HVA Report IS2-IS1: Acceptance Test Finished Successfully

This document summarizes the results of an acceptance test on a 33 kV XLPE insulated cable. The test was performed using a GH5238 test equipment and subjected the cable to alternating voltages of 19.0 kV and 44.0 kV at 0.1 Hz for 1 and 60 minutes respectively. The cable passed the test with no breakdown occurring and measurements of load capacitance and resistance within acceptable ranges.

Uploaded by

Ahmed Rabaa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
69 views1 page

HVA Report IS2-IS1: Acceptance Test Finished Successfully

This document summarizes the results of an acceptance test on a 33 kV XLPE insulated cable. The test was performed using a GH5238 test equipment and subjected the cable to alternating voltages of 19.0 kV and 44.0 kV at 0.1 Hz for 1 and 60 minutes respectively. The cable passed the test with no breakdown occurring and measurements of load capacitance and resistance within acceptable ranges.

Uploaded by

Ahmed Rabaa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 1

HVA Report IS2-IS1 Page 1 of 3

Company Location
Customer PO# Owner
Job# Owner
Representative
Date 11/26/2019 1:04:00 PM Temperature
Tested by Humidity
Substation Position
Circuit ID IS2-IS1
Device Under Test is Cable
Rated Voltage 33.0 kV Operating Voltage
Manufacturer Model
Insulation Type XLPE Insulation Thickness
Shield Type Grounding
Conductor Size Conductor Material
# of Conductors Length
Installed in Age
Cable Test End Cable Far End
Termination Type Termination Type
# of Splices Splice Locations
Jacket (Y/N) - Jacket Integrity

Equipment
Equipment Used GH5238 Serial No. GH5238.17E018

Test Setup
Type of HV Test Acceptance Test Voltage 19.0 / 44.0 kVrms
Waveform Sine Planned Test 1 / 60 min
Duration
Frequency 0.1 Hz Current Limit Trip out on Arc

Measurements / Results
Breakdown No Breakdown Voltage
Time to Failure
Acceptance Test finished successfully
Step Voltage Current Load Cap. Load Res. Frequency
1 19.0 kVrms 2.18 mArms 182 nF 5.0 GOhm 0.1 Hz
2 44.0 kVrms 5.04 mArms 182 nF 1.7 GOhm 0.1 Hz
3
4

Test Result X Acceptable Unacceptable

Comments