1.
Location
2. Equipment Details:
Make Alstom
3. Type VAA11
Sl.No
Vx 110 – 125V
General Inspection : OK
4. Pick up/Drop off Test:
Ref Pickup volt(V) Drop off Volt(V)
9,10 80.3 39.4
5. Functional checks: (Whether Operational Checks OK / Not OK / Not Available)
1 Correct operation of appropriate indicator / aux. relay OK
2 Correct operation of output contacts OK
3 Relay cover properly fixing OK
4 Correct operating reset switch OK
6. Comments : Nil.