CABLE GLAND SELECTION FLOW CHART FOR CMP PRODUCTS
Is the installation in an Yes
Do you need a barrier gland
Yes
explosive atmosphere? to seal the cable
CMP
No No
CMP PRODUCTS
No Is the cable armoured Yes No Is the cable armoured? Yes
or unarmoured?
Lead Sheath, Lead Sheath,
Single Seal Double Seal SWA Braid VSD / EMC Single Seal Double Seal SWA Braid
Dual Armour CTS, Others
Copper Tape Braided CALL CMP
Screen Screen PRODUCTS ON
A2F SS2K T3CDS
1300 GLANDS FOR
TECHNICAL
E1FW E1FX ASSISTANCE
CALL CMP
A2 CWD CX PRODUCTS ON
SS2K
1300 GLANDS FOR CABLE GLANDS FOR EXPLOSIVE ATMOSPHERES
TECHNICAL
TMC CX ASSISTANCE
INDUSTRIAL CABLE GLANDS
No Is the cable armoured? Yes
To obtain a quote, you require Size Type Thread
What is the Cable O.D.? the cable gland size, type and 25 CWD M25
entry thread configuration. Eg.
20 A2 3
Ú4ÓNPT
Lead Sheath,
SWA Braid
CTS, Others
CABLE SEALING RANGE FOR CMP UNARMOURED CABLE GLAND TYPES- A2, A2F, SS2K, PXS2K (Also for inner seal dimensions on armoured explosive atmosphere glands.)
Cable Gland Size 16 20S16 20S 20 25 32 40 50S 50 63S 63 75S 75 90 100 115 130
Overall Minimum 3.1 3.1 6.1 6.5 11.1 17.0 23.5 31.0 35.6 41.5 47.2 54.0 61.1 66.6 76.0 86.0 97.0
Cable ¯ Maximum 8.7 8.7 11.7 14.0 20.0 26.3 32.2 38.2 44.1 50.0 56.0 62.0 68.0 79.4 91.0 98.0 115.0 CALL CMP
PRODUCTS ON
CABLE SEALING RANGE FOR CMP ARMOURED CABLE GLAND TYPES- CWD, CX, E1FW, E1FX, T3CDS, PX2KW, PX2KX PXSS2K PX2KW PX2KX 1300 GLANDS FOR
Cable Gland Size 20S16 20S 20 25S 25 32 40 50S 50 63S 63 75S 75 90 100 115 130 TECHNICAL
Minimum 6.1 9.5 12.5 14.0 18.2 23.7 27.9 35.2 40.4 45.6 54.6 59.0 66.7 76.2 89.1 101.3 114.0
Overall ASSISTANCE
Cable ¯ Maximum 11.5 15.9 20.9 22.0 26.2 33.9 40.4 46.7 53.1 59.4 65.9 72.1 78.5 90.4 101.5 110.3 123.3
BARRIER GLANDS FOR EXPLOSIVE ATMOSPHERES
For armoured cables in Explosive Atmospheres the diameter
of the inner bedding or inner sheath also requires verification. What is the Cable O.D.?
www.cmp-products.com
The Worlds Leading Cable Gland & Connector Manufacturer