Cable HV Test Report

This document summarizes a high voltage cable acceptance test. The test was performed on a 33kV XLPE insulated cable using a GH5238 test equipment. The test applied voltages of 19kV and 44kV at 0.1Hz for 1 and 60 minutes respectively. The cable passed with measurements of 444nF capacitance and over 20GOhm resistance at each test step, indicating no breakdown occurred. The cable was deemed acceptable based on the test results.

Uploaded by

Ahmed Rabaa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
97 views1 page

Cable HV Test Report

This document summarizes a high voltage cable acceptance test. The test was performed on a 33kV XLPE insulated cable using a GH5238 test equipment. The test applied voltages of 19kV and 44kV at 0.1Hz for 1 and 60 minutes respectively. The cable passed with measurements of 444nF capacitance and over 20GOhm resistance at each test step, indicating no breakdown occurred. The cable was deemed acceptable based on the test results.

Uploaded by

Ahmed Rabaa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 1

HVA Report IS1-C.

B-B1 Page 1 of 4

Company Location
Customer PO# Owner
Job# Owner
Representative
Date 1/17/2020 12:48:00 PM Temperature
Tested by Humidity
Substation Position
Circuit ID IS1-C.B-B1
Device Under Test is Cable
Rated Voltage 33.0 kV Operating Voltage
Manufacturer Model
Insulation Type XLPE Insulation Thickness
Shield Type Grounding
Conductor Size Conductor Material
# of Conductors Length
Installed in Age
Cable Test End Cable Far End
Termination Type Termination Type
# of Splices Splice Locations
Jacket (Y/N) - Jacket Integrity

Equipment
Equipment Used GH5238 Serial No. GH5238.17E018

Test Setup
Type of HV Test Acceptance Test Voltage 19.0 / 44.0 kVrms
Waveform Sine Planned Test 1 / 60 min
Duration
Frequency 0.1 Hz Current Limit Trip out on Arc

Measurements / Results
Breakdown No Breakdown Voltage
Time to Failure
Acceptance Test finished successfully
Step Voltage Current Load Cap. Load Res. Frequency
1 19.0 kVrms 5.30 mArms 444 nF >20 GOhm 0.1 Hz
2 44.0 kVrms 12.3 mArms 444 nF >20 GOhm 0.1 Hz
3
4

Test Result X Acceptable Unacceptable

Comments