0% found this document useful (0 votes)
132 views1 page

Make Alstom Type VAA11 SL - No VX 110 - 125V

The document summarizes inspection results for electrical equipment with make Alstom, type VAA11, and serial number between 110-125V. Functional checks found the appropriate indicators, output contacts, relay cover, and reset switch were all operating correctly. The inspection remarks concluded the relay was found to be healthy.

Uploaded by

Subramaniam NP
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
132 views1 page

Make Alstom Type VAA11 SL - No VX 110 - 125V

The document summarizes inspection results for electrical equipment with make Alstom, type VAA11, and serial number between 110-125V. Functional checks found the appropriate indicators, output contacts, relay cover, and reset switch were all operating correctly. The inspection remarks concluded the relay was found to be healthy.

Uploaded by

Subramaniam NP
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 1

1.

Location

2. Equipment Details:

Make Alstom
3. Type VAA11
Sl.No
Vx 110 – 125V
General Inspection : OK

4. Pick up/Drop off Test:

Ref Pickup volt(V) Drop off Volt(V)


9,10 80.3 39.4

5. Functional checks: (Whether Operational Checks OK / Not OK / Not Available)

1 Correct operation of appropriate indicator / aux. relay OK


2 Correct operation of output contacts OK
3 Relay cover properly fixing OK
4 Correct operating reset switch OK

6. Comments : Nil.

7. Remarks : Relay found Healthy.