1.
Location : MRS#2/22 KV SWBD
Equipment Name : Tie feeder to MRS – 3 PNL No: 16 / P. No: 09
2. Equipment Details:
Make Alstom
Type VAJHM23
Sl.No. 93124532007
Volts 110 – 125 V DC
3. Pickup and Dropoff Voltage Test:
Reference Pickup Voltage(V) Dropoff Voltage(V)
9,10 38.9 HR
4. Functional Checks: (Whether Operational Checks OK/Not Ok/ Not Applicable)
1 Correct Operation of Appropriate Indication/Flag OK
2 Correct Operation of output Contacts OK
3 Correct Operation of Reset Knobs. OK
5. Comments : Nil.
6. Remarks : Relay Found Healthy.