Overview
    Power System Components
WESTCO | CORPORATE PROFILE
What is Protective Relay?
       In electrical engineering, a protective relay is a relay device designed to
       trip a circuit breaker when a fault is detected.
                             Detect and isolate the fault
                             Preserve continuity of supply
                                   sensors    current              Measure
                                               voltage
                                                                   Compare
                                         Tripping                  Decide
                                            coil
                               A protection device does not
                               prevent the fault from occurring,
                               but limits the consequences...
WESTCO | CORPORATE PROFILE
Power System Basic Requirements
      1. Selectivity also called discrimination
          a. Time grading
          b. Unit System
      2. Stability
      3. Speed
      4. Sensitivity
WESTCO | CORPORATE PROFILE
Basic Components of Protection
1. Voltage and Current Transformers
                         Voltage Transformer                 Current Transformer
                      P = Us2 / Z and Is = Us / Z           P = Z x Is2 and Us = Z x Is
           Never connect the VT in short-circuit       Never leave the CT in open-circuit
                                                    “CT star point should always towards the
                                                                 protected zone”
WESTCO | CORPORATE PROFILE
CT Protection Unit
WESTCO | CORPORATE PROFILE
Current Transformers
WESTCO | CORPORATE PROFILE
Voltage Transformers
WESTCO | CORPORATE PROFILE
 Basic Components of Protection
    2. Relays
    3. Fuses
    4. Circuit Breakers
    5. DC Batteries
WESTCO | CORPORATE PROFILE
BASLER Electric Solutions
 Typical Applications – BASLER Relays
WESTCO | CORPORATE PROFILE
Substation Bus & Breaker Protections
     1. Breaker Failure Protection = 50BF
     2. Stuck Breaker Protection = 51B
     3. Differential Busbar Protection = 87B
     4. Differential TEE Protection = 87TEE
     5. Pole Discrepancy Protection = PD
WESTCO | CORPORATE PROFILE
CB Trip Failure
WESTCO | CORPORATE PROFILE
UPPER BUS
LOWER BUS
UPPER BUS
LOWER BUS
  Breaker Failure Protection Solutions
    1. Supervision of the feeder current (with an overcurrent criteria) after a tripping
    Command
                             OR
    2. Supervision of the CB auxiliary contacts after a tripping command
                             OR
    3. Supervision of the feeder current (with the BBP measurement algorithm) after a
    Tripping command (only applicable if the BFP is installed in the BBP system)
    – BBP unbalancing
WESTCO | CORPORATE PROFILE
  Application & Features of Solution 1
  ➢ standard BFP application
  ➢ for line, transformer, generator, generator-transformer, reactors and coupler CB’s
  ➢ for all voltage levels and switchgear configurations
  ➢ overcurrent settable independently for all feeders (depending on the minimum
       feeder short current)
  ➢ operation independent on the CB auxiliary contacts (aux. contacts are a week part
       of the protection chain)
  ➢ for single, double and three phase auto-reclosure (tripping), (phase segregated
       starting inputs)
  ➢ for detection of evolving faults (phase segregated timers for t1)
  ➢ remote tripping signal settable after timer 1 or timer 2
  ➢ advanced trip redirection functionality in case of CB SF6 underpressure condition
WESTCO | CORPORATE PROFILE
  Application & Features of Solution 2
  ➢ applicable for very low fault currents (e.g. generator reverse power function)
  ➢ remote tripping signal settable after timer 1 or timer 2
  ➢ advanced trip redirection functionality in case of CB SF6 underpressure condition
  ➢ very good addition to solution 1
  ➢ no overcurrent (fault current) supervision
  ➢ the starting signal must be switch off by the CB “OFF” aux. contact to prevent an
       unwanted trip
  ➢ operation dependent on the CB auxiliary contacts (aux. contacts are a week part of
      the protection chain
  ➢ not applicable for single and double phase auto reclosure (tripping)
WESTCO | CORPORATE PROFILE
  Application & Features of Solution 3
 ➢ applicable as basic BBP coupler functionality for the detection of faults between
      coupler CB and CT (coupler function – CB reclaim time)
 ➢ not applicable for line, transformer, generator, generator-transformer, reactors
      feeders in HV system
 ➢ Overcurrent (fault current) supervision depending on the BBP differential current
      setting (high short current required)
 ➢ not applicable for single and double phase auto-reclosure (tripping)
 ➢ the starting signal must be switch off by the CB “OFF” aux. contact to prevent an
      unwanted trip to the CB after timer 1
 ➢ operation dependent on the CB auxiliary contacts (aux. contacts are a week part
      of the protection chain)
 ➢ no trip-redirection functionality in case of CB SF6 underpressure condition
 ➢ remote tripping signal fixed to timer 1
WESTCO | CORPORATE PROFILE
  Measuring Principle
  Kirchhoffs                 1st   Law: Node Rule
                                                         I2
       The sum of all currents must be zero
                                                    I1
       I1 + I2 + I3 = Σ I = 0                                 I3
WESTCO | CORPORATE PROFILE
Measuring Principle
Kirchhoffs   1st   Law: Node Rule
                                                  I2
     I1 + I2 + I3 = Σ I
     if ≠ 0 or                               I1
     if Σ I > differential current setting
                                                       I3
     Fault on the Busbar
     Trip Circuit Breaker
     Trip Busbar Protection
2. Stuck Breaker Protection = 51B
3. Differential Busbar Protection = 87B
Single Busbar with Section Coupler ( 1 coupler CT)
Single Busbar with Section Coupler ( 1 coupler CT)
Single Busbar with Section Coupler ( 1 coupler CT)
Single Busbar with Section Coupler ( 1 coupler CT)
Single Busbar with Section Coupler ( 1 coupler CT)
Single Busbar with Section Coupler ( 1 coupler CT)
  Coupler Functions I
        How can a busbar protection system detect a fault between the Coupler
       Circuit Breaker and Current Transformer?
       ➢ By deactivating of the current measurement in the coupler in case of
       Internal BBP tripping signal (= coupler blocking)
WESTCO | CORPORATE PROFILE
Differential Current Supervision
 Which failures in the CT circuits can the Differential current supervision
 detect?
 ➢ a missing CT input (e.g. CT circuit not connected to the system
 ➢ a wrong CT ratio
 ➢ a wrong current direction
 The “differential current alarm” is very important and must not be ignored
 by the operating personnel.
WESTCO | CORPORATE PROFILE
Double Bus Single Breaker Scheme
Breaker and a half scheme
87TEE-1
          87TEE-2
4. Differential TEE Protection = 87TEE
  5. Pole Discrepancy Protection
                             LOGIC
WESTCO | CORPORATE PROFILE
Multifunction Protection System
                                  Rear View
BE1-11 Family
 •   One software program for settings
 •   One logic library
 •   Many AC elements shared by all applications
 •   One easy to learn multifunction protection system covers most feeder,
     generator, intertie, motor, transformer, and DC Power applications
BESTCOMSPlus ®
  System Interface Software:
  • Metering explorer
  o Extensive real time and reporting capabilities.
  • Settings explorer
  o Quick and confident programming.
  o System summary
  o Compare settings
  o Visual logic and logic libraries
  o Compressed print preview
           BESTCOMSPlus ®             – Analog
                           Metering
•Meteringof all measured
and calculated values.
•Primaryand secondary
metering
•Phasor    diagrams
•Configurable
               BESTCOMSPlus –
                           ®       Status
•Inputs
                        Metering
•Outputs
•Targets
•Alarms
•Breaker     status
•All   digital points
•Configurable
              BESTCOMSPlus ®    – Reports
•Sequence       of events
•Fault   records
•Security   log
•Load    profile
•Breaker    monitor
•Differential   (g, m, t)
•Motor   starts (m)
•Transformer       damage (t)
     BESTCOMSPlus ®         – Demand
                    Metering
•Demand   current
•Demand   power
•Demand   vars
•Demand   VA
 BESTCOMSPlus –
             ®    Power Quality
•Voltage
•Distortion
•Dip/Swell
•Harmonics
            BESTCOMSPlus ®   – Control
•Virtual   switches
•Breaker    control switch
•Output    override
•Setting   group control
           BESTCOMSPlus ®   – Settings
•Intuitive   settings
•Meaningful     labels
•Built   in graphs
          BESTCOMSPlus –
                      ®          Settings
•Formatted   settings printout
•Easy   to read
•Showonly enabled
elements
           BESTCOMSPlus –
                       ®      Settings
•System   summary
•Easy confirmation of relay
setting
•Enabled    and pickup set
•No   pickup set
•Pickupset but mode
disabled
•Disabled
                        BESTlogic™Plus
•Programmable   logic
•Powerful tool within
BESTCOMSPlus®
featuring innovative and
comprehensive logic
schemes.
•Preprogrammed
BESTlogic™Plus schemes
provide a starting point for
customer applications.
•Userfriendly interface for
customizing schemes
                           BESTlogic™Plus
•Large
     selection of logic
elements
•Drag   and drop logic
•Visual   connectivity
•Self   documentation
•User   annotations
•On-line   logic library
                         BESTlogic™Plus
•Logic   file printout
•Provides a means of
making logic available
on location without
a computer.
             BESTlogic™Plus
•Offline
•Logic
•Simulator
        Communications Protocols
•   Modbus®   available over Ethernet and RS-485
•   DNP3 available over Ethernet and RS-485
•   IEC 61850
                            IEC 61850
•   Easily configure and document IEC 61850 between devices from several
    suppliers with BEST61850™.
•   Import and export Substation Configuration Language (SCL) files to
    simplify system setup.
•   Detect and report errors by comparing SCL files to the IEC 61850
    requirements.
•   Reduce engineering effort with intuitive drag and drop graphical user
    interface.
                            IEC 61850
•   Capable of Goose network containing greater than 255 devices
•   Supports configurable buffered reports
•   Enter style to create CID file
•   Alarm on the loss of any device subscribed to IEC 61850
Protection Testing
& Power System
Simulation
     Introduction to Testing
     1. Acceptance (or integrity) Testing
     2. Commissioning Testing
     3. Periodic Testing
     4. Functional Testing
     5. Performance Testing
WESTCO | CORPORATE PROFILE
          Test Automation
                             Result
                                      Output Contact
WESTCO | CORPORATE PROFILE
                    DOBLE F6150 – Power System Simulator
FOR TESTING ALL TYPES OF RELAYS
Technical Specifications :
Total Sources
The F6150 can provide up to twelve simultaneous user configurable AC/DC sources
including: six convertible sources and six current sources.
Convertible Sources
Each 150 VA Convertible Source can be used as a voltage source or optionally as a
high-power, low range current source. The F6150 has up to six Convertible Sources.
Source Configurations
Output Power
Continuous Transient for 1.5 Seconds Number of Sources
Each 150 VA convertible source can be split into two 75 VA sources.
Two 150 VA convertible sources can be combined in parallel into one 300 VA current source.
Three 150 VA convertible sources can be combined in parallel into one 450 VA current source.
WESTCO | CORPORATE PROFILE
                    DOBLE F6150 – Power System Simulator
     ▪ Using a Personal Computer and Protection suite software it is possible to test all types of
       relays, meter and PMUs.
     This includes
     ▪ Testing of high impedance ground over current using one convertible source at low
       current range high power.
     ▪ Testing of over current relay at high current up 210 A using transient mode
     ▪ Testing of modern numerical protection scheme, which may require up to 12 sources.
     ▪ F6150 allows steady state testing, dynamic state testing, transient testing and end to end
       protection scheme testing.
     ▪ Built in test routine to test PMU per IEEE C37.118
     ▪ Protection Suite allows users to test IEC61850 protections easily
WESTCO | CORPORATE PROFILE
                    DOBLE F6150 – Power System Simulator
WESTCO | CORPORATE PROFILE
  Requirements for Protection Testing
    • Single Line Diagram with Current & Voltage Transformer Data
    • Protection Logic Diagram
    • User Instruction Manual
    • Schematic Diagram / Three Line Diagram
    • Approved Final settings (based of Protection Coordination Study)
WESTCO | CORPORATE PROFILE
   Common Issues in Protection Testing
   ▪ Actual Current Transformer Polarity and Ratio
   ▪ Actual Current Transformer Position/Location based on protected zones
   ▪ Input and Output Logic Configuration
   ▪ Time Grading/Wrong and poorly coordinated settings
   ▪ Defects in the wiring to the relays
   ▪ Unforeseen faults at the design stage
   ▪ CT Single point earthing
   ▪ CT position/shielding of power cable entry
   ▪ Proper wiring supervision (trip circuit, DC supply)
   ▪ Schematic drawings not updated
   ▪ Termination of wire without removing the insulation
WESTCO | CORPORATE PROFILE
   Partners
                             The brain-child of Engr. Rodolfo R.
                             Peñalosa, PAMAVTech specialises in
                             competency-based and hands-on
                             technical trainings for practicing
                             professionals
                             A trading corporation established in 1990
                             to handle industrial electro-mechanical
                             and electrical devices
WESTCO | CORPORATE PROFILE
Questions?
Address:   8F, 68 Kalayaan VCP Building, 68 Kalayaan Avenue
           Teachers’ Village West, Quezon City 1101
Tel No.:   (632) 8365-0068
Email:     admin@westco-phil.com
           sales@westco-phil.com
Website:   www.westco-phil.com