Poly Urethane
Waterproofing & Flooring
July 25, 2018      JTCC. JT Construction Chemicals   1   1
Content
❑ Introduction of polyurethane
❑ Polyurethane waterproofing
❑ Application
❑ Trouble shooting
July 25, 2018        JTCC. JT Construction Chemicals   2   2
Overview of the urethane
  POLYURETHANE ?
          All polymer compounds formed by the urethane bond.
           OH alcohol group and an isocyanate group NCO combined to produce a urethane bond
                                 -OH       + -NCO                             -N-C-O-
                                                                                 H O
Resin    Hardener      Solvent            Cross-linking reaction of the resin and
                                          evaporation of the solvent is in progress
                                                                                         After a certain period of time
                                                                                         being a cross-linking reaction is
                                                                                         completed,
   Wet film                                The reaction temperature drying              The dried film
July 25, 2018                    JTCC. JT Construction Chemicals                                                             3   3
  Product
                                                 Mixing
    Product                 Product               ratio                           Characteristics                           Reference
                                                  (R:H)
                                                       A one-pack type moisture-curing to penetrate deep into the
                                                   1-
                                                       concrete material undercoating to enhance the strength and           Transparen
Urethane Primer         Nitoproof Primer         compo
                                                       form a strong adhesion between the material and the coating              cy
                                                  nent
                                                       film
                                                          2-component polyurethane top coat waterproofing paint finish
Urethane
                      Nitoproof TOP COAT          1:3     with excellent abrasion resistance and UV light resistant         Thin Film
Topcoat
                                                          pigment on
                                                          Urethane resin and water resistance, chemical resistance of
Tar-urethane                                                                                                                  Thick
                    PU2K C TAR UTRETHAN           1:3     unfilled 2-component elastic waterproofing manufactured from
waterproofing                                                                                                                 Film
                                                          coal tar outstanding
                                                          Tensile strength, tear strength, high elongation and excellent
Urethane                                                                                                                      Semi
                        Nitoproof PU2K            1:3     elastic and flexible forms a strong waterproof coating adhesion
waterproofing                                                                                                                 Hard
                                                          and waterproof elastic roof waterproofing
                                                   1-  As the moisture-curing one-component polyurethane sealants
Urethane                                                                                                                    Moisture
                        Nitoproof PU1K           compo prevent it represents an excellent waterproof effect let that
waterproofing                                                                                                                curing
                                                  nent may occur in the mixing step
                                                        Durability, excellent elongation, etc. can be used as flooring
Urethane hard elastic flooring                   1 : 2 and other indoor and outdoor track and field stadium, general          Hard
                                                        buildings
 July 25, 2018                        JTCC. JT Construction Chemicals                                                                 4   4
Properties
            product
                                                           Neothane                                     Urethane hard
                      NeoThane Primer Neothane topcoat                  Neothane #200   Neo easythane
                                                         TAR UTRETHAN                                   elastic flooring
Item
  Mixing ratio
                         One pack            1:3               1:3          1:3           One pack           1:2
     (B:H)
 Specific gravity        0.95±0.05         1.15±0.1          1.4±0.1       1.5±0.1        1.45±0.1         1.4±0.1
    Touch dry
                          1 hours           1 hours         12 hours       7 hours         8 hours         5 hours
      (25℃)
       Pot life
                          3 hours           2 hours          30 min        30 min          30 min           30 min
       (25℃)
                                                                                                           24 hours
Drying time (25℃)         24 hours         24 hours         48 hours      24 hours        72 hours
   Elongation
                             -                 -            550 over      450 over        450 over         300±100
      (%)
    Hardness
                             -                 -              50±5          60±5              -              80±5
   (Shore- A)
 Thinner usage
                        Less than 5       Less than 5           -             -          Less than 5           -
      (%)
 July 25, 2018                        JTCC. JT Construction Chemicals                                                  5   5
 Application
Unexposed polyurethane waterproofing SYSTEM
Indoor and outdoor waterproof roof Unexposed
                                                                                             - Remove laitance
Of Building Structures baths, sauna, balcony, etc.
                                                                           Floor cleanup     - Check water content
                                                                                             - Reinforcing fragile zone
   Construction sectional
                                                                                             - urethane primer: 0.2-0.4㎏/㎡
                                                                              Primer         - Corner area and around the
                                                                                               pipe reinforcement
                                                                                               Use polyurethane sealant
                                        Protection Mortar                                    - Unexposed urethane
                                                                           Urethane 1st
                                        Unexposed urethane(3㎜)                                 moderate : 1.5 ㎜
                                                                           Application
                                                                                             - Reinforcing health checks
                                        Urethane primer                                        and fragile zone
                                        Concrete
                                                                                             - Unexposed urethane
                                                                           Urethane 2nd
                                                                                               moderate : 1.5 ㎜
                                                                           Application
                                                                                             - Reinforcing health checks
                                                                                               and fragile zone
                                                                                             - (Wall) tiles attached upon
                                                                         Protection Mortar     silica spray
                                                                                               Protection Mortar
                                                                                               (waterproof layer damaged
                                                                                               during follow-up care)
   July 25, 2018                       JTCC. JT Construction Chemicals                                                       6   6
 Application
Exposure polyurethane waterproofing /Flooring SYSTEM
Common roof and interior and exterior, concrete
                                                                                       - Remove laitance
waterproofing
                                                                       Floor cleanup   - Check water content
                                                                                       - Reinforcing fragile zone
   Construction sectional
                                                                                       - urethane primer: 0.2-0.4㎏/㎡
                                                                          Primer       - Corner area and around the
                                                                                         pipe reinforcement
                                                                                         Use polyurethane sealant
                                      Finishing top coat
                                       Exposure urethane(3㎜)                           - Exposure urethane
                                                                       Urethane 1st
                                                                                         moderate : 1~1.5 ㎜
                                      Urethane primer                  Application
                                                                                       - Reinforcing health checks
                                      Concrete                                           and fragile zone
                                                                                       - exposure urethane
                                                                       Urethane 2nd      moderate : 1~1.5 ㎜
                                                                       Application      -Reinforcing health checks
                                                                                         and fragile zone
                                                                                       - urethane top coat:0.3-0.4㎏/㎡
                                                                         Top coat        Roller, spraying
                                                                                       - Uniformly coat
   July 25, 2018                     JTCC. JT Construction Chemicals                                                   7   7
 Application
Sports Facilities hard urethane paint SYSTEM
It requires resolution elastic bottom layer middle, top paint                            - Remove laitance
Basketball, tennis courts, table tennis, etc.                            Floor cleanup   - Check water content
                                                                                         - Reinforcing fragile zone
   Construction sectional                                                                - Primer: 0.2-0.4㎏/㎡
                                                                            Primer       - Reinforce corner area using
                                                                                         polyurethane sealant
                                           Top coat
                                           Hard urethane(2㎜)             Urethane 1st    - Apply body coat (hard): 3.0㎜
                                                                         Application     - Check and reinforce 1st layer
                                           Semihard urethane(3㎜)
                                           Urethane primer
                                           Concrete                                      - Apply 2nd body coat (hard): 2.0㎜
                                                                         Urethane 2nd
                                                                         Application     - Check and reinforce
                                                                                         - Apply top coat:0.3-0.4㎏/㎡
                                                                           Top coat      using Roller, or Spraying
                                                                         Line marking
   July 25, 2018                       JTCC. JT Construction Chemicals                                                 8      8
Application (Step 1)
    Substrate Preparation                                Priming(Neothane Primer)
     Repair Crack & damage                               Corner sealing(Urethane sealant)
July 25, 2018          JTCC. JT Construction Chemicals                                      9   9
Application (Step 2)
    Body Coat (Neoeasythane, Neothane #200)
July 25, 2018         JTCC. JT Construction Chemicals   10   10
Application (Step 3)
 TopCoat(Neothane#500), Green/Grey
July 25, 2018       JTCC. JT Construction Chemicals   11   11
Trouble shooting
 Polyurethane waterproof flooring construction defect causes and countermeasures
      Problem                              Causes                                                Measures
                   High temperatures (direct sunlight), the CO2 gas
                                                                            High heated waves (air: over 30 ℃, surface work:
                   generated by rapid curing reaction did not get out to
                                                                            more than 40 ℃) work zone should be avoided.
                   outside
                                                                            After application completely dry work surface
                   Swelling caused by water vapor pressure while the
                                                                            (concrete curing more than 28 days after the seal
                   surface changes into steam after application
                                                                            check moisture content of 8% or less)
  Film Swelling
  (Bubble,                                                                  Should be applied twice body coat
        Pinhole)   Thick middle coat in direct sunlight                     Primary scraping (0.5 ~ 1 ㎜) after the second
                                                                            coating
                   The formation of a thick coating (over 5㎜) , CO2 Gas
                                                                            One coat middle coat within the 3㎜
                   cannot get out
                                                                            A primer coating to at least twice
                   Excessive porosity of the surface (bubbles, pinholes),
                                                                            Middle coat coating after scraping a part of the
                   Not enough priming
                                                                            middle coat
July 25, 2018                    JTCC. JT Construction Chemicals                                                                12   12
Trouble shooting
 Polyurethane waterproof flooring construction defect causes and countermeasures
     Problem                         Causes                                                 Measures
                After the primer or middle coat coating in a
                                                                       Primer again using 10~25% diluted product
                state exposed to rain (interlayer adhesion
                                                                       (0.1 ㎏ / ㎡)
                failure)
                Swelling caused by water vapor pressure while          Should be applied at the dry condition
                the work surface changes into steam after              (concrete curing more than 28 days after the
  Attaching     application                                            seal check moisture content of 8% or less)
       defect
                                                                       Preprocessing conduct of the work surface
                Pretreatment of poor working surface (painted
                                                                       (removing cement, mortar dust, laitance,
                in the state in which the surface contamination)
                                                                       dirt, etc. to clean the grinder)
                                                                       Repainting interval (within 48 hours)
                Recoating intervals in excess(48hrs)                   Primer 10-20% dilution thin coating using a
                                                                       diluent (0.1 ㎏ / ㎡)
                                                               A : Penetration to the work surface by the strength
                                                               increasing effect
                                                               B : Improve the adhesion of the base surface, it prevents
                                                               air bubbles.
                                                               C : Liquidity prevent the reduction of floor Repair.
July 25, 2018                JTCC. JT Construction Chemicals                                                               13   13
Trouble shooting
 Polyurethane waterproof flooring construction defect causes and countermeasures
     Problem                            Causes                                                 Measures
                                                                           Uniformly stirring the resin and hardener using
                Mixing and stirring mistake
                                                                           power tools
                                                                           Mixing ratio compliance, using completely scraped
                It does not fit the blending ratio of resin and hardener
                                                                           some of the precipitation hardening agent
                                                                           Remove the hardener (mixing, stirring when using
                Hardener is located on the floor
                                                                           a pallet)
                                                                           Remove moisture and complete cure of the work
                If the moisture seep out from the work surface
                                                                           surface
      Curing
                Excessive dilution of diluent                              Amount used of diluent compliance
                                                                           The use of diluent dedicated
                The use of unsuitable thinner
                                                                           (Alcohol, lacquer thinner, epoxy thinner Do not use)
                When coating at a low temperature (below 5℃)               Working Temperature Compliance (more than 5 ℃)
                A high temperature (over 30 ℃), humidity (over 85%)        Working in hot and humid environment (the rainy
                in a working environment                                   season) should be avoided
July 25, 2018                  JTCC. JT Construction Chemicals                                                                14   14
Trouble shooting
 Polyurethane waterproof flooring construction defect causes and countermeasures
     Problem                            Causes                                                Measures
                If you have a large bubbles are generated in the resin
                                                                         Mixing ratio compliance
                is excessive and cracks after curing
                Excessive dilution of diluent                            Comply with the prescribed amount of diluent.
                Excess coating film formed on one (or more 5㎜)           Construction as per proper film thickness
                                                                         After sealing the cracks of the work surface
  Cracks in
                Crack the impact of the work surface                     pretreatment agent after the V-Cutting middle coat
  the coating
                                                                         painting
                Applied to the portion of the work surface cracks
                                                                         Uniformly forming an middle coat coating film to
                middle coat a thin coat
                                                                         within 3㎜
                (Within about 1㎜)
                Cracks caused by external forces such as vibration of    After you complete the installation process, such as
                the building before full cure of the middle coat         joint
July 25, 2018                 JTCC. JT Construction Chemicals                                                               15   15
Trouble shooting
 Polyurethane waterproof flooring construction defect causes and countermeasures
     Problem                             Causes                                                 Measures
                 middle coat curing defects and occurs when fully         middle coat coating method and then comply fully
                 cured before the topcoat paint                           cured topcoat paint
                 Topcoat paint in poor adhesion occurs when the state
     Top coat                                                             middle coat coating method complies
                 of the middle paint
       Paint
     wrinkles
                 When the middle coat coating thickness as low as less    Working with the middle coat coating thickness
                 than 1㎜ occurs when top coat paint                       regulation
                 middle coat the surface of the topcoat paint in oil or
                                                                          Before topcoat ensure cleanliness and removal
                 contamination by foreign substances
                 When topcoat paint in the middle coat surface
                                                                          Before topcoat ensure cleanliness and removal
                 contamination by oil or debris cratering phenomenon
      Topcoat
       coating
      defects                                                             If there is a possibility of rain, prohibited operation,
                 The discoloration of the color occurs when exposed to
                                                                          (If a larger temperature difference between day
                 moisture such as rain before fully cured topcoat
                                                                          and night dew note)
July 25, 2018                   JTCC. JT Construction Chemicals                                                                 16   16
Trouble shooting
Polyurethane coating waterproof flooring construction defect cases
 ➢ Topcoat coating defects
 July 25, 2018               JTCC. JT Construction Chemicals
                                                          ➢ Before Curing, Contact rain or water   17   17
Trouble shooting
Polyurethane coating waterproof flooring construction defect cases
         ➢ Above 8% water content on the surface>                  ➢ Apply top coating before set bodycoat>
           ➢ Overdosage thinner>                                   ➢ Over dosage thinner>
 July 25, 2018                   JTCC. JT Construction Chemicals                                              18   18
Trouble shooting
Polyurethane coating waterproof flooring construction defect cases
            ➢ Coating swells rising phenomenon caused by
              water after painting
                                                                    ➢ Apply topcoat on the uncured state
             ➢ Thickened by using the excess paint
               thinners
 July 25, 2018                    JTCC. JT Construction Chemicals                                          19   19
Trouble shooting
Polyurethane coating waterproof flooring construction defect cases
         Summer temperatures (direct sunlight) job
         Foam reacts with the moisture content when there
         are many topics
July 25, 2018                    JTCC. JT Construction Chemicals     20   20
Comparison of resin Product
July 25, 2018   JTCC. JT Construction Chemicals   21   21
Reference
July 25, 2018   JTCC. JT Construction Chemicals   22   22
Reference
July 25, 2018   JTCC. JT Construction Chemicals   23   23
Reference
July 25, 2018   JTCC. JT Construction Chemicals   24   24
Reference
July 25, 2018   JTCC. JT Construction Chemicals   25   25