A. EXTERNAL DIMENSIONS
   OF EACH UNITTABLE                          APPENDIX                                       B-64303EN/03
Fig. U21 Battery case for separate detector interface unit (ABS)
                                                                                                Minus terminal wi
                                                                                                3-M3 screw holes
                                                                                                 Plus terminal wi
                                                                                                 screw holes
                                               - 382 -
                                                            A.EXTERNAL DIMENSIONS
B-64303EN/03                           APPENDIX                      OF EACH UNIT
                                         - 383 -
A. EXTERNAL DIMENSIONS
   OF EACH UNITTABLE            APPENDIX    B-64303EN/03
                                  - 384 -
                                                        A.EXTERNAL DIMENSIONS
B-64303EN/03                         APPENDIX                    OF EACH UNIT
                                       - 385 -
A. EXTERNAL DIMENSIONS
   OF EACH UNITTABLE             APPENDIX           B-64303EN/03
                                   - 386 -
                                                       A.EXTERNAL DIMENSIONS
B-64303EN/03                         APPENDIX                   OF EACH UNIT
                                       - 387 -
A. EXTERNAL DIMENSIONS
   OF EACH UNITTABLE             APPENDIX           B-64303EN/03
                                   - 388 -
                                                                                      A.EXTERNAL DIMENSIONS
B-64303EN/03                                       APPENDIX                                    OF EACH UNIT
                                                       - 389 -
A. EXTERNAL DIMENSIONS
   OF EACH UNITTABLE                                 APPENDIX                                        B-64303EN/03
Connectors
                                                                        Specification drawing
                        Outline drawing name                                                          Fig.
                                                                               number
  PCR connector (soldering type)                                       PCR-E20FS                Fig. C1 (a)
  FI40 connector                                                       FI40-2015S               Fig. C1 (b)
  Connector case (HONDA PCR type)                                      PCR-V20LA/PCR-V20LB      Fig. C2 (a)
  Connector case (HIROSE FI type)                                      FI-20-CV                 Fig. C2 (b)
  Connector case (FUJITSU FCN type)                                    FCN-240C20-Y/S           Fig. C2 (c)
  Connector case (PCR type (Hirose Electric))                          FI-20-CV7                Fig. C2 (d)
  AMP connector (1): On the servo side                                 AMP1-178128-3            Fig. C3 (a)
  AMP connector (2): On the servo side                                 AMP2-178128-3            Fig. C3 (b)
  AMP connector (3): For +24 V power supply                            AMP1-178288-3            Fig. C3 (c)
  AMP connector (4): For +24 V power supply                            AMP2-178288-3            Fig. C3 (d)
  Contact for AMP connector                                            AMP1-175218-2/5          Fig. C3 (e)
                                                                       AMP1-175196-2/5
  HONDA connector (case)                                                                        Fig. C4 (a)
  Honda connector (angled–type case)                                                            Fig. C4 (b)
  HONDA connector (male)                                                                        Fig. C4 (c)
  HONDA connector (female)                                                                      Fig. C4 (d)
  HONDA connector (terminal layout)                                                             Fig. C4 (e)
  Connector made by FCI Japan (3 pins,black)                           SMS3PN-5                 Fig. C5
  Connector for HIROSE Flat cable                                      HIF3BB-50D-2.54R         Fig. C6
                                                                       HIF3BB-34D-2.54R
  Punch panel connector for reader/puncher interface                                            Fig. C8 (a)
  Locking plate plate for reader/puncher interface connector                                    Fig. C8 (b)
  Honda connector (for the distributed I/O connector printed circuit   MRH-50FD                 Fig. C9
  board)
                                                        - 390 -
                                             A.EXTERNAL DIMENSIONS
B-64303EN/03                      APPENDIX            OF EACH UNIT
                                   - 391 -
A. EXTERNAL DIMENSIONS
   OF EACH UNITTABLE         APPENDIX   B-64303EN/03
                              - 392 -
                                              A.EXTERNAL DIMENSIONS
B-64303EN/03                   APPENDIX                OF EACH UNIT
                                 - 393 -
A. EXTERNAL DIMENSIONS
   OF EACH UNITTABLE             APPENDIX     B-64303EN/03
                                   - 394 -
                                                A.EXTERNAL DIMENSIONS
B-64303EN/03                    APPENDIX                 OF EACH UNIT
                                  - 395 -
A. EXTERNAL DIMENSIONS
   OF EACH UNITTABLE              APPENDIX                B-64303EN/03
                                    - 396 -
                                                   A.EXTERNAL DIMENSIONS
B-64303EN/03                      APPENDIX                  OF EACH UNIT
                                    - 397 -
A. EXTERNAL DIMENSIONS
   OF EACH UNITTABLE              APPENDIX         B-64303EN/03
                                    - 398 -
                                                   A.EXTERNAL DIMENSIONS
B-64303EN/03                     APPENDIX                   OF EACH UNIT
                                   - 399 -
A. EXTERNAL DIMENSIONS
   OF EACH UNITTABLE             APPENDIX               B-64303EN/03
                                   - 400 -
                                             A.EXTERNAL DIMENSIONS
B-64303EN/03                     APPENDIX             OF EACH UNIT
                                   - 401 -
A. EXTERNAL DIMENSIONS
   OF EACH UNITTABLE            APPENDIX       B-64303EN/03
                                     - 402 -
                                                 A.EXTERNAL DIMENSIONS
B-64303EN/03                     APPENDIX                 OF EACH UNIT
                                   - 403 -
A. EXTERNAL DIMENSIONS
   OF EACH UNITTABLE            APPENDIX       B-64303EN/03
                                     - 404 -
                                            A.EXTERNAL DIMENSIONS
B-64303EN/03                    APPENDIX             OF EACH UNIT
                                  - 405 -
A. EXTERNAL DIMENSIONS
   OF EACH UNITTABLE             APPENDIX       B-64303EN/03
                                   - 406 -
                                                      A.EXTERNAL DIMENSIONS
B-64303EN/03                         APPENDIX                  OF EACH UNIT
                                      - 407 -
A. EXTERNAL DIMENSIONS
   OF EACH UNITTABLE            APPENDIX    B-64303EN/03
                                 - 408 -
                                                     A.EXTERNAL DIMENSIONS
B-64303EN/03                      APPENDIX                    OF EACH UNIT
                                    - 409 -
A. EXTERNAL DIMENSIONS
   OF EACH UNITTABLE             APPENDIX                           B-64303EN/03
Fig. C9   Honda connector (for the distributed I/O connector printed circuit
          board)
                                   - 410 -
                                                                         B.20-PIN INTERFACE
B-64303EN/03                                  APPENDIX              CONNECTORS AND CABLES
   These board-mounted connectors have been specially developed to achieve the high packing density
   required for FANUC products. As explained in the following subsection, Honda PCR series connectors
   can be used as cable connectors because the mating mechanism of the newly developed connectors is
   compatible with that of the Honda PCR series connectors. To support this specification extensively,
   many connector manufacturers are now developing custom-tailored cable connectors. (Note that these
   cables cannot be used with screw-fixing cable connector housings.)
   These connectors are used for the main and option boards. As cable connectors, they are compatible
   with screw-fixing connector housings as well as the spring locking connector housings.
   Cable connectors consist of a connector main body and housing. The models listed below are available.
   Those connectors not marked with an asterisk are currently being mass-produced as manufacturer's
   standard models. Those marked with an asterisk are produced according to custom specifications by
   FANUC.
                                                 - 411 -
B. 20-PIN INTERFACE
   CONNECTORS AND CABLES                        APPENDIX                                               B-64303EN/03
          Connector model
                                                                  Supplementary description
           (manufacturer)
   (formerly, FI40-2015S)              out some pins. Also features tougher pins, compared with its predecessor, the
                                       FI40-2015S. These pins can be soldered to wires as thick as #17AWG,
                                       provided that the cable diameter does not exceed 8.5 mm.
   In addition to the combinations shown in Fig. B.2, Hirose soldering-type connectors can be combined
   with the housings listed below. Ensure that the diameter of the cable used with each housing satisfies
   the requirements of that housing.
         Connector model                          Housing model (applicable cable diameter)
           FI40B-2015S                 ⇔             FI-20-CV (8.5 mm in diameter) only
      (formerly FI40-2015S)
                                                        - 413 -
B. 20-PIN INTERFACE
   CONNECTORS AND CABLES                          APPENDIX                                             B-64303EN/03
                                                                                 Compatible
    Connector name          FANUC-approved          FANUC-approved          cable(cable diameter)
    referenced in the      connector(manufact           housing             FANUC development          Remark
   Connection Manual              urer)              (manufacturer)         FANUC specification
                                                                                   number
                           FI40B-20S                                    A66L-0001-0367
                                                  FI-20-CV5
  FI40B-20S                (formerly FI40A-205)                         A66L-0001-0368              Plastic housing
                                                  (Hirose Electric)
  (formerly FI40A-2015S)   (Hirose Electric)                            (9.2 mm in diameter)
  Soldering type           FI40B-20S              FI-20-CV6             A66L-0001-0403(Note)
                                                                                                    Metal housing
                           (Hirose Electric)      (Hirose Electric)     (9.8 mm in diameter)
   NOTE
     Cable A66L-0001-0286 has been recommended for use as a pulse coder cable.
     It can be up to 20 m long. Two cables, A66L-0001-0402 and A66L-0001-0403,
     have recently been developed. A66L-0001-0402 and A66L-0001-0403 can be
     as long as 30 m and 50 m, respectively. (See Fig. 2 for detailed specifications.)
     Both cables have the same level of oil and bending resistance (cable, 100 mm in
     diameter, capable of withstanding at least 10 million bending cycles) as
     conventional cables, and are UL- and CSA-certified.
   NOTE
   1 Those tools indicated by shading are available from FANUC (specification
     number A02B-0120-K391).
   2 The tools available from each manufacturer are specifically designed for use with
     the connectors manufactured by that manufacturer.
                                                    - 414 -
                                                                                   B.20-PIN INTERFACE
B-64303EN/03                                          APPENDIX                CONNECTORS AND CABLES
10-pair cable
   (a) Specifications
                          Item                             Unit                       Specifications
   Product No.                                               -                    A66L-0001-0284#10P
   Manufacturer                                              -                      Hitachi Cable,Ltd.
                                                                               Oki Electric Cable, Co.,Ltd.
                                                                     SHINKO ELECTRIC INDUSTRIES CO., LTD.
   Rating                                                   -                      80°C 30V : UL20276
   Material       Conductor                                 -          Stranded wire of tinned annealed copper
                  Insulator                                 -                              Vinyl
                  Shield braid                              -                 Tinned annealed copper wire
                  Sheath                                    -                  Heat-resistant oilproof vinyl
   Number of pairs                                        Pairs                             10
   Conductor      Size                                    AWG                               28
                  Structure                           Conductors/mm                      7/0.127
                  Outside diameter                         mm                              0.38
   Insulator      Thickness                                mm                               0.1
                                                                             Thinnest portion : 0.8 (3.1mm)
                     Outside diameter (approx.)            mm                              0.58
   Twisted pair      Outside diameter (approx.)            mm                              1.16
                     Pitch                                 mm                           20 or less
   Lay                                                      -       Collect the required number of twisted pairs into
                                                                      a cable, then wrap binding tape around the
                                                                    cable. To make the cable round, apply a cable
                                                                                  separator as required.
   Lay diameter (approx.)                                  mm                               3.5
                                                        - 415 -
B. 20-PIN INTERFACE
   CONNECTORS AND CABLES                             APPENDIX                                             B-64303EN/03
                                                       - 416 -
                                                                                     B.20-PIN INTERFACE
B-64303EN/03                                          APPENDIX                  CONNECTORS AND CABLES
     NOTE
       The maximum outside diameter applies to portions other than the drain wire.
                                                         - 417 -
B. 20-PIN INTERFACE
   CONNECTORS AND CABLES                          APPENDIX                                              B-64303EN/03
 (c) Specifications
                  Item                                                    Specification
  FANUC specification number                        A66L-0001-0402                        A66L-0001-0403
  Manufacturer                                                   Oki Electric Cable Co., Ltd.
                                            A-conductor       B-conductor         A-conductor       B-conductor
  Conductor       Constitution                 16/0.12          3/22/0.12            16/0.12          7/16/0.12
                  Number of                  (0.18mm2)         (0.75mm2)           (0.18mm2)         (1.25mm2)
                  conductors/ mm
                  Typical outside               0.55               1.20                   0.55            1.70
                  diameter (mm)
  Insulation      Color                   White, red, black      Red, black      White, red, black     Red, black
  (polyester)     Typical thickness             0.16               0.23                0.16              0.25
                  (mm)
                  Typical outside               0.87               1.66                   0.87            2.20
                  diameter (mm)
  Pair twisting   Constitution              White-red,                             White-red,
                                          white-black, and                       white-black, and
                                             black-red                              black-red
                  Direction of twisting         Left                                   Left
                                          Typical pitch: 20                      Typical pitch: 20
                                                mm                                     mm
  Assembling by   Number of strands or            3                  6                   3                 6
  twisting        conductors
                  Direction of twisting                  Left                                    Left
                  Taping                  Twisting is wrapped with washi, or      Twisting is wrapped with washi, or
                                                Japanese paper, tape.                   Japanese paper, tape.
                  Typical outside                         5.7                                     6.9
                  diameter (mm)
  Braided         Typical strand                                              0.14
  shielding       diameter (mm)
                  Typical density (mm)                                      80
                  Drain                        A 12/0.18 mm wire is roughly wrapped under braided shielding.
                  Typical outside                        6.4                                  7.6
                  diameter (mm)
                                                       - 418 -
                                                                                   B.20-PIN INTERFACE
B-64303EN/03                                       APPENDIX                   CONNECTORS AND CABLES
                    Item                                                  Specification
   Sheath           Color                                                 Black (matted)
   (polyurethane)   Typical thickness                     1.05                                       1.1
                    (mm)
                    Vertical taping                       Vertically taped with washi under sheathing.
                    Outside diameter                     8.5±0.3                               9.8±0.3
                    (mm)
   Finished         Typical length (m)                                          100
   assembly         Short size                                        Basically not approved.
   Finished         Rating                                                  80°C 30V
   assembly         Standard                 Shall comply with UL STYLE 20236 and CSA LL43109 AWM I/II A 80°C
   performance                                                              30V FT-1.
                    Flame resistance                            Shall comply with VW-1 and FT-1.
   Electrical       Conductor resistance      103 or lower       25.5 or lower       103 or lower 15.0 or lower
   performance      Ω/km (20°C)
                    Insulation resistance                                   1 or higher
                    MΩ/km (20°C)
                    Dielectric strength                                      A.C 500
                    V-min
   Insulation       Tensile strength                                       9.8 or higher
   performance      N/mm2
                    Elongation %                                           100 or higher
                    Tensile strength after                       At least 70% of that before aging
                    aging %
                    Elongation after                             At least 65% of that before aging
                    aging %
                    Aging condition                                  For 168 hours at 113°C
   Sheathing        Tensile strength                                      9.8 or higher
   performance      N/mm2
                    Elongation %                                           100 or higher
                    Tensile strength after                       At least 70% of that before aging
                    aging %
                    Elongation after                             At least 65% of that before aging
                    aging %
                    Aging condition                                  For 168 hours at 113°C
   Cable cross
   section
                                                      - 419 -
B. 20-PIN INTERFACE
   CONNECTORS AND CABLES                        APPENDIX                                            B-64303EN/03
                                                   - 420 -
                                                                      B.20-PIN INTERFACE
B-64303EN/03                                     APPENDIX        CONNECTORS AND CABLES
   An example of circuit testing 20-pin interface cable
                               ⋅
                               ⋅
                               ⋅
                Ω
                    Resistor
               Check every     ⋅
               pin             ⋅
                               ⋅
                                                   - 421 -
C. CONNECTION CABLE
   (SUPPLIED FROM US)                        APPENDIX                                                   B-64303EN/03
    NOTE
    1 The maximum cable lengths listed above apply only when the respective
      recommended cables stated in the text are used. If a non-recommended cable
      is used, the maximum cable length may not be guaranteed. Cables other than
      the above are used. See the respective descriptions in this manual for details
      of these cables.
    2 This cable can be extended to up to 15 m if it is used within the cabinet.
                                                                                           A02B-0236-
                                                                                                           5m
                                                                                           K845
                                                      FI-20-CV7
  Electrical-to-electrical
                                         PCR-E20FA
  Spindle signal cable
                                                      PCR-E20FA
  Electrical-to-electrical
                                                 - 422 -
                                                                                       C.CONNECTION CABLE
B-64303EN/03                          APPENDIX                                          (SUPPLIED FROM US)
      ↑                                                                                            A02B-0236-
                                                                                                                   1m
      ↓                                                                                            K847
                                                  FI-20-CV7
   For optical adapter
                              FI40-2015S
   Control unit (JA3)                                                                              A02B-0120-
                                                                                                                   7m
      ↑                                                                                            K841
      ↓                                      M3 crimp style terminal
                                                                       2
                                            - 423 -
C. CONNECTION CABLE
   (SUPPLIED FROM US)                 APPENDIX                     B-64303EN/03
                                          - 424 -
B-64303EN/03                                             APPENDIX                         D.OPTICAL FIBER CABLE
           CAUTION
        1 During connection with optical fiber cables
        2 To relay a connection with optical fiber cables, only one replay point is allowed.
          In addition, the total length of two cables must be the maximum allowable
          transmission distance or less.
        3 See Subsection 7.2.2, “Interface to the Servo Amplifiers” for length restriction of
          FSSB line.
          • The length between the CNC and the first slave unit is 50 m or less.
          • The length between slave units is 40 m or less.
          • The total length including the above is 500 m or less.
21
Code
                                                              - 425 -
D.OPTICAL FIBER CABLE                                      APPENDIX                                                     B-64303EN/03
Unit: mm
8.2
21
                                                               - 426 -
B-64303EN/03                                      APPENDIX                   D.OPTICAL FIBER CABLE
   •    Use an external cable when part of the cabling is to be subject to movement. For example, when
        connecting a movable portable operation pendant box to the power magnetics cabinet, the use of an
        external cable is desirable because the cable is likely to be bent, pulled, or twisted repeatedly even
        though frequent system operation is not expected. However, the force likely to be applied when the
        cable is installed or moved for maintenance purposes does not need to be taken into consideration.
   •    Use an external cable in locations where sparks or flame are a danger. Although the internal cord
        type cable (A66L-6001-0023#~) is covered by nonflammable resin, the cover, if exposed to frame
        for a long time, may melt, allowing the fiber cable inside to burn.
   •    Use an external cable when the cable is expected to be pulled with considerable force during
        installation (the force applied to the cable must be within the specified tensile strength limit at all
        times). For example, even though installing a cable in a cable duct can be regarded as internal
        cabling, a cable of the appropriate type must be selected according to the tensile force to be applied
        to the cable during installation.
   •    Both the internal cord type and external cables have the same oil and heat resistance properties.
               Table D(d)   FANUC-approved cable manufacturers and cable model numbers (retail)
   <1> Internal cord type cable : A66L-6001-0023#LxRxxx
               Manufacturer                        Model number                           Remark
   Tyco Electronics AMP                   *-353373-*
   Japan Aviation Electronics Industry    PF-2HB209-**M-F-1                 ** indicates the cable length (m).
   Hirose Electric Co., Ltd.              H07-P22-F2VCFA-**                 ** indicates the cable length (m).
                                                    - 427 -
D.OPTICAL FIBER CABLE                                       APPENDIX                                 B-64303EN/03
Fig. D (c) Protection of electrical/optical conversion module and optical fiber cable (when not in use)
                                                             - 428 -
B-64303EN/03                                                   APPENDIX                        D.OPTICAL FIBER CABLE
Tape Tape
2 cords combined
        •       Take care to keep both parts of the optical connector (cable side and PCB side) clean. If they
                become dirty, wipe them with tissue paper or absorbent cotton to remove dirt. The tissue
                paper or absorbent cotton may be moistened with ethyl alcohol. Do not use any organic
                solvent other than ethyl alcohol.
        •       Fix the reinforcing cover of the external cable or the cord binding portion of the internal cord
                type cable by using a cable clamp, as shown in Fig. D(e), to prevent the weight of the optical
                fiber cable from being applied directly to the connecting part of the optical connector.
                                                                                         Reinforcing cover of external cable or cord
                Optical connector                       Optical fiber cord               binding portion of internal cord type cable
        •       Any superfluous portion of the cable may be wound into a loops. Should this prove necessary,
                make sure the diameter of each loop is at least 150 mm (for an external cable) or at least 100
                mm (for an internal cord type cable). Winding the cable into smaller loops may produce sharp
                curves that exceed the specified bending radius limit without the user being aware. Such
                bending can result in a greater transmission loss, ultimately leading to a communication failure.
        •       When using a nylon band (cable tie) as a cable clamp, follow the instructions given below.
                Also, take care not to apply a bending force to one particular part of the cable when fixing it
                with a clamp. Failing to clamp the cable correctly may cut or damage it.
                                                                   - 429 -
D.OPTICAL FIBER CABLE                             APPENDIX                                                    B-64303EN/03
            (External cable)
                  Do not clamp the uncovered portion of the cable with a nylon band. When clamping the
                  cable by the reinforcing cover, the clamping force is not an important factor to consider.
                  However, ensure that the clamping force is as small as possible to ensure that the
                  reinforcing cover is not deformed by the clamping. If possible, the clamping force
                  should be 5 kg or less.
            (Internal cord type cable)
                  Lightly clamp the optical cable with a nylon band so that the cable shield is not deformed.
                  If possible, the clamping force should be 1 or 2 kg (make sure that no force is applied to
                  the cable). Due care is required when clamping the internal cord type cable because its
                  cable shield is weaker than the reinforcing cover of the external cable.
                                                  10.16
                                 R1.6
6.6
                                                                                        8.2
                                                21±0.5
                                        3.2     42±0.5
                                                                             18.2±0.5
                           2.2
Mounting board
    NOTE
      Up to one relay points are permitte.
                                                     - 430 -
B-64303EN/03                                           APPENDIX                                 D.OPTICAL FIBER CABLE
                                                        10.16
                                    R1.6
6.6
                                                                                          8.2
                                                      21±0.3
                                              3.2     42±1.0
                                                                                   18.1
                              2.2
Mounting board
       NOTE
         Only one relay point is permitted.
                                                           - 431 -
D.OPTICAL FIBER CABLE                            APPENDIX                                          B-64303EN/03
        In the low-loss optical junction adapter, the ferrules are butted against each other, thus greatly
        reducing the reduction in repeater loss. Therefore, the two optical cables used with the low-loss
        optical junction adapters must be dedicated to the adapters.
        If a conventional PCF (plastic clad silica fiber) cable (A66L-6001-0026) is used as even one of the
        two optical fiber cables for joining the low-loss optical junction adapter, both cables may be
        damaged, resulting in deteriorated characteristics.
      NOTE
        Ferrule: Movable metal at the tip of an optical connector; the fiber is bonded to
        the ferrule.
Ferrule
Protective cover
                        Optical cable
                                                                         Optical connector
                                                    - 432 -
B-64303EN/03                                      APPENDIX                    D.OPTICAL FIBER CABLE
   •    When optical cables are attached to both ends of the junction adapter installed in a normal
        environment (such as within a cabinet), it is unlikely that dust will penetrate between the adapter
        and optical fiber to the degree that it may hamper normal optical linkage. If one or both ends of the
        adapter are left open, dust and dirt may accumulate even when the adapter is in a normal
        environment (such as within a cabinet). The dust and dirt on the adapter ends is likely to hamper
        normal optical linkage when the optical cables are attached. In such a case, clean the junction
        adapter and the optical connector using the optical fiber junction adapter cleaning method described
        below.
   •    Do not allow cutting fluid to splash over the adapter or those optical cable portions (such as
        connectors and cords) that are not covered with reinforcement coating. If the inside of the adapter
        and fiber end surfaces are contaminated with cutting fluid, a malfunction may occur.
   (10) Cleaning
   If the optical fiber junction adapter, optical-to-electrical conversion module, or optical cable are soiled,
   clean them according to the following procedures.
   •     Cleaning the optical fiber junction adapter and optical-to-electrical conversion module
         First, clean the entire housing by wiping it with a cloth moistened with, or by washing it in, ethyl
         alcohol. Similarly, wash the two sleeves in the adapter or wipe them with a cotton swab or the like.
   •     Cleaning optical cables
         For the optical cables, it is important to clean the connectors at their ends. Any soiling on the
         optical fiber end surfaces will hamper optical transmission, resulting in a malfunction. Wipe the
         optical fiber end surfaces (that is, the ferrule end surfaces) thoroughly with a soft, clean cloth (like
         gauze) moistened with ethyl alcohol, in the same way as described above. The use of cotton swabs
         may prove convenient. The fiber end surfaces of low-loss optical cables are lower than the ferrules.
         To remove any soiling from the fiber end surfaces completely, push the cotton swab or gauze into
         the depressions all the way through while rotating the ferrule.
         If the ferrules and optical connectors are contaminated with oily substances, and they may extend
         over a cleaned fiber end surface when it is attached to the optical-to-electrical conversion module, it
         is a good idea to wash them before wiping the optical fiber end surfaces, using the procedure stated
         above.
                                                    - 433 -
E.LIQUID CRYSTAL DISPLAY (LCD)                 APPENDIX                                         B-64303EN/03
                                                  - 434 -
B-64303EN/03                                      APPENDIX          F.MEMORY CARD INTERFACE
CF card
   Since a CF card includes flash memory, if read operation is repeated over a long period of time, an data
   error occurs in some rare cases due to internal data corruption. Commercial CF cards generally do not
   sufficiently address such a data error. In addition, read operation may take much time depending on the
   state of internal memory; if there is a delay in transferring data to the CNC during DNC operation, the
   finished quality of the machined surface may be affected.
   The CF cards recommended below have a superior capability of correcting data automatically and are
   designed so as not to read incorrect data even if a data error occurs. If these cards are used under the
   machining conditions defined below, the finished quality of the machined surface is not affected.
   2.    Others
         •   The format of the flash ATA card is the quick format.
             An unformatted flash ATA card needs to be formatted by your PC using FAT16. Other
             formats are not supported.
       NOTE
       1 To perform continuous operation with the CF adapter attached, be sure to push
         lock lever A downward and then close the cover of the memory card interface.
       2 The lock function is enabled only when the CF adapter (A02B-0303-K150) is
         used.
       3 The CF adapter must be inserted with label surface facing toward the screen.
  2.     Removal
         •  Open the cover of the memory card interface.
         •  Push lock lever A upward.
         •  Push eject button B once to project the button.
         •  Push eject button B again to eject the CF adapter.
         •  Remove the CF card with your fingers.
         •  Close the cover of the memory card interface.
       NOTE
       1 When lock lever A is in the lower position (in the locked state), eject button B
         cannot be pushed.
Lock lever A
G.1             OVERVIEW
   When a motor driven by analog servo amplifier is used, Analog servo adapter is required. Analog servo
   adapter is connected through an optical fiber cable as a unit on FSSB line.
G.2             SPECIFICATIONS
   •     Two types of analog servo interface
         -   Type F analog servo interface
           The ready signal and alarm signal from servo amplifier are 5VDC signals.
         -   Type M analog servo interface
           The ready signal and alarm signal from servo amplifier are 24VDC signals.
   •     Analog servo adapter consists of basic unit and additional unit. The basic unit has two analog servo
         axis interface and feedback interface. The additional unit has two analog servo axis interface and
         feedback interface. Therefore, up to 4 analog servo can be connected to Analog servo adapter.
   •     The maximum number of interface units like Analog servo adapter or a separate detector interface
         unit that can be connected to one FSSB line is two.
                                                   - 437 -
G.ANALOG SERVO ADAPTER              APPENDIX                                       B-64303EN/03
CNC
FSSB line
GND
                                                                   Battery
                               Analog
                                servo
                               adapter
                  Flat           unit
                  cable      (additional)
   Power
GND
                                                                   Battery
                               Analog
                                servo
                               adapter
                  Flat       (additional)
                  cable
                                        - 438 -
B-64303EN/03                                    APPENDIX                     G.ANALOG SERVO ADAPTER
                        COP10B
                                                   J37
                                    JA4L                           Battery         TG     servo
                                                                                          motor
                        COP10A
                                                   J156A / J156B                              Separate
                                 JF10nL
                                                                                              detector
               FSSB Lower step
                                                    - 439 -
G.ANALOG SERVO ADAPTER                              APPENDIX                                                  B-64303EN/03
                                 3
                       *ENBL
                                 4
                           0V
                                 13                                                       Note)
                        OVL
                                                                                          When OVL is not
                                 14                                                       used, OVL must be
                           0V
                                                                                          connected to 0V.
                                 10
                    *PRDY
                                 8
                           0V
                                                                                          Note)
                                 20                                                       When *VRDY is not
                    *VRDY
                                 18                                                       used, *VRDY must be
                           0V                                                             connected to 0V.
                           0V
                                 16
Shielded
                                                       - 440 -
B-64303EN/03                                    APPENDIX                G.ANALOG SERVO ADAPTER
       JF10nL
       (PCR-EV20MDV)
           1      A         11
                                              J156A
           2     ∗A         12    0V
           3      B         13
           4     ∗B         14    0V           Connector
           5       Z        15                 FI40-2015S
                                               Housing
           6      ∗Z        16    0V
                                               FI-20-CV
           7    (+6V)       17
           8   (REQ)        18    +5V
                                          +6V and REQ signals are for separate absolute pulse coder.
           9     +5V        19            When separate absolute pulse coder is not used, these signals
          10                20    +5V     connections are not necessary.
                             1
                        A                                                       A
                             2
                      ∗A                                                        ∗A
                             3
                        B                                                       B
                      ∗B     4                                                  ∗B
                             5
                        Z                                                       Z
                      ∗Z     6                                                  ∗Z
                             9
                    +5V                                                         +5V
                             18
                    +5V                                                         +5V
                             20
                    +5V                                                         +5V
                             12
                     0V                                                         0V
                             14
                     0V                                                         0V
                             16
                     0V                                                         0V
                             7
                   (+6V)                                                        (+6V)
                   (REQ)     8
                                                                                (REQ)
                                                  Shielded
                                                   - 441 -
G.ANALOG SERVO ADAPTER                                 APPENDIX                                                    B-64303EN/03
    JF10nL
     (PCR -EV20M D T)
         1      SD            11
                                                       J156B
         2      ∗SD           12        0V
         3                    13
         4                    14        0V              C onnector
         5     R EQ           15                        FI40-2015S
                                                        H ousing
         6    ∗R EQ           16        0V
                                                        FI-20-CV
         7     (+6V)          17
         8                    18        +5V
                                                  +6V and R EQ signals are for separate absolute pulse coder.
         9      +5V           19
                                                  W hen separate absolute pulse coder is not used, these signals
        10                    20        +5V       connections are not necessary.
Cable connection(J156B)
                                   1
                        SD                                                                     SD
                                   2
                        ∗SD                                                                    ∗SD
                                   5
                     REQ                                                                       REQ
                                   6
                    ∗REQ                                                                       ∗R EQ
                                   9
                        +5V                                                                    +5V
                                   18
                        +5V                                                                    +5V
                                   20
                        +5V                                                                    +5V
                                   12
                         0V                                                                    0V
                                   14
                         0V                                                                    0V
                                   16
                         0V                                                                    0V
                     (+6V)                                                                     (+6V)
                                                           Shielded
                                                          - 442 -
B-64303EN/03                                        APPENDIX                     G.ANALOG SERVO ADAPTER
               JA4L
               (PCR-EV20MDT)
                    1                   11                                     (M3 terminal)
                    2                   12               J37                        +              −
                    3     0V            13                                         +6V            0V
                    4                   14
                    5                   15
                    6                   16
                    7     +6V           17                       Connector
                    8                   18                       PCR-E20FS or PCR-E20FA
                    9                   19                       Housing
                   10                   20                       PCR-V20LA
                                        7                                                +
                                 +6V                                                         +6V
                                        3                                                −
                                  0V                                                         0V
                                                               Shielded
                  Recommended wire
                  0.2mm2(7/0.18) with shield
     NOTE
       If the cable is connected to JA4L when the separate absolute pulse coder
       battery case contains the battery, the battery voltage is applied to the battery
       power supply pin (+6 V) for each of the feedback connectors (JF101L to
       JF104L). In this case, if the battery line and 0 V are short-circuited, the battery
       may heat up or the protection circuit within Analog servo adapter may fail. First,
       make sure the battery case contains no battery or the cable is not connected to
       JA4L. Then, complete all cabling work and confirm cables are correctly
       connected. Finally, place the battery or connect the cable to JA4L.
                Electrical characteristics
                     Output voltage: -10V to +10V
                     Output current: 2mA
                     Output impedance: 100Ω
                                                     - 443 -
G.ANALOG SERVO ADAPTER                                 APPENDIX                                               B-64303EN/03
             Electrical characteristics
                  Maximum load current when output is on: -10V to +10V
                  Maximum output voltage when output is on: 6IL (VOlt), where IL: Load current
                  Withstand voltage when output is of: No more than 24V, including momentary values
                  Leakage current when output is of: No more than 100μA
                  Servo amplifier
                                                                               5V      Analog servo adapter
                                                                     *OVL                       Receiver
                                                                                                circuit
0V
             Electrical characteristics
                  Absolute maximum rating
                Item                   Symbol       Specification           Unit                 Supplement
  Input voltage range                   Vin          -3.6 to +13.6             V
                   Input characteristics
                Item                   Symbol       Specification           Unit                 Supplement
  High level input voltage              VH            3.6 to 10.5            V      Note
  Low level input voltage               VL              0 to 1.0             V
  High level input current              Iih            +1.5 max             mA      Vin=5V
                                                       +8.8 max             mA      Vin=10V
  Low level input current                Iil           -8.0 max             mA      Vin=0V
                   The plus sign (+) of Iih and Iil represents the direction of flow into the receiver, while the
                   minus sign (–) represents the direction of flow from the receiver.
                                                          - 444 -
B-64303EN/03                                            APPENDIX        G.ANALOG SERVO ADAPTER
     NOTE
       The input release state is also assumed to be the high level.
                                                       A phase signal
                             Shift in plus direction
B phase signal
                                                       A phase signal
                            Shift in minus direction
B phase signal
        The differential input signals shown below are applied to the connectors. The time duration, TD,
        from point α where the relative potential difference between A and *A becomes 0.5 V or more, to
        point β where the relative potential difference between B and *B becomes 0.5 V or less, must satisfy
        the condition indicated below. (This condition may restrict the maximum speed of movement.)
                                                           - 445 -
G.ANALOG SERVO ADAPTER                           APPENDIX                                       B-64303EN/03
                    Analog servo
                      adapter                           Analog
                                          J157          servo
                 COP10B      JV1nL                     amplifier
                                                                             Pulse        Analog
                 COP10A
                                                                            encoder     servo motor
                                                  - 446 -
B-64303EN/03                                    APPENDIX             G.ANALOG SERVO ADAPTER
                COP10B
                                         J37                            Pulse      Analog
                            JA4L                       Battery
                                                                       encoder   servo motor
                COP10A
                                         J156A/J156B                                           Separate
                         JF10nL
                                                                                               detector
     FSSB Lower step
                                                  - 447 -
G.ANALOG SERVO ADAPTER                               APPENDIX                                                    B-64303EN/03
                        PCA       1
                                                                                     OA+
                       *PCA       2
                                                                                     OA−
                        PCB       11
                                                                                     OB+
                       *PCB       12
                                                                                     OB−
                        PCZ       5
                                                                                     OZ+
                       *PCZ       9
                                                                                     OZ−
                     *SRDY        17
                                                                                     S−RDY
                        ALM       15
                                                                                     ALM
                     *PRDY        10
                                                                                     SRV−ON
                   24VOUT         19
                                                                                     COM+
                         0V       18
                                                                                     COM−
                         0V       16
                                                                                     GND
                                                                  Shield
       Maximum allowable cable length:50m (cable length has limitation by voltage drop)
       Recommended wire A66L-0001-0206
       (Individually shielded twisted pair #24AWG x 3 pairs + twisted pair #24AWG x 7 pairs)
       The external cable diameter is ∅11, preventing the use of the cable, as is, with connector case PCR-V20LB (∅8).
       Peel backs the sheath at the point where the cable meets the connector to reduce the cable diameter.」
       Recommended ferrite core:TDK ZCAT2032-0930
       Set ferrite core near Analog servo adapter.
                                                        - 448 -
B-64303EN/03                                            APPENDIX                  G.ANALOG SERVO ADAPTER
*SRDY 17 S−RDY
ALM 15 ALM
*PRDY 10 SRV−ON
COM+ 19 COM+
0V 18 COM−
0V 16 GND
Shield
      Maximum allowable cable length:50m (cable length has limitation by voltage drop)
      Recommended wire A66L-0001-0206
      (Individually shielded twisted pair #24AWG x 3 pairs + twisted pair #24AWG x 7 pairs)
      The external cable diameter is ∅11, preventing the use of the cable, as is, with connector case PCR-V20LB (∅8).
      Peel backs the sheath at the point where the cable meets the connector to reduce the cable diameter.
      Recommended ferrite core:TDK ZCAT2032-0930
      Set ferrite core near Analog servo adapter.
                                                           - 449 -
G.ANALOG SERVO ADAPTER                        APPENDIX                                         B-64303EN/03
                                                          ALM                    Receiver
                                                                                 circuit
0V
          Electrical characteristics
               Contact capacity: 30VDC, 16mV or greater
               Open-circuit contact-to-contact leakage: 1mA or less (for 26.4V)
               Closed-circuit contact-to-contact voltage drop: 2V or less (for8.5mA, including a voltage
               drop across the cable)
                                                - 450 -
B-64303EN/03                                      APPENDIX           G.ANALOG SERVO ADAPTER
                        CP11L                                         DC24V±10%
                            1     +24V                                (including an
                            2      0V                                 instantaneous value and
                            3                                         ripple)
GND
Cable
                       CP11L
                       AMP Japan
                       1-178288-3(Housing)
                       1-175218-5(Contact)                          External power supply
+24V(1)
0V(2)
   24VDC are supplied through the connector CP11L. The power can be supplied from CP11M to the next
   unit.
   Be sure to ground the 0-V line of the power supply to Analog servo adapter. In addition, keep any noise
   source (such as an AC power cable and contactor) away from the power line of Analog servo adapter as
   far as possible to prevent noise from being picked up through the power line.
                                                   - 451 -
G.ANALOG SERVO ADAPTER                           APPENDIX                                   B-64303EN/03
 Secure the ground line to the ground terminal (GND) for signals of Analog servo adapter, which is
 located at the bottom of the unit, with an M3 screw as shown in the figure below. Connect the ground
 line to the ground plate of the cabinet.
GND
   NOTE
     The torque with which a screw is tightened is 5 kgf × cm or less.
   NOTE
     In case of type M, 24VDC 0.25A per one axes is included for analog servo
     amplifier.
                                                   - 452 -
B-64303EN/03                                   APPENDIX                G.ANALOG SERVO ADAPTER
       NOTE
         Actual select switch SW1 has three positions. Up side to base PCB is M, middle
         and down side is F.
        Additional     Basic
                     CP11L/M
            JV13L      JV11L
           JF103L     JF101L
            JV14L      JV12L
           JF104L     JF102L
            JA4M       JA4L
COP10B/10A
G.10 NOTICE
   •     The maximum number of interface units like Analog servo adapter or a separate detector interface
         unit that can be connected to one FSSB line is two.
         When Analog servo adapter is connected to the FSSB line, the number of the separate detector
         interface unit can be connected to the same FSSB line is one.
   •     Analog servo adapter has four encoder interfaces. The unused one can be used for full closed
         control.
                                                  - 453 -
G.ANALOG SERVO ADAPTER                                 APPENDIX                                       B-64303EN/03
  •     When system alarm is occurred on CNC or communication alarm between CNC and Analog servo
        adapter is occurred, the signals *ENBL and *PRDY will be OFF. When the power of CNC or
        Analog servo adapter is turn off, the signals *ENBL and *PRDY will be OFF.
  •     The way to install this unit is similar to the one of the separate detector interface unit. Please refer to
        the Section 7.2.
  •     The sequence of power on/off is similar to the separate detector interface unit. Refer to the
        Subsections 4.2.3 and 4.2.4. But if the position feedback with A quad B interface is used and the
        +5VDC power is not supplied to it from Analog servo adapter, it is necessary to turn on the power
        for it before the power for Analog servo adapter is turned on. Furthermore, in this situation, it is also
        necessary that the A quad B interface signals of the separate detector become stable before turning
        on Analog servo adapter.
(2) Follow the procedure below to set parameters concerned with FSSB.
        In the case of using Analog servo adapter, the FSSB automatic setting function is not available. It is
        necessary to set the value of No.1023, No.1815, No.1905, No.14340 to14349, No.14376 to 14391
        and No.1936 to 1937 in the manual setting No.2 mode. Refer to “FSSB setting” of the connection
        manual (function edition) about the detail of the setting.
        When this parameter is set, Analog servo adapter is basically treated in the similar way to the
        separate type detector interface unit. (After this, Analog servo adapter and the separate type detector
        interface unit are called “an interface unit”.)
        Follow the explanation below and the Parameter Manual (B-64310EN) of CNC and set the
        appropriate value.
                                                          - 454 -
B-64303EN/03                                       APPENDIX                   G.ANALOG SERVO ADAPTER
     NOTE
       If you want to use Analog servo adapter, set 1.
                     The interface unit that is connected to the FSSB line on a servo card and is near the CNC
                     is the first interface unit (1st IF unit). Another one connected to the FSSB line is the
                     second interface unit (2nd IF unit).
CNC
                       Servo card
                                                FSSB line             1st IF unit            2nd IF unit
                                  COP10A-1
                                                                      PM1                    PM2
                                                      - 455 -
G.ANALOG SERVO ADAPTER                             APPENDIX                                             B-64303EN/03
                   In case of using interface unit, set the value, which subtracts 1 from the connector number
                   of each axis. (In case of using Analog servo adapter, set 0 to 3 to the axes connected with
                   connector JV1nL to JV4nL.)
                   Set 0 to the axis without interface unit.
                   It is possible to use any connectors at any axis.
CNC
                       Servo card
                                                 FSSB line           1st IF unit          2nd IF unit
                                    COP10A-1
                                                                     ATR=64               ATR= -56
                   -      In case of no slave:
                          Set -96.
                                                      - 456 -
B-64303EN/03                                                 APPENDIX                  G.ANALOG SERVO ADAPTER
      No.
     14384                                ATR value corresponding to connector 1 on the 2nd interface unit
       to
     14391                                ATR value corresponding to connector 8 on the 2nd interface unit
        (Reference)
             FSSB Setting example in case of using Analog servo adapter
                                       FSSB                                                       X axis
                                                                        JV11L   Analog servo
                                                       Analog servo
                                                                                amplifier 1
                                                       adapter
                                                                                        Slave 2
                                                       (Basic unit)
                                                                                                  Y axis
                                                                        JV12L   Analog servo
                    CNC                                                         amplifier 2
                                                             Slave 1                    Slave 3
                                         FSSB                                                        X axis
                                                         Digital servo amplifier
                                                                                 Slave 1
                                                FSSB
               CNC
                                                       Analog servo      JV11L   Analog amplifier    Y axis
                                                       adapter
                                                       (Basic unit)
                                                                                           Slave 3
Slave 2
                                                    14343 to
        No.     14340       14341       14342
                                                     14349
       Value         0        64          1              -96
                               14377 to
        No.     14376
                                14383
       Value         1             32
     Parameter
                              Description                                                     Data
      number
      No.2000            Automatic setting                                              00000000
      No.2020            Motor type                                                         252
      No.2001            AMR                                                            00000000
      No.1820            CMR                            Set the value similar to the one of digital servo according to mechanical
      No.2084            F × FG (Numerator)             system.
      No.2085            F × FG (Denominator)
      No.2022            Rotation direction             111 (CCW) or -111 (CW)
      No.1821            Reference counter size         Set the number (after F×FG) of pulse per one motor revolution as digital
                                                        servo.
      No.2023            Feedback pulse for             Set value = 1536.797 × E
                         velocity detection             E : the voltage (V) proportional to the 1000min-1 velocity command
      No.2024            Feedback pulse for             Set the number (before F × FG) of pulse per one motor revolution as
                         position detection             digital servo.
      No.            7           6          5           4           3          2           1          0
      2009                                          ANALOGG                                        SERDMY
                    NOTE
                      In case of analog servo axis, set 1.
                    NOTE
                      In case of analog servo axis, set 1.
                      After setting this bit, please turn off the power of CNC more than
                      one time.
      No.
      2165                                        Maximum amplifier current
                    NOTE
                      In case of analog servo axis, set 0.
                  When the initial setting of servo shown in previous section is done, 45 is set to this
                  address automatically. But clear this parameter to be 0. (If this parameter of analog servo
                  axis is not 0, the combination alarm of motor and amplifier will emerge.)
                                                  - 459 -
B-64303EN/03                                                                                                                                                               INDEX
INDEX
                                                                                                 Cable Length for Manual Pulse Generator ............142,199
<Number>                                                                                         Cables J156A/B............................................................447
   20-PIN INTERFACE CONNECTORS AND                                                               Cautions ................................................................209,361
   CABLES ......................................................................411              CE marking ..................................................................345
   2A DO (Output Signal) Connection .............................135                             Command Execution by a Ladder Program .................333
   2A Output Connector Pin Allocation ...........................134                             Command handshake sequence....................................334
   2A Output DO Signal Specifications ...........................136                             Command interface with a ladder program ..................333
   7-segment LED indication ...........................................339                       Component names ........................................................289
                                                                                                 Configuration .....................................................1,125,183
<A>                                                                                              Configurations of Control Units.......................................1
   About grounding types...................................................15                    Connecting DI/DO .......................................................212
   Address Assignment by Ladder ...................................237                           Connecting I/O Devices .................................................50
   Address map.................................................................308               CONNECTING THE FANUC SERVO UNIT β
   Analog Input Connector Pin Allocation .......................137                              SERIES WITH I/O LINK ............................................236
   ANALOG INPUT SEPARATE DETECTOR                                                                Connecting the Ground Terminal of the Control Unit
   INTERFACE................................................................100                   ................................................................................23,357
   Analog Input Separate Detector Interface                                                      Connecting the High-speed Skip (HDI) .........................60
   (Analog 1Vp-p Interface) .............................................106                     Connecting the Manual Pulse Generator ......................226
   Analog Input Separate Detector Interface Unit                                                 Connecting Three Serial Spindles ..................................75
   Specification.................................................................103             Connection ....................................... 113,234,237,296,323
   Analog Input Signal Connections.................................138                           Connection between Modules ......................................200
   Analog Input Signal Specifications..............................139                           Connection Between the Analog Input Separate
   Analog Input Specifications .........................................139                      Detector Interface Unit and Additional Unit ................109
   ANALOG SERVO ADAPTER....................................437                                   Connection Between the Basic Unit and Additional
   ANALOG SPINDLE......................................................80                        Unit ................................................................................95
   Anti-Noise Measure .......................................................66                  CONNECTION CABLE (SUPPLIED FROM US)......422
   Applicable Cables ........................................................415                 Connection Diagram ...............................126,185,361,438
   Applicable CNC ...........................................................318                 Connection of Basic and Expansion Modules ..............142
   Applicable wire ............................................................287               Connection of Battery for Absolute Position Detector
   AS-i connection............................................................325                 ................................................................................93,108
   AS-i master status indication........................................330                      CONNECTION OF CONNECTOR PANEL I/O
   AS-i versions and ordering information .......................317                             MODULE.....................................................................125
                                                                                                 Connection of Each Section .........................................260
<B>                                                                                              Connection of FANUC I/O Link by Electric Cable .....116
   Batteries ..................................................................37,360            Connection of FANUC I/O Link by Optical Fiber Cable
   Battery for Absolute Pulsecoder Built into the Motor                                           .....................................................................................117
   (6VDC) ..........................................................................42           CONNECTION OF I/O Link SLAVE DEVICES........124
   Battery for Memory Backup in the CNC Control Unit                                             CONNECTION OF I/O UNITS FOR 0i ......................207
   (3 VDC) .........................................................................37           Connection of One to Two Serial Spindles ....................73
   Battery for Separate Absolute Pulsecoders (6VDC) ......42                                     CONNECTION OF OPERATOR'S PANEL I/O
   Board status..................................................................331             MODULE (FOR MATRIX INPUT) ............................153
   BOARD-MOUNTED CONNECTORS .......................411                                           CONNECTION OF OPERATOR'S PANEL I/O
                                                                                                 MODULE AND POWER MAGNETICS CABINET
<C>                                                                                              I/O MODULE ..............................................................169
   Cabinet ...........................................................................21
                                                                                                 Connection of Power Supply...................................86,104
   Cable clamp and shield processing ................................19
                                                                                                 CONNECTION OF TERMINAL TYPE I/O
   Cable connection to a terminal block ...........................306
                                                                                                 MODULE.....................................................................282
   CABLE CONNECTORS .............................................411
                                                                                                 CONNECTION OF THE I/O LINK-AS-i
   Cable for Power Supply to Control Unit ..........37,210,359
                                                                                                 CONVERTER..............................................................317
   Cable J155....................................................................440
                                                                                                 Connection of the LCD Unit with a Touch Panel...........68
   Cable J156A (A quad B interface) ...............................441
                                                                                                 CONNECTION OF THE STAND-ALONE TYPE .....352
   Cable J156B (FANUC serial interface)........................442
                                                                                                 CONNECTION OF TYPE F ANALOG SERVO
   Cable J157....................................................................447
                                                                                                 INTERFACE................................................................439
   Cable J158....................................................................449
                                                                                                 CONNECTION OF TYPE M ANALOG SERVO
   Cable J37...............................................................443,447
                                                                                                 INTERFACE................................................................446
                                                                                           i-1
INDEX                                                                                                                                                              B-64303EN/03
                                                                                          i-2
B-64303EN/03                                                                                                                                                             INDEX
<I>                                                                                                Normal operation .........................................................344
   I/O Address ...........................................................250,268                  Notes on Installing a Separate Detector Interface Unit ..97
   I/O Address Allocation.................................................270                      Notes on Installing an Analog Input Separate Detector
   I/O Link connection .......................................242,261,325                          Interface Unit ...............................................................111
   I/O Link interface.........................................................234                  NOTICE .......................................................................453
   I/O Mapping.................................................................251
   I/O MODULE TYPE-2 FOR CONNECTOR PANEL.183                                                     <O>
   I/O Signal Requirements and External Power Supply                                               Operator's panel specification ......................................280
   for DO ..........................................................................221            OPTICAL FIBER CABLE...........................................425
   I/O signal specifications ...............................................284                    Order specification ................................................254,279
   In case of using the built-in pulse coder................439,446                                ORDER SPECIFICATIONS........................................437
   In case of using the separate detector....................439,447                               Other Notes .............................................148,165,180,205
   Input Signal Requirements (Parallel interface) ..............91                                 Others ....................................................................314,345
   Input Signal Rules for the High-speed Skip (HDI) ........61                                     Outline drawing and panel-cut drawing of the small
   Input Signal Specifications...........................................107                       machine operator's panel ..............................................274
   Input/output data area...................................................329                    Overall Connection Diagram............ 153,169,258,296,323
   Installation................................ 9,96,110,294,320,343,356                           Override signals ....................................................250,269
   Installation conditions ...........................................284,319
   Installation Environment ..............................................362                    <P>
   Installation of the Control Unit ......................................29                       Parallel DO (output signal) connection ........................316
   Installing the Control Unit............................................357                      PARAMETER SETTING ............................................454
   Interface to the Servo Amplifiers ...................................83                         PERIPHERAL EQUIPMENT AND CONNECTION..363
   Inter-module connection ..............................................305                       Personal Computer Specification .................................362
                                                                                                   Pin assignment .............................................................240
<K>                                                                                                POSITION CODER .......................................................81
   Key Layout of MDI........................................................46                     POWER AND HEAT GENERATED ..........................451
   Key Symbol Indication on Machine Operator’s Panel                                               Power connection ...........................................260,297,323
   ..............................................................................255,280           Power Connection .................................................154,170
   Keyboard of main panel ...............................................250                       Power ON/OFF control signal connection ...................243
   Keyboard of the operator's panel..................................268                           Power Supply Capacities of CNC-related Units.............10
                                                                                                   Power Supply Capacity ....................................10,286,356
<L>                                                                                                Power Supply Connection .........................32,199,241,358
   Layout of the key sheet (Same for both the small                                                Power Supply for the Control Unit.................................32
   machine operator's panel and small machine operator's                                           Power Supply Precautions............................................123
   panel B)........................................................................276             Power Supply Rating....................................................452
   LED indication.............................................................338                  Power supply specification....................................255,280
   LED Status Indication and Setting Switch Operation ..338                                        Power-off Sequence ................................................36,359
   LINKING THE EMBEDDED ETHERNET                                                                   Power-on Sequence .................................................36,358
   INTERFACE..................................................................62                   PREFACE .................................................................... p-1
   LIQUID CRYSTAL DISPLAY (LCD)........................434                                         Procedure for Installing Personal Computer Interface
                                                                                                   Boards ..........................................................................362
<M>                                                                                                Punch Panel (for Stand-alone Type Control Unit) .......365
   Main panel specification ..............................................254
   Maintenance Parts ........................................................282                 <R>
   Manual Pulse Generator Connection                                                               Recommended Cables ..................................................363
   ........................................... 141,163,177,199,246,261,305                         Recommended Connectors...........................................414
   Maximum Number of Units that can be Connected .....237                                          RECOMMENDED CONNECTORS, APPLICABLE
   Meaning of key symbols .......................................255,280                           HOUSINGS, AND CABLES .......................................413
   Measures Against Surges due to Lightning....................28                                  RS-232-C Interface Specification...................................53
   MEMORY CARD INTERFACE .................................435                                      RS-232-C Serial Port......................................................51
   Method of common pin expansion ...............................314
   Module Installation ......................................................144                 <S>
   Module Specifications....................................127,186,283                            SELECT SWITCH SW1 ..............................................453
   Mounting the Module...................................................201                       SEPARATE DETECTOR INTERFACE .......................84
                                                                                                   Separate Detector Interface (Parallel interface)..............90
<N>                                                                                                Separate Detector Interface (Serial Interface) ................88
   Network Installation.......................................................66                   Separate Detector Interface Unit Specification ..............85
   Noise Suppressor............................................................27                  Separating Signal Lines..................................................26
                                                                                           i-3
INDEX                                                                                           B-64303EN/03
<T>
  Temperature Rise within the Machine Tool Magnetic
  Cabinet ...........................................................................12
  Thermal Design of Operator's Panel ..............................13
  THERMAL DESIGN OF THE MACHINE TOOL
  MAGNETIC CABINET ................................................12
  Total Connection Diagram ...........................................239
  TOTAL CONNECTION DIAGRAMS.....................6,355
  TURNING ON AND OFF THE POWER TO THE
  CONTROL UNIT ...................................................32,358
  Types of commands executable by a ladder program ..333
  Types of modules .........................................................283
<U>
  Unit Dimensions...........................................................201
  UNITS CONNECTABLE WITH THE FANUC I/O
  LINK ............................................................................124
<V>
  Vertical-type Connectors .............................................411
<W>
  Weight..........................................................................286
                                                                                          i-4
                                                              Revision Record
              FANUC Series 0i/0i Mate-MODEL D CONNECTION MANUAL (HARDWARE) (B-64303EN)
* B - 6 4 3 0 3 E N / 0 3 *