Operating Instructions
Controller
MMC4000
V3
MS60024/05E
© 2019 MTU Onsite Energy GmbH, Augsburg
The original document was created in the German language.
This publication including all of its parts is protected by copyright. Each instance of use requires the prior written consent of
MTU Onsite Energy GmbH. This applies in particular to duplication, dissemination, editing, translation, microfilming, and stor-
age and/or processing in electronic systems, including databases and online services.
All of the information presented in this publication was current and up-to-date at the time of publishing. MTU Onsite Energy
GmbH reserves the right to make changes to, delete, or supplement the provided information and data as needed.
Table of Contents
1 Safety 7.7 System overview 40
7.8 Counter reading 41
1.1 Safety notes 5
8 Operation and Visualization - Main Menu
2 General
8.1 Engine overview 42
2.1 Installation 6 8.2 Electrical data 43
2.2 MMC system description 7 8.3 Grid code (optional) 44
2.3 MIP system description 8 8.4 Load stage control (optional) 45
2.4 Safety chain 9 8.5 Energy Measurement Module EMM 47
2.5 CPU 10 8.6 Voltage regulator / power factor controller 48
2.6 Selectivity of protective devices 11 8.7 Generator data 50
2.7 Wiring diagram documentation 12 8.8 Power reduction (optional) 51
2.8 Module control cabinet 13 8.9 Water system 52
2.9 Battery shutdown 14 8.10 Gas system 54
2.10 Critical fault messages 15 8.11 Gas system – Single-gas operation 55
8.12 Gas system – Two-gas operation with only
3 Maintenance one gas train (optional) 56
3.1 Maintenance 16 8.13 Gas system – Two-gas operation with two
gas trains (optional) 57
8.14 Gas compressor (optional) 58
4 Starting Sequence and Stopping Sequence
8.15 Gas compressor via frequency converter
4.1 System – Start 17 (optional) 59
4.2 Stopping the plant 19 8.16 Gas leak test 60
4.3 EMERGENCY STOP 20 8.17 Oil system 61
8.18 Fault messages 64
5 Operating Modes 8.19 Status signals 65
8.20 Alarm Logger 66
5.1 Manual operating mode 21 8.21 Power controller 69
5.2 Automatic operating mode 22 8.22 Power controller – Origin of the setpoint 70
5.3 Grid backup mode 23 8.23 Power controller – Manual mode 71
5.4 Grid backup mode via external control 8.24 Power controller – Automatic mode 72
system 24 8.25 Start/stop sequence 75
5.5 Switching the grid on 25 8.26 Cleaning window 77
8.27 Service menu 78
6 Floating Contacts
9 Operation and Visualization - Additional
6.1 Floating contacts – General 26
Functions
6.2 Floating contacts – MIP 27
6.3 Floating contacts – MMC 28 9.1 Overview of additional functions 79
9.2 Water temperature controller (optional) 80
DCL-ID: 0000038395 - 006
7 Operation and Visualization - General 9.3 Water temperature controller via two
Information control loops (optional) 82
9.4 Water mixture controller (optional) 84
7.1 Selector switch / pushbutton / EMERGENCY
9.5 Mixture blower and pump (optional) 85
STOP 29
9.6 Emergency cooling water controller
7.2 Display 31
(optional) 88
7.3 Parameter entry 32
9.7 Emergency cooler blower and pump
7.4 Description of the menu bar 33
(optional) 89
7.5 Logon 37
9.8 Room temperature control (optional) 93
7.6 Operation and visualization – Main menu 39
MS60024/05E 2019-03 | Table of Contents | 3
9.9 Room blower control (optional) 94 9.26 Load distributor parameters 127
9.10 CH4 control (optional) 97 9.27 Parameters for frequency controller 128
9.11 Gas tank (optional) 99 9.28 Data backup 129
9.12 Grid feed-in control (optional) 101 9.29 Heating water (optional) 131
9.13 Exhaust/bypass flap control (optional) 104 9.30 Additional controller (optional) 132
9.14 Engine heat mode (optional) 105
9.15 Boiler heat mode (optional) 109 10 Appendix A
9.16 Outside temperature shift (optional) 110
9.17 Buffer reservoir (optional) 111 10.1 Translation to the national language 133
9.18 Timer (optional) 112 10.2 Abbreviations 141
9.19 SMS/e-mail (optional) 115 10.3 MTU Onsite Energy contact person / service
9.20 External communication (optional) 116 partner 142
9.21 M-Graph: Single channel 118
9.22 M-Graph: Installation of the seconds graph 120 11 Appendix B
9.23 M-Graph: System daily progression 122 11.1 List of Figures 143
9.24 Screenshot function 124 11.2 Index 144
9.25 Load divider isolated parallel operation 125
DCL-ID: 0000038395 - 006
4 | Table of Contents | MS60024/05E 2019-03
1 Safety
1.1 Safety notes
• The system may only be operated by authorized personnel of the operator. Maintenance and switching
work may only be carried out by external personnel with the operator's authorized personnel present.
• It is essential to observe the regulations of the trade association when working on the switchgear.
• Only authorized personnel working with appropriate tools are permitted to replace safety elements.
• The manufacturer's maintenance instructions must be followed.
TIM-ID: 0000061922 - 001
MS60024/05E 2019-03 | Safety | 5
2 General
2.1 Installation
For this, the current "Installation guidelines" document from MTU Onsite Energy must be followed.
TIM-ID: 0000061926 - 001
6 | General | MS60024/05E 2019-03
2.2 MMC system description
• Industrial PC (IPC) with touch screen
• Control elements (key switches, pushbuttons, EMERGENCY STOP buttons)
• Peripheral assemblies of the PLC control system with digital and analog inputs and outputs
• Interfaces for connecting to external systems (floating contacts)
• Activation of the peripheral drives via floating contacts or power parts
TIM-ID: 0000061920 - 001
MS60024/05E 2019-03 | General | 7
2.3 MIP system description
• EMERGENCY STOP button
• PLC, programming in accordance with IEC 61131-3
• EMM (generator and mains network protection, synchronizer)
• Communication with ADEC governor and EMU engine monitoring via CAN bus and hardware signals
• Interfaces for connecting to external systems (floating contacts)
• Activation of auxiliary drives to genset
TIM-ID: 0000061921 - 001
8 | General | MS60024/05E 2019-03
2.4 Safety chain
The safety chain is equipped with two tested safety combinations:
• Machine EMERGENCY STOP safety chain (e.g. STL, centralized emergency off from PLC etc.)
• Manual EMERGENCY STOP safety chain (e.g. EMERGENCY STOP on the genset cabinet, building EMER-
GENCY STOP etc.)
The corresponding drives (e.g. gas valves etc.) are deactivated when one of the safety chains is triggered. A
manual EMERGENCY STOP deactivates all drives.
TIM-ID: 0000061923 - 002
MS60024/05E 2019-03 | General | 9
2.5 CPU
The PLC's CPU is monitored by a watchdog. When this responds, all the PLC outputs are deactivated under
defined conditions and the safety chain is triggered.
The CPU can only be reset by means of a cold restart (switch miniature circuit breaker off/on). If the fault
occurs again, contact the Service department.
TIM-ID: 0000061924 - 001
10 | General | MS60024/05E 2019-03
2.6 Selectivity of protective devices
The selectivity of the protective devices (fuses, circuit breakers etc.) is configured in the switchgear for the
short-circuit current in island operation or for mains parallel operation with the grid.
In island operation, however, only the lesser short-circuit currents are available to the switched-in genera-
tors, and the selectivity of the protective devices is restricted.
The customer must ensure that in this operating state the selectivity of the protective devices in the consum-
er switchgear is guaranteed.
TIM-ID: 0000061925 - 001
MS60024/05E 2019-03 | General | 11
2.7 Wiring diagram documentation
The wiring diagrams are specifically adapted for each system. The following documentation is available:
• Wiring diagrams
• Cable lists
• Material lists
• Terminal diagrams
TIM-ID: 0000061927 - 001
12 | General | MS60024/05E 2019-03
2.8 Module control cabinet
The control cabinet door must be kept closed if possible. The control cabinet door must be closed in any
event when the system is in operation.
TIM-ID: 0000061929 - 001
MS60024/05E 2019-03 | General | 13
2.9 Battery shutdown
If the battery charger is unavailable for a prolonged period (>5 h), the screw-in fuse-link (35 A) for the battery
system should be unscrewed. Otherwise, there is a risk of the controller batteries running completely dead.
TIM-ID: 0000061930 - 001
14 | General | MS60024/05E 2019-03
2.10 Critical fault messages
No. Fault message Meaning Remedial action
087 Generator circuit- The genset cannot be isolated from mains So not actuate the manual
breaker will not open due to switching failure, so the engine emergency stop!
would continue to rotate. If this fault oc- Have the generator circuit
curs, the system must not be switched off breaker opened by a qualified
with a manual EMERGENCY STOP. A man- electrician.
ual emergency stop switches off the auxili-
ary drives of the genset. As a conse-
quence, genset cooling is no longer provid-
ed. Overheating of the engine! Danger to
life due to ejected parts!
088 Generator circuit- This alarm is a result of fault message 087. So not actuate the manual
breaker will not open Fault message 087 was also followed by a emergency stop!
Trailing mode active shutting-down alarm. The genset is working Have the generator circuit
in trailing mode and driven by mains pow- breaker opened by a qualified
er. If this fault occurs, the system must not electrician.
be switched off with a manual EMERGENCY
STOP. A manual emergency stop switches
off the auxiliary drives of the genset. As a
consequence, genset cooling is no longer
provided. Overheating of the engine! Dan-
ger to life due to ejected parts!
TIM-ID: 0000061919 - 002
MS60024/05E 2019-03 | General | 15
3 Maintenance
3.1 Maintenance
The central unit (PLC) of the IPS and an optional UPS (Series 400) are equipped with a battery. These batter-
ies must be replaced at regular intervals as specified in the maintenance instructions.
The filters for the control cabinet fans and the optional control cabinet cooler must be changed.
Maintenance intervals:
• Battery change in central unit (PLC) every 4 years or when needed (see sticker on the control cabinet
door)
• Battery change in IPC every 2.5 years (see sticker on the control cabinet door)
• Change of the filter mats every 1800 h or when needed
• Cleaning of the control cabinet cooler every 2000 h or when needed (optional)
TIM-ID: 0000061928 - 001
16 | Maintenance | MS60024/05E 2019-03
4 Starting Sequence and Stopping Sequence
4.1 System – Start
DANGER
Rotating, moving engine parts.
Danger of crushing, danger of body parts being drawn in or caught!
• Ensure that the engine can not be started.
• After completion of work, make sure that all protective devices are installed.
WARNING
High level of engine noise when the engine is running.
Risk of damage to hearing!
• Wear suitable hearing protection.
NOTICE
Risk of engine damage due to incorrect action.
Risk of severe damage to property!
• Ensure engine is ready for operation before starting. See engine documentation.
Starting sequence
• Start command (local/remote)
• Manual/Automatic mode
• Enable key switch
Start precondition 1 ↔ • Genset ready for operation
• No grid failure (for systems without grid backup, mains circuit breaker is
on, or "no mains circuit breaker" option)
• Automatic: All start conditions for automatic mode OK.
Yes↓ | No→ • No start command
• Stop command to the ADEC governor
• Purging function on if the engine was previously stopped by an emergen-
cy stop
• Auxiliary drives and engine coolant pump on
Phase 1 ↔
• Open exhaust flap (optional)
• Oil priming on if necessary
• Start the gas leak test if the gas leak test is parameterized before engine
start
↓
• Engine coolant pump on
Start precondition 2 ↔ • Exhaust flap open (optional)
TIM-ID: 0000061972 - 002
• Gas leak test OK if the gas leak test is parameterized before engine start
Yes↓ | No→ • Start abort phase 1
Phase 2 ↔ • Open gas valves
↓
Start precondition 3 ↔ • Gas valves are open
Yes↓ | No→ • Start abort phase 2
• Rated speed reached
Phase 3 ↔ • Monitoring of generator voltage + generator frequency
• Activate run-on time for auxiliary drives
MS60024/05E 2019-03 | Starting Sequence and Stopping Sequence | 17
↓
• Generator voltage > limit value
Start precondition 4 ↔
• Generator frequency > limit value
Yes↓ | No→ • Start abort phase 3
• Synchronization enable (automatic or manual)
• Speed adjustment enable
Phase 4 ↔
• Automatic: Start time monitoring for synchronization
• Manual: Extended monitoring time for synchronization
↓
• Generator circuit breaker is on
Start precondition 5 ↔
• Time monitoring still running
Yes↓ | No→ • Start abort phase 4
Grid parallel: Monitoring of power regulation, ramp
Grid backup: Activate grid backup operation
TIM-ID: 0000061972 - 002
18 | Starting Sequence and Stopping Sequence | MS60024/05E 2019-03
4.2 Stopping the plant
Stop sequence
Phase 0 ↔ • Genset in operation and stop signal active
↓
Stop precondition 0 ↔ • Controlled stop (ramp function)
Yes↓ | No→ • Immediate stop (jump immediately to phase 2)
Phase 1 ↔ • Genset load is reduced to zero (ramp function)
↓
Stop condition 1 • Minimum power not reached or maximum time exceeded
↔
(delayed)
Yes↓ | No→ • Remains in phase 1
• Open generator circuit breaker
• Activate speed control
• Activate run-on time for auxiliary drives
Phase 2 ↔ • Stop command to the ADEC governor
• Activate relubrication function for exhaust turbocharger (optional)
• Start the gas leak test if the gas leak test is parameterized after engine
start
↓
Genset ready to start
TIM-ID: 0000061973 - 003
MS60024/05E 2019-03 | Starting Sequence and Stopping Sequence | 19
4.3 EMERGENCY STOP
NOTICE
An emergency stop subjects the engine system to an extremely high load.
Risk of overheating, damage to components!
• Trigger an emergency stop only in emergency situations.
EMERGENCY STOP
• Genset in operation and EMERGENCY STOP or immediate stop are pend-
Phase 1 ↔
ing
↓
Always deactivate without delay:
• Gas valves
• Ignition
• Governor
• Opening generator circuit breaker
• Start switching delay
In the case of machine EMERGENCY STOP - deactivate function with
delay:
• Coolant pump
• Exhaust flaps
• Heating water pump
• Bypass flaps
Phase 3 ↔
• Lube oil supply
• Ventilation
Exception: If one of these functions has triggered the EMERGENCY STOP,
it is deactivated without delay.
In the case of machine EMERGENCY STOP, deactivate function with-
out delay:
• Coolant pump
• Exhaust flaps
• Heating water pump
• Bypass flaps
• Lube oil supply
• Ventilation (option)
TIM-ID: 0000061974 - 002
20 | Starting Sequence and Stopping Sequence | MS60024/05E 2019-03
5 Operating Modes
5.1 Manual operating mode
In this operating mode, the genset is started on a start request (all start conditions must be met) and runs up
to idle speed. The genset then remains in idle speed (MMC400: maximum 2 h / MMC4000: maximum 1 h)
until the synchronization delay is introduced or a stop is activated.
In the case of synchronization operation being initiated and completed successfully, a setpoint of approx.
10 % is assigned to the power controller. Now the power can be changed manually.
TIM-ID: 0000061935 - 001
MS60024/05E 2019-03 | Operating Modes | 21
5.2 Automatic operating mode
In this operating mode, the genset starts following a start request and synchronizes with the grid automati-
cally. Depending on the selected mode of operation (fixed value control, variable value control, heat-control-
led etc.), the current setpoint is transferred to the power controller (MMC400) or ADEC governor
(MMC4000) and approached.
• In automatic mode, various auxiliary features are integrated in the starting sequence. Dependent upon
which function is active (e.g. timer, grid feed-in control, CH4 content etc.), the start enable for the relevant
feature is taken into account when a start request is active. If there is a problem, a summary alarm is
output.
• If a drive or a controller (e.g. engine coolant pump etc.) is in manual mode when a start is initiated, man-
ual mode is reset. This ensures that no undefined switching states occur in automatic mode (e.g. the gen-
set would overheat if the engine coolant pump was switched off).
TIM-ID: 0000061931 - 001
22 | Operating Modes | MS60024/05E 2019-03
5.3 Grid backup mode
In isolated operation the power is determined by whichever consumers are switched in.
Speed control simply has to readjust the speed setpoint after load changes. This setpoint is specified via a
frequency controller.
On systems with multiple engines, gensets working in parallel must not be allowed to run with differing per-
centage loads. An effective load distribution system is also provided for this purpose in addition to the fre-
quency controller.
TIM-ID: 0000061932 - 001
MS60024/05E 2019-03 | Operating Modes | 23
5.4 Grid backup mode via external control system
Not MCS.
See "Grid backup mode via external control system".
TIM-ID: 0000061933 - 001
24 | Operating Modes | MS60024/05E 2019-03
5.5 Switching the grid on
Synchronous generators may only be connected to an existing grid if their voltage, frequency and phase an-
gle are identical. To meet the required conditions, a synchronizer is required. The synchronizer uses the
speed controller to influence the frequency of the generator up to the point of switching-in. The synchronizer
uses the voltage regulator to influence the voltage of the generator up to the point of switching-in.
TIM-ID: 0000061934 - 001
MS60024/05E 2019-03 | Operating Modes | 25
6 Floating Contacts
6.1 Floating contacts – General
The control system outputs various floating contacts by default. These contacts can be used to activate
drives or to query the status of the system.
Specific projects may feature more of these messages.
TIM-ID: 0000061940 - 001
26 | Floating Contacts | MS60024/05E 2019-03
6.2 Floating contacts – MIP
Start request for auxiliary drives
The contact is switched on during a start sequence. When the engine meets the operating conditions, the
run-on timer is activated. When the genset is stopped again, the run-on timer for the auxiliary drives switches
in. This cools the engine. The contact is not switched off again until the run-on time has expired.
• The auxiliary drives are always switched off in the event of a "manual EMERGENCY STOP" (safety chain
has triggered).
• The auxiliary drives are also activated once for a run-on cycle if a PT1000 / PT100 temperature (e.g. en-
gine coolant temperature, intake air temperature, etc.) has been exceeded. The aim is to remove any heat
that might have become trapped and returning the engine to readiness for starting.
Open back-up switch
The contact closes if the fault message "088 - generator circuit breaker will not open -- trailing mode active"
is pending. Optionally, the contact can be activated with fault message "087 - generator circuit breaker will
not open."
Manual EMERGENCY STOP to outside
The contact opens if the safety chain of the manual EMERGENCY STOP is triggered.
TIM-ID: 0000061936 - 001
MS60024/05E 2019-03 | Floating Contacts | 27
6.3 Floating contacts – MMC
Ready-to-operate for external selection
This contact remains closed if the following criteria are met:
• Key switch set to enable genset
• Key switch set to remote
• Key switch set to automatic
• No stop or EMERGENCY STOP pending
• Engine stationary and no start command pending
Group fault
The contact opens if a stop or an EMERGENCY STOP is pending. Only notifications activated accordingly in
the fault message parameters are effective.
Engine running
The contact is closed as soon as the engine reaches a speed in excess of 1000 rpm (MMC4000) or
1400 rpm (MMC400).
Manual EMERGENCY STOP to outside
If the safety chain of the manual EMERGENCY STOP is triggered, the contact opens.
TIM-ID: 0000061938 - 001
28 | Floating Contacts | MS60024/05E 2019-03
7 Operation and Visualization - General
Information
7.1 Selector switch / pushbutton / EMERGENCY STOP
Switchgear
Designation Type of switch Position Action
Enabling genset opera- Key switch 0 Disabled
tion 1 Enabled
This switch is used to halt genset operation. If the machine is at a standstill, start-up of the genset is pre-
vented. If the machine is running, a controlled shutdown is activated.
Designation Type of switch Position Action
Local / Remote control Key switch 0 Local control
1 Remote control
This switch is used to set the control mode. If the plant is to be controlled directly at the genset, the switch
must be set to “Local”. This will then allow any target value to be altered at the IPC.
Also, the “Start/Stop” switch at the control cabinet will be active. If the plant is to be controlled remotely
(remote starting/stopping, remote target value control, control via interface), the switch must be set to
“Remote”.
Mixed control is not possible. For example, it is not possible to have the start request via hardware signals
and the power specification via the interface. In this case, both signals must be specified via the interface.
Designation Type of switch Position Action
Manual / Automatic Key switch 0 Manual mode
mode 1 Automatic mode
In automatic mode, the start process is initiated following a start command, the genset is synchronized
with the grid automatically and the power is raised (ramped up) to the set value. All regulating tasks are
performed automatically.
In manual mode, the start process is initiated following a start command. The genset starts up and remains
in a ready-to-synchronize state once the nominal speed is reached. During this phase, the speed can be
adjusted manually (higher/lower pulses via buttons on the display). Another button (on the display) can be
used to initiate the synchronization process. After successful synchronization with the grid, a power of 10%
is specified. The target value has to be adjusted manually. All regulating tasks are performed automatically.
Requirement for manual mode: “Local control” setting
Designation Type of switch Position
Start request Key switch 0/1
This switch can be used to start the engine in local mode. The “Local / Remote control” key switch must
TIM-ID: 0000061943 - 003
be set to “Local”.
Designation Type of switch Position Action
Enabling of grid backup Key switch 0 Disabled
mode 1 Enabled
Optional: This switch can be used to enable the automatic grid backup mode. If enabled, the grid backup
mode is initiated automatically in the event of a grid failure or grid circuit breaker failure (optional) in auto-
matic mode. In manual mode, the generator and power supply circuit breakers can be operated manually
(open/close).
MS60024/05E 2019-03 | Operation and Visualization - General Information | 29
Designation Type of switch Position Action
Grid failure test Key switch 0 No test
1 Initiation of test
Optional: This switch is used to allow a grid failure test to be performed. When set to the “1” position, one
phase of the grid measuring voltage is interrupted. A reaction is triggered according to setting of the “Ena-
ble grid backup mode” key switch. In the enabling position, grid backup operation is initiated.
Designation Type of switch Position
Reset Pushbutton –
This pushbutton is used to clear current fault messages. The safety relays drop out if an EMERGENCY STOP
is active. The safety relays and the corresponding fault messages can be activated and cleared only using
this button. Only fault messages for which no relays have to be activated can be cleared via the display (R
button).
Designation Type of switch Position
EMERGENCY STOP Pushbutton –
Pressing the EMERGENCY STOP pushbutton results in the manual EMERGENCY STOP sequence being trig-
gered immediately. All drive units and the genset are deactivated immediately. The EMERGENCY STOP se-
quence cannot be reactivated until the switch has been unlocked (using a key) and the reset pushbutton
has been pressed.
TIM-ID: 0000061943 - 003
30 | Operation and Visualization - General Information | MS60024/05E 2019-03
7.2 Display
All values read in by the genset and the system can be displayed on the touch screen.
The display comprises various menus and is designed for touch operation. A keyboard and mouse are not
required for any of the operations. Entries can also be made via software keyboards. Various menus, parame-
ters and switches are only enabled for specific users (a gray background indicates that they are disabled).
NOTE
A user needs to log on to perform operations and enter parameters.
TIM-ID: 0000061941 - 001
MS60024/05E 2019-03 | Operation and Visualization - General Information | 31
7.3 Parameter entry
All necessary parameters for the system can be modified via the display. Parameters are indicated by a red
font color. Click a parameter to open a data entry window.
Press "Enter" to confirm an entry.
The entry range is monitored for all parameters. If the entry is outside the entry range, the upper or lower
limit is applied automatically.
TIM-ID: 0000061939 - 001
32 | Operation and Visualization - General Information | MS60024/05E 2019-03
7.4 Description of the menu bar
Function keys in the menu bar
The upper area contains the function keys that are valid for all presentations. All commands required for op-
eration of the software are explained. The remaining information texts can be looked up in Appendix A
(→ Page 133).
Figure 1: Function keys
1 Home button Home button
2 Help button Help button
3 Fault messages button Fault messages button
• E: EMERGENCY STOP • N: EMERGENCY STOP
• S: Stop • S: Stop
• A: Alarm • A: Alarm
4 Start request Start request
5 Time and date button Time and date button
6 Main menu Main menu
7 Login button Logon button
TIM-ID: 0000061944 - 003
8 Country flag button Country flag button
Home
Symbol Designa- Explanation
tion
(→ Figure 1) Home Home With this button, you can return to the previous page.
button (1) Keep pressing this button until you reach the "main menu".
MS60024/05E 2019-03 | Operation and Visualization - General Information | 33
Help button in the main menu
You can call up the version number of the current display and of the control program on the PLC via the main
menu Help button.
Figure 2: Version information
1 Version list Version overview
Language selection
Symbol Designation Explanation
Country flag Language You can switch the language with this button. Two languages (Eng-
selection lish, German) are supported by default. The local language can be
incorporated optionally as a third language.
The national flag of the active language is displayed.
NOTE
Only possible from the main menu.
TIM-ID: 0000061944 - 003
Fault message
Symbol Designation Explanation
(→ Figure 1) Function Fault mes- This button indicates that a fault message is pending. Each of
keys sage these buttons is linked to a group fault message. When one of the
Fault message button buttons is pressed, the window switches to the fault message win-
(3) dow.
34 | Operation and Visualization - General Information | MS60024/05E 2019-03
There are three different types of fault message:
• EMERGENCY STOP (N):
System is shut down immediately, e.g. when the EMERGENCY-STOP button is pressed.
• Stop (S):
System is stopped. This can happen due to an "immediate stop" or "controlled stop".
Immediate stop: The circuit breaker is opened without delay.
Controlled stop: Genset is removed via power ramp.
• Alarm (A):
An alarm has occurred that does not initiate a genset shutdown.
The following states apply for all three buttons:
• No alarm pending:
The button is "blue".
• New unacknowledged alarm pending:
The EMERGENCY STOP (N) and stop (S) buttons flash "red".
The alarm (A) button flashes "yellow".
• Alarm pending and has already been acknowledged:
If a group alarm is pending and the operator has already acknowledged it (by pressing the "Reset" button),
the EMERGENCY STOP (N) and stop (S) buttons light "red".
The alarm (A) button lights "yellow".
Start request
Symbol Designation Explanation
(→ Figure 1) Function Start request When this button is pressed, all start conditions for automatic
keys mode are listed.
Start request (4) If the start condition is met (e.g. gas tank enables the system),
the LED for the gas tank turns green (otherwise it is red).
This means that you can quickly tell which start condition re-
mains to be met.
• If this button lights red, no start request is pending at this time.
• If this button lights green, a start request is currently pending (e.g. remote control and remote start com-
mand).
TIM-ID: 0000061944 - 003
MS60024/05E 2019-03 | Operation and Visualization - General Information | 35
Figure 3: Start request
1 Start conditions Start requirements
NOTE
Only possible from the main menu.
Time and date button
Symbol Designa- Explanation
tion
(→ Figure 1) Function Time This button is used to set the time of day and date on the control
keys Date system and the IPC. The project name is displayed.
Time and date button (5)
If you click this button, the display window for setting the time and date appears.
On this page the time and date can be set in the control system and in the IPC.
This time is important for time-stamping the fault message. Data is entered in the red boxes and then trans-
TIM-ID: 0000061944 - 003
ferred to the control system by pressing the "Set time" button.
If the transfer was successful, the current time of day (the set values) appears at the top and the seconds
counter is running.
NOTE
Only possible from the main menu.
36 | Operation and Visualization - General Information | MS60024/05E 2019-03
7.5 Logon
General
Symbol/Desig- Meaning
nation
Logon This button is used to log on as a specific user. Various parameters and menus are ena-
bled depending on which user has logged on.
Log on by entering the user name and password
For this logon method a user name and a password must be entered.
Default user and password: You will receive this information separately from the operating instructions.
Sequence:
• Press the "Logon" button in the main menu.
• Logon form opens
Figure 4: Logon form
1 User User
TIM-ID: 0000061937 - 004
2 Password Password
3 Logoff Logoff
4 Login Logon
5 Cancel Cancel
MS60024/05E 2019-03 | Operation and Visualization - General Information | 37
• Enter the "User" and "Password" (complete the relevant fields).
• Select "Logon" on the logon form.
• The current user is displayed in the status bar (level and logout time).
• The window is closed automatically after a short period.
• The user is logged out automatically after a specific period of time.
• If an incorrect entry is made, the message "Wrong User or Password" appears in the status bar.
• When the "Logoff" button is actuated, the currently logged-in user is logged off.
Logon by hardware USB dongle (optional)
This logon method does not require a user and password to be entered. Plug a USB dongle into the USB port
on the front of the IPC and press the "Logon" button on the logon window. The computer checks the dongle
and then activates the access level saved on the dongle. As long as the dongle remains plugged in, the user
will not be logged off automatically. If the dongle is removed, the user will be logged off within 60 minutes.
Checking of the validity period: After a user has logged on per USB dongle, the logon form is displayed.
On the logon form, the validity period of the dongle can be read out. If the logon form closes too quickly after
logon, the logon window can be opened again by pressing the Logon button on the main menu.
TIM-ID: 0000061937 - 004
38 | Operation and Visualization - General Information | MS60024/05E 2019-03
7.6 Operation and visualization – Main menu
The main menu appears automatically when the IPC starts up.
This view is the uppermost level of the visualization.
The various submenus can be selected with the menu buttons.
The following submenus are available for selection here:
• System overview
• Engine overview
• Electrical data
• Water system
• Gas system
• Oil system
• Fault messages
• Operating messages
• Power control
• Start/stop sequence
• Counter reading
• Additional functions
• Cleaning window
• Service menu
Additional buttons are available as reserve buttons for further submenus.
TIM-ID: 0000061945 - 001
MS60024/05E 2019-03 | Operation and Visualization - General Information | 39
7.7 System overview
The system overview varies from project to project. System-specific data are displayed on this page.
Essential system-specific data:
• Switch type
• State
• Auxiliary drives
• Active control
• Control cabinet temperature
• Battery status
• Exhaust gas temperature
TIM-ID: 0000061946 - 001
40 | Operation and Visualization - General Information | MS60024/05E 2019-03
7.8 Counter reading
The counter reading can be displayed here. To do this, press the "Counter reading" button.
Figure 5: Counter reading
1 Counter Counter
2 Unit Unit
3 Value Value
Some of the counter readings are optional (gas quantity, current counter, heat quantity, steam, reserve).
These counters are evaluated based on a pulse signal. Here, the pulse value for each pulse is added up. This
is specified in the module parameters. In addition, a backup of the last 365 days is saved, with the most
important operating values being date stamped. In the case of evaluation based on an analog signal, only the
current consumption is displayed.
NOTE
The desired counter values can be set using the "Settings" button. A desired counter
reading value can be entered in the "Setpoint" input field.
When the "Reset" button is pressed, this value is applied as the current counter read-
ing.
TIM-ID: 0000061942 - 003
MS60024/05E 2019-03 | Operation and Visualization - General Information | 41
8 Operation and Visualization - Main Menu
8.1 Engine overview
This screen shows an overview of all sensors and measured values associated with the engine as appropriate
for the particular type of engine.
The parameters displayed:
• Engine parameters
• Exhaust temperatures of the individual cylinder
• Mixture parameters
• Power control
The parameters displayed for the engine:
• Speed
• Coolant temperature before engine
• Coolant temperature after engine
• Coolant pressure before engine
• Coolant pressure after engine
• Lube oil pressure
• Lube oil temperature
• Crankcase pressure
• Intake air
• P-intake air B
The parameters displayed for the mixture:
• Mixture temperature
• Mixture pressure
• Position of the restrictor flaps
The displayed parameters of the power control:
• Setpoint value in %
• Actual value in %
• Actual value in kW
TIM-ID: 0000061948 - 001
42 | Operation and Visualization - Main Menu | MS60024/05E 2019-03
8.2 Electrical data
All important AC generator and grid data is displayed on this interface.
The overview and data are dependent on the selected options (e.g. with grid backup).
Figure 6: Electrical data
1 Mains failure Grid failure
2 Load steps Load stages
3 PMM EMM
4 Voltage-/power factor controller Voltage regulator / power factor controller
5 Grid code Grid code
From this interface, it is possible to operate the GCB manually (optionally also the mains circuit breaker with
grid backup systems).
The following preconditions must be met:
• "Remote/Local" key switch set to "Local"
• "Manual/Automatic" key switch set to "Manual"
• Authorized user logged on
TIM-ID: 0000061949 - 003
• The MCB can only be switched manually on a system that supports grid backup operation.
Precondition: The "Grid backup operation" key switch is set to "1".
GCB:
The "Close" button causes the circuit breaker, with closed mains circuit breaker, not to be turned on out of
sync. The circuit breaker cannot be closed at a standstill.
Mains circuit breaker:
The "Close" button causes the grid switch, with closed mains circuit breaker, not to be turned on out of sync.
MS60024/05E 2019-03 | Operation and Visualization - Main Menu | 43
8.3 Grid code (optional)
The following grid code functions can optionally be selected:
• Reduction of power depending on the line frequency (P(f) function)
• Power increase depending on the line frequency (P(f) function)
• Power reduction (derating) with underfrequency
• Reduction of power which is specified by the utility service provider
• Power ramp after a grid failure
• Power factor / Reactive power adjustment
• Selection of the reactive power function via the telecontrol interface
One of the following optional functions can be selected for adjusting the reactive power:
• Fixed power adjustment factor (fixed value or analog value)
• Fixed power adjustment factor(P)
• Fixed power adjustment factor Q(P)
• Fixed reactive power in MVar (fixed value or analog value), also with voltage limitation
• Reactive power characteristics / Voltage characteristics Q(U)
• Function for determining the reactive power adjustment time
The active function for power factor adjustment is displayed in the "Active power factor function" text field in
mains parallel operation.
If the functions Cosphi(P) Q(P) Fixed reactive power in MVar with voltage limitation, function for determination
of the reactive power adjustment time or Q(U) are active, the respective function is visualized by a character-
istic curve.
Parameters:
Designation Unit Meaning
Power factor None If the "fixed power factor" option is selected, a fixed power factor value can be
specification set here.
Reactive power kVAr If the "fixed reactive power" option is selected, a fixed reactive power value
specification can be set here.
Actual values:
Designation Unit Meaning
Power factor set- – Setpoint that is transferred to the power factor controller
point
Reactive power kVar Reactive power setpoint that is calculated from the power factor setpoint.
specification
Allowed power % It is possible to detect here if the actual power output is limited due to a grid
supporting function (e.g. P(f) function)
Power factor – Power factor actual value
Reactive power kVar Reactive power actual value
TIM-ID: 0000061947 - 002
Effective power % Actual value active power
output
Grid voltage V Grid voltage actual value
44 | Operation and Visualization - Main Menu | MS60024/05E 2019-03
8.4 Load stage control (optional)
Load shedding control can be activated in grid backup mode.
Up to 8 repair sizes can be activated with the Series 400 or 24 repair sizes with the Series 4000. If the grid
backup is initiated, the control system issues the "Load shedding" command.
Only when registered that the load shedding has been carried out successfully ("Load shedding" LED) does
the grid backup continue and the GCB is closed.
As soon as the GCB signals that it is closed, the stages are switched back in at staggered intervals. The re-
pair sizes continue to be switched in until the last repair size has been activated or an overload (optional
evaluation) occurs.
Staggered switching-in of load stages enables the engine to optimize load regulation.
• All load stages are switched back in at standstill or when the grid switch is closed.
• "Load shedding successful" checkback signal:
All checkback signals for the individual stages are connected in series.
• Stages for which a delay time of "0" has been entered are not shed (even in the event of an overload).
The load stage contactors have to be controlled so that the contactors switch in when the coupling relay
drops out.
This ensures that power will continue to be supplied to the consumers, even in the event of the control
system being affected by a failure or repair work.
With overload monitoring:
If the "Overload monitoring" option has been activated, power values can be assigned to the individual
stages.
If the current genset power actual value is > (power value (of the repair size currently switched in) + overload
limit value), a time delay expires.
At the end of this time a fault message is output (overload in grid backup mode) and a repair size is shed.
This process is repeated until the load returns to a value that does not reach the limit value, or the last stage
that can be shed has been shed. The stages are not switched back in until the fault message has been ac-
knowledged if the load still exceeds the limit value.
If the extent of the load connected is so great that the genset shuts down due to underfrequency, this moni-
toring mechanism will not function.
Monitoring also ensures that the next stage is not switched if the load to be expected exceeds the permissi-
ble load for grid backup mode. If this is the case, the fault message is also output and the next stage is not
switched in.
Series Delay Unit Meaning
Series 1–8 s The corresponding load stage is not switched in until the time interval
400 has expired. The next interval then runs, and a second stage is switch-
Series 1–24 s ed in.
4000 Special feature: Stages with a delay time of 0 s are not shed. Howev-
er, these steps may only be defined at the start (e.g. step 1 and
step 2). As soon as a delay time has been defined for a step (e.g.
TIM-ID: 0000061950 - 001
step 3), a delay time of 0 s cannot be entered for any subsequent step
(e.g. step 4).
Example for 4 load stages:
Correct: Stage 1 = 0 s, stage 2 = 0 s, stage 3 = 10 s, stage 4 = 10 s
Incorrect: Stage 1 = 0 s, stage 2 = 0 s, stage 3 = 10 s, stage 4 = 0 s
In the incorrect example, all delay times would then be set to the de-
fault value of 2 seconds.
This is done automatically by the system.
MS60024/05E 2019-03 | Operation and Visualization - Main Menu | 45
Optional parameters for overload monitoring:
Parameter Unit Meaning
Power value % A maximum permissible power value is assigned to each stage. The power to
be expected should not exceed this value. If the values entered exceed 100 %,
a default setting is applied (30/30/30). This is done automatically by the sys-
tem.
Overload limit % This value is added to the total power value (sum of all active stages). If the
current power actual value exceeds the limit value calculated in this way, once
the overload delay has expired, a fault message is sent and the step is shed.
Overload delay % If the calculated overload limit is exceeded, this time interval expires. Once the
interval has expired, the "Overload in grid backup" fault message is output and
the stages are shed as described above.
TIM-ID: 0000061950 - 001
46 | Operation and Visualization - Main Menu | MS60024/05E 2019-03
8.5 Energy Measurement Module EMM
Figure 7: EMM
1 Synchronization Synchronization
2 Voltage Voltage
3 Frequency Frequency
4 Current phase Current phase
5 Generator Generator
6 Bus bar Busbar
7 Mains Grid
8 Gen. voltage phase Gen. voltage phase
All measurement data from the energy measurement module that is not displayed on the main "Electrical
data" page can be read here.
TIM-ID: 0000061951 - 003
MS60024/05E 2019-03 | Operation and Visualization - Main Menu | 47
8.6 Voltage regulator / power factor controller
Figure 8: Voltage regulator / power factor controller
1 Voltage controller Voltage regulator
2 Power factor controller Power factor controller
Variable adjustment of the voltage and the power factor is possible through the MMC. The generator voltage
regulator controls the voltage or the power factor through an analog setpoint specification of the MMC. The
setpoints for the regulator and the corresponding control parameters can be set via the visualization.
When the genset has started and a set generator voltage is exceeded, the voltage regulator is active. The
voltage is now adjusted to a specified setpoint. During synchronization, automatic voltage adjustment to the
grid to be synchronized is carried out. When the genset is in sync with the grid, the voltage is fed to the grid.
Thus a power factor can be controlled by the power factor controller.
In grid backup/isolated operation, the voltage is controlled to a specified setpoint.
Parameters for voltage control:
Parameter Unit Explanation
Specified value V The setpoint required for grid backup/isolated operation is set here.
TIM-ID: 0000062022 - 003
Kp – Proportional component of the controller.
Tn s Follow-up time of the controller.
Approved / Not V If the generator reaches this voltage and the time for "On-delay" has expired,
approved the voltage regulator is activated.
On-delay s If the generator reaches the enable voltage and this time has expired, the
voltage regulator is activated.
48 | Operation and Visualization - Main Menu | MS60024/05E 2019-03
Parameter Unit Explanation
Low voltage ramp V/s Maximum speed for a setpoint change (low voltage).
setpoint
Medium voltage kV/s Maximum speed for a setpoint change (medium voltage).
ramp setpoint
Parameters for power factor control:
Parameter Unit Explanation
Specified value – The required setpoint is set here.
Kp – Proportional component of the controller.
Tn s Follow-up time of the controller.
Approved / Not % Start value of the power from which the control begins.
approved
Parameters for the setpoint:
Parameter Unit Explanation
Start % Start value with which the control system begins to control after the control-
ler enable.
TIM-ID: 0000062022 - 003
MS60024/05E 2019-03 | Operation and Visualization - Main Menu | 49
8.7 Generator data
If the "Generator" button is pressed, additional analog values can be called up by the generator.
The following generator data are displayed:
• Phase currents
• Power
• Effective power output
• Reactive power
• Power factor
• Phase voltages
• Temperature of the generator windings
• Bearing temperatures
The module for power reduction can also be called up.
TIM-ID: 0000062023 - 001
50 | Operation and Visualization - Main Menu | MS60024/05E 2019-03
8.8 Power reduction (optional)
The current electrical generator power of the generator in the mains parallel operation can be reduced with
this function. Power reduction by the generator if the required electric power depending on the generator
voltage (corresponds to the grid voltage in mains parallel operation), the power factor and the cooling air
temperature can no longer be made available to the fullest extent.
The corresponding nominal apparent power is assigned to the respective generator voltage in the "Generator
nominal data" diagram. Such data must be obtained from the generator manufacturer.
Parameters for generator nominal data:
Parameter Unit Meaning
X1 V Generator voltage value for nominal apparent power value Y1
Y1 kVA Nominal apparent power value for generator voltage value X1
X2 V Generator voltage value for nominal apparent power value Y2
Y2 kVA Nominal apparent power value for generator voltage value X2
X3 V Generator voltage value for nominal apparent power value Y3
Y3 kVA Nominal apparent power value for generator voltage value X3
X4 V Generator voltage value for nominal apparent power value Y4
Y4 kVA Nominal apparent power value for generator voltage value X4
X5 V Generator voltage value for nominal apparent power value Y5
Y5 kVA Nominal apparent power value for generator voltage value X5
A VTC reduction factor can be assigned to the respective cooling air temperature on the generator in the
"Cooling air power reduction" diagram.
Output values
Available power:
• The maximum available apparent power(kVA) and the actual power output (kW) are displayed.
• Available apparent power (kVA) = nominal apparent power (generator voltage) * VTC reduction factor
• Available actual power output (kW) = available apparent power (kVA) * power factor
Reduced power:
• If the current generator actual power output exceeds the available effective power output, the power is
reduced. The amount of reduction is displayed here.
Actual value:
• The current data of the generator are displayed here.
TIM-ID: 0000062024 - 001
MS60024/05E 2019-03 | Operation and Visualization - Main Menu | 51
8.9 Water system
All sensors and drives for the water/hydraulic system are included on this interface.
It is split into two areas:
• Heating water
• Coolant
The various functions are optionally activated or deactivated.
The pumps can be operated manually.
Figure 9: Water system
1 Heating water pump FC Hot water pump FC
2 Auxiliary drives Auxiliary drives
3 Cooling water pump Coolant pump
4 Manual Manual
5 Start Start
6 Stop Stop
7 Heating water temperature Hot water temperature
TIM-ID: 0000062025 - 004
8 Control valve Regulating valve
It is also possible to switch to the optional water temperature controller from this interface. To do so, the
regulating valve is actuated.
Parameters for run-on time of the auxiliary drives:
Parameter Unit Meaning
Run-on time min The auxiliary drives start running immediately during the start process and keeping
running for this adjustable time after stopping.
52 | Operation and Visualization - Main Menu | MS60024/05E 2019-03
Parameters for run-on time of the engine coolant pump(s):
Parameter Unit Meaning
Run-on time min The engine coolant pump(s) start(s) running immediately during the start process
and keeping running for this adjustable time after stopping.
Preheating:
With genset preheating, it is possible to keep the engine coolant temperature in an adjustable range.
• Internal preheating via installed heating cartridges
With active preheating, the engine coolant pump is also activated.
Warm-up ramp (hold value) - optional:
After switching in the GCB, the power ramp is increased to an adjustable value using this function. The ramp
is only continued if the engine coolant temperature has exceeded a likewise adjustable limit value.
Parameters for warm-up ramp:
Parameter Unit Meaning
Power setpoint % If the hold point is activated for the setpoint ramp, the power setpoint remains
at this set value until the engine coolant temperature after the engine has
reached the setpoint. Only then is the power setpoint increased further.
Engine coolant °C The ramp is only continued after reaching the set temperature.
after engine
NOTE
All functions are only active in automatic mode.
TIM-ID: 0000062025 - 004
MS60024/05E 2019-03 | Operation and Visualization - Main Menu | 53
8.10 Gas system
The following configurations of the gas systems are possible:
• Single-gas operation
• Two-gas operation with two gas trains
• Two-gas operation with one gas train
TIM-ID: 0000062026 - 001
54 | Operation and Visualization - Main Menu | MS60024/05E 2019-03
8.11 Gas system – Single-gas operation
Single-gas operation
The optional gas compressor can be selected and the gas leak test activated from this page.
Figure 10: Gas system
1 Valve Valve
2 Safety shut-off valve Safety shutoff valve (SAV)
3 Gas compressor Gas compressor
4 Tecjet Tecjet
5 Gas leakage test Gas leak test
Safety shutoff valve (SAV)
• The SAV is closed immediately upon a manual EMERGENCY STOP (hardware and software)
• The SAV is closed immediately upon a gas or fire alarm (hardware and software)
• Manual mode is possible for test purposes during a genset standstill
TIM-ID: 0000062027 - 003
MS60024/05E 2019-03 | Operation and Visualization - Main Menu | 55
8.12 Gas system – Two-gas operation with only one gas train
(optional)
No enable.
TIM-ID: 0000062028 - 001
56 | Operation and Visualization - Main Menu | MS60024/05E 2019-03
8.13 Gas system – Two-gas operation with two gas trains (optional)
No enable.
TIM-ID: 0000062029 - 001
MS60024/05E 2019-03 | Operation and Visualization - Main Menu | 57
8.14 Gas compressor (optional)
The gas compressor is activated in the event of a start request.
After expiry of the activation delay (the time it takes to build up a gas pressure), further starting of the engine
start is enabled.
When the engine is stopped again, the gas compressor runs on for an adjustable time (from "Gas valves
closed").
Parameters for gas compressor
Parameter Unit Meaning
Switch-on de- s Time that must expire before further starting of the engine is continued.
lay
Off delay s The gas compressor runs on for this time.
Time runs from closing of the gas valves.
Type of gas – In a two-gas system, the compressor must be assigned the gas type. This is
required in order to start the compressor with the corresponding gas type.
The same applies to switch-over:
1 = gas type A
2 = gas type B
TIM-ID: 0000062030 - 001
58 | Operation and Visualization - Main Menu | MS60024/05E 2019-03
8.15 Gas compressor via frequency converter (optional)
The gas compressor is activated upon a start request.
After expiry of the activation delay (the time it takes to build up a gas pressure), further starting of the engine
start is enabled.
When the engine is stopped again, the gas compressor runs on for an adjustable time (from "Gas valves
closed").
Parameters for frequency converter:
Parameter Unit Meaning
Start ramp mbar/s When the gas compressor is activated, the start setpoint of 0 mbar is increased
to the actual setpoint via this ramp.
Setpoint mbar This parameter corresponds to the setpoint for the control.
Kp – Proportional component of the controller. Depending on the mbar deviation, the
manipulated variable is increased or decreased by this factor (e.g. system devia-
tion +5 mbar, KP = 6: The proportional component of the manipulated variable is
30%).
Ki – Integral component of the controller. If the system deviation persists, whenever
the follow-up time (Tn) expires, the Ki value is added to the P component and
output. A high Ki value may result in oscillation of the setpoint for the frequency
converter.
Tn s The follow-up time is used to calculate the I component. The output value of the
I controller is then added to the output value of the P controller at these inter-
vals. A follow-up time that is too low may result in oscillation of the setpoint for
the frequency converter.
Manual set- % If manual mode is active, this setpoint is output to the frequency converter.
point
Min. manipu- % During operation, the gas compressor is only closed up to this manipulated vari-
lated variable able.
TIM-ID: 0000062031 - 001
MS60024/05E 2019-03 | Operation and Visualization - Main Menu | 59
8.16 Gas leak test
Figure 11: Gas leak test
1 Gas line Gas line
2 Release Approved / Not approved
3 Manual Manual
4 Successful Successful
5 Gas valve open Gas valves open
The gas leak test can be carried out manually when the machine is stopped.
The "Manual" button is selected for this. It then becomes orange.
The test can now be initiated with the "Enable" button.
TIM-ID: 0000062032 - 003
60 | Operation and Visualization - Main Menu | MS60024/05E 2019-03
8.17 Oil system
This interface displays an overview of the lube oil supply.
It is split into the following areas:
• Lube oil replenishment for genset (standard)
• Controller for used oil pump
• Controller for fresh oil pump (optional)
Figure 12: Oil system
1 Lube oil refill Oil replenishment
2 Selection Selecting
3 Lube oil pump Lube oil pump
4 Lube oil properties Lube oil properties
5 Waste/Prelube oil pump Used oil/oil priming pump
6 Waste oil solenoid valve Used oil solenoid valve
Oil replenishment:
TIM-ID: 0000062033 - 004
The automatic oil replenishment system is activated following a request from the engine governor ADEC. To
bridge the response time between the refill solenoid valve opening and the oil level monitor responding, the
solenoid valve is controlled as follows:
With the request from the engine governor ADEC, the solenoid valve is opened for the opening duration Tö. It
is then closed for the pause duration Tp. The Tö period is then initiated again.
This interplay repeats itself until the request from the engine governor ADEC is canceled.
The number of requests from the engine governor ADEC can be read off at the oil refill counter.
MS60024/05E 2019-03 | Operation and Visualization - Main Menu | 61
Parameters for oil refilling:
Parameter Unit Explanation
Tö s Opening duration for solenoid valve
Tp s Pause duration for solenoid valve
Used oil pump:
The used oil pump can be operated via the control system. There are two methods of activation:
The following buttons are available:
• Local operation via visualization: Activate manual button
• Remote operation via key switch (optional)
Functional description:
The used oil pump can be selected on the visualization.
The following buttons are available:
• Manual
• Start / Stop
Manual mode (press the "Manual" key):
When start is pressed, pumping is carried out until the pump can be switched off manually.
Lube oil pump (optional):
The lube oil pump can be operated via the control system. There are three methods of activation:
The following buttons are available:
• Automatic mode for oil refilling
• Local operation via visualization: Activate manual button
• Remote operation via key switch (optional)
Functional description:
The lube oil pump can be selected on the visualization.
The following buttons are available:
• Oil pan and remote tank
• Manual / Start / Stop
Automatic mode for oil replenishment:
The lube oil pump is activated at the same intervals as the solenoid valve.
Manual mode (press the "Manual" button):
Filling the oil pan:
• When buttons "Oil pan" and "Start" are activated, pumping continues until the "Level < min." contact is no
TIM-ID: 0000062033 - 004
longer active. For this purpose, the lube oil pump must be set to manual mode. Following this, the pulse
filling is activated until the "refill" contact is no longer active or the "Level > max." contact responds. The
pump can also be switched off manually.
Filling and draining the remote tank:
• When the buttons "Remote tank" and "Start" are actuated, pumping continues until the pump is manually
switched off. For this purpose, the lube oil pump must be set to manual mode.
Used oil solenoid valve:
The used oil solenoid must be activated in order to drain the engine oil pan.
62 | Operation and Visualization - Main Menu | MS60024/05E 2019-03
It can be selected using the following buttons in the visualization:
• Manual
• Start / Stop
Manual mode (press the "Manual" button):
When start is pressed, the used oil solenoid valve remains activated until it can be switched off manually.
TIM-ID: 0000062033 - 004
MS60024/05E 2019-03 | Operation and Visualization - Main Menu | 63
8.18 Fault messages
This interface provides an overview of pending fault messages.
It is also possible to switch to the Alarm Logger. The Logger records all fault and operating messages over a
prolonged period with time stamping. This also makes it easier to analyze faults.
Functionality:
The window opens automatically when a new fault message appears.
If a new fault message arrives, the corresponding collective message flashes in the menu bar (e.g. N flashes
red: there is a new EMERGENCY STOP). The fault messages can be acknowledged with the Reset button.
When the fault message is no longer pending, the text disappears.
• Stopped fault messages appear in red
• Non-stopped fault messages appear in yellow
Acknowledged fault messages are displayed in the "Quit" column by the "x" symbol.
The fault message window can be exited with the Home button.
The fault message window is then only opened again if a new fault message occurs or is selected via the N,
S, A buttons.
• The fault messages are included in a separate list.
• In some cases, there are system-specific messages that also appear there.
• The list is always compiled based on the project.
For the fault message overview, there are two important differences in the faults:
1. Self-acknowledging faults:
These faults are automatically reset after remedying the cause and deleted from the fault message over-
view.
2. Non-self-acknowledging faults:
These faults can only be reset by the user after remedying the cause by actuation of the Reset button
(on the control cabinet or on the fault message page).
• Fault messages which trigger the EMERGENCY STOP chain can only be acknowledged using the hardware
reset (button on the MMC cabinet).
The "Source" column is only of interest for systems with several gensets and central fault history as the gen-
set number is played back in order to decide which genset has the fault.
If the number of faults is so large that not all faults can be displayed in the table, the arrow buttons on the
right of the table can be used for scrolling up and down.
• Previously cleared faults can also be retrieved using the Alarm Logger. TIM-ID: 0000062034 - 001
64 | Operation and Visualization - Main Menu | MS60024/05E 2019-03
8.19 Status signals
This interface provides an overview of all pending status messages (engine coolant pump is on, generator
switch is off etc.).
The image structure is identical with that of the fault messages. Each active status message appears in
green.
The Alarm Logger can also be called up here.
TIM-ID: 0000062035 - 001
MS60024/05E 2019-03 | Operation and Visualization - Main Menu | 65
8.20 Alarm Logger
Screen page
Figure 13: Alarm Logger
1 Start Start
2 Filter Filters
3 Save Save
Switching to the "Alarm Logger" screen page is possible using the Alarm Logger button in the fault message
or operating message window. The fault history is displayed here.
When switching to the Alarm Logger page, the fault database is run through, and the coming and going of
faults in the last 24 hours is displayed.
If a fault has gone, the fault message is appended with "Gone!" and displayed.
The "Source" column only applies to systems with several gensets and the central fault history. The genset
number is played back here in order to decide which genset has the fault.
If the number of messages is so large that not all messages can be displayed in the table, the arrow buttons
on the right edge of the table can be used for scrolling up and down.
TIM-ID: 0000062036 - 003
Start button:
A new search run is started using the Start button.
Filter button:
The Filter button opens a selection window in which the criteria for the search run in the database can be
set.
66 | Operation and Visualization - Main Menu | MS60024/05E 2019-03
Filter criteria
Figure 14: Alarm Logger
1 Kind ID
2 Messages-Type Message type
3 Save Save
4 Alarm number Alarm number
5 Days Days
There are four filter criteria. A criterion is only active when it changes to green.
Alarm type:
Here it can be set that only fault messages (SM), only operating messages (BM) or both message types
(SM + BM) are listed. The default setting is fault message (SM).
ID:
Here it is possible to select that only the occurrence of a fault, the disappearance of a fault, or both is dis-
played. The default setting is both.
TIM-ID: 0000062036 - 003
Alarm number:
If there is a search for the occurrence of a specific alarm, the search for an alarm number can be activated
using the "No. search". The searched-for number must also be entered in the box underneath. Up to 4 num-
bers can be selected. The numbers can be reset using the "Reset" button.
Days:
By default the database always searches for events of the previous day. The database can also be set to
search for older events in the upper box. The largest value is 31 days.
MS60024/05E 2019-03 | Operation and Visualization - Main Menu | 67
The value of the second box must always be 1. If there is a search for events with a specific period, e.g. 10 to
20 days ago, the value must also be changed in the second box. The value of the second box must always be
greater than the value of the first box. The value of "31" cannot be exceeded.
Save button:
This button can be used to copy the current database (AlarmloggerAktuell.mbd) into the "D:\MTU\FileShar-
ing" directory that is accessible to the customer.
TIM-ID: 0000062036 - 003
68 | Operation and Visualization - Main Menu | MS60024/05E 2019-03
8.21 Power controller
An overview of the entire power control system is displayed on the "Power controller" screen page.
All important states and online data of the power control are shown on the right side of the screen page.
Figure 15: Power controller
1 Manual Manual
2 Derating Power reduction
3 ok OK
4 Setpoint Specified value
TIM-ID: 0000062037 - 004
MS60024/05E 2019-03 | Operation and Visualization - Main Menu | 69
8.22 Power controller – Origin of the setpoint
The top line shows which operating state is selected:
• Location
• From remote
• Via interface
• Via timer
• Manual mode (in the manual mode box)
The corresponding LED lights and the applicable operating mode (setpoint origin) appears on a green back-
ground (e.g. slip value).
TIM-ID: 0000062038 - 001
70 | Operation and Visualization - Main Menu | MS60024/05E 2019-03
8.23 Power controller – Manual mode
Setting the power setpoint manually
The power setpoint can also be set manually.
To do so, the key switch must be set to "Manual mode" and operation to "Local". After changing over the key
switch, the "Manual" button turns orange. A "Manual value" can now be entered manually and accepted
when the OK key is pressed.
When the Manual mode is exited again, the key switch must be set back to "Automatic mode". The currently
applicable setpoint is adopted again.
Parameters for manual mode:
Parameter Unit Meaning
Manual val- % The value for Manual mode is accepted when the OK key is pressed.
ue
TIM-ID: 0000062039 - 001
MS60024/05E 2019-03 | Operation and Visualization - Main Menu | 71
8.24 Power controller – Automatic mode
Specified value
Value Meaning
1 Genset off
2 Slip value
3 Fixed value 1
4 Fixed value 2
5 Grid feed-in control
6 Gas tank control
7 CH4 control
8 Peak current – fixed at 100%
9 Heat mode
10 Heat mode (slipping)
11 Heat mode (zero load limiting)
12 Buffer mode – fixed at 100%
13 Primary balancing power
Local changeover:
The key switch must be set to "Local". When the corresponding key is pressed, the system changes over to
the required operating mode (e.g. slip value).
Changeover from remote (hardware):
There are a maximum of four digital inputs available for this which can activate (in the right combination) all
operating modes (binary coding).
Interface mode must not be active.
Changeover via interface:
The interface must be active and the corresponding data point must contain the required number.
Changeover by timer:
Changeover is time-controlled (see description of timer).
Valid setpoint:
Slip value:
TIM-ID: 0000062040 - 002
Two values are displayed:
• Local
This value is valid if the "Control" key switch is set to "Local". The setpoint can be entered directly.
• From remote
This value is valid if the "Control" key switch is set to "From remote". The setpoint is defined by a
4 to 20 mA signal. If controlled over the interface, the value is determined via the telegram.
72 | Operation and Visualization - Main Menu | MS60024/05E 2019-03
Fixed value 1 (optional)
Two values are displayed:
• Local
This value is valid if the "Control" key switch is set to "Local". The setpoint can be entered directly.
• From remote
This value is valid if the "Control" key switch is set to "From remote". The value (corresponds to "Local"
value) is requested by a digital input signal. If controlled over the interface, the value is determined via the
telegram.
Fixed value 2 (optional)
Two values are displayed:
• Local
This value is valid if the "Control" key switch is set to "Local". The setpoint can be entered directly.
• From remote
This value is valid if the "Control" key switch is set to "From remote". The value (corresponds to "Local"
value) is requested by a digital input signal. If controlled over the interface, the value is determined via the
telegram.
Grid feed-in control (optional)
When this operating mode is active, the current setpoint comes from the grid feed-in control.
(See additional functions)
Gas tank (optional)
When this operating mode is active, the current setpoint comes from the gas tank control.
(See additional functions)
CH4 control (optional)
When this operating mode is active, the current setpoint comes from the CH4 control.
(See additional functions)
Peak current (optional)
When this operating mode is active, the setpoint is set to 100%.
Heat mode (optional)
When this operating mode is active, the current setpoint comes from the heat control.
(See additional functions)
Heat mode slipping (optional):
When this operating mode is active, the current setpoint comes from the heat control.
(See additional functions)
TIM-ID: 0000062040 - 002
Heat mode with zero load limiting (optional)
When this operating mode is active, the current setpoint comes from the heat control.
(See additional functions)
Buffer mode (optional)
When this operating mode is active, the setpoint is set to 100%.
(See additional functions)
MS60024/05E 2019-03 | Operation and Visualization - Main Menu | 73
Primary balancing power (optional)
When this operating mode is active, the power setpoint is determined based on the grid frequency.
Positive and negative power must always be offered. The working point is the power point at which a grid
frequency of 50 Hz is run over the complete additional period.
In case of underfrequency, power is increased as a function of the frequency and the sold primary balancing
power; in case of overfrequency, power is reduced as a function of the frequency and the sold primary bal-
ancing power.
Power reduction:
This displays whether a power reduction is active or not. The reduction can be triggered by various factors:
• Engine
The power reduction is carried out by the ADEC governor. A corresponding reduction is signaled.
• Gas exchange (optional)
The power is reduced to a configurable value during the gas exchange. This value can even remain below
the genset's minimum load.
• Generator (optional)
Power reduction by the generator if the required electric power depending on the generator voltage (cor-
responds to the grid voltage in mains parallel operation), the power factor and the cooling air temperature
can no longer be made available to the fullest extent.
• Mixed coolant temperature inlet (limit value 1) (optional)
If limit value 1 (set with the fault messages) is exceeded, the power is reduced from 100% to minimum
load (50% by default) in a linear fashion along a ramp between limit value 1 and limit value 2. If, however,
the second limit value is still exceeded, the genset shuts down.
• Mixed coolant temperature outlet (limit value 1) (optional)
Reaction as for mixed cooling water temperature inlet.
• Hot water temperature inlet (limit value 1) (optional)
Reaction as for mixed cooling water temperature inlet.
• Hot water temperature outlet (limit value 1) (optional)
Reaction as for mixed cooling water temperature inlet.
• Grid code
A power reduction as a function of the grid frequency and a power reduction by the grid operating compa-
ny is signaled here.
• Dew point lower limit violation:
Power reduction if the temperature at the mixture coolant inlet is below the setpoint. A limit value curve
as a function of the dew point is stored.
TIM-ID: 0000062040 - 002
74 | Operation and Visualization - Main Menu | MS60024/05E 2019-03
8.25 Start/stop sequence
Screen page
The sequence can be observed on this page in the event of a start or stop. When the genset starts, the indi-
vidual start phases are active. Synchronization, speed and power adjustment can also be controlled manual-
ly.
Figure 16: Start/stop sequence
1 State Status
2 Speed adjustment Speed variation
3 Up Higher
4 Down Lower
5 Synchronization Synchronization
6 Power displacement Power adjustment
Manual mode:
• Key switch set to "Local"
TIM-ID: 0000062041 - 004
• Key switch set to "Manual"
• Activate local start request (key switch)
• The engine starts and remains at Phase 3 (Series 4000) or Phase 8 (Series 400) (no synchronization initi-
ated).
• The speed can now be influenced with the Higher/Lower key at idle speed.
• To initiate synchronization, the "Synchronization" key must be pressed.
In the Series 4000, an enable for synchronization must also be present from the MTU governor for syn-
chronization, see "Synchronization enable" display.
• When the generator switch is closed, 10% is automatically activated. The power can now be specified.
MS60024/05E 2019-03 | Operation and Visualization - Main Menu | 75
There are two methods of changing the power:
• Pressing the Higher/Lower keys and the corresponding typed value
• With an adjustable manual setpoint and the OK key
Parameters for Manual mode:
Parameter Unit Meaning
Typed value % The setpoint is changed by this value each time the Higher/Lower
(between the "Higher" keys are touched.
and "Lower" buttons)
Manual value % This is the value for Manual mode that is accepted when the OK key is
(left next to the "OK" pressed.
key)
TIM-ID: 0000062041 - 004
76 | Operation and Visualization - Main Menu | MS60024/05E 2019-03
8.26 Cleaning window
The screen can be cleaned on this screen page without any problem as no control elements are present.
There is only one element (Home button) that causes an image change.
TIM-ID: 0000062042 - 001
MS60024/05E 2019-03 | Operation and Visualization - Main Menu | 77
8.27 Service menu
NOTE
The menu is present for service purposes and can only be opened by authorized per-
sons.
TIM-ID: 0000062055 - 001
78 | Operation and Visualization - Main Menu | MS60024/05E 2019-03
9 Operation and Visualization - Additional
Functions
9.1 Overview of additional functions
The individual subfunctions must be called up via the individual buttons in the same way as the main menu.
The disabled functions have a gray background and cannot be selected.
Additional functions:
• Water temperature controller
• Mixture coolant controller
• Mixture blower and pump
• Emergency cooling water governor
• Emergency cooling blower and pump
• Room temperature controller
• Room blower
• CH4 control
• Gas tank
• Grid feed-in control
• Exhaust gas/bypass flaps
• Heat mode: Engine
• Heat mode: Boiler
• Buffer reservoir
• Timer
• External communication
• SMS/e-mail
• M-Graph: Single channel daily progression
• M-Graph: System
• M-Graph: System daily progression
• Additional controller
• Load divider isolated parallel operation
TIM-ID: 0000062056 - 002
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 79
9.2 Water temperature controller (optional)
Screen page
Figure 17: Water temperature controller
1 Manual Manual
2 Setpoint Specified value
3 Actual value Actual value
4 Minimum opening Forced opening
The governor comprises a PI controller, its output value can set the regulating valve from closed (0%) to open
(100%).
Control mode:
Actual value<setpoint: Regulating valve closes (maximum up to set forced opening).
Actuator:
Two types of actuator can be used with the thermostat:
TIM-ID: 0000062057 - 003
• Analog actuator (standard: 0 to 10 V)
• Actuator with open/close pulses (with end positions)
A Manual mode can be initiated for both actuators. The Manual mode is reset again each time the genset is
restarted.
80 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
Special feature:
Actuator with open/close pulses and end positions:
• A reference travel is initiated after each expiry of the run-on time.
• This determines the run time of the valve and the current position of the regulating valve can always be
calculated via the pulse/pause ratio.
• The reference travel can also be activated manually during a standstill using the "Reference travel" button.
• An initiated reference travel can no longer be canceled.
Parameters for the thermostat:
Parameter Unit Explanation
Specified °C This parameter corresponds to the setpoint for the control. After expiry of the start
value ramp, the controller regulates the temperature to this value.
Start set- °C The start ramp for the temperature is started from this value.
point
Warm-up min. The start ramp is increased from the start setpoint up to the actual setpoint over
time this time.
Run-on min. When the control is activated, the controller still has an adjustable run-on time.
time
Kp – Proportional component of the controller. Per °C deviation, the correcting variable
is opened or closed by this factor (e.g. system deviation +5 °C, Kp=6: The propor-
tional component of the correcting variable is 30%).
The Kp is separately adjustable for normal operation and the warm-up time.
Ki – Integral component of the governor. If the system deviation persists, each time the
follow-up time (Tn) expires, the Ki value is added to the P component and output. A
higher Ki value may result in oscillation of the setpoint for the regulating valve.
Tn s The follow-up time is used to calculate the I component. The output value of the I
controller is then added to the output value of the P controller at these intervals. A
follow-up time that is too low may result in oscillation of the setpoint for the regu-
lating valve.
The Tn is separately adjustable for normal operation and the warm-up time.
Forced % In operation, the valve is only closed or opened up to this opening angle (depends
opening on the direction of action, which can be entered here).
Manual set- % If Manual mode is active, this setpoint is output to the regulating valve.
point
Additional parameters for three-point controller
Parameter Unit Explanation
Pulse time ms A pulse is output for the set time (open or close). After each pulse the same pause
expires.
Example: For a valve with a runtime of 130 s (from open to closed) and a time set-
ting of 1300 ms, a correcting variable change of 1% is achieved per pulse. The run-
TIM-ID: 0000062057 - 003
time is determined for a regulating valve with end position by the reference travel.
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 81
9.3 Water temperature controller via two control loops (optional)
General
Figure 18: Water temperature controller
1 Setpoint Specified value
2 T-coolant engine inlet Coolant temperature before engine
3 Heating water temperature outlet Hot water temperature at outlet
4 Control variable Correcting variable
5 Manual Manual
The controller comprises two separate PI controllers which operate in parallel. Each PI controller regulates
its own correcting variable; the larger value of the correcting variable is transferred to the regulating valve as
an output value.
The regulating valve can be set from closed (0%) to open (100%).
Example: If the first PI controller regulates to a correcting variable of 80% and the second PI controller to a
correcting variable of 72%, 80% is transferred to the regulating valve as an output value.
TIM-ID: 0000062058 - 003
If both PI controllers have a correcting variable of >10%, the controller with the smaller correcting variable is
set to the correcting variable of the other controller. An excessive step change in the correcting variable is
prevented when switching over the controllers.
Example: The first PI controller regulates to a correcting variable of 80%, the second PI controller regulates
to a correcting variable of 72%. The second PI controller reduces its correcting variable from 72% to 69.9%
due to the setpoint/actual value deviation. The correcting variable deviation is now greater than 10%, the
correcting variable of the second PI controller is then set to the correcting variable of the first PI controller,
i.e. 80%.
82 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
Control mode
The controller comprises two separate PI controllers which operate in parallel.
Actual value<setpoint: PI controller closes (maximum up to set forced opening).
Each PI controller regulates its own correcting variable. The larger value of the correcting variable is transfer-
red to the regulating valve as an output value.
Actuator
An analog actuator (standard: 0 to 10 V) is used for the thermostat. A Manual mode can be initiated for the
actuator. The Manual mode is reset again each time the genset is restarted.
Each PI controller provides the following parameters
Parameter Unit Explanation
Specified °C This parameter corresponds to the setpoint for the control. After expiry of the start
value ramp, the controller regulates the temperature to this value.
Start set- °C The start ramp (for the temperature) is started from this value.
point
Warm-up min The start ramp is increased from the start setpoint up to the actual setpoint over
time this time.
Run-on min When the control is deactivated, the controller still has an adjustable run-on time.
time
Kp – Proportional component of the controller. Per 1 °C deviation, the correcting varia-
ble is opened or closed by this factor (e.g. system deviation +5 °C, Kp=6: The pro-
portional component of the correcting variable is 30%).
The Kp is separately adjustable for normal operation and the warm-up time.
Ki – Integral component of the governor. If the system deviation persists, each time the
follow-up time (Tn) expires, the Ki value is added to the P component and output.
A higher Ki value may result in oscillation of the setpoint for the regulating valve.
Tn s The follow-up time is used to calculate the I component. The output value of the P
controller is then also added at these time intervals. A follow-up time that is too
low may result in oscillation of the setpoint for the regulating valve.
The Tn is separately adjustable for normal operation and the warm-up time.
Forced % In operation, the correcting variable is only closed or opened up to this opening
opening angle (depends on the direction of action, which can be entered here).
Common parameters for both PI controllers
Parameter Unit Explanation
Manual set- % If Manual mode is active, this setpoint is output to the regulating valve.
point
TIM-ID: 0000062058 - 003
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 83
9.4 Water mixture controller (optional)
General information
The mixture coolant of the engine is regulated to a defined setpoint using this function.
Control mode:
If actual value < setpoint, the regulating valve closes (maximum up to set forced opening).
This controller functions in the same way as the water temperature controller (→ Page 80).
TIM-ID: 0000062059 - 001
84 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
9.5 Mixture blower and pump (optional)
General
The mixture coolant (cooler) is cooled using this function.
Variant 1: Blower via stepped switching
General
Figure 19: Mixture blower and pump
1 Value to switch on Switch-on value
2 Switch-on delay On-delay
3 Value to switch off Switch-off value
4 Switch-off delay Off-delay
5 Mixture cooling pump 1 Mixture coolant pump 1
6 Manual Manual
7 Actual value Actual value
TIM-ID: 0000062060 - 004
8 Preheating unit Preheater
The number of stages present is determined via a module parameter.
A maximum of 8 stages are available. One stage represents only one switching threshold. This can also mean
that, with two stages, a blower is configured with star/delta connection.
For Manual mode it is possible to switch between the individual stages with the arrow keys.
When a stage is in operation, this is signaled by a green LED. It is also possible to operate each stage man-
ually. Manual mode is indicated by an orange LED.
The function of each individual stage can be defined via the following four parameters.
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 85
Parameter for cooler stages:
Parameter Unit Meaning
Switch-on °C If the actual temperature value exceeds this limit value, the cooler stage is acti-
value vated when the on-delay time expires.
On-delay s On-delay for the cooler stage
Switch-off °C If the actual temperature value falls below this limit value, the cooler stage is de-
value activated when the off-delay time expires.
Off-delay s Off-delay for the cooler stage
Pump:
The mixing pump is activated at nominal speed. The pump can also be operated manually during a standstill.
Variant 2: Blower via frequency converter
General
Figure 20: Mixture blower and pump
TIM-ID: 0000062060 - 004
1 Setpoint Specified value
2 Actual value Actual value
3 Mixture cooling pump 1 Mixture coolant pump 1
4 Manual Manual
5 Control variable Correcting variable
6 Preheating unit Preheater
In this variant, the heat exchanger blower is controlled by a frequency converter. A PI controller which out-
puts the correcting variable (0 to 10 V) to the frequency converter is used for this. The correcting variable
can also be set manually.
86 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
Parameters for frequency converter:
The control parameters of the PI controller are identical with those of the water temperature controller. But
there are no warm-up and run-on times.
Pump:
The mixing pump is activated at nominal speed. The pump can also be operated manually during a standstill.
Preheating:
General
With certain applications (e.g. fast gas), the mixture coolant must be preheated with the engine stationary.
The mixing pump is activated for this purpose.
Figure 21: Preheater
1 Value to switch off Switch-off value
2 Setpoint Specified value
3 Value to switch on Switch-on value
4 Actual value Actual value
TIM-ID: 0000062060 - 004
Parameters for preheating
Parameter Unit Meaning
Offset °C If the temperature actual value exceeds the setpoint plus offset value (= switch-
off value), the preheating is deactivated. The setpoint corresponds to the setpoint
of the mixture coolant controller.
Hysteresis °C If the temperature actual value undershoots the switch-off value minus hysteresis
value (= switch-on value), the preheating is activated.
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 87
9.6 Emergency cooling water controller (optional)
General information
The cooling circuit of the engine is regulated to a defined setpoint using this function.
Control mode
If the actual value is > setpoint, the regulating valve opens.
This controller functions in the same way as the water temperature controller (→ Page 80).
TIM-ID: 0000062061 - 001
88 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
9.7 Emergency cooler blower and pump (optional)
Variant 1: Emergency cooler blower via stepped switching
General
Figure 22: Emergency cooler blower and pump
1 Switch-on delay On-delay
2 Value to switch on Switch-on value
3 Pump Pump
4 Switch-off delay Off-delay
5 Value to switch off Switch-off value
6 Actual value Actual value
7 Manual Manual
The number of stages present is determined via a module parameter.
A maximum of 8 stages are available. One stage represents only one switching threshold. This can also mean
that, with two stages, a blower is configured with star/delta connection.
TIM-ID: 0000062062 - 003
For Manual mode it is possible to switch between the individual stages with the arrow keys. The current sta-
tus (Manual/Start/Stop) is displayed for the selected stage (no.). When a stage is in operation, this is sig-
naled by a green LED.
It is also possible to operate each stage manually. Manual mode is indicated by an orange LED.
The function of each individual stage can be defined via the following four parameters.
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 89
Parameters for emergency cooler stages:
Parameter Unit Explanation
Switch-on °C If the temperature actual value exceeds this limit value, the emergency cooler
value stage is activated when the on-delay time expires.
On-delay s On-delay for the emergency cooler stage
Switch-off °C If the temperature actual value falls below this limit value, the emergency cooler
value stage is deactivated when the off-delay time expires.
Off-delay s Off-delay for the emergency cooler stage
Emergency cooler pump:
Like the blower stages, the emergency cooler pump can also be set using a parameter set. The pump can
also be operated manually.
Parameters for emergency cooler pump:
Parameter Unit Explanation
Switch-on °C If the temperature actual value exceeds this limit value, the pump is activated
value when the on-delay time expires.
On-delay s On-delay for the pump
Switch-off °C If the temperature actual value falls below this limit value, the pump is deactivat-
value ed when the off-delay time expires.
Off-delay s Off-delay for the pump
TIM-ID: 0000062062 - 003
90 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
Variant 2: Emergency cooler blower via frequency converter
General
Figure 23: Emergency cooler blower and pump
1 Value to switch on Switch-on value
2 Value to switch off Switch-off value
3 Setpoint Specified value
4 Actual value Actual value
5 Pump Pump
6 Control variable Correcting variable
7 Manual Manual
In this variant, the emergency cooler blower is controlled via FC.
Up to 2 FCs can be used (0 to 100% / 0 to 10 V).
A PI controller which outputs the correcting variable (0 to 10 V) to the FC is used for this.
The correcting variable can also be set manually.
TIM-ID: 0000062062 - 003
When using 2 FCs, there is only one setpoint however.
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 91
Parameters for frequency converter:
Parameter Unit Explanation
Specified val- °C This parameter corresponds to the setpoint for the control.
ue
Switch-on val- % or °C When the limit value is reached, the FC is enabled.
ue System-dependent: For example, switch-on by the position of an emergency
cooler governor valve (%) or depending on the water temperature (°C).
When using 2 FCs, the second FC is enabled by means of the correcting varia-
ble of the first FC.
Switch-off val- % or °C The first FC is switched off depending on the water temperature (°C).
ue The second FC is deactivated by means of the correcting variable (%) of the
first FC.
Transfer value % Can be switched on depending on the system.
The transfer value can be linked with another control loop contingent on the
project. If this control circuit is deactivated, this transfer value is taken over by
the control. This ensures a smooth switch-over.
Kp – Proportional component of the controller. For each 1 °C deviation, the correct-
ing variable is increased or reduced by this factor (e.g. system deviation +5 °C,
Kp=6: The proportional component of the correcting variable is 30%).
Ki – Integral component of the governor. If the system deviation persists, each time
the follow-up time (Tn) expires, the Ki value is added to the P component and
output. A higher Ki value may result in oscillation of the setpoint for the FC.
Tn s The follow-up time is used to calculate the I component. The output value of
the I controller is then added to the output value of the P controller at these
intervals. A follow-up time that is too low may result in oscillation of the set-
point for the FC.
Manual cor- % If manual mode is active, this setpoint is output to the FC.
recting varia-
ble
TIM-ID: 0000062062 - 003
92 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
9.8 Room temperature control (optional)
General information
The room temperature is regulated to a defined setpoint using this function. Flap activation (supply air, ex-
haust air and circulating air) must be interconnected via the hardware so that all flaps can be brought to the
correct position with a control input (e.g. 0 to 10 V).
Control mode
If the actual value is > setpoint, the regulating valve opens.
This controller functions in the same way as the water temperature controller (→ Page 80).
TIM-ID: 0000062063 - 001
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 93
9.9 Room blower control (optional)
Variant 1: Room blower via stepped switching
Figure 24: Room blower
1 Switch-off delay Off-delay
2 Switch-on delay On-delay
3 Value to switch on Switch-on value
4 Value to switch off Switch-off value
5 Room air fans enable Room blower enable
6 Room air Ambient air
7 Inlet air fan Supply blower
8 Manual Manual
9 Outlet air fan Exhaust blower
The number of stages present is determined via a module parameter.
A maximum of 4 stages are available (supply air and exhaust air). One stage represents only one switching
TIM-ID: 0000062064 - 003
threshold. This can also mean that, with two stages, a blower is configured with star/delta connection.
For Manual mode it is possible to switch between the individual stages with the arrow keys. The current pa-
rameters are displayed for the selected stage (no.).
When a stage is in operation, this is signaled by a green LED. It is also possible to operate each stage man-
ually. Manual mode is indicated by an orange LED.
The function of each individual stage can be defined via the following four parameters.
94 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
Parameters for room blower stages:
Parameter Unit Explanation
Switch-on °C If the temperature actual value exceeds this limit value, the ambient air stage is
value activated upon expiry of the on-delay time.
On-delay s On-delay for the ambient air stage
Switch-off °C If the temperature actual value falls below this limit value, the ambient air stage is
value deactivated when the off-delay time expires.
Off-delay s Off-delay for the ambient air stage
Optional: If a gas alarm occurs, all blower stages are compulsorily activated.
Activation of the room blower (can be set as required)
The blower can be enabled as required using the "Room blower enable" button.
The following combinations are possible:
• Enable even during a standstill of the system
The blowers are switched on (even with a stopped machine) after exceeding the limit value.
• Enable only when operating the system
The blowers are only enabled when the machine is running and the limit value exceeded
• Stage 1 immediately upon operation
This option can be selected for the two variants mentioned above. The first blower stage is then switched
on immediately when the engine starts (independent of the limit value).
Variant 2: Room blower via frequency converter
In this variant each of the room blowers (supply air and exhaust air) are controlled by an FC. To do so, a PI
controller is used which outputs the setpoint (0 to 10 V) to the FC. The correcting variable can also be set
manually.
TIM-ID: 0000062064 - 003
Figure 25: Room blower
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 95
1 Value to switch on Switch-on value
2 Value to switch off Switch-off value
3 Setpoint Specified value
4 Actual value Actual value
5 Inlet air Supply air
6 Control variable Correcting variable
7 Manual Manual
8 Outlet air Exhaust air
Parameters for frequency converter
Parameter Unit Explanation
Specified °C This parameter corresponds to the setpoint for the control.
value
Standstill °C When the machine is stopped, this value is added to the setpoint. This prevents
offset constant switching on or off during a standstill and nevertheless eliminates accu-
mulated heat.
Switch-on °C This value is added to the setpoint. If the room temperature exceeds the total val-
value ue, the FC is enabled.
Switch-off °C This value is subtracted from the setpoint. If the room temperature is less that the
value total value, the FC is deactivated again.
Kp – Proportional component of the controller. For each 1 °C deviation, the correcting
variable is increased or reduced by this factor (e.g. system deviation +5 °C, Kp=6:
The proportional component of the correcting variable is 30%).
Ki – Integral component of the governor. If the system deviation persists, each time
the follow-up time (Tn) expires, the Ki value is added to the P component and out-
put. A higher Ki value may result in oscillation of the setpoint for the FC.
Tn s The follow-up time is used to calculate the I component. The output value of the I
controller is then added to the output value of the P controller at these intervals.
A follow-up time that is too low may result in oscillation of the setpoint for the FC.
Forced % During operation, if the correcting variable is lower than this value, it is not out-
opening put.
Manual set- % If manual mode is active, this setpoint is output to the FC.
point
Optional
If a gas alarm occurs, the room blowers are compulsorily activated with a setpoint of 100%.
TIM-ID: 0000062064 - 003
96 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
9.10 CH4 control (optional)
General
The CH4 control is divided into several areas:
• Start enabling for the engine based on the CH4 content (digital contact or limit value via analog actual-
value signal)
• Power limitation by means of the CH4 content (only works when an analog actual value signal is available).
NOTE
All functions are only active in automatic mode.
Start enable via digital contact
The genset is enabled or stopped by means of the CH4 content. A digital transmitter is read for this.
The following parameters are available:
Parameter Unit Meaning
Switch-on delay s If the contact is present, this time expires. Only after the time expires
and with the signal pending is the genset enabled.
Off-delay s If the contact is no longer pending, this time expires.
Start enable via analog signal (optional)
The genset is enabled or stopped by means of the CH4 content. To do so, an analog actual value signal is
read and compared with the limit value.
The following parameters are available:
Parameter Unit Meaning
With CH4 content on % If the actual value exceeds this limit, the on-time expires.
Switch-on delay s If the limit value is exceeded, this time expires. Only after the time has
expired and the limit value is exceeded is the genset enabled.
With CH4 content off % If the actual value falls below this limit, the off-time expires.
Off-delay s If the limit value is fallen below, this time expires. Only after the time
expires and the limit value is fallen below is the genset enabled.
The curve must be determined by the customer.
NOTE
The values can only be altered from a specific user level (service).
TIM-ID: 0000062065 - 002
Power limiting via analog signal (optional)
The power of the engine is limited by means of the CH4 content. To do so, an analog actual-value signal is
read in and compared with the limit values.
The following parameters are available:
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 97
Parameter Unit Meaning
At min. CH4 content % This CH4 value is assigned to the lowest power value.
Power at min. % If the CH4 value falls below the min. limit value, the power is limited to
this value.
The limit is calculated by a straight line between the minimum and maxi-
mum value.
At max. CH4 content. % This CH4 value is assigned to the highest power value.
Power at max. % If the CH4 value exceeds the max. limit value, the power is limited to this
value.
The limit is calculated by a straight line between the minimum and maxi-
mum value.
Start setpoint CH4 content
The engine start and engine operation up to 10% power are carried out in regard to the CH4 content via the
default from the MMC.
If the MMC receives a CH4 measurement signal via a sensor, the engine uses this transferred CH4 value up to
a power of 10%.
If the MMC does not receive a CH4 measurement signal via a sensor, the CH4 content is defined manually via
the MMC in a range from 45% to 65%.
Above an engine power of 10%, the ADEC governor basically calculates the current CH4 content automatical-
ly. The engine then also compensates for changing the CH4 contents independent of the CH4 measurement
signal.
Configurable parameters:
Parameter Unit Meaning
Start setpoint CH4 con- % The CH4 content can be changed in a range from 45% to 65%. The start
tent setpoint button must be actuated to do this. If the sensor for the CH4
measurement signal is not present or the sensor has a hardware fault,
the Start setpoint button is activated automatically
NOTE
The CH4 content start setpoint parameter is only used for engine start. The start enable
via CH4 content and power limiting are not affected by CH4 content functions. TIM-ID: 0000062065 - 002
98 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
9.11 Gas tank (optional)
General information
The gas tank control system is divided into several areas:
• Gas flare
• Start enable of the engine by means of the fill level/gas pressure
(digital contact or limit value via analog actual value signal)
• Power limiting by means of the fill level/gas pressure
(digital contact or limit value via analog actual value signal)
NOTE
All functions are only active in automatic mode.
NOTE
The analysis is either carried out via an analog signal (standard) or via digital signals
(3 contacts).
A combination is not possible.
All parameters must be determined by the customer.
Gas tank flare activation (fill level/pressure): Enable via analog signal
The flare is enabled or stopped by means of the fill level/pressure. To do so, an analog actual value signal is
read and compared with the limit value.
The following parameters are available:
Parameter Unit Meaning
Switch-on value % If the actual value exceeds this limit, the on-time expires.
Switch-on delay s Is the limit value is exceeded, this time expires. Only after the time expires
and the limit value is exceeded is the flare enabled.
Switch-off value % If the actual value falls below this limit, the off-time expires.
Off-delay s If the limit value is fallen below, this time expires. Only after the time expires
and the limit value is fallen below is the flare enabled.
Gas tank (fill level/pressure): Start enable via digital contact
The genset is enabled or stopped by means of the fill level/pressure. To do so, two digital transmitter are
read (Off/On).
The following parameters are available:
Parameter Unit Meaning
Switch-on delay s If the "On" contact is present, this time expires. Only after the time expires
and the signal is pending is the genset enabled.
TIM-ID: 0000062066 - 001
Off-delay s If the "Off" contact is present, this time expires. Only after the time expires
and the signal is pending is the genset disabled.
Gas tank (fill level/pressure): Start enable via analog signal
The genset is enabled or stopped by means of the fill level/pressure. To do so, an analog actual value signal
is read and compared with the limit value.
The following parameters are available:
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 99
Parameter Unit Meaning
Switch-on value % If the actual value exceeds this limit, the on-time expires.
Switch-on delay s If the limit value is exceeded, this time expires. Only after the time expires
and the limit value is exceeded is the genset enabled.
Switch-off value % If the actual value falls below this limit, the off-time expires.
Off-delay s If the limit value is fallen below, this time expires. Only after the time expires
and the limit value is fallen below is the genset enabled.
Gas tank (fill level/pressure): Power limiting via digital contacts
The power of the engine is limited by means of the fill level/pressure. To do so, a third switch is read (Off, On
and max. power value, min. power value).
The following parameters are available:
Parameter Unit Meaning
Power at max. % When the switch activates (On and max. power value), the power is set to this
setpoint.
Power at min. % When the switch activates (min. power value) and non-active switch (On and
max. power value), the power is set to this setpoint.
Gas tank (fill level/pressure): Power limiting via analog signal
The power of the engine is limited by means of the fill level/pressure. To do so, an analog actual value signal
is read and compared with the limit value.
The following parameters are available:
Parameter Unit Meaning
At fill level/ % This fill level/pressure value is assigned to the lowest power value.
pressure min.
Power at min. % If the fill level/pressure falls below the min. limit value, the power is limited
to this value. The limit is calculated by a straight line between the minimum
and maximum value.
At fill level/ % This fill level/pressure value is assigned to the highest power value.
pressure max.
Power at min. % If the fill level/pressure exceeds the max. limit value, the power is limited to
this value. The limit is calculated by a straight line between the minimum and
maximum value.
TIM-ID: 0000062066 - 001
100 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
9.12 Grid feed-in control (optional)
General information
Figure 26: Switch
1 Grid bar 3 Grid transfer power 5 Generator
2 Busbar 4 Generator power 6 Consumer power
There are three ways of regulating the grid transfer power:
• System draws power from the grid
• System feeds power into the grid
• Regulated to zero load at the grid transfer point (zero load control)
The actual value signal on the grid transfer point is a "±signal" (e.g. -1000 kW to +1000 kW).
The signal is assessed as follows:
• Generated power < consumed power
Signal is positive (+), system draws power from the grid.
• Generated power > consumed power
Signal is negative (-), system feeds power into the grid.
• Generated power = consumed power
Signal is zero, system feeds nothing into the grid and draws nothing from the grid
TIM-ID: 0000062067 - 001
The start enable of the genset can be set by means of the grid transfer power. The engine is only enabled if
the parameterizable switch-on threshold is exceeded. The same applies to the switch-off threshold.
The system can ideally be used in order not to have to count any peak currents, for example.
NOTE
All functions are only active in automatic mode.
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 101
NOTE
Care must be taken with the functions (grid feed-in control and start enable) that they
do not mutually eliminate each other (e.g. the grid feed-in control should regulate to a
value that is, however, already assessed as the deselection point of the system).
Status messages
Status messages:
• Active
When the grid feed-in control is activated is displayed here.
• Feed
This shows when the system is feeding into the grid.
• Reference
This shows when the system is drawing from the grid.
• Dead band
This shows if the system deviation is less than the dead band.
• Setpoint max
This shows if the calculated setpoint has reached the maximum permitted setpoint for the power control-
ler.
The maximum setpoint (%) is displayed in the power controller parameters. The setpoint is set in the mod-
ule parameters and cannot be changed.
• Setpoint min
This shows if the calculated setpoint has reached the minimum permitted setpoint for the power control-
ler.
The minimum setpoint (%) is displayed in the power controller parameters. The setpoint is set in the mod-
ule parameters and cannot be changed.
• Start enable
If the setpoint/actual value comparison is negative, the system is feeding into the grid.
If the setpoint/actual value comparison is positive, the system is drawing from the grid.
Parameters for grid feed-in control
Parameter Unit Meaning
Setpoint kW The power at the grid transfer point is regulated to this value. If this is a negative
value, the system should feed into the grid.
Dead band kW If the system deviation (xd) is below this value, the setpoint for the power control-
ler no longer changes. This stops any oscillation of the system.
Increment kW This value specifies by how many "kW" the setpoint for the power controller is
changed per second.
The setpoint for the power controller is only changed if the system deviation is
greater than the dead band. The increment value must be selected to be less than
the value of the dead band.
Pause time s This is the pause time between two changes of the setpoint for the power control-
ler.
TIM-ID: 0000062067 - 001
Parameters for start enable
Parameter Unit Meaning
X1 kW Non-delayed selection. If the actual value exceeds this limit, the engine is enabled
immediately.
X2 kW Delayed selection. If the actual value exceeds this limit and is less than the non-
delayed switch-on value, the engine is enabled after a delay. The delay time is cal-
culated on a straight line between the non-delayed and delayed switch-on value.
102 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
Parameter Unit Meaning
Y1 s Delay time for the selection. This time is calculated between the non-delayed and
delayed and delayed switch-on value via a straight line. The closer the current ac-
tual value comes to the non-delayed switch-on value, the shorter the delay time.
X3 kW Delayed deselection. If the actual value falls below this limit, the engine is dese-
lected after a delay. The delay time is calculated on a straight line between the
non-delayed and delayed switch-off value.
X4 kW Non-delayed deselection. If the actual value falls below this limit, the engine is de-
selected immediately.
Y2 s Delay time for the deselection. This time is calculated between the non-delayed
and delayed and delayed switch-off value via a straight line. The closer the cur-
rent actual value comes to the non-delayed switch-off value, the shorter the delay
time.
The limit value for the selection and deselection must always become smaller from left to right (on the X
axis). If this is not adhered to, a default value is activated.
TIM-ID: 0000062067 - 001
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 103
9.13 Exhaust/bypass flap control (optional)
General information
The exhaust flap is opened when the genset is started. It is necessary for systems with several gensets to
prevent the back flow of combustion air into the deselected gensets.
The task of the bypass flap is to guide the hot exhaust gas past the exhaust heat exchanger during low heat
consumption to prevent the heating water overheating.
The bypass mode can be activated by the parameterizable limit value or manually via the Select button. The
bypass mode can also be activated remotely via an optional input. Flap 2 is opened first and flap 1 closed
only after the "Open" limit switch activates.
All flaps can also be operated manually.
Parameters for bypass mode
Parameter Unit Meaning
Bypass mode limit °C If the limit value is exceeded, bypass flap 2 opens first and bypass flap 1
value then closes.
Hysteresis for by- °C If the hysteresis falls below the limit value, the bypass mode is deactivat-
pass mode ed.
NOTE
All functions are only active in automatic mode.
TIM-ID: 0000062068 - 001
104 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
9.14 Engine heat mode (optional)
Start enable by means of the water temperature
General
Figure 27: Engine heat mode
1 Start release Start enable
2 Outdoor temperature Outside temperature
3 Control active Control active
The genset is automatically started or stopped if the temperature has exceeded or fallen below various limit
values. Delay times can also be entered. The limit value selection can also be shifted by the outside tempera-
ture or by a reduction.
NOTE
All functions are only active in automatic mode.
TIM-ID: 0000062069 - 002
Parameters for the start request
Parameter Unit Explanation
Non-delayed selec- °C If the actual value falls below this limit, the engine is enabled immediate-
tion ly.
X1
Delayed selection °C If the actual value falls below this limit and is greater than the non-de-
X2 layed switch-on value, the engine is enabled after a delay.
The delay time is calculated on a straight line between the non-delayed
and delayed switch-on value.
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 105
Parameter Unit Explanation
Delay time for the s This time is calculated between the non-delayed and delayed and delayed
selection switch-on value via a straight line. The closer the current actual value
Y1 comes to the non-delayed switch-on value, the shorter the delay time.
Non-delayed dese- °C If the actual value exceeds this limit, the engine is deselected immediate-
lection ly.
X4
Delayed deselection °C If the actual value exceeds this limit and is less than the non-delayed limit
X3 value, the engine is enabled after a delay.
The delay time is calculated on a straight line between the non-delayed
and delayed switch-off value.
Delay time for the s This time is calculated between the non-delayed and delayed and delayed
deselection switch-off value via a straight line. The closer the current actual value
Y2 comes to the non-delayed switch-off value, the shorter the delay time.
Slipping: Start enable and power regulation by means of a water temperature
General
TIM-ID: 0000062069 - 002
Figure 28: Engine heat mode
1 Start release Start enable
2 Outdoor temperature Outside temperature
3 Control active Control active
The governor consists of a PI controller, its output value can change the power of the genset from 50% (set-
point min.) to 100%.
The limit value for the start enable can be influenced with the aid of the outside temperature.
106 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
NOTE
All functions are only active in automatic mode.
Example with heating water return temperature as setpoint:
Measuring the heating water return temperature using separate sensor in the system.
Start enable (values correspond to the current image):
If the genset is stopped and the heating water return temperature (actual value) falls below 66 °C (X2 in the
image), the system waits 30 s (Y1 in the image) until the genset is selected. The further the temperature falls
(X1 direction), the faster the genset is selected.
Control (values correspond to the current image):
When the genset is running, the set power is determined by means of the heating water return temperature
in the PI controller. The current actual value of the temperature is also displayed. There is an attempt to reg-
ulate the heating water return temperature to the "setpoint" (70 °C in the example). As long as the heating
water value is less than the heating water setpoint, the genset power setpoint (power setpoint) is increased
in accordance with the control parameters (to maximum 100%). If the heating water actual value rises above
the heating water setpoint, the genset power setpoint is reduced again (to min. setpoint).
"Heat mode with limiting function" special feature:
In this operating mode, the calculated setpoint is still limited by the grid feed-in control. The setpoint is not
increased further, like the currently calculated setpoint of the grid feed-in control.
Shutdown (start enable is deactivated):
As soon as the heat controller registers "Setpoint min." and the "Hot water temperature > limit value 1" fault
message appears, the genset is deselected. Thus, as long a runtime as possible of the genset is achieved.
Power control indicators
Parameter Unit Explanation
Control active – This LED lights green as soon as the control has been activated (start ena-
ble by heat mode and mains parallel operation active).
Warm-up time – This LED lights green while the start ramp is active, and hence the warm-up
time expires.
Setpoint min. – This LED lights green as soon as the calculated genset set power corre-
sponds to "min. setpoint".
100% – This LED lights green as soon as the calculated genset set power corre-
sponds to "max. setpoint", and thus 100%.
Grid feed-in con- – If no grid feed-in control is present, this indicator is deactivated.
trol In heat mode with limiting, this LED lights green as soon as the power of the
grid feed-in control is less than the power of the slipping heat mode.
The calculated power of the grid feed-in control is indicated underneath.
TIM-ID: 0000062069 - 002
Specified value °C The current heating water temperature setpoint is displayed here.
This is increased during the warm-up time from the start setpoint to the set-
point.
Actual value °C The current actual value on the temperature sensor for the heating water
temperature is displayed here.
Setpoint/actual °C The difference between the setpoint and the actual value is displayed here
value deviation (setpoint – actual value).
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 107
Parameter Unit Explanation
Power setpoint % The genset power setpoint is displayed here.
Actual power val- % The genset power actual value is displayed here.
ue
Parameters for power control
Parameter Unit Explanation
Specified value °C This parameter corresponds to the setpoint (heating water temperature) for
the control. After the start ramp expires, the controller regulates the heating
water temperature to this value via the genset power.
Start setpoint °C After the controller has been activated, the setpoint temperature is in-
creased via a start ramp.
The start ramp (for the temperature setpoint) is started from this value.
Warm-up time s During the warm-up time, the temperature setpoint is increased from the
start setpoint to the actual setpoint.
Only after this time expires is it regulated to the temperature value that was
entered for "Setpoint".
Kp – Proportional component of the controller. Per 1 °C deviation, the correcting
variable (genset power setpoint) is opened or closed by this factor (e.g. sys-
tem deviation +5 °C, Kp=6: The proportional component of the correcting
variable is 30%).
Ki – Integral component of the governor. If the system deviation persists, each
time the follow-up time (Tn) expires, the Ki value is added to the P compo-
nent and output. A higher Ki value may result in oscillation of the setpoint
for the genset power.
Tn s The follow-up time is used to calculate the I component. The output value of
the I controller is then added to the output value of the P controller at these
intervals. A follow-up time that is too low may result in oscillation of the set-
point for the genset power.
Setpoint min. % Corresponds to the minimum power at which the genset should operate.
TIM-ID: 0000062069 - 002
108 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
9.15 Boiler heat mode (optional)
General information
The boiler is automatically started or stopped if the temperature has exceeded or fallen below various limit
values.
Delay times can also be entered.
The limit values for the selection/deselection can also be shifted by the outside temperature or by a reduc-
tion.
NOTE
All functions are only active in automatic mode.
Parameters for boiler location request:
Parameter Unit Description
Non-delayed selec- °C If the actual value falls below this limit, the boiler is enabled immediately.
tion
X1
Delayed selection °C If the actual value falls below this limit and is greater than the non-de-
X2 layed switch-on value, the boiler is enabled after a delay.
The delay time is calculated on a straight line between the non-delayed
and delayed switch-on value.
Delay time for the s This time is calculated between the non-delayed switch-on value and de-
selection layed switch-on value via a straight line. The closer the current actual val-
Y1 ue comes to the non-delayed switch-on value, the shorter the delay time.
Non-delayed dese- °C If the actual value exceeds this limit, the boiler is disabled immediately.
lection
X4
Delayed deselection °C If the actual value exceeds this limit and is less than the non-delayed lim-
X3 it value, the boiler is disabled after a delay.
The delay time is calculated on a straight line between the non-delayed
and delayed switch-off value.
Delay time for the s This time is calculated between the non-delayed and delayed and de-
deselection layed switch-off value via a straight line. The closer the current actual val-
Y2 ue comes to the non-delayed switch-off value, the shorter the delay time.
TIM-ID: 0000062070 - 001
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 109
9.16 Outside temperature shift (optional)
General information
The outside temperature shift can be used for the heat mode (engine and boiler). The switching thresholds
for the enable are influenced by this function.
An offset (positive or negative) is calculated from the curve by means of the current outside temperature
which is then added to the switching thresholds. The shift can be adapted to the circumstances via 3 in-
clines. 4 parameter sets are needed for this.
The limit value for the X axis (outside temperature limit value) must always be greater from left to right.
The switching thresholds can also be shifted downward through lowering by an adjustable value (activated
via an optional input).
Parameter Unit Meaning
Offset °C All switching thresholds are shifted downward by this value.
Parameters for outside temperature
Parameter Unit Meaning
X1 °C Outside temperature value for offset value Y1
Y1 °C Offset value for outside temperature value X1
X2 °C Outside temperature value for offset value Y2
Y2 °C Offset value for outside temperature value X2
X3 °C Outside temperature value for offset value Y3
Y3 °C Offset value for outside temperature value X3
X4 °C Outside temperature value for offset value Y4
Y4 °C Offset value for outside temperature value X4
Parameters for lowering
Parameter Unit Meaning
Lowering °C This value is subtracted from the calculated offset.
value
TIM-ID: 0000062071 - 001
110 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
9.17 Buffer reservoir (optional)
General information
The genset is started or stopped by means of a buffer reservoir controller.
To do so, 4 sensors in the buffer reservoir are evaluated. Whether the buffer is full or empty is displayed.
When the start enable for the genset is given, an adjustable warm-up time expires.
After this warm-up time expires, further heat generators (e.g. boiler) are enabled for activation.
When the gradient evaluation detects that the buffer is full again, the selection of further heat generators is
stopped.
NOTE
All functions are only active in automatic mode.
Parameters for buffer reservoir
Parameter Unit Meaning
PT4 °C If the actual value falls below this limit, the engine is enabled immediate-
Non-delayed selec- ly. The buffer is empty.
tion
PT5 °C If the actual value falls below this limit, the engine is enabled after a de-
Delayed selection lay (see delay time).
PT5 s If the limit of PT5 is fallen below, this timer expires. After expiry of the
Delay time for the timer, the engine is enabled.
selection
PT7 °C If the actual value exceeds this limit, the engine is enabled immediately.
Non-delayed dese- The buffer is full.
lection
PT6 °C If the actual value exceeds this limit and is less than the non-delayed limit
Delayed deselection value of PT7, the engine is disabled after a delay (see delay time).
PT6 s If the limit of PT6 is exceeded, this timer expires. After expiry of the tim-
Delay time for the er, the engine is disabled.
deselection
Warm-up time min. After the warm-up time expires, further generators can be enabled.
Parameters for gradient evaluation
Parameter Unit Meaning
Time s Time in which the temperature difference was measured.
If the reservoir is full, no further heat generators (e.g. boiler) are enabled.
TIM-ID: 0000062072 - 001
Temperature °C Temperature difference that must be reached in order to detect whether
the reservoir is full or empty.
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 111
9.18 Timer (optional)
General
The mode of operation of the system for all times of day on all seven weekdays can be specified by means of
the timer.
NOTE
A maximum of five operating modes can be activated on an system.
Figure 29: Timer
1 Time Display Time display
2 Operating modes Modes
3 Current operating mode Current operating mode
Operation
The weekdays with the currently set operating mode for specific times of the day are displayed on the upper
TIM-ID: 0000062073 - 003
part of the screen page. The different operating modes are displayed in color.
A maximum of 8 switching thresholds can be set per day. The legend of the available operating modes is
shown under the weekdays. The current operating mode is shown at the bottom right of the display.
The following functions can be selected via the three buttons located on the left area of the screen page:
112 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
Button Explanation
Time program The operating modes of the system are controlled by the timer.
Always on The time program is not in use.
The genset is always enabled.
Always off The time program is not in use.
The genset is disabled.
Setting the switching threshold for a week day:
To set the switching threshold, click on the bar of the required weekday.
An input window opens:
Figure 30: Timer
1 Delete Delete
2 Save Save
3 New switching point New switching threshold
4 Accept Apply
The activated switching thresholds with the correspondingly selected operating mode is shown on the left
TIM-ID: 0000062073 - 003
side.
Deleting a switching threshold:
Switching thresholds are deleted by pressing the "Delete" button.
Adding a switching threshold (max. 8):
To enter a new switching threshold, the "h" and "min" entries are activated.
The corresponding operating mode key (colored legends) and the "Accept" key must then be pressed.
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 113
Thus it is possible to add the required switching thresholds for the day.
• To activate the set values, the "Save" key must still be pressed.
The button is only active when the data has also been changed.
• The overview is accessed by pressing the "Home" button in the middle of the screen.
TIM-ID: 0000062073 - 003
114 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
9.19 SMS/e-mail (optional)
General information
With this function it is possible to send a message via e-mail upon the occurrence of faults or operation mes-
sages.
These e-mails go to the MTU Onsite Energy server and are then forwarded to the registered customer ad-
dresses via e-mail or SMS.
The automatic maintenance call can therefore also be register.
If sent by e-mail, all the currently active alarms are grouped and sent via e-mail.
For the SMS recipients, all active messages are transmitted separately due to the character length. One
should proceed very selectively in choosing the messages to be sent.
Requirements:
See own document "User manual for remote diagnostics system 2008".
Operating data transfer (optional additional function):
The most important operating data (e.g. operating hours, start counter, other counter states, overview of oc-
curring fault messages) are sent automatically per e-mail to the customer address.
The operating data cannot be transferred via SMS as this is a large amount of data.
Overview window
The first text field in the overview window shows the collected SMS messages to be sent.
The second text field in the overview window shows the collected messages for e-mail notification.
The status of the sending process is recorded in the third text field.
When the pending messages have been processed and sent, they are deleted from the first two text fields.
This also occurs when sending of messages has failed for whatever reason, e.g. as result of failed data trans-
mission to the Internet provider.
Successful as well as failed transmission attempts are recorded in the status window. This window is deleted
once a day at 0:00.
The buttons which enable configuration of the SMS/e-mail client are in the bottom area of the overview win-
dow.
Selecting operating messages for notification
Actuation of the "Operating message" button in the overview window opens the page for setting the notifica-
tion options for the operating messages.
The first column shows whether the corresponding operating message is selected for notification per SMS or
not. When the message is selected, the cell had a green background and "YES" is displayed as the text. With
non-selected messages, the corresponding cell is white and "NO" is entered as the text.
TIM-ID: 0000062074 - 001
The selection for notification per e-mail of the corresponding operating message is made in the second col-
umn. The selection can be changed by touching the corresponding cell. Changes can only be made when
logged on in the operating main menu.
To process all messages, the content can be moved up and down using the four buttons on the right edge of
the table.
Selecting fault messages for notification
See selection of operating messages!
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 115
9.20 External communication (optional)
General
Figure 31: External communication
1 Interface status Interface status
2 Bus monitoring Bus monitoring
The active communication record is displayed. The current communication status can also be displayed. This
can be using for troubleshooting (see "Technical interface description").
Active communication
Clicking on the active communication (e.g. Profibus) opens the Parameter window:
TIM-ID: 0000062075 - 004
116 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
Figure 32: Parameter window
1 Accent parameters Accept parameters
This window shows all used parameters.
The address can be changed here for example. The data becomes active by actuation of the "Accept parame-
ters" button.
Simulation
Pressing the "Interface status" button switches to a simulation window for test purposes. A detailed descrip-
tion can be found in the document "Technical interface description".
TIM-ID: 0000062075 - 004
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 117
9.21 M-Graph: Single channel
General
Figure 33: M-Graph: Single channel
1 Zoom
1 Zoom Zoom
With this online writer, it is possible to display all available measured values in the form of graphs. A maxi-
mum of 250 channels are available. A maximum of two channels are displayed at the same time. All values
are updated in minute cycles.
Selecting channels:
The channels currently displayed are shown at the bottom of the screen. Touching the arrow at the end of
the display window opens a menu in which another channel can be selected. The corresponding channel can
be hidden by touching the color symbol.
Display range of the time axis (X):
The time axis is always set to 24 h. It is possible to scroll back 31 days.
TIM-ID: 0000062203 - 004
Scaling of the measurement ranges (Y):
The Y axis scales automatically to the maximum and minimum values.
Zoom:
Zooming out part of a range of the progression is possible using the Zoom button. To do so, touch the Zoom
button one again. The Zoom button then turns green.
Select a rectangle by dragging the mouse in the progression field. The excerpt is then magnified.
To deactivate the zoom again, tap once again on the "Zoom" button.
118 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
Activating:
The channels are automatically written to a database (time period of 31 days).
TIM-ID: 0000062203 - 004
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 119
9.22 M-Graph: Installation of the seconds graph
General
Figure 34: M-Graph: System
1 Zoom Zoom
2 Config. Config.
With this online writer, it is possible to display all available measured values in the form of graphs. A maxi-
mum of 8 channels are displayed at the same time. The values are updated every second.
Display range of the time axis (X):
The last 15 minutes are displayed.
Scaling of the measurement ranges (Y):
The Y axis scales automatically to the maximum and minimum values.
Zoom:
TIM-ID: 0000062204 - 003
Zooming out part of a range of the progression is possible using the Zoom button. To do so, touch the Zoom
button one again. The Zoom button then turns green.
Select a rectangle by dragging the mouse in the progression field. The excerpt is then magnified.
To deactivate the zoom again, touch once again on the "Zoom" button.
Activating:
The channels are automatically entered in an accumulator of 15 minutes.
120 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
Configuration:
Selecting the "Config." button switches to the configuration page. A maximum of five configurations can be
combined.
Figure 35: M-Graph: System
1 Activating the configuration Configuration activation
2 Saving the configuration Saving the configuration
8 channels can be selected per configuration. Four channels for one Y axis. A number must be specified here
for this under which the configuration is saved (max. 5).
After entering the name for the configuration, the channels must be selected. Then save using the "Save con-
figuration" button.
If a different configuration is to be displayed in the progression field, the corresponding number must be se-
lected here and the "Activate configuration" button selected. The corresponding configuration number is
then displayed in the "Active" box.
TIM-ID: 0000062204 - 003
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 121
9.23 M-Graph: System daily progression
General
With this online writer, it is possible to display up to eight important available measured values in the form of
graphs. The values are updated every minute.
Figure 36: M-Graph: System daily progression
1 Zoom Zoom
2 Config. Config.
Display range of the time axis (X):
The time axis is always set to 24 h. It is possible to scroll back 31 days.
Scaling of the measurement ranges (Y):
The Y axis scales automatically to the maximum and minimum values.
Zoom:
TIM-ID: 0000062205 - 003
Zooming out part of a range of the progression is possible using the Zoom button. To do so, touch the Zoom
button one again. The Zoom button then turns green.
Select a rectangle by dragging the mouse in the progression field. The excerpt is then magnified.
To deactivate the zoom again, touch once again on the "Zoom" button.
Activating:
The channels are automatically written to a database (time period of 31 days).
122 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
Changing configuration:
If a different configuration is to be displayed in the progression field, the corresponding number must be se-
lected here.
Configuration:
Selecting the "Config." button switches to the configuration page. A maximum of five configurations can be
combined.
8 channels can be selected per configuration. Four channels for one Y axis. A number must be specified here
for this under which the configuration is saved (max. 5).
After entering the name for the configuration, the channels must be selected. Then save using the "Save con-
figuration" button.
If a different configuration is to be displayed in the progression field, the corresponding number must be se-
lected here and the "Activate configuration" button selected. The corresponding configuration number is
then displayed in the "Active" box.
TIM-ID: 0000062205 - 003
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 123
9.24 Screenshot function
General information
The currently displayed page can be saved as a file using the Screenshot function. The MTU Onsite Energy
logo is used as the button. The screenshot is stored on the data partition and can be coped via the data
backup to a USB data carrier.
Designation Description
Path MTU\FileSharing\ScreenShot
File name JJJJMMDD_HHMMSS_MTU HMI_Titel.png
YYYY Year number
MM Month
DD Day
HH Hour
MM Minute
SS Second
MTU HMI Program name (Alarm Logger, HMI, Trending)
TIM-ID: 0000062206 - 001
124 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
9.25 Load divider isolated parallel operation
General
Figure 37: Load divider isolated parallel operation
1 Status Status
2 Number of gensets load sharing Number of load distribution modules
3 Active load sharing Effective load distribution
4 Parameter load sharing Load divider parameters
5 Parameter frequency control Frequency controller parameters
The load divider is needed in isolated parallel operation. An overview of all gensets involved in the load divi-
sion is displayed in the upper area.
Status messages:
• Fault:
A fault that results in shutdown is active.
• Genset active:
TIM-ID: 0000062207 - 003
Genset started or has detected revolutions per minute.
• GCB on:
Generator circuit breaker (GCB) is closed.
• Warm-up ramp active:
If the engine coolant temperature has been fallen below, a reduced power is selected provided that more
than one genset is in operation.
• Load division enable:
After the genset finishes the warm-up phase, the load division is enabled.
• Controlled release:
The genset is released upon removal of the start request or with a controlled stop slowly via a ramp, pro-
vided that more than one genset is involved in the load division.
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 125
Output values:
• Actual value power:
The current electrical power is displayed here.
• Utilization factor
Each genset sends its own utilization factor of the actual power output to all other involved gensets via
the bus system. The utilization factor of the reactive power is displayed here.
• Actual value of reactive power:
The current electrical reactive power is displayed here.
• Utilization factor kVar:
Each genset sends its own utilization factor of the reactive power to all other involved gensets via the bus
system. The utilization factor of the reactive power is displayed here.
Effective load distribution:
• Current I component:
The current integral component of the effective load distribution or frequency control is displayed.
• Current P component:
The current proportional component of the effective load distribution is displayed.
Reactive load distribution:
• Current I component:
The current integral component of the reactive load distribution or voltage control is displayed.
• Current P component:
The current proportional component of the reactive load distribution is displayed.
Power setpoint:
The set power of the genset is calculated as follows:
∑AF(all gensets)
Pset[kW] = x Pnominal[kW]
n
Parameter Unit Explanation
Pset kW Electrical set power
AF – Utilization factor = Pactual/Pnominal
n – Number of gensets involved in the isolated parallel operation on the effective
power distribution
Pnominal kW Electrical nominal power for isolated operation
Pactual kW Electrical actual power output
Reactive power setpoint:
∑AF(all gensets)
Qset[kVar] = x Pnominal[kW]
n
TIM-ID: 0000062207 - 003
Parameter Unit Explanation
Qset kVar Electrical set reactive power
AF – Utilization factor = Qactual/Pnominal
n – Number of gensets involved in the isolated parallel operation on the reactive
power distribution
Pnominal kW Electrical nominal power for isolated operation
Qactual kVar Electrical reactive power
126 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
9.26 Load distributor parameters
Parameter Unit Meaning
Number of load distribu- – Number of gensets involved on the internal load distribution. The set-
tion gensets ting of the node number switch on the X20CPU is thus important:
Genset 1 needs node number 11, genset 2 needs node number 12
etc.
Nominal power kW Nominal power in isolated operation. This is normally set to 90% of
the grid parallel nominal power. The nominal power is required for
calculation of the utilization factor of the genset.
Tn s Follow-up time of the governor. The smaller the value, the faster the
governor.
Kp – Proportional component of the governor. The larger the value, the
faster the governor.
Dead band nominal rpm The calculation of the integral component of the effective load distri-
speed for activating Tn bution can be suspended with this parameter. For a 50 Hz installation
(=1500 rpm), only the integral component is calculated, if the current
engine speed lies between 1500 rpm ± of the set value. For a set val-
ue of 30 rpm, this would correspond to a speed range from
1470 to 1530 rpm. After load connections and load disconnections,
the speed governor is given time to settle before the integral compo-
nent of the actual effective load distribution is active. "Running away"
of the integral component, so-called overshoot or undershoot, can
thus be prevented.
Time for activating Tn if ms When the engine speed is back in the dead band, the set delay is
dead band is active started. When the delay has expired, the integral component is recal-
culated.
Loading the ramp rpm/s Parameters for the Ramp up function. The Ramp up function is need-
ed if the genset is connected a genset already in isolated operation.
The set speed preset of the MMC to the governor is increased linearly
to the actual setpoint linear by the set value (rpm/s).
Releasing the ramp rpm/s Parameters for the Ramp down function. The Ramp down function is
needed if a genset is deselected in isolated parallel operation (by de-
selecting the start request or controlled stop). The set speed preset
of the MMC to the governor is decreased linearly from the actual set-
point linear by the set value (rpm/s). The GCB opens at 1% generator
actual power.
Diesel setpoint ramp kW/s This parameter is normally required in grid backup mode via external
control engineering a diesel engine interface. In isolated parallel oper-
ation, the setpoint for actual power output in kW is preset by the ex-
ternal control engineering. The setpoint ramp indicates how fast (in
kW/s) the setpoint should approach the end value. The ramp is line-
ar.
TIM-ID: 0000062208 - 001
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 127
9.27 Parameters for frequency controller
The most important parameters for the frequency controller can be set here.
Parameter Unit Meaning
Synchronization: Kp – Proportional component of the frequency controller during
synchronization of the GCB or the mains circuit breaker.
The larger the value, the faster the governor.
Synchronization: Ki – Integral component of the frequency controller during syn-
chronization of the GCB or the mains circuit breaker. The
larger the value, the faster the governor.
Synchronization: Tn ms Run-on time of the frequency controller during synchroniza-
tion of the GCB or the mains circuit breaker. The smaller
the value, the faster the governor.
Isolated operation/idle: Kp – Proportional component of the frequency controller in iso-
lated operation or idle mode. The larger the value, the fast-
er the governor.
Isolated operation/idle: Ki – Integral component of the frequency controller in isolated
operation or idle mode. The larger the value, the faster the
governor.
Isolated operation/idle: Tn ms Run-on time of the frequency controller in isolated opera-
tion or idle mode. The smaller the value, the faster the gov-
ernor.
Max. difference frequency for syn- Hz The generator frequency is controlled to a certain extent via
chronization the busbar frequency/grid frequency.
The maximum difference frequency is set with this parame-
ter. Ultimately the spacing of the generator frequency to
the max. difference frequency can then be set using the
"Factor for generator frequency to max. difference frequen-
cy spacing" parameter.
Factor for generator frequency to – The generator frequency is controlled to a certain extent via
max. difference frequency spac- the busbar frequency/grid frequency.
ing. This factor determines the spacing of the generator fre-
quency to the max. difference frequency.
Delayed enable for GCB synchroni- s After the synchronization of the GCB has been initiated, this
zation delay time expires before the frequency controller.
Setpoint frequency in isolated op- Hz This setpoint is used for the frequency controller in isolated
eration operation.
TIM-ID: 0000062209 - 001
128 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
9.28 Data backup
General
Press the Time and date button on the Additional function page, with an active valid customer password lev-
el, switches to the Data backup page.
Saving Access databases / csv files and Zip files:
The following Access databases can be saved on a USB stick on this page:
• Data for Declaration of Conformity:
The most important software version numbers and energy measurement module parameters are logged
here in a csv file.
• Screenshot:
The screenshot images are stored here.
• MMC database:
A copy of the database is saved here.
• Alarm Logger database:
All fault and operating messages occurring in the last six months are logged here.
• Trending database (M-Graph):
The measured values recorded by the M-Graph in the last 12 months are logged here.
• Operating log:
The counter states of the last 365 days are stored here in a csv file.
• Interface protocol:
The interface protocol of the software interface executed in the project (e.g. Ethernet UDP) is saved in a
csv file.
• Engine recorder (only 4000 Series):
The Zip files from the engine recorder are located in the PLC and are copied onto the USB stick per FTP.
An engine recorder file saves predefined engine measured values in case of an engine malfunction as a
Zip file; the evaluation is intended for MTU Service.
The customer must carry out the analysis of the Access databases and csv files.
TIM-ID: 0000062210 - 004
Figure 38: MTU OAG standard
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 129
1 Certification data Data for Declaration of Conformity
2 Back up screenshot Back up screenshot
3 Back up MMC database Back up MMC database
4 Back up alarmlogger database Back up Alarm Logger data
5 Back up M-Graph database Back up Trending data
6 Back up operations diary Back up operating log
7 Interface protocol Interface protocol
8 Engine Recorder Engine recorder
Proceed as follows to copy the data to a USB storage medium:
• Insert a USB stick in a free USB slot
• Press the corresponding button (e.g. "Back up Alarm Logger data")
• Once data transfer to the USB stick is complete, the "Saved, OK" message appears
• The USB stick can be removed again after backing up the data
The Access databases are stored on the USB stick in the following directories:
Designation Description
Path MTU\YYYYMMDD project name
Legend –
YYYY Year number
MM Month
DD Day
The following file names are used for the databases:
• File name "Logging_alarm.mbd" for Alarm Logger database
• File name "Logging_Trending:mbd" for Trending database (M-Graph)
The csv file of the Declaration of Conformity data is saved on the USB stick under the "MTU" folder.
The csv file from the operating log is saved on the USB stick under the "MTU\Journal" folder.
Proceed as follows to move the screenshots onto a USB storage medium:
• Insert a USB stick in a free USB slot
• At least one image must be stored in the screenshot document file
• An "MTU\Screenshot" document file is created on the USB stick if it does not exist
• When backing up the screenshots, the files are move to the USB stick and hence no longer present on the
IPC
• Once data transfer to the USB stick is complete, the "Saved, OK" message appears. The switch can no
longer be pressed until a new image is present in the screenshot document file
• The USB stick can be removed again after backing up the data
Proceed as follows to move the interface protocol onto a USB storage medium:
• Insert a USB stick in a free USB slot
• The interface protocol must be created under "External communication" → Interface status → Pressure
button.
• An "MTU\InterfaceProtocol" folder is created on the USB stick if it does not yet exist.
TIM-ID: 0000062210 - 004
• When backing up the interface protocol, the files are moved to the USB stick and are therefore no longer
present on the IPC.
• Once data transfer to the USB stick is complete, the "Saved, OK" message appears. The switch can no
longer be pressed until a new interface protocol is available.
• The USB stick can be removed again after backing up the data.
130 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
9.29 Heating water (optional)
Screen page
Figure 39: Heating water
1 Setpoint Specified value
2 Actual value Actual value
3 Control variable Correcting variable
4 Manual Manual
Heating water pump via frequency converter (FC):
The activation of the heating water pump by means of the frequency converter is shown in the upper part of
the window. To do so, a PI controller is used which outputs the setpoint (0 to 10 V) to the frequency convert-
er. The setpoint can also be set manually.
Parameters for frequency converter (FC):
The control parameters of the PI controller are identical with those of the water temperature controller. But
there are no warm-up, run-on times or start setpoint.
TIM-ID: 0000062211 - 003
MS60024/05E 2019-03 | Operation and Visualization - Additional Functions | 131
9.30 Additional controller (optional)
Screen page
Figure 40: Additional controller
1 Additional controller 1 Additional controller 1
2 Additional controller 2 Additional controller 2
3 Setpoint Specified value
4 Actual value Actual value
5 Control variable Correcting variable
6 Manual Manual
Additional controller:
Two additional controllers are available.
The first additional controller is shown in the upper section of the window; the second additional controller in
the lower section. A separate PI controller is used for every additional controller. The setpoint can also be set
manually for each controller.
TIM-ID: 0000086165 - 001
Parameters for additional controllers:
The control parameters of the PI controller are identical to those of the water temperature controller.
132 | Operation and Visualization - Additional Functions | MS60024/05E 2019-03
10 Appendix A
10.1 Translation to the national language
A A
Accept Apply
Active Active
Active operation mode Current operating mode
Active energy Active energy
Actual power Actual power value
Actual Tecjet position Current position of TecJet
Actual value Actual value
Adjustment Correction
Alarmlogger Alarm Logger
Alarms Fault messages
Alignment Adjustment
Alive counter Bus monitoring
Anti knocking control Knock control
Automatic mode Automatic mode
Auxilary drives Auxiliary drive units
Auxiliary features Additional functions
Average angle of rotation Angle of rotation average fluctuation
Always off Always off
Always on Always on
B B
BACnet BACnet
Basic version Basic version
Build Build
Biogas Biogas
btdc Before TDC
C C
Cancel Cancel
Certified tasks Certified tasks
Cleaning window Cleaning window
Clockwise rotating Clockwise rotating field
TIM-ID: 0000070124 - 001
Close Closing / closed
Closing time Closing time
Compression test Compression measurement
Constant Fixed value
Controller for CH 4 CH4 control
Control number Control no.
Control unloading Controlled release
Control valve Regulating valve
MS60024/05E 2019-03 | Appendix A | 133
Control valve gas line Gas line regulating valve
Control variable Correcting variable
Coolant engine inlet Coolant before engine
Coolant engin outlet Coolant downstream of engine
Counter Counter
Counter reading Counter reading
Cranking Starting process
Current angle of rotation Current angle of rotation fluctuation
Current steps Current steps
Current User: - Logout-Time is: - Current User: - Logout-Time is: -
Cylinder Cylinder
D D
Date Date
Delay Delay
Demand open safety shut-off valve Request opening of safety shutoff valve
Description Description
Deselection Deselecting
Detonation level Signal level
Detonation system Anti-knock regulator
Deviation Deviation
Deviation setpoint/actual value Setpoint/actual value deviation
Diff. angle Difference angle
Diff. voltage Difference voltage
Draining Drain
E E
Electrical data Electrical data
Emergency cooler and pump Emergency cooler blower and pump
Engine overview Engine layout
Exhaust gas damper Exhaust flap
Exhaust heat exchanger Exhaust gas heat exchanger
External button Remote button
External communication External communication
External tank Remote tank
F F
Fault Fault
Fault messages button Fault messages button
TIM-ID: 0000070124 - 001
• E: EMERGENCY STOP • N: EMERGENCY STOP
• S: Stop • S: Stop
• A: Alarm • A: Alarm
Firing Ignited
Filling Filling
Filter Filters
Fixed value Fixed value
Fellow-up time Run-on time
134 | Appendix A | MS60024/05E 2019-03
Fermentation gas Biogas
Friday Friday
Fresh oil tank fill level Fresh oil tank filling level
Fresh oil tank leakage Fresh oil tank leak
Fresh oil tank overfill Fresh oil tank overfilling
Frequency converter Frequency converter
Friction correction Friction correction
FRT Counter FRT counter
Fellow-up time Run-on time
Ethernet UDP Ethernet - UDP
G G
Gas compressor Gas compressor
Gas exchange Gas exchange
Gas leak test Gas leak test
Gas line Gas line
Gas pressure inlet (abs) Absolute gas pressure at inlet
Gas system Gas system
Gas tank Gas tank
Gas temperature Gas temperature
Gas valve open Gas valve open
GCB closed Gen. circuit breaker off
GCB - Switching cycles Gen. circuit breaker switching cycles
Generator Generator
Glead grounde Glead, grounded
Global ISP Global ignition time
Grid code Grid code
Grid feed-in control Grid feed-in control
Grid ok Power grid settled
H H
Heat operation Heat mode
Heating operation - floating Heat mode – floating
Heating operation - limit Heat mode - limitation
Heating water Heating water
Heating water inlet Heating water inlet
Heating water outlet Heating water outlet
Heating water pump FC Heating water pump FC
TIM-ID: 0000070124 - 001
Heating water reservoir Buffer reservoir
Home button Home button
I I
Individual ignition adjustment Individual ignition time
Ignition energy Ignition energy
Ignition system Ignition system
Ignition timing Time of ignition
Ignition time adjustment Ignition time adjustment
MS60024/05E 2019-03 | Appendix A | 135
Ignition voltage Ignition voltage
Info button Info button
Inlet Inlet
Insync Index registr.
Intake air Intake air
Interval Interval
Island op. Grid substitute
J J
K K
Knock integrators Knock integrators
Knock signal Knock signal
L L
Lambda controller Lambda controller
Lambda offset CH 4 Lambda offset CH4
Load release Load enabling
Load sharing island parallel mode Load divider isolated parallel operation
Load steps Load stages
Loading shedding Load shedding
Local Location
Login Logon
Login button Logon button
Logoff Logoff
Low gas correction Low gas correction
Lube oil pressure Lube oil pressure
Lube oil refill Oil refill point
Lube oil system Oil system
Lube oil tank 1 (2) overfilled Overfilling in lube oil tank 1 (2)
Lube oil tank 1 (2) leckage Leak in lube oil tank 1 (2)
Lube oil tank 1 (2) fill level > max. Filling level > max. in lube oil tank 1 (2)
Lube oil tank 1 (2) fill level < min. Filling level < min. in lube oil tank 1 (2)
Lube oil temperature Lube oil temperature
M M
Main menu Main menu
Mains failure Grid failure
Mains frequency Grid power frequency
Manual Manual
TIM-ID: 0000070124 - 001
Manual mode (key switch) Manual mode (key switch)
Message number Message no.
M-Graph: Single channel M-Graph: Single channel
M-Graph: System intra-day M-Graph: System daily progression
M-Graph: System seconds graph M-Graph: System
Minimum opening Forced opening
Matches found Matches found
Misc. Miscellaneous
136 | Appendix A | MS60024/05E 2019-03
Misfire detection Misfire detection
Misfiring Misfire
Mixture Mixture
Mixture cooler and pump Blower mixture and pump
Mixture water temperature Mixture coolant temperature
Mixture cooling water after cooler Mixture water downstream of cooler
Modbus TCP Modbus TCP
Moving value Adjustable value
Monday Monday
N N
New switching point New switching threshold
No. serarch No. search
Nominal speed reached Rated Speed Reached
Normal operation Operation
O O
Oil refill counter Oil refill counter
Oil sump Oil pan
ok OK
Off Off
Offset island op. “Grid backup” offset
Offset of starting positi Offset of start position
On On
On-Impulse Switch-on pulse
Operation hours Operating hours
Open Opening / open
Optimisation Optimization
Outlet Outlet
Overload Overloading
Overview Overview
P P
Parameter Parameter
Parameterisation Parameterization
P-Coolant diff. Coolant pressure differential
P-Lube oil before filter Oil pressure before filter
P-Lube oil filter diff. Oil pressure filter differential
Pause time Interval period
TIM-ID: 0000070124 - 001
Password Password
Peak shaving operation Peak current mode
Phase Phase
Please connect usb device. Please insert your USB memory stick in the
USB slot.
Power Power rating
Power controller Power regulation
Power displacement Power adjustment
MS60024/05E 2019-03 | Appendix A | 137
Power factor controller Power factor controller
Power measurement module Energy Measurement Module
Power reduction Power reduction
Power reduction steps Power reduction levels
Preheating unit Preheater
Prelubrication Oil priming
Profibus DP Profibus DP
Profinet Profinet
Propane Propane
PMM EMM
PSC reduction stage Power supply company reduction level
PSC stop Power supply company stop
Pulse duration Pulse time
Pulse mode active Pulse mode active
Q Q
R R
Ramp active Ramp active
Reduction stage Reduction level
Reduction value Reduction value
Reference Reference
Ref. drive Stepper motor
Reference drive active Reference run
Release Approved / Not approved
Release module Enable module
Release module is still active Enable module is still active
Remote Remote
Reset Reset
Returning to no Outgoing
Rising Incoming
r-max r-stepper motor
Room air fans Room blower
Running Running
Running time Runtime
S S
Safety shut-off valve Safety shutoff valve
Saturday Saturday
TIM-ID: 0000070124 - 001
Saving Fuse
Selection Selecting
Service menu Service menu
Setpoint Specified value
Setpoint actual Current specified value
Setpoint correction Specified value correction
Setpoint max. Max. specified value
Setpoint min. Min. specified value
138 | Appendix A | MS60024/05E 2019-03
Setpoint operation mode Operating mode specified value
Setpoint ramp medium voltage Medium voltage ramp specified value
Source Source
Speed Engine speed
Speed adjustment Speed/power adjustment
Speed controller / starter Speed control / starter
Speed release Speed enabling
Start condition Starting conditions
Start counter Start counter
Start request Start request
Start setpoint Start setpoint
Start-/Stop procedure Start/stop procedures
Status Operational messages
Status Status
Steps Steps
Sum Total
Sunday Sunday
Switch on Cut-in
Switch-on-pulse Switch-on pulse
Sync-mode Synchronizing mode
System overview Overview of systems
T T
Tank level > max. Tank level > max.
Thuesday Tuesday
Thursday Thursday
Time Time
Time and date button Time and date button
Time program Time program
Timer Timer
Trying Attempt
to lean make lean
to rich enrich
U U
Unit Unit
Unloading Unload
User User
TIM-ID: 0000070124 - 001
Utilization factor kVar Utilization factor kVar
V V
Value Value
Valve Valve
Version Version
Via Interface Via interface
Voltage Voltage
Voltage controller Voltage regulator
MS60024/05E 2019-03 | Appendix A | 139
Voltage-/power factor controller Voltage / Power factor (cos-phi) regulator
W W
Water temperature controller Water temperature controller
Warm-up ramp Warm-up ramp
Warm-up time Warm-up time
Waste oil solenoid valve Used oil solenoid valve
Waste oil tank fill level > max. Used oil tank filling level > max.
Waste oil tank leakage Used oil tank leak
Waste oil tank overfill Used oil tank overfilling
Waste/Prelube oil pump Used oil/oil priming pump
Water system Water system
Wednesday Wednesday
Write Parameter Accept parameters
X X
Y Y
Z Z
TIM-ID: 0000070124 - 001
140 | Appendix A | MS60024/05E 2019-03
10.2 Abbreviations
Abbreviation Meaning Explanation
ANSI American National Standards Institute –
AUX Auxilary-drives panel Auxiliary drives panel
BHKW (CHP) Blockheizkraftwerk Combined heat and power plant
CAN bus Controller Area Network-Bus Serial field bus system
CSA Canadian Standards Association Approval for USA and Canada
DIN Deutsche Institut für Normung e.V. German Standardization Organization, at the
same time identifier of German standards
(“Deutsche Industrie-Norm”)
DP Dezentrale Peripherie Communication record
ECU Engine Control Unit Engine governor
EEG (Renewa- Erneuerbare Energien Gesetz –
ble Energy Act)
EMM Energiemessmodul Energy Measurement Module
EMU Engine Monitoring Unit Engine monitoring unit
GCB Generator circuit breaker Generator circuit breaker
HTB heat–recovery–module terminal – box Heat recovery module terminal box
IEC Internationale elektrotechnische Kom- –
mission
IPC Industrie-PC Industrial PC
MCS MTU Control System MTU master control system
MIP MTU Interface Panel MTU Interface Panel
MMC MTU Genset control enclosure MTU Module / Genset, control cabinet
SMS Short Messages Service –
PLC Speicherprogrammierbare Steuerung Programmable Logic Controller
TCP Transmission Control Protocol –
UDP User Datagram Protocol –
UL Underwriters Laboratories Certification for USA
TIM-ID: 0000061969 - 005
MS60024/05E 2019-03 | Appendix A | 141
10.3 MTU Onsite Energy contact person / service partner
Service
The worldwide network of the sales organization with subsidiaries, sales offices, representatives and custom-
er service centers ensure fast and direct support on site and ensure the high availability of our products.
Local Support
Experienced and qualified specialists place their knowledge and expertise at your disposal.
For our locally available support, go to MTU's Internet site:
• http://www.mtuonsiteenergy.com/haendlersuche/index.de.html
24-h Hotline
With our 24-h hotline and the flexibility of our service staff, we are always ready to assist you - either during
operation, for preventive maintenance, corrective work in case of malfunction or changed operating condi-
tions, or for spare parts supply.
For our locally available support, go to MTU's Internet site:
• http://www.mtuonsiteenergy.com/haendlersuche/index.de.html
Your contact at Headquarters:
• info@cac-mtuonsiteenergy.com
Spare Parts Service
Quick, easy and correct identification of the spare part required for your system. The right spare part at the
right time at the right place.
With this aim in mind, we can call on a globally networked spares logistics system.
Your contact at Headquarters:
Germany:
• Tel.: +49 821 74800
• Fax: +49 821 74802289
• E-mail: spareparts-oeg@mtu-online.com
Worldwide:
• Tel.: +49 7541 908555
• Fax: +49 7541 908121
• E-mail: spare.parts@mtu-online.com
TIM-ID: 0000002624 - 006
142 | Appendix A | MS60024/05E 2019-03
11 Appendix B
11.1 List of Figures
Figure 1: Function keys 33
Figure 2: Version information 34
Figure 3: Start request 36
Figure 4: Logon form 37
Figure 5: Counter reading 41
Figure 6: Electrical data 43
Figure 7: EMM 47
Figure 8: Voltage regulator / power factor
controller 48
Figure 9: Water system 52
Figure 10: Gas system 55
Figure 11: Gas leak test 60
Figure 12: Oil system 61
Figure 13: Alarm Logger 66
Figure 14: Alarm Logger 67
Figure 15: Power controller 69
Figure 16: Start/stop sequence 75
Figure 17: Water temperature controller 80
Figure 18: Water temperature controller 82
Figure 19: Mixture blower and pump 85
Figure 20: Mixture blower and pump 86
Figure 21: Preheater 87
Figure 22: Emergency cooler blower and pump 89
Figure 23: Emergency cooler blower and pump 91
Figure 24: Room blower 94
Figure 25: Room blower 95
Figure 26: Switch 101
Figure 27: Engine heat mode 105
Figure 28: Engine heat mode 106
Figure 29: Timer 112
Figure 30: Timer 113
Figure 31: External communication 116
Figure 32: Parameter window 117
Figure 33: M-Graph: Single channel 118
Figure 34: M-Graph: System 120
Figure 35: M-Graph: System 121
Figure 36: M-Graph: System daily progression 122
Figure 37: Load divider isolated parallel operation 125
Figure 38: MTU OAG standard 129
Figure 39: Heating water 131
DCL-ID: 0000038395 - 006
Figure 40: Additional controller 132
MS60024/05E 2019-03 | Appendix B | 143
11.2 Index
A Gas system 54
Abbreviations 141 – Single-gas operation 55
Additional controller 132 – Two-gas operation
Additional functions – one gas train 56
– Overview 79 – two gas trains 57
Alarm Logger 66 Gas tank 99
Generator data 50
B Grid backup mode 23
Battery shutdown 14 – via external control system 24
Boiler Grid feed-in control 101
– Heat mode 109 Grid code 44
Buffer reservoir 111
H
Bypass flap control 104
Heat mode
C – Boiler 109
CH4 control 97 – Engine 105
Cleaning window 77 Heating water 131
Contact person
I
– MTU Onsite Energy 142
Counter reading 41 Installation 6
CPU 10
L
Critical fault messages 15
Load distributor
D – Parameters 127
Data backup 129 Load divider isolated parallel operation 125
Display 31 Load stage control 45
Logon 37
E
M
Electrical data 43
Emergency cooler blower Main menu
– Pump 89 – Operation 39
Emergency cooling water controller 88 – Visualization 39
EMERGENCY STOP 29 Maintenance 16
EMM 47 Menu bar
Energy Measurement Module 47 – Description 33
Engine Messages
– Heat mode 105 – External communication 116
Engine overview 42 – e-mail 115
Exhaust flap control 104 – SMS 115
MIP
F – System description 8
Fault messages 64 Mixture blower
Floating contacts – Pump 85
– General 26 MMC
DCL-ID: 0000038395 - 006
– MIP 27 – System description 7
– MMC 28 Module control cabinet 13
Frequency controller MTU Onsite Energy
– Parameters 128 – Contact person 142
– Service partner 142
G M-Graph
Gas compressor 58 – Daily progression 122
– via frequency converter 59 – Single channel 118
Gas leak test 60 – System seconds graph 120
144 | Index | MS60024/05E 2019-03
O W
Oil system 61 Water mixture controller 84
Operating mode Water system 52
– Automatic mode 22 Water temperature controller 80
– Manual mode 21 – Via two control loops 82
Outside temperature shift 110 Wiring diagram documentation 12
P
Parameter entry 32
Parameters
– Frequency controller 128
– Load distributor 127
Plant
– Stop
– Stop sequence 19
Power controller 69
– Automatic mode 72
– Manual mode 71
Power controller
– Origin of the setpoint 70
Power factor controller 48
Power reduction 51
Protective devices
– Selectivity 11
Pump
– Emergency cooler blower 89
– Mixture blower 85
Pushbutton 29
R
Room blower control 94
Room temperature controller 93
S
Safety chain 9
Safety notes 5
Screenshot function 124
Selector switch 29
Service menu 78
Service partner
– MTU Onsite Energy 142
Starting sequence 75
Status signals 65
Stop sequence 75
Switching the grid on 25
System
– EMERGENCY STOP 20
DCL-ID: 0000038395 - 006
– Start 17
System description
– MIP 8
– MMC 7
System overview 40
T
Timer 112
Translations 133
V
Voltage regulator 48
MS60024/05E 2019-03 | Index | 145