Anixter Ref PDF
Anixter Ref PDF
REFERENCE GUIDE
ANSI/TIA/EIA-606
ANSI/TIA/EIA-607
Now Including:
Current Telecommunications Systems Bulletins:
TSB-67, TSB-72, TSB-75 & TSB-95
Current Addendum
TIA/EIA-568-A-1, A-2, A-3, A-4, A-5(e) and B.3
Anixter Levels
  Anixter: The Cabling Systems Experts
Abbreviation References:
   ANSI American National Standards Institute
   ASTM American Society for Testing and Materials
   CSA     Canadian Standards Association
   EIA     Electronic Industries Alliance
   IEEE Institute of Electrical & Electronic Engineers
   NEC     National Electric Code
   NEMA National Electrical Manufacturers Association
   NFPA National Fire Protection Association
   TIA     Telecommunications Industry Association
   UL      Underwriters’ Laboratories
                        Table of Contents
                                                                                  i
Purpose of the ANSI/TIA/EIA-568-A Standard
 The Purpose:
    • Establish a generic telecommunications cabling
      standard that will support a multivendor environment
    • Enable the planning and installation of a structured
      cabling system for commercial buildings
    • Establish performance and technical criteria for
      various cabling system configurations
    ii
                          Table of Contents
                   ANSI/TIA/EIA-568-A
Commercial Building Telecommunications
Cabling Standard
Design Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
The Six Subsystems of a Structured Cabling System . . . . . . . . 1
    Building Entrance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
    Equipment Room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
    Backbone Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
        Design Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
    Telecommunications Closet . . . . . . . . . . . . . . . . . . . . . . . . . . 4
    Horizontal Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
        Specified Topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
        Maximum Distances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
        Telecommunications Outlet . . . . . . . . . . . . . . . . . . . . . . 5
        8-Position Modular Jack Pair Assignments . . . . . . . . . 6
    Work Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
        Work Area Components . . . . . . . . . . . . . . . . . . . . . . . . . 6
Media and Connecting Hardware
Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
    100 Ohm Unshielded Twisted-Pair Cabling Systems . . . 7
        Horizontal Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
        Backbone Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
        UTP Connecting Hardware and Cords . . . . . . . . . . . . 10
    150 Ohm Shielded Twisted-Pair (STP-A)
    Cabling Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
        Horizontal and Backbone STP-A Cable . . . . . . . . . . . 12
        150 Ohm STP-A Data Connector . . . . . . . . . . . . . . . . 13
        150 Ohm STP-A Patch Cable . . . . . . . . . . . . . . . . . . . 13
    Optical Fiber Cabling Systems . . . . . . . . . . . . . . . . . . . . . . . . 14
        Optical Fiber Cabling Media . . . . . . . . . . . . . . . . . . . . . . 14
        Optical Fiber Connector . . . . . . . . . . . . . . . . . . . . . . . . . 15
        Optical Fiber Telecommunications Outlet . . . . . . . . . . 15
                                                                                         iii
TSB-67 Bulletin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
TSB-72 Bulletin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
TSB-75 Bulletin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
TSB-95 Bulletin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Addenda to TIA/EIA-568-A . . . . . . . . . . . . . . . . . . . . . . . . 23
   568-A-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
   568-A-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
   568-A-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
   568-A-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
   568-A-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
TIA/EIA-568-B.3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
iv
Design Considerations
2. Equipment Room
     The design aspects of the equipment room are specified in
the TIA/EIA-569-A standard. Equipment rooms usually house
equipment of higher complexity than telecommunications
closets. Any or all of the functions of a telecommunications
closet may be provided by an equipment room.
                                                        1
3. Backbone Cabling
      The backbone cabling provides interconnection between
telecommunication closets, equipment rooms and entrance
facilities. It consists of the backbone cables, intermediate and
main cross-connects, mechanical terminations and patch
cords or jumpers used for backbone-to-backbone cross-
connection. This includes:
      • Vertical connection between floors (risers)
      • Cables between an equipment room and building
         cable entrance facilities
      • Cables between buildings (interbuilding)
   2
Other Design Requirements
    • Star topology
    • No more than two hierarchical levels of cross-connects
    • Bridge taps are not allowed
    • Main and intermediate cross-connect jumper or
      patch cord lengths should not exceed 20 meters
      (66 feet)
    • Avoid installing in areas where sources of high levels
      of EMI/RFI may exist
    • Grounding should meet the requirements as defined
      in TIA/EIA-607
                                           Equipment Room
                                               Intermediate
                                              Cross-connect
Telecommunications Closets
                                                              3
4. Telecommunications Closet
     A telecommunications closet is the area within a
building that houses the telecommunications cabling system
equipment. This includes the mechanical terminations and/or
cross-connect for the horizontal and backbone cabling
system. Please refer to TIA/EIA-569-A for the design
specifications of the telecommunications closet.
   4
           Maximum Distances for Horizontal Cabling
Telecommunications Outlet
                                                        5
       8-Position Modular Jack Pair Assignments for UTP
T568-A T568-B
6. Work Area
     The work area components extend from the
telecommunications (information) outlet to the station
equipment. Work area wiring is designed to be relatively
simple to interconnect so that moves, adds and changes
are easily managed.
Work Area Components
    • Station Equipment—computers, data terminals,
      telephones, etc.
    • Patch Cables—modular cords, PC adapter cables,
      fiber jumpers, etc.
    • Adapters(baluns, etc.)—must be external to
      telecommunications outlet
   6
Media and Connecting Hardware
Performance Specifications
100 ohm Unshielded Twisted-Pair (UTP)
Cabling Systems
Horizontal Cable
      As transmission rates have increased, higher performance
UTP cabling has become a necessity. In addition, some means
of classifying horizontal UTP cables and connecting hardware by
performance capability had to be established. These capabilities
have been broken down to a series of categories as follows:
Category 3
    Cables/connecting hardware with transmission
parameters characterized up to 16 MHz
Category 4
    Cables/connecting hardware with transmission
parameters characterized up to 20 MHz
Category 5
    Cables/connecting hardware with transmission
parameters characterized up to 100 MHz
                                                          7
                     Horizontal UTP Cable
   8
                      Backbone UTP Cable
                                                        9
UTP Connecting Hardware and Cords
     To ensure that installed connecting hardware
(telecommunications outlets, patch cords and panels,
connectors, cross-connect blocks, etc.) will have minimal effect
on overall cabling system performance, the characteristics and
performance parameters presented in this section shall be met.
 Attenuation/NEXT Loss
Frequency        Category 3      Category 4       Category 5
(MHz)            (dB)            (dB)             (dB)
 1.0             0.4 / 58        0.1 / 65         0.1 /65
 4.0             0.4 / 46        0.1 / 58         0.1 / 65
 8.0             0.4 / 40        0.1 / 52         0.1 / 62
 10.0            0.4 / 38        0.1 / 50         0.1 / 60
 16.0            0.4 / 34        0.2 / 46         0.2 / 56
 20.0            -/-             0.2 / 44         0.2 / 54
 25.0            -/-             -/-              0.2 / 52
 31.25           -/-             -/-              0.2 / 50
 62.5            -/-             -/-              0.3 / 44
 100.0           -/-             -/-              0.4 / 40
 10
 Maximum Attenuation of Cable Used in Patch Cords
Frequency       Category 3      Category 4       Category 5
(MHz)           (dB)            (dB)             (dB)
 1.0            3.1             2.6              2.4
 4.0            6.7             5.2              4.9
 8.0            10.2            7.4              6.9
 10.0           11.7            8.3              7.8
 16.0           15.7            10.7             9.9
 20.0           -               12.0             11.1
 25.0           -               -                12.5
 31.25          -               -                14.1
 62.5           -               -                20.4
 100.0          -               -                26.4
                                                          11
150 Ohm Shielded Twisted-Pair (STP-A)
Cabling Systems
     The recognized twisted-pair (STP) cables are IBM-type
1A for backbone and horizontal distribution and IBM-type 6A
for patch cables.
 12
                    STP-A Data Connector
 Attenuation/NEXT
 Frequency                       Attn/NEXT
 (MHz)                           (dB)
 4.0                             .05/ 65
 8.0                             .10/ 65
 10                              .10/ 65
 16                              .15/ 62.4
 20                              .15/ 60.5
 25                              .15/ 58.5
 31.25                           .15/ 56.6
 62.50                           .20/ 50.6
 100                             .25/ 46.5
 300                             .45/ 36.9
                                                      13
Optical Fiber Cabling Systems
Optical Fiber Cabling Media
    • Horizontal—62.5/125 µm multimode optical fiber
      (minimum of two fibers)
    • Backbone—62.5/125 µm multimode and 8.3/125 µm
      single-mode optical fiber
 Cable Transmission Performance Parameters
 Multimode (Horizontal and Backbone)
 Wavelength     Maximum Attenuation   Min. Bandwidth
 (nm)           (dB/km)               (MHz-km)
 850            3.75                  160
 1300           1.5                   500
 14
Optical Fiber Connector
Specified Connector: 568SC
Color Identification
     • beige—62.5/125 µm multimode connector/coupling
     • blue—8.3/125 µm single-mode connector/coupling
Note 1: Applications with an installed base of ST-type fiber
connectors are “grandfathered” for continued use in both
current and future updates of existing optical fiber networks.
                                                           15
TIA/EIA TSB-67
Transmission Performance Specification for
Field Testing of Unshielded Twisted-Pair Cabling
Systems (10/95)
     For the purposes of testing UTP cabling systems, the
horizontal link is assumed to contain a telecommunications
outlet/connector, a transition point, 90 meters of UTP Category
3, 4 or 5 cable, a cross-connect consisting of two blocks or
panels and a total of 10 meters of patch cords. The figure
below shows the relationship of these components.
           Cross-Connect
                               Transition
                               Point         Outlet
                                                      Patch Cord
          Patch
          Cord
Basic Link
Channel Link
 16
Basic/Channel Link Attenuation
Frequency    Category 3     Category 4        Category 5
(MHz)        (dB)           (dB)              (dB)
 1           3.2/4.2        2.2/2.6           2.1/2.5
 4           6.1/7.3        4.3/4.8           4/4.5
 8           8.8/10.2       6/6.7             5.7/6.3
 10          10/11.5        6.8/7.5           6.3/7
 16          13.2/14.9      8.8/9.9           8.2/9.2
 20          -              9.9/11            9.2/10.3
 25          -              -                 10.3/11.4
 31.25       -              -                 11.5/12.8
 62.5        -              -                 16.7/18.5
 100         -              -                 21.6/24
                                                     17
TIA/EIA TSB-72
Centralized Optical Fiber Cabling Guidelines (10/95)
      The ANSI/TIA/EIA-568-A standard provides maximum
flexibility for distributed electronics for multi-tenant
buildings. TSB-72 offers guidelines for single-tenant users
who prefer centralized electronics (i.e. server farms)
connected by a fiber horizontal and fiber backbone.
Termination Shelf
                                              Interbuilding
                                              Trunk Cable
                                                                                                  MDC
 18
TIA/EIA TSB-75
Additional Horizontal Cabling Practices for Open
Offices (8/96)
     This document specifies optional practices for open
office environments, for any Horizontal telecommunications
cabling recognized in TIA/EIA 568-A.
                                Multi-User
  Telecommunications            Telecommunications
  Closet                        Outlet Assembly
                   Patch
    Equipment      cords                             Work area cables
    cable
                                                           Work Area
   Backbone
   cable
                                                                        19
 Maximum Work Area Cable length is
 determined by the following table:
 Length of             Maximum                        Maximum combined length
 horizontal            length of work                 of work area cables, patch
 cable                 area cable                     cords and equipment cable
 m (ft)                m (ft)                         m (ft)
 90 (295)              3 (10)                         10 (33)
 85 (279)              7 (23)                         14 (46)
 80 (262)              11 (36)                        18 (59)
 75 (246)              15 (49)                        22 (72)
 70 (230)              20 (66)                        27 (89)
Note: No Work Area cable length may exceed 20 meters (66 feet).
     For Optical Fiber, any combination of Horizontal,
Work Area cables, patch cords and equipment cords may
not exceed 100 meters (328 ft).
                                                 Work area telecommunication
                                                 outlet/connector or multi-user
 Telecommunications                              telecommunications outlet assembly
 Closet                     Horizontal Cabling
  Horizontal          Consolidation
  Cross-Connect       Point
                                                             Work area
                       Connecting                            cables
                       hardware
   Backbone
   cable
                                                 Work Area
 20
TIA/EIA TSB 95
Additional Transmission Performance Guidelines for
4-Pair 100 MHz Category 5 Cabling (10/99)
     This Systems Bulletin describes Return Loss and Equal
Level Far End Crosstalk (ELFEXT) recommendations and
additional test methods for Cat 5 cable. It also describes
Power Sum ELFEXT, because newer applications (1000BASE-
T) will use simultaneous bi-directional transmission (full
duplex) over all four pairs.
     While the important topics of TSB-95 are covered
briefly here, appropriate test equipment is required, and
contemporary test equipment contains software to simplify,
compare and report the results (only up to 100 MHz).
     The Return Loss will be less than 15 dB for both the
basic link and channel for any frequency less than 20 MHz,
and decrease exponentially for frequencies from 20–100 MHz.
 Frequency                       Return Loss
 (MHz)                           (dB)
 1                               15
 4                               15
 8                               15
 10                              15
 16                              15
 20                              15
 25                              14.03
 31.25                           13.06
 62.5                            10.05
 100                             8.01
                                                     21
     ELFEXT and PSELFEXT upper limitations of the worst
pair of the channel are shown below.
              ELFEXT, Channel or       PSELFEXT, Channel
 Frequency    Basic Link, Worst Pair   or Basic Link
 (MHz)        (dB)                     (dB)
 1.0          57.0                     54.4
 4.0          45.0                     42.4
 8.0          38.9                     36.3
 10.0         37.0                     34.4
 16.0         32.9                     30.3
 20.0         31.0                     28.4
 25.0         29.0                     26.4
 31.25        27.1                     24.5
 62.5         21.1                     18.5
 100.0        17.0                     14.4
 22
Addenda to TIA/EIA-568-A
TIA/EIA-568-A-1 (Addendum 1) (9/97)
                                                        23
TIA/EIA-568-A-3 (Addendum 3) (12/98)
 24
FEXT (Far-End Crosstalk): A measure of the unwanted
signal coupling from a transmitter at the near-end into a
neighboring pair measured at the far-end.
PSELFEXT (Power Sum Equal-Level Far-End Crosstalk):
A computation of the unwanted signal coupling from multiple
transmitters at the near-end into a pair measured at the far-
end, relative to the received signal level on that same pair.
PSNEXT (Power Sum Near-End Crosstalk): A computation of
the unwanted signal coupling from multiple transmitters at
the near-end into a (non-energized) pair measured at the
near-end.
 UTP Cable
Frequency NEXT    PSNEXT   ELFEXT   PSELFEXT   Return Loss
(MHz) (dB)        (dB)     (dB)     (dB)       (dB)
 1        65.3    62.3     63.8     60.8       20.0
 4        56.3    53.3     51.7     48.7       23.0
 8        51.8    48.8     45.7     42.7       24.5
 10       50.3    47.3     43.8     40.8       25.0
 16       47.3    44.3     39.7     36.7       25.0
 20       45.8    42.8     37.7     34.7       25.0
 25       44.3    41.3     35.8     32.8       24.3
 31.25    42.9    39.9     33.9     30.9       23.6
 62.5     38.4    35.4     27.8     24.8       21.5
 100      35.3    32.3     23.8     20.8       20.1
                                                         25
UTP Connecting Hardware
 Frequency          NEXT        FEXT        Return Loss
(MHz)               (dB)        (dB)        (dB)
 1                  65.0        65.0        35.0
 4                  65.0        63.1        35.0
 8                  64.9        57.0        35.0
 10                 63.0        55.1        35.0
 16                 58.9        51.0        35.0
 20                 57.0        49.1        34.0
 25                 55.0        47.1        32.0
 31.25              53.1        45.2        30.1
 62.5               47.1        39.2        24.1
 100                43.0        35.1        20.0
26
UTP Channel
 Frequency   NEXT   PSNEXT   ELFEXT   PSELFEXT   Return Loss
(MHz)        (dB)   (dB)     (dB)     (dB)       (dB)
 1           60.0   57.0     57.4     54.4       17.0
 4           53.6   50.9     45.3     42.4       17.0
 8           48.6   45.7     39.3     36.3       17.0
 10          47.0   44.1     37.4     34.4       17.0
 16          43.6   40.6     33.3     30.3       17.0
 20          42.0   39.0     31.4     28.4       17.0
 25          40.4   37.3     29.4     26.4       16.0
 31.25       38.7   35.7     27.5     24.5       15.1
 62.5        33.6   30.6     21.5     18.5       12.1
 100         30.1   27.1     17.4     14.4       10.0
                                                         27
TIA/EIA-568-B.3
 28
Optical Fiber Connector
No Specified Connector: 568SC and other duplex designs
may be used.
Color Identification
     • beige—multimode connector/coupling
     • blue—single-mode connector/coupling
                                                         29
Purpose of the ANSI/TIA/EIA-569-A Standard
    30
                            Table of Contents
                     ANSI/TIA/EIA-569-A
Commercial Building Standard for
Telecommunications Pathways and Spaces
Design Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Service Entrance Pathways . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Entrance Facilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Equipment Room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Intrabuilding Backbone Pathways . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Telecommunications Closet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Horizontal Pathways . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
    Underfloor Duct . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
    Flushduct . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
    Multichannel Raceway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
    Cellular Floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
    Trenchduct . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
    Access Floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
    Plenum/Ceiling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
    Conduit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
    Cable Trays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
    Perimeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Consolidation Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Electromagnetic Interference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Firestops . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
                                                                                                 31
              Pathways and Spaces
 1. Electric Entrance
 2. Telco Entrance
 3. Telecom Equipment Room
 4. Data
 5. Voice
 6. Telecom Closet
 7. Grounding & Bonding
 8. Underfloor System
32
TIA/EIA-569-A Design Considerations
Service Entrance Pathways
     For underground facilities, use a minimum 4-inch
conduit or duct constructed of PVC type B, C or D; multiple
plastic duct; galvanized steel; fiber glass; with appropriate
encasement. No more than two 90° manufactured bends
are allowed (10 times the diameter). Drain slope should
not be less than 12 inches per 100 feet. Recommended
conduit fill varies but should not exceed 40 percent for
more than two cables.
     Maintenance holes (typically 3,500 lb./sq. in., concrete)
must be equipped with sump, corrosion-protected pulling
iron, cable racks, grounded ladder, and only such
power/light conductors as required for telecommunications
support per NEC requirements.
Entrance Facilities
      Entrance facilities include the pathways for outside carrier
services, interbuilding backbone, alternate entrance and
antennae entrance pathways. The entrance facilities consist
of a termination field interfacing any outside cabling to the
intrabuilding backbone cabling. The local telephone carrier is
typically required to terminate cabling within 50 feet of building
penetration, and to provide primary voltage protection.
      In buildings larger than 20,000 usable square feet, a
locked, dedicated, enclosed room is recommended. Beyond
70,000-square feet, a locked, dedicated room is required,
with a plywood termination field provided on two walls. In
buildings up to 100,000 usable square footage, a wall-
mounted termination field may serve as the entrance facility,
using 3/4-inch plywood, 8-feet high. Beyond 100,000-square
feet, rack-mounted and free-standing frames may also be
required. Minimum space requirements are given as follows:
                                                           33
 Gross Building
 Floor Space
 (sq. ft.)        Plywood Field            Room Dimension
 5,000            8’ high × 39” wide
 10,000           8’ high × 39”
 20,000           8’ high × 42”            (A room recommended
 40,000           8’ high × 68”            beyond this level)
 50,000           8’ high × 90”
 60,000           8’ high × 96”            (A dedicated room req’d.)
 80,000           8’ high × 120”           12’ × 6.3’
 100,000          8’ high × 2 walls        12’ × 6.3’
 200,000          8’ high × 2 walls        12’ × 9’
 400,000          8’ high × 2 walls        12’ × 13’
 500,000          8’ high × 2 walls        12’ × 15.6’
 600,000          8’ high × 2 walls        12’ × 18.3’
 800,000          8’ high × 2 walls        12’ × 22.3’
 1,000,000        8’ high × 2 walls        12’ × 27.7’
Rule of Thumb: Allow one square foot of plywood wallmount for
each 200 square-foot area of floor space.
Equipment Room
      An equipment room is essentially a large
telecommunications closet that may house the main
distribution frame, PBXs, secondary voltage protection, etc.
The equipment room is often appended to the entrance
facilities or a computer room to allow shared air conditioning,
security, fire control, lighting and limited access.
 Number of                             Equipment Room
 Workstations                          Floor Space (sq. ft.)
 1–100                                 150
 101–400                               400
 401–800                               800
 801–1,200                             1,200
Rule of Thumb: Provide 0.75 square feet of equipment room
floor space for every 100 square feet of user workstation area.
 34
Location
      Typically, rooms should be located away from sources of
electromagnetic interference (transformers, motors, x-ray,
induction heaters, arc welders, radio, radar) until interference
is less than 3 V/m across the frequency spectrum. Avoid
sources of flooding.
Perimeters
     Typically, no false ceiling; all surfaces treated to reduce dust;
walls and ceiling painted white or pastel to improve visibility.
Limited Access
       Typically, single or double 36" × 80" lockable doors.
Other
    Typically, no piping, ductwork, mechanical equipment or
power cabling should be allowed to pass through the
equipment room. No unrelated storage.
HVAC
    24 hours/day, 365 days/year, 64°-75°F, 30%-55%
humidity, positive pressure.
Lighting
     Typically, 8.5 feet high, providing 50-foot candles @
3 feet above floor.
Electrical
    Typically, a minimum of two dedicated 15A, 110VAC
duplex outlets on separate circuits is required. Convenience
duplex outlets shall be placed at 6-foot intervals around the
perimeter. Emergency power should be considered and
supplied, if available.
Dust
       Less than 100 micrograms/cubic meter/24-hour period
Note: The term “typically” is applied here to indicate, where
applicable, that these requirements also apply to other elements
of the cabling system spaces. Lighting requirements, for instance,
are largely identical for entrance facilities, equipment rooms and
telecommunications closets.
                                                               35
Intrabuilding Backbone Pathways
     Within a building, the intrabuilding backbone pathways
extend between the entrance facilities, equipment room and
telecommunications closets. Telecom closets should be
stacked vertically above each other on each floor, and
provided with a minimum of three 4-inch sleeves (a stub of
conduit through the floor) for less than 50,000 square feet
served. An equivalent 4" × 12" slot may be used in lieu of
three sleeves. Firestopping is required. If closets are not
vertically aligned, then 4-inch horizontal conduit runs are
required. Include no more than two 90° bends between pull
points. Pulling iron or eyes embedded in the concrete for
cable pulling is recommended. Fill should not exceed
40 percent for any run greater than two cables.
                                     8
                            7
                                     4
                            5
                       6
                                     3
                                                          2
10
 36
Telecommunications Closet
     The telecommunications closet on each floor is the
junction between backbone and horizontal pathways. It
contains active voice and data telecommunications
equipment, termination fields and cross-connect wiring.
     More than one telecom closet per floor is required if
distance to a work area exceeds 300 feet, or if floor area
served exceeds 10,000 square feet. Recommended closet
sizing is 10' × 11' for each 10,000 square-foot area served.
     Power, lighting, air conditioning and limited access
are typical. See requirements for Equipment Room. There
are a minimum of three 4-inch firestopped backbone sleeves
in the floor at the left side of a plywood termination field,
which are ideally located near the door. A fire extinguisher
is recommended.
                                           Power                                                         Power
                               Equipment    bar                       Instrument                          bar Equipment
                                 power                                  power                                   power
                                                        Front
Front
Riser Sleeve
                                                            4"
                                                     Inside Diameter
1" minimum
                                                                                                                                     37
Horizontal Pathways
      Horizontal pathways extend between the
telecommunications closet and the work area. A variety of
generic pathway options are described. Choice of pathway(s)
is left to the discretion of the designer. The most commonly
employed pathway consists of cable bundles run from the
telecom closet along J-hooks suspended above a plenum
ceiling, fanning out once a work zone is reached, dropping
through interior walls or support columns or raceways, and
terminating at an information outlet (I/O). Other options are:
Underfloor Duct
     Single- or dual-level rectangular ducts imbedded in
greater than 2.5-inch concrete flooring.
Flushduct
     Single-level rectangular duct imbedded flush in greater
than 1-inch concrete flooring.
Multichannel Raceway
     Cellular raceway ducts capable of routing telecom
and power cabling separately in greater than 3-inch
reinforced concrete.
Cellular Floor
     Pre-formed hollows, or steel-lined cells, are provided in
concrete, with header ducts from the telecom closet
arranged at right angles to the cells.
Trenchduct
      A wide, solid tray, sometimes containing compartments,
and fitted with a flat top(with gaskets) along its entire length.
It is embedded flush with the concrete finish.
Access Floor
   Modular floor panels supported by pedestals, used in
computer rooms and equipment rooms.
Plenum/Ceiling
     Bundled cables, suspended above a false ceiling, fan out
to drop through walls or along support columns to
baseboard level.
 38
Conduit
    To be considered only when outlet locations are
permanent, device density low and flexibility (future
changes) not required.
Cable Trays
     Options include channel tray, ladder tray, solid bottom,
ventilated and wireway.
Perimeter Pathways
     Options include surface raceway, recessed, molding and
multichannel (to carry separate power and lighting circuits).
Perimeter Pathway
Telcom
                                                              39
A Variety of Horizontal Pathways
Trenchduct
Access Floor
                Suspended
                  ceiling
                           Utility
                          Column
 40
Consolidation Points and MUTOs
      Consolidation Points provide limited area connection
access. Typically a permanent flush wall, ceiling or support
column-mounted panel serves modular furniture work areas.
The panels must be unobstructed and fully accessible without
moving fixtures, equipment or heavy furniture.
      A Multi-User Telecommunication Outlet (MUTO) is
another methodology to reduce cabling moves, adds and
changes in modular furniture settings. The user cord is
directly connected to the MUTO. A MUTO location must be
accessible and permanent, and may not be mounted in
ceiling spaces or under access flooring. Similarly, it cannot
be mounted in furniture unless that furniture is permanently
secured to the building structure.
      For more descriptive information on distance limitations
and purposes of Consolidation Points and MUTOs, see
ANSI/TIA/EIA TSB-75.
Electromagnetic Interference
      Voice and data telecommunications cabling should not
be run adjacent and parallel to power cabling—even along
short distances—unless one or both cable types are shielded
and grounded. For low-voltage communication cables, a
minimum 5-inch distance is required from any fluorescent
lighting fixture or power line over 2 kVA and up to 24 inches
from any power line over 5 kVA*. In general, telecommuni-
cations cabling is routed separately, or several feet away from
power cabling. Similarly, telecommunications cabling is
routed away from large motors, generators, induction
heaters, arc welders, x-ray equipment, and radio frequency,
microwave or radar sources.
*Note: Distance recommendations from (1990) TIA/EIA-569 are reproduced
here by popular request. For current recommendations, refer to NEC/NFPA 70,
Article 800-52.
                                                                       41
Firestops
      Annex A of the standard discusses various types of
packing used to re-establish the integrity of fire-rated
structures when these barriers have been penetrated by
cable. The section that briefly discusses passive mechanical
systems and non-mechanical systems such as putty, caulk,
cements, intumescent sheets and strips, silicone foams and
pre-manufactured pillows. The most common method is
stuffing the aperture with ceramic/mineral wool and caulking
both sides with fire-resistant putty. The information refers the
designer to check manufacturer specifications and UL ratings
against NFPA, ASTM and NEC codes.
                             Firestopping putty
                                  or caulk
                                       Metallic conduit
                                       sleeve or cable
                               Ceramic fibre
                              or mineral wool
Wall assembly
 42
Notes
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
                                                  43
Purpose of the ANSI/TIA/EIA-606 Standard
 44
                              Table of Contents
                        ANSI/TIA/EIA-606
Administration Standard for the
Telecommunications Infrastructure of
Commercial Buildings
Administration Concepts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
    Identifiers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
    Telecommunication Records . . . . . . . . . . . . . . . . . . . . . . . . . . 46
    Optional Linkages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
    Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
    Work Orders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
    Identification Formats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
    Circuit Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Administrative Labeling Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Summary of Record Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Pathway & Space Administration . . . . . . . . . . . . . . . . . . . . . . . . . . 51
    Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Wiring System Administration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
    Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Grounding and Bonding Administration . . . . . . . . . . . . . . . . . . . 54
    Label Text . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Label Color Coding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
                                                                                              45
TIA/EIA-606
Administrative Concepts
    The typical administration system includes records,
reports, drawings and work orders.
Identifiers
     Each space, pathway, cable termination point and
ground is assigned a unique identifier—a number that can
be simply encoded to provide supplemental information.
Telecommunication Records
     Minimum required records for each cable, space,
pathway, ground, termination hardware and position are
maintained. These records are required to be linked (cross-
referenced) to all related records.
Optional linkages
     Optional linkages may be made to other records. Such
records might include blueprints, PBX records, equipment
inventories (phones, PCs, software, LAN, furniture) and user
codes (extension, account billing number, passwords).
     It is desirable that reports can be generated from one or
more sets of interlinked records in a variety of formats.
Drawings
     Drawings, both conceptual and as-built, include floor
plans, cable schematics and rack layouts.
Work orders
     Work orders may involve spaces, pathways, cables,
splices, terminations or grounding, individually or in
combination. The work order should list those responsible
for physical changes, as well as those updating the
documentation to ensure future accuracy.
 46
Identification Formats
     A unique alphanumeric identification code is created
for every location, pathway, cable and termination point.
Suggestions in the standard include:
                                                         47
     The actual format in the preceding chart is not mandated
by the standard. However, the chosen format must be
consistent and provide a unique identifier number for each
system element. This method lends itself to organization and
updating of multiple records by the use of powerful relational
databases (three-dimensional spreadsheet) programs.
Some Identifier Examples
    J0001               Label for an information outlet jack
     D306              Designation for a work area
      3A-C17-005       Termination in closet 3A, column C,
                       row 17, block position 005
      Examples like those above (taken from the TIA/EIA 606
text and Administrative Labeling Map) indicate the flexibility
of conventions that can be established for purposes of
naming. Logical naming conventions can also convey
considerable additional information about other linkages.
Circuit Example
    As an alternate conceptual example, this string of
codes (resembling links on an Internet address) logically
describes a series of voice communication links. It can be
read as follows:
     JONES / X2440 / LC99 / A001V1 / C001 / TC.A001V1 /
     HC01 / Pr1.2. / MDF.C17005 / PBX.01A0203
     Bob Jones,
     at extension 2440,
     is connected by line cord 99
     to information outlet A001, voice jack 1.
     Cable 001 extends from that voice jack
     To telecom closet A, where it terminates on a block
     labeled by adding TC in front of A001V1 (the I/O label).
     The voice signals travel on house cable 01,
     Carried on pairs 1, 2.
     The pairs terminate at the main distribution frame in
     column C, row 17, block position 005.
     They are interconnected to PBX 01, row A, card 02, port 03.
 48
Administrative Labeling Map
     Here is a combination schematic/elevation view of a
structured telecommunications cabling system, detailing a
TIA/EIA-606-compliant labeling scheme. The example
records in this booklet follow the labeling shown below.
                               Telecommunications                Pathway          Work Area
                               Closet 3A                         CD34             D306
                                             Term. Hdwr.                    MH
            Term. Pos.                       B101-02                                Splice
  Eq.       C4R6-001                                                                S106
  Bond.
  Cond.     Term. Pos.                       Term. Pos.
  EC101     B101-01-A1                       C3R6-001
                                                                         HH
                                             Term. Hdwr.   Entrance Entrance
  TMGB      Term. Hdwr.                                    Cable    Pathway
                            EQUIPMENT        C3R6                                Handhole
            B101-01                                        CB01     CD02         HH01
                               LEGEND
               Grounding
               Electrode            Cross-        Grounding      Telecom.            Outside
               System               Connect       Busbar         Outlet              scope of
                                                                                     standard
                                                                                        49
Summary of Record Elements
     This table outlines the minimum required information
and required linkages. Further information is optional. A
multi-dimensional database or spreadsheet is helpful.
            Record        Required Information       Required Linkages To
            Pathway       Pathway Identification #   Cable Records
                          Pathway Type               Space Records
  Pathways                Pathway Fill               Pathway Records
    &                     Pathway Load               Grounding Records
  Spaces   Space          Space Identification #     Pathway Records
                          Space Type                 Cable Records
                                                     Grounding Records
            Cable         Cable Identification #     Termination Records
                          Cable Type                 Splice Records
                          Unterminated Pair #s       Pathway Records
                          Damaged Pair #s            Grounding Records
                          Available Pair #s
            Termination   Termination Hardware #s    Term. Position Records
  Wiring    Hardware      Term. Hardware Type        Space Records
                          Damaged Position #s        Grounding Records
            Termination   Termination Position #     Cable Records
            Position      Term. Position Type        Other Term. Records
                          User Code                  Term. Hardware Records
                          Cable Pair/Condition #s    Space Records
            Splice        Splice Identification #    Cable Records
                          Splice Type                Space Records
            TMGB          TMGB Identification #      Bonding Conductor
                          Busbar Type                Records
                          Grounding Conductor #s     Space Records
                          Resistance to Earth
                          Date of Measurement
  Grounding Bonding       Bonding Conductor ID#      Grounding Busbar
                          Conductor Type             Records
            Conductor     Busbar Identification #    Pathway Records
            TGB           Busbar Identification #    Bonding Conductor
                          Busbar Type                Records
                                                     Space Records
 50
Pathway & Space Administration
    Here are examples of a conduit path and telecom closet
space record (see Administrative Labeling Map). The TIA/EIA
606 standard also includes examples of cable tray, work area
and manhole records.
 Pathway Record             Sample Data    Explanatory Notes
 Required Information
 Pathway Identification #   CD43           conduit 43
 Pathway Type               2” EMT         size 2 metal conduit
 Pathway Fill               20%            present fill
 Pathway Load               N/A            no conduit load spec.
 Required Linkages
 Cable Records              C0001, C0002
 Space Record (end 1)       D306           office 306 floor 3,
 Space Record (end 2)       3A             closet A pull/splice
 Space Record (access)      D302           box above D302 other
 Pathway Record                            pathway record
 Grounding Record           N/A
                                                            51
Space Record                Sample Data      Explanatory Notes
Required Information
 Space Identification #     3A               floor 3, closet A
 Space Type                 TC               telecom closet
Required Linkages
 Pathway Records            CD34, CT64       pathways terminating here
 Cable Records              C0001, C0002     cables terminating here
 Grounding Record           TGB35            grounding busbar
 52
Termination Hardware         Sample Data Explanatory Notes
Required Information
 Term. Hardware ID#          3A-C17       closet 3A, column C, row 17
 Term. Hardware Type         110          110 punchdown block
 Damaged Position #s         0            none damaged
Required Linkages
 Term. Position Record 1     3A-C17-001   4-pair cable terminations
                                        (positions 2-9 not shown)
 Term. Position Record 10    3A-C17-010   last termination
 Space Record                3A           floor 3, closet A
 Grounding Record            N/A
Optional information could include voltage protection positions
and type, etc.
     Here is a termination position record for an information
outlet (see Administrative Labeling Map).
 Termination Position        Sample Data Explanatory Notes
 Required Information
 Term. Position ID#          J0011        information outlet jack 11
 Term. Position Type         IDC          insul. displacement
                                          connection
 User Code                   x8021        telephone extension
 Cable Pairs                 1–4          4-pair modular
 Required Linkages
 Cable Record                C0011        cable serving this
                                          information outlet
 Other Term. Pos. Record 1   3A-C17-005   term. at other end
 Other Term. Pos. Record 2   3A-A17-001   cross-connect term.
 Term. Hardware Record       N/A          N/A for work area
 Space Record                D307         office 307
Optional information c.ould include jack catalog number, signal
type (voice/data), category, etc.
                                                                53
     The TIA/EIA-606 standard provides numerous examples
of single and separately administered spliced cables.
 Splice Record             Sample Data Explanatory Notes
 Required Information
 Splice Identification #   S106       splice 106
 Splice Type               Fusion     splicing method
 Required Linkages
 Cable Record              F18        fiber cable 18
 Space Record              MH01       manhole 01
Grounding/Bonding Administration
     Telecommunications systems require a reliable electrical
ground reference potential, provided by a dedicated
grounding/bonding conductor network. Bonding conductor
cabling shall be colored green or labeled appropriately with
an alphanumeric identifier and warning label.
                            WARNING
                IF THIS CLAMP OR CABLE
            IS LOOSE OR MUST BE REMOVED,
               PLEASE CALL THE BUILDING
            TELECOMMUNICATIONS MANAGER
 54
Label Color Coding
      Shown here are the color codes used for termination
field labels.
                                                             55
   The Purpose of ANSI/TIA/EIA-607
 56
                            Table of Contents
                         ANSI/TIA/EIA-607
ANSI/TIA/EIA-607 Commercial Building
Grounding And Bonding Requirements For
Telecommunications
Design Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Schematic Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
                                                                                                 57
Design Considerations
    Solid copper grounding busbars are installed
with insulated standoffs in entrance facilities
(1/4" thick × 4" high × variable length) and the
equipment room, as well as each telecom closet
(2" high is sufficient here). Each busbar is drilled
with rows of holes according to NEMA standards,
for attachment of bolted compression fittings.
     Telecommunications equipment, frames,
cabinets and voltage protectors are typically
grounded to these busbars. Busbars are connected
by a backbone of insulated, solid copper cable
between all closets and rooms (minimum 6 AWG,
3/0 AWG recommended). This backbone is
connected to a main grounding busbar in the
telecommunications entrance facility, to an earth
ground in the electrical entrance facility, and
to structural steel on each floor. Bonding
conductor cabling shall be colored green or
labeled appropriately.
Terms
    • Telecommunications Main Grounding
      Busbar (TMGB)
    • Telecom Bonding Backbone (TBB)
    • Telecom Grounding Busbar (TGB)
    • Telecom Bonding Backbone Interconnecting Bonding
      Conductor (TBBIBC)
 58
        Schematic of Grounding/Bonding Network
                                                                    To Upper Floors
                               TGB Detail
                                Variable
                                                                        Telco Closet
                                                                    Telcom
                                                     1/4"          Equipment
                     2"
                                                                            Panel
                      TBB
                      6 AWG Minimum
                                                                          TGB
Structural Steel
Panel Panel
TMGB TGB
                                                                                          59
 The History of Anixter Levels Program
 60
                           Table Of Contents
Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
   The Levels Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
   Levels XP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Levels and the Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
   Comparison Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
                                                                                                  61
The Anixter Levels® Program
      The Levels Program is a set of purchasing specifications.
These specifications are designed to ensure the products we
sell perform to your expectations. Our cabling solutions are
divided into three distinct performance levels so you can
select the solution that best meets your application needs:
  Levels                            Application
    5                                 Ethernet
    6                               Fast Ethernet
    7                              Gigabit Ethernet
 62
Levels XP
     Levels XP—expanded performance—introduces
active (Mbps-based) testing. Active testing transcends the
passive (MHz-based) testing used in the Anixter Levels
Channel (ALC) and Levels component specifications and
those in industry standards.
     Levels XP specifications require testing that examines
and characterizes everything from the PC to the server—
NICs, hub/switch ports, environmental factors, short cable
lengths and much more. This active channel testing allows
Anixter to verify network efficiency. It also indicates how well
active and passive devices work together in the real world.
Testing an XP solution includes three essential steps:
      1. Passive testing of all Levels-rated components
      2. Passive and basic efficiency (SmartBits) testing
of all end-to-end Anixter Level Channels (ALC)
      3. Testing of active networking components over
cabling systems in many environments and a variety
of configurations.
      To achieve Anixter Levels XP certification, each channel
must be able to transmit a series of worst-case Ethernet
waveforms that represent typical network glitches. This
testing is accomplished by running Fast Ethernet and Gigabit
Ethernet over cabling systems and determining the efficiency
of that cabling channel.
                                                            63
                            Active Testing @ 100 Mbps
                                                          PSNEXT**
                                                            Cable                                not specified             32.3                   42.3
                                                            Connector                            not specified          not specified         not specified
                                                            Channel                              not specified             27.1                   37.1
                                                          PSACR**
                                                            Cable                                not specified          not specified             22.5
                                                            Channel                              not specified          not specified             15.8
                                                          PSELFEXT**
                                                            Cable                                not specified             20.8                   24.8
                                                            Connector                            not specified          not specified         not specified
                                                            Channel                              not specified             14.4                   20.3
                                                          Return Loss**
                                                            Cable                                    15.0                  20.1                   20.1
                                                            Connector                                14.0                  20.0                   24.0
                                                            Channel                              not specified             10.0                   12.0
                                                        *(The LOWER the number, the better the solution)    **(The HIGHER the number, the better the solution)
      64
How Anixter Levels Exceed the Standards
Cat 5
XP 7
                                                         Source: Anixter
                                                             Levels Lab
200 MHz 350 MHz 400 MHz 350 MHz 400 MHz
                                                                                                  65
Reference Documents for Further
Information on Cabling Standards
TIA/EIA-568-A     (1995)
    Commercial Building Telecommunications Cabling Standard
TIA/EIA-569-A     (1998)
    Commercial Building Standard for Telecommunications
    Pathways and Spaces
TIA/EIA-570-A     (1999)
    Residential and Light Commercial Telecommunication
    Wiring Standard
TIA/EIA-606       (1993)
    Administration Standard for the Telecommunications
    Infrastructure of Commercial Buildings
TIA/EIA-607       (1994)
    Commercial Building Grounding/Bonding Requirements
    for Telecommunications.
TIA/EIA-758       (1999)
    Customer-Owned Outside Plant Telecommunications
    Cabling Standard
IS0/IEC 11801     (1995)
    Generic Cabling for Customer Premises
IEEE 802.3-1998   (1998)
    Carrier Sense Multiple Access with Collision Detection
    (CSMA/CD) Access Method and Physical layer Specification
    (also known as ANSI/IEEE Std 802.3-1998 or ISO 8802-3:
    1990 (E))
IEEE 802.5-1998   (1998)
    Token Ring Access Method and Physical Layer
    Specifications (also known as ANSI/IEEE Std 802.5-1998)
 66
Obtaining TIA and EIA Documents
     TIA and EIA documents may be purchased through
Global Engineering Documents at 1-800-854-7179 or
www.global.ihs.com. IEEE documents may be purchased
through IEEE, P.O. Box 1331, Piscataway, NJ 08855 or
www.ieee.org. CSA documents may be purchased through
the Canadian Standards Association at www.csa.ca or call
(416) 747-4000.
                                                     67
Notes
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
 68
     For further assistance or more information contact your
local Anixter sales office, or 1-800-ANIXTER.
                 Worldwide Headquarters:
                        Anixter Inc.
                       4711 Golf Rd.
                  Skokie, IL 60076-1278
                      847/677-2600
                 http://www.anixter.com
                                                        69
                1 - 8 0 0 - A N I X T E R • w w w. a n i x t e r. c o m
     Worldwide Distribution • Technical Expertise • Best-in-Class Partnerships • Market Specialization
#148947 30K 07/00–CP Printed in U.S.A. on Recycled Paper 0H0004X0 © 2000 Anixter Inc.