Uniclass                        EPIC
JR20/JV50 L731/L75624            L634 L2242 L511
                                                              CI/SfB
                                                                        (56.3)
                                                              May 2009/rev Dec 2009   WM422
                Intelligent stormwater solutions by Wavin
Oil Separation Systems
Product and Installation Guide
                For residential, commercial, industrial and infrastructure applications
         Customer Services   Technical Enquiries   Technical Fax   Email
Page 2   01249 766611        01249 766655          01249 766653    technical.design@wavin.co.uk
Contents
     Separators
     Introduction                                            4
        Introduction to the Intesio Oil Separation Systems    4
        Benefits of the System                               4
     Applications                                            5
        Typical Full Retention Separation System            5
        Typical By-Pass Separation System                   5
     Product Selector                                    6-9
        P/E Unequal Flow Regulation Chamber                  6
        P/E Equal Sand/Sludge Separation Chamber             7
        P/E Equal Oil Separation Chamber                     8
        P/E Unequal Sampling Chamber                         9
     Typical Application                              10-12
        By-pass Configuration                           10-11
        Full Retention Configuration                         12
     Typical Installation Methods                     13-14
                                                                  Wavin operates a programme of continual product development, and therefore reserves the right to
                                                                  modify or amend the specification of their products without notice. All information in this publication
                                                                  is given in good faith, and believed to be correct at the time of going to press. However, no
                                                                  responsibility can be accepted for any errors, omissions or incorrect assumptions. Users should
                                                                  satisfy themselves that products are suitable for the purpose and application intended.
                                                                                      www.intesio.co.uk
                                                                                                                               Page 3
The Intesio Oil Separation Systems  Introduction
Intesio  for optimum stormwater management
                                                                           The system consists of the following components:
Continuing urban development, a changing climate and the
consequences of intensified rainfall: all are increasingly prominent
issues on the political and environmental agenda. In combination,         P/E Unequal Flow
they represent a complex need for the most intelligent, effective         Regulation Chamber
solution.
Intesio is Wavins specialist approach to responsible management
of stormwater, including its efficient capture, transportation,
control, cleansing and re-use. Were ready to contribute at any
stage in a project, with one central goal: to help achieve the
optimum project outcome. Our in-depth expertise, design insight
and proven system technology is applied wherever required to
ensure each installed scheme achieves maximum efficiency of
cost and integrated function, and full compliance with the latest
regulatory criteria.
                                                                          P/E Equal Sand/Sludge
                                                                          Separation Chamber
                                                                          (NSB151002 shown)
                                                                          P/E Equal NSB Oil
                                                                          Separation Chamber
   Benefits of the System
    Comprehensive range of separators
    Tested to, and meets the requirements of, BS EN 858-1
    Included within the Environment Agency List of
     Recommended Suppliers
                                                                          P/E Unequal Sampling
    Fulfils the UK requirements for Oil Separators (PPG3)                Chamber
    Suitable for use within car parks, roads and industrial
     areas
    Prevents the washout of the separator chamber during
     heavy downpours
    Economical solution for stormwater treatment of large
     areas
    Treats up to 95% of the annual rainfall
                                    Customer Services        Technical Enquiries   Technical Fax    Email
     Page 4                         01249 766611             01249 766655          01249 766653     technical.design@wavin.co.uk
The Intesio Oil Separation Systems  Applications
Due to the unique modular nature of the Intesio Oil Separation
System, the Oil Separation Chamber can be designed/installed in
such a way as to be fully compliant with the requirements of the
Environment Agencys PPG3 and European Standard BS EN 858-1
for both Full Retention and By-Pass separators.
Typical Full Retention Separation System                                               P/E Equal Sand/Sludge     Sludge and oil alarms linked to
The system fully treats all flows generated by rainfall rates of up to                   Separation Chamber        remote communication unit
65mm/hr. Full retention separators are used where there is a high        Surface water
                                                                            run-off
risk of regular contamination / spillage. The Intesio-Oil Separation
Chamber has an automatic closure devise incorporated in to the
unit as standard, compulsory for all EA PPG3 compliant full
                                                                                                                            P/E Unequal Sampling
retention separators.                                                                                                       Chamber
Contaminates enter the Oil Separation Chamber, the contaminates
                                                                                Clay or plastic pipe
are retained for a period which ensures that the oil which is lighter
then water separates and rises to the surface of the separator and
thus is retained within the Coalescing Filter Plates. See page 12
                                                                                           P/E Equal Oil Separation Chamber
for typical system layout.
                                                                                         Typical Full Retention separation system
Typical By-Pass Separation System                                                              P/E Unequal Flow
                                                                                                 Regulation Chamber
The system fully treats flows generated by rainfall rates of up to
                                                                         Surface                           Sludge and oil alarms linked to
6.5mm/hr. These types of separators are used when it is                                                    remote communication unit
                                                                          water
considered an acceptable risk not to provide full treatment for          run-off                                         Clay or plastic pipe
high flows, for example where the risk of spillage is small such as
                                                                                                                                P/E Unequal
short stay car parks.                                                                                                           Sampling Chamber
The system is designed to treat all of the first flush flow up to the
designed discharge rate. Any discharge in-excess of the design
rate is allowed to by-pass the separation chambers, thus keeping
contaminates, contained within the chambers. See Page 10 for             P/E Equal Sand/Sludge
typical system layout.                                                   Separation Chamber
                                                                                      P/E Equal Oil Separation Chamber
                                                                                           Typical By-Pass separation system
                                                                                      www.intesio.co.uk
                                                                                                                      Page 5
The Intesio Oil Separation System  Product Selector
P/E Unequal Flow Regulation Chamber
During a heavy downpour, the Intesio Unequal Flow Regulation
Chamber adjusts and restricts the incoming flow to the Oil
Separation Chamber. The Flow Regulation Chamber contains a
mechanical flow regulator, which provides an even design flow to
the Oil Separator. Excess flow is directed away from the Oil
Separator, via a bypass pipe to the discharge point as appropriate,
avoiding the Oil Separator. This design prevents any washout of
the oils and sands which are contained within the Oil Separator.
The Flow Regulation Chamber is designed to process
approximately 95% of the annual run-off.
                                     Pivot
                                                Float
                                                                                         Typical P/E Unequal Flow Regulation Chamber
                 Bypass pipe
                       Unrestricted flow is directed
                        through sand/sludge/oil
                                separators
During low flow conditions the discharge is directed through the separator.
                                                Float
                                    Pivot
                 Bypass pipe
                             Reduced flow is
                             directed through
                              sand/sludge/oil
                                separators
During peak flow conditions the minimum flow, equal to low flow conditions                       Detail of Flow Regulation Chamber
 is directed through the separator. Excess flow is directed to the discharge
                          point via the bypass pipe.
  Table 1 P/E Unequal Flow Regulation Chamber Properties
  Part no.         Overall            Overall              Low       Peak      Inlet    Outlet    Outlet to
                  diameter            height               flow      flow      (mm)     (mm)      separator
                    (mm)               (mm)              (lit/sec) (lit/sec)                        (mm)
  NSB31001          1300     1630 (min) - 3230 (max)         3         9       160       160         110
  NSB61001          1300     1630 (min) - 3230 (max)         6         18      225       225         160
  NSB101001         1300     1630 (min) - 3230 (max)        10         30      225       225         160
  NSB151001         1300     1630 (min) - 3230 (max)        15         45      300       300         225
                                       Customer Services          Technical Enquiries     Technical Fax       Email
     Page 6                            01249 766611               01249 766655            01249 766653        technical.design@wavin.co.uk
The Intesio Oil Separation System  Product Selector
P/E Equal Sand/Sludge Separation Chamber
The function of the Intesio Equal Sand/Sludge Chamber is to
separate the sand and sludge contaminates from the surface
water discharge. This process contributes to the smooth
operation of the oil separator and subsequently can contribute to
lower maintenance costs. A sand/sludge chamber should precede
the oil separator. The discharge to be treated flows into the
sand/sludge chamber, allowing the solids to settle by means of
gravitation; the solid particles which are heavier than water settle
on the bottom of the separator. The solid-free rainwater then flows
from the unit into the oil separator. BS EN 858-1 states that a
sand /sludge trap should always be part of the oil separation
system.
For sizing/capacity of chamber see BS EN 858-2.
The Intesio Sand/Sludge Chamber, comes complete with a
SandSET 1000 Sludge Alarm. The sludge alarm indicates when
the unit is full and must be emptied. The timely emptying and
routine maintenance of the chamber will ensure the smooth
operation of the Sand/Sludge Chamber.
                                                                                    Typical P/E Equal Sand/Sludge Chamber
               Typical Sand/Sludge Separation Chamber                                      SandSET 1000 Sludge Alarm
  Table 2 P/E Equal Sand/Sludge Separation Chamber Properties
  Part no.           Overall                Overall               Inlet   Outlet         Sand
                    diameter                height                (mm)    (mm)          storage
                      (mm)                   (mm)                                         (lit)
  NSB31002            1300          1600 (min) - 3200 (max)        110     110            600
  NSB61002            1300          1600 (min) - 3200 (max)        160     160            600
  NSB101002           1350          2000 (min) - 3600 (max)        160     160            1000
  NSB151002        1750 (ball)      2180 (min) - 3780 (max)        225     225            2000
                                                                                   www.intesio.co.uk
                                                                                                            Page 7
The Intesio Oil Separation System  Product Selector
P/E Equal Oil Separation Chamber
Intesio Equal Oil Separation Chambers are Class 1 separators,
tested in accordance with BS EN 858-1. The chambers are
suitable for treating oily rainwater. The Intesio Oil Separation
Chambers are available in size classes NSB3, 6, 10 and 15.
The chambers cleaning process is based on the coalescent 3D
filter concept.
The Intesio Oil Separation Chambers are equipped with
coalescing plates, which separate oil from water. The process is
based on the fact that oil droplets congeal when they gather
together on the oleophilic (oil attracting) plates. As the size of the
droplets grows their upward velocity grows (Stokes Law). The oil
droplets travel along the angled plates and then travel through the
holes in the coalescing plates, always travelling to the surface.
The separated oil is stored as a homogeneous layer on the
surface of the water within the chamber.
The Intesio Oil Separator is made from strong recycled PE plastic.
The chambers are light to transport and easy to install when
compared to more traditional solutions. The spherical bottom of the
chamber allows for the complete emptying of the unit if required.
The Intesio Oil Separation Chamber comes complete with a
OilSET-1000 oil alarm. The oil alarm indicates when the coalescing
                                                                                          Typical P/E Oil Separation Chamber
plates should be cleaned. Routine maintenance of the unit will
ensure the smooth operation of the Oil Separator.
         Detail showing the coalescent 3D filter housing                                             OilSET 1000 Oil Alarm
  Table 3 P/E Equal Oil Separation Chamber Properties
  Part no.           Overall                 Overall                 Flow       Inlet         Outlet
                    diameter                 height                (lit/sec)    (mm)          (mm)
                      (mm)                    (mm)
  NSB31003             1750          2180 (min) - 3780 (max)             3       110           110
  NSB61003             1750          2180 (min) - 3780 (max)             6       160           160
  NSB101003            2170          2630 (min) - 4230 (max)         10          160           160
  NSB151003            2170          2630 (min) - 4230 (max)         15          225           225
                                     Customer Services         Technical Enquiries     Technical Fax     Email
     Page 8                          01249 766611              01249 766655            01249 766653      technical.design@wavin.co.uk
The Intesio Oil Separation System  Product Selector
P/E Unequal Sampling Chamber
The Intesio Unequal Sampling Chamber is available as an optional
extra, for use in connecting the discharge from the oil separator
back into the main discharge pipework. The chambers are
designed for use within the system when the components are
designed in a by-pass configuration. The sampling shaft makes it
possible to monitor the quality of the discharge, and also contains
a shut-off valve for use in case of emergencies.
Should a sampling chamber be required for a full retention system
use either:
a) a standard Wavin Tegra 600 Non Man-Entry Inspection Chamber,
or alternatively, if a shut-off valve is required,
b) the standard Intesio Sampling Shaft and simply close off the
appropriate inlet pipe using a standard coupler/plug.
                                                                                       Typical P/E Unequal Sampling Chamber
    Detail showing the Intesio Sampling Shaft shut-off valve handle           Detail showing the Intesio Sampling Shaft shut-off valve
                        (supplied with the unit)
  Table 4 P/E Unequal Sampling Chamber Properties
  Part no.             Overall                  Overall               Inlet   Outlet       Inlet from
                      diameter                  height                (mm)    (mm)         separator
                        (mm)                     (mm)                                         (mm)
  NSB31004              1160            1330 (min) - 2930 (max)       160      160            110
  NSB61004*             1160            1330 (min) - 2930 (max)       225      225            160
  NSB151004             1300            1730 (min) - 3330 (max)       300      300            225
  * For use in both NSB6 and NSB10 oil separation systems
                                                                                       www.intesio.co.uk
                                                                                                                Page 9
The Intesio Oil Separation System  By-pass Configuration
Figure 1 Typical off-line bypass system (attenuation process shown)                                       Communication unit
     Vent pipe                                                  Sludge alarm                                                   Oil alarm
                                                                                                                                Ground level
                   P/E Unequal Flow
                  Regulation Chamber
  Part long section AA
                                                            P/E Equal Sand/Sludge
                                                             Separation Chamber
                                                                                                       P/E Equal Oil
                                                                                                    Separation Chamber
  Venting requirements
  For petrol stations: Comply with Health and Safety Guidance Note 41 (HS(G)41)
  For other applications: Comply with BS EN 752 Building Drainage
                   P/E Unequal Flow
                  Regulation Chamber
  Plan
                                    P/E Equal Sand/Sludge                                                                   P/E Equal Oil
                                     Separation Chamber                                                                  Separation Chamber
                                   Customer Services         Technical Enquiries    Technical Fax    Email
    Page 10                        01249 766611              01249 766655           01249 766653     technical.design@wavin.co.uk
                                                      AquaCell                                             Geotextile wrap
                                                      Box Unit                                                  over
                                                      assembly                                           geomembrane wrap
                                                                                                          Discharge to watercourse
           P/E Unequal Sampling                                        Control Chamber
                 Chamber                                                       with
                                                                     Vortex flow control unit
                                                                                                    AquaCell
                                   Geotextile wrap over geomembrane wrap                        Box Unit assembly
AquaCell Box Unit Assembly
When using the bypass
arrangement for the infiltration
process, enclose the AquaCell
box unit assembly with a
geotextile wrap only
           P/E Unequal Sampling
                 Chamber                             Manifold pipe
                                                      connection
                                                                                                          Discharge to watercourse
                                                                       Control Chamber
                                                                               with
                                                                     Vortex flow control unit
                                                                                                                                     A
                                                                              www.intesio.co.uk
                                                                                                         Page 11
The Intesio Oil Separation System  Full Retention Configuration
Figure 2 Plan of typical on-line full retention system (with off-line attenuation process shown)
Arrangement equally suitable for the infiltration process,
but enclose the AquaCell box unit assembly with a geotextile wrap only
                                                                          AquaCell Box Unit assembly
                                                                  with geotextile wrap over geomembrane wrap
                                                                                                                                       Discharge
                                                                                                   Manifold pipe                           to
                                                                                                    connection                        watercourse
                                                                               Control Chamber
  P/E Equal Sand/Sludge                                                                with
   Separation Chamber              P/E Equal Oil                             Vortex flow control unit
                                Separation Chamber
Figure 3 Plan of typical on-line full retention system (with on-line attenuation process shown)
                                                                                                                                       Discharge
                                                                                                                                           to
                                                                                                                                      watercourse
                                                                                                                          Control Chamber
  P/E Equal Sand/Sludge                                                                                                           with
   Separation Chamber              P/E Equal Oil                                                                        Vortex flow control unit
                                Separation Chamber
                                                                          AquaCell Box Unit assembly
                                                                  with geotextile wrap over geomembrane wrap
                                      Customer Services       Technical Enquiries       Technical Fax       Email
     Page 12                          01249 766611            01249 766655              01249 766653        technical.design@wavin.co.uk
The Intesio Oil Separation System  Installation Methods
Introduction                                                              Figure 4 For areas with light traffic and pedestrians
The following installation instructions outline the basic requirements
for the Intesio Oil Separation Chamber when installed in typical
installations as shown in Fig 4 and Fig 6. Full installation details,
together with details to be used when installing the chamber in
areas with high groundwater and/or in areas where the bearing
capacity of the soil is poor (see Fig 7), are available from Wavin
Technical Design Department.
Installation Procedure                                                                                8
1.   Excavate the chamber pit to the required depth, ensuring that                                           5
     the plan area is slightly greater than that of the chamber being
                                                                                                                                       9
     installed.
2.   Depending on site and/or soil conditions, lay a 300mm
     stone-free sand layer placed on the bottom of the pit
                                                                                                                  4
     (see Fig 4 for light traffic/pedestrian areas and/or Fig 6 for
     medium/heavy traffic areas).
3.   Pour approximately 200mm of water into the separator to
     stabilise it.
                                                                                                                                  3
4.   Surround the chamber as appropriate, with either concrete or
                                                                                                  7
     a suitable non-angular material. The type of surround
     depends on the individual site conditions, so guidance should
     be obtained from Wavin Technical Design Department prior to                                             2
     work commencing.
                                                                                                  1
     If using a non-angular material as the backfill, compact the
     sidefill around the chamber with care. Compaction should be
     carried out in 150mm layers up to the level of the inlet/outlet.
     While this work is being done, keep adding water to the
     chamber to keep it steady.
5.   Make the appropriate connection to the inlet and outlet of the
     chamber using the appropriate pipe system and/or adaptors.
6.   Remove the storage cover from the access hole of the chamber.
     Install the rubber sealing ring (provided) onto the bottom edge of
     the chamber shaft. Assemble the maintenance shaft in a vertical
     position onto the mounting collar of the chamber. Fix the
     maintenance shaft in its place with the threaded bars through        Figure 5 Fixing maintenance shaft to oil separator
     the lugs and tighten with nuts. See Fig 5.
7.   Fix the alarm device. Alarms are supplied with the chamber
     as appropriate but not installed. Detailed installation
     instructions are supplied with the alarm/chamber.                                                                     Maintenance shaft
                                                                             Threaded bar
8.   Connect the ventilation pipe to the chamber as appropriate.             Fixed nut and washer
     Continue compacting the granular surround in 150mm layers               Maintenance shaft
                                                                             fixing lug
     up to ground level. Avoid the use of heavy vibration tools when
     compacting the granular surround on top of the chamber.
                                                                             Rubber seal
9.   Cut the chamber shaft down to the correct height.                       Lifting screw ring                            Maintenance shaft
                                                                                                                           mounting collar
10. Install the appropriate cover and frame to the required loading
     for the application.
                                                                                                                           Oil separator
11. Finally, fill the chamber completely with water to ensure                                                              below
     effective operation of the unit.
                                                                                         www.intesio.co.uk
                                                                                                                   Page 13
The Intesio Oil Separation System  Installation Methods
Figure 6 For areas with medium or heavy traffic                    Figure 7 Anchoring the separator in groundwater and/or in
                                                                               areas where the bearing capacity of the soil is poor
                       8                                                                   8
                                 5                                                                    5
                                             11
                                                                                                                                  9
                                                         9
                                        4                                                                    4
     1m minimum                                   1m minimum
                                                    3                                                                       3
                   7                                                                   7
                                 2                                                   10               2
                                                                                                                        1
                       1
                                                                                                      6
Key to Details
1 Bedding (base)
2 200mm of water inside the unit
3 Backfill material
4 Chamber shaft
5 Cover and frame
6 Concrete slab
7 Oil separation chamber
8 Ventilation outlet
9 Alarm cable
10 Anchoring belts
11 Reinforced concrete slab around cover and frame
                                     Customer Services   Technical Enquiries    Technical Fax      Email
    Page 14                          01249 766611        01249 766655           01249 766653       technical.design@wavin.co.uk
www.intesio.co.uk
                    Page 15
                                                 Intelligent stormwater solutions by Wavin
Intesio  working to ensure
optimum stormwater management
The combination of urban development and intensified rainfall from climate
change can create serious problems. Stormwater situations are challenges
that may be unavoidable, but they can be very effectively overcome
when the right expertise is applied.
Intesio is Wavins specialist focus for the most efficient capture,
transportation, control, cleansing and re-use of stormwater at source.
The Intesio Team has the essential experience and design insight
to help engineer the best possible solution, in its widest sense,
every time.
Our well-proven system technology is intelligently applied to
the individual needs of each location and situation. We make
thorough checks to ensure efficient performance and full
adherence to the latest statutory regulations.
By making Intesio part of your project approach, the
outcome is assured: the optimum balance of cost,
function and compliance.
                                                                      Wavin operates a programme of continuous product development, and therefore reserves the right to modify or
                                                                      amend the specification of their products without notice. All information in this publication is given in good faith, and
                                                                      believed to be correct at the time of going to press. However, no responsibility can be accepted for any errors,
                                                                      omissions or incorrect assumptions. Users should satisfy themselves that products are suitable for the purpose and
                                                                      application intended.
Wavin Limited
Parsonage Way
Chippenham
Wiltshire
SN15 5PN
Tel: 01249 766600
www.intesio.co.uk                                                                                                                               WM422  May 2009/rev Dec 2009
                                                                                                                                                                                 CWD 2958