Emergency Diesel Generator Operation: Manual Starting Operation "Using Electrical Starting Motor"

The document provides instructions for manual and automatic operation of an emergency diesel generator. For manual starting with normal electrical starting, the steps are to check components, set the switch to manual, start the generator electrically, and close the circuit breaker. If the batteries are low, a hand pump must be used to start the generator mechanically before closing the circuit breaker. For automatic starting, the generator will start and close the circuit breaker when power fails and the switch is set to auto. Manual stopping requires opening the circuit breaker and turning the key, while automatic stopping occurs when the main generator starts.

Uploaded by

MARAWAN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
173 views2 pages

Emergency Diesel Generator Operation: Manual Starting Operation "Using Electrical Starting Motor"

The document provides instructions for manual and automatic operation of an emergency diesel generator. For manual starting with normal electrical starting, the steps are to check components, set the switch to manual, start the generator electrically, and close the circuit breaker. If the batteries are low, a hand pump must be used to start the generator mechanically before closing the circuit breaker. For automatic starting, the generator will start and close the circuit breaker when power fails and the switch is set to auto. Manual stopping requires opening the circuit breaker and turning the key, while automatic stopping occurs when the main generator starts.

Uploaded by

MARAWAN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Emergency diesel generator

Operation
Manual starting operation “using electrical starting motor”:
1- Make sure vent flap for cooling air suction.
2- Make sure inlet and return diesel oil valves.
3- Make sure emergency switch board mode switch is “MANUAL” mode.
4- Make sure water, oil and diesel oil levels are sufficient for operation.
5- Make sure starting key in place and turn to position “2” to start
generator.
6- Electrical starting motor starts diesel generator.
7- Return starting key to position “1”.
8- Pull circuit breaker handle and turn to “CLOSE” to close manually.
Manual starting operation “batteries low voltage”:
1- Make sure vent flap for cooling air suction.
2- Make sure inlet and return diesel oil valves.
3- Make sure emergency switch board mode switch is “MANUAL” mode.
4- Make sure starting key in place and turn to position “1”.
5- Use hydraulic hand pump to charge accumulator up to “100-130 Psi”.
6- Open driving unit lever to start the generator.
7- Once the generator start combustion restore lever position.
8- Pull circuit breaker handle and turn to “CLOSE” to close manually.
Automatic starting operation:
1- Starting key at position “1”.
2- When power failure occurs and emergency switch board mode switch
at “AUTO” mode, the diesel generator starts and close circuit breaker
automatically.
Manual stopping operation :
1- Pull circuit breaker handle and turn to “OPEN” to open manually.
2- Turn key to position “0” to stop the generator.
3- Start main diesel generator.
4- Turn key to position “1” and turn emergency switch board mode switch
to “AUTO” mode.
Automatic stopping operation:
When main diesel generator starts the emergency diesel generator
circuit breaker at emergency switch board “OPEN” and the generator
stops automatically.