On-site testing with AC voltages
Stefan Bergmann
HIGHVOLT Prüftechnik Dresden GmbH
   On-site testing with AC voltages
     Growing power demand and the impact on the grid
                                  forecast of required electrical energy                  Consequences for the grid:
                            120
                            100                                                           ▪ Extension of grid capacity
    electric power in TWh
                             80
                             60                                                           ▪ Higher loading on installed
                             40                                                             equipment
                             20
                              0                                                           ▪ Additional stress leads to
                              2015         2017       2019     2021      2023      2025
                                                                                            increased ageing and thus
                                     Sold energy      Purchased energy    Losses
                                                                                            a reduced lifetime
                              Transmission development plan 2014 – 2015
                              Final report, issued December 2016
06.12.2019                            Vortragstitel                                                                       2
   On-site testing with AC voltages
    Growing power demand and the impact on the grid
                               Quantity of Power transformers to be          Consequences for the grid:
                                            maintained
                       45                                                    ▪ A large number of HV components
                       40
                       35                                                      are reaching their end of life
     Number of units
                       30
                       25
                       20
                                                                             ▪ The probability of failures or
                       15                                                      defects increases
                       10
                        5
                        0                                                    ▪ A regular maintenance plan
                        2015        2016        2017   2018   2019    2020     should include a proper testing
                        Transmission development plan 2014 – 2015              program
                        Final report, issued December 2016
06.12.2019                      Vortragstitel                                                                    3
   On-site testing with AC voltages
    High voltage tests - Part of a reliable quality assurance program
     ▪ Validation of a correctly designed HV component
     ▪ Validation, that the component has been produced
       according to specified values
     ▪ Validation of a correct installation and commissioning
     ▪ Regular diagnosis & validation after repair measures
06.12.2019   Vortragstitel                                              4
   On-site testing with AC voltages
    High voltage tests - Steady part of the high voltage component’s life
             Deviation               Manufacturing
                                                             Routine test
              Damage                  Transport
              Mistake         Installation / Commissioning
                                                             Site acceptance test
              Ageing
                                                             Maintenance test
                                      Operation
               Defect                                        Test after repair
06.12.2019    Vortragstitel                                                         5
   On-site testing with AC voltages
    High voltage tests - Steady part of the high voltage component’s life
             Deviation               Manufacturing
                                                             Routine test
              Damage                  Transport
              Mistake         Installation / Commissioning
                                                             Site acceptance test
              Ageing
                                                             Maintenance test
                                      Operation
               Defect                                        Test after repair
06.12.2019    Vortragstitel                                                         6
   On-site testing with AC voltages
    On-site tests: What are the benefits?
                                                    Major assets of on-site testing:
                                                    ▪ Avoid long-lasting and
                                                      sophisticated transports to a
                                                      test shop
                                                    ▪ Decide, if and when a
                                                      repair can be done on-site
    Diagnostic test of power transformer,
                                                    ▪ Plan repair measures in advance
    using a frequency-converter based test system
06.12.2019    Vortragstitel                                                            7
   On-site testing with AC voltages
    On-site tests: What are the benefits?
                                                       Major assets of on-site testing:
                                                       ▪ Test the fully installed system
                                                         in its operational environment
                                                       ▪ Assess the quality of site works
                                                         e.g. jointing
                                                       ▪ Detect failures, that might have
    Commissioning test of 400 kV XLPE cable,
                                                         occured during installation
    using 4 frequency-variable resonant test systems
06.12.2019    Vortragstitel                                                                 8
   On-site testing with AC voltages
   Purchasing a system for field testing…
   ▪ …is usually a unique acquisition.
                                                   Test objects?
                                            Type test? Test field layout?
                    Prices?                      Test on tap changer?
                                                 Options? Routine test?
                                                       Ambient conditions?
                                                        Add-ons?
             Delivery times?                             Shunt reactors?
                                                     Factory test? On-site test?
                                                        Automatisation?
               Technical details?                     Consultancy?
                                                  Shielded test field?
                                                Power measuring?
   ▪ A good knowledge of the main parameters of test objects and the test
     location is decisive to select a suitable test system.
06.12.2019     Vortragstitel                                                       9
   On-site testing with AC voltages
   Cable tests: test object
   to be applied shall be subject to agreement between the purchaser and
   the contractor. The waveform shall be substantially sinusoidal and the frequency shall be
   between 20 Hz and 300Conductor               Conductor
                            Hz. A voltage according to Table 4, column 10, shall be applied for 1 h.
                          Inductance             Resistance                     Cable length (km)
                           (mH / km)              (Ω / km)
                                                       Insulation                                       Insulation
                                                       Resistance                                      capacitance
                                                       (MΩ / km)                                         (µF / km)
     „The a.c. test voltage to be applied shall be subject to agreement between
     the purchaser and the contractor. The waveform shall be substantially
     sinusoidal and the frequency shall be between 20 Hz and 300 Hz. A voltage
     […] shall be applied for 1 h.“ (IEC 60480)
06.12.2019        Vortragstitel                                                                                      10
   On-site testing with AC voltages
   Cable tests: Resonant test circuit
   to be applied shall be subject to agreement between the purchaser and
   the contractor. The waveform shall be substantially sinusoidal and the frequency shall be
   between 20 Hz and 300 Hz. A voltage according to Table 4, column 10, shall be applied for 1 h.
                                                                               reactor voltage
       Power
       Source
                                                                                                      frequency
                                                                                                                1
                    Simplified resonant test circuit                                                𝑓𝑟𝑒𝑠 =
                                                                                                             2𝜋 𝐿 ∗ 𝐶
06.12.2019       Vortragstitel                                                                                          11
   On-site testing with AC voltages
   The test system shall supply:
   ▪ Active power
     to feed the losses
   to be applied shall be subject to agreement between the purchaser and
   ▪ Reactive power
   the contractor. The waveform shall be substantially sinusoidal and the frequency shall be
   between 20 Hz and 300 Hz. A voltage according to Table 4, column 10, shall be applied for 1 h.
     to form the resonant circuit
     together with the cable capacitance
   ▪ Required information:
     Test voltage and -duration, test load or cable parameters,
     losses and load cycles
06.12.2019       Vortragstitel                                                                      12
   On-site testing with AC voltages
   Transformer tests: test objects
   to be applied shall be subject to agreement between the purchaser and
   the contractor. The waveform shall be substantially sinusoidal and the frequency shall be
                             Inductance Resistance                                 Inductance Resistance
   between 20 Hz and 300 Hz. A voltage according to Table 4, column 10, shall be applied for 1 h.
                               of prim.  of prim.                                    of sec.   of sec.
                               winding winding                                       winding winding
                                                      Core                           Main
                                                   resistance                      reactance
     No determined procedure for on-site testing in IEC or IEEE standards
     Guidelines and suggestions for testing, e.g. IEEE C57.152-2013
     “IEEE Guide for Diagnostic Field Testing of Fluid-Filled Power Transformers,
     Regulators, and Reactors”
06.12.2019       Vortragstitel                                                                             13
   On-site testing with AC voltages
   Transformer tests: test objects – no load condition
   to be applied shall be subject to agreement between the purchaser and
   the contractor. The waveform shall be substantially sinusoidal and the frequency shall be
   between 20 Hz and 300 Hz. A voltage according to Table 4, column 10, shall be applied for 1 h.
   ▪ Relevant for:
     induced voltage test (> 2 times power frequency)
     no-load loss measurements (power frequency)
06.12.2019       Vortragstitel                                                                      14
   On-site testing with AC voltages
   Transformer tests: test objects – short-circuit condition
   to be applied shall be subject to agreement between the purchaser and
   the contractor. The waveform shall be substantially sinusoidal and the frequency shall be
   between 20 Hz and 300 Hz. A voltage according to Table 4, column 10, shall be applied for 1 h.
   ▪ Relevant for:
     load loss measurements (power frequency)
     measurements of short-circuit impedance (power frequency)
06.12.2019       Vortragstitel                                                                      15
   On-site testing with AC voltages
   Transformer tests: test objects – applied voltage condition
   to be applied shall be subject to agreement between the purchaser and
   the contractor. The waveform shall be substantially sinusoidal and the frequency shall be
   between 20 Hz and 300 Hz. A voltage according to Table 4, column 10, shall be applied for 1 h.
   ▪ Relevant for:
     applied voltage tests (> 0.8 times power frequency)
06.12.2019       Vortragstitel                                                                      16
   On-site testing with AC voltages
   The test system shall supply:
   ▪ Active power
        -to feed the no-load losses
        -to compensate saturation
   to be applied shall be subject to agreement between the purchaser and
   the contractor.
         conditionsThe waveform shall be substantially sinusoidal and the frequency shall be
   between 20 Hz and 300 Hz. A voltage according to Table 4, column 10, shall be applied for 1 h.
        -to provide transient power during
         OLTC switching
        -to suppress harmonics
   ▪ Reactive power
     to compensate the load-loss
     conditions
     -to suppress harmonics
   ▪ Required information:
     Transformer parameters, losses and impedances, Test conditions
     and duration
06.12.2019        Vortragstitel                                                                     17
   On-site testing with AC voltages
   On-site diagnostic tests
   Fault location detection during dielectric tests with AC voltages
                              measuring device
                              (transient recorder)   l
        Time domain reflectrometry-based measuring circuit
06.12.2019    Vortragstitel                                            18
   On-site testing with AC voltages
   On-site diagnostic tests
   Fault location detection during dielectric tests with AC voltages
     left side: setup for HV cable test; right side: typical breakdown pattern, detected with fault locator
06.12.2019     Vortragstitel                                                                                  19
   On-site testing with AC voltages
   On-site diagnostic tests
   On-site PD diagnostic during maintenance of wind power transformer
                    Box 1                 Box 2                    Box 3
                                                                                       Test
                                                                                      object
     CEE 32
                    1              2              3               4               5
                    6              7                                              8
              1 – Static Frequency Converter          6 – Operator Panel
              2 – Power Sine Wave Filter              7 – Control Computer Unit
              3 – Step-up Transformer                 8 – Measuring Unit
              4 – PD Filter
              5 – Current and Voltage Sensors
    Test source for diagnostic tests on wind power transformers
06.12.2019              Vortragstitel                                                          20
   On-site testing with AC voltages
   On-site diagnostic tests
   On-site PD diagnostic during maintenance of wind power transformer
    Test source for diagnostic tests in the field
06.12.2019     Vortragstitel                                            21