Product Specifications                                                                              PSS 2B-4H1 A
130 Series
Pneumatic Indicating Controllers
                          130M                              130P                        130F
These controllers are designed for high-density control room mounting and are used wherever precise control is
required for efficient process management.
The basic controller is the 130M Series featuring              INDEPENDENT AUTOMATIC AND MANUAL
manual set point adjustment. The 130P Series is                CONTROL UNITS
similar to the 130M except that the set point is               Either the automatic control unit or the manual unit
pneumatically adjusted by a remote signal. The 130F            can be removed without disturbing the process. This
Series is similar to the 130M except that it includes a        design feature avoids costly shutdowns for controller
Remote/Local switch which allows either manual or              servicing.
pneumatic adjustment of the set point.
                                                               FULLY BALANCELESS AND BUMPLESS
HIGHLY VISIBLE AND BOLD DISPLAY                                TRANSFER
The large, brightly colored pointers, located directly         The 130 Series Controllers feature the “integral
behind the transparent vertical scale, provide a level         balancing” method for bumpless transfer. After
of visibility and ease of reading which has become a           transfer, the controller simply responds at the integral
benchmark for judging other display concepts. This             (reset) rate to eliminate any error between set point
system provides continuous full scale display of all           and measurement. In addition to providing easy,
variables, effective display of controller deviation, and      balanceless and bumpless transfer, this scheme
easy scale changing without tools.                             preserves the set point.
PSS 2B-4H1 A
Page 2
SIMPLE, LOW-COST MOUNTING                                  FORCE BALANCE CONTROL MODULE
One multiple unit shelf can accommodate up to 10           The time-proven force balance control module
instruments. All air connections are made when the         ensures long life and dependability. The use of metal
controllers are installed in the shelf. Piping costs are   bellows with virtually no motion of the flexure-
minimized because each shelf has its own integral air      suspended mechanism provides the user with a
supply header with individual air shutoff valves.          clearly superior controller.
EASY TO SERVICE                                            SPECIALIZED CONTROLLERS FOR EVERY
The introduction of the 130 series dramatically            APPLICATION
advanced the state-of-the-art of pneumatic control         Foxboro offers the widest selection of optional
systems with a unique pneumatic circuit board. This        accessories and unusual control functions in the
circuit board eliminates much of the tubing and many       industry. Among these, in addition to the normal
of the connections found in other controllers. All the     control modes, are single station ratio, single station
components are located on one side of this board and       computer-set, auto selector, differential gap, and
are easily accessible by sliding back one side cover.      “batch”.
                                       PERFORMANCE SPECIFICATIONS
                                     (Under Reference Operating Conditions)
Accuracy                                                   Dead Band
 MEASUREMENT AND SET-POINT INDICATORS                       AUTOMATIC CONTROL UNIT
  ±0.5% of span                                              Less than 0.1% of span
 OUTPUT INDICATOR                                           MEASUREMENT AND SET-POINT INDICATORS
  ±2% of span                                                Less than 0.1% of span
Repeatability (Measurement and Set-Point                   Supply Pressure Effect
Indicators)                                                 A 5% change in supply pressure, within the normal
  Better than 0.25% of span                                 operating limits, will cause the output to change less
                                                            than 0.1% of span in automatic at 100% proportional
Alignment Error (Automatic Control Unit)                    band; 0.2% of span in manual.
 Less than 0.5% of span
                                        FUNCTIONAL SPECIFICATIONS
                                                  MODEL CODE
  Controller with Manually Positioned Set Point                                                        130M-N
  Controller with Pneumatically Positioned Set Point                                                   130P-N
  Controller with Remote/Local Set Point                                                               130F-N
  Control Function
  On-Off                                                                                                  1
  Proportional                                                                                            2
  Proportional plus Derivative                                                                            3
  Proportional plus Integral (Reset)                                                                      4
  Proportional plus Integral (Reset) plus Derivative                                                      5
Mode Adjustment Limits                                     Ambient Temperature Limits
 PROPORTIONAL BAND                                          –20 and +65°C (0 and 150°F).
   5 to 500%
 INTEGRAL (RESET) ACTION                                   Supply Pressure
   0.01 to 50 minutes per repeat                            140 to 150 kPa (20 to 22 psi or 1.4 to 1.5 bar or
 DERIVATIVE ACTION                                          kg/cm2).
   0.01 to 50 minutes
                                                                                                  PSS 2B-4H1 A
                                                                                                        Page 3
                                     FUNCTIONAL SPECIFICATIONS (Cont.)
Input, Output Signal                                      Control Action Reversal
  20 to 100 kPa, 3 to 15 psi, or 0.2 to 1.0 bar or         The control action is reversed by a 90° rotation of the
  kg/cm2, as specified                                     reversing switch.
Air Consumption under Normal Operation                    Auto-Manual Transfer Unit
 0.5 m3/h at standard conditions (0.3 scfm) in             A two-position switch lever located on the front of the
 automatic; 1.0 m3/h at standard conditions                manual unit is used to switch directly from automatic
 (0.6 scfm) in manual. Add 0.08 m3/h at standard           to manual or, on controllers with integral (reset),
 conditions (0.05 scfm) for units with derivative          from manual to automatic without bumping the
 action.                                                   process.
                                           PHYSICAL SPECIFICATIONS
Mounting                                                  Scales
 These controllers are designed for flush mounting in      VERTICAL SCALE
 vertical panels 3 to 25 mm (0.13 to 1 in) thick using      Removable, transparent plastic with black
 101 or 102 Series Shelves. Each controller requires        markings; 100 divisions, scaled as specified.
 one unit of shelf capacity. They may be calibrated for    OUTPUT
 mounting in a panel inclined up to 75° from vertical       Black markings on a white background, 20
 with the rear of the instrument lower than the front.      divisions from 0 to 100% output signal. The black
 Specify mounting angle.                                    pointer continuously indicates automatic or manual
                                                            output.
Connections
 Separate electric and pneumatic connectors are           Nameplate
 located on the rear of the chassis in accordance with     White translucent plastic with 2.5 mm (0.1 in) high
 the standard arrangement for 100 Line Shelves.            black letters. There can be a maximum of 2 lines
                                                           with 17 characters or spaces per line.
Pointers
 MEASUREMENT                                              Construction
   Red                                                     The front and rear panels are die-cast aluminum
 MANUAL SET (130M SERIES) AND REMOTE SET                   secured between extruded aluminum top and
 (130P AND 130F SERIES)                                    bottom rails which retain sheet steel side covers.
   Black on white
 LOCAL SET (130F SERIES)                                  Finish
   Black                                                   The finish is gray acrylic enamel or equivalent.
 OUTPUT                                                   Nominal Dimensions (Including manual unit)
   Black                                                   205 mm high x 70 mm wide x 555 mm deep
                                                           (8.2 in high x 2.8 in wide x 21.8 in deep).
                                                          Mass (Approximate)
                                                           5 kg (11 lb)
PSS 2B-4H1 A
Page 4
                                                    OPTIONAL FEATURES
Output Gauge                                                         External Connection to Integral (Reset) Bellows
 A plug-in output gauge may be supplied in place of                   Used when an external feedback signal must be
 the manual unit to provide continuous indication of                  applied to prevent integral circuit saturation. Not
 the output signal. Specify by substituting 131 for 130               available with the ESPC option or “Batch”
 in the model number.                                                 modification. Specify AS Reference ECRB.
Controller Less Manual Unit                                          External Set Point Connection
 A plug-in blank base plate is supplied in place of the               The 130F Series is available with a connection
 manual unit. Specify by substituting 132 for 130 in                  providing access to the set point signal. The
 the model number.                                                    maximum transmission distance is 1.5 metres
                                                                      (5 feet) and all external connections must be leak-
“Batch” Modification                                                  tight due to low air delivery of the aspirating relay.
 Prevents integral (reset) circuit saturation during                  Use a 1:1 repeating relay for longer transmission
 shutdown or other periods of sustained set point and                 distances. Not available with the ECRB option or
 measurement deviation. Includes internal                             “Batch” modification. Specify AS Reference ESPC.
 adjustment for preload.
 HIGH “BATCH”                                                        Opaque Nameplates
  Operates when controller output signal exceeds                      Nameplates in several colors may be substituted for
  100 kPa, 15 psi, or 1.0 bar or kg/cm2. Specify by                   the standard nameplate at no extra charge.
  substituting 130FB, 130MB, or 130PB for 130F,                                 Description
                                                                                                              AS
  130M, or 130P in the model number.                                    Characters      Background         Reference
 LOW “BATCH”
  Operates when controller output signal falls below                   White                   Blue         N/P-B
                                                                                               Green        N/P-G
  20 kPa, 3 psi, or 0.2 bar or kg/cm2. Specify by
                                                                                               Orange       N/P-O
  substituting 130FB, 130MB, or 130PB for 130F,
  130M, or 130P in the model number and adding                                                 Red          N/P-R
  AS Reference BSL.                                                    Black                   Yellow       N/P-Y
Alarm Actuators and Alarm Lights
 Refer to GS 2B-12C1 A.
                                                 ORDERING INSTRUCTIONS
                                     1. Model Number
                                     2. Input, Output Signal
                                     3. Set Point and Measurement Scale Range
                                     4. Mounting Angle
                                     5. Nameplate Data
                                     6. Optional Features
                                     7. Tag and Application
 NOTE: Refer to GS 2B-12B1 A to Select and Specify 102 Series Shelf-Mounting Equipment.
       Refer to GS 2B-12B1 B to Select and Specify 101 Series Shelf-Mounting Equipment.
 The Foxboro Company                Foxboro is a registered trademark of The Foxboro Company.
 33 Commercial Street               Siebe is a registered trademark of Siebe, plc.
 Foxboro, MA 02035-2099
 United States of America
 http://www.foxboro.com
 Inside U.S.: 1-888-FOXBORO
             (1-888-369-2676)
 Outside U.S.: Contact your local
 Foxboro representative.            Copyright 1968-1995 by The Foxboro Company
 Facsimile (508) 549-4492           All rights reserved
 A Siebe Group Company              MB 010                                 Printed in U.S.A.                            0495