SPV8000
General Description                                                    Installing the Price SPV 8000 Terminal Unit
The SPV 8000 terminal unit controls room temperature by varying        The basic SPV 8000 is light enough that it can be supported by the
the flow of warm or cool air to the room. The terminal unit also       duct work in which it is installed. Where accessory modules, such
compensates for changes in inlet duct pressure, holding the air        as coils, attenuators or multiple outlets are included, the assembly
flow constant unless signaled to change by the thermostat. In other    should be supported directly. Use the support method prescribed
words, the SPV 8000 is pressure independent. Note: Because of          for the rectangular duct in the job specifications.
this compensating action, if it is necessary to counter a change
in duct pressure, then the damper may be seen closing when the          Important: For optimum performance there should be a minimum
thermostat is calling for air flow or opening when the thermostat       of 3 duct diameters of straight inlet duct, same size as the inlet,
is satisfied.                                                           between the inlet and any transition, take off or fitting. The
Both the room thermostat and the air flow sensor send air pressure      assembly must be mounted right side up. It must be level within
signals to the pneumatic controller.The controller in turn modulates    ±10 degrees of horizontal, both parallel to the air flow and at
the pneumatic damper actuator.                                          right angles to the air flow. The control side of the assembly is
                                                                        labelled with an arrow indicating UP.
Receiving Inspection
After unpacking the assembly, check it for shipping damage. If any     To prevent excess air leakage, all cleat joints should be sealed with
shipping damage is found, report it immediately to the delivering      an approved duct sealer.This would apply to all accessory module
carrier. During unpacking and installation do not handle by the        connections as well as the basic assembly.
inlet velocity sensor, damper shaft, or tubing connections. Damage
may result.                                                            Control Air Connections
                                                                       External lines are provided for main air and thermostat connections.
                                                                       Pipe according to the label on the inlet panel; main air to blue,
                                                                       thermostat line to white.
                                                                        NOTE:     The main air supply must be clean and dry,
                                                                                  delivered at 15 to 25 psi.
                                                                                                                    Controller
                                                                                                                    (CP101 Illustrated)
         SP300 Flow
             Sensor
                                                                                                                        Pneumatic
                                                                                                                        Actuator
         Capped tees                                                                                                Thermostat
    for field velocity                                                                                              Connection
             pressure
      measurements                                                                                                  Main Air
                                                                                                                    Connection
                                                                                                                    (20 psi)
The terminal's side panel is factory marked to identify the mounting   Capped tees are provided in the sensing lines from the Inlet Velocity
position for Johnson, Kreuter, Landis & Staefa and Honeywell           Sensor.These allow field connection of a differential pressure gauge
pneumatic actuators for both Normally Open or Normally Closed          for accurate air flow measurement.
operation (see page 4, Figures 1 and 2).
Damper rotation is always clockwise to the open position. An
identification mark on the end of the shaft indicates the damper
position.
                                                                                                              © Copyright E.H. Price Limited 2006
Product Labelling
All Price SPV8000 units are tagged with
a control assembly label as shown on
the right. This label identifies the model
number, size, location, controller type,
application and controller setpoints for
the unit. The label can be found on the
control side of the terminal unit.
All controllers are tagged with a controller
label as shown. The label identifies the
required sensor velocity pressure for
both minimum and maximum flow
setpoints.
© Copyright E.H. Price Limited 2006            
Actuator Mounting Instructions
The SPV 8000 has been designed to accommodate several manu-
facturers' actuators for both normally open or normally closed
fail-safe operation.
Figure 1 illustrates the standard actuator and linkage orientation
for normally open units. Figure 2 illustrates the orientation of a
normally closed unit.
If relocation of the actuator becomes necessary due to a change in
required damper fail-safe position from normally open to normally
closed or vice versa, the following procedure should be used:                                 Figure 1
                                                                                    Normally Open configuration
1.   Loosen the crank arm bolt (A) until the damper shaft rotates                     (Righthand Control only)
     freely.
2.   Remove the screws (B) securing the actuator mounting bracket
     to the base.
3.   Relocate the actuator to the proper mounting holes as per
     Figure 3 and Table 1.
4.   Insure the actuator linkage is in the proper orientation as
     per Figure 1 or Figure 2. Install screws (B) securing actuator
     mounting bracket to the terminal.
5.   Rotate the damper shaft until the damper is in the fail-safe
     position (full open or full closed) and tighten bolt on the crank                     Figure 2
     arm (A).                                                                      Normally Closed configuration
                                                                                     (Righthand Control only)
 Note: These illustrations are for a right hand unit only.
 The opposite orientation is required for left hand units
 (Figure 1 normally open, Figure 2 normally closed).
                                                                                                            Damper      Mounting
                                                                              Actuator Manufacturer         Position     Holes
                                                                           Johnson         D3062             N.O.            4
                                                                           Landis&Staefa   —                 N.O.            4
                                                                           Kreuter         MCP-0305          N.O.            4
                                                                           Kreuter         MCP-8031-3102     N.O.            2
                                                                           Honeywell       MP909E1158        N.O.            4
                                                                           Johnson         D3062             N.C.            3
                                                                           Landis&Staefa   —                 N.C.            3
                                                                           Kreuter         MCP-0305          N.C.            3
                                                                           Kreuter         MCP-8031-3102     N.C.            1
                                                                           Honeywell       MP909E1158        N.C.            3
                              Figure 3                                                            Table 1
                                                                                                           © Copyright E.H. Price Limited 2006
CP100 / CP200                                                         CP101
Reset Velocity Controller                                             Reset Velocity Controller
                               CP100 / CP200                                                        CP101
Description                                                           Description
CP100 - Direct Acting Reset (Tan)				                                 The CP101 Reset Velocity Controller provides pressure independent
CP200 - Reverse Acting Reset (Grey)                                   operation on the SPV8000 series of variable air volume
                                                                      terminals.
The CP100 and CP200 Reset Velocity Controllers provide pressure
independent operation on the SPV8000 series of variable air           Each controller is equipped with separate adjustment knobs for
volume terminals.                                                     minimum and maximum air flow settings. The minimum and
                                                                      maximum air flow settings are factory calibrated, however, they
Each controller is equipped with separate adjustment knobs for        can be readjusted in the field if necessary. (See Page 8)
minimum and maximum air flow settings. The minimum and
maximum air flow settings are factory calibrated, however they        The CP101 is used for either direct or reverse acting reset for
can be readjusted in the field if necessary. (See Page 7)             normally open or normally closed SPV8000 units. The CP101 has
                                                                      a factory calibrated reset start point which can be field adjusted,
The CP100 is a direct acting reset controller typically used for      and has a factory calibrated reset span which can be field adjusted.
normally open SPV8000 units. The CP200 is a reverse acting reset      The reset span is constant regardless of minimum and maximum
controller typically used for normally closed SPV8000 units.          set points.
Consult the appropriate Price control diagram for specific            Consult the appropriate Price control diagram for specific
applications.                                                         applications.
Specifications                                                        Specifications
Differential Pressure Range                                           Differential Pressure Range
      0 to 1.0" w.g. (249 Pa)                                               0 to 1.0" w.g. (249 Pa)
Minimum Set Point Range                                               Minimum Set Point Range
     0 to 1.0" w.g. (249 Pa)                                               0 to 1.0" w.g. (249 Pa)
Maximum Set Point Range                                               Maximum Set Point Range
    Minimum to 1.0" w.g. (249 Pa)                                         Minimum to 1.0" w.g. (249 Pa)
Reset Pressure Band (CP100)                                           Reset Pressure Span
     8.0 ± 0.5 to 13.0 psig (.55 ± .03 to .90 bar)                         Field adjustable 0.0 to 10.0 psig (0.0 to .69 bar)
Reset Pressure Band (CP200)                                           Main Air Pressure
     3.0 ± 0.5 to 8.0 psig (.21 ± .03 to .55 bar)                          15 to 30 psig (1.04 to 2.07 bar)
Main Air Pressure                                                     Air Consumption
     15 to 30 psig (1.04 to 2.07 bar)                                      1.0 scfm @ 20 psig (.472 I/min @ 1.38 bar)
Air Consumption                                                       Ambient Limits
     0.5 scfm @ 20 psig (.236 I/min @ 1.38 bar)                           40o F to 120o F operating (4o C to 49o C)
                                                                          -40o F to 140o F shipping (-40oC to 60o C)
Ambient Limits
    40o F to 120o F operating (4o C to 49o C)
    -40o F to 140o F shipping (-40oC to 60o C)
   NOTE: The controller should be supplied with clean, dry control air only. No attempt should be made to use any other medium.
© Copyright E.H. Price Limited 2006                                                                                                     
SP300 Calibration Curves
Calibration Equation                               Notes
                                                   1. Gauge taps are normally supplied with the terminal unit to allow
           VP =      Q    2
                                Unit Size     K       field measurement of the differential pressure at the sensor with
                   (K )            4         340      a manometer, magnahelic or other measuring device.
                                   5         426      If the terminal velocity controls utilize a flow-through transducer,
VP - differential pressure at      6         468      a proper velocity pressure reading will NOT be read at the
     sensor, inches w.g.           7         673      gauge taps and the calibration curves CANNOT be used for field
Q - air flow rate, cfm at          8         890      measurement. The flow-through transducer operates on the
     standard density.             9        1155      principle of mass flow rather than pressure differential.
K - calibration constant          10        1487      Controls utilizing a dead-ended pressure transducer will allow
                                  12        2141      field measurement with the gauge taps and calibration curves
                                  14        3045      provided.
                                  16        4074
                                                   2. Setting flow limits for a differential pressure of less than 0.02
                                24 x 16     7785
                                                      inches in NOT recommended. Stability and accuracy of flow
                                                      limits may not be acceptable due to low velocity pressure signal.
                                                      Performance will vary depending on the terminal unit controls
                                                      provided.
                                                   3. For field calibration of air flow limits refer to the control contractor's
                                                      documentation.
                                                                                                   © Copyright E.H. Price Limited 2006
CP100 / CP200 Calibration Procedure
General                                                                    CP200
1.    Remove the protective metal cover.                                   6.   Adjust the minimum (HI) air flow limit first.
2.    Aligned markings on the face and dials of the controller indicate    7.   Set the thermostat signal to 0 psi, or disconnect the thermostat
      that the factory settings are intact.                                     tube to the controller.
3.    Remove the caps from the tees in the HI (red) and LO (green)         8.   Turn the minimum (HI) dial on the controller (centre knob) until
      tubes leading from the air flow sensor in the assembly inlet.             the gauge reads the required differential pressure.Turn the dial
      Connect a differential pressure gauge to the tees. A gauge                slowly, allowing time for the damper actuator to complete its
      with a 0 to 1 inch w.g. scale is recommended.                             travel in response to the adjustments. (Verify the minimum
                                                                                set point by cycling the thermostat pressure).
4.    Refer to the calibration curve for the size assembly being
      serviced. From the curve read the differential pressure across       9.   Apply 15 psi minimum air pressure to the thermostat
      the sensor for the required air flow. (See Page 6)                        connection at the controller.
5.    Alternately, calculate the differential pressure from the equation   10. Turn the minimum (LO) dial on the controller (outer knob) until
      on page 6.                                                               the gauge reads the required differential pressure.Turn the dial
                                                                               slowly, allowing time for the damper actuator to complete its
CP100                                                                          travel in response to the adjustments. (Verify the maximum
                                                                               set point by cycling the thermostat pressure).
6.    Adjust the minimum (LO) air flow limit first.
7.    Set the thermostat signal to 0 psi, or disconnect the thermostat     General
      tube to the controller.                                              12. Reconnect the thermostat tube to the controller if it has been
8.    Turn the minimum (LO) dial on the controller (centre knob)               removed during the calibration procedure.
      until the gauge reads the required differential pressure. Turn       13. Disconnect the gauge and replace the caps on the tees.
      the dial slowly, allowing time for the damper actuator to
      complete its travel in response to the adjustments. (Verify the      14. Replace the protective cover.
      minimum set point by cycling the thermostat pressures).
9.    Apply 15 psi minimum air pressure to the thermostat
      connection at the controller.
10. Turn the maximum (HI) dial on the controller (outer knob) until
    the gauge reads the required differential pressure.Turn the dial
    slowly, allowing time for the damper actuator to complete its
    travel in response to the adjustments. (Verify the maximum
    set point by cycling the thermostat pressure).
© Copyright E.H. Price Limited 2006                                                                                                           
CP101 Calibration Procedure
A. Damper Action                                                        9.    Adjust the "HI STAT" dial on the controller (outer knob)
                                                                              until the gauge reads the required differential pressure for
1.   Damper action is factory set. To reset action, loosen damper             maximum air volume. Turn the dial slowly, allowing time for
     selection switch screw and align desired action with the damper          the damper actuator to complete its travel in response to the
     position. Retighten screw.                                               adjustments.
2.   Actuator must be repositioned to provide appropriate fail safe     10. Cycle the thermostat several times. This can be quickly
     position. (See Page 4 for instructions)                                accomplished by removing the cap from the gauge tap (Port
                                                                            G) and varying the bleed rate with finger pressure. Replace
B. Reset Start Point                                                        cap and check the air flow limits. If set points have changed,
1.   Reset start point is factory calibrated to the specified setting       repeat steps 4 to 10.
     on the control assembly label.
                                                                        Reverse Acting Cooling or Direct Acting Heating
2.   To field adjust, remove the gauge tap cap at "G" and attach
     a 0 - 30 psi pressure gauge.                                       4.    Adjust the maximum air flow limit first.
3.   Adjust the thermostat pressure at "T" port to the desired start    5.    Set the thermostat signal to 0 psi or disconnect the thermostat
     point value with a gradual switch or pressure regulator. (Start          tube from the controller.
     point is lowest span pressure).                                    6.    Adjust the "LO STAT" dial on the controller (centre knob)
4.   Adjust reset start knob until the gauge pressure begins to               until the gauge reads the required differential pressure for
     increase slightly (greater than zero but less than 0.3).                 maximum air volume. Turn the dial slowly, allowing time for
                                                                              the damper actuator to complete its travel in response to the
5.   Replace gauge tap cap.                                                   adjustments.
C. Reset Span                                                           7.    Adjust the minimum air flow limit, after verifying the maximum
                                                                              air flow limit is set correctly.
1.   Reset span is factory calibrated to the specified setting on the
     control assembly label.                                            8.    Apply 15 psi minimum air pressure to the thermostat
                                                                              connection at the controller.
2.   To field adjust, remove the gauge tap cap at "G" and attach
     a 0 - 30 psi pressure gauge.                                       9.    Adjust the "HI STAT" dial on the controller (outer knob)
                                                                              until the gauge reads the required differential pressure for
3.   Adjust the thermostat pressure at "T" port to above 15 psi.              minimum air volume. Turn the dial slowly, allowing time for
4.   Adjust reset span knob until the gauge pressure is equal to              the damper actuator to complete its travel in response to the
     the desired reset span (total span pressure, not end span                adjustment.
     pressure).                                                         10. Cycle the thermostat several times. This can be quickly
5.   Replace gauge tap cap.                                                 accomplished by removing the cap from the gauge tap (Port
                                                                            G) and varying the bleed rate with finger pressure. Replace
D. Air Volume Limits                                                        cap and check the air flow limits. If set points have changed,
                                                                            repeat steps 4 to 10.
1.   Remove the caps from the tees in the HI (red) and LO (green)
     tubes leading from the air flow sensor in the assembly inlet.      General
     Connect a differential pressure gauge to the tees. A gauge         11.   Always adjust the "LO STAT" dial first.
     with a 0 to 1 inch w.g. scale is recommended.
                                                                        12. After calibration is complete, reconnect the thermostat tube
2.   Refer to the calibration curve for the size assembly being             to the controller if is has been removed during the calibration
     serviced. From the curve read the differential pressure across         procedure.
     the sensor for the required air flow. (See Page 6)
                                                                        13. Disconnect the gauge and replace the caps on the tees.
3.   Alternately, calculate the differential pressure from the
     equations on page 6.                                               14. Replace the protective metal cover.
Direct Acting Cooling or Reverse Acting Heating
4.   Adjust the minimum air flow limit first.
5.   Set the thermostat signal to 0 psi or disconnect the thermostat
     tube from the controller.
6.   Adjust the "LO STAT" dial on the controller (centre knob)
     until the gauge reads the required differential pressure for
     minimum air volume. Turn the dial slowly, allowing time for
     the damper actuator to complete its travel in response to the
     adjustments.
7.   Adjust the maximum air flow limit, after verifying the minimum
     air flow limit is set correctly.
8.   Apply 15 psi minimum air pressure to the thermostat
     connection at the controller.
                                                                                                               © Copyright E.H. Price Limited 2006
Troubleshooting Guide
 General                                              1. Locate thermostat and cycle — direct acting stat will bleed on
                                                         heating.
                                                      2. Confirm box size and rating with drawing and box schedule
                                                         (check label on terminal). Check position of controller to ensure
                                                         it is installed level.
                                                      3. For CP101 controller, check the damper selector switch at the
                                                         face of the controller. Ensure that switch is set in the correct
                                                         mode.
                                                      4. Visually check piping and connections to box controls and
                                                         motor.
                                                           Blue   —          Main Air (M)
                                                           White  —          Thermostat (T)
                                                           Yellow —          Actuator (B)
                                                           Red    —          High Port (X - CP100) (Y - CP200)
                                                           		                (H - CP101)
                                                           Green  —          Low Port (Y - CP100) (X - CP200)
                                                           		                (L - CP101)
                                                      5. Confirm caps are securely in place on the tees in the sensor
                                                         lines between the sensor and the controller.
                                                      6. Confirm that the "G" port cap on controller is in place.
                                                      7.   Confirm main air pressure (15 psi minimum - 25 psi
                                                           maximum).
                                                      8. Confirm thermostat pressure. Cycle thermostat from full
                                                         cooling to full heating.
                                                      9. Confirm actuator pressure from controller by cycling
                                                         thermostat.
                                                  10. Confirm actuator operation by stroking actuator with a hand
                                                      pump noting at what pressure the actuator begins to stroke
                                                      and is fully stroked.
 If Velocity Pressure is Below Specified Value    1.       Connect a differential pressure gauge (0 - 1.0" w.g.) to the tees
 and the Damper is Fully Open                              in the sensor lines between the sensor and the controller.
                                                  2.       Check velocity pressure reading and compare with the value
                                                           indicated on the controller label.
                                                  3.       If the velocity pressure is below the specified value and the
                                                           damper is fully open, this would indicate insufficient inlet duct
                                                           static pressure, starving.
 If the Velocity Pressure Indicated by the        1.       If the damper of the control assembly is partially closed, this
                                                           indicates the unit is under control.
 Gauge Does Not Match the Specified Value.
                                                  2.       If the velocity pressure indicated by the gauge does not match
                                                           the specified value, recalibrate the controller according to the
                                                           procedures outlined in this manual.
 If Supply Air Flow Measured by 			               1.       If the supply air flow measured by other means (pitot tube
                                                           traverse, summation of outlets) is incorrect, inspect the inlet
 Other Means is Incorrect
                                                           connection to the control assembly.
                                                  2.       Price recommends a minimum of 3 duct diameters of straight
                                                           inlet duct, same size as inlet, between the inlet and any
                                                           transition, take off or fitting.
 If Velocity Pressure Indicated by the Gauge is   •        Check the low pressure tubing connection on the controller
 Lower then Specified but Actual Air Supply                to see if tubing is connected.
 Exceeds Design Flow
 If the Damper Remains Fully Open, but            •        The HI sensor port or control line may be plugged. Clear the
 Sufficient Static Pressure Exists at the Inlet            passage with compressed air.
 If the Damper Remains Fully Closed               •        The LO sensor port or control line may be plugged. Clear the
                                                           passage with compressed air.
© Copyright E.H. Price Limited 2006                                                                                            
10   © Copyright E.H. Price Limited 2006
© Copyright E.H. Price Limited 2006   11
                                                                   IN THE UNITED STATES
                                                                                                                          • US Head Office, Laboratory & Testing
                                                                                                                            Facilities, Manufacturing Facilities &
                                                                                                                            Distribution Warehouse in Atlanta, Georgia
                                                                   2975 Shawnee Ridge Court
                                                                   Suwanee, Georgia USA 30024                             • US Representatives in most major cities
                                                                   Ph: 770.623.8050 Fax: 770.623.6404
                                                                   IN THE UNITED STATES
                                                                                                                          • Manufacturing Facilities & Distribution Ware-
                                                                                                                            house in Casa Grande, Arizona
                                                                   999 North Thornton Road                                • US Representatives in most major cities
                                                                   Casa Grande, Arizona USA 85222-3809
                                                                   Fax: 520.423.0517
                                                                   IN CANADA
                                                                                                                          • Head Office, Export Sales Office,
                                                                                                                            Laboratory & Testing Facilities,
                                                                                                                            Manufacturing Facilities & Distribution
                                                                   638 Raleigh Street                                       Warehouse in Winnipeg, Manitoba
                                                                   Winnipeg, Manitoba Canada R2K 3Z9
                                                                   Ph: 204.669.4220 Fax: 204.663.2715                     • Canadian Sales Offices in most major cities
 Your Local Price Represntative:
The founding principles of our company have never changed – business integrity, first class service and a commitment to people.
Price manufacturing endeavours arose from our belief that we could supply superior products and services at a reasonable price.
Our mission is to become the worldwide supplier of preference for air distribution products and services.
You can rely on Price – our products and services – with confidence.
Product Improvement is a continuing endeavour at Price. Therefore, specifications are subject to change without notice.
Consult your Price sales representative for current specifications or more detailed information.
Warranty: The Company warrants and guarantees that all goods within this catalog that have been manufactured by the Company have been manufactured in accordance with the
specifications published herein and will be free from defects in material and workmanship for a period of twelve (12) months from the date of Bill of Lading issued by the Company.
The Company will replace defective product at its option, but will not be responsible for labor or material charges in replacing product or consequential damages. Any installation
not conforming with the Company's specifications, manuals, bulletins or instructions or any misuse or any modification not authorized by the Company voids this warranty. This
warranty is in lieu of all Provincial, State, and Federal statutory warranties and the conditions herein are in substitution and replacement of such warranties, statutory or otherwise.
® Price is a registered trademark of E.H. Price Limited. © 2006.                                                                                              Lithographed in Canada 02/06