NXZM、NXZ(H)M
Automatic Transfer Switch
User Instructions
3 You are prohibited from touching the conductive part when the product is
  operating.
4 Do not install the product at places where gas medium can cause metal
  corrosion and insulatin damage.
5 After installing the product, finishing the inspection of load side line and
  splitting the fire-resistance circuit, the controller must be set to “Manual”
  position and the product must be set to split position. Switch the controller
  to “Auto” position after line fault is eliminated.
 1 Applicatin Information
a) The normal application temperature of the product is -5℃~+40℃;
  Note: If you need to use the product under -25℃~+70℃, please consult the manufacturer.
b) If you need to use the product above 2000m altitude, please consult the manufacturer;
c) Pollution class: class 3;
d) Installation category of main circuit: Ⅲ;
e) Enclosure protection class: IP20.
Tools required
                                                                                                 1.Determine
                                                                          Phillips screwdriver
                                                                                                 product
                                                                                                 technical
                                                                          Word screwdriver
                                                                                                 parameters.
                                                                          Allen wrench           2.Type AT and
                                                                                                 BT controllers
                                                                          Hex wrench
                                                                                                 have the
                                                                                                 function of
                                                                                                 communication.
                                          Fig 1 Inspection
                                                                                                      3P 2X4
        Flash barrier
                                                                                                      4P 2X6
                 Type A                                                                                 5
       wiring
      terminal
         of      Type AT
                                                                                                        6
      external Type B
       signal
    (controller)
                 Type BT                                                                                7
                                                       01
                                     NXZM、NXZ(H)M Automatic Transfer Switch
Manual test
Power-on test
       Turn the toggle switch to              Automatic mode           Manual mode            Setting mode
        the Automatic position
   Stop mode         Generator activation        Failure alarm       Automatic transfer     Automatic transfer
                                             (absent for PC class)   Operating transfer      Return transfer
                                                                        delay time             delay time
                                            Fig 3 Power-on test
                                                     02
                  NXZM、NXZ(H)M Automatic Transfer Switch
                                                                                                       Hmax
                                         A
                                        C                                                              H1
                                  L                 G                                     H2
                                                                               B2
B1
         D
     B
                                                                               H             H1             H2
     Product model   A     B       B1   B2    C     D      G        L                                                 M    N
                                                                         S         H     S         H   S         H
     NXZM-63、125
                     300   240    230   223   267   220   25       178   178       190   151   161     47        56   9    17
 NXZHM-63、125
      NXZM-160
                     340   250    245   240   307   230   30       194   167       195   152   180          50        9    17
      NXZHM-160
      NXZM-250
                     390   250    367   240   357   230   35       225   181       216   155   190     49        50   9    17
      NXZHM-250
 NXZM-400、630
                     535   334    464   342   475   304   44       304       234             198            66        11   26
 NXZHM-400、630
      NXZM-800
                     660   344    477   344   600   314   58       385       238             203            68        11   26
      NXZHM-800
                                                          03
                                   NXZM、NXZ(H)M Automatic Transfer Switch
                                                                                     Unit: mm
                       64                 17     4.5          60
          105
                                    101
                                                                            60≤a≤62
                                                                            101≤b≤103
                                                                            Thickness≤2.5
                NXZM/NXZHM-63
                                                 8.0         17.5          6.5        4 N·m
                NXZM/NXZHM-125
                NXZM/NXZHM-400
                                                 10.5        30.5         11.5        30 N·m
                NXZM/NXZHM-630
NXZM/NXZHM-800 15 43 14 40 N·m
                                               04
                 NXZM、NXZ(H)M Automatic Transfer Switch
                                                                                                           1. Main power
                                                                                                           supply and
                                                                                                           voltage signal
                                         Load bus-bar                   4P
                                                                                                           sampling line
                                                                                                           phase
3P Product wiring diagram                                                                                  sequence must
                                                                                                           be consistent.
Normal power                   Alternative power
                                                                       Normal          Alternative         2. During
bus-bar                        bus-bar
                                                                       power           power               wiring, the
                                             Wiring terminal of
                                             neutral line                                                  voltage signal
                                                                                                           sampling line in
                                                                                                           order as shown.
                                                                                                           Wrong wiring
                                                                                                           may lead to
                                                                                                           burn down of
                                                                                                           the controller.
                                                                                  3P
                            Load bus-bar
                                                          05
                                                              NXZM、NXZ(H)M Automatic Transfer Switch
                                        neutrul line
                         neutral line
                                        Alternative
                                                                         Connect to the external
                         Normal
                                                                         terminal of controller
                                                                         directly.
                                                                         Any forms of electrical
                                                                         connection of these terminals is
                                                                         strictly forbidden.
Common Common
                                                                                                                                                              201      202
                                                                                                                                                             1. Any type of
                                                                             Note: Please tear off the sticker before use                                    electrical
                                                                             and keep it for future use.                                                     connection
                                                                                                                                                             between
                                                                                                                                                             terminal 201
                                                                                                                                                             and teminal
                                                   It is used under the                                                                                      202 is
                                                   Grid-power generator
                                                                                                                                             Note:
                                                                                                                                                             prohibited,
                                                   mode and may be omitted,
                                                   but the delay of generator
                                                                                           Do not connect                                    Active output   otherwise the
                                                                                           201 and 202.                                      AC230V/0.5A
                                                   start-up default to 0s.                                                                                   controller will
                                                                                                                                                             be burnt!
                                                                                                                                                             2. Terminal 501
                                                                                                                                                             and 502 of
                                                                                                                                                             controller can
                                                                                                                                                             only be
                                                                                                                                           Commom            connectd with
                                                                                                                                                             passive closing
                                                                                                                                                             signal to
                                                                                                                                                             achieve fire
                                                                                                                                                             cintrol linkage.
                                                                                                                                                             If they are
                                                                                                                                                             directly
                                                                                                                                                             connected to
                                                                                                                                                             any active
                                                                                                                                                             signal, the
                                                                                           To the remote power
                                                       terminal 601 land 603 are                                             Terminals 503 and 504 are
                                                       connected.                                                         connected after the off of fire    3. Strip at least
                                                                                                                          control. After the fire control
Note:                                                                                                                     signal bering removed, for the
                                                                                                                                                             8mm of the
1: Dotted line is the internal structure of the controller.                                                               ATSE switch to“Manual”and          insulation of
                                                                                                                          then press Confirm/Return in
2: Type A controller doesn’t have functions of generator control                                                                                             the wire before
                                                                                                                          automatic mode, or press
   (601 602 603) and feedback output of fire protection control (503, 504).                                               Comfirm/Return directly in         inserting it into
3: Type AT and BT controllers have the function of communication.
                                                                                                                          manual mode.                       the terminal.
                      Fig 8 Signal and control terminal wiring diagram
                                                                                   06
                NXZM、NXZ(H)M Automatic Transfer Switch
5 Controller setup
Instructions of controller operation interface
                                                      07
                                      NXZM、NXZ(H)M Automatic Transfer Switch
                                                     08
              NXZM、NXZ(H)M Automatic Transfer Switch
                                                                       09
                                                        NXZM、NXZ(H)M Automatic Transfer Switch
                                                                                Normal operation of
             Normal operation of                                                normal power supply
             normal power supply
                                                                                               Failure of normal
                             Failure of normal                                                 power supply T3
                             power supply T1
                                                                                Start-up of generator
                Disconnection of
              normal power supply
                                                                                               Generator output reaches
                                                                                               set value T1
                             Power up of alternative
                             power supply
                                                                                  Disconnection of
                                                                                normal power supply
              Connection of alternative
                  power supply
                                                                                               Power up of alternative
                                                                                               power supply
                             Recovery of normal
                             power supply T2
                                                                               Connection of alternative
                 Disconnection of                                                  power supply
             alternative power supply
                                                                                               Recovery of normal
                              Power up of normal                                               power supply T2
                              power supply
                                                                                    Disconnection of
              Connection of normal                                              alternative power supply
                 power supply
                                                                                               Power up of normal
                                                                                               power supply
                                                                                Connection of normal
      Flow Chart of Automatic Charge and Automatic                                 power supply
                                                                                                             Generator shutdown
            Normal operation of
            normal power supply
                                                                     Flow Chart of Automatic Charge and Automatic Recovery
                            Failure of normal
                            power supply T1                                  (Grid - Power Generation) of Controller
               Disconnection of
             normal power supply                                     I: Normal power supply
                            Power up of alternative
                            power supply
                                                                     II: Alternative power supply
                                                                     T1: Switching delay time
            Connection of alternative
                power supply
                                                                     Failure of normal power supply, time before
                            Recovery of normal
                            power supply
                                                                     disconnection of I
                                                                     T2: Return delay time
                Power supply of
            alternative power source
                                                                     Recovery of normal power supply, time
                            Failure of alternative
                                                                     before disconnection of II
                            power supply T2
                Disconnection of
                                                                     T3: Generator start-up delay time: 0s~180s
            alternative power supply                                 adjustable
                            Power up of normal
                            power supply                             T4: Generator shutdown delay time: 0s~180s
                                                                     adjustable
            Connection of normal
               power supply
                                                                     10
                    NXZM、NXZ(H)M Automatic Transfer Switch
6 Product troubleshooting
                                     Table 5 Non-common fault and solution
                                           The product is not connected to neutral Make sure the incoming line terminal is
The display interface of controller is     phase, especially for a 3P product.     firmly connected and in good contact.
not on after powering up
                                           Controller fuse is blown.                    Replace the fuse.
                                                               11
                                     NXZM、NXZ(H)M Automatic Transfer Switch
7 Environmental Protection
    In order to protect the environment, the product or product parts should be disposed of according to
the industrial waste treatment process, or be sent to the recycling station for assortment, dismantling and
recycling according to local regulations.