Manual L7
Manual L7
Varispeed L7
INSTRUCTION MANUAL
INVERTERS FOR ELEVATOR DRIVES
MODEL: CIMR-L7B
200V CLASS 3.7 to 55kW (7 to 93kVA)
400V CLASS 3.7 to 55kW (7 to 106kVA)
Upon receipt of the product and prior to initial operation, read these instructions
thoroughly, and retain for future reference.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system,
or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording,
or otherwise, without the prior written permission of Yaskawa. No patent liability is assumed
with respect to the use of the information contained herein. Moreover, because Yaskawa is con-
stantly striving to improve its high-quality products, the information contained in this manual is
subject to change without notice. Every precaution has been taken in the preparation of this
manual. Nevertheless, Yaskawa assumes no responsibility for errors or omissions. Neither is
any liability assumed for damages resulting from the use of the information contained in this
publication.
                                       Preface
              This manual is designed to ensure correct and suitable
              application of Varispeed L7-Series Inverters. Read this
              manual before attempting to install, operate, maintain,
              or inspect an Inverter and keep it in a safe, convenient
              location for future reference. Be sure you understand
              all precautions and safety information before attempt-
              ing application.
                                  General Precautions
 The diagrams in this manual may be indicated without covers or safety shields to show details.
  Be sure to restore covers or shields before operating the Units and run the Units according to the
  instructions described in this manual.
 Any illustrations, photographs, or examples used in this manual are provided as examples only
  and may not apply to all products to which this manual is applicable.
 The products and specifications described in this manual or the content and presentation of the
  manual may be changed without notice to improve the product and/or the manual.
 When ordering a new copy of the manual due to damage or loss, contact your Yaskawa represen-
  tatives or the nearest Yaskawa sales office and provide the manual number shown on the front
  cover.
 If nameplates become warn or damaged, order new ones from your Yaskawa representatives or
  the nearest Yaskawa sales office.
                                                                                                       I
     Safety Information
                    The following conventions are used to indicate precautions in this manual. Failure to heed pre-
                    cautions provided in this manual can result in serious or possibly even fatal injury or damage to
                    the products or to related equipment and systems.
                    Indicates precautions that, if not heeded, could possibly result in loss of life or serious injury.
         WARNING
                    Indicates precautions that, if not heeded, could result in relatively serious or minor injury, damage
         CAUTION    to the product, or faulty operation.
                    Failure to heed a precaution classified as a caution can result in serious consequences depending
                    on the situation.
IMPORTANT
II
Safety Precautions
Motor Selection
                                                                         WARNING
            Use only a Yaskawa permanent magnet motor in combination with this Inverter, specifically
             SSE4-F21. Running any other permanent magnet motor with this Inverter may cause the
             Inverter to operate abnormally. Consult with Yaskawa before attempting to use a motor other than
             the model specified.
                                                                         CAUTION
            Never install an Inverter that is damaged or missing components.
             Doing so can result in injury.
Installation
                                                                         CAUTION
            Always hold the case when carrying the Inverter.
             If the Inverter is held by the front cover, the main body of the Inverter may fall, possibly resulting in injury.
            Attach the Inverter to a metal or other noncombustible material.
             Fire can result if the Inverter is attached to a combustible material.
            Install a cooling fan or other cooling device when installing more than one Inverter in the same
             enclosure so that the temperature of the air entering the Inverters is below 45C.
             Overheating can result in fires or other accidents.
Wiring
                                                                         WARNING
            Always turn OFF the input power supply before wiring terminals.
             Otherwise, an electric shock or fire can occur.
            Wiring must be performed by an authorized person qualified in electrical work.
             Otherwise, an electric shock or fire can occur.
            Be sure to ground the ground terminal. (200 V Class: Ground to 100  or less, 400 V Class:
             Ground to 10  or less)
             Otherwise, an electric shock or fire can occur.
            Always check the operation of any fast stop circuits after they are wired.
             Otherwise, there is the possibility of injury. (Wiring is the responsibility of the user.)
            Never touch the output terminals directly with your hands or allow the output lines to come into con-
             tact with the Inverter case. Never short the output circuits.
             Otherwise, an electric shock or ground short can occur.
            Do not use the Inverter for any load other than a three-phase AC motor.
            A permanent magnet motor is a type of permanent magnet motor with a rotor in which a magnet is
             integrated. Unlike an induction motor, the permanent magnet motor terminal generates high volt-
             age when the motor is running, even when the Inverter power is shut off. Be sure to completely
             stop the motor before wiring, maintenance and inspection.
             Failure to do so may result in electric shock.
                                                                                                                                 III
                                                                          WARNING
               Wire the Inverter so that the Run command switches off when a Stop command (or Fast stop com-
                mand) is input to terminal BB or terminal BB1.
                If the Run command is not removed, then the motor will begin running as soon as the Stop com-
                mand (or Fast stop command) is cleared.
                This can result in personal injury.
                                                                          CAUTION
               Check to be sure that the voltage of the main AC power supply satisfies the rated voltage of the
                Inverter.
                Injury or fire can occur if the voltage is not correct.
               Do not perform voltage withstand tests on the Inverter.
                Otherwise, semiconductor elements and other devices can be damaged.
               Connect braking resistors, Braking Resistor Units, and Braking Units as shown in the I/O wiring
                examples.
                Otherwise, a fire can occur and the Inverter, braking resistors, Braking Resistor Units, and Braking Units can be damaged.
               Tighten all terminal screws to the specified tightening torque.
                Otherwise, a fire may occur.
               Do not connect AC power to output terminals U, V, and W.
                The interior parts of the Inverter will be damaged if voltage is applied to the output terminals.
               Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits.
                The Inverter can be damaged or interior parts burnt if these devices are connected.
               When a magnetic contactor is connected to the output circuits, do not switch it ON and OFF while
                the Inverter is running.
                Surge current will cause the overcurrent protection circuit inside the Inverter to operate.
               This Inverter can drive an induction motor or a permanent magnet motor. Select a suitable control
                method (parameter A1-02) for the motor you drive.
                Failure to do so will cause damage to the motor.
                                                                          WARNING
               Do not change the factory setting (0) in b1-03 (Run Command source selection).
                Doing so can cause the elevator to drop.
               Do not change the factory setting (1) in L8-05 (Input open-phase protection selection).
                You can change it to 0, but only after confirming that there are no factors that cause input open
                phase.
                Doing so may damage the Inverter main circuits.
IV
                                                                     CAUTION
          Disconnect the load (machine, device) from the motor before performing rotational autotuning or
           pole tuning.
           The motor may turn, possibly resulting in injury or damage to equipment. Also, motor parameters cannot be correctly set
           with the motor attached to a load.
          Stay clear of the motor until rotational autotuning or pole tuning has been successfully completed.
           The motor could stop and then start again unexpectedly and this could result in injury.
          Always confirm the following before rotational autotuning or pole tuning:
            The lock key has been removed from the motor shaft.
            There are neither people nor objects around the motor shaft.
            The motor is at a complete stop.
           Failure to do so may result in injury.
          Be careful when handling the shaft and coupling.
           Failure to do so may result in injury.
          Be careful not to injure yourself with the key groove when turning the motor shaft by hand.
           Failure to do so may result in injury.
          When operating a permanent magnet motor for the first time, or after exchanging a permanent
           magnet motor or an Inverter, set a correct motor parameter to the Inverter before the operation,
           and be sure to check the motor speed detection.
           Shortage of torque may be the cause when the motor is pulled in the load direction or when the motor does not run as
           directed, such as reverses, doesn't work, or over-accelerates.
           Refer to Chapter 4 Trial Operation for details.
          Do not change the parameter settings unnecessarily.
           Doing so may impede motor operation.
          When running a permanent magnet motor, be sure to set the following parameters.
            Motor related parameters (E1-, E5-)
            Parameters for PG open-circuit detection function (F1-)
            Parameters for excessive speed deviation detection function (F1-)
            Parameters for over-acceleration detection function (S3-)
           Failure to do so will cause damage to the equipment.
          If running a permanent magnet motor with any option cards other than the PG-F2 card, and not
           using the braking sequence recommended by this Inverter, set the following braking sequences
           externally.
            After inputting the operational order, or closing the pole detection complete signal, release the braking.
           A basket will be pulled by a counter weight. Be careful of this, as it can cause injury.
          If running a permanent magnet motor with any option cards other than the PG-F2 card, note that
           the Inverter has not been adapted for use with batteries. If so, do not select the battery as the
           power source for an operation.
           Shortage of torque may be the cause when the motor is pulled in the load direction or when the motor does not run as
           directed, such as reverses, doesn't work, or over-accelerates.
Trial Operation
                                                                     WARNING
          Check to be sure that the front cover is attached before turning ON the power supply.
           An electric shock may occur.
          Provide a separate fast stop switch; the Digital Operator STOP Key is valid only when its function is
           set.
           Injury may occur.
          Reset alarms only after confirming that the RUN signal is OFF.
           Injury may occur.
                                                                                                                                     V
                                                                        CAUTION
              Do not touch the radiation fins (heatsink), braking resistor, or Braking Resistor Unit. These can
               become very hot.
               Otherwise, a burn injury may occur.
              Be sure that the motor and machine is within the applicable ranges before starting operation.
               Otherwise, an injury may occur.
              Provide a separate holding brake if necessary.
               Always construct the external sequence to confirm that the holding brake is activated in the event
               of an emergency, a power failure, or an abnormality in the Inverter.
               Failure to observe this caution can result in injury.
              If using an Inverter with a elevator, take safety measures on the elevator to prevent the elevator
               from dropping.
               Failure to observe this caution can result in injury.
              Do not check signals while the Inverter is running.
               Otherwise, the equipment may be damaged.
              Be careful when changing Inverter settings. The Inverter is factory set to suitable settings.
               Otherwise, the equipment may be damaged.
                                                                        WARNING
              Do not touch the Inverter terminals. Some of the terminals carry high voltages and are extremely
               dangerous.
               Doing so can result in electric shock.
              Always have the protective cover in place when power is being supplied to the Inverter. When
               attaching the cover, always turn OFF power to the Inverter through the MCCB.
               Doing so can result in electric shock.
              After turning OFF the main circuit power supply, wait for the time indicated on the front cover, and
               make sure the CHARGE indicator light has gone out, and then perform maintenance and inspec-
               tion.
               The capacitor will remain charged and is dangerous.
              Maintenance, inspection, and replacement of parts must be performed only by authorized person-
               nel.
               Remove all metal objects, such as watches and rings, before starting work. Always use grounded
               tools.
               Failure to heed these warning can result in electric shock.
              Be sure to completely stop the permanent magnet motor before maintenance and inspection.
               Failure to do so may result in electric shock.
                                                                        CAUTION
              A CMOS IC is used in the control board. Handle the control board and CMOS IC carefully.
               The CMOS IC can be destroyed by static electricity if touched directly.
              Do not change the wiring, or remove connectors or the Digital Operator, during operation.
               Doing so can result in personal injury.
VI
Other
                                                                   WARNING
          Do not attempt to modify or alter the Inverter.
           Doing so can result in electrical shock or injury.
                                                                   CAUTION
          Do not subject the Inverter to halogen gases, such as fluorine, chlorine, bromine, and iodine, at any
           time even during transportation or installation.
           Otherwise, the Inverter can be damaged or interior parts burnt.
                                                                                                                   VII
       Warning Labels on the Inverter
                      Be sure to read and follow all warning labels on the Inverter before installation.
                                                                 Warnings
                                                                 listed
        Warnings                                                 here
        listed
        here
                                        ! WARNING
                                           Risk of electric shock.
                                       Read manual before installing.
                                       Wait 5 minutes for capacitor discharge
                                       after disconnecting power supply.
                                       After opening the manual switch between
                                       the drive and motor, please wait 5 minutes
                                       before inspecting, performing maintenance
                                       or wiring the drive.
                                        ! AVERTISSEMENT
                                            Risque de dcharge lectrique.
                                        Lire le manuel avant l' installation.
                                        Attendre 5 minutes aprs la coupure de
                                        l' allmentation. Pour permettre la
                                        dcharge des condensateurs.
                                        Aprs avoir dconncte la protection
                                        entra le drive et le moteur, veuillez
                                        patienter 5 minutes avant d' inspecter,
                                        d' effectuer une opration de montage
                                        ou de cblage du variateur.
VIII
Warranty Information
                                                                                                                    IX
    Registered Trademarks
X
                                                   Contents
    Safety Information ..........................................................................................II
    Safety Precautions ........................................................................................III
    Warning Labels on the Inverter ................................................................... VIII
    Warranty Information .................................................................................... IX
    Registered Trademarks ................................................................................. X
                                                                                                                                                 XI
          Wiring Control Circuit Terminals ................................................................ 2-18
                Wire Sizes ................................................................................................................... 2-18
                Control Circuit Terminal Functions .............................................................................. 2-20
                Control Circuit Terminal Connections .......................................................................... 2-23
                Control Circuit Wiring Precautions .............................................................................. 2-24
XII
5   Parameters ............................................................................. 5-1
    Parameter Descriptions ...............................................................................5-2
       Description of Parameter Tables .................................................................................... 5-2
    Digital Operation Display Functions and Levels ..........................................5-3
       Parameters Available in Quick Programming Mode ......................................................5-4
    Parameter Tables ......................................................................................5-10
         A: Setup Settings ......................................................................................................... 5-10
         Application Parameters: b ............................................................................................5-12
         Tuning Parameters: C .................................................................................................. 5-15
         Reference Parameters: d ............................................................................................. 5-21
         Motor Parameters: E ....................................................................................................5-23
         Option Parameters: F .................................................................................................. 5-26
         Terminal Function Parameters: H ................................................................................5-31
         Protection Function Parameters: L ..............................................................................5-38
         N: Special Adjustments ................................................................................................ 5-45
         Digital Operator/LED Monitor Parameters: o ............................................................... 5-47
         Elevator Function Parameters: S .................................................................................5-51
         U: Monitor Parameters .................................................................................................5-58
         Factory Settings that Change with the Control Method (A1-02) .................................. 5-66
         Parameters that change with V/f patterns .................................................................... 5-68
         Factory Settings that Change with the Inverter Capacity (o2-04) ................................ 5-73
                                                                                                                                                  XIII
      Speed Detection and Speed Limitation ..................................................... 6-32
         Speed Agreement Function ......................................................................................... 6-32
         Limiting the Elevator Speed ......................................................................................... 6-34
      Improving the Operation Performance ...................................................... 6-35
            Droop Control Function ............................................................................................... 6-35
            Reducing the Motor Speed Fluctuation (Slip Compensation Function) ....................... 6-36
            Torque Compensation Function Adjustments .............................................................. 6-39
            Automatic Speed Regulator (ASR) (Closed-loop Vector only) .................................... 6-41
            A/D Conversion Delay Time Tuning ............................................................................ 6-43
            Torque Compensation Reduction at Stop .................................................................... 6-44
            Stabilizing Speed (Automatic Frequency Regulator) (Open-loop Vector) .................... 6-45
            Inertia Compensation (Closed-loop Vector only) ......................................................... 6-47
            Improving the Leveling Accuracy by Slip Compensation ............................................ 6-48
            Field Forcing ................................................................................................................ 6-49
            Adjusting the DC Injection Current .............................................................................. 6-50
            Motor Rotation Direction Change ................................................................................ 6-51
XIV
    Digital Operator/LED Monitor Functions ....................................................6-85
         Setting Digital Operator/LED Monitor Functions ..........................................................6-85
         Copying Parameters (JVOP-160 only) ........................................................................6-89
         Prohibiting Overwriting of Parameters ......................................................................... 6-93
         Setting a Password ...................................................................................................... 6-94
         Displaying User-set Parameters Only .......................................................................... 6-95
         Machine Data Copy Function ......................................................................................6-95
    Troubleshooting .........................................................................................7-17
         If A Parameter Cannot Be Set ..................................................................................... 7-17
         If the Motor Does Not Operate Properly ...................................................................... 7-18
         If the Direction of the Motor Rotation is Reversed .......................................................7-18
         If the Motor Stalls or Acceleration is Slow .................................................................... 7-18
         If Motor Deceleration is Slow ....................................................................................... 7-19
         Motor torque is insufficient. .......................................................................................... 7-19
         If the Motor Overheats .................................................................................................7-19
         If Peripheral Devices are Influenced by the Starting or Running Inverter .................... 7-20
         If the Earth Leakage Breaker Operates When the Inverter is Running ....................... 7-20
         If There is Mechanical Oscillation ................................................................................7-20
                                                                                                                                               XV
      9    Specifications .........................................................................9-1
           Inverter Specifications ................................................................................. 9-2
              Specifications by Model ................................................................................................. 9-2
              Common Specifications ................................................................................................. 9-4
      10   Appendix ...............................................................................10-1
           Inverter Application Precautions ............................................................... 10-2
                Selection ...................................................................................................................... 10-2
                Installation ................................................................................................................... 10-2
                Settings ....................................................................................................................... 10-2
                Handling ...................................................................................................................... 10-3
Revision History
XVI
                                                                  1
Handling Inverters
    This chapter describes the checks required upon receiving or installing an Inverter.
1
                     Maximum                                       (Always specify through the protective structure when ordering.)
        Voltage       Motor                                                                Enclosed Wall-          Enclosed Wall-
                                    Output                           Open Chassis
         Class       Capacity                      Basic Model                                 mounted                mounted
                                   Capacity                            (IEC IP00)
                       kW                            Number                                   (NEMA 1)               (IEC IP20)
                                     kVA                               CIMR-L7B
                                                                                             CIMR-L7B                CIMR-L7B
                        3.7            7          CIMR-L7B23P7                                 23P71                  23P77
                        5.5            10         CIMR-L7B25P5                                 25P51                25P57
                                                                   Remove the top and
                        7.5            14         CIMR-L7B27P5    bottom covers from the       27P51                27P57
                        11             20         CIMR-L7B2011    Enclosed Wall-mounted        20111                20117
                                                                          model.
                        15             27         CIMR-L7B2015                                 20151                20157
       200 V class     18.5            33         CIMR-L7B2018                                 20181                20187
                        22             40         CIMR-L7B2022           20220                20221                20227
                        30             54         CIMR-L7B2030           20300                20301                20307
                        37             67         CIMR-L7B2037           20370                20371                20377
                        45             76         CIMR-L7B2045           20450                20451                20457
                        55             93         CIMR-L7B2055           20550                20551                20557
                        3.7            7          CIMR-L7B43P7                                 43P71                43P77
                        4.0            9          CIMR-L7B44P0                                 44P01                43P77
                        5.5            12         CIMR-L7B45P5    Remove the top and bot-      45P51                45P57
                                                                   tom covers from the
                        7.5            15         CIMR-L7B47P5                                 47P51                47P57
                                                                   Enclosed Wall-mount
                        11             22         CIMR-L7B4011            model.               40111                40117
                        15             28         CIMR-L7B4015                                 40151                40157
       400 V class
                       18.5            34         CIMR-L7B4018                                 40181                40187
                        22             40         CIMR-L7B4022           40220                40221                40227
                        30             54         CIMR-L7B4030           40300                40301                40307
                        37             67         CIMR-L7B4037           40370                40371                40377
                        45             80         CIMR-L7B4045           40450                40451                40457
                        55            106         CIMR-L7B4055           40550                40551                40557
             * 200 V/400 V class 30KW-55KW model is developing.
1-2
                                                                                   Permanent magnet motor Application Example
                                                                                                                                1-3
      Confirmations upon Delivery
       Checks
          Check the following items as soon as the Inverter is delivered.
1                              Item
          Has the correct model of Inverter been
                                                                                          Method
                                                      Check the model number on the nameplate on the side of the Inverter.
          delivered?
                                                      Inspect the entire exterior of the Inverter to see if there are any scratches or
          Is the Inverter damaged in any way?
                                                      other damage resulting from shipping.
          Are any screws or other components
                                                      Use a screwdriver or other tools to check for tightness.
          loose?
          If you find any irregularities in the above items, contact the agency from which you purchased the Inverter.
       Nameplate Information
          There is a nameplate attached to the side of each Inverter. The nameplate shows the model number, specifica-
          tions, lot number, serial number, and other information about the Inverter.
         Example Nameplate
          The following nameplate is an example for a standard domestic European Inverter: 3-phase, 400 VAC,
          3.7 kW, IEC IP20 standards
1-4
                                                                                                Confirmations upon Delivery
                                           CIMR  L7 B 2 3P7
                 Inverter
                    Varispeed L7                                                                                               1
                    No.        Specification                          No.   Max. Motor Capacity
                    B     IM Motor (PG optional)                     3P7          3.7 kW
                                                                     5P5         5.5 kW
                                                                      to            to
                    No.          Voltage Class                       55          55 kW
                     2      AC Input, 3-phase, 200 V              P Indicates the decimal point.
                    4       AC Input, 3-phase, 400 V
Inverter Specifications
  The Inverter specifications (SPEC: A) on the nameplate indicate the voltage class, maximum motor capac-
  ity, the protective structure, and the revision of the Inverter in alphanumeric codes.
                                                       2 3P7 1
               No.            Voltage Class
                2         AC Input, 3-phase, 200 V
                4         AC Input, 3-phase, 400 V
                                                                                                                              1-5
       Component Names
                                                                                         Mounting
                         Front cover
                                                                                        Diecast cover
                       Digital Operator
Nameplate
Terminal cover
Charge indicator
Ground terminal
1-6
                                                                                   Confirmations upon Delivery
 Inverters of 22 kW or More
  The external appearance and component names of the Inverter are shown in Fig 1.6. The Inverter with the ter-
  minal cover removed is shown in Fig 1.7.
Terminal cover
            Control
             circuit
          terminals                                                            Charge indicator
               Main
              circuit
           terminals
Ground terminals
                                                                                                                 1-7
      Exterior and Mounting Dimensions
Grommet
1-8
               Max.                                                                                      Dimensions (mm)                                                                                        Caloric Value (W)
              Appli-                Open Chassis (IP00)                                  Enclosed Wall-mounted (NEMA1)                                      Enclosed Wall-mounted (IP20)                                     Total Cool-
      Voltage cable                                                                                                                                                                                      Mount-
                                                                                                                                                                                                                             Heat   ing
       Class Motor                                                     App-                                                            App-                                                         App-  ing Exter- Inter-
                                                                                                                                                                                                                             Gen- Method
              Output W       H     D     W1 H1 H2 D1             t1    rox. W      H     D     W1 H0 H1 H2 H3 D1                 t1    rox. W       H      D   W1 H0 H1 H2 H3 D1                 t1 rox. Holes nal     nal
                                                                                                                                                                                                                             era-
               [kW]                                                    Mass                                                            Mass                                                         Mass   d*
                                                                                                                                                                                                                              tion
                  3.7                                                                                                                                                                                           112     74    186
                         140 280 177 126 266        7     59     5      4    140   280   177 126 280 266      7           59     5      4    140   280     177 126 280 266    7           59      5  4    M5
                  5.5                                                                                               0                                                               0                           164     84    248
                  7.5                                                   6          300                                                  6          300                                                 6         219    113   332
                         200 300 197 186 285              65.5               200         197 186 300 285      8           65.5               200           197 186 300 285    8           65.5
                  11                                                    7          310                              10                  7          310                             10                  7         374    170   544
                  15                                                               350                               0                             350                              0            2.3        M6   429    183   612
        200 V            240 350 207 216 335 7.5          78     2.3    11   240         207 216 350 335                  78     2.3    11   240           207 216 350 335                78           11
                18.5                                                               380                              30                             380                       7.5   30                            501    211   712    Fan
      (3-phase)                                                                                              7.5
                 22      250 400         195 385                        17   254   535         195 400 385          135                20    254   464     258 195 400 385         64 100              19        586    274   860
                                   258                    100                            258                              100
                  30     275 450         220 435                        20   279   615         220 450 435          165                23                                                                        865    352   1217
                  37               298                    100           52               298                              100          57                                                                        1015   411   1426
                         375 600         250 575                             380   809         250 600 575          209
                  45               328             12.5          3.2   57                328                 12.5                3.2   62                                                                        1266   505   1771
                                                          130                                                             130
                  55     450 725 348 325 700                           78    453 1027 350 325 725 700               302                86                                                                        1588   619   2207
                  3.7                                                                                                                                                                                             80    68    148
                  4.0    140 280 177 126 266        7     59     5      4    140   280   177 126 280 266      7           59     5      4    140   280     177 126 280 266    7           59     5     4    M5    91    70    161
                  5.5                                                                                                                                                                                            127    82    209
                  7.5                                                                                               0                                                               0                            193    114   307
                         200 300 197 186 285        8     65.5          6    200   300   197 186 300 285      8           65.5          6    200   300     197 186 300 285    8           65.5         6
                  11                                                                                                                                                                                             252    158   410
        400 V     15                                                                                                                                                                                             326    172   498
      (3-phase)          240 350 207 216 335              78            10   240   350   207 216 350 335                  78           10    240   350     207 216 350 335                78           10                            Fan
                  18.5                                                                                                                                                                                           426    208   634
                  22                                             2.3                                                             2.3                                                             2.3        M6   466    259   725
                         275 450 258 220 435              100           17   279   535   258 220 450 435                  100          20    279 514.5 258 220 450 435                    100          19
                  30                               7.5                                                       7.5    85                                                       7.5   64                            678    317   995
                  37                                                    31         635                                                 35          614                                                           784    360   1144
                                                                                                                                                                                                       34
                  45     325 550 283 260 535              105                329         283 260 550 535                  105                329           283 260 550 535                105                    901    415   1316
                                                                        30         715                              165                34          629.5                           79.5
                  55                                                                                                                                                                                   33        1203   495   1698
1-9
                                                                                                                                                                                                                 1
       Checking and Controlling the Installation Site
Install the Inverter in the installation site described below and maintain optimum conditions.
Installation Site
1 Install the Inverter under the following conditions in a pollution degree 2 environment.
1-10
                                                                                        Installation Orientation and Space
   Install the Inverter vertically so as not to reduce the cooling effect. When installing the Inverter, always pro-
   vide the following installation space to allow normal heat dissipation.
        A
                                                                             B
                                                                                                            Air
                                                                                                                                1
                                                                         A             B
                            200 V Class Inverter, 3.7 to 55 kW
                                                                      50 mm         120 mm
                            400 V Class Inverter, 3.7 to 55 kW
                1. The same space is required horizontally and vertically for both Open Chassis (IP00) and Enclosed Wall-
                   mounted (IP20, NEMA 1) Inverters.
                2. Always remove the protection covers before installing a 200 or 400 V Class Inverter with an output of
                   18.5 kW or less in a panel.
  IMPORTANT
                   Always provide enough space for suspension eye bolts and the main circuit lines when installing a 200 or
                   400 V Class Inverter with an output of 22 kW or more in a panel.
                                                                                                                              1-11
       Removing and Attaching the Terminal Cover
Remove the terminal cover to wire cables to the control circuit and main circuit terminals.
                                                   2
                                                                               1
Fig 1.11 Removing the Terminal Cover (Model CIMR-L7B43P7 Shown Above)
          Inverters of 22 kW or More
           Loosen the screws on the left and right at the top of the terminal cover, pull out the terminal cover in the direc-
           tion of arrow 1 and then lift up on the terminal in the direction of arrow 2.
Fig 1.12 Removing the Terminal Cover (Model CIMR-L7B4022 Shown Above)
1-12
                                           Removing/Attaching the Digital Operator/ LED Monitor and Front Cover
                                                     2
                                                                     1
Fig 1.13 Removing the Digital Operator/LED Monitor (Model CIMR-L7B43P7 Shown Above)
                                                                                                                     1-13
       Removing the Front Cover
         Press the left and right sides of the front cover in the directions of arrows 1 and lift the bottom of the cover in
         the direction of arrow 2 to remove the front cover as shown in the following illustration.
                                                                   1
                                                  2
Fig 1.14 Removing the Front Cover (Model CIMR-L7B43P7 Shown Above)
1-14
                                                Removing/Attaching the Digital Operator/ LED Monitor and Front Cover
                  1. Do not remove or attach the Digital Operator/LED Monitor or mount or remove the front cover using meth-
                     ods other than those described above, otherwise the Inverter may break or malfunction due to imperfect
                     contact.
                  2. Never attach the front cover to the Inverter with the Digital Operator/LED Monitor attached to the front
    IMPORTANT
                     cover. Imperfect contact can result.
                     Always attach the front cover to the Inverter by itself first, and then attach the Digital Operator/LED Moni-
                     tor to the front cover.
                                                                                                                                       1
 Inverters of 22 kW or More
    For Inverters with an output of 22 kW or more, remove the terminal cover and then use the following proce-
    dures to remove the Digital Operator/LED Monitor and front cover.
Fig 1.16 Removing the Front Cover (Model CIMR-L7B4022 Shown Above)
                                                                                                                                     1-15
                                                                                         2
                                                                                Wiring
This chapter describes the terminals, main circuit terminal connections, main circuit terminal wiring specifica-
tions, control circuit terminals, and control circuit wiring specifications.
Examples of connections between the Inverter and typical peripheral devices are shown in Fig 2.1.
Power supply
                                   Molded-case
                                   circuit breaker
                                   or ground fault
                                   interrupter
2                                  Magnetic con-
                                   tactor (MC)
Braking resistor
Inverter
                               Ground
                                Output noise filter
                                                                 Motor
                                                        Ground
2-2
                                                                                                                                                                                          Connection Diagram
Connection Diagram
                                                              Short-circuit Bar
                                                                 *2
                                                                                                                                                                               Motor        *4
                                                                                        1             2               B1        B2
                                       MCCB        MC
                                                                                                                                                                   U
                      R                                                 R/L1                                                         U/T1
  3-phase power
   380 to 480 V                                                                                                                                                    V
                      S                                                 S/L2                                                         V/T2                                     IM/PM
     50/60 Hz
                                                                                                                                                                   W
                      T                                                 T/L3                                                         W/T3
                                                                                                                                                                                                                         2
                                                                                                    Inverter
                                                                                                 CIMR-L7B43P7                                   (Ground to
                Input voltage for control power                         P0                                                                      10  max.)
                200 V Class: 250 to 300VDC                                    *8
                400 V Class: 500 to 600VDC0V                            N0
                                                                                                                        PG-X2
                                                         *5                                                                            TA1
                                                                                                                        (Option)
                          Forward run/stop                              S1                                                             1                         12V
                                                                                                                                       2                         0V
                                                                                                                                       3
                          Reverse run/stop                              S2                                                             4                          A+
                                                                                                                                       5                          A-
                                                                                                                                                                                 PG
                                                                                                                                       6                          B+
                          Nominal speed                                 S3                                                             7                          B-
                                                                                                                                       8                          Z+
                                                                                                                                       9                          Z-
                          Inspection Run                                S4                                                             10
                                                                                                                                                   *1
                                                                 *1          +24V
                                                                                                                                        7
                                                                                                                               SG
                                                                        E(G)       Shield wire
                                                                                   connection terminal
                                       2k   Frequency setting   *1
                                             adjustment
                                                                                                                                       MA
                     Frequ-                                             +V *3 Frequency setting                                                    MA
                     ency                                                          power +15 V 20 mA                                                               Fault contact output
                            3                                                                                                          MB
    External         setter                                                                                                                                        250 VAC, 10 mA min. 1 A max.
                                  2      0+10V                                    Master speed
    frequency        2k                                                A1                                                                                         30 VAC, 10 mA min. 1 A max.
    reference                                                                      reference 0 to 10 V (20k )                         MC
                                                                                                                                                   MC               Min. load
                              1
                                                                        AC *6                                                                                       5 VDC,10 mA
                                                                                                                                       M1    Multi-function contact output 1
                                                                               0V
                                                                                                                                              Factory setting:
                                                                                                                                       M2     Brake release command
                                                                                                 Terminating
                                                                                                 resistance                            M3    Multi-function contact output 2
                                                                        R+                                                                                                              Multi-function contact output
                                                                                                                                              Factory setting:
                                                                                                                                       M4                                               250 VAC, 10 mA min. 1 A max.
                                                                                                                                              Magnetic contactor control
                                      MEMOBUS                           R-                                                                                                              30 VAC, 10 mA min. 1 A max.
                                                                                                                                       M5                                               Min. load
                                      communications
                                                                        S+                                                                                                              5 VDC,10 mA
                                      RS-485/422                                                                                             Multi-function contact output 3
                                                                                                                                              Factory setting:
                                                                        S-                                                             M6     Inverter operation ready
                                                                 *1
                                                                        IG
                              Communication
                                    and
                               Control Cards                                 2CN
                                (For Option)
                                                                                                                                                                                                                        2-3
      * 6. Do not ground nor connect the AC terminal on the control circuit to the unit. Doing so may result in a malfunction or a breakdown of the Inverter.
      * 7. Disable the stall prevention during deceleration (set parameter L3-04 to 0) when using a Braking Resistor Unit or a Braking Unit. If this user parameter
           is not changed to disable stall prevention, the system may not stop during deceleration.
      * 8. During battery operation, input voltage for control power from the PO and NO terminals. The PO and NO terminals are set to the B1 (or       3) and
           terminals when shipping.
      * 9. To enable the Inverter, the BB and BB1 terminals must be closed. If one of the terminals is closed, "BB" will be displayed on the Digital Operator and
           the Inverter will not start.
                                     E(G)              R+ R- SC SC SC BB     +V A1 AC                                  M5 M6 MA MB MC E(G)
             IMPORTANT                            IG     S+ S- S1 S2 S3 S4 S5 S6 S7 BB1                                 M3 M4 M1    M2
2
                                 2. The output current capability of the +V terminal is 20 mA.
                                 3. Main circuit terminals are indicated with double circles and control circuit terminals are indicated with single
                                    circles.
                                 4. The wiring of the multi-function contact inputs S1 to S7, BB, and BB1 are shown for the connection of con-
                                    tacts or NPN transistors (0V common and sinking mode). This is the factory setting.
                                 5. A DC reactor is an option only for Inverters of 18.5 kW or less. Remove the short circuit bar when connecting
                                    a DC reactor.
                                 6. The minimum permissible load of a multi-function contact output and an error contact output is 10 mA.
                                 7. The master frequency reference is set to a voltage input reference as the factory setting.
2-4
                                                                                  Terminal Block Configuration
The terminal arrangements are shown in Fig 2.3 and Fig 2.4.
Ground terminal
Fig 2.3 Terminal Arrangement (200 V/400 V Class Inverter of 3.7 kW)
            Control
             circuit
          terminals                                                        Charge indicator
              Main
             circuit
          terminals
Ground terminals
                                                                                                                 2-5
      Wiring Main Circuit Terminals
2
                    R/L1, S/L2, T/L3,  ,   1,    2, B1, B2,
                    U/T1, V/T2, W/T3, PO, NO                                                   4           4
         L7B23P7                                                   M4       1.2 to 1.5
                                                                                           (12 to 10)    (12)
         L7B2015                                                                               10
                    B1, B2, PO                                     M5          2.5                         -
                                                                                            (8 to 6)
                                                                                              25         25
                                                                   M6       4.0 to 5.0
                                                                                              (4)        (4)
         L7B2022                                                                           10 to 16
                       3, PO                                       M6       4.0 to 5.0                     -
                                                                                           (8 to 4)
                                                                                           25 to 35      25
                                                                   M8      9.0 to 10.0
                                                                                           (4 to 2)      (4)
         L7B2030                                                                           10 to 16
                       3, PO                                       M6       4.0 to 5.0                     -
                                                                                           (8 to 4)
                                                                                           25 to 35       25
                                                                   M8      9.0 to 10.0
                                                                                           (4 to 2)       (4)
                                                                                            6 to 16
                        3, PO                                      M8      8.8 to 10.8                    
                                                                                           (10 to 4)
         L7B2037
                                                                                            35 to 70      35
                                                                   M10     17.6 to 22.5
                                                                                           (2 to 2/0)     (2)
                                                                                            0.5 to 4      1.5
                    r/l1, /l2                                     M4       1.3 to 1.4
                                                                                           (20 to 10)    (16)
2-6
                                                                                                     Wiring Main Circuit Terminals
                                                                                         6 to 16
                3, PO                                          M8      8.8 to 10.8                        
                                                                                        (10 to 4)
L7B2045
                                                                                        50 to 70         50
                                                               M10     17.6 to 22.5
                                                                                       (1 to 2/0)        (1)
                                                                                                                                      2
                                                                                        0.5 to 4          1.5
            r/l1, /l2                                         M4       1.3 to 1.4
                                                                                       (20 to 10)        (16)
                                                                                                                 Power cables,
                                                                                        50 to 95       50  2P e.g., 600 V vinyl
            R/L1, S/L2, T/L3,        ,     1, NO               M12     31.4 to 39.2
                                                                                      (1/0 to 4/0)    (1/0  2P) power cables
                                                                                          90              90
            U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31           M10     17.6 to 22.5
                                                                                         (4/0)           (4/0)
                                                                                         6 to 70
L7B2055         3, PO                                          M8      8.8 to 10.8                        
                                                                                       (10 to 2/0)
                                                                                        35 to 95         50
                                                               M10     17.6 to 22.5
                                                                                       (3 to 4/0)       (1/0)
                                                                                        0.5 to 4          1.5
            r/l1, /l2                                         M4       1.3 to 1.4
                                                                                       (20 to 10)        (16)
   * The wire thickness is given for copper wires at 75C
                                               Table 2.2 400 V Class Wire Sizes
                                                                                                                                     2-7
                                               Table 2.2 400 V Class Wire Sizes (Continued)
      L7B4018                                                                                        10          10
                  B1, B2, PO                                                 M5       2.5
                                                                                                     (8)         (8)
                                                                                                  10 to 25       10
                                                                             M6    4.0 to 5.0
                                                                                                  (8 to 4)       (8)
2     L7B4022
                  R/L1, S/L2, T/L3,  ,    1,    3, U/T1, V/T2,
                  W/T3, R1/L11, S1/L21, T1/L31, NO, PO
                                                                             M6    4.0 to 5.0
                                                                                                      16
                                                                                                   (6 to 4)
                                                                                                                 16
                                                                                                                 (6)
                                                                                                  16 to 35       16
                                                                             M8    9.0 to 10.0
                                                                                                  (6 to 2)       (6)
      L7B4045                                                                                     10 to 16
                      3, PO                                                  M6    4.0 to 5.0                     -
                                                                                                  (8 to 4)
                                                                                                  25 to 35       25
                                                                            M8     9.0 to 10.0
                                                                                                  (4 to 2)       (4)
      L7B4055                                                                                     10 to 16
                      3, PO                                                 M6     4.0 to 5.0                     -
                                                                                                  (8 to 4)
                                                                                                  25 to 35       25
                                                                            M8     9.0 to 10.0
                                                                                                  (4 to 2)       (4)
Table 2.3 Lug Sizes (JIS C2805) (200 V Class and 400 V Class)
M3.5 2 / 3.5
M4 2/4
2 M5 2/5
M6 2/6
M8 2/8
2-8
                                                                                            Wiring Main Circuit Terminals
Table 2.3 Lug Sizes (JIS C2805) (200 V Class and 400 V Class) (Continued)
                                                    M5                                           5.5 / 5
             3.5/5.5
                                                    M6                                           5.5 / 6
M8 5.5 / 8
M5 8/5
8 M6 8/6
                                                                                                                               2
                                                    M8                                            8/8
                                                     M6                                          14 / 6
               14
                                                     M8                                          14 / 8
                                                     M6                                          22 / 6
               22
                                                     M8                                          22 / 8
30/38 M8 38 / 8
                                                     M8                                          60 / 8
             50/60
                                                    M10                                         60 / 10
               80                                                                               80 / 10
                                                    M10
              100                                                                               100 / 10
100 100 / 12
                                                  M12 x 2                                       325 / 12
              325
                                                    M16                                         325 / 16
             Determine the wire size for the main circuit so that line voltage drop is within 2% of the rated voltage. Line
             voltage drop is calculated as follows:
IMPORTANT Line voltage drop (V) = 3 x wire resistance (/km) x wire length (m) x current (A) x 10-3
                                                                                                                              2-9
        Main Circuit Terminal Functions
            Main circuit terminal functions are summarized according to terminal symbols in Table 2.4. Wire the terminals
            correctly for the desired purposes.
                                Table 2.4 Main Circuit Terminal Functions (200 V Class and 400 V Class)
                                                                                                             Model: CIMR-L7
                      Purpose                              Terminal Symbol
                                                                                                    200 V Class             400 V Class
                                                R/L1, S/L2, T/L3                                     23P7 to 2055                     43P7 to 4055
2
         Main circuit power input
                                                R1/L11, S1/L21, T1/L31                               2022 to 2055                      4022 to 4055
         Inverter outputs                       U/T1, V/T2, W/T3                                     23P7 to 2055                      43P7 to 4055
         DC power input                            1,                                                23P7 to 2055                      43P7 to 4055
         Braking Resistor Unit connection       B1, B2                                               23P7 to 2018                      43P7 to 4018
         DC reactor connection                     1,     2                                          23P7 to 2018                      43P7 to 4018
               * When running a permanent magnet motor using an option card other than the PG-F2 card, do not use the P0 and N0 terminals, as they do not correspond
                 to the battery operation.
            Note:   The     1 and    input terminals for the DC power do not conform to UL/cUL standards.
2-10
                                                                                                              Wiring Main Circuit Terminals
                B2                                                                      B2
                B1                                                                      B1
                 +1
                 +2
               R/L1
                                                                          U/T1
                                                                                         +1
                                                                                         +2
                                                                                       R/L1
                                                                                                                                      U/T1
                                                                                                                                                2
                                                                          V/T2         S/L2                                           V/T2
               S/L2
               T/L3                                                       W/T3         T/L3                                           W/T3
- -
N0 P0 N0 P0
+ 1 + 1
              R/L1                                                                    R/L1
                                                                            U/T1                                                       U/T1
              S/L2                                                                    S/L2
              T/L3                                                          V/T2      T/L3                                             V/T2
            R1/L11                                                                  R1/L11
                                                                            W/T3                                                      W/T3
            S1/L21                                                                  S1/L21
            T1/L31                                                                  T1/L31
                -                                                                       -
N0 P0 N0 P0
+ 1
              R/L1
                                                                         U/T1
              S/L2
              T/L3                                                       V/T2
            R1/L11
                                                                         W/T3
            S1/L21
            T1/L31
                -
                r/l1
                200/                     Power              Control
                l200                      Supply             Circuit
N0 P0
                                                                                                                                              2-11
        Standard Connection Diagrams
              Standard Inverter connection diagrams are shown in Fig 2.5. These are the same for both 200 V Class and
              400 V Class Inverters. The connections depend on the Inverter capacity.
CIMR-L7B3P7 to 2018 and 43P7 to 4018 CIMR-L7B2022, 2030, and 4022 to 4055
2                                            Braking Resistor
                                             Unit (optional)
                                                                                                             Braking Unit
                                                                                                             (optional)
       Be sure to remove the short-circuit bar before connecting                     The DC reactor is built in.
       the DC reactor.
CIMR-L7B2037 to 2055
                                                    Braking Resistor
                                                    Unit (optional)
                                                    Braking Unit
                                                    (optional)
                 3-phase
                 200 VAC
Control power is supplied internally from the DC bus at all Inverter models.
2-12
                                                                                          Wiring Main Circuit Terminals
   Installing Fuses
    To protect the Inverter, it is recommended to use semiconductor fuses like they are shown in the table below.
                                    43P7           480            15          34 to 72
                                    44P0           480            20          50 to 570
                                    45P5           480            25         100 to 570
                                    47P5           480            30         100 to 640
                                    4011           480            50         150 to 1300
                                    4015           480            60         400 to 1800
                                    4018           480            70         700 to 4100
                                    4022           480            80         240 to 5800
                                    4030           480           100         500 to 5800
                                    4037           480           125         750 to 5800
                                    4045           480           150        920 to 13000
                                    4055           480           150        1500 to 13000
                                                                                                                          2-13
       Installing a Moulded-case Circuit Breaker
        When connecting the power input terminals (R/L1, S/L2, and T/L3) to the power supply using a moulded-case
        circuit breaker (MCCB) observe that the circuit breaker is suitable for the Inverter.
           Choose an MCCB with a capacity of 1.5 to 2 times of the Inverter's rated current.
           For the MCCB's time characteristics, be sure to consider the Inverter's overload protection (one minute at
            150% of the rated output current).
2-14
                                                                                  Wiring Main Circuit Terminals
Ground Wiring
  Observe the following precautions when wiring the ground line.
    Always use the ground terminal of the 200 V Inverter with a ground resistance of less than 100  and that
     of the 400 V Inverter with a ground resistance of less than 10 .
    Do not share the ground wire with other devices, such as welding machines or power tools.
    Always use a ground wire that complies with technical standards on electrical equipment and minimize the
     length of the ground wire.
     Leakage current flows through the Inverter. Therefore, if the distance between the ground electrode and the
     ground terminal is too long, potential on the ground terminal of the Inverter will become unstable.
    When using more than one Inverter, be careful not to loop the ground wire.
OK NO
                                                                                                                   2-15
       Connecting a Braking Resistor and Braking Unit (CDBR)
         Connect a Braking Resistor and Braking Unit to the Inverter like shown in the Fig 2.7.
         To prevent overheating of the braking unit/braking resistor, design the control circuit to stop the Inverter oper-
         ation when the overload contacts are operated.
        200 V and 400 V Class Inverters with 3.7 to 18.5 kW Output Capacity
                                                         Braking Resistor
2
                                                                                            Thermal over-
                                     Inverter
                                                                                           load relay contact
                      Inverter
                                                                                                      Thermal overload
                                                                                                       relay contact
                                                 Thermal overload
                                                 relay contact
2-16
                                                                                                                    Wiring Main Circuit Terminals
                                                                                                                           Thermal overload
                                                                                                                           relay contact
                                        Thermal overload relay contact          Thermal overload relay contact
                                                                                                                                                           2
                                                                                                      Braking                                 Braking
                                                             Braking                                  Resistor                                Resistor
                                                             Resistor
                             detector
                             Level
Inverter
               Braking Unit #1
                          Thermal overload relay                    Thermal overload relay                       Thermal overload relay
                          contact                                   contact                                      contact
Table 2.7
   L2-11 (Battery voltage)                                      Sets the voltage supplied by the backup battery.
   H1-05 (Terminal S7 function selection)                       Sets the battery run command 85.
                                                                                                     Inverter
                        UPS or backup battery                   Terminal
                                                                                      P0
N0
                                                                                                                                                         2-17
       Wiring Control Circuit Terminals
        Wire Sizes
           For remote operation using analog signals, the control line length between the Analog Operator or operation
           signals and the Inverter should be less than 30 m. Separate the lines from main power lines or other control
           circuits in order to reduce induction from peripheral devices.
           When setting frequency references from an external source (not from Digital Operator), used shielded twisted-
           pair wires and ground the shield for the largest area of contact between shield and ground.
           The terminal numbers and the appropriate wire sizes are shown in Fig 2.8.
2                                   Table 2.8 Terminal Numbers and Wire Sizes (Same for all Models)
                                                                                                       Recom-
                                                          Tightening        Possible Wire
                                           Terminal                                                  mended Wire
                 Terminals                                  Torque             Sizes                                              Wire Type
                                           Screws                                                       Size
                                                            (Nm)             mm2(AWG)
                                                                                                     mm2(AWG)
                                                                                 Single
         AC, SC, A1, +V, S1, S2, S3,                                             wire2:
          S4, S5, S6, S7, MA, MB,
                                           Phoenix                             0.14 to 2.5                   0.75     Shielded, twisted-pair wire1
         MC, M1, M2, M3, M4, M5,                            0.5 to 0.6          Stranded                              Shielded, polyethylene-covered,
                                            type                                                             (18)
          M6, BB, BB1, R+, R-, S+,                                                wire:                                viny1 sheath cable (KPEV-S by
                   S-, IG                                                      0.14 to 1.5                             Hitachi Electrical Wire or equiva-
                                                                               (26 to 14)
                                                                                                                       lent)
                                                                                 0.5 to 2                    1.25
                    E (G)                    M3.5           0.8 to 1.0
                                                                                (20 to 14)                   (12)
                                                                                             14 mm
                                                                                                     L
2-18
                                                                                            Wiring Control Circuit Terminals
Wiring Method
  Use the following procedure to connect wires to the terminal block.
  1. Loosen the terminal screws with a thin-slot screwdriver.
  2. Insert the wires from underneath the terminal block.
  3.Tighten the terminal screws firmly.
                               Thin-slot screwdriver
                                                                                 Blade of screwdriver
                                                             Control circuit
                                                             terminal block                                                      2
  Strip the end for
  7 mm if no sold-
  erless terminal is                                                                             3.5 mm max.
                                        Solderless terminal or wire
  used.
                                        without soldering                      Blade thickness: 0.6 mm max.
                       Wires
                                                                                                                               2-19
        Control Circuit Terminal Functions
           The functions of the control circuit terminals are shown in Table 2.10. Use the appropriate terminals for the
           correct purposes.
                        M1
                                  Brake command
                                                                          Brake command when ON.
                                  (1NO contact)
                        M2
                        MA
                                  Fault output signal (SPDT)              Fault when CLOSED across MA and MC
                        MB
                                  (1 Change over contact)                 Fault when OPEN across MB and MC
                        MC
                        R+        MEMOBUS                                                                                           Differential input
             RS-
             422/       R-        communication input                     When using two RS-485 wires, short-circuit                Photocoupler isolation
             485
            MEM         S+                                                between R+ and S+, R- and S-
                                  MEMOBUS                                                                                           Differential output
            OBUS                  communication output                                                                              Photocoupler isolation
            Com-         S-
            muni-                 Shielded wire for
            cation      IG                                                                                                         
                                  communication
Flywheel diode
2-20
                                                                              Wiring Control Circuit Terminals
                                                                                                                 2-21
        Sinking/Sourcing Mode (NPN/PNP Selection)
         The input terminal logic can be switched over between sinking mode (0-V common, NPN) and sourcing mode
         (+24V common, PNP) by using the jumper CN5. An external power supply is also supported, providing more
         freedom in signal input methods.
                                    Table 2.11 Sinking/Sourcing Mode and Input Signals
Internal Power Supply Sinking Mode (NPN) External Power Supply Sinking Mode (NPN)
S1 S1
2 S2 S2
B1 B2 B3 B1 B2 B3
SC + SC
24 VDC
Internal Power Supply Sourcing Mode (PNP) External Power Supply Sourcing Mode (PNP)
                                                                                 S1
                          S1
                                                                                 S2
                          S2
                                                                                      B1   B2 B3
                               B1    B2 B3
                                                                                                   CN5   IP24V
                                             CN5    IP24V
                                                                                                         (+24V)
                                                    (+24V)                            A1   A2 A3
                               A1    A2 A3
                                                                            -    SC
                          SC
24 VDC
2-22
                                                                                                                                               Wiring Control Circuit Terminals
Forward run/stop S1
Reverse run/stop S2
Nominal speed S3
Inspection Run S4
                                                                                                                                                                                                   2
    Multi-function       Intermediate speed                           S5
   contact inputs
  (Factory setting)
                         Leveling speed                               S6
Not used S7
                            Hardware
                            baseblock 1                               BB
                            Hardware
                            baseblock 2                               BB1
                                                                                             +24V 8mA
                                                                     CN5 (NPN setting)
                                                                      SC
+24V
                                        2k   Frequency setting
                                              adjustment
                                                                              Frequency setting                        MA
                      Frequ-                                          +V                                                          MA
                      ency                                                    power +15 V 20 mA                                                   Fault contact output
                             3                                                                                         MB
     External         setter                                                                                                                      250 VAC, 10 mA min. 1 A max.
                                   2      0+10V                              Master speed
     frequency        2k                                             A1                                                                          30 VAC, 10 mA min. 1 A max.
     reference                                                                reference 0 to 10 V (20k )              MC
                                                                                                                                  MC               Min. load
                               1
                                                                      AC                                                                           5 VDC,10 mA
                                                                                                                       M1   Multi-function contact output 1
                                                                             0V
                                                                                                                             Factory setting:
                                                                                                                       M2    Brake release command
                                                                                       Terminating
                                                                                       resistance                      M3   Multi-function contact output 2
                                                                      R+                                                                                         Multi-function contact output
                                                                                                                             Factory setting:
                                                                                                                       M4                                        250 VAC, 10 mA min. 1 A max.
                                                                                                                             Magnetic contactor control
                                       MEMOBUS                        R-                                                                                         30 VAC, 10 mA min. 1 A max.
                                                                                                                       M5                                        Min. load
                                       communications
                                                                      S+                                                                                         5 VDC,10 mA
                                       RS-485/422                                                                           Multi-function contact output 3
                                                                                                                             Factory setting:
                                                                      S-                                               M6    Inverter operation ready
IG
                               Communication
                                     and
                                Control Cards                              2CN
                                 (For Option)
                                        To terminal B1               P0
                                                                           Contr ol power supply
                                        To terminal                 N0
                                                                                  Shielded              Twisted-pair
                                                                                  wires                 wires
                                                                                                                                                                                                 2-23
        Control Circuit Wiring Precautions
           Observe the following precautions for wiring the control circuits.
             Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1, V/T2,
              W/T3,     ,     1,     2, and    3, PO, NO) and other high-power lines.
             Separate wiring for control circuit terminals MA, MB, MC, M1, M2, M3, M4, M5, and M6 (contact out-
              puts) from wiring to other control circuit terminals.
             If an optional external power supply is used, it should be a UL Listed Class 2 power supply.
2            Use twisted-pair or shielded twisted-pair cables for control circuits to prevent operating faults.
             Ground the cable shields with the maximum contact area of the shield and ground.
             Cable shields have to be grounded on both cable ends.
2-24
                                                                                                Wiring Check
Wiring Check
 Checks
   Check all wiring after wiring has been completed. Do not perform continuity check on control circuits. Per-
   form the following checks on the wiring.
     Is all wiring correct?
     Have no wire clippings, screws, or other foreign material been left?
     Are all screws tight?
     Are any wire ends contacting other terminals?
                                                                                                                 2-25
       Installing and Wiring Option Cards
2                                            PG-B2
                                                       Two phase (phase A and B), +12V inputs, max. response fre-
                                                       quency: 50 kHz
                                                                                                                         A
                PG Speed control boards                Three phase (phase A, B, Z), line driver inputs (RS422),
                                             PG-X2                                                                       A
                                                       max. response frequency: 300 kHz
PG-F2 EnDat/HIPERFACE R A
                    DeviceNet
                                             SI-N1     Option card for DeviceNet fieldbus                                C
                communications board*
                    Profibus-DP
                                             SI-P1     Option card for Profibus-DP fieldbus                              C
                communications board*
                    CANOpen
                                             SI-S1     Option card for CANOpen fieldbus                                  C
                communications board*
* Under development
        Installation
           Before mounting an option card, remove the terminal cover and be sure that the charge indicator inside the
           Inverter does not glow anymore. After that remove the Digital Operator/LED Monitor and front cover and
           mount the option card.
           Refer to documentation provided with the option card for the mounting instructions.
2-26
                                                                                     Installing and Wiring Option Cards
                                                                                          C option card
           Option clip
           (To prevent raising of                                                          D option card
           C and D option card)
Front Cover
Slit
Cut out the slits on the front cover with nippers. Be careful to avoid injury.
                                                                                                                          2-27
        PG Speed Control Board Terminals and Specifications
         PG-B2
           The terminal specifications for the PG-B2 are given in the following table.
2
                            2                                                   0 VDC (GND for power supply)
                            3                                                   H: +8 to 12 V (max. input frequency: 50 kHz)
               TA1                 Pulse input terminals phase A
                            4                                                   GND pulse input phase A
                            5                                                   H: +8 to 12 V (max. input frequency: 50 kHz)
                                   Pulse input terminals phase B
                            6                                                   GND pulse input phase B
                            1      Pulse monitor output terminals
                                                                                Open collector output, 24 VDC, 30 mA max.
                            2      phase A
               TA2
                            3      Pulse monitor output terminals
                                                                                Open collector output, 24 VDC, 30 mA max.
                            4      phase B
         PG-X2
           The terminal specifications for the PG-X2 are given in the following table.
2-28
                                                                                            Installing and Wiring Option Cards
Supported Encoders
  The PG-F2 option card can be used in combination with the following encoder types:
     HIPERFACE: SRS50/60 manufactured by STEGMANN.
     EnDat:      ECN113 (EnDat01), ECN413 (EnDat01), ECN1313 (EnDat01)
                 manufactured by HEIDEN HAIN
  The maximum encoder speed shall not exceed 1200 min-1.
Input/Output Specifications
                                              I
                                    S1               I:   8V (US = 7.5 to 10.5 V), for HIPERFACE
                                                  OFF:    5V (US = 5 V + to -5%), for EnDat, (factory setting)
                                           OFF
                                                                                                                                 2-29
        Wiring
               The following illustrations show wiring examples for the option card.
       Three-phase                                 Inverter
       200 VAC (400 VAC)
2
                                                                                                                        Power supply +12 V
                                                                                                                        Power supply 0 V
                                                                                                                        A-phase pulse output (+)
                                                                                                                        A-phase pulse output (-)
                                                                                                                        B-phase pulse output (+)
                                                                                                                        B-phase pulse output (-)
               PG power
               supply +12 V
                                                                                                                                                   A-phase pulse
                                                                                                                                                   monitor output
                                                                                                Division rate circuit
                                                                              A-phase
               A-phase pulse                                                  pulses
               input
                                                                                                                                                   B-phase pulse
                                                                                                                                                   monitor output
                                                                              B-phase
               B-phase pulse
                                                                              pulses
               input
                               When connecting to a voltage-output-type PG (encoder), select a PG that has an output impedance with a current of at
                                 least 12 mA to the input circuit photocoupler (diode).
                               The pulse monitor dividing ratio can be changed using parameter F1-06 (PG division rate).
                                                                                   A-phase pulses
                                                                                   B-phase pulses
                               The pulse monitor emitter is connected to common inside the PG-B2. The emitter common must be used for external
                                 circuits.
                                                  Fig 2.20 I/O Circuit Configuration of the PG-B2
2-30
                                                                                                   Installing and Wiring Option Cards
Three-phase                           Inverter
200 VAC (400 VAC)
                                   R/L1    U/T1
S/L2 V/T2
T/L3 W/T3
                                                                                                                                              2-31
       PG-F2
         Shielded line should be used to connect terminal TB4 to motor ground terminal. (HIPERFACE)
         Connect a shielded cable to terminal TB4. (EnDat)
         [HIPERFACE]
2                                                                                                        HIPERFACE Encoder
                                                                                                              SRS 50
                 L1(R)             U(T1)
                 L2(S)             V(T2)                                  PM
                 L3(T)             W(T3)
                                                                      PG-F2
                                    4CN                         4CN             TB3
                                                                                  1   COS
                                                                                               Pulse
                                                                                  2   GND
                                                                                               monitor
                                                                                  3   SIN
                                                                                               outputs
                                                                                  4   GND
                                                                                TB2
                                                                                  1    Not
                    Varispeed L7                                                       used
                                                                                  2
                                                                                TB1
                                                                                      Us
                                                                                  1
                                                                                      GND
                                                                                  2
                                                                                      REFSIN
                                                                      +           3
                                                                                      +SIN
                                                                                  4
                                                                                       REFCOS
                                                                                  5
                                                                      +               +COS
                                                                                  6
                                                                                      Data+
                                                                                  7
                                                                                      Data-
                                                                                  8
                                                                                TB4
                                        E                   E                         Screen
                                                                                                            SIN
                                                                                                            COS
                                                                                                            COS Pulse
                                                                                                             SIN Pulse
Note: TB1-2, TB3-2, and TB3-4 are GNDs for the PG-F2 option card.
2-32
                                                                                              Installing and Wiring Option Cards
[EnDat]
                                                                                                          EnDat Encoder
         L1(R)              U(T1)                                                                       ECN 1313 (EnDat01)
         L2(S)              V(T2)                                 PM
         L3(T)              W(T3)
                                                              PG-F2
                             4CN                        4CN            TB3
                                                                         1       A
                                                                                     Pulse
                                                                         2       GND monitor
                                                                                                                                           2
                                                                         3       B   outputs
                                                                         4       GND
                                                                       TB2
                                                               +                  CK
                                                                         1
             Varispeed L7                                                        /CK
                                                                         2
                                                                       TB1
                                                                                 Us
                                                                         1
                                                                                  GND
                                                                         2
                                                                                 B-
                                                              +          3
                                                                                 B+
                                                                         4
                                                                                 A-
                                                              +          5
                                                                                 A+
                                                                         6
                                                                                 Data+
                                                                         7
                                                                                 Data-
                                                                         8
                                                                       TB4
                                 E                  E                             Screen
                                                                                                              B
                                                                                                              A
                                                                                                              A Pulse
B Pulse
Note: TB1-2, TB3-2, and TB3-4 are GNDs for the PG-F2 option card.
                          The length of the PG wiring must not be more than 50 m for the signal lines and 30 m for the monitor output
                           at terminal TB3.
                          The direction of rotation of the PG can be set in user parameter F1-05 (PG Rotation).
        IMPORTANT         The signal voltage levels must be within the following limits:
                           REFSIN (B-), REFCOS (A-) offset:                       2.2 to 2.8 V
                           +SIN (B+), +COS (A+) peak-to-peak voltage (Vp-p) 0.9 to 1.1 V
                                                                                                                                         2-33
        Wiring the Terminal Blocks
           Use not more than 50 meters of wiring for PG (encoder) signal lines and keep them separate from power lines.
           Use shielded, twisted-pair wires for pulse inputs and pulse output monitor wires, and connect the shield to the
           shield connection terminal.
2                                           Terminal
                                                       Table 2.16 Wire Sizes
                        Terminal
                                             Screws     Wire Thickness (mm2)                        Wire Type
2 2 - 3.5
2-34
                                                                                                             Installing and Wiring Option Cards
  PG-B2
    The maximum response frequency is 32,767 Hz.
    Use a PG that outputs a maximum frequency of approximately 20 kHz for the rotational speed of the motor.
PG power supply
Signals
                                                                                                                                                                2-35
       PG-X2
         There are 5 V and 12 V PG power supplies.
         Check the PG power supply specifications before connecting.
         The maximum response frequency is 300 kHz.
         Use the following equation to computer the output frequency of the PG (fPG).
2        A separate power supply is required if the PG power supply capacity is greater than 200 mA. (If momentary
         power loss must be handled, use a backup capacitor or other method.)
                                            PG-X2
                                                                      PG power
                                                                      supply
                                              TA1
                                                               AC
                                                                          0V +12V
                                             IP12 1
                                                                                       0V
                                             IG   2
                                                          Capacitor for             +12 V
                                             IP5     3    momentary
                                                          power loss          +        +
                                             A (+) 4
                                                                                       -    PG
                                             A (-)   5
                                                                                       +
                                             B (+) 6
                                                                                       -
                                             B (-) 7
                                             Z (+) 8
                                             Z (-)   9
                                             IG      10
TA3
2-36
                                                                                      3
    LED Monitor/Digital
   Operator and Modes
The Varispeed L7 is equipped with the LED Monitor JVOP-163 which shows the inverter status. The optional
Digital Operator JVOP-160 can be used to adjust parameters as required.
This chapter describes Digital Operator displays and functions, and provides an overview of operating modes and
switching between modes.
       LED Monitor
         The LED monitor indicates the operation status by combinations of the LED display (Lights up, Blink, and
         Off) at RUN, DS1, and DS2.
          The LED pattern is as follows at each mode.
Alarm Indications
Fault Indications
         Alarm: The figure below shows an example of the LED display when a minor fault occurs.
                Refer to Chapter 7 Troubleshooting and take appropriate countermeasures.
                             RUN      DS1    DS2          POWER
         Fault:   The figure below shows an example of the LED display when an OV or UV fault has
                  occurred
                             RUN      DS1    DS2          POWER
3-2
                                                                                            Digital Operator JVOP-160
                                                              Data Display
                                                             Displays monitor data, parameter numbers and parameter
                                                             settings.                                                     3
                                                             Mode Display (displayed at the upper left of data display)
                                                             DRIVE:       Lights up in Inverter Mode.
                                                             QUICK:       Lights up in Quick Programming Mode.
                                                             ADV:         Lights up in Advanced Programming Mode.
                                                             VERIFY:      Lights up in Verify Mode.
                                                             A. TUNE:     Lights up in Autotuning Mode.
                                                             Keys
                                                             Execute operations such as setting parameters, monitoring,
                                                             jogging, and autotuning.
ESC Key Returns to the status before the DATA/ENTER key was pressed.
                                                                                                                          3-3
                                                         Table 3.1 Key Functions (Continued)
              Key                             Name                                                     Function
                                                                         Selects the rotation direction of the motor when the Inverter is oper-
                           FWD/REV Key
                                                                         ated by the Digital Operator.
                                                                         Selects menu items, sets parameter numbers, and increments set val-
                           Increment Key                                 ues.
                                                                         Used to move to the next item or data.
                                                                         Selects menu items, sets parameter numbers, and decrements set val-
                           Decrement Key                                 ues.
                                                                         Used to move to the previous item or data.
3 DATA/ENTER Key Enters menus and parameters, and set validates parameter changes.
      There are indicators on the upper left of the RUN and STOP keys on the Digital Operator. These indicators
      light or flash to indicate the Inverter operation status.
      The RUN key indicator flashes and the STOP key indicator lights during initial excitation or DC braking. The
      relationship between the indicators on the RUN and STOP keys and the Inverter status is shown in Fig 3.3.
                                   RUN
                                   STOP
                                         Light up     Blinking        Not light up
3-4
                                                                                                                 Digital Operator JVOP-160
The following table shows the relationship between the indicators on the RUN and STOP Keys and the
Inverter conditions.
The indicators are lit, unlit or blinking reflecting the order of priority.
4 Stopped Stopped
                                                                                                                                                        3-5
       Inverter Modes
          The Inverter's parameters and monitoring functions are organized in five groups which make it easy to read
          and adjust parameters.
          The 5 modes and their primary functions are shown in the Table 3.3.
3-6
                                                                                                                      Digital Operator JVOP-160
 Switching Modes
   The mode selection display appears when the MENU key is pressed. Press the MENU key from the mode
   selection display to switch through the modes in sequence.
   Press the DATA/ENTER key to enter a mode and to switch from a monitor display to the setting display.
    Mode Selection
                           MENU                 Monitor Display                                                        Setting Display
    Display
                                      DATA
                                      ENTER
             -DRIVE-
               ** Main Menu **
                                                -DRIVE-
                                                        Monitor
                                                U1 - 01=50.00Hz
                                                                      Rdy
                                                                            RESET
                                                                                    -DRIVE-
                                                                                        Frequency Ref
                                                                                    U1- 01=50.00Hz
                                                                                                      Rdy
                                                                                                                                                   3
                   Operation                       U1-02=50.00Hz                       U1-02=50.00Hz
                                                   U1-03=10.05A                        U1-03=10.05A
                                         ESC
MENU
                                        DATA                                                 DATA
              -QUICK-                           -QUICK-                                                                 -QUICK-
                                        ENTER                                             ENTER
               ** Main Menu **                   Control Method                                                           Control Method
                                                A1-02 = 0      *0*                                                      A1-02 = 0       *0*
                 Quick Setting                     V/f Control                                                              V/f Control
                                                           "0"                                                                     "0"
                                         ESC                                                  ESC
                                                                                                                                   DATA
                           MENU
                                                                                                                                   ENTER
                                        DATA                                                                   DATA
              -ADV-                             -ADV-                       RESET
                                                                                     -ADV-                              -ADV-
                                       ENTER                                                                  ENTER
               ** Main Menu **                      Initialization                    Select Language                     Select Language
                                                   A1 - 00=0                        A1-00 = 0      *0*                  A1-00 = 0      *0*
                  Programming                                                            English                             English
                                                 Select Language                                "0"                                 "0"
                                         ESC                                 ESC                               ESC
MENU
                                        DATA
              -VERIFY-                 ENTER    -VERIFY-                                       The constant number will be displayed if a
               ** Main Menu **
                                                   None Modified                               constant has been changed. Press the
                Modified Consts                                                                DATA/ENTER key to enable the change.
                                         ESC
MENU
                                        DATA                                                 DATA
              -A.TUNE-                          -A.TUNE-                                  ENTER                         -A.TUNE-
                                       ENTER
               ** Main Menu **                    Tuning Mode Sel                                                         Tuning Mode Sel
                                                   T1- 01 = 0 *0*                                                          T1- 01= 0 *0*
                  Auto-Tuning                       Standard Tuning                                                         Standard Tuning
                                                         "0"                                                                     "0"
                                         ESC                                                  ESC
                       To run the Inverter after viewing/changing parameters press the MENU key and the DATA/ENTER key
                       in sequence to enter the Drive mode. A Run Command is not accepted as long as the inverter is in any
      INFO             other mode.
                       To enable Run Commands from the terminals during programming set parameter b1-08 to 1.
                                                                                                                                                  3-7
       Drive Mode
         In the Drive mode the Inverter can be operated. All monitor parameters (U1-), fault informations and the
         fault history can be displayed in this mode
         When b1-01 (Reference selection) is set to 0, 1 or 3, the selected frequency reference value (d1-) can be
         changed from the frequency setting display using the Increment, Decrement, Shift/RESET and Enter keys.
         After confirming the change by pressing the ENTER key, the display returns to the Monitor display.
       Example Operations
         Example key operations in drive mode are shown in the following figure.
                  Display During Running
                      -DRIVE-            Rdy
                         Frequency Ref
                      U1- 01=50.00Hz
                        U1-02=50.00Hz
3
                        U1-03=10.05A
MENU
                                  MENU
                                                       -DRIVE-             Rdy             -DRIVE-           Rdy
                                                                 Monitor
                                                                                  RESET
                                                                                            No of Travels                   The fault name will be
                      -ADV-                              U1 - 55 = 11                       U1- 55 = 11                     displayed if the DATA/ENTER
                        ** Main Menu **                   U1-01=50.00Hz                      U1-01=50.00Hz
                                                          U1-02=50.00Hz                      U1-02=50.00Hz
                                                                                                                            Key is pressed while a constant
                          Programming                                              ESC
                                                                                                                            is being displayed for which a
                                                                                                1       2                   fault code is being displayed.
                                  MENU
                                                                                                3       4
                      -VERIFY-
                        ** Main Menu **                 -DRIVE-            Rdy             -DRIVE-            Rdy
                                                                                                                           DATA
                      -A.TUNE-                                                                                             DATA
                                                        -DRIVE-             Rdy            -DRIVE-            Rdy                                     Rdy
                        ** Main Menu **                      Fault Trace          RESET         Last Fault              ENTER
                                                                                                                                    U2 - 02= OV
                          Auto-Tuning                     U2 - 02 = OV                     U2 - 02 = OV
                                                          U3-03=50.00Hz                      U3-03=50.00Hz                        DC Bus Overvolt
                                                          U3-04=50.00Hz            ESC
                                                                                             U3-04=50.00Hz
                                                                                                                            ESC
                                                                                                3       4                            DATA
                                                                                                                                     ENTER
                                                                                                5       6
                                                                                                                           DATA
                                                       -DRIVE-              Rdy           -DRIVE-            Rdy        ENTER                         Rdy
                                                            Fault History         RESET         Last Fault                          U3 - 01= OC
                                                          U3 - 01= OC                       U3 - 01 = OC
                                                             U3-02= OV                          U3-02=OV                            Over Current
                                                             U3-03= OH                          U3-03=OH
                                                                                   ESC                                      ESC
                                                                                                                           DATA
                                                       -DRIVE-              Rdy                              Rdy        ENTER                         Rdy
                                                                                  RESET   -DRIVE-
                                                          Fault Message 2                    Fault Message 2                        U3 - 02= OV
                                                         U3 - 02 = OV                      U3 - 02 = OV                           DC Bus Overvolt
                                                             U3-03= OH                         U3-03= OH
                                                             U3-04= UV             ESC         U3-04= UV                    ESC
                                                                                                    5   6
                                                             A         B
         Note:   When changing the display with the Increment/Decrement keys, after the last monitor parameter the display jumps back to the first monitor parameter
                 and vice versa (e.g. U1-55 is followed by U1-01).
                 The display for the first monitor parameter (frequency reference) will be displayed when power is turned ON. The monitor item displayed at startup
                 can be set in o1-02 (Monitor Selection after Power Up).
3-8
                                                                                      Digital Operator JVOP-160
 Example Operations
   Example key operations in quick programming mode are shown in the following figure.
        Mode Selection Display                   Monitor Display                          Setting Display
         -DRIVE-
                    MENU
                                                                                                                     3
          ** Main Menu **
              Operation
                                                      A            B
                    MENU
                                     DATA                                  DATA
         -QUICK-                     ENTER        -QUICK-                 ENTER          -QUICK-
          ** Main Menu **                          Control Method                          Control Method
                                                  A1-02 = 0 *0*                           A1-02 =    0 *0*
            Quick Setting                           V/f Control                             V/f Control
                                                            "0"                                    "0"
                                      ESC                                  ESC
                    MENU                                                   DATA
                                                  -QUICK-                               -QUICK-
                                                     Accel Time 1         ENTER             Accel Time 1
         -ADV-                                    C1-01 = 1.50sec                        C1-01 =001.50sec
          ** Main Menu **                            (0.00 ~ 600.00)                        (0.00 ~ 600.00)
                                                         "1.50"                                 "1.50"
            Programming                                                    ESC
                                                                           DATA
                                                  -QUICK-                                -QUICK-
                    MENU                             Decel Time 1         ENTER             Decel Time 1
                                                  C1-01 = 1.50sec                        C1-01 =001.50sec
                                                     (0.00 ~ 600.00)                        (0.00 ~ 600.00)
        -VERIFY-                                         "1.50"                                 "1.50"
          ** Main Menu **                                                  ESC
           Modified Consts
                                                                           DATA
                                                  -QUICK-                                -QUICK-
                    MENU                          Mtr Rated Power         ENTER           Mtr Rated Power
                                                 E2-11 = 4.00kW                         E2-11 = 004.00kW
                                                     (0.00 ~ 650.00)                        (0.00 ~ 650.00)
        -A.TUNE-                                        "4.00kW"                               "4.00kW"
          ** Main Menu **                                                  ESC
            Auto-Tuning                                                    DATA
                                                  -QUICK-                                -QUICK-
                                                   MOL Fault Select       ENTER           MOL Fault Select
                                                  L1-01=1       *1*                      L1-01 = 1     *1*
                                                    Std Fan Cooled                         Std Fan Cooled
                                                             "1"                                    "1"
                                                                           ESC
A B
                                                                                                                    3-9
        Advanced Programming Mode
          In the advanced programming mode all Inverter parameters can be monitored and set.
          A parameter can be changed from the setting displays using the Increment, Decrement, and Shift/RESET
          keys. The parameter is saved and the display returns to the monitor display when the DATA/ENTER key is
          pressed.
          Refer to Chapter 5 Parameters for details about the parameters.
        Example Operations
          Example key operations in advanced programming mode are shown in the following figure.
               Mode Selection Display                          Monitor Display                                         Setting Display
3                                                     A   B                              1   2                DATA
                                                                                                              ENTER
                                    DATA
                 -ADV-                         -ADV-                             -ADV-                                -ADV-
                                    ENTER                              RESET
                 ** Main Menu **                  Initialization                  Select Language                      Select Language
                                                  A1-00=0                        A1- 00 = 0 *0*                        A1-02 =     0 *0*
                    Programming                                                       English                              English
                                               Select Language                            "0"                                  "0"
                                                                        ESC                           ESC
                                        ESC
                           MENU
                                                                                                      DATA
                                               -ADV-                             -ADV-                ENTER          -ADV-
                                                                       RESET
                -VERIFY-                          Initialization                   Control Method                       Control Method
                 ** Main Menu **
                                                  A1- 02 =0                      A1- 02 = 0 *0*                       A1-02 =     0 *0*
                                                                                     V/f Control                          V/f Control
                  Modified Consts               Control Method                           "0"           ESC
                                                                                                                              "0"
                                                                         ESC
MENU 1 2
                -A.TUNE-                                                                 3   4                DATA
                 ** Main Menu **                                                                              ENTER
                    Auto-Tuning               -ADV-
                                                                       RESET
                                                                                 -ADV-                                -ADV-
                                                 Accel/Decel                       Accel Time 1                         Accel Time 1
                                              C1- 01 =     1.50sec               C1- 01 =    1.5sec                  C1- 01 = 001.5sec
                            MENU                 Accel Time 1                      (0.00 ~ 600.00)                      (0.00 ~ 600.00)
                                                                                      "1.50sec"                            "1.50sec"
                                                                        ESC                            ESC
                -DRIVE-
                  ** Main Menu **                                                                     DATA
                                              -ADV-                              -ADV-                ENTER           -ADV-
                                                                       RESET
                    Operation                    Accel/Decel                       Accel Time 2                         Accel Time 2
                                              C1- 02 =     1.50sec               C1- 02 =    1.5sec                  C1- 02 = 001.5sec
                                                 Accel Time 1                      (0.00 ~ 600.00)                      (0.00 ~ 600.00)
                                                                                      "1.50sec"        ESC                 "1.50sec"
                            MENU                                         ESC
                -QUICK-                                                                  3   4
                  ** Main Menu **                     A   B
Quick Setting
MENU
3-10
                                                                                         Digital Operator JVOP-160
Setting Parameters
  Here the procedure to change C1-01 (Acceleration Time 1) from 1.5 s to 2.5 s is shown.
                 -DRIVE-
                   ** Main Menu **
        2
                      Operation
-QUICK-
        3
                   ** Main Menu **
                     Quick Setting
                                                Press the MENU key 3 times to enter the advanced programming
                                                mode.                                                                  3
                  -ADV-
                    ** Main Menu **
        4
                     Programming
                  -ADV-
                     Initialization
        5                                       Press the DATA/ENTER to access the monitor display.
                     A1-00=1
                   Select Language
                  -ADV-
                    Accel / Decel               Press the Increment or Decrement key to display the parameter
        6          C1-00 = 1.50sec
                     Accel Time 1
                                                C1-01 (Acceleration Time 1).
                  -ADV-
                    Accel Time 1                Press the DATA/ENTER key to access the setting display. The cur-
        7        C1-01 = 0 01.50sec
                   (0.00 ~ 600.0)               rent setting value of C1-01 is displayed.
                      "1.50sec"
                  -ADV-
                    Accel Time 1
        8        C1-01 = 0 01.50sec             Press the Shift/RESET key to move the flashing digit to the right.
                   (0.00 ~ 600.0)
                      "1.50sec"
                  -ADV-
                    Accel Time 1
        9        C1-01 = 0 01.50sec             Press the Increment key to change set value to 2.50 s.
                   (0.00 ~ 600.0)
                      "1.50sec"
                  -ADV-
                    Accel Time 1
       10        C1-01 = 0 02.50sec             Press the DATA/ENTER key to save the set data.
                   (0.00 ~ 600.0)
                      "1.50sec"
                  -ADV-
                                                Entry Accepted is displayed for 1 sec after pressing the
       11         Entry Accepted
                                                DATA/ENTER key.
                  -ADV-
                    Accel Time 1
       12        C1-01 =    2.50sec             The display returns to the monitor display for C1-01.
                   (0.00 ~ 600.0)
                      "1.50sec"
                                                                                                                     3-11
        Verify Mode
           The Verify mode is used to display the parameters that have been changed from their factory settings, either by
           programming or by autotuning. None will be displayed if no settings have been changed.
           The parameter A1-02 is the only parameter from the A1- group, which will be displayed in the modified
           parameter list if it has been changed before. The other parameters will not be displayed, even if they are differ-
           ent from the factory setting.
           In the verify mode, the same procedures as used in the programming mode can be used to change settings. Use
           the Increment, Decrement, and Shift/RESET keys to change a setting. When the DATA/ENTER key is pressed
           the parameter setting are written and the display returns to the Monitor display.
         Example Operations
           In the example below the following settings have been changed from their factory settings:
3            C1-01 (Acceleration Time 1)
             C1-02 (Acceleration Time 2)
             E1-01 (Input Voltage Setting)
             E2-01 (Motor Rated Current).
                   Mode Selection Display                 Monitor Display                           Setting Display
MENU
                    -ADV-
                    ** Main Menu **
                       Programming
                                                                A       B
                                MENU
                                            DATA                                    DATA
                   -VERIFY-                                -VERIFY-                             -VERIFY-
                                            ENTER
                     ** Main Menu **                          Accel Time 1          ENTER
                                                                                                    Accel Time 1
                                                          C1-01 = 002.0sec                      C1-01 = 002.0sec
                      Modified Consts                        (0.00 ~ 600.0)
                                                                "1.50sec"                           (0.00 ~ 600.00)
                                             ESC                                     ESC               "1.50sec"
                                MENU
                                                                                    DATA
                                                           -VERIFY-                              -VERIFY-
                                                              Accel Time 2          ENTER           Accel Time 2
                   -A.TUNE-                               C1-02 = 002.0sec                      C1-02 = 002.0sec
                     ** Main Menu **                         (0.00 ~ 600.0)                        (0.00 ~ 600.0)
                                                                "1.50sec"                             "1.50sec"
                       Auto-Tuning                                                   ESC
                                                                                    DATA
                                                           -VERIFY-                              -VERIFY-
                                MENU                          Input Voltage         ENTER           Input Voltage
                                                           E1-01=390VAC                          E1-01= 390VAC
                                                                 (310~510)                             (310~510)
                   -DRIVE-                                       "380VAC"                              "380VAC"
                     ** Main Menu **                                                 ESC
                         Operation                                                  DATA
                                                           -VERIFY-                              -VERIFY-
                                                            Motor Rated FLA         ENTER         Motor Rated FLA
                                                             E2-01=     7.20A                    E2-01 = 007.20A
                                MENU                           (0.80 ~ 16.00)                       (0.80 ~ 16.00)
                                                                   "7.00A"                               "7.00A"
                                                                                     ESC
                    -QUICK-
                     ** Main Menu **
                       Quick Setting
                                                                A       B
MENU
3-12
                                                                                                       Digital Operator JVOP-160
Autotuning Mode
   Autotuning automatically measures and sets the required motor data in order to achieve the maximum perfor-
   mance. Always perform autotuning before starting operation when using the vector control methods.
   When V/f control has been selected, stationary autotuning for line-to-line resistance can be selected only.
   When the motor cannot be operated (e.g. if the ropes cannot be removed from the traction sheave), and open-
   loop or closed-loop vector control shall be used, perform stationary autotuning.
MENU
      -VERIFY-
        ** Main Menu **
        Modified Consts
MENU
                                 DATA                                 DATA
      -A.TUNE-                            -A.TUNE-                            -A.TUNE-
                                 ENTER
        ** Main Menu **                     Tuning Mode Sel          ENTER      Tuning Mode Sel
                                             T1- 01 =2 *2*                         01 = 2    *2*
          Auto-Tuning                       Term Resistance                     Term Resistance
                                                     "2"                                 "2"
                                                                      ESC
                           ESC
                  MENU                                                DATA
                                          -A.TUNE-                            -A.TUNE-
                                                                     ENTER
                                           Mtr Rated Power                     Mtr Rated Power
       -DRIVE-                             T1- 02 = 4.00kW                    T1-02 = 004.00kW
        ** Main Menu **                       (0.00~650.00)                        (0.0~400.0)
                                                 "4.00kW"                           "4.00kW"
            Operation                                                 ESC
          Quick Setting
                                          -A.TUNE-          Rdy      RUN      -A.TUNE-                     -A.TUNE-
                                              Auto-Tuning                       Tune Proceeding             Tune Proceeding
                                             0.0Hz/0.0A                        40.0Hz/10.5A
                  MENU                      Tuning Ready ?
                                            Press RUN key                     START            GOAL          Tune Successful
       -ADV-
                                                                                                STOP
        ** Main Menu **                                    The display will
          Programming                                      automatically      -A.TUNE-                     -A.TUNE-
                                                                                 Tune Aborted               Tune Successful
                                                           change depending
                  MENU
                                                           on the status of        STOP key
                                                           autotuning.
                                                                                                                                   3-13
                                                                                           4
                                   Trial Operation
This chapter describes the procedures for trial operation of the Inverter and provides an example of trial operation.
START
Installation
Wiring
Turn power on
No-load operation
END
4-2
                                                                                      Performing a Trial Operation
                                                                                                                      4
 Display at Power Up
    After the Inverter is powered up without any problems, the operator display will show the following messages:
Base Block
    When a fault has occurred or an alarm is active a fault or alarm message will appear. In this case, refer to
    Chapter 7 Troubleshooting.
                                                                                                                     4-3
       Basic Settings
            When using a permanent magnet motor, set the control mode to Closed-loop vector control (PM) (A1-02 = 6).
            For more information on how the Digital Operator works, see Chapter 3. For more information on parameters
            and their settings, refer to Chapter 5 and Chapter 6.
                                For permanent magnet motors do not use any other control mode than closed-loop vector control (PM) (A1-02 =
                                6). Using any other control mode can cause damage to the equipment or cause the machinery to behave errati-
                                cally.
                  IMPORTANT
4              A1-02
                              Control method
                              selection
                                                   2: Open-loop vector 1 control
                                                   3: Closed-loop vector control
                                                                                                      0, 2, 3,
                                                                                                         6
                                                                                                                      0
                                                   6: Closed-loop vector control (PM)
                                                   This parameter is not changed by the initial-
                                                   ize operation.
                                                   Sets the frequency reference input method.
                                                   0: Digital Operator
                              Reference
               b1-01                              1: Control circuit terminal (analog input)*1       0 to 3          0
                              source selection
                                                   2: MEMOBUS communications
                                                   3: Option card*2
                                                   Sets the Run Command input method.
                                                   0: Digital Operator
                              Run command
               b1-02                              1: Control circuit terminal (sequence input)       0 to 3          1
                              source selection
                                                   2: MEMOBUS communications
                                                   3: Option card
                              Acceleration time Sets the time to accelerate from zero to max-        0.00 to         3.00
               C1-01
                              1                 imum frequency.                                      600.00            s
                              Deceleration time                                                       0.00 to        3.00
               C1-02                           Sets the time to decelerate to zero.
                              1                                                                       600.00           s
                              Frequency refer-                                                                    d1-01 to
                                                 These parameters must be set individually in                    04: 0.00%
                d1-01to       ence 1-4,                                                               0.00 to
        {                                        order to use the multi-step speed and Jog ref-
                04, 17        Jog frequency ref-                                                      120.00      d1-17:
                                                 erence functions.
                              erence                                                                               8.00%
4-4
                                                                                                                            Performing a Trial Operation
Setting
               Parame-              Parameter                                                                            Setting
Require                                                                        Description                                               Default    Remarks
                ter No.               Name                                                                               Range
  d
                                                          Sets the number of pulses per revolution
                                                                                                                          0 to
                                                          (PPM) of the encoder (PG).                                                      8192
           F1-01              PG parameter                                                                               8192
                                                          Should be set to a value that isnt signifi-                                    (PM)
                                                                                                                          (PM)
                                                          cantly less than the pulse count for motor 1
                                                          0: Phase A leads with Forward Run
                                                             Command. (Phase B leads with Reverse
                                                             Run Command.)                                                                  1
           F1-05              PG rotation                                                                                 0,1
                                                          1: Phase B leads with Forward Run                                               (PM)
                                                             Command. (Phase A leads with Reverse
                                                             Run Command.)
                                                Sets the serial line resolution for absolute
                                                encoders (HIPERFACE or EnDat).
                               Absolute encoder
  {         F1-21                               0: 16384                                                                  0 to 2                2
                               resolution
                                                1: 32768
                                                2: 8192
                               Magnet position
                                                          Sets the magnet position detection method.
                                                          0: Magnet position detection method 1
                                                                                                                                                                   4
                                                                                                                           0, 2,
           N8-35              detection selec-           2: Magnet position detection method 2                                                 2
                                                                                                                           4, 5
                               tion                       4: HIPERFACE method
                                                          5: EnDat method
                               Traction sheave                                                                           100 to            400
           S3-13                                         Sets the diameter of the traction sheave.
                               diameter                                                                                   2000             mm
                                                          Sets the roping ratio for the elevator.
           S3-14              Roping                     1: [1:1]                                                         1, 2                 2
                                                          2: [1:2]
                                                 Sets the maximum car acceleration value. If
                               Over acceleration the acceleration rate is higher than this                               0.0 to             1.5
           S3-16
                               detection level   value, the Inverter trips with an over acceler-                          50.0              *3
                                                 ation fault (DV6).
      * 1. If d1-18 is set to 1 or 2, an analog reference will have priority over a frequency reference from a multi-function contact input.
      * 2. If d1-18 is set to 1 or 2, a frequency reference from a multi-function contact input will be valid even if b1-01 is set to 2 or 3.
      * 3. Set parameter S3-16 to 0.0/ms2 whenever a DV6 fault occurs during a trial operation. When performing a trial operation with the machine connected to
           the motor, set the appropriate value after reviewing Chapter 6 Parameter Settings by Function.
                                                                                                                                                                  4-5
       Setting Motor Related Parameters
            Motor related parameters must to be set to the proper values when using a permanent magnet motor.
            Procedures for setting these values will differ depending on the motor being used, so be sure to follow the
            directions in the table below that correspond to the type of permanent magnet motor set up.
4           * 1. Use the PG option card appropriate for the combination of motor and encoder as listed in Table 4.2.
            * 2. Parameter N8-35 should be set according to the combination of motor and encoder as indicated in Table 4.2.
            * 3. Set the parameters listed in Table 4.2 according to the combination of motor and encoder used.
4-6
                                                                                         Performing a Trial Operation
                First time               NO
          operating the device?
              YES
                                    Was the motor or Inverter
                                           replaced?
                                                                NO
                                                                                                                         4
                                         YES                     Was the PG        NO
                                                                  replaced?
YES
END
Fig 4.2 Settings and Data Verification Before Operating the Inverter
                                                                                                                        4-7
      (2) Setting Motor Parameters
        Using a permanent magnet motor with an incremental encoder
         Refer to the motor parameter setting table provided by Yaskawa and enter the appropriate value into the
         Inverter. Verify the data entered after setting all motor parameters as indicated in the table.
Contact Yaskawa when using a motor type that is not listed in the motor parameter setting table.
IMPORTANT
                                                                                  min-1
4
                        E1-06       Base frequency
4-8
                                                                                              Performing a Trial Operation
                                 VARISPEED
                                 3-PHASE PERMANENT MAGNET MOTOR
                                 TYPE                     POLES E5-04
                                 PROTECTION           COOLING                    PARAMETER
                                   kW     V     Hz    RATING    A    r/min        r1  E5-05
                                  E5-02 E1-13                 E5-03 E1-04,06     Ld   E5-06
                                                                                 Lq   E5-07
                                                                                 Ke   E5-09
                                 INS. COOLANT TEMP.        C    ALTITUDE m         E5-11
                                 STD                             MASS     kg     '
                                 BRG NO DRIVE
                                        END
                                                           OPP
                                                           END                   Ki
                                 SER NO                          YEAR            Kt
                                 YASKAWA ELECTRIC CORPORATION            JAPAN
                                                                                                                             4-9
       (3) Selecting which way the motor should rotate
                                      The motor should be set so that when it rotates in the forward direction the elevator car goes up.
                                      Torque compensation at start uses a 0 to +10 V analog signal fixed in the forward direction. The elevator
                                       also requires positive torque compensation when ascending. The direction of the motor must be set so that
                IMPORTANT              the elevator goes up when the motor is rotating forwards.
       The factory setting for the PG rotation is Phase B leads with a Forward Run Command (F1-05 = 1).
       The motor is considered to be moving forwards if the shaft rotates counter-clockwise when looking from the
       load side.
       The motor wiring should be connected so that the elevator car goes up when the motor is rotating counter-
       clockwise (i.e., in the forward direction). Wiring should be corrected if this is not the case.
       Note: Follow the procedure below to change the direction of the motor so that it rotates clockwise looking from the load side of the shaft as the elevator car
             goes up.
             Step 1: Change the wiring between the motor and Inverter
                     Reconnect the wires so that the lines that ran to U, V, and W now run to U, W, and V.
             Step 2: Change the following parameters.
                     PG rotation (F1-05)
                      Change the setting value from 1 (Phase B leads with a Forward Run Command) to 0 (Phase A leads with a Forward Run Command).
4
                     PG home position offset (E5-11)
                      Set the value to its additive inverse.
                      For example, when adjustments to the PG home position have already been made, multiply the PG home position value by negative one and
                      set that value.
forward
                                                                                                               load
                                                                                                               side
4-10
                                                                                                        Performing a Trial Operation
        Corrective action for problems that may occur while verifying the direction of motor rotation:
                                                                                                                                              4
             Description of Problem                                                Corrective Action
Motor speed is displayed with the polarity reversed.     Double check the motor wiring, PG cable wiring, and PG rotation (F1-05).
Motor speed is zero or is clearly wrong.                 Refer to Chapter 2 Wiring to verify that the PG has been wired correctly.
                               Verify that the STOP LED on the Digital Operator is flashing, then check the direction of motor rotation.
                               Make sure that nothing gets wrapped up on the motor shaft or coupling.
              IMPORTANT        Take caution of the key slot when rotating the motor shaft by hand to avoid injury.
                                                                                                                                            4-11
       (5) PG Encoder Home Position Pulse Adjustment
        Procedure
        When performing autotuning, select Magnet position autotuning (T1-01 = 4) and press the RUN key.
        The Inverter will automatically begin assessing the amount of offset for the PG home position.
         After tuning is complete the Inverter will automatically save the offset value for the PG home position to
          parameter E5-11.
         If tuning is interrupted or stopped before completion
          The Inverter will abort the autotuning process if a fault occurs during autotuning, and no value will be
          saved to parameter E5-11 (PG home position offset).
          If a fault occurs during autotuning, refer to Chapter 7 Troubleshooting in order to solve the problem. After
          taking the necessary corrective action, perform autotuning again to calculate the proper PG home position
          offset.
        Notes Prior to Performing Autotuning
        Be sure to verify the following points prior to performing autotuning.
         Autotuning automatically checks motor parameter settings.
         This is the major difference when compared with the autotuning process used for a servo system (a servo
4
          system checks the size of the load).
         If the load is coupled with the motor when autotuning is performed (i.e., the rope is connected), motor
          parameters may not be set properly, which can lead to erratic and potentially dangerous behavior of the
          machine. Be absolutely sure to disconnect the load from the motor when performing autotuning.
         Autotuning measures takes various measurements while rotating the motor and saves that data.
         For this reason, the brake must be released prior to autotuning to allow the Inverter to rotate the motor. Be
          sure that any contact switches are closed before attempting autotuning.
         BB or BB1 signals (BB-SC) on the control terminal block that trigger baseblock should be closed so that
          baseblock is released when autotuning the Inverter and motor.
        Related Parameters
                                                                                                      Setting
            No.            Parameter Name                            Description                                Default
                                                                                                      Range
                                                   Sets the autotuning mode.
                                                   0: Rotational autotuning
                                                   1: Stationary autotuning                           0 to 4       4
           T1-01     Autotuning mode selection
                                                   2: Stationary autotuning for line to line resis-   (PM)       (PM)
                                                   tance only
                                                   4: Encoder offset tuning
        For more information on the Digital Operator and display screens when autotuning the Inverter and motor,
        see Chapter 3 LED Monitor/Digital Operator and Modes.
4-12
                                                                                                 Performing a Trial Operation
1 2 3 4 5
Forward, low speed (30 min-1) Forward, low speed (30 min-1)
Fig 4.5 Adjusting the PG Home Location Pulse Offset, Pattern of Operation 4
                                                                                                                                4-13
       Setting Motor Parameters: Procedure 2
        Follow the procedure below to set motor parameters when using a permanent magnet motor with a HIPER-
        FACE or EnDat encoder.
        (1) Setting and verification prior to operation
        Follow the procedure in the flowchart below whenever
          using Varispeed L7 (L7B) for the first time.
          changing motors or Inverters.
          replacing the PG.
          replacing wires running between the motor and Inverter.
                     First time                 NO
               operating the device?
4                   YES
                                             Was the motor or Inverter
                                                    replaced?
                                                                                     NO
                                                   YES                                                           NO
                                                                                    Was the PG
                                                                                     replaced?
YES
          Verify which way the motor rotates                             Verify which way the motor rotates
                 (see pages 4-15)                                                (see pages 4-15)
END
Fig 4.6 Settings and Data Verification Before Operating the Inverter
4-14
                                                                                                                    Performing a Trial Operation
                               The motor should be set so that when it rotates in the forward direction the elevator car goes up.
                               Torque compensation at start uses a 0 to +10 V analog signal fixed in the forward direction. The elevator also requires
                                positive torque compensation when ascending. The direction of the motor must be set so that the elevator goes up
         IMPORTANT              when the motor is rotating forwards.
The factory setting for the PG rotation is Phase B leads with a Forward Run Command (F1-05 = 1).
The motor is considered to be moving forwards if the shaft rotates counter-clockwise when looking from the
load side.
The motor wiring should be connected so that the elevator car goes up when the motor is rotating counter-
clockwise (i.e., in the forward direction). Wiring should be corrected if this is not the case.
Note:Follow the procedure below to change the direction of the motor so that it rotates clockwise looking from the load side of the shaft as the elevator car
     goes up.
     Step 1: Change the wiring between the motor and Inverter
             Reconnect the wires so that the lines that ran to U, V, and W now run to U, W, and V.
     Step 2: Change the following parameters.
             PG rotation (F1-05)
              Change the setting value from 1 (Phase B leads with a Forward Run Command) to 0 (Phase A leads with a Forward Run Command).
                                                                                                                                                                  4
             PG home position pulse offset (E5-11)
              Set the value to its additive inverse.
              For example, when adjustments to the PG home position have already been made, multiply the PG home position value by negative one and
              set that value.
forward
                                                                                                        load
                                                                                                        side
                                                                                                                                                                4-15
                                                  Table 4.6 Verifying Motor Rotation
        Proce-                                                             Digital Operator
                                      Objective                                                               Points to Verify
         dure                                                                   Display
                  Turn the power on and set the Digital Operator
           1
                  screen to display the motor speed (U1-05).
                  To have the forward direction be counter-clock-
                  wise:
                  Rotation moves counter-clockwise when looking          Example:                  Confirm that motor speed is dis-
           2      down the motor shaft from the load side.               Change U1-05 from         played as a positive value, and that it
                  To have the forward direction be clockwise:            0.00% to 3.00%            corresponds to the rotational speed.
                  Rotation moves clockwise when looking down the
                  motor shaft from the load side.
                  To have the forward direction be counter-clock-
                  wise:
                  Rotation moves clockwise when looking down the Example:                          Confirm that motor speed is dis-
           3      motor shaft from the load side.                 Change U1-05 from                played as a negative value, and that it
                  To have the forward direction be clockwise:     0.00% to -3.00%                  corresponds to the rotational speed.
                  Rotation moves counter-clockwise when looking
                  down the motor shaft from the load side.
4              Corrective action for problems that may occur while verifying the direction of motor rotation:
                    Description of Problem                                            Corrective Action
       Motor speed is displayed with the polarity reversed. Double check the motor wiring, PG cable wiring, and PG rotation (F1-05).
       Motor speed is zero or is clearly wrong.                Refer to Chapter 2 Wiring to verify that the PG has been wired correctly.
                                      Verify that the STOP LED on the Digital Operator is flashing, then check the direction of motor rotation.
                                      Make sure that nothing gets wrapped up on the motor shaft or coupling.
                     IMPORTANT        Watch out for the key slot when rotating the motor shaft by hand to avoid injury.
4-16
                                                                                  Performing a Trial Operation
                                                                                                                   4-17
           Related Parameters
       Parameter                                                                                                               Setting      Factory
                                      Name                                            Description
          No                                                                                                                   Range        Setting
                                                                 Sets the autotuning mode.
                                                                 0: Rotational autotuning
                                                                 1: Stationary autotuning                                          0 to 4      4
         T1-01        Autotuning mode selection
                                                                 2: Stationary autotuning for line-to-line                         (PM)      (PM)
                                                                    resistance only
                                                                 4:Encoder offset tuning
                                                                                                                               0.00 to       3.70
         T2-01        Motor output power                         Sets the output power of the motor in kW.                     300.00        kW
                                                                                                                                 *4           *2
                                                                                                                                              96
                                                                                                                                   0 to
         T2-02        Motor base frequency                       Sets the motor base frequency.
                                                                                                                                   3600      min-1
                                                                                                                                              *2
                                                                                                                                   0.0 to    200.0
         T2-03        Motor rated voltage                        Sets the rated voltage of the motor.                              255.0     VAC
                                                                                                                                     *1       *1
                                                                                                                               0.00 to       7.00
         T2-04        Motor rated current                        Sets the rated current of the motor.                           200.0         A
                                                                                                                               4 to 48
                                                                                                                                              *2
                                                                                                                                              32
                                                                                                                                             Pole
                                                                 Automatically sets parameter E5-06 after                                    30.20
                                                                                                                               0.00 to
         T2-06        Motor d-axis inductance                    tuning the d-axis inductance setting from the                                mH
                                                                                                                               300.00
                                                                 value indicated on the motor nameplate.                                      *2
                                                                                                                                             1251
                                                                 Sets the motor voltage parameter before                       50.0 to        mV
         T2-08        Motor voltage parameter ke
                                                                 autotuning.                                                   2000.0        s/rad
                                                                                                                                              *2
                                                                                                                                   0 to      8192
         T2-09        Number of PG pulses                        Sets the number of PG pulses per revolution.
                                                                                                                                   8192      PPR
                                                                 Selects if the voltage parameter is calculated
                                                                 during autotuning or if it has to input manu-
                      Motor voltage parameter
         T2-10                                                   ally.                                                              0,1       1
                      calculation selection
                                                                 0: Manual input in parameter T2-08
                                                                 1: Automatic calculation
          * 1. These are values for a 200 V Class Inverter. Values for a 400 V Class Inverter are double.
          * 2. The factory settings depend on the Inverter capacity. The values for a 200 V Class Inverter for 3.7 kW are given.
          * 3. The setting range is from 10% to 200% of the Inverter rated output current.
               The value for a 200 V Class Inverter for 3.7 kW is given.
          * 4. The setting range is from 10% to 200% of the Inverter rated capacity.
          Refer to Chapter 3 LED Monitor/Digital Operator and Modes for the operations and descriptions during auto-
          tuning.
4-18
                                                                                        Performing a Trial Operation
                                                                                                                         4
   system checks the size of the load).
  If the load is coupled with the motor when autotuning is performed (i.e., the rope is connected), motor
   parameters may not be set properly, which can lead to erratic and potentially dangerous behavior of the
   machine. Be absolutely sure to disconnect the load from the motor when performing autotuning.
  Autotuning measures takes various measurements while rotating the motor and saves that data.
  For this reason, the brake must be released prior to autotuning to allow the Inverter to rotate the motor. Be
   sure that any contact switches are closed before attempting autotuning.
  BB or BB1 signals (BB-SC) on the control terminal block that trigger baseblock should be closed so that
   baseblock is released when autotuning the Inverter and motor.
 Related Parameters
                                                                                                Setting
     No.            Parameter Name                            Description                                  Default
                                                                                                Range
                                            Sets the autotuning mode.
                                            0: Rotational autotuning
                                            1: Stationary autotuning                             0 to 4       4
    T1-01     Autotuning mode selection
                                            2: Stationary autotuning for line to line            (PM)       (PM)
                                               resistance only
                                            4: Encoder offset tuning
 For more information on the Digital Operator and display screens when autotuning the Inverter and motor,
 see Chapter 3 LED Monitor/Digital Operator and Modes.
                                                                                                                       4-19
             Adjusting the PG Home Location Pulse Offset, Pattern of Operation
1 2 3 4 5
Forward, low speed (30 min-1) Forward, low speed (30 min-1)
4 Fig 4.8 Adjusting the PG Home Location Pulse Offset, Pattern of Operation
        Application Settings
            User parameters are set as required in advanced programming mode (i.e., with the ADV indicator lit on the
            Digital Operator). All the parameters that can be set in quick programming mode can also be displayed and set
            in advanced programming mode.
          Setting Examples
            The following are examples of settings for applications.
                 When using an Inverter-mounted braking resistor (ERF), set L8-01 to 1 to enable ERF braking resistor
                  overheating protection.
                 To use a 0 to 10-V analog signal for a 500min-1 motor for variable-speed operation between 0 to 450 min-1
                  (0% to 90% speed deduction), set H3-02 to 90.0%.
                 To control speed between 20% and 80% to ensure smooth gear operation and limit the maximum speed of
                  the machine, set d2-01 to 80.0% and set d2-02 to 20.0%.
4-20
                                                                                                 Performing a Trial Operation
 No-load Operation
    To being no-load operation (without connecting the machine and the motor), press the LOCAL/REMOTE Key
    on the Digital Operator to change to Local mode (the SEQ and REF indicators on the Digital Operator should
    be OFF).
    Always confirm safety around the motor and machine before starting Inverter operation from the Digital
    Operator. Confirm that the motor works normally and that no errors are displayed at the Inverter.
    Jog Frequency Reference (d1-17, default: 8.00 Hz) can be started and stopped by pressing and releasing the
    JOG Key on the Digital Operator. If the external sequence prevent operation from the Digital Operator, con-
    firm that fast stop circuits and machine safety mechanisms are functioning, and then start operation in Remote
    mode (i.e., with a signal from the control signal terminals). The safety precautions must always be taken
    before starting the Inverter with the motor connected to the machine.
                         Both a Run Command (forward or reverse) and a frequency reference (or multi-step speed reference) must be
                         provided to start Inverter operation.
                         Input these commands and reference regardless of the operation method (i.e., LOCAL of REMOTE).
                                                                                                                                       4
          IMPORTANT
 Loaded Operation
    Connect the machine to the motor and then start operation as described for no-load operation (i.e., from the
    Digital Operator or by using control circuit terminal signals).
                                                                                                                                     4-21
        Check and Recording User Parameters
           Use verify mode (i.e., when the VERIFY indicator on the Digital Operator is lit) to check user parameters that
           have been changed for trial operation and record them in a user parameter table.
           Any user parameters that have been change by autotuning will also be displayed in verify mode.
           If required, the copy function in parameters o3-01 and o3-02 displayed in advanced programming mode can
           be used to copy the changed settings from the Inverter to a recording area in the Digital Operator. If changed
           settings are saved in the Digital Operator, they can be easily copied back to the Inverter to speed up system
           recovery if for any reason the Inverter has to be replaced.
           The following functions can also be used to manage user parameters.
             Recording user parameters
             Setting access levels for user parameters
             Setting a password
4-22
                                                                                                   Performance Optimization
Performance Optimization
       The following table gives adjustment advice for performance improvement after the basic setup has been
       done.
                           Too soft or too hard ASR con- Readjust the ASR proportional (P) gain 1 (C5-01) and the ASR inte-
                           troller settings.             gral (I) time 1 (C5-02).
                                                                                                                                   4-23
                                                                                         5
                                                     Parameters
This chapter describes all parameters that can be set in the Inverter.
5-2
                                                                     Digital Operation Display Functions and Levels
The following figure shows the Digital Operator display hierarchy for the Inverter.
                                                                                                                                        5-3
       Parameters Available in Quick Programming Mode
          The minimum parameters required for Inverter operation can be monitored and set in quick programming
          mode. The parameters displayed in quick programming mode are listed in the following table. These, and all
          other parameters, are also displayed in advanced programming mode.
5-4
                                                                          Digital Operation Display Functions and Levels
                                                                                                                   (Continued)
            Name                                                                                Control Methods
                                                                                Change                                  MEMO-
Param-                                                                   Fac-                   Open-            Closed- BUS
                                                              Setting            during                  Closed-
 eter                              Description                           tory                    loop             loop
           Display                                            Range             Opera-    V/f             loop           Regis-
Number                                                                  Setting                 Vector           Vector
                                                                                  tion                   Vector           ter
                                                                                                   1              (PM)
      S-curve char-
      acteristic
      time at accel-
C2-01 eration start                                                                       Q       Q       Q       Q     20BH
         S-Crv Acc @
         Start
      S-curve char-
      acteristic     Set the S-curve time to smooth out
      time at accel- any sudden changes in motor speed.
C2-02 eration end    The S-curve can be used at start and                                 Q       Q       Q       Q     20CH
                                                                                                                                   5
                     is set, the accel/decel times will
      S-Crv Dec @ increase by only half of the S-curve
      End            characteristic times at start and end.
      S-curve char-
      acteristic
      time below
C2-05 leveling                                                                            Q       Q       Q       Q      232H
      speed
         Scurve @
         leveling
      ASR propor-
      tional (P)                                                        40.00
                                                              0.00 to
C5-01 gain 1       Set the proportional gain 1 and the                           Yes      No     No       Q       Q     21BH
                                                              300.00
      ASR P Gain integral time 1 of the speed control                    3.00
                   loop (ASR) for the minimum fre-                      (PM)
      1
                   quency.
      ASR integral
                   The settings become active for accel-
      (I) time 1                                              0.000 0.500 s
C5-02              eration only.                                to               Yes      No     No       Q       Q     21CH
      ASR I Time                                              10.000 0.300 s
      1                                                               (PM)
      ASR propor-
      tional (P)                                                        20.00
                                                              0.00 to
C5-03 gain 2       Set the proportional gain 2 and the                           Yes      No     No       Q       Q     21DH
                   integral time 2 of the speed control       300.00
      ASR P Gain                                                         3.00
                   loop (ASR) for the maximum fre-                      (PM)
      2
                   quency.
      ASR integral
                   The settings become active for accel-      0.000
      (I) time 2   eration only.
C5-04                                                           to   0.500 s     Yes      No     No       Q       Q     21EH
      ASR I Time                                              10.000
      2
      ASR pri-         Sets the filter time parameter for out-
      mary delay       putting torque references from the      0.000 0.004 s
C5-06 time             speed control loop (ASR). It is set in    to               No      No     No       Q       Q      220H
      ASR Gain         1-second units.                         0.500 0.020 s
      SW Freq          Usually setting is not necessary.              (PM)
                                                                                                                                  5-5
                                                                                                                           (Continued)
                   Name                                                                                 Control Methods
                                                                                        Change                                  MEMO-
      Param-                                                                     Fac-                   Open-            Closed- BUS
                                                                      Setting           during                   Closed-
       eter                                Description                           tory                    loop             loop
                  Display                                             Range             Opera-   V/f              loop           Regis-
      Number                                                                    Setting                 Vector           Vector
                                                                                         tion                    Vector           ter
                                                                                                           1              (PM)
            ASR switch- Sets the frequency for switching              0.0 to
                                                                                0.0 Hz
            ing frequency between Proportion Gain 1, 2,3 and          120.0
      C5-07               Integral Time 1, 2, 3. Multi-function       0.0 to             No      No      No       Q       Q      221H
            ASR Gain      input speed control (ASR) propor-                     2.0%
                                                                      100.0
            SW Freq       tion gain switching has priority.                     (PM)
                                                                      (PM)
            ASR propor-
            tional (P)                                                          40.00
                                                                      0.00 to
      C5-09 gain 3       Set the proportional gain 3 and the                             Yes     No      No       Q       Q     22EH
                         integral time 3 of the speed control         300.00
            ASR P Gain                                                           3.00
                         loop (ASR) for the minimum fre-                        (PM)
            3
                         quency.
            ASR integral
                         The settings become active for decel-         0.000 0.500 s
            (I) time 3   eration only.
      C5-10                                                              to              Yes     No      No       Q       Q      231H
            ASR I Time                                                10.000 0.300 s
            3                                                                 (PM)
               Nominal
                                                                                50.00
               speed refer-
                        Sets the frequency reference when                        Hz
               ence
      d1-09             the nominal speed is selected by a                               Yes     Q*16    Q*16    Q*16    Q*16    288H
            Nomin Speed multi-function contact input.*10                        100.00
                                                                                   %
            vn
                                                                                 (PM)
               Inspection
                                                                        0 to    25.00
5
               speed refer-
                              Sets the frequency reference when       120.00     Hz
               ence
      d1-14                   the inspection speed is selected by a    *2 *3             Yes      Q       Q       Q       Q     28FH
               Inspect        multi-function contact input*18           *11     50.00
                                                                                  %
               Speed vi
                                                                                (PM)
            Leveling
                                                                                 4.00
            speed refer-      Sets the frequency reference when
      d1-17 ence                                                                  Hz
                              the leveling speed is selected by a                        Yes      Q       Q       Q       Q      292H
       *12
            Level Speed       multi-function contact input*10                   8.00%
            vl                                                                  (PM)
               Input volt-
               age setting    Sets the Inverter input voltage. This   155 to  200
      E1-01                   setting is used as a reference value     255    VAC        No       Q       Q       Q       Q      300H
               Input          for protection functions.                 *4   *4 *13
               Voltage
5-6
                                                                             Digital Operation Display Functions and Levels
                                                                                                                     (Continued)
            Name                                                                                  Control Methods
                                                                                  Change                                  MEMO-
Param-                                                                     Fac-                   Open-            Closed- BUS
                                                                Setting            during                  Closed-
 eter                                 Description                          tory                    loop             loop
            Display                                             Range             Opera-    V/f             loop           Regis-
Number                                                                    Setting                 Vector           Vector
                                                                                    tion                   Vector           ter
                                                                                                     1              (PM)
         Max. output                                                       60.0
                                                                0.0 to
         frequency                                                          Hz
                                                                120.0
         (FMAX)                                                            *13
E1-04                                                                      96       No      Q       Q       Q       Q      303H
         Max Fre-                                               20 to
                                                                          min-1
                                                                3600
         quency                                                           (PM)
                                                                (PM)
                                                                           *7
      Max. voltage                                              0.0 to 200.0
E1-05 (VMAX)              Output voltage (V)
                                                                255.0 VAC           No      Q       Q       Q       No     304H
         Max Voltage                                              *4   *4 *13
                                                                           60.0
         Base fre-                                              0.0 to
                                                                            Hz
         quency (FA)                                            120.0
                                                                           *13
E1-06                                                                      96       No      Q       Q       Q       Q      305H
         Base Fre-                                              20 to
                                                                          min-1
                                                                3600
         quency                                                           (PM)
                                                                (PM)
                                                                           *7
      Mid. output                          Frequency (Hz)
                                                                           14.0
      frequency    To set V/f characteristics in a straight     0.0 to     VAC
E1-08 voltage (VB) line, set the same values for E1-07          255.0      *13      No      Q       Q      No       No     307H
      Mid voltage and E1-09. In this case, the setting            *4       *14
      A            for E1-08 will be disregarded.                          *15
                                                                                                                                     5
                        Always ensure that the four frequen-
         Min. output
                        cies are set in the following manner:   0.0 to 1.5 Hz
         frequency
                        E1-04 (FMAX)  E1-06 (FA) > E1-         120.0 *5 *13
         (FMIN)
E1-09                   07 (FB)  E1-09 (FMIN)                                      No      Q       Q       A       A      308H
                                                                 0 to
         Min Fre-
                                                                3600      0 min-1
         quency                                                 (PM)       (PM)
                                                                                                                                    5-7
                                                                                                                         (Continued)
                  Name                                                                                Control Methods
                                                                                       Change                                 MEMO-
      Param-                                                                    Fac-                  Open-            Closed- BUS
                                                                     Setting           during                  Closed-
       eter                                 Description                         tory                   loop             loop
                  Display                                            Range             Opera-   V/f             loop           Regis-
      Number                                                                   Setting                Vector           Vector
                                                                                        tion                   Vector           ter
                                                                                                         1              (PM)
            Motor line-
                           Sets the motor phase-to-phase resis-
            to-line resis-                                            0.000    0.771
            tance          tance.
      E2-05                                                             to              No     Q       Q       Q       No     312H
                           This parameter is automatically set       65.000      *7
            Term Resis- during autotuning.
            tance
               Motor rated Sets the rated output power of the
               output power motor.                                              3.70
                                                                     0.00 to
      E2-11                                                                     kW       No     Q       Q       Q       No     318H
               Mtr Rated       This parameter is an input data for   650.00
                                                                                 *7
               Power           autotuning.
            Motor rated                                                         3.70
                               Sets the motor rated power (capac-    0.00 to
      E5-02 power                                                               kW       No     No     No      No       Q     32AH
                               ity).                                 300.00
               Rated power                                                       *7
5
            Motor line-
            to-line resis-                                          0.000
                                                                          3.860
      E5-05 tance          Sets the motor line-to-line resistance.   to                  No     No     No      No       Q     32DH
                                                                             *7
            Term resis-                                            65.000
               tance
               d-axis induc-
               tance                                                           30.20
                                                                     0.00 to
      E5-06                    Sets the motors d-axis inductance.               mH       No     No     No      No       Q     32EH
               d-ax induc-                                           300.00
                                                                                *7
               tance
               q-axis induc-
               tance                                                           36.00
                                                                     0.00 to
      E5-07                    Sets the motors q-axis inductance.               mH       No     No     No      No       Q     32FH
               q-ax induc-                                           600.00
                                                                                *7
               tance
            Motor volt-
            age parame-                                                        1251.0
                                                                     50.0 to     mV
      E5-09 ter                Sets the motor voltage parameter.                         No     No     No      No       Q      331H
                                                                     4000.0     s/rad
               Voltage                                                           *7
               Parameter
            PG home
            position off-      Sets the amount of pulses to align the -180.0
      E5-11 set                home position in units of 0.1            to   0.0 deg     No     No     No      No       Q      333H
               Zpuls-Mag       degrees.                                180.0
               Offset
                                                                      0 to      600
               PG parameter
                                                                     60000       *9
                               Sets the number of PG pulses per
      F1-01                                                            0 to              No     No     No       Q       Q      380H
               PG Pulses/      revolution                                       8192
                                                                      8192
               Rev                                                              (PM)
                                                                      (PM)
                               0: Phase A leads with Forward Run
               PG rotation                                                       0
                                  Command. (Phase B leads with
                                  Reverse Run Command)
      F1-05                                                           0, 1               No     No     No       Q       Q      384H
               PG Rotation     1: Phase B leads with Forward Run                  1
               Sel                Command. (Phase A leads with                  (PM)
                                  Reverse Run Command)
5-8
                                                                                        Digital Operation Display Functions and Levels
                                                                                                                                            (Continued)
               Name                                                                                                Control Methods
                                                                                            Change                                         MEMO-
Param-                                                                               Fac-                          Open-            Closed- BUS
                                                                         Setting             during                         Closed-
 eter                                      Description                               tory                           loop             loop
              Display                                                    Range              Opera-         V/f               loop           Regis-
Number                                                                              Setting                        Vector           Vector
                                                                                              tion                          Vector           ter
                                                                                                                      1              (PM)
          Absolute      Sets the serial line resolution for
          encoder reso- absolute encoders (HIPERFACE or
          lution        EnDat).
F1-21                                                                     0 to 2       2         No        No         No        No         Q       3B0H
                      0: 16384
          PG-F2 Reso-
                      1: 32768
          lution
                      2: 8192
                     Sets whether the motor thermal over-
      Motor pro-     load protection function is enabled or
      tection selec- disabled.                              0 to 3                     1
      tion           0: Disabled
                     1: Protection for general purpose
                        motor (fan cooled)
L1-01                                                                                            No         Q         Q          Q         A        480H
                     2: Protection for frequency converter
                        motor (external cooled)
      MOL Fault                                              0.5
                     3: Protection for special vector                               5 (PM)
      Select                                                (PM)
                        control motor
                     5: Permanent magnet parameter
                         torque motor protection
          Initial mag-      Determines the current for estimat-
          netic polar-      ing the initial magnetic polarity. Set
          ity estimation    as a percentage of the motor rated
          current           torque (E5-03).                                0 to
N8-01                                                                                75%         No        No         No        No         Q        540H
                            Usually setting is not necessary.              100
          MagPos Srch If the motor nameplate includes a
          Curr        value for Si, then that value should
                                                                                                                                                                5
                      be entered to this parameter.
          Magnet posi- Sets the magnet position detection
          tion detec-  method.
          tion method 0: Magnet position detection method
                         1
N8-35                                                                    0,2,4,5       2         No        No         No        No         Q        562H
                            2: Magnet position detection method
          Mag det sel          2
                            4: HIPERFACE method
                            5: EnDat method
*1. The setting ranges for acceleration/deceleration times depend on the setting of C1-10 (Accel/decel time setting unit). If C1-10 is set to 1, the setting
    range is 0.0 to 6000.0 (s).
*2. The unit is set in o1-03 (frequency units of reference setting and monitor, default: 0.01 Hz). If the display unit is changed, the setting range values
    also change.
*3. The maximum setting value depends on the setting of the maximum output frequency (E1-04).
*4. The values will change according to parameter o2-09. The values provided are for a 200 V class Inverter and for when o2-09 is set to 0 (Japanese
    specification). Values for a 400 V class Inverter are double.
*5. The factory settings will change when the control method is changed. Open-loop vector 1 control factory settings are given.
*6. The setting range is from 10% to 200% of the Inverter rated output current. The value for a 200 V class Inverter for 3.7 kW is given.
*7. The factory settings depend on the Inverter capacity. The values for a 200 V class Inverter for 3.7 kW are given.
*8. The setting ranges depend on the Inverter capacity. The values for a 200 V class Inverter of 3.7 kW are given
*9. The values will change according to parameter o2-09. The values provided are for when o2-09 is set to 0 (Japanese specification). The value will be
    1024 when o2-09 is set to 1 or 2.
*10. Enabled by the combined selection of the nominal speed command, the intermediate speed command, and the releveling speed command.
*11. The setting range becomes 0.00 to 100.00 when using closed-loop vector control (PM).
*12. Becomes the jog frequency reference when d1-18 is set to 0.
*13. The factory settings will change according to parameter o2-09. Values shown here are for when o2-09 is set to 0.
*14. These are values for a 200 V class Inverter. Values for a 400 V class Inverter are double.
*15. The factory settings will change when the control method is changed. (The V/f control factory settings are given.)
*16. d1-19 to d1-13 are not displayed if d1-18 is set to 0. These are changed to H1-01 (24), H1-02 (14), H1-03 (3), H1-04 (4), and H1-05 (6).
*17. After autotuning, E1-13 will contain the same value as E1-05.
*18. Enabled if the Inspection Run Command is set for a multi-function contact input.
                                                                                                                                                               5-9
       Parameter Tables
A: Setup Settings
Initialize Mode: A1
5        A1-01
                               A1-04.)
                            1: Used to select parameters (Only
                               parameters set in A2-01 to A2-32            0 to 2        2        Yes     Q       Q       Q       Q     101H
                                                                                                                                                 6-93
                                                                                                                                                 6-94
               Access Level    can be read and set.)
                            2: Advanced
                               (Parameters can be read and set in
                               both, quick programming mode
                               (Q) and advanced programming
                               mode (A).)
               Control      Used to select the control method
               method       for the Inverter
               selection    0: V/f control
                                  2: Open-loop vector 1 control
         A1-02                    3: Closed-loop vector control           0, 2, 3, 6     0        No      Q       Q       Q       Q     102H      -
                  Control
                                  6: Closed-loop vector control
                  Method
                                     (PM)
                                  This parameter is not changed by
                                  the initialize operation.
                  Initialize      Used to initialize the parameters
                                  using the specified method.
                                  0: No initializing
                                  1110: Initializes using the parame-       0 to
         A1-03 Init                                                                      0        No      A       A       A       A     103H      -
                                  ters                                      2220
               Parameters
                                  2220: Initializes using a two-wire
                                  sequence. (Initializes to the factory
                                  setting.)
                  Password        Password input when a password
                                  has been set in A1-05.
                                  This function write-protects some
                                  parameters of the initialize mode.
                                  If the password is changed, A1-01
                                                                            0 to
         A1-04 Enter              to A1-03 and A2-01 to A2-32                            0        No      A       A       A       A     104H     6-94
                                                                            9999
               Password           parameters can no longer be
                                  changed. (Programming mode
                                  parameters can be changed.)
                                  Zero is always displayed when o2-
                                  09 is set to 1 or 2.
5-10
                                                                                                                     Parameter Tables
                                                                                                                              (Continued)
            Name                                                                                    Control Methods
                                                                                     Change                                MEMO-
Param-                                                                                              Open-           Closed- BUS
                                                                 Setting   Factory   during                 Closed-
 eter                               Description                                                      loop            loop            Page
            Display                                              Range     Setting   Opera-   V/f             loop          Regis-
Number                                                                                              Vector          Vector
                                                                                      tion                   Vector          ter
                                                                                                       1             (PM)
         Password     Used to set a four digit number as the
         setting      password.
                      Usually this parameter is not displayed.
A1-05                 When the Password (A1-04) is displayed,               0        No      A       A       A       A     105H     6-94
         Select       hold down the RESET key and press the
         Password     Menu key. The password will be dis-
                      played.
User-set Parameters: A2
   The parameters set by the user are listed in the following table.
            Name                                                                                    Control Methods
                                                                                     Change                                MEMO-
Param-                                                                                              Open-           Closed- BUS
                                                                 Setting   Factory   during                 Closed-
 eter                               Description                                                      loop            loop            Page
            Display                                              Range     Setting   Opera-   V/f             loop          Regis-
Number                                                                                              Vector          Vector
                                                                                      tion                   Vector          ter
                                                                                                       1             (PM)
      User            Used to select the function for each
      specified       of the user specified parameters.
A2-01                                                                                                                       106H
      parameters      Parameters are the only accessible
 to                                                                                 No      A       A       A       A      to      6-95
A2-32 User Param      parameters if Parameter Access                                                                        125H
                      Level is set to parameters (A1-
      1 to 32
                      01=1)
                                                                                                                                            5-11
        Application Parameters: b
5              Method
               Control
               input scan
                               Used to set the responsiveness of the
                               control inputs (forward/reverse and
                               multi-function inputs.)
         b1-06                 0: Fast reading                                   0, 1          1         No          A         A         A            A   185H     -
               Cntl Input
               Scans           1: Normal reading (Can be used for
                                  possible malfunction due to
                                  noise.)
               Operation       Used to set the operation mode by
               selection after switching to the Remote mode using
               switching to the LOCAL/REMOTE Key.
               remote mode 0: Run signals that are input during
         b1-07                        mode switching are disregarded.             0,1          0         No          A         A         A            A   186H     -
                                      (Input Run signals after switching
                  LOC/REM             the mode.)
                  RUN Sel          1: Run signals become effective
                                      immediately after switching to
                                      the Remote mode.
               Run Com-            Used to set an operation prohibition
               mand                in programming modes.
               selection in 0: Operation prohibited.
               programming 1: Operation permitted [(Disabled
               modes           when Digital Operator is the
         b1-08                                                                  0 to 2         0         No          A         A         A            A   187H     -
                               selected Run Command source
                               (b1-02 = 0)].
               RUN CMD at
               PRG          2: Operation  prohibited (the
                               Digital Operator will not
                               enter the programming mode.
            * 1. If d1-18 is set to 1 or 2, an analog reference will have priority over a frequency reference from a multi-function contact input.
            * 2. If d1-18 is set to 1 or 2, a frequency reference from a multi-function contact input will be valid even if b1-01 is set to 2 or 3.
5-12
                                                                                                                              Parameter Tables
DC Injection Braking: b2
             Name                                                                                           Control Methods
                                                                                             Change                                 MEMO-
Param-                                                                                                      Open-            Closed- BUS
                                                                         Setting   Factory   during                  Closed-
 eter                                    Description                                                         loop             loop            Page
            Display                                                      Range     Setting   Opera-   V/f             loop           Regis-
Number                                                                                                      Vector           Vector
                                                                                              tion                   Vector           ter
                                                                                                               1              (PM)
      Magnetic
      flux compen- Sets the magnetic flux compensa-
                                                                         0 to
b2-08 sation       tion as a percentage of the no-load                              0%        No      No      A       No      No    190H       -
                                                                         1000
      volume       current.
         Field Comp
Timer Function: b4
             Name                                                                                           Control Methods
                                                                                             Change                                 MEMO-
Param-                                                                                                      Open-            Closed- BUS
                                                                         Setting   Factory   during                  Closed-
 eter                                    Description                                                         loop             loop            Page
            Display                                                      Range     Setting   Opera-   V/f             loop           Regis-
Number                                                                                                      Vector           Vector
                                                                                              tion                   Vector           ter
                                                                                                               1              (PM)
      Timer func-          Sets the timer function output ON-
      tion ON-             delay time (dead band) for the timer
                                                                         0.0 to
b4-01 delay time           function input, in 1-second units.                       0.0 s     No      A       A       A       A     1A3H      6-71
                                                                         3000.0
         Delay-ON          Enabled when a timer function is
         Timer             set in H1- or H2-.
      Timer func-          Sets the timer function output OFF-
      tion OFF-            delay time (dead band) for the timer
                                                                         0.0 to
b4-02 delay time           function input, in 1-second units.                       0.0 s     No      A       A       A       A     1A4H      6-71
                                                                         3000.0
         Delay-OFF
         Timer
                           Enabled when a timer function is
                           set in H1- or H2-.                                                                                                      5
Dwell Functions: b6
             Name                                                                                           Control Methods
                                                                                             Change                                 MEMO-
Param-                                                                                                      Open-            Closed- BUS
                                                                         Setting   Factory   during                  Closed-
 eter                                    Description                                                         loop             loop            Page
            Display                                                      Range     Setting   Opera-   V/f             loop           Regis-
Number                                                                                                      Vector           Vector
                                                                                              tion                   Vector           ter
                                                                                                               1              (PM)
         Dwell fre-                                                      0.0 to
                                                                                   0.0 Hz
         quency at start                                                 120.0
b6-01                                                                    0.0 to               No      A       A       A       A     1B6H      6-27
         Dwell Ref @                                                               0.0%
                                                                         100.0
         Start                                                                     (PM)
                                                                         (PM)
                           Run Command    ON
                                                            OFF
         Dwell time at
         start             Output frequency
                                                                         0.0 to
b6-02                                                                               0.0 s     No      A       A       A       A     1B7H      6-27
         Dwell Time                                                       10.0
         @ Start
                                              b6-01 b6-03         Time
         Dwell fre-                                     b6-04            0.0 to
                                     b6-02                                         0.0 Hz
         quency at stop                                                  120.0
b6-03                                                                    0.0 to               No      A       A       A       A     1B8H      6-27
         Dwell Ref @                                                               0.0%
                                                                         100.0
         Stop              The dwell function can be used to                       (PM)
                                                                         (PM)
                           hold the output frequency tempo-
         Dwell time at     rarily.
         stop                                                            0.0 to
b6-04                                                                               0.0 s     No      A       A       A       A     1B9H      6-27
         Dwell Time                                                       10.0
         @ Stop
                                                                                                                                                     5-13
       Droop Control: b7
                     Name                                                                                Control Methods
                                                                                         Change                                  MEMO-
       Param-                                                                                            Open-            Closed- BUS
                                                                     Setting   Factory    during                  Closed-
        eter                                 Description                                                  loop             loop            Page
                     Display                                         Range     Setting   Opera-    V/f             loop           Regis-
       Number                                                                                            Vector           Vector
                                                                                           tion                   Vector           ter
                                                                                                            1              (PM)
                Droop          Sets the slip as a percentage of
                control gain   maximum frequency when the
                               maximum output frequency is spec-     0.0 to
       b7-01                                                                   0.0 %      Yes      No      No      No      A     1CAH      6-35
                Droop          ified and the rated torque occurs.    100.0
                Quantity       Droop control is not performed
                               when the setting is 0.0.
             Droop
             control delay Droop control responsiveness
                                                               0.03 to
       b7-02 time          parameter. When hunting or oscilla-                 0.05 s     Yes      No      No      No      A     1CBH      6-35
                                                                 2.00
             Droop Delay   tion occurs, increase the value.
                Time
       Energy Saving: b8
                     Name                                                                                Control Methods
                                                                                         Change                                  MEMO-
       Param-                                                                                            Open-            Closed- BUS
                                                                     Setting   Factory    during                  Closed-
        eter                                 Description                                                  loop             loop            Page
                     Display                                         Range     Setting   Opera-    V/f             loop           Regis-
       Number                                                                                            Vector           Vector
                                                                                           tion                   Vector           ter
                                                                                                            1              (PM)
             Energy-sav-
                               Select whether to enable or disable
             ing mode
                               energy-saving control.
       b8-01 selection                                                0,1        0         No      No      No      No      A     1CCH       -
                               0: Disabled
5               Energy
                Save Sel
                               1: Enabled
                Energy
                savings   This coefficient maintains torque
             control      linearity.                                 0.00 to
       b8-16 parameter Ki                                                       0.10       No      No      No      No      Q     1F8H       -
                          Manually enter the value for Ki as          2.00
             EnergySave indicated by the motor nameplate.
                Ki
                Energy
                savings   This coefficient maintains torque
             control      linearity.                                 0.00 to
       b8-17                                                                    1.00       No      No      No      No      Q     1F9H       -
             parameter Kt Manually enter the value for Kt as          2.00
             EnergySave indicated by the motor nameplate.
                Kt
5-14
                                                                                                                                          Parameter Tables
Tuning Parameters: C
  Acceleration/Deceleration: C1
               Name                                                                                                Control Methods
                                                                                              Change                                       MEMO-
  Param-                                                                                                           Open-            Closed- BUS
                                                                       Setting     Factory    during                        Closed-
   eter                                  Description                                                                loop             loop                   Page
              Display                                                  Range       Setting    Opera-        V/f              loop           Regis-
  Number                                                                                                           Vector           Vector
                                                                                               tion                         Vector           ter
                                                                                                                      1              (PM)
        Acceleration Sets the acceleration time to accel-
                                                                                                                                                            6-23
  C1-01 time 1       erate from 0 Hz to the maximum                                              Yes        Q         Q         Q         Q       200H
                                                                                                                                                            6-25
        Accel Time 1 output frequency.
        Deceleration Sets the deceleration time to decel-
                                                                                                                                                            6-23
  C1-02 time 1       erate from the maximum output fre-                                         Yes         Q         Q         Q         Q       201H
                                                                                                                                                            6-25
        Decel Time 1 quency to 0 Hz.
        Acceleration Sets the acceleration time when the
                                                                                                                                                            6-23
  C1-03 time 2       multi-function input accel/decel                                          Yes         A         A         A         A       202H
                                                                                                                                                            6-25
        Accel Time 2 time 1 is set to ON.
        Deceleration Sets the deceleration time when the
                                                                                                                                                            6-23
  C1-04 time 2       multi-function input accel/decel                                          Yes         A         A         A         A       203H
                                                                                                                                                            6-25
        Decel Time 2 time 1 is set to ON.
        Acceleration Sets the acceleration time when the
                                                                                                                                                            6-23
  C1-05 time 3       multi-function input accel/decel                 0.00 to                   No         A         A         A         A       204H
                                                                                                                                                            6-25
        Accel Time 3 time 2 is set to ON.                             600.00      3.00 s
                                                                          *
        Deceleration Sets the deceleration time when the
  C1-06 time 3       multi-function input accel/decel
        Decel Time 3 time 2 is set to ON.
                                                                                                 No         A         A         A         A       205H      6-23      5
        Acceleration
        time 4       Sets the acceleration time when the
                                                                                                                                                            6-23
  C1-07              frequency reference is below the                                            No         A         A         A         A       206H
        Accel Time 4                                                                                                                                        6-25
                     value set in C1-11.
       * The setting ranges for acceleration/deceleration times depend on the setting of C1-10 (Accel/decel time setting unit). If C1-10 is set to 1, the setting
         range for acceleration/deceleration times becomes 0.0 to 6000.0 seconds.
                                                                                                                                                                    5-15
       S-curve Acceleration/Deceleration: C2
                   Name                                                                                Control Methods
                                                                                       Change                                  MEMO-
       Param-                                                                                          Open-            Closed- BUS
                                                                   Setting   Factory    during                  Closed-
        eter                              Description                                                   loop             loop            Page
                   Display                                         Range     Setting   Opera-    V/f             loop           Regis-
       Number                                                                                          Vector           Vector
                                                                                         tion                   Vector           ter
                                                                                                          1              (PM)
             S-curve char-
             acteristic
             time at accel-
       C2-01 eration start                                                               No      Q       Q       Q       Q     20BH      6-26
                S-Crv Acc @
                Start
             S-curve char-    Set the S-curve time to smooth out
             acteristic       any sudden changes in motor speed.
             time at accel- The S-curve can be used at start and
       C2-02 eration end    stop, as well as during acceleration                         No      Q       Q       Q       Q     20CH      6-26
5-16
                                                                                                                     Parameter Tables
                                                                                                                                              5
         Slip Comp        Reduce the setting when Slip
         Time              Compensation responsiveness is
                           low.
                          When speed is not stable,
                           increase the setting.
      Slip compen-
      sation limit Sets the slip compensation limit as           0 to
C3-03                                                                      200%      No      No      A       No      No    211H      6-37
      Slip Comp    a percentage of motor rated slip.             250
         Limit
         Slip compen-    0: Disabled
         sation selec-   1: Enabled
         tion during     When the slip compensation dur-
         regeneration    ing regeneration function has been
C3-04                    activated and regeneration capacity     0, 1       1        No      No      A       No      No    212H      6-37
                         increases momentarily, it might be
         Slip Comp
                         necessary to use a braking option
         Regen           (braking resistor, Braking Resistor
                         Unit or Braking Unit.)
      Output volt-
      age limit          0: Disabled
                         1: Enabled. (The motor flux will be                1
      operation
C3-05 selection             lowered automatically when the       0, 1                No      No      A       A       No    213H      6-37
                            output voltage become
         Output V           saturated.)                                      0
         limit Sel                                                         (PM)
                                                                                                                                            5-17
       Torque Compensation: C4
                   Name                                                                                              Control Methods
                                                                                                 Change                                      MEMO-
       Param-                                                                                                        Open-            Closed- BUS
                                                                           Setting    Factory     during                      Closed-
        eter                                 Description                                                              loop             loop            Page
                   Display                                                 Range      Setting    Opera-       V/f              loop           Regis-
       Number                                                                                                        Vector           Vector
                                                                                                   tion                       Vector           ter
                                                                                                                        1              (PM)
                Torque com- Sets the torque compensation gain.
                pensation   Usually changing this setting is not
                gain        necessary.
                               Adjust it under the following cir-
                               cumstances:
                                When the cable is long increase
                                 the set value.
                                When the motor capacity is
                                 smaller than the Inverter capac-
                                 ity (Max. applicable motor
                                                                     0.00 to
       C4-01                     capacity), increase the set values.                   1.00        Yes         A         A     No      No    215H      6-39
                                                                      2.50
                Torq Comp       When the motor is oscillating,
                Gain             decrease the set values.
                               Adjust the torque compensation
                               gain so that at minimum speed the
                               output current does not exceed the
                               Inverter rated output current.
                               Do not change the torque compen-
                               sation gain from its default (1.00)
                               when using open-loop vector 1 con-
                               trol.
                Torque com-    The torque compensation delay
5
                pensation      time is set in ms units.
                delay time     Usually changing this setting is not
                parameter      necessary.
                               Adjust it under the following cir-           0 to      200 ms
       C4-02                   cumstances:                                                          No         A         A     No      No    216H      6-39
                                                                           10000        *
                                When the motor is oscillating,
                Torq Comp
                                 increase the set values.
                Time
                                When the responsiveness of the
                                 motor is low, decrease the set
                                 values.
             Starting
             torque com-
             pensation         Sets the torque compensation value 0.0 to
       C4-03 (FWD)                                                                     0.0%         No        No         A     No      No    217H      6-39
                               at start in FWD direction          200.0%
                FTorqCmp
                @ Start
             Starting
             torque com-
             pensation         Sets the torque compensation value -200.0%
       C4-04 (REV)                                                                     0.0%         No        No         A     No      No    218H      6-40
                               at start in REV direction           to 0.0
                RTorqCmp
                @ Start
             Starting
             torque com-
             pensation    Sets starting torque start-up time.
       C4-05 time parame- When 0 to 4 ms is set, it is operated 0 to 200              10 ms         No        No         A     No      No    219H      6-40
             ter          without filter.
             TorqCmpDe-
             layT
             Torque com-
             pensation    Increase settings when acceleration
                          is complete, or if an OV fault or
             primary                                                        0 to        150
       C4-06 delay time 2 error occurs with sudden changes in                                       No        No         A     No      No    21AH       -
                                                                           10000        ms
                          the load.
             Start Torq
                          Usually setting is not necessary.
             Time
* The factory settings will change when the control method is changed. (V/f control factory settings are given.)
5-18
                                                                                                                 Parameter Tables
      ASR propor-
      tional (P)                                                 40.00
C5-09 gain 3       Set the proportional gain 3 and the 1.00 to                    Yes     No      No      Q       Q    22EH     6-42
                                         speed control 300.00
      ASR P Gain integral time 3 of the                           3.00
      3            loop (ASR)  for the minimum   fre-            (PM)
                   quency.
      ASR integral The settings become active for
                                                                0.500 s
      (I) time 3                                       0.000 to
C5-10              acceleration only.                                             Yes     No      No      Q       Q     231H    6-42
      ASR I Time                                        10.000 0.300 s
      3                                                          (PM)
      ASR gain for
                   Sets the ASR P gain which is used
      encoder off-
                   for the encoder offset tuning if HIP- 0.00 to
C5-15 set tuning                                                        5.00      No      No      No     No       A     238H     -
                   ERFACE or EnDat encoders are         300.00
      Pullin ASR
                   used.
      Pgain
                                                                                                                                        5-19
       Carrier Frequency: C6
                    Name                                                                                              Control Methods
                                                                                                  Change                                      MEMO-
       Param-                                                                                                         Open-            Closed- BUS
                                                                            Setting    Factory     during                      Closed-
        eter                                   Description                                                             loop             loop            Page
                   Display                                                  Range      Setting    Opera-        V/f             loop           Regis-
       Number                                                                                                         Vector           Vector
                                                                                                    tion                       Vector           ter
                                                                                                                         1              (PM)
                Carrier           Selects the carrier frequency.
                frequency         1: 2 kHz
                selection         2: 5 kHz
                                                                                          3
       C6-02                      3: 8 kHz                                  1 to 6                   No         A         A        A    No    224H      6-2
                                                                                          *3
                CarrierFreq       4: 10 kHz
                Sel               5: 12.5 kHz
                                  6: 15 kHz
             Carrier              Set the carrier frequency upper
             frequency            limit and lower limit in kHz units.       2.0 to       8.0
       C6-03 upper limit          With the vector control method, the        15.0        kHz         No         A         A        A    No    225H      6-2
                CarrierFreq       upper limit of the carrier frequency      *1 *2         *3
                Max               is fixed in C6-03.
             Carrier              Selects the carrier frequency during
             during               rotational autotuning (no-load cur-
             rotational           rent, rated motor slip, and iron-core
       C6-09 autotuning           saturation coefficients 1 and 2).           0,1         0          No        No         A        A    No    22BH       -
                Carrier in        0: 5kHz
                tune              1: Setting value for C6-03.
             Carrier              Selects the carrier frequency during
             during               stationary autotuning.
             stationary           0: 0.5 kHz
       C6-10 autotuning                                                     0 to 3        1          No        No         A        A    No    22CH       -
5               Fc Static
                Tuning
                                  1: 1.0 kHz
                                  2: 1.5 kHz
                                  3: 2.0 kHz
             Carrier
             frequency            1: 2 kHz 2: 4 kHz 3: 6 kHz                              4
       C6-11 selection 2                                                    1 to 6                   No        No        No        No   A     22DH      6-2
                                  4: 8 kHz 5: 12 kHz 6: 15 kHz                            *3
                CarrierFreq Sel
5-20
                                                                                                                       Parameter Tables
Reference Parameters: d
Preset Reference: d1
                                                                                                                                              5-21
                                                                                                                                                           (Continued)
                        Name                                                                                              Control Methods
                                                                                                      Change                                     MEMO-
       Param-                                                                                                             Open-           Closed- BUS
                                                                                Setting    Factory     during                     Closed-
        eter                                      Description                                                              loop            loop                   Page
                       Display                                                  Range      Setting    Opera-       V/f              loop          Regis-
       Number                                                                                                             Vector          Vector
                                                                                                        tion                       Vector          ter
                                                                                                                             1             (PM)
             Inspection
             speed                  Sets the frequency reference when                     25.00 Hz
       d1-14 reference              the inspection speed is selected by a                               Yes         Q        Q         Q         Q      28FH          6-14
             Inspect Speed          multi-function contact input.*8                       50.00%
             vi                                                                 0 to       (PM)
                                                                               120.00
             Leveling                                                           *1*2
             speed                  Sets the frequency reference when                     4.00 Hz
       d1-17                        the leveling speed is selected by a                                                                                               6-10
             reference                                                                                  Yes         Q        Q         Q         Q      292H
        *6                                                           *7
                                                                                                                                                                      6-12
             Level Speed            multi-function contact input.                          8.00%
             vl                                                                            (PM)
             Speed prior-           Speed reference priority selection
             ity selection0: Use multi-speed reference
                             (d1-01 to d1-08)                                                                                                                         6-8
       d1-18                                                    0 to 2                        0         No          A        A         A         A      2A7H          6-10
             SpeedPriori- 1: High speed reference has priority.                                                                                                       6-12
             tySel        2: Leveling speed reference has
                             priority.
          *    1.   The maximum setting value depends on the setting of the maximum output frequency (E1-04).
          *    2.   The setting range becomes 0.00 to 100.00 when using closed-loop vector control (PM).
          *    3.   The factory setting changes to 0.00% when using closed-loop vector control (PM).
          *    4.   d1-01 to d1-08 are not displayed if d1-18 is set to 1 or 2. These are changed to H1-01 (80), H1-02 (84), H1-03 (81), H1-04 (83), and H1-05 (F).
          *    5.   d1-09 to d1-13 are not displayed if d1-18 is set to 0. These are changed to H1-01 (24), H1-02 (14), H1-03 (3), H1-04 (4), and H1-05 (6).
          *    6.   Becomes the jog frequency reference when d1-18 is set to 0.
          *    7.   Enabled by the combined selection of the nominal speed command, the intermediate speed command, and the releveling speed command.
5 * 8. Enabled if the Inspection Run Command is set for a multi-function contact input.
       Field Forcing: d6
                        Name                                                                                              Control Methods
                                                                                                      Change                                      MEMO-
       Param-                                                                                                             Open-            Closed- BUS
                                                                                Setting    Factory     during                      Closed-
        eter                                      Description                                                              loop             loop                  Page
                       Display                                                  Range      Setting    Opera-       V/f              loop           Regis-
       Number                                                                                                             Vector           Vector
                                                                                                        tion                       Vector           ter
                                                                                                                             1              (PM)
             Field forcing
                           Enables or disables field forcing
             function
                           function.
       d6-03 selection                                                           0, 1         0         No         No        A         A        No      2A2H          6-49
                           0: Disabled
             Field Force
                           1: Enabled
             Sel
                    Field forcing Sets the upper limit for the excita-
                    function      tion current applied by the field
                    Limit         forcing function.
                                    A setting of 100% is equal to the           100 to
       d6-06                                                                               400%         No         No        A         A        No      2A5H          6-49
                                    motor no-load current.                       400
                    FieldForce
                                    Field forcing is active during all
                    Limit
                                    types of operation except DC Injec-
                                    tion.
5-22
                                                                                                                                        Parameter Tables
Motor Parameters: E
  V/f Pattern: E1
                  Name                                                                                               Control Methods
                                                                                                Change                                       MEMO-
  Param-                                                                                                             Open-            Closed- BUS
                                                                          Setting    Factory    during                        Closed-
   eter                                      Description                                                              loop             loop            Page
                 Display                                                  Range      Setting    Opera-        V/f              loop           Regis-
  Number                                                                                                             Vector           Vector
                                                                                                 tion                         Vector           ter
                                                                                                                        1              (PM)
        Input volt-
                              Sets the Inverter input voltage.            155 to       200
        age setting
  E1-01                       This setting is used as a reference          255        VAC          No         Q         Q          Q    Q    300H      6-83
        Input                                                               *1        *1 *4
                              value for protection functions.
        Voltage
        V/f pattern           0 to D: Select from the 15 preset
        selection                     patterns.
                              F: Custom user-set patterns (Appli-
  E1-03                                                           0 to FF               F          No         A        No          No   No   302H       -
              V/F                cable for settings E1-04 to
              Selection          E1- 10.)
                              FF: No internal voltage limit
              Max. output
                                                                           0.0 to    60.0 Hz
              frequency
                                                                           120.0       *4
              (FMAX)
  E1-04                                                                                            No         Q         Q          Q    Q    303H      6-83
                                                                           20 to
              Max
                                                                           3600     96 min-1
              Frequency                                                             (PM)*5
                                                                           (PM)
        Max. output
                                                                           0.0 to     200.0
        voltage
  E1-05                                                                    255.0      VAC          No         Q         Q          Q    No   304H      6-83
        (VMAX)
                                                                             *1
                                                                                                                                                                5
                                 Output voltage (V)                                   *1 *4
        Max Voltage
        Base fre-                                                          0.0 to    60.0 Hz
        quency (FA)                                                        120.0       *4
  E1-06                                                                    20 to                   No         Q         Q          Q    Q    305H      6-83
        Base
                                                                           3600     96 min-1
        Frequency                                                          (PM)     (PM)*5
        Mid. output
        frequency
                                                                           0.0 to    3.0 Hz
  E1-07 (FB)                                          Frequency                                    No         A         A          No   No   306H      6-83
                                                                           120.0     *2 *4
        Mid Fre-              To set V/f characteristics in a
        quency A              straight line, set the same values for
        Mid. output           E1-07 and E1-09. In this case, the
        frequency             setting for E1-08 will be disre-             0.0 to     14.0
  E1-08 voltage (VB)          garded.                                      255.0      VAC          No         Q         Q          No   No   307H      6-83
        Mid Voltage           Always ensure that the four fre-               *1      *1 *2*4
        A                     quencies are set in the following
        Min. output           manner:
                                                                           0.0 to    1.5 Hz
        frequency             E1-04 (FMAX)  E1-06 (FA) > E1-              120.0     *2 *4
        (FMIN)                07 (FB)  E1-09 (FMIN)
  E1-09                                                                                            No         Q         Q          A    A    308H      6-83
                                                                            0 to
        Min Fre-
                                                                           3600      0 min-1
        quency                                                                        (PM)
                                                                           (PM)
        Min. output
        frequency                                                          0.0 to
                                                                                    7.0 VAC
  E1-10 voltage                                                            255.0                   No         Q         Q          No   No   309H      6-83
                                                                                    *1*2 *4
        (VMIN)                                                               *1
        Min Voltage
                                                                           0.0 to
              Base voltage Sets the output voltage of the base                      0.0 VAC
  E1-13                                                                    255.0                   No         A        No          No   Q    30CH      6-83
              (VBASE)      frequency (E1-06).                                          *3
                                                                             *1
     *   1.   These are values for a 200 V class Inverter. Values for a 400 V class Inverter are double.
     *   2.   The factory settings will change when the control method is changed. (The V/f control factory settings are given.)
     *   3.   After autotuning, E1-13 will contain the same value as E1-05.
     *   4.   The factory settings will change according to parameter o2-09. Values shown here are for when o2-09 is set to 0.
     *   5.   The factory settings depend on the Inverter capacity. The values for a 200 V class Inverter for 3.7kW are given.
                                                                                                                                                              5-23
       .Motor Setup: E2
5
                Motor line-to- Sets the motor phase-to-phase resis-
                line resistance tance.                                  0.000
                                                                               0.771 
       E2-05                                                              to                   No      Q       Q       Q      No     312H     6-77
                Term Resis- This parameter is automatically set                   *2
                                                                        65.000
                tance           during autotuning.
                Motor leak      Sets the voltage drop due to motor
                inductance      leakage inductance as a percentage
                                of the motor rated voltage.              0.0 to    19.6%
       E2-06                                                                                   No      No      A       A      No     313H     6-77
                Leak Induc-                                               40.0       *2
                                This parameter is automatically set
                tance
                                during autotuning.
                Motor iron
                                Sets the motor iron saturation coef-
                saturation
                                ficient at 50% of magnetic flux.        0.00 to
       E2-07    coefficient 1                                                       0.50       No      No      A       A      No     314H     6-77
                                This parameter is automatically set      0.50
                Saturation
                                during rotating autotuning.
                Comp1
                Motor iron
                                Sets the motor iron saturation coef-
                saturation
                                ficient at 75% of magnetic flux.        E2-07 to
       E2-08    coefficient 2                                                       0.75       No      No      A       A      No     315H     6-77
                                This parameter is automatically set      0.75
                Saturation
                                during rotating autotuning.
                Comp2
                Motor           Sets the motor mechanical losses as
                mechanical a percentage of motor rated power.
                losses          Usually changing this setting is not
                               necessary.
                                                                         0.0 to
       E2-09                   The value can be adjusted if there is                0.0%       No      No      A       A      No     316H     6-77
                                                                          10.0
                Mechanical     e.g. a great torque loss due to heavy
                loss           friction in the machine. The output
                               torque will be compensated for the
                               set mechanical loss.
             Motor iron
             loss for torque
                                                                          0 to     112 W
       E2-10 compensation      Sets motor iron losses.                                         No      No      No     No      No     317H     6-78
                                                                         65535       *2
             Tcomp Iron
             Loss
             Motor rated       Sets the rated output power of the
             output power      motor.                                   0.00 to 3.70 kW
       E2-11                                                                                   No      Q       Q       Q      No     318H     6-78
             Mtr Rated         This parameter is an input data for      650.00     *2
             Power             autotuning.
5-24
                                                                                                                                      Parameter Tables
                                                                                                                                                 (Continued)
               Name                                                                                              Control Methods
                                                                                             Change                                     MEMO-
Param-                                                                                                           Open-           Closed- BUS
                                                                       Setting    Factory    during                      Closed-
 eter                                    Description                                                              loop            loop                 Page
              Display                                                  Range      Setting    Opera-        V/f             loop          Regis-
Number                                                                                                           Vector          Vector
                                                                                              tion                        Vector          ter
                                                                                                                    1             (PM)
          Motor iron
          saturation
                        This parameter is automatically set            1.30 to
E2-12     coefficient 3                                                             1.30        No        No         A        A      No         328H   6-78
                        during rotating autotuning.                     1.60
          Saturation
          Comp3
   * 1. The setting range is from 10% to 200% of the Inverter rated output current. The value for a 200 V class Inverter for 3.7 kW is given.
   * 2. The factory settings depend on the Inverter capacity. The values for a 200 V class Inverter for 3.7 kW are given.
   * 3. The setting ranges depend on the Inverter capacity. The values for a 200 V class Inverter of 3.7 kW are given.
 E5-04
          Number of
          motor poles
                           Sets the number of motor poles.             4 to 48
                                                                                  32 pole
                                                                                                No        No        No        No      Q         32CH    -
                                                                                                                                                                 5
          Number of                                                                  *
          poles
       Motor line-
       to-line
                           Sets the motor line-to-line resis-         0.000 to 3.860
 E5-05 resistance                                                                               No        No        No        No      Q         32DH    -
                           tance.                                      65.000     *
          Term
          resistance
          d-axis
          inductance                                                              30.20
                                                                      0.00 to
 E5-06                     Sets the motors d-axis inductance.                      mH           No        No        No        No      Q         32EH    -
          d-ax                                                        300.00
                                                                                    *
          inductance
          q-axis
          inductance                                                              36.00
                                                                      0.00 to
 E5-07                     Sets the motors q-axis inductance.                      mH           No        No        No        No      Q         32FH    -
          q-ax                                                        600.00
                                                                                    *
          inductance
       Motor volt-
       age                                                                        1251.0
                                                                      50.0 to       mV
 E5-09 parameter           Sets the motor voltage parameter.                                    No        No        No        No      Q         331H    -
                                                                      4000.0       s/rad
          Voltage                                                                    *
          Parameter
       PG home
       position            Sets the amount of pulses to align
                                                                       -180.0
 E5-11 offset              the home position in units of 0.1                   0.0 deg          No        No        No        No      Q         333H    -
                                                                      to 180.0
          Zpuls-Mag        degrees.
          Offset
* The factory settings depend on the Inverter capacity. The values for a 200 V class Inverter for 3.7 kW are given.
                                                                                                                                                               5-25
        Option Parameters: F
PG Option Setup: F1
5        F1-03
               (OS)         stop using the deceleration time 1,
                                 C1-02.)
                                                                         0 to 3      1         No      No      No      A       A     382H     6-97
                                 1: Coast to stop
                  PG Over-       2: Fast stop (Fast stop using the
                  speed Sel         deceleration time in C1-09.)
                                 3: Continue operation (To protect
                                    the motor or machinery, avoid to
                                    use this setting.)
                  Operation      Sets the stopping method when a
                  selection at   speed deviation (DEV) fault occurs.
                                                                                     3
                  speed       0: Ramp to stop (Deceleration to
                  deviation      stop using the deceleration time
                                 1, C1-02.)
         F1-04                1: Coast to stop                           0 to 3                No      No      No      A       A     383H     6-97
                              2: Fast stop (Fast stop using the
               PG                                                                    1
                                 deceleration time in C1-09.)
               Deviation Sel                                                       (PM)
                              3: Continue operation (DEV is
                                 displayed and operation
                                 continued.)
                              0: Phase A leads with Forward Run
               PG rotation       Command. (Phase B leads with                        0
                                 Reverse Run Command)                                                                                         6-51
         F1-05                                                            0, 1                 No      No      No      Q       Q     384H
                              1: Phase B leads with Forward Run                                                                               6-97
               PG Rotation                                                           1
                                 Command. (Phase A leads with
               Sel                                                                 (PM)
                                 Reverse Run Command)
               PG division Sets the division ratio for the PG
               rate (PG pulse speed control board pulse output.
               monitor)       Division ratio = (1+ n) /m
                                 (n=0 or 1 m=1 to 32)
                                 The first digit of the value of F1-06
         F1-06                   stands for n, the second and the third 1 to 132     1         No      No      No      A       A     385H     6-97
                  PG Output      stands for m.
                  Ratio          This parameter is effective only
                                 when a PG-B2 is used.
                                 The possible division ratio settings
                                 are: 1/32  F1-06  1.
5-26
                                                                                                                         Parameter Tables
                                                                                                                                  (Continued)
             Name                                                                                       Control Methods
                                                                                         Change                                MEMO-
Param-                                                                                                  Open-           Closed- BUS
                                                                    Setting    Factory   during                 Closed-
 eter                                   Description                                                      loop            loop            Page
            Display                                                 Range      Setting   Opera-   V/f             loop          Regis-
Number                                                                                                  Vector          Vector
                                                                                          tion                   Vector          ter
                                                                                                           1             (PM)
         Overspeed
         detection
                          Sets the overspeed detection
F1-08    level                                                     0 to 120    115%       No      No      No      A       A     387H     6-98
                          method.
         PG Overspd
         Level            Motor speeds that continue to
                          exceed the value set in F1-08 (set as
         Overspeed
                          a percentage of the maximum output
         detection
                          frequency) for the time set in F1-09
F1-09    delay time                                             0.0 to 2.0      0.0 s     No      No      No      A       A     388H     6-98
                          are detected as overspeed faults.
         PG Overspd
         Time
         Excessive
         speed devia-
                          Sets the speed deviation detection
         tion detection
F1-10                     method.                                   0 to 50     10%       No      No      No      A       A     389H     6-98
         level
                          Any speed deviation above the F1-
         PG Deviate
                          10 set level (set as a percentage of
         Level
                          the maximum output frequency) that
         Excessive
                          continues for the time set in F1-11 is
         speed
                          detected as a speed deviation.
         deviation
                          The speed deviation is the differ-        0.0 to
F1-11    detection                                                              0.5 s     No      No      No      A       A    38AH      6-98
                          ence between actual motor speed            10.0
         delay time
                          and the speed reference command.
         PG Deviate
         Time
         PG
F1-14
         open-circuit
         detection
                          Used to set the PG disconnection
                          detection time. PGO will be               0.0 to
                                                                                1.0 s     No      No      No      A       A    38DH      6-98
                                                                                                                                                  5
         delay time       detected if the detection time             10.0
         PGO Detect       exceeds the set time.
         Time
         DV3 fault        Sets the number of scans (5ms) until
         detection        a DV3 fault (wrong direction) is
         selection        detected.
F1-18                                                               0 to 5       1        No      No      No     No       A    3ADH       -
                          0: No DV3 detection
         DV3 detect
         sel              n: A DV3 fault is detected after n 
                             5ms.
         DV4 fault        Sets the number of pulses until a
         detection        DV4 fault (wrong direction) is
         selection        detected.
F1-19                                                              0 to 5000    1024      No      No      No     No       A    3AEH       -
                          0: No DV4 detection
         DV4 detect
         pulse            n: A DV3 fault is detected after n
                             pulses.
         Absolute         Sets the serial line resolution for
         encoder reso- absolute encoders (HIPERFACE
         lution        or EnDat).
F1-21                                                               0 to 2       2        No      No      No     No       Q    3B0H       -
      PG-F2 Reso- 0: 16384
      lution       1: 32768
                   2: 8192
      Magnet posi-
      tion offset  Sets the Offset between the rotor
F1-22                                                              0 to 360    60deg      No      No      No     No       A    3B1H       -
      PG-F2 Mag magnet and encoder zero position.
      Comp
                   Used to memorize encoder and
      Encoder copy
                   motor data in the encoder memory
      selection
                   (for HIPERFACE and EnDat
F1-25                     encoders)*2                               0 to 3       0        No      No      No     No       A    3B4H      6-95
         ENC Copy         0: Normal operation
         Sel              1: WRITE (Inverter to encoder)
                          2: COPY (Encoder to Inverter)
                          3: VERIFY
                                                                                                                                                5-27
                                                                                                                                                      (Continued)
                    Name                                                                                              Control Methods
                                                                                                 Change                                      MEMO-
       Param-                                                                                                         Open-           Closed- BUS
                                                                           Setting    Factory     during                      Closed-
        eter                                  Description                                                              loop            loop                  Page
                   Display                                                 Range      Setting    Opera-        V/f              loop          Regis-
       Number                                                                                                         Vector          Vector
                                                                                                   tion                        Vector          ter
                                                                                                                         1             (PM)
             Encoder copy       Sets wether saving parameters in the
             write permis-      encoder is permitted or not.
       F1-26 sion selection                                                  0,1          0         No        No        No        No        A      3B5H       6-95
                                0: Write prohibited
             Write Allow-
             able               1: Write permitted
          * 1. The factory settings depend on the Inverter capacity. The values for a 200 V class Inverter for 3.7 kW are given.
          * 2. Parameter F1-25 can only be set using the Digital Operator.
               Once F1-25 has been set to 1, 2, or 3, the copy function will be executed. Afterwards, Copy complete will appear on the Digital Operator screen, and
               F1-25 will be reset to zero.
               If F1-26 = 0, then Encoder write protected will still appear even when F1-25 is set to 1.
5
                                                                           0.0 to
       F4-02    gain           tor board is used.                                     100.0%        Yes        A         A        A         A       392H        -
                                                                           1000.0
                AO Ch1 Gain This function is enabled when the
                Channel 2      analog monitor board is used.
                monitor selec-
       F4-03    tion           Monitor selection: Sets the number          1 to 99        3         No         A         A        A         A       393H        -
                AO Ch2         of the monitor item to be output.
                Select         (Numerical portion  of U1-
                Channel 2      )
                                                                           0.0 to
       F4-04    gain           4, 10, 11, 12, 13, 14, 25, 28, 34, 35,                  50.0%        Yes        A         A        A         A       394H        -
                                                                           1000.0
                AO Ch2 Gain 39 and 40 cannot be set.
                Channel 1
                output                                                    -110.0 to
       F4-05                   Gain: Sets the percentage of the                        0.0%         Yes        A         A        A         A       395H        -
                monitor bias                                                110.0
                                      monitor item, which is
                AO Ch1 Bias
                                       equal to 10V output.
                Channel 2
                output
                                                                          -110.0 to
       F4-06    monitor bias Bias: Sets the percentage of the               110.0
                                                                                       0.0%         Yes        A         A        A         A       396H        -
                                      monitor item, which is
                AO Ch2 Bias            equal to 0V output.
                Analog output
                signal level Selects the analog output signal
       F4-07    for channel 1 level for channel 1 (effective for the         0, 1         0         No         A         A        A         A       397H        -
                AO Opt Level AO-12 option card only).
                Sel            0: 0 to 10V
                Analog         1: -10 to +10
                output signal Using an AO-08 option card the
                level for      possible outputs signal is 0 to +10V
       F4-08                                                                 0, 1         0         No         A         A        A         A       398H        -
                channel 2      only. The setting of F4-07 and F4-
                AO Opt Level 08 has no effect.
                Sel
5-28
                                                                                                                 Parameter Tables
                                                                                                                                          5
                      Set the number of the multi-function
         DO Ch5
                      output to be output.
         Select
         Channel 6
                      Effective when a DO-08 digital out-
         output
                      put boards is used.
F5-06    selection                                           0 to 47     37       No      A       A       A       A    39EH       -
                      Set the number of the multi-function
         DO Ch6
                      output to be output.
         Select
         Channel 7
                      Effective when a DO-08 digital out-
         output
                      put boards is used.
F5-07    selection                                           0 to 47     0F       No      A       A       A       A    39FH       -
                      Set the number of the multi-function
         DO Ch7
                      output to be output.
         Select
         Channel 8
                      Effective when a DO-08 digital out-
         output
                      put boards is used.
F5-08    selection                                           0 to 47     0F       No      A       A       A       A    3A0H       -
                      Set the number of the multi-function
         DO Ch8
                      output to be output.
         Select
                      Effective when a DO-08 digital out-
                      put boards is used.
      DO-08       Set the output mode.
F5-09 output mode 0: 8-channel individual outputs            0 to 2      0        No      A       A       A       A    3A1H       -
      selection   1: Binary code output
                  2: Output according to F5-01 to F5-
                     08 settings.
                                                                                                                                        5-29
       Serial Communications Settings: F6
                    Name                                                                                  Control Methods
                                                                                          Change                                 MEMO-
       Param-                                                                                             Open-           Closed- BUS
                                                                      Setting   Factory    during                 Closed-
        eter                               Description                                                     loop            loop            Page
                   Display                                            Range     Setting   Opera-    V/f             loop          Regis-
       Number                                                                                             Vector          Vector
                                                                                            tion                   Vector          ter
                                                                                                             1             (PM)
                Operation       Sets the stopping method for com-
                selection after munications errors.
                communica- 0: Deceleration to stop using the
                tions error        deceleration time in C1-02
       F6-01                                                          0 to 3      1         No      A       A       A       A    3A2H       -
                                1: Coast to stop
                Comm Bus 2: Fast stop using the deceleration
                Fault Sel          time in C1-09
                                3: Continue operation
                Input level of
                external error
                from commu-
                                0: Always detect
       F6-02    nications                                              0, 1       0         No      A       A       A       A    3A3H       -
                                1: Detect during operation
                option card
                EF0 Detec-
                tion
                Stopping
                method for      0: Deceleration to stop using the
                external error     deceleration time in C1-02
                from commu- 1: Coast to stop
       F6-03                                                          0 to 3      1         No      A       A       A       A    3A4H       -
                nications       2: Fast stop using the deceleration
                option card        time in C1-09
                EF0 Fault       3: Continue operation
                Action
5               Trace sam-
                pling from
                communica-
                                                                       0 to
       F6-04    tions option -                                                    0         No      A       A       A       A    3A5H       -
                                                                      60000
                card
                Trace Sample
                Tim
                Current moni-
                tor unit selec- Sets the unit of current monitor
       F6-05    tion            0: Ampere                              0, 1       0         No      A       A       A       A    3A6H       -
                Current Unit 1: 100%/8192
                Sel
                Torque refer-
                ence/torque
                limit selec-
                                0: Torque reference/torque limit by
                tion from
                                   communications option disabled.
       F6-06    communica-                                             0, 1       1         No      No      No      A       A    3A7H       -
                tions option 1: Torque reference/torque limit by
                                   communications option enabled.
                card
                Torque Ref/
                Lmt Sel
5-30
                                                                                                                          Parameter Tables
                                                                                                                                                 5-31
       Multi-function Contact Input Functions
                                                                                                                 Control Methods
       Setting                                                                                                                           Closed-
                                                   Function                                                   Open-loop     Closed-                Page
       Value                                                                                                                              loop
                                                                                                      V/f      Vector        loop
                                                                                                                                         Vector
                                                                                                                 1          Vector
                                                                                                                                          (PM)
         3       Multi-step speed reference 1                                                        Yes          Yes          Yes         Yes      6-8
         4       Multi-step speed reference 2                                                        Yes          Yes          Yes         Yes      6-8
         5       Multi-step speed reference 3                                                        Yes          Yes          Yes         Yes      6-8
                 Jog frequency command (higher priority than multi-step speed refer-
         6                                                                                           Yes          Yes          Yes         Yes       -
                 ence)
         7       Accel/decel time switch over 1                                                      Yes          Yes          Yes         Yes     6-24
         8       External baseblock NO (NO contact: Baseblock at ON)                                 Yes          Yes          Yes         Yes     6-70
         9       External baseblock NC (NC contact: Baseblock at OFF)                                Yes          Yes          Yes          Yes    6-70
         F       Not used (Set when a terminal is not used)                                            -           -            -            -       -
         14      Fault reset (Reset when turned ON)                                                  Yes          Yes          Yes         Yes       -
                 Fast stop. (NO: Deceleration to stop in deceleration time set in C1-09
         15                                                                                          Yes          Yes          Yes         Yes     6-14
                 when ON.)
                 Fast stop (NC: Deceleration to stop in deceleration time set in C1-09
         17                                                                                          Yes          Yes          Yes         Yes     6-14
                 when OFF)
                 Timer function input (the times are set in b4-01 and b4-02 and the timer
         18                                                                                          Yes          Yes          Yes         Yes     6-71
                 function output is set in H2-.)
        1A       Accel/decel time switch over 2                                                      Yes          Yes          Yes         Yes     6-24
       20 to     External fault; Input mode: NO contact/NC contact, Detection mode:
                                                                                                     Yes          Yes          Yes         Yes     6-70
5
        2F       Normal/during operation
                 DC injection braking command (ON: Performs DC injection braking)
         60      Can be set when o2-09 is set to 1 (American specification). The brake               Yes          Yes          Yes          No       -
                 sequence is disabled.
                 Communications test mode (Pass is displayed when the communica-
         67                                                                                          Yes          Yes          Yes         Yes       -
                 tions test is passed.)
         80      Nominal Speed Command (d1-09) *1                                                    Yes          Yes          Yes         Yes     6-18
5-32
                                                                                                                          Parameter Tables
                                                                                                      Control Methods
 Setting                                                                                                                  Closed-
                                            Function                                                            Closed-                    Page
 Value                                                                                            Open-loop                loop
                                                                                          V/f                    loop
                                                                                                   Vector 1               Vector
                                                                                                                Vector
                                                                                                                                                     5
                                                                                                                           (PM)
   0       During run 1 (ON: Run Command is ON or voltage is being output)                Yes         Yes        Yes          Yes          6-73
   1       Zero-speed                                                                     Yes         Yes        Yes          Yes          6-74
   2       fref/fout agree 1 (detection width L4-02 is used.)                             Yes         Yes        Yes          Yes          6-32
           fref/fset agree 1 (ON: Output frequency = L4-01, with detection width
   3                                                                                      Yes         Yes        Yes          Yes          6-32
           L4-02 used and during frequency agree)
           Frequency detection 1 (ON: +L4-01  output frequency  -L4-01, with
   4                                                                                      Yes         Yes        Yes          Yes          6-32
           detection width L4-02 used)
           Frequency detection 2 (ON: Output frequency  +L4-01 or output fre-
   5                                                                                      Yes         Yes        Yes          Yes          6-32
           quency  -L4-01, with detection width L4-02 used)
   6       Inverter operation ready; READY: After initialization or no faults             Yes         Yes        Yes          Yes          6-74
   7       During DC bus undervoltage (UV) detection                                      Yes         Yes        Yes          Yes          6-74
   8       During baseblock (NO contact, ON: during baseblock)                            Yes         Yes        Yes          Yes          6-74
           Frequency reference source selection (ON: Frequency reference from
   9                                                                                      Yes         Yes        Yes          Yes          6-74
           Operator)
           Run Command source selection status (ON: Run Command from Opera-
   A                                                                                      Yes         Yes        Yes          Yes          6-74
           tor)
           Car stuck/undertorque detection 1 NO (NO contact, ON: Overtorque/
   B                                                                                      Yes         Yes        Yes          Yes          6-55
           undertorque detection)
   C       Loss of frequency reference (Effective when 1 is set for L4-05)                Yes         Yes        Yes          Yes          6-53
   D       Braking transistor fault                                                       Yes         Yes        Yes          Yes           -
           Fault (ON: Digital Operator/Monitor communications error or fault
   E                                                                                      Yes         Yes        Yes          Yes          6-74
           other than CPF00 and CPF01 has occurred.)
   F       Not used. (Set when the terminal is not used.)                                  -           -           -           -            -
   10      Minor fault (ON: Alarm displayed)                                              Yes         Yes        Yes          Yes          6-74
   11      Fault reset command active                                                     Yes         Yes        Yes          Yes          6-74
   12      Timer function output                                                          Yes         Yes        Yes          Yes          6-71
   13      fref/fset agree 2 (detection width L4-04 is used)                              Yes         Yes        Yes          Yes          6-32
           fref/fset agree 2 (ON: Output frequency = L4-03, with detection width
   14                                                                                     Yes         Yes        Yes          Yes          6-32
           L4-04 is used, and during frequency agree)
                                                                                                                                                   5-33
                                                                                                                               (Continued)
                                                                                                 Control Methods
       Setting                                                                                                       Closed-
                                                 Function                                                  Closed-                 Page
       Value                                                                                   Open-loop              loop
                                                                                         V/f                loop
                                                                                                Vector 1             Vector
                                                                                                           Vector
                                                                                                                      (PM)
                 Frequency detection 3 (ON: Output frequency  -L4-03, detection width
         15                                                                              Yes     Yes        Yes       Yes          6-32
                 L4-04 is used)
                 Frequency detection 4 (ON: Output frequency  -L4-03, detection width
         16                                                                              Yes     Yes        Yes       Yes          6-32
                 L4-04 is used)
                 Car stuck/undertorque detection 1 NC (NC Contact, OFF: Torque detec-
         17                                                                              Yes     Yes        Yes       Yes          6-55
                 tion)
                 Car stuck/undertorque detection 2 NO (NO Contact, ON: Torque detec-
         18                                                                              Yes     Yes        Yes       Yes          6-55
                 tion)
                 Car stuck/undertorque detection 2 NC (NC Contact, OFF: Torque detec-
         19                                                                              Yes     Yes        Yes       Yes          6-55
                 tion)
        1A       During reverse run (ON: During reverse run)                             Yes     Yes        Yes       Yes          6-75
        1B       During baseblock 2 (OFF: During baseblock)                              Yes     Yes        Yes       Yes          6-75
        1D       During regenerative operation                                           No       No        Yes       Yes          6-75
         1E      Restart enabled (ON: Automatic fault restart enabled)                   Yes     Yes        Yes       Yes            -
                 Motor overload (OL1, including OH3) pre-alarm (ON: 90% or more of
         1F                                                                              Yes     Yes        Yes       Yes          6-61
                 the detection level)
                 Inverter overheat (OH) pre-alarm (ON: Temperature exceeds L8-02 set-
         20                                                                              Yes     Yes        Yes       Yes          6-64
                 ting)
         30      During torque limit (current limit) (ON: During torque limit)           No      Yes        Yes       Yes          6-57
5
         33      Zero-servo end (ON: Zero-Servo completed)                               No       No        Yes       Yes            -
                 During run 2 (ON: Frequency output, OFF: Baseblock, DC injection
         37                                                                              Yes     Yes        Yes       Yes          6-73
                 braking, initial excitation, operation stop)
         38      During cooling fan operation                                            Yes     Yes        Yes       Yes            -
        3C       Magnet Position Detection Complete                                      No       No         No       Yes            -
        3D       Internal Cooling Fan Fault                                              Yes     Yes        Yes       Yes          6-59
         40      Brake Release Command                                                   Yes     Yes        Yes       Yes          6-18
         41      Magnetic Contactor Close Command                                        Yes     Yes        Yes       Yes          6-18
         42      Speed detection at deceleration (Door zone)                             Yes     Yes        Yes       Yes          6-75
         43      Not zero-speed                                                          Yes     Yes        Yes       Yes          6-75
                 Hardware Baseblock 1
                                                                                                                                   6-5
         46      ON: Hardware baseblock is not being executed (terminals BB and BB1      Yes     Yes        Yes       Yes
                                                                                                                                   6-75
                     are both closed).
                 Hardware Baseblock 2
                                                                                                                                   6-5
         47      ON: Hardware baseblock is currently being executed (terminals BB and    Yes     Yes        Yes       Yes
                                                                                                                                   6-75
                     BB1 are both open).
5-34
                                                                                                                    Parameter Tables
Analog Inputs: H3
                                                                                                                                           5-35
                                                                                                                                           (Continued)
                     Name                                                                                       Control Methods
                                                                                                Change                                 MEMO-
       Param-                                                                                                   Open-           Closed- BUS
                                                                           Setting   Factory     during                 Closed-
        eter                                   Description                                                       loop            loop             Page
                    Display                                                Range     Setting    Opera-    V/f             loop          Regis-
       Number                                                                                                   Vector          Vector
                                                                                                  tion                   Vector          ter
                                                                                                                   1             (PM)
                 Analog input
                                 Sets delay filter time parameter for
                 filter time
                                 the three analog input channels of        0.00 to     0.03
       H3-12     parameter                                                                        No      A       A       A       A     41BH      6-31
                                 the AI-14B option card.                    2.00         s
                 CH1-3 Filter-
                                 Effective for noise control etc.
                 Time
                 Terminal A1     Sets the multi-function analog input
                 function        function for terminal A1.
       H3-15     selection                                                  0, 1        0         No      No      No      A       A     434H      6-31
                                 Frequency Reference
                 Terminal A1
                 Func            Torque compensation
                 Terminal A1     Sets the frequency reference value
                 input gain      when 10 V is input as a percentage        0.0 to
       H3-16                                                                         100.0%      Yes      A       A       A       A     435H      6-31
                 Terminal A1     of the maximum output frequency           1000.0
                 Gain            set in E1-04.
                 Terminal A1     Sets the frequency reference value
                 input bias      when 0 V is input as a percentage of -100.0
       H3-17                                                            to            0.0%       Yes      A       A       A       A     436H      6-31
                 Terminal A1     the maximum frequency set in E1-
                                                                      +100.0
                 Bias            04.
          Note: H3-01 to H3-11 are displayed if using an A1-14B option card.
        H3-05,H3-09 Settings
                                                                                                                        Control Methods
5      Setting
       Value
                                    Function                                       Contents (100%)
                                                                                                                  V/f
                                                                                                                        Open-
                                                                                                                         loop
                                                                                                                        Vec-
                                                                                                                                Closed-
                                                                                                                                 loop
                                                                                                                                Vector
                                                                                                                                        Closed-
                                                                                                                                         loop
                                                                                                                                        Vector
                                                                                                                                                  Page
                                                                                                                        tor 1            (PM)
         1F      Analog input not used.                                                     -                     Yes    Yes     Yes     Yes      6-61
                 Auxiliary frequency reference (is used as          Maximum output frequency (AI-14B use
         2                                                                                                        Yes    Yes     Yes     Yes      6-32
                 multi speed reference 2)                           only)
                 Auxiliary frequency reference (is used as          Maximum output frequency (AI-14B use
         3                                                                                                        Yes    Yes     Yes     Yes      6-32
                 multi speed reference 3)                           only)
         14      Torque compensation                                Motors rated torque                          No     No      Yes     Yes      6-32
5-36
                                                                                                                         Parameter Tables
MEMOBUS Communications: H5
             Name                                                                                       Control Methods
                                                                                     Change                                    MEMO-
Param-                                                                                                  Open-           Closed- BUS
                                                                Setting   Factory    during                     Closed-
 eter                                Description                                                         loop            loop            Page
            Display                                             Range     Setting    Opera-       V/f             loop          Regis-
Number                                                                                                  Vector          Vector
                                                                                      tion                       Vector          ter
                                                                                                           1             (PM)
         Slave address
                                                                0 to 20
H5-01 Serial Comm Set the Inverter's slave address.                          1F        No         A       A       A       A     425H     6-109
                                                                   *
      Adr
      Communica- Set the baud rate for 6CN MEMO-
      tion speed      BUS communications.
      selection       0: 1200 bps
H5-02                 1: 2400 bps                          0 to 4             3        No         A       A       A       A     426H     6-109
      Serial Baud 2: 4800 bps
      Rate            3: 9600 bps
                      4: 19200 bps
      Communica- Set the parity for 6CN MEMOBUS
      tion parity     communications.
H5-03 selection       0: No parity                         0 to 2             0        No         A       A       A       A     427H     6-109
      Serial Com 1: Even parity
      Sel             2: Odd parity
      Stopping        Set the stopping method for commu-
      method after nications errors.
      communica- 0: Deceleration to stop using
      tion error         deceleration time in C1-02
H5-04                                                      0 to 3             3        No         A       A       A       A     428H     6-109
                      1: Coast to stop
      Serial Fault 2: Fast stop using deceleration time
      Sel                in C1-09
                      3: Continue operation
      Communica- Set whether or not a communica-                                                                                                   5
      tion error      tions timeout is to be detected as a
H5-05 detection       communications error.                 0,1               1        No         A       A       A       A     429H     6-109
      selection       0: Do not detect.
      Serial Flt Dtct 1: Detect
      Send wait
                         Set the time from the Inverter
      time
H5-06                    receiving data to when the Inverter    5 to 65     5 ms       No         A       A       A       A    42AH      6-109
      Transmit
                         starts to send.
      WaitTIM
      RTS control        Select to enable or disable RTS con-
      ON/OFF             trol.
H5-07                    0: Disabled (RTS is always ON)           0,1         1        No         A       A       A       A    42BH      6-109
      RTS Control
                         1: Enabled (RTS turns ON only
      Sel
                            when sending)
* If H5-01 is set to zero, then the Inverter will no longer respond to MEMOBUS communications.
                                                                                                                                                 5-37
        Protection Function Parameters: L
         Motor Overload: L1
                     Name                                                                                              Control Methods
                                                                                                    Change                                    MEMO-
         Param-                                                                                                        Open-           Closed- BUS
                                                                             Setting     Factory     during                    Closed-
          eter                                  Description                                                             loop            loop            Page
                    Display                                                  Range       Setting    Opera-       V/f             loop          Regis-
         Number                                                                                                        Vector          Vector
                                                                                                      tion                      Vector          ter
                                                                                                                          1             (PM)
                              Sets whether the motor thermal
                              overload protection function is
               Motor protec- enabled or disabled.
                                                                              0 to 3        1
               tion selection 0: Disabled
                              1: General-purpose motor
                                 protection (fan cooled motor)
                              2: Inverter motor protection
                                 (externally cooled motor)
         L1-01                                                                                         No        Q       Q       Q       A     480H     6-60
                              3: Vector motor protection
                                 When the Inverter power supply
               MOL Fault         is turned off, the thermal value is           0.5          5
               Select            reset, so even if this parameter is          (PM)        (PM)
                                 set to 1, protection may not be
                                 effective.
                              5: Permanent magnet parameter
                                    torque motor protection
               Motor protec- Sets the electric thermal detection
               tion time      time in seconds units.
               parameter      Usually changing this setting is not
5        L1-02
                                 necessary.
                                 The factory setting is 150% over-
                                 load for one minute.
                                                                              0.1 to
                                                                               5.0
                                                                                        1.0 min
                                                                                           *
                                                                                                       No        A       A       A       A     481H     6-61
                  MOL Time                                                      *
                  Const          When the motor's overload capabil-
                                 ity is known, also set the overload
                                 resistance protection time for when
                                 the motor is hot started.
* Values will change according to parameter o2-09. Values shown here are for when o2-09 is set to 0.
* These are values for a 200 V class Inverter. Values for a 400 V class Inverter are the double.
5-38
                                                                                                                     Parameter Tables
Stall Prevention: L3
                                                                                                                                            5-39
                                                                                                                                             (Continued)
                    Name                                                                                           Control Methods
                                                                                                   Change                                 MEMO-
       Param-                                                                                                      Open-           Closed- BUS
                                                                            Setting    Factory      during                 Closed-
        eter                                   Description                                                          loop            loop            Page
                   Display                                                  Range      Setting     Opera-    V/f             loop          Regis-
       Number                                                                                                      Vector          Vector
                                                                                                     tion                   Vector          ter
                                                                                                                      1             (PM)
                Stall preven-     Set the stall prevention during run-
                tion level dur-   ning operation current level as a per-
                ing               centage of the Inverter rated current.
                running           Effective when L3-05 is 1 or 2.
       L3-06                                                               30 to 200 150%            No      A       No     No      No     494H     6-52
                                  Usually changing this setting is not
                StallP Run        necessary.
                Level             Reduce the setting when the motor
                                  stalls.
            * Setting range changes to 0, 1, and 2 when operating in closed-loop vector control.
Reference Detection: L4
5
             Level                                                                     (PM)
                                                                            (PM)
             Speed agree- Effective when f /f agree 1,
                                              ref out                       0.0 to
             ment detec-                                                               2.0 Hz
                          fout/fset agree 1 or Frequency                  20.0
             tion width
       L4-02              detection 1 or Frequency detec-                                          No      A       A       A       A    49AH      6-32
             Spd Agree                                                      0.0 to
                          tion 2 is set for a multi-function                          4.0%
                                                                             40.0
             Width        output.                                                      (PM)
                                                                            (PM)
             Speed agree-
             ment detec- Effective when f /f agree 2,                    -120.0 to
                                              out set                                0.0 Hz
             tion level (+/-                                                +120.0
                             Frequency detection 3 or Fre-
       L4-03 )                                                                                       No      A       A       A       A    49BH      6-32
                             quency detection 4 is set for a
             Spd Agree                                                     -100.0 to
                             multi-function output.                                    0.0%
                                                                             100.0
             Lvl+-                                                                     (PM)
                                                                             (PM)
             Speed agree-
             ment detec- Effective when fref/fout agree 2                 0.0 to
             tion width                                                                2.0 Hz
                          fout/fset agree 2, Frequency                    20.0
       L4-04 (+/-)        detection 3 or "Frequency detec-                                          No      A       A       A       A    49CH      6-32
                          tion 4" is set for a multi-function               0.0 to
             Spd Agree                                                                 4.0%
                          output.                                            40.0
             Wdth+-                                                                    (PM)
                                                                            (PM)
             Operation     0: Stop (Operation follows the
             when fre-        frequency reference.)
             quency refer- 1: Operation at 80% speed
             ence is          continues. (At 80% of speed
       L4-05 missing          before the frequency reference                  0,1        0           No      A       A       A       A    49DH      6-53
                              was lost)
                            Frequency reference is lost: Fre-
                Ref Loss Sel
                            quency reference dropped over 90%
                            in 400 ms.
             Frequency      If the frequency reference loss func-
             reference at tion is enabled (L4-05=1) when the
             frequency ref- frequency reference gets lost, the
                                                                   0.0 to
       L4-06 erence loss    Inverter will run at a reduced fre-                        80.0%         No      A       A       A       A    4C2H      6-53
                                                                  100.0%
                            quency reference determined by the
             Fref at Floss following formula:
                            Fref = Fref at time of loss  L4-06.
5-40
                                                                                                                    Parameter Tables
Fault Restart: L5
             Name                                                                                  Control Methods
                                                                                    Change                                MEMO-
Param-                                                                                             Open-           Closed- BUS
                                                                Setting   Factory   during                 Closed-
 eter                                 Description                                                   loop            loop            Page
            Display                                             Range     Setting   Opera-   V/f             loop          Regis-
Number                                                                                             Vector          Vector
                                                                                     tion                   Vector          ter
                                                                                                      1             (PM)
         Number of       Sets the number of auto restart
         auto restart    attempts.
         attempts        Automatically restarts after a fault
L5-01                    The retry fault code are the follow-   0 to 10     2        No      A       A       A       A    49EH      6-105
         Num of          ings
         Restarts        OV, GF, OC, OL2, OL3, OL4, UL3,
                         UL4, PF, LF, SE1, SE2, SE3
         Auto restart    Sets whether a fault contact output
         operation       is activated during fault restart.
         selection       0: No output (Fault contact is not
L5-02                                                            0, 1       1        No      A       A       A       A     49FH     6-105
                            activated.)
         Restart Sel     1: Output (Fault contact is
                            activated.)
         Fault restart
                    Sets the interval time between fault        0.5 to
L5-03 interval time                                                        2.0 s     No      A       A       A       A    4AOH 6-105
                    restarts.                                   180.0
      Retry time
      Under volt-        Selects the reset method for a UV1
      age fault          fault.
      restart selec-     0: UV1 fault is reset like set in
L5-05 tion                                                       0,1        0        No      A       A       A       A    4CCH 6-106
                            parameter L5-01
      UV1 Restart        1: UV1 fault is always
      Sel.                  automatically reset
                                                                                                                                            5-41
       Torque Detection: L6
                    Name                                                                                  Control Methods
                                                                                          Change                                 MEMO-
       Param-                                                                                             Open-           Closed- BUS
                                                                     Setting    Factory    during                 Closed-
        eter                               Description                                                     loop            loop            Page
                   Display                                           Range      Setting   Opera-    V/f             loop          Regis-
       Number                                                                                             Vector          Vector
                                                                                            tion                   Vector          ter
                                                                                                             1             (PM)
                Torque        0: Torque detection disabled.
                detection     1: Car stuck detection only with
                selection 1      speed agreement; operation
                                 continues (warning is output).
                              2: Car stuck detected continuously
                                 during operation; operation
                                 continues
                                 (warning is output).
                              3: Car stuck detection only with
                                 speed agreement; output stopped
                                 upon detection.
                              4: Car stuck detected continuously
                                 during operation; output stopped
       L6-01                     upon detection.                      0 to 8      4         No      A       A       A       A    4A1H      6-54
                Torq Det 1    5: Undertorque detection only with
                Sel              speed agreement; operation
                                 continues (warning is output).
                              6: Undertorque detected
                                 continuously during operation;
                                 operation continues
                                 (warning is output).
                              7: Undertorque detection only with
                                 speed agreement; output stopped
5
                                 upon detection.
                              8: Undertorque detected
                                 continuously during operation;
                                 output stopped upon detection.
                Torque detec- Vector control: Motor rated torque is
                tion level 1  set as 100%.
       L6-02                                                         0 to 300   150%        No      A       A       A       A    4A2H      6-54
                Torq Det 1    V/f control: Inverter rated current is
                Lvl           set as 100%.
                Torque detec-
                tion time 1   Sets the overtorque/undertorque         0.0 to
       L6-03                                                                    10.0 s      No      A       A       A       A    4A3H      6-54
                Torq Det 1    detection time.                          10.0
                Time
                Torque
                detection
       L6-04    selection 2                                           0 to 8      0         No      A       A       A       A    4A4H      6-54
                Torq Det 2
                Sel
                Torque detec-
                              See L6-01 to L6-03 for a descrip-
                tion level 2                                           0 to
       L6-05                  tion.                                             150%        No      A       A       A       A    4A5H      6-54
                Torq Det 2                                             300
                Lvl
                Torque detec-
                tion time 2                                           0.0 to
       L6-06                                                                     0.1 s      No      A       A       A       A    4A6H      6-54
                Torq Det 2                                             10.0
                Time
5-42
                                                                                                                            Parameter Tables
Torque Limits: L7
             Name                                                                                          Control Methods
                                                                                            Change                                MEMO-
Param-                                                                                                     Open-           Closed- BUS
                                                                        Setting   Factory   during                 Closed-
 eter                                   Description                                                         loop            loop            Page
            Display                                                     Range     Setting   Opera-   V/f             loop          Regis-
Number                                                                                                     Vector          Vector
                                                                                             tion                   Vector          ter
                                                                                                              1             (PM)
         Forward drive
         torque limit
L7-01                                                                                        No      No      A       A       A    4A7H      6-57
         Torq Limit
         Fwd
                         Sets the torque limit value as a per-
         Reverse drive
                         centage of the motor rated torque.
         torque limit
L7-02                    Four individual regions can be set.                                 No      No      A       A       A    4A8H      6-57
         Torq Limit
                                         Output torque
         Rev
                                                   Positive torque
         Forward
                                                           No. of
                                                                       0 to 300   200%
         regenerative
                                    Regenera-              motor
L7-03    torque limit     Reverse   tive state             rotations                         No      No      A       A       A    4A9H      6-57
         Torq Lmt                                Regenera- Forward
                                                 tive state
         Fwd Rgn
         Reverse                                 Negative torque
         regenerative
L7-04    torque limit                                                                        No      No      A       A       A    4AAH      6-57
         Torq Lmt Rev
         Rgn
         Torque limit
         time parame-
                         Sets the torque limit integration time          5 to
L7-06    ter                                                                      200 ms     No      No      A      No       A    4ACH      6-57
                         parameter                                      10000
         Torque Limit
         Time
         Torque Limit
         Operation
         during accel/
                         Sets the torque limit operation dur-
                         ing acceleration and deceleration.                                                                                          5
                         0: P-control (I control is added at
         decel              parameter speed operation)
                         1: I-control
                      Normally changing this setting is
L7-07                 not necessary.                                     0, 1       0        No      No      A      No       A    4C9H      6-57
         Torque Limit If the torque limitation accuracy
         Sel          during accel/decel. has preference, I
                      control should be selected. This may
                      result in an increased accel./decel.
                      time and speed deviations from the
                      reference value.
Hardware Protection: L8
                                                                                                                                                   5-43
                                                                                                                                      (Continued)
                    Name                                                                                    Control Methods
                                                                                            Change                                 MEMO-
       Param-                                                                                               Open-           Closed- BUS
                                                                       Setting    Factory    during                 Closed-
        eter                                   Description                                                   loop            loop            Page
                   Display                                             Range      Setting   Opera-    V/f             loop          Regis-
       Number                                                                                               Vector          Vector
                                                                                              tion                   Vector          ter
                                                                                                               1             (PM)
             Operation       Sets the operation when an Inverter
             selection after overheat pre-alarm occurs.
             overheat pre- 0: Decelerate to stop using the
             alarm              deceleration time C1-02.
                             1: Coast to stop
       L8-03                 2: Fast stop in fast-stop time C1-09.      0 to 3      3         No      A       A       A       A    4AFH      6-64
                             3: Continue operation (Monitor
             OH Pre-
                                display only.)
             Alarm Sel
                             A fault will be given in setting 0 to 2
                             and a minor fault will be given in
                             setting 3.
             Input open- 0: Disabled
             phase protec- 1: Enabled (Detects if input current
       L8-05 tion selection     open-phase, power supply
        *2                                                              0 or 1      1         No      A       A       A       A    4B1H       -
                                voltage imbalance or main circuit
             Ph Loss In Sel electrostatic capacitor
                                deterioration occurs.)
             Output open- 0: Disabled
             phase protec- 1: Enabled, 1 Phase Observation
             tion selection 2: Enabled, 2 and 3 Phase
                                Observation
                                 An output open-phase is detected at
                                 less than 5% of Inverter rated cur-
       L8-07                                                            0 to 2      2         No      A       A       A       A    4B3H      6-65
                                 rent.
5               Ph Loss Out
                Sel              When the applied motor capacity is
                                 small compared to the Inverter
                                 capacity, the detection may not
                                 work properly and should be dis-
                                 abled.
                Ground fault
                detection
                                 0: Disabled
       L8-09    selection                                                0, 1       1         No      A       A       A       A    4B5H      6-65
                                 1: Enabled
                Ground Fault
                Sel
                Cooling fan      Set the ON/OFF control for the
                control          cooling fan.
       L8-10    selection        0: ON when Inverter is                  0, 1       0         No      A       A       A       A    4B6H      6-66
                Fan On/Off          running only
                Sel              1: ON whenever power is ON
                Cooling fan
                                 Set the time in seconds to delay
                control delay
                                 turning OFF the cooling fan after
       L8-11    time                                                   0 to 300    60 s       No      A       A       A       A    4B7H      6-66
                                 the Inverter Stop Command is
                Fan Delay
                                 given. (Valid only if L8-10 = 0)
                Time
                Ambient
                temperature
       L8-12                     Sets the ambient temperature.         45 to 60   45 C       No      A       A       A       A    4B8H      6-67
                Ambient
                Temp
                Soft CLA
                                 0: Disabled
       L8-18    selection                                                0, 1       1         No      A       A       A       A    4BEH       -
                                 1: Enabled
                Soft CLA Sel
                Output phase
                loss detection   Sets the detection time of output      0.0 to
       L8-20                                                                       0.2 s      No      A       A       A       A    4C0H      6-65
                time             phase loss detection (LF.)              2.0
                Pha loss det T
5-44
                                                                                                                                  Parameter Tables
                                                                                                                                           (Continued)
               Name                                                                                              Control Methods
                                                                                             Change                                     MEMO-
  Param-                                                                                                         Open-           Closed- BUS
                                                                       Setting    Factory    during                      Closed-
   eter                                  Description                                                              loop            loop            Page
              Display                                                  Range      Setting    Opera-       V/f              loop          Regis-
  Number                                                                                                         Vector          Vector
                                                                                              tion                        Vector          ter
                                                                                                                    1             (PM)
           OH1
           detection       0: Alarm triggered if the internal
           during cool-       cooling fan fails.
  L8-32                                                                  0,1         1          No         A         A       A     A    4E2H      6-58
           ing fan failure 1: Fault situation detected if the
           OH1                cooling fan fails.
           Detect Sel
     * 1. The factory settings depend on the Inverter capacity. The values for a 200 V class Inverter of 3.7 kW are given.
     * 2. Applicable for L7-Series Inverters with software versions PRG: 2012 or later.
N: Special Adjustments
  Feed Forward: N5
               Name                                                                                              Control Methods
                                                                                             Change                                     MEMO-
  Param-                                                                                                         Open-           Closed- BUS
                                                                       Setting    Factory    during                      Closed-
   eter                                  Description                                                              loop            loop            Page
              Display                                                  Range      Setting    Opera-       V/f              loop          Regis-
  Number                                                                                                         Vector          Vector
                                                                                              tion                        Vector          ter
                                                                                                                    1             (PM)
        Feed forward       Enables or disables the feed forward
        control            control.
  N5-01 selection                                                       0, 1         0          No        No        No       A     A    5B0H      6-47
        Feedfoward         0: Disabled
        Sel                1: Enabled
                                                                                                                                                         5-45
                    Name                                                                                              Control Methods
                                                                                                  Change                                     MEMO-
       Param-                                                                                                         Open-           Closed- BUS
                                                                            Setting    Factory     during                     Closed-
        eter                                    Description                                                            loop            loop            Page
                   Display                                                  Range      Setting    Opera-        V/f             loop          Regis-
       Number                                                                                                         Vector          Vector
                                                                                                    tion                       Vector          ter
                                                                                                                         1             (PM)
                Motor accel- Set the time required to accelerate
                eration time the motor at the rated torque (T100)
                             to the rated speed (Nr).
                                 J: GD2/4, P: Motor rated output
       Startup Current: N8
                    Name                                                                                              Control Methods
                                                                                                  Change                                     MEMO-
       Param-                                                                                                         Open-           Closed- BUS
                                                                            Setting    Factory     during                     Closed-
        eter                                    Description                                                            loop            loop            Page
                   Display                                                  Range      Setting    Opera-        V/f             loop          Regis-
       Number                                                                                                         Vector          Vector
                                                                                                    tion                       Vector          ter
5
                                                                                                                         1             (PM)
                Initial mag-     Determines the current for estimat-
                netic polarity   ing the initial magnetic polarity. Set
                estimation       as a percentage of the motor rated
                current          torque (E5-03).
       N8-01                                                               0 to 100     75%          No        No        No        No   Q     540H      -
                                 Usually setting is not necessary.
                MagPos Srch If the motor nameplate includes a
                Curr           value for Si, then that value should
                               be entered to this parameter.
                Magnet posi- Sets the magnet position detection
                tion detection method.
                method         0: Magnet position detection
                                   method 1
       N8-35                     2: Magnet position detection               0,2,4,5       2          No        No        No        No   Q     562H      -
                Mag det sel         method 2
                                 4: HIPERFACE method
                                 5: EnDat method
             Magnet posi-
             tion detection
                                 Sets the frequency for magnet posi-
       N8-36 method 2 fre-                                           0 to 1000 500 Hz                No        No        No        No   A     563H      -
             quency              tion detection method 2.
             Inj freq
             Magnet posi-
             tion detection      Sets the amount of current for mag-
                                 net position detection method 2 as a       0.1 to
       N8-37 method 2 cur-                                                             30.0%         No        No        No        No   A     564H      -
                                 percentage of the motor rated cur-          99.9
             rent level
                                 rent.
             Inj cur lvl
             Low pass fil-
             ter cut-off fre-
             quency for
                                 Sets the low pass filter cut-off fre-
             magnet posi-
       N8-39                     quency for magnet position detec-         0 to 999     50 Hz        No        No        No        No   A     566H      -
             tion detection
                                 tion method 2.
             method 2
             LPF cutoff
             freq
5-46
                                                                                                                          Parameter Tables
  Factory-set Parameter: N9
               Name                                                                                      Control Methods
                                                                                          Change                                MEMO-
  Param-                                                                                                 Open-           Closed- BUS
                                                                     Setting    Factory   during                 Closed-
   eter                                  Description                                                      loop            loop            Page
              Display                                                Range      Setting   Opera-   V/f             loop          Regis-
  Number                                                                                                 Vector          Vector
                                                                                           tion                   Vector          ter
                                                                                                            1             (PM)
        A/D conver-
        sion start
        delay timer                                                   0.0 to
  N9-60                    Sets the A/D conversion delay time.                   0.0 s    No      No      No     No       A    64DH      6-43
        AD                                                             40.0
        DelayT@Star
        t
        Leakage cur-       Selects whether to reduce the leak-
        rent reduc-        age current.
        tion selection  If some carrier frequencies cause
  N9-74                 vibration due to leakage current,             0 or 1        0      No      No      No     No       A    65BH       -
    *
           Leak Cur Dec enable this function.
           Sel          0: Disabled
                        1: Enabled
        * Applicable for L7-Series Inverters with software versions PRG: 2012 or later.
                                                                                                                                                   5
  Monitor Selections: o1
               Name                                                                                      Control Methods
                                                                                          Change                                MEMO-
  Param-                                                                                                 Open-           Closed- BUS
                                                                     Setting    Factory   during                 Closed-
   eter                                  Description                                                      loop            loop            Page
              Display                                                Range      Setting   Opera-   V/f             loop          Regis-
  Number                                                                                                 Vector          Vector
                                                                                           tion                   Vector          ter
                                                                                                            1             (PM)
        Monitor
                           Selects which monitor will be dis-
        selection
  o1-01                    played in the operation menu upon         4 to 99        6      Yes     A       A       A       A     500H     6-85
        User Monitor
                           power-up when o1-02 is set to 4.
        Sel
        Monitor            Sets the monitor item to be dis-
        selection after    played when the power is turned on.
        power up           0: Frequency reference
  o1-02                                                               1 to 4        1      Yes     A       A       A       A     501H     6-85
                           1: Output frequency
        Power-On
                           2: Output current
        Monitor
                           3: The monitor item set for o1-01
                                                                                                                                                 5-47
                    Name                                                                                       Control Methods
                                                                                               Change                                 MEMO-
       Param-                                                                                                  Open-           Closed- BUS
                                                                           Setting   Factory    during                 Closed-
        eter                                  Description                                                       loop            loop            Page
                   Display                                                 Range     Setting   Opera-    V/f             loop          Regis-
       Number                                                                                                  Vector          Vector
                                                                                                 tion                   Vector          ter
                                                                                                                  1             (PM)
                                Sets the units that will be set and
                                displayed for the frequency refer-
                                ence and frequency monitor.
                Frequency
                                0: 0.01 Hz units
                units of refer-
                                1: 0.01% units (Maximum output                         0
                ence setting
                                   frequency is 100%)
                and monitor
                                2 to 39: min-1 units (Set the motor
                                poles.)
                                40 to 39999: User desired display
                                Set the desired values for setting and
                                display for the max. output fre-            0 to
       o1-03                                                                                     No      A       A       A       A     502H     6-85
                                quency.                                    39999
5 parameters
       o1-04 characteristics
                             Set the setting unit for frequency
             related to V/f reference-related parameters.
                             0: Hz
                                                                            0, 1
                                                                                       0
                                                                                                 No      No      No      A       A     503H     6-85
                                         1
                                1: min                                                 1
                Display Units
                                                                                     (PM)
5-48
                                                                                                                                  Parameter Tables
                                                                                                                                           (Continued)
               Name                                                                                              Control Methods
                                                                                             Change                                     MEMO-
Param-                                                                                                           Open-           Closed- BUS
                                                                       Setting    Factory    during                      Closed-
 eter                                    Description                                                              loop            loop            Page
              Display                                                  Range      Setting    Opera-        V/f             loop          Regis-
Number                                                                                                           Vector          Vector
                                                                                              tion                        Vector          ter
                                                                                                                    1             (PM)
      Parameter ini- Clears or stores user initial values.
      tial value     0: Stores/not set
                     1: Begins storing (Records the set
                        parameters as user initial values.)
o2-03                2: All clear (Clears all recorded user            0 to 2        0          No         A         A        A    A     507H     6-86
      User Defaults     initial values)
                           When the set parameters are
                           recorded as user initial values, 1110
                           will be set in A1-03.
      kVA selection
o2-04 Inverter             (Do not set this parameter.)               0 to FF        4*         No         A         A        A    A     508H     6-86
      Model #
      Frequency            Sets whether the ENTER key is
      reference set-       needed for a frequency reference
      ting method          change or not when the Digital
      selection            Operator is selected as frequency
                           reference source.
o2-05                                                                   0, 1         0          No         A         A        A    A     509H     6-86
                           0: Enter key needed
          Operator         1: Enter key not needed
          M.O.P.           If 1 is selected, a frequency refer-
                           ence change is accepted without the
                           need of pressing the Enter key.
          Operation        Sets the operation when the Digital
                                                                                                                                                           5
          selection        Operator/LED Monitor is
          when digital     disconnected.
          operator is    0: Operation continues even if the
          disconnected      Digital Operator/LED Monitor is
o2-06                       disconnected.                        0, 1                0          No         A         A        A    A    50AH      6-86
                         1: OPR is detected at Digital
          Oper              Operator/LED Monitor
          Detection         disconnection. Inverter output is
                            switched off, and the fault contact
                            is operated.
          Cumulative
          operation
                         Sets the cumulative operation time      0 to
o2-07     time setting                                                             0 hr.        No         A         A        A    A    50BH      6-86
                         in hour units.                         65535
          Elapsed Time
          Set
          Cumulative
          operation      0: Accumulated Inverter power on
o2-08     time selection time.                                   0, 1                1          No         A         A        A    A    50CH      6-86
          Elapsed Time 1: Accumulated Inverter run time.
          Run
          Initialize     0: Japanese specification
o2-09     Mode           1: American specification              0 to 2               0          No         A         A        A    A    50DH      6-86
          InitModeSet 2: European specification
          Fan operation Sets the initial value of the fan oper-
          time setting ation time.                               0 to
o2-10                                                                              0 hr.        No         A         A        A    A    50EH      6-86
          Fan ON Time The operation time is accumulated         65535
          Set            starting from this set value.
          Fault trace    0: No initialisation
          initialize     0: Initialize (= zero clear) after
o2-12                                                            0, 1                0          No         A         A        A    A     510H     6-86
          Fault Trace       setting 1 o2-12 will be returned
          Init              to 0
          Number of      Operation counter initialize.
          Travels        0: Number of travels counter is
o2-15     counter ini-      kept                                 0, 1                0          No         A         A        A    A     513H     6-87
          tialize        1: Number of travels counter
          Initialize Sel     monitor clear
        * The factory settings depend on the Inverter capacity. The values for a 200 V class Inverter for 3.7 kW are given.
                                                                                                                                                         5-49
        Copy Function: o3
                  Name                                                                             Control Methods
                                                                                   Change                                 MEMO-
       Param-                                                                                      Open-           Closed- BUS
                                                               Setting   Factory    during                 Closed-
        eter                              Description                                               loop            loop            Page
                 Display                                       Range     Setting   Opera-    V/f             loop          Regis-
       Number                                                                                      Vector          Vector
                                                                                     tion                   Vector          ter
                                                                                                      1             (PM)
             Copy function    0: Normal operation
             selection        1: READ (Inverter to Operator)
       o3-01                                                   0 to 3      0         No      A       A       A       A     515H     6-89
             Copy Func-       2: COPY (Operator to Inverter)
             tion Sel         3: Verify (compare)
             Read permis-
             sion selection   0: READ prohibited
       o3-02                                                    0, 1       0         No      A       A       A       A     516H     6-89
             Read             1: READ permitted
             Allowable
5-50
                                                                                                                       Parameter Tables
Brake Sequence: S1
                                                                                                                                              5-51
                                                                                                                                      (Continued)
                    Name                                                                                    Control Methods
                                                                                            Change                                 MEMO-
       Param-                                                                                               Open-           Closed- BUS
                                                                        Setting   Factory    during                 Closed-
        eter                                 Description                                                     loop            loop            Page
                   Display                                              Range     Setting   Opera-    V/f             loop          Regis-
       Number                                                                                               Vector          Vector
                                                                                              tion                   Vector          ter
                                                                                                               1             (PM)
                SE3 detec-      Used to set the delay time for the
                tion delay      detection of a SE3 fault.
                time            At the time S1-15 after the fwd/rev
                                                                          0
                                command was given, the Inverter                                                                              6-16
       S1-15                                                             to       200 ms      No      A       A       A      No    68EH
                                starts to observe the output current                                                                         6-62
                                                                        5000
                SE3 det T       continuously. If it falls below 25%
                                of the no-load current (E2-03) set-
                                ting a SE3 will be output.
                Run delay       Sets the delay time from the Run         0.00
       S1-16    time            signal input to the internal run          to      0.10 s      No      A       A       A       A    68FH      6-16
                Run Delay T enable.                                      1.00
                DC injection
                current gain at
                                Used to set the DC injection gain          0
                regenerative
       S1-17                    when Inverter is in the regenerative      to      100%        No      No      A      No      No     690H     6-16
                operation
                                mode.                                    400
                DC Inj
                gain@gen
                DC injection
                current gain at
                                Used to set the DC injection gain          0
                motoring
       S1-18                    when Inverter is in the motoring          to       20%        No      No      A      No      No     691H     6-16
                operation
                                mode.                                    400
                DC Inj
                gain@mot
5
                Magnetic
                contactor
                open delay                                               0.00
                                Sets the magnetic contactor control
       S1-19                                                              to      0.10 s      No      A       A       A       A     692H     6-16
                time            output delay time after stop.            1.00
                Cont open
                delay
                Zero-servo      Adjust the strength of the zero-servo
                gain            lock.
                                When closed-loop vector control is
                                selected, a position control loop is
       S1-20                                                          0 to 100      5         No      No      No      A       A     693H     6-17
                Zero-servo      created at start and stop. Increasing
                Gain            the zero-servo gain increases the
                                strength of the lock. Increasing this
                                too much may induce oscillation.
                Zero-servo      Sets the bandwidth of the zero-servo
                completion      completion output.
                width           Enabled when the zero-servo com-
                                pletion (end) is set for a multi-
                                function output. The zero-servo
                                completion signal is ON when the         0 to
       S1-21                                                                        10        No      No      No      A       A     694H     6-17
                                current position is within the range    16383
                Zero-servo
                                (the zero-servo position + zero-
                Count
                                servo completion width.)
                           Set S1-21 to 4 times of the allow-
                           able displacement pulse amount at
                           the PG.
             Starting      Sets the increase time for the analog
             torque com- input torque compensation signal.
             pensation     Sets the time the torque reference
             increase time needs to reach 300% torque refer-              0
       S1-22               ence.                                         to       500 ms      No      No      No      A       A     695H     6-17
                                                                        5000
                                Enabled when Torque compensation
                Torque incr T
                                is assigned for one of the multi-
                                function analog inputs.
5-52
                                                                                                                                Parameter Tables
                                                                                                                                         (Continued)
             Name                                                                                              Control Methods
                                                                                           Change                                     MEMO-
Param-                                                                                                         Open-           Closed- BUS
                                                                    Setting     Factory    during                      Closed-
 eter                                  Description                                                              loop            loop            Page
            Display                                                 Range       Setting    Opera-       V/f              loop          Regis-
Number                                                                                                         Vector          Vector
                                                                                            tion                        Vector          ter
                                                                                                                  1             (PM)
      Torque com-
      pensation          Sets the torque compensation gain at
      gain during                                             0.500
                         lowering in 0.001 seconds units
S1-23                                                           to               1.000       No         No        No     A       A     696H     6-17
      lowering           when the torque compensation at
                                                              10.000
      TorqComp-          start function is used.
      gain@low
      Torque com-
      pensation bias     Sets the torque compensation bias at -200.0
S1-24 during raising     raising when the torque compensa-      to               0.0%        No         No        No     A       A     697H     6-17
      TorqComp-          tion at start function is used.      +200.0
      Bias@ri
      Torque com-
      pensation bias     Sets the torque compensation bias at
      during lower-                                           -200.0
                         lowering as a percentage when the
S1-25                                                           to               0.0%        No         No        No     A       A     698H     6-17
      ing                torque compensation at start func-
                                                              +200.0
      TorqComp-          tion is used.
      Bias@red
      Dwell speed        Hold speed reference when the load
      reference          is heavy.The frequency reference
                         follows the C1-07 acceleration 4
                         setting time.                                 0.0                                                                      6-17
S1-26                                                                           0.0 Hz       No          A        A      A       A     699H
         DWELL                                                      to 120.0                                                                    6-24
                         Acceleration time will be changed
         speed
                         when the motor speed exceeds the
                         C1-11 setting frequency.
         Door zone
         speed level
                         Sets the door zone speed level.
                       If the motor speed (in CLV and
                                                                                                                                                         5
                       OLV) or the output frequency (in V/
                       f control) falls below S1-27 and a       0.0
S1-27                                                                  0.0 Hz                No          A        A      A       A    69AH      6-17
         Door Zone     multi-function output is set for the to 120.0
         Level         Door zone signal
                       (H2-=42), this output will be
                       closed.
         SE1 Selection 0: SE1 can be reset when stopped.
                       1: SE1 is automatically reset when
S1-28                                                          0 to 2     0                  No          A        A      A       A    69BH      6-18
         SE1 Selection stopped.
                       2: SE1 is not detected at any time.
         Torque limit
                       Sets the time which is used to
         time at stop
S1-31                  reduce the torque limit to 0 after    0 to 1000 0 ms                  No         No        No    No       A    69EH      6-18
         TrqLimit T
                       zero speed.
         @Stop
         Zero-servo    Adjust the strength of the position
         gain 2        control loop at start. Increasing
                       zero-servo gain 2 increases the
S1-33                  strength of the lock. Increasing this 0.00 to
                                                                        0.00                 No         No        No    No       A    6A0H      6-18
  *2                   too much may induce oscillation.        30.00
         ZeroSrvGain2
                       When 0.00 is set or the starting
                       torque compensation is enabled, this
                       function is disabled.
   * 1. The factory settings will change when the control method is changed. V/f control factory settings are given.
   * 2. Applicable for L7-Series Inverters with software versions PRG: 2013 or later.
                                                                                                                                                       5-53
       Slip Compensation: S2
                   Name                                                                                  Control Methods
                                                                                         Change                                 MEMO-
       Param-                                                                                            Open-           Closed- BUS
                                                                     Setting   Factory    during                 Closed-
        eter                                 Description                                                  loop            loop            Page
                   Display                                           Range     Setting   Opera-    V/f             loop          Regis-
       Number                                                                                            Vector          Vector
                                                                                           tion                   Vector          ter
                                                                                                            1             (PM)
             Motor rated                                             300       1380
       S2-01 speed            Sets the motor rated speed.             to                   No      A       No     No      No    6AEH      6-48
                                                                     1800      min-1
             Rated min-1
             Slip compen-
             sation gain in   Sets the slip compensation gain in
             motoring                                                 0.00
                              motoring mode.
       S2-02                                                           to       0.70      Yes      A       A      No      No    6AFH      6-48
             mode             It can be used to improve the level-
                                                                      5.00
             SlipComp         ing accuracy.
             gainMot
             Slip compen-
             sation gain in   Sets the slip compensation gain in
             regenerative                                             0.00
                              regenerative mode.
       S2-03                                                           to       1.00      Yes      A       A      No      No    6B0H      6-48
             mode             It can be used to improve the           5.00
             SlipComp         leveling accuracy.
             gainGen
             Slip compen-
             sation delay                                               0
                              Sets the Slip compensation delay
       S2-07 time                                                      to      200 ms      No      No      A      No      No    6B4H      6-49
                              time.                                  10000
             SlipCompDe-
             lay T
             Slip compen-     0: Disabled.
             sation selec-    1: Enabled.
             tion during      When the slip compensation during
5      S2-15
             regeneration     regeneration function has been acti-
                              vated, as regeneration capacity         0,1        1         No      A       A      No      No    6BCH       -
                              increases momentarily, it may be
                slip comp
                              necessary to use a braking option
                @gene
                              (braking resistor, Braking Resistor
                              Unit or Braking Unit.)
5-54
                                                                                                                        Parameter Tables
                                                                                                                                                 5
                                                                 50.0
         Over Acc Det trips with an over acceleration fault
         Lvl             (DV6).
         Over acceler-
         ation deceler- Sets the time for which an over
         ation time      acceleration must be detected before 0.000 to
S3-17                                                                  0.050 s           No      No      No     No       A    6CDH      6-67
         parameter       the Inverter stops with an over        5.000
         Over Acc Det acceleration fault (DV6).
         Fil
         Over acceler-
                         Selects wether the over acceleration
         ation detec-
                         detection is always active or during
         tion method
S3-18                    run only.                                0,1     0              No      No      No     No       A    6CEH      6-68
         selection
                         0: Detection during power on
         Over Acc Det
                         1: Detection during run only
         Sel
         Distance cal- Sets the conditions for detecting
         culation        overspeed.
                                                                          0
         deceleration 0: Begin watching for overspeed
         time gain           deviation once the speed
                             reference, soft start output
                             (calculated automatically by the
                             Inverter), and motor speed are all
S3-23                        the same.                          0 to 2                   No      No      No     No       A    6D3H       -
                         1: Begin watching for overspeed
         DEV Det             deviation as soon as the speed               2
         Cond Sel            reference and soft start output            (PM)
                             agree.
                         2: Always check to see if an
                             overspeed deviation situation is
                             present.
         Factory-set
S3-25    parameter 1 Factory-set parameter
                                                                0 or 1    0              No      No      No      A       A     6d5H      -
  *      Factory ADJ Do not change this setting.
         1
         Factory-set
S3-26    parameter 2 Factory-set parameter                       0 to
                                                                          0              No      No      No      A       A     6d6H      -
  *      Factory ADJ Do not change this setting.                 9999
         2
* Applicable for L7-Series Inverters with software versions PRG: 2013 or later.
                                                                                                                                               5-55
       Motor Autotuning: T1
                       Name                                                                                               Control Methods
                                                                                                      Change                                     MEMO-
       Param-                                                                                                             Open-           Closed- BUS
                                                                               Setting     Factory     during                     Closed-
        eter                                      Description                                                              loop            loop                      Page
                      Display                                                  Range       Setting    Opera-       V/f              loop          Regis-
       Number                                                                                                             Vector          Vector
                                                                                                        tion                       Vector          ter
                                                                                                                             1             (PM)
                   Autotuning      Sets the autotuning mode.
                   mode selec-   0: Rotational autotuning                       0 to 2       1*
                   tion          1: Stationary autotuning
       T1-01                                                                                            No         Yes       Yes      Yes       Yes      701H        6-82
                                 2: Stationary autotuning for line-to-
                   Tuning Mode                                                   0.4          4
                                    line resistance only                        (PM)        (PM)
                   Sel
                                 4: Encoder offset tuning
                   Motor output
                   power         Sets the output power of the motor            0.00 to     3.70 kW
       T1-02                                                                   650.00         *2
                                                                                                        No         Yes       Yes      Yes       No       702H        6-82
                   Mtr Rated     in kilowatts.
                   Power
                   Motor rated
                                                                              0 to 255.0 190.0 V
       T1-03       voltage       Sets the base voltage of the motor.                                    No         No        Yes      Yes       No       703H        6-82
                                                                                  *3       *3
                   Rated Voltage
                   Motor rated
                   current                                                     1.75 to
                                                                                           14.00 A
       T1-04                     Sets the base current of the motor.            35.00
                                                                                             *2
                                                                                                        No         Yes       Yes      Yes       No       704H        6-82
                   Rated                                                         *4
                   Current
                   Motor rated
                   frequency     Sets the rated frequency of the              0 to 120.0
       T1-05                                                                      *5
                                                                                         60.0 Hz        No         No        Yes      Yes       No       705H        6-82
                   Rated Fre-    motor.
                   quency
                   Number of
                   motor poles
5
                                                                               2 to 48
       T1-06                     Sets the number of motor poles.                poles
                                                                                           4 poles      No         No        Yes      Yes       No       706H        6-82
                   Number of
                   Poles
                   Motor base
                                                                                            1450
       T1-07       speed         Sets the base speed of the motor.            0 to 24000                No         No        Yes      Yes       No       707H        6-82
                                                                                            min-1
                   Rated Speed
                   Number of
                   PG pulses     Sets the number of PG pulses per                          600 PPR
       T1-08                                                                  0 to 60000
                                                                                              *2
                                                                                                        No         No        No       Yes       No       708H        6-82
                   PG Pulses/    revolution.
                   Rev
                   No load cur-
                   rent                                                         0.0 to
                                                                                             4.05
       T1-09                     Sets the no load current of motor.             35.00
                                                                                           (E2-03)
                                                                                                        No         No        Yes      Yes       No       709H        6-82
                   No load cur-                                                   *5
                   rent
          *   1.   Set T1-02 and T1-04 when 2 is set for T1-01. For V/f control a set value 2 is possible only.
          *   2.   The factory settings depend on the Inverter capacity. The values provided are for a 200 V class Inverter for 3.7 kW and when o2-09 is set to 0.
          *   3.   These are values for a 200 V class Inverter. Values for a 400 V class Inverter are double.
          *   4.   The setting range is from 10% to 200% of the Inverter rated output current. The value for a 200 V class Inverter for 0.4 kW is given.
          *   5.   The factory settings depend on the Inverter capacity. The values for a 200 V class Inverter for 3.7 kW are given.
5-56
                                                                                                                                         Parameter Tables
   *   1.   The setting range is from 10% to 200% of the Inverter rated capacity.
   *   2.   The factory settings depend on the Inverter capacity. The values for a 200 V class Inverter for 3.7 kW are given.
   *   3.   These are values for a 200 V class Inverter. Values for a 400 V class Inverter are double.
   *   4.   The setting range is from 10% to 200% of the Inverter rated output current. The value for a 200 V class Inverter for 3.7 kW is given.
                                                                                                                                                                  5-57
        U: Monitor Parameters
                voltage         Monitors the output voltage ref- 10 V: 200 VAC (400 VAC)                     0.1
       U1-06                                                                                                        A       A       A       A      45H
                Output          erence value.                    (0 to +10 V output)                        VAC
                Voltage
                DC bus
                voltage         Monitors the main DC bus volt- 10 V: 400 VDC (800 VDC)
       U1-07                                                                                                1 VDC   A       A       A       A      46H
                DC Bus          age.                           (0 to +10 V output)
                Voltage
                Output
                                                                       10 V: Inverter capacity
                power           Monitors the output power
       U1-08                                                           (max. applicable motor capacity) 0.1 kW      A       A       A       A      47H
                Output          (internally detected value).
                                                                       (0 to  10 V possible)
                kWatts
                Torque
                reference       Monitors the internal torque ref-
                                                                  10 V: Motor rated torque
       U1-09                    erence value for open vector                                                0.1%    No      A       A       A      48H
                Torque          control.                          (0 to  10 V possible)
                Reference
* The unit is set in o1-03 (Frequency units of reference setting and monitor).
5-58
                                                                                                                                      Parameter Tables
U1-11
         Output Term
                                                       contact output 2
                                                       (M3-M4) is ON
                                                    1: Multi-function
                                                                          (Cannot be output.)                   -     A       A      A       A     4AH        5
         Sts                                           contact output 3
                                                       (M5-M6) is ON
                                                    (Always 0)
                                                    1: Error output
                                                       (MA/MB-MC)
                                                       is ON
FLASH ID
                                                                                                                                                            5-59
                                                                                                                                      (Continued)
                       Name                                                                                          Control Methods
                                                                                                                                            MEMO-
       Param-                                                     Output Signal Level at Multi-Func-                 Open-           Closed BUS
                                                                                                       Min.                   Closed
        eter                               Description                   tion Analog Output                           loop            -loop
                   Display                                                                             Unit    V/f             -loop        Regis-
       Number                                                              (AO-option card)                          Vector          Vector
                                                                                                                              Vector         ter
                                                                                                                        1             (PM)
                Terminal A1
                or A1-14B
                                Monitors the input voltage level
                channel 1
                                of the multi-function analog     10 V: 100%
       U1-15    input voltage                                                                          0.1%    A       A      A       A     4EH
                                input A1. A value of 100% cor- (0 to  10 V possible)
                level
                                responds to 10V input.*1
                Term A1
                Level
                AI-14B chan- Monitors the input voltage level
                nel 2 input   of the multi-function analog
       U1-16    voltage level input AI-14B channel 1. A value 10 V/20 mA: 100%                         0.1%    A       A      A       A     4FH
                              of 100% corresponds to 10V/     (0 to 10 V possible)
                AI-14 Ch2
                IptLv1          20mA input.*2
                AI-14B chan- Monitors the input voltage level
                nel 3 input   of the multi-function analog
                voltage level input AI-14B channel 3.         10 V: 100% (10 V)
       U1-17                                                                                           0.1%    A       A      A       A     50H
                AI-14 Ch3     An input of 10 V corresponds to (-10 to 10 V possible)
                IptLv1        100%.*2
                Motor second-
                ary current   Monitors the calculated value of
                              the motor secondary current.     10 V: Motor rated current)
       U1-18    (Iq)                                                                                   0.1%    A       A      A       A     51H
                              The motor rated current corre-   (0 to 10 V output)
                Mot SEC Cur-
                              sponds to 100%.
5
                rent
                Motor excita- Monitors the calculated value of
                tion current  the motor excitation current.
                                                               10 V: Motor rated current)
       U1-19    (Id)          The motor rated current corre-                                           0.1%    No      A      A       A     52H
                                                               (0 to 10 V output)
                Mot EXC cur- sponds to 100%.
                rent
                Frequency       Monitors the frequency refer-
                reference after ence after the soft starter.
                soft-starter    This frequency value does not     10 V: Max. frequency                 0.01
       U1-20                                                                                                   A       A      A       A     53H
                                include compensations, such as    (0 to  10 V possible)                Hz
                SFS Output      slip compensation.
                                The unit is set in o1-03.
                ASR input       Monitors the input to the speed
                                control loop.                     10 V: Max. frequency
       U1-21                                                                                           0.01%   No     No      A       A     54H
                ASR Input       The maximum frequency corre- (0 to  10 V possible)
                                sponds to 100%.
                ASR output      Monitors the output from the
                                                                  10 V: Motor rated secondary
                                speed control loop.
       U1-22                                                      current                              0.01%   No     No      A       A     55H
                ASR output      The motor rated secondary cur-
                                rent corresponds to 100%.         (0 to  10 V possible)
5-60
                                                                                                                                  Parameter Tables
                                                                                                                                         (Continued)
             Name                                                                                                       Control Methods
                                                                                                                                               MEMO-
Param-                                                                Output Signal Level at Multi-Func-                Open-           Closed BUS
                                                                                                           Min.                  Closed
 eter                                Description                             tion Analog Output                          loop            -loop
            Display                                                                                        Unit   V/f             -loop        Regis-
Number                                                                         (AO-option card)                         Vector          Vector
                                                                                                                                 Vector         ter
                                                                                                                           1             (PM)
         Output volt-
         age reference Monitors the Inverter internal
         (Vd)                                            10 V: 200 VAC (400 VAC)                            0.1
U1-27                  voltage reference for motor exci-                                                          No      A      A       A     5AH
                                                         (0 to  10 V possible)                            VAC
         Voltage       tation current control.
         Ref(Vd)
         Software No.
         (CPU)            (Manufacturers CPU software
U1-28                                                                 (Cannot be output.)                   -     A       A      A       A     5BH
                          No.)
         CPU ID
         ACR output
         of q axis        Monitors the current control out- 10 V: 100%
                                                                                                           0.1
U1-32                     put value for the motor second-                                                         No      A      A       A     5FH
         ACR(q)                                             (0 to  10 V possible)                         %
                          ary current.
         Output
         ACR output       Monitors the current control out-
                                                            10 V: 100%                                     0.1
U1-33    of d axis        put value for the motor excita-                                                         No      A      A       A     60H
                                                            (0 to  10 V possible)                         %
         ACR(d) axis      tion current.
                                                                                                                                                          5
U1-35    pulses           zero-servo was activated. The   (Cannot be output.)                               -     No     No      A       A     62H
         Zero-servo       shown value is the actual pulse
         Pulse            number times 4.
         Cooling fan
         operating time Monitors the total operating time                                                   1
U1-40                   of the cooling fan. The time can (Cannot be output.)                                      A       A      A       A     67H
         FAN Elapsed be set in 02-10.                                                                      hr.
         Time
         Heatsink
         Temperature      Monitors the Inverter heatsink
U1-41                                                                 10/100C                             1C    A       A      A       A     68H
         Actual Fin       temperature.
         Temp
         ASR output
         without filter
                     Monitors the output from the       10 V: Rated secondary current of
U1-44                speed control loop (i.e., the pri- motor                            0.01%                    No     No      A       A     6BH
         ASR Out w/o mary filter input value). 100% is
                                                        (-10 to 10 V)
         Fil         displayed for rated secondary
                     current of the motor.
         Feed forward Monitors the output from feed
                                                                      10 V: Rated secondary current of
         control output forward control. 100% is dis-
U1-45                                                                 motor                            0.01%      No     No      A       A     6CH
         FF Cout Out- played for rated secondary cur-
                        rent of the motor.                            (-10 to 10 V)
         put
                                                                                                                                                        5-61
                                                                                                                                             (Continued)
                      Name                                                                                                  Control Methods
                                                                                                                                                   MEMO-
       Param-                                                            Output Signal Level at Multi-Func-                 Open-           Closed BUS
                                                                                                              Min.                   Closed
        eter                                   Description                      tion Analog Output                           loop            -loop
                     Display                                                                                  Unit    V/f             -loop        Regis-
       Number                                                                     (AO-option card)                          Vector          Vector
                                                                                                                                     Vector         ter
                                                                                                                               1             (PM)
                 Slip compen-
                              Monitors the slip compensation
                 sation value                                            10 V: Rated slip of motor
       U1-50                  value.100% is displayed                                                         0.01%   A       A      A      No     71H
                 Slip comp                                               (-10 to 10 V)
                              for rated slip
                 value
                 Max Current
                 during accel-                                           10 V: Rated current of motor
                 eration          Monitors the maximum current
       U1-51                                                             (0 to +10 V, absolute value out-     0.1 A   A       A      A       A     72H
                                  during acceleration.
                 Max Amp                                                 put)
                 at accel
                 Max Current
                 during decel-                                           10 V: Rated current of motor
                 eration          Monitors the maximum current
       U1-52                                                             (0 to +10 V, absolute value out-     0.1 A   A       A      A       A     73H
                                  during deceleration.
                 Max Amp                                                 put)
                 at decel
                 Max Current
                 during Top                                              10 V: Rated current of motor
                 speed            Monitors the maximum current
       U1-53                                                             (0 to +10 V, absolute value out-     0.1 A   A       A      A       A     74H
                                  at top speed.
                 Max Amp                                                 put)
                 at top speed
                 Max Current
5
                 during level-                                           10 V: Rated current of motor
                 ing speed        Monitors the maximum current
       U1-54                                                             (0 to +10 V, absolute value out-     0.1 A   A       A      A       A     75H
                                  at Vl speed.
                 Max Amp                                                 put)
                 at Vl sped
                 Operation        Monitors the elevator operation
       U1-55     counter          counter.                               (Cannot be output.)                  times   A       A      A       A     76H
                 Operation Cnt o2-15 can clear this counter.
                 AI-14B chan- Monitors the input voltage level
                 nel 1 input   of the multi-function analog
                 voltage level input AI-14B channel 1.         10 V: 100% (10 V)
       U1-56                                                                                                  0.1%    A       A      A       A     4FH
                                                               (-10 to 10 V possible)
                 AI-14 Ch1     An input of 10 V corresponds to
                 1ptLv1           100%.*2
                 Car accelera-    Shows the elevator car accelera-
                 tion rate        tion rate value.
                                                                         10V: 9.8 m/s2
       U1-57                      Set the diameter of the traction                                             0.1    No     No      No      A     78H
                                  sheave (S3-13) and the roping          (-10 to 10 V)
                 Cage accel
                                  ratio (S3-14) correctly.
                 q-axis motor
                 current refer-   Monitors the q-axis current ref-
       U1-74     ence                                                    10 V: Motor rated current            0.1%    No     No      No      A     7C6H
                                  erence.
                 Iq Reference
                 d-axis motor
                 current refer-   Monitors the d-axis current ref-
       U1-75     ence                                                    10 V: Motor rated current            0.1%    No     No      No      A     7C7H
                                  erence.
                 Id Reference
             Monitor for
       U1-90 factory setting Monitor for factory setting.                (Cannot be output.)                    -     No     No      A       A     720H
        *3   Factory ADJ
             Mon
5-62
                                                                                                                            Parameter Tables
Fault Trace: U2
      Reference
      frequency at
                         The reference frequency when                                              0.01
U2-03 fault                                                                                                A       A       A       A      82H
                         the last fault occurred.                                                   Hz
         Frequency
         Ref
      Output
      frequency at       The output frequency when the                                             0.01
U2-04 fault                                                                                                A       A       A       A      83H
                         last fault occurred.                                                       Hz
         Output Freq
         Output cur-
         rent at fault   The output current when the last
U2-05                                                                                             0.1 A    A       A       A       A      84H
         Output          fault occurred.
         Current
      Motor speed
                  The motor speed when the last                                                    0.01
U2-06 at fault
                                                                                                                                                     5
                                                                                                           No      A       A       A      85H
                  fault occurred.                                                                   Hz
      Motor Speed
      Output
      voltage refer-
                     The output reference voltage
U2-07 ence at fault                                                                               0.1 V    A       A       A       A      86H
                     when the last fault occurred.
      Output
      Voltage
      DC bus volt-                                           (Cannot be output.)
      age at fault The main current DC voltage
U2-08                                                                                             1 VAC    A       A       A       A      87H
      DC Bus       when the last fault occurred.
         Voltage
      Output
      power at
                         The output power when the last
U2-09 fault                                                                                       0.1 kW   A       A       A       A      88H
                         fault occurred.
         Output
         kWatts
      Torque refer- The reference torque when the
      ence at fault last fault occurred. The motor
U2-10                                                                                             0.1%     No     No       A       A      89H
      Torque        rated torque corresponds to
      Reference     100%.
      Input termi-
      nal status at      The input terminal status when
                         the last fault occurred.
U2-11 fault                                                                                         -      A       A       A       A      8AH
                         The format is the same as for
         Input Term
                         U1-10.
         Sts
      Output termi-
      nal status at The output terminal status when
U2-12 fault         the last fault occurred. The for-                                               -      A       A       A       A      8BH
      Output Term mat is the same as for U1-11.
         Sts
      Operation
      status at fault The operating status when the
U2-13                 last fault occurred. The format is                                            -      A       A       A       A      8CH
      Inverter        the same as for U1-12.
      Status
                                                                                                                                                   5-63
                                                                                                                                        (Continued)
                    Name                                                                                             Control Methods
                                                                                                                                              MEMO-
       Param-                                                     Output Signal Level at Multi-Func-                 Open-            Closed- BUS
                                                                                                       Min.                   Closed-
        eter                               Description                   tion Analog Output                           loop             loop
                   Display                                                                             Unit    V/f             loop           Regis-
       Number                                                              (AO-option card)                          Vector           Vector
                                                                                                                              Vector           ter
                                                                                                                        1              (PM)
             Cumulative
             operation          The operating time when the last                                         1
       U2-14 time at fault                                       (Cannot be output.)                           A       A       A       A      8DH
                                fault occurred.                                                         hr.
                Elapsed Time
             Soft Starter Shows the soft start speed refer-
             Speed Refer- ence when the most recent fault
             ence at Fault occurred. Setting units depend                                              0.01
       U2-15                                                                                                   No     No      No       A      7E0H
                           on parameter o1-03.                                                          Hz
                SFS Output      Displayed in the same way as
                                U1-20.
                q-Axis Cur-     Shows the q-axis current when
                rent at Fault   the most recent fault occurred.
                                Setting units depend on parame-
       U2-16                                                    No output available.                   0.10%   No     No      No       A     7E1H
                q-axis          ter o1-03.
                Current         Displayed in the same way as
                                U1-18.
                d-Axis Cur-     Shows the d-axis current when
                rent at Fault   the most recent fault occurred.
                                Setting units depend on parame-
       U2-17                                                                                           0.10%   No     No      No       A     7E2H
                d-axis          ter o1-03.
                Current         Displayed in the same way as
                                U1-19.
5
                                     The following errors are not recorded in the error log: CPF00, 01, 02, 03, UV1, and UV2.
                 IMPORTANT
5-64
                                                                                                                        Parameter Tables
  Fault History: U3
             Name                                                                                            Control Methods
                                                                                                                                      MEMO-
Param-                                                     Output Signal Level at Multi-Func-                Open-            Closed- BUS
                                                                                                Min.                  Closed-
 eter                              Description                    tion Analog Output                          loop             loop
            Display                                                                             Unit   V/f             loop           Regis-
Number                                                              (AO-option card)                         Vector           Vector
                                                                                                                      Vector           ter
                                                                                                                1              (PM)
         Last fault     The error content of 1st last                                                                                  90H
U3-01                                                                                            -     A       A       A       A
         Last Fault     fault.                                                                                                       (800H)
         Second last
         fault          The error content of 2nd last                                                                                  91H
U3-02                                                                                            -     A       A       A       A
         Fault Mes-     fault.                                                                                                       (801H)
         sage 2
         Third last
         fault          The error content of 3rd last                                                                                  92H
U3-03                                                                                            -     A       A       A       A
         Fault Mes-     fault.                                                                                                       (802H)
         sage 3
         Fourth last
         fault          The error content of 4th last                                                                                  93H
U3-04                                                                                            -     A       A       A       A
         Fault          fault.                                                                                                       (803H)
         Message 4
      Cumulative
      operation
                        The total operating time when                                            1                                     94H
U3-05 time at fault                                                                                    A       A       A       A
                        the 1st previous fault occurred.                                        hr.                                  (80AH)
         Elapsed
         Time 1
      Accumu-
      lated time of
U3-06 second fault
                    The total operating time when
                    the 2nd previous fault occurred.
                                                                                                 1
                                                                                                hr.
                                                                                                       A       A       A       A
                                                                                                                                       95H
                                                                                                                                     (80BH)
                                                                                                                                                 5
      Elapsed                                        (Cannot be output.)
      Time 2
      Accumu-
      lated time of
                    The total operating time when                                                1                                     96H
U3-07 third fault                                                                                      A       A       A       A
                    the 3rd previous fault occurred.                                            hr.                                  (80CH)
      Elapsed
      Time 3
      Accumu-
      lated time of
      fourth/oldest The total operating time when                                                1                                     97H
U3-08 fault                                                                                            A       A       A       A
                    the 4th previous fault occurred.                                            hr.                                  (80DH)
         Elapsed
         Time 4
      Fifth last to                                                                                                                   804H
                                                                                                                                      805H
U3-09 tenth last
      fault             The error content of the 5th to                                                                               806H
 to                                                                                                   A       A       A       A
                        10th last fault                                                                                               807H
U3-14 Fault Mes-
                                                                                                                                      808H
         sage 5 to 10                                                                                                                 809H
      Accumu-
                                                                                                                                      806H
      lated time of                                                                                                                   80FH
U3-15 fifth to tenth Total generating time when 5th...
                                                                                                                                      810H
 to   fault                                                                                     1hr    A       A       A       A
                     10th previous fault occurred                                                                                     811H
U3-20
      Elapsed                                                                                                                         812H
                                                                                                                                      813H
      Time 5 to 10
                            The following errors are not recorded in the error log: CPF00, 01, 02, 03, UV1, and UV2.
          IMPORTANT
                                                                                                                                               5-65
        Factory Settings that Change with the Control Method (A1-02)
5           C5-09
                       ASR proportional (P) gain 3
                       ASR P Gain 3
                                                        0.00 to 300.00       -           -         40.00          3.00
5-66
                                                                                                                                         Parameter Tables
                                                                                                                                                (Continued)
                                Name                                                                Control Methods
Parameter                                                                                                                     Closed-loop
                                                           Setting Range                       Open-loop      Closed-loop                         Remarks
 Number                        Display                                             V/f                                           Vector
                                                                                                Vector 1         Vector
                                                                                                                                  (PM)
              PG parameter                                   0 to 60000             -                -             600               -
  F1-01
              PG Pulses/Rev                                   0 to 8192              -               -               -            8192
              Operation selection at speed devia-
              tion
  F1-04                                                         0 to 3              -                -              3               1
              PG
              Deviation Sel
              PG rotation
  F1-05                                                          0, 1               -                -              0               1
              PG Rotation Sel
              Channel 1 monitor selection
  F4-01                                                        1 to 99              2               2               2               5
              AO Ch1 Select
              Motor protection selection                        0 to 3              1               1               1                -
  L1-01
              MOL Fault Select                                   0, 5               -                -               -              5
              Speed agreement detection width                0.0 to 20.0         2.0 Hz          2.0 Hz          2.0 Hz              -
  L4-02
              Spd Agree Width                                0.0 to 40.0             -               -               -            4.0%
              Speed agreement detection width
                                                             0.0 to 20.0         2.0 Hz          2.0 Hz          2.0 Hz              -
  L4-04       (+/-)
              Spd Agree Wdth+-                               0.0 to 40.0            -                -               -            4.0%
              Frequency units of reference setting
  o1-03       and monitor                                    0 to 39999             0               0               0               1
              Display Scaling
              Setting unit for frequency parame-
                                                                                                                                                                      5
  o1-04       ters related to V/f characteristics                0, 1               -                -              0               1
              Display Units
              Zero speed level at stop
  S1-01                                                      0.0 to 10.0         1.2 Hz          0.5 Hz          0.1 Hz          0.5 Hz
              ZeroSpeed@stop
* 1. These are values for a 200 V class Inverter. Values for a 400 V class Inverter are double. (Setting ranges, factory settings)
* 2. These values will change depending on o2-09, Inverter capacity, and the V/f pattern (E1-03). The values provided here are for a 200 V class, 3.7 kW
     Inverter when o2-09 is set to zero (factory setting), and E1-03 is set to F (factory setting). Refer to page 5-68, Parameters that change with V/f patterns.
* 3. The setting values will change depending on o2-09. The values provided are for when o2-09 is set to 0 (factory setting.) Refer to page 5-68, Parameters
     that change with V/f patterns.
* 4. The factory settings depend on the Inverter capacity. The values for a 200 V class Inverter for 3.7 kW are given.
                                                                                                                                                                    5-67
        Parameters that change with V/f patterns
5-68
                                                                                                                          Parameter Tables
                                                                                                                                                  5-69
           Inverter capacity: 200 V 55 kW
       Param-
        eter          Name            Unit                                       Factory Setting                                        Open- Closed-
       Number                                                                                                                            loop    loop
                                                                                                                                       Vector 1 Vector
                    V/f pattern                                                                                                        Control Control
       E1-03                          Hz      0    1     2     3     4     5     6     7      8    9     A     B     C     D     F
                    selection
                Max. output fre-
       E1-04                          Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 90.0 120.0 60.0                    60.0    60.0
                quency (FMAX)
                Max. output voltage
       E1-05                           V 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0        230.0
                (VMAX)
       E1-06    Base frequency (FA)   Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 60.0                     60.0    60.0
                Mid. output fre-
       E1-07                          Hz     2.5   3.0   3.0   3.0 25.0 25.0 30.0 30.0 2.5         2.5   3.0   3.0   3.0   3.0   3.0     3.0     0.0
                quency (FB)
                Mid. output fre-
       E1-08                           V     13.8 13.8 13.8 13.8 40.2 57.5 40.2 57.5 17.2 23.0 17.2 23.0 13.8 13.8 13.8                 12.6     0.0
                quency voltage (VB)
                Min. output fre-
       E1-09                          Hz     1.3   1.5   1.5   1.5   1.3   1.3   1.5   1.5   1.3   1.3   1.5   1.5   1.5   1.5   1.5     0.5     0.0
                quency (FMIN)
                Min. output fre-
       E1-10    quency voltage         V     6.9   6.9   6.9   6.9   5.7   6.9   5.7   6.9   8.0 10.3 8.0 12.6 6.9         6.9   6.9     2.3     0.0
                (VMIN)
       E1-06    Base frequency (FA)   Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 60.0                     60.0    60.0
                Mid. output fre-
       E1-07                          Hz     2.5   3.0   3.0   3.0 25.0 25.0 30.0 30.0 2.5         2.5   3.0   3.0   3.0   3.0   3.0     3.0     0.0
                quency (FB)
                Mid. output fre-
       E1-08                           V     32.2 32.2 32.2 32.2 80.5 115.0 80.5 115.0 41.4 52.9 41.4 52.9 32.2 32.2 32.2               25.3     0.0
                quency voltage (VB)
                Min. output fre-
       E1-09                          Hz     1.3   1.5   1.5   1.5   1.3   1.3   1.5   1.5   1.3   1.3   1.5   1.5   1.5   1.5   1.5     0.5     0.0
                quency (FMIN)
                Min. output fre-
       E1-10    quency voltage         V     16.1 16.1 16.1 16.1 13.8 16.1 13.8 16.1 20.7 25.3 20.7 29.9 16.1 16.1 16.1                  4.6     0.0
                (VMIN)
5-70
                                                                                                                          Parameter Tables
                                                                                                                                                    5
             selection
         Max. output fre-
E1-04                          Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 90.0 120.0 50.0                    50.0    50.0
         quency (FMAX)
         Max. output voltage
E1-05                           V 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 190.0 190.0        190.0
         (VMAX)
E1-06    Base frequency (FA)   Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 50.0                     50.0    50.0
         Mid. output fre-
E1-07                          Hz     2.5   3.0   3.0   3.0 25.0 25.0 30.0 30.0 2.5         2.5   3.0   3.0   3.0   3.0   3.0     3.0     0.0
         quency (FB)
         Mid. output fre-
E1-08    quency                 V     12.0 12.0 12.0 12.0 35.0 50.0 35.0 50.0 15.0 20.0 15.0 20.0 12.0 12.0 16.0                 12.5     0.0
      voltage (VB)
      Min. output fre-
E1-09                          Hz     1.3   1.5   1.5   1.5   1.3   1.3   1.5   1.5   1.3   1.3   1.5   1.5   1.5   1.5   0.5     0.3     0.0
      quency (FMIN)
      Min. output fre-
E1-10 quency voltage            V     6.0   6.0   6.0   6.0   5.0   6.0   5.0   6.0   7.0   9.0   7.0 11.0 6.0      6.0   8.3     2.5     0.0
      (VMIN)
                                                                                                                                                  5-71
           Inverter capacity: 400 V 55 kW
       Param-
        eter          Name            Unit                                       Factory Setting                                        Open- Closed-
       Number                                                                                                                            loop    loop
                                                                                                                                       Vector 1 Vector
                    V/f pattern                                                                                                        Control Control
       E1-03                          Hz      0    1     2     3     4     5     6     7      8    9     A     B     C     D     F
                    selection
                Max. output fre-
       E1-04                          Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 90.0 120.0 50.0                    50.0    50.0
                quency (FMAX)
                Max. output voltage
       E1-05                           V 400.0 400.0 400.0 400.0 400.0 400.0 400.0 400.0 400.0 400.0 400.0 400.0 400.0 400.0 380.0 380.0        380.0
                (VMAX)
       E1-06    Base frequency (FA)   Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 50.0                     50.0    50.0
                Mid. output fre-
       E1-07                          Hz     2.5   3.0   3.0   3.0 25.0 25.0 30.0 30.0 2.5         2.5   3.0   3.0   3.0   3.0   3.0     3.0     0.0
                quency (FB)
                Mid. output fre-
       E1-08                           V     24.0 24.0 24.0 24.0 70.0 100.0 70.0 100.0 30.0 40.0 30.0 40.0 24.0 24.0 32.0               25.0     0.0
                quency voltage (VB)
                Min. output fre-
       E1-09                          Hz     1.3   1.5   1.5   1.5   1.3   1.3   1.5   1.5   1.3   1.3   1.5   1.5   1.5   1.5   0.5     0.3     0.0
                quency (FMIN)
                Min. output fre-
       E1-10    quency voltage         V     12.0 12.0 12.0 12.0 10.0 12.0 10.0 12.0 14.0 18.0 14.0 22.0 12.0 12.0 16.6                  5.0     0.0
                (VMIN)
5-72
                                                                                                                   Parameter Tables
      E5-09
                 Q-axis inductance
                                                               1251
                                                                             24.5
                                                                             1305
                                                                                            14.6
                                                                                            797
                                                                                                             9.9
                                                                                                            835
                                                                                                                            9.9
                                                                                                                           835
                                                                                                                                        5
      L8-02      Overheat pre-alarm level           C          75            73             75              80             65
      N5-02      Motor acceleration time             s         0.121        0.081           0.075           0.082          0.099
     Parameter
                               Name                Unit                              Factory Setting
      Number
         -       Inverter Capacity                 kW         18.5      22           30              37            45        55
      o2-04      kVA selection                       -         9        A            B               C              D        E
      C6-02      Carrier frequency selection         -         3        3            3               2              2           2
      E1-04      Max. output frequency (FMAX)      min-1      168      168          168             168            168       168
      E1-06      Base frequency (FA)                     -1   168      168          168             168            168       168
                                                   min
      E2-01      Motor rated current                A         65.8     77.2         105.0           131.0         160.0     190.0
      E2-02      Motor rated slip                   Hz        1.67     1.70         1.80            1.33           1.60     1.43
      E2-03      Motor no-load current              A         15.7     18.5         21.9            38.2           44.0     45.6
      E2-05      Motor line-to-line resistance      W         0.101    0.079        0.064           0.039         0.030     0.022
      E2-06      Motor leak inductance              %         20.1     19.5         20.8            18.8           20.2     20.5
                 Motor iron loss for torque com-
      E2-10                                         W         505      538          699             823            852       960
                 pensation
      E5-03      Motor rated current                A         29.6     35.2         48.0            59.2           72.0     88.0
      E5-05      Motor line-to-line resistance      W         0.46     0.36         0.27            0.18           0.15     0.11
      E5-06      D-axis inductance                 mH         5.67     4.84         3.68            2.59           2.57     2.05
      E5-07      Q-axis inductance                 MH          8.0     6.83         5.36            3.78           3.73     2.97
                                                    mV
      E5-09      Motor voltage parameter                      835      835          835             835            835       835
                                                   s/red
      L8-02      Overheat pre-alarm level           C         75       75           70              85            90        80
      N5-02      Motor acceleration time             s        0.098    0.096        0.126           0.124        0.188      0.186
                                                                                                                                      5-73
       400 V Class Inverters
          Parameter
                                    Name                Unit                               Factory Setting
           Number
              -       Inverter Capacity                 kW          18.5           22              30              37            45
           o2-04      kVA selection                       -           9             A              B               C             D
           E1-04      Carrier frequency selection             -1     96            96             168             168           168
                                                        min
           E1-06      Max. output frequency (FMAX)      min-1        96            96             168             168           168
           E2-02      Base frequency (FA)                Hz         2.70           2.70           1.50            1.30          1.70
           E2-03      Motor rated current                A          2.30           2.30           2.60            4.00           5.6
           E2-05      Motor rated slip                   W          3.333        3.333            1.595           1.152         0.922
           E2-06      Motor no-load current              %          19.3           19.3           18.2            15.5          19.6
           E2-10      Motor line-to-line resistance      W           130           130            193             263           385
           E5-03      Motor leak inductance              A          3.50           3.50           5.50            7.25          10.5
                      Motor iron loss for torque com-
           E5-05                                         W          15.44        15.44            5.88            6.24          2.52
                      pensation
           E5-06      Motor rated current               mH          120.8        120.8            68.4            48.0          28.0
           E5-07      Motor line-to-line resistance     MH           144           144             98             58.4          39.6
                                                         mV
           E5-09      D-axis inductance                             2502          2502            2610            1594          1670
                                                        s/red
           L8-02      Q-axis inductance                  C          90            90              85              90            73
           N5-02      Motor voltage parameter             s         0.121         0.081           0.081           0.075         0.082
5         Parameter
           Number
              -
                                    Name
                      Inverter Capacity
                                                        Unit
                                                        kW         18.5      22
                                                                                           Factory Setting
                                                                                           30              37            45       55
           o2-04      kVA selection                       -         9        A             B               C              D       E
           C6-02      Carrier frequency selection         -         3        3             3               2              2        2
           E1-04      Max. output frequency (FMAX)      min-1      168      168           168             168           168
           E1-06      Base frequency (FA)               min-1      168      168           168             168           168
           E2-01      Motor rated current                A         32.9     38.6          52.3            65.6          79.7     95.0
           E2-02      Motor rated slip                   Hz        1.67     1.70          1.80            1.33          1.60     1.46
           E2-03      Motor no-load current              A          7.8      9.2          10.9            19.1          22.0     24.0
           E2-05      Motor line-to-line resistance      W         0.403    0.316         0.269           0.155         0.122    0.088
           E2-06      Motor leak inductance              %         20.1     23.5          20.7            18.8          19.9     20.0
                      Motor iron loss for torque com-
           E2-10                                         W         508      586           750             925           1125     1260
                      pensation
           E5-03      Motor rated current                A         14.8     17.6          24.0            29.6          36.0     44.0
           E5-05      Motor line-to-line resistance      W         1.84     1.44          1.08            0.72          0.60     0.44
           E5-06      D-axis inductance                 mH         22.7     19.4          14.7            10.4          10.3      8.2
           E5-07      Q-axis inductance                 MH          32      27.3          21.4            15.1          14.9     11.9
                                                         mV
           E5-09      Motor voltage parameter                      1670     1670          1670            1670          1670     1670
                                                        s/red
           L8-02      Overheat pre-alarm level           C         80       80            72              80            82       73
           N5-02      Motor acceleration time             s        0.098    0.096         0.126           0.124         0.188    0.186
5-74
                                                                  6
Parameter Settings by
            Function
     Carrier Frequency Derating and Current Limitation ...........6-2
     EN81-1 Compliance...........................................................6-4
     Control/Brake Sequence....................................................6-6
     Acceleration and Deceleration Characteristics ................6-23
     Adjusting Analog Input Signals ........................................6-30
     Speed Detection and Speed Limitation............................6-32
     Improving the Operation Performance.............................6-35
     Protective Functions ........................................................6-52
     Inverter Protection............................................................6-64
     Input Terminal Functions .................................................6-69
     Output Terminal Functions...............................................6-73
     Motor and V/f Pattern Setup ............................................6-77
     Digital Operator/LED Monitor Functions ..........................6-85
     PG Option Cards..............................................................6-97
     Emergency Operation ....................................................6-101
     Automatic Fault Reset....................................................6-105
     MEMOBUS Communications.........................................6-107
      Carrier Frequency Derating and
      Current Limitation
        Related Parameters
                             Name                                                                                                  Control Methods
                                                                                                            Change                                         MEMO-
              Param-                                                                                                               Open-            Closed- BUS
                                                                                     Setting     Factory    during                          Closed-
               eter                                     Description                                                                 loop             loop
                             Display                                                 Range       Setting    Opera-       V/f                 loop           Regis-
              Number                                                                                                               Vector           Vector
                                                                                                             tion                           Vector           ter
                                                                                                                                      1              (PM)
                         Carrier           Selects the carrier frequency.
                         frequency         1: 2 kHz
                         selection         2: 5 kHz
                                                                                                   3
               C6-02                       3: 8 kHz                                   1 to 6                  No          A          A       A       No    224H
                                                                                                   *3
                         CarrierFreq       4: 10 kHz
                         Sel               5: 12.5 kHz
                                           6: 15 kHz
                     Carrier               Set the carrier frequency upper
                     frequency             limit and lower limit in kHz units.        2.0 to      8.0
               C6-03 upper limit           With the vector control method, the         15.0       kHz         No          A          A       A       No    225H
                         CarrierFreq       upper limit of the carrier frequency       *1 *2        *3
                         Max               is fixed in C6-03.
                     Carrier
                     frequency             1: 2 kHz 2: 4 kHz 3: 6 kHz                              4
               C6-11 selection 2                                                      1 to 6                  No         No          No      No      A     22DH
                                           4: 8 kHz 5: 12 kHz 6: 15 kHz                            *3
6 CarrierFreq Sel
6-2
                                                                          Carrier Frequency Derating and Current Limitation
75%
                                         200 V Class 30 to 55 kW
                                         400 V Class 30 to 55 kW
                                                                                             Carrier
                                                                                             frequency
                                 0
                                     2           5          8      10             15         (kHz)
200 V Class 11 kW
                       If the torque at low frequencies is too low, check whether the current runs into the limitation explained
                        above. If so, check the motor data settings (E2-) and the V/f pattern (E1-).
                       If the current still runs into the limit it might be necessary to install a one size bigger Inverter.
    IMPORTANT          For selecting an Inverter please consider the low frequency current limit as described above and select
                        an Inverter with an appropriate current margin.
                                                                                                                                    6-3
      EN81-1 Compliance
       EN81-1 Conform Wiring with One Motor Magnetic Contactor
         In order to use the L7B with one motor magnetic contactor instead of two while keeping compliance to the
         EN81-1:1998, the following rules have to be followed:
           The hardware baseblock function using the terminals BB and BB1 must be used to enable/disable the
            Inverter.
           If the elevator safety chain is opened, the Inverter output must be cut. This means that the baseblock sig-
            nals at the terminals BB and BB1 must be opened, e.g. via an interposing relay.
           The baseblock monitor function must be programmed for one of the multi-function outputs (H2- = 46/
            47). The regarding multi-function contact must be implemented in the magnetic contactor supervision cir-
            cuit of the controller in order to prevent a restart in case of an Inverter baseblock or motor magnetic con-
            tactor malfunction.
           All magnetic contactors must be conform to the EN81-1:1998.
         Fig 6.3 shows an EN81-1:1998 wiring example.
                           Safety Chain
                              Circuit
                                                                    Lift Controller
                                                     Magnetic                                    Magnetic
                                                  Contactor Close                             Contactor Check
                                                    Command                                 (Restart Permission)
                                                       K01
                                                                    24VDC *1
6
                                          K1
                                                                               BB Monitor
                                                                                    (NC)
                                                               Yaskawa
                                                             CIMR-L7Bxxx
K2
                                                                         M
                        Fig 6.3 EN81-1 Conform Wiring with One Motor Magnetic Contactor (Example)
         The wiring rules and the wiring example are approved by the TUEV Sued, Germany. For more details please
         contact your Yaskawa sales representative.
6-4
                                                                                               EN81-1 Compliance
    If a multi-function output is programmed for this function, the output is switched if both baseblock inputs (BB
    and BB1) are enabled.
               Up/Down command
                  Baseblock Input
                  (Term BB and BB1)
                      BB Monitor 1
                      BB Monitor 2
                                                                                                                       6-5
      Control/Brake Sequence
       Travel stop
         The Inverter can be stopped as follows:
           The direction command (UP or Down) signal is removed.
           The speed reference selection signal is removed.
           If d1-18 is set to 3 and all speed inputs are removed
        Related Parameters
                       Name                                                                             Control Methods
                                                                                        Change                                  MEMO-
            Param-                                                                                      Open-            Closed- BUS
                                                                    Setting   Factory   during                   Closed-
             eter                         Description                                                    loop             loop
                      Display                                       Range     Setting   Opera-    V/f             loop           Regis-
            Number                                                                                      Vector           Vector
                                                                                         tion                    Vector           ter
                                                                                                           1              (PM)
                   Run Com-    Sets the Run Command input
                   mand source method.
                   selection   0: Digital Operator
             b1-02             1: Control circuit terminal          0 to 3      1        No        A      A       A       A     181H
                                  (sequence input)
                   Run Source
                               2: MEMOBUS communications
                               3: Option card
6-6
                                                                                                                                 Control/Brake Sequence
  Related Parameters
                        Name                                                                                                 Control Methods
                                                                                                         Change                                      MEMO-
         Param-                                                                                                              Open-            Closed- BUS
                                                                                  Setting    Factory     during                       Closed-
          eter                                      Description                                                               loop             loop Regis-
                       Display                                                    Range      Setting     Opera-       V/f              loop
         Number                                                                                                              Vector           Vector
                                                                                                          tion                        Vector           ter
                                                                                                                                1              (PM)
                   Reference         Sets the frequency reference input
                   source            method.
                   selection         0: Digital Operator
          b1-01                      1: Control circuit terminal (analog          0 to 3         0         No          A         A            A   A   180H
                   Reference            input)*1
                   Source            2: MEMOBUS communications
                                     3: Option card*2
    * 1. If d1-18 is set to 1 or 2, an analog reference will have priority over a frequency reference from a multi-function contact input.
    * 2. If d1-18 is set to 1 or 2, a frequency reference from a multi-function contact input will be valid even if b1-01 is set to 2 or 3.
                                                                                                                                                              6
  Input the Speed Reference from the Multi-function Contact Inputs (b1-01=0)
    When b1-01 is set to 0 the speed reference can be selected from preset speeds using the multi-function contact
    inputs of the Inverter. Refer to page 6-8, Speed Selection Sequence Using Multi-function Contact Inputs for
    details.
                                                                                                                                                             6-7
       Speed Selection Sequence Using Multi-function Contact Inputs
          If the multi-function contact inputs are used for speed selection, the speed selection method and the speed pri-
          ority depends on the setting of parameter d1-18.
                                 Name                                                                                                Control Methods
                                                                                                               Change                                       MEMO-
                   Param-                                                                                                            Open-           Closed- BUS
                                                                                        Setting    Factory     during                        Closed-
                    eter                                   Description                                                                loop            loop
                                Display                                                 Range      Setting     Opera-          V/f             loop          Regis-
                   Number                                                                                                            Vector          Vector
                                                                                                                tion                          Vector          ter
                                                                                                                                        1             (PM)
                             Speed prior-     Speed reference priority selection
                             ity selection
                                      0: Use multi-speed reference
                                         (d1-01 to d1-08)
                   d1-18                                                    0 to 2                      0        No            A       A        A        A       2A7H
                         SpeedPriori- 1: High speed reference has priority.
                         tySel        2: Leveling speed reference has
                                         priority.
         Related Parameters
                                                                                                                         Control Methods
                                                                                               Change                    Open-            Closed-          MEMO-
          Parame-                                                    Setting      Factory                                         Closed-
                                          Name                                                 during                     loop             loop             BUS
           ter No.                                                   Range        Setting                      V/f                 loop
                                                                                              Operation                  Vector           Vector           Register
                                                                                                                                  Vector
                                                                                                                            1              (PM)
                                                                      0 to
          d1-01 to                                                                0.00 Hz                      A           A            A           A        280H to
                             Sets the frequency reference            120.00                       Yes
           d1-08                                                                     *3                        *4          *4           *4          *4        287H
                                                                     *1 *2
6
          *   1.   The maximum setting value depends on the setting of the maximum output frequency (E1-04).
          *   2.   The setting range becomes 0.00 to 100.00 when using closed-loop vector control (PM).
          *   3.   The factory setting changes to 0.00% when using closed-loop vector control (PM).
          *   4.   d1-01 to d1-08 are not displayed if d1-18 is set to 1 or 2. These are changed to H1-01 (80), H1-02 (84), H1-03 (81), H1-04 (83), and H1-05 (F).
                                        Parameter
                    Terminal                                Set Value                                                Details
                                         Number
                        S4                H1-02                  3             Multi-step speed command 1
                        S5                   H1-03               4             Multi-step speed command 2
                        S6                   H1-04               5             Multi-step speed command 3
         Setting Notes
          To set up a 3 step speed sequence using the analog input terminals, follow the directions below.
          Speed Step 1
          If using analog input terminal A1 to enter the first speed in the sequence, set b1-01 to 1. If using d1-01 (Fre-
          quency reference 1) to supply the first speed in the sequence, set b1-01 to 0.
          Speed Step 2
          Enter the second speed in the sequence to analog input terminal A1-14B CH2 by setting H3-09 to 2 (Auxiliary
          frequency reference 1).
6-8
                                                                                                                              Control/Brake Sequence
  Speed Step 3
  Enter the third speed in the sequence to analog input terminal A1-14B CH3 by setting H3-05 to 3 (Auxiliary
  frequency reference 2).
 Related Parameters
                                                                                                                                                               6
                                                                                                                 Control Methods
                                                                                       Change                    Open-            Closed-          MEMO-
  Parame-                                                    Setting      Factory                                         Closed-
                                 Name                                                  during                     loop             loop             BUS
   ter No.                                                   Range        Setting                      V/f                 loop
                                                                                      Operation                  Vector           Vector           Register
                                                                                                                          Vector
                                                                                                                    1              (PM)
                                                               0 to
  d1-02 to          Multi-Step speed 2 to 8 reference                     0.00 Hz                      A           A           A          A         281H to
                                                             120.00                       Yes
   d1-08                         value                                       *3                        *4          *4          *4         *4         287H
                                                              *1 *2
  *   1.   The maximum setting value depends on the setting of the maximum output frequency (E1-04).
  *   2.   The setting range becomes 0.00 to 100.00 when using closed-loop vector control (PM).
  *   3.   The factory setting changes to 0.00% when using closed-loop vector control (PM).
  *   4.   d1-01 to d1-08 are not displayed if d1-18 is set to 1 or 2. These are changed to H1-01 (80), H1-02 (84), H1-03 (81), H1-04 (83), and H1-05 (F).
                               Parameter
            Terminal                                Set Value                                                Details
                                Number
                   S4            H1-02                   3             Multi-step speed command 1
                   S5             H1-03                  4             Multi-step speed command 2
                   S6             H1-04                  5             Multi-step speed command 3
                                                                                                                                                              6-9
                                Multi-step Speed Multi-step Speed Multi-step Speed
                   Speed                                                                                              Selected Frequency
                                 Command 1        Command 2        Command 3
        Related Parameters
                               Name                                                                                              Control Methods
                                                                                                             Change                                     MEMO-
                  Param-                                                                                                         Open-           Closed- BUS
                                                                                       Setting    Factory    during                      Closed-
                   eter                                   Description                                                             loop            loop
                              Display                                                  Range      Setting    Opera-       V/f              loop          Regis-
                  Number                                                                                                         Vector          Vector
                                                                                                              tion                        Vector          ter
                                                                                                                                    1             (PM)
                           Nominal
                           speed           Sets the frequency reference when                     50.00 Hz
                                           the nominal speed is selected by a                                             Q         Q        Q         Q
                  d1-09    reference                                                                           Yes                                           288H
                                                                            *6
                                                                                                                          *4        *4       *4        *4
                           Nomin Speed     multi-function contact input.                         100.00%
                           vn                                                                     (PM)
                           Intermediate
                           speed 1         Sets the frequency reference when
                                                                                                                          A         A        A         A
         *   1.   The maximum setting value depends on the setting of the maximum output frequency (E1-04).
         *   2.   The setting range becomes 0.00 to 100.00 when using closed-loop vector control (PM).
         *   3.   The factory setting changes to 0.00% when using closed-loop vector control (PM).
         *   4.   d1-09 to d1-13 are not displayed if d1-18 is set to 0. These are changed to H1-01 (24), H1-02 (14), H1-03 (3), H1-04 (4), and H1-05 (6).
         *   5.   Becomes the jog frequency reference when d1-18 is set to 0.
         *   6.   Enabled by the combined selection of the nominal speed command, the intermediate speed command, and the releveling speed command.
6-10
                                                                                                              Control/Brake Sequence
Higher Speed has Priority and a Leveling Speed Input is Selected (H1-=83)
 If d1-18 is set to 1 and one multi-function contact input is set to leveling speed selection (H1-=83), the
 Inverter decelerates to the leveling speed (d1-17) when the selected speed signal is removed. The selected
 travel speed must be different from leveling speed and inspection speed. The higher speed has priority over the
 leveling speed, i.e. as long as a higher speed is selected, the leveling signal is disregarded (see the fig. below)
 The Inverter stops when the leveling signal or the Up/Down signal is removed.
                           DC Injection/                                                                      DC Injection/
                            zero-servo                                                                         zero-servo
       Speed
   Hardware BB
     Up/Donw
 The following speed selection table shows the different speeds and the according multi-function contact
 inputs.
                                                      Nominal Intermed. Intermed. Intermed. Relevel.            Leveling
               Terminal function                       Speed   Speed 1 Speed 2 Speed 3       Speed               Speed         0Hz
Higher Speed Priority is Selected and a Leveling Speed Input is Not Selected (H1-)
 When the leveling speed command is not selected for any multi-function contact input, the Inverter deceler-
 ates to the leveling speed (d1-17) when the selected speed signal is removed. The selected travel speed must
 be different from leveling and inspection speed.
 The Inverter stops when the direction signal Up/Down is removed.
 When no speed selection input is set the leveling speed is taken as the speed reference.
                           DC Injection/                                                                       DC Injection/
                            zero-servo                                                                          zero-servo
       Speed
   Hardware BB
     Up/Down
  Selected speed
                                                                                                                                       6-11
         The following speed selection table shows the different speeds and the according multi-function contact
         inputs.
                                                                        Nominal      Intermed. Intermed. Intermed.               Relevel.       Leveling
                             Terminal function                           Speed        Speed 1 Speed 2 Speed 3                     Speed          Speed
                                                                         d1-09         d1-10     d1-11     d1-12                  d1-13          d1-17
          Nominal Speed command (H1-=80)                                 1              0         1         0                     0              0
          Intermediate speed command (H1-=81)                             0             1              1             1              0            0
          Releveling speed command (H1-=82)                               0             0              1             1              1            0
          Leveling speed command (H1-=83)                                N/A           N/A           N/A            N/A           N/A           N/A
The Inverter stops when the direction signal (UP or DOWN signal) is removed.
        Leveling Speed has Priority and a Leveling Speed Input is Selected (H1-=83)
         If d1-18 is set to 2 and one multi-function contact input is set to leveling speed (H1-=83) the Inverter
         decelerates to the leveling speed (d1-17) when the leveling speed selection input is activated. The leveling sig-
         nal has priority over the selected speed, i.e. the selected speed is disregarded. The selected travel speed must
         be different from leveling speed and inspection speed.
         The Inverter stops when the leveling speed command is removed.
                                     DC Injection/                                                                               DC Injection/
                                      zero-servo                                                                                  zero-servo
                Speed
6
             Hardware BB
              Up/Down
           Leveling speed                                                                                           Leveling speed has priority
          Selected speed*
* Indicates the speed selected from the Nominal speed reference, Intermediate speed reference, and the Releveling speed reference.
         The following speed selection table shows the different speeds and the according multi-function contact
         inputs.
                                                                   Nominal Intermed. Intermed. Intermed. Relevel.                     Leveling
                           Terminal function                        Speed   Speed 1 Speed 2 Speed 3       Speed                        Speed
                                                                    d1-09    d1-10     d1-11     d1-12    d1-13                        d1-17
           Nominal Speed command (H1-=80)                           1         0         1         0       0                            0
           Intermediate speed command (H1-=81)                       0            1             1             1            0             0
           Releveling speed command (H1-=82)                         0            0             1             1            1             0
           Leveling speed command (H1-=83)                           X            X             X            X             X             1
6-12
                                                                                                                               Control/Brake Sequence
  Leveling Speed Priority is Selected and a Nominal Speed Input is Not Selected (H1-)
    If d1-18 is set to 2 and no multi-function contact input is set to nominal speed selection, the speed reference
    with speed selection input set is nominal speed (d1-09). When the leveling speed signal is set, the Inverter
    starts to decelerate to the leveling speed. The leveling speed signal has priority over all other speed signals, i.e.
    the intermediate speed 1 and 2 and the releveling signals are disregarded when leveling speed is selected.
    The Inverter can be stopped by removing the leveling speed signal or the Up/Down command.
    CAUTION: This sequence can be risky if e.g. the speed selection doesnt work for any reason (broken wire
    etc.).
                                 DC Injection/                                                                                     DC Injection/
                                  zero-servo                                                                                        zero-servo
           Speed
      Hardware BB
         Up/Down
    Leveling speed
    The following speed selection table shows the different speeds and the according multi-function contact
    inputs.
                                                                   Nominal        Intermed.      Intermed.      Intermed.       Relevel.        Leveling
                        Terminal function                           Speed          Speed 1        Speed 2        Speed 3         Speed           Speed
                                                                    d1-09           d1-10          d1-11          d1-12          d1-13           d1-17
      Nominal Speed command (H1-=80)                               N/A             N/A            N/A            N/A            N/A             N/A
      Intermediate speed command (H1-=81)                             0              1                             1              0              X
      Releveling speed command (H1-=82)                               0              0                             1              1              X
      Leveling speed command (H1-=83)                                 0              0                             0              0              1
  Related parameters
                       Name                                                                                                 Control Methods
                                                                                                       Change                                       MEMO-
       Param-                                                                                                               Open-            Closed- BUS
                                                                                Setting     Factory    during                        Closed-
        eter                                      Description                                                                loop             loop
                      Display                                                   Range       Setting    Opera-        V/f              loop           Regis-
       Number                                                                                                               Vector           Vector
                                                                                                        tion                         Vector           ter
                                                                                                                               1              (PM)
                  Fast stop
                  time              Sets the deceleration time when the         0.00 to
        C1-09                       frequency reference is below the            600.00      3.00 s        No         A         A         A         A       208H
                  Fast Stop         value set in C1-11.                            *
                  Time
      * The setting ranges for acceleration/deceleration times depend on the setting of C1-10 (Accel/decel time setting unit). If C1-10 is set to 1, the setting
        range for acceleration/deceleration times becomes 0.0 to 6000.0 seconds.
                                                                                                                                                                   6-13
        Multi-function Contact Inputs (H1-01 to H1-05)
                                                                                                                          Control Methods
                                                                                                                          Open-            Closed-
          Setting                                                                                                                  Closed-
                                                            Function                                                       loop             loop
          Value                                                                                                   V/f               loop
                                                                                                                          Vector           Vector
                                                                                                                                   Vector
                                                                                                                             1              (PM)
            15       Fast Stop, NO contact                                                                        Yes       Yes      Yes     Yes
            17       Fast Stop, NC contact                                                                        Yes         Yes       Yes       Yes
        Inspection RUN
          A multi-function contact input can be used to activate the inspection run. Therefore a inspection speed must be
          set and any of the multi-function contact inputs must be set to Inspection Run Selection (H1-=84).
        Related parameters
                            Name                                                                                        Control Methods
                                                                                                     Change                                    MEMO-
              Param-                                                                                                    Open-           Closed- BUS
                                                                                Setting    Factory   during                     Closed-
               eter                                  Description                                                         loop            loop
                           Display                                              Range      Setting   Opera-      V/f              loop          Regis-
              Number                                                                                                    Vector          Vector
                                                                                                      tion                       Vector          ter
                                                                                                                           1             (PM)
                       Inspection
                       speed         Sets the frequency reference when      0 to 25.00 Hz
                 d1-14 reference     the inspection speed is selected by a 120.00                          Yes   Q        Q         Q         Q    28FH
                       Inspect Speed multi-function contact input.*3       *1 *2 50.00%
                       vi                                                          (PM)
          * 1. The maximum setting value depends on the setting of the maximum output frequency (E1-04).
          * 2. The setting range becomes 0.00 to 100.00 when using closed-loop vector control (PM).
          * 3. Enabled if the Inspection Run Command is set for a multi-function contact input.
          The inspection Run Command must be set before the Up/Down signal is set. During the start of the inspection
          RUN, the normal brake sequence is used and the Inverter accelerates to the inspection speed (d1-14).
6-14
                                                                                                                     Control/Brake Sequence
     The falling edge of the Inspection Speed command or UP/DOWN commands triggers the magnetic contactor
     open command, the motor brake close command and the baseblock.
                               Inspection RUN                                                           Inspection RUN
                      (Stop by Up/Down signal removal)                                     (Stop by Inspection Speed signal removal)
                                  DC Injection/                                                              DC Injection/
                                   zero-servo                                                                 zero-servo
             Speed                                                                                 Speed
       Hardware BB                                                                         Hardware BB
      Up/Down (D/I)                                                                       Up/Down (D/I)
   Inspection speed                                                                    Inspection speed
       Internal RUN                                                                        Internal RUN
    MC closed (D/O)                                                                     MC closed (D/O)
 Brake released (D/O)                                                                Brake released (D/O)
 Brake Sequence
     The Inverter supports two types of brake sequences, one with torque compensation at start using an analog
     input value and one without torque compensation at start.
 Related Parameters
                        Name                                                                                       Control Methods
                                                                                                    Change                                MEMO-
          Param-                                                                                                   Open-           Closed- BUS
                                                                             Setting     Factory    during                 Closed-
           eter                                   Description                                                       loop            loop Regis-
                        Display                                              Range       Setting    Opera-   V/f             loop
          Number                                                                                                   Vector          Vector
                                                                                                     tion                   Vector          ter
                                                                                                                      1             (PM)
                Terminal A1          Sets the multi-function analog input
                function             function for terminal A1.
                                                                                                                                                    6
          H3-15 selection                                                     0, 1          0         No     No      No      A     A     434H
                                     Frequency Reference
                Terminal A1
                Func                 Torque compensation
                Zero speed           Sets the speed level at which the DC
                level at stop        injection/zero speed operation starts
                                     during stop.                                          1.2
                                                                             0.0 to
          S1-01                  If S1-01 < E1-09, the DC injection/                       Hz         No     A       A       A     A     680H
                   ZeroSpeed@s                                                10.0
                                 zero speed operation starts from E1-                      *1
                   top
                                 09. For closed-loop vector control,
                                 the zero-servo starts from S1-01.
                   DC injection Sets the DC injection braking cur-
                   braking cur- rent as a percentage of the Inverter
                   rent at start rated current.                               0 to
          S1-02                                                                           50%         No     A       A       No    No    681H
                                DC excitation current in closed-loop          100
                   DC Inj I
                                vector control changes according to
                   @start
                                E2-03 setting.
                   DC injection Sets the DC injection braking cur-
                   braking cur- rent as a percentage of the Inverter
                   rent at stop rated current.                                0 to
          S1-03                                                                           50%         No     A       A       No    No    682H
                              DC excitation current in closed-loop            100
                DC Inj I
                              vector control changes according to
                @stop
                              E2-03 setting.
                DC injection Used to set the time to perform DC
                braking/zero- injection braking at start in units of
                speed time at 1 second.                                      0.00
          S1-04 start                                                          to        0.40 s       No     A       A       A     A     683H
                              Used to stop coasting motor and                              *1
                              restart it. When the set value is 0,           10.00
                DC Inj
                              DC injection braking at start is not
                T@start
                              performed.
                                                                                                                                                  6-15
                    Name                                                                                    Control Methods
                                                                                             Change                                MEMO-
       Param-                                                                                               Open-           Closed- BUS
                                                                         Setting   Factory   during                 Closed-
        eter                                Description                                                      loop            loop
                   Display                                               Range     Setting   Opera-   V/f             loop          Regis-
       Number                                                                                               Vector          Vector
                                                                                              tion                   Vector          ter
                                                                                                               1             (PM)
             DC injection      Used to set the time to perform DC
             braking/zero-     injection braking at stop in units of 1
             speed time at     second.                             0.00
       S1-05 stop          Used to prevent coasting after the       to     0.60 s             No      A       A       A       A     684H
                           Stop Command is input. When the        10.00
             DC Inj
                           set value is 0.00, DC injection brak-
             T@stop
                           ing at stop is not performed.
             Brake release Sets the time delay from the brake
             delay time    release command to the start of
                           acceleration.                           0.00
       S1-06                                                        to      0.20              No      A       A       A       A     685H
             Brake open This timer can be used to avoid run- 10.00
             delay         ning against the closed brake at
                           start.
             Brake close Sets the time delay from the internal
             delay time    brake close command until the
                           brake control output is switched.       0.00
       S1-07                                                        to      0.10              No      A       A       A       A     686H
             Brake         This timer can be used to avoid clos-
                                                                  S1-05
             CloseDelay ing the brake when the motor is still
                           turning.
             SE2 detec-    Used to set the delay time for the
             tion delay    detection of a SE2 fault.
             time          At the time S1-06 + S1-14 after the       0
                           Fwd/Rev command was given the            to
       S1-14                                                              200 ms              No      A       A       A      No    68DH
                           output current is measured. If it is  (S1-04 -
             SE2 det T     below 25% of the no-load current       S1-06)
                               (E2-03) setting a SE2 fault will be
                               output.
                SE3 detec-     Used to set the delay time for the
                tion delay     detection of a SE3 fault.
                time            At the time S1-15 after the fwd/rev
6
                                                                           0
                                command was given, the Inverter
       S1-15                                                              to       200 ms     No      A       A       A      No    68EH
                                starts to observe the output current     5000
                SE3 det T       continuously. If it falls below 25%
                                of the no-load current (E2-03) set-
                                ting a SE3 will be output.
                Run delay       Sets the delay time from the Run          0.00
       S1-16    time            signal input to the internal run           to      0.10 s     No      A       A       A       A     68FH
                Run Delay T enable.                                       1.00
                DC injection
                current gain at
                                Used to set the DC injection gain           0
                regenerative
       S1-17                    when Inverter is in the regenerative       to      100%       No      No      A      No      No     690H
                operation
                                mode.                                     400
                DC Inj
                gain@gen
                DC injection
                current gain at
                                Used to set the DC injection gain           0
                motoring
       S1-18                    when Inverter is in the motoring           to       20%       No      No      A      No      No     691H
                operation
                                mode.                                     400
                DC Inj
                gain@mot
                Magnetic
                contactor
                open delay      Sets the magnetic contactor control       0.00
       S1-19                                                               to      0.10 s     No      A       A       A       A     692H
                time            output delay time after stop.
                                                                          1.00
                Cont open
                delay
6-16
                                                                                                      Control/Brake Sequence
                                                                                                                                     6
      gain during                                              0.500
                         lowering in 0.001 seconds units
S1-23                                                            to        1.000      No      No     No      A      A     696H
      lowering           when the torque compensation at      10.000
      TorqComp-          start function is used.
      gain@low
      Torque com-
      pensation bias     Sets the torque compensation bias at -200.0
S1-24 during raising     raising when the torque compensa-      to          0.0%      No      No     No      A      A     697H
      TorqComp-          tion at start function is used.      +200.0
      Bias@ri
      Torque com-
      pensation bias     Sets the torque compensation bias at
      during lower-      lowering as a percentage when the    -200.0
S1-25                                                           to          0.0%      No      No     No      A      A     698H
      ing                torque compensation at start func-
                                                              +200.0
      TorqComp-          tion is used.
      Bias@red
      Dwell speed        Hold speed reference when the load
      reference          is heavy.The frequency reference
                         follows the C1-07 acceleration 4
                         setting time.                         0.0
S1-26                                                                      0.0 Hz     No      A       A      A      A     699H
         DWELL                                              to 120.0
                         Acceleration time will be changed
         speed
                         when the motor speed exceeds the
                         C1-11 setting frequency.
         Door zone       Sets the door zone speed level.
         speed level     If the motor speed (in CLV and
                         OLV) or the output frequency (in V/
                         f control) falls below S1-27 and a      0.0
S1-27                                                                      0.0 Hz     No      A       A      A      A     69AH
         Door Zone       multi-function output is set for the to 120.0
         Level           Door zone signal
                         (H2-=42), this output will be
                         closed.
                                                                                                                                   6-17
                            Name                                                                                                    Control Methods
                                                                                                          Change                                           MEMO-
             Param-                                                                                                                 Open-           Closed- BUS
                                                                                    Setting    Factory    during                            Closed-
              eter                                     Description                                                                   loop            loop
                            Display                                                 Range      Setting    Opera-        V/f                   loop          Regis-
             Number                                                                                                                 Vector          Vector
                                                                                                           tion                              Vector          ter
                                                                                                                                       1             (PM)
                      SE1 Selection 0: SE1 can be reset when stopped.
                                    1: SE1 is automatically reset when
                S1-28                                                       0 to 2                 0         No         A             A          A      A   69BH
                      SE1 Selection stopped.
                                    2: SE1 is not detected at any time.
                      Torque limit
                                    Sets the time which is used to
                      time at stop
                S1-31               reduce the torque limit to 0 after    0 to 1000              0 ms        No         No            No         No     A   69EH
                      TrqLimit T
                                    zero speed.
                      @Stop
                      Zero-servo    Adjust the strength of the position
                      gain 2        control loop at start. Increasing
                                    zero-servo gain 2 increases the
                S1-33               strength of the lock. Increasing this 0.00 to
                                                                                                 0.00        No        No             No         No     A   6A0H
                 *2                 too much may induce oscillation.        30.00
                      ZeroSrvGain2
                                    When 0.00 is set or the starting
                                    torque compensation is enabled, this
                                    function is disabled.
         * 1. The factory settings will change when the control method is changed. V/f control factory settings are given.
         * 2. Applicable for L7-Series Inverters with software versions PRG: 2013 or later.
6-18
                                                                                                                             Control/Brake Sequence
             Speed
                                   S1-06                                                                              S1-07
                                   Brake                                                                              Brake
                                  release                                                                             close
                                   delay                                                                              delay
                                    time                                                                               time
                     Run
t1 t2 t3 t4 t5 t6 t7 t8 t9
Fig 6.4 Timing Chart of Brake Sequence Without Torque Compensation at Start
        The timing chart above is divided in time zones. The following table explains the sequence in each time zone.
          Timing                                                                  Description
                      The Inverter gets the direction signal (UP/DOWN)
                      The Inverter gets the hardware baseblock disable signal (Not BB condition).
             t1
                      The Inverter receives the speed reference signal.
                      The Inverter sets the magnetic contactor closed signal.                                                                                      6
                      The Inverter waits for the magnetic contactor confirmation signal. If no multi-function contact input is set to magnetic
                      contactor confirmation signal (H1-=86), the sequence is proceeded after exceeding the operation start delay time (S1-
                      16).
                      When the RUN delay time (S1-16) has elapsed, DC injection (Open Loop) or zero-speed operation (Closed Loop) is
             t2       started.
                      When the brake open delay time (S1-06) has elapsed, the Inverter sets the brake release command.
                      The Inverter keeps DC injection/zero-speed operation until
             t3       * the time S1-04  S1-06 has elapsed if S1-06 < S1-04 or
                      * the time S1-06 has elapsed if S1-06 > S1-04 (try avoid this setting since the motor could be driven against the brake)
             t4       The speed is increased to the selected speed and is kept parameter until the leveling speed is selected.
                      The speed is decreased to the leveling speed and is kept parameter until the stop signal is given (depending on d1-18 either
             t5       by removing the direction signal, by removing the leveling signal or by deleting the speed inputs, see page 6-8, Speed
                      Selection Sequence Using Multi-function Contact Inputs)
              6       The speed is decreased to the zero-speed level.
                      When the zero-speed level is reached, the DC injection (Open Loop) or zero-speed operation (Closed Loop) is applied for
             t7       the time set in S1-05.
                      When the brake close delay time (S1-07) has elapsed, the brake release command is removed.
                      The Inverter continues DC Injection (Open Loop) or zero-speed operation (Closed Loop) until the time S1-06  S1-07 has
             t8
                      elapsed. After that the Inverter output is shut down and the hardware baseblock signal must be set.
             t9       After the magnetic contactor open delay time (S1-19) has elapsed, the magnetic contactor close signal is removed.
                                                                                                                                                                 6-19
           Brake Sequence with torque compensation at start
            (closed-loop vector control required)
                If a load measuring device is installed in the elevator, an analog input can be used to input a torque compensa-
                tion value to the Inverter. This function requires closed-loop vector control.
                The input torque compensation value is latched when the direction command is given. At the start it is
                increased from zero to the latched value using the torque increase time set in parameter S1-22. The torque
                compensation value fades out to 0 after the speed has reached the torque compensation fade out level.
                The torque compensation function can be adjusted using the parameters shown in the block diagram below.
                Adjust the parameter so that the torque compensation value is zero when the elevator is balanced.
                                                                                            Torque compensation
                                                                                              bias during raising
                                                     %                                            S1-24
                Terminal A1                                                                                           UP
                                             H3-16
                 H3-15=1                                                                           +   +           direction
                  Torque
                                                                                                                                            Torque compensation
               compensation                  H3-17
                                                                                 S1-23
                                                 0         10v                          +                            DOWN
                                                                                               +
                                                                 Torque compensation gain                            direction
                                                                      during lowering
                                                                                          S1-25
6                 one of the input channels Ch2 or Ch3 of an AI-14B option card can be used when the input function for is
                    set to Torque Compensation (H3-05 or H3-09=14). The setting of b1-01 has no influence here.
                The figure below shows the timing chart for this brake sequence.
                                                                                                                                                               S1-19
                                                                                                                                                               Magnetic
                                                                        Selected speed                                                                         contactor
                     S1-16                                                                                                                                     open delay
                                            S1-04                                                                                           S1-05              time
                  RUN delay time
                                         Zero-speed                                                                                      Zero-speed
                                        control at start          Torque compesation fade
                                                                                                            Leveling speed              control at stop
                                                                  out level S1-29
                    Speed
                                        300% torque                 Torque compesation fade                                       S1-07
                                        comp                        out using S1-22 when                                          Brake
            Torque comp                                             S1-29 is reached                                              close
                                                                                                                                  delay
             level at start                                                                                                        time
                                        Torque comp
                                        increase time
                                            S1-22
Run
t1 t2 t3 t4 t5 t6 t7 t8 t9
Fig 6.5 Timing Chart of Brake Sequence With Torque Compensation at Start
6-20
                                                                                                                Control/Brake Sequence
    The timing chart above is divided in time zones. The following table explains the sequence in each time zone
     Timing                                                            Description
              The Inverter gets the direction signal (UP/DOWN)
              The Inverter gets the hardware baseblock signal disable signal (Not BB condition).
              The Inverter receives the speed reference signal.
       t1
              The Inverter sets the magnetic contactor close signal.
              The Inverter waits for the magnetic contactor confirmation signal. If no multi-function contact input is set to magnetic con-
              tactor confirmation signal (H1-=86), the sequence is proceeded after exceeding the operation start delay time (S1-16).
              The zero-speed control operation is started.
              The analog torque compensation input is latched and the torque compensation value is increased from zero to the latch
       t2
              value using the time parameter set in parameter S1-22.
              After reaching the torque compensation level at start, the Inverter sets the brake release command.
       t3     The brake opens and the zero-speed operation is continued until S1-04 has elapsed.
              The speed is increased to the selected speed and is kept parameter until the leveling speed is selected.
       t4     During acceleration, when the torque fade out speed level S1-29 is reached, the torque compensation value is fade out to 0
              using the time parameter set in S1-22.
              The speed is decreased to the leveling speed and is kept parameter until the stop signal is given (depending on d1-18 either
       t5     by removing the direction signal, by removing the leveling signal or by deleting the speed inputs, see page 6-8, Speed Selec-
              tion Sequence Using Multi-function Contact Inputs).
       t6     The speed is decreased to the zero-speed level.
              When the zero-speed Level is reached, zero-speed operation is applied for the time set in S1-05.
       t7
              When the brake close delay time (S1-07) has elapsed, the brake release command is removed.
              The Inverter continues the zero-speed operation until the time S1-06  S1-07 has elapsed. After that the Inverter output is
       t8
              shut down and the hardware baseblock signal must be set.
       t9     After the magnetic contactor open delay time (S1-19) has elapsed, the magnetic contactor close signal is removed.
Related parameters
       Param-
                    Name
                                                                                               Change
                                                                                                              Control Methods
                                                                                                              Open-
                                                                                                                                     MEMO-
                                                                                                                              Closed- BUS
                                                                                                                                                6
                                                                       Setting   Factory       during                 Closed-
        eter                                Description                                                        loop            loop Regis-
                   Display                                             Range     Setting       Opera-   V/f             loop
       Number                                                                                                 Vector          Vector
                                                                                                tion                   Vector          ter
                                                                                                                 1             (PM)
              Short-floor     Enables or disables the short floor
              function        operation function
        S3-01                                                           0, 1         0          No      A       A      A        A     6BDH
              selection       0: disabled
              Short floor sel 1: enabled
  Principle
    The short floor operation is activated when the leveling signal is set before the nominal speed is reached. The
    Inverter calculates the distance for deceleration from nominal speed to 0.4 x the nominal speed, which is equal
    to the area S in the figure below.
                                                     Speed
Nominal speed
                                                                  S
                                  Nominal speed x 0.4
Leveling speed
0 t
                                                                                                                                              6-21
           If the leveling speed signal is set when minimal 40% of the nominal speed have been reached, the Inverter
            keeps the reached speed for the distance equal to the area S. After that it decelerates to the leveling speed.
           If the leveling signal is set before 40% of the nominal speed have been reached, the Inverter accelerates to
            40% of the nominal speed and keeps it for the distance equal to the area S. After that it decelerates to lev-
            eling speed.
                                              Speed
0 t
       Parameter Setup
         The short floor function can be activated by setting parameter S3-01 to 1.
         When parameter d1-18 is set to 1 or 2 (dedicated speed inputs), the value of parameter d1-09 is taken as nom-
         inal speed.
6-22
                                                                                  Acceleration and Deceleration Characteristics
  Related Parameters
                   Name                                                                              Control Methods
                                                                                      Change                                 MEMO-
       Param-                                                                                        Open-            Closed- BUS
                                                                  Setting   Factory   during                  Closed-
        eter                              Description                                                 loop             loop
                   Display                                        Range     Setting   Opera-   V/f             loop           Regis-
       Number                                                                                        Vector           Vector
                                                                                       tion                   Vector           ter
                                                                                                        1              (PM)
              Acceleration Sets the acceleration time to accel-
        C1-01 time 1       erate from 0 Hz to the maximum                              Yes      Q      Q       Q       Q     200H
              Accel Time 1 output frequency.
              Deceleration Sets the deceleration time to decel-
        C1-02 time 1       erate from the maximum output fre-                          Yes      Q      Q       Q       Q     201H
              Decel Time 1 quency to 0 Hz.
              Acceleration Sets the acceleration time when the
        C1-03 time 2       multi-function input accel/decel                           Yes      A      A       A       A     202H
              Accel Time 2 time 1 is set to ON.
              Deceleration Sets the deceleration time when the
        C1-04 time 2       multi-function input accel/decel                           Yes      A      A       A       A     203H
              Decel Time 2 time 1 is set to ON.
              Acceleration Sets the acceleration time when the
                                                                  0.00 to
                                                                  600.00    3.00 s
                                                                                                                                         6
                                                                     *
        C1-05 time 3       multi-function input accel/decel                            No      A      A       A       A     204H
              Accel Time 3 time 2 is set to ON.
              Deceleration Sets the deceleration time when the
        C1-06 time 3       multi-function input accel/decel                            No      A      A       A       A     205H
              Decel Time 3 time 2 is set to ON.
              Acceleration
              time 4       Sets the acceleration time when the
        C1-07              frequency reference is below the                             No      A      A       A       A     206H
              Accel Time 4
                           value set in C1-11.
                                                                                                                                       6-23
                                Name                                                                                                 Control Methods
                                                                                                               Change                                        MEMO-
               Param-                                                                                                                Open-            Closed- BUS
                                                                                        Setting     Factory    during                         Closed-
                eter                                      Description                                                                 loop             loop
                                Display                                                 Range       Setting    Opera-        V/f               loop           Regis-
               Number                                                                                                                Vector           Vector
                                                                                                                tion                          Vector           ter
                                                                                                                                        1              (PM)
                             Decel time     Sets the frequency for automatic
                                                                                         0.0 to
                             switching      acceleration/deceleration switch-                       0.0 Hz
                                                                                         120.0
                             frequency      ing.
                C1-11                   If the output frequency is below the                                      No         A         A         A          A      20AH
                                                                                         0.0 to
                             Acc/Dec SW set frequency: Accel/decel time 4                            0.0%
                                                                                         100.0
                             Freq       If the output frequency is above the                         (PM)
                                                                                         (PM)
                                        set frequency: Accel/decel time 1.
                             Dwell speed    Hold speed reference when the load
                             reference      is heavy.The frequency reference
                                            follows the C1-07 acceleration 4
                                            setting time.                                 0.0
                 S1-26                                                                              0.0 Hz        No         A         A         A          A      699H
                             DWELL                                                     to 120.0
                                            Acceleration time will be changed
                             speed
                                            when the motor speed exceeds the
                                            C1-11 setting frequency.
              * The setting ranges for acceleration/deceleration times depend on the setting of C1-10 (Accel/decel time setting unit). If C1-10 is set to 1, the setting
                range for acceleration/deceleration times becomes 0.0 to 6000.0 seconds.
6 Set the acceleration/deceleration time units using C1-10. The factory setting is 1.
6-24
                                                                                            Acceleration and Deceleration Characteristics
Switching Over the Acceleration and Deceleration Time Using Multi-Function Input
 Commands
  When two multi-function contact input terminals are set to Accel./Decel. time switch over 1 and 2 (H1-
  =7 and 1A), the acceleration/deceleration times can be switched over even during operation by a binary
  combination of the inputs. The following table shows the acceleration/deceleration time switching combina-
  tions.
   Acceleration/Deceleration              Acceleration/Deceleration
                                                                                     Acceleration Time                     Deceleration Time
   Time Selection 1 Terminal              Time Selection 2 Terminal
              OFF                                    OFF                                     C1-01                                 C1-02
                  ON                                   OFF                                   C1-03                                 C1-04
                  OFF                                   ON                                   C1-05                                 C1-06
                  ON                                    ON                                   C1-07                                 C1-08
           Decel. time
          switching freq.
              C1-11
                                     Motor speed
                                                                                               C1-11
  Note:    When C1-11 is set much higher than S1-26, the motor speed cannot reach C1-11 and the motor can not accelerate to the selected speed. Therefore
           always set C1-11 equal or lower than S1-26!
                                                                                                                                                            6-25
        Acceleration and S-curve Settings
           Five different S-curve times are used to reduce the jerk when the speed changes.
         Related Parameters
                          Name                                                                               Control Methods
                                                                                             Change                                  MEMO-
              Param-                                                                  Fac-                   Open-            Closed- BUS
                                                                             Setting         during                   Closed-
               eter                               Description                         tory                    loop             loop
                         Display                                             Range           Opera-   V/f              loop           Regis-
              Number                                                                 Setting                 Vector           Vector
                                                                                              tion                    Vector           ter
                                                                                                                1              (PM)
                    S-curve char-
                    acteristic
                    time at accel-
              C2-01 eration start                                                                     Q        Q       Q       Q     20BH
                       S-Crv Acc @
                       Start
                    S-curve char-
                    acteristic     Set the S-curve time to smooth out
                    time at accel- any sudden changes in motor speed.
              C2-02 eration end    The S-curve can be used at start and                               Q        Q       Q       Q     20CH
6
                                                2                  2
                    time at decel-
              C2-04 eration end    When    the S-curve characteristic time                            Q        Q       Q       Q     20EH
                                   is set, the accel/decel times will
                    S-Crv Dec @ increase by only half of the S-curve
                    End            characteristic times at start and end.
                    S-curve char-
                    acteristic
                    time below
              C2-05 leveling                                                                          Q        Q       Q       Q      232H
                    speed
                       Scurve @
                       leveling
C2-02 C2-03
                                                                                C2-04
                                                                                                 C2-05
                  C2-01                                                                                     Leveling speed
6-26
                                                                                                Acceleration and Deceleration Characteristics
  Related Parameters
                    Name                                                                                              Control Methods
                                                                                                      Change                                  MEMO-
       Param-                                                                                                         Open-            Closed- BUS
                                                                                Setting    Factory    during                   Closed-
        eter                                    Description                                                            loop             loop
                   Display                                                      Range      Setting    Opera-    V/f             loop           Regis-
       Number                                                                                                         Vector           Vector
                                                                                                       tion                    Vector           ter
                                                                                                                         1              (PM)
                Dwell fre-                                                      0.0 to
                                                                                           0.0 Hz
                quency at start                                                 120.0
        b6-01                                                                   0.0 to                     No   A       A       A       A     1B6H
                Dwell Ref @                                                                0.0%
                                                                                100.0
                Start                                                                      (PM)
                                                                                (PM)
                                  Run Command    ON
                                                                   OFF
                Dwell time at
                start             Output frequency
                                                                                0.0 to
        b6-02                                                                               0.0 s          No   A       A       A       A     1B7H
                Dwell Time                                                       10.0
                @ Start
                                                     b6-01 b6-03         Time
                Dwell fre-                                     b6-04            0.0 to
                                            b6-02                                          0.0 Hz
                quency at stop                                                  120.0
        b6-03                                                                   0.0 to                     No   A       A       A       A     1B8H
                Dwell Ref @                                                                0.0%
                                                                                100.0
                Stop              The dwell function can be used to                        (PM)
                                                                                (PM)
                                  hold the output frequency tempo-
                Dwell time at     rarily.
                stop                                                            0.0 to
        b6-04                                                                               0.0 s          No   A       A       A       A     1B9H
                Dwell Time                                                       10.0
                @ Stop
                                          Run Command                ON
                                                                                          OFF
                                           Output frequency
b6-02 b6-04
                                                                                                                                                        6-27
        Stall Prevention During Acceleration
           The Stall Prevention During Acceleration function prevents the motor from stalling if the load is too heavy.
           If L3-01 is set to 1 (enabled) and the Inverter output current reaches 85% of the set value in L3-02, the accel-
           eration rate will begin to slow down. When L3-02 is exceeded, the acceleration will stop.
           If L3-01 is set to 2 (optimal adjustment), the motor accelerates so that the current is held at the level set in L3-
           02. With this setting, the acceleration time setting is ignored.
         Related Parameters
                           Name                                                                                   Control Methods
                                                                                                   Change                                MEMO-
              Param-                                                                                              Open-           Closed- BUS
                                                                              Setting    Factory   during                 Closed-
               eter                                Description                                                     loop            loop
                          Display                                             Range      Setting   Opera-   V/f             loop          Regis-
              Number                                                                                              Vector          Vector
                                                                                                    tion                   Vector          ter
                                                                                                                     1             (PM)
                       Stall          0: Disabled (Acceleration as set.
                       prevention        With a too heavy load, the motor
                       selection         may stall.)
                       during accel   1: Enabled (Acceleration stopped
                                         when L3-02 level is exceeded.
                                         Acceleration starts again when
               L3-01                     the current has fallen below the      0 to 2      1        No      A       A      No      No    48FH
                                         stall prevention level).
                       StallP Accel
                                      2: Intelligent acceleration mode
                       Sel
                                         (Using the L3-02 level as a basis,
                                         acceleration is automatically
                                         adjusted. The set acceleration
                                         time is disregarded.)
                       Stall          Sets the stall prevention during
                       prevention     acceleration operation current level
                       level during   as a percentage of Inverter rated
                       accel          current.
6              L3-02
                       StallP Accel
                                      Effective when L3-01 is set to 1 or
                                      2.
                                                                              0 to 200   150%       No      A       A      No      No     490H
6-28
                                                                                    Acceleration and Deceleration Characteristics
Time Chart
  The following figure shows the output frequency characteristics when L3-01 is set to 1.
                 Output current
                                                                                                     Time
                    Output frequency
                                         *1.
                                                               *2.
Setting Precautions
    Set the parameters as a percentage taking the Inverter rated current to be 100%.
    Do not increase the stall prevention level unnecessarily. An extremely high setting can reduce the Inverter
     lifetime. Also do not disable the function.
    If the motor stalls with the factory settings check the V/f pattern settings (E1-) and the motor setup
     (E2-).                                                                                                                         6
    If the stall level has to be increased very much to get the elevator running, consider to use a one size bigger
     Inverter.
                                                                                                                                    6-29
       Adjusting Analog Input Signals
         Related Parameters
                           Name                                                                                 Control Methods
                                                                                                 Change                                MEMO-
              Param-                                                                                            Open-           Closed- BUS
                                                                             Setting   Factory   during                 Closed-
               eter                               Description                                                    loop            loop
                          Display                                            Range     Setting   Opera-   V/f             loop          Regis-
              Number                                                                                            Vector          Vector
                                                                                                  tion                   Vector          ter
                                                                                                                   1             (PM)
                       AI-14B Chan- Selects the input signal level of
                       nel 1 signal Channel 1 if an AI-14B option card
              H3-01    level selection is installed.                           0 or 1     0       No      A       A       A       A     410H
                       AI-14 CH1 0: 0 to +10V
                       LvlSel          1: -10 to +10V
                       AI-14B Chan- Sets the frequency reference value
                       nel 1 gain      when 10 V is input as a percentage      0.0 to
              H3-02                                                                    100.0%     Yes     A       A       A       A     411H
                       AI-14 CH1 of the maximum output frequency              1000.0
                       Gain            set in E1-04.
                       AI-14B Chan- Sets the frequency reference value
                       nel 1 bias      when 0 V is input as a percentage of -100.0
              H3-03                                                              to     0.0%      Yes     A       A       A       A     412H
                       AI-14 CH1 the maximum output frequency set +100.0
                       Bias            in E1-04.
                       AI-14B Chan- Selects the input signal level of
                       nel 3 signal Channel 3 if an AI-14B option card
              H3-04    level selection is installed.                           0 or 1     0       No      A       A       A       A     413H
                       AI-14 CH3 0: 0 to 10V
                       LvlSel          1: -10 to +10V
                       AI-14B Chan-
6
                       nel 3 function Selects the function for the channel
              H3-05    selection       3 input if an AI-14B option card is    2,3,14      2       No      A       A       A       A     414H
                       AI-14           installed.
                       CH3FuncSel
                       AI-14B          Sets the input level according to the
                       Channel3        100% value of the function set in
                       gain                                                    0.0 to
              H3-06                    parameter H3-05 when the voltage                100.0%     Yes     A       A       A       A     415H
                                                                              1000.0
                       AI-14 CH3       at channel  3 of the AI-14B option
                       Gain            card is 10 V.
                       AI-14B Chan- Sets the input level according to the
                       nel 3 Bias      0% value of the function set in
                                                                             -100.0 to
              H3-07                    parameter H3-05 when the voltage                 0.0%      Yes     A       A       A       A     416H
                       AI-14 CH3                                              +100.0
                                       at channel 3 of the
                       Bias
                                       AI-14B option card is 0 V.
                       AI-14B Chan- Selects the input signal level of
                       nel 2 signal Channel 2 if an AI-14B option card
                       level selection is installed.
                                     0: 0 to 10V
                                     1: -10 to +10V
              H3-08                                                          0 to 2      0        No      A       A       A       A     417H
                                     2: 4 to 20 mA.
                       AI-14 CH2
                       LvlSel        If current input is selected, channel
                                     2 must be set to current input by
                                     hardware as well. Refer to the AI-
                                     14B manual.
                    AI-14B Chan-
                    nel 2 function Selects the function for the channel
              H3-09 selection      2 input if an AI-14B option card is       0 to 1F     3        No      A       A       A       A     418H
                    AI-14          installed.
                    CH2FuncSel
6-30
                                                                                                      Adjusting Analog Input Signals
                                                                                                                                          6-31
       Speed Detection and Speed Limitation
        Related Parameters
                         Name                                                                                Control Methods
                                                                                             Change                                 MEMO-
             Param-                                                                                          Open-           Closed- BUS
                                                                        Setting    Factory   during                  Closed-
              eter                                 Description                                                loop            loop
                        Display                                         Range      Setting   Opera-    V/f             loop          Regis-
             Number                                                                                          Vector          Vector
                                                                                              tion                    Vector          ter
                                                                                                                1             (PM)
                    Speed agree-
                                                                        0.0 to
                    ment detec- Effective when fout/fset agree 1,                0.0 Hz
                                                                        120.0
                    tion level   Frequency detection 1 or Fre-
              L4-01                                                                           No       A        A      A       A     499H
                                 quency detection 2 is set for a       0.0 to
                    Spd Agree                                                      0.0%
                                 multi-function output.                 100.0
                    Level                                                          (PM)
                                                                        (PM)
                    Speed agree- Effective when f /f agree 1,
                                                     ref out            0.0 to
                    ment detec-                                                    2.0 Hz
                                 fout/fset agree 1 or Frequency       20.0
                    tion width
              L4-02              detection 1 or Frequency detec-                            No       A        A      A       A    49AH
                                                                        0.0 to
                    Spd Agree    tion 2 is set for a multi-function               4.0%
                                                                         40.0
                    Width        output.                                           (PM)
                                                                        (PM)
                    Speed agree-
                    ment detec- Effective when f /f agree 2,         -120.0 to
                                                  out set                        0.0 Hz
                    tion level                                          +120.0
                                 Frequency detection 3 or Fre-
              L4-03 (+/-)                                                                     No       A        A      A       A    49BH
                                 quency detection 4 is set for a
                                                                       -100.0 to
                    Spd Agree    multi-function output.                            0.0%
                                                                         100.0
                    Lvl+-                                                          (PM)
                                                                         (PM)
6                   Speed agree-
                    ment detec- Effective when fref/fout agree 2
                    tion width   fout/fset agree 2, Frequency
                                                                        0.0 to
                                                                         20.0
                                                                                   2.0 Hz
              L4-04 (+/-)        detection 3 or "Frequency detec-                            No       A        A      A       A    49CH
                                 tion 4" is set for a multi-function    0.0 to
                    Spd Agree                                                      4.0%
                                 output.                                 40.0
                    Wdth+-                                                         (PM)
                                                                        (PM)
        Setting Precautions
            With L4-01 an absolute speed agreement level is set, i.e. a speed agreement is detected in both directions
             (Up and Down).
            With L4-03 a signed speed agreement level is set, i.e. a speed agreement is detected only in the set direc-
             tion (positive level  Up direction, negative level  Down direction).
6-32
                                                                                                   Speed Detection and Speed Limitation
Time Charts
   The following table shows the time charts for each of the speed agreement functions.
   Related                        L4-01: Speed Agree Level                                         L4-03: Speed Agree Level +/
  parameter                       L4-02: Speed Agree Width                                          L4-04: Speed Agree Width
              fref/fout Agree 1                                               fref/fout Agree 2
               Frequency                                                      Frequency
               reference                                                      reference
                                                            L4-02                                                     L4-04
              fref/fout Agree 1      OFF ON                                    fref/fout Agree 2      OFF ON
              (Multi-function output setting = 2)                              (Multi-function output setting = 13)
L4-02
                          OFF ON                                                            OFF ON
              fout/fset Agree 1                                               fout/fset Agree 2
L4-02
                                                                      L4-01                                                    L4-03
               Output fre-                                                     Output fre-
               quency or                                                       quency or
               motor speed                                                     motor speed
L4-01
L4-02
                                                                                                                                          6-33
        Limiting the Elevator Speed
            To use a high speed limit in the UP or DOWN direction, one of the multi-function contact inputs must be set to
            High speed limit switch Up or High speed limit Down (H1- = 87/88).
6-34
                                                                                                 Improving the Operation Performance
Related Parameters
                                                                                                                                                 6
                       Name                                                                                  Control Methods
                                                                                              Change                                 MEMO-
           Param-                                                                                            Open-            Closed- BUS
                                                                          Setting   Factory   during                  Closed-
            eter                                Description                                                   loop             loop
                       Display                                            Range     Setting   Opera-   V/f             loop           Regis-
           Number                                                                                            Vector           Vector
                                                                                               tion                   Vector           ter
                                                                                                                1              (PM)
                    Droop           Sets the slip as a percentage of
                    control gain    maximum frequency when the
                                    maximum output frequency is spec-     0.0 to
           b7-01                                                                    0.0 %      Yes     No       No     No      A     1CAH
                    Droop           ified and the rated torque occurs.    100.0
                    Quantity        Droop control is not performed
                                    when the setting is 0.0.
                 Droop
                 control delay Droop control responsiveness
                                                                   0.03 to
           b7-02 time          parameter. When hunting or oscilla-                  0.05 s     Yes     No       No     No      A     1CBH
                                                                     2.00
                 Droop Delay tion occurs, increase the value.
                    Time
  Setting Precautions
       Droop control is disabled if b7-01 is set to 0.0.
       Set b7-01 to the amount of slip as the percentage of slip when the maximum output frequency is input and
           the rated torque is generated.
       Parameter b7-02 is used to adjust the responsiveness of droop control. Increase this setting if oscillation or
           hunting occur.
       Disable the feed forward control (N5-01 = 0) when using the droop control function.
                                                                                                                                               6-35
         Setting the Droop Control Gain
           Set the droop control gain as the speed reduction at a 100% motor torque, as a percentage of the maximum
           output frequency.
Torque
b7-01
100%
                                                                                                          Speed
                                          0                                     Speed reference
6        Related Parameters
                          Name
                                                                                               Change
                                                                                                                Control Methods
                                                                                                                                        MEMO-
              Param-                                                                                            Open-            Closed- BUS
                                                                           Setting   Factory   during                    Closed-
               eter                             Description                                                      loop             loop
                         Display                                           Range     Setting   Opera-     V/f             loop           Regis-
              Number                                                                                            Vector           Vector
                                                                                                tion                     Vector           ter
                                                                                                                   1              (PM)
                       Slip compen- Used to improve speed accuracy
                       sation gain  when operating with a load.
                                    Usually changing this setting is not
                                    necessary.
                                    Adjust this parameter under the fol-
                                    lowing circumstances.
                                     When motor speed is lower than
                                      the frequency reference increase     0.0 to
              C3-01                                                                    1.0      Yes       No      A       A       No    20FH
                       Slip Comp      the set value.                        2.5
                       Gain          When motor speed is higher than
                                      the frequency reference decrease
                                      the set value.
                                    In closed-loop vector control this
                                    value is the gain for compensating
                                    the slip caused by temperature vari-
                                    ation.
6-36
                                                                                                                                                  Improving the Operation Performance
                                                                                                                                                                                                              6
              Output V                saturated.)                                                                           0
              limit Sel                                                                                                   (PM)
                                                                                                                                                                                                            6-37
       Adjusting Slip Compensation Limit (C3-03)
         Using parameter C3-03 the upper limit for the slip compensation can be set as a percentage, taking the motor
         rated slip as 100%.
         If the speed is lower than the target value but does not change even after adjusting the slip compensation gain,
         the slip compensation limit may have been reached. Increase the limit, and check the speed again. Always
         make sure that the value of the slip compensation limit and reference frequency does not exceed the tolerance
         of the machine.
         The following diagram shows the slip compensation limit for the parameter torque range and fixed output
         range.
                             Slip compensation limit
Output frequency
6-38
                                                                                            Improving the Operation Performance
  Related Parameters
                   Name                                                                                 Control Methods
                                                                                         Change                                 MEMO-
       Param-                                                                                           Open-            Closed- BUS
                                                                     Setting   Factory   during                  Closed-
        eter                              Description                                                    loop             loop
                   Display                                           Range     Setting   Opera-   V/f             loop           Regis-
       Number                                                                                           Vector           Vector
                                                                                          tion                   Vector           ter
                                                                                                           1              (PM)
                Torque com- Sets the torque compensation gain.
                pensation   Usually changing this setting is not
                gain        necessary.
                              Adjust it under the following cir-
                              cumstances:
                               When the cable is long increase
                                the set value.
                               When the motor capacity is
                                smaller than the Inverter capac-
                                ity (Max. applicable motor
                                                                    0.00 to
        C4-01                   capacity), increase the set values.             1.00      Yes     A       A       No      No    215H
                                                                     2.50
                               When the motor is oscillating,
                                                                                                                                            6
                Torq Comp
                Gain            decrease the set values.
                              Adjust the torque compensation
                              gain so that at minimum speed the
                              output current does not exceed the
                              Inverter rated output current.
                              Do not change the torque compen-
                              sation gain from its default (1.00)
                              when using open-loop vector 1 con-
                              trol.
                Torque com-   The torque compensation delay
                pensation     time is set in ms units.
                delay time    Usually changing this setting is not
                parameter     necessary.
                              Adjust it under the following cir-      0 to     200 ms
        C4-02                 cumstances:                                                 No      A       A       No      No    216H
                                                                     10000       *
                               When the motor is oscillating,
                Torq Comp
                                increase the set values.
                Time
                               When the responsiveness of the
                                motor is low, decrease the set
                                values.
              Starting
              torque com-
              pensation       Sets the torque compensation value 0.0 to
        C4-03 (FWD)                                                             0.0%      No      No      A       No      No    217H
                              at start in FWD direction          200.0%
                FTorqCmp
                @ Start
                                                                                                                                          6-39
                           Name                                                                                               Control Methods
                                                                                                          Change                                      MEMO-
             Param-                                                                                                           Open-            Closed- BUS
                                                                                   Setting    Factory     during                       Closed-
              eter                                    Description                                                              loop             loop
                           Display                                                 Range      Setting     Opera-       V/f              loop           Regis-
             Number                                                                                                           Vector           Vector
                                                                                                           tion                        Vector           ter
                                                                                                                                 1              (PM)
                   Starting
                   torque com-
                   pensation            Sets the torque compensation value -200.0%
             C4-04 (REV)                                                                        0.0%        No         No       A       No      No    218H
                                        at start in REV direction           to 0.0
                       RTorqCmp
                       @ Start
                   Starting
                   torque com-
                   pensation    Sets starting torque start-up time.
             C4-05 time parame- When 0 to 4 ms is set, it is operated 0 to 200                 10 ms        No         No       A       No      No    219H
                   ter          without filter.
                   TorqCmpDe-
                   layT
* The factory settings will change when the control method is changed. (V/f control factory settings are given.)
        V/f control
            If the cable is very long, increase the set value.
6
            If the motor capacity is smaller than the Inverter capacity (max. applicable motor capacity), increase the
             set value.
            If the motor vibrates, reduce the set value.
        Setting precautions
            Adjust this parameter so that the output current during low-speed rotation does not exceed the Inverter
             rated output current range.
            Adjust the value in steps of 0.05 only.
6-40
                                                                                                 Improving the Operation Performance
                              OFF
                                       Time parameter: C4-02
   Time parameter: C4-05
                                                                              C4-03 (forward)
                                                                      C4-04 (reverse, negative polarity)
    Torque compensation
          volume
                                     C4-05 x 4
           E1-09
      Output frequency                                                                                      E1-09
  Related Parameters
                   Name                                                                                     Control Methods
                                                                                           Change                                   MEMO-
       Param-                                                                                               Open-            Closed- BUS
                                                                   Setting     Factory     during                    Closed-
        eter                             Description                                                         loop             loop
                  Display                                          Range       Setting     Opera-     V/f             loop           Regis-
       Number                                                                                               Vector           Vector
                                                                                            tion                     Vector           ter
                                                                                                               1              (PM)
              ASR propor-
              tional (P)                                                       40.00
                                                                   0.00 to
        C5-01 gain 1                                                                        Yes       No        No     Q         Q   21BH
                                                                   300.00
                ASR P Gain Set the proportional gain 1 and the             3.00
                1          integral time 1 of the speed control           (PM)
                           loop (ASR) for the maximum fre-
              ASR integral quency.
                                                                         0.500 s
              (I) time 1                                        0.000 to
        C5-02                                                                               Yes       No        No     Q         Q   21CH
              ASR I Time                                         10.000 0.300 s
              1                                                           (PM)
                                                                                                                                              6-41
                          Name                                                                                Control Methods
                                                                                               Change                                 MEMO-
            Param-                                                                                            Open-            Closed- BUS
                                                                           Setting   Factory   during                  Closed-
             eter                              Description                                                     loop             loop
                         Display                                           Range     Setting   Opera-   V/f             loop           Regis-
            Number                                                                                            Vector           Vector
                                                                                                tion                   Vector           ter
                                                                                                                 1              (PM)
                   ASR propor-
                   tional (P)                                                  20.00
             C5-03 gain 2       Set the proportional gain 2 and the 0.00 to                     Yes     No      No       Q      Q     21DH
                                integral time 2 of the speed control 300.00
                   ASR P Gain                                                   3.00
                                loop (ASR) for the minimum fre-                (PM)
                   2
                                quency.
                   ASR integral
                                The settings become active for
                   (I) time 2   acceleration only.                   0.000 to
             C5-04                                                            0.500 s           Yes     No      No       Q      Q     21EH
                   ASR I Time                                         10.000
                   2
                   ASR pri-        Sets the filter time parameter for
                   mary delay      outputting torque references from                 0.004 s
                                                                          0.000 to
             C5-06 time            the speed control loop (ASR). It is                          No      No      No       Q      Q     220H
                                                                           0.500
                     ASR Gain      set in 1-second units.
                                                                                     0.020 s
                     SW Freq       Usually setting is not necessary.
                   ASR switch- Sets the frequency for switching            0.0 to
                                                                                     0.0 Hz
                   ing frequency between Proportion Gain 1, 2,3 and        120.0
             C5-07               Integral Time 1, 2, 3. Multi-func-        0.0 to               No      No      No       Q      Q     221H
                   ASR Gain      tion input speed control (ASR) pro-                  2.0%
                                                                           100.0
                   SW Freq       portion gain switching has priority.                 (PM)
                                                                           (PM)
                   ASR integral Set the parameter to a small value
                   (I) limit    to prevent any radical load change.
             C5-08                                                  0 to 400          400%      No      No      No       A      A     222H
                                A setting of 100% is equal to the
                   ASR I Limit maximum output frequency.
                   ASR propor-
                   tional (P)                                                  40.00
             C5-09 gain 3       Set the proportional gain 3 and the 1.00 to                     Yes     No      No       Q      Q     22EH
                                integral time 3 of the speed control 300.00
                   ASR P Gain                                                   3.00
                                loop (ASR) for the minimum fre-
6
                   3                                                           (PM)
                                quency.
                   ASR integral
                                The settings become active for                0.500 s
                   (I) time 3   acceleration only.                   0.000 to
             C5-10                                                                              Yes     No      No       Q      Q     231H
                   ASR I Time                                         10.000 0.300 s
                   3                                                           (PM)
         When the ride starts with the nominal speed selected, the ASR P gain and I time change from C5-03/04 to C1-
         01/02 at nominal speed. When the speed selection changes to leveling speed, the P gain and I time are changed
         from C1-01/02 to C1-09/10.
6-42
                                                                                       Improving the Operation Performance
    If parameter d1-18 is set to 0, the nominal/leveling speed detection function must be enabled in order to use
    the ASR 3 settings.
  Related Parameters
                   Name                                                                            Control Methods
                                                                                    Change                                MEMO-
       Param-                                                                                      Open-           Closed- BUS
                                                                Setting   Factory   during                 Closed-
        eter                            Description                                                 loop            loop Regis-
                  Display                                       Range     Setting   Opera-   V/f             loop
       Number                                                                                      Vector          Vector
                                                                                     tion                   Vector          ter
                                                                                                      1             (PM)
              A/D conver-
              sion start
              delay timer                                       0.0 to
        N9-60             Sets the A/D conversion delay time.             0.0 s     No      No     No      No     A     64DH
              AD                                                 40.0
              DelayT@Star
              t
                                                                                                                                  6-43
         Adjustments
             Normally no adjustment is needed for this value. However, if cyclic oscillations as shown in Fig. 6.16 while
             operating at a parameter speed, the A/D conversion delay can be increased in order to eliminate the vibrations.
Torque Signal
Motor Speed
Selected speed
S1-04 S1-05
6
                                                                                                                                       S1-19
                               200                                                                                               100   Magnetic
                   S1-16                Zero-speed                                                              Zero-servo       ms
                   Run delay   ms                                                                                                      contactor
                   time                control at start                                                        control at stop         open delay
                                                                                    Leveling speed                                     time
                 Speed
                                       300% Torque
                                       comp                                                              S1-07
             Torque comp                                                                              Brake close
             level at start                                                                           delay time
                                        Torque comp
                                        increase time
                                            S1-22
           Run
         Inverter Hardware
         BB D/I
         Magnetic contactor
         control D/O
         Magnetic contactor
         confirmation D/I
         Brake release
         command
                                t1     t2         t3            t4                 t5            t6       t7              t8     t9
Fig 6.17 Timing Chart of Brake Sequence With Torque Compensation at Start
6-44
                                                                                                Improving the Operation Performance
    The timing chart above is divided in time zones. The following table explains the sequence in each time zone.
   Timing                                                                Description
             The Inverter receives a direction signal indicating up or down.
             The Inverter receives a signal to disable hardware baseblock (i.e., a signal indicating there is no baseblock condition).
             The Inverter receives the speed reference.
    t0-t1
             The Inverter receives a signal to close the magnetic contactor.
             The Inverter waits for verification that the magnetic contactor has closed. If no multi-function input has been programmed to
             issue a command verifying that the magnetic contactor has closed, then the Inverter will proceed to the next step once the time
             set to S1-16 has passed (Run delay time).
             Zero-servo operation begins.
             Analog torque compensation value is maintained and the Inverter begins generating torque compensation based on S1-22 (Start-
    t1-t2    ing torque compensation increase time).
             Once the torque compensation reaches the specified level at start, the Inverter then releases the brake and maintains the torque
             compensation value until it stops.
             After the time set to S1-04 has expired (DC braking at start, or DC excitation), the Inverter begins to accelerate the motor.
    t2-t3
             The Dwell function can be enabled at start.
    t3-t4    Inverter begins to accelerate.
    t4-t5    The Inverter speed reaches the specified speed reference.
    t5-t6    The Inverter begins to accelerate.
    t6-t7    Zero-speed is selected.
             The Inverter reaches the zero-speed level.
             The Inverter continues using zero-speed control.
    t7-t8    After the time set to S1-07 passes (Brake close delay time), the Inverter issues a command to close the brake.
             After the time set to S1-07 passes (Brake close delay time), the Inverter issues a command to close the brake.
             The Inverter continues operating with zero-speed until the time set to parameters S1-05 and S1-07 have passed.
             The signal indicating direction is disabled.
    t8-t9    Torque is reduced by the specified bias level: (300%) / (S1-31)
             The Inverter halts output once the torque compensation level drops to zero.
             The hardware baseblock signal is switched on.
    t9-t10
             Once the time set to S1-19 passes (Magnetic contactor open delay time), the Inverter will shut off the magnetic contactor control
             signal.                                                                                                                               6
fref fout
Iq
                                                                                                                                                 6-45
       Related Parameters
                         Name                                                                                  Control Methods
                                                                                                Change                                MEMO-
            Param-                                                                                             Open-           Closed- BUS
                                                                            Setting   Factory   during                 Closed-
             eter                                Description                                                    loop            loop
                        Display                                             Range     Setting   Opera-   V/f             loop          Regis-
            Number                                                                                             Vector          Vector
                                                                                                 tion                   Vector          ter
                                                                                                                  1             (PM)
                     Speed feed-    Sets the internal speed feedback
                     back detec-    detection control gain.
                     tion control   Normally, there is no need to change
                     (AFR) gain     this setting.
                                     If necessary, adjust this parameter
                                       as follows:                        0.00 to
             N2-01                   If hunting occurs, increase the set 10.00        1.00      No      No      A      No      No     584H
                                       value.
                     AFR Gain
                                    If response is low, decrease the set
                                    value.
                                    Adjust the setting by 0.05 at a time,
                                    while checking the response.
                   Speed feed-
                   back detec-
                                    This parameter determines the rate
                   tion control
             N2-02                  of change for speed feedback detec- 0 to 2000 50 ms          No      No      A      No      No     585H
                   (AFR) time
                                    tion.
                   parameter
                   AFR Time
                   Speed feed-
                   back detec-      Increase the setting if overvoltage
                   tion control     (OV) failures occur at the comple-
             N2-03                                                        0 to 2000 750 ms       No      No      A      No      No     586H
                   (AFR) time       tion of acceleration or when the load
                   parameter 2      changes radically.
                   AFR Time 2
6-46
                                                                                                          Improving the Operation Performance
  Related Parameters
                      Name                                                                                                  Control Methods
                                                                                                     Change                                        MEMO-
       Param-                                                                                                               Open-           Closed- BUS
                                                                              Setting     Factory    during                         Closed-
        eter                                      Description                                                                loop            loop Regis-
                      Display                                                 Range       Setting    Opera-       V/f                 loop
       Number                                                                                                               Vector          Vector
                                                                                                      tion                           Vector          ter
                                                                                                                               1             (PM)
              Feed forward         Enables or disables the feed forward
              control              control.
        N5-01 selection                                                         0, 1         0         No         No         No      A      A     5B0H
              Feedfoward           0: Disabled
              Sel                  1: Enabled
              Motor accel-         Set the time required to accelerate
              eration time         the motor at the rated torque (T100)
                                   to the rated speed (Nr).
                                   J: GD2/4, P: Motor rated output
      * The factory settings depend on the Inverter capacity. The values for a 200 V class Inverter for 3.7 kW are given.
                                                                                                                                                             6
                                                                                                                                                           6-47
         Adjustments
                                                                     measure
                                                                                     apply
         Related Parameters
                          Name                                                                                   Control Methods
                                                                                                  Change                                MEMO-
              Param-                                                                                             Open-           Closed- BUS
                                                                             Setting    Factory   during                 Closed-
               eter                               Description                                                     loop            loop
                         Display                                             Range      Setting   Opera-   V/f             loop          Regis-
              Number                                                                                             Vector          Vector
                                                                                                   tion                   Vector          ter
                                                                                                                    1             (PM)
                     Motor rated                                             300         1380
               S2-01 speed            Sets the motor rated speed.             to                   No      A       No     No      No    6AEH
                                                                             1800        min-1
                     Rated min-1
                     Slip compen-
                     sation gain in   Sets the slip compensation gain in
                     motoring                                                 0.00
                                      motoring mode.
               S2-02                                                           to        0.70      Yes     A       A      No      No    6AFH
                     mode             It can be used to improve the level-    5.00
                     SlipComp         ing accuracy.
                     gainMot
                     Slip compen-
                     sation gain in   Sets the slip compensation gain in
                     regenerative     regenerative mode.                      0.00
               S2-03                                                           to        1.00      Yes     A       A      No      No    6B0H
                     mode             It can be used to improve the
                                                                              5.00
                     SlipComp         leveling accuracy.
                     gainGen
6-48
                                                                                            Improving the Operation Performance
  Adjustments
    The Slip compensation values can be set separately for motoring and regenerative operation. Before adjusting
    this function the general setup should have been done (Motor Setup, V/f pattern, Speeds, ASR settings etc.).
    To adjust the Slip compensation function do the following in motoring and regenerative mode:
      Set the motor speed in S2-01 if V/f control is used.
      Try to measure the actual motor speed during leveling.
      If the motor speed is lower than the leveling speed reference increase S2-02 in motoring mode or decrease
       S2-03 in regenerative mode.
      If the motor speed is higher than the leveling speed reference decrease S2-02 in motoring mode or increase
       S2-03 in regenerative mode.
 Field Forcing
    The field forcing function controls the motor flux and compensates the flux establishment delay of the motor.
    Thereby it improves the motor responsiveness to changes in the speed reference or the load.
    Field forcing is applied during all operation conditions except DC Injection.
    Using parameter d6-06 a field forcing limit can be applied. A setting of 100% is equal to the no-load current
    set in parameter E2-03.
                                                                                                                                            6
  Related Parameters
                    Name                                                                                Control Methods
                                                                                         Change                                 MEMO-
       Param-                                                                                           Open-            Closed- BUS
                                                                     Setting   Factory   during                  Closed-
        eter                               Description                                                   loop             loop
                   Display                                           Range     Setting   Opera-   V/f             loop           Regis-
       Number                                                                                           Vector           Vector
                                                                                          tion                   Vector           ter
                                                                                                           1              (PM)
              Field forcing
                            Enables or disables field forcing
              function
                            function.
        d6-03 selection                                               0, 1       0        No      No      A       A       No    2A2H
                            0: Disabled
              Field Force
                            1: Enabled
              Sel
                Field forcing Sets the upper limit for the excita-
                function      tion current applied by the field
                Limit         forcing function.
                               A setting of 100% is equal to the     100 to
        d6-06                                                                  400%       No      No      A       A       No    2A5H
                               motor no-load current.                 400
                FieldForce
                               Field forcing is active during all
                Limit
                               types of operation except DC Injec-
                               tion.
                                                                                                                                          6-49
        Adjusting the DC Injection Current
           The DC current injection is used in V/f and open-loop vector control in order to hold the motor when the brake
           is opened or closed.
         Related Parameters
                           Name                                                                                  Control Methods
                                                                                                  Change                                MEMO-
              Param-                                                                                             Open-           Closed- BUS
                                                                              Setting   Factory   during                 Closed-
               eter                                Description                                                    loop            loop
                          Display                                             Range     Setting   Opera-   V/f             loop          Regis-
              Number                                                                                             Vector          Vector
                                                                                                   tion                   Vector          ter
                                                                                                                    1             (PM)
                       DC injection Sets the DC injection braking cur-
                       braking cur- rent as a percentage of the Inverter
                       rent at start rated current.                            0 to
               S1-02                                                                     50%       No      A       A      No      No     681H
                                    DC excitation current in closed-loop       100
                       DC Inj I
                                    vector control changes according to
                       @start
                                    E2-03 setting.
                       DC injection Sets the DC injection braking cur-
                       braking cur- rent as a percentage of the Inverter
                       rent at stop rated current.                             0 to
               S1-03                                                                     50%       No      A       A      No      No     682H
                                       DC excitation current in closed-loop    100
                       DC Inj I
                                       vector control changes according to
                       @stop
                                       E2-03 setting.
                     DC injection
                     current gain at
                                       Used to set the DC injection gain         0
                     regenerative
               S1-17                   when Inverter is in the regenerative     to      100%       No      No      A      No      No     690H
                     operation
                                       mode.                                   400
                     DC Inj
                     gain@gen
                     DC injection
                     current gain at
                                       Used to set the DC injection gain         0
                     motoring
6
               S1-18                   when Inverter is in the motoring         to       20%       No      No      A      No      No     691H
                     operation
                                       mode.                                   400
                     DC Inj
                     gain@mot
6-50
                                                                                          Improving the Operation Performance
  Related Parameters
                    Name                                                                              Control Methods
                                                                                       Change                                MEMO-
       Param-                                                                                         Open-           Closed- BUS
                                                                   Setting   Factory   during                 Closed-
        eter                              Description                                                  loop            loop Regis-
                   Display                                         Range     Setting   Opera-   V/f             loop
       Number                                                                                         Vector          Vector
                                                                                        tion                   Vector          ter
                                                                                                         1             (PM)
                               0: Phase A leads with Forward Run
                PG rotation       Command. (Phase B leads with                 0
                                  Reverse Run Command)
        F1-05                                                       0, 1                No      No     No      Q      Q     384H
                               1: Phase B leads with Forward Run
                PG Rotation                                                    1
                                  Command. (Phase A leads with
                Sel                                                          (PM)
                                  Reverse Run Command)
              Output phase
                           Sets the output phase order.
              order
        S3-08              0: Output phase order is U-V-W           0,1        0        No      No     No      No     A     6C4H
              ExChg Phase
                           1: Output phase order is U-W-V
              Sel
IMPORTANT
                                                                                                                                     6-51
       Protective Functions
         Related Parameters
                          Name                                                                               Control Methods
                                                                                              Change                                MEMO-
              Param-                                                                                         Open-           Closed- BUS
                                                                          Setting   Factory   during                 Closed-
               eter                              Description                                                  loop            loop
                          Display                                         Range     Setting   Opera-   V/f             loop          Regis-
              Number                                                                                         Vector          Vector
                                                                                               tion                   Vector          ter
                                                                                                                1             (PM)
                     Stall preven- Selects the stall prevention during
                     tion selection running.
                     during run- 0: Disabled (Runs as set. With a
                     ning               heavy load, the motor may stall.)
               L3-05                                                         0 to 2     1      No      A       No     No      No     493H
                                     1: Deceleration using deceleration
                     StallP Run         time 1 (C1-02.)
                     Sel             2: Deceleration using deceleration
                                        time 2 (C1-04.)
                     Stall preven- Set the stall prevention during run-
                     tion level dur- ning operation current level as a per-
                     ing             centage of the Inverter rated current.
6
                     running         Effective when L3-05 is 1 or 2.
               L3-06                                                        30 to 200 150%     No      A       No     No      No     494H
                                     Usually changing this setting is not
                     StallP Run      necessary.
                     Level           Reduce the setting when the motor
                                     stalls.
         Precautions
           If the motor capacity is smaller than the Inverter capacity or the motor stalls when operating at the factory set-
           tings, lower the stall prevention level during operation.
         Setting Precautions
             Set the parameters as a percentage taking the Inverter rated current to be 100%.
             Do not increase the stall prevention level unnecessarily. An extremely high setting can reduce the Inverter
              lifetime. Also do not disable the function.
             If the motor stalls with the factory settings check the V/f pattern (E1-) and the motor setup (E2-).
             If the stall level has to be increased very much to get the elevator running, check the mechanical system or
              consider using a one size bigger Inverter.
6-52
                                                                                                                    Protective Functions
  Related Parameters
                     Name                                                                                 Control Methods
                                                                                         Change                                  MEMO-
       Param-                                                                                             Open-           Closed- BUS
                                                                     Setting   Factory   during                   Closed-
        eter                               Description                                                     loop            loop Regis-
                    Display                                          Range     Setting   Opera-   V/f               loop
       Number                                                                                             Vector          Vector
                                                                                          tion                     Vector          ter
                                                                                                             1             (PM)
              Operation     0: Stop (Operation follows the
              when fre-        frequency reference.)
              quency refer- 1: Operation at 80% speed
              ence is          continues. (At 80% of speed
        L4-05 missing          before the frequency reference          0,1         0      No      A           A          A     A     49DH
                               was lost)
                             Frequency reference is lost: Fre-
                 Ref Loss Sel
                             quency reference dropped over 90%
                             in 400 ms.
              Frequency      If the frequency reference loss func-
              reference at tion is enabled (L4-05=1) when the
              frequency ref- frequency reference gets lost, the
                                                                    0.0 to
        L4-06 erence loss    Inverter will run at a reduced fre-               80.0%      No      A           A          A     A     4C2H
                                                                   100.0%
                             quency reference determined by the
              Fref at Floss following formula:
                             Fref = Fref at time of loss  L4-06.
                                                                                                                                                6
  Setting Value (Multi-function Contact Output)
                                                                                                                  Control Methods
       Setting                                                                                                                      Closed-
                                                      Function                                                     Open- Closed-
       Value                                                                                                                         loop
                                                                                                        V/f         loop    loop
                                                                                                                                    Vector
                                                                                                                  Vector 1 Vector
                                                                                                                                     (PM)
         C       Loss of frequency reference (Effective when 1 is set for L4-05)                        Yes        Yes       Yes     Yes
                                                                                                                                              6-53
       Related Parameters
                        Name                                                                                 Control Methods
                                                                                              Change                                MEMO-
           Param-                                                                                            Open-           Closed- BUS
                                                                         Setting    Factory   during                 Closed-
            eter                               Description                                                    loop            loop
                       Display                                           Range      Setting   Opera-   V/f             loop          Regis-
           Number                                                                                            Vector          Vector
                                                                                               tion                   Vector          ter
                                                                                                                1             (PM)
                    Torque        0: Torque detection disabled.
                    detection     1: Car stuck detection only with
                    selection 1      speed agreement; operation
                                     continues (warning is output).
                                  2: Car stuck detected continuously
                                     during operation; operation
                                     continues
                                     (warning is output).
                                  3: Car stuck detection only with
                                     speed agreement; output stopped
                                     upon detection.
                                  4: Car stuck detected continuously
                                     during operation; output stopped
            L6-01                    upon detection.                      0 to 8      4        No      A       A       A       A    4A1H
                    Torq Det 1    5: Undertorque detection only with
                    Sel              speed agreement; operation
                                     continues (warning is output).
                                  6: Undertorque detected
                                     continuously during operation;
                                     operation continues
                                     (warning is output).
                                  7: Undertorque detection only with
                                     speed agreement; output stopped
                                     upon detection.
                                  8: Undertorque detected
                                     continuously during operation;
                                     output stopped upon detection.
                    Torque detec- Vector control: Motor rated torque is
                    tion level 1 set as 100%.
6           L6-02
                    Torq Det 1
                    Lvl
                                  V/f control: Inverter rated current is
                                  set as 100%.
                                                                         0 to 300   150%       No      A       A       A       A    4A2H
                    Torque detec-
                    tion time 1   Sets the overtorque/undertorque         0.0 to
            L6-03                                                                   10.0 s     No      A       A       A       A    4A3H
                    Torq Det 1    detection time.                          10.0
                    Time
                    Torque
                    detection
            L6-04   selection 2                                           0 to 8      0        No      A       A       A       A    4A4H
                    Torq Det 2
                    Sel
                    Torque detec-
                                  See L6-01 to L6-03 for a descrip-
                    tion level 2                                           0 to
            L6-05                 tion.                                             150%       No      A       A       A       A    4A5H
                    Torq Det 2                                             300
                    Lvl
                    Torque detec-
                    tion time 2                                           0.0 to
            L6-06                                                                    0.1 s     No      A       A       A       A    4A6H
                    Torq Det 2                                             10.0
                    Time
6-54
                                                                                                                   Protective Functions
L6-01 and L6-04 Set Values and Operator Display (JVOP-160 only)
  The relationship between alarms displayed on the digital operator when overtorque or undertorque is detected,
  and the set values in L6-01 and L6-04, is shown in the following table.
                                                                                                              Operator Display
     Set                                                                                                 Overtorque/    Overtorque/
                                                       Function
    Value                                                                                                Undertorque Undertorque
                                                                                                         Detection 1    Detection 2
         0       Overtorque/undertorque detection disabled.                                                                 
                 Overtorque/Car stuck detection only with speed agree; operation continues (warning is
         1                                                                                               OL3 flashes     OL4 flashes
                 output).
                 Overtorque/Car stuck detected continuously during operation; operation continues
         2                                                                                               OL3 flashes     OL4 flashes
                 (warning is output).
         3
                 Overtorque/Car stuck detection only with speed agree; output is stopped upon detec-
                 tion.
                                                                                                         OL3 lights up   OL4 lights up
                                                                                                                                             6
                 Overtorque/Car stuck detected continuously during operation; output is stopped upon
         4                                                                                               OL3 lights up   OL4 lights up
                 detection.
         5       Undertorque detection only with speed agree; operation continues (warning is output).   UL3 flashes     UL4 flashes
                 Undertorque detected continuously during operation; operation continues (warning is
         6                                                                                               UL3 flashes     UL4 flashes
                 output).
         7       Undertorque detection only with speed matching; output is stopped upon detection.       UL3 lights up   UL4 lights up
         8       Undertorque detected continuously during operation; output is stopped upon detection. UL3 lights up     UL4 lights up
                                                                                                                                           6-55
       Timing Charts
         Fig 6.20 and Fig 6.21 show the timing charts for overtorque and undertorque detection.
                                Motor current (output torque)
L6-02 or L6-05
                                                L6-03 or                          L6-03 or
               Overtorque detection 1 NO                                          L6-06
                                                L6-06
               or overtorque detection 2 NO
                              *Overtorque detection switch off bandwidth is approximately 10% of the Inverter rated output
                              current (or motor rated torque).
L6-02 or L6-05
                                             L6-03 or                            L6-03 or
               Undertorque detection 1 NO
6                                            L6-06                               L6-06
               or undertorque detection 2 NO
                             *Undertorque detection switch off bandwidth is approximately 10% of the Inverter rated output
                             current (or motor rated torque).
                                                            DC injection/
                                                             zero-servo
                                        speed
                             Inverter enable (D/I)
                               Up/Down (D/I)
                            Selected speed (D/I)
                                     Fault
                                                     Torque is higher
                                                     than L6-02
                                                                                 detect. time
                                                                                 L6-03
6-56
                                                                                                                             Protective Functions
  Related Parameters
                      Name                                                                                          Control Methods
                                                                                                     Change                                MEMO-
        Param-                                                                                                      Open-           Closed- BUS
                                                                                Setting    Factory   during                 Closed-
         eter                                    Description                                                         loop            loop Regis-
                      Display                                                   Range      Setting   Opera-   V/f             loop
        Number                                                                                                      Vector          Vector
                                                                                                      tion                   Vector          ter
                                                                                                                       1             (PM)
                  Forward drive
                  torque limit
         L7-01                                                                                        No      No      A        A          A    4A7H
                  Torq Limit
                  Fwd
                                  Sets the torque limit value as a per-
                  Reverse drive
                                  centage of the motor rated torque.
                  torque limit
         L7-02                    Four individual regions can be set.                                 No      No      A        A          A    4A8H
                  Torq Limit
                                                  Output torque
                  Rev
                                                            Positive torque
                  Forward
                                                                                0 to 300   200%
                  regenerative                                      No. of
                                             Regenera-              motor
         L7-03    torque limit     Reverse   tive state             rotations                         No      No      A        A          A    4A9H
                  Torq Lmt                                Regenera- Forward
                                                          tive state
                  Fwd Rgn
                  Reverse                                 Negative torque
                  regenerative
         L7-04    torque limit                                                                        No      No      A        A          A    4AAH
                  Torq Lmt Rev
                  Rgn
                  Torque limit
         L7-06
                  time parame-
                  ter
                                  Sets the torque limit integration time
                                  parameter
                                                                                 5 to
                                                                                10000
                                                                                           200 ms     No      No      A        No         A    4ACH       6
                  Torque Limit
                  Time
                  Torque Limit    Sets the torque limit operation dur-
                  Operation       ing acceleration and deceleration.
                  during accel/   0: P-control (I control is added at
                  decel              parameter speed operation)
                                  1: I-control
                               Normally changing this setting is
         L7-07                 not necessary.                                     0, 1       0        No      No      A        No         A    4C9H
                  Torque Limit If the torque limitation accuracy
                  Sel          during accel/decel. has preference, I
                               control should be selected. This may
                               result in an increased accel./decel.
                               time and speed deviations from the
                               reference value.
                                                                                                                                                        6-57
         Setting the Torque Limit Using Parameters
           Using L7-01 to L7-04, four torque limits in the following directions can be set individually: Forward drive,
           reverse inverter, forward regenerative and reverse regenerative (see Fig 6.23)
                                                                 Output torque
                                                                                 Forward
                                                       Reverse
                                                                                  drive
                                                     regenerative
                                                                                             Output speed
                                                                             Forward
                                                       Reverse
                                                                           regenerative
                                                        drive
         Setting Precautions
             When the output torque reaches the torque limit, control and compensation of the motor speed is disabled
6             to prevent the output torque from exceeding the torque limit. The torque limit has the priority.
             The torque limit accuracy is 5% at an output frequency of 10 Hz or above. When output frequency is
              lower than 10 Hz, the accuracy is lower.
         Related Parameters
                           Name                                                                                      Control Methods
                                                                                                      Change                                MEMO-
              Param-                                                                                                 Open-           Closed- BUS
                                                                                  Setting   Factory   during                 Closed-
               eter                               Description                                                         loop            loop
                          Display                                                 Range     Setting   Opera-   V/f             loop          Regis-
              Number                                                                                                 Vector          Vector
                                                                                                       tion                   Vector          ter
                                                                                                                        1             (PM)
                       OH1
                       detection     0: Alarm triggered if the internal
                     during cool-       cooling fan fails.
               L8-32                                                                0,1       1        No      A       A       A       A    4E2H
                     ing fan failure 1: Fault situation detected if the
                     OH1                cooling fan fails.
                     Detect Sel
6-58
                                                                                                             Protective Functions
  The following table describes the operation of the motor and the display of the Digital Operator in accordance
  with the settings of the L8-32 if a cooling fan fault occurred.
            Setting                                                                                         Multi-function Contact
                                 Fault                   Digital Operator          Motor Operation
            Value                                                                                                   Output
                      Cooling Fin Overheating        OH1 (lit)                Coast to a stop             Fault
               0
                      Inverters Cooling Fan Fault   FAN (blink)              Continue operation          Minor fault
                      Cooling Fin Overheating        OH (lit)                 Coast to a stop             Fault
               1
                      Inverters Cooling Fan Fault   OH1 (lit)                Coast to a stop             Fault
  Refer to Multi-function Contact Outputs: H2 in Chapter 5, Parameters for more details on multi-function con-
  tact output.
                        If L8-32 is set to 0, be sure to set H2-01 to H2-03 multi-function contact outputs to 10 (minor fault) or to
                        3D (Inverters cooling fan fault.) If a cooling fan fault occurs, stop the Inverter immediately and replace
                        the cooling fan. If the Inverter continues to run while a cooling fan fault occurs, the Inverters cooling
       IMPORTANT        ability will be affected and the Inverters internal temperature will increase and shorten the Inverters
                        life.
                        During a cooling fan fault, the cooling fan stops for about 3 seconds every minute (interval operation.)
                                                                                                                                        6-59
         Fault Detection
Alarm Detection
6-60
                                                                                                                                 Protective Functions
                                                                                                                                                           6-61
         Setting Motor Protection Operation Time (L1-02)
           The motor protection operation time is the time for that the motor can handle a 150% overload when it was
           running with the rated load before (i.e. operating temperature was reached before applying the 150% over-
           load). Set the motor protection operation time in L1-02. The factory setting is 60 sec.
           Fig 6.24 shows an example of the characteristics of the electronic thermal protection operation time (L1-02 =
           1.0 min., operation at 50 Hz, general-purpose motor characteristics, when L1-01 is set to 1)
                              
                               
                               
                                                                               Cold start
                               
                             
                                                                                Hot start
                             
                                                                               Motor current (%)
                                                               
                                                                               E2-01 is set to 100%
         Related Parameters
                          Name                                                                                    Control Methods
                                                                                                   Change                                MEMO-
              Param-                                                                                              Open-           Closed- BUS
                                                                               Setting   Factory   during                 Closed-
               eter                                  Description                                                   loop            loop
                          Display                                              Range     Setting   Opera-   V/f             loop          Regis-
              Number                                                                                              Vector          Vector
                                                                                                    tion                   Vector          ter
                                                                                                                     1             (PM)
                       SE2 detec-       Used to set the delay time for the
                       tion delay       detection of a SE2 fault.
                       time             At the time S1-06 + S1-14 after the      0
                                        Fwd/Rev command was given the           to
               S1-14                                                                  200 ms        No      A       A       A      No    68DH
                                        output current is measured. If it is (S1-04 -
                       SE2 det T        below 25% of the no-load current      S1-06)
                                        (E2-03) setting a SE2 fault will be
                                        output.
                       SE3 detec-       Used to set the delay time for the
                       tion delay       detection of a SE3 fault.
                       time             At the time S1-15 after the fwd/rev
                                                                                  0
               S1-15                    command was given, the Inverter          to      200 ms     No      A       A       A      No    68EH
                                        starts to observe the output current    5000
                       SE3 det T        continuously. If it falls below 25%
                                        of the no-load current (E2-03) set-
                                        ting a SE3 will be output.
6-62
                                                                                        Protective Functions
                                                                                                               6-63
       Inverter Protection
         Related Parameters
                              Name                                                                                                 Control Methods
                                                                                                             Change                                       MEMO-
                Param-                                                                                                             Open-           Closed- BUS
                                                                                      Setting    Factory     during                        Closed-
                 eter                                    Description                                                                loop            loop
                              Display                                                 Range      Setting     Opera-       V/f                loop          Regis-
                Number                                                                                                             Vector          Vector
                                                                                                              tion                          Vector          ter
                                                                                                                                      1             (PM)
                          Overheat         Sets the detection temperature for
                          pre-alarm        the Inverter overheat detection pre-
                          level            alarm in C.
                L8-02                                                                50 to 130 75C*           No          A         A       A       A    4AEH
                                          The pre-alarm detects when the
                          OH Pre-
                                          heatsink temperature reaches the set
                          Alarm Lvl
                                          value.
                          Operation       Sets the operation when an Inverter
                          selection after overheat pre-alarm occurs.
                          overheat pre- 0: Decelerate to stop using the
                          alarm             deceleration time C1-02.
                                           1: Coast to stop
                L8-03                      2: Fast stop in fast-stop time C1-09.       0 to 3        3         No          A         A       A       A    4AFH
6                         OH Pre-
                          Alarm Sel
                                           3: Continue operation (Monitor
                                              display only.)
                                           A fault will be given in setting 0 to 2
                                           and a minor fault will be given in
                                           setting 3.
* The factory settings depend on the Inverter capacity. The values for a 200 V class Inverter of 3.7 kW are given.
6-64
                                                                                                                Inverter Protection
  Related Parameters
                    Name                                                                                Control Methods
                                                                                         Change                                MEMO-
       Param-                                                                                           Open-           Closed- BUS
                                                                     Setting   Factory   during                 Closed-
        eter                                Description                                                  loop            loop Regis-
                   Display                                           Range     Setting   Opera-   V/f             loop
       Number                                                                                           Vector          Vector
                                                                                          tion                   Vector          ter
                                                                                                           1             (PM)
                Output open- 0: Disabled
                phase protec- 1: Enabled, 1 Phase Observation
                tion selection 2: Enabled, 2 and 3 Phase
                                  Observation
                               An output open-phase is detected at
                               less than 5% of Inverter rated cur-
        L8-07                                                        0 to 2      2        No      A       A      A      A     4B3H
                               rent.
                Ph Loss Out
                Sel            When the applied motor capacity is
                               small compared to the Inverter
                               capacity, the detection may not
                               work properly and should be dis-
                               abled.
                Output phase
                loss detection Sets the detection time of output     0.0 to
        L8-20                                                                   0.2 s     No      A       A      A      A     4C0H
                time           phase loss detection (LF.)             2.0
                Pha loss det T
Related Parameters
       Param-
                    Name
                                                                     Setting   Factory
                                                                                         Change
                                                                                         during
                                                                                                        Control Methods
                                                                                                        Open-
                                                                                                                Closed-
                                                                                                                               MEMO-
                                                                                                                        Closed- BUS
                                                                                                                                         6
        eter                                Description                                                  loop            loop Regis-
                   Display                                           Range     Setting   Opera-   V/f             loop
       Number                                                                                           Vector          Vector
                                                                                          tion                   Vector          ter
                                                                                                           1             (PM)
              Ground fault
              detection
                           0: Disabled
        L8-09 selection                                               0, 1       1        No      A       A      A      A     4B5H
                           1: Enabled
              Ground Fault
              Sel
  Precautions
      It is not recommended to disable this function.
      A Ground Fault can also be detected if the magnetic contactors at the Inverter output are opened when the
       output is still active. Therefore, to prevent false Ground Fault detection check the sequence and make sure,
       that the output is switched of or baseblocked before opening the magnetic contactors.
                                                                                                                                       6-65
        Cooling Fan Control
           This function controls the fan which is mounted to the Inverters heatsink.
         Related Parameters
                          Name                                                                               Control Methods
                                                                                              Change                                MEMO-
              Param-                                                                                         Open-           Closed- BUS
                                                                         Setting    Factory   during                 Closed-
               eter                              Description                                                  loop            loop
                         Display                                         Range      Setting   Opera-   V/f             loop          Regis-
              Number                                                                                         Vector          Vector
                                                                                               tion                   Vector          ter
                                                                                                                1             (PM)
                     Cooling fan     Set the ON/OFF control for the
                     control         cooling fan.
               L8-10 selection       0: ON when Inverter is                0, 1       0        No      A       A       A       A    4B6H
                     Fan On/Off         running only
                     Sel             1: ON whenever power is ON
                     Cooling fan
                                     Set the time in seconds to delay
                     control delay
                                     turning OFF the cooling fan after
               L8-11 time                                                0 to 300    60 s      No      A       A       A       A    4B7H
                                     the Inverter Stop Command is
                     Fan Delay
                                     given. (Valid only if L8-10 = 0)
                     Time
6-66
                                                                                                                       Inverter Protection
  Related Parameters
                   Name                                                                                        Control Methods
                                                                                             Change                                   MEMO-
       Param-                                                                                                  Open-           Closed- BUS
                                                                       Setting    Factory    during                    Closed-
        eter                                  Description                                                       loop            loop Regis-
                  Display                                              Range      Setting    Opera-    V/f               loop
       Number                                                                                                  Vector          Vector
                                                                                              tion                      Vector          ter
                                                                                                                  1             (PM)
              Ambient
              temperature
        L8-12                  Sets the ambient temperature.           45 to 60   45 C          No        A     A      A      A     4B8H
              Ambient
              Temp
    At high ambient temperatures an output current derating has to be considered. The derating depends on the
    ambient temperature. The derating curve is shown in Fig 6.25. To ensure a safe Inverter protection at high
    ambient temperatures, always set parameter L8-15 to the actual ambient temperature.
100
80
                  Output current 60
                    in % of the
                   rated current
                                     40
20
                                      0
                                          0          10         20           30             40        50          60
                                                                       Temperature (C)
                                      Fig 6.25 Ambient Temperature Derating Curve                                                               6
  Related Parameters
                   Name                                                                                        Control Methods
                                                                                             Change                                   MEMO-
       Param-                                                                                                  Open-           Closed- BUS
                                                                       Setting    Factory    during                    Closed-
        eter                                  Description                                                       loop            loop Regis-
                  Display                                              Range      Setting    Opera-    V/f               loop
       Number                                                                                                  Vector          Vector
                                                                                              tion                      Vector          ter
                                                                                                                  1             (PM)
              Over acceler-    Sets the maximum car acceleration
              ation detec-     value. If the acceleration rate is
                                                                        0.0 to
        S3-16 tion level       higher than this value, the Inverter                 1.5          No    No       No      No     A     6CCH
                                                                         50.0
              Over Acc Det     trips with an over acceleration fault
              Lvl              (DV6).
              Over acceler-
              ation deceler-   Sets the time for which an over
              ation time       acceleration must be detected before 0.000 to
        S3-17                                                                0.050 s             No    No       No      No     A     6CDH
              parameter        the Inverter stops with an over       5.000
              Over Acc Det     acceleration fault (DV6).
              Fil
                                                                                                                                              6-67
                         Name                                                                                     Control Methods
                                                                                                   Change                                MEMO-
              Param-                                                                                              Open-           Closed- BUS
                                                                               Setting   Factory   during                 Closed-
               eter                                Description                                                     loop            loop
                         Display                                               Range     Setting   Opera-   V/f             loop          Regis-
              Number                                                                                              Vector          Vector
                                                                                                    tion                   Vector          ter
                                                                                                                     1             (PM)
                     Over acceler-
                                     Selects wether the over acceleration
                     ation detec-
                                     detection is always active or during
                     tion method
               S3-18                 run only.                                   0,1       0        No      No      No     No       A    6CEH
                     selection
                                     0: Detection during power on
                     Over Acc Det
                                     1: Detection during run only
                     Sel
Setting parameter S3-16 to 0.0 m/s disables the over acceleration detection.
                                It is imperative to set up the parameters S3-13 (Traction sheave diameter) and S3-14 (Roping) in
                                order to make this function working properly.
IMPORTANT
6 Speed
Motor speed
                                                                                                     Time
                                               C
6-68
                                                                                                                    Input Terminal Functions
    The multi-function inputs can be set to several functions using the H1-01 to H1-05 parameters (terminal S3 to
    S7 function selection). These following section describes the input functions not mentioned in any other sec-
    tion.
  Related Parameters
                      Name                                                                                        Control Methods
                                                                                                   Change                                MEMO-
       Param-                                                                                                     Open-           Closed- BUS
                                                                            Setting      Factory   during                 Closed-
        eter                                   Description                                                         loop            loop Regis-
                     Display                                                Range        Setting   Opera-   V/f             loop
       Number                                                                                                     Vector          Vector
                                                                                                    tion                   Vector          ter
                                                                                                                     1             (PM)
                 Terminal S3
                 function
                                                                                         24 (80)
        H1-01    selection       Multi-function input 1                                             No      A       A      A      A     400H
                                                                                            *
                 Terminal S3
                 Sel
                 Terminal S4
                 function
                                                                                         14 (84)
        H1-02    selection       Multi-function input 2                                             No      A       A      A      A     401H
                                                                                            *
                 Terminal S3
                 Sel
                 Terminal S5
                 function
                 selection                                                               3 (81)
        H1-03                    Multi-function input 3                    0 to 88                  No      A       A      A      A     402H
                                                                                            *
                 Terminal S3
                 Sel
                 Terminal S6
                 function
                 selection                                                               4 (83)
        H1-04                    Multi-function input 4                                             No      A       A      A      A     403H
                                                                                            *
                 Terminal S3
                 Sel
                 Terminal S7
                 function
                                                                                                                                                   6
                                                                                          6 (F)
        H1-05    selection       Multi-function input 5                                             No      A       A      A      A     404H
                                                                                            *
                 Terminal S3
                 Sel
   Hardware Baseblock
    When hardware baseblock is activated, the power supply of the IGBT driver circuit is cut off and the motor
    starts to coast. If the baseblock command is cleared, the Inverter output operation is resumed.
    To use this baseblock function the multi-function contact input S8 must be used. The input is a NC input, i.e. if
    terminal S8 is open, the Inverter is baseblocked.
   Software Baseblock
    When software baseblock is used, the Inverter output is cut by a software function. If the baseblock command
    is cleared, the Inverter output operation is resumed.
    To use this baseblock function one of the multi-function contact inputs must be set to baseblock, i.e. one of the
    parameters H1-01 to H1-05 (multi-function contact input terminal S3 to S7 function selection) must be set to 8
    or 9 (Baseblock command NO/NC). The input can be used with a NC as well as with a NO contact.
                                                                                                                                                 6-69
         Multi-function Inputs (H1-01 to H1-05)
                                                                                                                             Control Methods
                                                                                                                            Open-                    Closed-
             Set                                                                                                                      Closed-
                                                          Function                                                           loop                     loop
            Value                                                                                               V/f                     loop
                                                                                                                            Vector                   Vector
                                                                                                                                       Vector
                                                                                                                               1                      (PM)
               8     External baseblock NO (NO contact: Baseblock at ON)                                       Yes            Yes           Yes        Yes
9 External baseblock NC (NC contact: Baseblock at OFF) Yes Yes Yes Yes
6-70
                                                                                                             Input Terminal Functions
  Related Parameters
                    Name                                                                                   Control Methods
                                                                                          Change                                   MEMO-
        Param-                                                                                             Open-            Closed- BUS
                                                                      Setting   Factory   during                    Closed-
         eter                              Description                                                      loop             loop
                    Display                                           Range     Setting   Opera-   V/f               loop           Regis-
        Number                                                                                             Vector           Vector
                                                                                           tion                     Vector           ter
                                                                                                              1              (PM)
               Timer func-     Sets the timer function output ON-
               tion ON-        delay time (dead band) for the timer
                                                                      0.0 to
         b4-01 delay time      function input, in 1-second units.                0.0 s     No      A            A    A       A     1A3H
                                                                      3000.0
                 Delay-ON      Enabled when a timer function is
                 Timer         set in H1- or H2-.
               Timer func-     Sets the timer function output OFF-
               tion OFF-       delay time (dead band) for the timer
                                                                      0.0 to
         b4-02 delay time      function input, in 1-second units.                0.0 s     No      A            A    A       A     1A4H
                                                                      3000.0
                 Delay-OFF     Enabled when a timer function is
                 Timer         set in H1- or H2-.
      Set-
                                                                                                          Control Methods
                                                                                                         Open-
                                                                                                                   Closed-
                                                                                                                                 Closed-       6
      ting                                  Function                                                      loop                    loop
                                                                                             V/f                     loop
     Value                                                                                               Vector                  Vector
                                                                                                                    Vector
                                                                                                            1                     (PM)
       18    Timer function input                                                            Yes          Yes         Yes          Yes
  Setting Example
    When the timer function input is ON for longer than b4-01, the timer output function is turned ON. When the
    timer function input is OFF for longer than b4-02, the timer output function is turned OFF. An example of
    timer function operation is given in the following diagram.
                                                                                                                                             6-71
        Magnetic Contactor Answer Back Detection
           The magnetic contactors can be observed using the magnetic contactor answer back function. Therefore an
           auxiliary contact of the magnetic contactors must be connected to a multi-function contact input which is set
           to for this function
           (H1-=86). If the magnetic contactor close command is set and no answer back signal comes from the
           magnetic contactor, the Inverter detects a SE1 fault (see below).
6                                            Speed
                                            Up/Down
                                        Speed selection
                                     Inverter enable(D/I)
                                Magnetic contactor control (D/O)
6-72
                                                                                                        Output Terminal Functions
   The multi-function contact outputs can be set to several functions using the H2-01 to H2-03 parameters (ter-
   minal M1 to M6 function selection). These functions are described in the following section.
 Related Parameters
                  Name                                                                                  Control Methods
                                                                                         Change                                MEMO-
      Param-                                                                                            Open-           Closed- BUS
                                                                     Setting   Factory   during                 Closed-
       eter                              Description                                                     loop            loop Regis-
                  Display                                            Range     Setting   Opera-   V/f             loop
      Number                                                                                            Vector          Vector
                                                                                          tion                   Vector          ter
                                                                                                           1             (PM)
             Terminal M1-
             M2 function
                             Multi-function contact
       H2-01 selection                                               0 to 47     40        No     A        A       A    A     40BH
                             output 1
             Term
             M1-M2 Sel
             Terminal M3-
             M4 function
                             Multi-function contact
       H2-02 selection                                               0 to 47     41        No     A        A       A    A     40CH
                             output 2
             Term
             M3-M4 Sel
             Terminal M5-
             M6 function
                             Multi-function contact
       H2-03 selection                                               0 to 47      6        No     A        A       A    A     40DH
                             output 3
             Term
             M5-M6 Sel
Output frequency
                                                                                                                                       6-73
       Zero-speed (Setting: 1)
* The zero-speed Level depends on the control method. It is 0.1 Hz for closed-loop vector, 0.5 Hz for open-loop vector and 1.2 Hz for V/f control.
6-74
                                                                                                              Output Terminal Functions
                                                                                                                                             6
                 ON                                The output frequency is higher than the zero-speed level.
                          Up/Down command
                             Baseblock Input
                             (Term BB and BB1)
                                 BB Monitor 1
                                 BB Monitor 2
                                                                                                                                           6-75
        Magnetic Position Detection Status Signal
           When running a permanent magnet motor without a PG-F2 option card, an external braking sequence needs to
           be set up if not using the recommended braking sequence. This will ensure that the brake does not get released
           when the magnetic position detection status signal opens.
           The magnetic pole detection status switch is open when the unit is powered up. The three types of conditions
           that will trigger the magnetic position detection process are provided below.
           The magnetic position detection signal will close once the process is complete.
Condition 1: First time operating the Inverter after the power is switched on.
Run command
                              Magnetic position
                              detection complete
                                                          Magnetic position
                                                          detection process
                                                          (approx. 1.5 s)*
Fault occurring
6 Run command
                      Magnetic position
                      detection complete
                                                                               Magnetic position
                                                                               detection process
                                                                               (approx. 1.5 s)*
           Condition 3: Operation after the setting value of parameter N8-35 has been changed.
                                                    N8-35 changed
                                  Run command
                               Magnetic position
                               detection complete
                                                                        Magnetic position
                                                                        detection process
                                                                        (approx. 1.5 s)*
6-76
                                                                                                            Motor and V/f Pattern Setup
  Related Parameters
                    Name                                                                                     Control Methods
                                                                                             Change                                 MEMO-
       Param-                                                                                                Open-           Closed- BUS
                                                                        Setting    Factory   during                  Closed-
        eter                                Description                                                       loop            loop Regis-
                   Display                                              Range      Setting   Opera-   V/f              loop
       Number                                                                                                Vector          Vector
                                                                                              tion                    Vector          ter
                                                                                                                1             (PM)
                Motor rated    Sets the motor rated current in
                current        Amps.
                            This set value will become the refer- 1.75 to
                                                                                   14.00 A
        E2-01               ence value for motor protection and 35.00                         No      Q        Q      Q      No    30EH
                Motor Rated                                                          *2
                            torque limits.                          *1
                FLA
                            This parameter is an input data for
                            autotuning.
                Motor rated Sets the motor rated slip.
                slip        This set value will become the refer-
                                ence value for the slip compensa-       0.00 to    2.73 Hz
        E2-02                                                                                 No      Q        Q      Q      No    30FH
                Motor Rated tion.                                        20.00        *2
                Slip            This parameter is automatically set
                                during autotuning.
                Motor no-
                                Sets the motor no-load current.         0.00 to
                load current                                                       4.50 A
        E2-03                   This parameter is automatically set      13.99                No      Q        Q      Q      No    310H
                No-Load Cur-                                                         *2
                                during autotuning.                        *3
                rent
                Number of
                                                                                                                                              6
                                Sets the number of motor poles.
                motor poles
        E2-04                   This value is an input data for auto-   2 to 48    4 poles    No      No      No      Q      No    311H
                Number of
                                tuning.
                Poles
                Motor line-to- Sets the motor phase-to-phase resis-
                line resistance tance.                                   0.000
                                                                               0.771 
        E2-05                                                              to                 No      Q        Q      Q      No    312H
                Term Resis- This parameter is automatically set                   *2
                                                                        65.000
                tance           during autotuning.
                Motor leak      Sets the voltage drop due to motor
                inductance      leakage inductance as a percentage
                                of the motor rated voltage.              0.0 to    19.6%
        E2-06                                                                                 No      No       A      A      No    313H
                Leak Induc-                                               40.0       *2
                                This parameter is automatically set
                tance
                                during autotuning.
                Motor iron
                                Sets the motor iron saturation coef-
                saturation
                                ficient at 50% of magnetic flux.        0.00 to
        E2-07   coefficient 1                                                       0.50      No      No       A      A      No    314H
                                This parameter is automatically set      0.50
                Saturation
                                during rotating autotuning.
                Comp1
                Motor iron
                                Sets the motor iron saturation coef-
                saturation
                                ficient at 75% of magnetic flux.        E2-07 to
        E2-08   coefficient 2                                                       0.75      No      No       A      A      No    315H
                                This parameter is automatically set       0.75
                Saturation
                                during rotating autotuning.
                Comp2
                                                                                                                                            6-77
                            Name                                                                                                                                   Control Methods
                                                                                                                                       Change                                             MEMO-
             Param-                                                                                                                                                Open-           Closed- BUS
                                                                                                        Setting        Factory         during                              Closed-
              eter                                              Description                                                                                         loop            loop
                            Display                                                                     Range          Setting         Opera-            V/f                 loop          Regis-
             Number                                                                                                                                                Vector          Vector
                                                                                                                                        tion                                Vector          ter
                                                                                                                                                                      1             (PM)
                    Motor iron
                    loss for torque
                                                                                                         0 to           112 W
              E2-10 compensation           Sets motor iron losses.                                                                        No             No           No     No     No     317H
                                                                                                        65535             *2
                    Tcomp Iron
                    Loss
                    Motor rated            Sets the rated output power of the
                    output power           motor.                                                       0.00 to 3.70 kW
              E2-11                                                                                                                       No              Q            Q     Q      No     318H
                    Mtr Rated              This parameter is an input data for                          650.00     *2
                    Power                  autotuning.
                    Motor iron
                    saturation
                                           This parameter is automatically set                          1.30 to
              E2-12 coefficient 3                                                                                        1.30             No             No            A     A      No     328H
                                           during rotating autotuning.                                   1.60
                    Saturation
                    Comp3
         * 1. The setting range is from 10% to 200% of the Inverter rated output current. The value for a 200 V class Inverter for 3.7 kW is given.
         * 2. The factory settings depend on the Inverter capacity. The values for a 200 V class Inverter for 3.7 kW are given.
         * 3. The setting ranges depend on the Inverter capacity. The values for a 200 V class Inverter of 3.7 kW are given.
6 120
6-78
                                                                                                Motor and V/f Pattern Setup
 Autotuning
   Autotuning sets motor parameters automatically. Therefore some motor data which are usually written at the
   nameplate must be input and the autotuning has to be performed.
                    1. If the magnetic contactors are controlled by the Inverter, they will be closed during autotuning. If the
                       magnetic contactors are controlled by an external controller, make sure to close the contacts during
                       autotuning.
                    2. Make sure to close the baseblock contact during autotuning. Otherwise the autotuning can not be
     IMPORTANT
                       started and will terminate with a minor fault.
                    3. For rotating autotuning make sure that the brake is open during autotuning.
                    4. Never do rotating autotuning with the ropes installed.
                    Use this tuning mode only, if the motor can rotate freely which means that the ropes have to
                    be removed. The gearbox can remain connected to the motor.
IMPORTANT
                        1. Power will be supplied to the motor when stationary autotuning is performed even though the
                           motor will not turn. Do not touch the motor until autotuning has been completed.
                        2. When performing stationary autotuning connected to a conveyor or other machine, ensure that the
        IMPORTANT          holding brake is not activated during autotuning.
                                                                                                                                  6-79
        Non-rotating Autotuning for Line-to-Line Resistance (T1-01 = 2)
         Non-rotating autotuning for line-to-line resistance can be used in any control method. It is the only possible
         autotuning for V/f control.
         To perform autotuning in V/f control, set T1-02 (Motor rated power) and T1-04 (Motor rated current) and then
         press the RUN key on the Digital Operator. The Inverter supplies power to the motor for approximately 20
         seconds to measure the motor line-to-line resistance and cable resistance. The motor does not turn during this
         autotuning.
                                 1. Power will be supplied to the motor when stationary autotuning 1 is performed even though the
                                    motor will not turn. Do not touch the motor until autotuning has been completed.
                                 2. When performing stationary autotuning 1 connected to a conveyor or other machine, ensure that
             IMPORTANT              the holding brake is not activated during autotuning.
6           turn. Do not touch the motor until autotuning has been completed.
           To cancel autotuning, press the STOP key on the Digital Operator.
           Do not to rotating autotuning with the ropes installed.
                                                                                        T1-03
                         T1-05 = Base frequency from motor nameplate  -----------------------------------------------
                                                                       Motor rated voltage
6-80
                                                                                                      Motor and V/f Pattern Setup
  3. Perform autotuning.
  After the completion of autotuning, set E1-04 (Max. output frequency) to the base frequency from the motors
  nameplate.
                                Output voltage
                      Rated voltage
                      from motor
                      name plate
T1-03
                                  0                                                       Output frequency
                                                 Base frequency from           Base frequency
                                                                     x T1-03
                                                 motor name plate              from motor name
                                                 Rated voltage from motor      plate
                                                 name plate
Fig 6.29 Motor Base Frequency and Inverter Input Voltage Setting
  When speed precision is required at high speeds (i.e., 90% of the rated speed or higher), set T1-03 (Motor
  rated voltage) to the input power supply voltage  0.9. In this case at high speeds the output current will
  increase as the input power supply voltage is reduced. Be sure to provide sufficient margin in the Inverter cur-
  rent.
                                                                                                                                    6-81
       Parameter Settings for Autotuning
         The following parameters must be set for autotuning.
                               Name                                                                                                Control Methods
                                                                                                              Change                                      MEMO-
                  Param-                                                                                                           Open-           Closed- BUS
                                                                                        Setting    Factory    during                       Closed-
                   eter                                   Description                                                               loop            loop
                               Display                                                  Range      Setting    Opera-        V/f              loop          Regis-
                  Number                                                                                                           Vector          Vector
                                                                                                               tion                         Vector          ter
                                                                                                                                      1             (PM)
                           Autotuning       Sets the autotuning mode.
                           mode selec-   0: Rotational autotuning                       0 to 2        1*
                           tion          1: Stationary autotuning
                  T1-01                                                                                          No        Yes       Yes       Yes       Yes        701H
                                         2: Stationary autotuning for line-to-
                           Tuning Mode                                                    0.4          4
                                            line resistance only
                           Sel                                                           (PM)        (PM)
                                         4:Encoder offset tuning
                           Motor output
                           power         Sets the output power of the motor             0.00 to 3.70 kW
                  T1-02                                                                                          No        Yes       Yes       Yes       No         702H
                           Mtr Rated     in kilowatts.                                  650.00     *2
                           Power
                           Motor rated                                                    0 to
                                                                                                   190.0 V
                  T1-03    voltage       Sets the base voltage of the motor.             255.0                   No         No       Yes       Yes       No         703H
                                                                                                     *3
                           Rated Voltage                                                   *3
                           Motor rated
                           current                                                      1.75 to
                                                                                                   14.00 A
                  T1-04                  Sets the base current of the motor.             35.00                   No        Yes       Yes       Yes       No         704H
                           Rated                                                                     *2
                                                                                          *4
                           Current
                           Motor rated
                           frequency                                                      0 to
                                         Sets the rated frequency of the
                  T1-05                                                                  120.0     60.0 Hz       No         No       Yes       Yes       No         705H
                           Rated Fre-    motor.
                                                                                           *5
                           quency
                           Number of
                           motor poles                                                  2 to 48
                  T1-06                  Sets the number of motor poles.                           4 poles       No         No       Yes       Yes       No         706H
                           Number of                                                     poles
                           Poles
                           Motor base
                                                                                         0 to       1450
6
                  T1-07    speed         Sets the base speed of the motor.                                       No         No       Yes       Yes       No         707H
                                                                                        24000       min-1
                           Rated Speed
                           Number of
                           PG pulses     Sets the number of PG pulses per                0 to 600 PPR
                  T1-08                                                                                          No         No       No        Yes       No         708H
                           PG Pulses/    revolution.                                    60000    *2
                           Rev
                           No load cur-
                           rent                                                         0.0 to
                                                                                                     4.05
                  T1-09                  Sets the no load current of motor.             35.00                    No         No       Yes       Yes       No         709H
                           No load cur-                                                            (E2-03)
                                                                                          *5
                           rent
         *   1.   Set T1-02 and T1-04 when 2 is set for T1-01. For V/f control a set value 2 is possible only.
         *   2.   The factory settings depend on the Inverter capacity. The values provided are for a 200 V class Inverter for 3.7 kW and when o2-09 is set to 0.
         *   3.   These are values for a 200 V class Inverter. Values for a 400 V class Inverter are double.
         *   4.   The setting range is from 10% to 200% of the Inverter rated output current. The value for a 200 V class Inverter for 0.4 kW is given.
         *   5.   The factory settings depend on the Inverter capacity. The values for a 200 V class Inverter for 3.7 kW are given.
6-82
                                                                                                                        Motor and V/f Pattern Setup
  Related Parameters
                       Name                                                                                             Control Methods
                                                                                                Change                                          MEMO-
        Param-                                                                           Fac-                           Open-            Closed- BUS
                                                                                Setting          during                          Closed-
         eter                                      Description                           tory                            loop             loop
                      Display                                                   Range           Opera-           V/f              loop           Regis-
        Number                                                                          Setting                         Vector           Vector
                                                                                                  tion                           Vector           ter
                                                                                                                           1              (PM)
                   Input volt-
                   age setting      Sets the Inverter input voltage. This       155 to      200
         E1-01                      setting is used as a reference value         255       VAC        No         Q            Q   Q       Q      300H
                   Input            for protection functions.                     *1       *1 *4
                   Voltage
                   Max. output                                                             60.0
                                                                                0.0 to
                   frequency                                                                Hz
                                                                                120.0
                   (FMAX)                                                                   *4
         E1-04                                                                              96        No         Q            Q   Q       Q      303H
                                                                                 20 to
                   Max Fre-
                                                                                 3600      min-1
                   quency                                                        (PM)      (PM)
                                                                                            *5
               Max. voltage                                                     0.0 to     200.0
         E1-05 (VMAX)                                                           255.0      VAC        No         Q            Q   Q       No     304H
               Max Voltage                                                        *1       *1 *4
                                                                                           60.0
                   Base fre-          Output voltage (V)                        0.0 to
                                                                                            Hz
                   quency (FA)                                                  120.0
                                                                                            *4
         E1-06                                                                              96        No         Q            Q   Q       Q      305H
                                                                                 20 to
                   Base Fre-
                                                                                 3600      min-1
                   quency                                                        (PM)      (PM)
               Mid. output
                                                                                            *5
                                                                                                                                                            6
               frequency
                                                                                0.0 to    3.0 Hz
         E1-07 (FB)                                          Frequency (Hz)                           No         A            A   No      No     306H
                                                                                120.0     *2 *4
               Mid Fre-
                                    To set V/f characteristics in a straight
               quency A
                                    line, set the same values for E1-07
               Mid. output          and E1-09. In this case, the setting
               frequency            for E1-08 will be disregarded.                         14.0
                                                                                0.0 to
                                                                                           VAC
         E1-08 voltage (VB) Always ensure that the four frequen-                255.0                 No         Q            Q   No      No     307H
                                                                                           *1 *2
               Mid voltage cies are set in the following manner:                  *1
                                                                                            *4
               A            E1-04 (FMAX)  E1-06 (FA) > E1-
                   Min. output      07 (FB)  E1-09 (FMIN)
                                                                                0.0 to    1.5 Hz
                   frequency
                                                                                120.0     *2 *4
                   (FMIN)
         E1-09                                                                                        No         Q            Q   A       A      308H
                                                                                  0 to
                   Min Fre-
                                                                                 3600     0 min-1
                   quency                                                                  (PM)
                                                                                 (PM)
               Min. output
               frequency                                                                    7.0
                                                                                0.0 to
                                                                                           VAC
         E1-10 voltage                                                          255.0                 No         Q            Q   No      No     309H
               (VMIN)                                                                      *1 *2
                                                                                  *1
                                                                                            *4
                   Min Voltage
    * 1. These are values for a 200 V class Inverter. Values for a 400 V class Inverter are double.
    * 2. The factory settings will change when the control method is changed. (The V/f control factory settings are given.)
    * 3. After autotuning, E1-13 will contain the same value as E1-05.
                                                                                                                                                          6-83
         * 4. The factory settings will change according to parameter o2-09. Values shown here are for when o2-09 is set to 0.
         * 5. The factory settings depend on the Inverter capacity. The values for a 200 V class Inverter for 3.7kW are given.
Frequency (Hz)
                            To set the V/f characteristics linear, set E1-07 and E1-09 to the same value. In this case, E1-08 will be ignored.
             INFO
6
       Setting Precautions
         When a user-defined V/f pattern is used, consider the following points:
           By changing the control method, the parameters E1-07 to E1-10 are changed to the factory settings for the
             selected control method.
           Be sure to set the four frequencies as follows:
             E1-04 (FMAX)  E1-06 (FA) > E1-07 (FB)  E1-09 (FMIN)
6-84
                                                                                              Digital Operator/LED Monitor Functions
  Related Parameters
                   Name                                                                                     Control Methods
                                                                                             Change                                MEMO-
      Param-                                                                                                Open-           Closed- BUS
                                                                         Setting   Factory   during                 Closed-
       eter                                 Description                                                      loop            loop Regis-
                  Display                                                Range     Setting   Opera-   V/f             loop
      Number                                                                                                Vector          Vector
                                                                                              tion                   Vector          ter
                                                                                                               1             (PM)
             Monitor
                               Selects which monitor will be dis-
             selection
       o1-01                   played in the operation menu upon         4 to 99     6        Yes     A       A      A      A     500H
             User Monitor
                               power-up when o1-02 is set to 4.
             Sel
             Monitor           Sets the monitor item to be dis-
             selection after   played when the power is turned on.
             power up          0: Frequency reference
       o1-02                                                             1 to 4      1        Yes     A       A      A      A     501H
                               1: Output frequency
             Power-On
                               2: Output current
             Monitor
                               3: The monitor item set for o1-01
                               Sets the units that will be set and
                               displayed for the frequency refer-
                               ence and frequency monitor.
               Frequency
                               0: 0.01 Hz units
               units of refer-
                               1: 0.01% units (Maximum output                        0
               ence setting
                                  frequency is 100%)
               and monitor
                               2 to 39: min-1 units (Set the motor
                               poles.)
                               40 to 39999: User desired display
                               Set the desired values for setting and
                               display for the max. output fre-           0 to
       o1-03                                                                                  No      A       A      A      A     502H
                               quency.                                   39999
               Display
                                                Sets the value that is
                                                to be displayed at
                                                                                     1
                                                                                                                                             6
                                                100% excluding the
               Scaling                          decimal point.                     (PM)
                                                 Sets the number of
                                                 decimal places.
                                                                                                                                           6-85
                    Name                                                                                  Control Methods
                                                                                           Change                                MEMO-
       Param-                                                                                             Open-           Closed- BUS
                                                                       Setting   Factory   during                 Closed-
        eter                                 Description                                                   loop            loop
                   Display                                             Range     Setting   Opera-   V/f             loop          Regis-
       Number                                                                                             Vector          Vector
                                                                                            tion                   Vector          ter
                                                                                                             1             (PM)
             STOP key      Enables/Disables the Stop key in the
             during con- run mode.
             trol circuit  0: Disabled (When the Run
             terminal oper- Command is issued from an
       o2-02                                                            0, 1       0        No      A       A       A       A     506H
             ation            external terminal, the Stop key is
                                  disabled.)
                Oper Stop
                               1: Enabled (Effective even during
                Key
                                  run.)
                Parameter ini- Clears or stores user initial values.
                tial value     0: Stores/not set
                            1: Begins storing (Records the set
                               parameters as user initial values.)
       o2-03                2: All clear (Clears all recorded user 0 to 2          0        No      A       A       A       A     507H
             User Defaults     initial values)
                            When the set parameters are
                            recorded as user initial values, 1110
                            will be set in A1-03.
             kVA selection
       o2-04 Inverter       (Do not set this parameter.)           0 to FF         4*       No      A       A       A       A     508H
             Model #
             Frequency      Sets whether the ENTER key is
             reference set- needed for a frequency reference
             ting method change or not when the Digital
             selection      Operator is selected as frequency
                            reference source.
       o2-05                                                         0, 1          0        No      A       A       A       A     509H
                            0: Enter key needed
             Operator       1: Enter key not needed
             M.O.P.         If 1 is selected, a frequency refer-
                            ence change is accepted without the
                            need of pressing the Enter key.
6            Operation
             selection
                            Sets the operation when the Digital
                            Operator/LED Monitor is
             when digital disconnected.
             operator is    0: Operation continues even if the
             disconnected      Digital Operator/LED Monitor is
       o2-06                   disconnected.                         0, 1          0        No      A       A       A       A    50AH
                            1: OPR is detected at Digital
             Oper              Operator/LED Monitor
             Detection         disconnection. Inverter output is
                               switched off, and the fault contact
                               is operated.
             Cumulative
             operation
                            Sets the cumulative operation time       0 to
       o2-07 time setting                                                         0 hr.     No      A       A       A       A    50BH
                            in hour units.                         65535
             Elapsed Time
             Set
             Cumulative
             operation      0: Accumulated Inverter power on
       o2-08 time selection time.                                    0, 1          1        No      A       A       A       A    50CH
             Elapsed Time 1: Accumulated Inverter run time.
             Run
             Initialize     0: Japanese specification
       o2-09 Mode           1: American specification               0 to 2         0        No      A       A       A       A    50DH
             InitModeSet 2: European specification
             Fan operation Sets the initial value of the fan oper-
             time setting ation time.                                0 to
       o2-10                                                                      0 hr.     No      A       A       A       A    50EH
             Fan ON Time The operation time is accumulated         65535
             Set            starting from this set value.
             Fault trace    0: No initialisation
             initialize     0: Initialize (= zero clear) after
       o2-12                                                         0, 1          0        No      A       A       A       A     510H
             Fault Trace       setting 1 o2-12 will be returned
             Init              to 0
6-86
                                                                                                     Digital Operator/LED Monitor Functions
                                                                                                                                                         6-87
       Saving Parameters (o2-03)
         The Inverter parameter setting values can be saved as user-set parameter initial values by setting parameter o2-
         03 to 1.
         To initialize the Inverter using the user-set initial values, set parameter A1-03 to 1110. To clear the user-set ini-
         tial values set o2-03 to 2.
       Setting the Frequency Reference using the UP and DOWN Keys without Using the
        Enter Key (o2-05)
         This function is active when frequency references are input from the Digital Operator. When o2-05 is set to 1,
         the selected frequency reference can be incremented and decremented the UP and DOWN keys without using
         the Enter key. The function work only if parameter b1-01 is set to 0.
6-88
                                                                                     Digital Operator/LED Monitor Functions
  Related Parameters
                   Name                                                                            Control Methods
                                                                                    Change                                MEMO-
       Param-                                                                                      Open-           Closed- BUS
                                                                Setting   Factory   during                 Closed-
        eter                               Description                                              loop            loop Regis-
                  Display                                       Range     Setting   Opera-   V/f             loop
       Number                                                                                      Vector          Vector
                                                                                     tion                   Vector          ter
                                                                                                      1             (PM)
              Copy function    0: Normal operation
              selection        1: READ (Inverter to Operator)
        o3-01                                                   0 to 3      0        No      A       A      A      A     515H
              Copy Func-       2: COPY (Operator to Inverter)
              tion Sel         3: Verify (compare)
              Read permis-
              sion selection   0: READ prohibited
        o3-02                                                    0, 1       0        No      A       A      A      A     516H
              Read             1: READ permitted
              Allowable
                                                                                                                                  6-89
       Storing Inverter set values in the Digital Operator (READ)
         To store Inverter set values in the Digital Operator use the following method.
         Step
                                                       Explanation                                         Digital Operator Display
         No.
                                                                                                           -ADV-
                                                                                                            ** Main Menu **
          1     Press the Menu Key and select advanced programming mode.
                                                                                                                Programming
                                                                                                            -ADV-
                                                                                                                 Initialization
          2     Press the DATA/ENTER Key.
                                                                                                                A1 - 00=1
                                                                                                            Select Language
                                                                                                            -ADV-
                Press the Increment and Decrement Key until parameter o3-01 is displayed (Copy Function      COPY Function
          3
                Selection).                                                                                      o3 - 01=0
                                                                                                            Copy Funtion Sel
                                                                                                            -ADV-
                                                                                                            Copy Function Sel
          4     Press the DATA/ENTER Key and select the parameters setting display.
                                                                                                                 o3-01= 0         *0*
                                                                                                                COPY SELECT
                                                                                                            -ADV-
                                                                                                            Copy Function Sel
          5     Change the set value to 1 using the Increment Key.
                                                                                                                 o3-01= 1         *0*
                                                                                                             INV      OP READ
                                                                                                            -ADV-
                                                                                                                    READ
          6     Set the changed data using the DATA/ENTER Key. The READ function starts.
                                                                                                          INV     OP READING
6                                                                                                           -ADV-
                                                                                                                    READ
          7     If the READ function ends normally, End is displayed on the Digital Operator.
                                                                                                          READ COMPLETE
                                                                                                            -ADV-
                                                                                                            Copy Function Sel
          8     The display returns to o3-01 when a key is pressed.
                                                                                                                 o3 - 01=0        *0*
                                                                                                                COPY SELECT
         If an error is displayed, press any key to cancel the error display and return to the o3-01 display. Refer to
         page 7-15, Digital Operator Copy Function Faults for corrective actions.
6-90
                                                                                           Digital Operator/LED Monitor Functions
Writing Parameter Set Values Stored in the Digital Operator to the Inverter (COPY)
  To write parameter set values stored in the Digital Operator to the Inverter, use the following method.
  Step
                                                Explanation                                            Digital Operator Display
  No.
                                                                                                        -ADV-
                                                                                                         ** Main Menu **
   1     Press the MENU Key and select advanced programming mode.
                                                                                                            Programming
                                                                                                        -ADV-
                                                                                                             Initialization
   2     Press the DATA/ENTER Key.
                                                                                                            A1 - 00 = 1
                                                                                                           Select Language
                                                                                                        -ADV-
         Press the Increment and Decrement Key until parameter o3-01 is displayed (Copy Function           COPY Function
   3
         Selection).                                                                                        o3 - 01 = 0
                                                                                                        Copy Funtion Sel
                                                                                                        -ADV-
                                                                                                        Copy Function Sel
   4     Press the DATA/ENTER Key and select the parameters setting display.
                                                                                                             o3-01= 0         *0*
                                                                                                           COPY SELECT
                                                                                                        -ADV-
                                                                                                        Copy Function Sel
   5     Change the set value to 2 using the Increment Key.
                                                                                                             o3-01= 2         *0*
                                                                                                           OP     INV WRITE
                                                                                                        -ADV-
                                                                                                                COPY
   6     Set the changed data using the DATA/ENTER Key. The COPY function starts.
                                                                                                      OP     INV COPYING
                                                                                                        -ADV-
                                                                                                                COPY
                                                                                                                                      6
   7     If the COPY function ends normally, End is displayed on the Digital Operator.
                                                                                                      COPY COMPLETE
                                                                                                        -ADV-
                                                                                                        Copy Function Sel
   8     The display returns to o3-01 when a key is pressed.
                                                                                                             o3 - 01 =0       *0*
                                                                                                           COPY SELECT
  If an error is displayed, set the parameters again. Refer to page 7-15, Digital Operator Copy Function Faults
  for corrective actions.
                                                                                                                                    6-91
       Comparing Inverter Parameters and Digital Operator Parameter Set Values (VERIFY)
         To compare Inverter parameters and Digital Operator parameter set values, use the following method.
         Step
                                                       Explanation                                               Digital Operator Display
         No.
                                                                                                                  -ADV-
                                                                                                                  ** Main Menu **
          1     Press the MENU Key and select advanced programming mode.
                                                                                                                     Programming
                                                                                                                  -ADV-
                                                                                                                     Initialization
          2     Press the DATA/ENTER Key.
                                                                                                                     A1 - 00 = 1
                                                                                                                   Select Language
                                                                                                                  -ADV-
                Press the Increment and Decrement Key until the parameter o3-01 is displayed (Copy Func-           COPY Function
          3
                tion Selection).                                                                                     o3 - 01=0
                                                                                                                   Copy Funtion Sel
                                                                                                                  -ADV-
                                                                                                                  Copy Function Sel
          4     Press the DATA/ENTER Key and select the function setting display.
                                                                                                                      o3-01= 0        *0*
                                                                                                                   COPY SELECT
                                                                                                                  -ADV-
                                                                                                                  Copy Funtion Sel
          5     Change the set value to 3 using the Increment Key.
                                                                                                                      o3-01= 3        *0*
                                                                                                                OP         INV VERIFY
                                                                                                                  -ADV-
                                                                                                                          VERIFY
          6     Set the changed data using the DATA/ENTER Key. The VERIFY function starts.
                                                                                                                DATA VERIFYING
6                                                                                                                 -ADV-
                                                                                                                          VERIFY
          7     If the VERIFY function ends normally, End is displayed on the Digital Operator.
                                                                                                               VERIFY COMPLETE
                                                                                                                  -ADV-
                                                                                                                  Copy Function Sel
          8     The display returns to o3-01 when a key is pressed.
                                                                                                                     o3 - 01 = 0      *0*
                                                                                                                   COPY SELECT
         If an error is displayed, press any key to cancel the error display and return to the o3-01 display. Refer to
         page 7-15, Digital Operator Copy Function Faults for corrective actions.
Application Precautions
                           When using the copy function, check that the following settings are the same between the Inverter data and the
                           Digital
                            Inverter product and type
              INFO          Software number
                            Inverter capacity and voltage class
                            Control method
6-92
                                                                                       Digital Operator/LED Monitor Functions
  Related Parameters
                    Name                                                                             Control Methods
                                                                                      Change                                MEMO-
       Param-                                                                                        Open-           Closed- BUS
                                                                  Setting   Factory   during                 Closed-
        eter                               Description                                                loop            loop
                   Display                                        Range     Setting   Opera-   V/f             loop          Regis-
       Number                                                                                        Vector          Vector
                                                                                       tion                   Vector          ter
                                                                                                        1             (PM)
                Parameter      Used to set the parameter access
                access level   level (set/read.)
                          0: Monitoring only (Monitoring
                             drive mode and setting A1-01 and
                             A1-04.)
                          1: Used to select parameters (Only
       A1-01                 parameters set in A2-01 to A2-32     0 to 2      2        Yes     Q       Q       Q       Q     101H
             Access Level    can be read and set.)
                          2: Advanced
                             (Parameters can be read and set in
                             both, quick programming mode
                             (Q) and advanced programming
                             mode (A).)
                                                                                                                                      6-93
        Setting a Password
           When a password is set in A1-05 and if the set values in A1-04 and A1-05 do not match, only the settings of
           parameters A1-01 to A1-03, or A2-01 to A2-32 can be modified.
           The setting of all parameters except A1-00 can be prohibited using the password function in combination with
           setting parameter A1-01 to 0 (Monitor only).
         Related Parameters
                           Name                                                                               Control Methods
                                                                                               Change                                MEMO-
              Param-                                                                                          Open-           Closed- BUS
                                                                           Setting   Factory   during                 Closed-
               eter                               Description                                                  loop            loop
                          Display                                          Range     Setting   Opera-   V/f             loop          Regis-
              Number                                                                                          Vector          Vector
                                                                                                tion                   Vector          ter
                                                                                                                 1             (PM)
                       Parameter      Used to set the parameter access
                       access level   level (set/read.)
                                 0: Monitoring only (Monitoring
                                    drive mode and setting A1-01 and
                                    A1-04.)
                                 1: Used to select parameters (Only
              A1-01                 parameters set in A2-01 to A2-32       0 to 2      2        Yes     Q       Q       Q       Q     101H
                    Access Level    can be read and set.)
                                 2: Advanced
                                    (Parameters can be read and set in
                                    both, quick programming mode
                                    (Q) and advanced programming
                                    mode (A).)
                    Password     Password input when a password
                                 has been set in A1-05.
                                      This function write-protects some
                                      parameters of the initialize mode.
                                      If the password is changed, A1-01
                                                                           0 to
6             A1-04 Enter
                    Password
                                      to A1-03 and A2-01 to A2-32
                                      parameters can no longer be
                                      changed. (Programming mode
                                                                           9999
                                                                                       0        No      A       A       A       A     104H
         Setting a Password
           The password can be set in parameter A1-05. Normally A1-05 is not displayed. To display and modify A1-05
           the MENU and Reset key must be pressed together in the A1-04 display.
6-94
                                                                                                       Digital Operator/LED Monitor Functions
  Related Parameters
                      Name                                                                                              Control Methods
                                                                                                    Change                                     MEMO-
       Param-                                                                                                           Open-           Closed- BUS
                                                                              Setting    Factory    during                      Closed-
        eter                                     Description                                                             loop            loop Regis-
                     Display                                                  Range      Setting    Opera-       V/f              loop
       Number                                                                                                           Vector          Vector
                                                                                                     tion                        Vector          ter
                                                                                                                           1             (PM)
              User                Used to select the function for each
              specified           of the user specified parameters.
        A2-01                                                                                                                                         106H
              parameters          Parameters are the only accessible
         to                                                                                          No         A        A         A         A       to
        A2-32 User Param          parameters if Parameter Access                                                                                      125H
                                  Level is set to parameters (A1-
              1 to 32
                                  01=1)
  Related Parameters
                                                                                                                                                                   6
                      Name                                                                                              Control Methods
                                                                                                    Change                                     MEMO-
       Param-                                                                                                           Open-           Closed- BUS
                                                                              Setting    Factory    during                      Closed-
        eter                                     Description                                                             loop            loop Regis-
                     Display                                                  Range      Setting    Opera-       V/f              loop
       Number                                                                                                           Vector          Vector
                                                                                                     tion                        Vector          ter
                                                                                                                           1             (PM)
                              Used to memorize encoder and
                 Encoder copy
                              motor data in the encoder memory
                 selection
                              (for HIPERFACE and EnDat
        F1-25                     encoders)*                                  0 to 3        0          No        No        No       No         A      3B4H
                 ENC Copy         0: Normal operation
                 Sel              1: WRITE (Inverter to encoder)
                                  2: COPY (Encoder to Inverter)
                                  3: VERIFY
              Encoder copy        Sets wether saving parameters in the
              write permis-
                                  encoder is permitted or not.
        F1-26 sion selection                                                    0,1         0          No        No        No       No         A      3B5H
                                  0: Write prohibited
              Write Allow-
              able                1: Write permitted
                                                                                                                                                                 6-95
       Saved Parameters
         The following parameters are saved in the encoder memory:
                E1-04       Max. output frequency                            E5-06       D-axis inductance
                E1-06       Base frequency                                   E5-07       Q-axis inductance
                E1-13       Base voltage                                     E5-09       Motor voltage parameter
                E5-02       Motor rated power                                F1-01       PG parameter
                E5-03       Motor rated current                              F1-05       PG rotation
                E5-04       Number of motor poles                            F1-21       Absolute encoder resolution
                E5-05       Motor line-to-line resistance                    F1-22       Magnet position offset
6-96
                                                                                                                   PG Option Cards
PG Option Cards
   To have a more precise speed control the Inverter can be equipped with a PG option card for the connection of
   a pulse generator. Two different PG boards can be used, the PG-B2 and the PG-X2 board. Refer to page 2-26,
   Option Card Models and Specifications to see details.
 Related Parameters
                  Name                                                                                   Control Methods
                                                                                          Change                                MEMO-
      Param-                                                                                             Open-           Closed- BUS
                                                                      Setting   Factory   during                 Closed-
       eter                                Description                                                    loop            loop Regis-
                  Display                                             Range     Setting   Opera-   V/f             loop
      Number                                                                                             Vector          Vector
                                                                                           tion                   Vector          ter
                                                                                                            1             (PM)
                                                                        0 to
               PG parameter
                                                                       60000   600*1
                              Sets the number of PG pulses per
       F1-01                                                                               No      No     No      Q      Q     380H
             PG Pulses/       revolution                             0 to 8192 8192
             Rev                                                       (PM)    (PM)
             Operation     Sets the PG disconnection stopping
             selection at method.
             PG open       0: Ramp to stop (Deceleration to
             circuit (PGO)    stop using the deceleration time
                              1, C1-02.)
       F1-02               1: Coast to stop                           0 to 3      1        No      No     No      A      A     381H
                           2: Fast stop (Fast stop using the
             PG Fdbk Loss deceleration time in C1-09.)
             Sel
                           3: Continue operation (To protect
                              the motor or machinery, avoid to
                              use this setting.)
             Operation     Sets the stopping method when an
             selection at overspeed (OS) fault occurs.
             overspeed     0: Ramp to stop (Deceleration to
             (OS)             stop using the deceleration time
                              1, C1-02.)
       F1-03               1: Coast to stop                           0 to 3      1        No      No     No      A      A     382H
                           2: Fast stop (Fast stop using the
             PG Over-
                              deceleration time in C1-09.)
             speed Sel
                           3: Continue operation (To protect
                              the motor or machinery, avoid to
                                                                                                                                          6
                              use this setting.)
             Operation     Sets the stopping method when a
             selection at speed deviation (DEV) fault occurs.
                                                                                  3
             speed         0: Ramp to stop (Deceleration to
             deviation        stop using the deceleration time
                               1, C1-02.)
       F1-04                1: Coast to stop                          0 to 3               No      No     No      A      A     383H
                            2: Fast stop (Fast stop using the
             PG                                                                   1
                               deceleration time in C1-09.)
             Deviation Sel                                                      (PM)
                            3: Continue operation (DEV is
                               displayed and operation
                               continued.)
                            0: Phase A leads with Forward Run
             PG rotation       Command. (Phase B leads with                       0
                               Reverse Run Command)
       F1-05                                                           0, 1                No      No     No      Q      Q     384H
                            1: Phase B leads with Forward Run
             PG Rotation                                                          1
                               Command. (Phase A leads with
             Sel                                                                (PM)
                               Reverse Run Command)
             PG division Sets the division ratio for the PG
             rate (PG pulse speed control board pulse output.
             monitor)       Division ratio = (1+ n) /m
                              (n=0 or 1 m=1 to 32)
                              The first digit of the value of F1-06
       F1-06                  stands for n, the second and the third 1 to 132     1        No      No     No      A      A     385H
               PG Output      stands for m.
               Ratio          This parameter is effective only
                              when a PG-B2 is used.
                              The possible division ratio settings
                              are: 1/32  F1-06  1.
                                                                                                                                        6-97
                           Name                                                                                                  Control Methods
                                                                                                          Change                                        MEMO-
            Param-                                                                                                               Open-           Closed- BUS
                                                                                   Setting     Factory    during                         Closed-
             eter                                     Description                                                                 loop            loop
                           Display                                                 Range       Setting    Opera-       V/f                 loop          Regis-
            Number                                                                                                               Vector          Vector
                                                                                                           tion                           Vector          ter
                                                                                                                                    1             (PM)
                      Overspeed
                      detection
                                        Sets the overspeed detection
             F1-08    level                                                        0 to 120    115%         No         No          No      A       A     387H
                                        method.
                      PG Overspd
                      Level             Motor speeds that continue to
                                        exceed the value set in F1-08 (set as
                      Overspeed
                                        a percentage of the maximum output
                      detection
                                        frequency) for the time set in F1-09
             F1-09    delay time                                              0.0 to 2.0        0.0 s       No         No          No      A       A     388H
                                        are detected as overspeed faults.
                      PG Overspd
                      Time
                      Excessive
                      speed devia-
                                        Sets the speed deviation detection
                      tion detection
             F1-10                      method.                                    0 to 50      10%         No         No          No      A       A     389H
                      level
                                        Any speed deviation above the F1-
                      PG Deviate
                                        10 set level (set as a percentage of
                      Level
                                        the maximum output frequency) that
                      Excessive
                                        continues for the time set in F1-11 is
                      speed
                                        detected as a speed deviation.
                      deviation
                                        The speed deviation is the differ-          0.0 to
              F1-11   detection                                                                 0.5 s       No         No          No      A       A    38AH
                                        ence between actual motor speed              10.0
                      delay time
                                        and the speed reference command.
                      PG Deviate
                      Time
                      PG
                      open-circuit      Used to set the PG disconnection
                      detection         detection time. PGO will be                 0.0 to
             F1-14                                                                              1.0 s       No         No          No      A       A    38DH
                      delay time        detected if the detection time               10.0
                      PGO Detect        exceeds the set time.
                      Time
           * The factory settings depend on the Inverter capacity. The values for a 200 V class Inverter for 3.7 kW are given.
                           If open-loop vector control is used and a PG board is installed, the speed detected by the PG board is dis-
                           played in the monitor parameter U1-05. Therefore the PG parameter has to be set in parameter F1-01. The
                           direction of the speed detection can be changed by parameter F1-05.
                           To change the U1-05 value to the internally calculated value remove the PG board.
         IMPORTANT
6-98
                                                                                                        PG Option Cards
                                                                 Pulse output
               A-phase leads when set value = 0                      B-phase leads when set value = 1
               A-phase                                                A-phase
               B-phase                                                B-phase
With the used PG the A-phase leads (CCW) when motor rotation is forward.
  Generally, the A-phase leads when the rotation direction is counter-clockwise (CCW) seen from the shaft side
  (FWD command is input).
  The division ratio can be set within the following range: 1/32  F1-06  1. For example, if the division ratio is
  1/2 (set value 2), half of the number of pulses from the PG are output at the pulse monitor.
                                                                                                                          6-99
          Detecting a Speed Deviation between the Motor and Speed Reference (F1-04, F1-10
           and F1-11)
            A speed deviation fault is detected when the speed deviation (i.e., the difference between the speed reference
            and the actual motor speed) is too large. Speed deviation (DEV) is detected only after a speed agreement
            (speed reference and actual motor speed are within the setting range of L4-02) and if a speed deviation higher
            than the set value in F1-10 continues for longer than the time set in F1-11. After a speed deviation is detected,
            the Inverter stops according to the setting in F1-04.
6-100
                                                                                                                                 Emergency Operation
Emergency Operation
   Using emergency operation the car can be moved to the next floor if the power supply fails. In this case the
   Inverter must be supplied by a UPS or a battery and the emergency operation must be enabled by a multi-func-
   tion contact input (H1- = 85). The battery voltage has to be set in parameter L2-11. A light load detection
   function can be used to detect the light load direction for the car evacuation.
   Emergency operation powered by a backup battery requires the use of the PG-F2 option card. The Inverter
   cannot run a Permanent magnet motor with the backup battery if any other option card is used.
 Related Parameters.
                      Name                                                                                                Control Methods
                                                                                                        Change                                   MEMO-
       Param-                                                                                                             Open-           Closed- BUS
                                                                              Setting     Factory       during                    Closed-
        eter                                     Description                                                               loop            loop Regis-
                     Display                                                  Range       Setting       Opera-      V/f             loop
       Number                                                                                                             Vector          Vector
                                                                                                         tion                      Vector          ter
                                                                                                                             1             (PM)
             Battery
             Voltage                                                         0 to 400        0
       L2-11                      Sets the battery voltage.                                              No          A       A      A         A     4CBH
             Volt@bat-                                                           *           *
             terydr
* These are values for a 200 V class Inverter. Values for a 400 V class Inverter are the double.
* Battery-powered operation is not available if using a permanent magnet motor with an option card other than a PG-F2 option card.
     Note: When an AC power supply (e.g. a single phase UPS like example 3 below) is used, make sure that
                the rectified voltage meets the voltage range above.
                                                                                                                                                            6-101
        Battery operation wiring examples
            The following diagrams show some wirings examples for emergency operation
Example 1: Two Batteries, Main battery voltage lower than 280 VDC.
                                                         +1                   Magnetic contactor B
                                   Main power
                                                    B
                                                        R/L1                  Magnetic contactor A
                                                                   Inverter
                                                          -
                                                        P0
         Controller supply
             battery                      C
                                                        N0
                                                        Sx
                    Emergency operation
                       enable input                     SC
            The magnetic contactors must be operated, so that magnetic contactor B is always opened, before A and C are
            closed. Magnetic contactor C can be closed after A but not before. When battery operation is disabled, the
            magnetic contactors A and C must be opened, before B is closed.
A B1(+ 3)
                                                                               Magnetic contactor B
                                                          +1
                                    Main power                                 Magnetic contactor A
                                                          R/L1
          Main                                  B
          battery                         3               S/L2
                                          ~
                                                          T/L3
                                                                   Inverter
                                                             -
P0
N0
                                                         Sx
                     Emergency operation
                        enable input                     SC
            The magnetic contactors must be operated, so that magnetic contactor B is always opened, before A is closed.
            When the battery operation is disabled, the magnetic contactor A must be opened, before B is closed.
6-102
                                                                                                                                                                    Emergency Operation
Inverter
                                                             -
             Rectifier diode
             and capacity
                                                           P0
                               C
                                                           N0
                                                           Sx
                Emergency operation
                   enable input                            SC
  The magnetic contactors must be operated, so that magnetic contactor B is always opened, before A and C are
  closed. Magnetic contactor C can be closed after A but not before. When battery operation is disabled, the
  magnetic contactors A and C must be opened, before B is closed.
     for the 400 V class:                                               Battery Voltage L2-11  Base frequency E1-04
                                       Emergency Operation Speed Limit = -------------------------------------------------------------------------------------------------------------------
                                                                                                                      600 V  2                                                                   6
  If the emergency speed reference (d1-15) is higher than the emergency operation speed limit, the output fre-
  quency is automatically limited to the calculated limit. It prevents a voltage saturation and a possible motor
  stalling.
Precautions
  Because of the possibly low DC bus voltage during battery operation, the heatsink cooling fans may not work.
  A continuous operation under this condition can result in over heat faults and Inverter damage.
                                                                                                                                                                                               6-103
        Light Load Direction Detection
          The Inverter can detect the light load direction for emergency operation. Therefore, if the light load direction
          search is enabled (S3-06 is set to 1), the elevator is driven with the emergency speed in forward direction first
          and in reverse direction afterwards. The current/torque is measured in both directions and compared to each
          other.
            If the detected light direction is forward, the Inverter stops and restarts in the forward direction with the set
             emergency operation speed. At the restart the light load detection status output (H2-=45) and the light
             load direction output (H1-=44) are set.
                     D/I emergency
                     operation
                     External
                     controller fwd
                     or rev run                               Torque is measured
                                                               after speed agree
                                                                                        Car evacuation in
                                                                                        forward direction
                     Internal
                                                     Fwd                                Fwd
                     fwd run
                     Internal                                               Rev
                     rev run
            If the detected light load direction is reverse, the Inverter continues the operation with the set emergency
             operation speed. The light load detection status output (H1-=45) is set, the direction output is not
             changed.
6
                  D/I emergency
                  operation
                  External
                  controller fwd
                  or rev run                               Torque is measured
                                                            after speed agree
                  Internal
                                                 Fwd
                  fwd run
                  Internal                                              Rev         Car evacuation in
                  rev run                                                           reverse direction
6-104
                                                                                                                 Automatic Fault Reset
   The Inverter can reset faults automatically. The maximum number of resets can be selected as well as the oper-
   ation mode of the fault relay.
   Auto-resetable Fault codes are: UV1, GF, OC, OV, OL2, OL3, OL4, UL3, UL4, PF, LF, SE1, SE2, SE3
 Related Parameters.
                   Name                                                                                    Control Methods
                                                                                            Change                                MEMO-
      Param-                                                                                               Open-           Closed- BUS
                                                                        Setting   Factory   during                 Closed-
       eter                                  Description                                                    loop            loop Regis-
                  Display                                               Range     Setting   Opera-   V/f             loop
      Number                                                                                               Vector          Vector
                                                                                             tion                   Vector          ter
                                                                                                              1             (PM)
               Number of        Sets the number of auto restart
               auto restart     attempts.
               attempts         Automatically restarts after a fault
       L5-01                    The retry fault code are the follow-    0 to 10     2        No      A       A        A    A     49EH
               Num of           ings
               Restarts         OV, GF, OC, OL2, OL3, OL4, UL3,
                                UL4, PF, LF, SE1, SE2, SE3
               Auto restart     Sets whether a fault contact output
               operation        is activated during fault restart.
               selection        0: No output (Fault contact is not
       L5-02                                                              0, 1      1        No      A       A        A    A     49FH
                                   activated.)
               Restart Sel      1: Output (Fault contact is
                                   activated.)
               Fault restart
                           Sets the interval time between fault          0.5 to
       L5-03 interval time                                                         2.0 s     No      A       A        A    A    4AOH
                           restarts.                                     180.0
             Retry time
                                                                                                                                             6
 Fault Reset Interval Time Setting
   The Inverter allows the user to set the wait time required between fault resets.
   The time between fault resets in SPEC: A is fixed at 2 seconds.
                                                                                  Fault
                                             DC injection                                             DC injection
                                             zero-servo                                               zero-servo
                               Speed
                          Up/Down
                Speed reference
                    Hardware BB
  Brake release command (D/O)
               Fault output (D/O)
                      Auto-reset
                                                                                         Setting
                                                                                          value
                                                                                        in L5-03
                                                                                                                                          6-105
          Fault Relay Operation
            Parameter L5-02 can be used to enable or disable the fault relay (terminal MA-MB-MC) during the fault retry.
            Even if the fault relay is deactivated during the retries (L5-02=0), it is operated after the number of retries set
            in L5-01 has been reached.
              L5-02 = 1 enabled the fault relay.
              L5-02 = 0 disables the fault relay.
          Related Parameters
                             Name                                                                                             Control Methods
                                                                                                          Change                                     MEMO-
               Param-                                                                                                         Open-           Closed- BUS
                                                                                    Setting    Factory    during                      Closed-
                eter                                   Description                                                             loop            loop
                             Display                                                Range      Setting    Opera-       V/f              loop          Regis-
               Number                                                                                                         Vector          Vector
                                                                                                           tion                        Vector          ter
                                                                                                                                 1             (PM)
                      Under volt-        Selects the reset method for a UV1
                      age fault          fault.
                      restart selec-     0: UV1 fault is reset like set in
                L5-05                                                                 0,1          0         No         A        A         A         A      4CCH
                      tion                  parameter L5-01
                      UV1 Restart        1: UV1 fault is always
                      Sel.                  automatically reset
          Functions
              When L5-05 is set its default value of 0, the Inverter will restart itself after a fault occurs as has tradition-
               ally done.
              If L5-05 is set to 1, then the Inverter will always attempt to restart itself after a UV1 fault, regardless of the
                                   OFF                 ON
               Brake close
                                   OFF                 ON
                Baseblock
                    Fault          OFF            ON
                   contact
                   output                                                    *L5-03 or L2-03,
                                                                              whichever value is longer
6-106
                                                                                                    MEMOBUS Communications
MEMOBUS Communications
 RS-422/485 Interface
    You can perform serial communications with MEMOCON-series Programmable Controllers (PLCs) or simi-
    lar devices using the MEMOBUS protocol.
                     RS-485 connections
                     example
  Communications Specifications
    The MEMOBUS communications specifications are shown in the following table.
                                                                                                                                   6
                        Item                                                       Specifications
         Interface                            RS-422, RS-485
         Communications Cycle                 Asynchronous (Start-stop synchronization)
                                              Baud rate:       Select from 1,200, 2,400, 4,800, 9,600, and 19,200 bps.
                                              Data length: 8 bits fixed
         Communications Parameters
                                              Parity:          Select from even, odd, or none.
                                              Stop bits:       1 bit fixed
         Communications Protocol              MEMOBUS (RTU mode only)
         Number of Connectable Units          31 units max. (when using RS-485)
                                                                                                                                6-107
                           1. Separate the communication cables from the main circuit cables and other wiring and power cables.
                           2. Use shielded cables for the communication cables, connect the shield cover to the Inverter earth terminal, and
                              arrange the terminals so that the other end is not connected to prevent operating errors due to noise.
              IMPORTANT    3. When using RS-485 communications, connect S+ to R+, and S- to R-, on the Inverter exterior.
R+ R
S+ S
6                         Set the timer on the master to monitor response time from the slave. Set the master so that if the slave
                          does not respond to the master within the set time, the same command message will be sent from the
                          master again.
                 INFO
6-108
                                                                                                                          MEMOBUS Communications
Related Parameters
                      Name                                                                                                 Control Methods
                                                                                                      Change                                      MEMO-
       Param-                                                                                                               Open-          Closed- BUS
                                                                                Setting    Factory    during                       Closed-
        eter                                     Description                                                                 loop           loop Regis-
                     Display                                                    Range      Setting    Opera-        V/f             loop
       Number                                                                                                               Vector         Vector
                                                                                                       tion                        Vector           ter
                                                                                                                               1            (PM)
                 Reference        Sets the frequency reference input
                 source           method.
                 selection        0: Digital Operator
        b1-01                     1: Control circuit terminal (analog           0 to 3         0         No          A         A            A   A   180H
                 Reference           input)*1
                 Source           2: MEMOBUS communications
                          3: Option card*2
              Run Com-    Sets the Run Command input
              mand source method.
              selection   0: Digital Operator
        b1-02             1: Control circuit terminal                           0 to 3         1         No          A         A            A   A   181H
                             (sequence input)
              Run Source
                          2: MEMOBUS communications
                          3: Option card
                 Slave address
                                                                               0 to 20
       H5-01 Serial Comm Set the Inverter's slave address.                                    1F         No          A         A            A   A   425H
                                                                                 *3
             Adr
             Communica- Set the baud rate for 6CN MEMO-
             tion speed      BUS communications.
             selection       0: 1200 bps
       H5-02                 1: 2400 bps                          0 to 4                       3         No          A         A            A   A   426H
             Serial Baud 2: 4800 bps
             Rate            3: 9600 bps
                             4: 19200 bps
             Communica- Set the parity for 6CN MEMOBUS
             tion parity     communications.
       H5-03 selection
             Sel
                             0: No parity
             Serial Com 1: Even parity
                             2: Odd parity
                                                                  0 to 2                       0         No          A         A            A   A   427H
                                                                                                                                                              6
             Stopping        Set the stopping method for commu-
             method after nications errors.
             communica- 0: Deceleration to stop using
             tion error         deceleration time in C1-02
       H5-04                                                      0 to 3                       3         No          A         A            A   A   428H
                             1: Coast to stop
             Serial Fault 2: Fast stop using deceleration time
             Sel                in C1-09
                             3: Continue operation
             Communica- Set whether or not a communica-
             tion error      tions timeout is to be detected as a
       H5-05 detection       communications error.                 0,1                         1         No          A         A            A   A   429H
             selection       0: Do not detect.
             Serial Flt Dtct 1: Detect
             Send wait
                                  Set the time from the Inverter
             time
       H5-06                      receiving data to when the Inverter          5 to 65      5 ms         No          A         A            A   A   42AH
             Transmit
                                  starts to send.
             WaitTIM
             RTS control          Select to enable or disable RTS con-
             ON/OFF               trol.
       H5-07                      0: Disabled (RTS is always ON)                  0,1          1         No          A         A            A   A   42BH
             RTS Control
                                  1: Enabled (RTS turns ON only
             Sel
                                     when sending)
  * 1. If d1-18 is set to 1 or 2, an analog reference will have priority over a frequency reference from a multi-function contact input.
  * 2. If d1-18 is set to 1 or 2, a frequency reference from a multi-function contact input will be valid even if b1-01 is set to 2 or 3.
  * 3. If H5-01 is set to zero, then the Inverter will no longer respond to MEMOBUS communications.
                                                                                                                                                           6-109
          MEMOBUS communications can perform the following operations regardless of the settings in b1-01 and b1-
          02.
            Monitoring operation status from the PLC
            Setting and reading parameters
            Resetting errors
            Inputting multi-function commands
          An OR operation is performed between the multi-function commands input from the PLC and commands
          input from multi-function contact input terminals S3 to S7.
        Message Format
          In MEMOBUS communications, the master sends commands to the slave, and the slave responds. The mes-
          sage format is configured for both sending and receiving as shown below, and the length of data packets is
          changed by the command (function) contents.
                   Slave address
                   Function code
Data
Error check
        Slave Address
          Set the Inverter address from 0 to 20 Hex. If you set 0, commands from the master will be broadcast (i.e., the
          Inverter will not return responses).
        Function Code
          The function code specifies commands. There are three function codes, as shown below.
                                                                         Command Message              Response Message
                Function Code
                                                   Function               Min.          Max.           Min.        Max.
                (Hexadecimal)
                                                                         (Bytes)       (Bytes)        (Bytes)     (Bytes)
                     03H           Read storage register contents             8             8            7          37
                     08H           Loopback test                              8             8            8          8
                     10H           Write multiple storage registers           11            41           8          8
        Data
          Configure consecutive data by combining the storage register address (test code for a loopback address) and
          the data the register contains. The data length changes depending on the command details.
6-110
                                                                                     MEMOBUS Communications
Error Check
  Errors are detected during communications using CRC-16. Perform calculations using the following method.
  1. The factory setting for CRC-16 communications is usually 0, but when using the MEMOBUS system, set
     the factory setting to 1 (i.e., set all 16 bits to 1).
  2. Calculate CRC-16 using MSB as slave address LSB, and LSB as the MSB of the final data.
  3. Also calculate CRC-16 for response messages from the slaves, and compare them to the CRC-16 in the
     response messages.
                                                                                                                         6
                       Higher                               Lower                                Lower
                                  00H                                   65H                                  31H
                       place                                place                                place
         Quantity
                       Lower                                Higher
                                  04H                                   00H
                       place                Next storage    place
                       Higher                 register      Lower
                                  45H                                   00H
                       place                                place
         CRC-16
                       Lower                                Higher
                                  F0H                                   00H
                       place                Next storage    place
                                              register      Lower
                                                                        00H
                                                            place
                                                            Higher
                                                                        01H
                                            Next storage    place
                                              register      Lower
                                                                        F4H
                                                            place
                                                            Higher
                                                                       AFH
                                                            place
                                              CRC-16
                                                            Lower
                                                                        82H
                                                            place
                                                                                                                      6-111
        Loopback Test
         The loopback test returns command messages directly as response messages without changing the contents to
         check the communications between the master and slave. You can set user-defined test code and data values.
         The following table shows a message example when performing a loopback test with the slave 1 Inverter.
6                Command Message
                                                                 Response Message
                                                             (During Normal Operation)
                                                                                                                 Response Message
                                                                                                                  (During Error)
         Slave Address                       01H         Slave Address                       01H         Slave Address                  01H
         Function Code                       10H         Function Code                       10H         Function Code                  90H
                            Higher                                          Higher
                                             00H                                             00H               Error code               02H
           Start            place                          Start            place
          Address           Lower                         Address           Lower                                        Higher
                                             01H                                             01H                                        CDH
                            place                                           place                                        place
                                                                                                          CRC-16
                            Higher                                          Higher                                        Lower
                                             00H                                             00H                                        C1H
                            place                                           place                                         place
          Quantity                                        Quantity
                            Lower                                           Lower
                                             02H                                             02H
                            place                                           place
                                                                            Higher
               No. of data                   04H                                             10H
                                                                            place
                                                          CRC-16
                            Higher                                          Lower
                                             00H                                             08H
                            place                                           place
         Lead data
                            Lower
                                             01H
                            place
                            Higher
                                             02H
                            place
         Next data
                            Lower
                                             58H
                            place
                            Higher
                                             63H
                            place
          CRC-16
                            Lower
                                             39H
                            place
6-112
                                                                                        MEMOBUS Communications
                    Set the number of data specified using command messages as quantity of specified messages x 2. Han-
                    dle response messages in the same way.
INFO
Data Tables
  The data tables are shown below. The types of data are as follows: Reference data, monitor data, and broadcast
  data.
Reference Data
  The reference data table is shown below. You can both read and write reference data.
        Register No.                                                 Contents
          0000H           Not used
                          Frequency reference
                              Bit 0       Forward Run/Stop Command 1: Forward run 0: Stop
                              Bit 1       Reverse Run/Stop Command 1: Reverse run 0: Stop
                              Bit 2       External fault1: Error (EFO)
                              Bit 3       Fault reset1: Reset command
                              Bit 4       ComNet
            0001H             Bit 5       ComCtrl
                              Bit 6       Multi-function input command 3
                              Bit 7       Multi-function input command 4
                              Bit 8       Multi-function input command 5
                              Bit 9       Multi-function input command 6
                              Bit A
                            Bit B to F
                                          Multi-function input command 7
                                          Not used
                                                                                                                             6
            0002H         Frequency reference (Set units using parameter o1-03)
            0003H         Not used
            0004H         Not used
            0005H         Not used
            0006H         Not used
            0007H         Analog output 1 setting (-11 V/-1540 to 11 V/1540)
            0008H         Analog output 2 setting (-11 V/-1540 to 11 V/1540)
                          Multi-function contact output setting
                              Bit 0       Multi-function contact output (Terminal M1-M2) 1: ON 0: OFF
                              Bit 1       Multi-function contact output (Terminal M3-M4) 1: ON 0: OFF
                              Bit 2       Multi-function contact output (Terminal M5-M6) 1: ON 0: OFF
            0009H
                            Bit 3 to 5    Not used
                              Bit 6       Set error contact (terminal MA-MC) output using bit 7.1: ON 0: OFF
                              Bit 7       Error contact (terminal MA-MC) 1: ON 0: OFF
                            Bits 8 to F   Not used
       000AH to 000EH Not used
                                                                                                                          6-113
                Register No.                                                                    Contents
                                        Reference selection settings
                                          Bits 0 to B        Not used
                     000FH                      C            Broadcast data terminal S5 input 1: Enabled 0: Disabled
                                                D            Broadcast data terminal S6 input 1: Enabled 0: Disabled
                                                E            Broadcast data terminal S7 input 1: Enabled 0: Disabled
             Note: Write 0 to all unused bits. Also, do not write data to reserved registers.
        Monitor Data
         The following table shows the monitor data. Monitor data can only be read.
                Register No.                                                                    Contents
                                        Inverter status
                                              Bit 0          Operation 1: Operating 0: Stopped
                                              Bit 1          Reverse operation 1: Reverse operation 0: Forward operation
                                              Bit 2          Inverter startup complete 1: Completed 2: Not completed
                                              Bit 3          Error 1: Error
                     0020H
                                              Bit 4          Data setting error 1: Error
                                              Bit 5          Multi-function contact output (terminal M1 - M2) 1: ON 0: OFF
                                              Bit 6          Multi-function contact output 1 (terminal M3 - M4) 1: ON 0: OFF
                                              Bit 7          Multi-function contact output 2 (terminal M5 - M6) 1: ON 0: OFF
                                          Bits 8 to B        Not used
                                        Error details
                                              Bit 0          Overcurrent (OC) Ground fault (GF)
                                              Bit 1          Main circuit overvoltage (OV)
6                                             Bit 2
                                              Bit 3
                                                             Inverter overload (OL2)
                                                             Inverter overheat (OH1, OH2)
                                              Bit 4          Injection brake transistor resistance overheat (rr, rH)
                                              Bit 5          Fuse blown (PUF)
                                              Bit 6          PID feedback reference lost (FbL)
                                              Bit 7          External fault (EF, EFO)
                     0021H                    Bit 8          Hardware error (CPF)
                                                             Motor overload (OL1), overtorque 1 (OL3) detected, or overtorque 2 (OL4)
                                              Bit 9
                                                             detected
                                              Bit A          PG broken wire detected (PGO), Overspeed (OS), Speed deviation (DEV)
                                              Bit B          Main circuit undervoltage (UV) detected
                                                             Main circuit undervoltage (UV1), control power supply error (UV2), inrush pre-
                                              Bit C
                                                             vention circuit error (UV3), power loss
                                              Bit D          Main Circuit Voltage Fault (PF), Output Open-phase (LF)
                                              Bit E          MEMOBUS communications error (CE)
                                              Bit F          Operator disconnected (OPR)
                                        Data link status
                                              Bit 0          Writing data
                                              Bit 1          Not used
                     0022H                    Bit 2          Not used
                                              Bit 3          Upper and lower limit errors
                                              Bit 4          Data integrity error
                                          Bits 5 to F        Not used
6-114
                                                                                   MEMOBUS Communications
                                                                                                            6-115
                Register No.                                                                     Contents
                                       Communications error details
                                              Bit 0         CRC error
                                              Bit 1         Invalid data length
                                              Bit 2         Not used
                     003DH                    Bit 3         Parity error
                                              Bit 4         Overrun error
                                              Bit 5         Framing error
                                              Bit 6         Time-out
                                          Bits 7 to F       Not used
                     003EH             kVA setting
                     003FH             Control method
             Note: Communications error details are stored until an fault reset is input (you can also reset while the Unit is operating).
        Broadcast Data
         The following table shows the broadcast data. You can also write this data.
               Register Address                                                                    Contents
                                             Operation signal
                                                  Bit 0          Run Command 1: Operating 0: Stopped
                                                  Bit 1          Reverse operation command 1: Reverse 0: Forward
                                              Bits 2 and 3       Not used
                                                  Bit 4          External fault 1: Error (set using H1-01)
                        0001H                     Bit 5          Fault reset 1: Reset command (set using H1-02)
                                               Bits 6 to B       Not used
6                                                 Bit C
                                                  Bit D
                                                                 Multi-function contact input terminal S5 input
                                                                 Multi-function contact input terminal S6 input
                                                  Bit E          Multi-function contact input terminal S7 input
                                                  Bit F          Multi-function contact input terminal S8 input
                                             Frequency
                        0002H                                   30000/100%
                                             reference
             Note: Bit signals not defined in the broadcast operation signals use local node data signals continuously.
        ENTER Command
         When writing parameters to the Inverter from the PLC using MEMOBUS communications, the parameters are
         temporarily stored in the parameter data area in the Inverter. To enable these parameters in the parameter data
         area, use the ENTER command.
         There are two types of ENTER commands: ENTER commands that enable parameter data in RAM, and
         ENTER commands that write data to EEPROM (non-volatile memory) in the Inverter at the same time as
         enabling data in RAM.
         The following table shows the ENTER command data. ENTER command data can only be written.
         The ENTER command is enabled by writing 0 to register number 0900H or 0901H.
                Register No.                                                                     Contents
                  0900H                Write parameter data to EEPROM
                     0910H             Parameter data is not written to EEPROM, but refreshed in RAM only.
6-116
                                                                                          MEMOBUS Communications
                   The maximum number of times you can write to EEPROM using the Inverter is 100 thousand. Do not fre-
                   quently execute ENTER commands (0900H) written to EEPROM.
                   The ENTER command registers are write-only. Consequently, if reading these registers, the register
         INFO      address will become invalid (Error code: 02H).
Error Codes
  The following table shows MEMOBUS communications error codes.
         Error Code                                                Contents
                         Function code error
             01H
                          A function code other than 03H, 08H, or 10H has been set by the PLC.
                         Invalid register number error
             02H          The register address you are attempting to access is not recorded anywhere.
                          With broadcast sending, a start address other than 0000H, 0001H, or 0002H has been set.
                         Invalid quantity error
             03H          The number of data packets being read or written is outside the range 1 to 16.
                          In write mode, the number of data packets in the message is not No. of packets x 2.
                         Data setting error
                          A simple upper limit or lower limit error has occurred in the control data or when writing
             21H
                           parameters.
                          When writing parameters, the parameter setting is invalid.
                         Write mode error
                          Attempting to write parameters from the PLC during operation.
                          Attempting to write via ENTER commands from the PLC during operation.
             22H
                          Attempting to write parameters other than A1-00 to A1-05, E1-03, or 02-04 when warning
                           alarm CPF03 (defective EEPROM) has occurred.
                          Attempting to write read-only data.
                         Writing during main circuit undervoltage (UV) error
             23H          Writing parameters from the PLC during UV (main circuit undervoltage) alarm.
                          Writing via ENTER commands from the PLC during UV (main circuit undervoltage) alarm.             6
                         Writing error during parameters processing
             24H
                         Attempting to write parameters from the PLC while processing parameters in the Inverter.
Application Precautions
  Set a timer in the master to monitor response time from the slaves. Make the setting so that if no response is
  sent to the master from the slave within the set time, the same command message is sent again from the mas-
  ter.
                                                                                                                         6-117
        Self-Diagnosis
          The Inverter has a built-in function for self-diagnosing the operations of serial communications interface cir-
          cuits. This function is called the self-diagnosis function. The self-diagnosis function connects the communica-
          tions parts of the send and receive terminals, receives the data sent by the Inverter, and checks if
          communications are being performed normally.
          Perform the self-diagnosis function using the following procedure.
          1. Turn ON the power supply to the Inverter, and set 67 (communications test mode) in parameter H1-05
             (Terminal S7 Function Selection).
          2. Turn OFF the power supply to the Inverter.
          3. Perform wiring according to the following diagram while the power supply is turned OFF.
          4. Turn ON the terminating resistance. (Turn ON pin 1 on DIP switch 1.)
          5. Turn ON the power supply to the Inverter again.
                        R+        R-        SC        SC
                             S+        S-        S1        S2   S3     S4      S5       S6      S7
6-118
                                                                                         7
                           Troubleshooting
This chapter describes the fault displays and countermeasures for Inverter and motor problems.
           This section describes the fault and alarm functions of the Inverter. These functions include fault detection,
           alarm detection, programming error detection and auto-tuning error detection.
       Fault Detection
           When the Inverter detects a fault, the fault contact output is operated and the Inverter output is switched OFF
           and the motor coasts to stop. (The stopping method can be selected for some faults.) A fault code is displayed
           on the Digital Operator/LED Monitor.
           The faults can be categorized in two groups:
             Faults that can be reset without cycling the power using an input or the reset key at the Digital Operator
              (resetable faults)
             Faults that require to cycle the power (non-resetable faults)
           When a fault has occurred refer to the following to identify the fault and to correct the causes.
           To reset a fault it is necessary to remove the RUN signal and correct the fault reason. Otherwise a Reset is not
           accepted or the Inverter trips with the same fault again.
           The following tables shows a list of faults and corrective actions.
                                                                    One Inverter output was shorted to      Check the motor for a phase to
                           Ground Fault                                                                     ground short.
                                                                    ground or a DCCT is defective.
              GF           The ground current at the Inverter out-
          Ground Fault                                             The magnetic contactor was opened        Check the output current with a
                           put exceeded 50% of the Inverter rated
                                                                   when the Inverter output was still       clampmeter to verify the DCCT
                           output current and L8-09=1 (Enabled).
                                                                   active.                                  reading.
                                                                                                            Check the control sequence for
                                                                                                            wrong magnetic contactor signals.
7-2
                                                                                              Protective and Diagnostic Functions
                                                             The deceleration time is set too short      Increase the deceleration time (C1-
                                                             and the regenerative energy from the        02/04/06/08) or connect a braking
                                                             motor is too large.                         option.
                   DC Bus Overvoltage
                   The DC bus voltage has exceeded the
                   overvoltage detection level.                                                    Check the power supply and
     OV
                                                             The power supply voltage is too high. decrease the voltage to meet the
DC Bus Overvolt    Default detection levels are:
                                                                                                   Inverters specifications.
                   200 V class: 410 VDC
                   400 V class: 820 VDC
                                                             The braking chopper / braking resistor Check the braking chopper / resis-
                                                             is not working.                        tor.
                                                             External load was pulling down the          Remove all connection to the con-
                   Control Power Supply Undervoltage                                                     trol terminals and cycle the power
     UV2                                                     Inverters power supplies or there was
CTL PS Undervolt   Undervoltage of the control circuit                                                   to the Inverter.
                                                             an internal short in the power/gate drive
                   while the Inverter was running.           board.                                      Replace the Inverter.
    UV3
                   for the DC bus capacitors occurred.
                                                                                                                                                7-3
                                              Table 7.1 Resetable Faults (Continued)
           Display                      Meaning                              Probable Causes                       Corrective Actions
                                                                   There is a broken wire in the output
                          Output Open-phase                        cable.                              Reset the fault after correcting its
                          An open-phase occurred at the Inverter The motor winding is broken.          cause.
             LF           output.                                The output terminals are loose.
      Output Phase Loss   The fault is detected when the output
                          current falls below 5% of the Inverter The motor has a capacity less than 5% Check the motor and Inverter
                          rated current and L8-07=1 (enabled)    of the Inverter's maximum motor
                                                                                                       capacity.
                                                                 capacity.
                          Dynamic Braking Transistor              Defective or failed dynamic braking     Cycle power to the Inverter.
            RR
                          The built-in dynamic braking transistor resistor caused braking transistor dam-
       DynBrk Transistr
                          failed.                                 age.                                    Replace the Inverter.
                          tion) and L2-02 (Motor Protection        The setting of Motor Rated Current       Check the setting of Motor Rated
                          Time Parameter)                          (E2-01) is incorrect.                    Current Setting (E2-01).
                                                                                                             Recheck the cycle time and the size
                                                                   The load is too large. The acceleration of the load as well as the accel/
                                                                   time or deceleration times are too short. decel times
                          Inverter Overload                                                                  (C1-).
            OL2
        Inv Overload      The Inverter output current exceeded
                                                                   The voltage settings of the V/f pattern Check the V/f characteristics (E1-
                          the Inverters overload capability.
                                                                   is incorrect.                           ).
7-4
                                                                                            Protective and Diagnostic Functions
                                                            The acceleration time and deceleration Lengthen the acceleration time and
                  Excessive Speed Deviation                 time are too short.                    deceleration time.
                  Detected when F1-04 is set to 0, 1 or 2
                                                          The load is locked.                        Check the mechanical system.
     DEV          and A1-02 is set to 3
Speed Deviation   The speed deviation is higher than the The settings of F1-10 and F1-11 are not     Check the settings of F1-10 and F1-
                  setting of F1-10 for a time longer than appropriate.
                  the setting of F1-11.
                                                                                                     11.
                                                                                                                                           7-5
                                             Table 7.1 Resetable Faults (Continued)
          Display                      Meaning                              Probable Causes                         Corrective Actions
                                                                                                              Set the home position pulse
                                                                                                               compensation (E5-11) in accor-
                                                                                                               dance with  written on the
                                                                    The amount of compensation for the        motor nameplate. When replac-
                                                                     home position is set improperly (E5- ing the encoder or changing the
                                                                     11).                                      direction of the motor, be sure to
                                                                    Noise along the encoders A- or B-        adjust the pulses to the home
                         Reverse Detection                           phase lines.                              position.
                                                                    PG cable is not wired properly.          Check the direction of motor
                         Detection only during run.
                                                                    PG cable is not connected.                rotation.
                         The difference between the speed refer-    PG option card is damaged.               Correct the wiring.
           DV3           ence and the motor speed exceeded          Encoder on the motor side is dam-  Make sure there are no loose
                         30% during reverse (or forward) accel-      aged.                                     wire connections.
                         eration with a torque reference in the     The Inverter has been programmed  Check the operating conditions
                         opposite direction.                         to operate in such a way that the con- to make sure there arent any
                                                                     ditions trigger DV3.                      problems on the load side that
                                                                    Rotational direction of the encoder       would create the fault situation
                                                                     (F1-05) is in reverse phase relative to   described.
                                                                     the main motor cables.                   Reconnect the encoder.
                                                                                                              Make sure the U, V, and W
                                                                                                               phases from the motor are all
                                                                                                               wired properly.
7
                                                                   aged.
                                                                                                              would create the fault situation
                                                                  The encoder is rotating in the oppo-
                                                                                                              described.
                                                                   site direction of the speed reference
                                                                                                             Reconnect the encoder.
                                                                   and creating the fault conditions
                                                                                                             Make sure the U, V, and W
                                                                   described for DV4.
                                                                                                              phases from the motor are all
                                                                                                              wired properly.
                                                                                                             Disable DV4 fault detection in
                                                                                                              applications where the speed ref-
                                                                                                              erence is given to operate in the
                                                                                                              opposite direction of the load
                                                                                                              side. To do so, set F1-19 to 0.
7-6
                                                                                             Protective and Diagnostic Functions
                    Control Fault
                    A torque limit was reached continu-    Motor parameters were not set prop-
      CF
                    ously for 3 seconds or longer during a                                           Check the motor parameters.
 Out of Control                                            erly.
                    deceleration stop in open-loop vector
                    control.
       EF3
                    External fault at terminal S3
   Ext Fault S3
       EF4
                    External fault at terminal S4
   Ext Fault S4
                                                            An external fault was input from a
      EF5                                                                                            Eliminate the cause of the external
                    External fault at terminal S5           multi-function input terminal (S3 to
  Ext Fault S5                                                                                       fault condition.
                                                            S7).
      EF6
                    External fault at terminal S6
  Ext Fault S6
      EF 7
                    External fault at terminal S7
  Ext Fault S7
                                                                                                                                            7
     OPR                                                                                        Check the connection of the Digital
Oper Disconnect     removed and the Inverter receives its ing running or the Digital Operator   Operator.
                    Run Command through the Digital       cable is broken.
                    Operator. (b1-02=0)
     SE2            The output current at start was below   The magnetic contactor was not closed
                                                                                                  Check the magnetic contactor.
Sequence Error 2    25% of no-load current.                 at start.
     SE3            The output current during run was       The magnetic contactor was opened
                                                                                                     Check the magnetic contactor.
Sequence Error 3    below 25% of no-load current.           during run.
                                                                                                                                           7-7
                                                     Table 7.2 Not Resetable Faults
            Display                       Meaning                            Probable Causes                        Corrective Actions
                           Digital Operator/LED Monitor Com-                                               Disconnect the Digital Operator/
                           munication Fault 1                                                              LED Monitor and then connect it
                                                                   Digital operator cable was not securely again.
                           Communication with the digital opera-
                                                                   connected or digital operator is defec-
           CPF00           tor could not be established within 5
                                                                   tive and/or control board is defective
      COM-ERR(OP&INV)      seconds after the power was supplied to                                         Replace the Inverter.
                           the Inverter.
7
                           CPU External A/D Converter Fault        cuit input terminals or the control board
       External A/D Err                                                                                      Cycle the Inverter power supply.
                                                                   is damaged.
                                                                                                             Replace the Inverter.
                                                                   The option card is not connected prop- Turn off the power and re-
           CPF06                                                   erly.                                  install the option card again.
                           Option card Connection Fault
         Option Error
                                                                                                             Replace the option card or the
                                                                   The Inverter or option card is damaged.
                                                                                                             Inverter.
            CPF10
                           ASIC version fault                      The control circuit is damaged.           Replace the Inverter.
           ASIC-Err
7-8
                                                                                           Protective and Diagnostic Functions
Option card A/D converter is faulty. Cycle the Inverter power supply.
      CPF24
  PG-F2 Comm Err
                     PG-F2 Option Card Communication
                     Error
                                                           The option card is defective.          Replace the option card.                7
 Alarm Detection
     Alarms are Inverter protection functions that indicate unusual conditions without switching off the inverter
     and operating the fault output contact. The alarm automatically disappears when its cause is eliminated.
     During an alarm condition, the Digital Operator/LED Monitor alarm display flashes and an alarm output is
     generated at the multi-function outputs (H2-01 to H2-03) if programmed.
     When an alarm occurs, take appropriate countermeasures according to the table below.
                                                                                                                                         7-9
                                               Table 7.3 Alarm Detection (Continued)
           Display                       Meaning                             Probable causes                      Corrective Actions
                           DC Bus Undervoltage
                           The following conditions occurred
                            The DC bus voltage was below the
                             Undervoltage Detection Level Set-
              UV             ting (L2-05).                         For the probable reasons please have a For the corrective actions please
       DC Bus Undervolt     The MC of the inrush current pre-     look at UV1, UV2 and UV3 in table      have a look at UV1, UV2 and UV3
          (flashing)         vention circuit was opened.           7.1.                                   in table 7.1
                            The control power supply voltage
                             was below the CUV level.
                           UV Alarm is detected only, when the
                           inverter is in stop condition
                           DC Bus Overvoltage
                           The DC bus voltage exceeded the over-
              OV           voltage detection level.                                                      Check the power supply and
       DC Bus Overvolt     200 V class: 410 VDC                    The power supply voltage is too high. decrease the voltage to meet the
          (flashing)       400 V class: 820 VDC                                                          Inverters specifications
                           An OV Alarm is detected only, when
                           the inverter is in stop condition.
                           Overheat Alarm
             OH2           An OH2 alarm signal is input from a                                            Clear the multi-function input ter-
         Over Heat 2       multi-function contact input terminal An external overheat occurred.
                                                                                                          minals overheating alarm input.
          (flashing)       (S3 to S7) that is programmed to OH2
                           Alarm Signal Input.
7-10
                                                                                            Protective and Diagnostic Functions
       EF3
   Ext Fault S3     External fault at terminal S3
    (flashing)
       EF4
   Ext Fault S4     External fault at terminal S4
    (flashing)
                                                             An external fault was input by a multi-
       EF5                                                   function input terminal                 Eliminate the cause of the external
                                                                                                                                              7
   Ext Fault S5     External fault at terminal S5
    (flashing)                                               (S3 to S7) which is programmed for the fault condition
                                                             external fault function alarm output.
       EF6
   Ext Fault S6     External fault at terminal S6
    (flashing)
       EF7
   Ext Fault S7     External fault at terminal S7
    (flashing)
                                                                                                                                            7-11
        Operator Programming Errors
             An Operator Programming Error (OPE) occurs when two or more parameter related to each other are set inap-
             propriate or an individual parameter setting is incorrect. The Inverter does not operate until the parameter set-
             ting is set correctly; however, no other alarm or fault outputs will occur. If an OPE occurs, change the related
             parameter by checking the cause shown in Table 7.4. When an OPE error is displayed, press the ENTER key
             to see U1-34 (OPE Detected). This monitor displays the parameter that is causing the OPE error.
7            OPE06
         PG Opt Missing 6
                               Control method selection error
                                                                      6), but a PG option card is not installed. Recheck the setting of A1-02.
                                                                      Problem also may be due to a setting Confirm if the PG Speed control
                                                                      mismatch between parameter N8-35           card is attached.
                                                                      and the PG speed control card that is
                                                                      connected.
7-12
                                                                                             Protective and Diagnostic Functions
 Autotuning Faults
     Autotuning faults are shown below. When the following faults are detected, the fault is displayed on the digital
     operator and the motor coasts to stop. No fault or alarm outputs will be operated.
                                               Table 7.5 Autotuning Faults
       Display                      Meaning                            Probable causes                        Corrective Actions
                                                            There is an error in the data input for
                                                                                                      Check the input data.
                                                            autotuning.
      Er - 02
                      Alarm                                 An alarm is detected during autotuning. Check wiring and the machine.
     Minor Fault
                                                                                                                                             7-13
                                                   Table 7.5 Autotuning Faults (Continued)
               Display                          Meaning                            Probable causes                        Corrective Actions
                                                                                                                    Increase C1-01 (Acceleration
                                                                                                                     Time 1).
              Er - 09            Acceleration Fault                      The motor did not accelerate in the        Increase L7-01 and L7-02
             Accelerate          Detected only for rotating autotuning   specified time                              (Torque Limits) if they are low.
                                                                                                                    If the motor is connected to the
                                                                                                                     machine, disconnect it.
7-14
                                                                                                      Protective and Diagnostic Functions
                      CPE                 The Inverter type or software number was different Use stored data of the same product (L7) and soft-
                 ID UNMATCHED             from the stored data in the digital operator       ware number (U1-14) only.
                      VAE                 The capacity of the Inverter and the capacity of the Use stored data for the same Inverter capacity only
               INV. KVA UNMATCH           stored data in the Digital Operator are different.   (o2-04).
                               The control method of the Inverter and the control Use stored data for the same control
                    CRE
                               method of the stored data in the Digital Operator
 COPY        CONTROL UNMATCHED                                                    method (A1-02).
                               are different.
Function
                                          A parameter setting written to the Inverter was dif-
                        CYE
                                          ferent from the setting stored in the Digital Opera- Retry the COPY function (o3-01 = 2)
                     COPY ERROR
                                          tor.
 Verify              VYE                  The set value of the digital operator and the Inverter
                                                                                                 Retry the Verify function (o3-01 = 3)
Function         VERIFY ERROR             do not match
                                                                                                                                                     7-15
        Machine Data Copy Function Faults
                       Digital Operator
        Function                                          Probable Causes                                     Corrective Actions
                            Display
        WRITE                             A write to encoder command could not be per-
          from            ERE                                                                Make sure that no fault and no alarm is active and
                                          formed since the Inverter is in UV (under voltage)
       Inverter to     DATA ERROR                                                            retry.
        encoder                           status.
                                          A write to encoder command could not be per-
                            EDE           formed since F1-26 is set to 0 (write prohibited) or Set parameter F1-26 to 1 to permit a write to
                     WRITE IMPOSSIBLE     in CPF 24 (PG-F2 Option Card Communication           encoder command.
                                          Error) status.
                            EIF           A communication error occurred during the write to
                                                                                             Retry the write to encoder command.
                     WRITE DATA ERROR     encoder process.
       COPY from
       Encoder to                         A read to encoder command could not be per-
                          ECE                                                                Make sure that no fault and no alarm is active and
        Inverter                          formed since the Inverter is in UV (under voltage)
                       COPY ERROR                                                            retry.
                                          status.
                            EPE           The data in the encoder do not fit to the L7B data
                                                                                               Retry the Write command.
                       ID MISMATCH        format.
                           ECS            The check sum of the data, which were written into
                                                                                                                        -
                     SUM CHECK ERROR      the Inverter is wrong.
                           EVE            The data in the encoder and Inverter data do not
        VERFIY                                                                                                          -
                      VERIFY ERROR        match.
7-16
                                                                                                    Troubleshooting
Troubleshooting
    Due to parameter setting errors, faulty wiring etc., the Inverter and motor may not operate as expected when
    the system is started. If that occurs, use this section as a reference and perform the appropriate countermea-
    sures.
    If a fault code is displayed, refer to page 7-2, Protective and Diagnostic Functions.
  The display does not change when the Increment and Decrement keys are pressed.
    The following causes are possible:
                                                                                                                      7-17
        If the Motor Does Not Operate Properly
           The following causes are possible:
         The motor does not operate when an external operation signal is input.
           The frequency reference is 0.00 Hz or a no speed is selected by the multi-function contact inputs. Check the
           input signals and the frequency reference settings.
           Also make sure to set the Baseblock signal. The Inverter does not accept any input if it is baseblocked.
7-18
                                                                                                  Troubleshooting
                                                                                                                      7-19
        If Peripheral Devices are Influenced by the Starting or Running Inverter
           The following solutions are possible:
             Change the Inverter's Carrier Frequency Selection (C6-02) to lower the carrier frequency. This will help to
              reduce the amount of transistor switching noise.
             Install an Input Noise Filter at the Inverter's input power terminals.
             Install an Output Noise Filter at the Inverter's motor terminals.
             Use shielded motor cables or a conduit. Metal shields electrical noise.
             Check the grounding of the Inverter and motor.
             Separate main circuit wires from control circuit wires.
7          The torque compensation parameter settings may be incorrect for the machine. Adjust parameters C4-01
           (Torque Compensation Gain) and C4-02 (Torque Compensation Delay Time). Decrease C4-01 carefully in
           steps of 0.05 and/or increase C4-02.
           Furthermore the Slip Compensation Delay Time (C3-02) can be increased or decreased.
7-20
                                                                                     8
                       Maintenance and
                             Inspection
This chapter describes basic maintenance and inspection for the Inverter.
       Periodic Inspection
            Check the following items during periodic maintenance.
              The motor should not vibrate or make unusual noises.
              There should be no abnormal heat generation from the Inverter or motor.
              The ambient temperature should be within the Inverters specifications.
              The output current value shown in U1-03 should not be higher than the motor or the Inverter rated current
                for extended period of time.
              The cooling fan in the Inverter should be operating normally.
            Before attempting any maintenance checks, make sure that the three-phase power is disconnected. With power
            removed from the unit, the DC bus capacitors will stay charged for several minutes. The charge LED in the
            Inverter will light red until the DC bus voltage is below 10VDC. To ensure that the DC bus is completely dis-
            charged, measure between the positive and negative bus with a DC voltmeter. Be sure not to touch terminals
            immediately after the power has been turned off. Doing so can result in electric shock.
        External terminals         Are all screws and bolts tight?                    Tighten loose screws and bolts firmly.
        Mounting bolts connectors Are connectors tight?                               Reconnect the loose connectors.
                                                                                      Clean off any dirt and dust with an air gun using dry air at
        Heatsinks                  Are the fins dirty or dusty?                       a pressure of 4 x 105 to 6 x 105 Pa
                                                                                      (4 to 6 bar, 55 to 85 psi).
                                                                                      Clean off any dirt and dust with an air gun using dry air at
                                   Is there any conductive dirt or oil mist on the    a pressure of 4 x 105 to 6 x 105 Pa
        All PCBs
                                   PCBs?                                              (4 to 6 bar, 55 to 85 psi).
                                                                                      Replace the boards if they cannot be made clean.
        Input Diodes                                                                  Clean off any dirt and dust with an air gun using dry air at
                                   Is there any conductive dirt or oil mist on the
        Output Transistors Power                                                      a pressure of 4 x 105 to 6 x 105 Pa
                                   modules or components?
        Modules                                                                       (4 to 6 bar, 55 to 85 psi).
8-2
                                                                                                                     Maintenance and Inspection
  DC bus fuse
                                                              10 years                     Replace with new part.
  Control power fuse
     Note:   The standard replacement period is based on the following usage conditions:
             Ambient temperature:Yearly average of 30C/86F
             Load factor: 80%
             Operating rate: 12 hours per day
                                                                                                                                                  8-3
       Types and Number of Cooling Fans Used in the Inverter
          Cooling fans used for the Inverter has two types; Heatsink cooling fan and heatsink circulation fan. Heatsink
          cooling fan blows air to the Inverter cooling fin. Heatsink circulation fan stirs up the air inside the Inverter
          unit.
          Table 8.2 shows the number of cooling fans used in the Inverter. For more information on models and specifi-
          cations of cooling fans, contact your Yaskawa representative or YASKAWA ELECTRIC ENGINEERING
          CORPORATION.
          When replacing the fan, use the specified type of the fan. If the inapplicable fans are used, performance of the
          Inverter will not be fully obtained.
5.5 1 - 1 -
7.5 2 - 2 -
11 2 1 2 1
15 2 - 2 -
                 18.5                  2                       1                      2                        1
                  22                   2                       -                      2                        -
30 2 - 2 -
37 2 1 2 -
45 2 1 2 -
55 2 1 2 -
* No models
8-4
                                                                                         Maintenance and Inspection
Airflow direction
                                 Fan cover
                                              1                                                                           8
                     Fig 8.1 Cooling Fan Replacement (200 V Class Inverters of 5.5 kW)
                                                                                                                         8-5
      200 V and 400 V Class Inverters of 22 kW or More
        A cooling fan is attached to the top panel inside the Inverter.
        The cooling fan can be replaced without removing the Inverter from the installation panel.
8
                             Control board bracket                           Fan cover
                            Control                                        Connector
                            board
8-6
                                                                                     Maintenance and Inspection
Bottom Inverter
                                     Cooling fan
                                                                      Top Inverter
Fig 8.3
Fig 8.4
 3. Make sure that there is no gap between the fan cover and A. Then screw it in place with the three screws.
                         Make sure that
                         there is no gap.
                                                                 NG                                                8
                                                             A
                              A
Fig 8.5
                                                                                                                  8-7
      200 V Class Inverters of 55 kW
Front cover
Terminal cover
                                                                  Circulation fan
                                                                  mounting screws
                                                                                  Fan cable pullout position
                                                 Circulation fan
                                              Airflow direction
                          Fan support         Fan support
8           Fan support
                                                    Airflow
                                                                              Cooling fans
                                                   Resistor
                                                   unit
          Fan power
          relay board
                                               Cooling fans
                          Resistor unit
                          mounting screws                                               Cooling fan mounting screws
Fig 8.6 Cooling Fan Replacement (400 V Class Inverters of 75 kW and 90 kW)
8-8
                                                                                              Maintenance and Inspection
                                                         Gate drive
                                                         board
             Front cover
                                                         Panel
                                                         mounting
                                                         screws
Capacitor
Terminal cover
                                                         Terminal
                                                         board
                           Terminal cover mounting screws
                                                                                                                            8
                                 Circulation fan mounting screws
       Pay attention to
       the protruding part                               Circulation fan
                                                          Cooling fans
Airflow direction
                                                                                             Cooling fan
                                                                                             mounting screws
                                             Fan cover
Fig 8.7 Cooling Fan Replacement (200 V Class Inverters of 37 kW and 45 kW)
                                                                                                                           8-9
        Circulation Fan Replacement Outline
           With some capacities, there is a small fan installed inside the Inverter for the purpose of increasing circulation
           in areas where heat has built up. These fans have built-in fan sensors that output an alarm when the rotation
           rate of the fan drops to indicate that replacement is necessary.
                                                                    Control
                                                                    board
                                                                2
                                                                     1
8 Airflow direction
                                                                              Tabs (A)
                                                                         Circulation fan
Fig 8.8 Circulation Fan Replacement (200 V and 400 V Class Inverters of 11 kW)
8-10
                                                                                           Maintenance and Inspection
                               Circulation fan       4
                                                         2   1
                                                                 Relay connector tab (A)
                             Fan tabs (B)
                                        Airflow
                                        direction
            Fig 8.9 Circulation Fan Replacement (200 V and 400 V Class Inverters of 18.5 kW)
                                                                                                                          8
200 V Class Inverters of 37 kW or More
  The circulation fan is installed in front of the fan cover inside the Inverter. Remove the circulation fan using
  the procedure for replacing the cooling fan and replace it with the new fan. (The installation position for 200 V
  Class Inverters of 75 kW is different.)
                                                                                                                        8-11
        Removing and Mounting the Control Circuit Terminal Board
           The control circuit terminal board can be removed and mounted without disconnecting the control wiring.
8
                                    Fig 8.10 Removing the Control Circuit Terminal Board
                         Always confirm that the input power is removed and the Charge LED is off before removing or
                         mounting the control circuit terminal board.
           IMPORTANT
8-12
                                                                                          9
                                         Specifications
This chapter describes the basic specifications of the Inverter.
                             Inverter Specifications.........................................................9-2
      Inverter Specifications
       Specifications by Model
                                        Specifications are given by model in the following tables.
                                     200 V Class
                                                                                        Table 9.1 200 V Class Inverters
                                      Model Number
                                                                 23P7        25P5       27P5        2011        2015        2018       2022        2030        2037       2045        2055
                                      CIMR-L7B 
      Max. applicable motor out-
                                                                  3.7         5.5        7.5          11         15         18.5         22         30          37          45         55
      put (kW)*1
                                     Allowable frequency
                                                                                                                            5%
                                     fluctuation
                                        * 1. The maximum applicable motor output is given for a standard 4-pole Yaskawa standard motor. When selecting the actual motor and Inverter, be sure
                                             that the Inverter's rated current is higher than the motor's rated current.
                                        * 2. A transformer with dual star-delta secondary is required on the power supply for 12-pulse-rectification.
9-2
                                                                                                                                                          Inverter Specifications
                               400 V Class
                                                                                  Table 9.2 400 V Class Inverters
                                Model Number
                                                          43P7       44P0       45P5       47P5       4011      4015         4018     4022      4030       4037       4045       4055
                                CIMR-L7B 
Max. applicable motor out-
                                                           3.7        4.0        5.5        7.5        11        15          18.5      22         30        37         45         55
put (kW) *1
                                                           8.5         11        14         18         27        34          41        48         65        80         96        128
                               (A)
                               Allowable voltage
                                                                                                                 + 10%, - 15%
                               fluctuation
                               Allowable frequency
                                                                                                                       5%
                               fluctuation
                                  * 1. The maximum applicable motor output is given for a standard 4-pole Yaskawa standard motor. When selecting the actual motor and Inverter, be sure
                                       that the Inverter's rated current is higher than the motor's rated current.
                                  * 2. A transformer with dual star-delta secondary is required on the power supply for 12-pulse-rectification.
                                                                                                                                                                                          9-3
       Common Specifications
                                   The following specifications apply to both 200 V and 400 V class Inverters.
                                                                              Table 9.3 Common Specifications
                                 Model Number
                                                                                                          Specification
                                 CIMR-L7B 
                                                                                                        Sine wave PWM
                                Control method
                                                                                Closed-loop vector control, open-loop vector 1 control, V/f control
                                                                                                               8 kHz
                                Carrier Frequency
                                                                                      higher carrier frequency possible with current derating.
                                                                                                        3% (V/f control)
                                                                                                0.2% (open-loop vector 1 control)
                                Speed control accuracy
                                                                                                0.02% (closed-loop vector control)
                                                                                                          (25C  10C)
                                Torque limits                           Provided (4 quadrant steps can be changed by parameter settings.) (Vector control)
                                Torque accuracy                                                                 5%
      Control Characteristics
9-4
                                                                                                                              Inverter Specifications
                       Instantaneous overcur-
                                                                     Stops at approximately 200% of rated output current.
                       rent protection
                       Fuse blown protection                                         Stops for fuse blown.
                       Overvoltage protection
                                                            400 Class Inverter: Stops when main-circuit DC voltage is above 820 V.
Stall prevention Stall prevention during acceleration, deceleration and running independently.
Charge indicator Glows when the main circuit DC voltage is approximately 10 VDC or more.
                       Ambient operating
                                                                              95% max. (with no condensation)
Environment
humidity
                                                                                                                                                        9-5
                                                                                      10
                                                                  Appendix
This chapter provides precautions for the Inverter, motor, and peripheral devices and also provides lists of param-
eters.
        Selection
           Observe the following precautions when selecting an Inverter.
         Installing Reactors
           A large peak current can flow in the power input circuit when the Inverter is connected to a large-capacity
           power transformer (600 kVA or higher) or when switching a phase shifting capacitor. Excessive peak current
           can destroy the converter section. To prevent this, install a DC or AC reactor to improve the power supply
           power factor.
           If a thyristor converter, such as a DC inverter, is connected in the same power supply system, connect a DC or
           AC reactor regardless of the power supply conditions shown in the following diagram.
                                                        DC or AC reactor
                                     Power supply
                                                        required
                                     (kVA)
                                                                       DC or AC reactor not
                                                                       required
        Installation
           Observe the following precautions when installing an Inverter.
         Installation in Enclosures
           Install the Inverter in a clean location where it is not subjected to oil mist, dust, and other contaminants, or
           install the Inverter in a completely enclosed panel. Provide cooling measures and sufficient panel space so that
           the temperature surrounding the Inverter does not exceed the allowable temperature. Do not install the Inverter
           on wood or other combustible materials.
         Installation Direction
           Mount the Inverter vertically to a wall or other vertical surface.
        Settings
           Observe the following precautions when making settings for an Inverter.
10       Upper Limits
           The maximum output frequency can be set up to 120Hz. Setting the output frequency too high can damage the
           machine. So pay attention to the mechanical system and observe required limits for the output frequency.
         DC Injection Braking
           If the DC Injection Braking Current or the Braking Time are set too high the motor can overheat what can
           damage the motor
10-2
                                                                                  Inverter Application Precautions
 Acceleration/Deceleration Times
   The motor's acceleration and deceleration times are determined by the torque generated by the motor, the load
   torque, and the load's inertial moment (GD2/4). If the stall prevention functions are activated during accelera-
   tion or deceleration, it might be necessary to increase the acceleration or deceleration time.
   To reduce the acceleration or deceleration times, increase the capacity of the motor and Inverter.
 Handling
   Observe the following precautions during wiring or maintenance of an Inverter.
 Wiring Check
   The Inverter will be internally damaged if the power supply voltage is applied to output terminal U, V, or W.
   Check wiring for any mistakes before supplying power. Check all wiring and control sequences carefully.
10
                                                                                                                      10-3
       Motor Application Precautions
         Noise
           The noise generated in the motor depends on the carrier frequency. The higher the setting, the less is the gen-
           erated noise.
         Pole-changing Motor
           The rated input current of pole-changing motors differs from that of standard motors. Select an appropriate
           Inverter according to the maximum current of the motor.
         Single-phase Motor
           Do not use an Inverter for a single-phase motor. These motors are often equipped with capacitors Any capaci-
           tor directly connected to the Inverter output may damage the Inverter.
         Gearmotor
           The speed range for continuous operation differs according to the lubrication method and motor manufacturer.
           In particular, continuous operation of an oil-lubricated motor in the low speed range may result in burning. If
           the motor is to be operated at a speed higher than the rated speed, consult with the manufacturer.
10         If an oil-lubricated gearbox or speed reducer is used in the power transmission mechanism, oil lubrication will
           be affected when the motor operates only in the low speed range. The power transmission mechanism will
           make noise and experience problems with service life and durability if the motor is operated at a speed higher
           than the rated speed.
10-4
                                                                                                    EMC Compatibility
EMC Compatibility
 Introduction
   This manual was compiled to help system manufacturers using Yaskawa frequency Inverters to design and
   install electrical switch gear. It also describes the measures necessary to comply with the EMC Directive. The
   manual's installation and wiring instructions must therefore be followed.
   Our products are tested by authorized bodies using the standards listed below.
   Product standard: EN 61800-3:1996
   EN 61800-3; A11:2000
 Laying Cables
   Measures Against Line-Borne Interference:
   Line filter and frequency Inverter must be mounted on the same metal plate. Mount the two components as
   close to each other as possible, with cables kept as short as possible.
   Use a power cable with well-grounded shield. Use a shielded motor cable not exceeding 20 meters in length.
   Arrange all grounds so as to maximize the area of the end of the lead in contact with the ground terminal (e.g.
   metal plate).
   Shielded Cable:
   Use a cable with braided shield.
   Ground the maximum possible area of the shield. It is advisable to ground the shield by connecting the cable
   to the ground plate with metal clips (see following figure).
10
                                                                                                                           10-5
                                  Ground clip                         Ground plate
       The grounding surfaces must be highly conductive bare metal. Remove any coats of varnish and paint.
       Ground the cable shields at both ends.
       Ground the motor of the machine.
10
10-6
                                                                                                            Line Filters
Line Filters
 Recommended Line Filters for Varispeed L7
       Inverter Model                                           Line Filter
                                                                Current          Weight         Dimensions
       Varispeed L7                   Model
                                                                  (A)             (kg)          WxDxH
      CIMR-L7B23P77
                                  FS 5973-35-07                    35              1.4         141 x 46 x 330
      CIMR-L7B25P57
      CIMR-L7B27P57
                                  FS 5973-60-07                    60               3          206 x 60 x 355
      CIMR-L7B20117
      CIMR-L7B20157
                                 FS 5973-100-07                   100              4.9         236 x 80 x 408
      CIMR-L7B20187
      CIMR-L7B20227
                                 FS 5973-130-35                   130              4.3         90 x 180 x 370
      CIMR-L7B20307
      CIMR-L7B20377              FS 5973-160-40                   160               6          120 x 170 x 451
      CIMR-L7B20457
                                 FS 5973-240-37                   240               11         130 x 240 x 610
      CIMR-L7B20557
     IMPORTANT
                 2. Permissible emission of power inverter systems for commercial and light environment (EN61800-3, A11)
                    (general availability, 1st environment)                                                                10
                                                                                                                           10-7
       Installation Inverters and EMC filters
                      PE           L3
                                                        Ground bonds
                           L1 L2                    ( remove any paint )
PE
Line
                                                          Inverter
                            Filter
                            Load                        L2    V
                                                    PE L1 L3 U WPE
                        Cable length
                    as short as possible
Metal plate
10                                     Ground bonds
                                                                           Motor cable
                                                                            screened
                                   ( remove any paint )
                                                              M
                                                              3~
10-8
                                                                                         User Parameters
User Parameters
   The factory settings of each parameter are given in the following table.
                                                                               Factory
    No.                                                  Name                                  Setting
                                                                               Setting
   A1-00     Language selection for Digital Operator display                      0
   A1-01     Parameter access level                                               2
   A1-02     Control method selection                                             0
   A1-03     Initialize                                                           0
   A1-04     Password                                                             0
   A1-05     Password setting                                                     0
  A2-01 to
             User specified parameters                                            
   A2-32
   b1-01     Reference source selection                                           0
   b1-02     Run Command source selection                                         1
   b1-03     Stopping method selection                                            0
   b1-06     Control input scan                                                   1
   b1-07     Operation selection after switching to remote mode                   0
   b1-08     Run Command selection in programming modes                           0
   b2-08     Magnetic flux compensation volume                                   0%
   b4-01     Timer function ON-delay time                                       0.0 s
   b4-02     Timer function OFF-delay time                                      0.0 s
                                                                               0.0 Hz
   b6-01     Dwell frequency at start
                                                                              0.0% (PM)
   b6-02     Dwell time at start                                                0.0 s
                                                                               0.0 Hz
   b6-03     Dwell frequency at stop
                                                                              0.0% (PM)
   b6-04     Dwell time at stop                                                 0.0 s
   b7-01     Droop control gain                                                 0.0 %
   b7-02     Droop control delay time                                           0.05 s
   b8-01     Energy-saving mode selection                                         0
   b8-16     Energy savings control parameter Ki                                0.10
   b8-17     Energy savings control parameter Kt                                1.00
   C1-01     Acceleration time 1                                                3.00 s
   C1-02     Deceleration time 1                                                3.00 s
   C1-03     Acceleration time 2                                                3.00 s
   C1-04     Deceleration time 2                                                3.00 s
   C1-05     Acceleration time 3                                                3.00 s
   C1-06     Deceleration time 3                                                3.00 s
   C1-07     Acceleration time 4                                                3.00 s
   C1-08     Deceleration time 4                                                3.00 s
   C1-09     Fast stop time                                                     3.00 s
   C1-10     Accel/decel time setting unit                                        0
                                                                                                           10-9
                                                                                 (Continued)
                                                                    Factory
        No.                                                Name                  Setting
                                                                    Setting
        C3-02   Slip compensation delay time                        2000 ms
        C3-03   Slip compensation limit                              200%
        C3-04   Slip compensation selection during regeneration        1
                                                                       1
        C3-05   Output voltage limit operation selection
                                                                     0 (PM)
        C4-01   Torque compensation gain                              1.00
        C4-02   Torque compensation delay time parameter            200 ms *1
        C4-03   Starting torque compensation (FWD)                    0.0%
        C4-04   Starting torque compensation (REV)                    0.0%
        C4-05   Starting torque compensation time parameter          10 ms
        C4-06   Torque compensation primary delay time 2             150 ms
                                                                     40.00
        C5-01   ASR proportional (P) gain 1
                                                                   3.00 (PM)
                                                                     0.500 s
        C5-02   ASR integral (I) time 1
                                                                  0.300 s (PM)
                                                                     20.00
        C5-03   ASR proportional (P) gain 2
                                                                   3.00 (PM)
        C5-04   ASR integral (I) time 2                              0.500 s
                                                                     0.004 s
        C5-06   ASR primary delay time
                                                                     0.020 s
                                                                     0.0 Hz
        C5-07   ASR switching frequency
                                                                   2.0% (PM)
        C5-08   ASR integral (I) limit                               400%
                                                                     40.00
        C5-09   ASR proportional (P) gain 3
                                                                   3.00 (PM)
                                                                     0.500 s
        C5-10   ASR integral (I) time 3
                                                                  0.300 s (PM)
        C5-15   ASR gain for encoder offset tuning                    5.00
        C6-02   Carrier frequency selection                            3*2
10 d1-05
        d1-06
                Frequency reference 5
                Frequency reference 6
                                                                   0.00 Hz*3
                                                                   0.00 Hz*3
        d1-07   Frequency reference 7                              0.00 Hz*3
        d1-08   Frequency reference 8                              0.00 Hz*3
                                                                    50.00 Hz
        d1-09   Nominal speed reference
                                                                  100.00% (PM)
        d1-10   Intermediate speed 1 reference                      0.00 Hz*3
10-10
                                                                        User Parameters
                                                                             (Continued)
                                                            Factory
No.                                               Name                        Setting
                                                            Setting
d1-11   Intermediate speed 2 reference                     0.00 Hz*3
d1-12   Intermediate speed 3 reference                     0.00 Hz*3
d1-13   Reveling speed reference                           0.00 Hz*3
                                                            25.00 Hz
d1-14   Inspection speed reference
                                                          50.00% (PM)
                                                            4.00 Hz
d1-17   Leveling speed reference
                                                          8.00% (PM)
d1-18   Speed priority selection                               0
d6-03   Field forcing function selection                       0
d6-06   Field forcing function Limit                         400%
E1-01   Input voltage setting                             200 VAC*4*5
E1-03   V/f pattern selection                                  F
                                                           60.0 Hz*5
E1-04   Max. output frequency (FMAX)
                                                         96 min-1 (PM)*2
E1-05   Max. output voltage (VMAX)                        200 VAC*4*5
                                                           60.0 Hz*5
E1-06   Base frequency (FA)
                                                         96 min-1 (PM)*2
E1-07   Mid. output frequency (FB)                         3.0 Hz*1*5
E1-08   Mid. output frequency voltage (VB)               14.0 VAC*1*4*5
E1-09   Min. output frequency (FMIN)                       1.5 Hz*1*5
E1-10   Min. output frequency voltage (VMIN)             7.0 VAC*1*4*5
E1-13   Base voltage (VBASE)                               0.0 VAC*6
E2-01   Motor rated current                                14.00 A*2
E2-02   Motor rated slip                                   2.73 Hz*2
E2-03   Motor no-load current                               4.50 A*2
E2-04   Number of motor poles                                4 poles
E2-05   Motor line-to-line resistance                      0.771 *2
E2-06   Motor leak inductance                               19.6%*2
E2-07   Motor iron saturation coefficient 1                   0.50
E2-08   Motor iron saturation coefficient 2                   0.75
E2-09   Monitor mechanical losses                             0.0%
E2-10   Motor iron loss for torque compensation             112 W*2
E2-11   Motor rated output power                           3.70 kW*2
E2-12   Motor iron saturation coefficient 3                   1.30
E5-04
E5-05
        Number of motor poles
                                                            3.860*2
                                                                                            10
E5-06   d-axis inductance                                  30.20 mH*2
                                                                                           10-11
                                                                                                      (Continued)
                                                                                           Factory
        No.                                                 Name                                      Setting
                                                                                           Setting
                                                                                            600*2
        F1-01   PG parameter
                                                                                          8192 (PM)
        F1-02   Operation selection at PG open circuit (PGO)                                  1
        F1-03   Operation selection at overspeed (OS)                                         1
                                                                                              3
        F1-04   Operation selection at deviation
                                                                                           1 (PM)
                                                                                              0
        F1-05   PG rotation
                                                                                           1 (PM)
        F1-06   PG division rate (PG pulse monitor)                                           1
        F1-08   Overspeed detection level                                                   115%
        F1-09   Overspeed detection delay time                                              0.0 s
        F1-10   Excessive speed deviation detection level                                   10%
        F1-11   Excessive speed deviation detection delay time                              0.5 s
        F1-14   PG open-circuit detection delay time                                        1.0 s
        F1-18   DV3 fault detection selection                                                 1
        F1-19   DV4 fault detection selection                                               1024
        F1-21   Absolute encoder resolution                                                   2
        F1-22   Magnet position offset                                                     60deg
        F1-25   Encoder copy selection                                                        0
        F1-26   Encoder copy write permission selection                                       0
                                                                                              2
        F4-01   Channel 1 monitor selection
                                                                                           5 (PM)
        F4-02   Channel 1 gain                                                             100.0%
        F4-03   Channel 2 monitor selection                                                   3
        F4-04   Channel 2 gain                                                             50.0%
        F4-05   Channel 1 output monitor bias                                               0.0%
        F4-06   Channel 2 output monitor bias                                               0.0%
        F4-07   Analog output signal level for channel 1                                      0
        F4-08   Analog output signal level for channel 2                                      0
        F5-01   Channel 1 output selection                                                    0
        F5-02   Channel 2 output selection                                                    1
        F5-03   Channel 3 output selection                                                    2
        F5-04   Channel 4 output selection                                                    4
        F5-05   Channel 5 output selection                                                    6
        F5-06   Channel 6 output selection                                                   37
        F5-07   Channel 7 output selection                                                   0F
        F5-08   Channel 8 output selection                                                   0F
        F5-09   DO-08 output mode selection                                                   0
        F6-01   Operation selection after communications error                                1
10      F6-02
        F6-03
                Input level of external error from communications option card
                Stopping method for external error from communications option card
                                                                                              0
                                                                                              1
        F6-04   Trace sampling from communications option card                                0
        F6-05   Current monitor unit selection                                                0
        F6-06   Torque reference/torque limit selection from communications option card       1
        H1-01   Terminal S3 function selection                                            24 (80)*7
        H1-02   Terminal S4 function selection                                            14 (84)*7
        H1-03   Terminal S5 function selection                                             3 (81)*7
10-12
                                                                           User Parameters
                                                                                (Continued)
                                                                Factory
No.                                                 Name                         Setting
                                                                Setting
H1-04   Terminal S6 function selection                          4 (83)*7
H1-05   Terminal S7 function selection                          6 (F)*7
H2-01   Terminal M1-M2 function selection                         40
H2-02   Terminal M3-M4 function selection                         41
H2-03   Terminal M5-M6 function selection                          6
H3-01   Frequency reference AI-14B CH1signal level selection       0
H3-02   Frequency reference AI-14B CH1 input gain               100.0%
H3-03   Frequency referenceAI-14B CH1 input bias                 0.0%
H3-04   AI-14B CH3 signal level selection                          0
H3-05   AI-14B CH3 function selection                              2
H3-06   AI-14B CH3 input gain                                   100.0%
H3-07   AI-14B CH3 input bias                                    0.0%
H3-08   AI-14B CH2 signal level selection                          0
H3-09   AI-14B CH2 function selection                              3
H3-10   AI-14B CH2 input gain                                   100.0%
H3-11   AI-14B CH2 input bias                                    0.0%
H3-12   Analog input filter time parameter for the AI-14B        0.03 s
H3-15   Terminal A1 function selection                             0
H3-16   Terminal A1 input gain                                  100.0%
H3-17   Terminal A1 input bias                                   0.0%
H5-01   Slave address                                             1F
H5-02   Communication speed selection                              3
H5-03   Communication parity selection                             0
H5-04   Stopping method after communication error                  3
H5-05   Communication error detection selection                    1
H5-06   Send wait time                                           5 ms
H5-07   RTS control ON/OFF                                         1
                                                                   1
L1-01   Motor protection selection
                                                                5 (PM)
L1-02   Motor protection time parameter                        1.0 min*5
L2-05   Undervoltage detection level                           190 VDC*4
L2-11   Battery Voltage                                        0 VDC*4
L3-01   Stall prevention selection during accel                    1
L3-02   Stall prevention level during accel                      150%
L3-03   Stall prevention limit during accel                      50%
L3-04   Stall prevention selection during decel                    0
L3-05   Stall prevention selection during running                  1
L3-06   Stall prevention level during running                    150%
                                                                0.0 Hz
L4-01   Speed agreement detection level
                                                               0.0% (PM)
                                                                2.0 Hz
                                                                                               10
L4-02   Speed agreement detection width
                                                               4.0% (PM)
                                                                0.0 Hz
L4-03   Speed agreement detection level (+/-)
                                                               0.0% (PM)
                                                                2.0 Hz
L4-04   Speed agreement detection width (+/-)
                                                               4.0% (PM)
L4-05   Operation when frequency reference is missing              0
                                                                                              10-13
                                                                                                          (Continued)
                                                                                             Factory
         No.                                                 Name                                         Setting
                                                                                             Setting
        L4-06     Frequency reference at frequency reference loss                             80.0%
        L5-01     Number of auto restart attempts                                                2
        L5-02     Auto restart operation selection                                               1
        L5-03     Fault restart interval time                                                  2.0 s
        L5-05     Under voltage fault restart selection                                          0
        L6-01     Torque detection selection 1                                                   4
        L6-02     Torque detection level 1                                                     150%
        L6-03     Torque detection time 1                                                     10.0 s
        L6-04     Torque detection selection 2                                                   0
        L6-05     Torque detection level 2                                                     150%
        L6-06     Torque detection time 2                                                      0.1 s
        L7-01     Forward inverter torque limit                                                200%
        L7-02     Reverse inverter torque limit                                                200%
        L7-03     Forward regenerative torque limit                                            200%
        L7-04     Reverse regenerative torque limit                                            200%
        L7-06     Torque limit time parameter                                                 200 ms
        L7-07     Torque Limit Operation during accel/decel                                      0
        L8-02     Overheat pre-alarm level                                                    75 C*2
        L8-03     Operation selection after overheat pre-alarm                                   3
10      N8-46
        N9-60
                  Inductance measurement current level
                  A/D conversion start delay timer
                                                                                              10.0%
                                                                                              0.0 s
10-14
                                                                                              User Parameters
                                                                                                   (Continued)
                                                                                   Factory
No.                                                Name                                             Setting
                                                                                   Setting
                                                                                      0
o1-04   Setting unit for frequency parameters related to V/f characteristics
                                                                                   1 (PM)
o1-05   LCD Display contrast adjustment                                               3
o2-01   LOCAL/REMOTE key enable/disable                                               0
o2-02   STOP key during control circuit terminal operation                            0
o2-03   Parameter initial value                                                       0
o2-04   kVA selection                                                                4*2
o2-05   Frequency reference setting method selection                                  0
o2-06   Operation selection when digital operator / LED monitor is disconnected       0
o2-07   Cumulative operation time setting                                            0 hr.
o2-08   Cumulative operation time selection                                           1
o2-09   Initialize Mode                                                               0
o2-10   Fan operation time setting                                                   0 hr.
o2-12   Fault trace initialize                                                        0
o2-15   No of Travels monitor initialize                                            0
o3-01   Copy function selection                                                       0
o3-02   Read permission selection                                                     0
        Zero-servo gain 2
                                                                                    0 ms
                                                                                     0.00
                                                                                                                  10
 *11
                                                                                                                 10-15
                                                                                                                                                        (Continued)
                                                                                                                                    Factory
            No.                                                       Name                                                                               Setting
                                                                                                                                    Setting
        S3-01        Short-floor function selection                                                                                     0
        S3-08        Output phase order                                                                                                 0
        S3-09        Frequency reference loss fault detection                                                                           0
        S3-13        Traction sheave diameter                                                                                       400 mm
        S3-14        Roping                                                                                                             2
        S3-16        Over acceleration detection level                                                                                 1.5
        S3-17        Over acceleration deceleration time parameter                                                                   0.050 s
        S3-18        Over acceleration detection method selection                                                                       0
                                                                                                                                        0
        S3-23        Distance calculation deceleration time gain
                                                                                                                                     2 (PM)
        S3-25        Factory-set parameter 1                                                                                            0
            *11
                                                                                                                                       1*9
        T1-01        Autotuning mode selection
                                                                                                                                     4 (PM)
        T1-02        Motor output power                                                                                           3.70 kW*10
        T1-03        Motor rated voltage                                                                                           190.0 V*4
        T1-04        Motor rated current                                                                                          14.00 A*10
        T1-05        Motor base frequency                                                                                           60.0 Hz
        T1-06        Number of motor poles                                                                                           4 poles
        T1-07        Motor base speed                                                                                             1450 min-1
        T1-08        Number of PG pulses                                                                                          600 PPR*10
        T1-09        Motor no-load current                                                                                       4.05 (E2-03)
        *    1. The factory settings will change when the control method is changed. (V/f control factory settings are given.)
        *    2. The factory settings depend on the Inverter capacity. The values for a 200 V class Inverter for 3.7 kW are given.
        *    3. The factory setting changes to 0.00% when using closed-loop vector control (PM).
        *    4. These are values for a 200 V class Inverter. Values for a 400 V class Inverter are double.
        *    5. The factory settings will change according to parameter o2-09. Values shown here are for when o2-09 is set to 0.
        *    6. After autotuning, E1-13 will contain the same value as E1-05.
        *    7. Value will change to number in parenthesis when parameter d1-18 equals 1 or 2.
10      *
        *
        *
             8. Applicable for L7-Series Inverters with software versions PRG: 2012 or later.
             9. Set T1-02 and T1-04 when 2 is set for T1-01. For V/f control a set value 2 is possible only.
             10.The factory settings depend on the Inverter capacity. The values provided are for a 200 V class Inverter for 3.7 kW and when o2-09 is set to 0.
        *    11.Applicable for L7-Series Inverters with software versions PRG: 2013 or later.
10-16
Revision History
The revision dates and numbers of the revised manuals are given on the bottom of the back cover.
    Date of          Rev.
   Publication       No.          Section                                               Revised Content
YASKAWA
In the event that the end user of this product is to be the military and said product is to be
employed in any weapons systems or the manufacture thereof, the export will fall under
the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade
Regulations. Therefore, be sure to follow all procedures and submit all relevant
documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice
                                                                                                 MANUAL NO. TOEP C710676 08B
for ongoing product modifications and improvements.                                              Published in Japan June 2008 08-1 1
 2008 YASKAWA ELECTRIC CORPORATION. All rights reserved.                                        08-5-10