This document outlines the settings for various fault protections on a KTA 50G8 generator set. It includes parameters for overspeed, under frequency, over frequency, speed/frequency, low oil pressure, reverse power, high coolant temperature, high intake manifold temperature, overcurrent, and high oil temperature protections. The settings specify trip thresholds, delays, enable times and warning thresholds.

Uploaded by

Girva Girdan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
137 views1 page

Setup Genset KTA 50G8

This document outlines the settings for various fault protections on a KTA 50G8 generator set. It includes parameters for overspeed, under frequency, over frequency, speed/frequency, low oil pressure, reverse power, high coolant temperature, high intake manifold temperature, overcurrent, and high oil temperature protections. The settings specify trip thresholds, delays, enable times and warning thresholds.

Uploaded by

Girva Girdan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

OEM Setup Genset KTA 50G8

Overspeed Under Frequency Fault


1 50 Hz Trip Level 1725 rpm 1 Extended Thresh 2 Hz
2 50 Hz Trip Lvl - Adj 1725 rpm 2 Extended Delay 120 Sec
3 50 Hz Trip Lvl - 20 1150 rpm 3 Threshold 6 Hz
4 50 Hz Trip Lvl - 36 2070 rpm 4 Delay 10 Sec
5 50 Hz Trip Lvl - 60 3450 rpm
6 60 Hz Trip Level 2075 rpm Over Frequency Fault
7 60 Hz Trip Lvl - Adj 2075 rpm 1 Threshold 6 Hz
8 60 Hz Trip Lvl - 20 1380 rpm 2 Delay 20 Sec
9 60 Hz Trip Lvl - 36 2484 rpm
10 60 Hz Trip Lvl - 60 4140 rpm Speed/Frequency Fault
1 Threshold 1.5 Hz
Low Oil Pressure 2 Delay 4 Sec
1 Enable Time 2 Sec
2 Shutdown Thresh 35 Psi Reverse Power
3 Warning Thresh 40 Psi 1 kW Threshold 10 %
4 Idle Shutdown Thresh 10 Psi 2 kW Time Delay 3 Sec
5 Idle Warning Thresh 15 Psi 3 kVar Threshold 20 %
6 Shutdown Set Time 8 Sec 4 kVar Time delay 10 Sec
7 Warning Set Time 5 Sec
High Coolant Temp
High Intake Manifold Temp 1 Shutdown 102 °C
1 Shutdown thresh 72 °C 2 Shutdown Tresh 102 °C
2 Shutdown Set Time 5 Sec 3 Shutdown Set Time 2 Sec
3 Warning Thresh 65 °C 4 Warning Tresh 99 °C
4 Warning Set Time 5 Sec 5 Warning Set Time 2 Sec

Overcurrent High Oil Temp


1 Threshold 110 % 1 Shutdown Thresh 121 °C
2 Time Characteristic 7.4 Sec 2 Shutdown Set Time 2 Sec
3 Warning Tresh 118 °C
4 Warning Set Time 2 Sec