Selecting and deciding on circuit breakers
made easy with IEC specifications
                                                                                              Er. Say Leong LIM
                                                                                                     2019-11-29
Leading Global Electrical Equipment & Integrated Supplier
Purpose of my talk
•   Show the differences between the IEC standard specifications for circuit breakers
•   Stress the importance of differentiating between the users – important for safety
•   Explain the approach to select the circuit breakers in terms of load and fault current
•   Explain the co-ordination requirement
CHINT Project icons star
Shanghai, November 2018
InterContinental Shanghai Wonderland made history
• 88m deep hotel
• cling to a cliff below the horizon in a retired quarry
• one of the world's top 10 architectural wonders
CHINT & SUNLIGHT Project icons star
Shanghai, November 2018
InterContinental Shanghai Wonderland
CHINT Electric supplied the low-voltage
power distribution equipment
Environmental challenge                                CHINT made history
• corrosion protection using multi-process
   anticorrosive treatment to enhance performance
   by more than 50%
• seismic protection using innovation design and
   simulation analysis to ensure the equipment has a
   scale 9 seismic withstand
Component - Low Voltage
  Low Voltage Products
      The most complete low voltage product line: over 100 series and 10,000 specifications
      The largest manufacturer of LV electrical products in China
                                                                                              5
Continuously to be One-Stop Solution Provider
        Miniature                   Molded case         Air-break
     circuit breaker               circuit breaker   circuit breaker
          MCB                           MCCB               ACB
                                                                       6
  Values above functions
                                          Operating & Maintenance
                                               Cost Reduction
 Installation Space Saving                    System Efficiency Up                         Energy Loss Down
            -25%                                    +10%                                         -30%
                                                                                      NVF300 Series inverter
More Compact Product Series than before   Power Generation with your own properties              NCW all film shunt capacitor
                                                                                                                                7
Purpose of circuit breakers
          Protection of people and property by
         watching the electric circuit condition for
              overloading and short circuit
Global Standard Specifications - IEC
Circuit breaker
A mechanical switching                    ACB
device capable of
making, carrying and
breaking currents under
normal circuit conditions;
and also making,
                                   MCCB
carrying for a specified
time and breaking
currents under specified
abnormal circuit             MCB
conditions such as those
of short-circuit.
Function of circuit breaker
                              Utility supply
 • Isolate for safety         MV/LV transformer
 • Disconnect when
                                        Main LV switchboard
   danger arises
                                                   LV Power
                                                  switchboard
                                                     LV final
                                                   distribution
International Standards Developers
       The International Electrotechnical Commission website
       states:
                “The International Electrotechnical Commission
       (IEC) is the leading global organization that prepares
       and publishes international standards for all electrical,
       electronic and related technologies. These serve as a
       basis for national standardization and as references
       when drafting international tenders and contracts.”
       IEEE and IEC harmonize their standards, where possible
International Electrotechnical Commission
      • IEC - the leading global organization that prepares and
        publishes international standards for all electrical, electronic
        and related technologies.
      • These serve as a basis for national standardization and as
        references when drafting international tenders and contracts –
        like for CIRCUIT BREAKERS
      • IEC 60898 for circuit breakers up to 440V, 125A and 25 kA.
        Circuit breakers for use by uninstructed people and not to be
        maintained
      • IEC 60947-2 for circuit breakers up to 1000V, for whatever the
        rated current and short-circuit. Circuit breakers for use by the
        instructed people and to be maintained.
Global Standard Specifications - IEC
  •   Use by uninstructed person   •   Use by instructed person
  •   Not meant to be serviced     •   Needs to be serviced
Current-limiting MCB
Values of peak cut-off current and let-through energy
                                                                              Ip
           I
               Prospective short-circuit current
                                                                                       Icc
                      Limited short-circuit current
                                                                Prospective
                                                                peak value     I2t
                                                      Limited
                                                       peak
               Specific let-through                    value
                     energy
                                                                                   t
                                                                                        Icc
MCB of UL 489 vs IEC 60898
Current-limiting MCB vs Zero point extinguishing MCB
                             • Current limiting type of MCB to IEC 60898
                   t ms        would normally passed to UL 489.
                             • On the contrary, zero point extinguishing
                               type MCB to UL 489 would not necessarily
                   t ms
         3   8.3               passed to IEC 60898. Very likely can only
                               passed to IEC 60947-2.
                   t ms
                             • Between IEC 60898 & IEC 60947-2, for the
                               same duty IEC 60898 is more severe, in
                               the layman term.
                   t ms
             8.3
Engineered for uninstructed person safety
                                 IEC 61439-3 - distribution boards intended to be
                                 used by ordinary, uninstructed people and for not
                                 being maintained.
                                 IEC 60898-1 - MCB at 50/60 Hz, voltage not
                                 exceeding 440 V, current not exceeding 125 A and a
                                 rated short-circuit capacity not exceeding 25 kA.
IEC 61008-1   IEC 60898-1        Designed for use by uninstructed people and for not
                                 being maintained.
                   IEC 61439-3
                                 IEC 61008-1 – RCCB voltage not exceeding 440 V at
                                 50/60Hz and current not exceeding 125 A, intended
                                 principally for protection against shock hazard.
IIEE – The Fundamental Canons
1.To accept responsibility in making sound engineering decisions consistent with the safety, health and welfare of the public, and to disclose
1.To
promptlyaccept        responsibility
         the factors that                       in making
                          might endanger the public                  sound engineering decisions consistent with
                                                        or the environment;
the    safety,
2.To avoid          health
           real or perceived    andof interest
                             conflicts  welfare   wheneverof possible,
                                                               the public,          and
                                                                        and to disclose    toto affected
                                                                                        them    disclose  partiespromptly        the factors
                                                                                                                 when they do exist;
that    might endanger the public or the environment;
3.To be honest, objective, impartial and realistic in stating claims or estimates base on available facts
4.To prevent graft and corruption in all its forms
2.To avoid real or perceived conflicts of interest whenever possible, and to
5.To improve the understanding of technology and its advancement, its appropriate application, and potential consequences;
disclose      them to affected parties when they do exist;
6.To maintain and improve our technical competence and to undertake technological tasks for others only if qualified by education, training or
experience, or after full disclosure of pertinent limitations
3.To    be honest, objective, impartial and realistic in stating claims or estimates
7.To seek, accept, and offer honest and constructive criticism of technical work; to acknowledge and correct errors; and to credit properly their
base     on available facts
contributions;
8.To treat fairly all persons regardless of race, gender, disability, age or national origin
9.To avoid injury to other’s life property, reputation or livelihood by false or malicious actions; and
10.To assist colleagues and co-workers in their professional development and to support them in following this Code of Ethics.
   Philippines need to
consider circuit breakers
and enclosures to make
         it safe for
  uninstructed people,
     the Consumers
IEC 60947-2 for the instructed
Circuit-breakers voltage does not exceed 1 000
V a.c. or 1 500 V d.c.
Additional requirements                                  ACB
• integrally fused circuit-breakers.
• provide earth-leakage protection - Annex B
• circuit-breakers with electronic over-current
   protection - Annex F
• circuit-breakers for IT systems - Annex H
                                                  MCCB
The requirements for circuit-breakers for the
protection of wiring installations in buildings
and similar applications, and designed for use
by uninstructed persons, are contained in
IEC 60898.                             MCB
The requirements for circuit-breakers for
equipment (for example electrical appliances)
are contained in IEC 60934.
Think enclosures
Switchboard – safety and reliable service
Circuit breakers
Objective
 ▪ Fundamental requirement to prevent
    danger to person and property
How
                                                   Every live conductor
 ▪ Be alert all time to operate automatically on   needs to be protected
    overload or fault current                      in the event of:
Requirement
                                                    ▪ Overload current; and
 ▪ Adequate breaking capacity
 ▪ Operate safely without danger to person &        ▪ Fault or short circuit current.
    property in vicinity
 ▪ Ready and easy restoration
Illustration by products
                                                       NA8
      NM8LE          NM8             NM8                          NM8
                                                                                                 NZ7
     NB1LE           NB1
                           NC8                                             CJ19   NU6     NB1    NM8
                                                 NS2      NJR2      NVF2
                                           NR8
                                                                           NWC5    NCK3   NCH8   NB1
     NBH8LE   NBH8
                             motor    motor   motor    motor     motor
Circuit breaker – safe protection
Primary function is overcurrent protection
                                                Utilities supply
❑   Protect cable and                           MV/LV transformer
    components from damage
                                                          Main switchboard
    due to
    ▪ overload; or
    ▪ short circuit.                                                    Power
                                                                      switchboard
❑   Provide safe isolation.
❑   Protect against electric shock.
                                                                    Final or branch
                                      Protect                         distribution
                                       users
  Basic overcurrent protection
               Time (s)
                                                            Supply    ~
IB ≤ In ≤ Iz
I2 ≤ 1.45 Iz
                                                                          Cable
                                 Cable                         MCCB
 k2S2 = I2t
                                                                      Cable
                          MCCB
      S
  t=k
      I
                                   MCCB protects the cable by
                                   tripping before cable burns off.
                                            Load I(A)
Short circuit selection
For short-circuit protection, the                     Utilities supply
circuit breaker at the point of                       MV/LV transformer
installation should have a short-
                                       50kA or more             Main switchboard
circuit breaking capacity that is              50kA
sufficient to withstand the stresses
likely to occur.
                                                                              Power
                                                                            switchboard
                                                                          Final or branch
                                                                            distribution
Co-ordination
The circuit-breaker at the point of                    Utilities supply
installation could have a short-                      MV/LV transformer
circuit breaking capacity that is
                                      65kA or more                   Main switchboard
insufficient to withstand the                  65kA fault
stresses likely to occur.                            36kA rated CB
Then add another circuit-breaker at
the upstream.                                                                    Power
                                                            50kA fault         switchboard
Sometimes known as cascading,
or back-up protection.
                                                                            Final or branch
                                                                              distribution
Benefits of co-ordination
A lower breaking capacity is permitted if another protective device or devices having the
necessary breaking capacity is installed on the supply side.
In this situation, the characteristics of the devices shall be co-ordinated so that the energy let-
through of these devices does not exceed that which can be withstood, without damage, by
the device or devices on the load side.
When selecting circuit-breakers, consider the maximum let-through energy specified by the
manufacturer of the device, to ensure proper co-ordination.
The optimization of using circuit breakers to its full potential for the benefit of:
   •    Safe protection
         –    Proper discrimination
         –    Proper back-up protection
   •    Minimum use of space
   •    Easy installation design and selection.
As illustrated in IEC 60947-2
       Discrimination   Back-up   Discrimination   Back-up
             By current           By let-through energy
Co-ordination – The selection
                                            Utilities supply
Example of discrimination and
back-up values given by                    MV/LV transformer
manufacturer                    C2 65kA               Main switchboard
                                          C1 36kA
                                                                   Power
 Discrimination   C2 65kA                                        switchboard
    C1 36kA        14kA
                                                               Final or branch
    Back-up       C2 65kA                                        distribution
    C1 36kA        65kA
Level of discrimination
                                                          Utilities supply
Let us consider C2 and C1.
                                                          MV/LV transformer
 Discrimination         C2 65kA
    C1 36kA              14kA
                                         C2 65kA   Trip                Main switchboard
                                                      C1 36kA   Trip
 Fault at Fault value     C2      C1
                                                      Z
   W          5kA         ON      Trip
    X         10kA        ON      Trip                Y
    Y         14kA       Trip     Trip                X
                                                      W
    Z         36kA       Trip     Trip
Co-ordination – The selection
                                                      Utilities supply
When selecting circuit-breakers,
consider the maximum let-                            MV/LV transformer
through energy specified by the           C2 65kA               Main switchboard
manufacturer of the device, to
                                                    C1 36kA
ensure proper co-ordination.
                                                                             Power
 Discrimination   C2 65kA                                                  switchboard
    C1 36kA        14kA     Selectivity
                                                                         Final or branch
    Back-up       C2 65kA                                                  distribution
    C1 36kA        65kA
Back-up potection
                                                 Utilities supply
The combined breaking of the
fault current in the circuit by C2              MV/LV transformer
and C1 will have the capability      C2 65kA               Main switchboard
to break 65kA
                                               C1 36kA
      Back-up      C2 65kA                                              Power
                                                                      switchboard
      C1 36kA       65kA
                                                                    Final or branch
                                                                      distribution