MTL4516
MTL4516/C  MTL5516C
SWITCH/ PROXIMITY
DETECTOR INTERFACE
Hazardous area
680
2-channel, with line fault detection
22k
FSM
See also common specification
FUNCTIONAL SAFETY
MANAGEMENT
Number of channels
Two
IEC 61508:2010
Location of switches
Zone 0, IIC, T6 hazardous area
Div. 1, Group A hazardous location
Location of proximity detector
Zone 0, IIC, T46 hazardous area if suitably certified
Div. 1, Group A hazardous location
Hazardous-area inputs
Inputs conforming to BS EN6094756:2001 standards for
proximity detectors (NAMUR)
Voltage applied to sensor
7 to 9V dc from 1k 10%
Input/output characteristics
Normal phase
	 Outputs closed if input > 2.1mA (< 2k in input circuit)
	 Outputs open if input < 1.2mA (> 10k in input circuit)
Hysteresis: 200A (650) nominal
Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit. Line faults are
indicated by an LED for each channel. The channel output relay is
de-energised if an input line fault is detected.
Open-circuit alarm on if Iin < 50A
Open-circuit alarm off if Iin > 250A
Short-circuit alarm on if Rin < 100
Short-circuit alarm off if Rin > 360
Note:	 Resistors must be fitted when using the LFD facility with a contact input
500 to 1k in series with switch
20k to 25k in parallel with switch
Safe-area output
Two single-pole relays with changeover contacts
	
Note: reactive loads must be adequately suppressed
Relay characteristics
MTL4516/C
MTL5516C
Response time:
10ms maximum
10ms maximum
Contact rating
(Safe Area):
10W, 0.5A,
35V dc
250V ac, 2A, cos >0.7,
40V dc, 2A, resistive load
Contact rating
(Zone 2):
10W, 0.5A,
35V dc
35V, 2A, 100VA.
Maximum current consumption
35mA at 24V
Power dissipation within unit
0.84W at 24V
12
11
10
6
5
The MTLx516/C enable two safe-area loads to be controlled by a switch
or proximity detector located in a hazardous-area. When selected,
open or short circuit conditions in the field wiring are detected by
the line-fault-detect (LFD) facility and also indicated on the top of the
module. Phase reversal for each channel is selected by a switch on
the side of the module and output is provided by changeover relay
contacts.
SPECIFICATION
Safe area
680
22k
13
Switch-type sensors
require resistors
if LFD is selected
Ch 2
9
8
7
+
2
14
Ch 1
20 to 35V dc
Vs+
Vs
MTL4516C
Hazardous area
Safe area
680
6
5
 4
22k
12
11
10
680
9
8
7
+
2
 1
22k
13
Switch-type sensors
require resistors
if LFD is selected
Ch 2
14
Ch 1
20 to 35V dc
Vs+
Vs
MTL5516C
Hazardous area
Safe area
680
+
22k
6
5
7
8
9
Ch 2
10
11
12
Ch 1
680
+
2
22k
Vs
Vs+
13
14
Switch-type sensors
require resistors
if LFD is selected
20 to 35V dc
LED indicators
Green: power indication
Yellow: two: channel status, on when output energised
Red: two: LFD indication, on when line fault detected
Safety description (each channel)
Uo =10.5V Io =14mA Po =37mW Um = 253V rms or dc
SIL
2
IEC 61508:2010
SIL
3
IEC 61508:2010
SIL capable
These models have been assessed for use in
IEC 61508 functional safety applications.
SIL2 capable for a single device (HFT=0)
SIL3 capable for multiple devices in safety
redundant configurations (HFT=1)
See data on MTL web site and refer to the
safety manual
The given data is only intended as a product description and should not be regarded as a legal
warranty of properties or guarantee.
In the interest of further technical developments, we reserve the right to make design changes.
Measurement Technology Limited,
Great Marlings, Butterfield, Luton
Beds, LU2 8DL, UK.
Tel: + 44 (0)1582 723633 Fax: + 44 (0)1582 422283
E-mail: mtlenquiry@eaton.com
www.mtl-inst.com
12
 2016 MTL
All Rights Reserved
Publication No.
EPSx516/C Rev5 250516