What Are The Basic Troubleshooting Steps For The Smart-UPS SMT1000RM2U / SMT1500RM2U ?

The document provides basic troubleshooting steps for the Smart-UPS SMT1000RM2U and SMT1500RM2U UPS models. It lists common issues like the UPS not turning on, operating on battery with utility power, beeping, or not providing expected backup time. For each issue, it suggests possible causes such as a disconnected power cable, tripped circuit breaker, weak battery, overload, or internal fault. The resolution describes steps to check connections, reduce the load, allow the battery to recharge, or contact support for further assistance.

Uploaded by

robert rob
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
227 views4 pages

What Are The Basic Troubleshooting Steps For The Smart-UPS SMT1000RM2U / SMT1500RM2U ?

The document provides basic troubleshooting steps for the Smart-UPS SMT1000RM2U and SMT1500RM2U UPS models. It lists common issues like the UPS not turning on, operating on battery with utility power, beeping, or not providing expected backup time. For each issue, it suggests possible causes such as a disconnected power cable, tripped circuit breaker, weak battery, overload, or internal fault. The resolution describes steps to check connections, reduce the load, allow the battery to recharge, or contact support for further assistance.

Uploaded by

robert rob
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 4

SITE FOR REPAIR UPS: http://apc-fix.

com/forums

https://patents.google.com/patent/US5302858A/en

What are the basic troubleshooting steps


for the Smart-UPS SMT1000RM2U /
SMT1500RM2U ?
Published date: 15 August 2019

Issue:

What are the basic troubleshooting steps for the Smart-UPS SMT1000RM2U / SMT1500RM2U ?

Product Line:

Smart-UPS  

Environment:

SMT1000RM2U / SMT1500RM2U - All Serial Numbers

Cause:

During normal operation, you may find your UPS not functioning as expected. This may be due to a
malfunction, configuration issue, or the install environment.
This document will assist you with basic troubleshooting steps.

Resolution:
 
 

Problem Possible Cause Solution


     

The UPS will not turn Press the ON button once to turn on the
The unit has not been
on or there is no UPS. Please note that the LCD screen may
turned on.
output be lit even though the UPS is OFF.

The UPS is not Be sure that the power cable is securely


  connected to utility connected to the unit and to the utility powe
power. supply.

Reduce the load to the UPS, disconnect


The input circuit
  nonessential equipment and reset the circu
breaker has tripped.
breaker. 

The unit shows very Check the utility power supply to the UPS b
  low or no input utility plugging in a table lamp. If the light is very
voltage dim, check the utility voltage.

The battery connector


Be sure that all battery connections are
  plug is not securely
secure.
connected.

There is an internal Do not attempt to use the UPS. Unplug the


 
UPS fault. UPS and have it serviced immediately

     

The UPS is operating


Reduce the load to the UPS, disconnect
on battery, while The input circuit
nonessential equipment and reset the circu
connected to utility breaker has tripped.
breaker.
power

Move the UPS to a different outlet on a


There is very high, different circuit. Test the input voltage with
  very low, or distorted the utility voltage display. If acceptable to th
input line voltage. connected equipment, reduce the UPS
sensitivity.

     

The UPS display will indicate the current


The UPS is in normal
UPS is beeping operating mode that is causing the beeping
operation.
(On battery, replace battery, etc..)
     

Charge the battery. Batteries require


recharging after extended outages and wea
The UPS battery is out faster when put into service often or
UPS does not provide weak due to a recent when operated at elevated temperatures. If
expected backup time outage or is near the the battery is near the end of its service life,
end of its service life. consider replacing the battery even if the
replace battery indicator is not yet
illuminated.

The UPS is  Check the UPS load display. Unplug


 
overloaded. unnecessary equipment, such as printers

     

The UPS has been


Display interface shut down remotely
None. The UPS will restart automatically
LEDs flash through software or an
when utility power is restored.
sequentially optional accessory
card.

     

Contact APC Support for further assistance


Fault LED illuminates Possible Internal Fault Take care to note the exact fault message
on the LCD Display

     

All LEDs are The UPS has shut


None. The UPS will return to normal
illuminated and the down and the battery
operation when the power is restored and
UPS is plugged into a has discharged from
the battery has a sufficient charge.
wall outlet an extended outage.

     

Allow the battery to recharge for at least fou


The Replace Battery The battery has a hours. Then, perform a self-test. If the
LED is illuminated weak charge problem persists after recharging, replace
the battery

The replacement
Be sure that the battery connector is
  battery is not properly
securely connected.
connected.
     

Wiring faults detected


include missing
The UPS displays a If the UPS indicates a site wiring fault, have
ground, hot-neutral,
site wiring fault a qualified electrician inspect the building
polarity reversal, and
message wiring. (Applicable for 120 V units only.)
overloaded neutral
circuit.