2010 Acti9 Schneider
2010 Acti9 Schneider
Acti9
the efficiency you deserve
Catalogue
2010
Acti9 Summary (cont.) Acti9 Summary (cont.)
Acti 9
the fifth generation
100%
of modular systems
efficient
for your for your for your for the
safety business energy planet F70 F32 Multi 9 - C32 Multi 9 - C60
Acti9 - iC60
Acti 9 exclusivities
For absolute safety and improved continuity of service.
VISI-SAFE
VISI-TRIP Guaranteed
safe
intervention
on site
Fast location
of the faulty
outgoer to
minimize
dowtime
100%
The super
immunization
Front face
class 2
exclusive
"Si" on RCD Continuous safety
Improved continuity for operators and
of service, especially non-qualified
in polluted environments personnel.
and networks.
Catalogue Acti9 Katalog Acti9
> Guaranteed safe intervention on site, > Fast location of the faulty outgoer
in any environment, throughout the life of to minimize downtime.
the installation thanks to VISI-SAFE concept
combining:
Contact position indication with the green strip.
Exclusive safety features:
Impulse voltage withstand: Uimp 6 kV
Insulation voltage: Ui 500 V
Pollution degree: level 3 (conductive pollution, dust,etc.)
Exclusive to
Schneider Electric
Exclusive to
Schneider Electric
> Absolutely > Absolutely > Absolutely > The most competitive...
safe reliable certified
Acti 9, the most competitive range with:
iC offer:
the most complete offer suited to all needs.
The widest cascading combination on the market.
iK offer:
the optimized offer for simple applications.
Exclusive to
Schneider Electric
100%
Unrivalled aesthetically
attractive design
recyclable and recoverable
components
with thermoplastic enclosures.
-20%
heat losses,
due to the design and technological
choices made.
100%
operational
during the entire lifespan of your installation.
Protection iK60N circuit breakers Protection iK60N circuit breakers
Circuit protection Circuit protection
(curve C) (curve C) (cont.)
IEC/EN 60898-1
PB104434-40
b iK60N circuit breakers are circuit breakers which combine the following functions:
PB104459-40
PB104463-40
b Padlocking device
Catalogue numbers
iK60N circuit breaker
b Fast closing independent of the speed of actuation of the toggle.
DB123310
Type 1P 2P 3P 4P b Top or bottom electrical feeding.
1 1 3 1 3 5 1 3 5 7
Technical data
2 2 4 2 4 6 2 4 6 8
Clip on DIN rail 35 mm. Main characteristics
Auxiliaries Without auxiliaries Without auxiliaries Without auxiliaries Without auxiliaries According to IEC/EN 60898-1
Vigi iC60 Without Vigi iC60 Without Vigi iC60 Without Vigi iC60 Without Vigi iC60 Insulation voltage (Ui) 440 V AC
DB123312
Rating (In) Curve Curve Curve Curve Pollution degree 2
C C C C Rated impulse withstand voltage (Uimp) 4 kV
6A A9K24106 A9K24206 A9K24306 A9K24406 Thermal tripping Reference temperature 30°C
10 A A9K24110 A9K24210 A9K24310 A9K24410 Temperature derating See page 228
13 A(1) A9K24113 A9K24213 A9K24313 A9K24413 Magnetic tripping C curve 5 to 10 In
16 A A9K24116 A9K24216 A9K24316 A9K24416 Limitation class 3
20 A A9K24120 A9K24220 A9K24320 A9K24420
Indifferent position of installation. Rated making and breaking capacity of an Icn1 = Icn
25 A A9K24125 A9K24225 A9K24325 A9K24425 individual pole (Icn1)
32 A A9K24132 A9K24232 A9K24332 A9K24432 Additional characteristics
40 A A9K24140 A9K24240 A9K24340 A9K24440
Degree of protection Device in modular IP40
IP40
DB123391
Operating frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz (IEC 60529) enclosure Insulation classe II
Width in 9-mm modules 2 4 6 8 Endurance (O-C) Electrical 10,000 cycles
Accessories page 78 page 78 page 78 page 78 Mechanical 20,000 cycles
Overvoltage category (IEC 60364) III
Operating temperature -25°C to +60°C
Storage temperature -40°C to +85°C
69.5
6.5 mm 3P 54
1P+N / 2P 36
50 Circuit-breaker
PZ2 5.5
1P 18
Type iK60N
DB122945
DB122946
1P 100
C curve 1 to 32 A 2 N.m 1 to 25 mm2 1 to 16 mm2 4.4
2P 200
40 to 63 A 3.5 N.m 1 to 35 mm2 1 to 25 mm2
94 85 45 3P 300
4P 400
64
4.6
(1) VDE approved only.
DB123060
b iC60N circuit breakers are multi-standard circuit breakers which combine the torque Rigid Flexible Al connection Rigid Flexible
PB104437-40
PB104450-40
14 mm
following functions: 6.5 mm or ferrule terminal for ring cables cables
v circuit protection against short-circuit currents, terminal
v circuit protection against overload currents, PZ2
DB122945
DB122946
DB122935
DB118789
DB118787
v suitable for industrial isolation according to IEC/EN 60947-2, standard.
v fault tripping indication by a red mechanical indicator in circuit breaker front face.
DB123310
Thermal tripping Reference temperature 50 °C
Ph/N 230 V
Temperature derating See page 228
Rating (In) 0.5 to 63 A 6000 A
Magnetic tripping B curve 4 In ± 20 %
Direct current (DC) C curve 8 In ± 20 %
Breaking capacity (Icu) according to IEC/EN 60947-2 Service D curve 12 In ± 20 %
DB123312
individual pole (Icn1)
Additional characteristics
iC60N circuit breaker Degree of protection Device only IP20
Type 1P 2P 3P 4P (IEC 60529) Device in modular IP40
1 1 3 1 3 5 1 3 5 7 enclosure Insulation classe II
Endurance (O-C) Electrical 10,000 cycles
Mechanical 20,000 cycles
Indifferent position of installation. Overvoltage category (IEC 60364) IV
Operating temperature -35°C to +70°C
2 2 4 2 4 6 2 4 6 8 Storage temperature -40°C to +85°C
IP20 IP40
DB123314
Auxiliaries Remote tripping and indication, Remote tripping and indication, Remote tripping and indication, Remote tripping and indication, Tropicalization (IEC 60068-1) Treatment 2 (relative humidity 95 % to 55°C)
page 82 page 82 page 82 page 82
Vigi iC60 Vigi iC60 add-on residual current Vigi iC60 add-on residual current Vigi iC60 add-on residual current Vigi iC60 add-on residual current
device, page 46 device, page 46 device, page 46 device, page 46 Weight (g)
Rating (In) Curve Curve Curve Curve
Circuit-breaker
B C D B C D B C D B C D
Type iC60H
0.5 A A9F73170 A9F74170 A9F75170 A9F73270 A9F74270 A9F75270 A9F73370 A9F74370 A9F75370 A9F73470 A9F74470 A9F75470
1P 125
1A A9F73101 A9F74101 A9F75101 A9F73201 A9F74201 A9F75201 A9F73301 A9F74301 A9F75301 A9F73401 A9F74401 A9F75401
2A A9F73102 A9F74102 A9F75102 A9F73202 A9F74202 A9F75202 A9F73302 A9F74302 A9F75302 A9F73402 A9F74402 A9F75402 2P 250
3A A9F73103 A9F74103 A9F75103 A9F73203 A9F74203 A9F75203 A9F73303 A9F74303 A9F75303 A9F73403 A9F74403 A9F75403 3P 375
4A A9F73104 A9F74104 A9F75104 A9F73204 A9F74204 A9F75204 A9F73304 A9F74304 A9F75304 A9F73404 A9F74404 A9F75404 4P 500
6A A9F73106 A9F74106 A9F75106 A9F73206 A9F74206 A9F75206 A9F73306 A9F74306 A9F75306 A9F73406 A9F74406 A9F75406
10 A A9F73110 A9F74110 A9F75110 A9F73210 A9F74210 A9F75210 A9F73310 A9F74310 A9F75310 A9F73410 A9F74410 A9F75410
13 A A9F73113 A9F74113 A9F75113 A9F73213 A9F74213 A9F75213 A9F73313 A9F74313 A9F75313 A9F73413 A9F74413 A9F75413
Dimensions (mm)
16 A A9F73116 A9F74116 A9F75116 A9F73216 A9F74216 A9F75216 A9F73316 A9F74316 A9F75316 A9F73416 A9F74416 A9F75416 4P 72
78.5
DB123392
69.5
20 A A9F73120 A9F74120 A9F75120 A9F73220 A9F74220 A9F75220 A9F73320 A9F74320 A9F75320 A9F73420 A9F74420 A9F75420 3P 54
50
25 A A9F73125 A9F74125 A9F75125 A9F73225 A9F74225 A9F75225 A9F73325 A9F74325 A9F75325 A9F73425 A9F74425 A9F75425 1P+N / 2P 36
5.5
1P 18
32 A A9F73132 A9F74132 A9F75132 A9F73232 A9F74232 A9F75232 A9F73332 A9F74332 A9F75332 A9F73432 A9F74432 A9F75432
40 A A9F73140 A9F74140 A9F75140 A9F73240 A9F74240 A9F75240 A9F73340 A9F74340 A9F75340 A9F73440 A9F74440 A9F75440
50 A A9F73150 A9F74150 A9F75150 A9F73250 A9F74250 A9F75250 A9F73350 A9F74350 A9F75350 A9F73450 A9F74450 A9F75450 4.4
63 A A9F73163 A9F74163 A9F75163 A9F73263 A9F74263 A9F75263 A9F73363 A9F74363 A9F75363 A9F73463 A9F74463 A9F75463
94 85 45
Width in 2 4 6 8
9-mm
modules
Accessories page 78 page 78 page 78 page 78
64
4.6
IEC/EN 60947-2
PB104435-40
DB116619
b iC60H circuit breakers are multi-standard circuit breakers which combine the
Country approval pictograms following functions:
v circuit protection against short-circuit currents,
v circuit protection against overload currents,
v suitable for industrial isolation according to IEC/EN 60947-2, standard.
v fault tripping indication by a red mechanical indicator in circuit breaker front face.
PB104441-40
PB104451-40
2 N 2 2 4 2 4 6 2 4 6 8
Auxiliaries Remote tripping and indication, page 82 Remote tripping and indication,page 82 Remote tripping and indication, page 82 Remote tripping and indication, page 82 Remote tripping and indication, page 82
Vigi iC60 Vigi iC60 add-on residual current device, page 46 Vigi iC60 add-on residual current device, page 46 Vigi iC60 add-on residual current device, page 46 Vigi iC60 add-on residual current device, page 46 Vigi iC60 add-on residual current device, page 46
Rating (In) Curve Curve Curve Curve Curve
B C D B C D B C D B C D B C D
0.5 A A9F83170 A9F84170 A9F85170 A9F83670 A9F84670 A9F85670 A9F83270 A9F84270 A9F85270 A9F83370 A9F84370 A9F85370 A9F83470 A9F84470 A9F85470
1A A9F83101 A9F84101 A9F85101 A9F83601 A9F84601 A9F85601 A9F83201 A9F84201 A9F85201 A9F83301 A9F84301 A9F85301 A9F83401 A9F84401 A9F85401
2A A9F83102 A9F84102 A9F85102 A9F83602 A9F84602 A9F85602 A9F83202 A9F84202 A9F85202 A9F83302 A9F84302 A9F85302 A9F83402 A9F84402 A9F85402
3A A9F83103 A9F84103 A9F85103 A9F83603 A9F84603 A9F85603 A9F83203 A9F84203 A9F85203 A9F83303 A9F84303 A9F85303 A9F83403 A9F84403 A9F85403
4A A9F83104 A9F84104 A9F85104 A9F83604 A9F84604 A9F85604 A9F83204 A9F84204 A9F85204 A9F83304 A9F84304 A9F85304 A9F83404 A9F84404 A9F85404
6A A9F83106 A9F84106 A9F85106 A9F83606 A9F84606 A9F85606 A9F83206 A9F84206 A9F85206 A9F83306 A9F84306 A9F85306 A9F83406 A9F84406 A9F85406
10 A A9F83110 A9F84110 A9F85110 A9F83610 A9F84610 A9F85610 A9F83210 A9F84210 A9F85210 A9F83310 A9F84310 A9F85310 A9F83410 A9F84410 A9F85410
13 A A9F83113 A9F84113 A9F85113 A9F83613 A9F84613 A9F85613 A9F83213 A9F84213 A9F85213 A9F83313 A9F84313 A9F85313 A9F83413 A9F84413 A9F85413
16 A A9F83116 A9F84116 A9F85116 A9F83616 A9F84616 A9F85616 A9F83216 A9F84216 A9F85216 A9F83316 A9F84316 A9F85316 A9F83416 A9F84416 A9F85416
20 A A9F83120 A9F84120 A9F85120 A9F83620 A9F84620 A9F85620 A9F83220 A9F84220 A9F85220 A9F83320 A9F84320 A9F85320 A9F83420 A9F84420 A9F85420
25 A A9F83125 A9F84125 A9F85125 A9F83625 A9F84625 A9F85625 A9F83225 A9F84225 A9F85225 A9F83325 A9F84325 A9F85325 A9F83425 A9F84425 A9F85425
32 A A9F83132 A9F84132 A9F85132 A9F83632 A9F84632 A9F85632 A9F83232 A9F84232 A9F85232 A9F83332 A9F84332 A9F85332 A9F83432 A9F84432 A9F85432
40 A A9F83140 A9F84140 A9F85140 A9F83640 A9F84640 A9F85640 A9F83240 A9F84240 A9F85240 A9F83340 A9F84340 A9F85340 A9F83440 A9F84440 A9F85440
50 A A9F83150 A9F84150 A9F85150 A9F83650 A9F84650 A9F85650 A9F83250 A9F84250 A9F85250 A9F83350 A9F84350 A9F85350 A9F83450 A9F84450 A9F85450
63 A A9F83163 A9F84163 A9F85163 A9F83663 A9F84663 A9F85663 A9F83263 A9F84263 A9F85263 A9F83363 A9F84363 A9F85363 A9F83463 A9F84463 A9F85463
Width in 9-mm modules 2 4 4 6 8
Accessories page 78 page 78 page 78 page 78 page 78
IEC/EN 60947-2
PB104436-40
DB116619
DB123525
Country approval pictograms b iC60L circuit breakers are multi-standard circuit breakers which combine the
following functions:
v circuit protection against short-circuit currents,
v circuit protection against overload currents,
v suitable for industrial isolation according to IEC/EN 60947-2, standard.
v fault tripping indication by a red mechanical indicator in circuit breaker front face.
PB104442-40
PB104452-40
2 2 4 2 4 6 2 4 6 8
Auxiliaries Remote tripping and indication, page 82 Remote tripping and indication, page 82 Remote tripping and indication, page 82 Remote tripping and indication, page 82
Vigi iC60 Vigi iC60 add-on residual current device, page 46 Vigi iC60 add-on residual current device, page 46 Vigi iC60 add-on residual current device, page 46 Vigi iC60 add-on residual current device, page 46
Rating (In) Quality label Curve Curve Curve Curve
(2)
B C K Z B C K Z B C K Z B C K Z
0.5 A A9F93170 A9F94170 A9F95170 A9F92170 A9F93270 A9F94270 A9F95270 A9F92270 A9F93370 A9F94370 A9F95370 A9F92370 A9F93470 A9F94470 A9F95470 A9F92470
1A A9F93101 A9F94101 A9F95101 A9F92101 A9F93201 A9F94201 A9F95201 A9F92201 A9F93301 A9F94301 A9F95301 A9F92301 A9F93401 A9F94401 A9F95401 A9F92401
1.6 A - - A9F95172 A9F92172 - - A9F95272 A9F92272 - - A9F95372 A9F92372 - - A9F95472 A9F92472
2A A9F93102 A9F94102 A9F95102 A9F92102 A9F93202 A9F94202 A9F95202 A9F92202 A9F93302 A9F94302 A9F95302 A9F92302 A9F93402 A9F94402 A9F95402 A9F92402
3A A9F93103 A9F94103 A9F95103 A9F92103 A9F93203 A9F94203 A9F95203 A9F92203 A9F93303 A9F94303 A9F95303 A9F92303 A9F93403 A9F94403 A9F95403 A9F92403
4A A9F93104 A9F94104 A9F95104 A9F92104 A9F93204 A9F94204 A9F95204 A9F92204 A9F93304 A9F94304 A9F95304 A9F92304 A9F93404 A9F94404 A9F95404 A9F92404
6A A9F93106 A9F94106 A9F95106 A9F92106 A9F93206 A9F94206 A9F95206 A9F92206 A9F93306 A9F94306 A9F95306 A9F92306 A9F93406 A9F94406 A9F95406 A9F92406
10 A A9F93110 A9F94110 A9F95110 A9F92110 A9F93210 A9F94210 A9F95210 A9F92210 A9F93310 A9F94310 A9F95310 A9F92310 A9F93410 A9F94410 A9F95410 A9F92410
16 A A9F93116 A9F94116 A9F95116 A9F92116 A9F93216 A9F94216 A9F95216 A9F92216 A9F93316 A9F94316 A9F95316 A9F92316 A9F93416 A9F94416 A9F95416 A9F92416
20 A A9F93120 A9F94120 A9F95120 A9F92120 A9F93220 A9F94220 A9F95220 A9F92220 A9F93320 A9F94320 A9F95320 A9F92320 A9F93420 A9F94420 A9F95420 A9F92420
25 A A9F93125 A9F94125 A9F95125 A9F92125 A9F93225 A9F94225 A9F95225 A9F92225 A9F93325 A9F94325 A9F95325 A9F92325 A9F93425 A9F94425 A9F95425 A9F92425
32 A A9F93132 A9F94132 A9F95132 A9F92132 A9F93232 A9F94232 A9F95232 A9F92232 A9F93332 A9F94332 A9F95332 A9F92332 A9F93432 A9F94432 A9F95432 A9F92432
40 A A9F93140 A9F94140 A9F95140 A9F92140 A9F93240 A9F94240 A9F95240 A9F92240 A9F93340 A9F94340 A9F95340 A9F92340 A9F93440 A9F94440 A9F95440 A9F92440
50 A A9F93150 A9F94150 A9F95150(3) A9F92150 A9F93250 A9F94250 A9F95250 A9F92250 A9F93350 A9F94350 A9F95350 A9F92350 A9F93450 A9F94450 A9F95450 A9F92450
63 A A9F93163 A9F94163 A9F95163(3) A9F92163 A9F93263 A9F94263 A9F95263 A9F92263 A9F93363 A9F94363 A9F95363 A9F92363 A9F93463 A9F94463 A9F95463 A9F92463
Width in 9-mm modules 2 4 4 6
Accessories page 78 page 78 page 78 page 78
(1) 100 % of Icu for ratings 6 to 25 A under Ue 100 to 133 V AC Ph/Ph and Ue 12 to 60 V AC Ph/N.
(2) Information to be provided by the country.
(3) Without approval.
20 iC60H/L circuit breakers (curve B, C, K, Z) iC60H/L circuit breakers (curve B, C, K, Z) 21
Protection iC60H/L circuit breakers Protection iC60L circuit breakers
Circuit protection Motor protection
(curve B, C, K, Z) (cont.) instantaneous circuit breakers
(ICB) (curve MA)
DB116619
DBxxxxxx
DBxxxxxx
DBxxxxxx
Rating Tightening Copper cables 50 mm² Screw-on Multi-cables terminal
DB123060
DB122945
DB122946
DB122935
DB118789
DB118787
b iC60L curve MA circuit breakers combine the following functions:
v circuit protection against short-circuit currents,
PB104443-40
PB104453-40
v suitability for industrial isolation according to IEC/EN 60947-2, standard,
v fault tripping indication by a red mechanical indicator in circuit breaker front face,
0.5 to 25 A 2 N.m 1 to 25 mm2 1 to 16 mm2 - Ø 5 mm - -
v to be associated with overload protection for motor.
32 to 63 A 3.5 N.m 1 to 35 mm2 1 to 25 mm2 50 mm2 3 x 16 mm2 3 x 10 mm2
Technical data
DB123310
Main characteristics
According to IEC/EN 60947-2
Insulation voltage (Ui) 500 V AC
Pollution degree 3 Alternating current (AC) 50/60 Hz
Rated impulse withstand voltage (Uimp) 6 kV Breaking capacity (Icu) according to IEC/EN 60947-2 Service
Clip on DIN rail 35 mm. Thermal tripping Reference temperature 50 °C Voltage (Ue) breaking
capacity (Ics)
Temperature derating See page 228 Ph/Ph (2P, 3P, 4P) 220 to 240 V 380 to 415 V 440 V
Magnetic tripping B curve 4 In ± 20 % Rating (In) 1.6 to 4 A 100 kA 100 kA 50 kA 50 % of Icu
C curve 8 In ± 20 % 6.3 to 25 A 50 kA 25 kA 20 kA 50 % of Icu
DB123312
K curve 12 In ± 20 % 40 A 36 kA 20 kA 15 kA 50 % of Icu
Z curve 3 In ± 20 %
Utilization category A
According to IEC/EN 60898-1
Limitation class 3
Rated making and breaking capacity of an Icn1 = Icn
Indifferent position of installation. individual pole (Icn1)
Catalogue numbers
Additional characteristics
Degree of protection Device only IP20 iC60L instantaneous trip circuit breaker
(IEC 60529) Device in modular IP40 Type 2P 3P 4P
enclosure Insulation classe II
IP20 IP40
DB123314
1 3 1 3 5 1 3 5 7
Endurance (O-C) Electrical 10,000 cycles
Mechanical 20,000 cycles
Overvoltage category (IEC 60364) IV
Operating temperature -35°C to +70°C
Storage temperature -40°C to +85°C 2 4 2 4 6 2 4 6 8
Tropicalization (IEC 60068-1) Treatment 2 (relative humidity 95 % to 55°C) Auxiliaries Remote tripping and indication, Remote tripping and indication, Remote tripping and indication,
page 82 page 82 page 82
69.5
54
3P
50 Accessories page 78 page 78 page 78
2P 36
5.5
1P 18
4.4
45
94 85
22 iC60H/L circuit breakers (curve B, C, K, Z) iC60L circuit breakers instantaneous circuit breakers (ICB) (curve MA) 23
Protection iC60L circuit breakers DC circuit supplementary C60H-DC
Motor protection protectors for feeders /
instantaneous circuit breakers distribution systems
C curve
DB105730
DB123431
b Insulated terminals IP20
UL1077 (Supplementary Protector TC 3)
Country approval pictograms
PB104014-34
PB104013-34
(Industrial control and automations, transport, renewable energy...).
They combine the following functions of circuit protection against short-circuit and
overload currents, control and isolation.
Visi-trip window
b Fault tripping is indicated by a red
mechanical indicator on the front face
DB116587
DB116588
b Remote indication, open/closed/tripped, by optional auxiliary contacts.
b Top or bottom electrical feeding.
Technical data Supply from above or below, Supply from Supply from
or below
observing the polarity above
Main characteristics
Dimensions (mm/in) Standards UL1077 IEC 60947-2 UL1077 IEC 60947-2
DB123310
DB116740
Breaking capacity 5 kA / 250 V DC 20 kA / 110 V DC 5 kA / 500 V DC 20 kA / 220 V DC
Pollution degree 3
10 kA / 220 V DC 10 kA / 440 V DC
Rated impulse withstand voltage (Uimp) 6 kV 6 kA / 250 V DC 6 kA / 500 V DC
Thermal tripping Reference temperature 50 °C Rating (A)* UL 1077, IEC 60947-2, EN 60947-2, GB 14048.2
Temperature derating See page 228 0.5 MGN61500 MGN61520
Clip on DIN rail 35 mm.
Magnetic tripping MA curve 12 In ± 20 % 1 MGN61501 MGN61521
Utilization category A 2 MGN61502 MGN61522
Additional characteristics 3 MGN61503 MGN61523
DB123312
DB116741
Overvoltage category (IEC 60364) IV 15 MGN61510 MGN61530
Indifferent position of installation. Operating temperature -35°C to +70°C 16 MGN61511 MGN61531
Storage temperature -40°C to +85°C 20 MGN61512 MGN61532
Tropicalization (IEC 60068-1) Treatment 2 (relative humidity 95 % to 55°C) 25 MGN61513 MGN61533
IP20 IP40
DB123314
30 MGN61514 MGN61534
4P 72 69.5
3P 54 50 50 MGN61518 MGN61538
2P 36 5.5 63 MGN61519 MGN61539
* At 25°C / 77°F see temperature derating module 92515.
Kit for ring terminals
4.4
94 85 45
64
4.6
24 iC60L circuit breakers instantaneous circuit breakers (ICB) (curve MA) C60H-DC 25
DC circuit supplementary C60H-DC (cont.) DC circuit supplementary C60H-DC (cont.)
protectors for feeders / C curve protectors for feeders / C curve
distribution systems distribution systems
DB118851
DB118852
DB118853
earth
DB118787
DB122945
DB122946
DB122935
DB118789
F
O-OF
F
O-OF
DB116735
DB116735
3 Terminal 50 mm Al / Cu2
27060
4 Ring tongue terminal screw connection 27053
5 Ring tongue terminal connections kit 17400
Ø 5 mm, (upstream/downstream)
Load Load
6 Insulated distribution terminal 4 pieces 19091
3 pieces 19096
Downstream connection Load Load
DB116752
DB116738
DB116738
Mounting accessories
7 Sealable terminal shield 26976 Load
8 Inter-pole barrier 27001
9 Rotary handle 250 V < Un y 500 V Two-pole Two-pole Two-pole
Switching sub-assembly 27046 Upstream connection
DB116736
DB116735
DB116735
Disconnectable handle 27047
Fixed handle 27048
10 Screw shield 26981 Load Load Load
11 Padlocking accessory 26970
(to be locked in the "open" position)
Downstream connection Load Load Load
DB116737
DB116738
DB116738
12 Spacer 27062
13 Dividable mounting plate 26996
14 Marker strip
d
breaker and within a width of 54 mm.
b If the auxiliary SD contacts are associated with the tripping auxiliaries
(MN, MX, etc.), they must be installed to the left of these auxiliaries.
26 C60H-DC C60H-DC 27
DC circuit supplementary C60H-DC (cont.) DC circuit supplementary C60H-DC (cont.)
protectors for feeders / C curve protectors for feeders / C curve
distribution systems distribution systems
DB123588
DB123589
b The curves show the cold thermal tripping limits when poles are charged and the electromagnetic tripping limits
with 2 charged poles.
b The curves are used without any derating.
100 100
DB122667
t (s)
1000
50 - 63
32 - 40 50 - 63
20 - 25 32 - 40
100 16
10
20 - 25
16
6 10
4 6
1 3 1 4
3
2 2
10
≤1
≤1
0.1 0.1
1 0.01 0.1 1 10 100 0.01 0.1 1 10 100
Prospective current (kA rms) Prospective current (kA rms)
01
Temperature derating (according to UL 1077/ CSA22.2/ UL489A/ UL489/ IEC 60947-2 standards)
The maximum permissable current in a device depends on the ambient temperature in which it is placed.
Ambient temperature is the temperature inside the enclosure or switchboard in which the devices have been
0.01 installed.
0. 1 10 I / In The reference temperature is in the coloured column.
When several simultaneously operating devices are mounted side by side in a small enclosure, the temperature
rise inside the enclosure causes a reduction in the current rating. A reduction cœfficient of the order of 0.8 must
therefore be allocated to the rating (already derated if it depends on the ambient temperature).
Short circuit current limiting Temperature -30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
220 V with 1P, 440 V with 2P 250 V with 1P, 500 V with 2P (°C)
Ratings (A)
DB123591
DB123590
1000000 1000000 0.5 0.63 0.62 0.61 0.60 0.59 0.58 0.56 0.55 0.54 0.53 0.51 0.5 0.49 0.47 0.46 0.44 0.43 0.41 0.39 0.38 0.36
10 ms 10 ms 1 1.18 1.17 1.15 1.14 1.12 1.10 1.09 1.07 1.05 1.04 1.02 1 0.98 0.96 0.94 0.92 0.90 0.88 0.86 0.84 0.82
1.2 1.45 1.43 1.41 1.39 1.37 1.34 1.32 1.30 1.27 1.25 1.22 1.2 1.17 1.15 1.12 1.09 1.07 1.04 1.01 0.98 0.95
1.5 1.86 1.83 1.80 1.77 1.74 1.71 1.67 1.64 1.61 1.57 1.54 1.5 1.46 1.42 1.39 1.34 1.30 1.26 1.22 1.17 1.12
100000 100000 2 2.54 2.50 2.45 2.41 2.36 2.31 2.26 2.21 2.16 2.11 2.06 2 1.94 1.88 1.82 1.76 1.70 1.63 1.56 1.48 1.41
3 3.78 3.71 3.65 3.58 3.51 3.45 3.38 3.30 3.23 3.16 3.08 3 2.92 2.84 2.75 2.66 2.57 2.48 2.38 2.27 2.17
Limited energy (A2s)
4 5.08 4.99 4.90 4.81 4.71 4.62 4.52 4.42 4.32 4.22 4.11 4 3.89 3.77 3.65 3.53 3.40 3.27 3.13 2.98 2.83
50 - 63 50 - 63
5 6.00 5.92 5.83 5.74 5.66 5.57 5.48 5.39 5.29 5.20 5.10 5 4.90 4.80 4.69 4.58 4.47 4.36 4.24 4.12 4.00
32 - 40
32 - 40
10000 10000 20 - 25 6 7.26 7.15 7.04 6.94 6.83 6.71 6.60 6.48 6.37 6.25 6.12 6 5.87 5.74 5.61 5.47 5.33 5.19 5.04 4.89 4.73
20 - 25
16 16 7 8.76 8.62 8.47 8.32 8.17 8.01 7.85 7.69 7.52 7.35 7.18 7 6.82 6.63 6.44 6.24 6.03 5.82 5.60 5.37 5.13
10
10
6
8 9.64 9.50 9.36 9.22 9.08 8.93 8.78 8.63 8.48 8.32 8.16 8 7.83 7.67 7.49 7.31 7.13 6.95 6.76 6.56 6.36
6
4 10 12.59 12.38 12.16 11.94 11.71 11.49 11.25 11.01 10.77 10.52 10.26 10 9.73 9.45 9.17 8.87 8.57 8.25 7.92 7.58 7.22
4
1000 1000
3 13 15.49 15.28 15.07 14.85 14.63 14.41 14.19 13.96 13.72 13.49 13.25 13 12.75 12.49 12.23 11.97 11.69 11.41 11.13 10.83 10.53
3 2
0.5 - 2 15 18.61 18.31 18.01 17.70 17.38 17.06 16.74 16.40 16.07 15.72 15.36 15 14.63 14.25 13.85 13.45 13.03 12.60 12.16 11.69 11.21
16 19.43 19.14 18.85 18.55 18.25 17.95 17.64 17.32 17.00 16.68 16.34 16 15.65 15.29 14.93 14.56 14.17 13.78 13.37 12.95 12.52
20 24.06 23.72 23.37 23.02 22.67 22.31 21.94 21.56 21.18 20.80 20.40 20 19.59 19.17 18.74 18.30 17.85 17.39 16.92 16.43 15.93
100
0.5 - 1 25 30.35 29.91 29.45 28.99 28.52 28.05 27.56 27.07 26.57 26.06 25.53 25 24.46 23.90 23.33 22.74 22.14 21.53 20.89 20.24 19.56
100
0.01 0.1 1 10 100 0.01 0.1 1 10 100 30 37.35 36.74 36.12 35.50 34.86 34.21 33.54 32.86 32.17 31.46 30.74 30 29.24 28.46 27.66 26.83 25.98 25.10 24.19 23.24 22.25
Prospective current (kA rms) Prospective current (kA rms)
32 38.45 37.91 37.36 36.80 36.24 35.66 35.08 34.48 33.88 33.27 32.64 32 31.35 30.68 30.00 29.31 28.59 27.86 27.11 26.34 25.54
35 44.15 43.40 42.63 41.86 41.06 40.25 39.42 38.58 37.72 36.83 35.93 35 34.05 33.06 32.05 31.01 29.93 28.81 27.64 26.42 25.14
40 48.92 48.17 47.42 46.65 45.87 45.08 44.28 43.45 42.62 41.76 40.89 40 39.09 38.16 37.20 36.22 35.21 34.17 33.10 31.99 30.84
50 59.93 59.09 58.25 57.39 56.52 55.63 54.74 53.82 52.89 51.95 50.98 50 49.00 47.97 46.93 45.86 44.77 43.64 42.49 41.31 40.09
60 76.16 74.83 73.48 72.11 70.71 69.28 67.82 66.33 64.81 63.25 61.64 60 58.31 56.57 54.77 52.92 50.99 48.99 46.90 44.72 42.43
63 78.16 76.91 75.63 74.33 73.01 71.67 70.30 68.90 67.47 66.02 64.53 63 61.44 59.83 58.18 56.49 54.74 52.93 51.06 49.12 47.10
28 C60H-DC C60H-DC 29
DC circuit supplementary C60PV-DC, C60NA-DC DC circuit supplementary C60PV-DC, C60NA-DC
protectors for feeders / C curve protectors for feeders /
distribution systems distribution systems
DB122701
IEC / EN 60947-2 e torque file no. #E216919 Cu/Al connection for
Terminal ring terminal
Main characteristics Rigids Flexibles Rigid Flexible
14 mm PZ2 with ferrule cables cables
Operating voltage (Ue) 650 V DC
Rated insulation voltage (Ui) 1,000 V DC 6.5 mm
Breaking capacity (Icu) 1.5 kA
DB112804
DB112805
DB118755
DB118756
DB118757
Impulse voltage (Uimp) 6 kV
Electrical connection By the top for In and Out
Number of poles 2P
50 A 3.5 N.m 1 to 35 mm2 1 to 25 mm2 50 mm2 Ø 5 mm 3 x 16 mm2 3 x 10 mm2
Curve C
Number of modules of 9 mm 8
Diagrams 1
DB122506
DB122703
DB122508
1 3 2 4
1 3 2 4 1 Terminal 50 mm2 Al / Cu 27060
IN IN OUT OUT
DB122704
Tripping
10 MN undervoltage release 26960
Standards IEC 60947-3 11 MX + OF shunt release 26946
EN 60947-3
Catalogue number MGN61690
Additional characteristics
Rating (A) Voltage drop (mV) Impedance (mΩ) Power loss (W)
20 A 100 5.02 2
30 A 151 5.02 4.53 dThe electrical auxiliaries must be installed to the left of the circuit breaker and within a width of 54 mm.
If the auxiliary SD contacts are associated with the tripping auxiliaries (MN, MX, etc.), they must be installed to the left of these
40 A 201 5.02 8.04
auxiliaries.
60 A 251 5.02 12.55
DB126597
DB126598
C120N circuit breakers are multistandard circuit breakers that combine the following to IP20
(*)
functions:
Country approval pictograms b Circuit protection against short-circuit currents,
b Circuit protection against overload currents, b Location for 4 clip-on terminal
b Suitability for isolation in the industrial sector to IEC/EN 60947-2, markers
b Fault tripping and indication by adding auxiliaries.
056799N_SE-32
DB118767
DB122831
63 to 125 A - 10 kA 100 % Icu
Main characteristics
To IEC/EN 60947-2
Catalogue numbers Insulation voltage (Ui) 500 V AC
Degree of pollution 3
C120N circuit breaker
Rated impulse withstand voltage (Uimp) 6 kV
Type 1P 2P 3P 4P
Thermal Reference temperature 50 °C
1 1 3 1 3 5 1 3 5 7
Any installation position. tripping
Clips onto 35 mm DIN rail.
To IEC/EN 60898-1
Magnetic tripping Curve B 3 and 5 In
Curve C 5 and 10 In
Curve D 10 and 14 In
2 2 4 2 4 6 2 4 6 8
IP20 IP40
DB122932
Limitation class 3
Auxiliaries Remote indication and Remote indication and Remote indication and Remote indication and tripping, Additional characteristics
tripping, page 90 tripping, page 90 tripping, page 90 page 90 Degree of protection Device only IP20
Vigi C120 Vigi C120 add-on residual Vigi C120 add-on residual Vigi C120 add-on residual Vigi C120 add-on residual (IEC 60529) Device in a modular IP40
current device, page 52 current device, page 52 current device, page 52 current device, page 52 enclosure
Rating (In) Curve Curve Curve Curve Endurance (O-C) Electrical 63 A 10000 cycles (O-C)
B C D B C D B C D B C D 80...125 A 5000 cycles (O-C)
63 A 18340 18356 18378 18344 18360 18382 18348 18364 18386 18352 18371 18390 Mechanical 20000 cycles
80 A 18341 18357 18379 18345 18361 18383 18349 18365 18387 18353 18372 18391 Operating temperature -25 °C to +70 °C
100 A 18342 18358 18380 18346 18362 18384 18350 18366 18388 18354 18374 18392
Storage temperature -40 °C to +85 °C
125 A 18343 18359 18381 18347 18363 18385 18351 18367 18389 18355 18376 18393 Dimensions (mm) Tropicalisation (IEC 60068-1) Treatment 2
Largeur en pas de 9 mm 3 6 9 12 (relative humidity 95 % at 55 °C)
Accessories page 90 page 90 page 90 page 90
DB126144
DB126597
DB126598
to IP20
(*)
C120H circuit breakers are multistandard circuit breakers that combine the following
Country approval pictograms functions:
b circuit protection against short-circuit currents
b circuit protection against overload currents b Location for 4 clip-on terminal
b suitability for isolation in the industrial sector to IEC/EN 60947-2 markers
b fault tripping and indication by adding auxiliaries.
DB118767
DB122831
2P (in series) 24/48 V 125 V 250 V
10 to 125 A - - 15 kA 100 % Icu Main characteristics
DB122932
2 2 4 2 4 6 2 4 6 8
Auxiliaries Remote indication and tripping, Remote indication and tripping, Remote indication and tripping, Remote indication and tripping, Limitation class 3
page 90 page 90 page 90 page 90 Additional characteristics
Vigi C120 Vigi C120 add-on residual current Vigi C120 add-on residual current Vigi C120 add-on residual current Vigi C120 add-on residual current Degree of protection Device only IP20
device, page 52 device, page 52 device, page 52 device, page 52 (IEC 60529) Device in a modular IP40 (IPXXD)
Rating (In) Curve Curve Curve Curve enclosure
B C D B C D B C D B C D Endurance (O-C) Electrical 63 A 10000 cycles (O-C)
10 A 18394 18438 18482 18405 18449 18493 18416 18460 18504 18427 18471 18515 80...125 A 5000 cycles (O-C)
16 A 18395 18439 18483 18406 18450 18494 18417 18461 18505 18428 18472 18516 Mechanical 20000 cycles
20 A 18396 18440 18484 18407 18451 18495 18418 18462 18506 18429 18473 18517
25 A 18397 18441 18485 18408 18452 18496 18419 18463 18507 18430 18474 18518 Dimensions (mm) Operating temperature -30 °C to +60 °C
Storage temperature -40 °C to +70 °C
32 A 18398 18442 18486 18409 18453 18497 18420 18464 18508 18431 18475 18519
Tropicalisation (IEC 60068-1) Treatment 2
DB126144
40 A 18399 18443 18487 18410 18454 18498 18421 18465 18509 18432 18476 18520
(relative humidity 95% at 55°C)
50 A 18400 18444 18488 18411 18455 18499 18422 18466 18510 18433 18477 18521
63 A 18401 18445 18489 18412 18456 18500 18423 18467 18511 18434 18478 18522 Weight (g)
80 A 18402 18446 18490 18413 18457 18501 18424 18468 18512 18435 18479 18523
100 A 18403 18447 18491 18414 18458 18502 18425 18469 18513 18436 18480 18524 Circuit breaker
125 A 18404 18448 18492 18415 18459 18503 18426 18470 18514 18437 18481 18525
Type C120H
Width in 9 mm 3 6 9 12
modules 1P 205
Accessories page 90 page 90 page 90 page 90 2P 410
(*) NF B and C curves only. 3P 615
4P 820
DB116619
DBxxxxxx
DBxxxxxx
DBxxxxxx
DB116619
DBxxxxxx
DBxxxxxx
DBxxxxxx
b NG125N circuit breakers are circuit breakers which combine the following b NG125H circuit breakers are circuit breakers which combine the following
functions: Country approval pictograms functions:
Country approval pictograms
v circuit protection against short-circuit currents, v circuit protection against short circuit currents,
v circuit protection against overload currents, v circuit protection against overload currents,
v suitability for isolation in the industrial sector to IEC/EN 60947-2, v suitability for isolation in the industrial sector to IEC/EN 60947-2,
v tripping upon fault is indicated by a red mechanical state indicator light on the front v tripping upon fault is indicated by a red mechanical state indicator light on the front
face of the circuit breaker. face of the circuit breaker.
056900_SE-30
056902_SE-30
056915N_SE-30
056916N_SE-30
Breaking capacity (Icu) to IEC/EN 60947-2 Service Alternating current (AC) 50/60 Hz
Voltage (Ue) breaking Breaking capacity (Icu) to IEC/EN 60947-2 Service
Voltage (Ue) breaking
Ph/Ph - - 220 to - 380 to 440 V 500 V capacity
(2P, 3P, 3P+N, 4P) 240 V 415 V (Ics) Ph/Ph - - 220 to - 380 to 440 V 500 V capacity
Ph/N 110 to 220 to - 380 to - - - (2P, 3P, 4P) 240 V 415 V (Ics)
(1P) 130 V 240 V 415 V Ph/N 110 to 220 to - 380 to - - -
Rating 10 to 125 A 50 kA 25 kA 50 kA 6 kA(2) 25 kA 20 kA 10 kA 75 % of Icu (1P) 130 V 240 V 415 V
(In) Rating 10 to 80 A 70 kA 36 kA 70 kA 6 kA(2) 36 kA 30 kA 12 kA 75 % of Icu
NG125N 1P NG125N 2P NG125H 1P NG125H 2P (In)
056335_SE-30
056917N_SE-30
056918N_SE-30
Breaking capacity (Icu) to IEC/EN 60947-2 Service Direct current (DC)
Voltage (Ue) breaking Breaking capacity (Icu) to IEC/EN 60947-2 Service
capacity Voltage (Ue) breaking
Ph/Ph (2P, 3P, 3P+N, 4P) - - 250 V 500 V
(Ics) Ph/Ph (2P, 3P, 3P+N, 4P) - - 250 V 500 V capacity
Ph/N (1P) 60 V 125 V - -
Ph/N (1P) 60 V 125 V - -
(Ics)
Number of poles 1P 1P 2P 4P
Number of poles 1P 1P 2P 4P
Rating (In) 10 to 125 A 25 kA 25 kA 25 kA 25 kA 100 % of Icu
Rating (In) 10 to 80 A 36 kA 36 kA 36 kA 36 kA 100 % of Icu
NG125N 3P NG125N 4P NG125H 3P NG125H 4P
2 2 4 2 4 6 N 2 4 6 8 2 2 4 2 4 6 2 4 6 8
Auxiliaries Remote indication and tripping, page 98 – Vigi NG125 add-on residual current device, page 55 Auxiliaries Remote indication and tripping, page 98 –
Rating (In) Quality label Curve Curve Curve Curve Curve Vigi NG125 add-on residual current device,
(1) page 55
C C B C D C B C D
Rating (In) Quality label Curve C Curve C Curve C Curve C
10 A 18610 18621 - 18632 - - - 18649 - (1)
(1) Information to be supplied by the country concerned. (1) Information to be supplied by the country concerned.
(2) Breaking capacity under 1 pole in IT isolated neutral system (case of a double fault). (2) Breaking capacity under 1 pole in IT isolated neutral system (case of a double fault).
DBxxxxxx
DBxxxxxx
DBxxxxxx
accessories accessories
b NG125L circuit breakers are circuit breakers which combine the following Rating Tightening Copper cables 70 mm2 Screw-on Small Multi-cable
DB122861
NG125
Country approval pictograms functions: 80 A torque Al connection ring terminal
v circuit protection against short-circuit currents; 20 mm
v circuit protection against overload currents; Rigid Flexible or terminal for ring terminal Rigid Flexible
v suitability for isolation in the industrial sector to IEC/EN 60947-2; with terminal cables cables
v tripping upon fault is indicated by a red mechanical state indicator light on the front ferrule
face of the circuit breaker.
DB122945
DB122946
DB123410
DB123488
DB118789
DB118787
PZ2
6.5 mm 6 mm
NG125
56337_SE-30
56338_SE-30
Alternating current (AC) 50/60 Hz y 63 A 10 3.5 N.m 1.5 to 50 mm2 1 to 35 mm2 - - - 3 x 16 mm2 3 x 10 mm2
to 63 A
Breaking capacity (Icu) to IEC/EN 60947-2 Service
80 A 6 N.m 16 to 70 mm2 10 to 50 mm2 25 to 70 mm2 2 x 35 mm2 1 x 70 mm2
Voltage (Ue) breaking
1 x 50 mm2
Ph/Ph - - 220 to - 380 to 440 V 500 V capacity
b On 3P and 4P: upstream voltage taps for each pole, by 6.35 mm Fast-on terminal.
(2P, 3P, 4P) 240 V 415 V (Ics)
Ph/N (1P) 110 to 220 to - 380 to - - -
130 V 240 V 415 V
Rating 10 to 100 kA 50 kA 100 kA 6 kA(2) 50 kA 40 kA 15 kA 75 % of Icu
Technical data
(In) 80 A
Main characteristics
DB123310
DB123312
NG125L 1P NG125L 2P
According to IEC/EN 60947-2
Insulation voltage (Ui) 690 V AC
56339_SE-30
56340_SE-30
DB123314
Degree of protection Device only IP20
(IEC 60529) Device in modular IP40
enclosure Insulation class II
Catalogue numbers Endurance (O-C) Electrical y63 A: 10,000 cycles
u63 A: 5000 cycles
NG125L circuit breaker Mechanical 20,000 cycles
Type 1P 2P 3P 4P Operating temperature -10°C to +60°C
1 1 3 1 3 5 1 3 5 7 Storage temperature -40°C to +70°C
Tropicalization (IEC 60068-1) Treatment 2 (relative humidity of 95 % at 55°C)
Dimensions (mm)
DB122591
2 2 4 2 4 6 2 4 6 8
Auxiliaries Remote indication and tripping, page 98 – Vigi NG125 add-on residual current device, page 55
Rating (In) Quality label Curve Curve Curve Curve
(1)
B C D B C D B C D B C D
10 A 18741 18777 18830 18750 18788 18839 18759 18799 18848 18768 18810 18857
16 A 18742 18778 18831 18751 18789 18840 18760 18800 18849 18769 18811 18858
20 A 18743 18779 18832 18752 18790 18841 18761 18801 18850 18770 18812 18859
25 A 18744 18780 18833 18753 18791 18842 18762 18802 18851 18771 18813 18860
32 A 18745 18781 18834 18754 18792 18843 18763 18803 18852 18772 18814 18861
40 A 18746 18782 18835 18755 18793 18844 18764 18804 18853 18773 18815 18862
50 A 18747 18783 18836 18756 18794 18845 18765 18805 18854 18774 18816 18863
27.75 25.5 27.75 7 .5 2 .5
63 A 18748 18784 18837 18757 18795 18846 18766 18806 18855 18775 18817 18864 Weight (g)
DB123487
80 A 18749 18785 18838 18758 18796 18847 18767 18807 18856 18776 18818 18865
Circuit breaker
.25 .25
Width in 9 mm modules 3 6 9 12
Accessories page 98 Type NG125L
7 .5 7 .5 1P 240
2P 480
.25 .25 3P 720
53.25 2 .5 5 4P 960
(1) Information to be supplied by the country concerned. Spacing for mounting on panel
(2) Breaking capacity under 1 pole in IT isolated neutral system (case of a double fault).
DB116619
DBxxxxxx
DBxxxxxx
DBxxxxxx
v auxiliaries power supply
v measurement b NG125LMA circuit breakers are circuit breakers which combine the following
v emergency stop functions:
Country approval pictograms
v remote reporting v circuit protection against short-circuit currents,
v circuit protection against overload currents,
v suitability for isolation in the industrial sector to IEC/EN 60947-2,
b Cable strength: 1P, 2P v tripping upon fault is indicated by a red mechanical state indicator light on the front
v ribbed cage b Padlocking in position: face of the circuit breaker.
v terminal depth O or I, manual control is
v tightening by Allen hex inhibited, tripping is enabled
key (NG125 80 A)
056918N_SE-90
056924_SE-30
056939_SE-30
Alternating current (AC) 50/60 Hz
Breaking capacity (Icu) to IEC/EN 60947-2 Service
Voltage (Ue) breaking
Ph/Ph (2P, 3P) 220 to 240 V 380 to 415 V 440 V 500 V capacity
b Test button to check (Ics)
satisfactory operation of Rating (In) 4 to 80 A 100 kA 50 kA 40 kA 15 kA 75 % of Icu
the tripping mechanism (trip units)
NG125LMA 2P NG125LMA 3P
Catalogue numbers
NG125LMA circuit breaker
Type 2P 3P
1 3 1 3 5
b Pull-out strength
v metallic lock
3P, 4P
b Integrated padlocking
device
2 4 2 4 6
v suitability for isolation in the industrial sector to IEC/EN 60947-2 40 A 480 18874 18885
v the presence of the green strip guarantees that the contacts open physically 63 A 750 18875 18886
and allows work to be carried out safely on the downstream circuit 80 A 960 18876 18887
Width in 9 mm modules 6 9
Accessories page 98
DB116619
DBxxxxxx
DBxxxxxx
DBxxxxxx
accessories accessories
Rating Tightening Copper cables 70 mm2 Screw-on Small ring Multi-cable
DB122863
NG125
Country approval pictograms
80 A torque Al connection terminal terminal
20 mm b The NG125NA is a switch-disconnector with free tripping for making and breaking
Rigid Flexible or terminal for ring Rigid Flexible under load.
with terminal cables cables b It is especially suitable for the modular enclosure incoming feeder with remote
ferrule breaking (e.g. emergency cutoff) or earth leakage protection functions.
DB122945
DB122946
DB123410
DB123488
DB118789
DB118787
6 mm
PZ2
Catalogue numbers
056908N_SE-30
056909N_SE-30
6.5 mm
NG125 4 to 63 A 3.5 N.m 1.5 to 50 mm2 1 to 35 mm2 - - - 3 x 16 mm2 3 x 10 mm2
y 63 A 80 A 6 N.m 16 to 70 mm2 10 to 50 mm2 25 to 70 mm2 2 x 35 mm2 1 x 70 mm2 NG125NA switch
1 x 50 mm2
Type 3P 3P+N
b On 3P: upstream voltage taps for each pole, by 6.35 mm Fast-on terminal.
1 1
Technical data
DB123310
DB123312
Main characteristics
According to IEC/EN 60947-2 NG125NA 3P NG125NA 4P
2 2
Insulation voltage (Ui) 690 V AC
Degree of pollution 3 Auxiliaries Remote indication and tripping, page 55 –
Vigi NG125 add-on residual current device, page 98
Rated impulse withstand voltage (Uimp) 8 kV
Rating (In) Quality label
Thermal Reference 40°C (1)
tripping temperature
Clips on to 35 mm DIN rail. Any installation position. 63 A 18889 18893
Magnetic MA curve 12 In ± 20 %
tripping (Ii) 80 A 18890 18894
DB122588
Storage temperature -40°C to +70°C Technical data
Tropicalization (IEC 60068-1) Treatment 2 (relative humidity of 95 % at 55°C)
Main characteristics
Weight (g) According to IEC/EN 60947-3
Max. voltage rating (Ue) 500 V AC
Circuit breaker Insulation voltage (Ui) 690 V AC
Type NG125LMA Degree of pollution 3
2P 480
Rated impulse withstand voltage (Uimp) 8 kV
3P 720
Short time withstand current (50 ms) Icw 1.5 kA
Utilization category AC22A/B - AC23B
Dimensions (mm)
Additional characteristics
DB122862
.25 .25
.25
Weight (g)
7 .5 7 .5
7 .5
Choice of sensitivity
PG134083A_SE
STI Cartridges
IEC EN 60947-3 NF C 60-200, NF C 63-210 The choice of sensitivity of an earth leakage protection device depends both on the type of circuit to be protected and the type of protection to
be provided.
and IEC 60269-1/2
Type of Obligations Recommended Sensitivity (IΔn)
b The STI isolatable fuse-carriers provide overload and short-circuit protection. protection by
b They are used for industrial applications requiring a high breaking capacity.
b They perform the isolation function and must not be used as switches. National standard International standard Schneider 30 mA (*) 100 mA to 3000 mA 300 mA (or 500 mA)
To be filled in IEC 60364 (depending on the
b They can be equipped with an indicator light indicating blowing of the fuse cartridge. according to the
Electric earthing system)
15646 b Isolation of all poles is guaranteed for the 2P, 3P, and 3P+N versions during factory assembly. country standard
The general purpose fuse (gG fuse) provides overload and short-circuit protection. Protection from electric shock by direct contact
053461LD-30
The fuse for motor application (aM fuse) only provides short-circuit protection.
To be filled in Power supply for b Lighting in the home Setup in final
DB123167
It is used for protection of loads with a high peak current (motors, transformer primaries, etc.). according to the b General-purpose power distribution
country standard sockets, up to 20 A switchboard
Accessories b Appliances in the vicinity of b Residual
Comb busbar a bathtub, shower, pond or current device
b Used to quickly bridge several STI of the same kind. swimming pool protecting a
b Portable appliances for circuit
Busbar connectors outdoor use, up to 32 A
b Used to supply the busbar. b Lighting for exhibition b Residual
15668 current circuit
b For 25 mm2 cable. stands and shows
b Outdoor lighting breaker
PB102092_SE
DB123168
according to the system, except for devices: distribution
Clip-on markers (C60 type) country standard b With class II insulation switchboard
b Used to identify: b Operating at Safety Extra b Residual current
v either on the front face of the device Low Voltage (class III) circuit breaker or
v or on the downstream terminals. device, on incoming
To be modified according to feeder
Catalogue numbers national obligations (above)
Setup in
Fuse cartridge STI fuse holder subdistribution
board or main
Type Network type switchboard
Rating Voltage rating Short-circuit current
(Ue) (Isc) b Residual current
aM gG aM gG 1P 1P+N (1) 2P 3P 3P+N (1) device protecting a
1 N 1 1 3 1 3 5 N 1 3 5 circuit
DB112797
DB112798
DB112799
DB112800
DB110801
b Residual current
device or circuit
breaker protecting a
group of circuits
2 2 2 4 2 4 6 2 4 6 b On incoming
feeder: residual
2A 400 V AC 20 kA 20 kA 15733 15767 15635 15645 15650 15655 15657
4A 400 V AC 20 kA 20 kA 15734 15768 current circuit
8.5 x 31.5 6A 400 V AC 20 kA 20 kA 15735 15769 breaker or device
2 modules 2 modules 4 modules 6 modules 6 modules
10 A 400 V AC 20 kA - 15737 - of 9 mm of 9 mm of 9 mm of 9 mm of 9 mm Protection from fire due to current leakage
2A 500 V AC 120 kA 120 kA 15742 15775 15636 15646 15651 15656 15658
4A 500 V AC 120 kA 120 kA 15743 15776 To be filled in b High-risk premises: b Dilapidated Setup in final
DB123169
6A 500 V AC 120 kA 120 kA 15744 15777 according to the v explosion (BE3) buildings or electrical distribution
10.3 x 38 2 modules 2 modules 4 modules 6 modules 6 modules
10 A 500 V AC 120 kA 120 kA 15746 15779 country standard v fire (BE2) installations switchboard
25 A 400 V AC 120 kA - 15750 - of 9 mm of 9 mm of 9 mm of 9 mm of 9 mm b Agricultural and b Humid
32 A 400 V AC - - - - b Residual current
horticultural buildings atmospheres: circuit breaker or
Operating frequency : 50/60 Hz b Equipment for fairs, agricultural buildings, device, on incoming
Fuse cartridge SBI fuse holder exhibitions and shows public swimming pools feeder
Rating Voltage Short-circuit b Temporary outdoor b Presence of
rating (Ue) current (Isc) recreational installations chemical agents Setup in
aM gG aM gG N 1P 1P+N (1) 2P 3P 3P+N (1) subdistribution
N 1 1 3 1 3 5 N 1 3 5 To be modified according to board or main
DB112796
DB112797
DB112798
DB112799
DB112800
DB110801
N 1
national obligations (above) switchboard
b Residual current
device protecting
each circuit to a
high-risk zone
2 2 2 4 2 4 6 2 4 6
b Residual current
10 A 690 V AC - 80 kA - 15787 MGN15708 MGN15707 MGN15709 MGN15710 MGN15711 MGN15712 device or circuit
16 A 690 V AC - 80 kA - 15788 breaker protecting a
14 x 51 25 A 690 V AC 120 kA - 15762 - group of circuits
mm 32 A 500 V AC 120 kA 120 kA 15763 15791
3 modules 3 modules 6 modules 6 modules 9 modules 12 modules
40 A 500 V AC 120 kA 120 kA 15764 15792 b On incoming
50 A 400 V AC 120 kA - 15765 - of 9 mm of 9 mm of 9 mm of 9 mm of 9 mm of 9 mm
feeder: residual
32 A 690 V AC - 80 kA - 15794 MGN15714 MGN15713 MGN15715 MGN15716 MGN15717 MGN15718 current circuit
40 A 690 V AC 80 kA 80 kA 15751 15795
22 x 58 50 A 690 V AC 80 kA 80 kA 15752 15796 breaker or device
mm 63 A 690 V AC 80 kA 80 kA 15753 15797 (*) The 10 mA sensitivity is useful for certain very specific applications, where there is a risk that someone could sustain a non-dangerous current (10 to 30 mA)
80 A 690 V AC 80 kA 80 kA 15754 15798 4 modules 4 modules 8 modules 8 modules 12 modules 16 modules
100 A 500 V AC 120 kA - 15755 - of 9 mm of 9 mm of 9 mm of 9 mm of 9 mm of 9 mm without being able to get free. Example: healthcare equipment for hospital beds. Generally, devices with this very high sensitivity are liable to cause frequent
Operating frequency: 50/60 Hz tripping, due to the natural leakage currents of the installation.
(1) The neutral pole comes equipped with a locked tube.
Loads
With no special characteristics b General-purpose power sockets b b b
DB123165
b Incandescent lighting
b Household appliances: microwave oven, dishwasher,
clothes dryer
b Electric heating, water heater
Powered in single phase, b Household appliances: induction cooking appliances, washing – b b
including a rectifier machines (variable speed)
b Single-phase variable speed drives Standards IEC/EN 61008 IEC/EN 61008 IEC/EN 60947-2 and IEC/EN 60947-2 and IEC/EN IEC/EN 60947-2 IEC/EN 61009
Generating high-frequency b Fluorescent lighting powered by extra low voltage transformer, – – b IEC/EN 61009 61009
interference (current peaks, by electronic ballast Number of 1P+N – – – – – b
harmonics) b Variable luminosity lighting poles 2P b b b b b –
b Powerful IT equipment 3P – – b b b –
b Single-phase variable speed industrial drives
4P b b b b b –
b Air conditioning
Type AC b b b b b b
b Telecommunications equipment
b Capacitor banks A – – – b b b
b si(E) – b (1) b (1) b b b
Including a harmonic filter in the b Microcomputer systems – –
power supply b Computer peripherals (printers, scanners, etc.) B – – – – – –
Powered in three phase, b Three-phase variable speed industrial drives – – – Voltage (V) Ue 230/400 230/400 130, 230/400 230/400 110/220, 230/400, 440/500 230
including a rectifier b Three-phase uninterruptible power supplies Impulse Uimp 6 6 6 6 8 4
voltage (kV)
Insulation Ui 440 440 500 500 690 400
Electrical environment voltage (V)
Vicinity of equipment generating b High-powered switching devices – – b
DB123166
L – – –
100 - - - - - - - K – – –
300 - - - - - - - - - MA – – –
s or R 500 - - - - - - - - - - - For more details, see 63 60 48 52 55 65
1000 - - - - - - - - - - - page
3000 - - - - - - - - - - - - - Accessories – 78 78 92 98
Auxiliaries – 82 82 92 98 92
Selective s 100 - - - - - - - - - - -
300 - - - - - - - - - - - - (1) iID and Vigi iC60 Asi types only
500 - - - - - - - - - - - -
1000 - - - - - - - - - - - -
3000 - - - - - - - - - - - - -
Delayed R 1000 - - - - - - - - - - - - -
3000 - - - - - - - - - - - - -
46 Choice of earth leakage protection devices Overview of the earth leakage protection product range (cont.) 47
Protection iID K residual current Protection iID K residual current
Earth leakage protection Earth leakage protection
circuit breakers circuit breakers (cont.)
DB123430
DB122947
torque Rigid Flexible or
Country approval pictograms 16 mm ferrule
6.5 mm
b The iID K residual current circuit breakers provide:
DB122945
DB122946
v protection of persons against electric shock by direct contact (30 mA), PZ2
v protection of persons against electric shock by indirect contact (300 mA)
PB104497-40
PB104498-40
Catalogue numbers
iID K residual current circuit breakers
Type AC Width in 9-mm
modules
Product iID K Technical data
DB123310
Auxiliaries Without auxiliaries
Main characteristics
2P Sensitivity 30 mA 300 mA
According to IEC/EN 61008-1
Rating 25 A A9R50225 A9R75225 4
DB122476
DB123312
Conditional rated With iC60N/H/L, iK60N 6000 A
Rating 25 A A9R50425 A9R75425 8
DB122477
DB123391
PB104497-40
b Padlocking device
Dimensions (mm)
4P 72 69
DB122775
2P 36 5.5 44 20
b Large circuit labelling area
96 85 45
48 iID K residual current circuit breakers iID K residual current circuit breakers 49
Protection iID residual current Protection iID residual current
Earth leakage protection Earth leakage protection
circuit breakers (AC, Asi types) circuit breakers (AC, A, Asi types)
(cont.)
IEC/EN 61008-1
PB104548-40
DB116619
DB123430
DB122858
PB104473-40
The Asi type improves protection against electrical interference and polluted or
corrosive environments.
Catalogue numbers
PB104472-40
b Insulated terminals IP20
iID residual current circuit breakers
Type AC Width in 9 mm
Product iID module
Auxiliaries Can accept auxiliaries, page 82
2P Sensitivity 10 mA 30 mA 100 mA 300 mA 500 mA 300 mA s 500 mA s
b Test button
Rating 16 A A9R10216 - - - - - - 4
DB122476
25 A A9R30225 A9R61225 - - -
40 A - A9R61240 - A9R35240 - Asi type
63 A - A9R61263 - A9R35263 - The Asi type improves protection against electrical interference and polluted or
100 A - - - A9R35291 -
corrosive environments.
50 iID residual current circuit breakers (AC, Asi types) iID residual current circuit breakers (AC, A, Asi types) (cont.) 51
Protection iID residual current Protection Vigi iC60 add-on residual
Earth leakage protection Earth leakage protection
circuit breakers (AC, A, Asi types) current devices (AC type)
DB116619
DB123430
Type Tightening Copper cables 50 mm² Screw-on Multi-cables terminal
DB122947
DB122945
DB122946
DB122935
DB118789
DB118787
b Combined with iC60 circuit breaker, the Vigi iC60 provide:
PB104466-35
PB104471-35
v protection of persons against electric shock by direct contact (y30 mA),
v protection of persons against electric shock by indirect contact (u100 mA),
v protection of installations against the risk of fire (300 mA or 500 mA).
iID 3.5 N.m 1 to 35 mm2 1 to 25 mm2 50 mm2 Ø 5 mm 3 x 16 mm2 3 x 10 mm2
* See page 77
Technical data
DB123310
Main characteristics
According to IEC 60947
Insulation voltage (Ui) 500 V
Pollution degree 3
Rated impulse withstand voltage (Uimp) 6 kV
Catalogue numbers
Clip on DIN rail 35 mm.
According to IEC/EN 61008-1 Vigi iC60 add-on residual current devices
Making and breaking capacity (Im/IDm) 1500 A Type Width in 9 mm
AC
Surge current AC and A types (no selective s) 250 Â modules
DB123312
DB122462
With fuse 10,000 A
(Inc/IDc)
Additional characteristics 40 A - A9V41240 - A9V44240 A9V16240 - - 4
DB122463
Mechanical 20,000 cycles 40 A - A9V41340 - A9V44340 A9V16340 - - 7
Operating AC type -5°C to +60°C 63 A - A9V41363 - A9V44363 A9V16363 A9V15363 A9V19363 7
temperature A and Asi types -25°C to +60°C
Storage temperature -40°C to +85°C
DB122464
40 A - A9V41440 - A9V44440 A9V16440 - - 7
Residual current circuit breakers 63 A - A9V41463 A9V12463 A9V44463 A9V16463 A9V15463 A9V19463 7
Type iID
2P 210
4P 370 Voltage rating (Ue) 230 - 240 V, 400 - 415 V
Except * 130 V
Operating frequency 50/60 Hz
Accessories page 78
Dimensions (mm)
4P 72 69
DB122775
2P 36 5.5 44 20
96 85 45
52 iID residual current circuit breakers (AC, Asi types) Vigi iC60 add-on residual current devices (AC type) 53
Protection Vigi iC60 add-on residual Protection Vigi iC60 add-on residual
Earth leakage protection Earth leakage protection
current devices (AC/Asi types) current devices (AC, Asi types)
DB123430
DB122948
Rigid Flexible or ferrule
Country approval pictograms
DB122945
DB122946
6.5 mm
PZ2
b Combined with iC60 circuit breaker, the Vigi iC60 provide:
PB104466-35
PB104471-35
The Asi type improves protection against electrical interference and polluted or
corrosive environments.
Technical data
DB123312
Main characteristics
DB123310
According to IEC 60947-2
Insulation voltage (Ui) 500 V
Pollution degree 3
Rated impulse withstand voltage (Uimp) 6 kV
According to IEC/EN 61009-1
Clip on DIN rail 35 mm. Indifferent position of installation. Surge current AC and A types (no selective s) 250 Â
withstand (8/20 μs) 3 kÂ
without tripping AC, A types (selective s)
Catalogue numbers Asi type 3 kÂ
IP20 IP40
DB123314
Additional characteristics
Vigi iC60 add-on residual current devices
Degree of protection Device only IP20
Type Asi Width in 9 mm
Device in modular enclosure IP40
modules Insulation classe II
Product Vigi iC60
Operating AC type -5°C to +60°C
Auxiliaries Without auxiliaries
temperature A and Asi types -25°C to +60°C
2P Sensitivity 10 mA 30 mA 300 mA s 1000 mA s
Storage temperature -40°C to +85°C
Rating 25 A A9V30225 A9V61225 - - 3
DB122462
40 A - A9V61240 - - 4
63 A - A9V61263 A9V65263 A9V39263 4 Weight (g)
Add-on residual current devices
Type Vigi iC60
3P Sensitivity 10 mA 30 mA 300 mA s 500 mA s 2P 165
Rating 25 A - A9V61325 - - 6 3P 210
DB122463
40 A - A9V61340 - - 7 4P 245
63 A - A9V61363 A9V65363 A9V39363 7
Dimensions (mm)
Vigi iC60 25 A
DB122766
73 5
36 27 54 54 72 54 55 44 20
4P Sensitivity 10 mA 30 mA 300 mA s 500 mA s
Rating 25 A - A9V61425 - - 6
DB122464
40 A - A9V61440 - - 7
63 A - A9V61463 A9V65463 A9V39463 7
91 91 91 101 91 45
36 36 54 63 72 63 55 44 20
91 91 91 101 91 45
2P 3P 4P
54 Vigi iC60 add-on residual current devices (AC/Asi types) Vigi iC60 add-on residual current devices (AC, Asi types) 55
Protection Vigi iC60 add-on residual Protection Vigi C120 add-on residual
Earth leakage protection Earth leakage protection
current devices (AC, Asi types) current devices (types AC/A)
(cont.)
Association iC60a, N, H, L + Vigi iC60 EN 61009
PB104556-51
DB126596
iC60 Vigi iC60 Vigi iC60 Vigi iC60
25 A 40 A 63 A When a Vigi C120 device is combined with a C120 circuit breaker, it provides the
Country approval pictograms
0.5 A to 25 A b b b following functions:
32 A - 40 A NO b b b protection of persons against electric shock by direct contact (≤ 30 mA),
50 A - 63 A NO NO b b protection of persons against electric shock by indirect contact (≥ 300 mA),
b protection of installations against fire hazards (300 mA to 1000 mA).
Association iC60L-MA + Vigi iC60
2P 3P 4P
iC60 Vigi iC60 Vigi iC60 Vigi iC60
25 A 40 A 63 A
1.6 A to 16 A b b b
25 A - 40 A NO b b
Catalogue numbers
Vigi C120 add-on residual current devices
Type AC Width in 9 mm
Product Vigi C120 modules
Auxiliaries Without auxiliary
2P Sensitivity 30 mA 300 mA 500 mA 300 mA s 1000 mA s
18563 18564 18565 18544 18545 7
dess. 077
PB104466-40
1 3
T
Visi-trip window
b Fault tripping is indicated by a red
2 4
mechanical indicator on the front face.
3P Sensitivity 30 mA 300 mA 500 mA 300 mA s 1000 mA s
18566 18567 18568 18546 18547 10
dess. 079
1 3 5
T
b Test button
2 4 6
dess. 078B
1 3 5 7
T
2 4 6 8
dess. 077
1 3
T
dismounting with comb
busbar in place
2 4
1 3 5
T
2 4 6
1 3 5 7
T
The Asi type improves protection against electrical interference and polluted or
corrosive environments.
2 4 6 8
56 Vigi iC60 add-on residual current devices (AC/Asi types) Vigi C120 add-on residual current devices (types AC/A) 57
Protection Vigi C120 residual current Protection Vigi C120 residual current
Earth leakage protection Earth leakage protection
devices (types A "si" and "SiE") devices (types AC, A,
"si" and "SiE")
EN 61009 b Polarizing slot
DB126596
Country approval pictograms When a Vigi C120 device is combined with a C120 circuit breaker, it provides the
following functions:
b protection of persons against electric shock by direct contact (≤ 30 mA),
b Fault indication by the red
b protection of persons against electric shock by indirect contact (≥ 300 mA), b Test button
056841N_SE
056842N_SE
b protection of installations against fire hazards (300 mA to 1000 mA). strip on the reset toggle
etc.
b protected against nuisance tripping caused by transient voltage surges (lightning
strike, operation of switchgear on the network, etc.)
DB118767
DB122831
2P Sensitivity 30 mA 300 mA 500 mA 300 mA s 1000 mA s
18591 18592 18593 18556 18557 7
dess. 077
1 3
T
Technical data
2 4
Main characteristics
3P Sensitivity 30 mA 300 mA 500 mA 300 mA s 1000 mA s To IEC 60947-2
18594 18595 18596 18558 18559 10
dess. 079
1 3 5
T Clips onto 35 mm DIN rail. Any installation position. Insulation voltage (Ui) 500 V AC
Degree of pollution 3
Rated impulse withstand voltage (Uimp) 6 kV
2 4 6
To EN 61009
IP20 IP40
DB122932
4P Sensitivity 30 mA 300 mA 500 mA 300 mA s 1000 mA s Impulse current Types AC and A (non-selective s) 250 Â
18597 18598 18599 18560 18561 10 withstand (8/20 μs)
dess. 078B
1 3 5 7
T Types AC and A (selective s) 3 kÂ
without tripping
Types "si" and "SiE" (non-selective s) 3 kÂ
Types "si" and "SiE" (selective s) 5 kÂ
2 4 6 8
Additional characteristics
Type "SiE" Width in 9 mm Degree of protection Device only IP20
Product Vigi C120 modules Device in a modular enclosure IP40
Insulation class II
Auxiliaries Without auxiliary
Operating temperature Type AC -5 °C to +60 °C
3P Sensitivity 30 mA 300 mA 500 mA 300 mA s 1000 mA s Dimensions (mm) Types A, "si" and "SiE" -25 °C to +40 °C
18676 18677 - - - 10 C120 + Vigi C120
dess. 079
1 3 5
T Storage temperature -40 °C to +60 °C
148-0503
2 4 6
1 3 5 7
T
58 Vigi C120 residual current devices (types A "si" and "SiE") Vigi C120 residual current devices (types AC, A, "si" and "SiE") 59
Protection Vigi NG125 add-on residual Protection Vigi NG125 add-on residual
Earth leakage protection Earth leakage protection
current devices (A type) current devices (AC, Asi types)
DBxxxxxx
DBxxxxxx
DBxxxxxx
DB116619
DBxxxxxx
DBxxxxxx
DBxxxxxx
Country approval pictograms Country approval pictograms
PB103997-40
057484-40
PB103997-40
b When it is combined with an NG125 circuit breaker or switch, the Vigi NG125
add-on residual current device offers the following functions:
v protection of persons against electric shocks by direct contact (30 mA),
v protection of persons against electric shocks by indirect contact (u 300 mA),
v protection of installations against fire risks (300 mA or 500 mA).
DB122462
3P Sensitivity 30 mA 300 mA 300 mA s 1000 mA s 300…1000 I/S 300…3000 I/S/R 3P Sensitivity 30 mA 300 mA Sensitivity 30 mA 300…3000 I/S/R
Rating 63 A 19013 19014 19032 19033 - - 9 Rating 63 A 19002 19003 9 125 A 19100 19106 11
DB122463
DB122463
- - - - - 19036 11
4P Sensitivity 30 mA 300 mA 300 mA s 1000 mA s 300…1000 I/S 300…3000 I/S/R 4P Sensitivity 30 mA 300 mA Sensitivity 30 mA 300…3000 I/S/R
Rating 63 A 19015 19016 19034 19035 - - 9 Rating 63 A 19004 19005 9 125 A 19101 19107 11
DB122464
DB122464
- - - - - 19037 11
Voltage rating (Ue) 230 - 240 V, 400 - 415 V Voltage rating (Ue) 230 - 240 V, 400 - 415 V
Except: (1) 110…220 V and (2) 440…500 V
Operating frequency 50/60 Hz Operating frequency 50/60 Hz
Accessories page 98 Accessories page 98
60 Vigi NG125 add-on residual current devices (A type) Vigi NG125 add-on residual current devices (AC, Asi types) 61
Protection Vigi NG125 add-on residual Protection Vigi NG125 add-on residual
Earth leakage protection Earth leakage protection
current devices (AC, A, Asi types) current devices (AC, A, Asi types)
DB123404
According to IEC 60947-2 torque Rigid Flexible or Screw terminal connection for
Insulation voltage (Ui) 690 V ferrule clamp ring terminal
DB123310
DB122945
DB122946
DB123409
DB123410
DB123488
According to IEC/EN 61009-1
Surge current Selective s or R 5 k 20 mm
withstand (8/20 μs) Instantaneous 3 kÂ
without tripping 63 A 3.5 N.m 1.5 to 50 mm2 1 to 35 mm2 - - -
Clip on DIN rail 35 mm. Additional characteristics 125 A 6 N.m 16 to 70 mm2 10 to 50 mm2 - 25 to 70 mm2 2 x 35 mm2
DB123405
Degree of protection Device only IP20 1 x 50 mm2
DB123408
Additional characteristics 5 mm
Vigi 125 A and adjustable PZ1
Plug-in auxiliaries MXV Remote tripping
SDV Indication of tripping upon
earth fault
Adjustable Vigi
Indifferent position of installation.
Sensitivity adjustable by notch (IΔn) 300, 500, 1000, 3000 mA
Tripping time Instantaneous
Selective s 60 ms
Time-delayed 150 ms
Leakage current indication on 3P and 4P On front face by LED
300...3000 I/S/R (pre-alarm) Remote, by potential-free normally-open
contact 250 V - 1 A (low level)
IP20 IP40
DB123314
DB123406
NG125 NG125 NG125
2P 3P/4P 3P/4P
Weight (g)
Add-on residual current devices
2P (5 modules) 63, 125 A (9 modules) 63, 125 A (11 modules)
Number of 9 mm modules 2P 3P 4P
5 modules 250 - -
54.25 26.75 72.25 26.75
DB123587
9 modules - 410 450
11 modules - 750 800 NG125 16.25 NG125 16.25
3P/4P 3P/4P
101.75 101.75
62 Vigi NG125 add-on residual current devices (AC, A, Asi types) Vigi NG125 add-on residual current devices (AC, A, Asi types) 63
Protection Vigi NG125 add-on residual Protection Residual current devices
Earth leakage protection earth leakage protection
current devices (AC, A, Asi types) DPN N Vigi
(cont.)
Association NG125 + Vigi NG125 Function
056341_SE-50
PB104341-40
Vigi NG125 Vigi NG125 b The DPN N Vigi residual current device provides complete protection of final
63 A 125 A circuits (overcurrents and insulation faults):
NG125 y 63 A b NO v protection of people against electric shocks by direct contacts (30 mA),
NG125 80…125 A* NO b v protection of people against electric shocks by indirect contacts (300 mA),
(*) No Vigi add-on residual current device for 2P circuit breakers of rating 80 A. v protection of installations from fire hazards (300 mA).
b Fast closing.
b Positive break indication.
b Display of earth fault on the front panel by position of toggle.
b The "si" range has been designed to maintain a network with optimum safety and
continuity of service in installations disturbed by:
v extreme atmospheric conditions,
v harmonic generating loads,
v transient operating currents.
b Test button
Vigi 125 A and adjustable Catalogue numbers
b MXV remote tripping auxiliary
Vigi 125 A and adjustable DPN N Vigi
b Auxiliary for electrical indication of tripping Type AC Type A Type A-si Width in 9-mm
upon earth fault: SDV modules
Auxiliaries Can accept auxiliaries, module 90142
1P+N Curve B Sensitivity 30 mA 300 mA 30 mA 300 mA - -
Rated 4A 19650 - 19752 - - - 4
DB119073
N 1
PB104466-40
64 Vigi NG125 add-on residual current devices (AC, A, Asi types) Residual current devices DPN N Vigi 65
Protection Residual current devices Protection Residual current devices
earth leakage protection earth leakage protection
DPN N Vigi (cont'd) DPN N Vigi (cont'd)
rigid flexible or with end-piece Earth leakage protection with instantaneous 30, 300 mA
tripping
DB112804
DB112805
15 mm
PZ2 Setting temperature for ratings 4 to 40 A 30°C
5.5 mm Tripping curve Curve B: the magnetic tripping devices act at
between 3 and 5 In
4 to 40 A 3.5 N.m 1 to 16 mm2 1 to 10 mm2 Curve C: the magnetic tripping devices act at
between 5 and 10 In
Breaking capacity
6 Insulated connector 14885
DB119082
EN61009
7 Comb busbar 13 outgoing feeders 14880 Rated breaking capacity (Icn) 6,000 A
(bag of 2) 24 outgoing feeders 14890 Rated residual breaking and making capacity 6,000 A
(IDm)
Endurance
Ratings (A) Mechanical endurance Electrical endurance under rated
current
Number of O/C cycles Number of O/C cycles
Mounting 4 to 40 20 000 20,000 y 20 A
10,000 u 25 A
8 Padlocking facility 26970
(bag of 2 parts)
9 Spacer 27062 Other characteristics
10 Clip-on terminal markers Degree of protection IP4/IPxxD for the part outside of the enclosure
11 Interpole barrier 27001 Insulation voltage (Ui) 400 V
Rated impulse withstand voltage (Uimp) 4 kV
Service temperature Type AC: from -5°C to +60°C
Type A and type A-si: from -25°C to +60°C
Storage temperature -30°C to +70°C
8/20 µs impulse withstand Type AC and type A: 250 Â
Auxiliaries 54 mm max. Type A-si : 3 kÂ
Limitation class 3
Indication Auxiliary contacts Tripping devices
Insulation class 2
4 SD fault indicating switch
Tropicalization Treatment 2 (relative humidity 95% at 55°C)
5 OF or OF+SD/OF auxiliary contact
DB122729
or opening release for emergency stoppage MNx
3 Shunt release MX, MX+OF or voltage threshold 4.8
release MSU
81 45
3.6
72
Weight
Residual current device
Type DPN N Vigi
1P+N 125 g
66 Residual current devices DPN N Vigi Residual current devices DPN N Vigi 67
Protection PRF1 12.5r/PRF1 Master/ Protection PRF1 12.5r/PRF1 Master/
Load protection Load protection
PRD1 25r/PRD1 Master PRD1 25r/PRD1 Master
Type 1 and 2 LV surge arresters Type 1 and 2 LV surge arresters
The Type 1 range of surge arresters meets the PRF1 12.5r/PRF1 Master/PRD1 25r/PRD1 Master
normative withstand capability of current wave The Type 1 surge arrester is recommended for electrical installations in the service
type 10/350 μs (8/20 μs for Type 2 surge sector and industrial buildings protected by a lightning conductor or by a meshed
arresters). cage.
It protects electrical installations against direct lightning strikes.
It is suitable for use with TT, TN-S, TN-C and 230 V
It is used to conduct the direct lightning current, propagating from the earth
IT earthing connection systems (neutral point conductor to the network conductors.
connection). It must be installed with an upstream disconnection device, such as a fuse or
In addition, the PRF1 Master surge arrester covers circuit-breaker, whose breaking capacity must be at least equal to the maximum
the 400 V IT system. prospective short-circuit current at the installation point.
PRF1 12.5r and PRD1 surge arresters are fitted with PRF1 12.5r and PRD1 25r surge arresters also provide Type 2 protection and
a remote transfer contact to send «end-of-life protect the electrical installation by finely clipping the lightning wave overvoltages.
indication» information.
PRD1 surge arresters are fitted with easy-to-
DB123384
DB118911
DB119039
DB119038
replace withdrawable cartridges.
PRF1 12.5r (1P+N, 3P+N) PRF1 Master (1P) PRF1 12.5r (3P) PRF1 Master (2P, 3P, 4P)
arrester
Fixed surge 1P+N 3P+N 1P 2P 3P 4P
arrester
PRF1 12.5r 16632 16634 TT, TN-S
T1, T2
16633 TN-C
PRF1 Master 2 x 16630 IT (1) distributed neutral 16643
T1
16630 3 x 16630 IT (1) non-distributed 16644
neutral
4 x 16630 IT (1) distributed neutral 16645
PRF1 12.5r
DB122528
DB119036
DB119037
DB122527
DB122527
PB104260-35
PRD1 25r (1P+N, 3P+N) PRD1 Master (1P+N, 3P+N) PRD1 25r (1P) PRD1 25r (2P, 3P, 4P) PRD1 Master (2P, 3P, 4P)
Cartridge 1P+N 3P+N 1P 2P 3P 4P
surge arrester
PRD1 25r 16330 16332 TT, TN-S
PRD1 25r T1 + T2
2 x 16329 4 x 16329 IT 230 V
16329 16331 TN-C
PRD1 Master 16361 16363 TT, TN-S
PB104264-35
T1
2 x 16360 4 x 16360 IT 230 V
16362 TN-C
(1) Version without indicator light.
PRD1 Master
68 PRF1 12.5r/PRF1 Master/PRD1 25r/PRD1 Master PRF1 12.5r/PRF1 Master/PRD1 25r/PRD1 Master 69
Protection PRF1 12.5r/PRF1 Master/ Protection PRF1 12.5r/PRF1 Master/
Load protection Load protection
PRD1 25r/PRD1 Master PRD1 25r/PRD1 Master
Type 1 and 2 LV surge arresters Type 1 and 2 LV surge arresters
Name of the Nb. of Width I imp (kA) (10/350) I max (kA) In - kA Up - kV Un - V Uc - V Cat. Technical data
surge poles Impulse current (8/20) Rated Degree of Nominal Maximum no. PRF1 12.5r PRF1 Master PRD1 25r PRD1 Master
arrester Maximal discharge protection line steady Operating frequency 50 Hz 50/60 Hz 50 Hz 50 Hz
discharge current voltage state Degree of protection Front panel IP40 IP40 IP40 IP40
current voltage Terminals IP20 IP20 IP20 IP20
Fixed surge 9 mm Surge Surge arrester Impacts IK05 IK05 IK05 IK05
arrester modules arrester + disconnector Response time y 25 ns y 1 ms y 25 ns y 100 ns
End-of-life indication Green: correct operation - White: correct operation White: correct operation
PRF1 12.5r Type 1 + 2
Red: at end of life - Red: at end of life Red: at end of life
1P+N 4 12.5/50 N/PE 50 25 1.5 230 350 16632 Remote 1 A/250 V AC - 1 A/250 V AC. 1 A/250 V AC.
3P 8 12.5 50 25 1.5 230 / 400 350 16633 notification 0.2 A/125 V DC 0.2 A/125 V DC
3P+N 8 12.5/50 N/PE 50 25 1.5 230 / 400 350 16634 By tunnel terminal Rigid cable 10...35 mm² 10...50 mm² 2.5...35 mm² 10...35 mm²
Flexible 10...25 mm² 10...35 mm² 2.5...25 mm² 10...25 mm²
PRF1 Master Type 1
cable
1P 4 50 35 - 50 1.5 230 440 16630 Operating temperature -25°C to +60°C -40°C to +85°C -25°C to +60°C -25°C to +60°C
Withdrawable surge arrester Standards Type 1 IEC 61643-1 T1. IEC 61643-1 T1. IEC 61643-1 T1. IEC 61643-1 T1.
EN 61643-11 Type 1 EN 61643-11 Type 1 EN 61643-11 Type 1 EN 61643-11 Type 1
PRD1 25r Type 1 + 2
Type 2 IEC 61643-1 T2. - IEC 61643-1 T2. -
1P 4 25 40 25 1.5 230 350 16329 EN 61643-11 Type 2 EN 61643-11 Type 2
1P+N 8 25/100 N/PE 40 25 1.5 230/400 350 16330 Certification CE KEMAKEUR, CE KEMAKEUR, CE CE
3P 12 25 40 25 1.5 230 350 16331
3P+N 16 25/100 N/PE 40 25 1.5 230/400 350 16332
PRD1 Master Type 1
1P 4 25 - 25 1.5 230 350 16360
1P+N 8 25/100 N/PE - 25 1.5 230/400 350 16361
Choice of disconnector / surge arrester
3P 12 25 - 25 1.5 230 350 16362
Type Iimp: Isc: prospective short-circuit current at the installation point
3P+N 16 25/100 N/PE - 25 1.5 230/400 350 16363
Spare cartridge impulse 10 kA 15 kA 25 kA 36 kA 50 kA
C1 Master-350 - 4 - - - 25 1.5 - 350 16314
current
C1 25-350 - 23 mm - - - 25 1.5 - 350 16315 PRF1 12.5r 12.5 kA C120N 80 A curve C C120H 80 A curve C NG125N 80 A curve C Contact us
or
C2 40-350 - 12 mm - - - 20 1.4 - 350 16316 NG125N 80 A curve C
C1 Neutral-350 - 4 - - - - - - 350 16317 PRF1 Master 35 kA Compact NSX160B 160 A TM Compact NSX160F Compact NSX160N
160 A 160 A
PRD1 25r 25 kA NG125N 80 A curve C -
PRD1 Master 25 kA NG125N 80 A curve C NG125H 80 A curve C NG125L 80 A curve C
DB123370
arrester Type Number of poles Cat. no.
Phase Neutral 4P Wiring comb busbars 4 16643
Type 1 Type 2 6P Wiring comb busbars 6 16644
PRD1 25r 8P Wiring comb busbars 8 16645
PRD1 25r 1P 16315 16316 - 200 mm flexible cable (PRF1 Master) 16646
PRD1 25r 1P+N 16315 16316 16317
PRD1 25r 3P 3 x 16315 3 x 16316 -
PRD1 25r 3P+N 3 x 16315 3 x 16316 16317
PRD1 Master
PRD1 Master 1P 16314 - -
PRD1 Master 1P+N 16314 - 16317
PRD1 Master 3P 3 x 16314 - -
PRD1 Master 3P+N 3 x 16314 - 16317
70 PRF1 12.5r/PRF1 Master/PRD1 25r/PRD1 Master PRF1 12.5r/PRF1 Master/PRD1 25r/PRD1 Master 71
Protection iPF surge arresters Protection iPRD surge arresters
Load protection Type 2 or 3 LV surge arresters Load protection Type 2 or 3 LV withdrawable surge arresters
The iPRD multi-pole single-piece surge arrester iPRD withdrawable Spare cartridges
range is adapted for earthing systems: TT, TN-S, surge arresters allow Type Spare cartridges for Cat. no
TN-C. quick replacement of C 65-460 iPRD65r IT A9L16682
Type 2 surge arresters are tested with a 8/20 ms damaged cartridges. C 65-340 iPRD65r A9L16681
current wave. C 40-460 iPRD40r IT A9L16684
C 40-340 iPRD40, iPRD40r A9L16685
Type 3 surge arresters are tested with a 12/50 ms C 20-460 iPRD20r IT A9L16686
and 8/20 ms combined wave.
PB105274-35
C 20-340 iPRD20, iPRD20r A9L16687
C 8-460 iPRD8r IT A9L16688
C 8-340 iPRD8, iPRD8r A9L16689
Rated Type of Network Earthing Tr. Surge Wid. Up - (kV) Un - (V) Uc - (V) C neutral All products A9L16691
discharge protection system arrester in mod. Voltage protection level Rated Maximum continuous
current (Imax) / name of 9 mm volt. operating voltage
Nominal netw. Surge arrester/circuit breaker association
CM* DM* CM* DM* Type of surge arrester Associated circuit breaker
discharge
current (In) iPRD65 Curve C 50 A
iPRD40 Curve C 40 A
iPRD20 Curve C 25 A
Incom. Secon. L/t N/t L/N L/t N/t L/N 1P+N iPRD8 Curve C 20 A
65 kA / 20 kA iPRD65
Very high risk level iPRD65 1P A9L16555 IT b iPRD65r 1P IT y2 - - 230 460 - -
(strongly exposed 2
1P A9L16556 TT & TN b iPRD65r 1P y 1.5 - - - 340 - -
PB105275-35
site)
1P+N A9L16557 TT & TN-S b iPRD65r 1P+N - y 1.5 y 1.5 - - 260 340 Each surge arrester in the range has a specific application:
4
2P A9L16442 TN-C b iPRD65r 2P y 1.5 y 1.5 - - 340 340 - b incoming protection (type 2):
3P A9L16558 IT b iPRD65r 3P IT y2 - - 230/400 460 - - v the iPRD65(r) is recommended for a very high risk level (strongly exposed site)
6
3P A9L16443 TN-C b iPRD65r 3P y 1.5 - - - 340 - - v the iPRD40(r) is recommended for a high risk level
3P+N A9L16559 TT & TN-S b iPRD65r 3P+N - y 1.5 y 1.5 - - 260 340 v the iPRD20 is recommended for a medium risk level
8
4P A9L16659 TN-C b iPRD65r 4P y 1.5 y 1.5 - - 340 340 -
b secondary protection (type 2 or 3):
40 kA / 15 kA iPRD40 v the iPRD8 ensures secondary protection of loads to be protected and is placed in
High risk level iPRD40 1P A9L16561 TT & TN b iPRD40r 1P y 1.4 - - 230 340 - - cascade with the incoming surge arresters. This surge arrester is required when the
2
1P A9L16566 TT & TN iPRD40 1P y 1.4 - - - 340 - - loads to be protected are at a distance of more than 30 m from the incoming surge
1P+N A9L16562 TT & TN-S b iPRD40r 1P+N - y 1.4 y 1.4 - - 260 340
arrester.
1P+N A9L16567 TT & TN-S iPRD40 1P+N - y 1.4 y 1.4 - - 260 340 3P
4
2P A9L16444 TN-C b iPRD40r 2P y 1.4 y 1.4 - - 340 340 -
2P A9L16667 TN-C iPRD40 2P y 1.4 y 1.4 - - 340 340 - The iPRD surge arresters with “r” indication have remote transfer of the information:
3P A9L16445 TN-C b iPRD40r 3P y 1.4 - - 230/400 340 - - “surge arrester to be replaced”.
3P A9L16568 TN-C iPRD40 3P 6 y 1.4 - - - 340 - -
PB105276-35
3P A9L16563 IT b iPRD40r 3P IT y2 - - - 460 - -
3P+N A9L16564 TT & TN-S b iPRD40r 3P+N - y 1.4 y 1.4 - - 260 340
3P+N A9L16569 TT & TN-S iPRD40 3P+N - y 1.4 y 1.4 - - 260 340
4P A9L16597 IT b iPRD40r 4P IT 8 y2 y2 - - 460 460 -
4P A9L16664 TN-C b iPRD40r 4P y 1.4 y 1.4 - - 340 340 - Technical data
4P A9L16669 TN-C iPRD40 4P y 1.4 y 1.4 - - 340 340 -
20 kA / 5 kA iPRD20 Main characteristics
Operating frequency 50/60 Hz
Medium risk level iPRD20 1P A9L16571 TT & TN iPRD20 1P 2 y 1.1 - - 230 340 - -
Operating voltage (Ue) 230/400 V AC
1P+N A9L16672 TT & TN-S b iPRD20r 1P+N - y 1.4 y 1.1 - - 260 340
Permanent operating current (Ic) < 1 mA
1P+N A9L16572 TT & TN-S iPRD20 1P+N 4 - y 1.4 y 1.1 - - 260 340
Response time < 25 ns
2P A9L16446 TN-C iPRD20 2P y 1.1 y 1.1 - - 340 340 -
End of life indication: Green In operation
3P A9L16447 TN-C iPRD20 3P y 1.1 - - 230/400 340 - - 3P+N
6 by green/red mechanical indicator Red At end of life
3P A9L16573 IT b iPRD20r 3P IT y 1.6 - - - 460 - -
End of life remote indication By contact NO, NC 250 V / 0.25 A
3P+N A9L16674 TT & TN-S b iPRD20r 3P+N - y 1.4 y 1.1 - - 260 340
Additional characteristics
3P+N A9L16574 TT & TN-S iPRD20 3P+N - y 1.4 y 1.1 - - 260 340
8 Operating temperature -25°C to +60°C
PB105272-35
4P A9L16599 IT b iPRD20r 4P IT y 1.6 y 1.6 - - 460 460 -
Type of connection terminals Tunnel terminals, 2.5 to 35 mm²
4P A9L16673 TN-C iPRD20 4P y 1.1 y 1.1 - - 340 340 -
Standards IEC 61643-1 T2 and EN 61643-11 Type 2
8 kA / 2.5 kA iPRD8 (1) Type 2 / Type 3
Secondary iPRD8
A9L16576 TT & TN iPRD8 1P 2 y1/y1 - - 230 340 - -
protection: 1P
placed near the loads 1P+N A9L16677 TT & TN-S b iPRD8r 1P+N - y 1.4 / y 1 y 1 / y 1.1 - - 260 340
to be protected when 1P+N A9L16577 TT & TN-S iPRD8 1P+N 4 - y 1.4 / y 1 y 1 / y 1.1 - - 260 340
they are at a distance 2P A9L16448 TN-C iPRD8 2P y1/y1 y1/y1 - - 340 340 -
of more than 30 m 3P A9L16449 TN-C iPRD8 3P y1/y1 - - 230/400 340 - -
6
from the incoming 3P A9L16578 IT b iPRD8r 3P IT y 1.4 / y 1.6 - - - 460 - -
surge arrester 3P+N A9L16679 TT & TN-S b iPRD8r 3P+N - y 1.4 / y 1 y 1 / y 1.1 - - 260 340
3P+N A9L16579 TT & TN-S iPRD8 3P+N - y 1.4 / y 1 y 1 / y 1.1 - - 260 340
8 Cartridge
4P A9L16678 IT b iPRD8r 4P IT y 1.4 / y 1.6 y 1.4 / y 1.6 - - 460 460 -
4P A9L16680 TN-C iPRD8 4P y1/y1 y1/y1 - - 340 340 -
* CM: common mode (phase to earth and neutral to earth). * DM: differential mode (phase to neutral). (1)bUoc:
combinated waveform voltage: 10 kV.
Connection Withdrawable Quick PRD surge arresters allow They protect electrical and electronic equipment against lightning-induced surges.
damaged cartridges to be replaced quickly. Quick PRD surge arresters are prewired, incorporating their end-of-life disconnector.
Type Tightening torque Copper cables
DB123130
They offer remote reporting of the "cartridge Each surge arrester in the range has a specific use:
Rigid Flexible or ferrule b incoming protection (type 2):
must be changed" message.
14 mm v Quick PRD 40r is recommended for a high risk level
DB122945
DB122946
6.5 mm v Quick PRD 20r is recommended for a moderate risk level
PZ2
b close protection (type 2 or 3):
v Quick PRD 8r provides close protection for the loads to be protected and is
cascade-mounted with the incoming surge arresters. This surge arrester is required
iPRD 2 N.m 2.5 to 25 mm2 2.5 to 16 mm2 as close as possible to the loads to be protected when they are located more than 30
metres away from the incoming surge arrester.
1P 1P+N
2P
Diagrams
14
3P 3P+N
4P
DB123060
surge poles 9 mm Maximum Nominal (kV) (1) system Nominal Maximum no. torque Al connection terminal
arrester modules discharge discharge Protection level mains steady state 14 mm terminal for ring
6.5 mm Rigid Flexible Rigid Flexible
current current voltage voltage or ferrule terminal cables cables
PZ2
CM DM CM DM
DB122945
DB122946
DB122935
DB118789
DB118787
L/t N/t L/N L/t N/t L/N
Quick PRD 40r
Quick PRD 40r 1P+N 8 40 20 1.5 1.5 2.5 TT and TN-S 230 - 264 350 16292 iC60 0.5 to 25 A 2 N.m 1 to 25 mm2 1 to 16 mm2 - Ø 5 mm - -
Quick PRD 40r 3P 13 2 - - TN-C and IT 230 V 230/400 350 - - 16293 32 to 63 A 3.5 N.m 1 to 35 mm2 1 to 25 mm2 50 mm2 3 x 16 mm2 3 x 10 mm2
Quick PRD 40r 3P+N 15 1.5 1.5 2.5 TT and TN-S - 264 350 16294 Vigi iC60 25 A 2 N.m 1 to 25 mm2 1 to 16 mm2 - - - -
Quick PRD 20r 40 to 63 A 3.5 N.m 1 to 35 mm2 1 to 25 mm2
Quick PRD 20r 1P+N 8 20 5 1.5 1.5 1.5 TT and TN-S 230 - 264 350 16295 iID 16 to 100 A 3.5 N.m 1 to 35 mm2 1 to 25 mm2 50 mm2 Ø 5 mm 3 x 16 mm2 3 x 10 mm2
Quick PRD 20r 3P 13 1.5 - - TN-C and IT 230 V 230/400 350 - - 16296
Quick PRD 20r 3P+N 15 1.5 1.5 1.5 TT and TN-S 264 350 16297
Quick PRD 8r (2) Type 2 / Type 3 7 Splitter blocks Multiclip see page 176
DB123373
Quick PRD 8r 1P+N 8 8 2 1.5/1.4 1.5/1.5 1.2/1.4 TT and TN-S 230 - 264 350 16298 Distribloc see page 172
Quick PRD 8r 3P 13 1.2/1.4 - - TN-C and IT 230 V 230/400 350 - - 16299 8 50 mm² Al terminal 27060
Quick PRD 8r 3P+N 15 1.5/1.4 1.5/1.5 1.2/1.4 TT and TN-S 264 350 16300 9 Screw-on connection for ring terminal 27053
CM: common mode (between phase/earth and neutral/earth).
10 Multi-cables terminal 4 parts 19091
DM: differential mode (between phase and neutral).
(1) Up (MCB + SPD): total value measured between Modular Circuit Breaker (MCB) terminal 3 parts 19096
block and PE surge arrester device terminal block (SPD). 11 Comb busbar see module 91906
(2) Uoc: open-circuit voltage in combined wave: 10 kV.
Tripping devices
2 iMN undervoltage release see page 81
or iMNs undervoltage release
delayed or iMNx
undervoltage release with
external feeding
3 Shunt release iMX, iMX+OF see page 81
overvoltage release iMSU
Vigi iC60
1 Vigi iC60 add-on residual
current device
see page 47 d Tripping devices must be mounted first.
Respect specified position for SD functions.
76 Quick PRD surge arrester Accessorisation / Auxiliarisation iC60, iID, Vigi iC60 77
Protection Accessories for iC60, iID Protection Accessories for iC60, iID (cont.)
Circuit protection Circuit protection
Earth leakage protection Earth leakage protection
Mounting Security
Accessories Rotary handle Plug-in base Padlocking device Accessories Screw shield Terminal shield Inter-pole barrier Spacer
PB104493-35
PB104508-35
PB104492-15
PB104489-14
PB104488-14
PB104502-35
PB104503-35
PB104484-30
PB104483-35
DB123599
Function Function
Front or side-mounted control Allows a breaker to be removed or replaced Used to padlock breaker in open or Prevents any contact with the connecting Prevents any contact with the Enhances insulation b Used to:
b Degree of protection: IP55 rotary handle quickly, without handling the connections closed position screws terminals between connections: v complete rows
b Installation: b Degree of protection: IP20 b Padlock diameter: 3 to 6 mm b Upgrades degree of protection to IP20D b Upgrades degree of protection cables, terminals, v separate devices.
v the control mechanism is mounted on the device b Consists of: b Sealable (max. diameter: 1.2 mm) b Sealable, max. diameter 1.2 mm to IP20D lugs, etc Width: 1 x 9 mm module
v the rotary handle is fixed to the front or side of v a base to be fastened on a rail (or panel) b Locking in ON position does not b Sealable, max. diameter 1.2 mm b Allows cable routing
the enclosure v 2 "blades" to be fastened in the device's prevent tripping of the breaker in the b Set of two, for upstream and from one row to another,
b Front-mounted (on door or faceplate) terminals event of faults downstream terminals (above and below),
b Prevents the door from opening when the circuit b Connection: tunnel terminals for cable up to b Suitable for IEC/EN 60947-2 b For 3 poles: A9A26975 + A9A26976 up to 6 mm²
breaker is in the ON position (can be deactivated) 35 mm² rigid, 25 mm² flexible, compliant disconnection b For 4 poles: 2 X A9A26976
b Can be padlocked when the device is in the b Installation:
"open" position (can be padlocked with the device v in universal enclosure
in the "closed" position subject to adaptation) v on horizontal rail
b Can be locked by padlock of (dia. 5 to 8 mm), b Height: 178 mm
not supplied with the device b Not compatible with Vigi iC60 and auxiliaries
b Can be locked by padlock of (dia. 6 mm),
not supplied with the device
Catalogue A9A27005 A9A27006 A9A27008 A9A27003 A9A26970 Catalogue A9A26982 A9A26981 A9A26975 A9A26976 A9A27001 A9A27062
numbers black handle red handle no handle (1 per pole) numbers
Set of 1 1 1 1 10 Set of 12 x 1 pole 20 x 4 poles (splittable) 2 x 1 pole 2 x 2 poles 10 5
Suitability Suitability
iC60 b 2P, 3P, 4P b b iC60 – b b b b b
iC60 + Vigi iC60 b 2P, 3P, 4P – b Vigi iC60 b – – – – b
iID – b y 63 A b iID – b – b b b
Connection Marking
Accessories Multi-cable terminal 50 mm² terminal Al Screw-on connection for Accessories Marker strip
ring terminal
DB118785
DB118780
DB118781
DB118783
DB118789
b The electrical auxiliaries are combined with IEC/EN 60947-1 Combination table
iC60 circuit breakers, iID residual current circuit
b Tripping auxiliaries: Electrical auxiliaries Remote control Devices
breakers, RCA remote controls and ARA
automatic reclosers; they enable tripping or v iMN: undervoltage release Indication auxiliaries Tripping auxiliaries ARA automatic recloser iC60/iID Vigi
v iMNs: delayed undervoltage release or RCA remote control
remote indication of their position (open/closed/
v iMNx: undervoltage release, independant from supply voltage Position
PB104440-25
PB104466-25
tripped) upon a fault. v iMSU: overvoltage release
b They are fastened by clips (without tools) to the v iMX: shunt release Left Right Max quantity
left side of the breaker. v iMX+OF: shunt release with open/close contact. 1 iOF/SD+OF + 1 iOF/SD+OF + 1 (iMX or iMN or iMSU) –
b The iOF/SD+OF auxiliary is a 2-in-1 product: via a Or 1 iOF + 1 (iSD or iOF or iOF/SD+OF) + 2 (iMX or iMN or iMSU)
mechanical selector switch, it provides two IEC/EN 60947-5-1
contacts, OF+SD or OF+OF.
Or None + None + 3x iMSU
b Indication auxiliaries:
v iOF: open/close contact iC60 Vigi iC60
v iSD: fault indicating contact –
PB104472-25
v iOF/SD+OF: open/close contact and switchable OF or SD contact.
iID
DB123545
PB104440-25
PB104466-25
PB106256-25
Or 1 iOF + 1 (iSD or iOF or iOF/SD+OF) + None
PB104472-25
ARA iID
None + 1 (iSD or iOF or iOF/SD+OF) + 1 (iMX or iMN or iMSU)
PB104466-25
PB106253-25
PB104440-25
Or 1 iOF + 1 (iSD or iOF or iOF/SD+OF) + None
Connection
Type Tightening Copper cables Multi-cables terminal
DB123061
4 mm
DB122945
DB123007
DB123008
DB123011
PZ1
10 mm
Indication auxiliaries 1 N.m 1 to 4 mm2 0.5 to 2.5 mm2 2 x 2.5 mm2 2 x 1.5 mm2
Tripping auxiliaries 1 N.m 1 to 6 mm2 0.5 to 4 mm2 2 x 2.5 mm2 2 x 2.5 mm2
80 Electrical auxiliaries for iC60, iID, ARA and RCA Electrical auxiliaries for iC60, iID, ARA and RCA 81
Protection Electrical auxiliaries Protection Electrical auxiliaries
Circuit protection
Earth leakage protection for iC60, iID, ARA and RCA (cont.) Circuit protection for iC60, iID, ARA and RCA (cont.)
Earth leakage protection
Tripping Indication
Auxiliaries iMN iMNs iMNx iMSU iMX iMX+OF iOF iSD iOF/SD+OF
Type Undervoltage release Overvoltage release Shunt release Open/close Fault indicating contact Double open/close or
auxiliary contact fault indicating contact
Instantaneous Delayed Independent of the supply With Open/Close auxiliary contact
voltage
PB104477-35
PB104478-35
PB104480-35
PB104479-35
PB104496-35
PB104481-35
PB104474-35
PB104476-35
PB104475-35
Function
b Trips the device with which it is combined when its input voltage decreases b Switches off the power supply b Trips the breaker when powered b Changeover contact b Changeover contact b The iOF/SD+OF auxiliary
(between 70 % and 35 % Un). Prevents device closing again until its input voltage is restored by opening the breaker with indicates "open" or "closed" indicates position of the is a 2-in-1 product: via a
which it is combined, in the position of the breaker breaker; upon: mechanical selector switch,
event that the phase/neutral v electrical fault it provides two contacts,
voltage is exceeded (loss of v action on tripping auxiliary OF+SD or OF+OF
neutral). For a four-phase b Same indication as
network, use three iMSU tripping VISI-TRIP
auxiliaries
b Not tripping on b Separate input and power b Tripping b Tripping b Includes an open/close contact
transient voltage supply voltage: voltage: (OF) to indicate the "open" or
dip (up to 0.2 s) 275 V AC 255 V AC "closed" position of the breaker
Wiring diagrams
DB118804
DB118805
DB118806
DB123012
DB118808
DB118810
DB118811
DB118812
DB118813
U>
OF position SD position
Use
b Emergency stoppage by normally closed push button b Emergency stoppage with b Protection of equipment b Emergency stoppage by b Emergency stoppage by b Remote indication of b Remote indication of b Remote indication of
b Ensures the safety of power supply circuits for several machines fail-safe principle against overvoltages on the normally open push button normally open push button the position of the tripping upon a fault of the position and/or tripping upon
by preventing "uncontrolled" restarting b Insensitive to control circuit electrical network b Remote indication of the associated breaker associated breaker a fault of the associated
voltage variation to increase (neutral conductor break) position of the associated breaker breaker
service continuity b Voltage monitoring between
phase and neutral conductors
Catalogue numbers A9A26960 A9A26961 A9A26959 A9A26963 A9A26969 A9A26971 A9A26979 A9A26479 A9A26476 A9A26477 A9A26478 A9A26946 A9A26947 A9A26948 A9A26924 A9A26927 A9A26929
Technical specifications
Rated voltage V AC 220…240 48 115 220…240 220…240 380…415 230 230 100…415 48 12…24 100…415 48 12…24 240…415 240…415 240…415
(Ue) V DC – 48 – – – 110…130 48 12…24 110…130 48 12…24 24…130 24…130 24…130
Operating Hz 50/60 400 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60
frequency
Red mechanical indicator On front face On front face On front face On front face On front face On front face On front face On front face On front face
Test function – – – – – – On toggle On toggle On toggle
Width in 9 mm modules 2 2 2 2 2 2 1 1 1
Operating current – – – – – y24 V DC 6A 24 V DC 6A
48 V DC 2A 48 V DC 2A
y130 V DC 1A 60 V DC 1.5 A
y240 V AC 6A 130 V DC 1A
415 V AC 3A 240 V AC 6A
415 V AC 3A
Number of contacts – – – – – 1 NO/NC 1 NO/NC 1 NO/NC 1 NO/NC + 1 NO/NC
Operating °C -35…+70 -35…+70 -35…+70 -35…+70 -35…+70 -35…+70 -35…+70 -35…+70 -35…+70
temperature
Storage °C -40…+85 -40…+85 -40…+85 -40…+85 -40…+85 -40…+85 -40…+85 -40…+85 -40…+85
temperature
82 Electrical auxiliaries for iC60, iID, ARA and RCA Electrical auxiliaries for iC60, iID, ARA and RCA 83
Control RCA remote controls Control RCA remote controls (cont.)
Remote control For iC60 circuit breakers Remote control For iC60 circuit breakers
Available in 01/2011
The RCA remote control system allows: Standard RCA RCA Ti24
PB106253-40
b Remote electrical control (opening and closing) of circuit breakers with or without b The orders received on terminals Y1 and Y2 are
Vigi add-on RCD, with or without auxiliary. taken into account progressively in their order of arrival.
b Circuit-breaker resetting after tripping, in accordance with safety principles and
DB123570
DB123396
Centralized
the regulations in force.
control
b Local control by operating handle. (PLC)
b Circuit placing in safety configuration by padlocking.
24 V DC
2 choices of operation after tripping: iC60 Y3 Y3
b A: Enabling of remote circuit-breaker resetting; RCA Ti24 Ti24
RCA RCA
b B: Inhibition of remote resetting.
OF OF
The version with Ti24 interface allows:
b Direct interfacing of remote control with a programmable logic controller (PLC), N P Y2 Y1
a supervision system and any other communication device, having inputs/outputs in Y1/Y2 Y1/Y2
230 V 230 V
24 V DC (control, OF and SD indications).
Zone 1 Zone 2
b Remote indication by "OF" potential-free contact.
b Provision of 2 operating modes, "1 and 3".
Local control Local control
The iMDU auxiliary allows RCA control in 24/48 V AC/DC.
Catalogue numbers
RCA Ti24 mode 1
RCA remote control
DB123505
Type Width in 9 mm Mode 1: Locally or centrally controlled
230 V AC
modules circuit-breaker opening/closing
b The orders come from various control points, and they are 24 V c
For circuit breakers Voltage
0V
1P, 1P+N, 2P taken into account in their order of arrival
Y3
b Y1: Latched order local control OF
Without Ti24 interface 230 V AC, 50 Hz A9C70112 7 b Y2: Impulse-type local control SD
With Ti24 interface 230 V AC, 50 Hz A9C70122 7 b Y3: Latched order centralized control
Ti24
For 3P, 4P circuit breakers RCA
Without Ti24 interface 230 V AC, 50 Hz A9C70114 7
With Ti24 interface 230 V AC, 50 Hz A9C70124 7 OF
N P Y2 Y1 11 12 14
DB123507
Mode 3: Centrally controlled
DB123572
DB123571
DB123565
in open position
torque Rigid Flexible Flexible with ferrule
b Ti24 interface
for link to PLC
DB122945
DB123553
DB123554
3.5 mm
PZ1
10 mm
b Operating state Power supply (N/P) 1 N.m 0.5 to 10 mm2 0.5 to 6 mm2 0.5 to 4 mm2
indicator lamp Inputs (Y1/Y2) 2 x 0.5 to 2 x 2.5 mm2 2 x 0.5 to 2 x 2.5 mm2 2 x 0.5 to 2 x 2.5 mm2
Outputs (OF) 0.7 N.m 0.5 to 2.5 mm2 0.5 to 2.5 mm2 0.5 to 1.5 mm2
DB123568
2 x 0.5 to 2 x 1.5 mm2 2 x 0.5 to 2 x 1.5 mm2 2 x 0.5 to 2 x 1.5 mm2
8 mm
3.5 mm
b Compatible with
the circuit breaker's
electrical auxiliaries
b Selector
switch for
inhibition of all Ti24 interface Spring-loaded 0.5 to 1.5 mm2 0.5 to 1.5 mm2 -
DB123580
electrical terminals
controls
10 mm
3.5 mm
DB123567
4P
117
Supply voltage (Ue) (N/P) 230 V AC, 50 Hz
DB123577
3P
Legend 2P (1P+N)
99
81 70 Control voltage (Uc) Type 1 inputs (Y1/Y2) 230 V AC (as per IEC 61131-2)
Type Application 1P
63 3 5.5 44.5 Min. duration of control order (Y2) u200 ms
0V V DC power supply 2 Response time (Y2) y200 ms
+24VDC
Consumption y1 W
Y3 Latched order centralized control
Thermal self-protection with automatic Reset against overheating of the control circuit due to an
SD Circuit-breaker tripping information 85 45
abnormal number of operations
OF Control circuit state information (open/closed)
Endurance (O-C) (RCA combined with a circuit breaker)
Electrical/Mechanical 10,000 cycles
6
DB123578
DB123579
85 45
Additional characteristics
Degree of protection Device only IP20
Indication auxiliaries Tripping RCA remote iC60 circuit Vigi iC60 (IEC 60529) Device in a modular IP40
auxiliaries control breaker add-on RCD enclosure Insulation class II
6
Insulation voltage (Ui) 400 V
PB104474-25
PB104475-25
PB104496-25
80
97 Degree of pollution (IEC 60947) 3
Rated impulse withstand voltage (Uimp) 6 kV
+ + + + +
Operating temperature -25°C to +60°C
Storage temperature -40°C to +70°C
Tropicalization Treatment 2
(relative humidity of 93 % at +40°C)
No 1 (iSD or iOF or iOF/SD+OF) 1 (iMX or iMN or iMSU)
PB106253-25
PB104437-25
PB104437-25
max.
1 iOF 1 (iSD or iOF or iOF/SD+OF) No
Weight (g)
Remote controls
Type RCA
For 1P, 1P+N, 2P circuit breakers 400
For 3P, 3P+N, 4P circuit breakers 430
RCA iC60 Vigi iC60
b Perform automatic reclosing of the associated protection device, after tripping. The ARA automatic recloser makes a number of attempts at reclosing depending on
b Increase the availability of installations without supervision, isolated, hard of the program chosen by the user.
access and demanding very great availability (mobile telephony systems, The program includes the following settings:
motorways, pumping stations, airports, railways, meteorological stations, service b A time delay before reclosing (TA).
stations, automatic teller machines, public lighting, tunnels, etc.), by restoring them b A reinitialization time delay (TB).
to operation without intervention by personnel in the event of a transient fault b A maximum number of reclosing attempts.
(atmospheric disturbances, industrial overvoltages, etc.). If, following these attempts, the fault is still present, the device places itself in waiting
b The operator can choose predefined reclosing program which allows the safety for manual reclosing, or final remote reclosing (Y2).
and availability of facilities to be reconciled taking into account the facility's
environment.
DB123632
b The circuit is placed in safety configuration by the padlocking device.
Auto
NORMAL
PB106257-40
Catalogue numbers V
N P Y2 Y1 1
1 b – b Short cycle 1 60 s 6 min. Once after
DB123519
inhibition
4 1 b – b 3 60 s 2 min.
DB123520
3 min. 6 min.
3 min. 6 min.
Legend 2
DB123579
DB123582
DB123584
DB123521
Locked Automatic recloser inhibition indication contact 4 1 fixed time 4 min. 3 min.
21 22 24 10 min. 6 min.
OF Indicates the state of the circuit breaker or residual current 3 2 1h 10 min.
circuit breaker (opened or closed) 6h 10 min.
11 12 14 Long cycle 15 20 s 30 min.
– b b
DB123522
b Sealable cover
b Indication of ARA
Terminal Tightening Copper cables
DB123565
operating states b Placing in safety configuration by
integrated padlocking device (Ø 3 to 6 mm) torque Rigid Flexible Flexible with
ferrule
DB122945
DB123553
DB123554
3.5 mm
PZ1
10 mm Power supply (N/P) 1 N.m 0.5 to 10 mm2 0.5 to 6 mm2 0.5 to 4 mm2
Inputs (Y1/Y2) 2 x 0.5 to 2 x 2.5 mm2 2 x 0.5 to 2 x 2.5 mm2 2 x 0.5 to 2 x 2.5 mm2
Outputs (OF/Locked) 0.7 N.m 0.5 to 2.5 mm2 0.5 to 2.5 mm2 0.5 to 1.5 mm2
DB123566
b 4 predefined 2 x 0.5 to 2 x 1.5 mm2 2 x 0.5 to 2 x 1.5 mm2 2 x 0.5 to 2 x 1.5 mm2
programs
8 mm
3.5 mm
DB123567
117
of automatic recloser) (Y2) 3P
99 Min. duration of control order (Y2)
2P (1P+N) u200 ms
b Remote inhibition of 1P 81 70
Response time (Y2) y200 ms
remote reclosing (Y1) b Inhibition of automatic 63 3 5.5 44.5
2 Consumption y1 W
recloser (auto - OFF) and
resetting (Reset) Thermal self-protection with automatic Reset against overheating of the control circuit due to an
abnormal number of operations
85 Endurance
45 (O-C) (ARA combined with a circuit breaker)
Electrical 5000 cycles
Indication / Remote control
6 Potential-free changeover Min. 24 V AC/DC, 10 mA
Indication auxiliaries Tripping ARA remote iC60 or iID Vigi iC60 80
contact output (OF/Locked) Max. 230 V AC ,1 A
97
auxiliaries control device add-on RCD Input (Y1/Y2) 230 V AC 5 mA
135
PB104474-25
PB104475-25
PB104496-25
4P
3P 117 Additional characteristics
2P (1P+N) 99 Degree of protection Device only IP20
81 70
1P (IEC 60529) Device in a modular IP40
63 3 5.5 44.5
+ + + + + 2
Insulation voltage (Ui)
enclosure Insulation class II
400 V
Degree of pollution (IEC 60947) 3
85 45 Rated impulse withstand voltage (Uimp) 6 kV
No 1 (iSD or iOF or iOF/SD+OF) 1 (iMX or iMN or iMSU) Operating temperature -25°C to +60°C
PB106256-25
PB104437-25
PB104437-25
max.
Storage temperature -40°C to +70°C
1 iOF 1 (iSD or iOF or iOF/SD+OF) No 6
Tropicalization Treatment 2
80
(relative humidity of 93 % at +40°C)
97
Automatic reclosers
Type ARA
For 1P, 1P+N, 2P circuit breakers or iID 2P residual current 440
– circuit breaker
For 3P, 4P circuit breakers or iID 4P residual current circuit breaker 470
iID
Connection Without access. With accessories b The electrical auxiliaries are combined with the IEC/EN 60947-1
C120 circuit breakers; they provide the remote b Tripping auxiliaries:
Type Rating Tightening Copper cables 50 mm2 Al Screw-on Multi-cable
DB126143
DB122945
v
DB122935
DB118787
DB118789
DB122946
PZ2
b The OF+SD/OF auxiliary is a two-in-one product:
a mechanical selector switch is used to select one IEC/EN 60947-5-1
of two contacts: OF+SD/OF or OF+OF. b Indication auxiliaries:
C120 10 to 125 A 3.5 N.m 1 to 50 mm2 1.5 to 35 mm2 16 to 50 mm2 Ø 5 mm 3 x 16 mm2 3 x 10 mm2
v OF: open/closed contact
Vigi C120 10 to 125 A 3.5 N.m 1 to 50 mm2 1.5 to 35 mm2 - - - -
v SD: fault indicating contact
v OF+SD/OF: choice of open/closed contact and OF or SD contact
via the selector switch.
DB126530
or
7 50 mm2 Al terminal 27060
DB126307
8 Screw-on connection for ring 8 parts 27053
terminal
9 Multi-cable terminal 4 parts 19091 Indication Tripping
7 8 9 DPN DPN Vigi
3 parts 19096
10
10 Comb busbar see page 168
Mounting accessories
11 Sealable terminal shield for 1P (set of 2) 18526 OF SD C120
MX+OF, MN, MNs,
connection from above and
MX ou MSU MNx
below
12 Interpole barrier (set of 10) 27001
13 Screw shield 4P (set of 2) 18527
14 Clip-on terminal markers see page 94 OF+
15 2, 3 and 4-pole label holder 16 parts 27150 11 12 13 14 1 1 SD/OF
I-NA
on toggle
16 9 mm spacer 27062
17 Padlocking device 27145
Combination table
18 Plug-in base (1)
26996 Electrical auxiliaries Devices
19 Rotary handle 27047 Indication Tripping
Removable handle
Maximum number of indication auxiliaries Maximum number of tripping auxiliaries
PB104341_SE-17
056810N_SE-23
Fixed handle 27048 (from left to right)
Operating sub-assembly only (2) 27046 3 x OF or SD + 2 x MX or MN
(1)bFor 1P, centreline between 2 rows = 200 mm Or 2 x OF/SD+OF or OF or SD + 2 x MX or MN
(2)bA complete rotary handle consists of a circuit-breaker Or none 3 x MSU
operating sub-assembly, cat. no. 27046, a handle, cat. no.
27047 or a handle, cat. no. 27048.
2 x OF or SD 2 x MX or MN or MSU
057450N_SE-31
17 18 19 1 x OF + SD/OF 2 x MX or MN or MSU
Electrical auxiliaries
Indication Tripping
Indication C120 Vigi C120
3 SD fault indicating auxiliary contact 26927
4
5
OF open/closed auxiliary contact
OF/SD+OF auxiliary contact
(OF+SD or OF+OF combination)
26924
26929 d The trip units must be installed first.
DB122945
DB122946
PZ1
Vigi C120
d
6
Indication and tripping 1 N.m 0.5 to 2.5 mm² 2 x 1.5 mm2
The trip units must be installed first. auxiliaries
1 Vigi C120 add-on residual see page 94 9 mm
current device
92 Accessories and auxiliaries for C120 and Vigi C120 devices Electrical auxiliaries for C120, DPN, DPN Vigi, I-NA devices 93
Protection Electrical auxiliaries for C120, Protection Electrical auxiliaries for C120,
Circuit protection Circuit protection
Earth leakage protection DPN, DPN Vigi, I-NA devices Earth leakage protection DPN, DPN Vigi, I-NA devices
(cont.) (cont.)
Tripping Indication
Auxiliaries MN MNs MNx MSU MX MX+OF OF SD OF/SD+OF
Type Undervoltage release Voltage threshold release Shunt release Open/closed auxiliary Fault indicating contact Double open/closed or
contact fault indicating contact
Instantaneous Delayed Independent of the supply With open/closed auxiliary contact
voltage
PB100203_SE-30
PB100199_SE-30
PB100198_SE-30
PB100626_SE-30
PB100627_SE-30
PB100625_SE-30
PB100205_SE-30
PB100202_SE-30
PB100206_SE-30
Function
b Causes the device with which it is associated to trip when its input voltage decreases b Cuts off the power supply by b Trips the associated device when it is powered on. b Changeover contact b Changeover contact b The OF/SD+OF auxiliary
(between 70 % and 35 % of Un). Prevents the device from closing until its input voltage has been opening the device with which it is indicating the "open" or indicating the position of the is a two-in-one product:
restored. associated when the phase/neutral "closed" position of the associated device in the event choice of OF + SD or OF +
voltage is exceeded (loss of associated device. of: OF contact via the selector
neutral). For a four-phase network, v electrical fault switch.
use three MSU tripping auxiliaries. v action on the tripping
auxiliary.
b Same indication function as
VISI-TRIP.
b No tripping in b Separate input and power b Tripping volt.: b Tripping volt.: b Includes an open/closed contact
the event of supply 275 V AC 255 V AC (OF contact) to indicate the "open"
transient voltage or "closed" position of the
dips (up to 0.2 s) associated device.
Wiring diagrams
DB118804
DB118805
DB118806
DB123012
DB118808
DB118810
DB118811
DB118812
DB118813
U>
OF position SD position
Utilization
b Emergency stop via a normally-closed pushbutton. b Fail-safe emergency stop. b Protection of the devices against b Emergency stop via a b Emergency stop via a b Remote indication of the b Remote fault tripping b Remote position and/or
b Ensures the safety of the power supply circuits of several b Insensitive to the variation in overvoltages on the electrical normally-open pushbutton. normally-open pushbutton. position of the associated indication of the associated fault tripping indication of the
machines by preventing accidental startups. the control circuit voltage to network (break in the neutral b Remote indication of the device. device . associated device.
improve continuity of service. conductor). position of the associated device.
b Monitoring the voltage between
the phase conductor and the
neutral conductor.
Catalogue numbers 26960 26961 26959 26963 26969 26971 26979 26479 26476 26477 26478 26946 26947 26948 26924 26927 26929
Technical specifications
Rated voltage V AC 220…240 48 115 220…240 230 400 230 230 100…415 48 12…24 100…415 48 12…24 240…415 240…415 240…415
(Ue) V DC – 48 – – – 110…130 48 12…24 110…130 48 12…24 24…130 24…130 24…130
Operating Hz 50/60 400 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60
frequency
Mechanical state indicator On front face On front face On front face On front face On front face On front face _ On front face On front face
light, red
Test function – – – – – – On front face On front face On front face
Width in 9 mm modules 2 2 2 2 2 2 1 1 1
Operating current – – – – – 3 A / 415 V AC 3 A /415 V
6 A / y 240 V AC 6 A / y 240 V AC
Number of contacts – – – – – 1 NO/NF 1 NO/NF 1 NO/NF 1 NO/NF + 1 NO/NF
Operating °C -25…+50 -25…+50 -25…+50 -25…+50 -25…+50 -25…+50 -25…+50 -25…+50 -25…+50
temperature
Storage °C -40…+85 -40…+85 -40…+85 -40…+85 -40…+85 -40…+85 -40…+85 -40…+85 -40…+85
temperature
94 Electrical auxiliaries for C120, DPN, DPN Vigi, I-NA devices Electrical auxiliaries for C120, DPN, DPN Vigi, I-NA devices 95
Protection Accessories for C120 devices Protection Accessories for C120 devices
Circuit protection Circuit protection
Earth leakage protection Earth leakage protection (cont.)
Installation Safety
Accessories Rotary handle Plug-in base Padlocking device Accessories Screw shield Terminal shield Interpole barrier Spacer
Function Function
Front or side control of 2, 3 and 4-pole circuit Allows a circuit breaker or switch to be quickly Used to padlock a circuit breaker or Prevents all contact with the fixing screws Prevents all contact with the terminals Improves the b Used to:
breakers removed or replaced, without touching the a switch in the "open" or "closed" b The degree of protection becomes IP40. b Degree of protection IP40 insulation between the v complete the rows
b Degree of protection: IP 40, IK 10 connections position b Sealable. b Sealable, max. diameter 1.2 mm connections: cables, v separate the devices
b Installation: b Degree of protection: IP20 b Diameter of the padlock: 8 mm b Dividable. terminals, lugs, etc. b Width: 1 x 9 mm
v the circuit-breaker operating sub-assembly cat. b It consists of: max. module.
no. 27046 is fixed to the circuit breaker v a base to be fixed to a rail (or panel) b Locking in the ON position does not b Allows cables to be
v the removable handle cat. no. 27047 is mounted v 2 “blades” to be fixed in the device terminals prevent the circuit breaker or switch routed from one row to
on the removable front panel or on the enclosure b Connection: tunnel terminals for cables up to from tripping in the event of a fault another (above and
door 50 mm² (rigid) or 35 mm² (flexible) b Isolation: in conformity below), up to 6 mm².
v the fixed handle cat. no. 27048 is fixed to the b Installation: with IEC/EN 60947-2.
front or side panel of the enclosure v in a universal enclosure
b A complete rotary handle consists of: v on a horizontal rail
v a circuit-breaker operating sub-assembly, cat. b Centreline between two rows: 200 mm
no. 27046, b Only on the circuit breaker, without a Vigi device
v a handle cat. no. 27047 or a handle cat. no. or auxiliary
27048 b Padlocking option (8 mm dia. padlock not
supplied)
Catalogue 27047 27048 27046 26996 27145 Catalogue 18527 15826 27001 27062
numbers Removable Fixed Operating (1 per pole) numbers
extended handle sub-assembly (1)
handle
Set of 1 1 1 1 1 Set of 2 (4P dividable) 2 (for upstream and downstream 10 1
terminal)
Suitable for the following devices: Suitable for the following devices:
C120 b 2P, 3P, 4P b b C120 – b b b
C120 + Vigi C120 b 2P, 3P, 4P - b Vigi C120 – – – b
Connection Identification
Accessories Multi-cable terminal 50 mm² Al terminal Screw-on connection for Accessories Clip-on terminal marker strip Label holder
ring terminal
DB118786
DB118780
DB118782
DB118784
056367_SE-30
056367_SE-30
057084N_SE-30
056368_SE-35
056368_SE-30
v MXV: shunt release for Vigi add-on residual current device.
b The OF+ SD/OF auxiliary is a two-in-one
product: a mechanical selector switch allows a
choice between two contacts, OF+SD or OF+OF.
IEC/EN 60947-5-1
b Indication contacts:
v OF+OF: open/closed contact
v OF+SD: fault indicating contact
v OF+ SD/OF: choice of open/closed contact and OF or SD contact via the selector
switch
v MX+OF: shunt release with open/closed contact Function
v SDV: fault indicating contact for Vigi add-on residual current device. b Causes tripping of the device with which it is combined when its input voltage b Causes tripping of the associated device
decreases (between 70% and 35% of Un). Prevents closing of the device until its input when powered
voltage has been restored
b No tripping in b Separate input and power b Includes an open/closed contact (OF) to
DB123424
DB123415
DB123415
DB123416
DB123417
DB123418
U< U< U< U>
D1 D2 D1 D2 E1 E2 N L 14 12 C2 C1
Utilization
b Emergency stop by b Allows a time b Fail-safe emergency stop b Provided with a self-interrupting contact
normally-closed pushbutton delay of 0.5 s upon b Insensitive to variations in the
b Ensures safety of the power brownout or control circuit voltage for improved
supply circuits for several voltage dip continuity of service
machines by preventing
untimely restarting
Catalogue numbers 19067 19069 19070 19068 19061 19062 19064 19065 19066 19063
Technical specifications
Combination table Rated voltage (Ue) V AC 230…240 48 – 230…240 220…240 380…415 230…415 48…130 24 12
Electrical auxiliaries Device V DC – – 48 – – – 110…130 48 24 12
Indication auxiliaries Tripping auxiliaries Operating Hz 50/60 50/60 50/60 50/60
frequency
Max. quantity
056902N_SE-30
Mechanical state indicator On front face On front face On front face On front face
2 (OF+OF or OF+SD) + + 1 (MX+OF or MN or MNx) light, red
Width in 9 mm modules 2 4 4 2
Current rating – – – u 240 V AC 3A
< 240 V AC 6A
130 V CC 1A
y 48 V CC 2A
y 24 V CC 6A
NG125 Number of contacts – – – –
Operating °C -25…+60 -25…+60 -25…+60 -25…+60
temperature
Storage °C -40…+85 -40…+85 -40…+85 -40…+85
Connection temperature
DB123411
DB123412
DB123011
PZ1
10 mm
Indication 1 N.m 0.5 to 2.5 mm2 0.5 to 1.5 mm2 2 x 2.5 mm2 2 x 1.5 mm2
contacts
Tripping auxiliaries 1 N.m 0.5 to 2.5 mm2 0.5 to 1.5 mm2 2 x 2.5 mm2 2 x 1.5 mm2
98 Electrical auxiliaries for NG125 devices Electrical auxiliaries for NG125 devices 99
Protection Electrical auxiliaries for NG125 Protection Electrical auxiliaries for NG125
Circuit protection Circuit protection
devices and for Vigi NG125 add-on devices and for Vigi NG125 add-on
residual current devices (cont.) residual current devices (cont.)
Signalisation Indication
Auxiliaries OF+OF OF+SD OF+ SD/OF Auxiliaries MXV SDV
Type Auxiliary contact Fault indicating Switchable auxiliary contact Type Shunt release Vigi fault indicating contact
contact
054647_90250E_SE-35
054648_90250E_SE-35
056368_SE-30
056368_SE-30
Function
Function b At power up, actuates tripping of a circuit breaker b Normally-closed or normally-open contact indicating tripping upon an
b Double changeover contact b Double changeover b The OF+ SD/OF auxiliary is a two-in-one product: choice of or residual current circuit breaker earth fault (including tripped by MXV)
indicating "open" or "closed" position of contact indicating: OF + SD or OF + OF contact via the selector switch b It is provided with a self-interrupting contact
the associated device v the position of the Wiring diagrams
associated device in the
DB123423
DB123422
event of:
- electrical fault
DB123414
- actuation of the tripping U>
auxiliary
v the "open" or "closed"
M1 M2 11 12 13 14
position of the associated
device Utilization
Wiring diagrams b Adaptable to 125 A Vigi add-on residual current device, all types, and to 63 A Vigi add-on residual current device, adjustable
12 11 14 11 12 14 11 12 14 11 12 14 b Impulse withstand voltage: 6 kV
DB123419
DB123420
DB123421
b High-impedance input: use an iACTp if the
OF OF OF leakage current in the control unit exceeds 1 mA
SD OF OF (e.g. illuminated pushbutton)
SD SD Catalogue numbers 19060 19058 19059
21 22 24 95 98 96 21 22 24 21 22 24 Suitable for the following devices:
95 98 96 95 98 96 NG125 – –
OF position SD position Vigi NG125 b b
Utilization
b Remote indication of the position of b Remote indication of b Remote indication of position and/or tripping upon a fault of Technical specifications
the associated device tripping upon a fault of the the associated device Rated voltage (Ue) V AC 110…240 250
associated device
V DC 110 –
Catalogue numbers 19071 19072 19073
Operating Hz 50/60 50/60
frequency
Technical specifications
Number of contacts – 1 NO 1 NC
Rated voltage (Ue) V AC 220…240 220…240 240
Current rating – 0.1 to 1 A (AC14)
V DC – – –
Operating °C -25…+60 -25…+60
Operating Hz 50/60 50/60 50/60 temperature
frequency Storage °C -40…+85 -40…+85
Mechanical state indicator – – – temperature
light, red
Width in 9 mm modules 1 1 1
Current rating 240 V AC 6A 240 V AC 6A 240 V AC 6A
415 V AC 3A 415 V AC 3A 415 V AC 3A
Number of contacts 2 NO/NC 2 NO/NC 1 NO/NC + 1NO/NC
Operating °C -25…+60 -25…+60 -25…+60
temperature
Storage °C -40…+85 -40…+85 -40…+85
temperature
100 Electrical auxiliaries for NG125 devices Electrical auxiliaries for NG125 devices 101
Protection Accessories and auxiliaries for Protection Accessories for NG125 devices
Circuit protection Circuit protection
Earth leakage protection NG125 devices Earth leakage protection
Connection Mounting
DB123425
6 Comb busbar see page 168 Accessories Rotary handle Toggle Padlocking device
7 Splitter blocks Distribloc see page 174
125 A
DB123603
DB123604
DB123498
DB123605
8 70 mm2 Al terminal 19095
9 Multi-cable terminal 4 parts 19091
3 parts 19096
10 Screw-on 125 A (pack of 4) 19093
connection for ring
11 Small ring terminal (pack of 4) 19094
6 7 8 9 10 11 Function
Mounting accessories Extended rotary handle Direct rotary handle White toggle Allows padlocking:
12 Sealable terminal shield 1P 19080 b Degree of protection: rotary button b Front installation b Allows visual b In position I or O of NG125 1P or 2P
(upstream/downstream) IP55 b Keeps disconnection distinction of a circuit breakers
2P 19081 b Front installation: b Padlocking possible when the switchboard incoming b In position I of NG125 3P or 4P
3P 19082 b Prevents door opening when the circuit device is in position O device circuit breakers or switches
breaker is in position O b Padlock diameter: 3 to 6 mm b Padlock: dia. 5 to 8 mm
4P 19083
b Keeps disconnection (not supplied)
13 Residual current 63 A 2P 19074 b Padlocking possible when the device is
device terminal 3P 19075 in position O Note: NG125 3P/4P circuit breakers
shield (upstream of b Padlock diameter: 3 to 6 mm and switches are provided with
circuit breaker / 3P adjustable 19077 padlocking in position O
downstream of Vigi 4P 19076 (disconnected) as original equipment.
device) b Two versions:
4P adjustable 19078
v standard black
125 A 3P 19077 v red handle and yellow front
4P 19078 plate for machine tool control
12 13 14
14 Circuit breaker screw shield 1P (pack of 10) 19084 Catalogue 19088 19089 19092 19097 19099 19090
numbers Extended Extended safety Direct Direct safety White toggle
2P 19085 standard black standard red handle yellow
3P 19086 black background
4P 19087 Pack of 1 1 1 10 1
15 Rotary handle Suitable for the following devices:
Extended standard Black 19088 NG125 b 3P, 4P b b 3P, 4P b
Extended safety Red handle, yellow 19089 Vigi NG125 – – – –
Direct standard Black 19092
Direct safety Red handle, 19097
yellow background
16 Padlocking device (pack of 10) 19090 Connection
17 White toggle (pack of 10) 19099 Accessories Multi-cable terminal 70 mm2 Al terminal Screw-on connection for ring Small ring terminal
terminal
DB118780
DB123426
DB123427
DB123428
Electrical auxiliaries
15 16 17
Indication
3 Fault indicating auxiliary contact OF+SD 19071
Open/closed auxiliary contact OF+OF 19072 Function
Auxiliary contact OF+SD/OF 19073 For 3 copper cables: For aluminium cables from Installation: Connection ratings 80 to 125 A:
(OF+SD or OF+OF combination) b Rigid up to 16 mm2 25 to 70 mm2 b Upstream or downstream b Flexible copper cable: 50 mm2
b Flexible up to 10 mm2 b Connection ratings 80 to 125 A: b Rigid copper cable: 70 mm2
v copper terminal:
Tripping devices - flexible cable up to 35 mm2
- rigid cable up to 50 mm2
2 Undervoltage release MN or see page 98 NG125 Vigi NG125 v bars: 16 x 3 mm, 15 x 4 mm, 16 x 4 mm
delayed undervoltage release v small ring terminal
MNs or undervoltage release b Phase-to-phase insulation voltage: Ui = 1000 V
with external power supply
DB118787
DB118789
DB123497
DB122935
MNx
Shunt release MX+OF see page 98 6 mm
6 mm
l: 19 mm max.
102 Accessories and auxiliaries for NG125 devices Accessories and auxiliaries for NG125 devices 103
Protection Accessories for NG125 devices Control iCT contactors
Circuit protection Remote control
Earth leakage protection (cont.)
DB123399
DB116619
DB106604
Accessories Screw shield Circuit breaker terminal RCD terminal shield
iCT contactors are available in two versions:
shield b Contactors without manually-operated
Country approval pictograms
b Contactors with manually-operated.
DB123606
DB123607
DB123607
The breadth of the iCT contactor range satisfies most application cases.
iCT contactors can be combined with auxiliary control, protection and indication functions.
Contactors
iCT 2P
PB106120-34
PB106124-34
PB106123-34
PB106115-35
Function
b Prevents any contact with the b Prevents any contact with the b Installation: is mounted upstream of the circuit breaker and
connection screws terminals downstream of the Vigi device
b Protection against direct contact: b Installation: mounted upstream b Phase-to-phase insulation voltage Ui = 1000 V
v IP40: on front panel and downstream of circuit breaker b Protection against direct contact: IP40
v IP20: at the connection level b Phase-to-phase insulation voltage b Class II in steel or plastic enclosures (up to 440 V)
b Class II in steel or plastic Ui = 1000 V b Sealing possible (max. diameter: 1.2 mm)
enclosures b Protection against direct contact
b Sealing possible IP40
(max. diameter: 1.2 mm). b Class II in steel or plastic
enclosures (up to 440 V)
b Sealing possible
(max. diameter: 1.2 mm) manual control
Indication Interference Dual control
63 A 125 A iACTs filtering iACTc
1P 2P 3P 4P 1P 2P 3P 4P 2P 3P 3P 4P 4P 3P 4P
iCT 4P b This auxiliary allows iACTp b Used to control a
PB106105-35
adjustable adjustable indication or control of the b This auxiliary is an contactor in impulse-type
"open" or "closed" interference suppressor mode or to combine
Catalogue 19084 19085 19086 19087 19080 19081 19082 19083 19074 19075 19077 19076 19078 19077 19078 position of the contactor which limits overvoltages latched or impulse-type
numbers power contacts control orders
on the control circuit
PB106125-34
NG125 b b b b b This auxiliary is used to time delay for iCT and iTL.
Vigi NG125 – – b b According to cabling, there are 5 possible time delay types:
v 1 for iTL
b iCT contactors can be used v 4 for iCT
to remote control applications
Function type A: Function type C:
in alternative networks: late closing late opening
v lighting, heating, Delay energizing of contactor b Energize the contactor by closing a
ventilation, roller blinds, Function type B: push button
sanitary hot water time delay b The time delay starts when the
v mechanical ventilation b Energize the contactor by closing control contacts are opened
systems, etc a push button Function type H:
b The time delay starts as soon as fixed time operation
v load-shedding of
the control contacts are closed b Operate the contactor for a
non-priority circuits pre-determined time from the moment
of energizing
104 Accessories and auxiliaries for NG125 devices iCT contactors 105
Control iCT contactors (cont.) Control iCT contactors (cont.)
Remote control Remote control
DB106317-24
A1 1 3
DB106318-27
A1 1 R1
DB106586-27
A1 R1 R3
24 1NO+1NC A9C22115 2 A9C21862
I P
220...240 2NO 4
220 1NO+1NC A9C22515 2 auto
230...240 1NO+1NC A9C22715 2 O
R2 R4
20 A 6A 230...240 2NO A9C22722 2 A2
A1 1 3
3P
48 2NO A9C20232 2
25 A 8.5 A 220...240 3NO A9C21833 4
DB106319-27
A1 1 3 5
220 2NO A9C20532 2
40 A 15 A 220...240 3NO A9C21843 6
A2 2 4 230...240 2NO A9C20732 2 I P
auto
220 2NC A9C20536 2 O
DB106320-31
A1 1 3 5 7
A1 1 3 5 A2 2 4 6 8
25 A 8.5 A 220…240 3NO A9C20833 4 24 4NC A9C21147 6
40 A 15 A 220…240 3NO A9C20843 6 220...240 4NO A9C21844 6
DB106587-36
A1 R1 R3 R5 R7
A2 2 4 6 63 A 20 A 220…240 3NO A9C20863 6
I
63 A 20 A 24 4NO A9C21164 6
P
auto 220...240 4NO A9C21864 6
4P O
16 A 6A 24 4NO A9C22114 4 A2 R2 R4 R6 R8
DB122916
1 R1 R R R
1 1 R1 R
A1 1 3 5 7
63 A 20 A 24 4NO A9C20164 6
220...240 4NO A9C20864 6
A2 2 4 6 8 24 4NC A9C20167 6
220...240 4NC A9C20867 6
220...240 2NO+2NC A9C20868 6
DB122918
1 1 R1
Automatic return to
“auto” position
DB123608
DB123309
Power circuit
6 Sealable screw shields 3P, 4P 25 A A9A15921
Voltage rating (Ue) 1P, 2P 250 V AC
for top and bottom 2P 40/63 A A9A15922
3P, 4P 400 V AC
3P, 4P 40/63 A A9A15923
Frequency 50 Hz or 60 Hz
7 9 mm spacer A9A27062
Type of load See page 240
Clip on DIN rail 35 mm. 8 Yellow clips A9C15415
Endurance (O-C)
Electrical 100,000 cycles
Maximum number of switching operation a day 100
DB123300
Additional characteristics
Auxiliaries
iCT < 25 A
Insulation voltage (Ui) 500 V AC
Pollution degree 2
Indication
Rated impulse withstand voltage (Uimp) 2.5 kV (4 kV for 12/24/48 V AC)
2 iACTs 1NO + 1NC A9C15914
Degree of protection Device only IP20
(IEC 60529) 1CO A9C15915
Device in modular IP40
± 30° vertical. enclosure 2NO A9C15916
Operating temperature -5°C to +60°C (1)
Double control inputs
Storage temperature -40°C to +70°C 3 iACTc 230 V AC A9C18308
IP20 IP40 24 V AC A9C18309
DB123311
PB106124-34
PB106123-34
PB106125-34
Function
b This auxiliary allows indication of the "open" b This auxiliary is an interference b This auxiliary, combined with contactors, b This auxiliary is used to time delay for iCT and iTL. According to cabling, there are 5 possible time delay types:
or "closed" position of the contactor power contacts suppressor which limits overvoltages enables them to be controlled by v 1 for iTL
on the control circuit 2 order types: v 4 for iCT.
v impulse order for local control (input T) Function type A: late closing Function type B: time delay Function type C: late opening Function type H: fixed time operation
v latched order for centralised control b Delay energizing of contactor. b Energize the contactor by closing b Energize the contactor by closing b Operate the contactor for
(input X) a push button. a push button. a pre-determined time from the moment
v the last order received takes priority b The time delay starts as soon as the b The time delay starts when the of energizing.
control contacts are closed. control contacts are opened.
Wiring diagrams
DB123321
DB123322
DB123323
DB123324
DB123317
DB123318
DB123319
DB123316
DB123315
14 22 11 14 24 3 1 T
11 21 12 14 11 21 4 2 X
U U U U
1 1 1 1
0 0 0 0
A1 1 A1 1 A1 1 A1 1
iCT iCT iCT iCT
A2 0 t A2 0 t A2 0 t A2 0 t
T T T T
Mounting
b Mounted to the right of iCT b Mounted to the left of iCT b Mounted to the left of iCT b Mounted to the left of iCT by yellow clips (1)
by yellow clips (1) by yellow clips (1)
b By wires
Use
– b The iACTp has 2 separate and
b Mains power outages: _
identical circuits, allowing it to be
v < 1 s: keeps its initial status
combined with 2 different one on the
v u 5 s: reset
iCT the other by wires v put back into operation by manual
operation on input X or T.
b Minimum impulse duration: 250 ms
Catalogue numbers A9C15914 A9C15915 A9C15916 A9C15918 A9C15919 A9C15920 A9C18308 A9C18309 A9C15419
Technical specifications
Control voltage V AC 24…240 48 …127 12 …48 220 …240 230…240 24…48 24…240
(Ue)
V DC 24…130 – – 24…110
Operating Hz 50/60 50/60 50/60 50/60
frequency
Width in 9 mm modules 1 2 2 2
Auxiliary contact b Mininimum: 10 mA at 24 V DC/AC - cos φ = 1 – – –
(breaking capacity) b Maximum:
v 5 A at 240 V AC - cos φ = 1
v 1 A at 130 V DC
Number of contacts 1NO + 1NC 1CO 2NO – – –
Operating °C -5°C to +50°C -20°C to +50°C
temperature
Storage °C -40°C to +70°C -40°C to +80°C
temperature
Consumption – – OFF load: 3 VA Off-load: 5 VA
Inrush (2): 2 VA Inrush (2): 3 A
Holding (2): 0.2 VA Holding (2): 0.2 A
(1) Electrical and mechanical link.
(2) Maximum consumption of all contactors controlled.
Security Consumption
Accessories Sealable screw shields Yellow clips Spacer iCT contactors - 50 Hz
Type
PB104485-15
PB104486-15
PB104487-15
PB106143-10
PB104483-40
1P Rating (In) Control voltage Consumption Max.
(V AC) (50 Hz) power
AC7a AC7b Holding Inrush
24 3.8 VA 15 VA 1.3 W A9C22111
220 3.8 VA 15 VA 1.3 W A9C22511
230…240 2.7 VA 9.2 VA 1.2 W A9C22711
25 A 8.5 A 220 3.8 VA 15 VA 1.3 W A9C20531
230…240 2.7 VA 9.2 VA 1.2 W A9C20731
2P
24 3.8 VA 15 VA 1.3 W A9C22112
220 3.8 VA 15 VA 1.3 W A9C22512
Function 230...240 2.7 VA 9.2 VA 1.2 W A9C22712
b Designed to cover terminals to avoid contact with device screws. b Ensure the mechanical b Required to reduce temperature 24 3.8 VA 15 VA 1.3 W A9C22115
b Allow sealing and/or electrical link rise of modular devices installed side 220 3.8 VA 15 VA 1.3 W A9C22515
between contactors and by side.
b For iCT: b For iCT: b For iCT: 230...240 2.7 VA 9.2 VA 1.2 W A9C22715
their auxiliaries. b Recommended to separate
3P, 4P - 25 A 2P - 40/63 A 3P, 4P - 40/63 A
electronic devices (thermostat, 20 A 6.4 A 230...240 2.7 VA 9.2 VA 1.2 W A9C22722
programmable clock, etc.) from 25 A 8.5 A 24 3.8 VA 15 VA 1.3 W A9C20132
electromechanical devices (relays,
contactors). 220 3.8 VA 15 VA 1.3 W A9C20532
Use 230...240 2.7 VA 9.2 VA 1.2 W A9C20732
b Bag of 10 upstream/10 downstream b Bag of 10 b Bag of 5 220 3.8 VA 15 VA 1.3 W A9C20536
Catalogue numbers A9A15921 A9A15922 A9A15923 A9C15415 A9A27062 230...240 2.7 VA 9.2 VA 1.2 W A9C20736
40 A 15 A 220...240 4.6 VA 34 VA 1.6 W A9C20842
Technical specifications 63 A 20 A 24 4.6 VA 34 VA 1.6 W A9C20162
Width in 9 mm modules 4 4 6 – 1 220...240 4.6 VA 34 VA 1.6 W A9C20862
Number of poles 3P, 4P 2P 3P – – 100 A - 220...240 6.5 VA 53 VA 2.1 W A9C20882
3P
16 A 5A 220…240 4.6 VA 34 VA 1.6 W A9C22813
25 A 8.5 A 220…240 4.6 VA 34 VA 1.6 W A9C20833
40 A 15 A 220…240 6.5 VA 53 VA 2.1 W A9C20843
63 A 20 A 220…240 6.5 VA 53 VA 2.1 W A9C20863
4P
16 A 5A 24 4.6 VA 34 VA 1.6 W A9C22114
220...240 4.6 VA 34 VA 1.6 W A9C22814
220...240 4.6 VA 34 VA 1.6 W A9C22818
20 A 6.4 A 220 ...240 4.6 VA 34 VA 1.6 W A9C22824
25 A 8.5 A 24 4.6 VA 34 VA 1.6 W A9C20134
220...240 4.6 VA 34 VA 1.6 W A9C20834
24 4.6 VA 34 VA 1.6 W A9C20137
220...240 4.6 VA 34 VA 1.6 W A9C20837
220...240 4.6 VA 34 VA 1.6 W A9C20838
40 A 15 A 220...240 6.5 VA 53 VA 2.1 W A9C20844
220...240 6.5 VA 53 VA 2.1 W A9C20847
63 A 20 A 24 6.5 VA 53 VA 2.1 W A9C20164
220...240 6.5 VA 53 VA 2.1 W A9C20864
24 6.5 VA 53 VA 2.1 W A9C20167
220...240 6.5 VA 53 VA 2.1 W A9C20867
220...240 6.5 VA 53 VA 2.1 W A9C20868
220...240 6.5 VA 53 VA 2.1 W A9C20869
100 A - 220...240 13 VA 106 VA 4.2 W A9C20884
DB123376
DB123609
49
Type 49
5.5 23.5
18 36 5.5 23.5 36 54
2P Rating (In) Control voltage Consumption Max.
(V AC) (50 Hz) power
AC7a AC7b Holding Inrush
16 A 5A 220 2.7 VA 9.2 VA 1.2 W A9C23512 85
81 45 45
230...240 2.7 VA 9.2 VA 1.2 W A9C23712
220 3.8 VA 15 VA 1.3 W A9C23515
230...240 2.7 VA 9.2 VA 1.2 W A9C23715
25 A 8.5 A 24 3.8 VA 15 VA 1.3 W A9C21132 2.5
2.5
24 3.8 VA 15 VA 1.3 W A9C21136
iCT 16/25 A iCT 40/63 A
220 2.7 VA 9.2 VA 1.2 W A9C21532
230...240 2.7 VA 9.2 VA 1.2 W A9C21732
40 A 15 A 24 4.6 VA 34 VA 1.6 W A9C21142 68
DB123610
220...240 4.6 VA 34 VA 1.6 W A9C21842 49
54 108 5.5 23.5
63 A 20 A 24 4.6 VA 34 VA 1.6 W A9C21162
220...240 4.6 VA 34 VA 1.6 W A9C21862
3P
85
25 A 8.5 A 220...240 4.6 VA 34 VA 1.6 W A9C21833 45
DB123381
DB123382
6
220...240 6.5 VA 53 VA 2.1 W A9C21844 68
49
63 A 20 A 24 6.5 VA 53 VA 2.1 W A9C21164 18 36 5.5 23.5
36 3
81 45
iCT contactors - 60 Hz
Type
2.5
1P Rating (In) Control voltage Consumption Max.
(V AC) (60 Hz) power iCT manual control contactor 16/25 A iCT manual control contactor 40/63 A
AC7a AC7b Holding Inrush
220 ...240 2.7 VA 9.2 VA 0.9 W A9C20631
2P 68 60
DB123379
DB123380
49 44
220...240 2.7 VA 9.2 VA 0.9 W A9C22615 9 5.5 23.5 18 5
220...240 2.7 VA 9.2 VA 0.9 W A9C20632
220...240 2.7 VA 9.2 VA 0.9 W A9C20636
220...240 4.6 VA 34 VA 1.6 W A9C20642
81 45 81 45
3P
220...240 4.6 VA 34 VA 1.6 W A9C20633
220...240 6.5 VA 53 VA 2.1 W A9C20643
220...240 6.5 VA 53 VA 2.1 W A9C20663 iACTs iATEt
iACTp
iACTc
DB116619
PB106131-34
PB106134-34
iTL 2P 16 A and iTL 4P 16 A
PB106126-34
PB106128-34
b The impulse relays are used to control, b This impulse relay has a b Used to increase the number of impulse relay poles
relays by means of pushbuttons, lighting circuits changeover contact b Can be installed on the iTL, iTLi, iTLc,
consisting of: iTLm and iTLs
v incandescent lamps, low-voltage halogen
lamps, etc. (resistive loads)
v fluorescent lamps, discharge lamps, etc. + =
(inductive loads)
PB106125-34
Indication Centralised control +
PB106133-34
PB106139-34
iTLs
indication
PB106140-34
b Allows remote iATLs indication iATLc+s iATEt
indication of its operating b Allows remote b Used for centralised control, thanks to b Combined with an
state (open/closed) indication of the a "pilot line", of a group of impulse relays impulse relay,
associated impulse relay controlling separate circuit, while at the it automatically
same time maintaining local individual disconnects the circuit
control of each impulse relay after a preset time
b Remote indication of the mechanical
status of each relay
Control iATLz
PB106141-34
b Must be used when
installing several
Centralised iTLc Centralised control Multi-level centralised illuminated PBs in parallel
PB106130-34
PB106136-34
PB106137-34
PB106142-63
Step by step
control iATL4
b Allows step-by-step
control of two circuits via
a single pushbutton
Latched iTLm Latched control
PB106132-34
PB106138-34
Mounting accessories
PB106126-41
DB123631
Yellow clip
b A simple clip-on system
10 Yellow clips A9C15415 b Insulated terminals IP20
for flexible auxiliaries
11 9 mm spacer A9A27062 combination and improved
12 Clip-on terminal markers robustness
b For electrical and
mechanical connections
Auxiliaries
b Manual controls on front face: direct
Centralised control iTL (1P - 2P) and priority manual control by O-l toggle
2 iATLc (1), (3) 24...240 V AC A9C15404 b Mechanical contact position indicator
Indication
3 iATLs (1) 24...240 V AC A9C15405
DB123625
DB123626 + DB123630
DB123627
DB123617
DB123618
+ 5 9
1 NO 2 NO 1 NO + 1NO/NC + 1NO 4 NO
Rating (In) Control voltage (Uc) 6 8 10
(V AC) (V DC)
16 A 12 6 A9C30011 A9C30012 A9C30011 + A9C32016 A9C30012 + A9C32016
24 12 A9C30111 A9C30112 A9C30111 + A9C32116 A9C30114
48 24 A9C30211 A9C30212 A9C30211 + A9C32216 A9C30212 + A9C32216
1NO 3P
130 48 A9C30311 A9C30312 A9C30311 + A9C32316 A9C30312 + A9C32316
230...240 110 A9C30811 A9C30812 A9C30811 + A9C32816 A9C30814 Rating (In) Control voltage (Uc)
32 A 230...240 110 A9C30831 A9C30831 + A9C32836 A9C30831 + 2 x A9C32836 A9C30831 + 3 x A9C32836 (V AC)
Width in 9 mm modules 2 2 4 4 16 A 24 A9C33111 A9C33111 + A9C32116
48 A9C33211 A9C33211 + A9C32216
230...240 A9C33811 A9C33811 + A9C32816
Width in 9 mm modules 2 4
iTLI impulse relays
Type 1P
DB123628
DB123619
DB123620
1NO + 1NC
Rating (In) Control voltage (Uc)
(V AC) (V DC) 5 9
16 A 12 6 A9C30015
24 12 A9C30115 6 8 10
48 24 A9C30215
130 48 A9C30315
230...240 110 A9C30815
Width in 9 mm modules 2
1NO 3P
Rating (In) Control voltage (Uc)
(V AC)
iETL extensions for iTL and iTLI 16 A 230...240 A9C34811 A9C34811 + A9C32116
Type Width in 9 mm Width in 9 mm modules 2 4
modules
1P Rating (In) Control voltage (Uc)
(V AC) (V DC) iTLs impulse relay with remote indication
32 A 230...240 110 A9C32836 2
DB123629
Type 1P 3P
DB123621
DB123622
1NO
5 9
2P
16 A 12 6 A9C32016 2
DB123630
6 8 10
24 12 A9C32116 2
48 24 A9C32216 2
130 48 A9C32316 2
1NO/NC + 1NO
230...240 110 A9C32816 2
1NO 3P
Rating (In) Control voltage (Uc)
(V AC) (V DC)
16 A 24 12 A9C32111 A9C32111 + A9C32116
48 24 A9C32211 A9C32211 + A9C32216
230...240 110 A9C32811 A9C32811 + A9C32816
Width in 9 mm modules 2 4
120 Impulse relays auxiliaries iTLc , iTLm, iTLs with built-in auxiliary function 121
Remote control iTL impulse relays Remote control iTL impulse relays (cont.)
DB123309
Control circuit
Switch set to auto Switch set to OFF
iTL and iTLI 16 A iTL 32 A,
DB123623
iTLc, iTLm, iTLs, iETL 32 A
iETL 16 A
Dissipated power (during the impulse) 1, 2, 3P: 19 VA 19 VA
Clip on DIN rail 35 mm. 4P: 38 VA
Illuminated PB control Max. current 3 mA (if > use an ATLz)
Operating threshold Min. 85 % of Un in conformance with
EN/IEC 60669-2-2
Duration of the control order 50 ms to 1 s (200 ms recommended)
Response time 50 ms
DB123311
Power circuit
Voltage rating (Ue) 1P, 2P 24 ...250 V AC
3P, 4P 24....415 V AC
Frequency 50 Hz or 60 Hz
Maximum number of operations per minute 5
Maximum number of switching operation a day 100
Indifferent position of installation.
Additional characteristics to IEC/EN 60947-3
Insulation voltage (Ui) 440 V AC
Pollution degree 3
Rated impulse withstand voltage (Uimp) 6 kV
Endurance (O-C)
IP20 IP40
DB123313
Electrical to IEC/EN 60947-3 200,000 cycles (AC21) 50,000 cycles (AC21)
100,000 cycles (AC22) 20,000 cycles (AC22)
Overvoltage category IV
Connection
Other characteristics
Type Rating Circuit Tightening Copper cables
DB123132
DB123553
3.5 mm enclosure
PZ1 Operating temperature -20°C to +50°C
Storage temperature -40°C to +70°C
iTL, iTLi, iTLc, 16 A Control 1 N.m 0.5 to 4 mm2 1 to 4 mm2 Tropicalization (IEC 60068-1) Treatment 2 (relative humidity 95 % at 55°C)
iTLm, iTLs, iETL Power 1.5 to 4 mm2 1.5 to 4 mm2
iTL, iETL 32 A Control 0.5 to 4 mm2 1 to 4 mm2
Power 1.2 N.m 1.5 to 10 mm2 1.5 to 10 mm2
Auxiliaries 1 N.m 0.5 to 4 mm2 1 to 4 mm2
122 iTLc , iTLm, iTLs with built-in auxiliary function iTLc , iTLm, iTLs with built-in auxiliary function 123
Remote control iTL impulse relays Remote control iTL impulse relays
Electrical auxiliaries Electrical auxiliaries
for iTL impulse relays for iTL impulse relays (cont.)
PB106137-34
PB106140-34
PB106136-34
PB106138-34
PB106125-34
PB106142-63
PB106141-34
Function
b Allows remote indication of b Used for centralised control, thanks to a "pilot line", of a b Used to control the centralised b Combined with an impulse relay, b Combined with an impulse relay, b Allows the step by step sequence b Used to control impulse relays
the associated impulse relay group of impulse relays controlling separate networks, controls of a number of impulse it operates on latched orders it automatically disconnects the over 2 circuits by illuminated push-buttons,
while at the same time maintaining local individual control of relay groups, while at the same time circuit after a preset time without operating risks
each impulse relay maintaining local individual control
b And for remote indication and centralised control by level
of the mechanical status of
each relay
Wiring diagrams
DB123230
DB123233
DB123232
DB123231
DB123235
DB123234
DB123237
DB123552
iTL1 iTL2
– – – b Each group, made up of iTLc or – b 5 time setting ranges: b The cycle is as follows: b Provide an iATLz when the
(iTL or iTLl or iTLs) + iATLc+s, must v 1 to 10 s v 1st impulse - iTL 1 closed, iTL 2 open current drawn up by the illuminated
only contain a single iATLc+c v 6 to 60 s v 2nd impulse - iTL 1 open, iTL 2 closed push-buttons is higher than 3 mA
b Maximum number of impulse relays v 2 to 10 min v 3rd impulse - iTL 1 and 2 closed (this current is sufficient to keep
that can be controlled: v 6 to 60 min v 4th impulse - iTL 1 and 2 open the coils energised). Above this
v 230 V AC: 24 v 2 to 10 h v 5th impulse - iTL 1 closed, iTL 2 open, etc value, fit one extra iATLz per 3 mA.
v 130 V AC: 12 b For example: for 7 mA,
v 48 V AC: 5 fit 2 iATLz
Mounting
b Mounted to the right of iTL b Mounted to the right of iTL b Mounted to the right of iTL b Without mechanical link with b Mounted to the right of iTL b Mounted to the left of iTL b Assembled between 2 impulse relays: b Mounted to the left of iTL
by yellow clips by yellow clips by yellow clips impulse relays and auxiliaries by yellow clips by yellow clips according to the auxiliarisation table by yellow clips by yellow clips
Catalogue numbers A9C15405 A9C15404 A9C15409 A9C15410 A9C15414 A9C15419 A9C15412 A9C15413
Technical specifications
Control voltage V AC 24…240 24…240 24…240 24 …240 12…240 24…240 230 130…240
(Ue) V DC 24…240 – – – 6…110 24…110 – –
Width in 9 mm modules 1 1 2 2 1 2 4 2
Auxiliary contact b Mininimum: 10 mA at – b Mininimum: 10 mA at – – – – –
(breaking capacity) 24 V AC/DC 24 V AC/DC
b Maximum (IEC 60947-5-1): b Maximum (IEC 60947-5-1):
v 12…240 V AC 6A v 12…240 V AC 6A
v 12…24 V DC 6A v 12…24 V DC 6A
v 15…240 V AC 2A v 15…240 V AC 2A
v 13…24 V DC 2A v 13…24 V DC 2A
Number of contacts – – – – – – – –
Operating °C -20°C to +50°C -20°C to +50°C
temperature
Storage °C -40°C to +70°C -40°C to +70°C
temperature
124 iTLc , iTLm, iTLs with built-in auxiliary function iTLc , iTLm, iTLs with built-in auxiliary function 125
Remote control iTL impulse relays Control, remote control Reflex iC60N, iC60H
Integrated control circuit
breakers (curves B, C, D)
Available in 06/2011
DBxxxxxx
Accessories Yellow clips The Reflex iC60 devices are integrated control circuit breakers which combine the
following main functions in a single device:
PB106143-10
Country approval pictograms b Remote control by latched and/or impulse-type order according to the 3 operating
modes to be chosen by the user.
b Circuit breaker, to provide:
v circuit protection against short-circuit currents,
Function v circuit protection against overload currents,
b Ensure the mechanical and/or electrical link between contactors and their auxiliaries (set of 10). v disconnection in the industrial sector.
Catalogue numbers A9C15415
PB106239-40
Resetting after a fault is performed manually, by the resetting handle.
Technical specifications
The version with Ti24 allows direct interfacing of the Reflex iC60 with a PLC, to:
Width in 9 mm modules –
b Execute remote control (Y3).
Number of poles – b Indicate the state of the control circuit (OF) or circuit-breaker tripping (SD).
The iMDU auxiliary allows the Reflex iC60 to be controlled in 24/48 V AC/DC.
Dimensions (mm)
71 Alternating current (AC) 50 Hz
DB123375
67
Ultimate breaking capacity (Icu) as per IEC/EN 60947-2 Service
49
PB106238-40
18 36 5.5 23.5 Voltage (Ue) breaking
capacity (Ics)
Ph/Ph (2P, 3P, 4P) 220 to 240 V 380 to 415 V
Reflex iC60N
86 81 45 Rating (In) 10 to 40 A 20 kA 10 kA 75 % of Icu
Reflex iC60H
Rating (In) 10 to 40 A 30 kA 15 kA 75 % of Icu
iTL 1P iTL+iETL
iTLc iTL 4P
iTLm
iTLs
iTLi
iETL
Catalogue numbers
71
Reflex iC60 circuit breaker
DB123383
DB123380
67 69 60 Type 2P 3P 4P
49 49 44
18 36 5.5 23.5 9 5.5 23.5 18 5
Rating (In) Curve Curve Curve
B C D B C D B C D
Reflex iC60N
86 81 45 81 45 81 45 With Ti24 interface
10 A A9C61210 A9C62210 A9C63210 A9C61310 A9C62310 A9C63310 A9C61410 A9C62410 A9C63410
16 A A9C61216 A9C62216 A9C63216 A9C61316 A9C62316 A9C63316 A9C61416 A9C62416 A9C63416
25 A A9C61225 A9C62225 A9C63225 A9C61325 A9C62325 A9C63325 A9C61425 A9C62425 A9C63425
4 40 A A9C61240 A9C62240 - A9C61340 A9C62340 - A9C61440 A9C62440 -
iATLc+s iATLc iATEt Without Ti24 interface
iATLc+c iATLs
iATLz iATLm 10 A - A9C52210 - - A9C52310 - - A9C52410 -
iATL4 16 A - A9C52216 - - A9C52316 - - A9C52416 -
25 A - A9C52225 - - A9C52325 - - A9C52425 -
40 A - A9C52240 - - A9C52340 - - A9C52440 -
Reflex iC60H
With Ti24 interface
10 A A9C64210 A9C65210 A9C66210 A9C64310 A9C65310 A9C66310 A9C64410 A9C65410 A9C66410
16 A A9C64216 A9C65216 A9C66216 A9C64316 A9C65316 A9C66316 A9C64416 A9C65416 A9C66416
25 A A9C64225 A9C65225 A9C66225 A9C64325 A9C65325 A9C66325 A9C64425 A9C65425 A9C66425
40 A A9C64240 A9C65240 - A9C64340 A9C65340 - A9C64440 A9C65440 -
Width in 9 mm modules 9 11 13
Vigi iC60 Vigi iC60 add-on residual Vigi iC60 add-on residual Vigi iC60 add-on residual
current device, module CA902005 current device, module CA902005 current device, module CA902005
iMDU auxiliaries A9C18185 A9C18185 A9C18185
Accessories Module CA907001 Module CA907001 Module CA907001
126 iTLc , iTLm, iTLs with built-in auxiliary function Reflex iC60N, iC60H (curves B, C, D) 127
Control, remote control Reflex iC60N, iC60H Control, remote control Reflex iC60N, iC60H
Integrated control circuit Integrated control circuit
breakers (curves B, C, D) (cont.) breakers (curves B, C, D) (cont.)
DB123517
v disconnecting and padlocking (Ø 3 to 6 mm not supplied) in "open" position indicator lamp
v neutralizing remote control
Operating mode
Centralized
DB123569
b Ti24 interface control
for link to PLC (PLC)
b Pushbutton for:
v "mode" selection 24 V DC
v opening/closing Y3 Y3
Ti24 Ti24
manual control
Reflex iC60 Reflex iC60
PB105980_W_70
Manual
control by OF SD OF SD
b IP20 insulated terminals pushbutton
Y1/Y2 Y1/Y2
230 V 230 V
Zone 1 Zone 2
b Bistable operation:
does not change state in the Local control Local control
event of electrical power
b Operating state
outage
indicator lamp
DB123505
Mode 1: locally or centrally controlled
230 V AC
circuit-breaker opening/closing
b The orders come from various control points, and they are 24 V c
taken into account in their order of arrival 0V
Y3
b Y1: latched order local control
Positive contact indication b Y2: impulse-type local control
OF
SD
b Suitability for isolation in the industrial sector to b Y3: latched order centralized control
IEC/EN 60947-2 Ti24
RCA
b The presence of the green strip guarantees that Mode 2: locally controlled opening/closing,
the contacts open physically and allows work to be
centrally controlled closing OF
carried out safely on the downstream circuit
b Pushbutton: b The orders come from various control points.
v manual control: b Only the stoppage orders are taken into account by the
N P Y2 Y1 11 12 14
opening/closing inputs Y1, Y3
v choice of operating b Y1: latched order local closing control
b Y2: impulse-type local opening/closing control
"modes" b Y3: latched order centralized closing control
DB123598
b Longer product service life thanks to: Mode 3: centrally controlled opening/closing
v good overvoltage withstand capacity: products designed to provide a high + local override
230 V AC
industrial performance level (degree of pollution, rated impulse withstand voltage 24 c
b 3 positions allowing a choice between override and
and insulation voltage),
centralized control:
v high limitation performances (see limitation curves), b Y1: latched order local control OF
v fast closure independent of the speed of resetting of the operating handle. b Y2: latched order local control SD
b Y3: latched order centralized control 24
Legend
DB123508
Ti24 interface OF SD
0V V DC power supply
+24VDC 2 1 11 12 14 91 92 94
Y3 Remote control by latched order
Y2 Y1
SD Circuit-breaker tripping information
Stop
OF Control circuit state information (open/closed)
Override Centralized
operation control
DB123516
128 Reflex iC60N, iC60H (curves B, C, D) Reflex iC60N, iC60H (curves B, C, D) 129
Control, remote control Reflex iC60N, iC60H Control, remote control Reflex iC60N, iC60H
Integrated control circuit Integrated control circuit
breakers (curves B, C, D) (cont.) breakers (curves B, C, D) (cont.)
DB123310
Terminal Rating Tightening Copper cables Al Screw-on Multi-cable Control circuit
DB123561
torque terminal connection terminal Supply voltage (Ue) (N/P) 230 V AC, 50 Hz
14 mm 50 mm² for ring Control voltage (Uc) Inputs (Y1/Y2) 230 V AC
Rigid Flexible or Rigid Flexible
24…48 V AC/DC, with iMDU auxiliary
with ferrule terminal cables cables
Min. duration of control impulse (Y2) u250 ms
DB118787
DB122945
DB122946
DB122935
DB118789
Clip on DIN rail 35 mm. Response time (Y2) y200 ms
Consumption y1 W
Thermal self-protection with automatic Reset against overheating of the control circuit due to an
DB123312
Power 10 to 25 A 2 N.m 1 to 25 mm2 1 to 16 mm2 - Ø 5 mm - - abnormal number of operations
6.5 mm 40 A 3.5 N.m 1 to 35 mm2 1 to 25 mm2 50 mm2 3 x 16 mm2 3 x 10 mm2 Power circuit
PZ2 Max. working voltage (Ue) 400 V AC
Max. working voltage (Ue) 500 V
Rated impulse withstand voltage (Uimp) 6 kV in disconnected position
Thermal tripping Reference 50°C
Without accessories temperature
Indifferent position of installation. Magnetic tripping Curve B 4 In ± 20 %
Terminal Tightening Copper cables
DB123562
Curve C 8 In ± 20 %
torque Rigid Flexible Flexible with ferrule
Curve D 12 In ± 20 %
IP20 IP40
DB122945
DB123553
DB123554
DB123314
Overvoltage category (IEC 60364) IV
Endurance (O-C)
Electrical AC1 30,000 cycles
Power supply (N/P) 1 N.m 0.5 to 10 mm2 0.5 to 6 mm2 0.5 to 4 mm2 AC5a 6000 cycles
Inputs (Y1/Y2) 2 x 0.5 to 2 x 2.5 mm2 2 x 0.5 to 2 x 2.5 mm2 2 x 0.5 to 2 x 2.5 mm2
10 mm AC5b 6000 cycles
3.5 mm AC21 50,000 cycles
PZ1 Mechanical > 50,000 cycles
Outputs (OF/SD) 0.7 N.m 0.5 to 2.5 mm2 0.5 to 2.5 mm2 0.5 to 1.5 mm2 Indication / Remote control
DB123563
Weight (g)
Circuit breaker
Type Reflex iC60
2P 480
3P 620
4P 750
Dimensions (mm)
4P 117
DB123564
3P 99 77
2P 81 5.5 44.5
84 45
130 Reflex iC60N, iC60H (curves B, C, D) Reflex iC60N, iC60H (curves B, C, D) 131
Control iPB pushbuttons Control iSSW linear switches
Local control Local control
IEC 60669-1 and IEC 60947-5-1 IEC 60669-1 and IEC 60947-5-1
b iPB pushbuttons are used to control electric circuits by means of pulses. b iSSW linear switches are used for the manual control of electric circuits.
Catalogue numbers
iPB pushbuttons
Catalogue numbers
Type Single Double Single + indicator light
iSSW linear switches
Type 2 positions 3 positions
Diagram
Contact 1 changeover switch 2 changeover switches 1 NO + 1NC 1 changeover switch 2 changeover switches
Diagram
Pushbutton Colour Grey Red Grey Grey Green/red Grey/grey Grey Grey Grey Grey
Indicator Power - - - - - - 110…230 V AC 12…48 V AC/DC
light supply
Cat. no. A9E18070 A9E18071 A9E18072 A9E18073 A9E18074
Colour - - - - - - Green Red Green Red
Width in 9 mm modules 2 4 2 2 4
Cat. no. A9E18030 A9E18031 A9E18032 A9E18033 A9E18034 A9E18035 A9E18036 A9E18037 A9E18038 A9E18039
Width in 9 mm modules 2 2 2
Connection
Tightening Copper cables
Connection
DB123133
DB123134
Rigid Flexible or ferrule
torque Rigid Flexible or ferrule
DB122945
DB122946
4 mm
DB122945
DB122946
PZ1 4 mm
PZ1
9 mm 1 N.m 0.5 mm2 min. 0.5 mm2 min.
2 x 2.5 mm2 max. 2 x 2.5 mm2 max. 9 mm 1 N.m 0.5 mm2 min. 0.5 mm2 min.
2 x 2.5 mm2 max. 2 x 2.5 mm2 max.
b Phase-separated wall that can be divided to allow the teeth of all types of comb
busbar to pass through. b Phase-separated wall that can be divided to allow the teeth of all types of comb
b Staggered terminals to simplify connection. busbar to pass through.
b Staggered terminals to simplify connection.
Position contact indication iSW control switches (20, 32 A) Catalogue numbers (cont.)
b Suitable for industrial isolation according to
PB105264-40
IEC/EN 60669-1, iSW switch with indicator light. 20, 32 A iSW control switches with indicator light
IEC/EN 60947-3 standard.
Type Width in 9 mm modules
b The presence of the green strip guarantees IEC/EN 60669-2-4, iSW switch without indicator light.
physical opening of the contacts and allows 1P Rating 230 V indicator light
operations to be performed on the downstream These switches are used for: 20 A A9S61120 2
DB122819
1 3
circuit in complete safety. b Control (opening and closing of circuits under load). 32 A A9S61132
The 1P and 2P switches are available with or without indicator light.
PB105266-40
DB122820
1
IEC 60947-3
DB122818
32 A A9S61232
Control switches with indicator light
The switch-disconnectors combine the following functions:
b Control (opening and closing of circuits under load). 2
Operating frequency 50/60 Hz
OF iSW auxiliary
b Mounted on the left, it indicates the "open" or "closed" position of the switch and
has a normally open (NO) or normally closed (NC) contact.
Spare indicator lights for 20, 32 A iSW switches
Accessory
Type
b The padlocking facility locks the switch in the "open" or "closed" position.
Neon Voltage (Ue)
Supplied with a red diffuser 230 V AC 15111
Catalogue numbers (Pack of 10)
Incandescent bulb (P=1.2 W)
20, 32 A iSW control switches
PB105264-40
PB105265-40
1
32 A 250 V AC A9S60132
PB105266-40
PB105267-40
40 to 125 A iSW switch-disconnectors
2 Type Width in 9 mm modules
2P 1P Rating Voltage (Ue)
20 A 250 V AC - 2 40 A 250 V AC A9S60140 2
DB118998
1
DB118999
1
415 V AC A9S60220 63 A 250 V AC A9S60163
Control switches 32 A 250 V AC - 100 A 250 V AC A9S60191
415 V AC A9S60232 125 A 250 V AC A9S60192
2 2
3P 2P
20 A 415 V AC A9S60320 4 40 A 415 V AC A9S60240 4
DB118999
1
DB119000
1
32 A 415 V AC A9S60332 63 A 415 V AC A9S60263
Switch-disconnectors
100 A 415 V AC A9S60291
125 A 415 V AC A9S60292
2 2
4P 3P
20 A 415 V AC A9S60420 4 40 A 415 V AC A9S60340 6
DB119000
1
DB119001
1
32 A 415 V AC A9S60432 63 A 415 V AC A9S60363
100 A 415 V AC A9S60391
125 A 415 V AC A9S60392
2 2
Operating frequency 50/60 Hz 4P
40 A 415 V AC A9S60440 8
DB119001
1
63 A 415 V AC A9S60463
100 A 415 V AC A9S60491
125 A 415 V AC A9S60492
2
Operating frequency 50/60 Hz
DB122821
6A 250 V AC voltage presence
indicator light
PB105256-40
PB105257-40
PB105256-40
PB105258-40
1 1
OF iSW
IP40 Accessories
DB123597
Type
Padlocking facility (for Ø 8 mm padlock)
Pack of 2 parts 26970 Diagram
DB122563
DB122564
DB122565
DB122566
Colour Red Green White Blue Yellow Green/red White/ Red Red/red/red
white
Dimensions (mm) Technical data Cat. no.
12...48 V AC/DC A9E18330 A9E18331 A9E18332 A9E18333 A9E18334 A9E18335 - - -
Main characteristics 20, 32 A iSW 40 to 125 A iSW
DB122822
DB123137
voltage (Uimp)
1P, 2P 3P, 4P
Operating category AC - 22 A AC - 22 A torque Rigid Flexible or ferrule
20, 32 A iSW Permissible rated short-time - 40 A, 63 A: 1260 A
DB122945
DB122946
withstand current (Icw) 100 A, 125 A: 2500 A
4 mm
Conditional rated short-circuit 3 kA to IEC/EN 60669-2-4 6 kA to IEC 60947-3
4P current (Inc) PZ1
DB122823
40 to 125 A iSW
Main characteristics
Tropicalization Treatment 2 (relative humidity 95% at 55°C)
Pollution degree 3
Power circuit
DB122824
Choice table
> IC 100
IC 100 IC 2000 IC Astro
P111637
IC Astro 1C IC Astro 2C
P83237
Adjustable from 2 to 100 lux. Catalogue numbers 15482 CCT15284 CCT15368 CCT15223 (2) CCT15243 (2)
It comes with a wall-mounted cell.
Number of channels 1 1 1 1 2
Control by brigh tness detection ■ ■ ■
Coupling with weekly programming 84 switching times 84 switching times
Control by calculation of sunrise/sunset times ■ ■
Technical data
Adjustable brightness threshold 2 to 100 lx 2 to 2000 lx 2 to 2000 lx According to sunrise/ According to sunrise/
sunset times sunset times
Time delays (On and Off) 20 s (On) ≥ 60 s ≥ 60 s Difference in sunset Difference in sunset
Adjustable from 2 to 2000 lux.
P116858
80 s (Off) and/or sunrise times and/or sunrise times
It comes with a standard wall-mounted adjustable separately adjustable separately
or switchboard cell. by ±120 min. by ±120 min.
Monitoring indicator light, not time delayed, Red Red Red
lit when brightness is less than the threshold
Contact switching indicator light Green Green Green
LCD liquid crystal display Back-lit Back-lit
Program saving by lithium battery ■ ■
Operating reserve 6 years 6 years
Location for instruction manual on front face ■ ■ ■ ■
Cabling test function with a push-button on front face ■ ■
1 screw connection per pole ■
2 screwless connection per pole ■ ■ ■ ■
Mechanical compatibility with electrical distribution comb busbars ■ ■ ■
Delivered with standard switchboard cell ■
Delivered with standard wall-mounted cell ■ ■
P116858
P116858
P116859
IC 2000 standard IC 2000 standard IC 100k digital IC 100k digital
switchboard cell, wall-mounted cell, wall-mounted cell, switchboard cell,
15281 CCT15268 CCT15260 CCT15261
Choice table
The time switches control opening and closing of one or more separate circuits according to a programming pre-set by the user:
b by memorisation of On and Off switching operations for the IHP switches
b by positioning of jumpers or captive segments on a programming dial for the mechanical IH switches.
An IHP or IH time switch is chosen according to the following criteria:
Designation Number Cycle period Mnimum Number Saving on Width Override Output contact Time Back-lit "Absence Screwless Mechanical Input for Instruction Memory Cat. no.
of channels (d: day) time between of switching mains (modules controls changeover changeover display, for holidays" connection compatibility external manual key
2 switching operations cut off of 9 mm) On / Off switch (summer/ random function with electrical control holder integrated
operations (cos j =1) winter) function distribution on front face in front face
and pulse comb
programming busbars
(9)
(1) The IHP DCF is synchronised on the Frankfort transmitter via the ANT DCF antenna. (9) Pulse programming allows switching operations of a duration less than one minute (adjustable from 1 to 59 s); a pulse control always has priority.
(2) Supply voltage: 120 V CA.
(3) 4 output channels and 6 condition inputs.
(4) 45 time brackets in weekly time programming, 15 time brackets in annual time programming, 20 different pulses in pulse programming.
(5) 100 h for 100 V CA supply voltage.
P111632
P111626
P111612
P111613
P111619
(6) On/Off via an override input or a condition input.
(7) For IHP +1c and IHP+ 2c.
(8) For ITM 4c-6E.
140 IHP, IH, IHH, ITM IHP, IH, IHH, ITM 141
Timers MIN, MINs, MINp, MINt Timers MIN, MINs, MINp, MINt
P111644
N 4 N 4 3 N 4 N 4
R or or R R or R or
3 wires 3 wires 3 wires 3 wires
N N N
N
MIN MIN + PRE MINs MINp - MINt
Dimensions
MIN
5 63
18 38
MINp. MINt.
Catalogue numbers 83 83 45
6 60
44
18 26
89 45 73
142 MIN, MINs, MINp, MINt MIN, MINs, MINp, MINt 143
Dimmers STD- SCU range Dimmers STD- SCU range
STD400RC/RL-DIN & SAE STD400RC/RL-DIN & SAE
STD1000RL-DIN & SAE STD1000RL-DIN & SAE
SCU10-DIN & SAE SCU10-DIN & SAE
STD400RC/RL-DIN STD400RC/RL-SAE Common technical data for DIN&SAE types Specific operation for SAE type
b Local push-button: short push for On/Off control, long push for dimming. b STD400RC/RL-SAE, STD1000RL-SAE and SCU10-SAE dimmers have
b Auxiliary push-button input: short push for On/Off control, long push for dimming. 2 different operation modes (A and B) using auxiliary push-buttons connected on
v up to 25 parallel connected auxiliary push-buttons without indication lamps. digital inputs (1, 2, 3 and 4 terminals).
v up to 5 parallel connected auxiliary push-buttons with indication lamps. b Modes A and B can be changed by pushing the digital inputs 3 and 4
v max wire length 50 m. simultaneously for 10 s. After the mode is changed the load and the LED start to blink
b The minimum light level setting is adjustable. as long as the inputs are pushed.
b Indication blue LED (built in the local push-button) illuminates during the on-state. b In the mode A ,the input 1 dims the lights on with a short push and up with a long
The LED is blinking in error mode. push and turns light off with a short push and dims the light down with a long push.
b Protection and fuses: The direction is changed every time the input 1 is released. The input 2 dims
v electronic overload protection, the lights always off.
v electronic overvoltage protection, b In the mode B, the input 1 dims lights only up with a long push and turns lights on
v electronic over temperature protection, with a short push. The input 2 dims the lights only down with a long push and turns
v single shot thermal fuse. lights off with a short push.
b Supply voltage: 230 V AC ± 10 %, 50 Hz. b Inputs 3 and 4 are for memory places for light levels. The light level is called with
b Power loss: 3 W. a short push and set into the memory with a long push of 3 s.
STD1000RL-SAE b Standby consumption: 0.8 VA.
b Current sink for 1-10 V output: 0.2- 100 mA,
b Operating temperature: 0 °C to +40 °C , 40 °C to +70 °C with - 6 W /°C de-rating.
STD dimmers connection
b Top connection terminals: 2-pole screw connection for cables up to 4 mm².
b Storage temperature: 0 °C to +60 °C.
b Bottom connection terminals only available for SAE type: 5-pole screw connection
b Degree of protection: IP 20.
for cables up to 2.5 mm².
b Standards: according to EN 60669-2-1.
b With SAE types, it is possible to control a maximum of 20 dimmers combining
b Directives: according to CE, EMC 89/336/EEC and LVD 73/73/23/EEC.
STD400RC/RL-SAE and STD1000RL-SAE, with only one push-button via
the 4 digital inputs.
Specific technical data for SAE type
b The STD400RC/RL-SAE, STD1000RL-SAE and SCU10-SAE dimmers L L L
are supplied with 4 digital inputs: N N N
v input 1: On/Off and dimming up/down or only On and dimming up (depends on (1) (1)
function mode).
v input 2: Off and dimming down or only Off (depends on function mode). N L N L N L
N L N L
v input 3: adjustable lighting level memory 1 (50% default).
SCU10-SAE v input 4: adjustable lighting level memory 2 (100% default).
b Input voltage: 12- 30 V AC/ DC. D 00 C/ -D D 00 C/ - A D 00 C/ - A D 00 C/ - A D 00 C/ - A
b Max wire length: 50m. D1000 -D D1000 - A D1000 - A D1000 - A D1000 - A
Load table
STD400RC/RL-DIN, STD400RC/RL-SAE
230 V incandescent and halogen lamps 40 - 400 W
Low voltage halogen lamps with electronic or conventional transformer 40 - 400 W
Low voltage halogen lamps with toroidal transformer 40 - 300 W (2)
Motors (fans, ventilators...) 40 - 200 W
STD1000RL-DIN, STD1000RL-SAE 12-30 V AC/DC 12-30V AC/DC
N L N L N L N L N L
+ - L N + - L N + - L N + - L N + - L N
1- 10 V 1- 10 V 1- 10 V 1- 10 V 1- 10 V
(2)
(1) Use of maximum 25 push-buttons without indication lamp and 5 push-buttons with indication lamp, connected in parallel
(2) Use of maximum 25 push-buttons without indication lamp, connected in parallel, only for SCU10-SAE
Catalogue number
Type Cat. no.
STD400RC/RL-DIN CCTDD20001
STD400RC/RL-SAE CCTDD20002
STD1000RL-DIN CCTDD20003
STD1000RL-SAE CCTDD20004
SCU10-DIN CCTDD20011
SCU10-SAE CCTDD20012
Dimensions
Type Width (mod. of 9 mm)
STD400RC/RL-DIN , STD400RC/RL-SAE 4
STD1000RL-DIN , STD1000RL-SAE, SCU10-DIN, SCU10-SAE 8
85 45 68
6
36 72 56
DBxxxxxx
DBxxxxxx
DBxxxxxx
IEC 62053-21 and IEC 61557-12 IEC 61557-12
PMD/DD/K55/1 PMD/DD/K55/1
Country approval pictograms PMD/SD/K55/1 (ME4zrt)
MID approval IEC 62053-21
(accuracy)
PB105290-35
DB123207
DB123208
DB123209
DB123210
DB123211
DB123212
DB123213
DB123214
DB123212
Function
Digital kilowatt-hour meters designed for sub-metering of active energy (rms) consumed by a single-phase or three-phase electric Digital kilowatt-hour meters designed for sub-metering of active energy (rms) consumed by a single-phase or three-phase electric
circuit with or without distributed neutral. circuit with or without distributed neutral.
Catalogue numbers A9MEM2000 A9MEM2010 A9M17065 A9M17066 A9M17067 A9M17075 A9M17076 A9M17072 A9M17070 A9M17071 A9M17072
Technical specifications
Rating (A) 0…40 0…63 0…63 40…6000 0…63 40…6000
Voltage (Ue) V AC 230, ± 20 % 230, ± 20 % 400, ± 20 % 230/400, ± 20 %
Operating frequency Hz 48/62 48/62 48/62 48/62
Direct measurement Up to 40 A Up to 63 A Up to 63 A – Up to 63 A –
Measurement by CT – – – Up to 6000 A – Up to 6000 A
Metering and activity indicator 3,200 flashes per kWh 1,000 flashes per kWh 100 flashes per kWh 10,000/x flashes 100 flashes per kWh 10,000/x flashes
light (yellow) per kWh (x = CT rating)
(1)
per kWh (1) (x = CT rating)
Total meter (max. capacity) 999 999.9 MWh 999.99 MWh 999.99 MWh b Where CT y 150/5 A: 999.99 MWh b Where CT y 150/5 A:
on all 3 phases 999.99 MWh 999.99 MWh
b Where CT > 150/5 A: b Where CT > 150/5 A:
9,999.9 MWh 9,999.9 MWh
Total meter display In kWh with 7 significant digits In kWh or MWh with 5 significant digits. In kWh or MWh with 5 significant digits. – In kWh or MWh with 5 significant digits. No decimal
No decimal point in kWh; 2 digits after the decimal point in MWh No decimal point in kWh; 2 digits after the decimal point in MWh point in kWh; 2 digits after the decimal point in MWh
Partial meter (max. capacity) on – – 99.99 MWh – 99.99 MWh b Where CT y 150/5 A: – 99.99 MWh b Where CT y 150/5 A:
all 3 phases with RESET 99.99 MWh 99.99 MWh
b Where CT > 150/5 A: b Where CT > 150/5 A:
999.99 MWh 999.99 MWh
Partial meter display – – In kWh or MWh with 4 significant digits. – In kWh or MWh with 4 significant digits. 1 digit after – In kWh or MWh with 4 significant digits. 1 digit after
No decimal point in kWh; 2 digits after the decimal the decimal point in kWh the decimal point in kWh
point in MWh
Remote transfer – By static output: – – By NO impulse contact: – By NO impulse contact: By NO impulse contact: – By NO impulse contact: By NO impulse contact:
b ELV insulation b ELV insulation b ELV insulation voltage: b ELV insulation voltage: b ELV insulation voltage: b ELV insulation voltage:
voltage: 4 kV, 50 Hz voltage: 4 kV, 50 Hz 4 kV, 50 Hz 4 kV, 50 Hz 4 kV, 50 Hz 4 kV, 50 Hz
b 20 mA/35 V DC max. b 18 mA/24 V DC, b 18 mA/24 V DC, b 18 mA/24 V DC, b 18 mA/24 V DC, b 18 mA/24 V DC,
b 100 impulses of 100 mA/230 V AC 100 mA/230 V AC 100 mA/230 V AC 100 mA/230 V AC 100 mA/230 V AC
120 ms per kWh b 1 impulse of 200 ms b 1 impulse of 200 ms b 10/x impulse of 200 ms b 1 impulse of 200 ms b 10/x impulse of 200 ms
(contact closing) per (contact closing) every (contact closing) per (contact closing) every (contact closing) per
kWh 10 kWh kWh = x/10 kWh per 10 kWh kWh = x/10 kWh per
impulse (2) (x = CT rating) impulse (2) (x = CT rating)
Width in 9 mm modules 2 4 8 8
(1) example: 500/5 CT = 10,000/500 flashes per kWh = 20 flashes per kWh
(2) example: 500/5 CT = 500/10 kWh per impulse = 50 kWh per impulse.
DB118858
(iEM2010) (iME1zr) torque Rigid Flexible or ferrule
DB122945
DB122946
DB123310
iEM2000 / Remote transfer 0.8 ± 0.1 N.m 4 mm2 4 mm2
iEM2010 Power 1.2 ± 0.2 N.m 10 mm2 10 mm2
iME Remote transfer 0.9 ± 0.1 N.m 6 mm2 6 mm2
Power 1.5 ± 0.3 N.m 16 mm2 16 mm2
DB123312
to impulse meter to impulse meter
DB118859
DB118860
DB123314
Operating temperature -25°C to +65°C if < 32 A -25°C to +55°C
-25°C to +55°C if u 32 A
Storage temperature -40°C at +70°C
Tropicalization (IEC 60068-1) Treatment 2 (relative humidity 95% at 55°C)
DB118862
DB123314
IK05 IK05 Kilowatt-hour meters
iEM2000 / iEM2010 iME1 / iME1z / iME3 / iME3zr iME4 / iME4zr /
1 Protection (to be adapted to suit the iME1zr iME4zrt
short-circuit current at the connection 0.073 0.135 0.194 0.194
point).
2 Shorting switch unit.
iME
Dimensions (mm)
18 67
DB123013
DB123014
36 5 44 16
45 84 95
81 45
iME4 / iME4zr. iME4zrt.
Caution
b Do not earth the CT secondary (S2). b You must comply with the routing direction of power cables in the current iEM2000 / iEM2010 iME1, iME1z and iME1zr
transformer primary. Cables enter in "P1" and leave in "P2" to the loads.
72 5 44 16
DB123015
DB114265
DB114264
81 45