ABB general machinery drives
ACS350, 0.5 to 15 Hp Technical Catalog
BUSINESS PROFILE
INDUSTRIES
PRODUCTS
APPLICATIONS
EXPERTISE
PARTNERS
SERVICES
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Contents
Choice 1: Simply contact your local ABB drives sales office and let them know what you want. Use page 4 as a reference section for more information.
OR
Choice 2: Build up your own ordering code using the simple 7-step approach below. Then, contact your local ABB Drives sales office.
Type code
ACS350
01U
02A4
J400
1 2 3 4 5 6
Product series
Ratings and Types
Voltages
Construction (# input phases)
Dimension
Options
Technical Data Control connections
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
ABB general machinery drives
ACS350 - 01U - 02A4 - 2 + J400
What is the ACS350 Customer Value?
Dramatically reduces programming time and costs with FlashDrop Optimal installation layout with unified height and depth for all frames and DIN rail mounting up to 15Hp Reduced cost with built-in brake chopper and EMC filter Reduced wiring time and costs for easy access I/O and plug-in Fieldbus modules Increased standard or custom programming capacity, flexibility and capabilities for simple to complex motor control with: - Built-in intelligent triggering - Supervising parameters - Speed compensation - User specified macros - PLC-like functions
Where can it be used?
ABB general machinery drives are designed to meet the requirements of an extensive range of machinery applications. The drive is ideal for food and beverage, material handling, textile, printing, rubber and plastics, and woodworking applications.
Highlights
FlashDrop Sensorless Vector Motor Control Sequence programming Impressive software and compact hardware Optimized interfaces for users and machines Unified height and depth Convenient installation Coated boards as standard Built-in brake chopper as standard
The ABB ACS350 general machinery drive is designed specifically for the OEM machine-building sector. In this sector, the manufacturing time per unit is critical. The ACS350 is designed to be the fastest drive in terms of installation, setting parameters and commissioning. The ACS350 has been designed to be as user-friendly as possible, yet provide high application flexibility. The ACS350 offers diverse functionality to cater to the most demanding needs. Benefits
What are the ACS350's Main Features and Benefits supporting Customer Value?
Features
FlashDrop Sequence programming Software User interfaces
Notes
New fast, safe and trouble free method to download parameters available without electricity - Patented. Application specific 8-state programming with comprehensive triggering conditions. Sensorless vector and closed loop vector control Blank cover Basic panel with numerical display Advanced control panel with clear alphanumerical dynamic menus, real time clock and 14 languages. Screw, DIN-rail, sideways and side-by-side mounting. Unified height and depth. Enclosed plug-in type of fieldbus adapter. 2nd environment filter complying with IEC 61800-3 as standard. Protections against moisture and hostile particles as standard. 100% braking capability Motor output and I/O protected against miswiring. Protection against unstable supply networks. Coated boards included as standard.
Faster and easier drive set up and commissioning. Logic programming included as standard with PLC-like functions. State of the art technology and performance with exceptional flexibility. Cost efficient approach offering different control panels according to functionality need.
Cabinet compatibility Fieldbuses Built-in EMC filter Coated boards Built-in Brake Chopper Drive Protection
Optimum installation layout and efficient cabinet space usage. High speed communication with compact and robust fieldbus design. No extra space, parts, time or cost required. Longer lifetime in hostile environments. Reduced service. Reduced costs, saved space and simple wiring. Latest solutions to protect the drive and offer troublefree use and the highest quality
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Technical specification
ACS350 - 01U - 02A4 - 2 + J400
Input connection
Voltage and power range 1-phase, 200 to 240 V 10% 0.37 to 2.2 kW (0.5 to 3 hp) 3-phase, 200 to 240 V 10% 0.37 to 4 kW (0.5 to 5 hp) 3-phase, 380 to 480 V 10% 0.37 to 11 kW (0.5 to 15 hp) 48 to 63 Hz 0.98
EMC (according to EN61800-3)
2nd environment filter, unrestricted distribution with 30 m (98 ft) cable- standard.
Programmable control connections
Two analog inputs Voltage signal Unipolar Bipolar Current signal Unipolar Bipolar Potentiometer reference value (X1A:4) Resolution Accuracy One analog output Auxiliary voltage Five digital inputs 0 (2) to 10 V, Rin > 312 k -10 to 10 V, Rin > 312 k 0 (4) to 20 mA, Rin = 100 -20 to 20 mA, Rin = 100 10 V 1% max. 10 mA, R < 10 k 0.1% 1% 0 (4) to 20 mA, load < 500 24 V DC 10%, max. 200 mA 12 to 24 V DC with internal or external supply, PNP and NPN, pulse train 0 to 16 kHz 2.4 k NO + NC 250 V AC/30 V DC 0.5 A/30 V DC; 5 A/230 V AC 2 A rms Transistor output 30 V DC 100 mA/30 V DC, short circuit protected 10 to 16 kHz 1 Hz 0.2%
Frequency Power factor
Output connection
Voltage Frequency Continuous loading capability
(constant torque at a max. ambient temperature of 400C)
3-phase, from 0 to USUPPLY 0 to 500 Hz Rated output current I2N
Overload capacity
(at a max. ambient temperature of 400C)
1.5 x I2N for 1 minute every 10 minutes 1.8 x I2N for 2 s every 10 minutes 4 kHz 4 to 12 kHz with 4 kHz steps (16 kHz, v 2.41+) 0.1 to 1800 s 0.1 to 1800 s Brake chopper- standard (100% braking capability)
Switching frequency Default Selectable Acceleration time Deceleration time Braking
Input impedance One relay output Type Maximum switching voltage Maximum switching current Maximum continuous current One digital output Type Maximum switching voltage Maximum switching current Frequency Resolution Accuracy
Environmental limits
Ambient temperature Altitude Output current -10 to 40oC (14 to 104oF), no frost allowed 50oC (122oF) with 10% derating Rated current available at 0 to 1000 m (0 to 3281 ft) reduced by 1% per 100 m (328 ft) over 1000 to 2000 m (3281 to 6562 ft) Lower than 95% (without condensation) IP 20 / Protected Chassis NCS 1502-Y, RAL 9002, PMS 420 C IEC 60721-3-(1,2,3) No conductive dust allowed Class 1C2 (chemical gases) Class 1S2 (solid particles) Class 2C2 (chemical gases) Class 2S2 (solid particles) Class 3C2 (chemical gases) Class 3S2 (solid particles)
Relative humidity Protection class Enclosure color Contamination levels Transportation Storage Operation
Serial communication
Fieldbuses Refresh rate PROFIBUS DP Plug-in type < 10 ms (between drive and fieldbus module) 9-pin D-connector Baud rate up to 12 Mbit/s PROFIBUS DP and PROFIBUS DPV1 Network side based on PROFIdrive profile. 5-pin screw type connector Baud rate up to 500 kbit/s Network side based on ODVA AC/DC drive profile. 9-pin D-connector Baud rate up to 1 Mbit/s Network side based on CiA DS402 profile. 4-pin screw type connector Baud rate up to 115 kbit/s Available Q3, 2007
DeviceNet
Product compliance
Low Voltage Directive 73/23/EEC with supplements Machinery Directive 98/37/EC EMC Directive 89/336/EEC with supplements Quality assurance system ISO 9001 Environmental system ISO 14001 UL, cUL, and CE approvals, C-Tick, GOST-R RoHs (Verify RoHS label) IEC/EN 61800-5-1 (2003) IEC/EN 60204-1 (1999) IEC/EN 61800-3 (2004)
CANopen
Modbus RTU Modbus TCP EtherNet IP
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Ratings, types, voltages and construction
ACS350 - 01U - 02A4 - 2 + J400
EMC according to EN61800-3
2nd environment filter, unrestricted distribution, C3 with 30m (98 ft) cable, built-in as standard.
EMC Standards in general
EN 61800-3/A11 (2000), product standard EN 61800-3 (2004), EN 55011, product product standard family standard for industrial, scientific and medical (ISM) equipment 1st environment, unrestricted distribution 1st environment, restricted distribution 2nd environment, unrestricted distribution 2nd environment, restricted distribution Category C1 Group 1 Class B Group 1 Class A Group 2 Class A Not applicable
Category C2
Category C3
Category C4
Type code
This is a unique reference number that clearly identifies the drive by power rating, voltage, and construction. Once you have selected the type code, the frame size can be used to determine the drive dimensions, shown on the next page.
Type code
Frame size
Ratings PN hp 0.5 1 1.5 2 3 0.5 0.75 1 1.5 2 3 5 0.5 0.75 1 1.5 2 3 5 7.5 10 15 PN kW 0.37 0.75 1.1 1.5 2.2 0.37 0.55 0.75 1.1 1.5 2.2 4.0 0.37 0.55 0.75 1.1 1.5 2.2 4.0 5.5 7.5 11.0 I2N A 2.4 4.7 6.7 7.5 9.8 2.4 3.5 4.7 6.7 7.5 9.8 17.6 1.2 1.9 2.4 3.3 4.1 5.6 8.8 12.5 15.6 23.1
1-phase supply voltage 200 - 240 V units ACS350-01U-02A4-2 ACS350-01U-04A7-2 ACS350-01U-06A7-2 ACS350-01U-07A5-2 ACS350-01U-09A8-2 ACS350-03U-02A4-2 ACS350-03U-03A5-2 ACS350-03U-04A7-2 ASC350-03U-06A7-2 ACS350-03U-07A5-2 ACS350-03U-09A8-2 ACS350-03U-17A6-2 ACS350-03U-01A2-4 ACS350-03U-01A9-4 ACS350-03U-02A4-4 ACS350-03U-03A3-4 ACS350-03U-04A1-4 ACS350-03U-05A6-4 ACS350-03U-08A8-4 ACS350-03U-12A5-4 ACS350-03U-15A6-4 ACS350-03U-23A1-4 R0 R1 R1 R2 R2 R0 R0 R1 R1 R1 R2 R2 R0 R0 R0 R1 R1 R1 R1 R3 R3 R3
Voltages
The ACS350 is available in two voltage ranges: 2 = 200 - 240 V 4 = 380 - 480 V
3-phase supply voltage 200 - 240 V units
Construction
"01U" or the "03U" within the type code indicates the number of input phases for the power and EMC filtering. 01 = 1-phase (200 - 240V only) 03 = 3-phase (200 - 240V and 380 - 480V) U = EMC filter disconnected, 60 Hz motor data (In case the filter is required it can easily be connected.)
3-phase supply voltage 380 - 480 V units
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Dimensions, weight and noise
ACS350 - 01U - 02A4 - 2 + J400
Cabinet-mounted drives (IP 20 UL open)
Wall-mounted drives (NEMA 1)
H4 H5 H1 H2 H3
D W
Frame Size R0 R1 R2 R3
1)
D W
Noise level dBA 50 60 60 60
2)
H1 (in) 6.65 6.65 6.65 6.65
IP20 (cabinet) / UL Option H2 H3 W D Weight (in) (in) (in) (in) (lb) 2.4 7.95 9.41 2.76 6.34 7.95 7.95 7.95 9.41 9.41 9.29 2.76 4.13 6.65 6.34 6.5 6.65 2.9/2.61) 3.3 5.5
Frame Size R0 R1 R2 R3
NEMA 1 H4 (in) H5 (in) W (in) 2.76 2.76 4.13 6.65 D (in) 6.65 6.65 6.65 6.97 Weight (lb) 3.3 3.7/3.52) 4.2 6.8
Noise level dBA 50 60 60 60
10.12 11.02 10.12 11.02 10.12 11.10 10.24 11.77
UN=200...240 V: 2.9 lb, UN=380...480 V: 2.6 lb
UN=200...240 V: 3.7 lb, UN=380...480 V: 3.5 lb
NOTES: H1 = Height without fastenings and clamping plate. H2 = Height with fastenings but without clamping plate. H3 = Height with fastenings and clamping plate. H4 = Height with fastenings and NEMA 1 connection box. H5 = Height with fastenings, NEMA 1 connection box and hood. W = Width D = Depth
Options
ACS350 - 01U - 02A4 - 2 + J400
How to select options
The options shown in the table are available with the ACS350. Each has an option-unique 4-digit code, which is shown in the first column. This option code is added to the end of the basic drive option code using a "+" code. For example, an ACS350-03U-01A2-4+J400 would be a base drive with an Advanced Control Panel shipped together. Option descriptions are provided in the subsequent pages.
Selection table
Control panel J400 J404 Potentiometer J402 Fieldbus K451 K454 K457 K458 External Option Advanced control panel Basic control panel Potentiometer DeviceNet PROFIBUS DP CANopen ModBus RTU ModBus RTU PCB ACS-CP-A ACS-CP-C MPOT-01 FDNA-01 FPBA-01 FCAN-01 FMBA-01 FRSA-00
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Options
ACS350 - 01U - 02A4 - 2 + J400
User interfaces
Panel cover The purpose of the panel cover is to protect the drive's connection surfaces. In addition, there are two alternative control panels available as options. Basic control panel The basic control panel features a single line numeric display. The panel can be used to control the drive, set the parameter values or copy them from one drive to another. Advanced control panel For easy drive programming, a detachable, multi-lingual alphanumeric advanced control panel is available. The control panel provides assistants and a built-in help function to guide the user. It includes a real time clock, which can be used during fault logging and in controlling the drive, such as start/stop. The control panel can be used for copying parameters for back up or for downloading to another drive. A large graphical display and soft keys make it extremely easy to navigate. Potentiometer Potentiometer MPOT-01 with two switches: start/stop and forward/reverse. Polarity (PNP or NPN) is selected with DIP switches. No external power source is needed for the potentiometer. Panel mounting kits The panel mounting kits enable mounting of control panels on cabinet doors. They include a 3m extension cable, gasket, and all mounting hardware. OPMP-01: Permits mounting of panel to external surface of NEMA 1 or NEMA 12 enclosures. The panel remains removeable. ACS/H-CP-EXT: permits permanent mounting of panel to external surface of NEMA 1 or NEMA 12 enclosures. ACS/H-CP-EXT-IP66: permits permanent mounting of panel to external surface of NEMA 4x enclosures. FlashDrop (MFDT-01) FlashDrop is a powerful palm sized tool for fast and easy parameter selecting and setting. This tool can be used to download parameters to a drive in as little as two seconds. Using this tool, it is also possible to hide selected parameters to protect the machine. Only the parameters needed in the application are shown. FlashDrop does not require the drive to be powered. The drives shipping container is also designed to allow use of the FlashDrop tool without removing the drive. The MFDT-01 includes the DrivePM (Drive Parameter Manager) FlashDrop software tool to create, edit and copy (MFDT-01) parameter sets.
Basic control panel
Panel cover
Potentiometer
Advanced control panel
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Options
ACS350 - 01U - 02A4 - 2 + J400
Machine interfaces
Plug-in fieldbus modules bring connectivity to major automation systems. A single twisted pair of wire avoids large amounts of conventional cabling, thereby reducing costs and increasing system reliability. The ACS350 supports the following fieldbus protocols: DeviceNet PROFIBUS DP CANopen Modbus RTU Modbus TCP/IP, Ethernet IP (Available Q3, 2007)
Protection and installation
NEMA 1 kit The NEMA 1 kit includes a conduit box and hood for protection against dirt and dust. Two kits are available to cover all frame sizes of the ACS350. MUL1-R1 covers frame sizes R0 through R2 and MUL1-R3 covers frame size R3. Terminal Cover The terminal cover is for protection of the I/O connections. Clamping Plates The clamping plates are used for protection against electrical disturbances when compliance to EMC is mandated. The clamping plates are included in the drive package as standard.
FlashDrop connection Analog I/O Relay output Digital inputs Digital output
Terminal cover
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Options
External
A separate order line is required for any of these external options.
FlashDrop (MFDT-01)
FlashDrop is a powerful palm sized tool for fast and easy parameter selecting and setting. It provides the ability to hide selected parameters to protect the machine. Only the parameters needed in the application are shown. The tool can copy parameters between two drives or between a PC and a drive. All this can be accomplished without a power connection to the drive - in fact, it is not even necessary to unpack the drive. DrivePM DrivePM (Drive Parameter Manager) is a software tool to create, edit and copy parameter sets for FlashDrop. For each parameter/group the user has the ability to hide it, preventing the user from seeing the parameter or parameter group. DrivePM requirements Windows 2000/XP Serial port from a PC FlashDrop tool includes FlashDrop DrivePM software on a CD-Rom User's manual on CD-Rom Cable OPCA-02 for connection between the PC and FlashDrop Batter charger
Brake resistors
The brake resistor is selected using the table below. For more information about the selection of brake resistors, see the ACS350 Price List (ACS350-PNPL01U-EN).
Selection table
Type code Frame size R0 R1 R1 R2 R2 R0 R0 R1 R1 R1 R2 R2 R0 R0 R0 R1 R1 R1 R1 R3 R3 R3 Rmin ohm 70 40 40 30 30 70 70 40 40 30 30 30 200 175 165 150 130 100 70 40 40 30 Rmax ohm 390 200 130 100 70 390 260 200 130 100 70 40 1180 800 590 400 300 200 110 80 60 40 hp 0.5 1 1.5 2 3 0.5 0.75 1 1.5 2 3 5 0.5 0.75 1 1.5 2 3 5 7.5 10 15 PBRmax kW 0.37 0.75 1.1 1.5 2.2 0.37 0.55 0.75 1.1 1.5 2.2 4 0.37 0.55 0.75 1.1 1.5 2.2 4 5.5 7.5 11
1-phase supply voltage 200 - 240 V units ACS350-01U-02A4-2 ACS350-01U-04A7-2 ACS350-01U-06A7-2 ACS350-01U-07A5-2 ACS350-01U-09A8-2 ACS350-03U-02A4-2 ACS350-03U-03A5-2 ACS350-03U-04A7-2 ASC350-03U-06A7-2 ACS350-03U-07A5-2 ACS350-03U-09A8-2 ACS350-03U-17A6-2 ACS350-03U-01A2-4 ACS350-03U-01A9-4 ACS350-03U-02A4-4 ACS350-03U-03A3-4 ACS350-03U-04A1-4 ACS350-03U-05A6-4 ACS350-03U-08A8-4 ACS350-03U-12A5-4 ACS350-03U-15A6-4 ACS350-03U-23A1-4
3-phase supply voltage 200 - 240 V units
3-phase supply voltage 380 - 480 V units
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Options
Software tools
A separate order line is required for any of these external options.
DriveWindow Light 2.x
DriveWindow Light 2.x is an easy-to-use start-up and maintenance tool for ACS350 drives. It can be used in an offline mode, enabling parameter setting at the office before going to the actual site. The parameter browser enables viewing, editing and saving of parameters. The parameter comparison feature makes it possible to compare parameter values between a drive and a saved file. With the parameter subset, you can create individual parameter sets. Controlling the drive is also available using DriveWindow Light. With DriveWindow Light, you can monitor up to four signals simultaneously both in graphical or numerical format. Any signal can be set to stop being monitored at a pre-defined level. Sequence Programming Tool For ACS350 drives, DriveWindow Light 2.x offers sequence programming. This tool is useful for setting the drive sequence programming parameters. The tool draws the program graphically on the PC screen showing used states, active state, transition conditions, possible transition delay as well as references and ramps. Sequence programming enables application specific programming. This new and easy way to preset sequences reduces the need for an external programmable logic control (PLC). Start-up Wizards Start-up wizards make the setting of parameters easy. Simply launch the wizard, select an appropriate assistant (e.g. for setting analog outputs) and all parameters related to this function are shown together with help pictures.
Highlights Sequence programming tool for ACS350 Editing, saving and downloading parameters Graphical and numerical signal monitoring Drive control Start-up wizards
DriveWindow Light requirements Windows NT/2000/XP Serial port from a PC
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Technical data
Cooling
The ACS350 is configured with cooling fans as standard. The cooling air must be free from corrosive materials and must not be above the maximum ambient temperature of 40oC (50oC with derating). For more specific limits see the Technical specification - Environmental limits in this catalog.
Fuses
Standard semi-conductor fuses can be used with the ACS350. Recommended fuse ratings are shown in the table below.
Selection table
Type code Frame size IEC Fuses A 10 16 20 25 35 10 10 10 16 16 16 25 10 10 10 10 16 16 20 25 35 50 Fuse ) type* gG gG gG gG gG gG gG gG gG gG gG gG gG gG gG gG gG gG gG gG gG gG A 10 20 25 30 35 10 10 15 15 15 20 35 10 10 10 10 15 15 25 30 35 50 UL Fuses Fuse ) type* UL class T UL class T UL class T UL class T UL class T UL class T UL class T UL class T UL class T UL class T UL class T UL class T UL class T UL class T UL class T UL class T UL class T UL class T UL class T UL class T UL class T UL class T
Cooling air flow
Type code Frame size Heat dissipation main circuit W 25 46 71 73 96 19 31 38 60 62 83 152 11 16 21 31 40 61 94 130 173 266 BTU/Hr 85 157 242 249 328 65 106 130 205 212 283 519 38 55 72 106 137 208 321 444 591 908
3
1-phase supply voltage 200 - 240 V units Air flow m /h
-*
)
ACS350-01U-02A4-2 ACS350-01U-04A7-2 ACS350-01U-06A7-2 ACS350-01U-07A5-2 ACS350-01U-09A8-2 ACS350-03U-02A4-2 ACS350-03U-03A5-2 ACS350-03U-04A7-2 ASC350-03U-06A7-2 ACS350-03U-07A5-2 ACS350-03U-09A8-2 ACS350-03U-17A6-2 ACS350-03U-01A2-4 ACS350-03U-01A9-4 ACS350-03U-02A4-4 ACS350-03U-03A3-4 ACS350-03U-04A1-4 ACS350-03U-05A6-4 ACS350-03U-08A8-4 ACS350-03U-12A5-4 ACS350-03U-15A6-4 ACS350-03U-23A1-4
R0 R1 R1 R2 R2 R0 R0 R1 R1 R1 R2 R2 R0 R0 R0 R1 R1 R1 R1 R3 R3 R3
ft /min -*
)
1-phase supply voltage 200 - 240 V units ACS350-01U-02A4-2 ACS350-01U-04A7-2 ACS350-01U-06A7-2 ACS350-01U-07A5-2 ACS350-01U-09A8-2 ACS350-03U-02A4-2 ACS350-03U-03A5-2 ACS350-03U-04A7-2 ASC350-03U-06A7-2 ACS350-03U-07A5-2 ACS350-03U-09A8-2 ACS350-03U-17A6-2 ACS350-03U-01A2-4 ACS350-03U-01A9-4 ACS350-03U-02A4-4 ACS350-03U-03A3-4 ACS350-03U-04A1-4 ACS350-03U-05A6-4 ACS350-03U-08A8-4 ACS350-03U-12A5-4 ACS350-03U-15A6-4 ACS350-03U-23A1-4 R0 R1 R1 R2 R2 R0 R0 R1 R1 R1 R2 R2 R0 R0 R0 R1 R1 R1 R1 R3 R3 R3 24 24 21 21
) -* ) -*
14 14 12 12 -* ) -* 14 14 12 12 31 -* ) -* -* 8 8 11 14 31 31 42
) ) )
3-phase supply voltage 200 - 240 V units
3-phase supply voltage 200 - 240 V units
24 24 21 21 52 -* ) -* -*
) )
3-phase supply voltage 380 - 480 V units
3-phase supply voltage 380 - 480 V units
13 13 19 24 52 52 71
*) According to IEC-60269 standard.
*) Frame Size R0 with free convection cooling
Free space requirements
Enclosure type All frame sizes Space above mm/in 75/3.83 Space below mm/in 75/3.83 Space on left/right mm/in 0/0
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Control connections
These connections are shown as examples only. Please refer to the ACS350 User's Manual (3AFE68462401) for more detailed information.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com