Air Condenser
Air Condenser
Air Condenser
R K O S - 0100 - C S - H 2 -8
UNIT VOLTAGE: 2: 240/1/60
5: 208-240/3/60
9: 480/3/60
8: 600/3/60
Optional equipment
Mechanical Electrical
-Soldered or replaceble liquid line kit (dryer & sight glass) -Auxiliary contacts
-Solenoid valve -Phases monitor
-Suction accumulator, regular or with boil-out coil -Electric defrost kit with fuses
-Suction filter, soldered or replaceable and evaporator (s) contactor (s)
-Oil separator -Defrost timer
-Oil level control device (parallel) -Non fused disconnect switch
-Main suction and liquid valves -Fused disconnect switch
-Hot gas defrost kit -Fan cycling (2 or 3 fans) for indoor units
-Oversized receiver
-Suction to liquid heat exchanger
-Adjustable head pressure controls (under 10 HP)
-Custom color paint for housing
-Factory installed pressure gauges
-Hot gas by-pass valves
-Discharge line muffler
-Heat reclaim valve
-Etc. Custom made units are available,please consult factory
R22 COPELAND SEMI-HERMETIC COMPRESSORS
HIGH TEMPERATURE
LOW TEMPERATURE
MEDIUM TEMPERATURE
LOW TEMPERATURE
HIGH TEMPERATURE
MEDIUM TEMPERATURE
MEDIUM TEMPERATURE
LOW TEMPERATURE
MEDIUM TEMPERATURE
MEDIUM TEMPERATURE
LOW TEMPERATURE
DIMENSIONAL DATA
MODEL A B C D E F G
0008 @ 0030 38 21 41 22 18
0040 @ 0060 38 23 43 1/2 24 18
0070 @ 0100 44 23 43 1/2 24 21
0150 @ 0250 50 25 45 1/2 26 24
0270 @ 0400 60 25 45 1/2 26 30
Specification
Base and housing: Sturdy heavy gage galvanized steel formed base. The base also allows the contractor to
install pipes clamps to secure its pipe run to the roof opening. Weather proof enclosure made
of white pre-painted thick gage aluminum, rust proof hardware on unit from 0008 to 0200 and
galvanized steel enclosures on unit 0250 and higher. The hood style design, when open
gives full access to all the components on the outdoor units.
Condenser coil: The condenser coil is enclosed in a galvanized casing. The 3/8” copper riffled tubes are
mechanically expanded in self-spaced, full-collared aluminum corrugated plate fins for
permanent bond and maximum heat transfer. All coils have 10 fins per inch for easy cleaning
and high efficiency. A separate and efficient sub-cooling circuit is integrated at the base of the
coil to provide a vapor free liquid to the metering device. Coils are pressure tested under water
with 400 PSIG. They are dried with nitrogen and shipped pressurized. A factory installed fixed
head pressure flooding valve (adjustable for 10 HP or more) is installed to maintain an
adequate head pressure during the low ambient temperature operation, (outdoor units only).
The condenser coil incorporates a friction free expansion coil design.
Fans: Direct driven 20” diameter fans are installed on 1/2 hp motor on units from 0008 to 0220 and
30” diameter fans are installed on 1 hp motors for model 0250 and higher. 20 inch diameter
fans have 1" venturi and 30" diameter fans have 3 3/4 spun venturi to provide maximum fan
efficiency and minimum noise level. Fans are protected by a baked on powder epoxy coating
fan guard; each fan section is divided to prevent by-pass. Each fan is statically and
dynamically balanced to provide a vibration free operation.
Receiver: The receiver is sized to hold the entire charge of the evaporator, condenser and liquid line
refrigerant when the unit is in a pump down mode, (based on standard installations), oversized
receivers are available. On outdoor units, the receiver vessel is heated and insulated to
maintain an adequate pressure during the cold season. A fusible safety plug or pressure relief
valve and service valves are standard on each unit.
Controls: Located in a sturdy galvanized steel enclosure, built to provide an easy access to every
component, the control panel contains all the electrical devices such as contactors, fuses,
timer, compressor time delay relay, terminal block etc, standard and optional controls. A pump
down switch is mounted on the side of the box to be operated without the need to open the
enclosure.
Piping: Hard drawn copper pipes and vibration absorber are used in every condensing unit with
semi-hermetic compressor.
Compressor: Kool-Air will select the most efficient compressors, from a wide range of manufacturer to
perform the work. Adjustable dual pressure controls (with flexible hoses), crankcase heater
(outdoor unit), rubber or spring mounts are standard equipment. On some compressors oil
level sight glass, oil pump, oil failure switch, internal overheat protection, suction and discharge
valves are standard when required.
HEAD OFFICE:
REFRIGERATION KOOL-AIR INC.
Quebec, Canada
Tel: (450) 346-5007 • Toll free: 1-866-346-5007 • Fax: (450) 346-7631
Email: kool-air@kool-air-inc.com • Web site: www.kool-air-inc.com
Due to Kool-Air policies to continuously improve the quality of its products, specifications are subject to
change without notice