Megger Insulation Test Results

The document summarizes the results of an insulation resistance test performed on July 8, 2020 at the Karl Storz Endoskope facility. Insulation resistance measurements were taken of 16 circuits serving lighting outlets, air conditioning units, and convenience outlets. The main feeder wire showed a resistance of 500Ω across all phases. Most branch circuits measured between 4-5.5Ω except circuits 7 and 12 which showed lower resistances of 2.32Ω and 4.05Ω respectively. The tester and multi-meter used were verified as properly calibrated and in working order.

Uploaded by

klent jaleco
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views1 page

Megger Insulation Test Results

The document summarizes the results of an insulation resistance test performed on July 8, 2020 at the Karl Storz Endoskope facility. Insulation resistance measurements were taken of 16 circuits serving lighting outlets, air conditioning units, and convenience outlets. The main feeder wire showed a resistance of 500Ω across all phases. Most branch circuits measured between 4-5.5Ω except circuits 7 and 12 which showed lower resistances of 2.32Ω and 4.05Ω respectively. The tester and multi-meter used were verified as properly calibrated and in working order.

Uploaded by

klent jaleco
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

MEGGER INSULATION RESISTANCE TEST RESULT

Project Location: KARL STORZ ENDOSKOPE Dates of inspection: JULY 8,


2020
Panel board No. PICADILLY STAR REALTY MAIN CB: 100 AT POLE: 2
Instrument used: MEGGER TESTER
INSTRUMENT 500 V
SETTINGS

Circuit
Circuit No. Or Service Name L1-L2 L2- L3 L3- L3 L1-G L2-G L3-G L1-N L2-N L3-N WIRE
No.
MAIN FEEDER WIRE 500 500 500 500 500 500 500 500 500 14mm
1 LIGHTING OUTLET 4.72 Ω 4.12 Ω 12mm
2 LIGHTING OUTLET 5.50 Ω 5.50 Ω 12mm
3 AIR-CONDITIONING UNIT 5.50 Ω 5.50 Ω 12mm
4 AIR-CONDITIONING UNIT 5.50 Ω 5.50 Ω 12mm
5 NONE
6 AIR-CONDITIONING UNIT 5.50 Ω 5.50 Ω 12mm
7 LIGHTING OUTLET 2.32 Ω 2.07 Ω 12mm
8 NONE
9 CONVENIENCE OUTLET 5.50 Ω 5.50 Ω 12mm
10 CONVENIENCE OUTLET 5.50 Ω 5.50 Ω 12mm
11 AIR-CONDITIONING UNIT 5.50 Ω 5.50 Ω 12mm
12 AIR-CONDITIONING UNIT 4.05 Ω 4.03 Ω 12mm
13 AIRCONDITIONING UNIT 5.50 Ω 5.50 Ω 12mm
14 AIR-CONDITIONING UNIT 5.50 Ω 5.50 Ω 12mm
15 AIR-CONDITIONING UNIT 5.50 Ω 5.50 Ω 12mm
16 AIR-CONDITIONING UNIT 5.50 Ω 5.50 Ω 12mm

Check Items: Notes:


Equipment used & Calibration
(A) Check operation of each lighting fixture, outlet & ACU.
validity:
(B) Check/measure voltage on each outlet

(C) Check for grounding continuity 1.       Insulation Resistance


Tester (500V DC)
2.       Multi-meter (1000V AC)

Tested By: Acknowledged By:

Name:

Signature & Date: