Test Results: Title: Measurement Fault Calculator

1. The document reports the results of tests on an electrical protection relay, including measurement of currents, overcurrent and earth fault element settings, shot test configurations and results, and characteristic curves. 2. Shot tests were conducted on the relay at various current levels and phase angles to test the operation of the overcurrent and earth fault elements. All tests resulted in the element operating within accepted time deviations and the relay passing the tests. 3. Characteristic curves are presented for the various protection elements showing the operating times across a range of fault currents, consistent with the set inverse and definite time trip characteristics.

Uploaded by

imu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
27 views5 pages

Test Results: Title: Measurement Fault Calculator

1. The document reports the results of tests on an electrical protection relay, including measurement of currents, overcurrent and earth fault element settings, shot test configurations and results, and characteristic curves. 2. Shot tests were conducted on the relay at various current levels and phase angles to test the operation of the overcurrent and earth fault elements. All tests resulted in the element operating within accepted time deviations and the relay passing the tests. 3. Characteristic curves are presented for the various protection elements showing the operating times across a range of fault currents, consistent with the set inverse and definite time trip characteristics.

Uploaded by

imu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
You are on page 1/ 5

Test Results

Title: Measurement
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 1.000 A 0.00 ° 50.000 Hz
I L2 1.000 A -120.00 ° 50.000 Hz
I L3 1.000 A 120.00 ° 50.000 Hz
Generator Settings
I L1 1.000A 0.00° +90°
I L3

I L1
180° 0°

I L2
1.0 A -90°
I L2 1.000A -120.00°
I L3 1.000A 120.00°

.
Comment

IA=598.5A
IB=599.5A
IC=600AA
. .
. . . .
Assessment
Passed 02-May-2019 20:14:24

Comment

Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

OC & EF:
Test Object - Overcurrent &EarthFault Parameters
.
.
Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes 51 IEC Normal Inverse 1.00 Iref 0.05 0.95 Non Directional
Yes 50 IEC Definite Time 5.00 Iref 0.10 s 0.95 Non Directional
.
Elements - Residual:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction

Page 1 of 5
Yes 51N IEC Normal Inverse 0.15 Iref 0.25 0.95 Non Directional
Yes 50N IEC Definite Time 0.50 Iref 0.20 s 0.95 Non Directional

. .
.
Shot Test:
Type Relative To Factor Magnitude Angle tnom tmin tmax
L1-L2 51 2.000 2.000 A n/a 501.5 ms 428.2 ms 581.8 ms
L2-L3 51 2.000 2.000 A n/a 501.5 ms 428.2 ms 581.8 ms
L3-L1 51 2.000 2.000 A n/a 501.5 ms 428.2 ms 581.8 ms
L1-L2-L3 51 2.000 2.000 A n/a 501.5 ms 428.2 ms 581.8 ms
L1-L2 51 4.000 4.000 A n/a 249.0 ms 200.4 ms 298.7 ms
L2-L3 51 4.000 4.000 A n/a 249.0 ms 200.4 ms 298.7 ms
L3-L1 51 4.000 4.000 A n/a 249.0 ms 200.4 ms 298.7 ms
L1-L2-L3 51 4.000 4.000 A n/a 249.0 ms 200.4 ms 298.7 ms
L1-L2 50 1.100 5.500 A n/a 100.0 ms 60.00 ms 140.0 ms
L2-L3 50 1.100 5.500 A n/a 100.0 ms 60.00 ms 140.0 ms
L3-L1 50 1.100 5.500 A n/a 100.0 ms 60.00 ms 140.0 ms
L1-L2-L3 50 1.100 5.500 A n/a 100.0 ms 60.00 ms 140.0 ms
L1-E 51N 2.000 300.0 m A n/a 2.507 s 1.946 s 3.579 s
L2-E 51N 2.000 300.0 m A n/a 2.507 s 1.946 s 3.579 s
L3-E 51N 2.000 300.0 m A n/a 2.507 s 1.946 s 3.579 s
L1-E 50N 1.500 750.0 m A n/a 200.0 ms 160.0 ms 240.0 ms
L2-E 50N 1.500 750.0 m A n/a 200.0 ms 160.0 ms 240.0 ms
L3-E 50N 1.500 750.0 m A n/a 200.0 ms 160.0 ms 240.0 ms
L1-E 51N 3.000 450.0 m A n/a 1.576 s 160.0 ms 1.855 s
L2-E 51N 3.000 450.0 m A n/a 1.576 s 160.0 ms 1.855 s
L3-E 51N 3.000 450.0 m A n/a 1.576 s 160.0 ms 1.855 s
.

.
Shot Test Results:
Type Relative To Factor Magnitude Angle tnom tact Deviation Overload Result
L1-L2 51 2.000 2.000 A n/a 501.5 ms 524.9 ms 4.676 % No Passed
L2-L3 51 2.000 2.000 A n/a 501.5 ms 526.3 ms 4.955 % No Passed
L3-L1 51 2.000 2.000 A n/a 501.5 ms 525.3 ms 4.756 % No Passed
L1-L2-L3 51 2.000 2.000 A n/a 501.5 ms 522.8 ms 4.257 % No Passed
L1-L2 51 4.000 4.000 A n/a 249.0 ms 269.6 ms 8.278 % No Passed
L2-L3 51 4.000 4.000 A n/a 249.0 ms 268.6 ms 7.877 % No Passed
L3-L1 51 4.000 4.000 A n/a 249.0 ms 268.7 ms 7.917 % No Passed
L1-L2-L3 51 4.000 4.000 A n/a 249.0 ms 266.8 ms 7.154 % No Passed
L1-L2 50 1.100 5.500 A n/a 100.0 ms 132.1 ms 32.10 % No Passed
L2-L3 50 1.100 5.500 A n/a 100.0 ms 132.2 ms 32.20 % No Passed
L3-L1 50 1.100 5.500 A n/a 100.0 ms 132.9 ms 32.90 % No Passed
L1-L2-L3 50 1.100 5.500 A n/a 100.0 ms 129.9 ms 29.90 % No Passed
L1-E 51N 2.000 300.0 m A n/a 2.507 s 2.532 s 982.9 m % No Passed
L2-E 51N 2.000 300.0 m A n/a 2.507 s 2.527 s 803.4 m % No Passed
L3-E 51N 2.000 300.0 m A n/a 2.507 s 2.528 s 823.3 m % No Passed
L1-E 50N 1.500 750.0 m A n/a 200.0 ms 226.8 ms 13.40 % No Passed
L2-E 50N 1.500 750.0 m A n/a 200.0 ms 224.0 ms 12.00 % No Passed
L3-E 50N 1.500 750.0 m A n/a 200.0 ms 226.1 ms 13.05 % No Passed
L1-E 51N 3.000 450.0 m A n/a 1.576 s 1.597 s 1.379 % No Passed
L2-E 51N 3.000 450.0 m A n/a 1.576 s 1.597 s 1.359 % No Passed
L3-E 51N 3.000 450.0 m A n/a 1.576 s 1.597 s 1.366 % No Passed

Page 2 of 5
.
Charts for Fault
Types:
Type Angle
L1-L2 n/a
10000.00

1000.00

100.00
t/s

10.00

1.00

0.10

1.0 2.0 3.0 5.0 7.0 10.0 20.0


I/A

.
Charts for Fault
Types:
Type Angle
L2-L3 n/a
10000.00

1000.00

100.00
t/s

10.00

1.00

0.10

1.0 2.0 3.0 5.0 7.0 10.0 20.0


I/A

.
Charts for Fault
Types:
Type Angle
L3-L1 n/a
10000.00

1000.00

100.00
t/s

10.00

1.00

0.10

1.0 2.0 3.0 5.0 7.0 10.0 20.0


I/A

Page 3 of 5
Charts for Fault
Types:
Type Angle
L1-L2-L3 n/a
10000.00

1000.00

100.00
t/s

10.00

1.00

0.10

1.0 2.0 3.0 5.0 7.0 10.0 20.0


I/A

.
Charts for Fault
Types:
Type Angle
L1-E n/a
10000.00

1000.00

100.00
t/s

10.00

1.00

0.10

0.20 0.50 1.00 2.00 5.00 10.00


I/A

.
Charts for Fault
Types:
Type Angle
L2-E n/a
10000.00

1000.00

100.00
t/s

10.00

1.00

0.10

0.20 0.50 1.00 2.00 5.00 10.00


I/A

.
Charts for Fault

Page 4 of 5
Types:
Type Angle
L3-E n/a
10000.00

1000.00

100.00
t/s

10.00

1.00

0.10

0.20 0.50 1.00 2.00 5.00 10.00


I/A

.
State:
21 out of 21 points tested.
21 points passed.
0 points failed.

General Assessment: Test passed!