Logik 9 is an industrial electronic controller suitable for operating low-to-medium sized screw compressors. It has basic functions and can be operated via an input for a pressure transducer that is software configurable. It has an RS485 serial port to connect to a PC for remote monitoring or to connect multiple Logik 9, 19, 26-S, or 33-S controllers for master-slave or multi-unit operation. It constantly monitors pressure, temperature, and alarms.

Uploaded by

sebastian
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views2 pages

2015 Logik 9 GB

Logik 9 is an industrial electronic controller suitable for operating low-to-medium sized screw compressors. It has basic functions and can be operated via an input for a pressure transducer that is software configurable. It has an RS485 serial port to connect to a PC for remote monitoring or to connect multiple Logik 9, 19, 26-S, or 33-S controllers for master-slave or multi-unit operation. It constantly monitors pressure, temperature, and alarms.

Uploaded by

sebastian
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

LOGIK 9 Electronic Controller Logik 9

Logik 9 is an industrial electronic control device suitable for the operation of low-medium size
screw compressors with basic functions. Thanks to the input for pressure transducer, settable via
software, Logik 9 allows to operate the compressor also by electromechanical pressure switch.
Logik 9 is provided with nr. 1 serial port RS485 suitable for the connection to PC through Logik
Ethernet Interface (remote monitoring) or to other compressors equipped with Logik 9, Logik 19,
Logik 26-S, Logik 33-S for Master/Slave or Multiunit operation.

Pressure - Temperature and


alarms constantly monitored

Visualizations:
- working pressure
- working temperature
- working hours
- maintenance timer

Alarms:
- wrong rotation - power failure
- generic alarm - starts/hour
- high temperature alarm - security pressure switch
- warning high temperature - high pressure alarm
- probe failure - transducer failure
- low temperature - emergency stop button

Via Garibaldi, 83A - 20834 Nova Milanese (MB) Italy


Tel. +39/0362/3700.1 - Fax +39/0362/370030
www.logikacontrol.it
LOGIK 9 TECHNICAL FEATURES

• Conformity to EC and UL 508 regulation ACCESSORIES:


• Inputs and outputs via terminal-block board to wires • nr. 1 temperature probe KTY 13.5 with rubber silicone
• Black auto-extinguishing box in ABS cable, length 2.5 m, working range –10° ÷ 130°C,
a) according EC: resolution 1°C, precision ± 1°C, to detect air-end
IP64 for the front panel and IP20 for the other parts; temperature
b) according UL: • nr. 1 pressure transducer 4-20 mA for working pressure
Type 1 and Type 12 for front panel mounting, control: 2 wires, AISI 316L stainless steel membrane,
installation in pollution degree 2 for the other parts working range 0 ÷ 15 bar, resolution 0,1bar,
• Working temperature: - 10°C (14°F) ÷ 50°C (122°F) precision ± 0,1bar.
90% RH (non condensing)
• Storage temperature: -20°C (-4°F) ÷ 70°C (158°F)
• Power supply: 12Vac ± 15% 50 ÷ 60 Hz
• Visualization through custom LCD
• nr. 4 key buttons: Start/Stand by + 3 function buttons
(up-down-enter)
• nr. 1 input for temperature probe to detect air-end
temperature
• nr. 1 input settable via software into pressure transducer
or electromechanical pressure switch
• nr. 4 opto isolated digital inputs 12/24Vac to detect:
- IN 1 = emergency stop button
- IN 2 = OR alarms
- IN 3 = phase sequence ralay
- IN 4 = remote start/stop (settable)
- IN 4 = air filter pressure switch (settable)
• nr. 5 outputs via relay with contact 1.5A max.:
- RL1 = line contactor
- RL2 = star contactor
- RL3 = delta contactor
- RL4 = load solenoid valve
- RL5 = alarm or fan contactor (settable) 61,6 mm

• nr. 1 serial port RS484 for:


- Master/Slave or Multiunit operation, connecton to PC
or Ethernet Interface (remote monitoring)
• Non volatile memory to store setting data, working
hours,compressor status, alarm list 166,6 mm
29 mm
• Check min. and max. power supply to the controller
• The controller switches OFF due to micro interruption
longer than ~ 300 ms

Via Garibaldi, 83A - 20834 Nova Milanese (MB) Italy


Tel. +39/0362/3700.1 - Fax +39/0362/370030
www.logikacontrol.it APRIL 2015 EDITION