Drive Moog
Drive Moog
DBM 04
User's Manual
SECTION 2 fuses II - 2
Installation soft start 2
transformers 3
thermal sizing of cabinet 3
recovery circuit 4
fan assembly 5
wire type 6
power supply - wiring 10
power supply - led's 14
power supply - internal card jumpers 14
module wiring 19
resolver wiring 22
motor phases wiring 29
module - leds 32
personality card jumpers 33
potentiometer/button 35
input/output characteristics 35
serial link connection 36
starting sequence 41
resolver to encoder option 46
mechanical brake 48
module replacement 49
I - 1 - 30/Oct/01
SECTION 4 power supply IV - 1
Protections drive module 2
I - 2 - 30/Oct/01
Accident Protection
The safety instructions provided in this Manual are included to prevent injury to personnel
(WARNINGS) or damage to equipment (CAUTIONS).
CAUTION: it is recommended to disconnect the drive and the EMC filters to carry out
the AC Voltage Tests of EN 60204-1 (1997), par.19.4, in order to not damage the Y-
type capacitors between phases and ground. Moreover the DC voltage dielectric test
required by EN 50178 (1997), product family standard, has been carried out in factory
as a routine test. The DC Insulation Resistance Tests of EN 60204-1 (1997), par.19.3,
may be carried out without disconnecting the drive and the EMC filters.
CAUTION: when required for an emergency stop, opening U2-V2-W2 pins and closing
motor phases to resistors, must be preceded by disabling the axis. The delay time
must be at least 30 ms.
CAUTION: in case of repetitive switching on and off, wait 1 minute between off and
on.
CAUTION: it is recommended to close the WP jumper on the Personality Card at the
end of installation and setup.
CAUTION: do not exceed the tightening torque of the table (but see proper data
sheets for the tightening torque of input capacitors and power modules and see
Section 2 of this Manual for the tightening torque of terminal blocks)
Screw Tightening torque
Thread [Nm] [lb in]
M3 1.00 8.85
M4 3.00 26.55
M5 6.00 53.10
M6 8.00 70.80
M8 20.0 177.0
I - 3 - 30/Oct/01
I - 4 - 30/Oct/01
CE Requirements
• Fixed connection for protection. The equipment may have a continuous leakage current
of more than a.c. 3.5 mA or d.c. 10 mA in normal use and a fixed ground connection is
required for protection.
• RCD. A d.c. component can occur in the fault current in the event of a fault connection to
earth. Only a residual-current-operated protective device (RCD) of Type B is allowed.
When the protection in installations with regard to indirect contact is achieved by means of
an RCD, their appropriate function/combination shall be verified.
I - 5 - 30/Oct/01
I - 6 - 30/Oct/01
UL Requirements
• These Brushless Servo-Drives shall be assembled with the guidelines specified in this
Manual. Only the configurations with the components tested and described in the UL
Report, file E194181, Vol.2, Sec.1, Issue date 03-28-01 and following Revisions can bear
the Recognized Component (R/C) Mark. Each assembled configuration shall be evaluated
in the UL Listed end-use application.
• These drives shall be used within their ratings, as specified in the marking of the
equipment. In particular:
- rated input voltage, input current, system duty cycle, auxiliary input voltage, auxiliary
input power, fan input voltage, fan input power on the label affixed on the fan assembly
- rated axis continuous output current, axis max output current, module duty cycle on the
label affixed on the module
• Duty Cycle. The maximum continuous Drive output current shall be limited to 65 A and to
the Maximum Module Current, due to the rated current of the Power Supply and of the
Module. According to this reason, the Drive shall be used with a Duty Cycle, as specified
in the marking of the equipment.
• Short Circuit Ratings. “Equipment suitable for use on a circuit capable of delivering not
more than 5000 rms Symmetrical Amperes, 460 V ac +10% maximum”
• Branch Circuit Protection. The Branch Circuit Protection for Short Circuit shall be
provided in the end-use applications by external R/C Fuses (JFHR2), manufactured by
Bussmann Div Cooper (UK) Ltd, Semiconductor fuse type, Mod.No. 160 FEE, rated 160
A, 660 Vac, 200 kA A.I.C.
I - 7 - 30/Oct/01
• Overspeed Protection. The Power Conversion Equipment is incorporating an Overspeed
Protection. See MV command in Section 6 of this Manual.
• Overload Protection. The equipment does not incorporate internal overload protection for
the motor load. The drive is intended to be used with motors that must have integral
thermal protection through a PTC. The overtemperature fault of the drive will trip when the
PTC reaches 1.2 kΩ. See J4-J5-J6 connectors in Section 2 of this Manual for wiring.
• Over-Current Protection. The drive is provided with a current limiting circuitry. See IL and
IT commands in Section 6 of this Manual.
• Factory Wiring. These equipments are suitable only for Factory Wiring only, that is the
Terminal Blocks and the Connectors for Power Connection Wiring are not suitable for
Field Wiring. In particular the DC-Bus Terminal Blocks for the Power Supply and Modules
Interconnection shall be usable only with the DC-Bus Interconnection Cables provided by
the manufacturer.
• Wiring. Wiring shall be made by stranded and/or solid, copper (Cu), 60/75°C (140/167°F)
conductor only, and, for terminal blocks, the tightening torque values specified in Section 2
of this Manual shall be applied. These requirements do not pertain to control circuit
terminals.
• Wiring of Recovery Resistor. The Dynamic Brake Unit Recovery Resistor shall have the
connection wiring made with R/C (AVLV2) or insulated with R/C (YDPU2) or R/C (UZCW2)
in the end-use installation.
I - 8 - 30/Oct/01
SECTION 1 - DESCRIPTION
1.1 Description
DBM04 four quadrant servodrives provide unrivaled compactness and flexibility through the
integration of three axes in a single module.
A power supply is connected directly to the power distribution line at 400 or 460V and can
supply up to 6 modules (18 axes). The result is a very suitable solution for all multi-axis
applications like machine tools, robotics, packaging, special material working (wood, plastics,
glass, rubber, leather, paper).
A microprocessor based structure allows high servo performances with FASTACT and FC
servomotors all equipped with a resolver feedback. Drive tuning and configuration are
performed via digital parameters (not potentiometers) and stored in non-volatile memory
(EEPROM).
Drive set up is possible via a keypad or PC, therefore simplifying installation and providing
easy fault diagnosis.
General features:
• digital speed loop
• sinusoidal current waveform
• SMD technology with boards automatically assembled and tested
• automatic Resolver to Digital (R/D) resolution switching (from 16 to 10 bit) to achieve high
motion accuracy in the whole speed range (from 0 to 10000 RPM).
• up to 99 axis system configuration
• 10 kHz switching frequency
• operating temperature: 0 to +40°C (exceeding Class 3K3)
• relative humidity: 5% to 85% (no condensation, no formation of ice)
• air pressure: 86 kPa to 106 kPa
• storage temperature: -25 to +55°C (Class 1K4)
• transportation temperature: -25 to +70°C (Class 2K3)
• immunity to vibration: Class V.H.2 according to HD 413.3 S1 (1987)
• maximum case depth of 310 mm
• 3-phase power input voltage: 400 or 460 Vac (selectable via switch), ±10%, 50/60 Hz
• 1-phase auxiliary input voltage: 110 or 230 Vac (selectable via jumper), ±10%, 50/60 Hz
• input current: 65 A
• output current: see tab. 1.1
• max number of modules supplied: 4
I - 9 - 30/Oct/01
PS-6M Power Supply (Standard Plus)
• 3-phase power input voltage: 400 or 460 Vac (selectable via switch), ±10%, 50/60 Hz
• 1-phase auxiliary input voltage: 110 or 230 Vac (selectable via jumper), ±10%, 50/60 Hz
• input current: 65 A
• output current: see tab. 1.1
• max number of modules supplied: 6
• 3-phase power input voltage: 400 Vac or 460 Vac (set in factory), ±10%, 50/60 Hz
• 1-phase auxiliary input voltage (for data saving): 230 Vac, ±10%, 50/60 Hz
• input current: 65 A
• output current: see tab. 1.1
• max number of modules supplied: 4
• 3-phase power input voltage: 400 Vac or 460 Vac (set in factory), ±10%, 50/60 Hz
• 1-phase auxiliary input voltage (for data saving): 230 Vac, ±10%, 50/60 Hz
• input current: 120 A
• output current: see tab. 1.1
• max number of modules supplied: 4
DBM 04 Module
• BUS BAR rated voltage: 540 Vdc (with 400 Vac) or 620 Vdc (with 460 Vac)
• three-phase output voltage: 325 Vac (with 400 Vac) or 375 Vac (with 460 Vac)
• output current: see tab. 1.1
• input voltage: 230 Vac or 115 Vac, +6%/-10%, 50/60 Hz, or 24 Vdc, ±4%
• input power: see tab. 2.1
I - 10 - 30/Oct/01
TAB. 1.1 - OUTPUT CURRENT
Output Current
Model Axis 1 Axis 2 Axis 3 Width Weight
Rated Max Rated Max Rated Max
(Arms) (Arms) (A) (Arms) (Arms) (A) (Arms) (Arms) (A) (mm) (kg)
DBM 04 3-3 3 6.4 9 3 6.4 9 - - - 120 8
DBM 04 6-6 6 10.6 15 6 10.6 15 - - - 120 8
DBM 04 8-8 8 15.6 22 8 15.6 22 - - - 120 8
DBM 04 15-15 15 29.7 42 15 29.7 42 - - - 120 9
DBM 04 25-25 25 49.5 70 25 49.5 70 - - - 180 13
DBM 04 35-35* 35 63.6 90 35 63.6 90 - - - 270 18
DBM 04 3-3-3 3 6.4 9 3 6.4 9 3 6.4 9 120 9
DBM 04 6-6-6 6 10.6 15 6 10.6 15 6 10.6 15 120 9
DBM 04 8-8-8 8 15.6 22 8 15.6 22 8 15.6 22 120 9
DBM 04 15-15-15 15 29.7 42 15 29.7 42 15 29.7 42 180 14
* a duty cycle of 92% applies
Current Auxiliary
Model Output Output Input Width Weight
Rated Max Braking Voltage
(A) (A) (A) (V) (mm) (kg)
PS-Standard Power Supply 65 100 100 110/230 Vac 120 13
PS-6M Power Supply (Standard Plus) 65 100 100 110/230 Vac 120 13
PS-Standalone Power Supply 65 100 100 230 Vac* 120 13
PS-120 Power Supply (Powered Standalone) 120 280 175 230 Vac* 180 20
PS-U Power Supply (Special Standalone) 65 100 100 24 Vdc* 120 13
* this is not necessary for normal duty but only for data saving
EXPANSIONS
An external expansion module should be used for some configurations, including an axis rated over 35A. This is due to thermal
constrictions.
Available expansions modules are shown in the table. To specify an expansion module, please replace the third axis rating number with E,
this ensures that the drive is configured for use with an expansion module (e.g. DBM 04 15-15-E).
Output Current
Model Rated Max Width Weight
(Arms) (A) (A) (mm) (kg)
EBM 04 50/140 50 99 140 270 18
EBM 04 60/180 60 127 180 270 18
I - 11 - 30/Oct/01
1.3 Dimensions
Fig. 1.1 and 1.2 (dimensions in mm) show the drilling jig between power supply and drive
module. The modules must be mounted vertically, with the fan housing at the bottom. Leave a
clear space of at least 50 cm (19.7 in) over and under the system for air circulation.
Configuration L L1 L2
1 DBM04 PS + 1 DBM04 120 mm 241 266 282
1 DBM04 PS + 1 DBM04 180 mm 301.5 326 342
1 DBM04 PS + 2 DBM04 120 mm 362 387 403
1 DBM04 PS + 1 DBM04 270 mm 391 416 432
1 DBM04 PS + 1 DBM04 120 mm + 1 DBM04 180 mm 422.5 447 463
1 DBM04 PS + 2 DBM04 180 mm 483 508 524
1 DBM04 PS + 3 DBM04 120 mm 483 508 524
1 DBM04 PS + 1 DBM04 120 mm + 1 DBM04 270 mm 512 537 553
1 DBM04 PS + 2 DBM04 120 mm + 1 DBM04 180 mm 543.5 568 584
1 DBM04 PS + 1 DBM04 180 mm + 1 DBM04 270 mm 572.5 597 613
1 DBM04 PS + 1 DBM04 120 mm + 2 DBM04 180 mm 604 629 645
1 DBM04 PS + 4 DBM04 120 mm 604 629 645
Note: the width of the Power Supply PS-120 is 180 mm. Contact our Sales Locations or Service Centers for the
available configurations and dimensions with this Power Supply.
I - 12 - 30/Oct/01
Fig. 1.2 Side View (Drill For M5 Screws)
I - 13 - 30/Oct/01
1.4 Component Identification
I - 14 - 30/Oct/01
1.5 System Grounding
I - 15 - 30/Oct/01
1.6 Options
• software programmable (from 128 to 16384 pulses per electrical revolution) simulated
encoder with marker
• A/D 14 bit converter on the speed reference with the possibility of software choice
between 12 bit standard conversion and 14 bit optional conversion
• R/D converter resolution: 8 arc/min 2-axis, 4 arc/min 2-axis, 2 arc/min 2-axis,
8 arc/min 3-axis, 4 arc/min 3-axis, 2 arc/min 3-axis
• installation and setup keypad
• PC communication package: see par. 2.11.2.1
• ADR function: external 24 Vdc UPS with added capacitance to recover braking energy
(see Application Note GB-4528)
• frequency reference to use a velocity reference generated by Pulse Frequency
Modulation (PFM) from 0 to 100 kHz instead of the standard analog signal (see
Application Note I-4521)
• master-slave (electric shaft) special software for DBM 04 with expansion (see Application
Note GB-4527)
The following informations are supplied on the rating plate of DBM 04.
I - 16 - 30/Oct/01
1.7.2 Module
To comply with the UL requirements, the following data are shown on the rating plate of the
Fan Assembly. These data are referred to the complete DBM 04 system, UL Recognized,
that is Power Supply, one or more modules, fan assembly.
The Duty Cycle is related to the max nominal current of the Power Supply (65A for PS-
Standard, PS-Standalone and PS-U).
The Flow Rate (F.R.) is the sum of the fan flow rates of the fan assembly.
Power Supplies and modules intended to be part of a complete DBM 04 system, UL
Recognized, are marked “Part of a Recognized System”.
Example:
I - 17 - 30/Oct/01
This page intentionally blank
I - 18 - 30/Oct/01
SECTION 2 - INSTALLATION
CAUTION: make sure that the correct input voltage, 400V or 460V, has been set.
Top Panel
CAUTION: make sure that the correct Fig.2.2 PS-Standard and PS-6M -
wiring has been set for auxiliary input 110/230V Jumper
voltage on the PS-Standard and PS-6M
front panel.
II - 1 - 30/Oct/01
2.1 Fuses
A delayed type fuse, rated 4A/250V, is provided on the front panel, to protect the auxiliary
power circuit. The following types are approved:
- Mod.No.SPT 0001.2510 by Schurter AG
- Mod.No. ST520240 by Bussmann Div Cooper (UK) Ltd
A delayed type fuse, rated 3.15A/250V, is provided on the internal base card, to protect the
auxiliary power circuit. The following types are approved:
- Mod.No.SPT 0001.2509 by Schurter AG
- Mod.No. ST520231 by Bussmann Div Cooper (UK) Ltd
2.1.2 External Power Fuses (one in each phase of the power line)
CAUTION: equipment suitable for use on a circuit capable of delivering not more than
5000 RMS symmetrical Amperes, 460V +10% maximum, when protected by
semiconductor type fuses, mod.No.160-FEE, manufactured by Bussmann Div.Cooper
(UK) Ltd
2.1.2.2 PS-120
II - 2 - 30/Oct/01
2.3 Transformers
The system is designed to allow direct operation from a 400/460 Vac three phase power line,
without isolation transformer. An isolation transformer may still be required to meet local safety
regulations. It is the user responsibility to determine if an isolation transformer is required to
meet these requirements.
To size the power transformer It is necessary to refer to the rated output power of the motors
(the output power with 65K winding overtemperature is included in the Technical Data table of
catalogs of servomotors), to sum the power of single axes, to multiply the sum by the
contemporaneity factor (factors often utilized are Kc=0.63 for 2 axes, Kc=0.5 for 3 axes,
Kc=0.38 for 4 axes, Kc=0.33 for 5 axes, Kc=0.28 for 6 axes), and by a correction coefficient
(=1.2), accounting for the losses of the motor/drive system.
If data need to be saved in case of three phase power line failure, a 230 Vac monophase
auxiliary line must be connected, via isolation transformer, to the PS-Standalone and PS-120
versions of Power Supply. This is not necessary for normal duty but only for data saving.
CAUTION: do not connect directly the auxiliary line but only through a dedicated,
isolation transformer with 230Vac ±10%, 50/60 Hz secondary voltage. Rated power
must be 60VA for each module (e.g. 240VA for 4 modules)
To calculate cabinet cooling requirements, table below provides estimated equipment power
dissipation values. If the application employs continuous braking, it is necessary to include
the recovery resistor power dissipation (use the nominal power of recovery resistor if actual
application recovery dissipation is unknown).
Power Dissipation
PS-Standard PS-120 Module IGBT's Input
PS-6M Bridge
PS-Standalone
PS-U
25 W 50 W 50 W 16 W/A 1 W/A
Example: with one PS-Standard, two modules, a total output current of 60 Arms and
continuous unknown braking, the dissipated power is as follows.
II - 3 - 30/Oct/01
2.5 Recovery Circuit
The recovery circuit is formed by a switching regulator, a recovery transistor and a recovery
resistance. While braking the motor returns energy which cannot be sent to the line since the
rectifier circuit is not regenerative. Returned energy tends to increase the BUS BAR DC
voltage. When HV reaches 680V (for 400Vac version) or 790V (for 460V version) the
switching regulator brings the recovery transistor into conduction, thus connecting the
recovery resistance in parallel with filter capacitors. The recovery resistance is formed by
enameled wire fixed resistor(s).
If the recovery resistance works for intervals shorter than the time necessary to reach
thermal equilibrium, the resistor can temporarily handle power levels up to 10 times the
nominal power rating of the resistor (short time overload).
If not specifically requested, PS-Standard, PS-6M, PS-Standalone are provided with 8.2 Ω,
750W recovery resistor, while PS-U is provided with 12 Ω, 750W recovery resistor and PS-
120 with 3.9 Ω, 1000W recovery resistor.
WARNING: High Voltage. The recovery resistor is connected to the Bus Bar’s and can
have voltage ≥810Vdc
CAUTION: an unusual application with motor driven by the load, a large portion of the
time, could result in overheating of the recovery resistor.
An unusual application with motor driven by high inertial load from high velocity in very
short deceleration time could require a non standard recovery resistor.
It is suggested contacting our Service Centers.
CAUTION: shielding of the recovery resistor cable, provided in kit for test purposes, is
recommended for ensuring compliance with the EMC standards.
CAUTION: for UL approval in the end-use installation, the Dynamic Brake Unit
Recovery Resistor shall have the connection wiring made with R/C (AVLV2) or
insulated with R/C (YDPU2) or R/C (UZCW2)
II - 4 - 30/Oct/01
2.6 Fan Assembly
The ventilation is provided by fans mounted under the modules. The size and the number of
fans are according to the system configuration. Selection of the correct Fan Assembly is due
by matching Fan Assembly width to the total of the DBM drives package (i.e. Fan = Power
Supply and DBM module(s) and DBM expansion module(s)).
Fan input voltage is 230 Vac or 115 Vac or 24 Vdc.
II - 5 - 30/Oct/01
2.7 Wire Type
It is recommended to use Cu, stranded and/or solid wires, 60/75°C (140/167 °F), UL
approved, per the following table.
Note that in the table the wires are sized according to the nominal current. The wires can be
undersized if the actual rms current of the application is lower.
AWG 22 20 18 16 14 12 10 8 6 4 3 2 1 1/0
mm2 0.3 0.5 0.8 1.3 2.1 3.3 5.3 8.4 13 21 27 34 42 54
II - 6 - 30/Oct/01
Fig. 2.3A Power Supply - Front Panels
II - 7 - 30/Oct/01
Fig. 2.3B Power Supply PS-120 - Front Panel
II - 8 - 30/Oct/01
Fig. 2.3C Power Supply PS-U - Front Panel
II - 9 - 30/Oct/01
2.8 Power Supply - Wiring
See Par.2.7 for sizing of power wires, tightening torque and wire stripping length. See Section 3
for shielding procedures according to EMC Directive.
Tab. 2.6 - Power Supply - J1 Conn. - Auxiliary Power Supply (to Modules)
Panel side: shrouded header with 13 male contacts
Wiring side: connector with 13 female contacts (provided in kit with cable)
Pos. Function
1 Not connected (N.C.)
2 +18Vdc referred to -HV (540/620 Vdc)
3 -HV (540/620 Vdc)
4 158kHz square wave to high side drives
5 N.C.
6 N.C.
7 +18Vdc referred to logic 0V
8 - 18Vdc referred to logic 0V
9 +8Vdc referred to logic 0V
10 +8Vdc referred to logic 0V
11 Logic 0V
12 Resolver 0V
13 10 kHz sinusoidal wave for resolver and synchronism (carrier)
Tab. 2.7 - Power Supply - J2 Conn. - RS485 Port/Fault signals (to Modules)
Panel side: Sub-D with 9 male contacts
Wiring side: Sub-D with conductive shell, 9 female contacts (supplied with cable)
Pos. Function
1 + Rx (RS485 serial link)
2 N.C.
3 + Tx (RS485 serial link)
4 Power supply binary coded faults (see Tab.2.8)
5 + 5Vdc input referred to logic 0V
6 - Rx (RS485 serial link)
7 Logic 0V
8 - Tx (RS485 serial link)
9 Power supply binary coded faults (see Tab.2.8)
J2/pos. 4 J2/pos. 9
0 0 OK
0 1 DBR FAULT. Recovery fault
1 0 OVER TEMP. Overtemperature
1 1 Not Used.
II - 10 - 30/Oct/01
Tab. 2.9 - Power Supply - J10 Connector - RS485 Port (to keypad or to converter)
Panel side: Sub-D with 9 female contacts
Wiring side: Sub-D with 9 male contacts (supplied with the optional RS232/485 converter kit
or with the optional keypad)
Pos. Function
1 +Rx (RS485 serial link)
2 N.C.
3 +Tx (RS485 serial link)
4 N.C.
5 +5Vdc output referred to logic 0V for power supply
6 -Rx (RS485 serial link)
7 Logic 0V
8 -Tx (RS485 serial link)
9 N.C.
Name Function
U1 "L1" phase, three-phase input voltage 400Vac (or 460Vac)
V1 "L2" phase, three-phase input voltage 400Vac (or 460Vac)
W1 "L3" phase, three-phase input voltage 400Vac (or 460Vac)
Ground
Name Function
AUX PWR Auxiliary power supply 230Vac/110Vac
JUMPER Jumper (see Fig.2.2)
JUMPER Open=230Vac - Closed=110Vac
AUX PWR Auxiliary power supply 230Vac/110Vac
II - 11 - 30/Oct/01
2.8.2.2 PS-Standalone
Name Function
AUX PWR Auxiliary power supply 230Vac
AUX PWR Auxiliary power supply 230Vac
U1 "L1" phase, three-phase input voltage 400Vac (or 460Vac)
V1 "L2" phase, three-phase input voltage 400Vac (or 460Vac)
W1 "L3" phase, three-phase input voltage 400Vac (or 460Vac)
Ground
2.8.2.3 PS-120
Tab. 2.13 - J11 Connector - Power
Aux Power: Terminal Blocks Mod.No.HDFK 4 by Phoenix Contact Gmbh
Power: Terminal Blocks Mod.No.HDFK 25 by Phoenix Contact Gmbh
See Par.2.7 for sizing of power wires, tightening torque and wire stripping length
Name Function
AUX PWR Auxiliary power supply 230Vac
AUX PWR Auxiliary power supply 230Vac
U1 "L1" phase, three-phase input voltage 400Vac (or 460Vac)
V1 "L2" phase, three-phase input voltage 400Vac (or 460Vac)
W1 "L3" phase, three-phase input voltage 400Vac (or 460Vac)
Ground
II - 12 - 30/Oct/01
2.8.2.4 PS-U
Tab. 2.14 - J11 Connector - Power
Aux Power: Terminal Blocks Mod.No.HDFK 4 by Phoenix Contact Gmbh
Power: Terminal Blocks Mod.No.HDFK 10 by Phoenix Contact Gmbh
See Par.2.7 for sizing of power wires, tightening torque and wire stripping length
Name Function
AUX PWR Auxiliary power supply 24Vdc
AUX PWR Auxiliary power supply 24Vdc
U1 "L1" phase, three-phase input voltage 400Vac (or 460Vac)
V1 "L2" phase, three-phase input voltage 400Vac (or 460Vac)
W1 "L3" phase, three-phase input voltage 400Vac (or 460Vac)
Ground
II - 13 - 30/Oct/01
2.9 Power Supply - Led's
Name Function
Yellow LED - PWR-BUS BUS BAR voltage > 40Vdc
WARNING: with PS-Standard and PS-6M, active only if
the aux power supply is ON
Red LED - DBR FAULT Recovery unit fault
Red LED - OVER TEMP Module overtemperature via PTC (threshold 70 °C)
Green LED - AUX POWER Auxiliary power supply OK
JP1 closed (default) = connects a 120 Ω resistor between RX+ and RX- of serial link.
JP2 closed (default) = connects TX- of serial link to 0V via pull-down resistor
JP3 closed (default) = connects TX+ of serial link to +5V via pull-up resistor
II - 14 - 30/Oct/01
Fig. 2.6 Module - Removable Control Panels
II - 15 - 30/Oct/01
Fig. 2.7 Expansion-EBM - Removable Control Panel
II - 16 - 30/Oct/01
Fig. 2.8 Module (120 mm/180 mm) - Fixed Panels
II - 17 - 30/Oct/01
Fig. 2.9 Module/ Expansion (270 mm) - Fixed Panel
Note: the grey connectors are mounted only in some configurations (see tab.2.27 and 2.28)
II - 18 - 30/Oct/01
2.11 Module Wiring
See Par.2.7 for sizing of power wires, tightening torque and wire stripping length. See Section 3
for shielding procedures according to EMC Directive.
Pos. Function
1 Not connected (N.C.)
2 +18Vdc referred to -HV (540/620 Vdc)
3 -HV (540/620 Vdc)
4 158kHz square wave to high side drives
5 N.C.
6 N.C.
7 +18Vdc referred to logic 0V
8 - 18Vdc referred to logic 0V
9 +8Vdc referred to logic 0V
10 +8Vdc referred to logic 0V
11 Logic 0V
12 Resolver 0V
13 10 kHz sinusoidal wave for resolver and synchronism (carrier)
Pos.
1 +Rx
2 N.C.
3 +Tx
4 Power supply binary coded faults (see Tab.2.19)
5 +5Vdc output referred to logic 0V
6 -Rx
7 logic 0V
8 -Tx
9 Power supply binary coded faults (see Tab.2.19)
J2/pos. 4 J2/pos. 9
0 0 OK
0 1 DBR FAULT. Recovery fault
1 0 OVER TEMP. Overtemperature
1 1 Not Used
II - 19 - 30/Oct/01
2.11.1 Limit Switches/Expansion Wiring
The J3 connector allows, when the Expansion is not present, the availability of CW/CCW
limit switches for each axis. With the input enabled (to 0V), the rotation is disabled in one
direction and enabled in the other direction.
When the Expansion is present, the J3 connector is used for signal connection to the
Expansion module.
DBM 04
1 0V
2 CW Limit switch axis 1
grounding of shield
via connector shell
*=see Section 3
II - 20 - 30/Oct/01
Tab. 2.20 - Module - J3 Connector - Limit Switches (When EBM Expansion Is Not
Panel side: Sub-D with 15 female contacts Present)
Wiring side: Sub-D with conductive shell, 15 male solder contacts
Pos.
1 0V common
2 CW limit switch, axis 1
3 N.C.
4 N.C.
5 CCW limit switch, axis 1
6 CW limit switch, axis 2
7 N.C.
8 N.C.
9 N.C.
10 N.C.
11 N.C.
12 CCW limit switch, axis 2
13 CW limit switch, axis 3
14 CCW limit switch, axis 3
15 0V common
Pos.
1 0V common
2 Auxiliary voltages referred to logic 0V not OK signal
3 Phase U reference current signal
4 Torque enabled signal
5 Short circuit signal
6 Overtemperature signal
7 Expansion present signal
8 Overtemperature signal
9 N.C.
10 Phase V reference current signal
11 Overtemperature signal
12 N.C.
13 BUS BAR fault signal
14 Auxiliary voltages referred to - HV (540/620 Vdc) not OK signal
15 N.C.
II - 21 - 30/Oct/01
2.11.2 Resolver Wiring
cosϕ
cosϕ
sinϕ
sinϕ
PTC
PTC
0V
V-Ref
RESOLVER CONNECTOR,
MOTOR SIDE
Signal FAS T/ FAS N
Type FAS K
Pos. Pos.
cosϕ C 1
cosϕ E 2
V-Ref D 10
0V B 7
PTC N 8
PTC A 9
sinϕ G 11
sinϕ H 12
shield S 3
II - 22 - 30/Oct/01
Each DBM module can be connected up to 3 resolvers. Axis 1 resolver must be connected to
J4 M1 connector, axis 2 resolver to J5 M2 and axis 3 resolver to J6 M3.
Figure 2.11 shows the wiring lay-out of the resolver with differential output.
We recommend to use 4 pair cables, each pair twisted and individually shielded with an
independent overall shield. 20 AWG (0.60 mm² ²) or 22 AWG (0.38 mm² ²) wire with low
capacitance can be used. We suggest to use ground connections as shown in Fig. 2.11.
Cable length should not exceed 30 m (100 ft.). It is recommended that the signal cable and
power cable be separated, if possible, through the use of independent duct (conduit) or by a
distance of 12 inches (30 cm).
See Section 3 for shielding procedures according to EMC Directive.
Pos. Name
1 cos Differential cos signal non-inverted input
II - 23 - 30/Oct/01
2.11.3 I/O Wiring
All the signal cables must be separated from power cables by a distance ≥30 cm.
See Section 3 for shielding procedures according to EMC Directive.
REMARKs:
• DRIVE OK (J7 connector): it is suggested to connect the isolated output " DRIVE OK " to
a remote control switch so that, if a fault occurs, the power supply is disconnected to avoid
system damages.
• SIMULATED ENCODER SIGNALS (J7 connector):
- in specially noisy environments it is suggested to connect a 220 ÷ 680 Ω resistor
between A and A, B and B, C and C at the receiver input.
- for lengths in excess of 5 m (16 ft.) the cable must have 3 pairs, each pair twisted.
DBM 04
CNC
REF
REF
0V
0V
J7
DIFFERENTIAL INPUT
DBM 04
CNC
REF
0V REF
0V
J7
UNIPOLAR INPUT
II - 24 - 30/Oct/01
Tab. 2.23 - J7 Connector - I/O Commands, Signals and Encoder Outputs
Panel side: Sub-D with 37 female contacts
Wiring side: Sub-D with conductive shell, 37 male solder contacts
Pos. Name
1 0V Logic 0V (it can be used as common for analog output
supplies ±15V)
2 A1 Encoder output: inverted phase A - motor 1
3 B1 Encoder output: inverted phase B - motor 1
4 C1 Encoder output: inverted phase C - motor 1
5 A2 Encoder output: inverted phase A - motor 2
6 B2 Encoder output: inverted phase B - motor 2
7 C2 Encoder output: inverted phase C - motor 2
8 A3 Encoder output: inverted phase A - motor 3
9 B3 Encoder output: inverted phase B - motor 3
10 C3 Encoder output: inverted phase C - motor 3
11 TP2 Testing point 2
12 ILIMIT3 Analog Current Limit input axis 3
0V = zero current
+10V (or not connected) = max current
13 ILIMIT2 Analog Current Limit input axis 2
(0 to +10V )
14 ILIMIT1 Analog Current Limit input axis 1
(0 to +10V )
15 Shield. Internally connected to 0V
16 REF3 Differential inverting analog input for the speed reference
signal (or torque ref. signal, see TC command) axis 3, max
range ±10V (see MR command). See Fig. 2.12
17 REF2 Differential inverting analog input for the speed reference
signal (or torque ref. signal, see TC command) axis 2, max
range ±10V (see MR command). See Fig. 2.12
18 REF1 Differential inverting analog input for the speed reference
signal (or torque ref. signal, see TC command) axis 1, max
range ±10V (see MR command). See Fig. 2.12
19 +15V +15Vdc output (I max = 30mA)
20 A1 Encoder output: phase A - motor 1
21 B1 Encoder output: phase B - motor 1
22 C1 Encoder output: phase C - motor 1
23 A2 Encoder output: phase A - motor 2
24 B2 Encoder output: phase B - motor 2
25 C2 Encoder output: phase C - motor 2
26 A3 Encoder output: phase A - motor 3
27 B3 Encoder output: phase B - motor 3
28 C3 Encoder output: phase C - motor 3
29 TP1 Testing point 1
II - 25 - 30/Oct/01
30 Shield. Internally connected to 0V
31 DRIVE Drive OK output, axis 1. Imax=5mA.
OK 1 * 0V=not OK
+5V=OK
32 DRIVE Drive OK output, axis 2. Imax=5mA.
OK 2 * 0V=not OK
+5V=OK
33 DRIVE Drive OK output, axis 3. Imax=5mA.
OK 3 * 0V=not OK
+5V=OK
34 REF3 Differential non-inverting analog input for the speed reference
signal (or torque ref. signal, see TC command) axis 3, max
range ±10V (see MR command). See Fig. 2.12
35 REF2 Differential non-inverting analog input for the speed reference
signal (or torque ref. signal, see TC command) axis 2, max
range ±10V (see MR command). See Fig. 2.12
36 REF1 Differential non-inverting analog input for the speed reference
signal (or torque ref. signal, see TC command) axis 1, max
range ±10V (see MR command). See Fig. 2.12
37 -15V - 15Vdc output (I max = 30mA)
II - 26 - 30/Oct/01
Fig. 2.13 - Input/Output Wiring
+24V
0V
CNC DBM 04
+24V
0V 9 Optoisolated input common
Drive Enable * Drive Enable
Ref. Enable 17 Reference Enable
10 Drive OK
Drive OK Optoisolated Output
11
12 Motor OK
Motor OK 13 Optoisolated Output
2
2.5 mm min Ground
Ground 19
DBM 04
7 0V Common
8 +15V dc output
9 Optoisolated input common
* Drive Enable
17 Reference Enable
J8
II - 27 - 30/Oct/01
Tab. 2.24 - J8 Connector - I/O Commands and Signals
Panel side: shrouded open end header with 20 male contacts
Wiring side: connector with 20 female contacts, screw termination
Pos. Name
1 TACHO TEST 1 tachometer output, axis 1. Range: (ET*/10)V for max speed
2 TACHO TEST 2 tachometer output, axis 2. Range: (ET*/10)V for max speed
3 TACHO TEST 3 tachometer output, axis 3. Range: (ET*/10)V for max speed
4 ANALOG OUT 1 analog output 1. See Tab. 2.25/26 and ES, SO commands
5 ANALOG OUT 2 analog output 2. See Tab. 2.25/26 and ES, SO commands
6 ANALOG OUT 3 max current output, axis 3 (100% of max current = 10V)
7 0L logic 0V
8 +15V +15Vdc output (Imax = 30mA)
9 OPTO 0V Optoisolated 0V
10 DRIVE OK Collector of Drive OK optoisolator (see Fig.2.13)
11 DRIVE OK Emitter of Drive OK optoisolator (see Fig.2.13)
12 MOTOR OK Collector of Motor OK optoisolator (see Fig.2.13)
13 MOTOR OK Emitter of Motor OK optoisolator (see Fig.2.13)
14 DRIVE EN1 Drive enable 1: optoisolated input for axis 1 torque enable.
See Fig. 2.13
15 DRIVE EN2 Drive enable 2: optoisolated input for axis 2 torque enable.
See Fig. 2.13
16 DRIVE EN3 Drive enable 3: optoisolated input for axis 3 torque enable.
See Fig. 2.13
17 REF EN Reference enable: optoisolated input for the confirmation of
the common reference to the three axis (REF EN not active
means no speed reference or zero torque)
18 REM RESET Remote reset: optoisolated input for logic section reset,
equivalent to push button on the front panel
19 GROUND Ground. It must be connected to CNC ground with 2.5 mm2
wire as short as possible
20 GROUND Ground (connected to 19)
* default ET=80
II - 28 - 30/Oct/01
2.11.4 Motor Phases Wiring
Motor DBM 04
U U
V V
W W
ground ground
J9
J9/J10/J11
grounding of
of shield
shield via grounding of shield
grounding
via connector
connector clamp
clamp (or RF via connector clamp
(or RF connection
connection to
to PG gland in
the ground
case screwboard)
of terminal in
case of terminal board)
All the motor phases must be connected from J9 connector(s) to motor connector(s). Note
that M1 always corresponds to the more powerful axis, while M3 must not be connected in 2
axis configuration.
There several motor power connections, depending on module configuration (see Tab.2.27
and Tab.2.28).
See Section 3 for shielding procedures according to EMC Directive.
CAUTION: the resolver wiring must match the motor wiring, i.e. the resolver cable
running from M1 motor must be connected to J4 M1 connector, the resolver cable
running from M2 motor must be connected to J5 M2 connector, the resolver cable
running from M3 motor must be connected to J6 M3 connector.
CAUTION: the U-V-W motor phase sequence of the connector at the drive side must
match the U-V-W motor phase sequence of the connector at the motor side.
CAUTION: do not parallel power connection cables to achieve requested section: this
will increase the capacitance value at levels that may irreversibly damage the drive. If
the value of capacitance of motor and cables, seen from drive output, exceeds 30 nF it
is necessary to verify with Moog technicians the need of an adequate choke in series.
II - 29 - 30/Oct/01
Tab. 2.27 - J9 Connector(s) - Motor Phases (1/2)
16 pins connector: Mod.No. Han16E by Harting Kgaa
4 pins connector: Mod.No.HanK 4/0 by Harting Kgaa
See Par.2.7 for sizing of power wires, tightening torque and wire stripping length
II - 30 - 30/Oct/01
Tab.2.28 - J9 Connector(s) - Motor Phases (2/2)
16 pins connector: Mod.No. Han16E by Harting Kgaa
4 pins connector: Mod.No.HanK 4/0 by Harting Kgaa
See Par.2.7 for sizing of power wires, tightening torque and wire stripping length
II - 31 - 30/Oct/01
2.12 Module - Led's
Name Function
Red LED generic fault: the fault can correspond, according to the
DRF type, to a LED on the front end; if other red LED's are not
on, out of the considered one, it is necessary to
interrogate the drive via serial link to know the fault
reason (see FA command)
Red LED Watch dog - signal; microprocessor circuit faults; this
WTD LED is on during reset
Red LED Resolver 1 fault - signal; resolver M1 fault, sin /cos
RF1 signals interrupted, short circuit between signals or
10kHz carrier abnormal
Red LED Resolver 2 fault - signal; resolver M2 fault, sin /cos
RF2 signals interrupted, short circuit between signals or
10kHz carrier abnormal
Red LED Resolver 3 fault - signal; resolver M3 fault, sin /cos
RF3 signals interrupted, short circuit between signals or
10kHz carrier abnormal
Red LED Motor M1 overtemperature
OT1
Red LED Motor M2 overtemperature
OT2
Red LED Motor M3 overtemperature
OT3
Red LED Module overtemperature
DR.OVT
Red LED Intelligent Power Module axis 1 fault
PWRF1
Red LED Intelligent Power Module axis 2 fault
PWRF2
Red LED Intelligent Power Module axis 3 fault
PWRF3
Green LED Reference enable
REF.EN
Green LED Axis 1 enable (see also ON command)
DR.EN 1
Green LED Axis 2 enable (see also ON command)
DR.EN 2
Green LED Axis 3 enable (see also ON command)
DR.EN 3
Green LED Auxiliary power OK
PWR OK
II - 32 - 30/Oct/01
2.13 Personality Card Jumpers
WP (default: open): if closed, the EEPROM is write protected and the Save (SV) command
is disabled
G1 (default: open) : if closed, connects TX- of serial link to 0V via pull-down resistor
G2 : if closed, gives priority to "opto" , if open gives priority to "keypad"
G3 (default: open) : if closed, set 9600 Baud rate and basic address 1
G4 (default: open) : if closed, connects TX+ of serial link to 5V via pull-up resistor
G5 (default: open) : if closed, connects a 120 Ω resistor between RX+ and RX- of serial link
Jumper open
Jumper closed
The jumper G2 on the personality card gives priority to keypad or to opto to execute "Drive
Enable" command. " Drive Enable" opto isolated signals are connected to J8/ pos.13, 14, 15.
G2 open = keypad priority = the keypad (or the device connected to the serial link) is the
master, i.e. it allows to enable or disable motor current, whereas the optocouplers can only
disable (protection); they can enable after resetting only.
The "Drive Enable" and "Reference Enable" opto-isolated signals must be driven at +15V.
G2 closed = opto priority = the optocouplers are the master and the keypad can only be
used for parameters setup.
Note:
1. See par.2.16.1 if the keypad does not communicate with the drive
2. "Drive Enable" priority is different from the use of the analog or digital reference.
You can choose an analog or digital reference by "AR" (Analog) or "DR" (Digital) commands,
and save. The drives are supplied set to digital reference "DR".
II - 33 - 30/Oct/01
2.13.2 G1-G4-G5 Jumpers: Link Termination's
By default G1, G4 and G5 jumpers on the personality card are open (no link termination's on
modules). In fact, usually, it is not necessary to close G1, G4 and G5 jumpers because the
link termination's are already closed on the power supply; anyway, in specially noisy
environments, could be necessary to close them also, as follows.
Power
Supply Module Module Module Module
Power
Supply Module Module Module Module
The jumper G3 on the personality card allows, if closed, to set 9600 Baud rate and basic
address 1. This configuration can be used to restore the communication in case of fault of
the serial link. When the communication has been restored, the G3 jumper must be open.
The jumper WP on the personality card allows, if closed, to write protect the EEPROM. If
closed, the Save (SV) command is disabled.
II - 34 - 30/Oct/01
2.14 Potentiometer/Button
OPTOISOLATED z in =1.2 kΩ
INPUTS I nom = 10 mA (8 to 20 mA)
Drive enable 1,2,3 Vmin = 15Vdc
Reference enable Vmax = 25V
Remote reset
OPTOISOLATED z out = 1.2 kΩ
OUTPUTS I max = 20 mA
Drive OK/ Motor OK Vnom < 25 Vdc
Analog tacho z out = 100 Ω
outputs 1,2,3 I max = 5 mA
Range: see ET command
Gain error = ±10% over production spread
Max linearity error: ±2% over full range
Analog Out1 z out = 100 Ω
Analog Out2 I max = 10 mA
Full scale = ±10V
Velocity differential z in > 20 kΩ
Reference Signals Full scale = ±10V
1,2,3
Simulated Encoder z out = 100 Ω
differential output Full scale = 7V (RS422/RS485 compatible)
signals
II - 35 - 30/Oct/01
2.16 Serial Link Connection
REMARK: for the first installation it is strongly recommended to use either the
optional keypad or the DBTALK communication program.
The keypad is an optional accessory product which can be used for drive setup and
monitoring. The keypad must be connected to J10 connector of Power Supply.
If problems occur when attempting to communicate, the keypad is most likely set incorrectly.
To start the setup procedure press <CTRL>, then <CR>. For each parameter the current
setting is displayed, together with a question asking if you want to change it.
The correct setting is:
BAUD = 9600
WORD = 8D+E+1 STOP
BLOCK MODE
SINGLE LINE MODE
FLASHING OFF
KEY REPEAT ON SLOW
Be sure to save at the end of the procedure by pressing <Y> when the display shows: "Make
changes permanent Y/N".
The RS422 interface wiring is based on one-to-one, no multidrop, principle. Four wires are
used. With RS422, you can transmit and receive data simultaneously (full-duplex).
The RS485 half-duplex uses only two wires. It allows multidrop communication. With RS485
half-duplex, you cannot transmit and receive simultaneously.
We supports RS485 full-duplex with four wires (RS422 compatible). Up to 99 DBM and up to
15 DBS drives can be connected in multidrop configuration.
This very small external converter provides a full-duplex interface between PC and DBM.
The converter must be fit directly into a COM port (RS232) of a PC. This way the link
becomes purely RS485, less susceptible to noise and able to transmit over much longer
distances than RS232.
II - 36 - 30/Oct/01
• An optoisolated PC board RS 485 full-duplex driver can also be used. The following wiring
must be used.
• PC REQUIREMENTS
- 80286, 80386, 80486 microprocessor or better
- Hard disk and one diskette drive. You need 2 Mbytes of disk space and 512 kbytes of RAM
- CGA, EGA, VGA, MCGA graphics card (color VGA recommended)
- MS-DOS 6.2 or later
- ANSI.SYS in CONFIG.SYS
• DBTALK PROGRAM
The DBTALK program is available on floppy disk
• INSTALL PROGRAM
- Insert diskette into drive A or drive B
- Type <a:install> (or <b:install>)
The installation program will create the Directory C:\DBTALK, will copy all the files in this new directory and will
start the program
II - 37 - 30/Oct/01
• SELECT PROGRAM
⇒ DBM linker
⇒ DBS linker
⇒ PDBS Linker (see PDBS Application Manual)
⇒ Setup
• SETUP to choose
⇒ Language: Italian or English
⇒ Serial link : COM1 or COM2
• UTILITY to
⇒ Scan Baud rates
⇒ Scan Faults
II - 38 - 30/Oct/01
⇒ Restore/store Personality Card parameters
To save the actual parameter set, select STORAGE PARAMETER, select the file (e.g. ST1), press <TAB> to
change the description and press <CR>
• MANUAL to
⇒ See/Reset Faults
If the fault condition is not present anymore, the fault will be reset automatically. To reset the fault on the
screen, go to the next screen with the arrow keys
II - 39 - 30/Oct/01
⇒ Display the Status
⇒ See/Change parameters
To change one parameter type the command string on the PC keyboard. Example: 3VE3000
II - 40 - 30/Oct/01
Fig.2.16 - STARTING SEQUENCE - TIMING CHART
110/230 Vac
1-phase
400/460 Vac
3-phase
Drive
Enable
Drive OK
400/460 Vac
3-phase
Drive
Enable
Drive OK
(*) CAUTION: the Remote Reset must be a single nonrepetitive signal. Otherwise it
must be filtered with 500 Hz cutoff frequency.
II - 41 - 30/Oct/01
3. PS-U: t1 = 6 s, t2 = 2 to 4 s, t3 = 4 s
WARNING: make sure that the AUX EXT CONTACT (pos.5 and 6 of J12 connector) is
connected to 24Vdc before starting.
t1 t2 t3
24 Vdc
400-460 Vac
3-phase
Drive
Enable
Motor OK
Drive OK
II - 42 - 30/Oct/01
2.17 Starting Sequence
The starting sequence depends on the type of Power Supply. See Fig.2.16 for the Timing-chart.
∗ PS-U
1. Apply the 24 Vdc auxiliary voltage
2. Apply the 400Vac (or 460Vac) three phase power voltage
• Multimodule configuration only. Disconnect the first module from the serial link and assign
basic address to the second module and so on for the next modules (all the modules from
factory being usually configured with address 1,2,3 if triple-axis or with address 1,2 if double-
axis).
Example of basic address assignment for the 2nd module, if the first module is triple-axis:
FROM KEYPAD
1 SA 4 <CR> Assign basic address 4 to the second module
4 SV <CR> Save the address configuration
Note: A module programmed as "address 4" will automatically assign for the other axes the
following addresses, i.e. 5 - 6 (if triple-axis) or 5 (if double-axis); and so on for the next basic
addresses.
• Check if NP (pole number), MV (max velocity), MR (max reference) and other required
parameters are OK for the application.
• Make a hardware reset via button on drive or via positive logic on pin 18 of J8 connector
(software reset via FA command being useless for digital control card reinitialization).
2.17.1 Autophasing
II - 43 - 30/Oct/01
Example for a double module with axis 4 and axis 5:
FROM KEYPAD
4 PW91 <CR> Give the password for the 2nd module
PASSWORD ON The correct answer is displayed
<CR> Only for optional keypad.
4 AP <CR> Allow axis 4 autophasing.
AUTOPHASING IN PROGRESS
AXIS PHASED
5 AP <CR> Allow axis 5 autophasing.
AUTOPHASING IN PROGRESS
AXIS PHASED
4 SV <CR> Save module 4 phasing.
• Repeat the password and autophasing procedures for subsequent modules (if applicable).
• Make a hardware reset via button on drive or via positive logic on pin 18 of J8 connector.
Axes being phased it is possible to check the wiring by rotating the motor via its digital reference.
FROM KEYPAD
5 ON <CR> Enable digital drive-enable for axis 5
{ Drive enable led will be on
5 VE 50 <CR> Set CW rotation at 50 rpm
5 VE-50 <CR> Set CCW rotation at 50 rpm
5 OF <CR> Disable digital drive-enable for axis 5
z Drive enable led will be off
To set the modules to use the analog references from the CNC, it is necessary to enter the
password, to send the AR command to every axis and to save. ST command can be sent to
check if the commands have been accepted.
II - 44 - 30/Oct/01
Note that:
• AR command can be sent via global address (*).
• If there are two or more modules, PW (password) and SV (save) commands can be sent to
each module.
Example of enabling all the analog references for two modules with axes 1,2,3 and 4,5:
FROM KEYPAD
1 PW91 <CR> Give the password for the 1st module
PASSWORD ON The correct answer is displayed
4 PW91 <CR> Give the password for the 2nd module
PASSWORD ON The correct answer is displayed
* AR <CR> Enable analog reference for all axes
1 SV <CR> Save the configuration for the 1st module
4 SV <CR> Save the configuration for the 2nd module
1 ST <CR> Ask the status for axis 1
A1 ST___ E___ I_0___ Displays the axis 1 status. Check the 0 in the 2nd bit after I
... Repeat ST command and check other axes
To give the priority for enabling and disabling the drive from the CNC, it is necessary to pull out
the personality card from the module, to solder G2 jumper and to pull in the card.
REMARK: if there are more than one module, do not swap the personality cards, this will swap
the module data.
When the above procedure is completed, the CNC is the master and the keypad is the slave, as
follows:
PARAMETERS MANAGED BY CNC: drive enable, reference enable, speed references.
PARAMETERS MANAGED BY KEYPAD: all dynamic parameters (acceleration,
deceleration, KI, KP, etc.), status and fault.
If it is necessary you can adjust the analog velocity offset by providing 0 analog speed
reference and setting VO command for an automatic adjustment. A fine adjustment can be
done with successive steps via OV command.
REMARK: the adjustment of the digital velocity offset must not be used to adjust the analog
velocity offset and it is reserved to setup technicians. It can be made by providing 0 digital
speed reference (VE=0) and setting OC command. The opto Drive Enable must be high.
II - 45 - 30/Oct/01
2.18 - Resolver To Encoder Option
For position sensing a resolver to encoder option (simulated encoder) is available.
Encoder signals are 7V, 100 Ω impedance, as follows:
• 2 channels of square wave output with a resolution from 128 to 16384 pulses per electrical
revolution. Channel B leads channel A by 90° for clockwise rotation when viewed from
shaft end.
• 1 marker pulse per electrical revolution (i.e. 1∗ 3 = 3 marker pulses per mechanical
revolution with a 6 pole resolver).
•. complementary outputs A, B and C.
Fig. 2.17 - Simulated Encoder (CW Rotation When Viewed From Shaft End)
Channel A
Channel B
C Marker
Channel A
Channel B
C Marker
Note: to make C Marker high when Channel A and Channel B are high (like Siemens), swap
Channel A with Channel A and Channel B with Channel B.
II - 46 - 30/Oct/01
2.18.1 Setup For Encoder Resolution
The number of pulses per electrical revolution of simulated encoder can be set via SE
software command.
FROM KEYPAD
1 PW91 <CR> Give the standard password for axis 1
PASSWORD ON The correct answer is displayed
<CR> Only for optional keypad
1 SE 4096 <CR> Set 4096 ppr to axis 1
1 SE <CR> Ask the number of ppr for axis 1
A01 SIMULATED ENCODER = 4096
1 SV <CR> Save
REMARK: the maximum number of pulses per electrical revolution depends on the R/D
resolution. See the following Table.
The width of C marker can be A (360°), A/2 (180°) or A/4 (90°); it must be specified in the
order. This parameter does not depend on the software commands.
Note: to obtain the resolution per mechanical revolution it is necessary to multiply the pole
pairs by the electrical resolution.
Example: if a FAS T motor with 6 pole resolver is used, 1024 pulses per electrical revolution
mean 1024 ∗ 3 = 3072 pulses per mechanical revolution.
Tab. 2.32 - Max speed and max ppr versus R/D resolution
Resolution (bit)
10 12 14 16
Max number of pulses per 256 1024 4096 16384
electrical revolution
Max speed with 2 pole 24000 12000 3510 877
resolver (rpm)
Max speed with 6 pole 8000 4600 1170 292
resolver (rpm)
Max speed with 8 pole 6000 3510 877 219
resolver (rpm)
II - 47 - 30/Oct/01
2.19 Mechanical Brake
FAS series servomotors have as option a 24 Vdc electromagnetic safety brake.
CAUTION: safety brake must be clamped and released with motor at standstill.
Premature failure of the brake will result if brake is used for dynamic stopping of the
motor.
The release of the brake (from 0V to +24V) and the clamp (from +24V to 0V) must follow the
sequence in Fig. 2.18.
T1 T2 T3 T4
ON
OFF
DRIVE ENABLE
ON
OFF
BRAKE 24V
POWER SUPPLY
RELEASE
CLAMP
BRAKE
0V REFERENCE
ENABLE
0 rpm
MOTOR SPEED
II - 48 - 30/Oct/01
2.20 Module Replacement
Once DBM module to be replaced has been identified, it is necessary to follow this procedure:
REMARK: on the personality card a EEPROM is mounted. All dynamic parameters (dynamic
settings, autophasing, analog interfaces, ...) are stored in this EEPROM after every reset.
In case of module replacement, it is recommended to save all parameters with the save (SV)
command before removing the Personality Card ready for installation in the replacement
module. This retains and transfers all the previous module information's.
Remove the Personality Card from the new module and replace with the old one.
• Mount the new module and tighten the anchor screw at the top.
• Reassemble the Bus Bars, all the connectors and flat cables.
• Check all connections.
• Enable the auxiliary voltage and check by keypad or PC all application dependent parameters. In
particular: pole number, max velocity, max reference voltage, Ilimit, internal ramp generator.
II - 49 - 30/Oct/01
This page intentionally blank
II - 50 - 30/Oct/01
SECTION 3 - ELECTROMAGNETIC COMPATIBILITY (EMC)
3.1 European Directive (89/336/EEC)
Compliance with the European Directive 89/336/EEC is required for all electric and electronic
products brought onto the European market after December 31st, 1995.
DBM04 drives with FASTACT motors meet the following EMC product standard related to
the Directive:
EN 61800-3 (1996) and EN 61800-3/A11 (2000): "Adjustable speed electrical power drive
systems. Part 3: EMC product standard including specific test methods".
Second environment (industrial) compatibility levels.
Remark: equipments not intended to be used on a low-voltage public network which supplies
domestic premises. May cause radio frequency interference.
The installer of the drive is responsible for ensuring compliance with the EMC regulations
that apply where the drive is to be used. We recommend filtering as per par.3.2 and wiring,
grounding and screening as per par.3.3 and 3.4.
3.2 Filtering
III - 1 - 30/Oct/01
3.2.2 Filter Sizing
The filter/drive coupling in the previous table is a standard coupling. The filter can be
undersized according to the rms input current of the actual application. This should be done
not only because, as a matter of fact, undersizing the filter means less money, but because
the undersized filter provides better performance to EMC.
Example:
- DBM04 PS-Standard + DBM 04 6-6-6 + DBM 04 6-6-6 and contemporaneity factor of 0.8.
For this application it is not necessary to use the 55A filter of the table.
L2
L6
L3 L4
III - 2 - 30/Oct/01
3.2.4 Filter Installation
CAUTION: leave a clear space of at least 60mm around the filter for air circulation
when the cabinet does not have forced ventilation.
- The filter must be connected as close as possible to the drive input. If the separation
between filter and drive exceeds around 30 cm (1 ft.) then a flat cable should be used for
the RF connection between filter and drive
REMARK: when mounting the drive and the filter to the panel, it is essential that any paint or
other covering material be removed before mounting the drive and the filter.
FILTER Max
torque
FN 250 - 6/07 0.8 Nm
FN 250 - 12/07 0.8 Nm
FN 258 - 7/07 0.8 Nm
FN 258 - 16/07 0.8 Nm
FN 258 - 30/07 1.8 Nm
FN 258 - 42/07 1.8 Nm
FN 258 - 55/07 3.0 Nm
FN 258 - 75/34 3.0 Nm
FN 258 - 100/35 4.0 Nm
- The filter can produce high leakage currents (see Data Sheets by Schaffner)
CAUTION: the filter must be connected to ground before connecting the supply
WARNING: High Voltage - Discharge time approx. 10 seconds
- The single phase filter can be installed on the left shoulder of the fan housing (Power
Supply side), as in the following figure:
To 220 Vac
(110 Vac) To
main supply AUX PWR
connector
III - 3 - 30/Oct/01
3.3 Wiring And Grounding Fig. 3.2 - Grounding Of Shield To
Connectors At Motor Side
All the following cables must be shielded,
with 85% minimum shielding coverage:
- resolver cable (see Fig.2.11 and Fig.3.2 In case of Sub-D connector, cable shield
motor side) must be grounded to the metallic hood.
III - 4 - 30/Oct/01
Fig. 3.4 - Cable Grounding At Drive Side
III - 5 - 30/Oct/01
It is not necessary to shield the input power wires, the bus bars, the flat cables between the
modules.
Screen is effectively
earthed 360° of its
radius
REMARK: when mounting the enclosure of recovery resistor or motor choke to the panel, it is
essential that any paint or other covering material be removed before mounting the enclosure
of recovery resistor or motor choke.
III - 6 - 30/Oct/01
3.5 Screening
To effectively screening the system all the single screens (CNC, electronic cabinet, machine,
motor housing, cables) must be connected together to effectively form one screen (see
Fig.1.4).
CAUTION: it is recommended to disconnect the drive and the EMC filters to carry out
the AC Voltage Tests of EN 60204-1 (1997), par.19.4, in order to not damage the Y-
type capacitors between phases and ground. Moreover the DC voltage dielectric test
required by EN 50178 (1997), product family standard, has been carried out in factory
as a routine test. The DC Insulation Resistance Tests of EN 60204-1 (1997), par.19.3,
may be carried out without disconnecting the drive and the EMC filters.
III - 7 - 30/Oct/01
This page intentionally blank
III - 8 - 30/Oct/01
SECTION 4 - PROTECTIONS
Indicated by: LED's DRF (drive fault) on all drives, LED DBR FAULT, optoisolated output
DRIVE OK, bit H of the FA string (see FA command).
Set condition: when recovery circuit or recovery resistor is broken, in short circuit; when the
recovery is active for too much time.
Reset condition: if the condition is not present anymore, power off and on monophase
voltage (PS-Standard and PS-6M) or 3-phase voltage (PS-Standalone, PS-120 and PS-U)).
Indicated by: LED's DRF (drive fault) on all drives, LED OVER TEMP, optoisolated output
DRIVE OK, bit I of the FA string (see FA command).
Reset condition: if the condition is not present anymore, power off and on monophase
voltage (PS-Standard and PS-6M) or 3-phase voltage (PS-Standalone, PS-120 and PS-U).
IV - 1 - 30/Oct/01
4.2 Drive Module
Indicated by: LED DRF, LED RF1/RF2/RF3 (Resolver Fault), optoisolated output DRIVE OK,
bit B of the FA string (see FA command).
Set condition: when the resolver is not connected or in short circuit at the power up, when the
resolver fails or is disconnected during running.
Reset condition: if the condition is not present anymore, reset button on drive or send pulse
to REM RESET.
Indicated by: LED DRF, LED OT1/OT2/OT3, optoisolated outputs DRIVE OK and MOTOR
OK, bit C of the FA string (see FA command).
Reset condition: if the condition is not present anymore, reset button on drive or send pulse
to REM RESET.
Notes: the fault information via LEDS and opto is reset when the motor temperature goes
down the limit, while the drive is disabled until the reset condition has been met.
Power fault.
Indicated by: LED DRF, LED PWRF1/PWRF2/PWRF3, optoisolated output DRIVE OK, bit D
of the FA string (see FA command).
Set conditions:
1. When a short circuit is detected between motor phases, phase and ground, phase and
HV.
2. When overcurrent is detected in motor phases.
3. Overheating of power modules (locked rotor condition).
4. Undervoltage of internal supply of power modules
Reset condition: if the condition is not present anymore, power off and on the power supply.
In case of condition 3. (overheating) wait at least 3 minutes before power up the drive.
IV - 2 - 30/Oct/01
Auxiliary voltages not normal
Set condition: when the level of +/- 15V or 5V becomes out of tolerance.
Reset condition: if the condition is not present anymore, reset button on drive or send pulse
to REM RESET.
Indicated by: LED DRF, optoisolated output DRIVE OK, bit L of the FA string .
Set condition: when the personality card is not present or taken away during running.
Reset condition: if the condition is not present anymore, reset button on drive or send pulse
to REM RESET.
EEPROM error
Indicated by: LED DRF, optoisolated output DRIVE OK, bit L of the FA string (see FA
command), "EE ERROR" on the keyboard.
Set condition: when, after the SV command, a reset has been sent before 5 sec.
Reset condition: check the parameters (e.g. KP, KI,..), correct the wrong values and save.
IV - 3 - 30/Oct/01
Bus not normal.
Indicated by: LED DRF, LED POWER OK, optoisolated output DRIVE OK, bit M of the FA
string (see FA command).
Reset condition: if the condition is not present anymore at analog level (with hysteresis),
reset button on drive or send pulse to REM RESET.
810 V (overvoltage)
410 V (Undervoltage)
IV - 4 - 30/Oct/01
Auxiliary HV referred voltages not norm.
Indicated by: LED DRF, optoisolated output DRIVE OK, bit N of the FA string (see FA
command).
Set condition: when the level of auxiliary voltages referred to power stage (-HV) becomes out
of tolerance.
Reset condition: if the condition is not present anymore at analog level (with hysteresis) reset
button on drive or send pulse to REM RESET.
Overspeed
Indicated by: LED DRF, optoisolated output DRIVE OK, bit F of the FA string (see FA
command).
Set condition: when an error between set speed and actual speed bigger than the
programmed via EV command is detected.
Reset condition: when the condition is no longer present, reset button on drive or send pulse
to REM RESET.
Drive overtemperature.
Indicated by: LED's DRF and DR.OVT, optoisolated output DRIVE OK, bit O of the FA string
(see FA command).
Reset condition: if the condition is not present anymore power off and on monophase
voltage.
IV - 5 - 30/Oct/01
IT
Set condition: when the current exceeds the nominal motor current for a time longer than the
time stated by the motor thermal model (see IT command and Tab.6.6)
Effect: when the fault is going on the current limit is reduced to the level of the motor rated
current (set by PC command).
Reset condition: if the condition is not present anymore, the protection is reset. To reset the
fault status in FA string, push button on drive or send pulse to REM RESET.
Watchdog.
Indicated by: LED DRF, LED WTD, optoisolated output DRIVE OK.
Reset condition: if the condition is not present anymore reset button on drive or send pulse to
REM RESET.
IV - 6 - 30/Oct/01
SECTION 5 - ADJUSTMENT OF TORQUE/SPEED CURVE
In most of the DBM 04 applications, the magneto-motive force (MMF, that is, the stator
current vector) is perpendicular to the rotor flux. In such a way, the torque constant ( [Nm]
per Ampere) is maximized.
In some applications requiring extremely high speed and high frequency of the stator current,
the phase lag caused by the current controller imperfection might degrade the drive torque
constant. The current controller implemented within the DBM 04 drive results in a phase lag
of 9 degrees at the output frequency of 270 Hz.
Due to the phase lag, the spatial displacement between the rotor flux and the stator MMF will
be less than 90 degrees (electrical) and the torque will diminish as the cosine function of the
phase lag, and to optimize the Torque/Speed curve.
DBM 04 drive might compensate this phase lag and the lack of torque through the user
programmable phase advance. That is, an additional phase advance might be inserted into
the drive vector rotator, rendering the possibility to compensate for the current controller
phase lag.
Along with the conventional synchronous PM motors, the DBM 04 might run PM motors with
pronounced saliency effect (Ld ≠ Lq) and ensuring reluctance torque. The peak of total
electromagnetic torque for this family of PM motors is obtained with flux-MMF angles
different that 90 electrical degrees.
For the purpose of maximizing the torque per Amp constant of synchronous reluctance
motors, the phase advance in function of the speed and stator current is provided as a
standard feature of the DBM 04
According to the requirements, the phase-speed curve equals zero for all the speeds below
the speed S1[rpm] (see Fig. 5.1). Above that speed, the phase rises with the speed with a
constant slope. Hence, two parameters (TF and TG in the following text) are sufficient for the
purpose of customizing the phase-speed demagnetization curve. TF parameter will define
the speed S1[rpm]. From the stall up to the S1[rpm], the phase(speed) correction will have
the value zero. Above S1[rpm], the phase(speed) correction will rise up with the constant
slope. This slope is defined by the second, TG parameter.
Phase (degrees)
S1[rpm]
= f(TF)
Slope = f(TG)
Speed [rpm]
V - 1 - 30/Oct/01
5.2 Phase-current relation
The phase-current curve is linearly rising or falling for the currents IQ>0, starting at the
current level S2[%] defined by the TY parameter, with a slope defined by TQ parameter.
Phase (degrees)
S2[%] => TY
Slope=> TQ
Current IQ [%]
Hence, the point S2[%] is defined by TY parameter. According to requirements, the phase-
current curve might increase at a steeper slope for the values of IQ superior to S2[%]. For
this purpose, the fourth, TQ parameter is provided in order to program the slope of the
phase-current curve for the values bigger than S2[%].
To optimize the match between FAST-V brushless servomotors and DBM 04 drive, the
following parameters settings have been found to be the best choice. With these parameters
the motor provides, at the nominal speed and with nominal voltage - 5% (that is 380Vac for
400Vac-and 437Vac for 460Vac), a Max Torque from 1.5 to 3 times the Max Torque without the
optimization algorithm.
V - 2 - 30/Oct/01
Tab. 5.1 - Parameters Setting for 400V and 6-pole resolver
V - 3 - 30/Oct/01
Tab. 5.2 - Parameters Setting for 400V and 2-pole resolver
V - 4 - 30/Oct/01
Tab. 5.3 - Parameters Setting for 460V and 6-pole resolver
V - 5 - 30/Oct/01
Tab. 5.4 - Parameters Setting for 460V and 2-pole resolver
V - 6 - 30/Oct/01
SECTION 6 - COMMANDS
This is because the protocol is configured so that the drives are able to communicate only if
inquired by the master, to avoid contentions on the line. As a consequence, all the
commands have been configured individually (single axis questioned), except those for
which an answer is not foreseen; therefore all the drives can be reached simultaneously.
• status monitoring
Monitor commands on the status of the drive, which displays axis configuration and eventual
faults.
• data monitoring
Monitor commands for displaying memorized motion parameters (e.g. I limit=100%, etc.).
Remark: if a mistake has been made while digitizing, it is possible to reset the command by
pressing <CR> ( <CARRIAGE RETURN> ).
1 bit-start
8 bit-data
1 bit-parity even
1 bit-stop
VI - 1 - 30/Oct/01
Command syntax is as follows:
Remark: press <CR> after each command string if the optional keypad is used.
Axis: it is a number from 1 to 9 ( max. number of axes in a system); it identifies the axis
selected for data monitoring / input.
Module: the "module" (or "basic") address is referred to the possibility to get the execution of
the command either addressing the chosen axis (axis) or any axis inside the module (
module ). This last possibility is valid for all axes within a module common commands (e.g.
temperature).
Global: it is also possible to globally address all axes (global address) using the <∗> in place
of the address number.
• Datum: it can be composed by a max. of 4 figures or 3 figures and the <-> symbol. The
<+> symbol is optional. Any data without a symbol is considered as positive.
VI - 2 - 30/Oct/01
6.2 Commands
All commands available for system management can be used to monitor and execute every
datum.
To monitor, it is sufficient to enter the address and the command; to execute, the address,
the command and the datum must be typed.
VI - 3 - 30/Oct/01
Tab. 6.2 - Standard/Default Configuration
Standard 1 2 3 4 5 6
address address address address address address
AC 0
AL DL
AR DR
BR 9600
CG 2
CU -
CV -
DE 0
DF 0
DL DL
DR DR
ES 16
ET 80
EV 0
IL 100
IT see Tab.6.6
KI 10
KP 20
MR 100
MV -
NP -
OC -
OV 128
PC see Tab.6.6
PR -
RN -
RX -
RS -
SA 1
SE -
TC VC
TF see Sect.V
TG see Sect.V
TQ see Sect.V
TY see Sect.V
VC VC
VO 128
VS 1
Note: with G3 jumper on the personality card closed, BR=9600 and SA=1 are set.
VI - 4 - 30/Oct/01
AC - Acceleration
Examples:
1 AC 100 <CR>: it sets an acceleration ramp = 100ms for axis1.
2 AC <CR>: it questions axis 2 about the acceleration ramp. In case no one has been set, the answer
is: "A2 ACC. TIME = ms 0".
rpm
MV
VE DE
AC ms
DE AC
VI - 5 - 30/Oct/01
AD - Axis Disabled
Function: AD command makes the logic section ignore an axis and the
relatives faults. It is useful with DBM 2-axis: if the
third axis were not disabled, the logic would reveal resolver
fault and motor overtemperature, preventing the drive from
running.
Syntax: data monitoring: address AD <CR>
data input: address AD n <CR>
Address type: axis
Unit of measure: n = axis number
Range: 1 to 99
Default: -
Password: yes
(∗) addressing: no
Opposite to: AE
See also: AE
Note: the axis disabled holds his address, which can be interrogated via FA command.
REMARK: AD and AE commands must be set only when the motor is standstill
Examples:
1 AD 3 <CR>: it disables the 3rd axis of a module, whose first address is 1.
4 AD 6 <CR>: it disables the 3rd axis of a module, whose first address is 4.
1 AD <CR>: "1 AXIS DISABLED 3" will be displayed if the 3rd axis is disabled. "1 AXIS DISABLED 1 3"
will be displayed if the 1st and 3rd axis is disabled.
AE - Axis Enabled
Examples:
1 AE 3 <CR>: it enables the 3rd axis of a module, whose first address is 1.
4 AE 6 <CR>: it enables the 3rd axis of a module, whose first address is 4.
1 AE <CR>: "1 AXIS ENABLED 3" will be displayed if the 3rd axis is enabled. "1 AXIS ENABLED 1 3"
will be displayed if the 1st and 3rd axis is enabled.
VI - 6 - 30/Oct/01
AL - Analog Limit
Examples:
1 AL <CR>: Sets the analog I limit for axis 1. The display is cleared. After this command a current
limit can be set via J7 connector, pos. 12, 13 and 14 (range 0 to 10V).
The status can be interrogated via ST command.
AP - Autophasing
Note: To execute AP, all module axes must have optoisolated Drive Enable signals "on" and digital ones "off"
(see paragraph 2.2.3) via OF command. To execute AP, it is necessary that the "G2" jumper on the
personality card is open, which means priority from the keypad (see paragraph 2.2.2.).
Examples:
1 AP <CR>: it allows axis 1 auto-phasing. During such operation (a few seconds) "AUTOPHASING IN
PROGRESS" will be displayed; when auto-phasing is successfully carried out "AXIS PHASED" will be
displayed, otherwise "ERROR IN AUTOPHASING" will be shown. If digital Drive Enable is enabled (ON) (see
above) the message "WARNING DRIVE EN. CLOSED" will appear. The auto-phasing is not allowed if a
fault is on. This case, the message displayed will be "ERROR: FAULT STATUS".
VI - 7 - 30/Oct/01
AR - Analog Reference
AS - Address Show
Examples:
∗ AS <CR>: if the "base" address for such a module is 1, the answer will be "ADDRESS MODULE 1".
VI - 8 - 30/Oct/01
BR - Baud Rate
Note: To modify the Baud Rate also at keypad side, it is necessary to type <Control> and after <CR>.
Type <Y> to change Baud Rate and after <CR>.
CG - Current Gain
Function: The current loop gain of the DBM drive might be adjusted through
the serial link communication. A dedicated CG parameter with
4 discrete values is introduced in order to set the current error gain.
Syntax: data monitoring: address CG <CR>
data input: address CG n <CR>
Address type: axis
Unit of measure: -
Range: 0=very low gain
1=medium low
2=medium high
3=very high
Unit of measure: -
Default: 2
Password: YES
(∗) addressing: no
Opposite to: -
See also: -
VI - 9 - 30/Oct/01
CP - Current Position
Examples:
2 CP <CR>: Interrogates axis 2 about the current position. If the starting position is 4006, the
answer will be : "A02 CURRENT POSITION = 4006".
Note: the CU command must be executed with digital Drive Enable disabled (via OF command) and the opto
Drive Enable enabled.
Examples:
2 CU <CR>: Interrogates axis 2 about the offset of the U current. If U current offset is 128, the
answer will be : "A02 CURRENT U OFFSET = 128".
VI - 10 - 30/Oct/01
CV - Current V offset (only for setup technicians)
Note: the CV command must be executed with digital Drive Enable disabled (via OF command) and the opto
Drive Enable enabled.
Examples:
1 CV <CR>: Interrogates axis 1 about the offset of the V current. If V current offset is 128, the
answer will be : "A01 CURRENT V OFFSET = 128".
DE - Deceleration
Examples:
1 DE 100 <CR>: it sets a deceleration ramp = 100 ms for axis 1.
1 DE <CR>: it questions axis 1 about the deceleration ramp. In case no one has been set, the
answer is: "A01 DECEL. TIME = ms 0"
VI - 11 - 30/Oct/01
DF - Digital Filter
Function: it allows to set a low-pass digital filter. The filter reduces high
frequency noise and resonance's
When the Velocity Structure command is VS=0 or VS=1, the
velocity reference is filtered.
When the Velocity Structure command is VS=2 or VS=3, the
velocity error is filtered.
The value DF=0 switches the filter OFF
Syntax: data monitoring: address DF <CR>
data input: address DF n <CR>
Address type: axis
Unit of measure: -
Range: 0 to 255. The filter bandwidth is:
f [Hz] = {ln[1/(1-DF/512)]}/(2π∗300 10-6)
Default: 0 (disabled)
Password: yes
(∗) addressing: no
Opposite to: -
See also: VS
Note: the DF command must be executed with digital Drive Enable disabled (via OF command) and the opto
Drive Enable enabled.
Examples:
2 DF 165 <CR>: sets the filter bandwidth to 206 Hz for axis 2.
2 DF <CR>: Interrogates axis 2 about the reference filter on the velocity reference. The answer will be
: "A02 DIG.FIL. REF. PAR. = 165".
VI - 12 - 30/Oct/01
DI - Direction
Example:
4 DI <CR>: it reverses the direction of motor rotation for axis 4. The display is cleared.
DL - Digital Limit
VI - 13 - 30/Oct/01
DR - Digital Reference
Function: it allows to scale the Analog Outputs (max current, speed reference
or error reference) on J8 connector.
Syntax: data monitoring: address ES <CR>
data input: address ES n <CR>
Address type: 1=Analog Output 1 (see J8 connector, pos.4)
2=Analog Output 2 (see J8 connector, pos.5)
Unit of measure: -
Range: 0 to 255. Analog outputs on J8 connector (±10V, 10 mA max):
Max current for axis 1 (SO=1), axis 2 (SO=2) or axis 3 (SO=3):
±(10∗ES/16)V for ±100% max current
Speed reference for axis 1 (SO=4), axis 2 (SO=5) or axis 3 (SO=6),
and velocity error for axis 1 (SO=7), axis 2 (SO=8) or axis 3 (SO=9):
±[(ES∗NP∗MV)/(786∗MR)]V for ±MV (max velocity)
Default: 16
Password: yes
(∗) addressing: no
Opposite to: -
See also: MR, MV, NP, SO, Tab.6.4, Tab.6.5
Examples:
1 SO 1 <CR>: sets analog out1 (J8 conn., pos.4) to max current of axis 1 of the first module
1 ES 16 <CR>: sets analog out1 to ±10V for ±100% max current of axis 1
1 ES 32 <CR>: sets analog out1 to ±10V for ±50% max current (zoom-in) of axis 1
1 ES 8 <CR>: sets analog out1 to ±5V for ±100% max current (zoom-out) of axis 1
8 SO 5 <CR>: sets analog out2 (J8 conn., pos.5) to speed reference of axis 2 of the third module
2 ES 16 <CR>: sets analog out2 to ±10V for ±6140 rpm (if NP=8 and MR=100 have been set for axis 2)
VI - 14 - 30/Oct/01
Tab. 6.4 - ES for Max Current (SO=1 to SO=3)
ES MAX ANALOG
CURRENT OUT
8 100 % 5V
16 100 % 10 V
32 50 % 10 V
REMARK
actual current
Imax
2. To calculate the max rms current, Imrms = :
2
SPECIAL CASES
Imax
2 Imax
Sinusoidal Analog Output: Irms = =
2 2
Imax
2 Imax
Triangular Analog Output (I Limit): Irms = =
3 2.45
Tab. 6.5 - ES for Speed Reference and Velocity Error (MR=100, SO=4 to SO=9)
2 pole resolver 6 pole resolver 8 pole resolver
VI - 15 - 30/Oct/01
ET - Extra parameter for Tacho output
Examples:
1 MV 3000 <CR>: sets max velocity to 3000 rpm for axis 1.
1 MR 100 <CR>: sets max velocity reference to 10 V for axis 1.
1 ET 50 <CR>: sets ET parameter to 50 for axis 1. The Tacho Test 1 (J8, pos.1) will be ± 5V for
± 3000 rpm.
1 ET <CR>: questions axis 1 about the extra parameter for Tacho Test 1. The answer is: "A01 EXTRA
PAR. FOR TO = 50".
EV - Error Velocity
Remark: While testing the drives via step response, it is advisable to disable this protection or set a
high value of tolerated error, to avoid continuous faults.
Examples:
1 EV 100 <CR>: it sets axis 1 to tolerate up to 100 rpm error, without fault.
1 EV <CR>: it questions axis 1 about the maximum error allowed. The answer is: "A1 VELOCITY
ERROR RPM = 100".
VI - 16 - 30/Oct/01
FA - Fault
Function: as only main faults have front panel LED indications, when the
generic LED DRF lights up, it is necessary to interrogate
the drive via FA command. The answer is a codified ASCII string
(see below). Another function of the command is to reset the faults
occurred at logic level (also resettable via push button).
Syntax: status monitoring and reset: address FA <CR>
Address type: axis
Password: no
(∗) addressing: no
Answer explanation: A a FA b c d e f g P h i j k l MA m n o B p q r
A = axis
a = axis address
FA = fault
b = Resolver connection 0 = OK 1 = not OK
c = Motor temperature 0 = OK 1 = overtemperature
d = Axis short circuit 0 = OK 1 = short circuit
e = Bus Bar voltage (Axis 3 only) 0 = OK 1 = under 430V
f = Velocity error 0 = OK 1 = not OK
g = It 0 = off 1 = on
P = Power supply
h = Recovery unit 0 = OK 1 = not OK
i = PWRS temperature 0 = OK 1 = overtemperature
j = n.c.
k = n.c.
l = Personality card 0 = OK 1 = not OK*
* = in case of checksum error, check the parameters (e.g. KP, KI,...), correct the wrong values and save.
Note: If the expansion missing, the last characters are not significant.
Examples:
1 FA <CR>: if OK, the answer will be: "A1 FA 000000 P 00000 MA 000 B 000"
VI - 17 - 30/Oct/01
IL - I Limit (Current Limit)
Examples:
2 IL <CR>: it asks axis 2 about I limit. In default case the answer will be: "A2 CURRENT LIMIT % =
100".
2 IL 90 <CR>: it sets 90% current limit for axis 2.
IT - IT Protection
CAUTION: do not change IT parameter. A wrong set of IT can damage the motor.
VI - 18 - 30/Oct/01
Tab. 6.6 - IT Protection
The following table shows IT and PC values set in factory.
REMARK: the "operating time at drive peak current" is the operating time after a reset. In a steady state
condition, this time can be shorter according to the motor thermal simulation.
An overtemperature protection via PTC is also provided.
VI - 19 - 30/Oct/01
KI - Integral Gain
Function: it allows to set the speed loop integral gain. KI value is directly
proportional to the intensity of the integral action.
Syntax: data monitoring: address KI <CR>
data input: address KI n <CR>
Address type: axis
Unit of measure: -
Range: 0 to 255
Default: 20
Password: no
(∗) addressing: yes
Opposite to: -
See also: KP
Examples:
2 KI <CR>: it asks axis 2 about KI. If it is 40, the answer will be "A4 KI = 40".
2 KI 50 <CR>: it sets the integral gain to 50 for axis 2
KP - Proportional Gain
Function: it allows to set the speed loop error proportional correction gain. KI
value is directly proportional to the intensity of the requested action.
Syntax: data monitoring: address KP <CR>
data input: address KP n <CR>
Address type: axis
Unit of measure: -
Range: 0 to 255
Default: 80
Password: no
(∗) addressing: yes
Opposite to: -
See also: KI
Examples:
4 KI <CR>: it asks axis 4 about KP. If it is 90 the answer will be "A04 KI = 90".
4 KI 50 <CR>: it sets the integral gain to 100 for axis 4.
VI - 20 - 30/Oct/01
MR - Max Reference
Examples:
1 MV 2000 <CR>:
1 MR 100 <CR>: for axis 1, 10V correspond to 2000 rpm.
3 MR <CR>: it interrogates axis 3 about max. reference. If MR = 10V the answer will be: "A3 MAX
REFER. V = 10.0"
VI - 21 - 30/Oct/01
MV - Max Velocity
Examples:
1 MV 2000 <CR>: sets max velocity for axis 1 to 2000 rpm.
1 MR 100 <CR>: for axis 1, 10V correspond to 2000 rpm.
1 MV <CR>: interrogates axis 1 about max. velocity. The answer will be: "A1 RPM MAX = 2000"
Examples:
1 NP 2 <CR>: allows to set 2 poles for axis 1.
1 NP <CR>: allows to know the resolver pole number for axis 1. The answer will be: "A1 NUM. OF
POLES = 2"
VI - 22 - 30/Oct/01
OC - Digital Offset Compensation (only for setup technicians)
Examples:
1 OC 8 <CR>: adjust 30 rpm CCW offset for axis 1 with 6 pole resolver.
4 OC <CR>: if OC = 90, the answer will be "A4 OC = 90".
OF - Off
Function: it allows to disable the digital Drive Enable for the addressed axis
Syntax: command input: address OF <CR>
Address type: axis
Unit of measure: -
Range: -
Default: digital Drive Enable off
Password: no
(∗) addressing: yes
Opposite to: ON
See also: ON
REMARK: if opto Drive Enable are not enabled, the following message will be displayed: "ERROR: DRIVE
EN. OPEN". If the axis is not phased "AXIS NOT PHASED" will appear. If the jumper G2 is in
position 1-2 (closed) the message "NOT POSSIBLE" will appear.
VI - 23 - 30/Oct/01
ON - On
Function: it allows to enable the digital Drive Enable for the addressed axis
To use the digital Drive Enable, G2 jumper on the personality card
must be open (see par. 2.9.1) and the opto Drive Enable on J8
connector must be enabled (to +15V)
Syntax: command input: address ON <CR>
Address type: axis
Unit of measure: -
Range: -
Default: Digital Drive Enable off
Password: no
(∗) addressing: yes
Opposite to: OF
See also: OF
REMARK: if opto Drive Enable are not enabled, the following message will be displayed: "ERROR: DRIVE
EN. OPEN". If the axis is not phased "AXIS NOT PHASED" will appear. If the jumper G2 is in
position 1-2 (closed) the message "NOT POSSIBLE" will appear.
OV - Analog Offset
Function: it allows to monitor and to set the analog offset of speed/ torque
analog reference.
A fine adjustment of the analog offset can be done with successive
steps by setting and monitoring the OV parameter.
Syntax: data monitoring: address OV <CR>
data input: address OV n <CR>
Address type: axis
Unit of measure: -
Range: 0 to 255
Default: 128
Password: yes
(∗) addressing: no
Opposite to: -
See also: VO
VI - 24 - 30/Oct/01
PC - Peak Current
Function: it informs the drive control section about the ratio between motor
current and drive peak rms current. This way, when IT protection is
on, drive current will be reduced to nominal motor current.
Syntax: data monitoring: address PC <CR>
data input: address PC xx n <CR>. xx = special password
Address type: axis
Unit of measure: n=%
Range: 0 to 100
Default: see Tab. 6.6
Password: special password
(∗) addressing: no
Opposite to: -
See also: IT
CAUTION: do not change PC parameter. A wrong set of PC can damage the motor.
VI - 25 - 30/Oct/01
PR - Motor Poles to Resolver Poles Ratio
Function: it allows to set the ratio between the motor pole number and the
resolver pole number.
Syntax: data monitoring: address PR <CR>
data input: address PR n <CR>
Address type: axis
Unit of measure: -
Range: 1 to 24
Default: -
Password: yes
(∗) addressing: no
Opposite to: -
See also: NP
Examples:
2 PR 3 <CR>: sets axis 2 for 6 pole motor and 2 pole resolver
2 PR <CR>: questions axis 2 about the ratio between motor poles and resolver pole number. The
answer is: "A02 MOTOR/RES. POLES = 3".
VI - 26 - 30/Oct/01
PW - Password
Examples:
1 PW91 <CR>: if previously OFF, the answer is "PASSWORD ON"
1 PW137 <CR>: enters a new password. The answer is "NEW PASSWORD IS 137 SAVE? "
1 SV <CR> saves the new password. Note that all new parameters will be saved, if changed.
1 PW137 <CR>: the answer is be "PASSWORD OFF"
CAUTION: Password protected parameters must be set only when the motor is standstill.
VI - 27 - 30/Oct/01
RE - A/D Resolution
Example:
1 RE <CR>: it questions module 1 about the resolution of A/D converter. The standard answer is: "12
BIT A/D CONVERTER IS PRESENT".
VI - 28 - 30/Oct/01
RN - Minimum of R/D Resolution
Example:
2 NP 8 <CR>: allows to set the resolver pole number of axis 2 to 8
2 MV 3000 <CR>: allows to set max velocity of axis 2 to 3000 rpm
2 RN 12 <CR>: allows to set min R/D resolution to 12 bit (max R/D resolution with 8 poles/ 3000 rpm
according to Tab. 6.7)
2 RN <CR>: questions axis 2 about the minimum of R/D resolution. The answer is: "A02 MINIMAL R/D
RES. = 12".
Resolution (bit)
10 12 14 16
Max speed with 2 pole 24000 12000 3510 877
resolver (rpm)
VI - 29 - 30/Oct/01
RS - Resolver Shaft
Function: it informs about the phase shift between motor and resolver.
Syntax: data monitoring: address RS <CR>
data input: address RS n <CR>
Address type: axis
Unit of measure: -
Range: 0 to 65535
Default: -
Password: yes
(∗) addressing: no
Opposite to: -
See also: -
Examples:
1 RS <CR>: the answer for axis 1 will be: "A1 RESOLVER SHAFT BIT = XXXXX". Where, if the
autophasing has been correctly made:
XXXXX = 14000 to 16000 for 6 pole motor and resolver or 8 pole motor and resolver
XXXXX = approx. 17000 or approx. 39000 or approx. 61000 for 2 pole resolver and 6 or 8
pole motor.
Example:
2 RX <CR>: questions axis 2 about the maximum resolution of R/D. The answer is: "A02 MAXIMAL R/D
RES. = 16" (if 16 bit R/D resolution has been set for axis 2).
VI - 30 - 30/Oct/01
SA - Set Address
REMARK: To perform SA command, only one module at the time must be connected to J2 flat cable.
REMARK: to enable a new SE value (after setting and saving), reset button on front panel or send pulse to REM
Reset.
Example:
2 RN 12 <CR>: allows to set min R/D resolution for axis 2 to 12 bit.
2 ES 1024 <CR>: allows to set the pulses per electr. revolution for axis 2 to 1024.
Resolution (bit)
10 12 14 16
Max number of pulses per 256 1024 4096 16384
electrical revolution
VI - 31 - 30/Oct/01
SO - Spare Output
Note: the SO command must be executed with digital Drive Enable disabled (via OF command) and the opto
Drive Enable enabled.
VI - 32 - 30/Oct/01
SR - Show Release
Examples:
1 SR <CR>: the answer can be: "SOFTWARE REL. MC 0.3 DSP 0.12" .
ST - Status
Answer explanation: A a ST b c d E e f g l h i j k l
A = Axis
a = Axis address
ST = Status
b = Priority (G2 jumper on person.card) 0 = opto (G2=closed) 1 = keypad (G2=open)
c = DRIVE OK opto output 0 = absent 1 = present
d = Expansion module 0 = absent 1 = present
VI - 33 - 30/Oct/01
SV - Save
CAUTION: the SV command execution time is 5s. If a reset has been sent during this time
"EEPROM ERROR" will appear and some data can be lost. In this case, the following
steps must be met:
- close G3 on the personality card
- send 1SV command
- if the basic address is not 1, send 1SA command
- if 2-axis module, disable 3rd axis via AD command
- open G3 on the personality card
TC - Torque Control
VI - 34 - 30/Oct/01
TF - Parameter for the adjustment of Torque/Speed curve
Function: Current loop of a typical AC drive suffers the phase lag at extremely
high output frequencies (speeds). This lag reduces the resulting
torque-per-amp ratio. To counterbalance this phenomenon
the current vector relative to the motor flux is advanced, through TF,
TG, TY, and TQ parameters (see the dedicated Section 5).
The values TF=255, TG=0, TQ=0, TY=255 disable the function.
Syntax: data monitoring: address TF <CR>
data input: address TF n <CR>
Address type: axis
Unit of measure: -
Range: 0 to 255
Default: see Tab.5.1 to 5.4
Password: yes
(∗) addressing: no
Opposite to: -
See also: TG, TQ, TY
Function: Current loop of a typical AC drive suffers the phase lag at extremely
high output frequencies (speeds). This lag reduces the resulting
torque-per-amp ratio. To counterbalance this phenomenon
the current vector relative to the motor flux is advanced, through TF,
TG, TY, and TQ parameters (see the dedicated Section 5).
The values TF=255, TG=0, TQ=0, TY=255 disable the function.
Syntax: data monitoring: address TG <CR>
data input: address TG n <CR>
Address type: axis
Unit of measure: -
Range: 0 to 255
Default: see Tab.5.1 to 5.4
Password: yes
(∗) addressing: no
Opposite to: -
See also: TF, TQ, TY
VI - 35 - 30/Oct/01
TQ - Parameter for the adjustment of Torque/Speed curve
Function: Current loop of a typical AC drive suffers the phase lag at extremely
high output frequencies (speeds). This lag reduces the resulting
torque-per-amp ratio. To counterbalance this phenomenon
the current vector relative to the motor flux is advanced, through TF,
TG, TY, and TQ parameters (see the dedicated Section 5).
The values TF=255, TG=0, TQ=0, TY=255 disable the function.
Syntax: data monitoring: address TQ <CR>
data input: address TQ n <CR>
Address type: axis
Unit of measure: -
Range: 0 to 255
Default: see Tab.5.1 to 5.4
Password: yes
(∗) addressing: no
Opposite to: -
See also: TF, TG, TY
Function: Current loop of a typical AC drive suffers the phase lag at extremely
high output frequencies (speeds). This lag reduces the resulting
torque-per-amp ratio. To counterbalance this phenomenon
the current vector relative to the motor flux is advanced, through TF,
TG, TY, and TQ parameters (see the dedicated Section 5).
The values TF=255, TG=0, TQ=0, TY=255 disable the function.
Syntax: data monitoring: address TY <CR>
data input: address TY n <CR>
Address type: axis
Unit of measure: -
Range: 0 to 255
Default: see Tab.5.1 to 5.4
Password: yes
(∗) addressing: no
Opposite to: -
See also: TF, TG, TQ
VI - 36 - 30/Oct/01
VC - Velocity Control
VE - Velocity
Note: the maximum range for - MV is -9999. To have extended range (up to 32000) for negative speed, it is
necessary to set +MV and to change direction via DI command.
Examples:
1 VE 500 <CR>: it sets axis 1 to 500 rpm.
2 VE -500 <CR>: it sets axis 2 to -500 rpm.
VI - 37 - 30/Oct/01
VO - Analog Velocity Offset Automatic Setting
REMARK'S: The VO command must be executed with digital Drive Enable off (stopped motor). Before
executing the command it is necessary to check that the external opto input Drive Enable is
enabled and keypad Drive Enable is off (OF command).
VI - 38 - 30/Oct/01
VS - Velocity Structure
Function: it allows to set 4 different structures of the velocity control. All the
structures have a digital low pass filter processing the speed
reference or the speed error signal. The cutoff frequency of this
filter can be adjusted by DF parameter (see DF). The value DF=0
switches the filter OFF.
VS=0 selects the speed controller having the feedback KP and KI
gains four times higher than the standard gains and a digital low
pass filter processing the speed reference signal.
This structure should be used in applications where the analog
speed reference lines from the CNC are noisy, and high gains are
required.
VS=1 selects the speed controller having standard feedback KP
and KI gains and a digital low pass filter processing the speed
reference signal.
This structure should be used in applications where the analog
speed reference lines from the CNC are noisy, and normal gains
are required.
VS=2 selects the speed controller having the feedback KP and KI
gains four times higher than the standard gains and a digital low
pass filter processing the speed error signal.
This structure should be used in applications with high ratios
between load and motor inertia (inertia mismatch), and high gains
are required.
VS=3 selects the speed controller having standard feedback KP
and KI gains and a digital low pass filter processing the speed
error signal.
This structure should be used in applications with high ratios
between load and motor inertia (inertia mismatch), and normal
gains are required.
Syntax: data monitoring: address VS <CR>
data input: address VS n <CR>
Address type: axis
Unit of measure: -
Range: 0 to 3.
VS=0: gains multiplied by 4, reference filtering
VS=1: standard gains, reference filtering
VS=2: gains multiplied by 4,error filtering
VS=3: standard gains , error filtering
Default: 1
Password: yes
(∗) addressing: no
Opposite to: -
See also: DF
Note: the VS command must be executed with digital Drive Enable disabled (via OF command) and the opto
Drive Enable enabled.
VI - 39 - 30/Oct/01
This page intentionally blank
VI - 40 - 30/Oct/01
SECTION 7 - TROUBLESHOOTING
YES
Verify the correct Ambient temperature
cooling of cabinet > 40 °C ?
NO
NO
Power the fans
Fans powered?
YES
VII - 1 - 30/Oct/01
FIG. 7.2 - DBM-PS Power Supply - DBR FAULT red LED on
Recovery Fault
NO Recovery
Connect the
recovery resistance resistance
connected?
YES
YES Recovery
Replace the recovery resistance open or
resistance short-circuited?
NO
NO
Correctly tighten at
6 Nm (53 Lb in) the Bus Bars tightening
Bus Bars OK?
YES
VII - 2 - 30/Oct/01
FIG. 7.3 - DBM-PS Power Supply - PWR BUS yellow LED off
NO Is three-phase
Connect 3-phase ac-line connected to
400 or 460 Vac DBM-PS?
YES
NO
Fault of 3-phase input Voltage of Fig.4.1
rectifier circuit present on Bus Bars?
YES
VII - 3 - 30/Oct/01
FIG. 7.4 - DBM PS-Standard and PS-6M Power Supply - AUX PWR green LED off
NO Auxiliary power
Connect single phase
230 Vac (or 110 Vac) supply on DBM-PS
+/-10% Standard present?
YES
YES
NO
Replace the fuse 4A/250V fuse on front
panel OK?
YES
VII - 4 - 30/Oct/01
FIG. 7.5 - DBM Module - POWER OK green LED off
Green LED
NO AUX PWR on
See Fig. 7.4 DBM-PS standard
lit ?
YES
YES
NO
Flat cable between
Change flat cable
DBM-PS and DBM
module OK?
YES
VII - 5 - 30/Oct/01
FIG. 7.6 - DBM Module - DR.EN1/DR.EN2/DR.EN3 green LED off
Drive Enable Axis 1/Axis 2/Axis 3
YES
NO
J8/pin 7 (common)
Make connection
connected to J8/pin 9
(opto common)?
YES
VII - 6 - 30/Oct/01
FIG. 7.7 - DBM Module - REF.EN green LED off
Reference Enable
YES
NO
J8/pin 7 (common)
Make connection
connected to J8/pin 9
(opto common)?
YES
VII - 7 - 30/Oct/01
FIG. 7.8 - DBM Module - DR.OVT red LED on
DBM Overtemperature
NO
Power the fan
Fan powered?
YES
YES
Verify the correct Ambient temperature
cooling of cabinet > 40°C ?
NO
VII - 8 - 30/Oct/01
FIG. 7.9 - DBM Module - PWRF1/PWRF2/PWRF3 red LED on
Power Circuit Fault Axis 1/Axis 2/Axis 3
NO
NO Auxiliary
Change DBM-PS
voltages on
power supply
J1 connector
OK?
YES
NO
Change flat cable Flat cable on J1 OK?
YES
VII - 9 - 30/Oct/01
FIG. 7.10 - DBM Module - OT1/OT2/OT3 red LED on
Motor Overtemperature Axis 1/Axis 2/Axis 3
Red LED OT = ON
NO Motor PTC
connected to J4,
Connect PTC
J5, J6?
YES
NO
PTC value at 20°C
Fault on motor PTC correct?
(20 to 400 ohm)
YES
VII - 10 - 30/Oct/01
FIG. 7.11 - DBM Module - RF1/RF2/RF3 red LED on
Resolver Fault Axis 1/Axis 2/Axis 3
Red LED RF = ON
YES
NO
NO
Other resolver
Make correct
connection OK?
connection
YES
NO
Vref carrier present on J4, J5,
Fault on oscillator J6 (20 Vpp, 10 kHz)?
circuit
YES
NO
Resolver fault or Sin and cos signals
connection not OK at present on J4, J5, J6
(6.5 Vpp max, 10 kHz
motor side for resolver)?
YES
Internal fault
VII - 11 - 30/Oct/01
FIG. 7.12 - DBM Module - WTD red LED on
Watch Dog
Reset via:
- Pushbutton on front
panel
- Remote Reset
YES
Fault caused by noise Red LED WTD =
OFF ?
NO
VII - 12 - 30/Oct/01
FIG. 7.13 - DBM Module - DRF red LED on
Drive Fault
NO
Other red LEDs lit ?
Check via FA
command the fault not
reported by LEDs.
It can be:
VII - 13 - 30/Oct/01
FIG. 7.14 - Motor vibrates
NO 6 resolver/motor
poles or
8 resolver/motor
poles ?
2 pole resolver
with 6 pole YES
motor?
YES
Check via RS
command. RS = NO NO
Check via RS command.
approx. 17,000 or RS = 14,000 to 16,000 ?
39,000 or 61,000?
YES
YES
VII - 14 - 30/Oct/01
FIG. 7.15 - Keypad fault
NO
Serial cable and/or
J10 cable OK?
Make correct
connection
YES
YES
Baud rate > 9600 ?
Close G3 on
Personality Card
(Baud rate set to
9600)
NO
VII - 15 - 30/Oct/01
FIG. 7.16 - Motor at zero speed
NO
REF EN = ON ?
Make REF EN = ON
on J8/pin 17
YES
YES AR = ON with
digital reference or
DR = ON with
analog reference?
NO
Check via ST
command. Use
coherent reference.
NO
YES
KI = 0 ?
Internal fault.
VII - 16 - 30/Oct/01
FIG. 7.17 - Runaway or locked motor (6 pole motor and resolver)
NO Resolver wiring
Correct resolver wiring (see Fig.2.10)
OK ?
NO
YES
NO
NO
NO
NO
Ask the
Service Center
VII - 17 - 30/Oct/01
M
Moog Italiana S.r.l.
Electric Division
Via Avosso, 94
16015 Casella (Genova) - Italy
Phone: (+39) 010 9671
Fax: (+39) 010 9671 280
www.moog.com
GB-4517 Rev.9 - Oct/01 Moog Italiana S.r.l. reserves the right to alter any dimensions or data without prior notice
Printed in Italy